INSTALLATION MANUAL
MANUEL DINSTALLATION
INSTALLATIONS-HANDBUCH
MANUALE DI INSTALLAZIONE
MANUAL DE INSTALACIÓN
MANUAL DE INSTALAÇÃO
INSTALLATIE HANDLEIDING
ÅÃ×ÅÉÑÉÄÉÏ ÅÃÊÁÔÁÓÔÁÓÇÓ
SUPER MODULAR MULTI SYSTEM AIR CONDITIONER
SMMS CLIMATISEUR
SMMS KLIMAGERÄT
SMMS CONDIZIONATORE D'ARIA
SMMS APARATO DE AIRE ACONDICIONADO
SMMS AR CONDICIONADO
SMMS AIRCONDITIONER
SMMS ÊËÉÌÁÔÉÓÔÉÊÏ
SMMS
For commercial use (Not accessible to the general public)
Indoor Unit
Pour usage commercial (Vente interdite au grand public)
Nur für gewerbliche Nutzung (kein öffentlicher Zugang)
Per uso commerciale (Non accessibile a clienti generici)
Para uso comercial (no destinado al público en general)
Para uso comercial (não acessível ao público em geral)
Voor commercieel gebruik (niet geschikt voor huishoudelijk gebruik)
Ãéá åìðïñéêÞ ÷ñÞóç (Ìç äéáèÝóéìï óôï åõñý êïéíü)
Unité intérieure
Raumeinheit
Unità interna
Unidad interior
Unidade interior
Binnenunit
ÅóùôåñéêÞ mïíÜäá
<High-Wall Type>
<Type mural haut>
<Wand modell>
<Tipo per mura alte>
<Tipo parte alta de la pared>
<Tipo para Parede Alta>
<Hogewandmodel>
<Ôýðïò ôïðïèåôçìÝíïõ øçëÜ óôïí ôïß÷ï>
MMK-AP0072H,
MMK-AP0092H,
MMK-AP0122H
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTENTS
Accessory parts and parts to be procured locally ....................................... 1
7 DRAINAGE ............................................................................................. 9
8 REFRIGERANT PIPING ....................................................................... 10
9 ELECTRICWORK ................................................................................ 12
10 APPLICABLE CONTROLS .................................................................. 16
11 TEST RUN ............................................................................................ 18
12 TROUBLESHOOTING .......................................................................... 20
1 PRECAUTIONS FOR SAFETY ............................................................... 2
2 SELECTION OF INSTALLATION PLACE ............................................... 3
3 INSTALLATION OF INDOOR UNIT ........................................................ 5
4 CUTTING A HOLE AND MOUNTING INSTALLATION PLATE .............. 6
5 PIPING AND DRAIN HOSE INSTALLATION .......................................... 7
6 INDOOR UNIT FIXING ............................................................................ 9
SOMMAIRE
Pièces accessoires et pièces non fournies ................................................ 25
1 MESURES DE SECURITE ................................................................... 26
2 SELECTION DU LIEU D’INSTALLATION ............................................. 27
3 INSTALLATION DE L’UNITE INTERIEURE .......................................... 29
6 FIXATION DE L’UNITÉ INTÉRIEURE ................................................... 33
7 ÉVACUATION ........................................................................................ 33
8 TUYAUX DE RÉFRIGÉRANT ............................................................... 34
9 TRAVAUX D’ÉLECTRICITÉ .................................................................. 36
10 COMMANDES UTILISABLES .............................................................. 40
11 ESSAI DE FONCTIONNEMENT ........................................................... 42
12 DÉPANNAGE ........................................................................................ 44
4 DÉCOUPAGE D’UNTROU ET MONTAGE DE LA PLAQUE
D’INSTALLATION ................................................................................. 30
5 INSTALLATION DE LATUYAUTERIE ET DUTUYAU FLEXIBLE
D’ÉVACUATION .................................................................................... 31
INHALT
Zubehör und bauseits bereitzustellendeTeile ............................................ 49
1 SICHERHEITSVORKEHRUNGEN........................................................ 50
2 AUSWAHL DES AUFSTELLUNGSORTES .......................................... 51
3 INSTALLATION DER RAUMEINHEIT ................................................... 53
6 BEFESTIGUNG DER INNENEINHEIT .................................................. 57
7 KONDENSATABLAUF .......................................................................... 57
8 KÜHLMITTELLEITUNGEN ................................................................... 58
9 ELEKTROARBEITEN ........................................................................... 60
10 STEUERUNGSMÖGLICHKEITEN ....................................................... 64
11 TESTLAUF ............................................................................................ 66
12 FEHLERSUCHE ................................................................................... 68
4 HERAUSTRENNEN EINER ÖFFNUNG UND MONTAGE DER
INSTALLATIONSPLATTE ..................................................................... 54
5 INSTALLATION DER ROHRLEITUNGEN UND DES
KONDENSATSCHLAUCHS .................................................................. 55
INDICE
Accessori e parti da acquistare sul posto .................................................. 73
1 PRECAUZIONI PER LA SICUREZZA .................................................. 74
2 SCELTA DEL POSTO D’INSTALLAZIONE ........................................... 75
3 INSTALLAZIONE DELL’UNITÀ INTERNA ............................................ 77
7 SCARICO .............................................................................................. 81
8 TUBAZIONI DEL REFRIGERANTE ...................................................... 82
9 COLLEGAMENTI ELETTRICI .............................................................. 84
10 COMANDI APPLICABILI ...................................................................... 88
11 FUNZIONAMENTO DI PROVA ............................................................. 90
12 RISOLUZIONE DEI PROBLEMI ........................................................... 92
4
TAGLIARE UN FORO E MONTARE LA PIASTRA D’INSTALLAZIONE ... 78
INSTALLAZIONE DEITUBI E DELTUBO FLESSIBILE DI SCARICO ...... 79
6 FISSAGGIO UNITÀ INTERNA .............................................................. 81
5
CONTENIDO
Componentes accesorios y componentes de suministro local ................ 97
1 PRECAUCIONES PARA SU SEGURIDAD........................................... 98
2 SELECCIÓN DEL LUGAR DE INSTALACIÓN ..................................... 99
3 INSTALACIÓN DE LA UNIDAD INTERIOR ........................................ 101
4 Hacer un agujero y montar la placa de instalaciÓN ........................ 102
5 INSTALACIÓN DE LATUBERÍAY LA MANGUERA DE DESAGÜE ... 103
6 FIJACIÓN DE LA UNIDAD INTERIOR ............................................... 105
7 DESAGÜE ........................................................................................... 105
8 TUBERÍA DE REGRIGERANTE......................................................... 106
9 INSTALACIÓN ELÉCTRICA ............................................................... 108
10 CONTROLES APLICABLES .............................................................. 112
11 PRUEBA DE FUNCIONAMIENTO ...................................................... 114
12 RESOLUCIÓN DE PROBLEMAS ....................................................... 116
ÍNDICE
Acessórios e peças adquiridas localmente ............................................. 121
1 PRECAUÇÕES DE SEGURANÇA ..................................................... 122
2 SELECÇÃO DO LOCAL DE INSTALAÇÃO ....................................... 123
3 INSTALAÇÃO DA UNIDADE INTERIOR ............................................ 125
4 ABRIR UM ORIFÍCIO E MONTAR A CHAPA DE INSTALAÇÃO ....... 126
5 INSTALAÇÃO DATUBAGEM E MANGUEIRA DE DRENAGEM ....... 127
6 FIXAÇÃO DA UNIDADE INTERIOR ................................................... 129
7 DRENAGEM ........................................................................................ 129
8 TUBAGEM DE REFRIGERANTE ....................................................... 130
9 TRABALHOS DE ELECTRICIDADE .................................................. 132
10 CONTROLOS APLICÁVEIS ............................................................... 136
11 TESTE DE FUNCIONAMENTO .......................................................... 138
12 RESOLUÇÃO DE PROBLEMAS ........................................................ 140
INHOUD
