System Sensor Smoke Alarm 2W B User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS  
Series  
3825 Ohio Avenue, St. Charles, Illinois 60174  
1-800-SENSOR2, FAX: 630-377-6495  
Photoelectric Smoke Detector  
Models: 2W-B, 2WT-B  
4W-B, 4WT-B  
Before Installing  
Two LEDs on the detector provide a local visual indication of the  
detector’s status:  
Please read thoroughly System Sensor manual A05-1003,  
Applications Guide for System Smoke Detectors, which provides  
detailed information on detector spacing, placement, zoning, wir-  
ing, and special applications. Copies of this manual are available  
from System Sensor at no charge.  
Table 1: Detector LED Modes  
Green LED  
Red LED  
Blink 10 sec  
Power-up  
Blink 10 sec  
NOTICE: This manual shall be left with the owner/user of this  
equipment.  
Normal (standby)  
Out of sensitivity  
Freeze Trouble  
Alarm  
Blink 5 sec  
Blink 5 sec  
Blink 10 sec  
Solid  
IMPORTANT: This detector must be tested and maintained regu-  
larly following NFPA 72 requirements. At a minimum, cleaning  
should be performed annually.  
After an initial power-up delay, the red and green LEDs will blink  
synchronously once every ten seconds. It will take approximately 80  
seconds for the detector to finish the power-up cycle (see Table 2).  
General Description  
Models 2W-B and 2WT-B are 2-wire photoelectric smoke detec-  
tors; models 4W-B and 4WT-B are 4-wire photoelectric smoke  
detectors. All models incorporate a state-of-the-art optical sensing  
chamber and an advanced microprocessor. The microprocessor  
allows the detector to automatically adjust its sensitivity back  
to the factory setting when it becomes more sensitive due to  
contaminants settling in its chamber. In order for this feature  
to work properly, the chamber must never be opened while  
power is applied to the smoke detector. This includes cleaning,  
maintenance or screen replacement. Should it become necessary,  
the screen/sensing chamber is field replaceable. Models 2WT-B  
and 4WT-B also feature a restorable, built-in, fixed temperature  
(135°F) thermal detector and are also capable of sensing a freeze  
condition if the temperature is below 41°F.  
Table 2: Power-up Sequence for LED Status Indication*  
Condition  
Duration  
Initial LED Status Indication  
Initial LED Status Indication  
(if excessive electrical noise is present)  
80 seconds  
4 minutes  
*Refer to Electrical Specifications for start-up time in conjunction with panel alarm  
verification.  
NOTE: If, during power-up, the detector determines there is  
excessive electrical noise in the system such as those caused by  
improper grounding of the system or the conduit, both LEDs will  
blink for up to 4 minutes before displaying detector status (see  
Table 2).  
After power-up has completed and the detector is functioning  
normally within its listed sensitivity range, the green LED blinks  
once every five seconds. If the detector is in need of maintenance  
because its sensitivity has shifted outside the listed limits, the red  
LED blinks once every five seconds. When the detector is in the  
alarm mode, the red LED latches on. The LED indication must not  
be used in lieu of the tests specified under Testing. In a freeze  
trouble condition, the red LED will blink once every 10 seconds  
(refer to Table 1).  
All i3 Series detectors are designed to provide open area protec-  
tion. Two-wire models must be used with compatible UL Listed  
panels only.  
When used with an i3 Series compatible control panel or the i3  
Series 2W-MOD module (refer to installation manual D500-46-00),  
the 2W-B and 2WT-B are capable of generating a “maintenance  
needed” signal. The 2W-MOD can indicate a need for cleaning,  
replacement, or a freeze condition (2WT-B only) at the control  
panel or module.  
To measure the detector’s sensitivity, the i3 Series Model SENS-  
RDR Infrared Sensitivity Reader tool (see Figure 4) should be  
used.  
Installation of the 2W-B, 2WT-B, 4W-B, and 4WT-B detectors is  
simplified by the use of a mounting base that may be pre-wired  
to the system, allowing the detector to be easily installed or  
removed. The mounting base installation is further simplified by  
the incorporation of features compatible with drywall fasteners.  
Models 2W-B and 2WT-B also include an output that allows an  
optional Model RA400Z Remote Annunciator to be connected.  
Mounting  
Each i3 Series detector is supplied with a mounting base that can  
be mounted:  
1. To a single gang box, or  
2. To a 312-inch or 4-inch octagonal box, or  
3. To a 4-inch square box with a plaster ring, or  
4. Direct mount or to ceiling using drywall fasteners (Figure 2).  
D100-96-00  
1
I56-1800-08R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. If the detector is within the listed sensitivity limits, the  
detector’s red LED should light within five seconds.  
