Field Intelligent Device – Mount Anywhere Series - Flanged
Electromagnetic Flowmeter
Introduction
The electromagnetic flowmeter uses Faraday’s Law of
electromagnetic induction to measure the process flow.
The device consists of two units: a detector, through
which the fluid to be measured flows and in which
low-level signals proportional to flow rates are
obtained; and a converter, which supplies excitation
current to the detector, and amplifies the signals from
the detector and then processes and converts the signals
into the 4–20 mAdc current signal or communication
signal. The meter features a Mount-Anywhere
magnetic field distribution technology, the meter is
highly immune to upstream flow disturbances.
Combined with a multi-functional converter LF620
(combined type) or LF622 (separate type) equipped
with its patented Noise-Sentry original noise-
suppression circuit and advanced algorithms. The
LF654 has a very high tolerance to noise, giving the unit
a very stable output even for slurry fluid measurement.
IR (Infrared) switches enable parameter setting of the
converter without removing the cover. Flow direction
can be set in either way, and its unique 128 x 128 dot
matrix LCD display allows the LCD to be rotated
electronically to 90, 180 and 270 degrees without
opening the cover.
LF654/LF620F
LF654
LF622F
Figure2. LF654 Mount-Anywhere Series
Flowmeters
Certification
No. Z01207
For PU and
HR lined flowmeter
Specifications
*
HART protocol (Highway Addressable Remote Transducer) is
a communication protocol for industrial sensors recommended
by the HCF (HART Communication Foundation).
Overall Specifications
** DevComm2000 Smart Device Communicator available
through TIC for performing HART device configurations on
PC or laptop.
Measurement range in terms of flow velocity:
0 –1.0 ft/s to 0 – 39.4ft/s (0 – 0.3 m/s to 0 –12 m/s).
0 – 0.3 ft/s to 0 – 1.0 ft/s (0 – 0.1 m/s to 0 – 0.3 m/s)
range is available optionally.
*
PROFIBUS is the communications protocol for factory and
process automation that the PROFIBUS Organization
recommends. Instead of analog control with a conventional
analog signal (4-20 mA), it is fieldbus which digitizes all
signals. Flowmeters support PROFIBUS-PA.
Accuracy:
< 1/2" to 18" ( 15mm to 450mm) >
±0.2 % of Rate*
*
Modbus is the communication protocol that Modicon Inc.
developed. Physical layer is RS485.
*
*
This pulse output error result is established under standard
operating conditions at Toshiba admitted flow calibration
facility. (NIST Traceable)
Individual meter measurement error may vary up to ±0.5% of
Rate at 1.64 ft/s (0.5m/s) or more and ±0.3% of rate ±0.039
inch/s (1mm/s) at 1.64 ft/s or less.
*
*
Current output: plus ± 8µA (0.05% of span.)
Refer to individual calibration data for each individual meter's
measurement error.
Combined type
Separate type
Figure1. Configuration
TIC-LF654L
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
Pulse width: 0.5 to 500ms (but less than half of
Model LF620 and LF622 converters
Input signals
the period for 100% flow rate)
Note: The same and simultaneous pulse is not available
between DO1 and DO2.)
Analog signal — the voltage signal from detector,
proportional to process flow rate (for LF622
separate type converter).
• Multi-range selection outputs (Note 1)
• High, High high, Low, and/or Low low alarm
outputs (Note 2)
Digital input DI
Signal type: 20 to 30Vdc voltage signal
Input resistance: 2.7k
• Empty pipe alarm output (Note 2)
• Preset count output
Number of inputs: one point
Note: DI cannot be used with the Modbus communication.
DI function — One of the following functions can
• Converter failure alarm output
Note 1: Two outputs (DO1 and DO2) are needed for 4-range
switching and forward/reverse 2-range switching.
Note 2: Normal Open (default set) or Normal Close is selected
for alarm outputs when programming.
be assigned to the DI signal.
Range switching — Selects either the higher or
lower range in the unidirectional or bidirectional
2-range setting.
When power failure occurs, unit will be fault to Normal
Open.
Totalizer control — ‘Starts and stops’ or ‘Rest and
start’ the built-in totalizer.
Communications output:
Fixed-value outputs —Outputs fixed-values for
• HART (std.) — Digital signal is superimposed on
current and pulse outputs for loop check.
4–20mAdc current signal as follows:
Conforms to HART protocol
Load resistance: 240 to 750
Load capacitance: 0.25µF maximum
Load inductance: 4mH maximum
• PROFIBUS (opt.)
Zero adjustment — Executes zero adjustment
(on-stream at zero flow rate).
