Thomas Betts Furnace RGM 405 User Manual

Model CAUA  
Gas-Fired, Indoor, Vertical (Upflow)  
Power-Vented Heater  
C E R T I F I E D  
INSTALLATION FORM RZ 405 (Version B)  
Obsoletes Form RGM 405 (Version A)  
APPLIESTO:  
Installation  
Table of Contents  
Installation and Operation ...........................Paragraphs 1-18 .... Pages 1-18  
Optional Accessories ................................ Paragraphs 19-21 .. Pages 19-21  
Check Installation and Start-Up ........................Paragraph 22 .. Pages 22-23  
Index  
By Page No.  
Index  
By Page No. Index  
By Page No.  
Belt Drive ............................................. 15  
Blower Motor and Drive ...................... 15  
Check/Test/Start-Up ............................. 22  
Clearances ................................................ 2  
Combustion Air ...................................... 4  
Combustion Air Proving Switch ........... 15  
Concentric Adapter ............................ 2, 5  
Condensate Drain .......................... 14  
Confined Space Installation .................. 10  
Cased Cooling Coil (Model ACU) ..... 2, 19  
Control Location Illustration ................. 15  
Dimensions ............................................. 3  
Discharge Plenum (Optional) ............ 2, 21  
Duct Connections ................................. 12  
Electrical Supply and Connections ....... 14  
Filter Cabinet (Optional) .................. 2, 20  
Gas Piping and Pressures ..................... 13  
Gas Valve .............................................. 16  
General .................................................... 1  
Hazard Intensity Levels ......................... 2  
Ignition System ..................................... 16  
Inlet Base (Optional) ......................... 2, 21  
Installation Codes ................................... 2  
Mixing Cabinet (Optional) .............. 2, 21  
Motor Amps ......................................... 16  
Mounting the Heater .............................. 2  
Start-Up ................................................. 22  
Thermostat ........................................... 14  
Uncrating and Preparation ...................... 2  
Vent and Combustion Air ....................... 4  
Determine Type of Vent ........................ 4  
Power Vent Only Installation ......... 10-11  
Separated-Combustion Installation ... 5-9  
Warranty .................................................. 2  
Wiring Diagrams .............................. 17-19  
REFERENCES:  
Installation Manual for Optional Filter Cabinet, RZ 405-FC  
Installation Manual for Optional Mixing Box, RZ 405-MB  
Installation Instructions for Optional Inlet Base, RZ 405-IB  
Installation Instructions for Optional Discharge Plenum, RZ 405-DP  
Operation/Maintenance/Service Manual, Form RZ 405-OMS  
Installation Manual for Model ACU Cooling Coil, RZ 405-CC  
Gas Conversion Instructions for Model CAUA, RZ 405-GC  
FOR YOUR SAFETY  
FOR YOUR SAFETY  
What to do if you smell gas:  
Do not store or use gasoline or other flammable  
vapors and liquids in the vicinity of this or any  
other appliance.  
• Do not try to light any appliance.  
• Do not touch any electrical switch; do not  
use any phone in your building.  
GENERAL  
Installation should be done by a qualified agency in accordance with the  
instructions in this manual and in compliance with all codes and re-  
quirements of authorities having jurisdiction. The instructions in this  
manual apply to the heater model shown below.  
• Immediately call your gas supplier from a  
neighbor's phone. Follow the gas supplier's  
instructions.  
Model  
CAUA  
Description  
• If you cannot reach your gas supplier, call  
your fire department.  
Gas-Fired,  
Power-Vented,  
Vertical (Upflow)  
Heater  
WARNING: Improper installation, adjustment,  
alteration, service, or maintenance can cause  
property damage, injury, or death. Refer to this  
manual. For assistance or additional information,  
consult a qualified installer, service agency, or the  
gas supplier.  
Model CAUA heaters are design-certified by the Canadian Standards  
Association (CSA) to ANSI Z83.6 and CGA 2.6-M96 for industrial/  
commercial installations in the United States and Canada. Heaters are  
available for use with either natural or propane gas. The type of gas, the  
firing rate, and the electrical characteristics are on the unit rating plate.  
A Model CAUA heater requires installation of an inlet air duct or an  
optional inlet air base and a supply duct or an optional discharge ple-  
num. This heater may be installed as a separated-combustion system  
(taking combustion air from outside) or as a power-vented system  
(taking combustion air from the space where the heater is installed).  
WARNING: Gas-fired appliances are not  
designed for use in hazardous atmospheres  
containing flammable vapors or combustible dust.  
See Hazard Levels, page 2.  
Mfg No. 164771, Page 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Dimensions  
Figure 1 - Dimensions of Model CAUA  
1” (25mm)  
3-5/8” (92mm)  
Right  
Side  
View  
13-1/4”  
(337mm)  
Top View  
A
C Plenum Opening  
Alternate  
Gas  
Connection  
D
Plenum  
Opening  
Corner indicators for  
cutting inlet air opening  
B
16”  
(406mm)  
Electrical  
(supply voltage)  
Combustion Air Cutout  
Venter Outlet  
Gas  
150, 200, 250 -  
5” (127mm);  
300, 350, 400 -  
6” (152mm)  
150, 200 - 5” (127mm);  
250, 300, 350, 400 - 6” (152mm)  
6-3/8  
(162mm)  
E
F
4-1/8  
(105mm)  
2-1/8” (54mm)  
1-1/2” (38mm)  
K
G
2-3/8” (60mm)  
H
Rear  
View  
24-3/8”  
(619mm)  
Control Door  
46-1/2”  
(1181mm)  
Corner indicators for cutting  
inlet air opening  
16”  
(406mm)  
22-1/4”  
(565mm)  
Blower Door  
2-1/8” (54mm)  
2-1/2” (64mm)  
J
1/2” (13mm)  
Control Side of Hater  
Front View  
Corner indicators for  
cutting inlet air opening.  
NOTE: Composite drawings are  
not proportional for all sizes.  
Bottom  
View  
M
BOTTOM VIEW  
Dimensions (inches + or - 1/8")  
Size  
A
B
C
D
E
F
G
H
24  
24  
J
K
M
N
P
P
150 38 34-3/4 36 21 7-1/4 3-3/4 12-1/2  
200 38 34-3/4 36 21 7-1/4 3-3/4 12-1/2  
250 50 34-3/4 48 21 7-1/4 4-3/8 12-3/4 27-1/4 45 31 16 46 4-3/4  
300 50 34-3/4 48 21 7-1/4 4-3/8 12-3/4 27-1/4 45 31 16 46 4-3/4  
33 31 19 34 4-5/8  
33 31 19 34 4-5/8  
N
2”  
(51mm)  
350 50 49-3/4 48 34  
400 50 49-3/4 48 34  
7
7
4-3/8 14-1/8 26-3/4 45 44 32 46 4-7/8  
4-3/8 14-1/8 26-3/4 45 44 32 46 4-7/8  
Air Opening Dimensions  
Supply Air (Discharge with duct flange) C x D  
Dimensions (mm +or- 3)  
Inlet Air Opening (location selected by installer)  
Right Side of Heater  
Left Side* of Heater  
Rear of Heater  
K x 16" (406mm)  
K x 16" (406mm)  
J x 16" (406mm)  
Size  
A
B
C
D
E
F
G
H
J
K
M
N
P
150 965 883 914 533 184 95 318 610 838 787 483 864 117  
200 965 883 914 533 184 95 318 610 838 787 483 864 117  
250 1270 883 1219 533 184 111 324 692 1143 787 406 1168 121  
300 1270 883 1219 533 184 111 324 692 1143 787 406 1168 121  
350 1270 1238 1219 864 178 111 359 679 1143 1118 813 1168 124  
400 1270 1238 1219 864 178 111 359 679 1143 1118 813 1168 124  
Bottom of Heater  
M x N  
*Right side is illustrated; corner indicators for open-  
ing are the same on the left side.  
Mfg No. 164771, Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Venting and Combustion Air  
concentric adapter combustion air/vent system. Flue products must  
always be vented to the outdoors.  
Installation should be done by a qualified agency in accordance with  
these instructions. The qualified service agency installing the vent or  
vent/combustion air system is responsible for the installation.  
WARNING: The vent must be installed in  
accordance with national and local regulations.  
Failure to provide proper venting could result in  
death, serious injury and/or property damage. This  
unit must be installed with a vent to the outside of  
the building. Safe operation of any power-vented  
gas-fired equipment requires a properly operating  
vent system, correct provision for combustion air,  
and regular maintenance and inspection.  
The venting or venting/combustion air systems illustrated in this manual  
are the only ones approved for a Model CAUA heater. However, since  
more than one system is approved and requirements vary depending on  
the type of installation, the first step must be deciding which vent or  
vent/combustion air system is going to be installed. Review the follow-  
ing matrix of vent types and installation requirements. If there is any  
doubt as to what type of vent is required, contact the equipment dis-  
tributor before beginning installation.  
WARNING: Units installed in multiples require  
individual vent pipe runs and vent caps.  
Manifolding of vent runs is not permitted due to  
possible recirculation of combustion products into  
the building and back pressure effects on the  
combustion air proving switch.  
Hazards of Chlorines - The presence of chlorine vapors in the com-  
bustion air of gas-fired heating equipment presents a potential corro-  
sion hazard. Chlorine will, when exposed to flame, precipitate from the  
compound, usually freon or degreaser vapors, and go into solution with  
any condensation that is present in the heat exchanger or associated  
parts. The result is hydrochloric acid which readily attacks all metals  
including 300 grade stainless steel.  
Care should be taken to separate these vapors from the combustion  
process. This may be done by installing a separated combustion sys-  
tem and/or wise location of the furnace with regard to exhausters or  
prevailing wind direction. Chlorine is heavier than air. This fact should  
be kept in mind when determining installation locations of heating equip-  
ment and building exhaust systems.  
Venting must be in accordance with the National Fuel Gas Code Z223.1  
or CAN/CGA B149.1 and B149.2, Installation Code for Gas Burning  
Appliances and Equipment, and all local codes. Local requirements  
supersede national requirements. Combustion air for this heater may be  
either taken from the space or may be ducted from the outside using the  
STEP 1 - Decide which Venting System to Install:  
Type of  
Installation  
Vent Configuration/Options  
Required  
Type of Vent System  
(Description/Instructions)  
Type of VENT Pipe* Required  
Horizontal Vent / Option CC6  
(includes concentric adapter box,  
exhaust terminal, and inlet air guard)  
Vertical Vent / Option CC2  
(includes concentric adapter box,  
exhaust terminal, and combustion air  
inlet)  
Use either vent pipe approved for a Category III  
appliance OR single-wall, 26-gauge or heavier  
galvanized (or a material of equivalent durability  
and corrosion resistance) vent pipe.  
COMMERCIAL/ S eparated-Combustion  
(uses a power venter to duct  
combustion air from outdoors  
and exhaust flue products to  
INDUS TRIAL  
(Harmonized  
ANSI Z83.8-1996  
and Canadian  
Standard  
the outdoors) -  
(follow  
Instructions in Section 7A)  
CAN/CGA 2.6-  
M96)  
(uses a power  
Use either vent pipe approved for a Category III  
appliance OR appropriately sealed 26-gauge  
galvanized steel or equivalent single-wall pipe. If  
local code requires, the terminal section may be  
double-wall pipe with a single-wall vent run.  
Power-Vented  
Horizontal Vent / Option CC1  
venter to draw combustion air Vent Cap or field-supplied  
from the indoor space and  
exhaust flue products to the  
equivalent (see page 11)  
outdoors) -  
(follow  
Instructions in Section 7B)  
Vent pipe listed above for a horizontal power-  
vented system may be used, OR vent pipe  
approved for a Category I heater may be used.  
Single-wall pipe or double-wall (Type B) vent  
pipe are suitable for use with a Category I heater.  
At least 1/2 of the Equivalent  
Vent Length is Vertical / Option  
Vent Cap or field-supplied  
CC1  
equivalent (see page 11)  
If local code requires, the terminal section may be  
double-wall pipe with a single-wall vent run.  
STEP 2 - Follow the instructions that apply to the type of vent being  
installed  
Separated-Combustion -- requires air inlet pipe, exhaust vent pipe, and concentric adapter kit (Option CC2 or CC6)  
Using required pipe (See Table above), FOLLOW INSTRUCTIONS IN SECTION 7A  
Power Vent -- requires vent pipe and vent cap (Option CC1 or field-supplied Type L Breidert Air-x-hauster® or equivalent vent  
cap)  
Using required pipe (See Table above), FOLLOW INSTRUCTIONS IN SECTION 7B  
Form 405, Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7A. Venting and Combustion Air Requirements for Separated-Combustion  
Installation (must use either Option CC2 or CC6)  
Specific Requirements (read all before installing)  
Comply with the specific requirements and instructions in the following paragraphs and illustrations.  
1. Combustion Air Inlet  
Diameter is 5" for Sizes 150 and 200 and 6" for Sizes 250, 300,  
350, and 400.  