Accessoires en niet meegeleverde onderdelen ....................................... 145
1 VOORZORGSMAATREGELEN VOOR UWVEILIGHEID ................... 146
2 KEUZE VAN DE LOCATIE VOOR DE INSTALLATIE .......................... 147
3 INSTALLATIEVAN DE BINNENUNIT ................................................. 149
6 MONTERENVAN DE BINNENUNIT ................................................... 153
7 AFVOER.............................................................................................. 153
8 KOELMIDDELLEIDINGEN ................................................................. 154
9 ELEKTRISCHE BEDRADING ............................................................ 156
10 BEDIENINGSELEMENTEN ................................................................ 160
11 WERKINGSTEST ............................................................................... 162
12 STORINGEN VERHELPEN................................................................. 164
4 EEN DOORVOEROPENING MAKEN EN DE INSTALLATIEPLAAT
MONTEREN ........................................................................................ 150
5 INSTALLATIE VAN DE LEIDINGEN EN DE AFVOERSLANG .......... 151
ÐÅÑÉÅ×ÏÌÅÍÁ
Ðáñåëêüìåíá áíôáëëáêôéêÜ êáé ÅîáñôÞìáôá áðü ôçí ôïðéêÞ áãïñÜ .... 169
1 ÐÑÏÖÕËÁÎÅÉÓ ÁÓÖÁËÅÉÁÓ ............................................................. 170
2 ÅÐÉËÏÃÇ ÔÏÕ ×ÙÑÏÕ ÅÃÊÁÔÁÓÔÁÓÇÓ ......................................... 171
3 ÅÃÊÁÔÁÓÔÁÓÇ ÔÇÓ ÅÓÙÔÅÑÉÊÇÓ ÌÏÍÁÄÁÓ ................................ 173
6 ÓÔÅÑÅÙÓÇ ÔÇÓ ÅÓÙÔÅÑÉÊÇÓ ÌÏÍÁÄÁÓ....................................... 177
7 ÁÐÏÓÔÑÁÃÃÉÓÇ ................................................................................. 177
8 ÓÙËÇÍÙÓÇ ØÕÊÔÉÊÏÕ ÌÅÓÏÕ....................................................... 178
9 ÇËÅÊÔÑÉÊÇ ÅÑÃÁÓÉÁ ....................................................................... 180
10 ÅÖÁÑÌÏÓÉÌÏÉ ÅËÅÃ×ÏÉ .................................................................. 184
11 ÄÏÊÉÌÇ ËÅÉÔÏÕÑÃÉÁÓ...................................................................... 186
12 ÁÍÔÉÌÅÔÙÐÉÓÇ ÐÑÏÂËÇÌÁÔÙÍ .................................................... 188
4
ÊÏØÉÌÏ ÔÑÕÐÁÓ ÊÁÉ ÔÏÐÏÈÅÔÇÓÇ ÔÇÓ ÐËÁÊÁÓ ÅÃÊÁÔÁÓÔÁÓÇÓ ..... 174
5 ÅÃÊÁÔÁÓÔÁÓÇ ÓÙËÇÍÙÓÇÓ ÊÁÉ ÅÕÊÁÌÐÔÏÕ ÓÙËÇÍÁ
ÁÐÏÓÔÑÁÃÃÉÓÇÓ ............................................................................... 175
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessory parts and parts to be procured locally
r Accessory parts
Part
No.
Part
No.
Part
No.
Part name (Q'ty)
Part name (Q'ty)
Part name (Q'ty)
1
2
3
4
5
6
Installation plate × 1
Battery × 2
Mounting screw Ø4 × 25 l x 6
Wireless remote controller × 1
Remote controller holder × 1
Pan head wood screw Ø3.1 × 16 l × 2
<Others>
<Separate sold parts>
Name
Part name
Q’ty
Shape
Usage
Owner’ s manual
Installation manual
Paper pattern
Standard wired remote controller
1
Model : RBC-AMT21E
Refrigerant piping
• Piping material used for the conventional refrigerant cannot be used.
• Use copper pipe with 0.8 mm or more thickness for Ø6.4, Ø9.5.
• Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut
attached to the indoor unit of the air conditioner, and use it.
r Parts to be procured locally
Connecting pipe (Liquid side)
(6.4mm (diam.), Nominal (diam.) 1/4” thick 0.8mm)
MMK-AP0072H to MMK-AP0122H
Connecting pipe (Gas side)
(9.5mm (diam.), Nominal (diam.) 3/8” thick 0.8mm)
MMK-AP0072H to MMK-AP0122H
Power supply cord
Cable 3-core 2.5mm2, in conformity with Design 60245 IEC57
1
Download from Www.Somanuals.com. All Manuals Search And Download.
1
PRECAUTIONS FOR SAFETY
• Ensure that all Local, National and International regulations are satisfied.
• Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.
• The precautions described below include the important items regarding safety. Observe them without fail.
• After the installation work, perform a trial operation to check for any problem.
Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
• Ask the customer to keep the Installation Manual together with the Owner’s Manual.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT
DESTROY OZONE LAYER.
The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure is
approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also
been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil
does not enter the refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of
the main unit and installation tools are charged from those for the conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant (R410A).
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does
not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance force and
impurity in it.
CAUTION
To Disconnect the Appliance from Main Power Supply
This appliance must be connected to the main power supply by means of a switch with a contact separation of at
least 3 mm.
WARNING
• Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.
Inappropriate installation may result in water leakage, electric shock or fire.
• Turn off the main power supply switch or breaker before attempting any electrical work.
Make sure all power switches are off. Failure to do so may cause electric shock.
• Connect the connecting wire correctly.
If the connecting wire is connected in a wrong way, electric parts may be damaged.
• When moving the air conditioner for the installation into another place, be very careful not to
enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally
high and it as a result causes pipe burst and injuries on persons.
• Do not modify this unit by removing any of the safety guards or by by-passing any of the safety
interlock switches.
• Exposure of unit to water or other moisture before installation may cause a short-circuit of
electrical parts.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully if there are possible damage.
• Do not install in a place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when handling parts.
• Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
• When the air conditioner is installed in a small room, provide appropriate measures to ensure that
the concentration of refrigerant leakage occur in the room does not exceed the critical level.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
1
PRECAUTIONS FOR SAFETY
• Install the air conditioner securely in a location where the base can sustain the weight adequately.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might
generate.
• Electrical work must be performed by a qualified electrician in accordance with the Installation
Manual. Make sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
• Use the specified wires for wiring connect the terminals securely fix. To prevent external forces
applied to the terminals from affecting the terminals.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.
If a combustible gas leaks, and stays around the unit, a fire may occur.
2
SELECTION OF INSTALLATION PLACE
WARNING
• Install the air conditioner where there is sufficient strength to weight of the unit.
If strength is insufficient, the unit may fall down resulting in human injury.
• Perform a specified installation work to guard against an earthquake.
An incomplete installation can cause accidents by the units failing and dropping.
CAUTION
• Do not install the air conditioner in a location subject to a risk of exposure to combustible gas.
Should the combustible gas leak and collect near the unit, fire may occur.
Upon approval of the customer, install the air conditioner in a place that satisfies the following
conditions.
• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be ensured for safe maintenance and check.
• Place where drained water will not cause any problem.
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas
(hot spring). (Should the unit be used in these places, special protective measures are needed.)
• Place exposed to oil, vapor, oil smoke or corrosive gas.
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place near door or window where may come to contact with the outside air of high humidity. (Dewing may be caused.)
• Place where special spray is frequently used.
• Place with poor ventilation.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation space
Reserve space required to install the indoor unit and for service work.
Keep 100mm or more for clearance between top plate of the indoor unit and the ceiling surface.
