System Sensor Smoke Alarm DH500 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS  
DH500 Intelligent Air Duct Smoke  
Detector Housing  
3825 Ohio Avenue, St. Charles, Illinois 60174  
1-800-SENSOR2, FAX: 630-377-6495  
Specifications  
Length:  
14.5 inches (36.7 cm)  
Width:  
Depth:  
Weight:  
5 inches  
3.5 inches  
2.8 lbs.  
(12.7 cm)  
(8.9 cm)  
(1.1 kg)  
Operating Temperature Range:  
Operating Humidity Range:  
Duct Air Velocity:  
Electrical Ratings for DH500  
Voltage Range:  
Standby Current (nominal):  
Power-Up Surge at Max.  
Rated Voltage:  
32° to 120°F (0° to 49°C)  
10% to 93% Relative Humidity  
500 – 4000 ft./min. (91.4 – 1219.2 m/min.)  
14.5 – 32 VDC Peak  
150uA at 24 VDC  
1.5mA-sec.  
LED current (nominal):  
6mA at 24 VDC  
Before Installing  
blowers, change over air handling systems, etc. This can  
prevent the distribution or isolation of toxic smoke and fire  
gases throughout the areas served by the duct system.  
Please thoroughly read System Sensor’s Guide for Proper  
Use of Smoke Detectors in Duct Applications (I56-473-XX),  
which provides detailed information on detector spac-  
ing, placement, zoning, wiring, and special applications.  
Copies of this manual are available from System Sensor.  
NFPA Standards 72 and 90A should also be referenced for  
detailed information.  
Two LEDs on each detector latch ON to provide a local  
alarm indication. There is also a remote alarm output  
for use with auxiliary devices. The DH500 has remote  
test capability with the RTS451/RTS451KEY Remote Test  
Station.  
NOTICE: This manual should be left with the owner/user  
of this equipment.  
Contents of the Duct Detector Housing Kit  
IMPORTANT: This detector must be tested and maintained  
regularly following NFPA 72 requirements. The detector  
should be cleaned at least once a year.  
The DH500 consists of the following items: (See Figure 1.)  
See Note 1 on Page 2 for inlet sampling tube and detector  
supply information.  
General Description  
An HVAC system supplies conditioned air to virtually every  
area of a building. Smoke introduced into this air duct sys-  
tem will be distributed to the entire building. Smoke detec-  
tors designed for use in air duct systems are used to sense  
the presence of smoke in the duct.  
1. Complete housing base and cover assembly.  
2. Two #10 sheet metal mounting screws.  
3. Two sampling tube filters.  
4. One test magnet.  
5. Drilling template.  
6. Two 5/16-inch O-rings.  
The DH500 Air Duct Detector Housings are used with  
System Sensor’s intelligent model 1551 ionization detector  
head and model 2551 photoelectronic detector head. These  
two principal smoke detection methods are combined with  
an efficient housing design that samples air passing through  
a duct and allows early detection of a developing hazardous  
condition. When sufficient smoke is sensed, an alarm signal  
is initiated at the fire control panel monitoring the detector,  
and appropriate action can be taken to shut off fans and  
7. Two rubber tube bushings seals.  
8. Four #6 self-tapping mounting screws for the sampling  
tube.  
9. One filter adapter.  
10. One inlet tube end plug.  
11. Four #6x7/10 cover mounting screws.  
12. Two #10 speed nuts.  
13. One test coil and parts bag.  
D500-08-00  
1
I56-512-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 2A. Speed nut mounting location:  
Figure 2B. Installation of foam gaskets over sam-  
pling tube bushings:  
HOLE B  
DUCT DETECTOR  
INLET SAMPLING  
HOLE A  
DUCT  
WALL  
HOUSING  
TUBE BUSHING  
MOUNTING  
SCREWS  
EXHAUST TUBE  
(EXTENSION BUSHING)  
O-RINGS  
FOAM GASKETS  
SPEED  
NUT  
SCREW HOLES FOR AT TACHING  
DETECTOR HOUSING TO DUCT  
H0116-00  
H0238-00  
of air inlet holes on the tube. This tube must be purchased  
separately. Order the correct length, as specified in Table  
1, for the width of the duct where it will be installed. The  
exhaust tube is molded into the base of the duct housing.  
Table 1. Sampling (Inlet) Tubes  
Tube  
ST-1.5  
ST-3  
ST-5  
ST-10  
Outside Duct Width  
1 to 2 ft.  