Use tin snips or aviation shears to cut out the hole in the top of  
the heater (See Figure 2). Insert the pipe through the hole and  
attach it to the collar inside the heater. Seal the joint. (Larger size  
heaters have oval collars. If the collar is oval, form the pipe to fit  
the collar.)  
Figure 2 - Attach Combustion Air Pipe  
Venter  
Outlet  
Use tin snips  
to cut out  
hole for  
combustion  
air pipe  
2. Venter Outlet  
Collar for  
connecting  
combustion air  
pipe  
The venter outlet size is 5" for Sizes 150, 200, and 250 and 6" for  
Sizes 300, 350, and 400. A minimum length of 12" of straight  
pipe is required at the venter outlet.  
3. Concentric Adapter  
If installed as a separated-combustion unit, a concentric adapter  
is required.  
1) Remove door panel.  
2) Cut out the hole.  
3) Slide pipe down through hole.  
4) If collar is oval, form pipe to fit. Attach pipe to collar with  
sheetmetal screws and seal the connection.  
Option CC2 and CC6 - The concentric adapter is a  
metal box that attaches to the inside of the building. See  
the illustrations and dimenstions in Figures 3A and 3B.  
Option CC6 is horizontal; Option CC2 is vertical. (Op-  
tion kits also include a vent terminal and combustion air  
inlet or guard.)  
Figure 3A - Concentric Adapter Assembly in Options CC2 and CC6  
View of Heater Connection Side  
View of Vent Terminal Connection Side  
2” (51mm)  
Collar for  
connecting  
indoor portion  
of the  
6” (152mm)  
2” (51mm)  
Collar for outside portion of the  
combustion air pipe (vent pipe  
extends through the box  
internally concentric to the  
outside portion of the combustion  
air pipe)  
combustion  
air pipe  
Install rubber seal  
for vent pipe  
End View  
H
F
Figure 3B - Concentric Adapter Box  
Dimensions - inches (mm)  
Top View of the Concentric Adapter  
Box Showing Air Flow  
E
CAUA  
150,200  
5 (127)  
250,300,350,400  
6 (152)  
B
= Combustion Air Flow  
A
B
C
D
E
F
= Exhaust (Vent) Gas Flow  
4 (102)  
5 (127)  
4 (102)  
4 (102)  
Field-supplied vent  
pipe passes  
through the  
rubber seal on the  
concentric adapter  
box, extending out  
both sides of the  
box  
7-1/2 (191)  
5 (127)  
7-1/2  
G
D
5 (127)  
4 (102)  
5 (127)  
G
H
J
16-1/2 (419)  
8 (203)  
16-1/2 (419)  
10 (254)  
8 (203)  
C
6 (152)  
A = Diameter of the  
Collar for attaching  
the inside  
Combustion Air Pipe  
from the Heater  
J
= Diameter of the  
Side View - Side of the  
Adapter Box that Connects  
to the Heater  
Collar for attaching the  
"Outside" Portion of the  
Combustion Air Pipe  
Mfg No. 164771, Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Venting and Combustion Air (cont'd)  
7A. Venting and Combustion Air Requirements for Separated-Combustion  
Installation (must use either Option CC2 or CC6) (cont'd)  
either tape suitable for 550°F (such as Option FA1, P/N 98266) or  
high-temperature (450°F) silicone sealant.  
4. Pipe Diameter and Length  
Maximum Pipe Length from Heater to Concentric Adapter -  
If using Category III vent pipe, follow the pipe manufacturer's in-  
minimum length is five feet (1524mm)  
structions for joining pipe sections.  
Model  
Pipe Diameter  
Maximum 90° Elbow 45° Elbow  
In Concentric Pipes (outdoor portion) from Concentric Adapter  
Box to Air Inlet and Vent Terminal - Follow the installation instruc-  
tions for the specific option (CC6 for horizontal vent; CC2 for vertical  
vent).  
CAUA  
150-200  
Vent Inlet Air  
Length  
40 ft  
Equals*  
5 ft  
Equals*  
2.5 ft  
5"  
5"  
6"  
5"  
6"  
6"  
12.2 M  
50 ft  
1524 mm  
5 ft  
762 mm  
2.5 ft  
250  
Joints Requiring Taper-type Connections (See Figure 4) - When  
the diameter of the pipe in the vent pipe run is different from the vent  
pipe in the terminal section, the joint must be made with a taper-type  
pipe connector. Install the connector no more than 6" (152mm) from the  
concentric adapter box. A 5" to 4" reducer is required in the vent pipe on  
Sizes 150 - 200; a 6" to 5" reducer is required on Sizes 300 - 400.  
15.2 M  
50 ft  
1524 mm  
5 ft  
762 mm  
2.5 ft  
300-400  
15.2 M  
1524 mm  
762 mm  
*Reduce maximum length by this amount for each elbow.  
Concentric Pipes (the vent pipe runs concentric through the out-  
door portion of the combustion air pipe) - Sizes 150 and 200 require  
a 6" diameter combustion air pipe for outdoor portion and a 4" diam-  
eter vent pipe through the concentric adapter to the terminal; Sizes  
250-400 require an 8" diameter combustion air pipe for the outdoor  
portion and a 5" diameter vent pipe through the concentric adapter to  
the terminal.  
Figure 4 - When joining different pipe diameters, use taper-  
type pipe connectors  
Taper-type Connector  
Reducer  
Either collar  
or smaller  
diameter pipe  
Airflow  
Length depends on building construction; specific requirements are  
included with the concentric adapter kit instructions.  
Secure joints with sheetmetal  
screws and seal.  
5. Joints  
6. Support  
Determined by type of pipe - Provide field-supplied vent pipe as  
specified in the Table on page 4.  
Support horizontal runs every six feet (1829mm); do not rely on the  
heater or concentric adapter for support of either horizontal or vertical  
pipes.  
If using single wall, 26-gauge or heavier galvanized pipe, secure  
slip-fit connections using sheet metal screws or rivets. Seal all  
joints. Seal combustion air pipe with pressure sensitive tape ordi-  
narily used for warm-air ductwork. Seal flue exhaust pipe with  
7. Clearance  
Clearance from the vent pipe to combustibles is 6" (152mm). Do not  
enclose the vent pipe.  
Instructions and Requirements for Installing Horizontal Vent Terminal/Combustion Air Inlet  
Option CC6  
Mounting brackets for concentric adapter box (or box may be  
mounted flush, depending on building construction)  
Taper-type reducers as required (see requirements above)  
Option CC6 Package includes:  
Qty Description  
150,  
200  
250, 300,  
350, 400  
Installation Instructions for Option CC6  
1
1
1
Complete Horizontal Vent Kit  
(Same as Option CC6)  
Concentric Box Assembly  
(See Figures 3A and 3B)  
Screened  
157158 82131  
155392 68404  
155096 53316  
1. Determine the location on the outside wall for the vent terminal  
(Applies to all horizontal vent kits). In most applications, the terminal  
would be on a level with the heater mounting height. Allow 1/4" per foot  
downward pitch toward the terminal for draining of condensation.  
The distance of the termination of the horizontal vent from adjacent public  
walkways, adjacent buildings, openable windows, and building openings  
must be in accordance with local codes or, in the absence of local codes,  
must conform with National Fuel Gas Code. Local codes supersede all  
provisions in these instructions and in the National Fuel Gas Code. Mini-  
mum clearances for the horizontal vent terminal are as shown in the table on  
page 7.  
Exhaust Assy  
1
Inlet  
Guard  
151755 124940  
4
1
1
#10-16x1/2" lg Screws (to  
attach the inlet guard)  
Rubber seal for vent pipe opening 164492 164493  
in concentric adapter  
Tube of high temperature (450°F) 53335  
silicone sealant  
37661  
37661  
Products of combustion can cause discoloration of some building finishes  
and deterioration of masonry materials. Applying a clear silicone sealant  
that is normally used to protect concrete driveways can protect masonry  
materials. If discoloration is an esthetic problem, relocate the vent or install  
a vertical vent.  
53335  
Field-supplied installation requirements:  
Thimble (a thimble is not required if wall is of non-combus-  
tible construction)  
Flashing  
Vent pipes (see requirements on pages 4 and 6)  
Combustion air pipes (see requirements on pages 4 and 6)  
WARNING: All vent terminals must be positioned or  
located away from fresh air intakes, doors and  
windows to preclude combustion products from  
entering occupied space. See Hazard Levels, page 2.  
Form 405, Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Minimum Clearances for Vent  
Termination Location (all  
directions unless specified)  
Collar for  
combustion  
air pipe.  
Concentric Adapter Box  
Field-supplied  
5A  
Structure  
mounting brackets  
Forced air inlet within 10 ft 3 ft (0.9m) above  
(3.1m)  
Combustion air inlet of  
another appliance  
Door, window, or gravity air 4 ft (1.2m) horizontally  
inlet (any building opening) 4 ft (1.2m) below  
1 ft (30cm) above  
6 ft (1.8m)  
Combustion air pipe  
Seal the seam in the vent pipe.  
Combustion  
Flow  
Air  
ent Flow  
V
*Do not terminate  
the vent directly  
Electric meter, gas meter *  
and relief equipment  
4 ft (1.2m)  
horizontally  
above a gas meter  
or service regulator.  
Gas regulator *  
3 ft (0.9m)  
Install rubber seal in  
vent pipe opening.  
16” (406mm) minimum  
2” (51mm)  
ox plus  
Adjoining building or parapet 6 ft (1.8m)  
Adjacent public walkways  
Grade (ground level)  
appr  
wall thickenss  
7 ft (2.1m) above  
7 ft (2.1m) above  
Vent Pipe - when a taper-type  
reducer is required in  
the vent pipe; the connection  
must be no more than 6”  
(152mm) from the box.  
2. Prepare clearance hole through the outside wall for a 6"  
diameter pipe (Size 150 or 200) or an 8" diameter pipe  
(Size 250, 300, 350, or 400). Outside wall construction  
thickness should be between 1" (25mm) minimum and 30"  
(762mm) maximum. The larger diameter combustion air  
pipe serves as clearance for the exhaust pipe on non-com-  
bustible construction. A thimble may or may not be re-  
quired depending on wall construction and/or local codes.  
3. Prepare the concentric adapter box.  
3a) Determine whether field-supplied brackets are  
required. The box must be positioned so that the  
distance from the outside of the wall to the box is a  
minimum of 12" (305mm). Maximum distance is 60"  
(1524mm). If brackets are used, box should be angled  
slightly to allow for downward pitch of pipes. If used,  
attach brackets securely; do not leave any unsealed  
holes in the adapter box.  
Figure 5A. On all Sizes except 250, no more than 6" (152mm) of vent pipe  
should extend out the heater side. Any time the pipe is re-positioned, re-check  
the seal to be sure that it has not rolled. Adjust the pipe and seal until the pipe is  
the correct length on each side of the box and the seal is over the edge of the hole  
and tight to the entire circumference of the pipe.  
3c) Attach the outside portion of the combustion air pipe to the box. Determine  
the length by measuring the bracket length (if brackets are used), plus the wall  
thickness, plus 2" (51 mm). The inlet pipe should extend beyond the outside  
wall approximately 2" (51mm). Attach the inlet air pipe to the collar of the  
concentric adapter with sheetmetal screws being careful not to penetrate the  
vent pipe.  
4. Attach the concentric adapter box to the wall. Insert  
the vent pipe and combustion air pipe through the wall.  
Push the concentric adapter box flush against the inside  
wall or attach to the wall with the field-supplied brackets.  
Caulk or flash inlet air pipe on the outside wall. Flashing is  
field supplied.  
Flash or caulk  
the inlet air pipe  
on the outside  
If brackets are not used, when the box is installed,  
position it tight against the wall.  
3b) Install the rubber seal and the vent pipe. Locate the  
vent pipe opening (no collar) and place the rubber seal  
around and over the edge of the metal.  
wall  
5. Slide the inlet guard over the end of the vent pipe  
and position it on the end of the combustion air pipe. See  
Determine the length of the section of vent pipe by  
adding the requirements. On the heater side of all Sizes  
except CAUA 250, the vent pipe must extend no more  
than 6" (152mm) (length limit does not apply to Size  
250 because the pipe diameter does not change); plus  
6" (152mm) through the box; plus bracket length; plus  
the width of the wall; plus a minimum of 18" (457mm)  
on the outside (if  
Figure 5B. Attach the guard to the inlet air pipe with the  
four 1/2" lg screws provided.  
6. Position the vent cap on the end of the vent pipe. Align the cap so that its baffle  
strips are positioned on the horizontal and vertical centerlines (See Figure 5C).  
Attach the exhaust cap to the vent pipe with sheetmetal screws.  
5B  
First, attach the inlet air guard;  
Second, attach the exhaust cap  
5C  
Inlet Air Guard  
Worksheet - Determine Length of  
the inlet air pipe  
extends recom-  
Vent Pipe through the Box  
inches mm  
IMPORTANT: Install  
mended  
2"  
Heater Side (max if +  
diameter changes)  
6
152  
exhaust cap with baffles  
positioned on horizontal and  
vertical centerlines as illustrated.  
(51mm) beyond  
the wall).  
