| Model CAUA   Gas-Fired, Indoor, Vertical (Upflow)   Power-Vented Heater   C E R T I F I E D   INSTALLATION FORM RZ 405 (Version B)   Obsoletes Form RGM 405 (Version A)   APPLIESTO:   Installation   Table of Contents   Installation and Operation ...........................Paragraphs 1-18 .... Pages 1-18   Optional Accessories ................................ Paragraphs 19-21 .. Pages 19-21   Check Installation and Start-Up ........................Paragraph 22 .. Pages 22-23   Index   By Page No.   Index   By Page No. Index   By Page No.   Belt Drive ............................................. 15   Blower Motor and Drive ...................... 15   Check/Test/Start-Up ............................. 22   Clearances ................................................ 2   Combustion Air ...................................... 4   Combustion Air Proving Switch ........... 15   Concentric Adapter ............................ 2, 5   Condensate Drain .......................... 14   Confined Space Installation .................. 10   Cased Cooling Coil (Model ACU) ..... 2, 19   Control Location Illustration ................. 15   Dimensions ............................................. 3   Discharge Plenum (Optional) ............ 2, 21   Duct Connections ................................. 12   Electrical Supply and Connections ....... 14   Filter Cabinet (Optional) .................. 2, 20   Gas Piping and Pressures ..................... 13   Gas Valve .............................................. 16   General .................................................... 1   Hazard Intensity Levels ......................... 2   Ignition System ..................................... 16   Inlet Base (Optional) ......................... 2, 21   Installation Codes ................................... 2   Mixing Cabinet (Optional) .............. 2, 21   Motor Amps ......................................... 16   Mounting the Heater .............................. 2   Start-Up ................................................. 22   Thermostat ........................................... 14   Uncrating and Preparation ...................... 2   Vent and Combustion Air ....................... 4   Determine Type of Vent ........................ 4   Power Vent Only Installation ......... 10-11   Separated-Combustion Installation ... 5-9   Warranty .................................................. 2   Wiring Diagrams .............................. 17-19   REFERENCES:   Installation Manual for Optional Filter Cabinet, RZ 405-FC   Installation Manual for Optional Mixing Box, RZ 405-MB   Installation Instructions for Optional Inlet Base, RZ 405-IB   Installation Instructions for Optional Discharge Plenum, RZ 405-DP   Operation/Maintenance/Service Manual, Form RZ 405-OMS   Installation Manual for Model ACU Cooling Coil, RZ 405-CC   Gas Conversion Instructions for Model CAUA, RZ 405-GC   FOR YOUR SAFETY   FOR YOUR SAFETY   What to do if you smell gas:   Do not store or use gasoline or other flammable   vapors and liquids in the vicinity of this or any   other appliance.   • Do not try to light any appliance.   • Do not touch any electrical switch; do not   use any phone in your building.   GENERAL   Installation should be done by a qualified agency in accordance with the   instructions in this manual and in compliance with all codes and re-   quirements of authorities having jurisdiction. The instructions in this   manual apply to the heater model shown below.   • Immediately call your gas supplier from a   neighbor's phone. Follow the gas supplier's   instructions.   Model   CAUA   Description   • If you cannot reach your gas supplier, call   your fire department.   Gas-Fired,   Power-Vented,   Vertical (Upflow)   Heater   WARNING: Improper installation, adjustment,   alteration, service, or maintenance can cause   property damage, injury, or death. Refer to this   manual. For assistance or additional information,   consult a qualified installer, service agency, or the   gas supplier.   Model CAUA heaters are design-certified by the Canadian Standards   Association (CSA) to ANSI Z83.6 and CGA 2.6-M96 for industrial/   commercial installations in the United States and Canada. Heaters are   available for use with either natural or propane gas. The type of gas, the   firing rate, and the electrical characteristics are on the unit rating plate.   A Model CAUA heater requires installation of an inlet air duct or an   optional inlet air base and a supply duct or an optional discharge ple-   num. This heater may be installed as a separated-combustion system   (taking combustion air from outside) or as a power-vented system   (taking combustion air from the space where the heater is installed).   WARNING: Gas-fired appliances are not   designed for use in hazardous atmospheres   containing flammable vapors or combustible dust.   See Hazard Levels, page 2.   Mfg No. 164771, Page 1   Download from Www.Somanuals.com. All Manuals Search And Download.   6. Dimensions   Figure 1 - Dimensions of Model CAUA   1 (25mm)   3-5/8 (92mm)   Right   Side   View   13-1/4   (337mm)   Top View   A C Plenum Opening   Alternate   Gas   Connection   D Plenum   Opening   Corner indicators for   cutting inlet air opening   B 16   (406mm)   Electrical   (supply voltage)   Combustion Air Cutout   Venter Outlet   Gas   150, 200, 250 -   5 (127mm);   300, 350, 400 -   6 (152mm)   150, 200 - 5 (127mm);   250, 300, 350, 400 - 6 (152mm)   6-3/8   (162mm)   E F 4-1/8   (105mm)   2-1/8 (54mm)   1-1/2 (38mm)   K G 2-3/8 (60mm)   H Rear   View   24-3/8   (619mm)   Control Door   46-1/2   (1181mm)   Corner indicators for cutting   inlet air opening   16   (406mm)   22-1/4   (565mm)   Blower Door   2-1/8 (54mm)   2-1/2 (64mm)   J 1/2 (13mm)   Control Side of Hater   Front View   Corner indicators for   cutting inlet air opening.   NOTE: Composite drawings are   not proportional for all sizes.   Bottom   View   M BOTTOM VIEW   Dimensions (inches + or - 1/8")   Size   A B C D E F G H 24   24   J K M N P P 150 38 34-3/4 36 21 7-1/4 3-3/4 12-1/2   200 38 34-3/4 36 21 7-1/4 3-3/4 12-1/2   250 50 34-3/4 48 21 7-1/4 4-3/8 12-3/4 27-1/4 45 31 16 46 4-3/4   300 50 34-3/4 48 21 7-1/4 4-3/8 12-3/4 27-1/4 45 31 16 46 4-3/4   33 31 19 34 4-5/8   33 31 19 34 4-5/8   N 2   (51mm)   350 50 49-3/4 48 34   400 50 49-3/4 48 34   7 7 4-3/8 14-1/8 26-3/4 45 44 32 46 4-7/8   4-3/8 14-1/8 26-3/4 45 44 32 46 4-7/8   Air Opening Dimensions   Supply Air (Discharge with duct flange) C x D   Dimensions (mm +or- 3)   Inlet Air Opening (location selected by installer)   Right Side of Heater   Left Side* of Heater   Rear of Heater   K x 16" (406mm)   K x 16" (406mm)   J x 16" (406mm)   Size   A B C D E F G H J K M N P 150 965 883 914 533 184 95 318 610 838 787 483 864 117   200 965 883 914 533 184 95 318 610 838 787 483 864 117   250 1270 883 1219 533 184 111 324 692 1143 787 406 1168 121   300 1270 883 1219 533 184 111 324 692 1143 787 406 1168 121   350 1270 1238 1219 864 178 111 359 679 1143 1118 813 1168 124   400 1270 1238 1219 864 178 111 359 679 1143 1118 813 1168 124   Bottom of Heater   M x N   *Right side is illustrated; corner indicators for open-   ing are the same on the left side.   Mfg No. 164771, Page 3   Download from Www.Somanuals.com. All Manuals Search And Download.   7. Venting and Combustion Air   concentric adapter combustion air/vent system. Flue products must   always be vented to the outdoors.   Installation should be done by a qualified agency in accordance with   these instructions. The qualified service agency installing the vent or   vent/combustion air system is responsible for the installation.   WARNING: The vent must be installed in   accordance with national and local regulations.   Failure to provide proper venting could result in   death, serious injury and/or property damage. This   unit must be installed with a vent to the outside of   the building. Safe operation of any power-vented   gas-fired equipment requires a properly operating   vent system, correct provision for combustion air,   and regular maintenance and inspection.   The venting or venting/combustion air systems illustrated in this manual   are the only ones approved for a Model CAUA heater. However, since   more than one system is approved and requirements vary depending on   the type of installation, the first step must be deciding which vent or   vent/combustion air system is going to be installed. Review the follow-   ing matrix of vent types and installation requirements. If there is any   doubt as to what type of vent is required, contact the equipment dis-   tributor before beginning installation.   WARNING: Units installed in multiples require   individual vent pipe runs and vent caps.   Manifolding of vent runs is not permitted due to   possible recirculation of combustion products into   the building and back pressure effects on the   combustion air proving switch.   Hazards of Chlorines - The presence of chlorine vapors in the com-   bustion air of gas-fired heating equipment presents a potential corro-   sion hazard. Chlorine will, when exposed to flame, precipitate from the   compound, usually freon or degreaser vapors, and go into solution with   any condensation that is present in the heat exchanger or associated   parts. The result is hydrochloric acid which readily attacks all metals   including 300 grade stainless steel.   Care should be taken to separate these vapors from the combustion   process. This may be done by installing a separated combustion sys-   tem and/or wise location of the furnace with regard to exhausters or   prevailing wind direction. Chlorine is heavier than air. This fact should   be kept in mind when determining installation locations of heating equip-   ment and building exhaust systems.   Venting must be in accordance with the National Fuel Gas Code Z223.1   or CAN/CGA B149.1 and B149.2, Installation Code for Gas Burning   Appliances and Equipment, and all local codes. Local requirements   supersede national requirements. Combustion air for this heater may be   either taken from the space or may be ducted from the outside using the   STEP 1 - Decide which Venting System to Install:   Type of   Installation   Vent Configuration/Options   Required   Type of Vent System   (Description/Instructions)   Type of VENT Pipe* Required   Horizontal Vent / Option CC6   (includes concentric adapter box,   exhaust terminal, and inlet air guard)   Vertical Vent / Option CC2   (includes concentric adapter box,   exhaust terminal, and combustion air   inlet)   Use either vent pipe approved for a Category III   appliance OR single-wall, 26-gauge or heavier   galvanized (or a material of equivalent durability   and corrosion resistance) vent pipe.   COMMERCIAL/ S eparated-Combustion   (uses a power venter to duct   combustion air from outdoors   and exhaust flue products to   INDUS TRIAL   (Harmonized   ANSI Z83.8-1996   and Canadian   Standard   the outdoors) -   (follow   Instructions in Section 7A)   CAN/CGA 2.6-   M96)   (uses a power   Use either vent pipe approved for a Category III   appliance OR appropriately sealed 26-gauge   galvanized steel or equivalent single-wall pipe. If   local code requires, the terminal section may be   double-wall pipe with a single-wall vent run.   Power-Vented   Horizontal Vent / Option CC1   venter to draw combustion air Vent Cap or field-supplied   from the indoor space and   exhaust flue products to the   equivalent (see page 11)   outdoors) -   (follow   Instructions in Section 7B)   Vent pipe listed above for a horizontal power-   vented system may be used, OR vent pipe   approved for a Category I heater may be used.   Single-wall pipe or double-wall (Type B) vent   pipe are suitable for use with a Category I heater.   At least 1/2 of the Equivalent   Vent Length is Vertical / Option   Vent Cap or field-supplied   CC1   equivalent (see page 11)   If local code requires, the terminal section may be   double-wall pipe with a single-wall vent run.   STEP 2 - Follow the instructions that apply to the type of vent being   installed   • Separated-Combustion -- requires air inlet pipe, exhaust vent pipe, and concentric adapter kit (Option CC2 or CC6)   Using required pipe (See Table above), FOLLOW INSTRUCTIONS IN SECTION 7A   • Power Vent -- requires vent pipe and vent cap (Option CC1 or field-supplied Type L Breidert Air-x-hauster® or equivalent vent   cap)   Using required pipe (See Table above), FOLLOW INSTRUCTIONS IN SECTION 7B   Form 405, Page 4   Download from Www.Somanuals.com. All Manuals Search And Download.   7A. Venting and Combustion Air Requirements for Separated-Combustion   Installation (must use either Option CC2 or CC6)   Specific Requirements (read all before installing)   Comply with the specific requirements and instructions in the following paragraphs and illustrations.   