System Sensor Smoke Alarm DH100LP User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS  
DH100LP Air Duct Smoke Detector  
with Extended Air Speed Range  
3825 Ohio Avenue, St. Charles, Illinois 60174  
1-800-SENSOR2, FAX: 630-377-6495  
The Innovair DH100LP model is a photoelectric detector action can be taken to shut off fans, blowers, change over  
approved for an extended air speed range of 100 to 4000 air handling systems, etc. These actions can facilitate the  
feet per minute (0.5 m/s to 20.3 m/s) and has an opera- management of toxic smoke and fire gases throughout the  
tional temperature range of 32°F to 131°F (0°C to 55°C).  
areas served by the duct system.  
Before Installing  
DH100LP detectors are designed to operate with 12/24VDC  
UL listed compatible 2-wire control panels. Alarm current  
must be limited to 130mA or less by the control panel.  
Auxiliary relay contacts for control purposes are not avail-  
able for use with the DH100LP. Control must initiate from  
Please thoroughly read the System Sensor Guide for Proper  
Use of Smoke Detectors in Duct Applications (A05-1004),  
which provides detailed information on detector spacing,  
placement, zoning, wiring, and special applications. Copies  
ofthismanualareavailableonlineatwww.systemsensor.com  
or via System Sensor’s toll free fax-back service, Documents the control panel.  
on Demand at 800/736-7672. NFPA Standards 72 and 90A  
should also be referenced for detailed information.  
For testing, the alarm can be enabled by a magnet activated  
test switch or by the optional remote test station. The duct  
smoke detector latches into alarm state when an alarm  
occurs. A green LED flashes to indicate power, a red LED  
signals local alarm indication, and optional accessories  
offer a variety of annunciation capabilities.  
NOTICE: This manual shall be left with the owner/user of  
this equipment.  
IMPORTANT: This detector must be tested and maintained  
regularly following NFPA 72 requirements. The detector  
should be cleaned at least once a year.  
The DH100LP can be reset by a momentary power interrup-  
tion, the reset button on the front cover, the control panel,  
or remote reset accessory.  
Table of Contents  
Page  
[1] General Description ................................................... 1  
[2] Limitations of Duct Smoke Detectors........................... 1  
[3] Exploded View of Duct Smoke Detector Components.. 2  
[4] Contents of the Duct Smoke Detector Kit..................... 2  
[5] Installation Sequence.................................................. 2  
[6] Duct Smoke Detector Maintenance  
and Test Procedures.................................................... 5  
[7] Detector Cleaning Procedures...................................... 7  
[8] Board Replacement..................................................... 7  
[9] Specifications.............................................................. 8  
Warranty........................................................................... 8  
[2] Limitations Of Duct Smoke Detectors  
WARNING  
The National Fire Protection Association has established  
that DUCT DETECTORS MUST NOT BE USED AS A  
SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION  
as a means of providing life safety. Nor are they a substi-  
tute for early warning in a building’s regular fire detection  
system.  
System Sensor supports this position and strongly recom-  
mends that the user read NFPA Standards 90A, 72, and 101.  
The DH100LP Air Duct Smoke Detectors are listed per UL  
268A.  
[1] General Description  
An HVAC system supplies conditioned air to virtually every  
area of a building. Smoke introduced into this air duct  
system will be distributed throughout the entire building.  
Smoke detectors designed for use in air duct systems are  
used to sense the presence of smoke in the duct.  
WARNING  
This device will not operate without electrical power.  
Fire situations may cause an interruption of power. The  
system safeguards should be discussed with your local fire  
protection specialist.  
Model DH100LP Air Duct Smoke Detectors utilizes photo-  
electric technology for the detection of smoke. This detec-  
tion method when combined with an efficient housing  
design samples air passing through the duct and allows  
detection of a developing hazardous condition. When suf-  
ficient smoke is sensed, an alarm signal is initiated at the  
WARNING  
This device will not sense smoke unless the ventilation  
system is operating and the cover is installed.  
fire control panel monitoring the detector, and appropriate  
D200-15-00  
1
I56-0083-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
[5.3] Secure The Detector Housing To The Duct  
the inlet hole on the opposite side of the duct to allow for  
moisture drainage. If the tube is shorter than the width of  
the air duct, install the end cap into the sampling tube as  
shown in Figure 4. Sampling tubes over 3 ft. long must  
be supported at the end opposite the duct detector.  