Width of Box  
Bracket Length  
Width of Wall  
+
+
+
6
152  
Lubricate the seal  
and pipe with liq-  
uid soap or a rub-  
ber lubricant. (In-  
stallation Tip:  
Spray cooking oil  
__ ___  
__ ___  
7. Horizontal vent terminal/combustion air inlet Option CC6 is installed and ready  
for connection to the heater.  
Terminal Side (min) + 18 457  
Length of Pipe  
=
8. Connect the Concentric Adapter Box to the Heater - Use the pipe specified  
and joints required for type of pipe. If collar or opening at the heater or adapter are  
different diameters from the pipe (use only diameters allowed on page 6), make joint  
connection with field-supplied taper-type reducer or enlarger.  
A minimum of 12" (305 mm) of straight pipe is required at the venter outlet.  
Due to the high temperature, do not enclose the exhaust pipe or place pipe closer  
than 6" (152 mm) to combustible material.  
Installation of the horizontal vent and combustion air system on your separated-  
combustion unit is complete. Refer to Figure 5D and verify that all installation  
requirements are met. Continue to Paragraph 8.  
works well as a lubricant for this task.)  
Being sure the pipe is in the proper flow direction,  
slide the end through the box and push it out through  
the rubber seal. Push evenly using caution not to dis-  
place the seal from its position on the edge of the hole.  
If the rubber seal moves, slide the pipe back slightly,  
re-position the seal, and slide the pipe through again.  
Position the vent pipe so that it will extend a minimum  
of 16" past the end of the combustion air pipe. See  
Mfg No. 164771, Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Venting and Combustion Air (cont'd)  
7A. Venting and Combustion Air Requirements for Separated-Combustion  
Installation (must use either Option CC2 or CC6) (cont'd)  
60” (1524mm) maximum  
12” (305mm) minimum  
Figure 5D - Installation of a Typical Separated-  
Combustion Unit with Horizontal Vent and Combustion  
Air Pipes (Option CC6)  
Top  
View  
Concentric Adapter  
Seal Joints  
Wall  
Combustion Air Pipe  
Seal joints; see Require-  
ment No. 5 on page 6.  
Inlet Air  
Guard  
Vent (Flue Exhaust) Pipe  
Maximum Length (See Requirement  
No. 4 on page 6.)  
Building Overhang  
Screened  
Exhaust  
Cap  
Minimum length is 5 ft (1.5M)  
Side View  
Vent Pipe  
- PITCH  
TO  
DRAIN  
Concentric Adapter Box  
6ft (1829mm)  
minimum  
16”(406mm)  
minimum  
24”(610mm)  
minimum  
Thimble  
Adjoining  
Building  
Combustion Air Pipe  
(PITCH TO DRAIN)  
Wall  
"Through-the-Wall" View of a typical  
installation of a horizontal vent/inlet air  
terminal and concentric adapter  
(Option CC6)  
IMPORTANT NOTE: Exhaust cap must be installed so the baffles  
are positioned on horizontal and vertical centerlines.  
Building Projection  
Instructions and Requirements for Installing a Vertical Vent Terminal/Combustion Air Inlet  
(Requires Concentric Adapter Kit, Option CC2)  
Vertical Vent Terminal/Combustion Air Package  
Installation Instructions for Option CC2  
(Option CC2) includes:  
Qty Description  
1. Determine the location for the vent terminal on the roof, allowing room for the  
150,  
200  
250,300,  
350,400  
concentric adapter box inside. A thimble may or may not be required depending  
on building construction and/or local codes. Prepare a hole through the roof for  
the combustion air pipe (Sizes 150 and 200, pipe is 6"; Sizes 250-400, pipe is 8").  
The air inlet pipe must be flashed or sealed to the roof. Flashing is to be supplied  
by the installer as required by roof construction and/or codes.  
1
Complete Vertical Vent Kit 157156 54444  
(Same as Option CC2)  
1
1
Concentric Box Assembly  
Exhaust  
155392 68404  
155631 53326  
WARNING: All vent terminals must be positioned or  
located away from fresh air intakes, doors and windows to  
preclude combustion products from entering occupied  
space. See Hazard Levels, Page 2.  
Terminal  
1
Combustion  
Air Inlet  
155635 53330  
2. Prepare the concentric adapter box.  
1
1
Rubber seal for vent pipe  
opening in concentric adapter  
Tube of High Temperature  
(450°F) Silicone Sealant  
164492 164493  
2a) Determine whether field-supplied brackets are required. If used, attach  
brackets securely; do not leave any unsealed holes in the adapter box.  
If brackets are not used, when in-  
53335  
53335  
Worksheet - Determine Length of  
stalled, the box should be tight against  
the roof.  
2b) Install the rubber seal and the  
Vent Pipe through the Box  
Field-supplied installation requirements:  
inches mm  
Thimble (a thimble is not required if wall is of non-  
combustible construction)  
Flashing  
Vent pipes (see requirements on pages 4 and 6)  
Combustion air pipes (see requirements, pages 4 and 6)  
Mounting brackets for concentric adapter box (or box  
may be mounted flush, depending on building construc-  
tion)  
Heater Side (max if +  
diameter changes)  
6
152  
vent pipe. Locate the vent pipe open-  
ing and place the rubber seal around  
and over the edge of the metal.  
Determine the length of the section of  
vent pipe by adding the requirements.  
On the heater side of all Sizes except  
CAUA 250, the vent pipe must ex-  
tend no more than 6" (152mm) (length  
limit does not apply to Size 250 be-  
Width of Box  
+
+
+
+
6
152  
Bracket Length  
Width of Roof  
Inlet Pipe Height  
__ ___  
__ ___  
__ ___  
Terminal Side (min) + 22 559  
Taper-type reducers as required (see requirements on  
page 6)  
Length of Pipe  
=
Form 405, Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2c) Attach the outside portion of the com-  
bustion air pipe to the box. Determine  
the length of the combustion air pipe so  
that dimension "X" (Figure 6A) is equal  
to the roof thickness, plus snow depth  
and ridge or parapet clearance, but does  
not exceed 60" (1524 mm). Attach the  
combustion air pipe to the collar with  
sheetmetal screws being careful not to  
penetrate the vent pipe.  
3. Attach the concentric adapter. Insert  
the vent pipe and combustion air pipe up  
through the roof and secure the adapter box.  
Flash the combustion air pipe to the outside  
of the roof as required.  
6B  
"X" is the length of combustion air  
pipe required through and above  
the roof  
"X" must equal roof thickness  
plus clearance required for  
anticipated snow  
6A  
22"  
(559mm)  
minimum  
Install the vent pipe  
by inserting it into the  
terminal side of the  
box and pushing it out  
through the seal on the  
heater side.  
Seal the seam in  
the vent pipe.  
plus ridge and/or  
parapet clearance  
NOTE: Be sure flow  
direction is correct.  
"X" must not  
exceed 60"  
(1524mm)  
Snow  
Clearance  
Combustion  
air pipe  
Field-supplied  
mounting brackets  
4. Slide the combustion air inlet over the  
vent pipe and fasten the collar  
to the end of the combustion air  
pipe with sheet metal screws  
(See Figure 6C). Seal joint at top  
between vent pipe and combus-  
tion air inlet with silicone seal-  
ant to prevent water leakage.  
5. Attach the exhaust termi-  
nal with sheet metal screws (See  
Figure 6D).  
6C  
1)Slide combustion  
air inlet over the  
vent pipe  
Concentric  
Adapter Box  
2)Fasten to the end  
Collar for combustion  
air pipe.  
of the combus-  
tion air pipe  
3)Seal the top joint  
with silicone  
Vent Pipe - when a taper-type reducer  
is required in the vent pipe; it must be no  
more than 6” (152mm) from the box.  
Install seal  
in vent pipe  
opening  
cause the pipe diameter does not change); plus bracket length;  
plus the width of the roof; plus the length of the outer inlet air  
pipe; plus a minimum of 22" (559mm).  
Install field-supplied  
flashing at roof  
opening (flashing not  
illustrated).  
6. Vertical vent terminal/combus-  
tion air inlet is installed and ready  
for connection to the heater.  
7. Connect Concentric Adapter  
Lubricate the seal and pipe with liquid soap or a rubber lubri-  
cant. (Installation Tip: Spray cooking oil works well as a lubri-  
cant for this task.) Being sure the pipe is in the proper flow  
direction, slide the end through the box and push it out through  
the rubber seal. Push evenly using caution not to displace the  
seal from its position on the edge of the hole. If the rubber seal  
moves, slide the pipe back slightly, re-position the seal, and  
slide the pipe through again.  
Position the vent pipe so that it will extend a minimum of 22"  
(559mm) past the end of the combustion air pipe. See Figure  
6B.  
A maximum of 6" (152mm) of vent pipe should extend out the  
heater side. Any time the pipe is re-positioned, re-check the  
seal to be sure that it has not rolled. Adjust the pipe and seal  
until the pipe is the correct length on each side of the box and  
the seal is over the edge of the hole and tight to the entire  
circumference of the pipe.  
Box to the Heater - Use the pipe speci-  
fied and joints required for type of pipe.  
If collars at the heater or adapter are dif-  
ferent diameters from the pipe (use only  
diameters allowed on page 6), make con-  
nection with field-supplied taper-type re-  
ducer or enlarger.  
A minimum of 12" (305 mm) of  
straight pipe is required at the venter  
outlet. Due to the high temperature, do  
not enclose the vent pipe or place pipe  
closer than 6" (152 mm) to combustible  
material.  
Exhaust  
Terminal  
12" (305mm)  
minimum  
Combustion  
Air Inlet  
6D  
Installation of the vertical vent and combustion air system on your sepa-  
rated-combustion unit is complete. Refer to Figure 6E and verify that all  
installation requirements are met.  
Figure 6E - Installation of Separated-Combustion Unit with Vertical Vent and Combustion Air Pipes (Option CC2)  
Vent  
Termina  
Side View  
9-3/8”  
(238mm)  
l
6 ft (1829mm)  
minimum  
12” (305mm)  
Seal with high  
Flue  
Exhaust  
(Vent )  
Pipe  
temperature silicone  
rubber sealant supplied  
with the kit.  
Wall or  
Adjoining  
Building  
11” (279mm)  
Combustion  
Air Inlet  
5 ft (1524mm)  
maximum (Size  
according to  
anticipated  
Flashing  
(field supplied)  
18”(457mm)  
minimum  
Roof  
snow depth.  
Flashing  
(field supplied)  
Roof  
Concentric  
Adapter  
Thimble  
Combustion Air Pipe  
Rear  
View  
"Through-the-Roof" View of a typical installation  
of a vertical vent/inlet air terminal and concentric  
adapter (Option CC2)  
Concentric  
Adapter  
Vent  
Pipe  
Mfg No. 164771, Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Venting and Combustion Air (cont'd)  
7B. Venting and Combustion Air Requirements for Power Vent Drawing  
Combustion Air from THE INSIDE SPACE and Venting Flue Products to  
the Outdoors (vent cap is required)  
If the environment has a positive pressure and is such that it is  
not detrimental to combustion air, this system may be installed.  
To provide combustion air to the heater sufficient air must enter  
the equipment location to replace that exhausted through the  
heater vent system. In the past, the infiltration of outside air  
assumed in heat loss calculations (one air change per hour) was  
assumed to be sufficient. However, current construction methods  
using more insulation, vapor barriers, tighter fitting and gasketed  
doors and windows, weather-stripping, and/or mechanical ex-  
haust fans may now require the introduction of outside air through  
wall openings or ductwork to the equipment room.  
Figure 8 - Alternate  
Vent in any  
Vent Directions  
position above  
horizontal  
A minimum of 12" of  
straight pipe is required  
before an elbow  
The requirements for combustion and ventilation air depend upon  
whether the unit is located in a confined or unconfined space. An  
"unconfined space" is defined as a space whose volume is not less  
than 50 cubic feet per 1000 BTUH of the installed appliance.  
Under all conditions, enough air must be provided to ensure  
there will not be a negative pressure condition within the equip-  
ment room or space. Follow the specific requirements below for  
a confined space installation.  
Confined Space Installation - Do not install a unit in a con-  
fined space without providing wall openings leading to and from  
the space. Provide openings near the floor and ceiling for ventila-  
tion and air for combustion as shown in Figure 7, depending on  
the combustion air source as noted in Items 1, 2, and 3 below.  
Do not install dampers or any other type of flue restrictor device.  
2) Vent Pipe Diameter and Length  
Maximum Vent Length - minimum length is 5 ft (1.5M)  
CAUA  
Pipe  
Diameter  
Maximum  
Length  
90° Elbow  
Equals*  
45° Elbow  
Equals*  
150-250  
300-400  
5"  
6"  
50 ft (15.2M) 5 ft (1.5M)  
50 ft (15.2M) 5 ft (1.5M)  
2.5 ft (.8M)  
2.5 ft (.8M)  
*Reduce by this amount for each elbow.  
Note: If the system contains all vertical pipe or a combination of horizontal  
and vertical vent pipe, the Maximum Permissible Vent Length may be in-  
creased one foot (305mm) for each foot (305mm) of vertical rise up to a  
maximum increase of ten feet (3M).  