1. Combustion Air Inlet   Diameter is 5" for Sizes 150 and 200 and 6" for Sizes 250, 300,   350, and 400.   Use tin snips or aviation shears to cut out the hole in the top of   the heater (See Figure 2). Insert the pipe through the hole and   attach it to the collar inside the heater. Seal the joint. (Larger size   heaters have oval collars. If the collar is oval, form the pipe to fit   the collar.)   Figure 2 - Attach Combustion Air Pipe   Venter   Outlet   Use tin snips   to cut out   hole for   combustion   air pipe   2. Venter Outlet   Collar for   connecting   combustion air   pipe   The venter outlet size is 5" for Sizes 150, 200, and 250 and 6" for   Sizes 300, 350, and 400. A minimum length of 12" of straight   pipe is required at the venter outlet.   3. Concentric Adapter   If installed as a separated-combustion unit, a concentric adapter   is required.   1) Remove door panel.   2) Cut out the hole.   3) Slide pipe down through hole.   4) If collar is oval, form pipe to fit. Attach pipe to collar with   sheetmetal screws and seal the connection.   • Option CC2 and CC6 - The concentric adapter is a   metal box that attaches to the inside of the building. See   the illustrations and dimenstions in Figures 3A and 3B.   Option CC6 is horizontal; Option CC2 is vertical. (Op-   tion kits also include a vent terminal and combustion air   inlet or guard.)   Figure 3A - Concentric Adapter Assembly in Options CC2 and CC6   View of Heater Connection Side   View of Vent Terminal Connection Side   2 (51mm)   Collar for   connecting   indoor portion   of the   6 (152mm)   2 (51mm)   Collar for outside portion of the   combustion air pipe (vent pipe   extends through the box   internally concentric to the   outside portion of the combustion   air pipe)   combustion   air pipe   Install rubber seal   for vent pipe   End View   H F Figure 3B - Concentric Adapter Box   Dimensions - inches (mm)   Top View of the Concentric Adapter   Box Showing Air Flow   E CAUA   150,200   5 (127)   250,300,350,400   6 (152)   B = Combustion Air Flow   A B C D E F = Exhaust (Vent) Gas Flow   4 (102)   5 (127)   4 (102)   4 (102)   Field-supplied vent   pipe passes   through the   rubber seal on the   concentric adapter   box, extending out   both sides of the   box   7-1/2 (191)   5 (127)   7-1/2   G D 5 (127)   4 (102)   5 (127)   G H J 16-1/2 (419)   8 (203)   16-1/2 (419)   10 (254)   8 (203)   C 6 (152)   A = Diameter of the   Collar for attaching   the inside   Combustion Air Pipe   from the Heater   J = Diameter of the   Side View - Side of the   Adapter Box that Connects   to the Heater   Collar for attaching the   "Outside" Portion of the   Combustion Air Pipe   Mfg No. 164771, Page 5   Download from Www.Somanuals.com. All Manuals Search And Download.   7. Venting and Combustion Air (cont'd)   7A. Venting and Combustion Air Requirements for Separated-Combustion   Installation (must use either Option CC2 or CC6) (cont'd)   either tape suitable for 550°F (such as Option FA1, P/N 98266) or   high-temperature (450°F) silicone sealant.   4. Pipe Diameter and Length   Maximum Pipe Length from Heater to Concentric Adapter -   • If using Category III vent pipe, follow the pipe manufacturer's in-   minimum length is five feet (1524mm)   structions for joining pipe sections.   Model   Pipe Diameter   Maximum 90° Elbow 45° Elbow   In Concentric Pipes (outdoor portion) from Concentric Adapter   Box to Air Inlet and Vent Terminal - Follow the installation instruc-   tions for the specific option (CC6 for horizontal vent; CC2 for vertical   vent).   CAUA   150-200   Vent Inlet Air   Length   40 ft   Equals*   5 ft   Equals*   2.5 ft   5"   5"   6"   5"   6"   6"   12.2 M   50 ft   1524 mm   5 ft   762 mm   2.5 ft   250   Joints Requiring Taper-type Connections (See Figure 4) - When   the diameter of the pipe in the vent pipe run is different from the vent   pipe in the terminal section, the joint must be made with a taper-type   pipe connector. Install the connector no more than 6" (152mm) from the   concentric adapter box. A 5" to 4" reducer is required in the vent pipe on   Sizes 150 - 200; a 6" to 5" reducer is required on Sizes 300 - 400.   15.2 M   50 ft   1524 mm   5 ft   762 mm   2.5 ft   300-400   15.2 M   1524 mm   762 mm   *Reduce maximum length by this amount for each elbow.   Concentric Pipes (the vent pipe runs concentric through the out-   door portion of the combustion air pipe) - Sizes 150 and 200 require   a 6" diameter combustion air pipe for outdoor portion and a 4" diam-   eter vent pipe through the concentric adapter to the terminal; Sizes   250-400 require an 8" diameter combustion air pipe for the outdoor   portion and a 5" diameter vent pipe through the concentric adapter to   the terminal.   Figure 4 - When joining different pipe diameters, use taper-   type pipe connectors   Taper-type Connector   Reducer   Either collar   or smaller   diameter pipe   Airflow   Length depends on building construction; specific requirements are   included with the concentric adapter kit instructions.   Secure joints with sheetmetal   screws and seal.   5. Joints   6. Support   Determined by type of pipe - Provide field-supplied vent pipe as   specified in the Table on page 4.   Support horizontal runs every six feet (1829mm); do not rely on the   heater or concentric adapter for support of either horizontal or vertical   pipes.   • If using single wall, 26-gauge or heavier galvanized pipe, secure   slip-fit connections using sheet metal screws or rivets. Seal all   joints. Seal combustion air pipe with pressure sensitive tape ordi-   narily used for warm-air ductwork. Seal flue exhaust pipe with   7. Clearance   Clearance from the vent pipe to combustibles is 6" (152mm). Do not   enclose the vent pipe.   Instructions and Requirements for Installing Horizontal Vent Terminal/Combustion Air Inlet   Option CC6   • Mounting brackets for concentric adapter box (or box may be   mounted flush, depending on building construction)   Taper-type reducers as required (see requirements above)   Option CC6 Package includes:   Qty Description   150,   200   250, 300,   350, 400   • Installation Instructions for Option CC6   1 1 1 Complete Horizontal Vent Kit   (Same as Option CC6)   Concentric Box Assembly   (See Figures 3A and 3B)   Screened   157158 82131   155392 68404   155096 53316   1. Determine the location on the outside wall for the vent terminal   (Applies to all horizontal vent kits). In most applications, the terminal   would be on a level with the heater mounting height. Allow 1/4" per foot   downward pitch toward the terminal for draining of condensation.   The distance of the termination of the horizontal vent from adjacent public   walkways, adjacent buildings, openable windows, and building openings   must be in accordance with local codes or, in the absence of local codes,   must conform with National Fuel Gas Code. Local codes supersede all   provisions in these instructions and in the National Fuel Gas Code. Mini-   mum clearances for the horizontal vent terminal are as shown in the table on   page 7.   Exhaust Assy   1 Inlet   Guard   151755 124940   4 1 1 #10-16x1/2" lg Screws (to   attach the inlet guard)   Rubber seal for vent pipe opening 164492 164493   in concentric adapter   Tube of high temperature (450°F) 53335   silicone sealant   37661   37661   Products of combustion can cause discoloration of some building finishes   and deterioration of masonry materials. Applying a clear silicone sealant   that is normally used to protect concrete driveways can protect masonry   materials. If discoloration is an esthetic problem, relocate the vent or install   a vertical vent.   53335   Field-supplied installation requirements:   • Thimble (a thimble is not required if wall is of non-combus-   tible construction)   Flashing   Vent pipes (see requirements on pages 4 and 6)   Combustion air pipes (see requirements on pages 4 and 6)   WARNING: All vent terminals must be positioned or   located away from fresh air intakes, doors and   windows to preclude combustion products from   entering occupied space. See Hazard Levels, page 2.   • • • Form 405, Page 6   Download from Www.Somanuals.com. All Manuals Search And Download.   Minimum Clearances for Vent   Termination Location (all   directions unless specified)   Collar for   combustion   air pipe.   Concentric Adapter Box   Field-supplied   5A   Structure   mounting brackets   Forced air inlet within 10 ft 3 ft (0.9m) above   (3.1m)   Combustion air inlet of   another appliance   Door, window, or gravity air 4 ft (1.2m) horizontally   inlet (any building opening) 4 ft (1.2m) below   1 ft (30cm) above   6 ft (1.8m)   Combustion air pipe   Seal the seam in the vent pipe.   Combustion   Flow   Air   ent Flow   V *Do not terminate   the vent directly   Electric meter, gas meter *   and relief equipment   4 ft (1.2m)   horizontally   above a gas meter   or service regulator.   Gas regulator *   3 ft (0.9m)   Install rubber seal in   vent pipe opening.   16 (406mm) minimum   2 (51mm)   ox plus   Adjoining building or parapet 6 ft (1.8m)   Adjacent public walkways   Grade (ground level)   appr   wall thickenss   7 ft (2.1m) above   7 ft (2.1m) above   Vent Pipe - when a taper-type   reducer is required in   the vent pipe; the connection   must be no more than 6   (152mm) from the box.   2. Prepare clearance hole through the outside wall for a 6"   diameter pipe (Size 150 or 200) or an 8" diameter pipe   (Size 250, 300, 350, or 400). Outside wall construction   thickness should be between 1" (25mm) minimum and 30"   (762mm) maximum. The larger diameter combustion air   pipe serves as clearance for the exhaust pipe on non-com-   bustible construction. A thimble may or may not be re-   quired depending on wall construction and/or local codes.   3. Prepare the concentric adapter box.   3a) Determine whether field-supplied brackets are   required. The box must be positioned so that the   distance from the outside of the wall to the box is a   minimum of 12" (305mm). Maximum distance is 60"   (1524mm). If brackets are used, box should be angled   slightly to allow for downward pitch of pipes. If used,   attach brackets securely; do not leave any unsealed   holes in the adapter box.   Figure 5A. On all Sizes except 250, no more than 6" (152mm) of vent pipe   should extend out the heater side. Any time the pipe is re-positioned, re-check   the seal to be sure that it has not rolled. Adjust the pipe and seal until the pipe is   the correct length on each side of the box and the seal is over the edge of the hole   and tight to the entire circumference of the pipe.   3c) Attach the outside portion of the combustion air pipe to the box. Determine   the length by measuring the bracket length (if brackets are used), plus the wall   thickness, plus 2" (51 mm). The inlet pipe should extend beyond the outside   wall approximately 2" (51mm). Attach the inlet air pipe to the collar of the   concentric adapter with sheetmetal screws being careful not to penetrate the   vent pipe.   4. Attach the concentric adapter box to the wall. Insert   the vent pipe and combustion air pipe through the wall.   Push the concentric adapter box flush against the inside   wall or attach to the wall with the field-supplied brackets.   Caulk or flash inlet air pipe on the outside wall. Flashing is   field supplied.   Flash or caulk   the inlet air pipe   on the outside   If brackets are not used, when the box is installed,   position it tight against the wall.   3b) Install the rubber seal and the vent pipe. Locate the   vent pipe opening (no collar) and place the rubber seal   around and over the edge of the metal.   wall   5. Slide the inlet guard over the end of the vent pipe   and position it on the end of the combustion air pipe. See   Determine the length of the section of vent pipe by   adding the requirements. On the heater side of all Sizes   except CAUA 250, the vent pipe must extend no more   than 6" (152mm) (length limit does not apply to Size   250 because the pipe diameter does not change); plus   6" (152mm) through the box; plus bracket length; plus   the width of the wall; plus a minimum of 18" (457mm)   on the outside (if   Figure 5B. Attach the guard to the inlet air pipe with the   four 1/2" lg screws provided.   6. Position the vent cap on the end of the vent pipe. Align the cap so that its baffle   strips are positioned on the horizontal and vertical centerlines (See Figure 5C).   Attach the exhaust cap to the vent pipe with sheetmetal screws.   5B   First, attach the inlet air guard;   Second, attach the exhaust cap   5C   Inlet Air Guard   Worksheet - Determine Length of   the inlet air pipe   extends recom-   Vent Pipe through the Box   inches mm   IMPORTANT: Install   mended   2"   Heater Side (max if +   diameter changes)   6 152   exhaust cap with baffles   positioned on horizontal and   vertical centerlines as illustrated.   (51mm) beyond   the wall).   Width of Box   Bracket Length   Width of Wall   + + + 6 152   Lubricate the seal   and pipe with liq-   uid soap or a rub-   ber lubricant. (In-   stallation Tip:   Spray cooking oil   __ ___   __ ___   7. Horizontal vent terminal/combustion air inlet Option CC6 is installed and ready   for connection to the heater.   Terminal Side (min) + 18 457   Length of Pipe   = 8. Connect the Concentric Adapter Box to the Heater - Use the pipe specified   and joints required for type of pipe. If collar or opening at the heater or adapter are   different diameters from the pipe (use only diameters allowed on page 6), make joint   connection with field-supplied taper-type reducer or enlarger.   A minimum of 12" (305 mm) of straight pipe is required at the venter outlet.   Due to the high temperature, do not enclose the exhaust pipe or place pipe closer   than 6" (152 mm) to combustible material.   Installation of the horizontal vent and combustion air system on your separated-   combustion unit is complete. Refer to Figure 5D and verify that all installation   requirements are met. Continue to Paragraph 8.   works well as a lubricant for this task.)   Being sure the pipe is in the proper flow direction,   slide the end through the box and push it out through   the rubber seal. Push evenly using caution not to dis-   place the seal from its position on the edge of the hole.   If the rubber seal moves, slide the pipe back slightly,   re-position the seal, and slide the pipe through again.   Position the vent pipe so that it will extend a minimum   of 16" past the end of the combustion air pipe. See   Mfg No. 164771, Page 7   Download from Www.Somanuals.com. All Manuals Search And Download.   7. Venting and Combustion Air (cont'd)   7A. Venting and Combustion Air Requirements for Separated-Combustion   Installation (must use either Option CC2 or CC6) (cont'd)   60 (1524mm) maximum   12 (305mm) minimum   Figure 5D - Installation of a Typical Separated-   Combustion Unit with Horizontal Vent and Combustion   Air Pipes (Option CC6)   Top   View   Concentric Adapter   Seal Joints   Wall   Combustion Air Pipe   Seal joints; see Require-   ment No. 5 on page 6.   Inlet Air   Guard   Vent (Flue Exhaust) Pipe   Maximum Length (See Requirement   No. 4 on page 6.)   Building Overhang   Screened   Exhaust   Cap   Minimum length is 5 ft (1.5M)   Side View   Vent Pipe   - PITCH   TO   DRAIN   Concentric Adapter Box   6ft (1829mm)   minimum   16(406mm)   minimum   24(610mm)   minimum   Thimble   Adjoining   Building   Combustion Air Pipe   (PITCH TO DRAIN)   Wall   "Through-the-Wall" View of a typical   installation of a horizontal vent/inlet air   terminal and concentric adapter   (Option CC6)   IMPORTANT NOTE: Exhaust cap must be installed so the baffles   are positioned on horizontal and vertical centerlines.   Building Projection   Instructions and Requirements for Installing a Vertical Vent Terminal/Combustion Air Inlet   (Requires Concentric Adapter Kit, Option CC2)   Vertical Vent Terminal/Combustion Air Package   Installation Instructions for Option CC2   (Option CC2) includes:   Qty Description   1. Determine the location for the vent terminal on the roof, allowing room for the   150,   200   250,300,   350,400   concentric adapter box inside. A thimble may or may not be required depending   on building construction and/or local codes. Prepare a hole through the roof for   the combustion air pipe (Sizes 150 and 200, pipe is 6"; Sizes 250-400, pipe is 8").   The air inlet pipe must be flashed or sealed to the roof. Flashing is to be supplied   by the installer as required by roof construction and/or codes.   1 Complete Vertical Vent Kit 157156 54444   (Same as Option CC2)   1 1 Concentric Box Assembly   Exhaust   155392 68404   155631 53326   WARNING: All vent terminals must be positioned or   located away from fresh air intakes, doors and windows to   preclude combustion products from entering occupied   space. See Hazard Levels, Page 2.   Terminal   1 Combustion   Air Inlet   155635 53330   2. Prepare the concentric adapter box.   1 1 Rubber seal for vent pipe   opening in concentric adapter   Tube of High Temperature   (450°F) Silicone Sealant   164492 164493   2a) Determine whether field-supplied brackets are required. If used, attach   brackets securely; do not leave any unsealed holes in the adapter box.   If brackets are not used, when in-   53335   53335   Worksheet - Determine Length of   stalled, the box should be tight against   the roof.   2b) Install the rubber seal and the   Vent Pipe through the Box   Field-supplied installation requirements:   inches mm   • Thimble (a thimble is not required if wall is of non-   combustible construction)   Flashing   Vent pipes (see requirements on pages 4 and 6)   Combustion air pipes (see requirements, pages 4 and 6)   Mounting brackets for concentric adapter box (or box   may be mounted flush, depending on building construc-   tion)   Heater Side (max if +   diameter changes)   6 152   vent pipe. Locate the vent pipe open-   ing and place the rubber seal around   and over the edge of the metal.   Determine the length of the section of   vent pipe by adding the requirements.   On the heater side of all Sizes except   CAUA 250, the vent pipe must ex-   tend no more than 6" (152mm) (length   limit does not apply to Size 250 be-   • • • • Width of Box   + + + + 6 152   Bracket Length   Width of Roof   Inlet Pipe Height   __ ___   __ ___   __ ___   Terminal Side (min) + 22 559   • Taper-type reducers as required (see requirements on   page 6)   Length of Pipe   = Form 405, Page 8   Download from Www.Somanuals.com. All Manuals Search And Download.   2c) Attach the outside portion of the com-   bustion air pipe to the box. Determine   the length of the combustion air pipe so   that dimension "X" (Figure 6A) is equal   to the roof thickness, plus snow depth   and ridge or parapet clearance, but does   not exceed 60" (1524 mm). Attach the   combustion air pipe to the collar with   sheetmetal screws being careful not to   penetrate the vent pipe.   3. Attach the concentric adapter. Insert   the vent pipe and combustion air pipe up   through the roof and secure the adapter box.   Flash the combustion air pipe to the outside   of the roof as required.   6B   "X" is the length of combustion air   pipe required through and above   the roof   "X" must equal roof thickness   plus clearance required for   anticipated snow   6A   22"   (559mm)   minimum   Install the vent pipe   by inserting it into the   terminal side of the   box and pushing it out   through the seal on the   heater side.   Seal the seam in   the vent pipe.   plus ridge and/or   parapet clearance   NOTE: Be sure flow   direction is correct.   "X" must not   exceed 60"   (1524mm)   Snow   Clearance   Combustion   air pipe   Field-supplied   mounting brackets   4. Slide the combustion air inlet over the   vent pipe and fasten the collar   to the end of the combustion air   pipe with sheet metal screws   (See Figure 6C). Seal joint at top   between vent pipe and combus-   tion air inlet with silicone seal-   ant to prevent water leakage.   5. Attach the exhaust termi-   nal with sheet metal screws (See   Figure 6D).   6C   1)Slide combustion   air inlet over the   vent pipe   Concentric   Adapter Box   2)Fasten to the end   Collar for combustion   air pipe.   of the combus-   tion air pipe   3)Seal the top joint   with silicone   Vent Pipe - when a taper-type reducer   is required in the vent pipe; it must be no   more than 6 (152mm) from the box.   Install seal   in vent pipe   opening   cause the pipe diameter does not change); plus bracket length;   plus the width of the roof; plus the length of the outer inlet air   pipe; plus a minimum of 22" (559mm).   Install field-supplied   flashing at roof   opening (flashing not   illustrated).   6. Vertical vent terminal/combus-   tion air inlet is installed and ready   for connection to the heater.   7. Connect Concentric Adapter   Lubricate the seal and pipe with liquid soap or a rubber lubri-   cant. (Installation Tip: Spray cooking oil works well as a lubri-   cant for this task.) Being sure the pipe is in the proper flow   direction, slide the end through the box and push it out through   the rubber seal. Push evenly using caution not to displace the   seal from its position on the edge of the hole. If the rubber seal   moves, slide the pipe back slightly, re-position the seal, and   slide the pipe through again.   Position the vent pipe so that it will extend a minimum of 22"   (559mm) past the end of the combustion air pipe. See Figure   6B.   A maximum of 6" (152mm) of vent pipe should extend out the   heater side. Any time the pipe is re-positioned, re-check the   seal to be sure that it has not rolled. Adjust the pipe and seal   until the pipe is the correct length on each side of the box and   the seal is over the edge of the hole and tight to the entire   circumference of the pipe.   Box to the Heater - Use the pipe speci-   fied and joints required for type of pipe.   If collars at the heater or adapter are dif-   ferent diameters from the pipe (use only   diameters allowed on page 6), make con-   nection with field-supplied taper-type re-   ducer or enlarger.   A minimum of 12" (305 mm) of   straight pipe is required at the venter   outlet. Due to the high temperature, do   not enclose the vent pipe or place pipe   closer than 6" (152 mm) to combustible   material.   Exhaust   Terminal   12" (305mm)   minimum   Combustion   Air Inlet   6D   Installation of the vertical vent and combustion air system on your sepa-   rated-combustion unit is complete. Refer to Figure 6E and verify that all   installation requirements are met.   Figure 6E - Installation of Separated-Combustion Unit with Vertical Vent and Combustion Air Pipes (Option CC2)   Vent   Termina   Side View   9-3/8   (238mm)   l 6 ft (1829mm)   minimum   12 (305mm)   Seal with high   Flue   Exhaust   (Vent )   Pipe   temperature silicone   rubber sealant supplied   with the kit.   Wall or   Adjoining   Building   11 (279mm)   Combustion   Air Inlet   5 ft (1524mm)   maximum (Size   according to   anticipated   Flashing   (field supplied)   18(457mm)   minimum   Roof   snow depth.   Flashing   (field supplied)   Roof   Concentric   Adapter   Thimble   Combustion Air Pipe   Rear   View   "Through-the-Roof" View of a typical installation   of a vertical vent/inlet air terminal and concentric   adapter (Option CC2)   Concentric   Adapter   Vent   Pipe   Mfg No. 164771, Page 9   Download from Www.Somanuals.com. All Manuals Search And Download.   7. Venting and Combustion Air (cont'd)   7B. Venting and Combustion Air Requirements for Power Vent Drawing   Combustion Air from THE INSIDE SPACE and Venting Flue Products to   the Outdoors (vent cap is required)   If the environment has a positive pressure and is such that it is   not detrimental to combustion air, this system may be installed.   To provide combustion air to the heater sufficient air must enter   the equipment location to replace that exhausted through the   heater vent system. In the past, the infiltration of outside air   assumed in heat loss calculations (one air change per hour) was   assumed to be sufficient. However, current construction methods   using more insulation, vapor barriers, tighter fitting and gasketed   doors and windows, weather-stripping, and/or mechanical ex-   haust fans may now require the introduction of outside air through   wall openings or ductwork to the equipment room.   Figure 8 - Alternate   Vent in any   Vent Directions   position above   horizontal   A minimum of 12" of   straight pipe is required   before an elbow   The requirements for combustion and ventilation air depend upon   whether the unit is located in a confined or unconfined space. An   "unconfined space" is defined as a space whose volume is not less   than 50 cubic feet per 1000 BTUH of the installed appliance.   Under all conditions, enough air must be provided to ensure   there will not be a negative pressure condition within the equip-   ment room or space. Follow the specific requirements below for   a confined space installation.   Confined Space Installation - Do not install a unit in a con-   fined space without providing wall openings leading to and from   the space. Provide openings near the floor and ceiling for ventila-   tion and air for combustion as shown in Figure 7, depending on   the combustion air source as noted in Items 1, 2, and 3 below.   • Do not install dampers or any other type of flue restrictor device.   