2. Slide the tube into the housing bushing that meets the  
air flow first. Position the tube so that the arrow points  
into the air flow.  
Slide the foam gaskets over the tube bushings as shown in  
1
Figure 3. Use the two 14long sheet metal screws to screw  
the detector housing to the duct.  
CAUTION: Do not overtighten the screws.  
Figure 3. Installation of foam gaskets over sampling  
tube bushings:  
SCREW HOLES FOR  
ATTACHING HOUSING  
TO DUCT WORK.  
3. Secure the tube flange to the housing bushing with two  
#6 self-tapping screws.  
4. For tubes longer than the width of the air duct, the tube  
should extend out of the opposite side of the duct. If  
there are more than 2 holes in the section of the tube  
extending out of the duct, select a different length using  
Table 1. Otherwise, trim the end of the tube protruding  
through the duct so that 1to 2of the tube extend out-  
side the duct. Plug this end with the end cap and tape  
closed any holes in the protruding section of the tube.  
Be sure to seal the duct when the tube protrudes.  
H0107-00  
[5.4] Sampling Tube Installation of Ducts Greater  
Than 112 Feet Wide  
NOTE: The sampling tube end cap is critical to the proper  
operation of the duct smoke detector. The end cap  
is needed to create the proper air flow to the sensor  
of the duct smoke detector.  
The sampling tube is identified by a series of air inlet holes  
on the tube. One plastic tube is included for ducts up to 18″  
in width. All other lengths must be purchased separately.  
Order the correct length, as specified in Table 1, for width  
of the duct where it will be installed. It is recommended  
Figure 4. Air duct detector inlet sampling tube:  
2
that the sampling tube length extend at least 3across  
AIR HOLES  
the duct width for optimal performance. The exhaust tube  
is molded onto the base of the duct housing, and the A2440-00  
Exhaust Tube Extension is available as an accessory in  
those cases where the molded exhaust port does not extend  
at least 2 inches into the duct.  
SAMPLING  
TUBE  
FLANGE  
END CAP  
ARROW  
AIR FLOW DIRECTION  
MUST FACE  
INTO AIR FLOW  
The sampling tube is always installed with the air inlet  
holes facing into the air flow. To assist proper installation,  
the tube’s mounting flange is marked with an arrow. Make  
sure the sampling tube is mounted so that the arrow points  
into the air flow (see Figure 4). Figure 5 shows the various  
combinations of tube mounting configurations with respect  
to air flow. Mounting the detector housing in a vertical ori-  
entation is acceptable, provided that the air flows directly  
into the sampling tube holes as indicated in Figure 4.  
H0108-02  
Figure 5. Tube mounting configurations with varying  
air flow direction:  
DOTS INDICATE POSITION OF  
SAMPLING TUBE HOLES  
AIR FLOW  
AIR FLOW  
DIRECTION  
DIRECTION  
DETECTOR  
HOUSING  
DETECTOR  
HOUSING  
B.  
A.  
Table 1. Sampling tubes recommended for different  
duct widths:  
Outside Duct Width Sampling Tube Recommended*  
SAMPLING  
TUBE  
EXHAUST  
TUBE  
EXHAUST  
TUBE  
SAMPLING  
TUBE  
HORIZONTAL MOUNTING OF HOUSING  
1 to 2 ft.  
2 to 4 ft.  
4 to 8 ft.  
8 to 12 ft.  
ST-1.5  
ST-3  
ST-5  
DETECTOR  
HOUSING  
EXHAUST  
TUBE  
AIR FLOW  
AIR FLOW  
DIRECTION  
DIRECTION  
ST-10  
SAMPLING  
TUBE  
2
DETECTOR  
HOUSING  
*Must extend a minimum of 3 the duct width  
D.  
