TANDBERG Home Theater System 11907602 User Manual

TANDBERG  
Telepresence T3  
ROOM REQUIREMENTS  
The Room Requirements Description presents the room dimensions  
requirements, weights, wall- and ceiling loads, power outlet requirements as  
well as the heating, ventilation and air-conditioning (HVAC) requirements for the  
TANDBERG Telepresence T3 system.  
Independent of whether customers plan to install a TANDBERG Immersive  
Room, or create their own, this document is important to read.  
Note that the entrance door is not a part of the TANDBERG Immersive Room  
package. The door should open outwards.  
ROOM dIMENSIONS  
Overall system dimensions:  
2800mm×4800mm / 9214×159” (d×w)  
Optimal room dimensions (immersive room):  
4680mm×7170mm /15414×23614” (d×w)  
Room Height: 2550mm / 8438  
Note that the  
door is not a part  
of the Immersive  
Room Package and  
that the door should open  
outwards.  
WEIGHT ANd lOAd REQUIREMENTS  
Weight of total system:  
1.075kg  
Weight of Wooden Wall panels:  
Weight of Glass Wall Panels:  
15kg/m2 (0.021lbs/inch2)  
60kg (132lbs)  
The Floor load for the glass panels: 240kg (528lbs) / 8 adjustable legs  
This document is confidential and remains proprietary  
to TANDBERG Telecom AS (“TANDBERG”).  
(A=314mm2) 0.76kg/mm2 (135lbs/inch2)  
Without TANDBERG’s prior written approval, this  
document, either in whole or in part, may not be  
reproduced in any form or by any means, disclosed  
to others outside the Client’s organisation or used for  
any purpose whatsoever other than for evaluatory  
purposes by the Client.  
Wall load for sidewalls: (for maximum size room)  
Wall load for front/back wall (3.9m2):15×3.9=58.5kg (129lbs)  
Wall Load for side wall (11.47m2): 15×11.47=172kg (378lbs)  
All information, descriptions, examples and  
calculations contained in this document are for  
guidance purposes only and should not be treated as  
definitive.  
Ceiling load:  
Ceiling lights:  
Document camera: 12kg (26lbs)  
42kg (92lbs)  
Whilst all reasonable care has been taken to ensure  
that the information contained in the presentation is  
accurate and not misleading, TANDBERG shall not be  
liable for any loss resulting from reliance placed on the  
information contained in this document.  
CONTENTS  
Room requirements................................................................................................1  
System dimensions................................................................................................2  
Room depth requirements optimal and maximal depth .........................................3  
Minimum room depth requirements ......................................................................4  
Minimum room width requirements ......................................................................5  
Optimum and maximum room height ....................................................................6  
Minimum room height requirements .....................................................................7  
Maximum room height...........................................................................................8  
HVAC requirements................................................................................................9  
Acoustics requirements........................................................................................11  
Power outlet fuse requirements...........................................................................12  
Electronic versions of Technical drawings............................................................13  
TANDBERG WORLD HEADQUARTERS  
Philip Pedersens vei 20  
1366 Lysaker, Norway  
Tel: +47 67 125 125  
Fax: +47 67 125 234  
Video: +47 67 126 126  
1212 Avenue of the Americas  
24th Floor  
New York, NY U.S.A. 10036  
Tel: +1 212 692 6500  
Fax: +1 212 692 6501  
Video: +1 212 692 6535  
119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08  
PAGE 1/22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TANDBERG  
HVAC REQUIREMENTS  
Telepresence T3  
Tip! An average person emits approximately  
65W at rest. You may want to consider this  
when calculating the HVAC requirements.  
The following HVAC (heating, ventilation, air-conditioning) requirements apply to  
the TANDBERG Telepresence T3:  
Power consumption System: 1725 W  
Power consumption Table:  
300 W  
Power consumption Lighting: 1300 W  
Noise from air-conditioning should be less or equal to 27dB(A) measured at  
all seating positions.  
e
n
i
l
r
e
t
n
e
C
Note: Dimensions are between floor and  
underside of light modules.  
228cm  
7’534  
Make sure that HVAC mounting neither conflicts with the ceiling lights positions  
nor the document camera position.  
A detailed drawing of the ceiling mounting of the lights can be found overleaf,  
while the drawing 119082 on page 14 shows the position of the document camera.  
