INSTALLATION INSTRUCTIONS
SDVST Direct-Vent
Gas Fireplaces
P/N 700037M Rev. F 01/2011
This manual is one of a set of two supporting this product.
Refer to P/N 725035M for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement
en faire la demande. Numéro de la pièce 700037CF.
MODELS
MILLIVOLT:
SDVST-N-B
SDVPF-N-B
Portland
US
OTL Report No. 116-F-32-5
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l'appareil.
CONSOMMATEUR : Conservez cette notice pour
consultation ultérieure.
This appliance may be installed as an OEM installation in a manufactured home (USA only) and must be
installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and
Safety Standard, Title 24 CFR, Part 3280, in the United States or the Standard for Installation in Manufactured
Homes, CAN/CSA Z240 MH, in Canada. This appliance is only for use with the type of gas indicated on the
rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
/
/
WARNING AVERTISSEMENT AVISO
• HOT GLASS WILL CAUSE
BURNS.
• UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
• EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA
• DO NOT TOUCH GLASS
UNTIL COOLED.
TOCAR EL VIDRIO CALIENTE.
• NEVER ALLOW CHILDREN
TO TOUCH GLASS.
• NE PERMETTEZ JAMAIS À UN ENFANT • LOS NIÑOS DEBEN NUNCA
DE TOUCHER LA SURFACE VITRÉE.
TOCAR EL VIDRIO.
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may
result, causing property damage, personal injury,
or death.
AVERTISSEMENT : Assurez-vous de bien suivre les
instructions données dans cette notice pour réduire au
minimum le risque d’incindie ou d’explosion ou pour
éviter tout dommage matériel, toute blessure ou la mort.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs
ou liquides inflammables dans le voisinage de cet appareil
ou de tout autre appareil.
-
vapors and liquids in the vicinity of this or any other
appliance.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifié ou par le
fournisseur de gaz.
•
department.
- Installation and service must be performed by a
Download from Www.Somanuals.com. All Manuals Search And Download.
Note: Installation and repair should be done
by a qualified service person. The appliance
should be inspected before use and at least
annually by a professional service person.
More frequent cleaning may be required
due to excessive lint from carpeting, bed-
ding material, etcetera. It is imperative
that control compartments, burners and
circulating air passageways of the appliance
be kept clean.
The appliance, when installed, must be electri-
cally grounded and wired in accordance with
local codes or, in the absence of local codes,
with the National Electrical Code, ANSI/NFPA
70 - latest edition, or the Canadian Electrical
Code, CSA C22.1 - latest edition.
WARNING
Improper installation, adjust-
ment, alteration, service or
maintenance can cause injury
or property damage. Refer to
this manual. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
Provide adequate clearances around air open-
ings and adequate accessibility clearance for
service and proper operation. Never obstruct
the front or back openings of the appliance.
Remarque : L’installation et la réparation
devraitêtreconfiéesàuntechnicienqualifié.
L’appareil devrait faire l’objet d’une inspec-
tion par un technicien professionnel avant
d’être utilisé et au moins une fois l’an par la
suite.Desnettoyagesplusfréquentspeuvent
être nécessaires si les tapis, la literie, et
ceteraproduisentunequantitéimportantede
pous-sière. Il est essentiel que les comparti-
mentsabritantlescommandes,lesbrûleurset
les conduits de circulation d’air de l’appareil
soient tenus propres.
These appliances are designed to operate on
natural or propane gas only. The use of other
fuels or combination of fuels will degrade
the performance of this system and may be
dangerous.
WARNING
Failure to comply with these
installationinstructionswillresult
in an improperly installed and
operating appliance, voiding its
warranty. Anychangetothisappli-
anceand/oritsoperatingcontrols
is dangerous.
These fireplaces are designed as supplemental
heaters. Therefore, it is advisable to have an
alternate primary heat source when installed
in a dwelling.
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
Do not use these appliances if any part
has been under water. Immediately call a
qualified, professional service technician
to inspect the appliance and to replace any
parts of the control system and any gas
control which have been under water.
These millivolt appliances are manually con-
trolled and feature a spark igniter (piezo) that
allows the appliance's pilot gas to be lit without
the use of matches or batteries. This system
provides continued service in the event of a
power outage.
WARNING
Clothing or other flammable
material should not be placed
on or near the appliance.
Nepasutilisercetappareils’ilaétéplongé,
même partiellement, dans l’eau. Ap-
peler un technicien qualifié pour inspecter
l’appareil et remplacer toute partie du
systèmedecommandeettoutecommande
qui a été plongée dans l’eau.
These millivolt models come standard with a
manually-modulated gas valve; flame appear-
ance and heat output can be controlled at the
gas valve. The BTU Input for these appliances
is shown in Table 1.
AVERTISSEMENT
On ne devrait pas placer de
vêtements ni d’autres matières
inflammables sur l’appareil ni à
proximité.
Only trim kit(s) supplied by the manufacturer
shall be used in the installation of this ap-
pliance.
Input (BTU) Manually-Modulated Gas
Valves (all models)
Models
Fuel Type
Input Rate
(BTU / HR)
WARNING
Seules les trousses de garniture fournies
par le fabricant doivent être utilisées pour
l’installation de cet appareil.
Any safety screen or guard
removed for servicing the appli-
ance must be replaced prior to
operating the appliance.
Natural or
Propane Gas
37,500 high
30,000 low
SDVST
SDVPF
These appliances comply with National Safety
Standards and are tested and listed by OMNI-
TestLaboratories,Inc. (ReportNo.116-F-32-5)
to ANSI Z21.88 (in Canada, CSA-2.33), and
CAN/CGA-2.17-M91 in both USA and Canada,
as vented gas fireplace heaters.
Table 1
AVERTISSEMENT
Tout écran ou protecteur retiré
pour permettre l’entretien de
l’appareil doit être remis en
place avant de mettre l’appareil
en marche.
These millivolt appliances are listed by
OMNI-Test Laboratories for installation in
bedrooms and Manufactured Homes.
Misc. Codes / Standards -
WARNING
TheInstallationmustconformtolocalcodesor,
in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest
edition(InCanada,thecurrentCAN/CSA-B149.1
installation code).
Improper installation or use of
thisappliancecancauseserious
injury or death from fire, burns,
explosion or carbon monoxide
poisoning.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Pressure - All Models
Orifice Sizes - Sea Level to High Altitude
(All Models)
Gas Valve Diagrams - See Figure 1.
Tables 2 and 3 show the appliances' gas
pressure requirements:
These appliances are tested and approved for
installation at elevations of 0-4500 feet (0-1372
meters) above sea level using the standard
burnerorificesizes(marked with an "*" inTable
4). Forelevationsabove4500feet,contactyour
gas supplier or qualified service technician.
HI/LO Variable
Flame Height
Adjustment
Inlet Pressure Tap
Manifold Pressure Tap
Inlet Gas Supply Pressure
(all models)
O U T I N
Fuel #
Minimum
Maximum
I
H
O
F
5.0" WC
(1.24 kPa)
10.5" WC
(2.61 kPa)
P
I
L
Natural Gas
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced
by either:
O
L
O
W
T
O
N
P
I
L
T
11.0" WC
(2.74 kPa)
13.0" WC
(3.23 kPa)
Propane
•
Using gas that has been derated by the gas
company.
Main Gas Control Knob
OFF/PILOT/ON
Table 2
Pilot Adjustment
Screw
•
Changing the burner orifice to a smaller size
as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel
Gas Code NFPA 54/ANSI Z223.1 - latest
edition or, in Canada, the CAN/CSA-B149.1
codes - latest edition.
Manifold Gas Supply Pressure
(all models)
Figure 1 - SIT Millivolt Gas Valve
Fuel #
Low
High
REQUIREMENTS FOR THE COMMON-
WEALTH OF MASSACHUSETTS
Natural (Lo) 2.2" WC
(Hi) 3.5" WC
(.87 kPa)
Installtheapplianceaccordingtotheregulations
of the local authorities having jurisdiction and,
in the USA, the National Fuel Gas Code NFPA
54 / ANSI Z223.1 - latest edition or, in Canada,
the CAN/CSA-B149.1 - latest edition.
Gas
(.55 kPa)
(Lo) 6.3" WC (Hi) 10.0" WC
(1.57 kPa) (2.49 kPa)
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
Propane
Table 3
NOTE: Flame appearance will diminish 4% per
thousand feet.
Testgaugeconnectionsareprovidedonthefront
ofthemillivoltgascontrolvalve,identifiedINfor
the inlet and OUT for the manifold side.
NOTE: Each model has two burners and 2
Orifices.
• The flexible gas line connector used shall
not exceed 36 inches (92 centimeters) in
length.
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step down regulators to reduce the
pressure to safe levels.
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
• The individual manual shut-off must be a
T-handle type valve.
Model
Nat.Gas
Propane
Series
drill size (inches)
drill size (inches)
Massachusetts Horizontal Vent Requirements
These appliances must be isolated from the
gas supply piping system (by closing their
individual manual shut-off valve) during any
pressure testing of the gas supply piping
system at test pressures equal to or less
than 1/2 psig (3.5 kPa).
#44 (.086")
60J80 •
#55 (.052")
*
**
SDVST
SDVPF
19L52 •
IntheCommonwealthofMassachusetts,hori-
zontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements:
• A hard wired carbon monoxide detector
with an alarm and battery back-up must be
installed on the floor level where the gas
fireplace is installed. The carbon monoxide
detector must comply with NFPA 720, be
ANSI/UL 2034 listed and be ISA certified.
• A metal or plastic identification plate must
be permanently mounted to the exterior of
thebuildingataminimumheightofeight(8)
feet above grade and be directly in line with
the horizontal termination. The sign must
read, in print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS.
* Standard size installed at factory
** Standard size in LP conversion kit
• Part /Cat. Number
Table 4
Theseappliancesandtheirindividualshut-off
valves must be disconnected from the gas
supply piping system during any pressure
testing of that system at pressures greater
than 1/2 psig (3.5 kPa).
NEW YORK CITY, NEW YORK (MEA)
Installation of these fireplaces are approved
for installation in New York City in the US state
of New York.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks
around your appliance with noncombustible
material and wherever cold air could enter
the room. It is especially important to insulate
outside chase cavity between studs and under
floor on which appliance rests, if floor is above
ground level. Gas line holes and other open-
ings should be caulked or stuffed with unfaced
fiberglass insulation.
Vertical
Vent
Horizontal Vent
(top vent)
If the fireplace is being installed on a cement
slab in cold climates, a sheet of plywood or
other raised platform can be placed underneath
to prevent cold transfer to the fireplace and into
the room. It also helps to sheetrock inside
surfaces and tape for maximum air tightness
and caulk firestops.
Horizontal Vent
(side vent)
MANUFACTURED HOME
REQUIREMENTS
This appliance may be installed in an aftermar-
ket permanently located, manufactured home
(USA only) or Manufactured Home, where not
prohibited by local codes.
This appliance may be installed as an OEM
installation in a manufactured home (USA
only) or Manufactured Home and must be
installedinaccordancewiththemanufacturer's
instructions and the Manufactured Home
Construction and Safety Standard, Title 24
CPF, Part 3280 or Standard for Installation
in Manufactured Homes, CAN/CSA Z240 MH.
Vertical
Venting
Offset Venting
(one end flush
with wall)
Figure 2 - Typical Locations
Cet appareil peut être installé comme du
matériel d'origine dans une maison préfabri-
quée (É.-U. seulement) ou mobile et doit être
installé selon les instructions du fabricant et
conformémentàlanormeManufacturedHome
ConstructionandSafetyStandard,Title24CPF,
Part 3280 ou à la norme CAN/CSA Z240 Série
MM, Maisons Mobiles.
The location should also be free of electrical,
plumbing or other heating/air conditioning
ducting.
CAUTION: This appliance must be
grounded to the chassis of the manu-
factured home in accordance with local
codes or in the absence of local codes,
with the National Electrical Code ANSI /
NFPA 70 - latest edition or the Canadian
Electrical Code CSA C22.1 - latest edi-
tion.
These direct-vent appliances are uniquely
suited for installations requiring a utility shelf
positioned directly above the fireplace. Utility
shelveslikethesearecommonlyusedforlocat-
ing television sets and decorative plants.
Cet appareil peut être installé dans un maison
préfabriquée(É.-U. seulement) ou mobile déjà
installée à demeure si les réglements locaux
le permettent.
Be aware that this is a heat producing ap-
pliance. Objects placed above the unit are
exposed to elevated temperatures.
LOCATION
Thisapplianceisonlyforusewiththetypeofgas
indicated on the rating plate. This appliance is
notconvertibleforusewithothergases, unless
a certified kit is used.
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to
the exterior and access to the fuel supply are
also important.
Do not insulate the space between the ap-
pliance and the area above it (see Figure 8
on Page 8).
Cet appareil doit être utilisé uniquement avec le
type de gaz indiqué sur la plaque signalétique.
Cet appareil ne peut être converti à d'autres
gaz, sauf si une trousse de conversion est
utilisée.
Theminimumheightfromthebaseoftheappli-
ance to the underside of combustible materials
used to construct a utility shelf in this fashion
is shown in Figure 8 on Page 8.
Due to high temperatures, the appliance
should be located out of traffic and away from
furniture and draperies (Figure 2).
The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
onornearconventionalconstructionmaterials.
However, if installed on combustible materials,
such as carpeting, vinyl tile, etc., a metal or
woodbarriercoveringtheentirebottomsurface
must be used.
Enraisondestempératuresélevées,l’appareil
devrait être installé dans un endroit où il y a
peu de circulation et loin du mobilier et des
tentures (Figure 2).
CAUTION: Ensure that the cross mem-
bers are not cut or weakened during
installation. The structural integrity of
the manufactured home floor, wall, and
ceiling / roof must be maintained.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
VENT TERMINATION CLEARANCES
Vertical Vent Termination Clearances
Termination Heights For Vents
Above Flat Or Sloped Roofs
Ref. NFPA 54 / ANSI Z223.1
These instructions should be used as a
guideline and do not supersede local codes
in any way. Install venting according to local
codes,theseinstructions,thecurrentNational
Fuel Gas Code (ANSI-Z223.1) in the USA or
the current standards of CAN/CSA-B149.1
in Canada.
TERMINATION HEIGHTS FOR VENTS ABOVE
FLAT OR SLOPED ROOFS
Horizontal Overhang
Roof Pitch
Flat to 6/12
* Feet
1.0
* Meters
0.3
2 FT
MIN.
Vertical
Wall
2 FT MIN.
Lowest
Discharge
Opening
6/12 to 7/12
1.25
1.5
0.38
0.46
0.61
0.76
0.99
1.22
1.52
1.83
2.13
2.29
2.44
Vent
Termination
7/12 to 8/12
H*
8/12 to 9/12
2.0
Storm Collar
Flashing
X
Vertical Vent Termination Clearances
12
9/12 to 10/12
10/12 to 11/12
11/12 to 12/12
12/12 to 14/12
14/12 to 16/12
16/12 to 18/12
18/12 to 20/12
20/12 to 21/12
2.5
Roof Pitch is X/12
3.25
4.0
Terminate multiple vent terminations according
to the installation codes listed above. Also see
Figure 3A.
1 inch (25.4 mm) Minimum
Clearance to Combustibles
5.0
Concentric
Vent Pipe
*H = MINIMUM HEIGHT FROM ROOF TO
LOWEST DISCHARGE OPENING OF VENT
6.0
Terminate single vent caps relative to building
components according to Figure 3B.
The vent / air intake termination clearances
above the high side of an angled roof is as
shown in the following chart:
7.0
7.5
8.0
Figure 3B
12”
(305mm)
Minimum
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 6" (152 mm) clearance to any overhead
combustible projection of 2-1/2" (64 mm) or less (see Figure 4). For projections exceeding 2-1/2"
(64 mm), see Figure 4. For additional vent location restrictions refer to Figure 5 on Page 7.
Horizontal Vent Termination Clearances
Figure 3A - Multiple Terminations
Combustible Projection
2-1/2 inches or less in length
All horizontal terminations
may be located as close as
6” (152mm) to any
(non-combustible and
combustible) exterior
sidewall. This distance
may be decreased to 2”
(51mm) for non-
combustible exterior
sidewalls only, if the
SV4.5HT-2 termination
is used.