C.  
VERTICAL MOUNTING OF HOUSING  
[5.4.1] Installation For Ducts Greater Than 112 Feet  
But Less Than 8 Feet Wide  
H0109-01  
1. If the tube is longer than the width of the air duct, drill a  
34-inch hole in the duct opposite the hole already cut for  
NOTE: Only metal sampling tubes may be used on ori-  
entations C and D.  
the sampling tube. Make sure the hole is 1to 2below  
D200-15-00  
3
I56-0083-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
[5.4.3] Modifications of Sampling Tubes  
WARNING  
There may be applications where duct widths are not what  
is specified for the installation. In such cases, it is permis-  
sible to modify a sampling tube that is longer than neces-  
sary to span the duct width.  
In no case should more than 2 air inlet holes be cut off the  
tube. There must be a minimum of 10 holes in the tube  
exposed to the air stream.  
[5.4.2] Installation For Ducts More Than 8 Feet Wide  
NOTE: To install sampling tubes in ducts more than 8  
feet wide, work must be performed inside the air  
duct. Sampling of air in ducts wider than 8 feet is  
accomplished by using the ST-10 sampling tube. If  
the tube is shorter than the width of the air duct,  
install the end cap into the sampling tube as shown  
in Figure 4 and support the end opposite the duct  
smoke detector.  
Use a 0.193-inch diameter (#10) drill and add the appro-  
priate number of holes so that the total number of holes  
exposed to the air flow in the duct is 10 to 12. Space the  
additional holes as evenly as possible over the length of  
the tube.  
NOTE: This procedure should only be used as a temporary  
fix. It is not intended as a permanent substitute for  
ordering the correct length tubes.  
Install the sampling tube as follows:  
1. Drill a ⁄4-inch hole in the duct opposite the hole already  
[5.5] Install The Filters  
3
To install the sampling tube filters, simply push the filters  
into the sampling and exhaust tube holes as shown in  
Figure 6. If a metal sampling tube is used, install the filter  
over the sampling tube.  
drilled for the sampling tube. Drill the hole 1to 2″  
below the inlet hole on the opposite side of the duct to  
allow for moisture drainage away from the detector.  
2. Slide the sampling tube with the flange into the housing  
bushing that meets the air flow first. Position the tube so  
that the arrow points into the air flow. Secure the tube  
flange to the housing bushing with two #6 self-tapping  
screws.  
Figure 6. Sampling tube filter installation:  
3. From inside the duct, couple the other sections of the  
sampling tube to the section already installed using the  
1
⁄2-inch conduit fittings supplied. Make sure that the  
holes on both of the air inlet tubes are lined up and fac-  
ing into the air flow.  
4. Trim the end of the tube protruding through the duct so  
that 1to 2of the tube extend outside the duct. Plug  
this end with the end cap and tape closed any holes in  
the protruding section of the tube. Be sure to seal the  
duct when the tube protrudes.  
WARNING  
Filters require periodic cleaning or replacement, depend-  
ing on the amount of dust and dirt accumulated. Visually  
inspect the filters at least quarterly; inspect them more  
often if the dust accumulation warrants it. See Section [6]  
for more information. Replacement filters can be ordered  
from System Sensor, 3825 Ohio Ave., St. Charles, IL 60174.  
(Exhaust tube/intake tube filter P/N F36-09-11)  
NOTE: An alternate method to using the ST-10 is to use  
two ST-5 sampling tubes. Remove the flange from  
one of the tubes and install as described above.  
After the installation, use electrical tape to close  
off some of the sampling holes so that there are a  
total of 10 to 12 holes spaced as evenly as possible  
across the width of the duct.  
[5.6] Field Wiring  
Installation Guidelines  
NOTE: Air currents inside the duct may cause excessive  
vibration, especially when the longer sampling tubes are  
used. In these cases a 3 inch floor flange (available at most  
plumbing supply stores) may be used to fasten the sam-  
pling tube to the other side of the duct. When using the  
All wiring must be installed in compliance with the  
National Electrical Code and the local codes having juris-  
diction. Proper wire gauges should be used. The conduc-  
tors used to connect smoke detectors to control panels and  
accessory devices should be color-coded to prevent wiring  
mistakes. Improper connections can prevent a system from  
responding properly in the event of a fire.  
