Superior Indoor Fireplace VF4000 CHN 2 User Manual

INSTALLATION AND  
OPERATION INSTRUCTIONS  
STANDARD SERIES  
Unvented Decorative Gas Fireplaces  
P/N 903590, REV. P, 04/2010  
MODELS  
VF4000-CHN-2  
VF4000-CMN-2  
VF4000-CHP-2  
VF4000-CMP-2  
FOR USE ONLY WITH DECORATIVE TYPE  
UNVENTED ROOM HEATERS.  
DO NOT BUILD A WOOD FIRE.  
WARNING: IMPROPER INSTALLATION, ADJUSTMENT,  
ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE  
INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL.  
FOR ASSISTANCE OR ADDITIONAL INFORMATION CONSULT  
A QUALIFIED INSTALLER, SERVICE AGENCY OR THE  
GAS SUPPLIER.  
Portland  
US  
INSTALLER: Leave this manual with the appliance.  
CONSUMER: Retain this manual for future reference.  
WARNING: DO NOT BURN WOOD OR OTHER MATERIAL IN  
THESE APPLIANCES.  
WARNING: If the information in this manual is  
not followed exactly, a fire or explosion may  
result causing property damage, personal injury  
or loss of life.  
CAREFULLY REVIEW THE INSTRUCTIONS SUPPLIED WITH  
THE DECORATIVE TYPE UNVENTED ROOM HEATER FOR  
THE MINIMUM FIREPLACE SIZE REQUIREMENT.  
DO NOT INSTALL THE APPLIANCE IN THIS FIREBOX, UNLESS  
THIS FIREBOX MEETS THE MINIMUM DIMENSIONS  
REQUIRED FOR THE INSTALLATIONS.  
Do not store or use gasoline or other flammable  
vapors and liquids in the vicinity of this or any  
other appliance.  
WHAT TO DO IF YOU SMELL GAS  
This is an unvented gas-fired heater. It uses air  
(oxygen) from the room in which it is installed.  
Provisionsforadequatecombustionandventilation  
air must be provided. Refer to Combustion  
and Ventilation Air Section, Page 3.  
• Do not try to light any appliance.  
• Do not touch any electrical switch; do not use  
any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier's  
instructions.  
Due to high temperatures, the appliance should be located out  
of traffic and away from furniture or draperies.  
• If you cannot reach your gas supplier, call  
the fire department.  
Donotplaceclothingorothermaterialsonornearthisappliance.  
Installation and service must be performed by  
a qualified installer, service agency or the gas  
supplier.  
IMPORTANT: READ AND UNDERSTAND THESE INSTRUCTIONS  
COMPLETELY BEFORE INSTALLING YOUR UNVENTED ROOM  
HEATERS.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The heater must be isolated from the gas  
supply piping system by closing its individual  
manual shut-off valve during any pressure test-  
ing of the gas supply piping system at test  
pressures equal to or less than 1/2 psig.  
• Vent-Free appliances may NOT be installed in  
bedrooms or bathrooms.  
WARNING: FAILURE TO COMPLY WITH  
THE INSTALLATION AND OPERATING  
INSTRUCTIONS PROVIDED IN THIS  
DOCUMENT WILL RESULT IN AN IM-  
PROPERLY INSTALLED AND OPERAT-  
ING UNVENTED ROOM HEATER, VOID-  
ING ITS WARRANTY. ANY CHANGE TO  
THIS HEATER AND/OR ITS OPERATING  
CONTROLS IS DANGEROUS. IMPROPER  
INSTALLATION OR USE OF THIS HEATER  
CAN CAUSE SERIOUS INJURY OR DEATH  
FORM FIRE, BURNS, EXPLOSION OR  
CARBON MONOXIDE POISONING.  
• A working smoke detector must be installed  
in the area where vent-free appliances are  
installed.  
Any safety screen or guard removed for  
servicing the heater must be replaced prior to  
operating the heater.  
Seller of unvented propane or natural gas-  
fired supplemental room heaters shall pro-  
vide to each purchaser a copy of 527 CMR 30  
upon sale of the unit.  
Keep heater area clear and free from com-  
bustible materials, gasoline and other flam-  
mable vapors and liquids.  
New York:  
These fireplaces are approved for installation  
in the US state of New York, but not in New  
York City.  
Do not use these appliances if any part has  
been under water. Immediately call a qualified  
professional service technician to inspect the  
appliance and to replace any parts of the control  
system and any gas control which have been  
under water.  
Carbon Monoxide Poisoning: Early signs of  
carbon monoxide poisoning are similar to the  
flu with headaches, dizziness and/or nausea. If  
you have these signs, obtain fresh air immedi-  
ately. Turn off the gas supply to the heater and  
have it serviced by a qualified professional, as  
it may not be operating correctly.  
COMBUSTION AND VENTILATION AIR  
These heaters shall not be installed in a con-  
fined space. The heater may be located in  
unusually tight construction provided the  
space is unconfined, or if confined, is pro-  
vided with two permanent openings commu-  
nicating directly with an additional room(s)  
of sufficient volume so that the combined  
volume of all connected spaces meets the  
criteria for an unconfined space, (National  
Fuel Gas Code ANSI Z223.1 (latest edition),  
Section 5.3). Generally 50 ft3 per 1,000 BTU  
input of all operatingappliances in the space.  
Input ratings are shown in BTU per hour and  
are for elevations up to 7,000 feet. Operating  
heater above elevations of 7,000 feet may cause  
ODS pilot outage.  
Due to high temperatures, the heater should  
be located out of traffic and away from furniture  
and draperies.  
Ensure that the heater is clean when operat-  
ing. Excessive dust accumulation on the burner  
and logs will increase the amount of carbon  
monoxide formation and could lead to carbon  
monoxide poisoning and death.  
Children and adults should be alerted to the  
hazard of high surface temperatures and should  
stay away to avoid burns or clothing ignition.  
CODES  
Young children should be carefully super-  
vised when they are in the same room with  
the heater.  
The National Fuel Gas Code defines a con-  
fined space as a space whose volume is less  
Adhere to all local codes or in their absence the  
latest edition of The National Fuel Gas Code  
ANSI Z223.1 or NFPA54 which can be obtained  
from The American National Standards Insti-  
tute, Inc. (1430 Broadway, New York, NY,  
10018) or National Fire Protection Association,  
Inc. (Batterymarch Park, Quincy, MA, 02269).  
3
than 50 ft 3 per 1,000 BTU/Hr (4.8 m per kw)  
of the aggregate input rating of all appliances  
installed in that space and an unconfined  
space as a space whose volume is not less  
than 50 ft3 per 1,000 BTU/Hr (4.8m3 per kw)  
of the aggregate input rating of all appliances  
installed in that space. Rooms communicat-  
ing directly with the space in which the appli-  
ances are installed, through openings not  
furnished with doors, are considered a part of  
the unconfined space.  
Do not place clothing or other flammable  
material on or near the heater for the purpose  
of drying.  
Installation and repair should be done by a  
qualified service person. The heater should be  
inspected before use and at least annually by a  
professional service person. More frequent clean-  
ing may be required due to excessive lint from  
carpeting, bedding material, etc. It is important  
that control compartments, burners and circulat-  
ing air passageways of the heater be kept clean.  
