INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
DH100 Air Duct Smoke Detector
Before Installing
DH100 detectors are designed to operate with 12 or 24
Please thoroughly read the System Sensor Guide for Proper VDC UL listed compatible 2-wire control panels. Alarm
Use of Smoke Detectors in Duct Applications (I56-473), current must be limited to 100mA or less by the control
which provides detailed information on detector spacing, panel. Auxiliary relay contacts for control purposes are
placement, zoning, wiring, and special applications. Cop- not available for use with the DH100. Control must ini-
ies of this manual are available from System Sensor. NFPA tiate from the control panel.
Standards 72 and 90A should also be referenced for de-
tailed information.
For testing, the alarm can be enabled by a magnet acti-
vated test switch or by the optional remote test station.
NOTICE: This manual should be left with the owner/user The duct smoke detector latches into alarm state when
of this equipment.
an alarm occurs. A green LED flashes to indicate power,
a red LED signals local alarm indication, and optional
IMPORTANT: This detector must be tested and maintained accessories offer a variety of annunciation capabilities.
regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.
The DH100 can be reset by a momentary power interrup-
tion, the reset button on the front cover, the control panel,
or remote reset accessory.
Table of Contents
Page
[1] General Description
[2] Limitations of Duct Smoke Detectors
1
1
[2] Limitations Of Duct Smoke Detectors
[3] Exploded View of Duct Smoke Detector Components 2
WARNING
[4] Contents of the Duct Smoke Detector Kit
[5] Installation Sequence
[6] Duct Smoke Detector Maintenance and Test Procedures 5
[7] Detector Cleaning Procedures
[8] Board Replacement
[9] Specifications
2
2
The National Fire Protection Association has established
that DUCT DETECTORS MUST NOT BE USED AS A SUB-
STITUTE FOR OPEN AREA DETECTOR PROTECTION as a
means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.
7
7
8
8
Warranty
System Sensor supports this position and strongly recom-
mends that the user read NFPA Standards 90A, 72, and 101.
The DH100 Air Duct Smoke Detectors are listed per UL 268A.
[1] General Description
An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense
the presence of smoke in the duct.
WARNING
This device will not operate without electrical power.
Fire situations may cause an interruption of power. The
system safeguards should be discussed with your local fire
protection specialist.
Model DH100 Air Duct Smoke Detectors are supplied as a
photoelectronic model. This smoke detection method is
combined with an efficient housing design that samples air
passing through a duct and allows detection of a develop-
ing hazardous condition. When sufficient smoke is sensed,
an alarm signal is initiated at the fire control panel monitor-
ing the detector, and appropriate action can be taken to
shut off fans, blowers, change over air handling systems,
etc. These actions can facilitate the management of toxic
smoke and fire gases throughout the areas served by the
duct system.
WARNING
This device will not sense smoke unless the ventilation sys-
tem is operating and the cover is installed.
WARNING
For this detector to function properly, it MUST be installed
according to the instructions in this manual. Furthermore,
the detector MUST be protected from the elements and op-
erated within ALL electrical and environmental specifica-
tions listed in this manual. Failure to comply with these
requirements may prevent the detector from activating
when smoke is present in the air duct.
D100-67-00
1
I56-1148-04
Download from Www.Somanuals.com. All Manuals Search And Download.
[5.3] Secure The Detector Housing To The Duct
Slide the foam gaskets over the tube bushings as shown in
Figure 3. Use the two machine screws to screw the detector
housing to the duct.
the inlet tube. Make sure the hole is 1″ to 2″ below the in-
let hole on the opposite side of the duct to allow for mois-
ture drainage. If the tube is shorter than the width of the air
duct, install the end plug into the inlet tube as shown in
Figure 4. Sampling tubes over 3 ft. long must be supported
at the end opposite the duct detector.
CAUTION: Do not overtighten the screws.
Figure 3. Installation of foam gaskets over sampling
tube bushings:
2. Slide the tube into the housing bushing that meets the
air flow first. Position the tube so that the arrows point
into the air flow.
3. Secure the tube flange to the housing bushing with two
#6 self-tapping screws.
4. For tubes longer than the width of the air duct, the tube
should extend out of the opposite side of the duct. If
there are more than 2 holes in the section of the tube ex-
tending out of the duct, select a different length using
Table 1. Otherwise, trim the end of the tube protruding
through the duct so that 1″ to 2″ of the tube extend out-
side the duct. Plug this end with the end plug and tape
closed any holes in the protruding section of the tube. Be
sure to seal the duct when the tube protrudes.