1
flange/connector mounting technique, drill a 1 to 1 ⁄4 inch  
hole where the flange will be used.  
D200-15-00  
4
I56-0083-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For signal wiring, (the wiring between interconnected service. Disable the zone or system under test to prevent  
detectors or from detectors to auxiliary devices), it is usu- unwanted alarms.  
ally recommended that single conductor wire be no smaller  
than 18 gauge. The duct smoke detector terminals accom-  
[6.1.1] Air Flow  
[6.1] Smoke Entry Tests  
modate wire sizes up to 12 gauge. The last foot of conduit  
The DH100LP is designed to operate over an extended air  
should be flexible conduit (available in electrical supply  
speed range of 100 to 4000 FPM. To verify sufficient sampling  
houses), which facilitates easier installation and puts less  
of ducted air, turn the air handler on and use a manometer  
strain on the conduit holes in the housing. Solid conduit  
to measure the differential pressure between the two sam-  
connections may be used if desired.  
pling tubes. The differential pressure should measure at least  
Smoke detectors and alarm system control panels have 0.0015 inches of water and no more than 1.2 inches of water.  
specifications for allowable loop resistance. Consult the Because most commercially available manometers cannot  
control panel manufacturer’s specifications for the total accurately measure very low pressure differentials, applica-  
loop resistance allowed for the particular model control tions with less than 500 FPM of duct air speed may require  
panel being used before wiring the detector loop.  
one of the following: 1) the use of a current-sourcing pressure  
transmitter (Dwyer Series 607) per Section 6.1.4 or; 2) the use  
of aerosol smoke per section 6.1.2.  
Wiring Instructions  
The DH100LP detectors are designed for easy wiring. The  
housing provides a terminal strip with clamping plates. [6.1.2] Air Flow Test using Aerosol Smoke  
Wiring connections are made by stripping about 3/8-inch This test is intended for low-flow systems (100-500FPM).  
of insulation from the end of the wire, sliding the bare end If the air speed is greater than 500FPM, use a conventional  
under the plate, and tightening the clamping plate screw.  
manometer to measure differential pressure between the  
1
The DH100LP duct smoke detector is designed to operate sampling tubes as described in 6.1.1. Drill a ⁄4” hole 3  
with 12 or 24 VDC UL listed 2-wire compatible control pan- feet upstream from the duct smoke detector. With the air  
els. Alarm current must be limited by the control panel to handler on, measure the air velocity with an anemometer.  
100mA or less. An example of a UL listed compatible con- Air speed must be at least 100 FPM. Spray aerosol smoke*  
1
trol panel is the Fire-Lite model Sensiscan 1000 using zone into the duct through the ⁄4” hole for five seconds. Wait  
card ANC-2 and compatibility identification A”. Install per two minutes for the duct smoke detector to alarm. If the  
installation instruction S1000/801. A maximum of 20 detec- duct smoke detector alarms, air is flowing through the  
tors may be installed per zone.  
detector. Remove the duct smoke detector cover and blow  
out the residual aerosol smoke from the chamber and reset  
the duct smoke detector. Use duct tape to seal the aerosol  
smoke entry hole.  
[5.7] Perform Detector Check  
1. Perform STANDBY AND TROUBLE TEST per Section  
[6.2.1].  
2. Perform MAGNET TEST per Section [6.2.2.1]. The  
RTS451 test of Section [6.2.2.2] may substitute for this  
requirement.  
*Aerosol smoke can be purchased from Home Safeguard Industries,  
Malibu, CA. Phone: 310/457-5813.  
[6.1.3] Smoke Entry Test  
To determine if smoke is capable of entering the sens-  
ing chamber, visually identify any obstructions. Plug the  
exhaust and inlet tube holes to prevent ducted air from  
carrying smoke away from the detector head, then blow  
smoke such as cigarette, cotton wick, or punk directly at  
the head to cause an alarm. REMEMBER TO REMOVE THE  
PLUGS AFTER THIS TEST, OR THE DETECTOR WILL NOT  
FUNCTION PROPERLY.  