2) Vent Pipe Diameter and Length   Maximum Vent Length - minimum length is 5 ft (1.5M)   CAUA   Pipe   Diameter   Maximum   Length   90° Elbow   Equals*   45° Elbow   Equals*   150-250   300-400   5"   6"   50 ft (15.2M) 5 ft (1.5M)   50 ft (15.2M) 5 ft (1.5M)   2.5 ft (.8M)   2.5 ft (.8M)   *Reduce by this amount for each elbow.   Note: If the system contains all vertical pipe or a combination of horizontal   and vertical vent pipe, the Maximum Permissible Vent Length may be in-   creased one foot (305mm) for each foot (305mm) of vertical rise up to a   maximum increase of ten feet (3M).   Figure 7 - Confined Space:   A space whose   3) Vent Pipe and Joints   volume is less than   50 cubic feet per   1000 BTUH of the   installed appliance   input rating   Provide field-supplied vent pipe as specified in the Table on page 4.   • • • If using single wall, 26-gauge or heavier galvanized pipe, secure slip-fit   connections using sheet metal screws or rivets. Seal pipe joints either with   tape suitable for 550°F (such as Option FA1, P/N 98266) or high-tem-   perature silicone sealant.   If using Category III vent pipe, follow pipe manufacturer's instructions   for joining pipe sections. When attaching Category III pipe to the venter   outlet or the vent cap, make secure, sealed joints following a procedure   that best suits the style of Category III pipe being used.   If using double-wall (Type B) vent pipe (at least 1/2 of the equivalent vent   length must be vertical), follow pipe manufacturer's instructions for join-   ing pipe sections. For joining double-wall pipe to the venter outlet collar,   single-wall pipe, and/or the vent cap, follow the instructions below:   Add total BTUH of all appliances in the confined space and   divide by figures below for square inch free area size of each (top   and bottom) opening.   1. Air from inside the building -- openings 1 square inch free   area per 1000 BTUH. Never less than 100 square inches free area   for each opening. See (1) in Figure 7.   2. Air from outside through duct -- openings 1 square inch free   area per 2000 BTUH. See (2) in Figure 7.   3. Air direct from outside -- openings 1 square inch free area per   4000 BTUH. See (3) in Figure 7.   Instructions for attaching double-wall (Type B) vent pipe to the ven-   ter outlet, a single-wall pipe run, or to the vent cap (use these in-   structions for either full length double-wall or terminal only):   Hardware and Sealant Required: 3/4" long sheetmetal screws; and a tube of   high temperature silicone sealant   1) Look for the "flow" arrow on the vent pipe; attach according to the   arrow. Slide the pipe so that the venter outlet, the single-wall pipe, or the   vent cap is inside the double-wall pipe.   2) Drill a hole through the pipe into the outlet collar, the single-wall pipe,   or the vent cap. (Hole should be slightly smaller than the sheet metal   screw being used.) Using a 3/4" long sheet metal screw, attach the pipe.   Do not overtighten. Repeat, drilling and inserting two additional screws   evenly spaced (120° apart) around the pipe.   3) Use silicone sealant to seal any gaps. If there is an annular opening, run   a large bead of sealant in the opening. The bead of sealant must be large   enough to seal the opening, but it is not necessary to fill the full volume   of the annular area.   NOTE: For further details on supplying combustion air to a   confined space, see the National Fuel Gas Code ANSI Z223.1a   (latest edition).   Specific Venting Requirements (read all   before installing)   1) Venter (Flue) Outlet   Venter   Model Size   150, 200, 250 300, 350, 400   5" 6"   Outlet   Size:   Outlet Diameter   Venter Outlet Attachment Requirements:   • A minimum of 12" of straight pipe is required at the venter   outlet before installing an elbow in the vent system. An elbow   should never be attached directly to the venter. An elbow   attached to the straight pipe can be in any position at or above   horizontal. See Figure 8.   4) Vent System Support   Lateral runs should be supported every six feet (1.8M) using a non-combus-   tible material, such as strap steel or chain. Do not rely on the heater for   support of either horizontal or vertical vent pipe.   Form 405, Page 10   Download from Www.Somanuals.com. All Manuals Search And Download.   heater manufacturer (Option CC1) or a field-supplied cap. If the vent cap is   field-supplied, use a Type L Breidert Air-x-hauster® or equivalent vent cap.   (Type L Air-x-hauster® is a trademark of The G. C. Breidert Company.) Use   of a vent cap supplied by the pipe manufacturer is not permitted; the vent   cap must be the type approved for use with this heater. A different style   vent cap could cause nuisance problems or unsafe conditions.   See the illustrations in Figures 9A and 9B for requirements of vertical and   horizontal vent termination. The vent terminal pipe may be either single-   wall or double-wall (Type B). If double-wall pipe is used in the vent termi-   nal with a single-wall vent run, follow the instructions on page 10 to attach   the vent cap and to connect the double-wall pipe to the single-wall vent pipe   run.   5) Condensation   Any length of single-wall vent pipe exposed to cold air or run   through an unheated area or an area with an ambient temperature   of 45°F or less must be insulated along its entire length with a   minimum of 1/2" foil-faced fiberglass, 1-1/2# density insulation.   Where extreme conditions are anticipated, install a means of con-   densate disposal.   6) Vent Terminal (Pipe and Vent Cap)   The vent system must be terminated with the type of vent cap   approved for use with this heater. The vent cap must be the same   size as the vent pipe. Use either a vent cap available from the   Figure 8 - Horizontal Vent Terminals   Single-Wall Vent   Single-Wall   Vent Run   and Double-   Wall   Terminal   Roof or Building Overhang   Roof or Building Overhang   Run and Single-   Wall Terminal   12   12   (305mm)   minimum   6 (2M)   (305mm)   minimum   6 (2M)   minimum   minimum   Wall   Wall   Note position of   vent cap openings.   Note position of vent   Approved clearance   thimble for single-wall   vent pipe is required   when flue pipe extends   through combustible   materials.   cap openings.   Approved clearance   thimble for single-wall   vent pipe is required   when flue pipe extends   through combustible   materials. Follow   Pitch flue pipe down toward   outlet 1/4 per foot for con-   densate drainage.   (NOTE: Applies to entire   horizontal vent run.)   Pitch flue pipe down toward outlet   1/4 per foot for condensate drainage.   (NOTE: Applies to entire horizontal   vent run.)   the requirements   of the double-wall   pipe manufacturer.   Follow instructions on page 10 to join single   and double-wall pipe and to seal the connection.   Horizontal Vent Terminal Clearances   Structure   Minimum Clearances for Vent Termination   Location (all directions unless specified)   3 ft (0.9m) above   6 ft (1.8m)   4 ft (1.2m) horizontally   4 ft (1.2m) below   A vent cap is required. Maintain a clearance   of 12" from the wall to the vent terminal cap   for stability under wind conditions.   Forced air inlet within 10 ft (3.1m)   Combustion air inlet of another appliance   Door, window, or gravity air inlet   (any building opening)   Products of combustion can cause discolora-   tion of some building finishes and deteriora-   tion of masonry materials. Applying a clear   silicone sealant that is normally used to pro-   tect concrete driveways can protect masonry   materials. If discoloration is an esthetic prob-   lem, relocate the vent or install a vertical vent.   1 ft (30cm) above   Electric meter, gas meter* and relief   equipment   Gas regulator*   Adjoining building or parapet   Adjacent public walkways   Grade (ground level)   4 ft (1.2m)   *Do not terminate the vent   horizontally directly above a gas meter   3 ft (0.9m)   6 ft (1.8m)   or service regulator.   7 ft (2.1m) above   7 ft (2.1m) above   Figure 9 - Vertical Vent Terminals   Single-Wall Vent   Run and Single-   Wall Terminal   Single-Wall Vent   Run and Double-   Wall Terminal   6 (2M) minimum   Vertical flue extension   to be 6 (152mm) higher   than anticipated snow   depth but no less than   2 feet (610mm) above the   roof.   Vertical flue extension to   be 6 (152mm) higher than   anticipated snow depth but   no less than 2 feet (610mm)   above the roof.   Vertical pipe extension   must be insulated.   6 (2M) minimum   Roof Flashing   Roof Flashing   Roof - pitched   from 0 to 45°   Roof - pitched   from 0 to 45°   6 (152mm) minimum   Approved clearance thimble   for single-wall vent pipe is   Approved clearance thimble   for single-wall vent pipe is   required when flue pipe   extends through   required when flue pipe extends   through combustible materials.   Follow the requirements of the   double-wall pipe manufacturer.   Follow instructions on page 10   to join single and double-wall   pipe and to seal the connection.   combustible materials.   Mfg No. 164771, Page 11   Download from Www.Somanuals.com. All Manuals Search And Download.   The cut edges of the metal will be sharp.   8. Duct Connections and   Ductwork   If installing an optional filter or filter/mixing cabinet shipped with the   heater, attach the cabinet at the "cutout" opening (See Optional Acces-   sories, Paragraph 18 or 19). Depending on the cabinet and how it is   installed, the inlet opening may be horizontal or vertical.   Attach the ductwork to the heater or to the inlet cabinet.   Both inlet air ductwork and supply air discharge ductwork are required   unless the heater is equipped with an optional inlet base and/or an   optional discharge plenum. IMPORTANT NOTE: If a Model ACU   cased cooling coil is part of the installation, it must be installed before   attaching discharge ductwork. Installation of a filter cabinet is rec-   ommended when a cooling coil is installed.   Figure 12 - Duct Opening for Connecting the Inlet Air   Duct to the field-installed Filter or Mixing Cabinet   Depending on the heater size and whether the cabinet is on the side   or the rear, the inlet opening may be either vertical (on the top of the   filter cabinet) or horizontal (on the side of the filter cabinet.)   Discharge Duct Connection - The discharge duct connects to the top   of the heater or to the outlet of the optional cooling coil cabinet. See   Figures 10 and 11. Connect the ductwork plenum to the duct flange as   illustrated in Figure 11.   1) The duct connection on the top of the heater has a 90° flange.   2) The duct may either have no flange or a 90° flange.   Filter Cabinet Inlet Opening   150, 200 - Rear or Side Filter Cabinet - 32 (813mm)   250, 300 - Side Filter Cabinet - 32 (313mm)   3) Position ductwork around the outside of the heater flange.   250, 300 - Rear Filter Cabinet - 45-1/8 (1146mm)   350, 400 - Rear or Side Filter Cabinet = 45-1/8 (1146mm)   4) If the ductwork has a flange, drill holes vertically through duct   flange into the top of the heater and secure with sheetmetal   screws. If the ductwork does not have a flange, drill holes hori-   zontally through the ductwork and the heater flange; secure with   sheetmetal screws.   16   (406mm)   Inlet   Opening   Figure 10 - Top View showing Discharge Duct   Connection Dimensions (inches)   A Requirements and Suggestions for Connecting   and Installing Ducts   B • Type of Ductwork - The type of duct installation to be used de-   pends in part on the type of construction of the building.   • Ductwork Material - Rectangular duct should be constructed of   not lighter than No. 26 U.S. gauge galvanized iron or No. 24 B & S   gauge aluminum.   Electrical   Combustion Air Knockout   Venter Outlet   Gas   • Ductwork Structure - All duct sections 24 inches or wider, and   over 48 inches in length, should be cross broken on top and bottom   and should have standing seams or angle-iron braces. Joints should   be S and drive strip, or locked.   6-3/8   (162mm)   4-1/8   (105mm)   2-3/8 (60mm)   • Through Masonry Walls - No warm air duct should come in con-   tact with masonry walls. Insulate around all air duct through ma-   sonry walls with not less than 1/2" (1" is recommended) of insula-   tion.   • Through Unheated Space - Insulate all exposed warm air ducts   passing through an unheated space with at least 1/2" (1" is recom-   mended) of insulation.   • Duct Supports - Suspend all ducts securely from buildings mem-   bers. Do not support ducts from unit duct connections.   • Duct Sizing - Proper sizing of the supply air ductwork is neces-   sary to ensure a satisfactory heating installation. The recognized   authority for such information is the Air Conditioning Contractors   Association, 1228 17th Street N.W., Washington, D.C. 20036. A   manual covering duct sizing in detail may be purchased directly   Size   A B 150, 200   250, 300   350, 400   36" (914mm) 48" (1219mm) 48" (1219mm)   21" (533mm) 21" (533mm) 34" (864mm)   Figure 11 - Connecting Discharge Ductwork   Removable   Access Panel in   the Ductwork -   6" x 10"   (152mm x   254mm)   minimum   from them.   