A78-2045-00
[5.4] Sampling Tube Installation of Ducts Greater
Than 11/2 Feet Wide
Figure 4. Air duct detector inlet sampling tube:
The sampling tube is identified by a series of air inlet holes
on the tube. One telescoping tube is included for ducts up
to 18″ in width. All other lengths must be purchased sepa-
rately. Order the correct length, as specified in Table 1, for
width of the duct where it will be installed. The exhaust
tube is molded onto the base of the duct housing, and the
A2440-00 Exhaust Tube Extension is available as an acces-
sory in those cases where the molded exhaust port does not
extend at least 2 inches into the duct.
AIR HOLES
INLET
TUBE
END
FLANGE
PLUG
ARROWS
MUST FACE
INTO AIR FLOW
AIR FLOW DIRECTION
A78-2047-00
The inlet tube is always installed with the air inlet holes
facing into the air flow. To assist proper installation, the
tube’s mounting flange is marked with arrows. Make sure
the inlet tube is mounted so that the arrows point into the
air flow (see Figure 4). Figure 5 shows the various combi-
nations of tube mounting configurations with respect to air
flow. Mounting the detector housing in a vertical orienta-
tion is acceptable, provided that the air flows directly into
the sampling tube holes as indicated in Figure 4.
Figure 5. Tube mounting configurations with varying
air flow direction:
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
AIR FLOW
AIR FLOW
DIRECTION
DIRECTION
DUCT
DUCT
DETECTOR
DETECTOR
HOUSING
HOUSING
B.
A.
Table 1. Inlet tubes required for different duct
widths:
INLET
TUBE
EXHAUST
TUBE
EXHAUST
TUBE
INLET
TUBE
AIR FLOW
DIRECTION
Outside Duct Width
1 to 2 ft.
Inlet Tube Required
INLET
TUBE
EXHAUST
TUBE
ST-1.5
ST-3
ST-5
2 to 4 ft.
4 to 8 ft.
DUCT
DETECTOR
HOUSING
DUCT
DETECTOR
HOUSING
8 to 12 ft.
ST-10
D.
C.
[5.4.1] Installation For Ducts Greater Than 1 1/2 Feet
But Less Than 8 Feet Wide
INLET
TUBE
EXHAUST
TUBE
AIR FLOW
DIRECTION
NOTE: Orientations C and D apply only to metal sampling tubes.
1. If the tube is longer than the width of the air duct, drill a
A78-1812-08
3
/4-inch hole in the duct opposite the hole already cut for
D100-67-00
3
I56-1148-04
Download from Www.Somanuals.com. All Manuals Search And Download.
[5.4.3] Modifications of Inlet Sampling Tubes
There may be applications where duct widths are not what
is specified for the installation. In such cases, it is permis-
sible to modify an inlet sampling tube that is longer than
necessary to span the duct width.
WARNING
In no case should more than 2 air inlet holes be cut off the
tube. There must be a minimum of 10 holes in the tube ex-
posed to the air stream.
[5.4.2] Installation For Ducts More Than 8 Feet Wide
NOTE: To install inlet tubes in ducts more than 8 feet wide,
work must be performed inside the air duct. Sampling
of air in ducts wider than 8 feet is accomplished by
using the ST-10 inlet sampling tube. If the tube is
shorter than the width of the air duct, install the end
plug into the inlet tube as shown in Figure 4 and sup-
port the end opposite the duct smoke detector.
Use a 0.193-inch diameter (#11) drill and add the appropriate
number of holes so that the total number of holes exposed to
the air flow in the duct is 10 to 12. Space the additional holes
as evenly as possible over the length of the tube.
NOTE: This procedure should only be used as a temporary
fix. It is not intended as a permanent substitute for
ordering the correct length tubes.
Install the inlet tube as follows:
[5.5] Install The Filters
1. Drill a 3/4-inch hole in the duct opposite the hole already
drilled for the inlet tube. Drill the hole 1″ to 2″ below the
inlet hole on the opposite side of the duct to allow for
moisture drainage away from the detector.
To install the sampling tube filters, simply push the filters
into the sampling and exhaust tube holes as shown in Fig-
ure 6. If a metal sampling tube is used, install the filter over
the sampling tube.
2. Slide the inlet tube with the flange into the housing bush-
ing that meets the air flow first. Position the tube so that
the arrows point into the air flow. Secure the tube flange to
the housing bushing with two #6 self-tapping screws.