Massachusetts And New York Require-  
ments  
These appliances are approved for installation  
in the following USA locations listed in the  
following:  
Unusually tight construction is defined as con-  
struction where:  
Allow the heater to cool before servicing.  
Always shut off any electricity or gas to the  
heater while performing service work.  
Massachusetts:  
a. wall and ceilings exposed to the outside  
atmosphere have a continuous water vapor  
retarder with a rating or one perm or less with  
openings gasketed or sealed, and  
These fireplaces are approved for installation  
in the US state of Massachusetts if the follow-  
ing additional requirements are met-  
Do not install the VF4000 series heaters in a  
bedroom or bathroom.  
• Installation and repair must be done by a  
plumber or gas fitter licensed in the Common-  
wealth of Massachusetts.  
b. weather stripping has been added on oper-  
able windows and doors, and  
The installation must conform with local  
codes or, in the absence of local codes with the  
National Fuel Gas Code, ANSI Z223.1.  
c. caulking or sealants are applied to areas such  
as joints around window and door frames,  
between sole plates and floors, between wall-  
ceiling joints, between wall panels, at penetra-  
tions for plumbing, electrical, and gas lines,  
and at other openings.  
• The flexible gas line connector used shall not  
exceed 36 inches (92 centimeters) in length.  
The heater and its individual shut-off valve  
must be disconnected from the gas supply  
piping system while performing any tests of the  
gas supply piping system at pressures in ex-  
cess of 1/2 psig.  
• The individual manual shut-off must be a T-  
handle type valve.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Use the following equations to determine if you  
have a confined or unconfined space.  
This appliance may be installed in an after-  
market* manufactured (Mobile) Home, where  
not prohibited by state or local codes.  
*Aftermarket: Completion of sale, not for pur-  
pose of resale, from the manufacturer.  
WARNING: IF THE AREA IN WHICH THE  
HEATER MAY BE OPERATED IS SMALLER  
THAN THAT DEFINED AS AN UNCON-  
FINED SPACE, PROVIDE ADEQUATE  
COMBUSTION AND VENTILATION AIR BY  
ONE OF THE METHODS DESCRIBED IN  
THE NATIONAL FUEL GAS CODE, ANSI  
Z223.1 1992, SECTION 5.3 OR APPLI-  
CABLE LOCAL CODES.  
1. Determine the volume of space — ft 3.  
Length x Width x Height = _____ ft 3  
(Include adjoining rooms with doorless pas-  
sageways or ventilation grills between  
rooms.)  
Minimize modifications to existing construc-  
tion. Refer toFigure 1 for location suggestions.  
3
Example: 20' (L) x 16' (W) x 8' (H) = 2560 ft  
2. Divide the volume of space by 50 ft  
3 to  
Your options are:  
determine the maximum BTU/Hr the space  
can support.  
a. Rework equations adding the space of ad-  
joining room(s). If the extra volume provides  
an unconfined space, then remove door or  
add ventilation grills between rooms. Refer  
to National Fuel Gas Code, ANSI Z223.1  
1992, Section 5.3.  
3
______ (volume of space – ft 3)/ 50 ft  
=
(Maximum BTU/Hr the space can support)  
Example: 2560 ft 3 / 50 ft 3 = 51.2  
or 51,200 BTU/Hr the space can support.  
b. Vent room directly to the outdoors. Refer to  
National Fuel Gas Code, ANSI Z223.1 1992,  
Section 5.3.  
Figure 1  
3. Add the BTU/Hr of all the fuel burning appli-  
ances in the space.  
To ensure even heat distribution, it is best to  
position the heater centrally against the longest  
wall of the room. Make sure there is adequate  
ventilation where the heater is installed. The  
gas appliance will shut off if the oxygen level  
falls below 18%.  
c. Install a lower BTU/Hr heater, to make the  
area an unconfined space.  
Vent-Free heater  
Gas appliance #1*  
Gas appliance #2  
_______ BTU/Hr  
_______ BTU/Hr  
+ _______ BTU/Hr  
If the actual BTU/Hr used is less than the  
maximum BTU/Hr the space can support, then  
the space is an unconfined space. You will need  
no additional fresh air ventilation for an uncon-  
fined space.  
Total = _______ BTU/Hr  
These appliances are uniquely suited for instal-  
lations requiring a utility shelf positioned di-  
rectly above the fireplace. Utility shelves like  
these are commonly used for locating televi-  
sion sets and decorative plants.  
Example:  
VF4000 Vent-free heater 25,000 BTU/Hr  
Gas appliance #1  
(water heater)  
34,000 BTU/Hr  
LOCATION OF FIREPLACE  
Total = 59,000 BTU/Hr  
Carefully select the best location for installa-  
tion of your VF4000 series Unvented Room  
Heater. The following factors should be taken  
into consideration:  
To provide for the lowest possible shelf sur-  
face, combustible materials used to support a  
utility shelf directly above these appliances  
should be positioned just above the appliance  
top spacers. The minimum height from the  
base of the VF4000 to the underside of com-  
bustible materials used to construct a utility  
shelf is 37-1/4” (946 mm).  
* Do not include direct-vent gas appliances.  
Direct-vent is sealed combustion and draws  
combustion air from the outdoors.  
4. Compare the maximum BTU/Hr the space  
can support with the actual amount of BTU/  
Hr used.  
Clearance to side wall, ceiling, woodwork  
and windows.  
Location must not be affected by drafts  
caused by kitchen exhaust fans, return air reg-  
isters for forced air furnaces/air conditioners,  
windows or doors.  
_________ BTU/Hr  
(max. the space can support)  
_________ BTU/Hr  
The appliance should be mounted on a fully  
supported base extending the full width and  
depth of the unit. The appliance may be located  
on or near conventional construction materi-  
als. However, if installed on combustible mate-  
rials, such as carpeting, vinyl tile, etc., a metal  
or wood barrier covering the entire bottom  
surface must be used.  
(actual amount of BTU/Hr used)  
Installation must provide adequate ventila-  
tion and combustion air.  
Example:  
51,200 BTU/Hr  
(max. the space can support)  
59,000 BTU/Hr  
Do not install the VF4000 series heaters in a  
sleeping room or bathroom.  
(actual amount of BTU/Hr used)  
If the appliance is to be elevated above floor  
level, a solid continuous platform must be  
constructed.  
Never obstruct the front opening of the heater  
or restrict the flow of combustion and ventila-  
tion air.  
The space in the above example is a confined  
space because the actual BTU/Hr used is more  
than the maximum BTU/Hr the space can sup-  
port. You must provide additional fresh air.  
WARNING: MAINTAIN MINIMUM  
CLEARANCES.  
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Do not install in the vicinity of gasoline or other Note: Combustible wall finish materials and/or  
Note: The following steps represent the normal  
sequence of installation. Each installation is  
unique, however, and might require a different  
sequence.  
flammable liquids. The heater must be kept  
clear and free from these combustible materi-  
surround materials must not be allowed to  
encroach the area defined by the appliance  
als and may not be located near where they are front face (black sheet metal). Never allow  
stored.  
combustible materials to be positioned in front  
of or overlapping the appliance front face.  
