Superior Indoor Fireplace DR 400CEN User Manual

INSTALLATION  
INSTRUCTIONS  
DIRECT VENT  
DT-400 & DR-400  
VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS  
P/N 700,020M REV. M 11/2004  
RETAIN THESE INSTRUCTIONS  
FOR FUTURE REFERENCE  
MODELS  
This appliance may be installed in an aftermar-  
ket permanently located, manufactured home  
(USA only) or mobile home, where not prohib-  
ited by local codes. This appliance is only for  
use with the type of gas indicated on the rating  
plate. This appliance is not convertible for use  
with other gases, unless a certified kit is used.  
Millivolt  
Models  
DT-400CMN DT-400CEN  
DT-400CMP DT-400CEP  
DR-400CMN DR-400CEN  
DR-400CMP DR-400CEP  
Electronic  
Models  
WARNING:IFTHEINFORMATIONINTHISMANUAL  
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO-  
SION MAY RESULT CAUSING PROPERTY DAM-  
AGE, PERSONAL INJURY OR LOSS OF LIFE.  
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE  
LESINSTRUCTIONSDONNÉDANSCETTENOTICEPOUR  
RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU  
POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE  
BLESSURE OU LA MORT.  
FOR YOUR SAFETY: Do not store or use gasoline  
or other flammable vapors or liquids in the vicin-  
ity of this or any other appliance.  
POURVOTRESÉCURITÉ: Nepasentreposerniutiliser  
d'essencenid'autrevapeursouliquidesinflammables  
dans le voisinage de cet appareil ou de tout autre  
appareil.  
FOR YOUR SAFETY: What to do if you smell gas:  
• DO NOT light any appliance.  
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une  
• DO NOT touch any electrical switches.  
• DO NOT use any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow your gas suppliers  
instructions.  
odeur de gaz:  
Ne pas tenter d'allumer d'appareil.  
Netouchezàaucuninterrupteur. Nepasvousservir  
des téléphones se trouvant dans le batiment où  
vous vous trouvez.  
Evacuez la piéce, le bâtiment ou la zone.  
Appelez immédiatement votre fournisseur de gaz  
depuis un voisin. Suivez les instructions du  
fournisseur.  
• Ifyourgassuppliercannotbereached, callthe  
fire department.  
Installation and service must be performed by a  
qualified installer, service agency or the gas  
supplier.  
Si vous ne pouvez rejoindre le fournisseur de gaz,  
appelez le service dos incendies.  
L'installationetservicedoitêtreexécutéparunqualifié  
installeur,agencedeserviceoulefournisseurdegaz.  
OTL Report No. 116-F-17-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Millivolt Models -  
The millivolt appliances are manually controlled  
andfeatureasparkignitor(piezo)thatallowsthe  
appliance's pilot gas to be lit without the use of  
matches or batteries. This system provides  
continuedserviceintheeventofapoweroutage.  
These appliances must be isolated from the gas  
supplypipingsystem(byclosingtheirindividual  
manualshut-offvalve)duringanypressuretest-  
ing of the gas supply piping system at test  
pressures equal to or less than¹⁄₂ psig (3.5 kPa).  
Millivolt models come standard with the  
manually-modulated gas valve; flame ap-  
pearance and heat output can be con-  
trolled at the gas valve. Input of millivolt  
models is shown in the following table:  
Donotusetheseappliancesifanyparthasbeen  
under water. Immediately call a qualified, pro-  
fessional service technician to inspect the ap-  
pliance and to replace any parts of the control  
system and any gas control which have been  
under water.  
These appliances and their individual shut-off  
valves must be disconnected from the gas  
supply piping system during any pressure test-  
ing of that system at pressures in excess of ¹⁄₂  
psig (3.5 kPa).  
Millivolt Models with  
Manually-Modulated Gas Valve  
Natural and Propane Gas  
Model Numbers  
DT-400  
Input rate (BTU/H)  
13,500 to 17,500  
DR-400  
These appliances must not be connected to a  
chimney or flue serving a separate solid fuel  
burning appliance.  
Ne pas se servir de cet appareil s'il a été plongé  
dans l'eau, complètement ou en partie. Appeler  
untechnicienqualifiépourinspecterl'appareilet  
remplacertoutepartiedusystèmedecontrôleet  
toute commande qui ont été plongés dans l'eau.  
Electronic Models -  
Electronic models have a fixed rate gas valve.  