2 to 4 ft.  
4 to 8 ft.  
8 to 12 ft.  
(0.3 to 0.6 m)  
(0.6 to 1.2 m)  
(1.2 to 2.4 m)  
(2.4 to 3.7 m)  
The inlet tube is always installed in the right house bush-  
ing, with the air inlet holes facing into the air flow. To  
assure proper installation, the tube mounting flange is  
marked with arrows. Mount the inlet tube so that the  
arrows point into the air flow. Figure 4 shows the various  
combinations of tube mounting configurations with respect  
to air flow.  
Step 4. Install the Inlet Tube  
The inlet tube (shown in Figure 3) is identified by a series  
Figure 3. Air duct detector inlet sampling tube:  
AIR HOLES  
FLANGE  
INLET  
TUBE  
END  
PLUG  
ARROWS  
MUST FACE  
INTO AIR FLOW  
AIR FLOW DIRECTION  
H0108-00  
A. Installation for Ducts Less Than 8 Feet Wide  
1. If the inlet tube is longer than the width of the air duct,  
drill a 3/4-inch hole in the duct directly opposite the  
hole already cut for the inlet tube.  
If the inlet tube is shorter than the width of the air duct,  
install the end cap into the inlet tube (see Figure 3).  
2. Slide the inlet tube into the right housing bushing.  
Position the tube so that the arrows point into the air  
flow.  
there are more than 2 holes in the section of the tube  
extending out of the duct, select a different tube length  
using Table 1. Otherwise, trim the end of the tube pro-  
truding through the duct so that 1 to 2 inches of the tube  
extends outside the duct. Plug this end with the tube  
end plug and tape closed any holes in the protruding  
section of the tube. Be sure to seal the duct when the  
tube protrudes.  
5. Any inlet tube over 3 feet long must be supported on the  
opposite side of the duct detector housing.  
3. Secure the tube flange to the housing bushing with the  
two #6 self-tapping screws.  
4. For tubes longer than the width of the air duct, the tube  
should extend out of the opposite side of the duct. If  
D500-08-00  
3
I56-512-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 4. Tube mounting configurations with varying air flow direction and orientation of detector housing.  
Vertical as well as horizontal mounting is acceptable.  
DOTS INDICATE POSITION OF  
SAMPLING TUBE HOLES  
AIR FLOW  
AIR FLOW  
DIRECTION  
DIRECTION  
DETECTOR  
HOUSING  
DETECTOR  
HOUSING  
B.  
A.  
INLET  
TUBE  
EXHAUST  
TUBE  
EXHAUST  
TUBE  
INLET  
TUBE  
HORIZONTAL MOUNTING OF HOUSING  
EXHAUST  
TUBE  
DETECTOR  
HOUSING  
EXHAUST  
TUBE  
AIR FLOW  
DIRECTION  
AIR FLOW  
DIRECTION  
INLET  
INLET  
TUBE  
TUBE  
C.  
DETECTOR  
HOUSING  
H0109-00  
D.  
VERTICAL MOUNTING OF HOUSING  
NOTE: An alternate method to using the ST-10 is to use  
two ST-5 inlet tubes. Remove the flange from one  
of the tubes and install as described above. After  
the installation, use electrician’s tape to close off  
some of the sampling holes so that there are a total  
of 12 holes spaced as evenly as possible across the  
width of the duct.  
WARNING  
In no case should more than 2 air inlet holes be cut off the  
tube. There must be a minimum of 10 holes in the tube  
exposed to the air stream.  
B. Installation for Ducts More Than 8 Feet Wide  
NOTE: To install inlet tubes in ducts more than 8 feet  
wide, work must be performed inside the air duct.  
Sampling of air in ducts wider than 8 feet is accom-  
plished by using the ST-10 inlet sampling tube.  
NOTE: Air currents inside the duct may cause excessive  
vibration. This vibration can slowly open the  
seal around the tube and permit air to escape. To  
prevent this from occurring, a 3-inch floor flange,  
available at most plumbing supply houses, may be  
used. This flange/connector mounting technique  
makes the initial installation easier because a 1-  
inch to 1-1/4-inch hole may be drilled where the  
flange/connector will be used. It is easier to push  
the inlet tube through the larger hole.  
Install the inlet tube as follows:  
1. Drill a 3/4-inch hole in the duct directly opposite the  
hole already drilled for the inlet tube.  