Combustible Projection greater
than 2-1/2 inches in length
Ventilated
Soffit
Unventilated
Soffit
6"
(152 mm)
18"
12"
(457 mm)
(305 mm)
Termination Kit
Side Elevation View
Termination Kit
Note - See Figure 35 on Page 21 for the exterior wall recess
allowances of the square horizontal termination.
Figure 4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
VENT TERMINATION CLEARANCES
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
NOTE: Local Codes Or Regulations
May Require Different Clearances.
* See Item D in the Text Below.
Exterior Wall
P
V
N
N
NOTE: Location Of The Vent Termination
Must Not Interfere With Access To The
Electrical Service.
Inside
Corner Detail
O
*18”
V
G
V
Q
Horizontal
Termination
6”
Inside Corner
Detail D
Ventilated Soffit
A
= 9” in U.S.
= 12” in Canada
�
A
H
3 ft.
B
B
B
D
E
X
C
C
�
�
A
V
V
V
Fixed
Operable
Window
L
V
Closed
3 ft.
Window
V
F
J
M
V
C
B
B
C
X
V
I
A
X
K
V
= Air Supply Inlet
= Vent Termination
= Area where Termination is not Permitted
Canadian Installation*
12 inches (30cm)*
US Installation**
12 inches (30cm)**
A = Clearance above grade, veranda, porch,
deck, or balcony.
B = Clearance to window or door that may be
opened.
6 in (15cm) for appliances
6 in (15cm) for appliances
< 10,000 Btuh (3kW), 9 in (23cm)
for appliances > 10,000 Btuh (3kW) and
< 50,000 Btuh (15kW), 12 inches (30cm)
for appliances > 50,000 Btuh (15kW)**
< 10,000 Btuh (3kW), 12 in (30cm)
for appliances > 10,000 Btuh (3kW) and
< 100,000 Btuh (30kW), 36 inches (91cm)
for appliances > 100,000 Btuh (30kW)*
C = Clearance to permanently closed window
12" (305mm) recommended to prevent
window condensation
9" (229mm) recommended to prevent
window condensation
D = Vertical clearance to ventilated soffit
located above the terminal within a horizontal
distance of 18 inches (458mm) from the center
line of the terminal
18" (458mm)
18" (458mm)
E = Clearance to unventilated soffit
12" (305mm)
12" (305mm)
F = Clearance to outside corner
G = Clearance to inside corner
5" (12.7cm) minimum
5" (12.7cm) minimum
2" (5.08cm) minimum - SV4.5HT-2 •
2" (5.08cm) minimum - SV4.5HT-2 •
6" (15.2cm) minimum - SV4.5HTSS
6" (15.2cm) minimum - SV4.5HTSS
H = Clearance to each inside of center line
extended above meter/regulator assembly
3 feet (91cm) within a height of 15 feet
above the meter/regulator assembly*
3 feet (91cm) within a height of 15 feet
above the meter/regulator assembly**
I = Clearance to service regulator vent outlet
3 feet (91cm)*
3 feet (91cm)**
J = Clearance to nonmechanical air supply inlet 6 in (15cm) for appliances
6 in (15cm) for appliances
to building or the combustion air inlet to any
other appliance
< 10,000 Btuh (3kW), 12 in (30cm)
< 10,000 Btuh (3kW), 9 in (23cm)
for appliances > 10,000 Btuh (3kW) and
< 50,000 Btuh (15kW), 12 inches (30cm)
for appliances > 50,000 Btuh (15kW)**
for appliances > 10,000 Btuh (3kW) and
< 100,000 Btuh (30kW), 36 inches (91cm)
for appliances > 100,000 Btuh (30kW)*
K = Clearance to a mechanical air supply inlet
6 feet (1.83m)*
7 feet (2.13m)‡
12 inches (30cm)*‡
3 feet (91cm) above if within 10 feet (3m)
horizontally**
7 feet (2.13m)‡
L = Clearance above paved sidewalk or paved
diveway located on public property
M = Clearance under veranda, porch, deck or
balcony
12 inches (30cm)‡
* In accordance with the current CSA-B149.1 National Gas And Propane Installation Code.
** In accordance with the curent ANSI SZ223.1/NFPA 54 National Fuel Gas Codes.
‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves
both dwellings.
*‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:
• 2" Clearance to Non-Combustibles for SV4.5HT-2 Only.
Figure 5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Appliance and Vent Clearances
MINIMUM CLEARANCES TO COMBUSTIBLES
Maintain clearances from appliance to
combustible materials as detailed in Table
5, with the following exception: When the
appliance is installed with one side flush
with a wall, the wall on the other side of the
appliance must not extend beyond the front
edge of the appliance. In addition, when the
applianceisinstalledinthemiddleofaroom,the
side walls surrounding the appliance must not
extend beyond the front edge of the appliance.
See Figure 2 on Page 5.
Hearth Extension - A hearth extension is not required with this appliance. If a hearth extension is used,
do not block the lower control compartment access door. Any hearth extension used is for appearance
only and does not have to conform to standard hearth extension installation requirements.
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach
the area defined by the appliance front and back faces (black sheet metal). Never allow combustible
materials to be positioned in front of or overlapping the appliance front and back faces. See Figure
58 on Page 32.
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the
appliance front and back faces with the following exception: If the optional radiant panels are
installed, the non-combustible material may cover any portion of the top radiant panel or the air
gaps surrounding the top radiant panel down to the top edge of eyebrow hood. The material must
NOT cover any portion of the glass door or louvered panels.
MINIMUM CLEARANCES Inches (millimeters)
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See
Figure 6. Mantels constructed of non-combustible materials may be installed at any height above the
appliance opening; however, do not allow anything to hang below the hood.
Sides
Top Spacers
Floor
1/2 (13)
0 (0)
0 (0)
NOTE: We recommend the use of high temperature paint (rated 175° F or higher) on the under-
side of the mantel.
Bottom of Appliance
To Ceiling
64 (1626)
Mantel Depth
Minimum Mantel Clearances
3 (76) Top u
1 (25.4) Sides & Bottom
Vent
14 (356)
12 (305)
10 (254)
8 (203)
6 (152)
SERVICE CLEARANCES Feet (meters)
inches (millimeters)
Front & Back Faces
3 ft. (0.9 m)
Table 5
Top of
Appliance
uNote: 3 in. (75 mm) above any horizontal /
inclined vent component.
4 (102)
Side Clearances
12 10
8
6
4
2
Combustible materials may project beyond the
sides of the fireplace opening as long as they
are kept within the shaded areas illustrated in
Figure 8.
(305) (254) (203) (152) (102) (51)
Hood
Front or Rear Face
of Appliance
Figure 6
Combustible Materials Allowed In
Shaded Area “Safe Zone.” Com-
bustible Walls shown in dark gray.
At 14" mini-
Do not insulate this space
above the appliance.
Top View
Fireplace
At 8-1/4" side
wall clearance,
a combustible
wall can project
12"
mum side wall
clearance, a
Do not insulate this space
above the appliance.
combustible wall
can project to any
length.
Shelf Height
(see table)
Shelf Height
(see table)
45o
5
(127)
Shelf Above Fireplace With Side Venting
Shelf Above Fireplace With Top Venting
12 (305)
19 (483)
To achieve the lowest possible shelf height, use the side vent outlet. Do not insulate space between
appliance and the area above it. Maintain the minimum height from appliance base to the underside
of combustible materials (used to construct a utility shelf) as shown here.
SDVST & SDVPF Shelf Height - Inches (millimeter)
Side Vent - Straight Out Back
Secure Vent & Secure Flex
41-1/8 (1045)
Top Vent - with One 90 Degree Elbow
Protected wall
shown in white
14
(356)
8-1/4
(209)
Secure Vent
Secure Flex
Minimum Distance to
Unprotected Side Wall
53-7/8 (1366)
55-5/8 (1410)
Figure 8
Inches (millimeters)
Figure 7 - Shelf Height Minimum Clearances
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL INSTALLATION SEQUENCE
Step 1. FRAMING
WARNING
The typical sequence of installation is outlined
below. However, each installation is unique
and may result in variations to the steps
described.
FrametheseappliancesasillustratedinFigures
11 or 12. All framing details must allow for a
minimum clearance to combustible framing
members as shown in Table 5 on Page 8.
Failure to position the parts in
accordance with these diagrams
orfailuretouseonlypartsspecifi-
callyapprovedwiththisappliance
may result in property damage or
personal injury.
See the page numbers references in the follow-
ing steps for detailed procedures.
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed below the appliance.
Step 1. (Page 9) Construct the appliance
framing. Position the appliance within
the framing and secure with nailing
flanges.
Step 2. (Page 12) Route gas supply line to ap-
pliance location.
Step 3. (Page 13) Install the vent system and
exterior termination.
Step 4. (Page 26) Field Wiring – Install the
OFF/ON burner control switch and
bring in electrical service line for
forcedair-circulatingblower(optional
equipment).
Step 5. (Page 27) Install blower kit (optional
equipment).
Step 6. (Page 28) Make connection to gas sup-
ply.
Step 7. (Page 29) Verify appliance operation.
Step 8. (Page 29) Install the logs, decorative
volcanic stone and glowing embers.
Step 9. (Page 31) Install glass door assem-
blies.
Step 10. (Page 31) Adjust burner primary air
shutter to achieve proper flame appear-
ance.
AVERTISSEMENT
Headers may be in direct contact with the
appliance top spacers but must not be sup-
ported by them or notched to fit around them.
All construction above the appliance must be
self-supporting, DO NOT use the appliance for
structural support.
Risque de dommages ou de
blessures si les pièces ne sont
pas installées conformément à
ces schémas et ou si des pièces
autres que celles spécifiquement
approuvéesaveccetappareilsont
utilisées.
Side Nailing Flanges
The fireplace should be secured to the fram-
ing at the side(s) of the appliance using the
factory-provided nailing flanges. Install the 8
nailing flanges as shown in Figure 10 using the
existing screws. Position the fireplace within
the framing. When required, the tabs may be
bent 90 degrees by hand or with the assistance
of a hammer. Use wood screws to secure the
nailing flanges to the framing. See Table 5 on
Page 8 for clearances of framing members
to cabinet parts. The nailing flange itself can
directly contact framing.
DETAILED INSTALLATION STEPS
The appliance is shipped with all gas controls
and components installed and pre-wired.
1. Remove the shipping carton. Remove the
shipping pad, exposing the front glass
door.
2. Open the two latches (located under the
firebox floor) securing the glass door. Re-
move the door by tilting it outward at the
bottom and lifting it up. Set the door aside
protecting it from inadvertent damage. See
Removing Glass Panels on Page 31.
2. Remove the top louvered panel and locate
the pressure relief plates.
3. Lift the pressure relief plates and remove
the cardboard from beneath each plate (be
careful not to damage the white gasket).
See Figure 9.
Floor Nailing Tabs - Secure the fireplace to the
floor as shown in Figure 10.
Step 11. (Page 32) Install the decorative trim
and hoods.
Step 12. (Page33)AttachSafetyinOperation
Warnings.
SDVST Shown (SDVPF - No nailing
flanges on end with glass panel)
Remove these screws and use them
when installing nailing flanges.
* NOTE: INSTALLATION DIAGRAMS AND
INSTRUCTIONSSHOW THE FRONTOF THE
APPLIANCEASTHESIDEWHICHHASVALVE
ACCESS, EXCEPT WHERE NOTED.
Pressure Relief Plates
Nailing Flanges
Turn nailing tabs down and secure to floor with
8d nails or other appropriate fasteners on both
sides of appliance which do not have viewing
glass panels.
REMOVE
REMOVE
CARDBOARD
CARDBOARD
BEFORE USING
BEFORE USING
Figure 10 - Nailing Flanges
Remove Cardboard Before
Using Appliance
Figure 9
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
FIREPLACE SPECIFICATIONS - MODEL SDVST (SEE-THROUGH)
SPECIFICATIONS
• Inches (millimeters)
Fireplace Framing
Specifications
•
Minimum Framing Stud Size is 2 x 4
• See side views of fireplace below for
gas line inlet location options.
Natural & Propane
Gas BTU Input
37,500
(MV Low 30,000)
*25-1/4
v
11-3/8
(289)
(641)
4-1/2" Inner
7-1/2" Outer
10-1/2
(267)
Co-axial DV Vent Size
Vent Framing
- Top Vent With
One 90º Elbow
Dimension A
Secure Vent 47-1/8 (1197)
Secure Flex 48-3/4 (1238)
Vent Center - Top
Vent with one 90
degree elbow
10-1/2
(267)
NOTES
Vent Framing - Rear
Vent With No Elbows
7
• Annual Fuel Utilization Efficiency
(178)
12-1/8
12-1/8
(308)
Diagrams, illustrations and photographs are
not to scale – consult installation instruc-
tions. Product designs, materials, dimen-
sions, specifications, colors and prices are
subject to change or discontinuance without
notice.
(308)
5-1/8
7
(130)
(178)
5-1/8
(130)
Vent Center- Side
Vent (no elbows)
12-1/8
(308)
5-1/8
(130)
A
Appliance has a factory-installed vent seal cap
(see Figures 14 and 15 on Page 13) in each
flue outlet.
12-1/8
(308)
A
5-1/8
(130)
26-3/4
(679)
Gas
Line
*41-1/2
6-1/4
(159)
PRODUCT REFERENCE INFORMATION
26-3/4
(648)
(1054)
u
Cat.
No.
Model
Ship
Wt.
Ship.
Volume
22-3/4
(578)
H4633
SDVST
282 lbs 52W x 27D x 44-
1/2H (36.2 cu.ft).
48-1/2
(1108)
Gas Line Center of gas line is 3 in. (76 mm) up from floor.
u This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm) clearance between framing and unit framing
spacers. (The 41-1/2 in. dimension permits easier fireplace installation, if unit is installed after framing is erected).
v This dimension based on 5/8" drywall. For 1/2" drywall use 25-1/2" (648 mm). The finished dimension should be 26-1/2" (673 mm).
See also, Side Vent Seal Cap note below.
EFFICIENCIES
SDVST
61% (NG)
62 % (LP)
Vertical Venting Through the Ceiling:
Frame ceiling opening -Useaplumblinefromtheceilingabovetheappliancetolocatecenteroftheverticalrun. Cutand/orframeanopening,
10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center mark (see Figure 18 on Page 15).
72 % (NG)
73 % (LP)
Steady State
• AFUE
68 % (NG)
68 % (LP)
10
(254)
FINISH WALL BRACKET
(Front and back edge of unit top)
12 (305)
FRAMING SPACERS
(Top and Both Sides)
1/2
FLUE
(13)
(Top or Side)
5/8
(16)
40-1/8
(1019)
3-1/2
(89)
Stepped to Accept Drywall (all 4 corners)
3-1/2(89)
Detail fo Finish
Wall Bracket
Top View
2-1/2
(63.5)
1/2
(13)
24
(610)
47-1/8
(1197)
12
(305)
1/2
(13)
4 (102)
10-1/4
(260)
34-3/8
(873)
41
(1041)
2-1/2
(63.5)
Provide additional
space for Side Vent
Seal Cap if installing
against a solid wall.
GAS INLET
24
(610)
FLUE
(Top or Side)
ELECTRICAL
INLETS
37
(940)
ELECTRICAL
INLETS
3
(76)
GAS INLET
ELECTRICAL
INLETS
3 (76)
6-7/8
(175)
10-1/2
(267)
Front View
Louvered Control
Compartment Door
Figure 11
Left Side View
Right Side View
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
FIREPLACE SPECIFICATIONS - MODEL SDVPF (PENINSULA VIEW)
Fireplace Framing Specifications
• Inches (millimeters)
SPECIFICATIONS
•
Minimum Framing Stud Size is 2 x 4
• See right side viewsof fireplace below for gas line inlet location options.
Natural & Propane
Gas BTU Input
37,500
inches (millimeters)
25-1/4
v
11-3/8
(MV Low 30,000)
(641)
Minimum Framing
Stud Size is 2 x 4
Dimension A
10-1/2
(267)
4-1/2" Inner
7-1/2" Outer
Secure Vent 47 (1194)
Secure Flex 48-3/4 (1238)
Co-axial DV Vent Size
Vent Framing - Top Vent
With One 90º Elbow
Vent Center - Top
Vent with one 90
degree elbow
10-1/2
(267)
Vent Framing - Rear Vent
With No Elbows
NOTES
7
(178)
• Annual Fuel Utilization Efficiency
12-1/8
(308)
12-1/8
(308)
Diagrams, illustrations and photographs are
not to scale – consult installation instruc-
tions. Product designs, materials, dimen-
sions, specifications, colors and prices are
subject to change or discontinuance without
notice.