CAUTION: HEATERS CREATE WARM AIR CUR-  
RENTS. THESE CURRENTS MOVE HEAT TO  
WALL SURFACES NEXT TO HEATER. INSTALL-  
ING HEATER NEXT TO VINYL OR CLOTH WALL  
COVERINGS OR OPERATING HEATER WHERE  
IMPURITIES IN THE AIR (SUCH AS TOBACCO  
SMOKE) EXISTS, MAY DISCOLOR WALLS.  
Clearances  
6" Clearance  
to Combustible  
Side Wall  
WARNING: DO NOT INSTALL VF SE-  
RIES UNVENTED ROOM HEATERS IN  
SLEEPING QUARTERS, OR IN RECRE-  
ATIONAL VEHICLES.  
Max. Projection (See Fig. 2)  
37-1/2" Min.  
to Ceiling  
Step 1. Position heater in desired location  
(freestanding, onto surround base or into pre-  
pared framing) and secure.  
(953 mm)  
WARNING: DO NOT INSTALL THE VF  
UNVENTED ROOM HEATER:  
Combustible  
Mantel  
• WHERE CURTAINS, FURNITURE,  
CLOTHING OR OTHER FLAMMABLE  
OBJECTS ARE LESS THAN 42" FROM  
THE FRONT OF THE UNVENTED ROOM  
HEATER.  
• IN HIGH TRAFFIC AREAS.  
• IN WINDY OR DRAFTY AREAS.  
(See Fig. 2)  
Step 2.Plumb gas line. (Gas connections should  
only be performed by an experienced, licensed/  
certified tradesman.)  
Figure 3  
Step 3. Assemble logs and test flame appear-  
ance.  
PREINSTALLATION  
Step 4. Complete finish wall material, sur-  
round and optional hearth extension to your  
individual taste.  
Check that all listed parts have been received.  
Ensure the minimum clearances shown in  
Figures 2 and 3 are maintained.  
Carefully inspect the heater case and contents  
for shipping damage and immediately inform  
the dealer from whom you purchased the gas  
fireplace if any damage is found.  
Minimum clearance to combustibles are:  
INSTALLATION STEPS  
Built-In Systems  
Appliance:  
side and back - 0"  
floor - 0"  
WARNING: DO NOT ALLOW FANS TO  
BLOW DIRECTLY INTO THE FIREPLACE.  
AVOID ANY DRAFTS THAT ALTER  
BURNER FLAME PATTERNS.  
The appliance is shipped with all gas controls  
and components installed and pre-wired. Re-  
move the shipping carton. The nailing flanges  
are installed at each side of the appliance back-  
wards when shipped from the factory to protect  
the unit from shipping damage. Remove the  
nailing flanges and retain for use when install-  
ing the appliance in framing. Remove three  
screws and remove the screen panel. Remove  
the logs and set aside.  
adjacent wall - 6"  
ceiling - 37-1/2” (953 mm)  
Combustible  
Finished Wall  
Materials  
12"  
( mm)  
WARNING: DO NOT USE A BLOWER IN-  
SERT, HEAT EXCHANGER INSERT OR  
OTHER ACCESSORY NOT APPROVED  
FOR USE WITH THIS HEATER.  
10''  
Header  
Spacer  
26"  
8''  
6''  
( mm)  
22-1/2"  
( mm)  
Check Gas Type  
Do not burn solid fuels in this listed unvented  
gas room heater.  
18-5/8"  
( mm)  
1/4" Gap  
Required  
2-1/2"  
( mm)  
14-1/2"  
( mm)  
This appliance can only be connected to the gas  
type specified on the appliance data plate. This  
appliance can not be modified in the field for a  
different gas type. If the gas type to be used is  
not the one specified contact the dealer to  
obtain the correct gas appliance.  
Step 1. Frame VF4000 appliance enclosures  
as illustrated in Figures 4, 5 and 6.  
8"  
( mm)  
Top of Appliance  
Top of Door Frame  
Note: The framed depth (15-1/2" for a flat wall,  
29" for a corner VF4000) must always be  
measured from a finished surface. If a wall  
covering such as drywall is to be attached to  
the rear wall, then the dimension must be  
measured from the drywall surface.  
VF Series  
Figure 2  
Note: Illustrations shown in this manual reflect  
“typical” installations with nominal dimensions  
and are for design and framing reference only.  
Actual installations may vary due to individual  
design preferences. However, always maintain  
minimum clearances to combustible materials  
and do not violate any specific installation re-  
quirements.  
A hearth extension is not required with this  
appliance. If a hearth extension is used, do not  
block the lower control compartment door. Any  
hearth extensions used is for appearance only  
and does not have to conform to standard  
hearth extension installation requirements.  
Note: Framing dimensions in Figures 4 - 6  
are calculated for a nailing flange depth of  
1/2" (13 mm).  
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Back Wall of  
Chase/Enclosure  
Including Finishing  
Materials If Any.  
Outside Wall  
15-1/2"  
(394mm)  
Control Valve  
(Standard)  
37" (940mm)  
Lower Control  
Compartment Door  
Figure 4  
Back Wall of  
3"  
7"  
Chase/Enclosure  
Including Finishing  
Materials If Any.  
(76 mm)  
(178 mm)  
Figure 9  
41"  
Secure all joints tightly using appropriate  
tools and sealing compounds (ensure pro-  
pane resistant compounds are used in  
propane applications).  
(1041mm)  
13-1/2"  
Figure 7  
(343mm)  
29"  
(737mm)  
The gas control valve is located in the lower  
control compartment. To access the valve  
open the lower control compartment door  
(Figure 9 ).  
Turn on gas supply and test for gas leaks,  
using a gas leak test solution (also referred to  
as bubble leak solution).  
37" (940mm)  
58-1/2" (1486mm)  
The regulator has a 3/8" NPT thread inlet port  
and is fitted with a 3" (76 mm) long nipple³,⁄₈"  
NPT on both ends. Plan the connections ac-  
cordingly.  
Note: Using a soapy water solution (50% dish  
soap, 50% water) is an effective leak test  
solution but it is not recommended, because  
the soap residue that is left on the pipes/  
fittings can result in corrosion over timeN.ever  
use an open flame to check for leaks.  
Figure 5  
We recommend that the gas line be routed for  
the right side of the appliance to ensure ad-  
equate access to the rear lower compartment  
for installation and servicing of the optional  
FAB-1100 blower.  
37-1/4"  
(946 mm)  
Gas Flex Line Kit, Model GFLV  
3/8" NPT x 3/8"  
Flare Fitting  
1/2" x 3/8" Flare  
Shut-Off Valve  
Gas Valve  
15-1/2"  
(394 mm)  
37"  
(940 mm)  
3/8" Flex Tubing  
Figure 6  
Step 2. Route a 1/2" (13 mm) gas line along the  
left or right side framing (Figure 7 ).  
3/8" Nipple, Standard  
with all Units  
All appliances have a 3" long 3/8" NPT nipple  
installed at the regulator. To quickly and easily  
complete the gas line routing, use the gas flex  
line kit, Model GFLV.  
3/8" Union  
3/8" Close Nipple  
Gas Stub  
Step 3. Position appliance into prepared fram-  
ing, secure with 6d nails at the nailing flange  
along each side.  