Input of electronic models is shown in the  
following table:  
Carbon Monoxide Poisoning: Early signs of  
carbon monoxide poisoning are similar to  
the flu with headaches, dizziness and/or  
nausea. If you have these signs, obtain fresh  
air immediately. Turn off the gas supply to  
the appliance and have it serviced by a  
qualified professional, as it may not be op-  
erating correctly.  
Electronic Models with Fixed-Rate  
Gas Valve  
This appliance may be installed in an af-  
termarket permanently located, manufac-  
tured home (USA only) or mobile home,  
where not prohibited by local codes. This  
appliance is only for use with the type of  
gas indicated on the rating plate. This ap-  
pliance is not convertible for use with  
other gases, unless a certified kit is used.  
Natural and Propane Gas  
Model Numbers  
DT-400  
Input rate (BTU/H)  
17,500  
DR-400  
WARNING: FAILURE TO COMPLY WITH  
THEINSTALLATIONANDOPERATINGIN-  
STRUCTIONS PROVIDED IN THIS DOCU-  
MENT WILL RESULT IN AN IMPROP-  
ERLY INSTALLED AND OPERATING AP-  
PLIANCE,VOIDINGITSWARRANTY. ANY  
CHANGE TO THIS APPLIANCE AND/OR  
ITSOPERATINGCONTROLSISDANGER-  
OUS. IMPROPERINSTALLATIONORUSE  
OF THIS APPLIANCE CAN CAUSE SERI-  
OUS INJURY OR DEATH FROM FIRE,  
BURNS, EXPLOSION OR CARBON MON-  
OXIDE POISONING.  
All Models -  
Maximum manifold pressure is 3.5 in. w.c.  
(0.87 kPa) for natural gas and 10 in. w.c.  
(2.49 kPa) for LP/Propane gas.  
Cet appareil peut être installé dans un  
maison préfabriquée (É.-U. seulement)  
ou mobile déjà installée à demeure si  
les réglements locaux le permettent. Cet  
appareil doit être utilisé uniquement  
avec les types de gaz indiqués sur la  
plaque signalétique. Ne pas l'utiliser  
avec d'autres gaz sauf si un kit de con-  
version certifié est installé.  
Installations at Altitudes of 0 to 4500 ft.-  
Units are tested and approved for elevations  
of 0 to 4500 feet (0 to 1372 meters).  
Installations at Altitudes above 4500 ft.-  
For elevations above 4500 feet (1372  
meters), install the unit according to the  
regulations of the local authorities having  
jurisdictionand,intheUSA,thelatestedition  
of the National Fuel Gas Code (ANSI Z223.1)  
or, in Canada, the latest edition of the  
CAN1-B149.1 and .2 codes.  
Test gage connections are provided on the  
front of the millivolt gas control valve (iden-  
tified IN for the inlet and OUT for the mani-  
fold side). A ¹⁄₈" NPT test gage connection  
is provided at the inlet and outlet side of  
the electronic gas control valve.  
WARNING: CHILDREN AND ADULTS  
SHOULD BE ALERTED TO THE HAZARDS  
OFHIGHSURFACETEMPERATURES.USE  
CAUTION AROUND THE APPLIANCE TO  
AVOID BURNS OR CLOTHING IGNITION.  
YOUNG CHILDREN SHOULD BE CARE-  
FULLY SUPERVISED WHEN THEY ARE IN  
THE SAME ROOM AS THE APPLIANCE.  
Table 1 shows the units' gas orifice size for  
the elevations indicated.  
Minimum inlet gas pressure to these appli-  
ances is 5.0 inches water column (1.24 kPa)  
for natural gas and 11 inches water column  
(2.74 kPa) for propane for the purpose of input  
adjustment.  
Orifice size  
Model No.  
Natural Propane  
Maximum inlet gas supply pressure to these appli-  
ances is 10.5 inches water column (2.61 kPa) for  
natural gas and 13.0 inches water column (3.23  
kPa) for propane.  
DT-400  
WARNING: DO NOT PLACE CLOTHING  
OR OTHER FLAMMABLE MATERIALS  
ON OR NEAR THIS APPLIANCE.  
0.048  
inch  
#45  
DR-400  
AVERTISSEMENT: SURVEILLER LES  
ENFANTS. GARDER LES VÊTEMENTS,  
LES MEUBLES, L'ESSENCE OU AUTRES  
LIQUIDES À VAPEUR INFLAMMABLES  
À COTE DE L'APPAREIL.  