7
5-1/8
(178)
5-1/8
(130)
(130)
Vent Center- Side
Vent (no elbows)
12-1/8
(308)
5-1/8
(130)
A
A
5-1/8
(130)
26-3/4
(679)
Appliance has a factory-installed vent seal cap
(see Figures 14 and 15 on Page 13) in each
flue outlet.
12-1/8
(308)
Gas Line
6-1/4
(159)
*41-1/2
(1054)
u
Center of gas line
is 3 in. (76 mm)
up from floor.
26-3/4
(648)
PRODUCT REFERENCE INFORMATION
22-3/4
(578)
Dimension A
Secure Vent - 46-1/2 (1181)
Secure Flex - 48-1/4 (1226)
Cat.
No.
Model
Ship
Wt.
Ship.
Volume
43-5/8
(1108)
H4634 SDVPF
270 lbs 52W x 27D x 44-
1/2H (36.2 cu.ft).
Gas Line Center of gas line is 3 in. (76 mm) up from floor.
u This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm) clearance between framing and unit framing
spacers. (The 41-1/2 in. dimension permits easier fireplace installation, if unit is installed after framing is erected).
v This dimension based on 5/8" drywall. For 1/2" drywall use 25-1/2" (648 mm). The finished dimension should be 26-1/2" (673 mm).
See also, Side Vent Seal Cap note below.
EFFICIENCIES
SDVPF
58 % (NG)
61 % (LP)
Vertical Venting Through the Ceiling:
Frame ceiling opening -Useaplumblinefromtheceilingabovetheappliancetolocatecenteroftheverticalrun. Cutand/orframeanopening,
10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center mark (see Figure 18 on Page 15).
72 % (NG)
73 % (LP)
Steady State
10
(254)
FINISH WALL BRACKET
(Front, back, and left edge of unit top)
Stepped to Accept Drywall on 2 Corners
68 % (NG)
68 % (LP)
FRAMING SPACERS
• AFUE
(Top and Side)
12 (305)
FLUE
(Top or Side)
DETAIL OF
FINISH WALL BRACKET
1/2
(13)
5/8
(16)
40-1/8
(1019)
(89)
3-1/2
Top View
2-1/2
(63.5)
12
(305)
24
(610)
43-5/8
(1108)
1/2 (13)
4 (102)
10-1/4
(260)
37
34-3/8
(873)
(940)
41
(1041)
Provide
additional
space for Side
Vent Seal Cap
if installing
against a solid
wall.
2-1/2
(63.5)
FLUE
(Top or Side)
24
(610)
24
(610)
ELECTRICAL
INLETS
GAS INLET
3 (76)
18-1/4
(464)
Left Side View
6-7/8
(175)
Louvered Control
Compartment Door
Right Side View
Front View
Figure 12
11
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Notes:
Step 2. ROUTING GAS LINE
Proper Sizing of Gas Line
• All appliances are factory-equipped with a
flexiblegaslineconnectorand1/2inchshutoff
valve (see Figure 47 on Page 28).
Properly size and route the gas supply line
from the supply regulator to the area where the
appliance is to be installed per requirements
outlined in the National Fuel Gas Code, NFPA
54 - latest edition (USA) or CAN/CSA-B149.1
- latest edition (Canada).
Routeagaslinealongtheinsideoftherightside
framing as shown in Figure 13. Gas lines must
be routed, constructed and made of materials
that are in strict accordance with local codes
and regulations.
• See Massachusetts Requirements on Page
4for additional requirements for installations
in the state of Massachusetts in the USA.
• The gas supply line should Not be connected
to the appliance until Step 6 (Page 28).
• A pipe joint compound rated for gas should be
used on the threaded joints. Ensure propane
resistant compounds are used in propane
applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment trap
in the supply line as close as possible to the
appliance (see Figure 47). Appliances using
Propane should have a sediment trap at the
base of the tank.
Never use galvanized or plastic pipe. Refer
to Table 6 for proper sizing of the gas sup-
ply line, if black iron pipe is being used. Gas
lines must be routed, constructed and made
of materials that are in strict accordance with
local codes and regulations. We recommend
that a qualified individual such as a plumber
or gas fitter be hired to correctly size and route
the gas supply line to the appliance. Installing
a gas supply line from the fuel supply to the
applianceinvolvesnumerousconsiderationsof
materials,protection,sizing,locations,controls,
pressure,sediment,andmore.Certainlynoone
unfamiliarandunqualifiedshouldattemptsizing
or installing gas piping.
Also see Figures
11 and 12 on
Pages 10 and 11
3-1/8"
(79 mm)
5-5/8"
(143 mm)
• Checkwithlocalbuildingofficialforlocalcode
requirements(i.e.arebelowgradepenetrations
of the gas line allowed?, etc).
Figure 13 - ROUTE GAS LINE
IMPORTANT: If propane is used, be aware that
if tank size is too small (i.e. under 100-lbs, if
this is the only gas appliance in the dwelling.
Ref. NPFA 58), there may be loss of pressure,
resulting in insufficient fuel delivery (which
can result in sooting, severe delayed ignition
or other malfunctions). Any damage resulting
from an improper installation, such as this, is
not covered under the limited warranty.
Schedule 40
Black Iron Pipe
Inside Diameter (Inches)
Schedule 40 Pipe
Length (feet)
Natural
Gas
Propane
Gas
0-10
10-40
1/2
1/2
1/2
3/4
3/4
3/8
1/2
1/2
1/2
1/2
40-100
100-150
150-200
Table 6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 3. INSTALL THE VENT SYSTEM
General Information
Vent Seal Cap
Insulation
These instructions should be used as a guideline and do not supersede
local codes in any way. Install venting according to local codes, these
instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the
USA or the current standards of CAN/CSA-B149.1 in Canada.
CROSS SECTION
(OUTSIDE of
Appliance)
(INSIDE of
Appliance)
Ensure clearances are in accordance with local installation codes and
the requirements of the gas supplier.
Dégagementconformeauxcodesd'installationlocauxetauxexigences
du foumisseunde gaz.
Side Vent
Securing Screws
Use only approved venting components. See Approved Vent
Components on Page 2.
Cabinet Back
SIDE VENT SEAL CAP REMOVAL
(SIDE VENT INSTALLATIONS ONLY)
Figure 15 -
These fireplaces must be vented directly to the outside.
The vent system may not service multiple appliances, and must never
be connected to a flue serving a solid fuel burning appliance. The vent
pipe is tested to be run inside an enclosed wall (such as a chase). There
is no requirement for inspection openings in the enclosing wall at any of
the joints in the vent pipe.
WARNING
The VENT SEAL CAP must remain securely installed
on unused vent collar. Failure to do so could result in
leakage of flue products into living space.
REMOVE VENT SEAL CAP
(From the vent that will be used only)
Installation of Vent Restrictor
Top Vent - See Figure 14 and Side Vent - See Figure 15
(Top Vent Installations with Vertical Terminations Only)
Preparing the Appliance Vent Collar
A vent restrictor (provided) may be needed with this appliance. If needed,
install the vent restrictor (provided) in the appliance top flue outlet as
shown in Figure 16 when vertically terminating the vent system above
the roof. It may be installed either from inside or outside the appliance,
in the inner fireplace collar. It is press-fitted in place.
Each of the appliances' two vent collars are sealed with a seal cap which
must be removed from the vent collar being used. Refer to Figure 14
for top vent installations and Figure 15 for side vent installations and
the following steps to prepare the appropriate collar for use.
From the vent collar being used, remove the two screws securing the
vent seal cap. Twist the cap counterclockwise. Pull it away from the
appliance and discard, along with the piece of insulation.
Note: The restrictor is included within the firebox.
Restrictor
Securing Screws
Top Vent
Vent Seal Cap
(OUTSIDE OF
APPLIANCE)
Insulation
Vent Restrictor
Installation
(Top Vent)
Cabinet Top
Appliance Top
Vent Outlet
Figure 16
CROSS SECTION
Firebox Top
Select Venting System - Horizontal or Vertical
(INSIDE of Appliance)
TOP VENT SEAL CAP REMOVAL
(TOP VENT INSTALLATIONS ONLY)
With the appliance secured in framing, determine vent routing and identify
the exterior termination location. The following sections describe vertical
(roof) and horizontal (exterior wall) vent applications. Refer to the section
relating to your installation. A list of approved venting components is
shown on Pages 34 to 36.
Figure 14 -
13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
VERTICAL TERMINATION SYSTEMS (ROOF)
VENT SECTION LENGTH CHART
VENT SECTION LENGTH CHART
T
O
T
A
L
Nominal
Section Length
(inches)
6
12
24
36
48
NominalSection
Length (inches)
6
12
24
36
48
See Figure 17 and Figures 28 to 32 (Pages 18
and19)andtheirassociatedVerticalVentTables
illustratetheverticalventingconfigurationsthat
are allowed to be used with these appliances.
Secure Vent™ pipe applications are shown in
these figures; Secure Flex™ pipe may also be
used. See Page 25. A Vertical Vent Table sum-
marizeseachsystem’sminimumandmaximum
verticalandhorizontallengthvaluesthatcanbe
used to design and install the vent components
in a variety of applications.
T
O
T
A
L
NetSection
Length (inches)
4 ½ 10 ½ 22 ½ 34 ½ 46 ½
Number of Vent Sections
NetSection
Length (inches)
4 ½ 10 ½ 22 ½ 34 ½
Number of Vent Sections
46
½
Q
T
Y
Height of Vent
Q
T
Height of Vent
uinch
feet
Y
uinch
feet
144
150
12
1
0
1
0
0
1
0
0
1
0
0
0
1
0
1
1
2
0
0
1
0
0
1
1
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
5
5
5
0
0
0
5
6
6
3
3
3
3
0
0
0
4
4
4
0
0
0
4
4
5
5
5
6
6
4
5
5
7
6
7
4.5
9
0.375
0.75
1
2
0
1
2
0
0
1
0
0
1
0
0
1
1
1
2
0
2
3
0
1
0
0
0
0
0
0
1
0
0
0
1
0
0
0
0
0
0
0
0
0
1
0
0
0
0
1
2
1
2
3
2
1
3
3
1
3
12.5
154.5 12.875
160.5 13.375
172.5 14.375
10.5 0.875
15 1.25
19.5 1.625
21 1.75
0
0
Both these vertical vent systems terminate
through the roof. The minimum vent height
above the roof and/or adjacent walls is speci-
fied in ANSI Z223.1-(latest edition) (In Canada,
the current CAN/CSA-B149.1 installation code)
by major building codes. Always consult your
localcodesforspecificrequirements.Ageneral
guide to follow is the Gas Vent Rule (refer to
Figure 3B on Page 6).
177
183
186
14.75
15.25
15.5
0
0
0
0
0
0
22.5 1.875
25.5 2.125
31.5 2.625
34.5 2.875
37.5 3.125
190.5 15.875
196.5 16.375
205.5 17.125
43.5 3.625
0
0
0
1
2
0
0
0
1
2
0
2
0
0
0
0
0
0
1
0
3
2
1
3
207
17.25
45
3.75
211.5 17.625
A vent restrictor will need to be installed when
vertical termination is used. See Installation of
Vent Restrictor on Page 13 for guidelines.
46.5 3.875
49.5 4.125
217.5 18.125
229.5 19.125
232.5 19.375
0
0
0
1
0
1
0
0
0
0
1
1
0
0
0
1
0
1
0
0
1
0
1
0
0
1
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
6
6
0
0
5
5
0
0
0
0
0
6
0
6
6
6
0
0
7
7
7
0
0
8
8
0
9
9
7
7
51
4.25
1
0
0
0
0
0
1
1
0
0
0
0
0
1
1
0
1
0
2
0
0
0
0
1
0
2
0
0
0
0
0
2
1
2
3
0
3
0
0
0
1
2
0
1
0
0
0
1
0
0
2
0
2
2
1
0
0
0
2
0
1
0
0
0
0
0
0
0
0
1
1
1
2
0
2
2
3
2
4
3
2
4
3
3
2
4
3
2
4
3
0
5
Vertical (Straight) Installation
237
19.75
0
6
55.5 4.625
Determine the number of straight vent sections
required. 4-1/2" (114 mm), 10-1/2" (267 mm),
22-1/2" (572 mm), 34-1/2" (876 mm) and 46-
1/2" (1181 mm) net section lengths are avail-
able (see Table 7 and Page 34 - Item 3). It is
recommended that you plan the vent lengths
so that a section joint does not occur within the
space defined by ceiling joists or roof rafters.
Refer to the Vent Section Length Chart.
241.5 20.125
7
7
57
66
4.75
5.25
246
252
264
276
279
20.5
21
7
8
7
8
67.5 5.625
22
7
8
69
72
5.75
6
23
8
8
23.25
0
6
73.5 6.125
79.5 6.625
280.5 23.375
283.5 23.625
289.5 24.125
301.5 25.125
310.5 25.875
8
9
0
7
81
90
6.75
7.5
0
7
SV4.5CGV-1
0
7
91.5 7.625
SV4.5FA orSV4.5FB
Termination
9
9
93
96
7.75
8
Flashing and SV4.5SC
Storm Collar
315
26.5
9
10
7
325.5 27.125
0
97.5 8.125
102 8.5
103.5 8.625
330
336
345
27.5
28
0
8
2
0
1
0
0
0
0
0
0
0
3
3
2
0
0
4
3
4
0
8
108
114
117
9
28.75
10
10
0
10
11
8
1” (25.4 mm)
Minimum
Clearance to
Combustibles
349.5 29.125
372 31
9.5
9.75
0
1
1
0
1
0
0
0
1
2
0
1
0
0
0
0
0
0
0
5
0
1
1
6
0
0
0
0
0
3
3
3
0
4
0
4
2
0
0
0
0
0
0
3
0
4
6
5
4
5
6
4
3
5
376.5 31.375
379.5 31.625
418.5 34.875
0
9
118.5 9.875
126 10.5
130.5 10.875
11
0
11
9
SV4.5VF
u
Firestop / spacer
423
465
35.25
38.75
0
10
135
138
11.25
11.5
0
10 10
139.5 11.625
142.5 11.875
40 ft. Max.
(12.2 M)
SV4.5L6 / 12 / 24 / 36 / 48
Vent Sections
Effective Vent Length
Model
Effective Length
When using Secure
u
Flex use Firestop / spacer
SF4.5VF
* Convert inches into metric equiva-
lent measure, as follows:
SV4.5L6
SV4.5L12
SV4.5L24
SV4.5L36
SV4.5L48
4-1/2"
10-1/2"
22-1/2"
34-1/2"
46-1/2"
See Figure 22 on Page
16 for "support strap"
requirements
Millimeters (mm) = Inches x 25.4
Centimeters (cm) = Inches x 2.54
Meters (M) = Inches x .0254
Figure 17
Table 7
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Vertical (Offset) Installation
B. Attach vent components to appliance - Se-
cure Vent SV4.5 direct-vent system compo-
nents are unitized concentric pipe components
featuring positive twist lock connections (see
Figure 19).
Push the vent component against the previous
section until it fully engages, then twist the
componentclockwiserunningthedimplesdown
and along the incline channels until they seat at
the end of the channels. This seating position
isindicatedbythealignmentofthearrowand
dimple as shown in Figure 19.
Analyze the vent routing and determine the
number of vent sections and elbows required.
Refer to Vertical Vent Figures and Tables on
Pages 18 and 19 to select the type of vertical
installation desired. Vent sections are available
in net lengths of 4-1/2" (114 mm), 10-1/2" (267
mm), 22-1/2"(572mm), 34-1/2"(876mm)and
46-1/2" (1181 mm). Refer to the Vent Section
LengthChartsonPage14 foranaidinselecting
ventlengthcombinations. Elbowsareavailable
in 45° and 90° configurations. Refer to Figure
24 on Page 16 for the SV4.5E45 and SV4.5E90
elbow dimensional specifications.