3/8" Shut-Off Valve  
1/2" x 3/8" Reducer  
Step 4. Connecting Gas Line – Make gas line  
connections. All codes require a shut-off valve  
mounted in the supply line.Figure 8 illustrates  
two methods for connecting the gas supply.  
Installation methods and materials must be in  
compliance with local codes.  
Figure 8  
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
A. Light the appliance (refer to safety and  
lighting instructions on pages 14 and 16).  
Step 6. Installing the Optional Forced Air  
Blower Kit Wiring – A receptacle plate is  
provided for the installation of the FAB-1100  
forced air blower kit (optional). Electrical  
power must be provided to this plate to oper-  
ate the blower.  
VF4000-CMN/P Series  
Optional Wiring Diagram  
If any of the original wire as supplied must be replaced, it  
must be replaced with Type AWM 105°C – 18 GA. wire.  
B. Brush all joints and connections with the  
gas leak test solution to check for leaks. If  
bubbles are formed, or gas odor is detected,  
turn the gas control knob to the “OFF” posi-  
tion. Either tighten or refasten the leaking  
connection and retest as described above.  
From Thermocouple  
Optional ON/OFF  
Wall Switch/Rocker Switch  
*
*
Route a 3-wire, 120Vac power line with con-  
trol switch to the lower left front corner of the  
appliance. Supply wires are to be connected to  
the outlet as shown inFigure 12, ensuring that  
the polarity (as determined by the colors of the  
wires) is exactly as shown. The black and red  
wire loop must be left intact, with the mating  
connectors connected.  
Thermopile  
C. When the gas lines are tested and leak free,  
be sure to rinse off the leak testing solution.  
D. When the gas lines are tested and leak free,  
observe the individual tongues of flame on the  
burner. Make sure all ports are open and  
producing flame evenly across the burner. If  
any ports are blocked, or partially blocked,  
clean out the ports.  
Factory Wired  
Field Wired  
* For Rocker Switch Attachment Only.  
Figure 11  
An external regulator must be used on all pro-  
pane (L.P.G.) heaters, in addition to the regula-  
tor fitted to the heater, to reduce the supply tank  
pressure to 13" w.c. (maximum).  
OFF/ON Blower  
Wall Switch  
To Fuse or  
Circuit Breaker  
Black  
120V  
AC  
Receptacle  
White  
WARNING: CONNECTING DIRECTLY TO  
AN UNREGULATED PROPANE TANK CAN  
CAUSE AN EXPLOSION.  
}
60Hz  
Fireplace  
Junction Box  
Blower Wiring Diagram  
Step 5. Installing the Optional Remote Wall  
Switch (VF4000-CMN/P models only) – The  
millivolt system comes from the factory wired  
as shown in Figure 10. Select a convenient  
location for the remote wall switch and connect  
the wiring to the appliance (Figure 11 ).  
Ground Wire  
Connection  
White  
(Supply)  
Blower  
(Lower)  
Outlet  
CAUTION: DO NOT CONNECT THE OPTIONAL  
REMOTE SWITCH TO A 120V POWER SUPPLY.  
120 Vac  
60 Hz  
Bipolar  
Terminal  
Screw  
Note: The optional rocker switch is mounted to  
the appliance and wired in the same way as the  
remote wall switch.  
Black  
Wire  
Black  
(Supply)  
VF4000-CMN/P Series  
Wiring Diagram  
If any of the original wire as supplied must be replaced, it  
must be replaced with Type AWM 105°C – 18 GA. wire.  
From Thermocouple  
Mating  
Connectors  
*
*
Thermopile  
Red Wire  
Figure 12  
Note: Supply wires may be alternatively connected to the outlet using the screw terminals,  
however the black supply wire must be ganged wired to the same terminal that the pre-wired black  
wire is attached to and the white supply wire must be connected to the opposite side of the outlet.  
* For Rocker or ON/OFF Wall Switch Attachment Only.  
Figure 10  
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT: Ground lead must be connected  
to the green screw located on the junction box  
cover plate. Failure to do so will prevent the  
appliance from operating.  
Assembling the Logs  
WARNING: DO NOT ADD EXTRA LOGS OR  
ORNAMENTS SUCH AS PINE CONES, VER-  
MICULITE OR ROCK WOOL. USING THESE  
ADDED ITEMS CAN CAUSE SOOTING.  
The appliance must be electrically grounded in  
accordance with local codes or, in the absence  
of local codes, the National Electrical Code,  
ANSI/NFPA 70-(latest edition). (In Canada, the  
current CSA C22-1 Canadian Electrical Code.)  
WARNING: DO NOT PLACE ANY LAVA  
ROCK ON LOGS OR BURNERS. THIS MAY  
CAUSE SOOTING.  
The forced air blower kit may be mounted at  
initial appliance installation or at any time there-  
after. Follow the instructions provided with the  
blower kit.  
Step 12. The heater includes a unitized set of  
ceramic fiber logs. The heater and logs are  
assembled as shown in Figure 14 . Handle  
these logs with great care. The logs can be  
easily damaged, but when handled properly  
they can provide years of performance and  
enjoyment.  
Finished Wall Details  
It is sometimes best to frame the appliance  
after it has been positioned in place. Frame with  
2 x 4s or heavier lumber. Always frame in  
accordance with local building codes.  
Figure 13  
Note: The heater may be installed directly on a  
floor made of standard combustible wood con-  
struction materials. Do not install the heater  
directly on carpeting or other soft floor cover-  
ing such as vinyl tile or flooring materials. Use  
a wood or metal panel that extends the full  
width and depth of the heater between the  
heater and any soft floor covering material.  
Refer to Figure 20 for base dimensions.  
Note: The header may rest on the top spacers  
but must not be notched to fit around them.  
In order to install the appliance facing flush with  
the finished wall, position the framework to  
accommodate the thickness of the finished wall  
(Refer to Figures 2 and 3 ).  
Step 8. Secure Heater – Bend the tabs down  
(Figure 13 ). Using two (2) screws securely  
tighten the appliance to the platform.  
If you live in a cold climate, seal all cracks  
around your appliance with noncombustible  
material and wherever cold air could enter the  
room. It is especially important to insulate  
outside chase cavity between studs and under  
floor on which appliance rests, if floor is above  
ground level.  
Note: Heater must be anchored to the floor or  
platform.  
Step 9. Install Optional 120V Wiring –Refer  
to Step 6 for wiring instructions.  
Proceed to Step 10.  
Connecting Gas Line  
Surround Installations  
Step 10. A qualified gas appliance installer  
must connect the gas room heater to the gas  
supply.  
Note: The VF4000 series appliances must be  
installed giving full consideration to the clear-  
ance and height requirements identified in this  
manual.  
Consult all local codes and refer to Step 5.  
Step 7. Position Heater – Place the heater in  
desired location. It may be helpful to tempo-  
rarily assemble the surround around the appli-  
ance to properly locate the unit. Refer to  
Figure 13 for floor and platform installations.  
If the heater is to be installed into a framed wall  
refer to the built-in assembly steps beginning  
on page 5.  
The heater gas inlet connection is 3/8" NPT,  
located on the right side facing the heater. If a  
left side connection is required, route the gas  
line under the valve to end at the right hand side  
for connection to the inlet. This may be re-  
quired to allow for installation of the blower.  