119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08  
PAGE 9/22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TANDBERG  
Telepresence T3  
HVAC REQUIREMENTS  
Centerline  
675  
2658  
"
2100  
8258  
"
2025  
7934  
"
2247  
8812  
"
320  
1258  
"
150  
587  
"
Baseline  
Make sure that HVAC mounting neither conflicts with the ceiling lights positions nor the document  
2280  
89 43  
"
119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08  
PAGE 10/22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TANDBERG  
Telepresence T3  
ACOUSTICS REQUIREMENTS  
It is essential to have a good acoustic environment for the system to provide the  
true telepresence experience. This means that there should be sufficient sound  
insulation to minimize noise from adjacent rooms and to ensure that confidential  
information is kept within the meeting room. A good choice of acoustic materials  
for the surfaces and low background noise will ensure comfort in long meetings  
in addition to high speech intelligibility. You may want to contact acoustic  
specialists when looking into this matter.  
REQUIREMENTS IN GENERAl  
All walls around the room should have a sound insulation of R’w 48dB  
(corresponding to STC 50).  
The door should have a sound insulation of Rw 38dB.  
Background noise level should be less or equal to 30dB(A). This includes both  
noise from technical installations (air-conditioning in particular) and outdoor traffic  
noise etc.  
REQUIREMENTS SPECIfIC fOR IMMERSIVE ROOMS  
Absorptive ceiling should have an absorption factor 0.9 in the octave bands  
125–4000 [Hz]. This will normally require a mineral wool ceiling of good quality.  
REQUIREMENTS SPECIfIC fOR NON-IMMERSIVE ROOMS  
Reverberation time (RT) should be within 0.3–0.6 [s] in the octave bands  
125–4000 [Hz].  
The acoustic absorption should to some extent be distributed on the walls in  
addition to the ceiling to avoid flutter-echo effects from parallel walls.  
The ceiling is recommended to have an absorption factor 0.9 in the octave  
bands 125–4000 [Hz]. This will normally require a mineral wool ceiling of good  
quality.  
The walls should at least have sound absorbing fields at the side, front and back  
walls corresponding to the TANDBERG Immersive Room Package. Both the  
placement and area should be approximately the same. If perforated or slotted  
panels are used, the opening area of the panel must be at least 20%.  
Sound absorption on walls could also be made with mineral wool wall panels,  
curtains or other absorptive materials.  
119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08  
PAGE 11/22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TANDBERG  
POWER OUTlET fUSE  
Telepresence T3  
REQUIREMENTS  
Note! The table lists minimum fuse  
requirements. All electrical work must  
be done by electricians with local  
knowledge.  
The following minimum power outlet fuse requirements apply to the TANDBERG  
Telepresence T3:  
ITEM  
WATT  
2400  
60  
PlACEMENT  
Back wall  
fUSE  
ON/Off SWITCH  
T1 Module×3  
A
A
1
1
Presentation  
splitter×2  
Back wall  
Table power outlet×6  
TCU  
2400  
400  
50  
Back wall  
Back wall  
Back wall  
Back wall  
B
C
C
C
2
2
2
2
Note! Outside the room—adjacent to the  
entrance—there shall be an emergency  
power switch to switch off the power to  
the entire system and the room.  
Table quick buttons  
Presentation input  
switch  
5
On the inside adjacent to the exit there  
shall be a sign with the following text:  
Touch collaboration  
display splitter  
20  
Back wall  
Back wall  
C
C
2
2
fire emergency switch is  
located on the outside of  
this room.  
Touch collaboration  
display  
750  
Document camera  
300  
750  
Ceiling  
Ceiling  
D
D
2
3
T3 Ceiling mounted  
lights  
T3 LED Module  
1000 Back- / Front wall  
9335  
D
4
Total power  
119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08  
PAGE 12/22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TANDBERG  
ElECTRONIC VERSIONS Of  
Telepresence T3  
TECHNICAl dRAWINGS  
The technical drawings on the following pages are also available in electronic  
formats as pdf, dwg and dxf. To obtain copies of these drawings, send an e-mail  
The following drawings are available:  
119082 T3 Ceiling  
119083 T3 Electrical System  
119083-US T3 Electrical System US  
119084 T3 Furniture Plan  
119086 T3 Short Structure  
119087 T3 Long Structure  
119088 T3 Structural Elements  
119089 T3 Lighting  
119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08  
PAGE 13/22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp Flat Panel Television LU630E User Manual
Shaw Universal Remote M1055 User Manual
Silva GPS Receiver DGPS 200 User Manual
Socket Mobile GPS Receiver BluetoothTM Connection Kit User Manual
Sony Cassette Player E40ST User Manual
Sony Digital Camera 4 429 666 221 User Manual
Sony Microphone ECM S80 User Manual
Sony TV Mount SFM1 User Manual
Sylvania VCR 6120PA User Manual
Tanaka Trimmer TBC 4000 User Manual