Figure 7 - Confined Space:  
A space whose  
3) Vent Pipe and Joints  
volume is less than  
50 cubic feet per  
1000 BTUH of the  
installed appliance  
input rating  
Provide field-supplied vent pipe as specified in the Table on page 4.  
If using single wall, 26-gauge or heavier galvanized pipe, secure slip-fit  
connections using sheet metal screws or rivets. Seal pipe joints either with  
tape suitable for 550°F (such as Option FA1, P/N 98266) or high-tem-  
perature silicone sealant.  
If using Category III vent pipe, follow pipe manufacturer's instructions  
for joining pipe sections. When attaching Category III pipe to the venter  
outlet or the vent cap, make secure, sealed joints following a procedure  
that best suits the style of Category III pipe being used.  
If using double-wall (Type B) vent pipe (at least 1/2 of the equivalent vent  
length must be vertical), follow pipe manufacturer's instructions for join-  
ing pipe sections. For joining double-wall pipe to the venter outlet collar,  
single-wall pipe, and/or the vent cap, follow the instructions below:  
Add total BTUH of all appliances in the confined space and  
divide by figures below for square inch free area size of each (top  
and bottom) opening.  
1. Air from inside the building -- openings 1 square inch free  
area per 1000 BTUH. Never less than 100 square inches free area  
for each opening. See (1) in Figure 7.  
2. Air from outside through duct -- openings 1 square inch free  
area per 2000 BTUH. See (2) in Figure 7.  
3. Air direct from outside -- openings 1 square inch free area per  
4000 BTUH. See (3) in Figure 7.  
Instructions for attaching double-wall (Type B) vent pipe to the ven-  
ter outlet, a single-wall pipe run, or to the vent cap (use these in-  
structions for either full length double-wall or terminal only):  
Hardware and Sealant Required: 3/4" long sheetmetal screws; and a tube of  
high temperature silicone sealant  
1) Look for the "flow" arrow on the vent pipe; attach according to the  
arrow. Slide the pipe so that the venter outlet, the single-wall pipe, or the  
vent cap is inside the double-wall pipe.  
2) Drill a hole through the pipe into the outlet collar, the single-wall pipe,  
or the vent cap. (Hole should be slightly smaller than the sheet metal  
screw being used.) Using a 3/4" long sheet metal screw, attach the pipe.  
Do not overtighten. Repeat, drilling and inserting two additional screws  
evenly spaced (120° apart) around the pipe.  
3) Use silicone sealant to seal any gaps. If there is an annular opening, run  
a large bead of sealant in the opening. The bead of sealant must be large  
enough to seal the opening, but it is not necessary to fill the full volume  
of the annular area.  
NOTE: For further details on supplying combustion air to a  
confined space, see the National Fuel Gas Code ANSI Z223.1a  
(latest edition).  
Specific Venting Requirements (read all  
before installing)  
1) Venter (Flue) Outlet  
Venter  
Model Size  
150, 200, 250 300, 350, 400  
5" 6"  
Outlet  
Size:  
Outlet Diameter  
Venter Outlet Attachment Requirements:  
A minimum of 12" of straight pipe is required at the venter  
outlet before installing an elbow in the vent system. An elbow  
should never be attached directly to the venter. An elbow  
attached to the straight pipe can be in any position at or above  
horizontal. See Figure 8.  
4) Vent System Support  
Lateral runs should be supported every six feet (1.8M) using a non-combus-  
tible material, such as strap steel or chain. Do not rely on the heater for  
support of either horizontal or vertical vent pipe.  
Form 405, Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
heater manufacturer (Option CC1) or a field-supplied cap. If the vent cap is  
field-supplied, use a Type L Breidert Air-x-hauster® or equivalent vent cap.  
(Type L Air-x-hauster® is a trademark of The G. C. Breidert Company.) Use  
of a vent cap supplied by the pipe manufacturer is not permitted; the vent  
cap must be the type approved for use with this heater. A different style  
vent cap could cause nuisance problems or unsafe conditions.  
See the illustrations in Figures 9A and 9B for requirements of vertical and  
horizontal vent termination. The vent terminal pipe may be either single-  
wall or double-wall (Type B). If double-wall pipe is used in the vent termi-  
nal with a single-wall vent run, follow the instructions on page 10 to attach  
the vent cap and to connect the double-wall pipe to the single-wall vent pipe  
run.  
5) Condensation  
Any length of single-wall vent pipe exposed to cold air or run  
through an unheated area or an area with an ambient temperature  
of 45°F or less must be insulated along its entire length with a  
minimum of 1/2" foil-faced fiberglass, 1-1/2# density insulation.  
Where extreme conditions are anticipated, install a means of con-  
densate disposal.  
6) Vent Terminal (Pipe and Vent Cap)  
The vent system must be terminated with the type of vent cap  
approved for use with this heater. The vent cap must be the same  
size as the vent pipe. Use either a vent cap available from the  
Figure 8 - Horizontal Vent Terminals  
Single-Wall Vent  
Single-Wall  
Vent Run  
and Double-  
Wall  
Terminal  
Roof or Building Overhang  
Roof or Building Overhang  
Run and Single-  
Wall Terminal  
12”  
12”  
(305mm)  
minimum  
6’ (2M)  
(305mm)  
minimum  
6’ (2M)  
minimum  
minimum  
Wall  
Wall  
Note position of  
vent cap openings.  
Note position of vent  
Approved clearance  
thimble for single-wall  
vent pipe is required  
when flue pipe extends  
through combustible  
materials.  
cap openings.  
Approved clearance  
thimble for single-wall  
vent pipe is required  
when flue pipe extends  
through combustible  
materials. Follow  
Pitch flue pipe down toward  
outlet 1/4” per foot for con-  
densate drainage.  
(NOTE: Applies to entire  
horizontal vent run.)  
Pitch flue pipe down toward outlet  
1/4” per foot for condensate drainage.  
(NOTE: Applies to entire horizontal  
vent run.)  
the requirements  
of the double-wall  
pipe manufacturer.  
Follow instructions on page 10 to join single  
and double-wall pipe and to seal the connection.  
Horizontal Vent Terminal Clearances  
Structure  
Minimum Clearances for Vent Termination  
Location (all directions unless specified)  
3 ft (0.9m) above  
6 ft (1.8m)  
4 ft (1.2m) horizontally  
4 ft (1.2m) below  
A vent cap is required. Maintain a clearance  
of 12" from the wall to the vent terminal cap  
for stability under wind conditions.  
Forced air inlet within 10 ft (3.1m)  
Combustion air inlet of another appliance  
Door, window, or gravity air inlet  
(any building opening)  
Products of combustion can cause discolora-  
tion of some building finishes and deteriora-  
tion of masonry materials. Applying a clear  
silicone sealant that is normally used to pro-  
tect concrete driveways can protect masonry  
materials. If discoloration is an esthetic prob-  
lem, relocate the vent or install a vertical vent.  
1 ft (30cm) above  
Electric meter, gas meter* and relief  
equipment  
Gas regulator*  
Adjoining building or parapet  
Adjacent public walkways  
Grade (ground level)  
4 ft (1.2m)  
*Do not terminate the vent  
horizontally directly above a gas meter  
3 ft (0.9m)  
6 ft (1.8m)  
or service regulator.  
7 ft (2.1m) above  
7 ft (2.1m) above  
Figure 9 - Vertical Vent Terminals  
Single-Wall Vent  
Run and Single-  
Wall Terminal  
Single-Wall Vent  
Run and Double-  
Wall Terminal  
6’ (2M) minimum  
Vertical flue extension  
to be 6” (152mm) higher  
than anticipated snow  
depth but no less than  
2 feet (610mm) above the  
roof.  
Vertical flue extension to  
be 6” (152mm) higher than  
anticipated snow depth but  
no less than 2 feet (610mm)  
above the roof.  
Vertical pipe extension  
must be insulated.  
6’ (2M) minimum  
Roof Flashing  
Roof Flashing  
Roof - pitched  
from 0 to 45°  
Roof - pitched  
from 0 to 45°  
6” (152mm) minimum  
Approved clearance thimble  
for single-wall vent pipe is  
Approved clearance thimble  
for single-wall vent pipe is  
required when flue pipe  
extends through  
required when flue pipe extends  
through combustible materials.  
Follow the requirements of the  
double-wall pipe manufacturer.  
Follow instructions on page 10  
to join single and double-wall  
pipe and to seal the connection.  
combustible materials.  
Mfg No. 164771, Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The cut edges of the metal will be sharp.  
8. Duct Connections and  
Ductwork  
If installing an optional filter or filter/mixing cabinet shipped with the  
heater, attach the cabinet at the "cutout" opening (See Optional Acces-  
sories, Paragraph 18 or 19). Depending on the cabinet and how it is  
installed, the inlet opening may be horizontal or vertical.  
Attach the ductwork to the heater or to the inlet cabinet.  
Both inlet air ductwork and supply air discharge ductwork are required  
unless the heater is equipped with an optional inlet base and/or an  
optional discharge plenum. IMPORTANT NOTE: If a Model ACU  
cased cooling coil is part of the installation, it must be installed before  
attaching discharge ductwork. Installation of a filter cabinet is rec-  
ommended when a cooling coil is installed.  
Figure 12 - Duct Opening for Connecting the Inlet Air  
Duct to the field-installed Filter or Mixing Cabinet  
Depending on the heater size and whether the cabinet is on the side  
or the rear, the inlet opening may be either vertical (on the top of the  
filter cabinet) or horizontal (on the side of the filter cabinet.)  
Discharge Duct Connection - The discharge duct connects to the top  
of the heater or to the outlet of the optional cooling coil cabinet. See  
Figures 10 and 11. Connect the ductwork plenum to the duct flange as  
illustrated in Figure 11.  
1) The duct connection on the top of the heater has a 90° flange.  
2) The duct may either have no flange or a 90° flange.  
Filter Cabinet Inlet Opening  
150, 200 - Rear or Side Filter Cabinet - 32” (813mm)  
250, 300 - Side Filter Cabinet - 32” (313mm)  
3) Position ductwork around the outside of the heater flange.  
250, 300 - Rear Filter Cabinet - 45-1/8” (1146mm)  
350, 400 - Rear or Side Filter Cabinet = 45-1/8 (1146mm)  
4) If the ductwork has a flange, drill holes vertically through duct  
flange into the top of the heater and secure with sheetmetal  
screws. If the ductwork does not have a flange, drill holes hori-  
zontally through the ductwork and the heater flange; secure with  
sheetmetal screws.  
16”  
(406mm)  
Inlet  
Opening  
Figure 10 - Top View showing Discharge Duct  
Connection Dimensions (inches)  
A
Requirements and Suggestions for Connecting  
and Installing Ducts  
B
Type of Ductwork - The type of duct installation to be used de-  
pends in part on the type of construction of the building.  
Ductwork Material - Rectangular duct should be constructed of  
not lighter than No. 26 U.S. gauge galvanized iron or No. 24 B & S  
gauge aluminum.  
Electrical  
Combustion Air Knockout  
Venter Outlet  
Gas  
Ductwork Structure - All duct sections 24 inches or wider, and  
over 48 inches in length, should be cross broken on top and bottom  
and should have standing seams or angle-iron braces. Joints should  
be S and drive strip, or locked.  
6-3/8”  
(162mm)  
4-1/8”  
(105mm)  
2-3/8” (60mm)  
Through Masonry Walls - No warm air duct should come in con-  
tact with masonry walls. Insulate around all air duct through ma-  
sonry walls with not less than 1/2" (1" is recommended) of insula-  
tion.  
Through Unheated Space - Insulate all exposed warm air ducts  
passing through an unheated space with at least 1/2" (1" is recom-  
mended) of insulation.  
Duct Supports - Suspend all ducts securely from buildings mem-  
bers. Do not support ducts from unit duct connections.  
Duct Sizing - Proper sizing of the supply air ductwork is neces-  
sary to ensure a satisfactory heating installation. The recognized  
authority for such information is the Air Conditioning Contractors  
Association, 1228 17th Street N.W., Washington, D.C. 20036. A  
manual covering duct sizing in detail may be purchased directly  
Size  
A
B
150, 200  
250, 300  
350, 400  
36" (914mm) 48" (1219mm) 48" (1219mm)  
21" (533mm) 21" (533mm) 34" (864mm)  
Figure 11 - Connecting Discharge Ductwork  
Removable  
Access Panel in  
the Ductwork -  
6" x 10"  
(152mm x  
254mm)  
minimum  
from them.  
CAUTION: An external duct system static pressure  
not within the limits shown on the rating plate, or  
improper motor pulley or belt adjustment, may  
overload the motor. See Hazard Levels, page 2.  
Attach to Duct  
Flange  
Heater  
Removable Panels - The ducts should have removable access pan-  
els on both upstream and downstream sides of the furnace. These  
openings must be accessible when the furnace is in service and  
should be a minimum of 6" x 10" in size so smoke or reflected light  
may be observed inside the casing to indicate the presence of leaks  
in the heat exchanger. The covers for the openings must be attached  
in such a manner as to prevent leakage. See Figure 11.  