When tightening up the joint to the valve hold  
the valve securely with a wrench to prevent the  
valve from moving.  
Step 11 . For Surround Installations Only –  
Finish the assembly of the surround compo-  
nents and secure the surround to the appliance.  
Figure 14  
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
After setting the logs into position as described  
above, ensure they are properly and firmly  
situated. The heater will not function as in-  
tended if the logs are not correctly positioned.  
Step 13. Checking the System –With gas line  
installed run initial system checkout before  
closing up the front of the unit. Follow the pilot  
lighting instructions on pages 14 and 16.  
Periodically check the positioning of the logs.  
Note: Instructions are also found on the pull  
out panel located on the bottom surface of the  
appliance.  
WARNING: FAILURE TO POSITION THE  
PARTS IN ACCORDANCE WITH THESE  
DIAGRAMS OR FAILURE TO USE ONLY  
PARTS SPECIFICALLY APPROVED WITH  
THIS HEATER MAY RESULT IN PROP-  
ERTY DAMAGE OR PERSONAL INJURY.  
When first lighting the appliance, it will take a  
few minutes for the line to purge itself of air.  
Once purging is complete, the pilot and burner  
will light and operate as indicated in the instruc-  
tion manual. Subsequent lightings of the appli-  
ance will not require such purging. Inspect the  
pilot flame (remove logs, if necessary, handling  
carefully).  
Standard (Manual)  
Version Shown  
Figure 16  
In normal operation, at full rate, after 15 min-  
utes the following flame appearance should be  
observed:  
Flame Appearance  
REFER TO THE OPERATING INSTRUCTIONS  
LOCATED AT THE BACK OF THIS MANUAL  
BEFORE LIGHTING THE HEATER TO OBSERVE  
THE FLAMES.  
The pilot flame should be steady, not lifting or  
floating. Flame should be blue in color with  
traces of orange at the outer edge.  
Rear Burner Flame Characteristics The rear  
flames should be yellow. The flames should  
extend about 3 – 4" above the front log for  
natural gas and 2 – 3" above for propane  
(L.P.G.) gas (Figure 17 ).  
The top 3/8" (10 mm) at the pilot thermocouple  
should be engulfed in the pilot flame (NG only).  
Flames from the pilot, front and rear burner  
should be visually checked as soon as the  
heater is installed. In addition a periodic visual  
check of the flames should be made. The pilot  
flame should always be present when the heater  
is in operation and should just envelope the tip  
of the thermocouple (Figure 15 ).  
Replace logs if removed for pilot inspection.  
To light the burner; rotate the gas valve control  
knob counterclockwise to the “ON” position.  
Step 14. Installing the Hood Assembly –  
Attach the hood assembly over the firebox  
opening with three (3) screws.  
WARNING: NO ADJUSTMENTS ARE TO  
BE MADE TO THE ODS PILOT SYSTEM.  
TAMPERING WITH THIS SYSTEM CAN  
BE EXTREMELY HAZARDOUS.  
Step 15. Installing the Screen Assembly –  
Position the screen assembly in front of the  
firebox opening, with the joint in the gasket  
down (Figure 18 ). Locate the three (3) tabs at  
the bottom edge of the frame into the three (3)  
brackets at the base of the fireplace front  
opening. Lean the frame back towards the  
fireplace. Install the three (3) 1/4"-20 x 1"  
Phillips pan head screws removed previously  
and tighten to secure.  
Figure 17  
Main Burner – The flames at the front burner  
holes will be blue becoming yellowish as they  
hit the bark-like texture of the base and front  
face of the front log (Figure 17 ).  
Appliance Operation  
WARNING: THE LOWER CONTROL COM-  
PARTMENT AREA AND LOWER CONTROL  
COMPARTMENT ACCESS DOOR ARE EX-  
TREMELY HOT WHEN THE APPLIANCE IS  
IN OPERATION. EXERCISE EXTREME CARE  
WHEN ACCESSING THIS AREA. TOUCH  
ONLY THE FAR ENDS OF THE LOWER  
CONTROL COMPARTMENT DOOR WHEN  
OPENING WHILE THE APPLIANCE IS HOT.  
Standard (Manual)  
Version Shown  
Figure 15  
An incorrect pilot flame is shown inFigure 16.  
This pilot flame will cause the thermocouple to  
cool. When the thermocouple cools, the heater  
will shut off. If pilot flame pattern is incorrect,  
or if heater shuts off, contact your service  
representative.  
Screws  
Figure 18  
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL EQUIPMENT  
Decorative Volcanic Stone  
Blower Motor  
An incomparable package of options are avail-  
able for use with these appliances. These op-  
tions can both customize the operation of these  
unique appliances and enhance their beauty  
and charming appeal. All options are available  
in kit form, are easy to install and are packaged  
complete with all required parts and instruc-  
tions. Some of the option kits need to be fitted  
prior to completing the installation of the appli-  
ance. The following paragraphs detail the kit  
options available for use with the appliances  
covered in this manual.  
The decorative volcanic stone, Model FDVS,  
can be used to enhance the look of your  
appliance. Spread the decorative volcanic stone  
evenly around the bottom of the firebox.  
Grounded  
to Appliance  
Refractory Liner Kit  
Motor Plug  
One of the most beautiful enhancements you  
can make to this appliance is the addition of  
refractory liners. The refractory liner kit in-  
cludes tan ceramic fiber panels for the rear and  
side walls of the firebox. The ceramic fiber  
panels have brick-like features in relief. To  
install the three panels, simply place them in  
position against the firebox walls. This kit can  
be retrofitted into previously installed appli-  
ances.  
Receptacle  
120V  
Appliance Junction Box  
These outstanding optional items can be added  
individually or in sets of two or more to custom-  
ize your vent-free appliance to fit your homes  
unique needs. Kit part numbers are provided  
on page 12 along with descriptive illustrations.  
Figure 20  
Brass Louver Kit  
Screen Panel Kit  
Brass louvers are available for use with these  
appliances. These louvers are designed to  
replace the standard black louvers that are  
provided with the appliance. The brass louver  
kit includes six (6) louvers that simply snap  
into place. They provide a touch of elegance to  
the VF appliance. This kit can be retrofitted to  
previously installed appliances.  
The appliances covered in this manual are  
heater rated and produce a great deal of heat.  
Decorative brass trim pieces and hoods may  
tarnish because of their proximity to the heater  
opening and front face. Tarnishing of these  
pieces is normal, unavoidable and should be  
expected.  
An optional fixed fine mesh screen panel can be  
installed on the VF4000 Series Units. This screen  
panel is easy to install. This kit can be retrofitted  
to previously installed VF4000 appliances.  
Gas Flex Line with Valve  
Forced Air Kit  
A gas flex line kit is available to aid in attaching  
the appliance to the gas supply. This kit can  
only be used where local codes permit. The kit  
includes a 1/2" NPT to 3/8" flare in line shut-off  
valve, a 12" flex line 3/8" female flare through  
and a 3/8" flare to 3/8" NPT fitting. The compo-  
nents of this kit are rated for both natural and  
propane gas. This kit is designed to be used as  
an aid in installing the appliance.  