3. From inside the duct, couple the other sections of the in-
let tube to the section already installed using the 1/2-inch
conduit fittings supplied. Make sure that the holes on
both of the air inlet tubes are lined up and facing into
the air flow.
Figure 6. Sampling tube filter installation:
4. Trim the end of the tube protruding through the duct so
that 1″ to 2″ of the tube extend outside the duct. Plug
this end with the end plug and tape closed any holes in
the protruding section of the tube. Be sure to seal the
duct when the tube protrudes.
A78-2106-01
CAUTION
NOTE: An alternate method to using the ST-10 is to use
two ST-5 inlet tubes. Remove the flange from one
of the tubes and install as described above. After
the installation, use electrical tape to close off
some of the sampling holes so that there are a total
of 10 to 12 holes spaced as evenly as possible
across the width of the duct.
Filters require periodic cleaning or replacement, depending
on the amount of dust and dirt accumulated. Visually in-
spect the filters at least quarterly; inspect them more often
if the dust accumulation warrants it. See Section [6] for
more information. Replacement filters can be ordered from
System Sensor, 3825 Ohio Ave., St. Charles, IL 60174. (Ex-
haust tube/intake tube filter P/N F36-09-00)
NOTE: Air currents inside the duct may cause excessive
vibration, especially when the longer sampling
tubes are used. In these cases a 3 inch floor flange
(available at most plumbing supply stores) may be
used to fasten the sampling tube to the other side
of the duct. When using the flange/connector
mounting technique, drill a 1″ to 11/4″ inch hole
where the flange will be used.
[5.6] Field Wiring
Wiring Installation Guidelines
All wiring must be installed in compliance with the Na-
tional Electrical Code and the local codes having jurisdic-
tion. Proper wire gauges should be used. The conductors
used to connect smoke detectors to control panels and ac-
cessory devices should be color-coded to prevent wiring
mistakes. Improper connections can prevent a system from
responding properly in the event of a fire.
D100-67-00
4
I56-1148-04
Download from Www.Somanuals.com. All Manuals Search And Download.
For signal wiring, (the wiring between interconnected de- Before conducting these tests, notify the proper authorities
tectors or from detectors to auxiliary devices), it is usually that the smoke detection system will be temporarily out of
recommended that single conductor wire be no smaller service. Disable the zone or system under test to prevent
than 18 gauge. The duct smoke detector terminals accom- unwanted alarms.
modate wire sizes up to 12 gauge. The last foot of conduit
should be flexible conduit (available in electrical supply [6.1] Smoke Entry Tests
houses), which facilitates easier installation and puts less [6.1.1] Air Flow
strain on the conduit holes in the housing. Solid conduit To verify sufficient sampling of ducted air, use a manometer
connections may be used if desired.
to measure the differential pressure created from air flow
across the sampling tubes. The pressure should measure no
Smoke detectors and alarm system control panels have less than 0.03 inches of water and no greater than 1.4 inches
specifications for allowable loop resistance. Consult the of water. The air handler must be operating for this test.
control panel manufacturer’s specifications for the total
loop resistance allowed for the particular model control [6.1.2] Smoke Response
panel being used before wiring the detector loop.
To determine if smoke is capable of entering the sensing
chamber, visually identify any obstructions. Plug the ex-
haust and inlet tube holes to prevent ducted air from carry-
Wiring Instructions
The DH100 detectors are designed for easy wiring. The ing smoke away from the detector head, then blow smoke
housing provides a terminal strip with clamping plates. such as cigarette, cotton wick, or punk directly at the head
Wiring connections are made by stripping about 3/8-inch of to cause an alarm. REMEMBER TO REMOVE THE PLUGS
insulation from the end of the wire, sliding the bare end un- AFTER THIS TEST, OR THE DETECTOR WILL NOT FUNC-
der the plate, and tightening the clamping plate screw.
TION PROPERLY.
The DH100 duct smoke detector is designed to operate with [6.1.3] Filter Replacement
12 or 24 VDC UL listed 2-wire compatible control panels. The filters do not substantially affect smoke performance
Alarm current must be limited by the control panel to even when up to 90% of the filter is clogged. Quarterly vi-
100mA or less. An example of a UL listed compatible con- sual inspection usually suffices to determine whether the
trol panel is the Fire-Lite model Sensiscan 1000 using zone filters should be replaced because only a high percentage of
card ANC-2 and compatibility identification “A”. Install per contamination affects performance. If further testing is re-
installation instruction S1000/801. A maximum of 20 detec- quired, compare differential pressure readings with and
tors may be installed per zone.
without the filters installed. If the difference exceeds 10%
replace the filters. In no case should the pressure differen-
tial fall below 0.03 inches of water.