Inlet Air Ductwork - The location of the inlet air duct connection  
depends on the installation. Corner indicators for the opening are pro-  
vided on the right side, the left side, and the rear of the heater. (See  
Dimensions in Figure 1, page 3.) Determine where the inlet air opening(s)  
should be and cut out using tin snips or aviation shears. CAUTION:  
Form 405, Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
From Gas Supply  
Immediately upstream of the gas  
supply connection, install a manual  
shutoff valve with a 1/8” NPT  
plugged tap accessible for test  
gauge connection.  
9. Gas Piping and Pressures  
WARNING: This appliance is equipped for a  
maximum gas supply pressure of 1/2 pound, 8  
ounces, or 14 inches water column. Supply  
pressure higher than 1/2 pound requires  
installation of an additional lockup-type service  
regulator external to the unit.  
To Controls  
From  
Gas  
Supply  
Manual  
Gas Valve  
Ground Joint Union  
NOTE:  
PRESSURETESTINGSUPPLYPIPING  
Test Pressures Above 1/2 PSI: Disconnect the heater and manual  
valve from the gas supply line which is to be tested. Cap or plug the  
supply line.  
Test Pressures Below 1/2 PSI: Before testing, close the manual  
valve on the heater.  
Connections  
shown are by  
the installer.  
6” Drip Leg  
Figure 13 -  
Supply Piping  
Connection  
WARNING: All components of a gas supply  
system must be leak tested prior to placing  
equipment in service. NEVER TEST FOR  
LEAKS WITH AN OPEN FLAME. Failure to  
comply could result in personal injury, property  
damage or death.  
All piping must be in accordance with requirements outlined in the  
National Fuel Gas Code ANSI Z223.1a (latest edition) or CAN/CGA-  
B149.1 and B149.2 (See Paragraph 1). Gas supply piping installation  
should conform with good practice and with local codes.  
Unit heaters are orificed for operation with natural gas having a heating  
value of 1000 (± 50) BTUH per cubic ft or propane gas with a heating  
value of 2550 BTUH per cubic ft. If the gas at the installation site does  
not meet these specifications, consult the factory for proper orificing.  
Pipe joint compounds (pipe dope) shall be resistant to the action  
of liquefied petroleum gas or any other chemical constituents of  
the gas being supplied.  
Install a ground joint union and manual shutoff valve upstream of the  
unit control system as shown in Figure 13. The 1/8" plugged tapping in  
the shutoff valve provides connection for a supply line pressure test  
gauge. The National Fuel Gas Code requires the installation of a trap  
with a minimum 3" drip leg. Local codes may require a minimum drip  
leg longer than 3" (typically 6"). Bleed gas lines of trapped air.  
Gas connection is either 1/2" or 3/4" depending on size and type of gas.  
Manifold or Orifice Pressure Settings  
Measuring manifold gas pressure cannot be done until the heater is in  
operation. It is included in the steps of the "Check-Test-Start" proce-  
dure in Paragraph 22. The following warnings and instructions apply.  
WARNING: Manifold gas pressure must never  
exceed 3.5" w.c. for natural gas or 10" w.c. for  
propane gas.  
For Natural Gas: Manifold gas pressure is regulated by the combina-  
tion valve to 3.5" w.c. Inlet pressure to the valve must be a minimum of  
5" w.c. or as noted on the rating plate and a maximum of 14" w.c.  
Size  
Gas  
Gas Connection  
150-200  
250-400  
150-400  
Natural  
Natural  
Propane  
1/2"  
3/4"  
1/2"  
For Propane Gas: Manifold gas pressure is regulated by the combina-  
tion valve to 10" w.c. Inlet pressure to the valve must be a minimum of  
11" w.c. and a maximum of 14" w.c.  
Leak-test all connections by brushing on a leak-detecting solution.  
Before attempting to measure or adjust manifold gas pressure, the inlet  
Sizing a Gas Supply Line  
- Cubic Feet per Hour based on 0.3" w.c. Pressure Drop  
Capacity of Piping  
Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)  
Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)  
Length  
of  
Diameter of Pipe  
1/2"  
3/4"  
1"  
1-1/4"  
1-1/2"  
2"  
Pipe Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane  
20’  
30’  
40’  
50’  
60’  
70’  
80’  
90’  
100’  
125’  
150’  
175’  
200’  
92  
73  
63  
56  
50  
46  
43  
40  
38  
34  
31  
28  
26  
56  
45  
38  
34  
31  
28  
26  
24  
23  
21  
19  
17  
16  
190  
152  
130  
115  
105  
96  
90  
84  
79  
72  
116  
93  
79  
70  
64  
59  
55  
51  
48  
44  
39  
36  
34  
350  
285  
245  
215  
195  
180  
170  
160  
150  
130  
120  
110  
100  
214  
174  
149  
131  
119  
110  
104  
98  
92  
79  
73  
67  
730  
590  
500  
440  
400  
370  
350  
320  
305  
275  
250  
225  
210  
445  
360  
305  
268  
244  
226  
214  
195  
186  
168  
153  
137  
128  
1100  
890  
760  
670  
610  
560  
530  
490  
460  
410  
380  
350  
320  
671  
543  
464  
409  
372  
342  
323  
299  
281  
250  
232  
214  
195  
2100  
1650  
1450  
1270  
1105  
1050  
990  
930  
870  
780  
710  
1281  
1007  
885  
775  
674  
641  
604  
567  
531  
476  
433  
397  
372  
64  
59  
55  
650  
610  
61  
Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.  
Refer to National Fuel Gas Code for additional information on line sizing.  
Mfg No. 164771, Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 14 - Burner Condensate Drain Connection  
9. Gas Piping and  
Pressures (cont'd)  
Manifold Pressure Settings (cont'd)  
(supply) pressure must be within the specified range for the  
gas being used both when the heater is in operation and on  
standby. Incorrect inlet pressure could cause excessive mani-  
fold gas pressure immediately or at some future time.  
! Hex Locknut (silver)  
1
Instructions to Check Manifold  
Pressure (when unit is operating):  
1) With the manual valve positioned to prevent flow to the  
main burners, connect a manometer to the 1/8" pipe outlet  
pressure tap in the valve. NOTE: A manometer (fluid-filled  
gauge) is recommended rather than a spring type gauge due  
to the difficulty of maintaining calibration of a spring type  
gauge.  
Burner Bottom Pan—  
" Sealing Washer  
# Brass Nut  
2
3
4
$ 90° Nylon Fitting  
2) Open the valve and operate the heater. Measure the gas  
pressure to the manifold. Normally adjustments should not  
be necessary to the factory preset regulator.  
1) Assemble the brass nut, the sealing washer, and the 90° fitting.  
2) Position the threaded fitting up through the hole so that the hose barb is  
toward the bushing in the side of the cabinet. Attach using the silver-colored  
locknut.  
If adjustment is necessary, set pressure to correct settings  
by turning the regulator screw IN (clockwise) to increase  
pressure. Turn regulator screw OUT (counterclockwise) to  
decrease pressure.  
3) Under the burner, push the tubing onto the hose barb, being sure that it is  
secure. Maintaining a downward slope, extend the hose out through the  
cabinet side.  
4) Just after exiting the cabinet, create a trap in the line by making a loop in  
the hose. Secure the loop with the wire ties.  
5) Continue downward with the tubing, connecting it into the coil drain pipe.  
10. Burner Condensate  
Drain  
11. Electrical Supply and Connections  
All electrical wiring and connections, including electrical grounding, MUST be  
made in accordance with the National Electric Code ANSI/NFPA No. 70 (latest  
edition) or, in Canada, the Canadian Electrical Code, Part I-C.S.A. Standard C22.1.  
In addition, the installer should be aware of and comply with any local ordinances  
or gas company requirements.  
If an optional cooling coil is installed on a Model CAUA  
heater (either now or at a later time), a burner condensate  
drain line must be installed.  
The following parts to install the drain line are packaged and  
shipped with all Model CAUA heaters.  
Check the rating plate on the heater for the supply voltage and current require-  
ments. A separate line voltage supply with fused disconnect switch should be run  
directly from the main electrical panel to the heater. All external wiring must be  
within approved conduit and have a minimum temperature rise rating of 60°C.  
Conduit from the disconnect switch must be run so as not to interfere with the  
service panels of the heater.  
The electrical supply and control wiring enter at the top of the heater (See Figure  
1, page 3) and connect to the terminal strip behind the gas valve (See Figure 15).  
Consult the wiring diagram supplied with your heater. Typical wiring diagrams are  
on pages 17 and 18.  
Qty  
1
1
P/N  
165955  
165952  
Description  
6-ft length of 3/8" I.D. Tubing  
90° Nylon Fitting, 1/4" NPT x 3/8"  
tubing  
1
1
1
2
1
110628  
171527  
165953  
20913  
1/4" NPT Brass Nut  
1/4" Locknut, Hex, T& B 139  
Sealing Washer  
Nylon Wire Ties, T&B #TY-24M  
Snap Bushing, Heyco SB 625-8  
87556  
Instructions for Installing the Burner  
Condensate Drain (Figure 14)  
1. Remove the burner compartment door.  
CAUTION: If any of the original wire as supplied with the  
appliance must be replaced, it must be replaced with wiring  
material having a temperature rating of at least 105°C,  
except for sensor lead wires which must be 150°C. See  
Hazard Levels, page 2.  
2. The burner box cover is in two sections. On the left side  
of the burner box cover, disconnect the flame sensor wire  
and the flame rollout switch wires. Disconnect the sili-  
cone tubing from the static tap. Remove the left section  
of the burner box cover.  
12. Thermostat and Connections  
3. Determine which side of the cabinet will be most conve-  
nient for the drain line. Remove the hole plug on that side  
and insert the snap bushing from the package.  
A thermostat is not standard equipment but is an installation requirement. Use  
either an optional thermostat available with the heater or a field-supplied 24-volt  
thermostat. Install according to the thermostat manufacturer's instructions. Con-  
trol wiring enters on the right side of the heater and connects to the terminal strip  
in the control compartment; see Figure 15.  
4. Locate the hole in the bottom center of the burner pan  
and remove the plug. Follow the instructions in Figure 14  
to install the drain. Complete all steps as listed in the  
illustration.  
Make sure that the heat anticipator setting on the thermostat is in accordance with  
the amperage value noted on the wiring diagram of your heater.  
When installation of the burner condensate drain is com-  
plete, re-assemble the heater.  
WARNING: If you turn off the power supply, turn off the  
gas. See Hazard Levels, page 2.  
Form 405, Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 15 - Control  
Locations  
Venter  
Limit Control  
Supply Wiring Terminal Block  
(behind the gas valve)  
(Line voltage enters the control  
compartment through a hole in  
the top of the heater cabinet.)  
Pressure Switch  
Transformer  
Gas  
Valve  
Thermostat  
Terminal Strip  
(Thermostat wires enter  
the control compartment  
through a hole in the right  
side of the heater cabinet.)  
Terminal Strip  
Contactors  
Ignition Control  
Module  
14. Blower Motor and Drive  
13. Combustion Air Proving  
Switch  
Model CAUA units are equipped with either direct drive motor(s) and  
blower(s) or adjustable belt-drive blower(s) and motor.  
The combustion air proving switch is a pressure sensitive switch  
that monitors air pressure to ensure that proper combustion air is  
available.  
Direct Drive  
All direct drive blower motors are 1 horsepower. Sizes 150-200 have a  
single motor. Size 150 has a 12-9 blower; Size 200 has a 12-12 blower.  
Sizes 250-400 have dual motors with dual 12-9 blowers.  
The switch is single pole/double throw with the normally open  
contacts closing when the proper airflow is sensed in the system.  
Belt Drive  
On start-up when the heater is cold, the sensing pressure is at the  
most negative level, and as the heater and flue system warm up, the  
sensing pressure becomes less negative. After the system has reached  
equilibrium (about 20 minutes), the sensing pressure levels off.  
The motor horsepower on a belt drive unit is whatever was specified on  
the order ranging in size from 1/4 HP to 5 HP. Check the heater rating plate  
and the motor rating plate.  
As part of the start-up procedure, check belt tension. Proper belt tension  
is important to the long life of the belt and motor. A loose belt will cause  
wear and slippage. Too much tension will cause excessive motor and blower  
bearing wear. Adjust the belt tension by turning the adjusting screw on the  
motor base until the belt can be depressed 3/4". (See Figure 16.) After  
correct tension is achieved, re-tighten the locknut on the adjustment screw.  
Be sure that the belt is aligned in the pulleys.  
If a restriction or excessive flue length or turns cause the sensing  
pressure to be outside the switch setpoint, the pressure switch will  
function to shut off the main burners. The main burners will remain  
off until the system has cooled and/or the flue system resistance is  
reduced. The table below lists the approximate water column nega-  
tive pressure readings and switch setpoints for sea level operating  
conditions.  