All of the appliances covered in this document
are fitted with collars having locking inclined
channels. The dimpled end of the vent com-
ponents fit over the appliance collar to create
the positive twist lock connection.
D1. Install firestop/spacer at ceiling between
stories - Install a firestop/spacer (catalog
no. H2247 - Secure Vent; catalog no. H2249
- Secure Flex) at the bottom side of the ceiling
to the ceiling joists. Route the vent sections
through the framed opening and secure the
firestop/spacer with appropriate fasteners at
each corner.
Align the dimple (four places) of the
upper vent section with the opening
of the locking incline channel on the
lower vent section or appliance col-
lar. Twist vent component clockwise
to engage and seal until arrow and
Where required, a Telescopic Vent Section
(SV4.5LA) may be used to provide the installer
with an option in installing in tight and confined
spaces or where the vent run made up of fixed
length pieces develops a joint in a undesirable
location, or will not build up to the required
length. The SV4.5LA Telescopic Vent Section
has an effective length of from 1-1/2" (38 mm)
to 7-1/2" (191 mm). The SV4.5LA is fitted with
a locking inclined channel end (identical to a
normalventsectioncomponent)andaplainend
with 3 pilot holes. Slip the plain end over the
locking channel end of a standard SV4.5 vent
component the required distance and secure
with three screws.
dimple align.
Arrow
Remember to maintain 1" (25 mm) clear-
ance between vertical chimney sections and
combustibles, framing members, and attic
or ceiling insulation.
Dimple
Locking Incline
Channel
D2. Install firestop thimble at the ceiling to
roof location - Position appropriate firestop
thimble (see Table on Page 36) at the bottom
side of ceiling and secure temporarily with
twoappropriatefasteners.Attachpermanently,
usingatleasttwomorefasteners,afterventsec-
tionshavebeenassembledthroughthefirestop
thimble and after any necessary adjustments
have been made.
Connected Vent
Sections
Arrow
Appliance Collar or
Vent Section
Figure 19
Maintain a minimum 1" (25 mm) clearance
to combustible materials for all vertical ele-
ments.Clearancesforallhorizontalelements
are 3" (76 mm) on top, 1" (25 mm) on sides
and 1" (25 mm) on the bottom.
To attach a vent component to the appliance
collar, align the dimpled end over the collar,
adjustingtheradialalignmentuntilthefourlock-
ing dimples are aligned with the inlet of the four
inclined channels on the collar (refer to Figure
19).Pushtheventcomponentagainstthecollar
until it fully engages, then twist the component
clockwise,runningthedimplesdownandalong
the incline channels until they seat at the end of
thechannels. TheunitizeddesignoftheSecure
Vent components will engage and seal both the
innerandouterpipe withouttheneedforsealant
or screws. If desired a #6 x 1/2" screw may be
used at the joint, but it not required as the pipe
will securely lock when twisted.
Ensurethethimblepenetratestheroofopening.
Thethimblemustextendcompletelythroughthe
ceiling or roof cavity to the outermost plane of
the roof. Use thimble extension SVTE26 when
thedistancebetweentheoutsideoftheroofand
the inside of the ceiling exceeds the height of
the firestop thimble. The thimble provides for
zero clearances to combustibles and must be
usedattheceiling/roofinmanufacturedhomes
with Secure Vent double wall vent sections.
Maintain 1 in. (25.4 mm) clearance between
the thimble and the outer pipe of the secure
vent chimney system. See Figure 21 (Page
16) for pitched roofs or flat roofs with flat
ceilings or Figure 20 for pitched roofs with
cathedral ceilings.
A. Frame ceiling opening - Use a plumb line
from the ceiling above the appliance to locate
center of the vertical run. Cut and/or frame
an opening, 10-1/2" x 10-1/2" (267 mm x 267
mm)insidedimensions, aboutthiscentermark
(Figure 18).
10-1/2" Min.
(267 mm)
Note: An elbow may also be attached to the
appliance collar. Attach in the same manner
as you would a vent section.
C. Attach vent components to each other
- Other vent sections may be added to the
previously installed section in accordance with
the requirements of the vertical vent Figures
and Tables. To add another vent component
to a length of vent run, align the dimpled end
over the inclined channel end of the previously
installedsection, adjustingtheradialalignment
until the four locking dimples are aligned with
the inlets of the four incline channels of the
previous section.
Roof
10-1/2" Min.
(267 mm)
Framing
Outer Pipe Of
Chimney
14" Min.
Ceiling
Framing
Plumb
Bob
Use correct firestop
thimble depending on the
pitch of the interior
ceiling.
Note: Regular Thimble
(SV-FSTFE) Can Be Used
If A Header Is Constructed
At This Point
Figure 20
Figure 18
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
F.Changeventdirectiontohorizontal/inclined
run - At transition from or to a horizontal / in-
clined run, install the SV4.5E45 and SV4.5E90
elbows in the same manner as the straight vent
sections. The elbows feature a twist section to
allow them to be routed about the center axis
of their initial collar section to align with the
required direction of the next vent run element.
Twist elbow sections in a clockwise direction
onlysoastoavoidthepossibilityofunlocking
anyofthepreviouslyconnectedventsections.
See Figure 24.
Outer Pipe Of
Chimney
14" Min.
Firestop
Thimble
Blocking
Support Straps
(Plumber's tape)
Pitched Roof
Outer Pipe Of
Chimney
Note: Trim Thimble/
Extension To Desired Length
And Pitch At The Roof Line
14" Min.
8 feet (2.4 m)
Maximum
Extension
Thimble
SV-FSTFE
13"
Firestop
Thimble
8-1/8"
(206 mm)
4-13/16
1 inch (25.4
Pitched Roof
(122 mm)
mm) minimum
clearance to
combustibles
Outer Pipe Of
Chimney
Swivel Joint
(360° swivel)
SV4.5E45
Swivel Joint
(360° swivel)
SV4.5E90
14" Min.
Figure 22
Firestop
Thimble
45° Elbow)
90° Elbow)
Another method, where the vent is not adjacent
to a wall, is illustrated in Figure 23. Here,
support straps (96K93) and support plates
(96K92) can be used to support the weight
of the vent.
Figure 24
Bow Roof
Figure 21
G.Continueinstallationofhorizontal/inclined
sections - Continue with the installation of the
straightventsectionsinhorizontal/inclinedrun
as described in Step C. Install support straps
every 5 feet (1.52 m) along horizontal / inclined
vent runs using conventional plumber’s tape.
See Page 20, Figure 33. It is very important
thatthehorizontal/inclinedrunbemaintained
in a straight (no dips) and recommended to
be in a slightly elevated plane, in a direction
awayfromthefireplaceof1/4"riseperfoot(20
mm per meter) which is ideal, though rise per
footrunratiosthataresmallerareacceptable
all the way down to at or near level.
E. Support the vertical vent run sections -
Note-Properventingsupportisveryimportant.
The weight of the vent must not be supported
by the fireplace in any degree.
SV4.5CGV-1
SV4.5FA or
Termination
SV4.5FB Flashing
and SV4.5SC
Storm Collar
Support the vertical portion of the venting
system every 8 feet (2.4 m) above the fireplace
vent outlet.
1” (25.4 mm)
vWhen using
secure Flex, use
Firestop/Spacer
SF4.5VF
Minimum
Clearance to
Combustibles
One method of support is by utilizing field pro-
vided support straps (conventional plumber's
tape). Secure the plumber's tape to the framing
members with nails or screws. Loop the tape
aroundthevent,securingtheendsofthetapeto
the framing. If desired, sheet metal screws #6
x 1/2" length may be used to secure the support
straps to the vent pipe. See Figure 22.
vSV4.5VF
Ceiling Framing
Firestop / spacer
uSV4.5SP
Support Plate
8 ft. (2.4 M)
Maximum
uSV4.5SU
Support Strap
uSecured
to Vent with
Appropriate
Fasteners
Figure 23
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Use a carpenter’s level to measure from a
constant surface and adjust the support straps
as necessary.
I. Install the roof flashing - Extend the vent
sections through the roof structure. Install the
roof flashing over the vent section and position
such that the vent column rises vertically (use
carpenters level - see Figure 26). Nail along
perimeter to secure flashing or adjust roofing
to overlap the flashing edges at top and sides
only and trim where necessary. Seal the top
and both sides of the flashing with waterproof
caulking.
K. Install the vertical termination - The final
Step involves installation of the SV4.5CGV-1
Vertical Termination. Extend the vent sections
to the height as shown in the "Vertical vent
termination section" (Page 6, Figures 3A and
3B). The SV4.5CGV-1 Vertical Termination
(Figure 27) can be installed in the exact same
fashionasanyotherSecureVentsection. Align
the termination over the end of the previously
installedsection, adjustingtheradialalignment
untilthefourlockingdimplesofthetermination
are aligned with the inlets of the four incline
channels of the last vent section. Push the ter-
mination down until it fully engages, then twist
the termination clockwise running the dimples
down and along the incline channels until they
are seated at the end of the channels.
It is important to maintain the required clear-
ancestocombustibles:1"(25mm)atallsides
forallverticalruns;and3"(76mm)atthetop,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal / inclined runs.
H. Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per
Roof Framing Chart and Figure 25.
J. Install the storm collar - Install the storm
collar, suppliedwiththeflashing, overthevent/
flashingjoint.SeeFigure26. Loosenthestorm
collar screw. Slide collar down until it meets
the top of the flashing. Tighten the adjusting
screw. Apply non-combustible caulking or
mastic around the circumference of the joint
to provide a water tight seal.
C
D
Storm
Collar
Framing Dimensions for Roof
Inches (millimeters)
Pitch
0/12
C
D
10-1/2 in.
(267 mm)
10-1/2 in.
(267 mm)
Flashing
6/12
10-1/2 in.
(267 mm)
12 in.
(305 mm)
12/12
10-1/2 in.
(267 mm)
17 3/4 in.
(451 mm)
Figure 26
Figure 27
Figure 25 - Roof Framing
If the vent system extends more than 5 feet (1.5
m) above the roof flashing, stabilizers may be
necessary. Additional screws may be used at
section joints for added stability. Guide wires
may be attached to the joint for additional sup-
port on multiple joint configurations.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
VERTICAL VENT FIGURES/TABLES
Notes:
Table A
V Minimum
• Secure Vent™ (rigid vent pipe) is shown
intheFigures;SecureFlex™(flexiblevent
pipe) may also be used.
H Maximum
feet (meter)
uCeiling Firestop / Spacer (SV4.5VF)
feet
(meter)
(0.305)
(0.610)
(0.914)
(1.219)
• It is very important that the horizontal/in-
clined run be maintained in a straight (no
dips) and recommended to be in a slightly
elevated plane, in a direction away from
the fireplace of 1/4" rise per foot (20 mm
per meter) which is ideal, though rise per
footrunratiosthataresmallerareacceptable
all the way down to at or near level.
• SV4.5VF (Secure Vent), SF4.5VF (Secure
Flex) firestop/spacer must be used anytime
vent pipe passes through a combustible
floor or ceiling. SV4.5HF (Secure Vent),
SF4.5HF (Secure Flex) firestop/spacer must
be used anytime vent pipe passes through
a combustible wall.
• Two 45 degree elbows may be used in place
of one 90 degree elbow. The same rise to
run ratios, as shown in the venting Figures
for90elbows, mustbefollowedif45degree
elbows are used.
• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF
VERTICALRISEEXCEPTWHEREANELBOW
IS THE ONLY VERTICAL COMPONENT IN
THE SYSTEM (See Figure 37).
2
4
6
8
(0.610)
(1.219)
(1.829)
(2.438)
1
2
3
4
V
V + H = 40 feet (12.2 meters) Max.
H = 8 feet (2.4 meters) Max.
Ratio V to H ratio is 1:2
uWhen using Secure Flex, use Firestop /
H
Spacer SF4.5VF.
Example: If 8 feet of (H) horizontal vent run is needed, then 4 feet minimum (V) vertical vent will be
required.
This table shows a 1(V) to 2(H) ratio. For every 1 foot of (V) vertical, you are allowed 2 feet of (H)
horizontal run, up to a maximum horizontal run of 8 feet.
Figure 29 - Side Vent - ONE 90 DEGREE ELBOW
Table B
H Maximum
feet (meter)
V Minimum
feet (meter)
Elbow Only
WARNING
Undernocircumstances,maysepa-
rate sections of concentric flexible
vent pipe be joined together.
H
5
(1.524)
(1.524)
(3.048)
(4.572)
(6.096)
5
1
(0.305)
(0.610)
(0.914)
(1.219)
10
15
20
2
3
4
Ceiling Firestop /
Spacer (SV4.5VF)
u
uCeiling Firestop /
V + V + H = 40 feet (12.2 m) Max.
1
Spacer (SV4.5VF)
H = 20 feet (6.096 meters) Max.
V1
Example: If 20 feet of (H) hori-
zontal vent run is needed, then 4
feet minimum of (V) vertical vent
40 feet
will be required.
V
(12.2 meters)
Maximum
This table shows a 1(V) to 5(H)
ratio. Forevery1footof(V)verti-
cal, you are allowed 5 feet of (H)
horizontal run, up to a maximum
horizontal run of 20 feet.
A Vent Restrictor, as
shown in Figure 16,
Page 13, must be used
in this application
Wall Firestop/
v
Spacer (SV4.5HF)
An elbow is acceptable as 1 foot
of vertical rise except where
an elbow is the only vertical
component in the system. See
Figure 37.
uWhen using Secure Flex, use
vWFirheesntoupsi/nSgpSaecceurrSeFF4l.e5xV,Fu.se
Firestop / Spacer SF4.5HF.
WhenusingSecureFlex,useFirestop/Spacer
SF4.5VF
u
Figure 30 - Top Vent - TWO 90 DEGREE ELBOWS
Figure 28 - Top Vent - STRAIGHT
18
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
VERTICAL VENT FIGURES / TABLES (CONTINUED)
Table C
H1
H+H Maximum
HMaximum
V Minimum
1
feet (meter) feet (meter)
feet
(meter)
(0.305)
(0.610)
(0.914)
(1.219)
Ceiling Firestop /
u
5
(1.524)
(3.048)
(4.572)
(6.096)
2
4
6
8
(0.610)
(1.219)
(1.829)
(2.438)
1
2
3
4
Spacer (SV4.5VF)
10
15
20
V + V + H + H = 40 feet (12.2 m) Max
H = 8 feet (2.438 meters) Max.
Wall Firestop/
v
1
1
Spacer (SV4.5HF)
V1
H + H = 20 feet (6.096 meters) Max.
1
Ceiling Firestop /
u
Spacer (SV4.5VF)
uWhen using Secure Flex, use Firestop / Spacer SF4.5VF
vWhen using Secure Flex, use Firestop / Spacer SF4.5HF
Example: If 20 feet total (H+H1) horizontal vent run is needed,
then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H+H1) horizontal run up to a
maximum total horizontal run of 20 feet.
V
H
Figure 31 - Side Vent - THREE ELBOWS
Table D
V Minimum
(meter)
Elbow Only
(0.305)
H + H Maximum
1
feet
(meter)
(1.524)
(1.524)
(3.048)
(4.572)
(6.096)
feet
5
Ceiling
u
Firestop / Spacer
(SV4.5VF)
5
1
2
3
4
V
1
Wall Firestop/
v
10
15
20
(0.610)
(0.914)
(1.219)
Spacer (SV4.5HF)
H
H + H = 20 feet (6.096 m) Max.
V + V + H + H = 40 ft. (12.192 m) Max.
1
1
1
V
H
uWhen using Secure Flex, use Firestop / Spacer SF4.5VF
1
vWhen using Secure Flex, use Firestop / Spacer SF4.5HF
Example: If 20 feet total (H+H1) horizontal vent run is needed, then 4 feet minimum
of (V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V) vertical, you are allowed
5 feet of (H+H1) horizontal run up to a maximum total horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only
vertical component in the system. See Figure 37.
Figure 32 - Top Vent - THREE ELBOWS
19
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Push the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples
down and along the incline channels until they
seat at the end of the channels. This seating
position is indicated by the alignment of the
arrow and dimple as shown in Figure 19 on
Page 15.