[5.7] Perform Detector Check
1. Perform STANDBY AND TROUBLE TEST per Section
[6.2.1].
[6.2] Standby, Alarm, And Sensitivity Tests
2. Perform MAGNET TEST per Section [6.2.2.1]. The [6.2.1] Standby And Trouble
RTS451 test of Section [6.2.2.2] may substitute for this Standby — Look for the presence of the flashing green
requirement.
LED through the transparent housing cover.
The LED should flash approximately every 10
seconds.
3. Perform AIR FLOW TEST per Section [6.1.1].
4. Perform SMOKE RESPONSE TEST per Section [6.1.2].
5. Perform SENSITIVITY TEST per Section [6.2.3].
Trouble — If the Green LED does not flash, then the de-
tector lacks power (check wiring, panel, or
power supply), the detector board is missing
(replace), or the unit is defective (return for
repair)
[5.8] Install The Cover
Install the cover using the four screws that are captured in
the housing cover. Be certain filters are installed as speci-
fied in Section [5.5]. Make sure that the cover fits into the
base groove and that all gaskets are in their proper posi-
tions. Tighten the four screws.
Test —
The trouble condition can be caused inten-
tionally to verify correct operation of the sys-
tem. Remove the detector board to cause a
trouble condition locally and at the system
control panel.
[6] Duct Smoke Detector Maintenance And Test
Procedures
Test and maintain duct smoke detectors as recommended in NFPA
72. The tests contained in this manual were devised to assist main-
tenance personnel in verification of proper detector operation.
D100-67-00
5
I56-1148-04
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 7. System wiring diagram for 2-wire duct smoke detectors (detectors powered from initiating circuit):
CAUTION
Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.
UL LISTED
COMPATIBLE 2-WIRE
CONTROL PANEL
1ST DETECTOR
IN LOOP DH100
LAST DETECTOR
IN LOOP DH100
EOL RESISTOR
SUPERVISORY
SWITCH
SUPERVISORY
SWITCH
SPECIFIED BY
PANEL MANUFACTURER
7
6
7
6
(+)
(+) IN
(+) OUT
(+) IN
(+) OUT
(+)
(–)
(+)
(–)
4
4
(+)
(–)
(+)
(–)
E
RA400Z (OPTIONAL)
REMOTE ALARM LED
RA400Z (OPTIONAL)
O
L
REMOTE ALARM LED
ALARM
INITIATION
LOOP
R
5
8
5
8
2.8 VDC NOM.
IN ALARM
2.8 VDC NOM.
IN ALARM
(–) IN
(–) OUT
(–) IN
(–) OUT
(–)
STYLE D OPTIONAL WIRING
Figure 8. Wiring diagram for RTS451/RTS451KEY Remote Test Station to 2-wire duct smoke detectors:
7
8
V In +
V In / V Out –
DH100
Test +
RTS451 KEY
Test
5
1
2
3
4
5
6
7
8
Test / Reset –
Reset +
4
3
1
2
Alarm
LED
RA +
Reset
RA –
V Out +
V In +
6
No Connection
Panel
+
V In / V Out –
–
A78-2350-00
D100-67-00
6
I56-1148-04
Download from Www.Somanuals.com. All Manuals Search And Download.
[6.2.2] Alarm Tests
[7] Detector Cleaning Procedures
[6.2.2.1] M02-04-00 Magnet Test
Notify the proper authorities that the smoke detector sys-
1. Place the painted surface of the magnet onto the TEST tem is undergoing maintenance, and that the system will
locator on the bottom of the housing (Figure 9). temporarily be out of service. Disable the zone or system
2. The red alarm LEDs on the detector should latch on, as undergoing maintenance to prevent unwanted alarms and
should any accessories (i.e. RA400Z, RTS451). Verify possible dispatch of the fire department.
system control panel alarm status, and control panel ex-
ecution of all intended auxiliary functions (i.e. fan shut- [7.1] Air Filters
down, damper control, etc.).
1. Turn off power to the system.
3. The detector must be reset by the system control panel, 2. Remove and inspect sampling tube filters.
the local reset button, or the remote accessory.
3. If filters are heavily coated with dirt, replace them with
new filters. If they are not heavily coated, use a vacuum
cleaner or compressed air nozzle to remove dust, then
reinstall the filters.