Output signals
Current output:
4–20mAdc (load resistance 0 to 750)
Protocol: PROFIBUS-PA
Baud rate: 31.25kbps
Bus voltage: 9-30VDC
Note: The current output cannot be used with the
PROFIBUS-PA communication.
(Refer table 6 for details)
Consumption electric current of bus: less than 16mA
Manufacture Ident-No.: 093BHEX
Standard Ident-No.: 9740HEX
Slave address: 0-126 (Default address is 126)
Profile: Profile Ver.3.01 for Process Control
Devices
Digital outputs — Two points are available as
follows.
Digital output DO1:
Output type: Transistor open collector
Number of outputs: One point
Output capacity: 30Vdc, 200mA maximum
Note: DO1 cannot be used if Modbus
communication connection is 3 lines.
(Refer table 6 for details)
Function blocks: AI(Flow)×1 , Totalizer×1
• MODBUS (opt.)
Physical layer : RS485
Protocol : Modbus
Digital output DO2 :
Output type:
Mode : RTU
Solid-state relay output (non polarity)
Baudrate : 4800, 9600, 19200bps
Data length : 8bit
Number of outputs: One point
Output capacity: 150Vdc, 150mA maximum or
150Vac (peak to peak), 100mA maximum
Parity bit : None, Odd, Even
Stop bit : 1bit, 2bit
Error check : CRC-16
Max. station number : 32(with Master device)
Max. cable length : 1.2km (Note)
Note: DO2 cannot be used with the Modbus
communication. (Refer table 6 for details)
DO1 and DO2 functions — One of the following
functions can be assigned to DO1 and/or DO2 .
Note: This length is specification of 3 line
• Pulse output (available only for DO1, DO2)
Pulse rate: MAX 10kHz (10000pps)(DO1)
MAX 100Hz (100pps)(DO2)
connection.
(Over 1kpps, auto-setting)
3
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
LCD display:
Surge protection:
Arresters are installed in the power supply and a
current signal output circuit to help protect the meter
from lightning and improve personnel safety.
Full dot-matrix 128×128 dot LCD display
(back–light provided)
A parameter change will rotate the display.
Case: Aluminum alloy (equal to IP 67)
Parameter settings — Parameters can be set as
follows:
Coating:
• IR Switches: Three key switches are provided
Acrylic resin-baked coating, pearl–gray colored
to set configuration parameters.
Cable connection port:
• Digital communication: HART, PROFIBUS
Cable glands —
or Modbus is needed to set parameters.
LF620 and LF622 without cFMus Approval:
• Zero adjustment: Zero point adjustment can
be started by pressing the switch in the
converter.
Provided as standard, outer diameter of cableφ
11~13mm
Material Nylon 66
G (PF) 1/2 male threads.
• Damping: 0.1 to 60 seconds (selectable in one
second increments)
LF620F and LF622F with cFMus Approval:
“Field re-verification” Mag-Prover– Toshiba’s
Zero span calibration tool allows unit to be
re-calibrated and verified using an internal software
program (For more information contact Toshiba
International Corp.)
Not provided, 1/2–14NPT male threads are
required.
Applicable diameter —
0.433 to 0.512 inch (11 to 13mm)
Note: When PROFIBUS option is specified, cable gland size is
φ6~8mm for signal cable, φ11~13mm for power
cable
Conditions when power fails:
Parameter setting values are stored in non–volatile
memory and the values will be restored when the
power returns to normal condition. The outputs and
display will remain as follows when power fails.
Vibration resistance:
No resonance to the following levels of vibration:
• 10 to 150Hz with acceleration of 9.8m/s2
• Vibration of 30Hz with 29.4 m/s2 in 4h in each
• Current output: 0mAdc
• Digital output: OFF
direction will not cause any defect to unit.
Note: Avoid using the flowmeter in an environment with
constant vibration.
• LCD display: No display
• HART:
No communication
• PROFIBUS: No communication
Dimensions and Weights:
• Modbus:
No communication
See Figure 7 (for Separate type)
Power supply:
MTBF:
One of the following can be selected:
• 100 to 240Vac, 50/60Hz
(allowable voltage 80 to 264Vac)
110Vdc
Converter: 220,000 hours (25 years) at 77 °F (25 °C)
based on strict military specification
MIL-HDBK-217F
(allowable voltage 90 to 130Vdc)
• 24Vdc (allowable voltage 18 to 36Vdc)
Detector: 350,000 hours (40 years) at 77 °F (25 °C)
based on strict military specification
MIL-HDBK-217F
4
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
Installation
Dimensions
Unit: inch (mm)
Note1: Eye bolts are provided at the top for flowmeters sized 8" (200mm) or above, and further, a roll-prevention base is provided for
flowmeters sized 10" (250mm) or larger.
Note2: Cable glands are not provided for LF654 of cFMus approved type. Refer to the cable connection port at converter.