CAUTION: An external duct system static pressure   not within the limits shown on the rating plate, or   improper motor pulley or belt adjustment, may   overload the motor. See Hazard Levels, page 2.   Attach to Duct   Flange   Heater   • Removable Panels - The ducts should have removable access pan-   els on both upstream and downstream sides of the furnace. These   openings must be accessible when the furnace is in service and   should be a minimum of 6" x 10" in size so smoke or reflected light   may be observed inside the casing to indicate the presence of leaks   in the heat exchanger. The covers for the openings must be attached   in such a manner as to prevent leakage. See Figure 11.   Inlet Air Ductwork - The location of the inlet air duct connection   depends on the installation. Corner indicators for the opening are pro-   vided on the right side, the left side, and the rear of the heater. (See   Dimensions in Figure 1, page 3.) Determine where the inlet air opening(s)   should be and cut out using tin snips or aviation shears. CAUTION:   Form 405, Page 12   Download from Www.Somanuals.com. All Manuals Search And Download.   From Gas Supply   Immediately upstream of the gas   supply connection, install a manual   shutoff valve with a 1/8 NPT   plugged tap accessible for test   gauge connection.   9. Gas Piping and Pressures   WARNING: This appliance is equipped for a   maximum gas supply pressure of 1/2 pound, 8   ounces, or 14 inches water column. Supply   pressure higher than 1/2 pound requires   installation of an additional lockup-type service   regulator external to the unit.   To Controls   From   Gas   Supply   Manual   Gas Valve   Ground Joint Union   NOTE:   PRESSURETESTINGSUPPLYPIPING   Test Pressures Above 1/2 PSI: Disconnect the heater and manual   valve from the gas supply line which is to be tested. Cap or plug the   supply line.   Test Pressures Below 1/2 PSI: Before testing, close the manual   valve on the heater.   Connections   shown are by   the installer.   6 Drip Leg   Figure 13 -   Supply Piping   Connection   WARNING: All components of a gas supply   system must be leak tested prior to placing   equipment in service. NEVER TEST FOR   LEAKS WITH AN OPEN FLAME. Failure to   comply could result in personal injury, property   damage or death.   All piping must be in accordance with requirements outlined in the   National Fuel Gas Code ANSI Z223.1a (latest edition) or CAN/CGA-   B149.1 and B149.2 (See Paragraph 1). Gas supply piping installation   should conform with good practice and with local codes.   Unit heaters are orificed for operation with natural gas having a heating   value of 1000 (± 50) BTUH per cubic ft or propane gas with a heating   value of 2550 BTUH per cubic ft. If the gas at the installation site does   not meet these specifications, consult the factory for proper orificing.   Pipe joint compounds (pipe dope) shall be resistant to the action   of liquefied petroleum gas or any other chemical constituents of   the gas being supplied.   Install a ground joint union and manual shutoff valve upstream of the   unit control system as shown in Figure 13. The 1/8" plugged tapping in   the shutoff valve provides connection for a supply line pressure test   gauge. The National Fuel Gas Code requires the installation of a trap   with a minimum 3" drip leg. Local codes may require a minimum drip   leg longer than 3" (typically 6"). Bleed gas lines of trapped air.   Gas connection is either 1/2" or 3/4" depending on size and type of gas.   Manifold or Orifice Pressure Settings   Measuring manifold gas pressure cannot be done until the heater is in   operation. It is included in the steps of the "Check-Test-Start" proce-   dure in Paragraph 22. The following warnings and instructions apply.   WARNING: Manifold gas pressure must never   exceed 3.5" w.c. for natural gas or 10" w.c. for   propane gas.   For Natural Gas: Manifold gas pressure is regulated by the combina-   tion valve to 3.5" w.c. Inlet pressure to the valve must be a minimum of   5" w.c. or as noted on the rating plate and a maximum of 14" w.c.   Size   Gas   Gas Connection   150-200   250-400   150-400   Natural   Natural   Propane   1/2"   3/4"   1/2"   For Propane Gas: Manifold gas pressure is regulated by the combina-   tion valve to 10" w.c. Inlet pressure to the valve must be a minimum of   11" w.c. and a maximum of 14" w.c.   Leak-test all connections by brushing on a leak-detecting solution.   Before attempting to measure or adjust manifold gas pressure, the inlet   Sizing a Gas Supply Line   - Cubic Feet per Hour based on 0.3" w.c. Pressure Drop   Capacity of Piping   Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)   Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)   Length   of   Diameter of Pipe   1/2"   3/4"   1"   1-1/4"   1-1/2"   2"   Pipe Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane   20’   30’   40’   50’   60’   70’   80’   90’   100’   125’   150’   175’   200’   92   73   63   56   50   46   43   40   38   34   31   28   26   56   45   38   34   31   28   26   24   23   21   19   17   16   190   152   130   115   105   96   90   84   79   72   116   93   79   70   64   59   55   51   48   44   39   36   34   350   285   245   215   195   180   170   160   150   130   120   110   100   214   174   149   131   119   110   104   98   92   79   73   67   730   590   500   440   400   370   350   320   305   275   250   225   210   445   360   305   268   244   226   214   195   186   168   153   137   128   1100   890   760   670   610   560   530   490   460   410   380   350   320   671   543   464   409   372   342   323   299   281   250   232   214   195   2100   1650   1450   1270   1105   1050   990   930   870   780   710   1281   1007   885   775   674   641   604   567   531   476   433   397   372   64   59   55   650   610   61   Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.   Refer to National Fuel Gas Code for additional information on line sizing.   Mfg No. 164771, Page 13   Download from Www.Somanuals.com. All Manuals Search And Download.   Figure 14 - Burner Condensate Drain Connection   9. Gas Piping and   Pressures (cont'd)   Manifold Pressure Settings (cont'd)   (supply) pressure must be within the specified range for the   gas being used both when the heater is in operation and on   standby. Incorrect inlet pressure could cause excessive mani-   fold gas pressure immediately or at some future time.   ! Hex Locknut (silver)   1 Instructions to Check Manifold   Pressure (when unit is operating):   1) With the manual valve positioned to prevent flow to the   main burners, connect a manometer to the 1/8" pipe outlet   pressure tap in the valve. NOTE: A manometer (fluid-filled   gauge) is recommended rather than a spring type gauge due   to the difficulty of maintaining calibration of a spring type   gauge.   —Burner Bottom Pan—   " Sealing Washer   # Brass Nut   2 3 4 $ 90° Nylon Fitting   2) Open the valve and operate the heater. Measure the gas   pressure to the manifold. Normally adjustments should not   be necessary to the factory preset regulator.   1) Assemble the brass nut, the sealing washer, and the 90° fitting.   2) Position the threaded fitting up through the hole so that the hose barb is   toward the bushing in the side of the cabinet. Attach using the silver-colored   locknut.   If adjustment is necessary, set pressure to correct settings   by turning the regulator screw IN (clockwise) to increase   pressure. Turn regulator screw OUT (counterclockwise) to   decrease pressure.   3) Under the burner, push the tubing onto the hose barb, being sure that it is   secure. Maintaining a downward slope, extend the hose out through the   cabinet side.   4) Just after exiting the cabinet, create a trap in the line by making a loop in   the hose. Secure the loop with the wire ties.   5) Continue downward with the tubing, connecting it into the coil drain pipe.   10. Burner Condensate   Drain   11. Electrical Supply and Connections   All electrical wiring and connections, including electrical grounding, MUST be   made in accordance with the National Electric Code ANSI/NFPA No. 70 (latest   edition) or, in Canada, the Canadian Electrical Code, Part I-C.S.A. Standard C22.1.   In addition, the installer should be aware of and comply with any local ordinances   or gas company requirements.   If an optional cooling coil is installed on a Model CAUA   heater (either now or at a later time), a burner condensate   drain line must be installed.   The following parts to install the drain line are packaged and   shipped with all Model CAUA heaters.   Check the rating plate on the heater for the supply voltage and current require-   ments. A separate line voltage supply with fused disconnect switch should be run   directly from the main electrical panel to the heater. All external wiring must be   within approved conduit and have a minimum temperature rise rating of 60°C.   Conduit from the disconnect switch must be run so as not to interfere with the   service panels of the heater.   The electrical supply and control wiring enter at the top of the heater (See Figure   1, page 3) and connect to the terminal strip behind the gas valve (See Figure 15).   Consult the wiring diagram supplied with your heater. Typical wiring diagrams are   on pages 17 and 18.   Qty   1 1 P/N   165955   165952   Description   6-ft length of 3/8" I.D. Tubing   90° Nylon Fitting, 1/4" NPT x 3/8"   tubing   1 1 1 2 1 110628   171527   165953   20913   1/4" NPT Brass Nut   1/4" Locknut, Hex, T& B 139   Sealing Washer   Nylon Wire Ties, T&B #TY-24M   Snap Bushing, Heyco SB 625-8   87556   Instructions for Installing the Burner   Condensate Drain (Figure 14)   1. Remove the burner compartment door.   CAUTION: If any of the original wire as supplied with the   appliance must be replaced, it must be replaced with wiring   material having a temperature rating of at least 105°C,   except for sensor lead wires which must be 150°C. See   Hazard Levels, page 2.   2. The burner box cover is in two sections. On the left side   of the burner box cover, disconnect the flame sensor wire   and the flame rollout switch wires. Disconnect the sili-   cone tubing from the static tap. Remove the left section   of the burner box cover.   12. Thermostat and Connections   3. Determine which side of the cabinet will be most conve-   nient for the drain line. Remove the hole plug on that side   and insert the snap bushing from the package.   A thermostat is not standard equipment but is an installation requirement. Use   either an optional thermostat available with the heater or a field-supplied 24-volt   thermostat. Install according to the thermostat manufacturer's instructions. Con-   trol wiring enters on the right side of the heater and connects to the terminal strip   in the control compartment; see Figure 15.   4. Locate the hole in the bottom center of the burner pan   and remove the plug. Follow the instructions in Figure 14   to install the drain. Complete all steps as listed in the   illustration.   Make sure that the heat anticipator setting on the thermostat is in accordance with   the amperage value noted on the wiring diagram of your heater.   When installation of the burner condensate drain is com-   plete, re-assemble the heater.   WARNING: If you turn off the power supply, turn off the   gas. See Hazard Levels, page 2.   Form 405, Page 14   Download from Www.Somanuals.com. All Manuals Search And Download.   Figure 15 - Control   Locations   Venter   Limit Control   Supply Wiring Terminal Block   (behind the gas valve)   (Line voltage enters the control   compartment through a hole in   the top of the heater cabinet.)   Pressure Switch   Transformer   Gas   Valve   Thermostat   Terminal Strip   (Thermostat wires enter   the control compartment   through a hole in the right   side of the heater cabinet.)   Terminal Strip   Contactors   Ignition Control   Module   14. Blower Motor and Drive   13. Combustion Air Proving   Switch   Model CAUA units are equipped with either direct drive motor(s) and   blower(s) or adjustable belt-drive blower(s) and motor.   The combustion air proving switch is a pressure sensitive switch   that monitors air pressure to ensure that proper combustion air is   available.   Direct Drive   All direct drive blower motors are 1 horsepower. Sizes 150-200 have a   single motor. Size 150 has a 12-9 blower; Size 200 has a 12-12 blower.   Sizes 250-400 have dual motors with dual 12-9 blowers.   