2. Slide the inlet tube with the flange into the right housing  
bushing. Position the tube so that the arrows point into  
the air flow. Secure the tube flange to the housing bush-  
ing with the two #6 self-tapping screws.  
3. From inside the duct, couple the other section of the  
inlet tube to the section already installed using the 1/2-  
inch conduit fitting supplied. Make sure the holes on  
both of the air inlet tubes are lined up facing the air  
flow.  
4. Trim the end of the tube protruding through the duct so  
that 1 to 2 inches of the tube extends outside the duct.  
Plug this end with the tube end cap and tape closed any  
holes in the protruding section of the tube. Be sure to  
seal the duct when the tube protrudes.  
Modification of Inlet Sampling Tubes  
There may be applications where duct widths are not what  
is specified for the installation. In such cases, it is permis-  
sible to modify an inlet sampling tube that is longer than  
necessary to span the duct width.  
Use a 0.193-inch diameter (#11) drill and add the appro-  
priate number of holes so that the total number of holes  
exposed to the air flow in the duct is 10 to 12. Space the  
additional holes as evenly as possible over the length of  
the tube.  
5. Any tube (over 3 feet long) that doesn’t protrude through  
the duct (on the side opposite the housing) must be sup-  
ported by other means.  
D500-08-00  
4
I56-512-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: This procedure should only be used in an emergen- left, as shown in Figure 6. Then install the other filter over  
cy, and it is not intended as a permanent substitute the end of the inlet sampling tube.  
for ordering the correct length tubes.  
CAUTION  
Step 5. Field Wiring  
Wiring Installation Guidelines  
Filters require periodic cleaning or replacement, depend-  
ing on the amount of dust and dirt accumulated. Visually  
All wiring must be installed in compliance with the inspect the filters at least quarterly; inspect them more  
Canadian Electrical Code and the local codes having juris- often if the dust accumulation warrants it. Replacement  
diction. Proper wire gauges should be used. The conduc- filters can be ordered from System Sensor (exhaust tube/  
tors used to connect smoke detectors to control panels and intake tube filter P/N F36-05-00).  
accessory devices should be color-coded to prevent wiring  
mistakes. Improper connections can prevent a system from The filters do not substantially affect smoke performance  
responding properly in the event of a fire.  
under normal conditions. There is very little restriction of  
smoke entry even when up to 90% of the filter is clogged.  
For signal wiring, (the wiring between interconnected Visual inspection is usually adequate to determine whether  
detectors or from detectors to auxiliary devices), it is rec- the filters should be replaced because such a high percent-  
ommended that single-conductor wire be no smaller than age of contamination is required to affect performance.  
16 gauge (1.5 square mm), and that two- or three-conduc-  
tor wire be no smaller than 18 gauge (1.0 square mm). The However, if further testing is desired, a Dwyer Model 460  
last foot or so of conduit should be flexible steel conduit (or equivalent) Differential Pressure Gauge may be used.  
(available in electrical supply houses) which facilitates Simply compare the differential pressure readings with  
easier installation and puts less strain on the conduit holes and without the filters attached. There should be little or  
in the housing. Solid conduit connections may be used if no difference. If the difference exceeds 10%, replace the  
desired.  
filters. In no case, however, should the pressure differential  
be less than 0.01 inches of water or greater than 1.2 inches  
Smoke detectors and alarm system control panels have of water.  
specifications for allowable loop resistance. Consult the  
control panel manufacturer’s specifications for the total Step 7. Perform Detector Check  
loop resistance allowed for the particular model control 7.1 Air Flow  
panel being used before wiring the detector loop.  
1. To verify sufficient sampling of ducted air, use a manom-  
eter to measure the differential pressure created from  
air flow across the sampling tubes. The pressure should  
measure no less than 0.01 inches of water and no greater  
than 1.20 inches of water.  
Wiring Instructions  
The DH500 is designed for easy wiring. The housing pro-  
vides a terminal strip with clamping plates. Wiring con-  
nections are made by stripping approximately 1/2-inch of  
insulation from the end of the wire, sliding this bare end Figure 6. Sampling tube filter installation:  
under the plate, and tightening the clamping plate screw.  
Step 6. Install the Filters  
Most duct installations are subject to dust accumulation.  
INLET SAMPLING TUBE  
System filters remove a large percentage of this contami-  
nation, but cannot remove all of it. Dust inside the duct  
detector causes problems. First, very fine particles of dust  
can enter the detector sensing chamber and cause the unit  
to go into alarm. Second, the accumulation of dust and dirt  
necessitates a more frequent periodic cleaning schedule,  
FOAM GASKET  
SAMPLING TUBE  
MOUNTING  
SCREWS  
which can result in substantial cost and/or down time.  