Model Start-Up Equilibrium Set Point Set Point  
Size  
150  
200  
250  
300  
350  
400  
Cold  
1.45  
1.50  
1.55  
1.60  
1.30  
1.20  
“OFF”  
.75  
.75  
.75  
.75  
“ON”  
.90  
.90  
.90  
.90  
1.05  
1.05  
1.10  
1.15  
1.05  
1.00  
Figure 16 -  
Check Belt  
Tension  
3/4” (19mm)  
.75  
.75  
.90  
.90  
Most blower motors are equipped with thermal overload protection of the  
automatic, reset type. If the motor is not equipped with thermal overload  
protection, the unit will be equipped with a starter. The adjustable setting  
on the starter will be factory set to match the amp draw of the motor and  
sealed. No change should be made to the starter setting unless the original  
motor is replaced. Starters are equipped with a manual reset. If an overload  
condition is experienced, the condition must be corrected and the starter  
must be manually reset.  
After the installation is complete including all ductwork, the amp draw of  
the motor should be checked with an amp meter to verify that the motor  
amp rating on the motor nameplate is not being exceeded. Amps may be  
adjusted downward by reducing the blower speed or by increasing the duct  
system static pressure. The temperature rise must be within the range  
specified on the unit rating plate.  
DANGER: Safe operation of this unit requires  
proper venting flow. NEVER bypass the com-  
bustion air proving switch or attempt to operate  
the unit without the venter running and the  
proper flow in the vent system. Hazardous  
conditions could result. See Hazard Levels, page  
2.  
Mfg No. 164771, Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
motor specifications. At final adjustment, amperes should not ex-  
ceed motor nameplate amp rating. The installation must be ad-  
justed to obtain a temperature rise within the range specified on  
the heater rating plate.  
14. Blower Motor and Drive  
(cont'd)  
Adjusting Blower Speed  
Full Load Amps - Blower Motors (Open)  
The blower speed may be adjusted to achieve the desired outlet tem-  
perature, as long as the adjustment is within the temperature rise and  
the static pressure limits shown on the heater rating plate. Direct drive  
motors are factory set at medium speed for heating and high speed for  
cooling (if ordered). Belt drive motors are factory set between maxi-  
mum and minimum blower speeds.  
HP  
1/4 1/3 1/2 3/4  
Direct-Drive Motors  
-- --  
6.3  
Optional Belt Drive Motors  
1
1-1/2  
2
3
5
230V 1PH --  
--  
--  
--  
--  
--  
208V 1 PH 2.1 3.2 5.1 6.3 7.5 8.3 10.0  
230V 1PH 2.3 2.8 4.4 5.5 6.5 7.5 10.2  
--  
--  
--  
--  
If the duct resistance is low, the blower may deliver too high an air  
volume. If the resistance is very low, the blower may deliver excess air  
to overload the motor, causing the overload protector to activate. Re-  
ducing the blower speed will correct these conditions. If ductwork is  
added to an installation, it may be necessary to increase the blower  
speed.  
208V 3 PH 1.1 1.4 3.0 2.9 3.7 5.6 7.0 9.0 13.4  
230V 3PH 1.4 1.6 2.5 2.6 3.2 5.0 6.6 8.6 13.2  
460V 3PH 0.75 0.8 1.0 1.3 1.6 2.7 3.5 4.3 6.6  
575V 3PH --  
--  
--  
--  
1.1 1.6 2.1 3.6 5.4  
Direct drive motors have multi-speed taps for speed adjustment. If  
your installation requires an adjustment of the blower speed, the motor  
may be re-wired to an alternate tap by following these instructions.  
1. Turn off the gas and electric power.  
CAUTION: An external duct system static  
pressure not within the limits shown on the rating  
plate, or improper motor pulley or belt adjustment,  
may overload the motor or cause the limit control  
to activate. See Hazard Levels, page 2.  
2. Remove the blower door panel.  
3. Consult the wiring diagram on the heater and follow the chart below  
to choose the wiring for the desired adjustment. Units are wired at  
high speed for cooling (if ordered) and medium speed for heating.  
15. Gas Valve  
Model Sizes  
Speed  
Use these two motor wires:  
The main operating gas valve is powered by the 24-volt control circuit  
through the thermostat and safety controls. The main control valve is  
of the diaphragm type providing regulated gas flow preset at the fac-  
tory.  
150, 200, 250, 350  
High  
White and Black  
Medium  
Low  
White and Blue  
White and Red  
300 and 400  
High  
White and Black  
Medium White and Blue  
WARNING: The operating valve is the prime  
safety shutoff. All gas supply lines must be free of  
dirt or scale before connecting the unit to ensure  
positive closure. See Hazard Levels, page 2.  
4. Cut the crimped cap for the end of the wire that you intend to use  
and strip the insulation.  
5. Disconnect the factory-wired connection and re-wire, using the newly  
stripped wire.  
6. Put a wire nut on the end of the blower motor wire that was discon-  
nected.  
16. Ignition System  
7. Replace the heater door panel. Turn on the gas and electric. Check  
for proper operation.  
This heater is equipped with a direct spark integrated control system.  
The system monitors the safety devices and controls the operation of  
the blower and venter motors and the gas valve.  
Belt drives have an adjustable pulley which permits adjustment of the  
blower speed. Follow these instructions to adjust blower speed.  
1. Turn off the gas and the electric power.  
Ignition System Operating Sequence  
On a call for heat from the thermostat, the system energizes the venter  
motor and goes through a 10-second prepurge. The system verifies that  
the pressure switch has changed states closing the normally open con-  
tactor and that the high limit is in the closed state.  
The gas valve is then energized, and the ignition system provides the  
high voltage spark to the electrode to ignite the main burner gas. Burner  
flame is electronically sensed by the control (minimum 1.0 microamps)  
upon carryover of all burners. (A separate solid metal probe is used as  
the flame sensing function. A low voltage electrical signal is imposed on  
the metal probe which is electrically isolated from ground. When the  
flame impinges on the flame sensing probe, the flame acts as a conduc-  
tion path to ground. The flame rectifies and completes the DC circuit,  
and the ignition system acknowledges the flame.)  
2. Loosen belt tension and remove the belt.  
3. Loosen the set screw on the side of the pulley away from the motor.  
4. To increase the blower speed, turn the adjustable half of the pul-  
ley inward. To decrease the blower speed, turn the adjustable half  
of the pulley outward. One turn of the pulley will change the speed  
8-10%.  
5. Tighten the set screw on the flat portion of the pulley shaft.  
6. Replace the belt and adjust the belt tension. Adjust tension by  
turning the adjusting screw on the motor base until the belt can be  
depressed 3/4". (See Figure 16.) Re-tighten the lock nut on the  
adjusting screw. Be sure that the belts are aligned in the pulley  
grooves properly and are not angled from pulley to pulley.  
7. Turn on the gas and electric. Light the heater following the instruc-  
tions on the lighting instruction plate.  
The blower motor is energized by the system after 30 seconds of flame  
sensing.  
8. Check the motor amps with an amp meter. The maximum motor  
amp rating on the motor nameplate must not be exceeded.  
When service is complete, check for proper operation.  
After the thermostat has been satisfied, the system de-energizes the gas  
valve, the venter motor goes through a 45-second post-purge, and the  
blower motor remains energized for an additional 135 seconds.  
NOTE: This is a three trial system. The unit will lockout for one hour  
before initiating another trial for ignition. If the unit fails after one  
recycle interval, the unit will go into hard lockout and must be reset by  
interrupting power or resetting the thermostat. To initiate another trial  
for ignition before the one hour interval, either reset the thermostat or  
interrupt power to the unit for 30 seconds.  
Motor Amps  
Use an amp meter to check motor amps. The chart lists full load amps  
for various HP's and voltages. Amps may be adjusted downward by  
reducing blower RPM or increasing duct system static pressure.  
The chart below can be used for sizing line wiring but should not be  
interpreted as the exact motor amps. See the motor rating plate for exact  
Form 405, Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL WIRING DIAGRAMS  
Figure 17 - Typical Wiring Diagram for Model CAUA with Direct-Drive Blower Motor(s)  
GRD  
OPTIONAL DISCONNECT SWITCH  
(SEE NOTE)  
G
BL  
BL  
INHERENTLY  
PROTECTED  
BLOWER  
MOTOR  
HEAT SPEED  
CONTACTS  
INHERENTLY  
PROTECTED  
BLOWER  
MOTOR  
BK  
BL  
BL  
W
L1  
(SEE NOTE #7)  
BK  
R
R
W
W
W
COOL SPEED CONTACTS  
BK  
BK  
BK  
BK  
BK  
W
W
W
MOTOR WIRE COLORS  
W
L2  
W
WHITE - NEUTRAL  
BLACK - HIGH SPEED  
BLUE - MEDIUM SPEED  
RED - LOW SPEED  
GRD  
(DO NOT USE WITH 208V)  
G
BK  
W
VENTER MOTOR  
(SEE NOTE #8)  
DSI CONTROL  
BK OR BR  
HEAT SPEED  
BK OR BL  
BK  
BL  
BL  
BK  
LINE  
CMB  
BLWR AUX  
L1  
L2  
L2  
VAC HOT  
CONTACTOR COIL  
W
BL  
BL  
BK  
24VAC  
HOT  
ACB HEAT  
ACB COOL  
GROUND  
1
1
WIRING CODE  
BLACK - BK  
BROWN - BR  
RED - R  
ORANGE - O  
YELLOW - Y  
GREEN - G  
BLUE - BL  
FLAME  
ROLLOUT SWITCH  
COOL SPEED  
CONTACTOR COIL  
BL  
BK  
W
ROLLOUT  
IN  
CUSTOMER'S  
COOL RELAY COIL  
BR  
BR  
C
7
7
PURPLE - PR  
WHITE - W  
IGNITOR  
BR  
BURNER GROUND  
HV LEAD  
THERMOSTAT  
TERMINAL STRIP  
BL  
R
R
FLAME SENSING  
PROBE  
HIGH  
LIMIT  
R
R
FLAME SENSE  
PSW  
PRESSURE SWITCH  
NC  
Y
Y
2
C
BR  
C
C
NO  
Y
R
R
HI LIMIT  
IN  
Y
R
Y
2
Y1  
BL  
M
W
HI LIMIT  
OUT  
BK  
Y
R
Y2  
G
TR OR  
PV-MV  
BK  
BR  
W
G
7
W1  
P
R
BL  
BL  
LED  
W2  
VALVE  
TH OR  
MV  
FACTORY WIRING  
Y
G
FIELD WIRING  
CHASSIS GRND.  
OPTIONAL FACTORY WIRING  
TH-TR  
OR PV  
DOOR SWITCH  
BL  
BR  
BR  
BL  
BL  
24V  
1
3
7
MAIN TERMINAL BLOCK  
UNIT TERMINAL STRIP  
40 VA. CONTROL  
TRANSFORMER  
BK  
Y
Y
L1  
L2  
LINE VOLT  
R
OPERATING SEQUENCE  
THERMOSTAT TERMINAL STRIP  
1. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION, FAN SWITCH AT "AUTO" POSITION.  
2. TURN ON MANUAL GAS VALVE.  
3. TURN ON POWER TO UNIT.  
4. SET THERMOSTAT SYSTEM SWITCH AT "HEAT" POSITION; FAN SWITCH AT "AUTO" POSITION.  
5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.  
6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT.  
7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE BLOWER MOTOR IS ENERGIZED.  
LED CODES  
8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION, THE INTEGRATED CONTROL SYSTEM  
SLOW FLASH NORMAL OPERATION - NO CALL FOR HEAT  
FAST FLASH NORMAL OPERATION - CALL FOR HEAT  
2 FLASHES SYSTEM LOCKOUT - FAILED TO DETECT OR SUSTAIN FLAME  
3 FLASHES PRESSURE SWITCH OPEN OR CLOSED  
4 FLASHES HIGH LIMIT OPEN  
5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED  
STEADY ON INTERNAL FAILURE (MICRO-CONTROLLER FAILURE: SELF CHECK)  
CLOSES THE MAIN VALVE AND MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT  
(SEE LIGHTING INSTRUCTIONS).  
9. SET THERMOSTAT SYSTEM SWITCH AT "COOL" POSITION, FAN SWITCH AT "AUTO" POSITION.  
(A) ON A CALL FOR COOLING, BLOWER MOTOR IS ENERGIZED AT HIGH SPEED AND COOLING  
CIRCUIT IS ENERGIZED.  
10. WHEN BLOWER DOOR IS OPENED, THE UNIT IS SHUTDOWN.  
11. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION, FAN SWITCH AT "AUTO" POSITION, FOR SHUTDOWN..  
NOTES  
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT  
2. DOTTED WIRING AND COOL RELAY COIL INSTALLED BY OTHERS.  
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE  
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL  
HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR  
LEAD WIRE WHICH MUST BE 150° C.  
FIELD CONTROL WIRING  
TOTAL WIRE  
LENGTH  
DISTANCE FROM  
UNIT TO CONTROL  
MIN. RECOMMENDED  
WIRE GUAGE  
#18 GA. WIRE  
#16 GA. WIRE  
#14 GA. WIRE  
150'  
250'  
350'  
75'  
125'  
175'  
4. USE 18 GA. WIRE FOR CONTROL WIRING ON THE UNIT.  
5. USE 14 GA. WIRE FOR LINE AND MOTOR WIRING ON UNIT.  
6. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT  
VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.  