ASME B 16.5 class 150 dimensions:
JIS B 2220 10K dimensions:
Meter size
(inch)
L1
L2
L3
No. of
bolts
Weight
(lbs)
Meter size
L1
L2
L3
No. of
bolts
Weight
(kg)
(inch)
(inch)
(inch)
(mm)
(mm)
(mm)
(mm)
1/2
1
1-1/4
1-1/2
2
2-1/2
3
4
5
6
8
10
12
14
16
18
5.51
6.30
7.87
6.69
7.09
7.87
9.06
9.45
9.84
10.24
11.81
13.78
15.75
17.72
19.69
21.65
8.07
8.31
8.62
8.66
9.09
9.84
4
4
4
4
4
4
4
8
8
approx. 11.0
approx. 16..0
approx. 20.0
approx. 20.0
approx. 29.0
approx. 38.0
approx. 45..0
approx. 64.0
approx. 73.0
approx. 93.0
approx. 139.0.
approx. 207.0
approx. 315.0
approx. 403.0
approx. 509.0
approx. 617.0
15
25
32
40
50
140
160
200
170
180
200
230
240
250
260
300
350
400
450
500
550
203
209
217
218
232
237
255
262
273
285
310
335
365
374
397
420
251
272
285
288
310
325
347
367
399
425
475
535
588
619
677
730
4
4
4
4
4
4
8
8
8
approx. 6.0
approx. 8.5
10.43
10.94
11.18
12.09
12.80
13.43
14.80
15.71
16.85
19.02
21.14
24.13
25.39
27.20
29.21
approx. 10.5
approx. 10.0
approx. 13.5
approx. 16.5
approx. 18.0
approx. 23.5
approx. 30.0
approx. 37.0
approx. 48.5
approx. 74.0
approx. 102.0
approx. 127.0
approx. 175.0
approx. 217.0
9.29
9.69
65
80
10.28
10.71
11.34
12.24
13.15
14.65
14.88
15.79
16.69
100
125
150
200
250
300
350
400
450
8
8
8
12
12
16
16
16
20
12
12
12
16
16
EN 1092-1 PN 16 dimensions:
Note 3 : 1 inch = 25.4 mm
Meter size
(mm)
L1
L2
L3
No. of
bolts
Weight
(kg)
(mm)
(mm)
(mm)
15
25
32
40
50
140
160
200
170
180
200
230
240
250
260
300
350
400
450
500
550
203
209
217
218
232
237
255
262
273
285
310
335
365
374
397
420
251
272
285
288
310
325
347
367
399
425
475
535
588
619
677
730
4
4
4
4
4
4
8
8
8
approx. 6.0
approx. 7.5
Figure 3. LF650/LF620 and LF654/LF620F
combined type flowmeters
approx. 10.0
approx. 10.5
approx. 14.5
approx. 16.5
approx. 21.5
approx. 26.5
approx. 31.0
approx. 37.5
approx. 54.0
approx. 78.0
approx. 117.0
approx. 156.5
approx. 202.5
approx. 249.5
Meter Sizes 1/2" (15) to 18"
(450mm) for Toshiba lay length
65
80
100
125
150
200
250
300
350
400
450
8
12
12
12
16
16
20
5
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
Note1: Eye bolts are provided at the top for flowmeters sized 8" (200mm) or above, and further, a roll-prevention base is
provided for flowmeters sized 10" (250mm) or larger.
Note2: Cable glands are not provided for LF654 of cFMus approved type. Refer to the cable connection port at converter.
ASME B 16.5 class 150 dimensions:
JIS B 2220 10K dimensions:
Unit: inch (mm)
Meter size
(inch)
L1
L2
L3
No. of
Weight
Meter size
(mm)
L1
L2
L3
No. of
bolts
Weight
(kg)
(inch)
(inch)
(inch)
bolts
(lbs)
(mm)
(mm)
(mm)
1/2
1
1-1/4
1-1/2
2
2-1/2
3
4
5
6
8
10
12
14
16
18
7.90
7.90
7.90
7.90
7.90
7.90
7.90
9.80
9.80
11.80
13.80
17.70
19.70
21.70
23.60
23.60
8.07
8.31
8.62
8.66
9.09
9.84
4
4
4
4
4
4
4
8
8
8
8
12
12
12
16
16
approx. 11.0
approx. 16..0
approx. 20.0
approx. 20.0
approx. 29.0
approx. 38.0
approx. 45..0
approx. 64.0
approx. 73.0
approx. 93.0
approx. 139.0.