Brass Square Surround Kit  
The FAB-1100 assembly provides a forced air  
circulation feature for your appliance. This kit  
mounts directly into the lower intake chamber  
with an electrical connection made at the recep-  
tacle provided. The appliance must have an  
independent 120Vac power line incorporated at  
the time of installation. Refer to Step 5 of the  
installation instructions supplied with the forced  
air kit (Figures 19 and 20 ).  
A decorative brass square surround kit is  
available for use with these appliances. The  
BSK-5 is designed to attach directly to the  
front face of the appliance at its extreme edges.  
The BSK-5 provides a picture frame finish for  
the appliance 2-1/2" wide. The brass square  
surround kit can be retrofitted onto previously  
installed appliances.  
WARNING: CHILDREN AND ADULTS  
SHOULD BE ALERTED TO THE HAZARDS  
OF HIGH SURFACE TEMPERATURES. USE  
CAUTION AROUND THE APPLIANCE TO  
AVOID BURNS OR CLOTHING IGNITION.  
YOUNG CHILDREN SHOULD BE SUPER-  
VISED WHEN THEY ARE IN THE SAME  
ROOM AS THE APPLIANCE.  
Square Trim Kit  
A square trim kit is available for use with this  
appliance. This kit is easy to install and does  
not require hardware to attach it as de-  
signed, directly to the standard door frame.  
The four piece square trim kit can be in-  
stalled without the bottom or bottom and  
side pieces to customize the look of our  
appliance. This kit can be retrofitted to  
previously installed appliances.  
Figure 19  
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION AND CARE OF YOUR  
APPLIANCE  
Remote Control Kit  
CLEANING AND SERVICING  
The Model RCL adds the convenience of re-  
mote control for your millivolt controlled ap-  
pliance. The kit includes a wireless, hand held  
transmitter and a receiver that replaces the  
wall switch. This special receiver permits ei-  
ther manual or remote control modes. Both  
receiver and transmitter operate on standard 9  
volt batteries (not included). Refer to the RCL  
installation instruction for specific details.  
WARNING: TURN OFF THE UNVENTED  
GAS ROOM HEATER AND ALLOW TO COOL  
BEFORE CLEANING.  
1. Blower operation may be controlled through  
the ON/OFF unit rocker switch, located in the  
lower control compartment.  
2. These heater rated units are equipped with  
a two stage (HI, LOW) gas control valve. To set normal use of the heater. Dust the front grate, the  
the burner at the HI and LOW settings, rotate  
the control knob to the desired position.  
Only limited cleaning will be required under the  
top of the piezo cover and the control knob  
occasionally. Do not use cleaning fluids to clean  
the logs or any other part of the room heater.  
Wall Switch Kit  
3. When lit for the first time, the appliance will  
emit a slight odor for an hour or two. This is  
due to the “burn-in” of the internal paints and  
lubricants used in the manufacturing process.  
Additionally, when lit for the first time, this  
appliance may produce smoke, this is normal  
and should be expected. For the first few  
hours, operate the appliance with doors and  
windows open to encourage the dissipation of  
smoke and fumes.  
Remove the log assembly, gently handling by  
holding each log at each end. Use a vacuum  
cleaner to remove loose particles from the base  
and from around the burners. Gloves are rec-  
ommended to prevent the fibers from pricking  
your skin. If the skin is pricked, wash gently  
with soap and water. Replace the logs as de-  
tailed in Step 12 Assembling the Logs.  
An optional wall switch kit can be installed  
along with the millivolt controlled appliances.  
The kit consists of a standard UL wall switch  
with cover plate. This kit provides for remote  
(wall) operation of the appliance. Replace the  
wall switch and cover plate of this kit with the  
components of the FWSK and you can have true  
remote control of your vent-free appliance,  
turning it on and off from your favorite easy  
chair. The wall switch kit should be installed  
along with the appliance. Refer to Figure 11  
and Step 5 for detailed installation instructions.  
If, after a period of use, the flames start to  
exhibit unusual shapes and behavior, or the  
burners fail to ignite smoothly, then the burner  
holes may require some cleaning. If this hap-  
pens, it is preferable to contact your nearest  
dealer to get the appliance serviced.  
4. Keep lower control compartment clean by  
vacuuming or brushing at least twice a year.  
More frequent cleanings may be required due  
to excessive lint from carpeting, bedding ma-  
terials, etc. It is important that the control  
compartments, burners and circulating air pas-  
sageways of the heater be kept clean.  
Rocker Switch Kit  
REPLACEMENT PARTS  
An optional rocker switch kit can be installed  
directly on VF4000-CMN/P series appliances  
to provide for On and Off operation in lieu of a  
wall switch. This kit is designed to install in the  
lower control compartment out of view and is  
perfect for use in high volume areas such as  
lobbies and model homes where limited ac-  
cess to the appliance On/Off switch is desir-  
able. This kit can be retrofitted to previously  
installed appliances and may be temporarily  
installed in place of other switch circuitry.  
5. Always turn off gas to pilot before cleaning.  
Before relighting, refer to the lighting instruc-  
tions in this manual. Instructions are also  
found on a pull-out panel located on the floor  
of the appliance.  
An exploded view of the room heater with  
numbered parts and a parts list can be found  
on pages 20 and 21. All parts should be or-  
dered through your Lennox distributor or  
dealer. Parts will be shipped at prevailing  
prices at time of order.  
6. Always keep the appliance area clear and  
free from combustible materials, gasoline and  
other flammable liquids.  
When ordering repair parts, always give the  
following information:  
7. Remember, this appliance has a continuous  
burning pilot flame. Exercise caution when  
using products with combustible vapors.  
1. The model number of the heater.  
2. The serial number of the heater.  
3. The part number.  
4. The description of the part.  
5. The quantity required.  
Wall Thermostat Kit  
A wall thermostat kit is available for use with  
the millivolt controlled appliances. The wall  
thermostat is designed to be wired directly to  
the appliance millivolt gas control circuit and  
provide automatic On/Off control of the appli-  
ance to maintain a desired temperature within  
the room.  
6. The installation date of the heater.  
If you encounter any problems or have any  
questions concerning the installation of this  
heater, please contact your distributor. For the  
name of your nearest distributor contact:  
LHP  
1110 West Taft Avenue  
Orange, CA 92865  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES AND COMPONENTS  
Forced Air Kit  
FAB-1100  
Brass Louver Kit  
BRLK-5C  
Wall Switch Kit  
FWSK  
Wood Surround-Wall  
SUR-5PW  
Rocker Switch Kit  
FRS  
Refractory Liner Kit  
VF5RLK  
Remote Control  
RCL  
Wood Surround-Corner  
SUR-5PC  
Gas Flex Line Kit  
FFGC  
Thermostat  
WTK  
BSK-5  
Brass Surround Kit  
BRLK-CS  
Square Trim Kit  
STK-5-4  
Decorative  
Volcanic Stone  
FDVS  
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VF4000 SPECIFICATIONS  
37"  
(940 mm)  
31-1/2"  
15"  
(800 mm)  
(381 mm)  
30" (762 mm)  
36" (914 mm)  
Front View  
5-1/2"  
(140 mm)  
1/2  
"
(13 mm)  
37"  
(940 mm)  
31-1/2"  
(800 mm)  
3-3/4"  
(95 mm)  
8"  
(203 mm)  
J Box  
Opening  
Gas Line  
Opening  
3-1/2"  
3"  
(89 mm)  
(76 mm)  
15-1/2" (394 mm)  
Left Side View  
(Right Side View - Opposite)  
27"  
(686 mm)  
15-1/2"  
(394 mm)  
36"  
(914 mm)  
Top View  
Figure 21  
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VF4000-CHM/P OPERATING INSTRUCTIONS (STANDARD VALVES)  
FOR YOUR SAFETY READ BEFORE LIGHTING  
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY  
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.  