Installation diagram of Indoor and outdoor units
Before installing the
For the rear left and left piping
Wall
wireless remote controller
• With the remote controller cover
open, load the batteries supplied
correctly, observeing their polarity.
170mm
or more
Hook
1
Installation
plate
2 Wireless remote controller
Cover
Insert the cushion between the
indoor unit and wall, and tilt the
indoor unit for better operation.
170mm
or more
Hook
3
Batteries
Shield pipe
Do not allow the drain hose to
get slack
Cut the piping hole
sloped slightly
Make sure to run the drain hose
sloped downward.
6
Pan head wood screw
The auxiliary piping can be connected the left, rear left, rear right,
right, bottom right or bottom left.
2
Wireless
remote controller
Right
4
Remote control holder
Rear right
Bottom right
Left
Rear left
Bottom left
∗ When installing the Flow Selector Unit (FS Unit),
keep a space more than 300mm for wiring work.
Installation place
• A place which provides the spaces around the indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet and outlet.
• A place that allows easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit’ s wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to RF noise sources.
(For details, see the owner’ s manual.)
4
Download from Www.Somanuals.com. All Manuals Search And Download.
2
SELECTION OF INSTALLATION PLACE
Remote controller
• A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
• Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such as a
stove.
• Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment.
(This is necessary to prevent image distur-bances or noise interference.)
• The location of the remote controller should be determined as shown below.
(Side view)
(Top view)
Indoor unit
Reception range
Remote controller
Reception
range
Remote controller
* : Axial distance
3
INSTALLATION OF INDOOR UNIT
WARNING
Install the air conditioner certainly to sufficiently withstand the weight.
If the strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work to guard against strong wind or earthquake.
An incomplete installation can cause accidents by the units falling and dropping.
REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be
sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, do not apply force to the refrigerant pipe, drain pan, foamed parts, or resin parts, etc.
• Carry the package by two or more persons, and do not bundle it with PP band at positions other than specified.
Be careful to the following items when installing the unit.
• Considering air discharge direction, select an
installation place where discharge air can circulate
evenly in a room. Avoid to install the unit at place with
“NO GOOD” mark in the right figure.
OK
NO GOOD
Bad installation place
: Not cooled well.
Good installation place
Cooled well all over.
Screen
5
Download from Www.Somanuals.com. All Manuals Search And Download.
4
CUTTING A HOLE AND MOUNTING INSTALLATION PLATE
Cutting a hole
In case of installing the refrigerant pipes from the rear:
1. Decide the hole position for piping at 100mm from
the arrow mark (
drill a hole with Ø65mm at a slight downward slant
) on the installation plate and
Pipe
hole
65 mm
toward outdoor side.
The center of the pipe
hole is above the arrow.
100 mm
NOTE
• When drilling a wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold
separately.
Mounting the installation plate
107
127.5
Hook
For installation of the indoor unit,
use the paper pattern in the accessory parts.
170
85
1
Installation
plate
Hook
Pipe hole
Thread
Hook
Pipe hole
Indoor unit
5
Mounting screw
Weight
When the installation plate is directly mounted on the wall
1. Securely fit the installation plate onto the wall by screwing
it in the upper and lower parts to hook up the indoor unit.
2. To mount the installation plate on a concrete wall with
anchor bolts, utilize the anchor bolt holes as illustrated in
the above figure.
NO OK NO
GOOD GOOD
Anchor bolt
3. Install the installation plate horizontally in the wall.
5mm dia. hole
Projection
15mm or less
CAUTION
When installing the installation plate with a mounting
screw, do not use the anchor bolt hole.
7
Mounting screw
Ø4 × 25
Otherwise the unit may fall down and result in personal
injury and property damage.
Clip anchor
(local parts)
CAUTION
Failure to firmly install the unit may result in personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type walls, make 5mm dia. holes in the wall.
• Insert clip anchors for appropriate
mounting screws.
ꢀ
NOTE
• Secure four corners and lower parts of the installation plate with 4 to 6 mounting screws to install it.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
5
PIPING AND DRAIN HOSE INSTALLATION
Piping and drain hose forming
* Apply thermal-insulation for both refrigerant pipe and drain hose surely so that no dewing generates inside of the
equipment. (Use polyethylene foam for insulating material.)
Rear right
Rear left
Changing
Bottom left
drain hose
Piping
preparation
Left
Die-cutting
front panel slit
Bottom right
Right
1. Die- cutting front panel slit
For piping work at the left side, cut off the left slit for notching of the front panel.
(A knife will produce flaws on the panel, so use nippers.)
2. Changing drain hose
For piping work at the left side, lower left side, and left back side, it is necessary to change the drain hose and
drain cap.
How to remove the drains cap
How to install the drain hose
Clip drain cap by needle- nose pliers, and pull out.
Firmly insert drain hose connecting part until hitting on
a heat insulator.
Heat insulator
Drain hose
How to fix the drains cap
1) Insert hexagonal wrench (Ø4mm) in a center
head.
2) Firmly insert drains cap.
No gap
Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap.
Application causes deterioration
and drain leakage of the plug.
Insert a hexagon
wrench (4 mm)
4 mm
CAUTION
Firmly insert the drain hose and drain cap; otherwise, water may leak.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
In case of right or left piping
• After scribing slits of the front panel with a knife or a
marking-off pin, cut them with a pair of nippers or an
equivalent tool.
Slit
In case of bottom right or bottom left piping
• After scribing slits of the front panel with a knife or a
marking- off pin, cut them with a pair of nippers or an
equivalent tool.
Slit
Left- hand connection with piping
(To the fore front of flare)
Liquid side
Bend the connecting pipe so that it is laid within 43mm above
the wall surface. If the connecting pipe is laid exceeding
43mm above the wall surface, the indoor unit may unstably
be set on the wall. When bending the connecting pipe, make
sure to use a spring bender so as not to crush the pipe.
270mm
170mm
Gas side
Bend the connection pipe within a radius of 30 mm.
Outward form of indoor unit
To connect the pipe after installation of the unit (figure)
R 30 mm (Use polish polyethylene
core or the like for bending pipe.)
˚
80
Use the handle of screwdriver, etc.
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and
wrap the facing tape around them.
CAUTION
• Bind the auxiliary pipes (two) and connecting cable with facing tape tightly. In case of leftward piping and rear-
leftward piping, bind the auxiliary pipes ( two) only with facing tape.
Indoor unit
Auxiliary pipes
Connecting cable
Installation plate
• Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound
on the connecting pipe to avoid double- taping at the joint, moreover, seal the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make sure to insulate both the connecting pipes.
(Use polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
6
INDOOR UNIT FIXING
1. Pass the pipe through the hole in the wall, and hook the
Hook here
Installation plate
1
indoor unit on the installation plate at the upper hooks.
1
2. Swing the indoor unit to right and left to confirm that it is firmly
hooked up on the installation plate.
2
3. While pressing the indoor unit onto the wall, hook it at the
lower part on the installation plate. Pull the indoor unit toward
you to confirm that it is firmly hooked up on the installation
plate.
Hook
Press
(unhook)
• For detaching the indoor unit from the installation plate, pull the
indoor unit toward you while pushing its bottom up at the
specified parts.
Push
Push
7
DRAINAGE
1. Run the drain hose sloped downwards.
Do not form the drain hose
into a wavy shape.
Do not rise the drain hose.
NOTE
• Hole should be made at a slight downward
slant on the outdoor side.
50 mm
or more
2. Put water in the drain pan and make sure that
the water is drained out of doors.
Do not put the
Do not put the
drain hose end in
the drainage ditch.
drain hose end
into water.
3. When connecting extension drain hose,
insulate the connecting part of extension
drain hose with shield pipe.
Shield pipe
Extension drain hose
Inside the
room
Drain hose
CAUTION
Wall
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew- dropping.