approx. 207.0
approx. 315.0
approx. 403.0
approx. 509.0
approx. 617.0
15
25
32
40
50
200
200
200
200
200
200
200
250
250
300
350
450
500
550
600
600
203
209
217
218
232
237
255
262
273
285
310
335
365
374
397
420
251
272
285
288
310
325
347
367
399
425
475
535
588
619
677
730
4
4
4
4
4
4
8
8
8
approx. 6.5
approx. 8.5
10.43
10.94
11.18
12.09
12.80
13.43
14.80
15.71
16.85
19.02
21.14
24.13
25.39
27.20
29.21
approx. 10.5
approx. 10.5
approx. 13.5
approx. 16.5
approx. 18.0
approx. 23.5
approx. 30.0
approx. 38.0
approx. 50.0
approx. 80.0
approx. 110.5
approx. 136.0
approx. 187.5
approx. 224.5
9.29
9.69
65
80
10.28
10.71
11.34
12.24
13.15
14.65
14.88
15.79
16.69
100
125
150
200
250
300
350
400
450
8
12
12
16
16
16
20
Note 3 : 1 inch = 25.4 mm
EN 1092-1 PN16 dimensions:
Meter size
(mm)
L1
L2
L3
No. of
bolts
Weight
(kg)
(mm)
(mm)
(mm)
15
25
32
40
50
200
200
200
200
200
200
200
250
250
300
350
450
500
550
600
600
203
209
217
218
232
237
255
262
273
285
310
335
365
374
397
420
251
272
285
288
310
325
347
367
399
425
475
535
588
619
677
730
4
4
4
4
4
4
8
8
8
approx. 6.0
approx. 7.5
Figure 4. LF650/LF620 and LF654/LF620F
combined type flowmeters
approx. 10.0
approx. 10.5
approx. 15.0
approx. 17.0
approx. 21.5
approx. 26.5
approx. 31.0
approx. 38.0
approx. 55.5
approx. 83.5
approx. 125.5
approx. 166.0
approx. 215.0
approx. 257.0
Meter Sizes 1/2" (15) to 18"
(450mm) for ISO lay length
65
80
100
125
150
200
250
300
350
400
450
8
12
12
12
16
16
20
6
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
Note1: Eye bolts are provided at the top for flowmeters sized 8”(200mm) or above, and further, a
roll-prevention base is provided for flowmeters 10”(250mm) or larger.
Note2: Cable glands are not provided for LF654 of cFMus approved type. Refer to the cable connection
JIS B 2220 10K dimensions:
ASME B 16.5 class 150 dimensions:
Meter size
(inch)
L1
L2
L3
No. of
bolts
Weight
(lbs)
Meter size
L1
(L2)
L3
No. of
bolts
Weight
(kg)
(inch)
(inch)
(inch)
(mm)
(mm)
(mm)
(mm)
1/2
1
5.51
6.30
6.77
7.01
8.54
9.13
4
4
approx. 9.0
15
25
140
160
200
170
180
200
230
240
250
260
300
350
400
450
500
550
170
176
184
185
199
204
222
229
240
252
277
302
332
341
364
387
218
239
252
255
277
292
314
334
366
392
442
502
555
586
644
697
4
4
approx. 4.0
approx. 14.0
approx. 18.0
approx. 18.0
approx. 27.0
approx. 36.0
approx. 42.0
approx. 62.0
approx. 71.0
approx. 91.0
approx. 137.0
approx. 205.0
approx. 313.0
approx. 401.0
approx. 507.0
approx. 614.0
approx. 6.5
1-1/4
1-1/2
2
7.87
7.32
9.65
4
32
4
approx. 8.5
6.69
7.36
9.88
4
40
4
approx. 8.0
7.09
7.80
10.79
11.50
12.13
13.50
14.41
15.55
17.72
19.84
22.83
24.09
25.91
27.91
4
50
4
approx. 11.5
approx. 14.5
approx. 16.0
approx. 21.5
approx. 28.0
approx. 35.0
approx. 46.5
approx. 72.0
approx. 100.0
approx. 125.0
approx. 173.0
approx. 215.0
2-1/2
3
7.87
7.99
4
65
4
9.06
8.39
4
80
8
4
9.45
8.98
8
100
125
150
200
250
300
350
400
450
8
5
9.84
9.41
8
8
6
10.24
11.81
13.78
15.75
17.72
19.69
21.65
10.04
10.94
11.85
13.35
13.58
14.49
15.39
8
8
8
8
12
12
16
16
16
20
10
12
14
16
18
12
12
12
16
16
EN1092-1 PN 16 dimensions:
Meter size
L1
(L2)
L3
No. of
bolts
Weight
(kg)
(mm)
(mm)
(mm)
(mm)
15
25
140
160
200
170
180
200
230
240
250
260
300
350
400
450
500
550
170
176
184
185
199
204
222
229
240
252
277
302
332
341
364
387
218
239
252
255
277
292
314
334
366
392
442
502
555
586
644
697
4
4
approx. 4.0
approx. 5.5