DETECTOR BASE  
Disposable sampling tube filters can greatly reduce the  
EXHAUST  
FILTER ADAPTER  
nuisance alarms caused by dust, and can also significantly  
extend the maintenance interval. To install the sampling  
DETECTOR HEAD  
tube filters, simply push the filter adapter into the exhaust  
SAMPLING TUBE  
H0294-00  
FILTERS  
tube, and then push the filter onto the adapter tube on the  
D500-08-00  
5
I56-512-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RA400Z (+)  
(+)  
(-)  
RA400  
RA400Z or (-)  
RTS451/  
RTS451KEY  
REMOTE ALARM  
LED OPTION  
1 PER UNIT  
8mA CURRENT DRAW  
Figure 5A.  
Unused  
4
5
(+)  
(-)  
Remote  
Test  
*
EXTERNAL  
(-) POWER (+)  
SUPPLY  
1
2
3
(+)  
RA400Z  
RTS451/RTS451KEY  
RTS451/RTS451KEY (+)  
RA400Z or  
REMOTE TEST STATION  
(-)  
RTS451/RTS451KEY  
LED OPTION  
1 PER UNIT  
8mA CURRENT DRAW  
(-)  
Comm.  
Line  
(+)  
TEST COIL OPTION  
1 PER UNIT  
95mA CURRENT DRAW  
Figure 5B.  
*The RTS451/RTS451KEY test coil circuit requires an external 24VDC  
power supply which must be UL listed  
Comm. Line (+)  
Alarm  
Initiation  
Loop  
Comm.  
Line (-)  
UL Listed  
Control Panel  
1st  
Detector  
in Loop  
2nd  
Detector  
in Loop  
Figure 5C. System wiring diagram  
for duct detectors using a UL listed  
control panel.  
H0295-00  
D500-08-00  
6
I56-512-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. To determine that smoke is capable of entering the sens-  
ing chamber, a visual examination should be conducted Figure 8. Detector head removal:  
to note any obscurations around the sensing chamber. If  
a smoke test is required, smoke such as cigarette, cot-  
ton wick, or punk smoke may be blown directly at the  
smoke detector head. It is important to plug the exhaust  
and sampling tube hole to prevent ducted air from blow-  
DETECTOR  
HEAD  
ing smoke away from the smoke detector head. Record  
all test records in the Detector Test Log (page 12).  
TWIST  
COUNTERCLOCKWISE  
TO REMOVE  
CAUTION  
Remember to remove the plugs after this test or the detec-  
tor will not sense smoke in the air duct.  
DUCT  
HOUSING  
H0276-00  
7.2 Alarm Tests  
TWIST  
CLOCKWISE  
Before replacing the duct housing cover, the detector  
TO INSTALL  
interconnections should be checked. The DH500 may be  
checked as follows:  
A. M02-04-00 Magnet Test  
1. Make sure power is applied to the detector.  
2. Place the painted surface of the test magnet against B. RTS451/RTS451KEY Remote Test Station  
the housing next to the rib molded onto the outside The RTS451/RTS451KEY Remote Test Station facilitates test  
of the housing (see Figure 7). of the alarm capability of the duct detector as indicated in  
3. The LEDs on the detector should latch on as should the RTS451/RTS451KEY manual. The DH500 duct detector  
any accessories (i.e. RA400ZA, RTS451), and the cannot be reset by the RTS451/RTS451KEY. It must be reset  
alarm condition should be verified at the control at the system control panel.  
panel.  
To install the RTS451/RTS451KEY test coil, connect the  
device as shown in Figure 9; wire runs must be limited to  
Figure 7. Testing detector  
25 ohms or less per interconnecting wire. Place the coil in  
the detector housing with the arrow facing up and pointing  
toward the detector as in Figure 9. Attach the coil leads to  
the housing terminals as shown; polarity is not important.  
Firmly screw the bracket in place over the test coil.  
7.3 MOD400 Sensitivity Test  
TEST  
MAGNET  
MOLDED RIB  
After verification of alarm capability, the MOD400 test  
module may be used with a voltmeter to check detector  
sensitivity as indicated in the MOD400 installation manual.  
The housing cover must be removed to perform this test.  