Table 1  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
REAR VENT  
APPLICA  
TION  
TOP VENT  
TION  
APPLICA  
APPLICATION  
TOP VENT  
HORIZONTAL VENT  
HORIZONTAL VENT  
VERTICAL VENT  
(Top Vent  
Application)  
HORIZONTAL VENT  
(Top Vent  
Application)  
VERTICAL VENT  
(Rear Vent  
Application)  
(Rear Vent Application (Rear Vent Application  
without a chase)  
With a chase)  
RECESSED  
INSTALLATION  
TOP VENT  
APPLICATION  
Typical Locations  
Figure 2  
LOCATION  
Shelf Height inches (mm)  
Top Vent - with One 90 Degree Elbow Rear Vent - Straight Out the Back  
Model No.  
In selecting the location, the aesthetic and  
functional use of the appliance are primary  
concerns. However, vent system routing to  
the exterior and access to the fuel supply are  
also important. Consideration should be given  
to traffic ways, furniture, draperies, etc., due  
to elevated surface temperatures (Figure 2 ).  
The location should also be free of electrical,  
plumbing or other heating/air conditioning  
ducting.  
Secure Vent  
44 1/8 (1121)  
N/A  
Secure Flex  
45 7/8 (1165)  
N/A  
Secure Vent  
N/A  
33 1/4 (845)  
Secure Flex  
N/A  
33 1/4 (845)  
DT-400  
DR-400  
Do not insulate the  
space between the  
appliance and the  
area above it.  
Do not insulate the  
space between the  
appliance and the  
area above it.  
Thesedirectventappliancesareuniquelysuited  
for installations requiring a utility shelf posi-  
tioned directly above the fireplace. Utility  
shelves like these are commonly used for  
locating television sets and decorative plants.  
Shelf Height  
(
see table)  
Shelf Height  
(
see table)  
To provide for the lowest possible shelf surface  
use the alternate rear vent outlet with attached  
venting routed in a way to minimize obstruc-  
tions to the use of the space above the appli-  
ance. Do not insulate the space between the  
applianceandtheareaaboveit.SeeFigure3.  
The minimum height from the base of the  
appliance to the underside of combustible ma-  
terials used to construct a utility shelf in this  
fashion is shown in the table in Figure 3.  
Shelf Above Fireplace With Top Venting  
Shelf Above Fireplace With Rear Venting  
Figure 3  
APPLIANCE AND VENT CLEARANCES  
1/2 in. (13 mm)  
0 in. (0 mm) spacers  
BACK  
The appliance is approved with zero clearance  
to combustible materials on all sides (as de-  
tailed in Table 2 ), with the following excep-  
tion: When the unit is installed with one side  
flush with a wall, the wall on the other side of  
the unit must not extend beyond the front edge  
of the unit. In addition, when the unit is re-  
cessed, the side walls surrounding the unit  
must not extend beyond the front edge of the  
unit. See Figure 2.  
1/2 in. (13 mm)  
0 in. (0 mm) spacers  
SIDES  
The appliance should be mounted on a fully  
supported base extending the full width and  
depthoftheunit. Theappliancemaybelocated  
on or near conventional construction materi-  
als. However, if installed on combustible ma-  
terials, such as carpeting, vinyl tile, etc., a  
metal or wood barrier covering the entire bot-  
tom surface must be used.  
TOP SPACERS  
FLOOR  
0 in. (0 mm)  
0 in. (0 mm)  
From Bottom  
of Unit to  
Ceiling  
64 in. (1626 mm)  
1 in. (25.4 mm)*  
VENT  
SERVICE CLEARANCES  
FRONT  
3 Feet. (0.9 meters)  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 1. FRAMING  
VENT TERMINATION CLEARANCES  
Horizontal Vent Termination Clearances  
Frame these appliances as illustrated in Fig-  
ures 8 on page 7, unless the appliance is to be  
installed in a corner. See Figure 9 on page 7  
for corner framing installations. All framing  
details must allow for a minimum clearance to  
combustible framing members as shown in  
Table 2 on page 4.  
Iftheapplianceistobeelevatedabovefloorlevel,  
asolidcontinuousplatformmustbeconstructed.  
Headers may be in direct contact with the appli-  
ance top spacers but must not be supported by  
themornotchedtofitaroundthem. Allconstruc-  
tionabovetheappliancemustbeselfsupporting,  
DONOTusetheapplianceforstructuralsupport.  