Figure 5. Separate type detectors LF654
Meter sizes 1/2" (15) to 18"
32
4
approx. 8.0
40
4
approx. 8.5
(450mm) for Toshiba lay length
50
4
approx. 12.5
approx. 14.5
approx. 19.5
approx. 24.5
approx. 29.0
approx. 35.5
approx. 52.0
approx. 76.0
approx. 115.0
approx. 154.5
approx. 200.5
approx. 247.5
65
4
80
8
100
125
150
200
250
300
350
400
450
8
8
8
12
12
12
16
16
20
7
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
Note1: Eye bolts are provided at the top for flowmeters sized 8" (200mm) or
above, and further, a roll-prevention base is provided for flowmeters sized
ASME B 16.5 class 150 dimensions:
JIS B 2220 10K dimensions:
Meter size
(inch)
L1
L2
L3
No. of
bolts
Weight
(lbs)
Meter size
L1
(L2)
L3
No. of
bolts
Weight
(kg)
(inch)
(inch)
(inch)
(mm)
(mm)
(mm)
(mm)
7.90
7.90
1/2
1
6.77
7.01
8.54
9.13
4
4
approx. 9.0
approx. 14.0
approx. 18.0
approx. 18.0
approx. 27.0
approx. 36.0
approx. 42.0
approx. 62.0
approx. 71.0
approx. 91.0
approx. 137.0
approx. 205.0
approx. 313.0
approx. 401.0
approx. 507.0
approx. 614.0
15
25
200
200
200
200
200
200
200
250
250
300
350
450
500
550
600
600
170
176
184
185
199
204
222
229
240
252
277
302
332
341
364
387
218
239
252
255
277
292
314
334
366
392
442
502
555
586
644
697
4
4
approx. 4.5
approx. 6.5
7.90
1-1/4
1-1/2
2
7.32
9.65
4
32
4
approx. 8.5
7.90
7.36
9.88
4
40
4
approx. 8.5
7.90
7.80
10.79
11.50
12.13
13.50
14.41
15.55
17.72
19.84
22.83
24.09
25.91
27.91
4
50
4
approx. 11.5
approx. 14.5
approx. 16.0
approx. 21.5
approx. 28.0
approx. 36.0
approx. 48.0
approx. 78.0
approx. 108.5
approx. 134.0
approx. 185.5
approx. 222.5
7.90
2-1/2
3
7.99
4
65
4
7.90
8.39
4
80
8
9.80
4
8.98
8
100
125
150
200
250
300
350
400
450
8
9.80
5
9.41
8
8
11.80
13.80
17.70
19.70
21.70
23.60
23.60
6
10.04
10.94
11.85
13.35
13.58
14.49
15.39
8
8
8
8
12
12
16
16
16
20
10
12
14
16
18
12
12
12
16
16
EN 1092-1 PN16 dimensions:
Note 3 : 1 inch = 25.4 mm
Meter size
L1
(L2)
L3
No. of
bolts
Weight
(kg)
(mm)
(mm)
(mm)
(mm)
15
25
200
200
200
200
200
200
200
250
250
300
350
450
500
550
600
600
170
176
184
185
199
204
222
229
240
252
277
302
332
341
364
387
218
239
252
255
277
292
314
334
366
392
442
502
555
586
644
697
4
4
approx. 4.0
Figure 6. Separate type detectors LF654
Meter sizes 1/2" (15) to 18"
approx. 5.5
32
4
approx. 8.0
(450mm) for ISO lay length
40
4
approx. 8.5
50
4
approx. 13.0
approx. 15.0
approx. 19.5
approx. 24.5
approx. 29.0
approx. 36.0
approx. 53.5
approx. 81.5
approx. 123.5
approx. 164.0
approx. 213.0
approx. 255.0
65
4
80
8
100
125
150
200
250
300
350
400
450
8
8
8
12
12
12
16
16
20
8
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
5.35(136)
4.84(123)
2.91(74)
0.59(15)
3.82(97)
Unit: inch (mm)
Weight: Approx. 7 lb (3.5 kg)
Note: Cable glands are not provided for LF622F cFMus approved type.
Refer to the part Cable connection port at detector.
Note: 1 inch = 25.4 mm
Figure 7. Separate type converter LF622 and LF622F
External Connections
● Combined type LF650/LF620 flowmeter and LF654/LF620F flowmeters
Instrument panel : Ordered separately
Grounding with 100Ω or less
Ⅳwire 5.5mm2 or more
ground resistance
Power switch
(External double-pole power switch)
Grounding with 100Ω or less
ground resistance
Power supply
Current output (4~20mAdc)
NOTE:
or PROFIBUS
Digital inp ut
In the case ofthe integral type, the signal line
(A, B, G) and the excitationline ( E, X, Y ) are
the connector joints.