Drain
guide
This air conditioner has the structure designed to drain water collected
from dew, which forms on the back of the indoor unit, to the drain pan.
Space for pipes
Therefore, do not store the power cord and other parts at a height
above the drain guide.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
8
REFRIGERANT PIPING
WARNING
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.
• If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
• After the installation work, confirm that refrigerant gas does not leak.
• If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may
generate.
REQUIREMENT
When the refrigerant pipe is long, set the support brackets to fix the pipe with 2.5 to 3m intervals. If the pipe is
not fixed, abnormal sound may generate.
Be sure to use the flare nuts attached to the indoor unit or those for R410A.
Permissible pipe length and permissible height difference
They are different according to the used outdoor unit. For details, refer to the Installation Manual attached to the
outdoor unit.
Piping material and dimensions
Piping material
Model
Phosphor deoxidization joint-less pipe for air conditioner
MMK-AP0072H to MMK-AP0122H
Gas side
Ø9.5
Pipe size (mm)
Liquid side
Ø6.4
• Use a clean and new pipe, and check that impurity such as dust, oil, moisture, etc. does not adhere in the pipe.
A
• Flaring diam. meter size :
Pipe Forming/End Positioning
A (Unit : mm)
Flaring
1. Cut the pipe with a pipe cutter.
+0
A
-
0.4
Outer diam. of copper pipe
R410A
9.1
OK NO GOOD
6.4
9.5
90˚
Obliquity Roughness
Warp
13.2
16.6
19.7
12.7
15.9
2. Insert a flare nut into the pipe, and flare the pipe.
In case of flaring for R410A with the conventional
flare tool, pull it out approx. 0.5 mm more than that
for R22 to adjust to the specified flare size.
The copper pipe gauge is useful for adjusting
projection margin size.
*
As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly manufactured
for R410A are recommended.
However, the conventional tools can be used by
adjusting projection margin of the copper pipe.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
8
REFRIGERANT PIPING
B
• Projection margin in flaring :
B (Unit : mm)
Airtight test/Air purge, etc.
For airtight test, air purge, addition of refrigerant, and
gas leak check, follow the Installation Manual attached
to the outdoor unit.
Rigid (Clutch type)
R410A tool used
Outer diam. of
Conventional tool used
R410A R22
copper pipe
R410A
R22
Open fully valves of the outdoor unit
Gas leak check
6.4
9.5
0 to 0.5 (Same as left) 1.0 to 1.5 0.5 to 1.0
0 to 0.5 (Same as left) 1.0 to 1.5 0.5 to 1.0
0 to 0.5 (Same as left) 1.0 to 1.5 0.5 to 1.0
0 to 0.5 (Same as left) 1.0 to 1.5 0.5 to 1.0
12.7
15.9
Check with a leak detector or soap water whether gas
leaks or not, from the pipe connecting section or cap
of the valve.
Imperial (Wing nut type)
REQUIREMENT
Use a leak detector manufactured exclusively for
HFC refrigerant (R410A, R134a, etc.).
Outer diam. of copper pipe
R410A
R22
6.4
9.5
1.5 to 2.0
1.5 to 2.0
2.0 to 2.5
2.0 to 2.5
1.0 to 1.5
1.0 to 1.5
1.5 to 2.0
1.5 to 2.0
12.7
15.9
Connection of refrigerant pipe
Connect all the refrigerant pipes with flare connecting
work.
• Since the atmospheric pressure only is sealed as the
sealing gas, it is not abnormal that “Pushu…” sound
is not heard when the flare nut is removed.
• Be sure to use a double spanner for pipe connecting
work of the indoor unit.
Work using double spanner
• Refer to the following table for tightening torque.
Connecting pipe Tightening torque
Re-tightening
torque (N•m)
outer dia. (mm)
(N•m)
14 to 18
(1.4 to 1.8 kgf•m)
18
Ø6.4
(1.8 kgf•m)
33 to 42
(3.3 to 4.2 kgf•m)
42
Ø9.5
Ø12.7
Ø15.9
(4.2 kgf•m)
50 to 62
(5.0 to 6.2 kgf•m)
50
(5.0 kgf•m)
68 to 82
(6.8 to 8.2 kgf•m)
68
(6.8 kgf•m)
11
Download from Www.Somanuals.com. All Manuals Search And Download.
9
ELECTRIC WORK
WARNING
1. Using the specified wires, ensure to connect the wires, and fix wires securely so that the
external strength of the wires do not transmit to the connecting part of the terminals.
Incomplete connection or fixation may cause a fire, etc.
2. Be sure to connect earth wire. (Grounding work)
Do not connect the earth wire to gas pipe, city water pipe, lightning rod, or the earth wire of telephone.
Incomplete grounding causes an electric shock.
3. For electric work, strictly follow to the Local Regulation in each country and the Installation
Manual, and use an exclusive circuit.
Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.
CAUTION
Be sure to install an earth leakage breaker.
If an earth leakage breaker is not installed, an electric shock may be caused.
REQUIREMENT
• For power supply wiring, strictly conform to the Local Regulation in each country.
• For wiring of power supply of the outdoor units, follow to the Installation Manual of each outdoor unit.
• Never connect 220–240V power to the terminal blocks (A, B, U1, U2, X, Y, etc.) for control wiring.
(Otherwise, the system will be failed.)
• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.
The coating may melt resulted in an accident.
• After connecting wires to the terminal blocks, provide a trap and fix wires with the wire clamp.
• Store the refrigerant piping line and control wiring line in the same line.
• Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.
Power supply specifications
Cables and remote controller wires are procured locally.
For the power supply specifications, follow to the table below. If capacity is little, it is dangerous because overheat or
seizure may be caused.
For specifications of the power capacity of the outdoor unit and the power supply cables, refer to the Installation
Manual attached to the outdoor unit.
220–240V ~ 50Hz
Power supply
220V ~ 60Hz
Power supply switch/Earth leakage breaker or power supply wiring/fuse rating for
indoor units should be selected by the accummulated total current values of the indoor units.
Indoor unit power supply (*1)
20m or less
50m or less
Q’ty
Twist wire : 2.0 mm²
Twist wire : 2.5 mm²
2
Power supply wiring
Indoor/Outdoor inter-unit wiring (*2)
(Up to 1000m) Twist wire : 1.25 mm²
(Up to 2000m) Twist wire : 2.00 mm²
Wire size
Q’ty
2
Communication line
Central control line wiring (*3)
Remote controller wiring (*4)
(Up to 1000m) Twist wire : 1.25 mm²
(Up to 2000m) Twist wire : 2.00 mm²
Wire size
Q’ty
2
Wire size
Twist wire : 0.5 to 2.0 mm²
12
Download from Www.Somanuals.com. All Manuals Search And Download.
9
ELECTRIC WORK
Indoor unit power supply (*1)
• For the power supply of the indoor unit, prepare the exclusive power supply separated from that of the outdoor unit.
• Arrange the power supply, earth leakage breaker, and main switch of the indoor unit connected to the same
outdoor unit so that they are commonly used.
• Power supply cord specification : Cable 3-core 2.5mm², in conformity with Design 60245 IEC 57.
Indoor/Outdoor inter-unit wiring, Central controller wiring
(*2) (*3)
• 2-core with polarity wires are used for the Indoor/Outdoor inter-unit wiring and Central controller wiring.
• To prevent noise trouble, use 2-core shield wire.
• The length of the communication line means the total length of the inter-unit wire length between indoor and
outdoor units added with the central control system wire length.
Remote controller wiring
(*4)
• 2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.
CAUTION
Remote controller wiring, remote
controller inter-unit wiring
Twist wire: 0.5mm2 to 2.0mm2 × 2
The remote controller wire
(Communication line) and
AC220–240V wires cannot be
parallel to contact each other and
Total wire length of remote controller
wiring and remote controller inter-unit
wiring = L + L1 + L2 + … Ln
In case of wired type only
Up to 500m
cannot be stored in the same
conduits. If doing so, a trouble
may be caused on the control
system due to noise, etc.