A. This heater has a pilot which must be lit by hand. When  
Immediately call your gas supplier from a neighbor’s  
phone. Follow the gas supplier’s instructions.  
lighting the pilot, follow these instructions exactly.  
B. BEFORE OPERATING smell all around the heater area for gas.  
Be sure to smell next to the floor because some gas is heavier  
than air and will settle on the floor.  
If you cannot reach your gas supplier, call the fire  
department.  
C. Use only your hand to push in or turn the gas control knob.  
Never use tools. If the knob will not push in or turn by hand, do  
not try to repair it, call a qualified service technician. Forced or  
attempted repair may result in a fire or explosion.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electric switch; do not use any phone  
in your building.  
D. Do not use this heater if any part has been under water.  
Immediately call a qualified service technician to inspect the  
appliance and to replace any part of the control system and any  
gas control which has been under water.  
LIGHTING INSTRUCTIONS  
8. With the control knob pressed in, push in and release the  
1. Stop! Read the safety information above.  
2. Make sure manual shut-off valve is fully open.  
3. Locate gas control knob and piezo.  
piezo igniter button to light the pilot.  
9. Hold the control knob in for a further 10 seconds to prevent  
the flame failure detector from shutting off the gas while the  
probe is warming up.  
4. Depress control knob in and turn clockwise  
to the  
10. Release the control knob while turning counterclockwise  
“OFF” position (Figure 22 ).  
to the "HI" or "LOW" Position.  
5. Wait 5 minutes to clear out any gas. Then smell for gas,  
including near the floor. If you smell gas, STOP! Follow “B” in  
the safety information above. If you do not smell gas, go to the  
next step.  
If the knob does not pop out when released, stop and  
immediately call your service technician or gas supplier.  
If the pilot will not stay lit after several tries, depress and  
turn the gas control knob clockwise  
to “OFF”  
6. The pilot is located on the right side in front of the burner  
and wait 30 seconds. Depress and turn knob counter-  
(Figure 23 ).  
clockwise  
to “IGN” and  
press igniter button again. If your pilot  
does not relight depress and turn  
7. Depress control knob in and turn counterclockwise  
to the “IGN” position (Figure 24 ). Press the control knob all  
the way in for 5 seconds.  
control knob clockwise  
to  
“OFF” and call your service technician  
or gas supplier.  
Note: If you are running the heater for the first time it will be  
necessary to press the control knob all the way in for 30  
seconds to allow air to bleed out of the gas piping.  
11. Wait 30 seconds before readjusting the heater when the  
control knob has been turned down to a lower setting.  
TO TURN OFF GAS TO HEATER  
to the “OFF”  
1. Depress and turn control knob clockwise  
position (Figure 22 ).  
MANUAL MATCH LIGHTING PROCEDURE — EMERGENCY ONLY  
1. If the pilot cannot be lit with the piezo igniter, the heater can be  
3. Light the match and hold the flame to the end of the pilot and  
manually lit with a match.  
ignite the pilot.  
2. With the right hand, depress and turn the control knob  
4. Continue to hold control knob for an additional 10 seconds to  
counterclockwise  
knob.  
to the “ON” position. Hold in the  
insure pilot remains lit.  
5. Release the control while turning control knob to desired  
setting.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
O
F
F
N
W
O
L
G
I
I
H
H
I
Turn Control Knob to “OFF” Position  
Turn Control Knob to “IGN” Position  
Figure 24  
Figure 22  
Pilot  
Pilot Location  
Figure 23  
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VF4000-CMN/P OPERATING INSTRUCTIONS (MILLIVOLT VALVES)  
FOR YOUR SAFETY READ BEFORE LIGHTING  
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION  
MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.  
A. This appliance has a pilot which must be lighted by hand.  
Do not use any phone in your building.  
When lighting the pilot, follow these instructions exactly.  
Immediately call your gas supplier from a neighbor’s phone.  
If your gas supplier cannot be reached, call the fire department.  
B. BEFORE OPERATING smell all around the appliance area for  
gas. Be sure to smell next to the floor because some gas is  
heavier than air and will settle on the floor.  
C. Use only your hand to push in or turn the gas control knob.  
Never use tools. If the knob will not push in or turn by hand,  
do not try to repair it, call a qualified service technician. Force  
or attempted repair may result in a fire or an explosion.  
WHAT TO DO IF YOU SMELL GAS  
Extinguish any open flame.  
Open windows.  
D. Do not use this appliance if any part has been under water.  
Immediately call a qualified service technician to inspect the  
appliance and to replace any part of the control system and  
any gas control which has been under water.  
Do not light any appliance.  
Do not touch any electrical switches.  
LIGHTING INSTRUCTIONS  
1. STOP! Read the safety information above on this page.  
2. Access left side louver.  
6. Wait five (5) minutes to clear out any gas. If you then smell  
gas, STOP! Follow “B” in the safety information above on this  
page. If you do not smell gas, go to the next step.  
3. Turn remote wall switch to “OFF.”  
7. Push in gas control knob slightly and turn counterclockwise  
to “PILOT.”  
4. Verify main line shut-off valve is open.  
8. Push in control knob all the way and hold in. Immediately  
light the pilot by triggering the spark ignitor (pushing red  
button) until pilot lights. Continue to hold the control knob in  
for about 1 ¹⁄₂ minutes after the pilot is lit. Release knob and  
it will pop back up. Pilot should remain lit. If it goes out,  
repeat steps 5 through 8.  
5. Push in gas control knob slightly and turn clockwise  
to “OFF.”  
Gas Control Knob  
Flame Adjustment Knob  
SIT Millivolt  
Valve  
L
I
P
Thermopile  
N
O
T
O
If knob does not pop up  
I
P
F
when released, stop and  
Thermocouple  
immediately call your  
service technician or gas  
supplier.  
E
A
Piezo Ignitor  
Ignitor  
If pilot will not stay lit after  
O
several tries, turn the control knob to “OFF” and call your  
service technician or gas supplier.  
L
O
P
I
H
O I  
F
T
Honeywell  
Millivolt Valve  
9. Turn gas control knob counterclockwise  
to “ON.”  
Gas Control Knob  
Spark Ignitor  
10. Close the side louver.  
Note: Knob cannot be turned from “PILOT” to “OFF”  
unless the knob is pushed in slightly. Do not force.  
Note: If the gas valve is turned directly from the “ON” to “OFF”  
position, the valve will latch in the “OFF” position for 60 seconds.  
TO TURN OFF GAS TO APPLIANCE  
1. Turn remote wall switch “OFF.” The pilot will remain lit for  
4. Depress gas control knob slightly and turn clockwise  
normal service.  
to “OFF.” Do not force.  