(20~30Vdc)
Digital output 2
or Modbus
Signal common for DI and DO
Digital output 1
Grounding with 100Ω or less
ground resistance
I/O cable Power cable
*1 Locate an external double-pole power switch on the power line near the flowmeter within easy reach of operation.
Use the appropriate switch rating as shown below:
Switch rating: 250Vac, 6A or more
In rush current: 15A or more
Figure 8. Combined type LF650/LF620 and LF654/LF620F flowmeters Wiring Diagram
9
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
● Separate type LF650/LF622 flowmeter and LF654/LF622F flowmeter
Instrument panel : Ordered separately
Grounding with 100Ω or less
ground resistance
Ⅳwire 5.5mm2 or more
Power switch
(External double-pole power switch)
Grounding with 100Ω or less
ground resistance
Power supply
Thick walled steel conduit
Signal cable
Current output (4~20mAdc)
or PROFIBUS
(2-wireshielded hard-rubbersheathed cable)
Digital input
(20~30Vdc)
Excitation cable
(3-wire shielded hard-rubber cable)
or Modbus
Digital output 2
Signal common for DIand DO
Digital output 1
Grounding with 100Ω or less
ground resistance
Power cable
Connected detector
I/O cable
Figure 9. Separate type LF650/LF622 and LF654/LF622F flowmeters wiring Diagram
Table 1. LF620, LF620F, LF622 and LF622F Converters Signal Table
Symbol
L1 (+)
L2 (-)
GND
FG
Description
Cable
Power supply
Power cable (CVV)
Ground (for arrester)
Frame ground
DI
DO1
Digital Input (20~30Vdc)
Digital Output 1
DO2
Digital Output 2
I/O cable (CVV-S)
COM
Signal Common for DI, DO1, DO2
+
-
Current Output (4~20mAdc)
or PROFIBUS
Shielded cable for
PROFIBUS-PA
X
Y
E
A
B
Excitation cable
(for LF622,LF622F only)
Excitation Output
Signal Input
Signal cable
(for LF622,LF622F only)
G
T+
T-
TG
Modbus(+)
Modbus(-)
Modbus(GND)
Twisted-pair polyethylene
insulated vinyl sheath cable
(JKEV,AWG24(0.2mm2))
Note: Symbol of the terminal is changed as follows for Modbus.
DO2 → T+, DI → T-, COM → TG
10
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
(6) The electromagnetic flowmeter is not equipped with
terminating resistors. Use the terminating resistor
unit for PROFIBUS-PA or junction box, if
necessary.
Wiring Precautions
(1)Explosion proof type flowmeters are not provided
with cable glands.
Refer to the part Cable connection port at detector
and converter.
(7) Only one PROFIBUS-PA cable goes through a
cable gland of the Electromagnetic Flowmeter.
Please use the junction box at system configuration.
(2) Connect the grounding wire (IV wire 5.5mm² or
more) to a good earth ground (100 or less ground
resistance). Make the wire as short as possible. Do
not use a common ground shared with other
equipment where earth current may flow. An
independent earth ground is recommended.
(8) Install a terminator to flowmeter that connected to
end of Modbus network.
300
200
100
(3) The allowable cable lengths between the detector
and converter for the separate type flowmeter
depend on the electrical conductivity of the object
fluid. See Figure 10.
50
30
20
10
(4) DO1, DO2 and DI use the same common terminal
(COM). This COM can not be connected to other
equipment which have their own ground terminal.
(Power supply for connecting to DI or DO, etc…)
Need to wire separately.
5
3
3
5
10 20 30 50100200
Conductivity (S/cm)
Figure 10. Electrical Conductivity and Cable
Length
Wiring Precautions (PROFIBUS or
Modbus)
Meter Size
To select the meter size:
(1) For wiring path, avoid places near electrical
equipment that may cause electromagnetic induction
or electrostatic induction interference (such as a
motor, transformer and wireless transmitter).
See Table 2 and 3 to find meter sizes within the velocity
of 0.3 to 39.4 ft/s (0.1 to12m/s) for a specified full-scale
(measuring range high limit) flow. Select one that has
its full-scale velocity between 3.0 and 10 ft/s (1 and
3m/s).
Note: Make sure the full-scale flow rate used for the final
planning stage stays within 39.4ft/s (12m/s) in terms of
flow velocity.
(2) Use a PROFIBUS-PA cable or a RS485 twisted-pair
cable for signal cable.
In addition, make sure to use a shielded cable to
improve noise resistance. Installation of signal cable
in metal conduit is recommended.