Support
Brackets
Horizontal / Inclined Run
Building
Support
Framing
SV4.5HT-2
Termination
Shown
SV4.5E90
Elbow
SV4.5L6/12/24/36/48
Vent Sections
Exterior
Wall
Ceiling
Firestop / Spacer
u
F. Install firestop / spacer at ceiling -
SV4.5VF
Vertical
Rise
Install a Secure Vent SV4.5VF firestop/spacer
at the bottom side of the ceiling to the ceiling
joists. Route the vent sections through the
framedopeningandsecurethefirestop/spacer
with appropriate fasteners at each corner.
Support Bracket Spacing
Every 5 ft (1.52 m)
When Using Secure Flex,
u
Use Firestop / Spacer SF4.5VF
SV4.5HT-2
Termination
Shown
See Figures 22 and 23 on
Page 16 for vertical vent
section support.
If there is living space above the ceiling level,
the firestop/ spacer must be installed on the
bottom side of the ceiling. If attic space is
above the ceiling, the firestop/ spacer must
be installed on the top side of the joist. Route
the vent sections through the framed opening
and secure the firestop / spacer with 8d nails
or other appropriate fasteners at each corner.
Fireplace
Figure 33 -TYPICAL HORIZONTAL VENT INSTALLATION
B. Frame exterior wall opening -
HORIZONTAL (OUTSIDE WALL)
TERMINATION SYSTEM
Locate the center of the vent outlet on the exte-
rior wall according to the dimensions shown in
Figures 11 and 12 on Pages 10 and 11.
Remember to maintain 1" (25 mm) clearance
tocombustibles,framingmembers,andattic
or ceiling insulation when running vertical
chimney sections. Attic insulation shield
(H3907) may be used to obtain the required
clearances indicated here. See installation
accessories tables on Pages 34 through 36.
See Figure 33, and Figures 36 to 41 (Pages
22 to 24) and their associated Horizontal Vent
Table which illustrates the horizontal venting
configurations that are allowed to be used with
theseappliances. SecureVentpipeapplications
areshowninthesefigures;SecureFlexpipemay
also be used (see Page 25). A Horizontal Vent
Tablesummarizeseachsystem’sminimumand
maximum vertical and horizontal length values
that can be used to design and install the vent
components in a variety of applications.
Cut and/or frame an opening, 10-1/2" x 12-1/8"
(267 mm x 308 mm) inside dimensions, about
this center.
C. Frame ceiling opening - If the vertical route
istopenetrateaceiling,useplumblinetolocate
thecenterabovetheappliance.Cutand/orframe
an opening, 10-1/2" x 10-1/2" (267 mm x 267
mm)insidedimensions,aboutthiscenter(refer
to Figure 18 on Page 15).
G. Support the vertical run sections -
See Step E on Page 16.
H. Change vent direction - At transition from
or to a horizontal / inclined run, install the
SV4.5E45 and SV4.5E90 elbows in the same
manner as the straight vent sections. The
elbows feature a twist section to allow them to
be routed about the center axis of their initial
collar section to align with the required direc-
tion of the next vent run element. Twist elbow
sections in a clockwise direction only so as
to avoid the possibility of unlocking any of
the previously connected vent sections. See
Figure 24 on Page 16.
Bothofthesehorizontalventsystemsterminate
throughanoutsidewall. BuildingCodeslimitor
prohibit terminating in specific areas. Refer to
Figure 5 on Page 7 for location guidelines.
D. Attach vent components to appliance - To
attachaventcomponenttotheappliancecollar,
align the dimpled end over the collar, adjust-
ing the radial alignment until the four locking
dimples are aligned with the inlets of the four
incline channels on the collar (refer to Figure
19 on Page 15).
Secure Vent SV4.5 direct-vent system compo-
nents are unitized concentric pipe components
featuring positive twist lock connection, (refer
to Figure 19 on Page 15). All of the appli-
ances covered in this document are fitted with
collars having locking inclined channels. The
dimpled end of the vent components fit over
the appliance collar to create the positive twist
lock connection.
Push the vent component against the collar
until it fully engages, then twist the component
clockwise,runningthedimplesdownandalong
the incline channels until they seat at the end of
thechannels.TheunitizeddesignoftheSecure
Ventcomponentswillengageandsealboththe
inner and outer pipe elements with the same
procedure. Sealant and securing screws are
not required.
I.Continueinstallationofhorizontal/inclined
sections - Continue with the installation of the
straightventsectionsinhorizontal/inclinedrun
as described in Step E. Install support straps
every 5 ft. (1.52 m) along horizontal / inclined
vent runs using conventional plumber’s tape.
See Figure 33. It is very important that the
horizontal / inclined run be maintained in a
straight (no dips) and recommended to be in
a slightly elevated plane, in a direction away
from the fireplace of 1/4" rise per foot (20 mm
per meter) which is ideal, though rise per foot
runratiosthataresmallerareacceptableallthe
way down to at or near level. Use a carpenter’s
level to measure from a constant surface and
adjust the support straps as necessary.
A. Plan the vent run -
Analyze the vent routing and determine the
types and quantities of sections required
4-1/2"(114mm),10-1/2"(267mm),22-1/2"(572
mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm)
net section lengths are available. It is recom-
mended that you plan the vent lengths so that
a section joint does not occur within the space
definedbyceilingjoists,roofraftersorwallstuds.
MakeallowancesforelbowsasindicatedinFigure
24 on Page 16.
E. Attach vent components to each other
- Other vent sections may be added to the
previouslyinstalledsectioninaccordancewith
the requirements of the vent tables.
To add another vent component to a length
of vent run, align the dimpled end of the
component over the inclined channel end of
the previously installed section, adjusting the
radial alignment until the four locking dimples
are aligned with the inlets of the four incline
channels of the previous section.
Maintain a minimum 1" (25 mm) clearance to
combustibles on the vertical sections. Clear-
ances for the horizontal runs are; 3" (76 mm)
on top, 1" (25 mm) on sides, and 1" (25 mm)
at the bottom.
20
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
It is important to maintain the required clear-
ancestocombustibles:1"(25mm)atallsides
for all vertical runs; and 3" (76 mm) at the
top, 1" (25 mm) at sides, and 1" (25 mm) at
the bottom for all horizontal / inclined runs.
To help minimize water infiltration it is
recommended that the Firestop/Spacer
(SV4.5HF) be installed on the exterior
side of the wall.
SV4.5 HT-2
Termination
7"
(178)
10¹⁄₂"
12¹⁄₈"
(267mm)
(308 mm)
J. Assemble vent run to exterior wall - If not
previously measured, locate the center of the
vent at the exterior wall. Prepare an opening
as described in Step B. Assemble the vent
system to point where the terminus of the last
sectionislocatedrelativetotheexteriorsurface
to which the termination is to be attached as
shown in Figure 34.
5¹⁄₈"
(130 mm)
3"
(76 mm)
1"
Adapter
SV4.5RCH
(25.4 mm)
If the terminus of the last section is not within
this distance, use the telescopic vent section
SV4.5LA, as the last vent section. For wall
thicknesses greater than that shown in Figure
35, refer to Table 8 on Page 22. This Table lists
the additional venting components needed (in
addition to the termination and adapter) for a
particular range of wall thicknesses.
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Framed Opening.
See Figures 11 and 12 on Pages 10 and
11 for Min. Distance to Base of Appliance.
6 to 48 inch Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Base of Appliance
Figure 34 - INSTALLING SQUARE HORIZONTAL TERMINATION (SV4.5HT-2)
K. Attach termination adapter - Attach the
adapter (SV4.5RCH - provided with the termi-
nation) to the vent section or telescoping vent
section), elbow or appliance collar as shown in
Figures 34 and 35 in the same manner as any
SV4.5 vent component (refer to Step E).
Maximum wall thickness
Use silicone caulking to seal
�
9
-
1/ (2 5m
in
4
.
3
m)
v
the top and sides of the
termination, up to the
underlayment, stucco, or
masonry wall surface.
Exterior Surface of Siding
Exterior Surface of
Framing
Interior Surface of
Finished Wall
Maximum Extent of
Vent Run Sections
Relative to Exterior
Surface of Framing
L. Install Firestop / Spacer at exterior wall
Siding
6 in. to 9-1/4 in.
(152 to 235 mm)
�
Caulk
-
When using the square termination, install
�
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)
Firestop/Spacerovertheopeningattheexterior
sideoftheframing, longsideup, withthe3inch
spacer clearance at the top as shown in Figure
34, and nail into place.
Last Vent Section.
Use Telescopic Vent
Section (SV4.5LA), If
Necessary
SV4.5 HT-2
Termination
Caulk
�
(TheFirestop/Spacermayalsobeinstalledover
the opening at the interior side of framing).
SV4.5 HT-2
Termination
Adapter
SV4.5RCH
1-1/4” Maximum Recess of
Square Termination
M. Install the Square Termination (SV4.5HT-2)
into Exterior Finishing Material
For the last step, from outside the exterior wall,
slide the collars of the termination onto the
adapter until the termination seats against the
exteriorwallsurfacetowhichitwillbeattached.
Orient the housing of the termination with the
arrowpointedupwards. Securethetermination
totheexteriorwall. Thehorizontaltermination
must not be recessed into the exterior wall
or siding by more than the 1-1/4" (32 mm) as
shown in Figure 35.
Stucco
For thicknesses greater than
v
9-1/4", see Table 8 on Page 22
Venting Connection and Exterior Wall Recessing of the Horizontal Square
Termination (SV4.5HT-2).
Figure 35
Horizontal terminations have been designed to perform in a wide range of weather condi-
tions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termina-
tion where water from eaves and adjoining rooflines may create a heavy flow of cascad-
ing water onto the termination cap. If the cap must be placed where the possibility of
cascading water exists, it is the responsibility of the builder to direct the water away
from the termination cap by using gutters or other means.
IMPORTANT: The vent termination is hot
whileinoperationandforaperiodoftime
following the use of the fireplace. Young
children should be carefully supervised
when they are in the same area as a hot
termination. To prevent contact with hot
surfaces, we recommend the use of a
Termination Guard. See Page 34. This
can be purchased at your local dealer.
Take care to carefully follow the installation instructions for the termination, including
the use of silicon caulking where required.
21
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
See Table 8 as an aid in venting component selection for a particular
range of exterior wall thicknesses.
Square termination
(SV4.5HT-2) shown.
H = 28 in. (711 mm)
Maximum
Venting Components Required for Various Exterior Wall Thick-
nesses, when using Square Termination Kit (SV4.5HT-2)
21 in. (533 mm)
Maximum
Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only
6 to 9-1/4 (152 to 235)
7 in. (711 mm)
TerminationKitand 6In.Vent
Section (SV4.5L6)
10-3/4 to 14 (273 to 356)
Termination Kit and 12 in.
Vent Section (SV4.5L12)
u
Wall Firestop / Spacer
(SV4.5HF)
16-3/4 to 20 (426 to 508)
Termination Kit and Tele-
scopic Section (SV4.5L12)
uWhen using Secure Flex, use Firestop / Spacer SF4.5HF
11-3/4 to 20 (299 to 508)
Note: See Table 8 as an aid in venting component selection for a particular
range of exterior wall thicknesses.
Note: See Figure 35 on Page 21 showing wall thickness
range when using SV4.5HT-2 termination kit only.
Table 8
Figure 36 - Side Vent, NO ELBOWS
HORIZONTAL VENT FIGURES/TABLES
Notes:
Example: If 20 feet of (H)
Table E
horizontal vent run is needed,
• Secure Vent™ components (rigid vent pipe and terminal) are shown
in the Figures; Secure Flex™ components (flexible vent pipe and
terminal) may also be used.
V Minimum
feet (meter) feet (meter)
then 4 feet minimum of (V)
vertical vent will be required.
H Maximum
This table shows a 1(V) to
5(H) ratio. For every 1 foot
of vertical, you are allowed 5
feet of (H) horizontal run up
to a maximum (H) horizontal
run of 20 feet.
3
(0.914)
(1.524)
(3.048)
(4.572)
(6.096)
Elbow Only
(0.305)
• Two 45 degree elbows may be used in place of one 90 degree elbow.
The same rise to run ratios, as shown in the venting Figures for 90
elbows, must be followed if 45 degree elbows are used.
5
1
2
3
4
10
15
20
(0.610)
• SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must
be used anytime vent pipe passes through a combustible floor or ceil-
ing. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer
must be used anytime vent pipe passes through a combustible wall.
(0.914)
(1.219)
V + H = 40 feet (12.2 m) Max.
H = 20 ft. (6.096 m) Max.
• It is very important that the horizontal/inclined run be maintained
in a straight (no dips) and recommended to be in a slightly elevated
plane, in a direction away from the fireplace of 1/4" rise per foot (20
mm per meter) which is ideal, though rise per foot run ratios that are
smaller are acceptable all the way down to at or near level.
Square termination
(SV4.5HT-2) shown.
H
• The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run
of 20 feet except for installations where an elbow is the only vertical
vent section in the system (see Figure 37).
V
• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT
WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE
SYSTEM. See Figure 37.
vWall Firestop/
WARNING
Spacer (SV4.5HF)
Under no circumstances, may separate sections of
concentric flexible vent pipe be joined together.
uWhen using Secure Flex, use Firestop / Spacer SF4.5VF
vWhen using Secure Flex, use Firestop / Spacer SF4.5HF
Square termination (SV4.5HT-2) shown
Figure 37 - Top Vent, ONE 90 DEGREE ELBOW
22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
HORIZONTAL VENT FIGURES / TABLES (CONTINUED)
Table F
V Minimum
H
+H1 Maximum
H Maximum
H
H
1
feet
5
(meter)
(1.524)
(3.048)
(4.572)
(6.096)
feet (meter)
feet
(meter)
(0.305)
(0.610)
(0.914)
(1.219)
2
4
6
8
(0.610)
(1.219)
(1.829)
(2.438)
1
2
3
4
10
15
20
Wall Firestop/
v
Spacer (SV4.5HF)
V + H + H = 40 feet (12.2 m) Max
1
uCeiling Firestop
H = 8 feet (2.438 meters) Max.
/ Spacer (SV4.5VF)
H + H = 20 feet (6.096 meters) Max.
1
Square termination
(SV4.5HT-2) shown
V
Example: If 20 feet of (H + H ) horizontal
vent run is needed, then 4 feet 1minimum of
(V) vertical vent will be required.
Thistableshowsa1(V)to5(H)ratio. Forevery
1 foot of (V) vertical, you are allowed 5 feet
of (H+ H1) horizontal run, up to a maximum
horizontal run of 20 feet.
uWhen using Secure Flex, use Firestop /
Spacer SF4.5VF
vWhen using Secure Flex, use Firestop /
Spacer SF4.5HF
Note: See Table 8 on Page 22 as an aid in
venting component selection for a particular
range of exterior wall thicknesses.
Figure 38 - Side Vent, TWO 90 DEGREE ELBOWS
Table G
vWall Firestop/
Spacer (SV4.5HF)
V Minimum
feet (meter)
Elbow Only
H + H Maximum
1
feet
3
(meter)
(0.914)
(1.524)
(3.048)
(4.572)
(6.096)
H
5
1
(0.305)
(0.610)
(0.914)
(1.219)
H
1
10
15
20
2
3
4
V
V + H + H = 40 feet (12.2 m) Max.
1
H + H = 20 ft. (6.096 m) Max.
vWall Firestop/
Spacer (SV4.5HF)
1
uWhen using Secure Flex, use Firestop /
Spacer SF4.5VF
vWhen using Secure Flex, use Firestop /
Spacer SF4.5HF
Example: If 20 feet of (H + H ) horizontal
vent run is needed, then 4 feet 1minimum of
(V) vertical vent will be required.
uCeiling Firestop /
Note: See Table 8 on Page 22 as an aid in
venting component selection for a particular
range of exterior wall thicknesses.
Thistableshowsa1(V)to5(H)ratio. Forevery
1 foot of (V) vertical, you are allowed 5 feet
of (H+ H1) horizontal run, up to a maximum
horizontal run of 20 feet.
Spacer (SV4.5VF)
Square termination (SV4.5HT-2) shown
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only vertical
component in the system. See Figure 37.
