Sylvania Home Safety Product SC11 User Manual

SYLVANIA Emergency Lighting  
Installation Instructions  
Installation Instructions for Emergency Lights  
Model SC36, SC11  
SAVE THESE INSTRUCTIONS  
Before Installation, read instructions and understand all safety information.  
WHEN INSTALLING AND USING ELECTRICAL EQUIPMENT, ALL WORK SHOULD BE PERFORMED BY A LICENSED  
ELECTRICIAN AND BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING BUT NOT LIMITED TO  
THE FOLLOWING:  
WARNING  
To prevent shock or damage, turn power off before inspection, installation or removal.  
The use of accessory equipment is not recommended and may cause an unsafe condition.  
Do not use this electrical equipment for other than its specific intended purpose.  
This unit has been supplied with specified lamps. To avoid malfunction, use only lamps specified  
by manufacturer.  
To avoid risk of fire, do not store or place flammable materials near lamp.  
Use caution when changing or inspecting lamps as they can become hot and may cause burns if  
handled improperly.  
To avoid electrocution or property damage, do not install or use where exposed directly to water or  
outdoor weather conditions.  
This product contains a chemical known to the state of California to cause cancer, birth defects or other  
reproductive harm.  
INSTALLATION  
Step 1:  
Remove dust cover from unit by applying gentle, even pressure around edges. If you are installing the light during a  
building construction phase, please save dust cover for reinstallation to protect the unit prior to the final connection  
by electrician.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 2:  
Remove cover plate by first removing the screw caps and then unscrewing the screws. Save screws.  
Step 3:  
If installing into OPEN wall or ceiling in NEW construction, set adjustable flange to proper depth according to the  
thickness of the drywall you plan to use. Measure height and depth of installation and use two of the four screws - to  
anchor the flange to the stud. A standard hanger bar can also be utilized for more stability.  
After installing the unit, secure interior plastic dust cover to metal unit box by lining the dust cover up with the screw  
holes on the metal box and applying gentle even pressure until it snaps into place. If cover does not fit properly,  
please tape in place for extra securing. This dust cover protects important electronic components within the unit from  
dust and debris, leave dust cover in place until final wiring connections are made and then discard. Final step is to  
install front painted cover plate with provided screws and plastic screw covers.  
If RETROFITTING installation into EXISITING drywall, set adjustable flanges to be even with top of metal box. Cut  
hole in ceiling or wall using provided plastic template and secure metal housing in using your desired drywall screws,  
or the ones provided with unit.  
If installing into drop ceiling, use a hanger bar designed to secure fixtures of similar weight. (Check specification  
sheet for weight.) Adjust flanges to proper depth of ceiling tile. Flange will secure above ceiling tile. This will provide  
additional support.  
Step 4:  
With no power to unit (AC circuit breaker switched o) feed AC wire through knockout (KO) on metal housing.  
Connect AC wiring to internal wire leads provided within unit.  
For connecting to 120Vac power source, connect BLACK lead wire (Phase), WHITE lead wire (Neutral) and GREEN lead  
wire (Ground). Use wire nuts on all wire connections.  
For connecting to 277Vac power source, connect ORANGE lead wire (Phase), WHITE lead wire (Neutral) and GREEN  
wire (Ground) Use wire nuts on all wire connections.  
Connect wiring to emergency light in accordance with NEC and / or local regulations.  
CAUTION  
Be sure to not cross the wires during connection or serious damage to the emergency light unit  
can occur.  
Step 5:  
Turn ON AC the power supply to emergency light unit. The Green LED will light.  
Then securely connect the white battery lead wire that can be found taped to the top of the battery, to the positive  
(+) terminal on the internal battery.  
To test the unit, gently depress and hold the green LED button and the lens housing will automatically extend  
outward to the open position and the lamps will turn on. Release the green LED button and the unit will  
automatically retract and the lamps will turn off.  
Replace front cover plate via metal screws and screw cap covers.  
Green LED charge indicator will stay on as an indication that AC power is energizing the fixture and the internal  
rechargeable battery is charging.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
NOTICE  
Replace internal battery every three years or according to ambient temperature guidelines provided by battery unit  
manufacturer (sold separately), to ensure proper operation.  
NOTE: Servicing of parts should be performed by qualified service personnel. For replacement lamps or batteries,  
contact your local representative.  
Painting or wallpapering front cover plate:  
1. When painting cover plate, be sure to first use a primer coat, prior to final color matching.  
2. After each coat of paint, ENSURE FREE MOVEMENT OF THE LENS DOOR by opening and closing it several times  
until paint is completely dry. When paint is completely dry, test unit operation using the push to test GREEN led  
button. If door sticks, safely trim residual paint from around lens door with utility knife or similar tool and test unit  
operation again.  
3. When wallpapering the cover plate, be sure to trim around the edges of the lens door to ENSURE FREE  
MOVEMENT. After wallpaper is installed, test the unit operation via the push to test GREEN led button.  
OPERATION  
To test existing unit when fully installed in wall or ceiling, depress and hold GREEN led/ac test switch. Lamp housing  
will automatically extend outward and lamps will illuminate. After test, release GREEN led/ac switch to return  
housing to original position.  
NOTICE  
This SC Series Emergency Light is furnished with a sophisticated low voltage battery dropout circuit to protect the  
battery from over discharge after the useful output has been reached. Allow 24 hour recharge time after installation  
or power failure for full load testing.  
Questions, problems, missing parts? Before returning to your retailer, call our customer  
service department at 1-800-LIGHTBULB (1-800-544-4828)  
Imported by:  
OSRAM SYLVANIA Inc.  
54 Cherry Hill  
Danvers, MA 01923  
Made in China  
SYLVANIA is a registered trademark of OSRAM SYLVANIA Inc.  
Copyright © 2011 OSRAM SYLVANIA Inc. 04/20  
E13878  
DQ3-144-006A  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp Flat Panel Television LC 32GD9E User Manual
Snapper Snow Blower MCS2000 User Manual
Sony Cassette Player CFD F10L User Manual
Sony CD Player RCD W50C W10 User Manual
Sony Home Theater System BDV EF1100 User Manual
Sony Kitchen Entertainment Center VGN FJ100 User Manual
Sony Projector VPL VW60 User Manual
Sony Speaker System CMT HX7BT User Manual
SUPER MICRO Computer Personal Computer X8DA3 User Manual
Symphonic DVD Recorder SR90VE User Manual