Table 2. Flow Rate and Flow velocity
(English unit)
(3) General cables are designed for indoor use where
cables are not exposed to humidity, rain, etc. When
you install cables, make sure to check the operating
conditions such as the operating temperature range
of the cable by contacting its manufacturer.
Unit: gal/min
Flow rate
3.0ft/s
2.561
7.115
11.66
18.21
28.46
48.09
72.85
113.8
177.9
256.1
455.3
711.5
1,025
1,394
1,821
2,305
Size
(inch)
1/2'
1
1 ¼
1 ½
2
2 ½
3
4
5
6
8
10
12
14
16
18
0.328 ft/s 0.98 ft/s
10 ft/s
8.532
23.72
38.86
60.71
94.86
160.3
242.8
379.4
592.9
853.8
1,518
2,372
3,415
4,648
6,071
7,684
39.4 ft/s
33.61
93.37
153.0
239.0
373.5
631.2
956.1
1,494
2,334
3,361
5,975
9,337
13,445
18,300
23,902
30,251
0.2801
0.7781
1.275
1.992
3.112
5.260
7.967
12.45
19.45
28.01
49.80
77.81
112.0
152.5
199.2
252.1
0.8403
2.334
3.824
5.975
9.337
15.78
23.90
37.35
58.35
84.03
149.4
233.4
336.1
457.5
597.5
756.3
(4) When you carry out cable end treatment, use a
dedicated cable stripper to avoid the core wire of the
cable being nicked or damaged. In addition, for
cables, be careful of allowable maximum bend
diameter. (Do not allow excessive twisting or
bending of cables).
(5) Consider installing a PROFIBUS-PA arrester in the
communication path of PROFBUS-PA so that the
electromagnetic flowmeter will not be affected by
lightning, etc.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
Table 3. Flow Rate and Flow velocity
(SI unit)
Ordering Information
1. When ordering the LF654 series flowmeters, refer
to Tables 4 and 5 (Type Specification Codes).
An entry must be made for each of the columns in
each of these tables.
Unit: m3/h
Flow rate
Size
(mm)
15
25
32
40
50
65
80
100
125
150
200
250
300
350
400
450
3.0
m/s
12
m/s
0.1 m/s
0.3 m/s 1.0 m/s
2. Fluid characteristics:
0.06362
0.1767
0.2895
0.4523
0.7067
1.195
1.809
2.827
4.417
6.361
11.31
17.67
25.45
34.64
45.23
57.25
0.1908
0.5301
0.8686
1.357
2.120
3.583
5.428
8.482
13.25
19.08
33.93
53.01
76.34
103.9
135.7
171.7
0.6361
1.767
2.895
4.523
7.067
11.95
18.09
28.27
44.17
63.61
113.1
176.7
254.5
346.4
452.3
572.5
1.908 7.634
5.301 21.21
8.686 34.74
13.57 54.29
21.20 84.82
35.83 143.4
54.28 217.1
84.82 339.3
132.5 530.1
190.8 763.4
229.3 1,357
530.1 2,121
763.4 3,054
1,039 4,156
1,357 5,429
1,717 6,871
(1) Type of fluid to be measured and its characteristics
(2) Fluid temperature
(3) Fluid pressure
(4) Electrical conductivity of the fluid
3. Measuring range
4. I/O function setting
5. Ordering scope
Flow calibration data
6. Other items
Specifications other than standard items
Consult a Toshiba representative when choosing
materials for lining, electrodes, and grounding rings.
Toshiba International Corp. (Houston) stocks
Hazardous location certification type
flowmeters as standard inventory.
About establishment environment
Do not store or install the flowmeter:
• Where there is direct sunlight.
• Where excessive vibration or mechanical shock
occurs.
• Where high temperature or high humidity
conditions exist.
• Where corrosive atmospheres exist.
• Places that can be submerged under water.
• When placing the flowmeter temporarily on the
floor, support it, i.e., with a block so that the
flowmeter does not topple over.
In areas like the following, there may be the case that
infrared switches do not function correctly. (If these
are unavoidable, use an appropriate cover.)
(1) Where unit (operation panel) is exposed to direct
sunlight, reflection of light onto window pane
and diffused light reflection.
(2) Where smoke and steam may occur.