In case of wireless type included Up to 400m
Up to 200m
Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Remote
controller
wiring
L1
L2
Ln
(Max. 8 units)
Remote
controller
Remote controller inter-unit wiring
Wiring connection
How to connect the power cable
For the air conditioner that does not have power cable, connect a power cable to it as mentioned below.
1. Open the air inlet grille upward.
2. Remove the four screws securing the front panel.
3. Slightly open the lower part of the front panel then pull the upper part of the front panel toward you to remove it
from the rear plate.
4. After removing the front panel, remove the power cable connect cover and the cord clamp.
5. Connect and secure the power supply cable and secure the cord clamp and the power connect cover.
6. Cut the slit and front panel, and put the power supply cable through the notch.
7. Be sure to smooth the notch with a file, etc.
Air inlet grille
Front panel
REQUIREMENT
• Be sure to pass the cable through the cable
connection port of the indoor unit.
1
2
3
• The low-voltage circuit is provided for the remote
controller.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
• Tighten the screws of the terminal block, and fix the cables with cord
clamp attached to the electric parts box.
(Do not apply tension to the connecting section of the terminal block.)
L
N
U1 U2
A
B
U1 U2
A
B
L
N
Cord clamp
Cord clamp
R(L) S(N)
10mm
Remote
controller cable
L
N
>
ABS
<
Notch
Power supply
cable
110mm
Screw
10mm
Terminal block
40mm
Connector cover
Wiring connection for flow selector unit
How to connect the wiring of flow selector unit
For the flow selector unit that have power supply cord, connect a power supply cable to it as mentioned below.
1. Open the air inlet grille upward.
2. Remove the four screws securing the front panel.
3. Slightly open the lower part of the front panel then pull the upper part of the front panel toward you to remove it
from the rear plate.
4. After removing the front panel, remove the wiring cover and the cord clamp.
5. Connect and secure the power supply cable of flow selector unit and secure the cord clamp.
6. The control wires are included in terminal block part of the power supply.
Take out the control wires outwards through the slit of the terminal block.
7. Fasten the wiring cover surely with screws.
8. Connect the control wire taken out through the slit on the terminal block and the control wire from the flow
selector unit at the relay terminal section.
Earth line
Terminal
block
Cord clamp
Screw
Terminal
block
Screw
Screw
Control wire from
the flow selector
Control wire
Power supply cable
for flow selector unit
Slit of the
terminal block
Wiring cover
14
Download from Www.Somanuals.com. All Manuals Search And Download.
9
ELECTRIC WORK
Remote controller wiring
• Strip off approx. 14mm cover of the wire to be connected.
• Twist wire of the remote controller to be connected with wire of the remote controller unit (or sensor), and press-fit
them with a wire joint. (Wire joints (White: 2 pieces) are included in the accessory of the main remote controller
(sold separately) or wireless remote controller kit (sold separately).)
• As the remote controller wire has no polarity, there is no problem if connections to indoor unit terminal blocks A
and B are reversed.
<Wiring diagram>
Terminal block
for remote controller
wiring of indoor unit
Approx. 200mm
W : White
B : Black
Remote controller wiring
A
B
W
B
Remote
controller unit
or sensor part
Wire from remote
controller or sensor
Wire joint
Remote controller wire
(Local procure)
Wire from remote controller unit
or sensor
Connecting
part
Wiring between indoor and outdoor units
NOTE
An outdoor unit connected
with indoor/outdoor inter-unit
wire becomes automatically
the header unit.
Header unit
Follower unit
Earth leakage breaker
(Earth)
Earth
Outdoor power supply
3-phase
380–415V, 50Hz
380V, 60Hz
Inter-unit wire between outdoor units
Central control line wire
Connection of shield
wire closed terminal
(Open)
Power supply
Indoor/Outdoor inter-unit wire
220–240V
~
50Hz
Connection of shield
wire closed terminal
220V
~
60Hz
Pull box
Remote controller,
for central control, etc.
(Earth)
Earth leakage breaker
Indoor power supply
220–240V
~
50Hz
Switch
220V
~
60Hz
(Remote controller group operation)
Indoor unit
Address setup
Set up the addresses according to the Installation Manual attached to the outdoor unit.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
10
APPLICABLE CONTROLS
NOTIFICATION
When using the equipment at the first time, it will take a lot of time that the remote controller accepts an
operation after power was on. However, it is not a trouble.
• Automatic address
• While automatic addressing, the operation cannot be performed on the remote controller.
• For automatic addressing, Max. 10 minutes (generally, approx. 5 minutes) are required.
• When power will be turned on after finish of automatic addressing;
• It will require Max. 10 minutes (generally, approx. 3 minutes) that outdoor unit starts operation after power was on.
As all have been set to [Standard] at the shipment, change the setup of the indoor unit if necessary.
To change the setup, use the main remote controller (wired remote controller).
The wireless remote controller is unavailable for address setting.
* The setup change for wireless remote controller, sub remote controller, or remote controller-less system
(Central control remote controller only is provided.) is impossible. In these cases, prepare and mount a
separate main remote controller.
CODE No.
Exchange of applicable control setup
UNIT No.
R.C. No.
Basic operation procedure for setup exchange
4
2
Change the setup while operation of the equipment stops.
6
UNIT
(Be sure to stop the operation of a set.)
3
1
SET CL
5
Procedure
Description
buttons simultaneously for 4 seconds or more, after a while, the display part
CL
SET
When pushing
,
, and
flashes as shown in the figure.
Check that the displayed item code is [10].
CODE No.
• If the item code indicates other than [10], push
button to erase
*
UNIT No.
the display, and then retry the operation from the first step.
1
(For some time after
button has been pushed, the operation of
R.C. No.
the remote controller cannot be accepted.)
(In a group control, the firstly displayed
indoor unit No. becomes the header unit.)
(* The display changes according to the indoor unit model.)
UNIT
Every pushing
button, the indoor unit No. in the group control is displayed successively. Select an
indoor unit of which setup to be changed.
In this time, the position of the indoor unit of which setup to be
changed can be confirmed because the fan and the flap of the
selected indoor unit work.
2
Using
code [**].
,
buttons of set temperature, specify the item
CODE No.
3
4
UNIT No.
** **
R.C. No.
Using
,
buttons of timer time, select set data [****].
** **
**
SET
Push
button. In this time, if the display changes from flashing to lighting, the setup completes.
• To change the setup of an indoor unit other than the selected one, start operation from Procedure 2.
5
6
• To change the setup of another setup in the selected indoor unit, start operation from Procedure 3.
CL
Pushing
button clears the set up contents which have been already set. In this case, retry from Procedure 2.
When the setup finished, push
button. (The setup is determined.)
Pushing
button deletes the display and returns the status to
normal stop status.
(For some time after
button has been pushed, the operation of
the remote controller cannot be accepted.)
16
Download from Www.Somanuals.com. All Manuals Search And Download.
10
APPLICABLE CONTROLS
Change of lighting time of filter sign
Adjustment of air direction
According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
1. Using the remote controller switch, change the up/
down air direction by moving the horizontal flap.
2. Adjust the right/left air direction by bending the
vertical grille inside of the air outlet port with hands.
Follow to the basic operation procedure
(1 → 2 → 3 → 4 → 5 → 6 ).
• For the item code in Procedure 3 , specify [01].
• For the [Set data] in Procedure 4 , select the setup
data of filter sign lighting time from the following
table.
REQUIREMENT
Do not touch the horizontal flap directly with
hands; otherwise a trouble may be caused.
For handling of the horizontal flap, refer to
“Owner’s Manual” attached to the outdoor unit.
Setup data
0000
Filter sign lighting time
None
0001
150H (At shipment from factory)
Group control
0002
2500H
5000H
In a group control, a remote controller can control up
to maximum 8 units.