3. Perform AIR FLOW TEST per Section [6.1.1].  
4. Perform SMOKE RESPONSE TEST per Section [6.1.2].  
5. Perform SENSITIVITY TEST per Section [6.2.3].  
[5.8] Install The Cover  
Install the cover using the six screws that are captured in  
the housing cover. Be certain filters are installed as speci-  
fied in Section [5.5]. Make sure that the cover fits into the  
base groove and that all gaskets are in their proper posi-  
tions. Tighten the six screws.  
[6.1.4] Air Flow Test using Dwyer Series 607  
Differential Pressure Transmitter  
[6] Duct Smoke Detector Maintenance And Test  
Procedures  
Test and maintain duct smoke detectors as recommended  
in NFPA 72. The tests contained in this manual were  
devised to assist maintenance personnel in verification of  
proper detector operation.  
Verify the air speed of the duct using an anemometer. Air  
speed must be at least 100 FPM. Wire the Dwyer transmit-  
ter as shown in Figure 7. Connect the leads of the meter  
to either side of the 1000Ω resistor. Allow unit to warm up  
for 15 seconds. With both HIGH and LOW pressure ports  
open to ambient air, measure and record the voltage drop  
acrossthe 1000Ω resistor (measurement 1), 4.00 volts is  
typical. Using flexible tubing and rubber stoppers, connect  
the HIGH side of the transmitter to the sampling tube of  
Before conducting these tests, notify the proper authorities  
that the smoke detection system will be temporarily out of  
D200-15-00  
5
I56-0083-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
the duct smoke detector housing, and the LOW side of the [6.1.5] Filter Replacement  
transmitter to the exhaust tube of the duct smoke detec- The filters do not substantially affect smoke performance  
tor housing. Measure and record the voltage drop across even when up to 90% of the filter is clogged. Quarterly  
the 1000Ω resistor (measurement 2). Subtract the voltage visual inspection usually suffices to determine whether the  
recorded in measurement 1 from the voltage recorded in filters should be replaced because only a high percentage  
measurement 2. If the difference is greater than 0.15 volts, of contamination affects performance. If further testing is  
there is enough air flow through the duct smoke detector required, compare differential pressure readings with and  
for proper operation.  
without the filters installed. If the difference exceeds 10%  
replace the filters. In no case should the pressure differen-  
tial fall below 0.0015 inches of water.  
Figure 7. Procedure for verifying air flow:  
TO SAMPLING TUBE  
TO EXHAUST TUBE  
[6.2] Standby, Alarm, And Sensitivity Tests  
[6.2.1] Standby And Trouble  
HIGH  
LOW  
DIFFERENTIAL  
Standby — Look for the presence of the flashing green  
LED through the transparent housing cover.  
The LED should flash approximately every 10  
seconds.  
PRESSURE  
TRANSMITTER  
15 TO 36VDC  
SUPPLY  
9 VOLT  
BATTERY  
9 VOLT  
BATTERY  
1000 OHM 5% 1 WATT RESISTOR  
9 VOLT  
Trouble — If the Green LED does not flash, then the de-  
tector lacks power (check wiring, panel, or  
power supply), the detector board is missing  
(replace), or the unit is defective (return for  
replacement).  
BATTERY  
VOLT METER  
FLUKE MODEL 87  
OR EQUIVALENT  
Figure 8. System wiring diagram for 2-wire duct smoke detectors (detectors powered from initiating circuit):  
CAUTION  
Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.  