PAINTED SIDE  
TOWARD HOUSING  
DUCT  
DETECTOR  
HOUSING  
If the MOD400 readings indicate that the detector head is  
outside of the acceptable range, the detector head requires  
cleaning. (See Periodic Maintenance Requirements on page  
9.)  
H0275-00  
DETECTOR  
HEAD  
7.4 Trouble Test  
The capability of “TROUBLE” detection is tested by remov-  
ing the detector head from the duct housing. The detector  
head is removed by turning it counterclockwise about 10  
degrees (Figure 8). The system control panel should indi-  
cate a trouble condition. Reinserting the detector head  
should clear the trouble condition.  
D500-08-00  
7
I56-512-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 9. RTS451/RTS451KEY test coil installation:  
TEST COIL  
DETECTOR  
HEAD  
H0292-00  
Step 8. Install the Cover  
Install the cover using the four screws. Be certain filters are  
installed as specified in Step 6. Make sure that the cover fits  
new filters. If they are not heavily coated, use a vacuum  
cleaner or compressed air nozzle to remove dust, then  
reinstall the filters.  
into the base groove and that all gaskets are in their proper 4. Remove detector from housing. (See Figure 8.)  
positions. Tighten the four cover screws to 10 in/lbs.  
Photo Units  
Step 9. Perform the Final System Check  
Place the magnet in position as shown in Figure 7. The  
LEDs on the detector should light. Any accessory LED(s)  
will also light. The system control panel should indicate an  
alarm condition.  
5. Remove detector cover by inserting a small blade screw-  
driver into the slot located 90 degrees from the MOD400  
test jack receptacle, twisting the cover counterclockwise  
to remove (see Figure 10).  
6. Lift screen from photo chamber. Vacuum screen and  
cover before using clean, compressed air to loosen and  
blow out any remaining debris. (Replacement screens  
are available, part no. RS24.)  
Periodic Maintenance Requirements  
Air duct smoke detectors should be maintained at least  
once a year. They should be maintained more often if the 7. Vacuum photo chamber, then use clean compressed air  
detector heads become obviously dirty in less than a year. to blow area clean.  
The detectors must also be cleaned immediately after a fire. 8. Replace screen by aligning arrow on top with the field  
Failure to properly maintain air duct smoke detectors may  
cause unnecessary false alarms.  
test slot on the base of the detector. Push screen into  
place. Screen should fit tightly to chamber.  
It is recommended that a permanent Detector Test Log be Ionization Units  
set up and maintained, with a record for each individual 9. Remove the detector cover and screen assembly by  
smoke detector in each building. Each detector should be  
clearly described, with information on the type of detector,  
the model number, the serial number (if any), the location,  
and the type of environment. Data entries should include  
depressing the three lock prongs on the top of the cover  
and rotating the cover counterclockwise. The CRT400  
Cover Removal Tool makes cover removal easier. (See  
Figure 11.)  
test dates, type of test mode, test results, maintenance, and 10. Carefully pull the screen out of the cover.  
comments. A detector test log is included in this manual.  
11. Clean the screen thoroughly with a soft brush or vacu-  
um (replacement screen available, part no. RS14).  
12. Brush or vacuum the inside of the cover. Cover may  
then be blown out using clean, compressed air. DO  
NOT APPLY WATER TO THIS AREA.  
Recommended Detector Maintenance Procedure  
NOTE: Notify the proper authorities that the smoke detec-  
tor system is undergoing maintenance, and there-  
fore the system will temporarily be out of service. 13. Vacuum the sensing chamber before using clean,  
Disable the zone or system undergoing mainte-  
nance to prevent unwanted alarms and possible  
dispatch of the fire department.  
compressed air to loosen and blow out any remaining  
debris. DO NOT APPLY WATER TO THIS AREA.  
14. Press the screen back into the cover.  
15. Replace the detector cover and screen assembly on  
the sensing chamber. Rotate it clockwise to lock it into  
place.  
1. Turn off power to the system.  
2. Remove and inspect sampling tube filters.  
3. If filters are heavily coated with dirt, replace them with  
D500-08-00  
8
I56-512-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Both Types Of Units  
16. Reinstall the detector housing.  
17. Restore power to the system.  
Ionization Replacement Screen  
Sensitivity Test Kit  
Ionization Cover Removal Tool  
RS14  
MOD400  
CRT400  
18. Put detector into alarm using appropriate method  
described in STEP 7. PERFORM DETECTOR CHECK Programming Specifications/Requirements for  
(page 7 of this manual).  