Figure 39 - Top Vent, TWO 90 DEGREE ELBOWS
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
HORIZONTAL VENT FIGURES / TABLES (CONTINUED)
uWhen using Secure Flex, use
Firestop / Spacer SF4.5VF
vWhen using Secure Flex, use
Firestop / Spacer SF4.5HF
v Wall Firestop / Spacer
(SV4.5HF)
H
1
Note: See Table 8 on Page 22 as an
aid in venting component selection
H
foraparticularrangeofexteriorwall
thicknesses.
2
Table H
HMaximum
V Minimum
H + H + H Maximum
1
2
uCeiling Firestop /
feet
5
(meter)
(1.524)
(3.048)
(4.572)
(6.096)
feet
(meter)
(0.610)
(1.219)
(1.829)
(2.438)
feet
(meter)
(0.305)
(0.610)
(0.914)
(1.219)
Spacer (SV4.5VF)
2
4
6
8
1
2
3
4
V
10
15
20
V + H + H + H = 40 feet (12.2 m) Max
1
2
H
H = 8 feet (2.438 meters) Max.
H + H + H = 20 feet (6.096 meters) Max.
1
2
Example: If 20 feet total (H+H1+H2) horizontal vent run is needed, then 4 feet minimum
of (V) vertical vent will be required.
Square termination (SV4.5HT-2) shown
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V) vertical, you are allowed 5
feet of horizontal run up to a maximum total (H+H1+H2) horizontal run of 20 feet.
Figure 40 - Side Vent, THREE 90 DEGREE ELBOWS
Table I
Square termination
(SV4.5HT-2) shown.
V Minimum
(meter)
Elbow Only
(0.305)
H + H Maximum
1
feet
5
(meter)
(1.524)
(1.524)
(3.048)
(4.572)
(6.096)
feet
H
1
5
1
2
3
4
Ceiling Firestop /
u
Spacer (SV4.5VF)
10
15
20
(0.610)
(0.914)
(1.219)
H + H = 20 feet (6.096 m) Max.
1
H
V + V + H + H = 40 ft. (12.192 m) Max.
1
1
V
Wall Firestop / Spacer
v
(SV4.5HF)
1
Example: If20feettotal(H+H1)horizontal
ventrunisneeded,then4feetminimumof
(V) vertical vent will be required.
When using Secure Flex,
uuse Firestop / Spacer
V
This table shows a 1(V) to 5(H) ratio. For
every1footof(V)vertical, youareallowed
5 feet of (H+ H ) horizontal run, up to a
maximum horiz1ontal run of 20 feet.
SF4.5VF
When using Secure Flex,
vuse Firestop / Spacer
SF4.5HF
An elbow is acceptable as 1 foot of verti-
cal rise except where an elbow is the only
vertical component in the system. See
Figure 37.
Wall Firestop
v
Note: See Table 8 on Page 22
as an aid in venting component
selectionforaparticularrangeof
exterior wall thicknesses.
/ Spacer (SV4.5HF)
Figure 41- Top Vent, THREE 90 DEGREE ELBOWS
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
VERTICAL OR HORIZONTAL VENTING USING
SECuRE FLEX KITS AND COMPONENTS
Flex Vent
NOTE: Outer pipe is pulled away to show
the detail of the inner pipe.
Securing Screw - 3 places,
equally spaced, just below
gear clamp.
Secure Flex™ venting kits and components
may be used in any venting application in place
of rigid Secure Vent™ (SV4.5) direct-vent
components. All restrictions, clearances and
allowances that pertain to the rigid piping apply
to the flexible venting. Secure Flex kits may
notbemodified;also,undernocircumstances
may separate sections of flex pipe be joined
together.
APPLY ONLY MIL-PAC BLACK
HIGH TEMPERATURE SEALANT
(Cat. No. 10K81) to the outside
surface of both collars of the
adapter (be especially careful to
fill the grooves of the outer collar
tobecoveredbytheflexiblepipe)
and slide flexible pipe over inner
and outer adapter collars.
Gear Clamps
Using adapter (SV4.5RF), Secure Flex kits
may be added to the end of a vent run made
up of rigid Secure Vent (SV4.5) vent sections
provided that doing so does not violate any of
the venting length, height, routing, horizontal
to vertical ratio requirements or clearance
considerations detailed in this manual.
1-3/4 inch (44 mm) flexible
pipeandadaptoroutercollar
overlap
1-3/4 in. (44 mm) flexible
pipeandadaptorinnercollar
overlap
Adapter (SV4.5RF)
Securing Screw
- 3 places, 120° apart
(equally spaced) just
below gear clamp
Secure Flex kits come with an adapter that
can be fitted to the inclined channel end of the
last Secure Vent (SV4.5) vent section in a rigid
system in the exact same fashion as any other
Secure Vent section.
Attach adaptor to appliance
Collar, or secure vent sections
Figure 42
D. Install Firestop / Spacers at ceilings and walls
- When Secure Flex penetrates a wall or ceiling,
a firestop / spacer is required: use the SF4.5 VF
firestop / spacer for ceilings and the SF4.5 HF
firestop / spacer for walls. See the appropriate
sectionsandFiguresshownthroughoutthevent-
ing section for their installation requirements.
B. Install the Outer Flex Pipe -
Align the dimpled end of the adapter over
the previously installed section or appliance
collar, adjusting the radial alignment until the
four locking dimples of the adapter are aligned
with the inlets of the four incline channels of
the last vent section or collar. Push on the
adapter until it fully engages, then twist the
adapter clockwise running the dimples down
and along the incline channels until they seat
at the end of the channels.
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out
of the way.
2. ApplyabeadofMill-PacBlack(700°F,high
temperature sealant - Catalog No. 10K81)
to the outer adapter collar; to the grooves
of the collar which extend approximately 1
inch from the end and to the flat surface,
approximately 1 3/8 inches from the end.
3. Pull and extend outer flexible vent pipe.
4. Slidetheouterflexpipeovertheadaptercol-
lar. Ensure the flexible vent pipe completely
engages the adapter collar to a distance of
1³⁄ inches from the end, and that it is free
from damage or tears.
5. Slide the gear clamp down and tighten it
fullytosecuretheflexibleventtotheadapter
outer collar approximately 3/4 inch from the
end of the flex.
6. Install three screws, 120 degrees apart,
through the flexible vent pipe and into the
adapter collar just below the gear clamp to
provide additional security to the connec-
tion.
Flexible Vent
Section
Attach the flexible vent to the adapter as fol-
lows (see also Figure 42):
A. Install the Inner Flex Pipe -
1. Install the small gear clamp loosely around
the inner flexible vent pipe, push it back out
of the way.
2. ApplyabeadofMill-PacBlack(700°F)high
temperature sealant - Catalog No. 10K81
to the inner adapter collar, approximately
1/2 inch from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slidetheinnerflexpipeovertheadaptercol-
lar. Ensure the flexible vent pipe completely
engages the adapter collar to a distance of 1
3/4 inches from the end, and that it is free
from damage or tears.
5. Slide the gear clamp down and tighten it
fullytosecuretheflexibleventtotheadapter
inner collar approximately 3/4 inch from the
end of the flex.
6. Install three screws, 120 degrees apart,
through the flexible vent pipe and into the
adapter collar just below the gear clamp to
provide additional security to the connec-
tion.
5” (127 mm)
Radius
Minimum
Figure 43
E. Attach Flex Vent to Termination -
Secure Flex components can be purchased
separately and attached to bulk lengths of Se-
cure Flex flexible tubing cut to size at the job
site. SecuretheflexibleventtotheSecureFlex
terminations in the same manner (see Figure
42) as it was attached to the adapter.
C. Route Flex Vent -
Ensure that the flex vent is properly routed to
providetherequiredclearance.Donotallowthe
flexible vent to bend in a radius tighter than 5"
(127 mm). Refer to Figure 43. Space out the
internalflexventspacersevenly-approximately
every 6 inches - and avoid kinking of inner pipe.
Support horizontal sections of flex with metal
straps at 2 foot (0.61 m) intervals.
Note: Secure Flex vent must be attached to Se-
cure Flex terminations only. DO NOT substitute
Secure Vent terminations or the Secure Vent
adapterforSecureFlexcomponents.Thecollars
ofSecureFlexterminationsandadaptershavea
differentdiameterthanthatusedwiththeSecure
Ventpipe. Additionally,SecureFlexcomponents
have an extended length center tube for use in
attaching the flexible vent.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Note:Thegasvalveissetinplaceandpre-wired
at the factory.
Step 4. FIELD WIRING
Receptacle, Junction Box
and Cover Plate Installation
Junction Box
CAUTION
A. SIT and Honeywell Millivolt Wiring
(See Figure 44)
Outlet Receptacle
Ground supply lead must be con-
nected to the wire attached to the
green ground screw located on the
outletbox. SeeFigure45.Failureto
dosowillresultinapotential safety
hazard. The appliance must be
electricallygroundedinaccordance
withlocalcodesor,intheabsenceof
local codes, the National Electrical
Code,ANSI/NFPA70-latestedition.
(In Canada, the current CSA C22-1
Canadian Electrical Code).
1. Select anyofthefollowingoptionalcontrols:
wall-mounted switch, wall thermostat or
remote control kit. If appliance-mounted
ON/OFF control is selected mount it in the
gas valve mounting bracket.
2. If wall-mounted ON/OFF control or ther-
mostat is selected mount it in a convenient
location on a wall near the fireplace.
3. Wire the control within the millivolt control
circuit using the 15 feet of 2 conductor wire
supplied with the unit . Caution: Do NOT
connect the optional wall switch to a 120V
power supply.
4. Alternatively, theappliancemaybeoperated
without the use of the controls indicated in
Step 1, solely by manipulating the gas valve
control knob. In order to use this method,
twistthefreeendsofthetwoconductorwire
(which would otherwise go to an Optional
ControlSwitch)togetherasshowninFigure
44.
View Of Right
Bottom Corner Of Unit
Field-provided Metal Junction Box
Cover Plate With Screw
CAUTION: Label all wires prior to disconnec-
tionwhenservicingcontrols.Wiringerrorscan
cause improper and dangerous operation.
Junction Box
knock-out (2
Fireplace
Side
places each side)
ATTENTION: Au moment de l'entretien des
commandes, étiquetez tous les fils avant de
les débrancher. Des erreurs de cáblage peu-
vent entraîner un fonctionnement inadéquat
et dangereux.
Press snap
bushing into the
knock-out for
control switch
wires.
Note: Wire is located inside the control
compartment.
Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to
the gas valve circuit and the other end of each
conductor placed loose inside the control
compartment.
Verify proper operation after servicing.
Figure 46
S'assurer que l'appareil fonctionne adé-
quatement une fois l'entretien terminé.
Wiring Diagram
Showing the Blower Wiring
for the Optional FBK-100 Kit
1. If any of the original wire as supplied must be replaced,
1. it must be replaced with Type AWM 105°C – 18 GA. wire.
2. 120V, 60Hz – Less than 3 amps.
Thermopile
u
Plug blower
Green
*
into this
White
Black
Ground - Green
Neutral - White
120 VAC - Black
receptacle
Optional
Blower
Schematic
Representation
Only
uOptional
Control Switch
Junction Box
u Twist wires together to operate
unit solely by manipulating the gas
valve control knob; or connect wires
to optional wall thermostat, wall
switch or remote control to operate
unit.
Ground
Tab
Broken
Field Wired
Tab Intact
Red
Factory
Wired
Green
Ground
Screw
Neutral
Hot
Side of
Side of
Receptacle
Receptacle
*Optional Accessory Switch
�
• If any of the original wire as supplied must be replaced, it must be replaced with Type AWM
*J-BOX WIRING FOR
�
Factory Wired
Field Wired
105 C - 18 gage wire.
OPTIONAL (BLOWER
CONTROL) ACCESSORY
SWITCH
u Optional Kits Installed - ON/OFF wall switch, wall thermostat or remote control receiver.
Schematic Representation Only
Figure 44 - Millivolt Wiring Diagram
Figure 45 - Blower Wiring Diagram
26
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
See Figure 45. It is not necessary to remove
the outlet box.
Step5.WIRING-OPTIONALFORCEDAIR
BLOWER (FBK-100) (See Figure 45) -
CAUTIONS
• Remove the carton support from
the control compartment before
operating the appliance.
• Ensure that wires are positioned
awayfrom hotsurfacesandsharp
edges.
• Do not connect the optional wall
switch to a 120 Volt AC power
supply.
3. Connectthegroundsupplywiretotheoutlet
An optional ON/Off (FRS) control switch is also
available (installs on bracket below valve). An
electrical outlet box is factory installed for the
connection of the electrical power supply to
the blower.
box green ground screw as shown.
4. Plug the blower cord into the bottom recep-
tacle of the outlet box.
1. Route a 3-wire, 120Vac 60Hz 1ph power
line to the lower right rear corner of the
appliance.
2. Connect the black supply wire to the top
outlet'sblackpigtailleadandtotheswitch's
black lead. Connect the white supply wire to
the neutral terminal of the outlet box.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 6. CONNECTING GAS LINE
Gas Flex Line Connector
All codes require a shut-off valve mounted in
the supply line. The orientation of the shut-off
valveshouldfacethefront. Figure47illustrates
two methods for connecting the gas supply.
A Sediment Trap is recommended to prevent
moisture and debris in gas line from damaging
the valve.
GAS CONNECTION
3/8" NPT x
Flare Fitting
Gas
1/2" x 3/8" Flare
Shut-off Valve
Valve
Note: The gas supply line
must be installed in accor-
dance with building codes
by a qualified installer
approved and/or licensed
as required by the locality.
In the Commonwealth of
Massachusetts, installation
must be performed by a
licensed plumber or gas
fitter.
3/8" Flex Tubing
Gas
1/2" x 3/8"
Stub
The flex-line method is acceptable in the U.S.A.
where local codes permit, however, Canadian
requirementsvarydependingonlocality.Instal-
lation must be in compliance with local codes.
These appliances are equipped with a gas flex-
line for use in connecting the unit to the gas
line. See Figure 47 for flex-line description.
The flex-line is rated for both natural gas and
propane gas. A manual shut off valve is also
provided with the flex-line.
Reducer
3/8" Nipple
3/8" Union
3/8" Close
Nipple
3/8" Shut-off Valve
Gas Solid Line Connector
Figure 47
Gas Shut-Off
The gas control valve is located in the lower
control compartment.
Valve
OFF/PILOT/ON
(gas control knob)
Glass Door is Above
Control Compartment
HI/LO (flame height
control knob)
Access the valve compartment by removing
the lower control compartment panel (see
Figure 49).
Gas Flex-line
The incoming gas line should be piped into the
valve compartment and connected (see Figures
47and48).The millivolt control valve has a 3/8"
(10mm) NPT thread inlet port. The electronic
control valve has a 1/2" (13 mm) NPT thread
inletportandisfittedwitha1/2"x3/8"(13mmx
10mm) NPT fitting.
Optional OFF/ON
Switch Can be
Installed Here
Latch for
Glass Door
Gas Valve
Piezo Igniter
Control Compartment Access
Figure 48
Secure all joints tightly using appropriate
toolsandsealingcompounds(ensurepropane
resistant compounds are used in propane ap-
plications). Itisrecommendedtosealaround
the gas line to prevent cold air leakage.
CONTROL COMPARTMENT ACCESS/LOUVER
Reinstalling Control Compartment Door:
PANEL INSTRUCTIONS (Ref. Figure 49)
Toreinstall,insertthehookcatchesoneachside
of the door into the corresponding slots in the
controlcompartmentopening,thengentlypush
forward and slide down until it locks in place.
NOTE: The top louvered panel and the bottom
louvered control panel door remove and install
the same way as follows:
Gas line connection may be performed largely
outside of the confines of the control compart-
ment and without having to enter the firebox
behind the glass. Proceed as follows:
Thegascontrolscanbefoundbehindthecontrol
compartment access door.
Lift the Lower Control
Compartment Door
up and pull out to
remove.
Acquire the shut-off valve and gas lex line and
pull the assembly forward out of the compart-
ment. Separate the shut-off valve from the gas
flex-line. Determine the length of pipe needed
to route the gas line from the last fitting (shown
in Figure 13 on Page 12) to a point within the
control compartment that will allow the shut-
off valve to be easily attached by hand to the
gas flex-line.
Removing Control Compartment Door:
Open the door by gently lifting it upward until
thehookcatchesonbothsidesclearthelocating
slots. Then pull door out to remove.