UL LISTED  
COMPATIBLE 2-WIRE  
CONTROL PANEL  
1ST DETECTOR  
IN LOOP DH100LP  
LAST DETECTOR  
IN LOOP DH100LP  
EOL RESISTOR  
DETECTOR  
BOARD  
DETECTOR  
BOARD  
SPECIFIED BY  
PANEL MANUFACTURER  
7
6
7
6
(+)  
(+) IN  
(+) OUT  
(+) IN  
(+) OUT  
(+)  
(–)  
(+)  
(–)  
4
4
(+)  
(–)  
(+)  
(–)  
E
RA400Z (OPTIONAL)  
REMOTE ALARM LED  
RA400Z (OPTIONAL)  
O
L
REMOTE ALARM LED  
ALARM  
INITIATION  
LOOP  
R
5
8
5
8
2.8 VDC NOM.  
IN ALARM  
2.8 VDC NOM.  
IN ALARM  
(–) IN  
(–) OUT  
(–) IN  
(–) OUT  
(–)  
STYLE D OPTIONAL WIRING  
A78-2696-00  
Figure 9. Wiring diagram for the DH100LP to RTS451/RTS451KEY:  
DH100LP  
Test +  
RTS451/RTS451KEY  
Test  
5
1
2
3
4
5
Test / Reset –  
Reset +  
RA +  
4
3
1
2
Alarm  
Reset  
LED  
RA –  
A78-2697-00  
D200-15-00  
6
I56-0083-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Test —  
The trouble condition can be caused inten- If test module readings indicate that the detector head is  
tionally to verify correct operation of the sys- outside of the acceptable range that is printed on the label  
tem. Remove the detector board to cause a of the detector, the detector requires cleaning per Section  
trouble condition locally and at the system [7] of this manual.  
control panel.  
[7] Detector Cleaning Procedures  
[6.2.2] Alarm Tests  
[6.2.2.1] M02-04-00 Magnet Test  
Notify the proper authorities that the smoke detector sys-  
tem is undergoing maintenance, and that the system will  
1. Place the painted surface of the magnet onto the TEST temporarily be out of service. Disable the zone or system  
locator on the bottom of the housing (Figure 9). undergoing maintenance to prevent unwanted alarms and  
2. The red alarm LEDs on the detector should latch on, possible dispatch of the fire department.  
as should any accessories (i.e. RA400Z, RTS451). Verify  
system control panel alarm status, and control panel [7.1] Air Filters  
execution of all intended auxiliary functions (i.e. fan 1. Turn off power to the system.  
shutdown, damper control, etc.).  
2. Remove and inspect sampling tube filters.  
3. The detector must be reset by the system control panel, 3. If filters are heavily coated with dirt, replace them with  
the local reset button, or the remote accessory.  
new filters. If they are not heavily coated, use a vacuum  
cleaner or compressed air nozzle to remove dust, then  
reinstall the filters.  
Figure 10. Testing detector alarm:  
[7.2] Photo Detector Boards  
1. Remove the screen by gently grasping on each side and  
pulling straight off  
2. Lift the photo chamber in the same fashion. Vacuum  
the screen and cover. Use clean, compressed air to  
loosen and blow out any remaining debris. Replacement  
screens (S08-39-01) are available.  
3. Vacuum photo chamber, then use clean compressed air  
to blow area clean.  
4. Replace the chamber by pressing it onto the base. Press  
the screen into place. It should fit tightly on the chamber.  
[8.0] Board Replacement  
[8.1] Detector Board Replacement (part no. A5180)  
1. Remove the two detector board mounting screws.  
2. Pull gently on the board to remove it.  
3. To replace the board, align the board mounting features,  
holes, and the interconnect terminals. Push the board  
into place.  
4. Secure board with the two mounting screws.  
[8.2] Power Board replacement (part no. A5061)  
1. Disconnect wiring from the terminal block.  
2. Remove the two power board mounting screws.  
3. Pull gently on the board to remove it.  
4. To replace the board, align the board mounting features,  
holes, and the interconnect terminals. Push the board  
into place.  
[6.2.2.2] RTS451/RTS451KEY Remote Test Station  
The RTS451/RTS451KEY Remote Test Station facilitates  
test of the alarm capability of the duct smoke detector as  
indicated in the RTS451/RTS451KEY manual. The DH100LP  
duct smoke detector can be reset by the RTS451/RTS451KEY.  