0003
• The wired remote controller only can control a group
control. The wireless remote controller is unavailable
for this control.
0004
10000H
• For cabling procedure and cables of the individual
line (Identical refrigerant line) system, refer to
“Electric work” in this Manual.
To secure better effect of heating
• Cabling between indoor units in a group is performed
in the following procedure.
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Connect the indoor units by connecting the remote
controller inter-unit cables from the remote controller
terminal blocks (A, B) of the indoor unit connected
with a remote controller to the remote controller
terminal blocks (A, B) of the other indoor unit.
(No polarity)
Follow to the basic operation procedure
(1 → 2 → 3 → 4 → 5 → 6 ).
• For the item code in Procedure 3 , specify [06].
• For address setup, refer to the Installation Manual
• For the set data in Procedure 4 , select the setup
data of shift value of detection temperature to be set
up from the table below.
attached to the outdoor unit.
NOTE
Setup data
0000
Detection temp shift value
Net work adapter (Model TCB-PCNT20E) can not
connect to this High Wall type air conditioner.
No shift
0001
+1°C
0002
+2°C (At shipment from factory)
0003
+3°C
+4°C
+5°C
+6°C
0004
0005
0006
17
Download from Www.Somanuals.com. All Manuals Search And Download.
11
TEST RUN
Before test operation
WARNING
• Before turning on the power supply, carry out the following items.
To protect the compressor at
starting time, keep power-ON
condition before 12 hours or more.
1) Using 500V-megger, check there is 1MΩ or more between the
terminal block of the power supply and the earth. If 1MΩ or less
is detected, do not run the unit.
2) Check that all the valves of the outdoor unit are fully opened.
• Never push the electromagnetic contactor to carry out a forced test operation.
(It is very dangerous because a protective device does not work.)
How to execute test operation
• Using the remote controller, check the operation in the usual operation. For the operation procedure, refer to the
attached Owner’s Manual.
A forced test operation can be executed in the following procedure under condition of thermo-OFF of room
temperature.
In order to prevent a serial operation, the forced test operation is released after 60 minutes and returns to the
usual operation.
NOTE
2, 4
Do not use a forced operation in cases other
than test operation because it applies an
excessive load to the air conditioner.
3
UNIT
1, 5
SET CL
In case of wired remote controller
Procedure
Description
Keep
button pushed for 4 seconds or more. [TEST] is displayed
on the display part and the selection of mode in the test mode is
permitted.
1
TEST
Push
button.
2
3
4
5
Using
button, select the operation mode, [COOL] or [HEAT].
• Do not run the air conditioner in a mode other than [COOL] or [HEAT].
• The temperature controlling function does not work during test
operation.
• The detection of error is performed as usual.
After the test operation, push
button to stop the operation.
(Display part is same as procedure 1 )
Push
button to cancel (release from) the test operation mode.
([TEST] disappears on the display part and the status returns to a
normal stop status.)
18
Download from Www.Somanuals.com. All Manuals Search And Download.
11
TEST RUN
In case of wireless remote controller (Forced test operation is performed in a different way.)
REQUIREMENT
1. For the operation procedure, be sure to follow the Owner’s Manual.
2. Finish the forced cooling operation in a short time because it applies excessive strength to the air conditioner.
3. A test operation of forced heating is unavailable. Perform a test operation by heating operation using the
switches of the remote controller.
However heating operation may be not carried out according to the temperature conditions.
• Check wiring/piping of indoor and outdoor units
1. Open the front panel.
2. When pushing “TEMPORARY” button for 10 seconds or more, “Pi!” sound is heard and the operation changes
to a forced cooling operation. After approx. 3 minutes, a cooling operation starts forcedly.
Check cool air starts blowing. If the operation does not start, check wiring again.
3. To stop a test operation, push “TEMPORARY” button once again (Approx. 1 second).
The up/down air flow adjusting plate closes and the operation stops.
• Check transmission of remote controller
1. Push “START/STOP” button of the remote controller to check an operation can also start by the remote
controller.
• When pushing “TEMPORARY” button once (For 1 second), the operation changes to automatic operation.
For a forced cooling operation, keep the “TEMPORARY” button pushed over 10 seconds.
• “Cooling” operation by the remote controller may be unavailable according to the temperature conditions.
Check wiring/piping of the indoor and outdoor units in forced cooling operation.
TEMPORARY button
TEMPORARY button
19
Download from Www.Somanuals.com. All Manuals Search And Download.
12
TROUBLESHOOTING
Confirmation and check
When a trouble occurred in the air conditioner, the
check code and the indoor unit No. appear on the
display part of the remote controller.
CODE No.
UNIT No.
The check code is only displayed during the operation.
R.C. No.
If the display disappears, operate the air conditioner
according to the following “Confirmation of error
history” for confirmation.
Check code
Indoor unit No. in which
an error occurred
Confirmation of error history
When a trouble occurred on the air conditioner, the
error history can be confirmed with the following
procedure.
(The error history is stored in memory up to 4 errors.)
UNIT
This history can be confirmed from either operating
status or stop status.
3
2
SET CL
1
Procedure
Description
buttons simultaneously for 4 seconds or
SET
When pushing
and
more, the right display appears.
CODE No.
If [Service Check] is displayed, the mode enters in the error history
mode.
UNIT No.
1
• [01: Order of error history] is displayed in CODE No. window.
R.C. No.
• [Check Code] is displayed in CHECK window.
• [Indoor unit address in which an error occurred] is displayed in
UNIT No.
Every pushing
,
buttons, the error history stored in the memory is displayed in order.
The numbers in CODE No. indicates CODE No. [01] (Latest) → [04] (Oldest).
2
3
CAUTION
Do not push
button because all the error history of the indoor unit will be deleted.
CL
After confirmation, push
button to return to the usual display.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
12
TROUBLESHOOTING
Check method
On the remote controller (Main remote controller, Central control remote controller) and the interface P.C. board of
the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C.
board) to display the operation is provided. Therefore the operation status can be known. Using this self-diagnosis
function, a trouble or position with error of the air conditioner can be found as shown in the table below.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of check from indoor remote controller: See “Main remote controller display” in the list.
• In case of check from outdoor unit: See “Outdoor 7-segment display” in the list.
• In case of check from indoor unit with wireless remote controller: See “Sensor block display of receiving unit” in the list.
AI-NET : Artificial Intelligence.
IPDU : Intelligent Power Drive Unit
Terminology
¡ : Lighting,
: Flashing, l : Goes off
¤
ALT. : Flashing is alternately when there are two flashing LED.
SIM : Simultaneous flashing when there are two flashing LED.