(3) Where exposed to direct snow, ice or mud.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
Table 4. Specification Code (Flange type detector LF654 Series)
Model
Specification Code
Detector category
Description
1
2
3
4
5
6
7
8
9
10 11 12 13 14
Gr.-A
Gr.-B
L
F
6
5
Flange type electromagnetic flowmeter detector
Usage
4
cFMus Class 1 Division 2 Hazardous Location
√
√
Meter size
D
E
S
½"(15mm)
1"(25mm)
1¼"(32mm)
1½"(40mm)
2"(50mm)
2½"(65mm)
3"(80mm)
4"(100mm)
5”(125mm)
6"(150mm)
8"(200mm)
10"(250mm)
12"(300mm)
14"(350mm)
16"(400mm)
18"(450mm)
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
F
G
W
H
J
U
K
L
M
N
P
Q
R
√
√
√
√
√
√
√
√
√
Mounting Style(Note1)(Note6)
Detector/Converter combined type
Detector/Converter separate type
L
M
√
√
√
√
Connection flange standard, Overall length
ASME B 16.5 class 150, ISO length
ASME B 16.5 class 300, ISO length
EN 1092-1 PN 10, ISO length
EN 1092-1 PN 16, ISO length
ASME B 16.5 class 150, Toshiba length
ASME B 16.5 class 300, Toshiba length
EN 1092-1 PN 10, Toshiba length
EN 1092-1 PN 16, Toshiba length
Other (Note 2)
C
D
G
H
1
2
5
6
Z
Electrode Material (Note 3)(Note 4)
316L stainless steel (Standard for PU, HR lining)
Ti (titanium)
Pt-Ir (platinum/iridium)
Ta (tantalum)
Hastelloy C (Equivalent) (Standard for PFA lining)
Lining Materials (Note 3)
PFA
PU(Polyurethane) with NSF certified
HR(Hard Rubber) with NSF certified
Grounding Ring Material (Note 3)(Note 4)
316 stainless steel
B
C
D
E
F
–
–
C
N
E
–
–
–
C
D
E
F
G
H
–
–
316L stainless steel
Ti (titanium)
Ta (tantalum)
Pt-Ir (platinum/iridium)
Hastelloy C (Equivalent)
Flow and calibration velocity range
1.0 to 32.8 ft/s (standard range calibration)
(Note 5)
Excitation and Signal Cables
not provided
A
A
Coating
F
C
PU coating pearl-gray colored
black tar epoxy resin
Size code explanation: √ : Object
: Standard : Option
–: Not available
Note1: In case of LF654 with cFMus approval, Cable glands are not provided. Refer to the part of “Cable connection port” at detector and converter.
Note2: Connection flange standard EN 1092-1 PN10, EN 1092-1 PN 16,JIS B 2220 10K and JIS B 2220 20K are optional for both ISO length and Toshiba
length.
Note3: Consult Toshiba before ordering when choosing materials at the wetting parts.
Note4: In case of PU and HR lining with NSF approval, only 316/316L stainless steel are available, and Hastelloy C & Ti are undergoing testing.
Note5: User specified range upon request, additional charges apply.
Note6: Potting kit is available for submersible option when selecting Detector/Converter separate type with PU or HR lining. Please consult Toshiba for
details.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
TIC-LF654L
Table 5. Specification Code for converters
Model
Specification Code
8
Contents
LF620 LF622
1
L
2
3
6
4
2
5
6
7
9 10 11 12 13 14
type
type
F
Electromagnetic flowmeter converter
0
2
Combined (Integral) type
Separate (Remote) type
Purpose
–
–
F
cFMus class I, Division 2 approved
Shape
Standard type with case
Converter mounting fitting
A
A
C
E
None
–
–
Panel, Accessory for wall mounting (BNP material: SUS304)
Accessory for pipe installation (BNP material: SUS304)
Digital input/output
2
Digital output points 2 (DO1+DO2) +Digital input point 1 (DI)
Current output and Communication function(Note1)
Current output + HART communication
PROFIBUS communication
1
2
3
Current output + Modbus (RS485) communication
Power supply(Note2)
100Vac-240Vac 50/60Hz, 110Vdc
24Vdc
1
2
3
110Vdc
Instruction manual
English
E
Code explanation: : Standard : Option
–: Not available
Note 1: When PROFIBUS communication is provided, current output(4-20mA) and HART communication cannot be used.
When Modbus communication is provided, digital output points 1(DO1) and digital output points (DO2),
digital input point 1(DI), HART communication cannot be used.
Refer to Table 6 for more details.
Note2: Select 110Vdc for test report inspected under the condition of 110Vdc.
Table6. Communication functions and output selection table
Selection of Function
Availability of outputs
Code
(10th digit)
Selected
Communication
HART
4-20mAdc
DO1
DO2
DI
1
2
PROFIBUS
X
3
Modbus
X
X
(Note)
Code explanation: :Available X:Not Available
Note: When digital output 1 function and Modbus communication function are used at one time, TG (signal ground) of the
Modbus communication function cannot be connected (2 line connection).
ISO9001 and ISO14001 are certified.
Specifications are subject to change without notice.