7. SECOND BLOWER MOTOR ON 250-400 UNITS ONLY.  
8. VENTER MOTOR ON 350-400 UNITS HAS BROWN AND BLUE WIRES.  
9. ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.  
FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).  
FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW)  
.
10. WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH  
USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO  
TIMES THE MAXIMUM TOTAL INPUT AMPS.  
CAUA SERIES 150 - 400 DWG. # B-164607 REV #1  
AG1 - AK2 OR AK3 - CL10 - DIRECT DRIVE  
BABS  
Mfg No. 164771, Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL WIRING DIAGRAMS (cont'd)  
Figure 18 - Typical Wiring Diagram for Models CAUA with Belt-Drive Blower Motor  
OPTIONAL DISCONNECT SWITCH  
GRD  
G
(SEE NOTE)  
INHERENTLY  
PROTECTED  
BLOWER  
MOTOR  
MOTOR  
CONTACTOR  
BK  
BK  
L1  
L2  
MAIN TERMINAL BLOCK  
UNIT TERMINAL STRIP  
W
W
THERMOSTAT TERMINAL STRIP  
GRD  
G
BK  
W
VENTER MOTOR  
(SEE NOTE #8)  
DSI CONTROL  
BK OR BR  
WIRING CODE  
BLACK - BK  
BROWN - BR  
RED - R  
ORANGE - O  
YELLOW - Y  
GREEN - G  
BLUE - BL  
BK OR BL  
MOTOR  
BK  
BL  
BL  
BK  
LINE  
CMB  
L1  
L2  
L2  
L2  
VAC HOT  
BLWR AUX  
CONTACTOR COIL  
BL  
BK  
W
24VAC  
HOT  
ACB HEAT  
1
FLAME  
ROLLOUT SWITCH  
BL  
BL  
BK  
ROLLOUT  
IN  
ACB COOL  
GROUND  
1
PURPLE - PR  
WHITE - W  
CUSTOMER'S  
COOL RELAY COIL  
BR  
BR  
7
C
IGNITOR  
BR  
BURNER GROUND  
HV LEAD  
7
THERMOSTAT  
TERMINAL STRIP  
BL  
R
R
FLAME SENSING  
PROBE  
FLAME SENSE  
FACTORY WIRING  
FIELD WIRING  
C
OPTIONAL FACTORY  
WIRING  
PRESSURE SWITCH  
NC  
HIGH  
LIMIT  
R
R
Y
R
R
Y
Y
PSW  
R
Y
2
Y1  
C
NO  
W
HI LIMIT  
IN  
BK  
Y
Y
Y2  
2
G
BK  
HI LIMIT  
OUT  
R
W
G
W1  
R
TR OR  
PV-MV  
BL  
LED  
BR  
W2  
7
BR  
C
Y
BL  
G
VALVE  
BL  
TH OR  
MV  
M
CHASSIS GRND.  
TH-TR  
OR PV  
DOOR SWITCH  
BL  
P
BR  
BR  
BL  
BL  
24V  
1
3
7
40 VA. CONTROL  
TRANSFORMER  
BK  
Y
Y
L1  
L2  
LINE VOLT  
R
OPERATING SEQUENCE  
LED CODES  
1. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION; FAN SWITCH AT "AUTO" POSITION.  
2. TURN ON MANUAL GAS VALVE.  
3. TURN ON POWER TO UNIT.  
4. SET THERMOSTAT SYSTEM SWITCH AT "HEAT" POSITION; FAN SWITCH AT "AUTO" POSITION.  
5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.  
6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT.  
7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE BLOWER  
MOTOR IS ENERGIZED.  
SLOW FLASH NORMAL OPERATION - NO CALL FOR HEAT  
FAST FLASH NORMAL OPERATION - CALL FOR HEAT  
2 FLASHES SYSTEM LOCKOUT - FAILED TO DETECT OR SUSTAIN FLAME  
3 FLASHES PRESSURE SWITCH OPEN OR CLOSED  
4 FLASHES HIGH LIMIT OPEN  
5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED  
STEADY ON INTERNAL FAILURE (MICRO-CONTROLLER FAILURE: SELF CHECK)  
8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,  
THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND  
MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT  
(SEE LIGHTING INSTRUCTIONS).  
9. SET THERMOSTAT SYSTEM SWITCH AT "COOL" POSITION, FAN SWITCH AT "AUTO" POSITION.  
(A) ON A CALL FOR COOLING, BLOWER MOTOR IS ENERGIZED AND COOLING  
CIRCUIT IS ENERGIZED.  
FIELD CONTROL WIRING  
10. WHEN BLOWER DOOR IS OPENED, THE UNIT IS SHUTDOWN.  
TOTAL WIRE  
LENGTH  
DISTANCE FROM  
UNIT TO CONTROL  
MIN. RECOMMENDED  
WIRE GUAGE  
#18 GA. WIRE  
#16 GA. WIRE  
#14 GA. WIRE  
11. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION, FAN SWITCH AT "AUTO" POSITION, FOR SHUTDOWN.  
NOTES  
150'  
250'  
350'  
75'  
125'  
175'  
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT  
2. DOTTED WIRING AND COOL RELAY COIL INSTALLED BY OTHERS.  
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE  
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL  
HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR  
LEAD WIRE WHICH MUST BE 150° C.  
4. USE 18 GA. WIRE FOR CONTROL WIRING ON THE UNIT.  
5. USE 14 GA. WIRE FOR LINE AND MOTOR WIRING ON UNIT.  
6. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT  
VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.  
7. ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.  
FOR 230V. UNITS, USE BLACK AND YELLOW LEADS (CAP RED).  
FOR 208V. UNITS, USE BLACK AND RED LEADS (CAP YELLOW).  
8. VENTER MOTOR ON 350-400 UNITS HAS BROWN AND BLUE WIRES.  
9. WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH  
USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25  
TIMES THE MAXIMUM TOTAL INPUT AMPS.  
Form 405, Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
17. Optional Cased Cooling Coil, Model ACUA, ACUB, or ACUC  
This cased cooling coil is designed for use with the Model CAUA upflow heater. It is shipped separately for field installation over the discharge  
opening of the heater. Before installing, verify that the coil cabinet is the same size as the heater cabinet.  
Follow the installation instructions shipped with the cooling coil (Installation Form RZ 405-CC), the wiring diagram, and the instructions provided  
by the compressor manufacturer.  
Model  
Size  
ACUA  
060 072 090  
ACUB  
090 120 150  
90 120 150  
ACUC  
120 150 180  
120 150 180  
Heater/Coil Cross-Reference  
Table by Cabinet Size  
Heater Model CAUA  
Nominal Cooling Capacity (MBH) 60  
72  
90  
Refrigerant Type  
Thermal Expansion Valves*  
Approximate Weight (lbs)  
No. of Intertwining Circuits  
Face Area (sq ft)  
Rows-Fins/Inch  
Airflow (cfm) Low  
Nominal  
R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22  
1
83  
8
1
1
1
2
2
2
2
2
150 200  
250 300 350  
400  
86 105  
12  
110 122 140  
12 12 18  
176 180 188  
12 16 18  
ACUA  
060  
ACUB  
090  
ACUC  
120  
8
7.79 7.79 9.38 14.04 11.67 13.70 17.13 15.38 17.13  
2-10 2-12 3-10 2-12 3-10 3-12 2-12 3-10 3-10  
072  
090  
120  
150  
150  
180  
1800  
2400  
3000  
4000  
4000  
5000  
High  
3000**  
5000**  
6000**  
* - TXV's are factory supplied. Models with two TXV's have intertwined circuiting.  
** - Airflow in excess of maximum values shown may result in blow-off of condensation.  
Figure 19 - A Model ACU cooling coil installed on a Model CAUA heater and the line connection sizes  
Model Size  
Connections  
Suction Line  
ACUA 060/072  
Connection(s)  
(1) 7/8" Suction Line  
(1) 3/8" Liquid Line  
(1) 1/2" Liquid Line  
(2) 7/8" Suction Lines  
(2) 3/8" Liquid Lines  
(2) 7/8" Suction Lines  
(2) 3/8" Liquid Lines  
(2) 1/2" Liquid Lines  
(2) 7/8" Suction Lines  
(2) 3/8" Liquid Lines  
(2) 1/2" Liquid Lines  
ModelACU  
Cased  
Cooling Coil  
060  
Liquid Line  
Connection(s)  
3/4" Drain Line  
Connection  
072  
090  
090  
ACUB 090/120/150  
090/120  
Hole for Burner  
Condensate Drain  
Tube (use this hole  
or the one on the  
opposite side) - see  
Paragraph 10, page  
14  
ModelCAUA  
Heater  
150  
ACUC 120/150/180  
120  
150/180  
Drain line connection is 3/4" for all sizes.  
Burner Condensate Drain  
When a system includes a cooling coil, a burner condensate drain must be installed. The parts required for the drain are shipped with the heater.  
Instructions for installing the drain are in Paragraph 10, page 14.  
Electrical Connections  
Figure 20 - Typical  
Heater Terminal Strip  
Thermostat  
Connections  
(Read thermostat  
manufacturer’s  
installation  
Condensing Unit  
Connections  
(Read  
Low Voltage Wiring  
(field-supplied)  
24V Supply *  
Common  
R
C
manufacturer’s  
installation  
Common  
instructions  
instructions  
before wiring.)  
before wiring.)  
1st Stage Cooling  
2nd Stage Cooling  
1st Stage Heating  
Y
Y
1
1st stage cooling  
24V control relay  
2
2nd stage cooling  
24V control relay  
for Sizes 090, 120,  
150, and 180  
W
W
G
1
Optional 2-Stage Heating  
Fan  
2
* A separate 24V control transformer may  
Legend (field-supplied 24V wiring)  
be required for the condensing equipment controls  
Install a jumper wire between RH and RC terminals  
on the thermostat for single transformer operation.  
Consult the thermostat manufacturer’s instructions.  
Thermostat wiring - 24V  
Field control wiring - 24V  
Mfg No. 164771, Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES (cont'd)  
18. Optional Filter Cabinet (return air only)  
A filter cabinet designed for 2" pleated disposable or permanent metal filters is shipped separately for field assembly and installation. Depending on  
the option selected, filters are either shipped with the cabinet or are field-supplied.  
To adapt to a variety of applications, the heater cabinet is designed so that the filter cabinet can attach on either the right side, the left side, or the rear  
of the heater. The larger filter cabinets (left two tables below) are uniquely designed so that the same cabinet can be field-assembled and installed with  
either a horizontal or vertical air inlet. The smaller filter cabinet in the table on the right is limited to Sizes 150 and 200 and is available with a  
horizontal inlet only. All cabinets have door panels for easy filter removal for changing or cleaning.  
All of the filter cabinets have a duct flange for attaching the inlet air duct. For inlet duct dimensions, see Paragraph 8.  
Follow the step-by-step instructions included with the filter cabinet package to assemble and attach it to the heater.  
Figure 21 - Filter Cabinets with Filter Arrangements and Filter Sizes  
Option CW8 with 2" Pleated Filters  
Option CW4 with 2" Pleated Filters  
Option CW5 with 2" Permanent Filters  
Option CW6 for Field-Supplied Filters  
Option CW7 with 2" Pleated Filters  
Option CW12 with 2" Permanent Filters  
Option CW11 for Field-Supplied Filters  
Option CW9 with 2" Permanent  
Filters  
Option CW10 for Field-Supplied  
Filters  
Attaches on Either Side of the Heater  
Vertical (Top) or Horizontal Inlet Opening  
"V" Filter Rack Arrangement  
Attaches on the Rear of the Heater  
Vertical (Top) or Horizontal Inlet  
Opening  
Attaches on either Side or the Rear  
of a Size 150 or 200 Heater  
Horizontal Inlet Opening  
"V" Filter Rack Arrangement  
"V" Filter Rack Arrangement  
Figure 21B -  
Assembled  
with  
Horizontal  
Air Inlet  
Opening  
Figure 21A -  
Assembled with  
Vertical Air  
Figure 21C -  
Small Filter  
Cabinet for Sizes  
150 and 200 only  
-- Horizontal Air  
Inlet Only  
Inlet Opening  
Sizes of Permanent or Pleated 2"  
Filters for Options CW4, CW5, or CW6  
Sizes of Permanent or Pleated 2"  
Filters for Options CW7, CW12, or  
CW11  
Filters for Options CW8, CW9, CW10  
Size  
150  
CFM  
1800  
2400  
3000  
2400  
3000  
3000  
*4000  
FPM  
281  
375  
469  
375  
469  
469  
625  
Filters  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
Size  
CFM  
1800  
2400  
3000  
2400  
3000  
3000  
4000  
5000  
3000  
4000  
5000  
4300  
5000  
*6000  
4300  
5000  
*6000  
FPM  
281  
375  
469  
375  
469  
313  
417  
521  
313  
417  
521  
448  
521  
625  
448  
521  
625  
Filters  
SizeCFM FPM  
2" Filters  
150  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(4) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
(6) 16 x 16  
Pleated Permanent  
150 1800 375 (2) 12 x 32 (4) 12 x 16  
200  
250  
2400 500 (2) 12 x 32 (4) 12 x 16  
200  
250  
*3000 625  
200 2400 500 (2) 12 x 32 (4) 12 x 16  
*3000 625 -- (4) 12 x 16  
--  
(4) 12 x 16  
**5000 781  
300  
3000  
*4000  
**5000 781  
469  
625  
300  
350  
400  
350  
400  
4300  
5000  
*6000  
4300  
5000  
*6000  
448  
521  
625  
448  
521  
625  
NOTES:  
* Requires 2" permanent filters.  