Figure 9. Testing detector alarm:
[7.2] Photo Detector Boards
1. Remove the screen by gently grasping on each side and
pulling straight off
2. Lift the photo chamber in the same fashion. Vacuum the
screen and cover. Use clean, compressed air to loosen
and blow out any remaining debris. Replacement
screens (S08-39-01) are available.
3. Vacuum photo chamber, then use clean compressed air
to blow area clean.
4. Replace the chamber by pressing it onto the base. Press
the screen into place. It should fit tightly on the chamber.
[8.0] Board Replacement
[8.1] Detector Board Replacement
A78-2325-00
1. Remove the two detector board mounting screws.
2. Pull gently on the board to remove it.
3. To replace the board, align the board mounting fea-
tures, holes, and the interconnect terminals. Push the
board into place.
[6.2.2.2] RTS451/RTS451KEY Remote Test Station
The RTS451/RTS451KEY Remote Test Station facilitates test
of the alarm capability of the duct smoke detector as indi-
cated in the RTS451/RTS451KEY manual. The DH100 duct
smoke detector can be reset by the RTS451/RTS451KEY. If a
system control panel is used, the panel itself may also re-
quire testing.
4. Secure board with the two mounting screws.
[8.2] Power Board replacement
1. Disconnect wiring from the terminal block.
2. Remove the two power board mounting screws.
3. Pull gently on the board to remove it.
4. To replace the board, align the board mounting fea-
tures, holes, and the interconnect terminals. Push the
board into place.
To install the RTS451/RTS451KEY, connect the device as
shown in Figure 8; wire runs must be limited to 25 ohms or
less per interconnecting wire.
5. Secure board with the two mounting screws.
6. Re-connect wiring to terminal block.
[6.2.3] Sensitivity Tests
[6.2.3.1] MOD400 or MOD400R Test
After verification of alarm capability, use the MOD400R test
module with a voltmeter to check detector sensitivity as in-
dicated in the test module’s manual. The housing cover
must be removed to perform this test.
If test module readings indicate that the detector head is
outside of the acceptable range that is printed on the label
of the detector, the detector requires cleaning per Section
[7] of this manual.
D100-67-00
7
I56-1148-04
Download from Www.Somanuals.com. All Manuals Search And Download.
[9] Model DH100 Air Duct Smoke Detector Specifications
Temperature:
Humidity:
Air Velocity:
Dimensions:
Weight:
32° to 131° F
0° to 55° C
10% to 93% R.H. noncondensing
500 to 4000 ft./min.
14.38″ L x 5.5″ W x 2.75″ D
3.25 pounds
2.5 to 20.3 m/sec.
36.5cm L x 14cm W x 7cm D
1.5 kg
Electrical Ratings — includes base and detector
System Voltage:
12/24 VDC
Maximum Ripple Voltage:
Start-up Capacitance:
Standby Ratings:
4 Volts peak to peak
0.02 µF maximum
8.5 VDC minimum
35 VDC maximum
120 µA maximum
Alarm Ratings:
4.2 VDC minimum at 10mA
6.6 VDC maximum at 100mA
Alarm current must be limited to 100mA or less by the control panel.
If used, the RA400Z remote lamp operates within the specified alarm currents.
Reset Voltage:
Reset Time:
Start-up Time:
2.50 VDC minimum
0.3 Sec. maximum
34.0 Sec. maximum
Three-Year Limited Warranty
System Sensor warrants its enclosed air duct smoke detector to be free
from defects in materials and workmanship under normal use and service
for a period of three years from date of manufacture. System Sensor makes
no other express warranty for this air duct smoke detector. No agent, rep-
resentative, dealer, or employee of the Company has the authority to in-
crease or alter the obligations or limitations of this Warranty. The
Company’s obligation of this Warranty shall be limited to the repair or re-
placement of any part of the air duct smoke detector which is found to be
defective in materials or workmanship under normal use and service dur-
ing the three year period commencing with the date of manufacture. After
phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a
Return Authorization number, send defective units postage prepaid to:
System Sensor, Repair Department, RA #__________, 3825 Ohio Avenue,
St. Charles, IL 60174. Please include a note describing the malfunction and
suspected cause of failure. The Company shall not be obligated to repair
or replace units which are found to be defective because of damage, un-
reasonable use, modifications, or alterations occurring after the date of
manufacture. In no case shall the Company be liable for any consequential
or incidental damages for breach of this or any other Warranty, expressed
or implied whatsoever, even if the loss or damage is caused by the
Company’s negligence or fault. Some states do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation
or exclusion may not apply to you. This Warranty gives you specific legal
rights, and you may also have other rights which vary from state to state.