Sylvania Indoor Furnishings RM36 User Manual

SYLVANIA Emergency Lighting  
Installation Instructions  
Installation Instructions for Emergency Lights  
Model RM36  
SAVE THESE INSTRUCTIONS  
Before Installation, read instructions and understand all safety information.  
WHEN INSTALLING AND USING ELECTRICAL EQUIPMENT, ALL WORK SHOULD BE PERFORMED BY A LICENSED  
ELECTRICIAN AND BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING BUT NOT LIMITED TO  
THE FOLLOWING:  
WARNING  
To prevent shock or damage, turn power off before inspection, installation or removal.  
The use of accessory equipment is not recommended and may cause an unsafe condition.  
Do not use this electrical equipment for other than its specific intended purpose.  
This unit has been supplied with specified lamps. To avoid malfunction, use only lamps specified  
by manufacturer.  
To avoid risk of fire, do not store or place flammable materials near lamp.  
Use caution when changing or inspecting lamps as they can become hot and may cause burns if  
handled improperly.  
To avoid electrocution or property damage, do not install or use where exposed directly to water or  
outdoor weather conditions.  
This product contains a chemical known to the state of California to cause cancer, birth defects or other  
reproductive harm.  
INSTALLATION  
Step 1:  
Remove dust cover from unit by applying gentle, even pressure around edges. If you are installing the light during a  
building construction phase, please save dust cover for reinstallation to protect the unit prior to the final connection  
by electrician.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 2:  
Remove cover plate by first removing the screw caps and then unscrewing the screws. Save screws.  
Step 3:  
If installing into wall or ceiling of new construction, set adjustable flange to proper depth according to the  
thickness of the drywall you plan to use. Measure height and depth of installation and use two of the four  
screws or similar metal/wood screws to anchor the flange to the stud. A standard hanger bar can also be  
utilized for more stability.  
After installing the unit, secure interior plastic dust cover to metal unit box by lining the dust cover up with  
the screw holes on the metal box and applying gentle even pressure until it snaps into place. If cover does  
not fit properly, please tape in place for extra securing. This dust cover protects important electronic  
components within the unit from dust and debris, leave dust cover in place until final wiring connections  
are made and then discard. Final step is to install front painted cover plate with provided screws and plastic  
screw covers.  
If RETROFITTING installation into EXISITING drywall, set adjustable flanges to be even with top of metal  
box. Cut hole in ceiling or wall using provided plastic template and secure metal housing in using your  
desired drywall screws, or the ones provided with unit.  
If installing into drop ceiling, use a hanger bar designed to secure fixtures of similar weight. (Check  
specification sheet for weight.) Adjust flanges to proper depth of ceiling tile. Flange will secure above  
ceiling tile. This will provide additional support.  
Step 4:  
With no power to unit (AC circuit breaker switched o), feed AC wire through knockout (KO) on metal  
housing. Connect building wires to + RED and - BLACK 12Vdc leads on emergency light in accordance with  
NEC and/or local regulations.  
CAUTION  
Be sure to not cross the wires during connection or serious damage to the emergency light unit  
can occur.  
Step 5:  
Connect building wires to central battery unit. Please refer to the voltage drop information  
furnished with the central battery unit (sold separately) to ensure proper operation of the  
emergency light unit.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 6:  
Turn ON AC the power supply (circuit breaker) to emergency light unit. The green LED will light. To test unit,  
gently depress and hold the green LED button and the lens housing will automatically extend outward to  
the open position and the lamps will turn on. Release the green LED button and the unit will automatically  
retract and the lamps will turn off. Replace front cover plate via metal screws and screw cap covers. Green  
LED charge indicator will stay on as an indication that AC power is energizing the fixture and the internal  
rechargeable battery is charging.  
MAINTENANCE  
NOTICE  
Equipment should be tested regularly in accordance with local codes.  
NOTE: Servicing of parts should be performed by qualified service personnel. For replacement lamps  
or batteries see fixture labels.  
Painting or wallpapering front cover plate:  
1. When painting cover plate, be sure to first use a primer coat, prior to final color matching.  
2. After each coat of paint, ENSURE FREE MOVEMENT OF THE LENS DOOR by opening and closing it several  
times until paint is completely dry. When paint is completely dry, test unit operation using the push to test  
led/ac test switch located on central battery unit . If door sticks, safely trim residual paint from around lens  
door with utility knife or similar tool and test unit operation again.  
3. When wallpapering the cover plate, be sure to trim around the edges of the lens door to ENSURE FREE  
MOVEMENT. After wallpaper is installed, test the unit operation via the push to test GREEN led button.  
OPERATION  
To test existing unit when fully installed in wall or ceiling, depress and hold led/ac test switch located on  
central battery unit . Lamp housing will automatically extend outward and lamps will illuminate. After test,  
release the led/ac test switch located on central battery unit to return housing to original position.  
NOTICE  
This SC Series Emergency Light is furnished with a sophisticated low voltage battery dropout circuit to protect the  
battery from over discharge after the useful output has been reached. Allow 24 hour recharge time after installation  
or power failure for full load testing.  
Questions, problems, missing parts? Before returning to your retailer, call our customer  
service department at 1-800-LIGHTBULB (1-800-544-4828)  
Imported by:  
OSRAM SYLVANIA Inc.  
54 Cherry Hill  
Danvers, MA 01923  
Made in China  
SYLVANIA is a registered trademark of OSRAM SYLVANIA Inc.  
Copyright © 2011 OSRAM SYLVANIA Inc. 04/20  
E13885  
DQ3-144-003A  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp Flat Panel Television LC 42D43U User Manual
Sharp Projector XG C55X User Manual
Shindaiwa Trimmer 80844 User Manual
Soehnle Building Set 7755 User Manual
Sony Car Stereo System MXD D3 User Manual
Sony DVD Player DVP FX930 User Manual
Sony Security Camera SNP 3350 User Manual
Star Micronics Printer NX 2480 User Manual
StarTechcom Computer Drive S3540BU33E User Manual
Suunto Heart Rate Monitor T6 User Manual