** If using side inlets, two cabinets must be  
installed, one on each side.  
19. Mixing Cabinet (Outside and Return Air)  
The optional mixing box for the Reznor® Model CAUA heater is designed  
to provide the system with a supply air mixture of return air and outside  
air. Any percentage of outside air can be supplied to the unit as long as the  
air temperature entering the blower is 35°F or above. The mixing box is  
available in an assortment of configurations with a selection of actuators  
and controls. All mixing boxes are completely assembled at the factory for  
field attachment to the rear of a Model CAUA heater.  
instructions for routing the damper motor wires, and connect the  
wires according to the wiring diagram. If there are both return air and  
outside air dampers, follow the directions to adjust the damper  
linkage.  
All mixing box inlet air openings have duct flanges for attachment of  
ductwork. Ductwork must be attached to the outside air opening.  
Removable door panels provide for filter access from either end of  
the cabinet. If the box was ordered with optional filters, it is shipped  
with the filters installed.  
Follow the instructions packed with the mixing box to cut out the opening  
and attach the mixing box. If the mixing box has dampers, follow the  
Form 405, Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Option Configuration  
Top Outside Air Opening with Dampers/  
GA1  
GA2  
GA3  
GA4  
GA5  
GA6  
GA7  
GA8  
GA9  
Rear or Bottom Return Air Opening without Dampers  
Rear Outside Air Opening with Dampers/  
Top or Bottom Return Air Opening without Dampers  
Figure 22 -  
Optional  
Outside Air  
and Return  
Air Mixing  
Box  
Bottom Outside Air Opening with Dampers/  
Top or Rear Return Air Opening without Dampers  
Bottom Outside Air Opening with Dampers/  
Rear Return Air Opening with Dampers  
Bottom Outside Air Opening with Dampers/  
Top Return Air Opening with Dampers  
Rear Outside Air Opening with Dampers/  
Top Return Air Opening with Dampers  
Configurations/Accessories  
Rear Outside Air Opening with Dampers/  
Bottom Return Air Opening with Dampers  
Before installing, check to be sure that the configuration of the mixing  
box matches the order and that any accessories ordered are part of the  
cabinet. Factory-installed optional accessories could include a damper  
motor, potentiometer, return air controller, mixed air controller, and/or  
filters. NOTE: If the potentiometer is to be field-installed, it is shipped  
in a separate carton.  
Top Outside Air Opening with Dampers/  
Rear Return Air Opening with Dampers  
Top Outside Air Opening with Dampers/  
Bottom Return Air Opening with Dampers  
Figure 23 - Dimensions of Optional  
Mixing Box - inches (mm)  
150-200  
38 (965)  
250-400  
50 (1270)  
A
B
C
22-3/4 (578)  
7-5/8 (194)  
36-1/2 (927)  
6-3/4 (171)  
Note: Damper frame fits in the inlet opening.  
21. Inlet Base (Sizes 350 and 400 only)  
20. Discharge Plenum (Sizes 350  
The optional mounting base is designed to support a Model CAUA 350  
or 400 heater while providing an inlet for return air. The mounting base  
is designed to be used with an optional discharge plenum (Paragraph 20)  
creating a "packaged stand-alone" heating or heating/cooling upflow  
system which can be used in an air turnover application.  
However, if the installation requires it, the mounting base may also be  
used with discharge ductwork.  
and 400 only)  
The optional discharge plenum is designed to be used with a screened  
mounting base (Paragraph 21) to create a "packaged stand-alone" upflow  
system that circulates building air. However, the discharge plenum  
may also be used in place of ductwork in applications that do not have  
an optional mounting base.  
The discharge plenum is available in three types. Option CD60 and  
CD61 are for a heater without a cooling coil; Option CD60 is designed  
for an open area and Option CD61 includes field-installed blockoff  
plates to block off one or two sides. Option CD62 can only be ordered  
with a cooling coil and includes blockoff plates to provide higher veloc-  
ity required for cooling.  
The mounting base has guarded openings on all four sides and is avail-  
able with optional 1" flat disposable, 1" permanent aluminum, or 1"  
pleated disposable filters.  
The base is designed for a fairly open area and must have at least three  
of the four sides open.  
The base adds 36-1/2" (927mm) to the overall height.  
A discharge plenum adds 49-15/16" (1268mm) to the height of the  
heater. (If installing Option CD62, this height includes the cooling  
coil.)  
Mfg No. 164771, Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check/Test/Start-Up  
22. Check Installation & Start-Up  
Check the installation prior to start-up:  
replace any part of the control system and any  
gas control which has been under water.  
%Check clearances from combustibles. Requirements are shown in  
Operating Instructions and Operating Sequence  
1. Set thermostat at lowest setting.  
Paragraph 4.  
%If installed as a separated-combustion unit, check vent/combustion  
air system to be sure that it is installed according to the instructions  
in Paragraph 7A.  
2. Turn off all electric power to the appliance.  
3. This appliance is equipped with an ignition device which  
automatically lights the burner. Do not try to light the burner  
by hand. Open the access door and locate the gas valve.  
%Check piping for leaks and proper gas line pressure. Bleed gas lines  
of trapped air. See Paragraph 9.  
4. Models CAUA 150 and 200 - Locate the gas control (ON/OFF)  
knob on the gas valve. Turn the gas control knob clockwise  
to "OFF".  
%Check the blower compartment to be sure that all shipping sup-  
ports have been removed. Close the blower compartment door se-  
curely. Heater will not operate if the blower compartment door is  
not closed.  
Models CAUA 250, 300, 350, and 400 - Locate the gas con-  
trol (ON/OFF) knob on the gas valve. Turn knob clockwise to  
align the line on the knob with the position indicator. Depress  
knob and continue rotation to the "OFF" position.  
%Check electrical wiring. Be sure all wire gauges are as recommended.  
A service disconnect switch should be used. Verify that fusing or  
circuit breakers are adequate for the load use.  
Top View of Gas Valve used on  
Control Knob on Top of  
Start-Up  
CAUA 150 and 200  
Gas Valve used on CAUA  
250 - 400  
WARNINGS: For your safety, read before  
operating. If you do not follow these instructions  
exactly, a fire or explosion may result causing  
property damage, personal injury, or loss of life.  
• This appliance does not have a pilot. It is  
equipped with an ignition device which auto-  
matically lights the burner. Do not try to light  
the burner by hand.  
5. Wait five (5) minutes to clear out any gas. Then smell for gas,  
including near the floor. If you smell gas, STOP! and follow  
the steps in the WARNINGS printed in the right column or  
on the Operating Label on the heater. If you do not smell gas,  
proceed to the next step.  
• Before operating, smell all around the appliance  
area for gas. Be sure to smell next to the floor  
because some gas is heavier than air and will  
settle on the floor.  
6. Models CAUA 150 and 200 - Turn the gas control knob coun-  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
terclockwise to "ON".  
Models CAUA 250, 300, 350, and 400 - Turn knob counter-  
clockwise to align the line on the knob with the position indi-  
cator. Allow knob to "pop up", and continue rotation to the  
"ON" position.  
• Do not touch any electrical switch; do not  
use any phone in your building.  
• Immediately call your gas supplier from a  
neighbor's phone. Follow the gas  
supplier's instructions.  
7. Close the access door.  
8. Turn on the electric power to the heater.  
9. Set the thermostat to the desired setting.  
• If you cannot reach your gas supplier, call  
your fire department.  
NOTE: If the appliance does not operate, follow the instructions  
"To Turn Off Gas to the Appliance" printed below (and on the  
Operating Label on the heater). Call your service technician.  
• Use only your hand to turn the gas control ON/  
OFF knob on the gas valve. Never use tools. If  
the valve ON/OFF knob will not turn by hand,  
do not try to repair it. Call a qualified service  
technician. Force or attempted repair may re-  
sult in a fire or explosion.  
10. Thermostat calls for heat, energizing the venter motor.  
11. Venter pressure switch closes, allowing the unit to fire.  
12. Burner flame is sensed and in 30 seconds, the blower motor  
is energized.  
13. If the flame is extinguished during the main burner operation,  
the integrated control system closes the main valve and must  
be reset by interrupting power to the control circuit. (See  
lighting instructions on the heater.).  
• Do not use this appliance if any part has been  
under water. Immediately call a qualified ser-  
vice technician to inspect the appliance and to  
Form 405, Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TO TURN OFF GAS TO THE APPLIANCE  
DANGER: The gas burner in this gas-fired  
equipment is designed and equipped to provide  
safe and economically controlled complete  
combustion. However, if the installation does not  
permit the burner to receive the proper supply of  
combustion air, complete combustion may not  
occur. The result is incomplete combustion which  
produces carbon monoxide, a poisonous gas that  
can cause death. Safe operation of indirect-fired  
gas burning equipment requires a properly  
operating vent system which vents all flue  
products to the outside atmosphere. FAILURE TO  
PROVIDE PROPER VENTING WILL RESULT  
IN A HEALTH HAZARD WHICH COULD  
CAUSE SERIOUS PERSONAL INJURY OR  
DEATH.  
1) Set thermostat to lowest setting  
2) If service is to be performed, turn off all electric power  
to the appliance.  
3) Open the access door.  
4) Turn the gas control knob to "OFF" (follow instruc-  
tions in No. 4 above). Do not force control knob.  
5) Close the access door.  
Check installation after start-up:  
%&Vent System Testing Procedure - Power Vent  
Units (does not apply to separated-combustion  
installation)  
1. Seal any unused openings in the venting system.  
2. Inspect the venting system for proper size and horizontal  
pitch, as required in the National Fuel Gas Code, ANSI  
Z223.1 or CAN/CGA B149.1 and B149.2, Installation Code  
for Gas Burning Appliances and Equipment, and this  
manual. Determine that there is no blockage or restric-  
tion, leakage, corrosion and other deficiencies which could  
cause an unsafe condition.  
If installed as a separated-combustion unit, install  
either the horizontal or vertical combustion air/  
vent system illustrated in Paragraph 7A using the  
concentric adapter supplied. Always comply with  
the combustion air requirements in the installation  
codes and instructions. Combustion air at the  
burner should be regulated only by manufacturer-  
provided equipment. NEVER RESTRICT OR  
OTHERWISE ALTER THE SUPPLY OF  
COMBUSTION AIR TO ANY HEATER.  
CHECK THE VENT SYSTEM FOR  
SOUNDNESS AND FUNCTION; MAINTAIN IT  
IN PROPER OPERATING CONDITION.  
3. In so far as practical, close all building doors and win-  
dows and all doors between the space where the heater is  
and other spaces of the building. Turn on clothes dryers  
and exhaust fans, such as range hoods and bathroom  
exhausts, so they shall operate at maximum speed. Do not  
operate a summer exhaust fan. Close fireplace dampers.  
4. Light the heater following the lighting instructions. Ad-  
just the thermostat for continued operation. Verify that  
combustion products are venting properly. After deter-  
mining that the heater vents properly, return doors, win-  
dows, exhaust fans, and fireplace dampers to their previ-  
ous conditions. If improper venting is observed, the vent-  
ing system must be corrected.  
%With the unit in operation, measure manifold gas pressure.  
Manifold pressure for natural gas should be 3.5" w.c. and 10"  
w.c. for propane gas. See Paragraph 9.  
%Turn the unit off and on, pausing two minutes between each  
cycle. Observe for smooth ignition.  
%Place the "Owner's Envelope" containing the Limited War-  
ranty, this booklet, the operation/maintenance/service manual,  
and any control or optional information in an accessible loca-  
tion near the heater. Follow the instructions on the envelope.  
Mfg No. 164771, Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
©2001 Thomas & Betts Corporation, All rights reserved.  
Printed in the U.S.A.  
MANUFACTURER OF HEATING, COOLING, AND VENTILATING SYSTEMS  
Trademark Note: Reznor® is registered in the United States and other countries.  
2/01 YL Form RZ 405 (Version B)  
Form 405, Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  

TC electronic SDN BHD Guitar NDY 1 User Manual
Technicolor Thomson Stereo System MS6000 User Manual
Thule Automobile Accessories 083 User Manual
Toshiba CRT Television 35AF44 User Manual
Toshiba Recording Equipment ES48 User Manual
Ultra Products Automobile Battery Charger ULT40056 User Manual
Viking Outdoor Storage 30 inch W User Manual
Vizio Computer Monitor VA220E User Manual
VTech Cordless Telephone TL86009 User Manual
Vulcan Hart Gas Heater SG4 User Manual