2-Wire i3 Detector Wired in Style D Configuration:  
CAUTION  
Figure 5: Recessed Test Switch Opening and SENS-RDR  
Position  
Any 2-wire i3 smoke detector (2W-B, 2WT-B, 2WTA-B, or 2WTR-B)  
wired in the Style D initiating device circuit (IDC) configuration  
requires the use of a 2W-MOD2 module. This is because fire  
alarm control panels vary by manufacturer on the implementa-  
tion of Style D circuits. Therefore, the only way to insure proper  
operation of 2-wire i3 smoke detectors (2W-B, 2WT-B, 2WTA-B, or  
2WTR-B) on Style D IDC’s is to use a 2W-MOD2 module. Refer  
to the 2W-MOD2 installation manual, document D500-46-00,  
for Style D wiring diagrams. The 2W-MOD2 installation  
manual may be downloaded from the System Sensor web site  
POSITION SENS-RDR  
AT AN ANGLE ON THE  
OVAL AREA OR AT THE  
CHAMBER OPENING  
BY THE WORD “PAINT”  
LED  
PUSH RECESSED  
SWITCH WITH A  
0.18w MAX.  
DIAMETER TOOL  
RECESSED TEST SWITCH  
S0135-00  
B. Smoke Entry Test  
Hold a smoldering punk stick or cotton wick at the side of the  
detector and gently blow the smoke through the detector until  
it alarms.  
Installation  
WARNING  
C. Direct Heat Method (models 2WT-B and 4WT-B only)  
Using a 1000-1500 watt hair dryer, direct the heat toward either  
of the thermistors. Hold the heat source about 12 inches from  
the detector to avoid damage to the plastic.  
Remove power from alarm control unit or initiating device circuits  
before installing detectors.  
NOTE: To install units so that corresponding LEDs are lined up,  
refer to the “Green LED” indicator on the base.  
1. Wire the mounting base screw terminals per Figure 3a or  
Figure 3b, as applicable.  
NOTE: For the above tests, the detector will reset only after the  
power source has been momentarily interrupted.  
2. Place detector on the base and rotate clockwise. The detector  
will drop into the base and lock into place with a “click.  
3. After all detectors have been installed, apply power to the  
alarm control unit.  
If a detector fails any of the above test methods, its wiring should be  
checked and it should be cleaned as outlined in the Maintenance  
section. If the detector still fails, it should be replaced.  
Notify the proper authorities when the system is back in service.  
4. Test each detector as described in Testing.  
5. Reset all the detectors at the alarm control unit.  
6. Notify the proper authorities that the system is in operation.  
Loop Verification (models 2W-B and 2WT-B only)  
Loop verification is provided by the EZ Walk loop test feature.  
This feature is for use with i3 Series compatible control panels or  
the i3 Series 2W-MOD module only. The EZ Walk loop test verifies  
the initiating loop wiring and provides visual status indication at  
each detector.  
CAUTION  
Dust covers are an effective way to limit the entry of dust into  
the smoke detector sensing chamber. However, they may not  
completely prevent airborne dust particles from entering the detec-  
tor. Therefore, System Sensor recommends the removal of detectors  
before beginning construction or other dust producing activity. When  
returning the system to service, be sure to remove the dust covers  
from any detectors that were left in place during construction.  
1. Ensure proper wiring and power is applied. Wait approxi-  
mately six minutes before performing EZ Walk test.  
2. Place control panel or module in EZ Walk Test mode (refer  
to panel manufacturer’s manual or 2W-MOD manual D500-  
46-00).  
3. Observe the LEDs on each detector:  
Testing  
Table 3: EZ Walk Test Detector Modes  
Detectors must be tested after installation and following  
maintenance.  
Green LED  
Red LED  
Proper Operation  
Out of Sensitivity  
Freeze Condition  
Double blink 5 sec  
NOTE: Before testing, notify the proper authorities that mainte-  
nance is being performed and the system will be temporarily out  
of service. Disable the zone or system undergoing maintenance to  
prevent any unwanted alarms.  
Double Blink 5 sec  
Double Blink 10 sec  
NOTE: The EZ Walk loop test must not be used instead of alarm  
Ensure proper wiring and power is applied. After power up, allow  
80 seconds for the detector to stabilize before testing.  
testing.  
Maintenance  
Test i3 Series detectors as follows:  
A. Test Switch  
NOTE: Before performing maintenance on the detector, notify  
the proper authorities that maintenance is being performed and  
the system will be temporarily out of service. Disable the zone or  
system undergoing maintenance to prevent any unwanted alarms.  
Power must be removed from the detector before performing  
maintenance of any kind.  
1. An opening for the recessed test switch is located on the  
detector housing (See Figure 5).  
2. Insert a small screwdriver or allen wrench (0.18w max.) into  
the test switch opening; push and hold.  
D100-96-00  
3
I56-1800-08R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Remove the detector cover by turning counterclockwise. (See Figure 6: Removing/Replacing Screen/Sensing Chamber  
Figure 6.)  
REMOVABLE  
DETECTOR  
2. Vacuum the cover or use canned air to remove any dust or  
COVER  
debris.  