Check code
Wireless remote controller
Sensor block display
of receiving unit
Main
remote
Outdoor 7-segment display
Auxiliary code
Check code name
Judging device
controller
display
Operation
Timer Ready Flash
Communication error between indoor and
remote controller
(Detected at remote controller side)
E01
—
—
Remote controller
l
l
¤
E02
E03
—
—
—
—
Remote controller transmission error
Remote controller
Indoor
l
l
l
l
¤
¤
Communication error between indoor and
remote controller (Detected at indoor side)
Communication circuit error between indoor/
outdoor (Detected at indoor side)
E04
—
—
Indoor
I/F
l
l
l
l
l
l
¤
¤
¤
No. of indoor units in which
sensor has been normally received
Decrease of No. of indoor units
E06
E06
E07
Communication circuit error between indoor/
outdoor (Detected at outdoor side)
—
—
I/F
E08
E09
E10
E08
—
Duplicated indoor addresses
Duplicated indoor addresses
Indoor / I/F
Remote controller
Indoor
l
l
l
l
l
l
¤
¤
¤
—
—
Duplicated main remote controllers
Communication error between indoor MCU
—
01: Indoor/Outdoor communication
02: Communication between
outdoor units
E12
E12
Automatic address start error
I/F
l
l
¤
E15
E16
E18
E19
E15
E16
—
—
Indoor is nothing during automatic addressing
Capacity over / No. of connected indoor units
Communication error between indoor units
Outdoor header units quantity error
I/F
I/F
l
l
l
l
l
¤
¤
l
00: Capacity over
01 ~: No. of connected units
l
—
Indoor
I/F
¤
l
00: Header is nothing
02: Two or more header units
E19
¤
¤
01: Outdoor of other line connected
02: Indoor of other line connected
Other line connected during automatic
address
E20
E20
I/F
l
l
Sending error in communication between
outdoor units
E23
E25
E26
E28
E23
E25
E26
E28
—
—
I/F
I/F
I/F
I/F
l
l
l
l
l
l
l
l
¤
¤
¤
¤
Duplicated follower outdoor addresses
Decrease of No. of connected outdoor units
Follower outdoor unit error
No. of outdoor units which
received signal normally
Detected outdoor unit number
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 error
E31
E31
04: Fan IPDU error
05: IPDU + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
IPDU communication error
I/F
l
l
¤
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Check code
Wireless remote controller
Sensor block display
of receiving unit
Main
remote
Outdoor 7-segment display
Check code name
Judging device
controller
display
Auxiliary code
Operation
Timer Ready Flash
F01
F02
F03
F04
F05
F06
F07
F08
F10
F12
—
—
—
—
—
—
—
—
—
—
—
—
ALT
ALT
ALT
ALT
ALT
ALT
ALT
ALT
ALT
ALT
Indoor TCJ sensor error
Indoor
Indoor
Indoor
I/F
l
l
l
¡
¡
¡
¡
¡
l
¡
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
Indoor TC2 sensor error
Indoor TC1 sensor error
TD1 sensor error
—
F04
F05
F06
F07
F08
—
TD2 sensor error
I/F
TE1 sensor error
I/F
TL sensor error
I/F
TO sensor error
I/F
Indoor TA sensor error
TS1 sensor error
Indoor
I/F
F12
01: Comp. 1 side
02: Comp. 2 side
F13
F13
ALT
TH sensor error
IPDU
¡
¤
¤
F15
F16
F23
F24
F29
F31
F15
F16
F23
F24
—
—
—
—
—
—
—
ALT
ALT
ALT
ALT
SIM
SIM
Outdoor temp. sensor miscabling (TE, TL)
Outdoor pressure sensor miscabling (Pd, Ps)
Ps sensor error
I/F
I/F
¡
¡
¡
¡
l
¡
¤
¤
¤
¤
¤
¤
l
l
l
¤
¤
¤
¤
¤
¤
¤
¤
¤
I/F
Pd sensor error
I/F
Indoor other error
Indoor
I/F
F31
Indoor EEPROM error
01: Comp. 1 side
02: Comp. 2 side
H01
H02
H03
H01
H02
H03
Compressor break down
IPDU
l
l
l
Magnet switch error
Overcurrent relay operation
Compressor trouble (lock)
MG-SW
Overcurrent relay
IPDU
01: Comp. 1 side
02: Comp. 2 side
01: Comp. 1 side
02: Comp. 2 side
Current detect circuit system error
IPDU
H04
H06
H07
H04
H06
H07
—
—
—
Comp 1 case thermo operation
Low pressure protective operation
Oil level down detective protection
I/F
I/F
I/F
l
l
l
l
l
l
¤
¤
¤
01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
04: TK4 sensor error
H08
H14
H16
H08
H14
H16
Oil level detective temp sensor error
Comp 2 case thermo operation
I/F
I/F
l
l
l
l
l
l
¤
¤
¤
—
01: TK1 oil circuit system error
02: TK2 oil circuit system error
03: TK3 oil circuit system error
04: TK4 oil circuit system error
Oil level detective circuit error
Magnet switch error
Overcurrent relay operation
I/F
MG-SW
Overcurrent relay
L03
L04
—
—
—
SIM
SIM
Indoor center unit duplicated
Indoor
I/F
l
¤
¤
¤
¤
¤
¤
L04
Outdoor line address duplicated
¡
Duplicated indoor units with priority
(Displayed in indoor unit with priority)
L05
L06
—
—
SIM
SIM
I/F
I/F
l
l
Duplicated indoor units with priority
(Displayed in unit other than indoor unit with priority)
L06
No. of indoor units with priority
¤
¤
L07
L08
L09
L10
L20
L28
—
—
—
—
—
—
—
SIM
SIM
SIM
SIM
SIM
SIM
Group line in individual indoor unit
Indoor group/Address unset
Indoor capacity unset
Indoor
Indoor, I/F
Indoor
l
l
l
¡
¡
¡
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
¤
L08
—
L10
L20
L28
Outdoor capacity unset
I/F
Duplicated central control addresses
Over No. of connected outdoor units
AI-NET, Indoor
I/F
01: IPDU1 error
02: IPDU2 error
03: IPDU3 error
L29
L29
04: Fan IPDU error
05: IPDU1 + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
SIM
SIM
No. of IPDU error
I/F
¡
¤
¤
¤
¤
L30
L30
L31
Detected indoor address
Indoor outside interlock
Extended I/C error
Indoor
I/F
¡
—
—
—
22
Download from Www.Somanuals.com. All Manuals Search And Download.
12
TROUBLESHOOTING
Check code
Wireless remote controller
Sensor block display
of receiving unit
Main
remote
Outdoor 7-segment display
Auxiliary code
Check code name
Judging device
controller
display
Operation
Timer Ready Flash
ALT
P01
P03
—
—
—
Indoor fan motor error
Indoor
I/F
l
¤
l
¤
¤
P03
ALT
ALT
Discharge temp. TD1 error
¤
01: Comp. 1 side
02: Comp. 2 side
P04
P05
P07
P04
P05
P07
High-pressure SW system operation
IPDU
I/F
l
l
l
¤
¤
¤
l
l
l
¤
¤
¤
01: Phase-missing detection
02: Phase error
ALT
ALT
Phase-missing detection /Phase error
Heat sink overheat error
01: Comp. 1 side
02: Comp. 2 side
IPDU, I/F
P10
P12
P13
P10
—
Detected indoor address
ALT
ALT
ALT
Indoor overflow error
Indoor
Indoor
I/F
¤
¤
¤
¤
¤
¤
—
—
Indoor fan motor error
P13
Outdoor liquid back detection error
01: TS condition
02: TD condition
P15
P15
ALT
Gas leak detection
I/F
l
¤
¤
P17
P19
P20
P17
P19
P20
—
Detected outdoor unit number
—
ALT
ALT
ALT
Discharge temp. TD2 error
4-way valve inverse error
I/F
I/F
I/F
l
l
l
¤
¤
¤
¤
¤
¤
High-pressure protective operation
0
1
: IGBT short
: Fan motor position
detective circuit error
: Fan motor trouble
: TH sensor temp. error
(Heat sink overheat)
: TH sensor error
: Vdc output error
3
C
P22
P22
ALT
Outdoor fan IPDU error
IPDU
l
¤
¤
D
E
01: Comp. 1 side
02: Comp. 2 side
P26
P29
P26
P29
ALT
ALT
ALT
G-TR short protection error
IPDU
IPDU
l
l
l
¤
¤
¤
¤
¤
¤
01: Comp. 1 side
02: Comp. 2 side
Comp position detective circuit system error
Other indoor unit error
(Group terminal unit error)
P31
P31
—
—
Indoor
—
—
By alarm deviceALT
Error in indoor group
AI-NET
Error detected by TCC-LINK central control device
Check code
Outdoor 7-segment display
Auxiliary code
—
Wireless remote controller
Sensor block display
of receiving unit
Central
control
Check code name
Judging device
device
indication
Operation
Timer Ready Flash
Sending error in TCC-LINK central
control device
C05
C06
C12
—
—
—
—
TCC-LINK
TCC-LINK
Receiving error in TCC-LINK central
control device
—
—
—
—
Batch alarm of general-purpose
equipment control interface
General-purposeequipment
I/F
Group control branching unit error
Duplicated central control addresses
Differs according to error contents of unit with occurrence of alarm
(L20 is displayed.)