2. For complete shutdown, turn remote wall switch to “OFF.”  
5. Close the side louver.  
3. Access the left side louver.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING GUIDE FOR UNVENTED GAS PRODUCTS  
OBSERVED PROBLEM  
POSSIBLE CAUSE  
A. Igniter electrode positioned wrong.  
B. Igniter electrode broken.  
REMEDY  
1. When igniter button is  
pressed, there is no spark  
at ODS/pilot.  
Replace igniter.  
Replace igniter.  
C. Igniter electrode not connected to igniter cable.  
D. Igniter cable pinched or wet.  
Reconnect igniter cable.  
Free igniter cable if pinched by any metal or tubing. Keep igniter cable dry.  
Tighten nut.  
E. Piezo igniter nut is loose.  
F. Broken igniter cable.  
Replace igniter cable.  
G. Bad piezo igniter.  
Replace piezo igniter.  
2. Heater produces unwanted  
A. Heater burning vapors from paint, hair spray, glues, etc.  
B. Gas leak. See Warning statement on the front page.  
A. Not enough fresh air is available.  
B. Low line pressure.  
Ventilate room. Stop using odor-causing products while fireplace is running.  
Locate and correct all leaks.  
odors.  
3. Heater shuts off in use  
Open window and/or door for ventilation.  
Contact local gas company.  
(ODS operates).  
C. ODS/pilot is partially clogged.  
Clean ODS/pilot.  
4. Gas odor even when control  
A. Gas leak. See Warning statement on the front page.  
B. Control valve defective.  
Locate and correct all leaks (see Checking Gas Connections, page 7).  
Replace control valve.  
knob is in “OFF” position.  
A. Gas supply turned off or manual shut-off valve closed.  
B. Control knob not in “PILOT” position.  
C. Control knob not pressed in while in “PILOT” position.  
D. Air in gas lines when installed.  
Turn on gas supply or open manual shut-off valve.  
Turn control knob to pilot position.  
5. When igniter button is  
pressed, there is spark at  
ODS/pilot, but no ignition.  
Press in control knob while in pilot position.  
Continue holding down control knob. Repeat igniting operation until air is  
removed.  
E. ODS/pilot is clogged.  
Replace ODS/pilot assembly or get it serviced.  
Replace gas regulator.  
F. Gas regulator setting is not correct.  
A. Control knob not fully pressed in.  
B. Control knob not pressed in long enough.  
C. Manual shut-off valve not fully open.  
D. Thermocouple connection loose at control valve.  
6. ODS/pilot lights, but flame  
goes out when control knob  
is released.  
Press in control knob fully.  
After ODS/pilot lights, keep control knob pressed in 30 seconds.  
Fully open manual shut-off valve.  
Hand tighten until snug, then tighten ¹⁄₄ turn more.  
E. Pilot flame not touching thermocouple, which allows  
thermocouple to cool, causing pilot flame to go out. This  
problem could be caused by one or both of the following:  
1). Low gas pressure  
1). Contact local gas company.  
2). Replace ODS/pilot assembly or get pilot serviced.  
2). Dirty or partially clogged ODS/pilot  
F. Thermocouple damaged.  
Replace thermocouple.  
G. Control valve damaged.  
Replace control valve.  
7. Burner does not light after  
A. Burner orifice is clogged.  
Clean burner or replace burner orifice.  
Replace burner orifice.  
ODS/pilot is lit.  
B. Burner orifice diameter is too small.  
C. Inlet gas pressure is too low.  
A. Manifold pressure is too low.  
B. Burner orifice is clogged.  
Contact local gas company.  
Contact local gas company.  
Clean burner or replace burner orifice.  
Clean burner or replace burner orifice.  
Replace burner.  
8. Delayed ignition of burner.  
9. Burner backfiring during  
A. Burner orifice is clogged or damaged.  
B. Burner damaged.  
combustion.  
C. Gas regulator defective.  
Replace gas regulator.  
10. Slight smoke or odor during  
A. Vapors from paint or curing process of logs.  
Problem will stop after a few hours of operation. SFC recommends running the  
heater with excess ventilation for the first few hours.  
initial operation.  
11. Heater produces a whistling  
A. Turning control knob to “HI” position when burner is cold.  
Turn control knob to “LO” position and let warm up for a minute.  
noise when burner is lit.  
B. Air in gas line.  
Operate burner until air is removed from line. Have gas line checked by local gas  
company.  
C. Dirty or partially clogged burner orifice.  
Clean burner or replace burner orifice.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPLACEMENTPARTS LIST  
VF4000-CHN(Manual)  
VF4000-CHP(Manual)  
VF4000-CMN(Millivolt)  
VF4000-CMP(Millivolt)  
Item  
No.  
Description  
Part No.  
H4111  
H4111  
Qty.  
Part No.  
Qty.  
1.  
Valve(Natural)  
Valve(Propane)  
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
SIT Valve(Natural)  
Honeywell Valve(Natural)  
SIT Valve(Propane)  
Honeywell Valve(Propane)  
Injector, Burner(Natural)  
Injector, Burner(Propane, LPG)  
Pilot (Natural)  
H4173  
24M13  
H4278  
67L02  
H4115  
H4116  
H4113  
H4170  
903218  
112081  
H4170  
H6430  
H6430  
H4110  
H4118  
H4119  
10K86  
H4868  
H2335  
H4317  
H4315  
H4178  
H4141  
2.  
3.  
4.  
H4115  
H4116  
H4114  
H4112  
H4869  
H4870  
H4170  
H6430  
H6430  
H4110  
H4118  
H4119  
10K86  
H4868  
H2335  
H4317  
H4315  
H4178  
H4141  
Pilot (Propane, LPG)  
Regulator(Natural)  
Regulator (Propane, LPG)  
Front Burner  
5.  
6.  
RearBurner(Natural)  
Rear Burner(Propane, LPG)  
Crossover Burner  
7.  
8.  
Injector, Crossover Burner(Natural)  
Injector, Crossover Burner(Propane, LPG)  
Piezo  
9.  
10.  
11.  
12.  
13.  
14.  
15.  
Piezo Wire  
Log Set  
Bar, Louver-Black  
Panel, Radiant  
Replacement Screen  
Hood  
18  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPLACEMENT PARTS  
13  
11  
14  
12  
15  
CM Models  
(SIT Valve  
Shown)  
CH Models  
8
1
12  
13  
2
CH Models  
3
4
CM Models  
7
10  
6
9
5
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications and prices, and also to discontinue colors, styles and products.  
Consult your local distributor for fireplace code information.  
LHP  
Printed in U.S.A. © 1997 by Lennox Hearth Products  
1508 Elm Hill Pike, Suite 108  
P/N 903590 REV. P 04/2010  
Nashville, TN 37210  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp All in One Printer MX M160D User Manual
Speco Technologies DVR 16TL User Manual
Sprint Nextel Network Card PC 5740 User Manual
StarTechcom Computer Hardware PEXHDCAP60L User Manual
Sunbeam Fryer 6107 33 User Manual
Sunbeam Mixer ODF 510 User Manual
Sylvania Car Satellite TV System C6427TF User Manual
Sylvania Portable DVD Player SSD204 User Manual
Talkswitch Telephone TS 600 User Manual
Tapco Musical Instrument Blend 6 User Manual