OPENING CONTROL
COMPARTMENT DOOR
Hook Catch
Out
On millivolt systems, the piezo igniter, HI/LO
flame adjustment knob, and pilot and main gas
OFF/ONcontrolknobarelocatedbelowtheglass
panel enclosure.
Control Valve
Up
Lower Control
Compartment Door
Using pipe-dressing materials appropriate for
the gas type, securely affix the shut-off valve
to this determined pipe length at a convenient
location outside of the appliance lower control
compartment.
Figure 49
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Note: The (pull-out) Lighting instructions label
can be found in the control compartment (see
Figure 48 on Page 28).
TEST ALL CONNECTIONS FOR GAS LEAKS
(FACTORY AND FIELD):
Step 8. INSTALLING LOG SET, VOLCANIC
STONE AND GLOWING EMBERS
When first lighting the appliance, it will take
a few minutes for the line to purge itself of
air. Once purging is complete, the pilot and
burner will light and operate as indicated in
the instruction manual. Subsequent lighting
of the appliance will not require such purging.
Inspect the pilot flame.
WARNING
Never use an open flame to
check for leaks.
WARNING
• DO NOT attempt to install the
logsuntiltheapplianceinstal-
lationhasbeencompleted,the
gas line connected and tested
forleaksandtheinitialburner
operation has been checked
out.
Turn on gas supply and test for gas leaks using a
gas leak test solution (also referred to as bubble
leak solution).
Millivolt Appliance Checkout
Note: Using a soapy water solution is an effec-
tive leak test solution but it is not recommended,
because the soap residue that is left on the pipes/
fittings can result in corrosion over time.
The pilot flame should be steady, not lifting
or floating. Flame should be blue in color with
traces of orange at the outer edge.
• Thesizeandpositionofthelog
setwasengineeredtogivethe
appliance a safe, reliable and
attractive flame pattern. Any
attempt to use a different log
set in the fireplace will void
the warranty and will result in
incompletecombustion,soot-
ing, and poor flame quality.
• Logs get very hot and will
remain hot up to one hour
after gas supply is turned off.
Handle only when logs are
cool. Turn off all electricity
to the appliance before you
install grate, volcanic stone,
vermiculite, embers and
logs.
• Thisapplianceisnotdesigned
to burn wood. Any attempt
to do so could cause irrepa-
rabledamagetotheappliance
and prove hazardous to your
safety.
• If logs are not installed
according to the log instal-
lation instructions, flame
impingement and improper
combustion could occur and
resultinsootand/orexcessive
productionofcarbonmonoxide
(CO), a colorless, odorless,
toxic gas.
The top 3/8" (10 mm) at the pilot generator
(thermopile) and the top 1/8" minimum (tip)
of the quick drop out thermocouple should be
engulfed in the pilot flame.
A. Light the appliance (refer to the lighting
instructionslabelinthecontrolcompartment
or in the Care and Operation Instructions
manual).
B. Brush all joints and connections with the gas
leak test solution to check for leaks. If bubbles
are formed, or gas odor is detected, turn the
gas control knob (off/pilot/on) to the “OFF”
position. Either tighten or refasten the leaking
connection, then retest as described above.
C. Whenthegaslinesaretestedandleakfreebe
sure to rinse off the leak testing solution.
The flame should project 1" (25 mm) beyond
the hood at all three ports (Figure 50).
To light the burner; rotate the gas valve control
knob counterclockwise to the “ON” position
then turn “ON” the OFF/ON switch (installed
at Step 4).
Hood Igniter Rod
MILLIVOLT
Step 7. VERIFYING APPLIANCE OPERA-
TION
Thermocouple
Turn on burner then observe the individual
tongues of flame on the burner. Make sure
all ports are open and producing flame evenly
across the burner. If any ports are blocked, or
partially blocked, clean out the ports.
3/8" Min
(9 mm)
Pilot
Nozzels
With the gas line installed, run initial system
checkout before closing up the front of the
appliance. Follow the pilot lighting instructions
provided in the Care and Operation Instruc-
tions manual. For piezo igniter location see
Figure 48.
Thermopile
Figure 50
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
LOG AND VOLCANIC STONE INSTALLATION
PROCEDURE:
Install the unitized log set:
NOTE: INSTALL REAR BURNER FIRST,
THEN FRONT BURNER.
a. The bottom of the log set is notched to ac-
commodate the pilot.
BURNER
PORTS
BRACKET A
REAR BURNER
Thelogsetfoampackageislocatedinthefirebox
and the bags of decorative volcanic stone and
the glowing embers (rockwool) are located in
thecontrolcompartment.Refertothefollowing
information and Figures 51 to 54 for detailed
placement instructions.
b. Placethelogsetsothatthe fourinnernotches
on the underside of the log set fit over the
four risers located on the burner ends. See
Figure 54. This procedure is accomplished
primarily by feel, as the log set masks the
burner risers as it is being installed.
PILOT
BURNER
c. Asafinalcheckforcorrectlogsetplacement,
check that the four outer notches on the
underside of the log set fit over the burner
tines as indicated in Figure 52.
Install the decorative volcanic stone and
glowing embers (rockwool):
FRONT BURNER
Note: The burners are not identical. Position them so
that the circular burner ports run as shown. Note
especially the vertical run of ports relative to the pilot
burner. Bracket A on the rear burner will interfere
with the pilot burner if an attempt is made to install
the rear burner in the front burner’s position.
Burner / Grate Location Reference
(see Figures 52 to 54)
Spread the decorative volcanic stone on the
simulated brick floor of the firebox around
the burners to simulate ashes. Maintain a 1/2
inch (13 mm) gap between the bottom of the
horizontal grate section and the top of the pile
of decorative volcanic stone. Place a few quar-
ter-sized pieces of the glowing ember material
on the pan burner in front of the burned out
area on both sides of the log set. The glowing
embers may touch one another, but should not
overlap each other.
Note: If the burners have been removed for
any reason, rear burner must be installed
before front burner. See Figures 52 to 54.
Figure 53
NOTE: INSTALL REAR BURNER FIRST,
THEN FRONT BURNER.
Glowing Embers
Outer Log
Notch Location
REAR BURNER
Separate into Quarter
Size (separate) Pieces
Outer Log
Notch Location
Riser - Inner Log
Notch Location
Riser - Inner Log
Notch Location
Outer Log
Notch Location
Outer Log
FRONT BURNER
Bag of Glowing
Embers (rockwool)
Notch Location
Pilot Assembly
Figure 51
REFERENCE
Firebox Accessories / Parts
FIREBOX SUBFLOOR
FRONT OF FIREPLACE
LOG NOTCH LOCATION RELATIVE TO BURNER
Cat. No.
88L53
Model No.
Description
FGE
Bag of Glowing Embers
Bag of Decorative
Volcanic Stone
80L42
FDVS
Figure 54
Proper Burner Flame Appearance
unitized Log Set
Volcanic Stone
Figure 52
30
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Removing Glass Enclosure Panels
(see Figure 55)
Step 10. BURNER ADJUSTMENTS
Step 9. INSTALLATION AND REMOVAL
OF GLASS DOOR
Flame Appearance and sooting
Proper flame appearance is a flame which is
blueatthebaseandbecomesyellowish-orange
in the body of the flame.
1. Remove the top louver assembly by lifting it
up and pulling it out.
2. Remove the control compartment access
door (see removal instructions on Page 28
- Removing Control Compartment Door).
3. Locate the two (2) latches at the top of the
control compartment. To disengage the two
latches from the bottom vee-flange of the
glassenclosurepanel, reachforthehandles
located towards the back of the latches and
pull the handles down toward the front of
the appliance.
WARNING
When the appliance is first lit, the entire flame
may be blue and will gradually turn yellowish-
orangeduringthefirst15minutesofoperation.
After 15 minutes of operation, if the flame is
blue, or if the flame is orange with evidence of
sooting (black tip), the air shutter opening may
need to be adjusted.
• Donotattempttosubstitutethe
materialsusedonthesedoors,
or replace cracked or broken
glass.
• Handlethisglasswithextreme
care! Glass is susceptible to
damage – Do not scratch or
handleroughlywhilereinstall-
ing the glass door frame.
• The glass door(s) of this appli-
ance must only be replaced as
a complete unit as provided
by the manufacturer. Do not
attempt to replace broken,
crackedorchippedglasssepa-
rately.
4. Swing the bottom of the door out and raise
it slightly to lift the top flange of the door
frame away from the appliance.
If the air shutter openings are closed too far,
sooting may develop. Sooting is indicated by
black puffs developing at the tips of very long
orangeflames. Sootingresultsinblackdeposits
forming on the logs, appliance inside surfaces
and on exterior surfaces adjacent to the vent
termination.
Installing Glass Enclosure Panels
(see Figure 55)
1.Visuallyinspectthegasketonthebacksideofthe
glasspanel.Thegasketsurfacemustbeclean,
free of irregularities and seated firmly.
2. Positiontheglassenclosurepanelinfrontof
thefireboxopeningata45degreeangleand
engage the top flange over the lip at the top
of the firebox opening. See Figure 55.
3. Swing the glass enclosure panel down and
back. Ensure the gasket seats evenly as the
panel draws shut. Engage the Vee-flange at
the bottom of the panel with the latches and
close the latches to secure the panel.
4. Reinstall top louver assembly and control
compartment door see installation instruc-
tions on Page 28, Reinstalling Control
Compartment Door).
Sootingiscausedbyincompletecombustionin
the flames and lack of combustion air entering
the air shutter opening. To achieve a warm yel-
lowish-orange flame with an orange body that
does not soot, the shutter opening must be
adjusted between these two extremes.
• Do not attempt to touch the
frontenclosureglasswithyour
hands while the fireplace is in
use.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, first check
the log set positioning to ensure that the
flames are not impinging on any of the logs.
If the log set is properly positioned and a
sooting condition still exists, then the air
shutter opening should be increased.
WARNING
Do not operate appliance with
theglassfrontremoved,cracked
or broken.
Top Flange on
Glass Door
• Themoreoffsetsintheventsystem,thelarger
the air shutter opening will need to be.
• An appliance operated with the air shutter
opened too far, may have flames that appear
blue and transparent. These weak, blue and
transparent flames are termed anemic.
• Propane models may exhibit flames which
candle or appear stringy. If this is present and
persists, adjust the air shutter to a more closed
position, then operate the appliance for a few
moreminutestoensurethattheflamenormal-
izes and the flames do not appear sooty.
The following chart is provided to aid you in
achieving the correct air shutter adjustment
for your installation.
Glass Door
AVERTISSEMENT
Ne pas utiliser l'appareil si le
panneau frontal en verre n'est
pas en place, est craqué ou
brisé.
Only doors certified with the appliance
shall be used.
Seules des portes certifiées pour cet
appareil doivent être utilisées.
Air Shutter Adjustment Guidelines:
Bottom Vee-flange
Glass Door
Amount of
Primary Air
Flame
Color
Air Shutter
Adjustment
Firebox Floor
Glass Door Latch
CAUTION: DO NOT abuse glass door by
striking or slamming shut.
If air shutter is
closed too far
Flame will Air shutter
be orange gap should be
increased
Note: When installing the glass door, ensure the
spacing on both sides are equal.
Figure 55 -
INSTALLING OR REMOVING GLASS DOOR
If air shutter is
open too far
Flame will Air shutter
be blue gap should be
decreased
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Burner Air Shutter Adjustment Procedure
Air Shutter
Adjusting
Rod
Burner
Venturi
Tube
Air Shutter
Opening
WARNINGS
***Main Burner Factory Air Shutter
Opening Setting - All Models
• Air shutter adjustment should
only be performed by a quali-
fiedprofessionalservicetech-
nician.
Orifice
Natural Gas
inches (millimeters)
Propane Gas
inches (millimeters)
* TWO 1/8 (3) Slots
** TWO 11/16 (17) Slots
• Ensure front glass panel are
in place and sealed during
adjustment.
Increase Shutter
Adjustment Rod Positions, viewed from above:
* Natural Gas - fully clockwise
** Propane- fully counter clockwise
***Settings are shown for each burner.
Opening In This
Direction
Air Shutter
Adjusting
Arms
Decrease Shutter
Opening In This
Direction
Ref. Air shutter Patent:
U.S. Pat. 5,553,603
CAUTIONS
Note - Both air shutters open and close simultaneously
when the air shutter adjusting rod is moved.
• Soot will be produced if the
airshutterisclosedtoomuch.
Any damage due to carboning
resulting from improperly
setting the air shutter is not
covered under the warranty.
• Theairshutterdoorandnearby
appliance surfaces are hot.
Exercise caution to avoid
injury while adjusting flame
appearance.
Note - Burners are omitted in this view for clarity.
Figure 56 - Burner Air Shutter Adjustment
1. Locateadjustmentrodandadjustairshutter
to the standard setting as shown in Figure
56 (adjustment rod is located in the lower
control area).
Note: Rotating the adjustment rod coun-
terclockwise decreases air and clockwise
increases air.
2. Light appliance (follow lighting procedure
on lighting label in control compartment or
see care and operation manual).
Figure 57 - Burner Flame Appearance
3. Allow the burner to operate for at least 15
minutes while observing the flame continu-
ouslytoensurethattheproperflameappear-
ance has been achieved (see Figure 57). If
the following conditions are present, adjust
accordingly.
Step 11. HOOD INSTALLATION
All of these appliances must have hoods
installed prior to operating (see Figure 58).
This Area Must
Remain Clear of
3"
(76 mm)
Slide the hood into the slots on the lower edge
of the cabinet top (see Figure 58).
Combustible
Combustible
• If flame appears weak or sooty, adjust
theairshutter,incrementally,toamore
open position until the proper flame
appearance is achieved.
• If flame stays lowered blue, adjust the
air shutter, incrementally, to a more
closed position until the proper flame
appearance is achieved.
Materials
Finished
Wall Materials
1 in. Min.
(25 mm)
FINISHING REQUIREMENTS
Wall Details
Header
Top Spacers
Complete finished interior wall. To install the
appliance facing flush with the finished wall,
positionframeworktoaccommodatethethickness
of the finished wall (Figure 58).
Drywall
Bracket/Spacer
4. Leave the control knob (off/pilot/on) in the
ON position and the burner OFF/ON switch
OFF (and remote switches, if applicable).
5. When satisfied that the burner flame ap-
pearance is normal, close the lower control
compartment door then proceed to finish
the installation.
Combustible
material may
touch
appliance
top
See Page 5 for Cold Climate Insula-
tion and Page 8 for Clearances.
Top of Appliance
Louvers
Top of Door Frame
Hood must be installed as shown.
Figure 58 - Combustible Wall Framing
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 12. ATTACHING SAFETY-IN-OPERATION WARNINGS
It is the installer's responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY-IN-OPERATION
WARNINGS
APPOSITION DES MISES EN GARDE RELATIVES
à LA SéCURITé D’UTILISATION
COLOCACIóN DE ADVERTENCIAS DE
SEGURIDAD EN OPERACIóN
Yourfireplacehasbeenfurnishedwithsafetyinstruc- Votrefoyeraétélivréavecdesétiquettesdesécuritéqui Su chimenea incluye etiquetas de instrucciones
tion labels that are to be affixed to the operation and doivent être collées à côté des dispositifs de contrôle de seguridad que deben colocarse en el punto de
control point of the fireplace. A safety instruction du foyer. Une étiquette de sécurité doit être collée sur operación y control de la chimenea. Se debe colocar
labelshouldbeaffixedtothewallswitchplatewhere la plaque de l’interrupteur contrôlant l’allumage du una etiqueta de instrucciones de seguridad en la placa
the fireplace is turned on and off (See Figure A) or foyer (voir Figure A) ou sur le thermostat mural (voir del interruptor de pared desde el cual se enciende y se
wall thermostat (See Figure B) and if used on the Figure B) et, le cas échéant, sur le boîtier de la télé- apaga la chimenea (ver la Figura A) o en el termostato
remote control handheld transmitter (Figure C). commande(FigureC). Lesmisesengardeauraientdû de pared (ver la Figura B)y en el transmisor de control
The warnings should already have been put in place êtrecolléesaumomentdel’installationinitialedufoyer. remoto (Figura C)siseusa.Lasadvertenciasyadeben
when the fireplace initial set-up was completed. Si ce n’est pas le cas, prenez les étiquettes adhésives haberse colocado cuando se completó la instalación
If they are not affixed at these spots, locate the multilingues fournies avec ces instructions et procédez inicial de la chimenea. Si no están colocadas en estos
multi-lingual adhesive labels provided with these comme suit:
lugares,encuentrelasetiquetasadhesivasmultilingües
instructions and proceed as follows:
1. Repérez l’interrupteur ou le thermostat mural proporcionadas con estas instrucciones y prosiga de
qui contrôle le foyer (vérifiez que l’interrupteur la siguiente manera:
1. Locate the wall switch or wall thermostat that
controlsthefireplace(verifytheswitchoperates
the fireplace by turning it on and off). Clean the
wall switch plate or wall thermostat thoroughly
to remove any dust and oils. Affix the label to
the surface of the plate of the wall switch that
controls the fireplace (Figure A) or the wall
thermostat (Figure B). Choose the language
primarily spoken in the home.
contrôle le fonctionnement du foyer en le faisant 1. Identifique el interruptor o el termostato de pared
basculerdeMarcheàArrêt,etvice-versa). Nettoyez
soigneusement la plaque murale de l’interrupteur
ou le thermostat mural pour éliminer la poussière
et les traces de graisse ou d’huile. Collez l’étiquette
sur la surface de la plaque de l’interrupteur mural
qui contrôle le foyer (Figure A) ou du thermostat
mural (Figure B). Choisissez la langue qui est
principalement parlée dans la résidence du
propriétaire.
quecontrolalachimenea(verifiquequeelinterruptor
opera la chimenea encendiéndola y apagándola).