Intelligent System Control Panels  
19. Notify the proper authorities that testing has been  
completed and the smoke detector system is again  
operational.  
CAUTION  
The 1551 and 2551 models can be used with the DH500 if  
20. Other checks that should be made during mainte- the following constraints are observed.  
nance procedures:  
–Holes or cracks in duct work near vicinity of detec- There is a limit to the number of devices per zone that can  
tor  
have their LEDs latched ON. The actual number of devices  
–Air leaks where detector housing or sampling tubes is determined by the control panel and its ability to supply  
are attached to duct  
–Dust accumulations in or on sampling tubes  
–Wiring terminal screw tightness  
LED current. Refer to the equipment manual supplied by  
the control panel manufacturer for details.  
Accessories  
Part No.  
Remote LED  
RA400ZA  
RTS451/RTS451KEY  
PA400  
F36-05-00  
M02-04-00  
P48-21-00  
A2650-01  
Remote Test Station  
Piezo Alert Sounder  
Replacement Filters  
Magnet  
End Plug For Sampling Tube  
Installation Kit (Parts bag)  
Figure 11. Ion head exploded view:  
Figure 10. Photo head exploded view:  
HEAD COVER  
LOCK PRONGS  
REMOVABLE HEAD COVER  
REMOVABLE  
COVER  
FOR  
CLEANING  
TEST SLOT  
REMOVABLE SCREEN  
(P/N RS14)  
CLEANABLE SCREEN  
P/N RS24 (W/O THERMAL)  
HOUSING  
LOCK PRONGS  
HEAD COVER  
REMOVAL SLOT  
VANED CHAMBER  
H0296-00  
H0261-00  
D500-08-00  
9
I56-512-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D500-08-00  
10  
I56-512-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Please refer to insert for the Limitations of Fire Alarm Systems  
Three-Year Limited Warranty  
System Sensor warrants its enclosed smoke detector to be free from  
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.  
Please include a note describing the malfunction and suspected cause  
of failure. The Company shall not be obligated to repair or replace units  
which are found to be defective because of damage, unreasonable use,  
modifications, or alterations occurring after the date of manufacture. In  
no case shall the Company be liable for any consequential or incidental  
damages for breach of this or any other Warranty, expressed or implied  
whatsoever, even if the loss or damage is caused by the Company’s neg-  
ligence or fault. Some states do not allow the exclusion or limitation of  
incidental or consequential damages, so the above limitation or exclusion  
may not apply to you. This Warranty gives you specific legal rights, and  
you may also have other rights which vary from state to state.  
defects in materials and workmanship under normal use and service for a  
period of three years from date of manufacture. System Sensor makes no  
other express warranty for this smoke detector. No agent, representative,  
dealer, or employee of the Company has the authority to increase or alter  
the obligations or limitations of this Warranty. The Company’s obliga-  
tion of this Warranty shall be limited to the repair or replacement of any  
part of the smoke detector which is found to be defective in materials or  
workmanship under normal use and service during the three year period  
commencing with the date of manufacture. After phoning System Sensor’s  
toll free number 800-SENSOR2 (736-7672) for a Return Authorization  
number, send defective units postage prepaid to: System Sensor, Repair  
D500-08-00  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I56-512-07R  
DETECTOR TEST LOG  
Detector Identification Information  
Manufacturer and  
Serial  
Date  
Detector Model:______________________ Number:______________________ Installed: ___________________  
Description of Detector Location:  
________________________________________________________________________________________________  
________________________________________________________________________________________________  
________________________________________________________________________________________________  
Test Results and Maintenance Data  
Date  
Tested  
Test  
Description  
Test  
Results  
Maintenance  
Performed  
Comments  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_______  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
_________  
______  
______  
______  
______  
______  
______  
______  
______  
______  
______  
______  
______  
______  
______  
______  
______  
______  
______  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
__________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
D500-08-00  
12  
I56-512-07R  
© 2003 System Sensor  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sennheiser Microphone 912 S User Manual
Sharp All in One Printer MX M450 User Manual
Singer Sewing Machine 11W8 User Manual
Sony Bluetooth Headset DR BT160IK User Manual
Sony Computer Drive Memory Stick Camera Application Version 10 User Manual
Sony Projection Television KP 46WT520 User Manual
Soundstream Technologies Stereo Amplifier SMA2340 User Manual
StarTechcom Switch SV215MICUSBA User Manual
Sunbeam Fryer 40L User Manual
Symphonic TV VCR Combo SC1304 User Manual