3. Remove the top half of the screen/sensing chamber by lifting  
straight up (Figure 6).  
SCREEN/SENSING  
CHAMBER  
(TOP HALF)  
4. Vacuum or use canned air to remove any dust or particles that  
are present on both chamber halves.  
5. Replace the top half of the screen/sensing chamber by align-  
ing the arrow on the screen/sensing chamber with the arrow  
on the housing. Press down firmly until the screen/sensing  
chamber is fully seated.  
6. Replace the detector cover by placing it over the screen/sensing  
DETECTOR  
HOUSING  
chamber and turning it clockwise until it snaps into place.  
S0136-00  
7. Reinstall the detector and test. (See the Testing section.)  
8. Notify the proper authorities when the system is back in service.  
Physical Specifications  
Heat Sensor  
Electrical Specifications 2-wire 4-wire  
System Voltage – Nominal: 12/24 12/24 Volts Non-polarized  
(Model 2WT-B and 4WT-B): 135°F (57.2°C)  
Freeze Trouble  
(Model 2WT-B and 4WT-B): 41°F (5°C)  
Operating Temperature Range:  
Min.:  
Max.:  
Max. Ripple Voltage:  
8.5  
35  
30  
8.5 Volts  
35 Volts  
30 % peak to peak  
of applied voltage  
50 µA average  
2W-B and 4W-B:  
32 to 120°F (0 to 49°C)  
Max. Standby Current:  
Peak Standby Current:  
Max. Alarm Current:  
(For 2W-B and 2WT-B,  
50  
100  
130  
2WT-B and 4WT-B:  
32 to 100°F (0 to 37.8°C)  
µA  
Operating Humidity Range:  
0 to 95% RH non-condensing  
20 mA 12 Volt Systems  
Storage Temperature Range: –4 to 158°F (–20 to 70°C)  
Diameter (including base):  
Height (including base):  
Weight:  
5.3 inches  
2.0 inches  
6.3 oz.  
panel must limit current) 130  
23 mA 24 Volt Systems  
0.5 Amp @ 30 V AC/DC  
0.3 sec  
Alarm Contact Ratings:  
Alarm Reset Time:  
0.3  
Max. Start-up Capacitance: 0.1  
µF  
Latching Alarm:  
Maximum Initial  
Start-up Time:  
Alarm Verification*  
Start-up Time:  
Reset by momentary power interruption  
45  
15  
15 sec  
15 sec  
*Assumes the panel’s alarm verification reset time is 10 seconds or less. Should the alarm verification reset exceed 10 seconds, use the maximum initial start-up time.  
Please refer to insert for the Limitations of Fire Alarm Systems  
Three-Year Limited Warranty  
System Sensor warrants its enclosed smoke detector to be free from defects in  
materials and workmanship under normal use and service for a period of three  
years from date of manufacture. System Sensor makes no other express war-  
ranty for this smoke detector. No agent, representative, dealer, or employee of  
the Company has the authority to increase or alter the obligations or limitations  
of this Warranty. The Company’s obligation of this Warranty shall be limited to  
the repair or replacement of any part of the smoke detector which is found to  
be defective in materials or workmanship under normal use and service during  
the three year period commencing with the date of manufacture. After phon-  
ing System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return  
Authorization number, send defective units postage prepaid to: System Sensor,  
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.  
Please include a note describing the malfunction and suspected cause of failure.  
The Company shall not be obligated to repair or replace units which are found to  
be defective because of damage, unreasonable use, modifications, or alterations  
occurring after the date of manufacture. In no case shall the Company be liable for  
any consequential or incidental damages for breach of this or any other Warranty,  
expressed or implied whatsoever, even if the loss or damage is caused by the  
Company’s negligence or fault. Some states do not allow the exclusion or limita-  
tion of incidental or consequential damages, so the above limitation or exclusion  
may not apply to you. This Warranty gives you specific legal rights, and you may  
also have other rights which vary from state to state.  
FCC Statement  
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this  
device must accept any interference received, including interference that may cause undesired operation.  
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to  
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if  
not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference  
will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the  
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:  
– Reorient or relocate the receiving antenna.  
– Increase the separation between the equipment and receiver.  
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.  
– Consult the dealer or an experienced radio/TV technician for help.  
D100-96-00  
4
I56-1800-08R  
©2005 System Sensor  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp Camcorder VL Z500E User Manual
Silvercrest Electric Heater SOR 2600 A1 User Manual
Sony Digital Camera 4 187 045 111 User Manual
Sony Ericsson Bluetooth Headset HBH GV435a User Manual
Sony MiniDisc Player MDS JA333ES User Manual
Sony Stereo Amplifier XM 440EX User Manual
Sony Video Game Console 3 285 687 11 User Manual
SpectraLink Telephone LINK 6020 User Manual
Spin Master Games Stink Blaster User Manual
Sylvania VCR 6221CVB User Manual