Limpiebienlaplacadelinterruptoroeltermostatode
pared para quitar el polvo y aceite. Pegue la etiqueta
enlasuperficiedelaplacadelinterruptorquecontrola
la chimenea (Figura A) o en el termostato de pared
(Figura B). Seleccione el idioma que más se habla
en la casa.
2. Ifaremotecontrolisusedtocontrolthefireplace,
locate the transmitter and clean it thoroughly
2. Si se usa un control remoto para controlar la
chimenea, encuentre el transmisor y límpielo bien
para quitar el polvo y aceite. Pegue la etiqueta en la
superficie del transmisor (Figura C). Seleccione el
idioma que más se habla en la casa.
to remove any dust and oils. Affix the label to 2. Si une télécommande est utilisée pour contrôler
the surface of handheld transmitter (Figure C).
Choose the language primarily spoken in the
home.
le foyer, nettoyez la soigneusement pour éliminer
la poussière et les traces de graisse ou d’huile.
Collez l’étiquette sur le boîtier de la télécommande
3. If you are unable to locate the labels, please call
LennoxHearthProductsoryournearestLennox
(Figure C). Choisissez la langue qui est principale- 3. Si no puede encontrar las etiquetas, sírvase llamar
ment parlée dans la résidence du propriétaire.
a Lennox Hearth Products o al distribuidor de
Lennox Hearth Products más cercano para recibir
etiquetasdeinstruccionesdeseguridadadicionales
gratuitas.
Hearth Products dealer to receive additional 3. Si vous ne trouvez pas les étiquettes, veuillez
safety instruction labels free of charge.
appeler Lennox Hearth Products ou votre distribu-
teur Lennox Hearth Products local pour recevoir
gratuitement des étiquettes supplémentaires.
Cat. No. H8024 Replacement Label Kit
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS
1-800-9-LENNOX
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS
1-800-9-LENNOX
LENNOX HEARTH PRODUCTS
1-800-9-LENNOX
Note: English is red text on clear label. French and
Spanish are white text on black label.
Nota: La etiqueta en inglés es transparente con texto
rojo. Las etiquetas en francés y español son negras
con texto blanco.
Remarque : Le texte anglais est rouge sur un support
transparent. Le texte français et espagnol est blanc
sur un support noir.
SAFETY LABEL
DIAGRAMS
DIAGRAMMES DES éTIQUETTES
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
DE SéCURITé
Figure C
Figure B
Figure A
33
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION ACCESSORIES
1
Item
Cat. No.
Model
Description
1
H1968
SV4.5HT-2
Horizontal Square Termination With Firestop / spacer
(H2246) & Adapter (74L61)
2
3
3
3
3
3
3
4
5
H2152
77L70
77L71
77L72
77L73
77L74
77L75
77L76
77L77
SV4.5CGV-1
SV4.5L6
Vertical Termination Cap
6 Inch (152 mm) Vent Section
12 Inch (305 mm) Vent Section
24 Inch (610 mm) Vent Section
36 Inch (914 mm) Vent Section
48 Inch (1219 mm) Vent Section
Telescopic Section (1-1/2" to 7-1/2" effective length)
45 Degree Elbow
SV4.5L12
SV4.5L24
SV4.5L36
SV4.5L48
SV4.5LA
3
SV4.5E45
SV4.5E90
90 Degree Elbow
The following flashings come packaged with a storm collar:
4
5
6
6
6
77L78
77L79
77L80
SV4.5F
SV4.5FA
SV4.5FB
Flat Roof Flashing
1/12 to 7/12 Adjustable Flashing
7/12 to 12/12 Adjustable Flashing
7
8
77L81
H2246
SV4.5SC6
SV4.5HF
Storm Collar (6 per box)
Firestop / Spacer-Horizontal (3-1-1 spacing), 10 Pack
6
8
H2247
96K93
H3907
96K92
17M52
SV4.5VF
SV4.5SU
SV4.5RSA
SV4.5SP
Firestop / Spacer-Vertical (1-1-1 spacing), 10 Pack
Support Strap
9
10
11
12
Attic Insulation Shield, w/adjustable height, 12"-22
Support Plate
7
SV4.5HGS-1 Termination Guard, Square (1 pack)
(for square termination)
12
13
14
17M53
87L02
H5820
SV4.5HGS-12 Termination Guard, Square (12 pack)
(for square termination)
12
SV4.5HGS
Termination Guard for Square Termination (Deluxe)
(1 pack) (for square termination)
4.5HTSK
Termination Shroud (Guard) for Horizontal Square Ter-
mination (1 pack)
Ref. 750,109M
11
8
10
9
13
Ref. 750,055M
14
2
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Item Cat. No.
Model
SF4.5HT-2
SFKIT12S
SFKIT18S
SFKIT24S
SFKIT36S
SFKIT48S
SFVT30
Description
19
18
18
18
18
18
18
19
H1969
77L87
77L88
77L89
77L90
77L91
56L74
Horizontal Square Termination (without flex)
Flex Square Term. (with 12 inch [305 mm] * compressed flex)
Flex Square Term. (with 18 inch [457 mm] * compressed flex)
Flex Square Term. (with 24 inch [610 mm] * compressed flex)
Flex Square Term. (with 36 inch [914 mm] * compressed flex)
Flex Square Term. (with 48 inch [1219 mm] * compressed flex)
Vertical Termination forflex (flat to 6/12) with flex adapter, section of rigid vent,
roof support collar assembly, roof flashing and storm collar.
19
56L75
SFVT45
Vertical Termination for flex (6/12 to 12/12) with flex adapter, section of rigid
vent, roof support collar assembly, roof flashing and storm collar.
*20
*20
22
23
23
8
60L10
98K03
10K81
91L66
91L67
H2248
H2249
SF-18
18 ft. (5.49 m) * compressed flex
SF-12
12 ft. (3.66 m) * compressed flex
SFMP
Mill-Pac, Black, High Temperature Sealant
Gear Clamp 4.5 in. (114 mm) for flex (6 pieces)
Gear Clamp 7.5 in. (190.5 mm) for flex (6 pieces)
Firestop / Spacer - Horizontal (flex) (3-1-1 spacing), 10 Pack
Firestop / Spacer - Vertical (1-1-1 spacing), 10 Pack
SF-GC4-6
SF-GC7-6
SF4.5HF
SF4.5VF
8
All compressed flex vents can be expanded up to two times.
*
18
22
20
23
S
e
a
l
a
n
t
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION ACCESSORIES
Item
24
24
25
25
25
26
27
Cat. No.
92L07
92L08
92L09
92L10
92L11
92L06
H5816
Model
SV-MHPK1
SV-MHPK2
SV-FSTFE
SV-FST1E
SV-FST2E
SVTE26
Description
Manufactured Home Pipe Kit (SV) - 1/12 Pitch
Manufactured Home Pipe Kit (SV) - 2/12 Pitch
Firestop Thimble (SV) - Flat, with Extension
Firestop Thimble (SV) - 1/12 Pitch, with Extension
Firestop Thimble (SV) - 2/12 Pitch, with Extension
Thimble Extension (SV) - 26 inches
SV4.5-TWSK
Through Wall Shield Kit (used to shield the direct-vent pipe from blown insulation)
24
25
26
27
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
GAS CONVERSION KITS
INSTALLATION INSTRUCTIONS
Step 1. TURN OFF THE GAS SUPPLY TO THE
APPLIANCEanddisconnectpowersupply atthe
circuit breaker. Ensure appliance is cold.
WARNING
Thisconversionkitshallbeinstalledbyaqualifiedserviceagencyinaccor-
dance with the manufacturer’s instructions and all applicable codes and
requirementsoftheauthorityhavingjurisdiction.Iftheinformationinthese
instructionisnotfollowedexactly,afire,explosionorproductionofcarbon
monoxide may result causing property damage, personal injury or loss of
life.Thequalifiedserviceagencyisresponsiblefortheproperinstallation
of this kit. The installation is not proper and complete until the operation
of the converted appliance is checked as specified in the manufacturer’s
instructionssuppliedwiththekit.Thequalifiedserviceagencyperforming
this installation assumes responsibility for this conversion.
CAUTION: THE GAS SUPPLY SHALL BE
SHUT OFF PRIOR TO DISCONNECTING THE
ELECTRICALPOWER,BEFOREPROCEEDING
WITH THE CONVERSION.
ATTENTION : AVANT D’EFFECTUER
LA CONVERSION, COUPEZ D’ABORD
L’ALIMENTATION EN GAZ, ENSUITE,
COUPEZ L’ALIMENTATION éLECTRIQUE.
Step 2. Remove the front glass door assembly
fromtheappliance(see RemovingGlassEnclo-
sure Panels on Page 31). Remove the control
compartment door (see Control Compartment
Door Removal on Page 28).
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé,
selon les instructions du fabricant et selon toutes les exigences et tous les
codes pertinents de l’autorité compétente. Assurez-vous de bien suivre
les instructions dans cette notice pour réduire au minimum le risque
d’incendie,d’explosionoulaproductiondemonoxydedecarbonepouvant
causer des dommages matériels, des blessures ou la mort. Le tecnicien
agrééestresponsabledel’installationdecettetrousse.L’installationn’est
pas adéquate ni complète tant que le bon fonctionnement de l’appareil
convertin’apasétévérifiéselonlesinstructionsdufabricantfourniesavec
la trousse. Le fournisseur de service qualifié ayant réalisé l'installation
assume les responsabilités liées à la conversion.
Step 3. Carefully remove the logs. Exercise
care so as not to break the logs.
Step 4. Refer to Figure 59.
Remove the front burner and then the rear
burner.
NOTE: REMOVE FRONT BURNER FIRST,
THEN REAR BURNER.
REAR BURNER
VENTURI
TUBE ARM
In Canada:
THE CONVERSION SHALL BE CAR-
RIED OUT IN ACCORDANCE WITH THE
REQUIREMENTS OF THE PROVINCIAL
AUTHORITIES HAVING JURISDICTION
AND IN ACCORDANCE WITH THE RE-
QUIREMENTS OF THE CAN/CSA-B149.1
INSTALLATION CODE.
Natural Gas to Propane Gas
FRONT BURNER
VENTURI
Conversion Kits
TUBE ARM
AIR SHUTTER
ADJUSTMENT LEVER
Fireplace
Type
Cat. No.
(model)
85L65
FGCK-DMOMNP
Millivolt
FIREBOX SUBFLOOR
FRONT OF FIREPLACE
LACONVERSIONDEVRAêTREEFFECTUéE
CONFORMéMENT AUX RECOMMANDA-
TIONS DES AUTORITéS PROVINCIALES
AYANT JURIDICTION ET CONFORMé-
MENT AUX EXIGENCES DU CODE
D'INSTALLATION CAN/CSA-B149.1.
Propane Gas to Natural Gas
Conversion Kits
Figure 59
Fireplace
Type
Cat. No.
(model)
Millivolt Appliances
85L72
FGCK-DMOMPN
Step 5. - SIT Systems - Refer to Figure 60 and
the instructions provided with the kit. Using a
Torx T20 (with 1/4" shank and center hole), tool
or standard flat screwdriver remove and discard
the three pressure regulator mounting screws.
Removethepressureregulator, spring, poppet,
diaphragm and bushing. Discard all removed
components.
Millivolt
Gasconversionkitsareavailabletoadaptyour
appliance from the use of one type of gas to
the use of another. These kits contain all the
necessary components needed to complete
the task including labeling that must be af-
fixed to ensure safe operation.
Kit part numbers are listed here and the
following steps detail the conversion pro-
cedure. Refer to the instructions provided
with the conversion kit when performing any
gas conversion.
Ensuretherubbergasketinstalledonthebackof
the replacement pressure regulator is properly
positioned and install the new pressure regula-
tor using the new screws supplied with the kit.
Tighten screws to 25 In. lb. torque.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Step8.Reassembletheremainingcomponents
by reversing the procedures outlined in the
preceding steps.
NOTE: Flame appearance will diminish 4% per
SIT Millivolt Gas Valve
thousand feet.
NOTE: Each model has two burners and 2
Orifices.
Step 9. Attach the conversion label provided
in the conversion kit to the rating plate on the
appliance.
Pressure
Regulator
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Step 10. Turn on gas supply and test for gas
leaks. See Test All Connections For Gas Leaks
on Page 29.
Elevation
Natural Gas
Propane
Feet (meters)
drill size (inches)
Gas
drill size (inches)
Remove
These
0-4500
(0-1372)
#44 (.086") *
60J80 •
#55 (.052")**
19L52 •
Components
Step 11. Attach manometer to the manifold
side pressure test fitting and verify manifold
pressure reads 3.5 inches water column (0.87
kPa) for natural gas, and 10.0 inches water
column (2.49 kPa) for propane gas.
Figure 60
* Standard size installed at factory
** Standard size in LP conversion kit
• Part /Cat. Number
Table 9
Step 6. See Figure 61 and remove the pilot
hoodassemblytoaccessthehexedpilotorifice.
Remove and replace the orifice with the one
provided with the kit.
ALWAYS TEST PRESSURES WITH THE VALVE
REGULATOR CONTROL AT THE HIGHEST
SETTING.
BURNER
ORIFICE
Figure 62
Pilot for SIT Millivolt
Gas Valve
BURNER POSITIONING
NOTE: INSTALL REAR BURNER FIRST,
THEN FRONT BURNER.
Pilot
Orifice
BURNER
PORTS
BRACKET A
REAR BURNER
Figure 61
PILOT
BURNER
Step 7. (Refer to Figure 59 on Page 37 and
Figure 62)
VERIFY THE PROPER ORIFICE SIZES
BEFORE INSTALLING THEM.
FRONT BURNER
A. Remove the two orifices from the manifold
and replace them with the ones provided in the
kit. Table 9 shows the orifice sizes for natural
and propane models. Figure 62 illustrates the
orifice. Use pipe joint compound or Teflon tape
on all pipe fittings before installing (ensure
propane resistant compounds are used in
propane applications, do not use pipe joint
compounds on flare fittings).
Note: The burners are not identical. Position them so
that the circular burner ports run as shown. Note
especially the vertical run of ports relative to the pilot
burner. Bracket A on the rear burner will interfere with
the pilot burner if an attempt is made to install the
rear burner in the front burner’s position.
Figure 63
B. Install rear burner first, followed by front
burner, as shown in Figure 63. Ensure that the
armoftheventuriofeachburnerishookedonto
the air shutteradjustment lever (refer to Figure
59 on Page 37). The primary air opening can
be adjusted by rotating the adjustment lever
from beneath the firebox floor. Refer to Figure
56onPage32fortherecommendedminimum
primary air opening setting.
38
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design,
materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2006 Lennox Hearth Products
P/N 700037M REV. F 01/2011
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
Download from Www.Somanuals.com. All Manuals Search And Download.
|