P30
TCC-LINK
—
—
Terminology
TCC-LINK : TOSHIBA Carrier Communication Link.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
New check code
1. Difference between the new check code and the current system
The displaying method of the check code changes in this model and after.
Check code in current system
New check code
Used characters
Characteristics of code classification Few classification of communication/incorrect setup system
Block display Indoor P.C. board, Outdoor P.C. board, Cycle, Communication
Hexadecimal notation, 2 digits
Alphabet + Decimal notation, 2 digits
Many classification of communication/incorrect setup system
Communication/Incorrect setup (4 ways), Indoor protection,
Outdoor protection, Sensor, Compressor protection, etc.
<Display on wired remote controller>
• [ ] goes on.
Display
Classification
A
C
E
F
H
J
Unused
• [UNIT No.] + Check code + Operation lamp (Green) flash
Central control system error
Communication system error
Each sensor error (Failure)
Compressor protective system error
Unused
<Display on sensor part of wireless>
• Block display of combination of [ ] [ ] [
]
→
<Display on indicater on wireless remote controller
receiver part>
• Unit No. and check code are displayed.
L
P
Setup error, Other errors
Protective device operation
• In a case of error with auxiliary code, check code and
auxiliary code are displayed alternately.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNINGS ON REFRIGERANT LEAKAGE
Important
Check of Concentration Limit
NOTE 2 :
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its concentration will not
exceed a set limit.
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws to be imposed
which protect the ozone layer. However, since it
contains more than air, it poses the risk of suffocation if
its concentration should rise excessively. Suffocation
from leakage of R410A is almost non-existent. With the
recent increase in the number of high concentration
buildings, however, the installation of multi air
conditioner systems is on the increase because of the
need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying
power etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of
the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure
so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event
of an emergency, measures can be made before injury
can occur).
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned room
and the refrigerant piping is interconnected, the
smallest room of course becomes the object. But
when a mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device.
The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
≤ Concentration limit (kg/m³)
Refrigerant piping
Outdoor unit
The concentration limit of R410A which is used in multi
air conditioners is 0.3kg/m³.
Very
small
Indoor unit
room
NOTE 1 :
Small
room
Medium
room
Large room
Mechanical ventilation device - Gas leak detector
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.
NOTE 3 :
The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows:
(When the ceiling is 2.7m high)
Outdoor unit
e.g., charged
e.g.,
amount (10kg)
charged amount (15kg)
40
Range below the
35
m²
density limit
of 0.3 kg/m³
30
25
20
15
10
5
(countermeasures
not needed)
Room A Room B Room C Room D Room E Room F
Indoor unit
Range above
the density limit
of 0.3 kg/m³
(countermeasures
needed)
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15kg.
0
10
20
30
Total amount of refrigerant
kg
Download from Www.Somanuals.com. All Manuals Search And Download.
CONFIRMATION OF INDOOR UNIT SETUP
Prior to delivery to the customers, check the address and setup of the indoor unit, which has been installed in this
time and fill the check sheet (Table below). Deta of four units can be entered in this check sheet. Copy this sheet
according to the No. of the indoor units. If the installed system is a group control system, use this sheet by entering
each line system into each installation manual attached to the other indoor units.
REQUIREMENT
This check sheet is required for maintenance after installation. Be sure to fill this sheet and then pass this
Installation Manual to the customers.
Indoor unit setup check sheet
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Room name
Model
Room name
Model
Room name
Model
Room name
Model
Check indoor unit address. (For check method, refer to Applicable controls in this sheet.)
* In case of a single system, it is unnecessary to enter the indoor address. (Item code: Line [12], Indoor [13], Group [14], Central control [03] )
Line Indoor Group Line Indoor Group Line Indoor Group Line
Indoor
Group
Central control address
Central control address
Central control address
Central control address
Various setup
Various setup
Various setup
Various setup
Have you changed high ceiling setup? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.
(For check method, refer to Applicable controls in this sheet.) * In case of replacement of short plugs on indoor microcomputer P.C. board, setup is automatically changed.
High ceiling setup
(Item code [5d])
High ceiling setup
(Item code [5d])
High ceiling setup
(Item code [5d])
High ceiling setup
(Item code [5d])
o NO CHANGE
o NO CHANGE
o NO CHANGE
o NO CHANGE
o STANDARD
o HIGH CEILING 1
o HIGH CEILING 3
[0000]
[0001]
[0003]
o STANDARD
o HIGH CEILING 1
o HIGH CEILING 3
[0000]
[0001]
[0003]
o STANDARD
o HIGH CEILING 1
o HIGH CEILING 3
[0000]
[0001]
[0003]
o STANDARD
o HIGH CEILING 1
o HIGH CEILING 3
[0000]
[0001]
[0003]
Have you changed lighting time of filter sign? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.
(For check method, refer to Applicable controls in this sheet.)
Filter sign lighting time
(Item code [01])
Filter sign lighting time
(Item code [01])
Filter sign lighting time
(Item code [01])
o NO CHANGE
o NONE
Filter sign lighting time
(Item code [01])
o NO CHANGE
o NONE
o NO CHANGE
o NONE
o NO CHANGE
o NONE
[0000]
[0001]
[0002]
[0003]
[0004]
[0000]
[0001]
[0002]
[0003]
[0004]
[0000]
[0001]
[0002]
[0003]
[0004]
[0000]
[0001]
[0002]
[0003]
[0004]
o
o
o
150H
2500H
5000H
o
o
o
150H
2500H
5000H
o
o
o
150H
2500H
5000H
o
o
o
150H
2500H
5000H
o 10000H
o 10000H
o 10000H
o 10000H
Have you changed detected temp. shift value? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.
(For check method, refer to Applicable control in this sheet.)
Detected temp. shift value setup
(Item code [06])
Detected temp. shift value setup
(Item code [06])
Detected temp. shift value setup
(Item code [06])
Detected temp. shift value setup
(Item code [06])
o NO CHANGE
o NO CHANGE
o NO CHANGE
o NO CHANGE
o NO SHIFT
o +1°C
o +2°C
o +3°C
o +4°C
o +5°C
o +6°C
[0000]
[0001]
[0002]
[0003]
[0004]
[0005]
[0006]
o NO SHIFT
o +1°C
o +2°C
o +3°C
o +4°C
o +5°C
o +6°C
[0000]
[0001]
[0002]
[0003]
[0004]
[0005]
[0006]
o NO SHIFT
o +1°C
o +2°C
o +3°C
o +4°C
o +5°C
o +6°C
[0000]
[0001]
[0002]
[0003]
[0004]
[0005]
[0006]
o NO SHIFT
o +1°C
o +2°C
o +3°C
o +4°C
o +5°C
o +6°C
[0000]
[0001]
[0002]
[0003]
[0004]
[0005]
[0006]
Incorporation of parts sold separately Incorporation of parts sold separately Incorporation of parts sold separately Incorporation of parts sold separately
Have you incorporated the following parts sold separately? If incorporated, fill check mark [×] in each [ITEM].
(When incorporating, the setup change is necessary in some cases. For setup change method, refer to Installation Manual attached to each part sold separately.)
Panel
o Standard panel
Panel
o Standard panel
Panel
o Standard panel
Panel
o Standard panel
Filter
Filter
Filter
Filter
o Super long life filter
o Super long life filter
o Super long life filter
o Super long life filter
o Others (
o Others (
)
)
o Others (
o Others (
)
)
o Others (
o Others (
)
)
o Others (
o Others (
)
)