The switch is single pole/double throw with the normally open   contacts closing when the proper airflow is sensed in the system.   Belt Drive   On start-up when the heater is cold, the sensing pressure is at the   most negative level, and as the heater and flue system warm up, the   sensing pressure becomes less negative. After the system has reached   equilibrium (about 20 minutes), the sensing pressure levels off.   The motor horsepower on a belt drive unit is whatever was specified on   the order ranging in size from 1/4 HP to 5 HP. Check the heater rating plate   and the motor rating plate.   As part of the start-up procedure, check belt tension. Proper belt tension   is important to the long life of the belt and motor. A loose belt will cause   wear and slippage. Too much tension will cause excessive motor and blower   bearing wear. Adjust the belt tension by turning the adjusting screw on the   motor base until the belt can be depressed 3/4". (See Figure 16.) After   correct tension is achieved, re-tighten the locknut on the adjustment screw.   Be sure that the belt is aligned in the pulleys.   If a restriction or excessive flue length or turns cause the sensing   pressure to be outside the switch setpoint, the pressure switch will   function to shut off the main burners. The main burners will remain   off until the system has cooled and/or the flue system resistance is   reduced. The table below lists the approximate water column nega-   tive pressure readings and switch setpoints for sea level operating   conditions.   Model Start-Up Equilibrium Set Point Set Point   Size   150   200   250   300   350   400   Cold   1.45   1.50   1.55   1.60   1.30   1.20   “OFF”   .75   .75   .75   .75   “ON”   .90   .90   .90   .90   1.05   1.05   1.10   1.15   1.05   1.00   Figure 16 -   Check Belt   Tension   3/4 (19mm)   .75   .75   .90   .90   Most blower motors are equipped with thermal overload protection of the   automatic, reset type. If the motor is not equipped with thermal overload   protection, the unit will be equipped with a starter. The adjustable setting   on the starter will be factory set to match the amp draw of the motor and   sealed. No change should be made to the starter setting unless the original   motor is replaced. Starters are equipped with a manual reset. If an overload   condition is experienced, the condition must be corrected and the starter   must be manually reset.   After the installation is complete including all ductwork, the amp draw of   the motor should be checked with an amp meter to verify that the motor   amp rating on the motor nameplate is not being exceeded. Amps may be   adjusted downward by reducing the blower speed or by increasing the duct   system static pressure. The temperature rise must be within the range   specified on the unit rating plate.   DANGER: Safe operation of this unit requires   proper venting flow. NEVER bypass the com-   bustion air proving switch or attempt to operate   the unit without the venter running and the   proper flow in the vent system. Hazardous   conditions could result. See Hazard Levels, page   2.   Mfg No. 164771, Page 15   Download from Www.Somanuals.com. All Manuals Search And Download.   motor specifications. At final adjustment, amperes should not ex-   ceed motor nameplate amp rating. The installation must be ad-   justed to obtain a temperature rise within the range specified on   the heater rating plate.   14. Blower Motor and Drive   (cont'd)   Adjusting Blower Speed   Full Load Amps - Blower Motors (Open)   The blower speed may be adjusted to achieve the desired outlet tem-   perature, as long as the adjustment is within the temperature rise and   the static pressure limits shown on the heater rating plate. Direct drive   motors are factory set at medium speed for heating and high speed for   cooling (if ordered). Belt drive motors are factory set between maxi-   mum and minimum blower speeds.   HP   1/4 1/3 1/2 3/4   Direct-Drive Motors   -- --   6.3   Optional Belt Drive Motors   1 1-1/2   2 3 5 230V 1PH --   --   --   --   --   --   208V 1 PH 2.1 3.2 5.1 6.3 7.5 8.3 10.0   230V 1PH 2.3 2.8 4.4 5.5 6.5 7.5 10.2   --   --   --   --   If the duct resistance is low, the blower may deliver too high an air   volume. If the resistance is very low, the blower may deliver excess air   to overload the motor, causing the overload protector to activate. Re-   ducing the blower speed will correct these conditions. If ductwork is   added to an installation, it may be necessary to increase the blower   speed.   208V 3 PH 1.1 1.4 3.0 2.9 3.7 5.6 7.0 9.0 13.4   230V 3PH 1.4 1.6 2.5 2.6 3.2 5.0 6.6 8.6 13.2   460V 3PH 0.75 0.8 1.0 1.3 1.6 2.7 3.5 4.3 6.6   575V 3PH --   --   --   --   1.1 1.6 2.1 3.6 5.4   Direct drive motors have multi-speed taps for speed adjustment. If   your installation requires an adjustment of the blower speed, the motor   may be re-wired to an alternate tap by following these instructions.   1. Turn off the gas and electric power.   CAUTION: An external duct system static   pressure not within the limits shown on the rating   plate, or improper motor pulley or belt adjustment,   may overload the motor or cause the limit control   to activate. See Hazard Levels, page 2.   2. Remove the blower door panel.   3. Consult the wiring diagram on the heater and follow the chart below   to choose the wiring for the desired adjustment. Units are wired at   high speed for cooling (if ordered) and medium speed for heating.   15. Gas Valve   Model Sizes   Speed   Use these two motor wires:   The main operating gas valve is powered by the 24-volt control circuit   through the thermostat and safety controls. The main control valve is   of the diaphragm type providing regulated gas flow preset at the fac-   tory.   150, 200, 250, 350   High   White and Black   Medium   Low   White and Blue   White and Red   300 and 400   High   White and Black   Medium White and Blue   WARNING: The operating valve is the prime   safety shutoff. All gas supply lines must be free of   dirt or scale before connecting the unit to ensure   positive closure. See Hazard Levels, page 2.   4. Cut the crimped cap for the end of the wire that you intend to use   and strip the insulation.   5. Disconnect the factory-wired connection and re-wire, using the newly   stripped wire.   6. Put a wire nut on the end of the blower motor wire that was discon-   nected.   16. Ignition System   7. Replace the heater door panel. Turn on the gas and electric. Check   for proper operation.   This heater is equipped with a direct spark integrated control system.   The system monitors the safety devices and controls the operation of   the blower and venter motors and the gas valve.   Belt drives have an adjustable pulley which permits adjustment of the   blower speed. Follow these instructions to adjust blower speed.   1. Turn off the gas and the electric power.   Ignition System Operating Sequence   On a call for heat from the thermostat, the system energizes the venter   motor and goes through a 10-second prepurge. The system verifies that   the pressure switch has changed states closing the normally open con-   tactor and that the high limit is in the closed state.   The gas valve is then energized, and the ignition system provides the   high voltage spark to the electrode to ignite the main burner gas. Burner   flame is electronically sensed by the control (minimum 1.0 microamps)   upon carryover of all burners. (A separate solid metal probe is used as   the flame sensing function. A low voltage electrical signal is imposed on   the metal probe which is electrically isolated from ground. When the   flame impinges on the flame sensing probe, the flame acts as a conduc-   tion path to ground. The flame rectifies and completes the DC circuit,   and the ignition system acknowledges the flame.)   2. Loosen belt tension and remove the belt.   3. Loosen the set screw on the side of the pulley away from the motor.   4. To increase the blower speed, turn the adjustable half of the pul-   ley inward. To decrease the blower speed, turn the adjustable half   of the pulley outward. One turn of the pulley will change the speed   8-10%.   5. Tighten the set screw on the flat portion of the pulley shaft.   6. Replace the belt and adjust the belt tension. Adjust tension by   turning the adjusting screw on the motor base until the belt can be   depressed 3/4". (See Figure 16.) Re-tighten the lock nut on the   adjusting screw. Be sure that the belts are aligned in the pulley   grooves properly and are not angled from pulley to pulley.   7. Turn on the gas and electric. Light the heater following the instruc-   tions on the lighting instruction plate.   The blower motor is energized by the system after 30 seconds of flame   sensing.   8. Check the motor amps with an amp meter. The maximum motor   amp rating on the motor nameplate must not be exceeded.   When service is complete, check for proper operation.   After the thermostat has been satisfied, the system de-energizes the gas   valve, the venter motor goes through a 45-second post-purge, and the   blower motor remains energized for an additional 135 seconds.   NOTE: This is a three trial system. The unit will lockout for one hour   before initiating another trial for ignition. If the unit fails after one   recycle interval, the unit will go into hard lockout and must be reset by   interrupting power or resetting the thermostat. To initiate another trial   for ignition before the one hour interval, either reset the thermostat or   interrupt power to the unit for 30 seconds.   Motor Amps   Use an amp meter to check motor amps. The chart lists full load amps   for various HP's and voltages. Amps may be adjusted downward by   reducing blower RPM or increasing duct system static pressure.   The chart below can be used for sizing line wiring but should not be   interpreted as the exact motor amps. See the motor rating plate for exact   Form 405, Page 16   Download from Www.Somanuals.com. All Manuals Search And Download.   TYPICAL WIRING DIAGRAMS   Figure 17 - Typical Wiring Diagram for Model CAUA with Direct-Drive Blower Motor(s)   GRD   OPTIONAL DISCONNECT SWITCH   (SEE NOTE)   G BL   BL   INHERENTLY   PROTECTED   BLOWER   MOTOR   HEAT SPEED   CONTACTS   INHERENTLY   PROTECTED   BLOWER   MOTOR   BK   BL   BL   W L1   (SEE NOTE #7)   BK   R R W W W COOL SPEED CONTACTS   BK   BK   BK   BK   BK   W W W MOTOR WIRE COLORS   W L2   W WHITE - NEUTRAL   BLACK - HIGH SPEED   BLUE - MEDIUM SPEED   RED - LOW SPEED   GRD   (DO NOT USE WITH 208V)   G BK   W VENTER MOTOR   (SEE NOTE #8)   DSI CONTROL   BK OR BR   HEAT SPEED   BK OR BL   BK   BL   BL   BK   LINE   CMB   BLWR AUX   L1   L2   L2   VAC HOT   CONTACTOR COIL   W BL   BL   BK   24VAC   HOT   ACB HEAT   ACB COOL   GROUND   1 1 WIRING CODE   BLACK - BK   BROWN - BR   RED - R   ORANGE - O   YELLOW - Y   GREEN - G   BLUE - BL   FLAME   ROLLOUT SWITCH   COOL SPEED   CONTACTOR COIL   BL   BK   W ROLLOUT   IN   CUSTOMER'S   COOL RELAY COIL   BR   BR   C 7 7 PURPLE - PR   WHITE - W   IGNITOR   BR   BURNER GROUND   HV LEAD   THERMOSTAT   TERMINAL STRIP   BL   R R FLAME SENSING   PROBE   HIGH   LIMIT   R R FLAME SENSE   PSW   PRESSURE SWITCH   NC   Y Y 2 C BR   C C NO   Y R R HI LIMIT   IN   Y R Y 2 Y1   BL   M W HI LIMIT   OUT   BK   Y R Y2   G TR OR   PV-MV   BK   BR   W G 7 W1   P R BL   BL   LED   W2   VALVE   TH OR   MV   FACTORY WIRING   Y G FIELD WIRING   CHASSIS GRND.   OPTIONAL FACTORY WIRING   TH-TR   OR PV   DOOR SWITCH   BL   BR   BR   BL   BL   24V   1 3 7 MAIN TERMINAL BLOCK   UNIT TERMINAL STRIP   40 VA. CONTROL   TRANSFORMER   BK   Y Y L1   L2   LINE VOLT   R OPERATING SEQUENCE   THERMOSTAT TERMINAL STRIP   1. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION, FAN SWITCH AT "AUTO" POSITION.   2. TURN ON MANUAL GAS VALVE.   3. TURN ON POWER TO UNIT.   4. SET THERMOSTAT SYSTEM SWITCH AT "HEAT" POSITION; FAN SWITCH AT "AUTO" POSITION.   5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.   6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT.   7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE BLOWER MOTOR IS ENERGIZED.   LED CODES   8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION, THE INTEGRATED CONTROL SYSTEM   SLOW FLASH NORMAL OPERATION - NO CALL FOR HEAT   FAST FLASH NORMAL OPERATION - CALL FOR HEAT   2 FLASHES SYSTEM LOCKOUT - FAILED TO DETECT OR SUSTAIN FLAME   3 FLASHES PRESSURE SWITCH OPEN OR CLOSED   4 FLASHES HIGH LIMIT OPEN   5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED   STEADY ON INTERNAL FAILURE (MICRO-CONTROLLER FAILURE: SELF CHECK)   CLOSES THE MAIN VALVE AND MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT   (SEE LIGHTING INSTRUCTIONS).   9. SET THERMOSTAT SYSTEM SWITCH AT "COOL" POSITION, FAN SWITCH AT "AUTO" POSITION.   (A) ON A CALL FOR COOLING, BLOWER MOTOR IS ENERGIZED AT HIGH SPEED AND COOLING   CIRCUIT IS ENERGIZED.   10. WHEN BLOWER DOOR IS OPENED, THE UNIT IS SHUTDOWN.   11. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION, FAN SWITCH AT "AUTO" POSITION, FOR SHUTDOWN..   NOTES   1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT   2. DOTTED WIRING AND COOL RELAY COIL INSTALLED BY OTHERS.   3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE   APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL   HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR   LEAD WIRE WHICH MUST BE 150° C.   FIELD CONTROL WIRING   TOTAL WIRE   LENGTH   DISTANCE FROM   UNIT TO CONTROL   MIN. RECOMMENDED   WIRE GUAGE   #18 GA. WIRE   #16 GA. WIRE   #14 GA. WIRE   150'   250'   350'   75'   125'   175'   4. USE 18 GA. WIRE FOR CONTROL WIRING ON THE UNIT.   5. USE 14 GA. WIRE FOR LINE AND MOTOR WIRING ON UNIT.   6. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT   VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.   7. SECOND BLOWER MOTOR ON 250-400 UNITS ONLY.   8. VENTER MOTOR ON 350-400 UNITS HAS BROWN AND BLUE WIRES.   9. ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.   FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).   FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW)   . 10. WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH   USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO   TIMES THE MAXIMUM TOTAL INPUT AMPS.   CAUA SERIES 150 - 400 DWG. # B-164607 REV #1   AG1 - AK2 OR AK3 - CL10 - DIRECT DRIVE   BABS   Mfg No. 164771, Page 17   Download from Www.Somanuals.com. All Manuals Search And Download.   TYPICAL WIRING DIAGRAMS (cont'd)   Figure 18 - Typical Wiring Diagram for Models CAUA with Belt-Drive Blower Motor   OPTIONAL DISCONNECT SWITCH   GRD   G (SEE NOTE)   INHERENTLY   PROTECTED   BLOWER   MOTOR   MOTOR   CONTACTOR   BK   BK   L1   L2   MAIN TERMINAL BLOCK   UNIT TERMINAL STRIP   W W THERMOSTAT TERMINAL STRIP   GRD   G BK   W VENTER MOTOR   (SEE NOTE #8)   DSI CONTROL   BK OR BR   WIRING CODE   BLACK - BK   BROWN - BR   RED - R   ORANGE - O   YELLOW - Y   GREEN - G   BLUE - BL   BK OR BL   MOTOR   BK   BL   BL   BK   LINE   CMB   L1   L2   L2   L2   VAC HOT   BLWR AUX   CONTACTOR COIL   BL   BK   W 24VAC   HOT   ACB HEAT   1 FLAME   ROLLOUT SWITCH   BL   BL   BK   ROLLOUT   IN   ACB COOL   GROUND   1 PURPLE - PR   WHITE - W   CUSTOMER'S   COOL RELAY COIL   BR   BR   7 C IGNITOR   BR   BURNER GROUND   HV LEAD   7 THERMOSTAT   TERMINAL STRIP   BL   R R FLAME SENSING   PROBE   FLAME SENSE   FACTORY WIRING   FIELD WIRING   C OPTIONAL FACTORY   WIRING   PRESSURE SWITCH   NC   HIGH   LIMIT   R R Y R R Y Y PSW   R Y 2 Y1   C NO   W HI LIMIT   IN   BK   Y Y Y2   2 G BK   HI LIMIT   OUT   R W G W1   R TR OR   PV-MV   BL   LED   BR   W2   7 BR   C Y BL   G VALVE   BL   TH OR   MV   M CHASSIS GRND.   TH-TR   OR PV   DOOR SWITCH   BL   P BR   BR   BL   BL   24V   1 3 7 40 VA. CONTROL   TRANSFORMER   BK   Y Y L1   L2   LINE VOLT   R OPERATING SEQUENCE   LED CODES   1. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION; FAN SWITCH AT "AUTO" POSITION.   2. TURN ON MANUAL GAS VALVE.   3. TURN ON POWER TO UNIT.   4. SET THERMOSTAT SYSTEM SWITCH AT "HEAT" POSITION; FAN SWITCH AT "AUTO" POSITION.   5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.   6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT.   7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE BLOWER   MOTOR IS ENERGIZED.   SLOW FLASH NORMAL OPERATION - NO CALL FOR HEAT   FAST FLASH NORMAL OPERATION - CALL FOR HEAT   2 FLASHES SYSTEM LOCKOUT - FAILED TO DETECT OR SUSTAIN FLAME   3 FLASHES PRESSURE SWITCH OPEN OR CLOSED   4 FLASHES HIGH LIMIT OPEN   5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED   STEADY ON INTERNAL FAILURE (MICRO-CONTROLLER FAILURE: SELF CHECK)   8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,   THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND   MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT   (SEE LIGHTING INSTRUCTIONS).   9. SET THERMOSTAT SYSTEM SWITCH AT "COOL" POSITION, FAN SWITCH AT "AUTO" POSITION.   (A) ON A CALL FOR COOLING, BLOWER MOTOR IS ENERGIZED AND COOLING   CIRCUIT IS ENERGIZED.   FIELD CONTROL WIRING   10. WHEN BLOWER DOOR IS OPENED, THE UNIT IS SHUTDOWN.   TOTAL WIRE   LENGTH   DISTANCE FROM   UNIT TO CONTROL   MIN. RECOMMENDED   WIRE GUAGE   #18 GA. WIRE   #16 GA. WIRE   #14 GA. WIRE   11. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION, FAN SWITCH AT "AUTO" POSITION, FOR SHUTDOWN.   NOTES   150'   250'   350'   75'   125'   175'   1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT   2. DOTTED WIRING AND COOL RELAY COIL INSTALLED BY OTHERS.   3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE   APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL   HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR   LEAD WIRE WHICH MUST BE 150° C.   4. USE 18 GA. WIRE FOR CONTROL WIRING ON THE UNIT.   5. USE 14 GA. WIRE FOR LINE AND MOTOR WIRING ON UNIT.   6. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT   VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.   7. ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.   FOR 230V. UNITS, USE BLACK AND YELLOW LEADS (CAP RED).   FOR 208V. UNITS, USE BLACK AND RED LEADS (CAP YELLOW).   8. VENTER MOTOR ON 350-400 UNITS HAS BROWN AND BLUE WIRES.   9. WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH   USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25   TIMES THE MAXIMUM TOTAL INPUT AMPS.   Form 405, Page 18   Download from Www.Somanuals.com. All Manuals Search And Download.   OPTIONAL ACCESSORIES   17. Optional Cased Cooling Coil, Model ACUA, ACUB, or ACUC   This cased cooling coil is designed for use with the Model CAUA upflow heater. It is shipped separately for field installation over the discharge   opening of the heater. Before installing, verify that the coil cabinet is the same size as the heater cabinet.   Follow the installation instructions shipped with the cooling coil (Installation Form RZ 405-CC), the wiring diagram, and the instructions provided   by the compressor manufacturer.   Model   Size   ACUA   060 072 090   ACUB   090 120 150   90 120 150   ACUC   120 150 180   120 150 180   Heater/Coil Cross-Reference   Table by Cabinet Size   Heater Model CAUA   Nominal Cooling Capacity (MBH) 60   72   90   Refrigerant Type   Thermal Expansion Valves*   Approximate Weight (lbs)   No. of Intertwining Circuits   Face Area (sq ft)   Rows-Fins/Inch   Airflow (cfm) Low   Nominal   R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22   1 83   8 1 1 1 2 2 2 2 2 150 200   250 300 350   400   86 105   12   110 122 140   12 12 18   176 180 188   12 16 18   ACUA   060   ACUB   090   ACUC   120   8 7.79 7.79 9.38 14.04 11.67 13.70 17.13 15.38 17.13   2-10 2-12 3-10 2-12 3-10 3-12 2-12 3-10 3-10   072   090   120   150   150   180   1800   2400   3000   4000   4000   5000   High   3000**   5000**   6000**   * - TXV's are factory supplied. Models with two TXV's have intertwined circuiting.   ** - Airflow in excess of maximum values shown may result in blow-off of condensation.   Figure 19 - A Model ACU cooling coil installed on a Model CAUA heater and the line connection sizes   Model Size   Connections   Suction Line   ACUA 060/072   Connection(s)   (1) 7/8" Suction Line   (1) 3/8" Liquid Line   (1) 1/2" Liquid Line   (2) 7/8" Suction Lines   (2) 3/8" Liquid Lines   (2) 7/8" Suction Lines   (2) 3/8" Liquid Lines   (2) 1/2" Liquid Lines   (2) 7/8" Suction Lines   (2) 3/8" Liquid Lines   (2) 1/2" Liquid Lines   ModelACU   Cased   Cooling Coil   060   Liquid Line   Connection(s)   3/4" Drain Line   Connection   072   090   090   ACUB 090/120/150   090/120   Hole for Burner   Condensate Drain   Tube (use this hole   or the one on the   opposite side) - see   Paragraph 10, page   14   ModelCAUA   Heater   150   ACUC 120/150/180   120   150/180   Drain line connection is 3/4" for all sizes.   Burner Condensate Drain   When a system includes a cooling coil, a burner condensate drain must be installed. The parts required for the drain are shipped with the heater.   Instructions for installing the drain are in Paragraph 10, page 14.   Electrical Connections   Figure 20 - Typical   Heater Terminal Strip   Thermostat   Connections   (Read thermostat   manufacturers   installation   Condensing Unit   Connections   (Read   Low Voltage Wiring   (field-supplied)   24V Supply *   Common   R C manufacturers   installation   Common   instructions   instructions   before wiring.)   before wiring.)   1st Stage Cooling   2nd Stage Cooling   1st Stage Heating   Y Y 1 1st stage cooling   24V control relay   2 2nd stage cooling   24V control relay   for Sizes 090, 120,   150, and 180   W W G 1 Optional 2-Stage Heating   Fan   2 * A separate 24V control transformer may   Legend (field-supplied 24V wiring)   be required for the condensing equipment controls   Install a jumper wire between RH and RC terminals   on the thermostat for single transformer operation.   Consult the thermostat manufacturers instructions.   Thermostat wiring - 24V   Field control wiring - 24V   Mfg No. 164771, Page 19   Download from Www.Somanuals.com. All Manuals Search And Download.   OPTIONAL ACCESSORIES (cont'd)   18. Optional Filter Cabinet (return air only)   A filter cabinet designed for 2" pleated disposable or permanent metal filters is shipped separately for field assembly and installation. Depending on   the option selected, filters are either shipped with the cabinet or are field-supplied.   To adapt to a variety of applications, the heater cabinet is designed so that the filter cabinet can attach on either the right side, the left side, or the rear   of the heater. The larger filter cabinets (left two tables below) are uniquely designed so that the same cabinet can be field-assembled and installed with   either a horizontal or vertical air inlet. The smaller filter cabinet in the table on the right is limited to Sizes 150 and 200 and is available with a   horizontal inlet only. All cabinets have door panels for easy filter removal for changing or cleaning.   All of the filter cabinets have a duct flange for attaching the inlet air duct. For inlet duct dimensions, see Paragraph 8.   Follow the step-by-step instructions included with the filter cabinet package to assemble and attach it to the heater.   Figure 21 - Filter Cabinets with Filter Arrangements and Filter Sizes   Option CW8 with 2" Pleated Filters   Option CW4 with 2" Pleated Filters   Option CW5 with 2" Permanent Filters   Option CW6 for Field-Supplied Filters   Option CW7 with 2" Pleated Filters   Option CW12 with 2" Permanent Filters   Option CW11 for Field-Supplied Filters   Option CW9 with 2" Permanent   Filters   Option CW10 for Field-Supplied   Filters   • • • Attaches on Either Side of the Heater   Vertical (Top) or Horizontal Inlet Opening   "V" Filter Rack Arrangement   • • Attaches on the Rear of the Heater   Vertical (Top) or Horizontal Inlet   Opening   • Attaches on either Side or the Rear   of a Size 150 or 200 Heater   Horizontal Inlet Opening   • "V" Filter Rack Arrangement   • • "V" Filter Rack Arrangement   Figure 21B -   Assembled   with   Horizontal   Air Inlet   Opening   Figure 21A -   Assembled with   Vertical Air   Figure 21C -   Small Filter   Cabinet for Sizes   150 and 200 only   -- Horizontal Air   Inlet Only   Inlet Opening   Sizes of Permanent or Pleated 2"   Filters for Options CW4, CW5, or CW6   Sizes of Permanent or Pleated 2"   Filters for Options CW7, CW12, or   CW11   Filters for Options CW8, CW9, CW10   Size   150   CFM   1800   2400   3000   2400   3000   3000   *4000   FPM   281   375   469   375   469   469   625   Filters   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   Size   CFM   1800   2400   3000   2400   3000   3000   4000   5000   3000   4000   5000   4300   5000   *6000   4300   5000   *6000   FPM   281   375   469   375   469   313   417   521   313   417   521   448   521   625   448   521   625   Filters   SizeCFM FPM   2" Filters   150   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (4) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   (6) 16 x 16   Pleated Permanent   150 1800 375 (2) 12 x 32 (4) 12 x 16   200   250   2400 500 (2) 12 x 32 (4) 12 x 16   200   250   *3000 625   200 2400 500 (2) 12 x 32 (4) 12 x 16   *3000 625 -- (4) 12 x 16   --   (4) 12 x 16   **5000 781   300   3000   *4000   **5000 781   469   625   300   350   400   350   400   4300   5000   *6000   4300   5000   *6000   448   521   625   448   521   625   NOTES:   * Requires 2" permanent filters.   ** If using side inlets, two cabinets must be   installed, one on each side.   19. Mixing Cabinet (Outside and Return Air)   The optional mixing box for the Reznor® Model CAUA heater is designed   to provide the system with a supply air mixture of return air and outside   air. Any percentage of outside air can be supplied to the unit as long as the   air temperature entering the blower is 35°F or above. The mixing box is   available in an assortment of configurations with a selection of actuators   and controls. All mixing boxes are completely assembled at the factory for   field attachment to the rear of a Model CAUA heater.   instructions for routing the damper motor wires, and connect the   wires according to the wiring diagram. If there are both return air and   outside air dampers, follow the directions to adjust the damper   linkage.   All mixing box inlet air openings have duct flanges for attachment of   ductwork. Ductwork must be attached to the outside air opening.   Removable door panels provide for filter access from either end of   the cabinet. If the box was ordered with optional filters, it is shipped   with the filters installed.   Follow the instructions packed with the mixing box to cut out the opening   and attach the mixing box. If the mixing box has dampers, follow the   Form 405, Page 20   Download from Www.Somanuals.com. All Manuals Search And Download.   Option Configuration   Top Outside Air Opening with Dampers/   GA1   GA2   GA3   GA4   GA5   GA6   GA7   GA8   GA9   Rear or Bottom Return Air Opening without Dampers   Rear Outside Air Opening with Dampers/   Top or Bottom Return Air Opening without Dampers   Figure 22 -   Optional   Outside Air   and Return   Air Mixing   Box   Bottom Outside Air Opening with Dampers/   Top or Rear Return Air Opening without Dampers   Bottom Outside Air Opening with Dampers/   Rear Return Air Opening with Dampers   Bottom Outside Air Opening with Dampers/   Top Return Air Opening with Dampers   Rear Outside Air Opening with Dampers/   Top Return Air Opening with Dampers   Configurations/Accessories   Rear Outside Air Opening with Dampers/   Bottom Return Air Opening with Dampers   Before installing, check to be sure that the configuration of the mixing   box matches the order and that any accessories ordered are part of the   cabinet. Factory-installed optional accessories could include a damper   motor, potentiometer, return air controller, mixed air controller, and/or   filters. NOTE: If the potentiometer is to be field-installed, it is shipped   in a separate carton.   Top Outside Air Opening with Dampers/   Rear Return Air Opening with Dampers   Top Outside Air Opening with Dampers/   Bottom Return Air Opening with Dampers   Figure 23 - Dimensions of Optional   Mixing Box - inches (mm)   150-200   38 (965)   250-400   50 (1270)   A B C 22-3/4 (578)   7-5/8 (194)   36-1/2 (927)   6-3/4 (171)   Note: Damper frame fits in the inlet opening.   21. Inlet Base (Sizes 350 and 400 only)   20. Discharge Plenum (Sizes 350   The optional mounting base is designed to support a Model CAUA 350   or 400 heater while providing an inlet for return air. The mounting base   is designed to be used with an optional discharge plenum (Paragraph 20)   creating a "packaged stand-alone" heating or heating/cooling upflow   system which can be used in an air turnover application.   However, if the installation requires it, the mounting base may also be   used with discharge ductwork.   and 400 only)   The optional discharge plenum is designed to be used with a screened   mounting base (Paragraph 21) to create a "packaged stand-alone" upflow   system that circulates building air. However, the discharge plenum   may also be used in place of ductwork in applications that do not have   an optional mounting base.   The discharge plenum is available in three types. Option CD60 and   CD61 are for a heater without a cooling coil; Option CD60 is designed   for an open area and Option CD61 includes field-installed blockoff   plates to block off one or two sides. Option CD62 can only be ordered   with a cooling coil and includes blockoff plates to provide higher veloc-   ity required for cooling.   The mounting base has guarded openings on all four sides and is avail-   able with optional 1" flat disposable, 1" permanent aluminum, or 1"   pleated disposable filters.   The base is designed for a fairly open area and must have at least three   of the four sides open.   The base adds 36-1/2" (927mm) to the overall height.   A discharge plenum adds 49-15/16" (1268mm) to the height of the   heater. (If installing Option CD62, this height includes the cooling   coil.)   Mfg No. 164771, Page 21   Download from Www.Somanuals.com. All Manuals Search And Download.   Check/Test/Start-Up   22. Check Installation & Start-Up   Check the installation prior to start-up:   replace any part of the control system and any   gas control which has been under water.   %Check clearances from combustibles. Requirements are shown in   Operating Instructions and Operating Sequence   1. Set thermostat at lowest setting.   Paragraph 4.   %If installed as a separated-combustion unit, check vent/combustion   air system to be sure that it is installed according to the instructions   in Paragraph 7A.   2. Turn off all electric power to the appliance.   3. This appliance is equipped with an ignition device which   automatically lights the burner. Do not try to light the burner   by hand. Open the access door and locate the gas valve.   %Check piping for leaks and proper gas line pressure. Bleed gas lines   of trapped air. See Paragraph 9.   4. Models CAUA 150 and 200 - Locate the gas control (ON/OFF)   knob on the gas valve. Turn the gas control knob clockwise   to "OFF".   %Check the blower compartment to be sure that all shipping sup-   ports have been removed. Close the blower compartment door se-   curely. Heater will not operate if the blower compartment door is   not closed.   Models CAUA 250, 300, 350, and 400 - Locate the gas con-   trol (ON/OFF) knob on the gas valve. Turn knob clockwise to   align the line on the knob with the position indicator. Depress   knob and continue rotation to the "OFF" position.   %Check electrical wiring. Be sure all wire gauges are as recommended.   A service disconnect switch should be used. Verify that fusing or   circuit breakers are adequate for the load use.   Top View of Gas Valve used on   Control Knob on Top of   Start-Up   CAUA 150 and 200   Gas Valve used on CAUA   250 - 400   WARNINGS: For your safety, read before   operating. If you do not follow these instructions   exactly, a fire or explosion may result causing   property damage, personal injury, or loss of life.   • This appliance does not have a pilot. It is   equipped with an ignition device which auto-   matically lights the burner. Do not try to light   the burner by hand.   5. Wait five (5) minutes to clear out any gas. Then smell for gas,   including near the floor. If you smell gas, STOP! and follow   the steps in the WARNINGS printed in the right column or   on the Operating Label on the heater. If you do not smell gas,   proceed to the next step.   • Before operating, smell all around the appliance   area for gas. Be sure to smell next to the floor   because some gas is heavier than air and will   settle on the floor.   6. Models CAUA 150 and 200 - Turn the gas control knob coun-   WHAT TO DO IF YOU SMELL GAS   • Do not try to light any appliance.   terclockwise to "ON".   Models CAUA 250, 300, 350, and 400 - Turn knob counter-   clockwise to align the line on the knob with the position indi-   cator. Allow knob to "pop up", and continue rotation to the   "ON" position.   • Do not touch any electrical switch; do not   use any phone in your building.   • Immediately call your gas supplier from a   neighbor's phone. Follow the gas   supplier's instructions.   7. Close the access door.   8. Turn on the electric power to the heater.   9. Set the thermostat to the desired setting.   • If you cannot reach your gas supplier, call   your fire department.   NOTE: If the appliance does not operate, follow the instructions   "To Turn Off Gas to the Appliance" printed below (and on the   Operating Label on the heater). Call your service technician.   • Use only your hand to turn the gas control ON/   OFF knob on the gas valve. Never use tools. If   the valve ON/OFF knob will not turn by hand,   do not try to repair it. Call a qualified service   technician. Force or attempted repair may re-   sult in a fire or explosion.   10. Thermostat calls for heat, energizing the venter motor.   11. Venter pressure switch closes, allowing the unit to fire.   12. Burner flame is sensed and in 30 seconds, the blower motor   is energized.   13. If the flame is extinguished during the main burner operation,   the integrated control system closes the main valve and must   be reset by interrupting power to the control circuit. (See   lighting instructions on the heater.).   • Do not use this appliance if any part has been   under water. Immediately call a qualified ser-   vice technician to inspect the appliance and to   Form 405, Page 22   Download from Www.Somanuals.com. All Manuals Search And Download.   TO TURN OFF GAS TO THE APPLIANCE   DANGER: The gas burner in this gas-fired   equipment is designed and equipped to provide   safe and economically controlled complete   combustion. However, if the installation does not   permit the burner to receive the proper supply of   combustion air, complete combustion may not   occur. The result is incomplete combustion which   produces carbon monoxide, a poisonous gas that   can cause death. Safe operation of indirect-fired   gas burning equipment requires a properly   operating vent system which vents all flue   products to the outside atmosphere. FAILURE TO   PROVIDE PROPER VENTING WILL RESULT   IN A HEALTH HAZARD WHICH COULD   CAUSE SERIOUS PERSONAL INJURY OR   DEATH.   1) Set thermostat to lowest setting   2) If service is to be performed, turn off all electric power   to the appliance.   3) Open the access door.   4) Turn the gas control knob to "OFF" (follow instruc-   tions in No. 4 above). Do not force control knob.   5) Close the access door.   Check installation after start-up:   %&Vent System Testing Procedure - Power Vent   Units (does not apply to separated-combustion   installation)   1. Seal any unused openings in the venting system.   2. Inspect the venting system for proper size and horizontal   pitch, as required in the National Fuel Gas Code, ANSI   Z223.1 or CAN/CGA B149.1 and B149.2, Installation Code   for Gas Burning Appliances and Equipment, and this   manual. Determine that there is no blockage or restric-   tion, leakage, corrosion and other deficiencies which could   cause an unsafe condition.   If installed as a separated-combustion unit, install   either the horizontal or vertical combustion air/   vent system illustrated in Paragraph 7A using the   concentric adapter supplied. Always comply with   the combustion air requirements in the installation   codes and instructions. Combustion air at the   burner should be regulated only by manufacturer-   provided equipment. NEVER RESTRICT OR   OTHERWISE ALTER THE SUPPLY OF   COMBUSTION AIR TO ANY HEATER.   CHECK THE VENT SYSTEM FOR   SOUNDNESS AND FUNCTION; MAINTAIN IT   IN PROPER OPERATING CONDITION.   3. In so far as practical, close all building doors and win-   dows and all doors between the space where the heater is   and other spaces of the building. Turn on clothes dryers   and exhaust fans, such as range hoods and bathroom   exhausts, so they shall operate at maximum speed. Do not   operate a summer exhaust fan. Close fireplace dampers.   4. Light the heater following the lighting instructions. Ad-   just the thermostat for continued operation. Verify that   combustion products are venting properly. After deter-   mining that the heater vents properly, return doors, win-   dows, exhaust fans, and fireplace dampers to their previ-   ous conditions. If improper venting is observed, the vent-   ing system must be corrected.   %With the unit in operation, measure manifold gas pressure.   Manifold pressure for natural gas should be 3.5" w.c. and 10"   w.c. for propane gas. See Paragraph 9.   %Turn the unit off and on, pausing two minutes between each   cycle. Observe for smooth ignition.   %Place the "Owner's Envelope" containing the Limited War-   ranty, this booklet, the operation/maintenance/service manual,   and any control or optional information in an accessible loca-   tion near the heater. Follow the instructions on the envelope.   Mfg No. 164771, Page 23   Download from Www.Somanuals.com. All Manuals Search And Download.   ©2001 Thomas & Betts Corporation, All rights reserved.   Printed in the U.S.A.   MANUFACTURER OF HEATING, COOLING, AND VENTILATING SYSTEMS   Trademark Note: Reznor® is registered in the United States and other countries.   2/01 YL Form RZ 405 (Version B)   Form 405, Page 24   Download from Www.Somanuals.com. All Manuals Search And Download.   |