If a system control panel is used, the panel itself may also  
require testing.  
To install the RTS451/RTS451KEY, connect the device as  
shown in Figure 9; wire runs must be limited to 25 ohms  
or less per interconnecting wire.  
[6.2.3] Sensitivity Tests  
[6.2.3.1] MOD400 or MOD400R Test  
After verification of alarm capability, use the MOD400R test  
module with a voltmeter to check detector sensitivity as  
indicated in the test module’s manual. The housing cover  
must be removed to perform this test.  
5. Secure board with the two mounting screws.  
6. Re-connect wiring to terminal block.  
D200-15-00  
7
I56-0083-07R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
[9] Model DH100LP Air Duct Smoke Detector Specifications  
Operating Temperature:  
Storage Temperature:  
Humidity:  
Air Velocity:  
Dimensions:  
+32° to +131° F  
–22° to +158° F  
10% to 93% R.H. noncondensing  
100 to 4000 ft./min.  
14.38” L x 5.5” W x 2.75” D  
3.25 pounds  
0° to +55° C  
–30° to +70° C  
0.5 to 20.3 m/sec.  
36.5cm L x 14cm W x 7cm D  
1.5 kg  
Weight:  
Electrical Ratings — includes base and detector  
System Voltage:  
12/24 VDC  
Maximum Ripple Voltage:  
Start-up Capacitance:  
Standby Ratings:  
4 Volts peak to peak  
0.02 µF maximum  
8.5 VDC minimum  
35 VDC maximum  
120 µA maximum  
Alarm Ratings:  
4.2 VDC minimum at 10mA  
6.6 VDC maximum at 130mA  
Alarm current must be limited to 130mA or less by the control panel.  
If used, the RA400Z remote lamp operates within the specified alarm currents.  
Reset Voltage:  
Reset Time:  
Start-up Time:  
2.50 VDC minimum  
0.3 Sec. maximum  
34.0 Sec. maximum  
Please refer to insert for the Limitations of Fire Alarm Systems  
Three-Year Limited Warranty  
System Sensor warrants its enclosed air duct smoke detector to be free  
Avenue, St. Charles, IL 60174. Please include a note describing the mal-  
function and suspected cause of failure. The Company shall not be obli-  
gated to repair or replace units which are found to be defective because  
of damage, unreasonable use, modifications, or alterations occurring  
after the date of manufacture. In no case shall the Company be liable for  
any consequential or incidental damages for breach of this or any other  
Warranty, expressed or implied whatsoever, even if the loss or damage is  
caused by the Company’s negligence or fault. Some states do not allow  
the exclusion or limitation of incidental or consequential damages, so the  
above limitation or exclusion may not apply to you. This Warranty gives  
you specific legal rights, and you may also have other rights which vary  
from state to state.  
from defects in materials and workmanship under normal use and ser-  
vice for a period of three years from date of manufacture. System Sensor  
makes no other express warranty for this air duct smoke detector. No  
agent, representative, dealer, or employee of the Company has the author-  
ity to increase or alter the obligations or limitations of this Warranty. The  
Company’s obligation of this Warranty shall be limited to the repair or  
replacement of any part of the air duct smoke detector which is found to  
be defective in materials or workmanship under normal use and service  
during the three year period commencing with the date of manufacture.  
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672)  
for a Return Authorization number, send defective units postage prepaid  
to: System Sensor, Returns Department, RA #__________, 3825 Ohio  
D200-15-00  
8
I56-0083-07R  
2003 System Sensor  
©
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sherwood Stereo Receiver RX 765 User Manual
Sony Digital Camera SRS U10 User Manual
Sony Microcassette Recorder M 427 User Manual
SoundCraft Music Mixer MPM 12 2 User Manual
Sprint Nextel Cell Phone PG86100 User Manual
StarTechcom Switch SV431DVIUAHR User Manual
StudioTech Network Router M46 00180 User Manual
Sylvania DVD Player dbc840e User Manual
Sylvania MP3 Player SMP2012 User Manual
Sylvania TV VCR Combo 6720FDF User Manual