The fireplace should be secured to the side framing  
members using the unit's nailing flanges - one top  
and bottom on each side of the fireplace front. See  
Figure 6. Use 8d nails or their equivalent.  
Combustible Projection  
Theseinstructionsshouldbeusedasaguide-  
line and do not supersede local codes in any  
way. Install vent according to local codes,  
these instructions, the current National Fuel  
Gas Code (ANSI-Z223.1) in the USA or the  
current standards of CAN/CGA-B149.1 and -  
B149.2 in Canada.  
2¹⁄₂ inches or less in length  
Combustible Projection  
greater than 2¹⁄₂ inches in length  
Ventilated  
Soffit  
Unventilated  
Soffit  
3"  
Vertical Vent Termination Clearances  
Terminate single vent caps relative to building  
components according to Figure 4.  
(76 mm)  
18"  
12"  
(457 mm)  
(305 mm)  
TERMINATION HEIGHTS FOR VENTS ABOVE  
FLAT OR SLOPED ROOFS  
Horizontal Overhang  
Termination Kit  
2 FT  
MIN.  
Vertical  
Wall  
2 FT MIN.  
See Figure 31 or 32 for the recess allowances,  
into exterior walls, of the round and square  
horizontal terminations.  
Lowest  
Discharge  
Opening  
Vent  
Termination  
H*  
Figure 5 - Side Elevation View  
Storm Collar  
Flashing  
X
12  
Roof Pitch is X/12  
Step 2. (page 5) Route gas supply line to  
appliance location.  
Unit Nailing Flange  
1 inch (25.4 mm) Minimum  
Clearance to Combustibles  
Side  
(No clearance to  
Framing  
Step 3. (page 8) Installtheventsystemand  
exterior termination.  
combustible  
Concentric  
Vent Pipe  
*H = MINIMUM HEIGHT FROM ROOF TO  
LOWEST DISCHARGE OPENING OF VENT  
framing is required)  
Step 4. (page 20) Field Wiring  
Millivolt Appliances The operating control  
switch is factory installed.  
Step 5. (page 20) Install blower kit (optional  
equipment).  
Step 6. (page 21) Make connection to gas  
supply.  
Step 7. (page 22) Install the logs, vermicu-  
lite and glowing embers.  
Step 8. (page 22) Checkoutapplianceopera-  
tion.  
Step 9. (page 22) Install glass door frame  
assembly.  
Step 10. (page 23) Adjust burner to ensure  
H
(feet)  
1.0  
1.25  
1.5  
2.0  
2.5  
3.25  
4.0  
Roof Pitch  
Flat to 6/12  
Over 6/12 to 7/12  
Over 7/12 to 8/12  
Over 8/12 to 9/12  
Over 9/12 to 10/12  
Over10/12 to 11/12  
Over 11/12 to 12/12  
Left Side Front Corner of Fireplace Shown  
(Right Side Requirements the Same)  
Unit Being Secured By Its Nailing Flanges  
To The Framing  
Note: The nailing flanges, combustible members  
and screw heads located in areas directly adjacent  
to the nailing flanges, are EXEMPT from the 1/2”  
clearance to combustible requirements for the  
firebox outer wrapper. Combustible framing may be  
in direct contact with the nailing flanges and may  
be located closer than 1/2from screw heads and  
the firebox wrapper in areas adjacent to the nailing  
flanges. Frame the opening to the exact dimensions  
specified in the framing details of this manual.  
Figure 4  
Terminate multiple vent terminations accord-  
ing to the installation codes listed at the top of  
this page.  
Figure 6  
proper flame appearance.  
Step 11. (page 23) Install the hoods.  
Step 2. ROUTING GAS LINE  
Horizontal Vent Termination Clearances  
The horizontal vent termination must have a  
minimum of 3" (76 mm) clearance to any  
overhead combustible projection of 2 ¹⁄₂" (64  
mm) or less. See Figure 5. For projections  
exceeding 2 ¹⁄₂" (64 mm), see Figure 5. For  
additional vent location restrictions refer to  
Figure 7 on page 6.  
Route a ¹⁄₂" (13 mm) gas line along the inside of  
the right side framing as shown in Figure 7.  
Gas lines must be routed, constructed and  
made of materials that are in strict accordance  
with local codes and regulations.  
DETAILED INSTALLATION STEPS  
The appliance is shipped with all gas controls  
and components installed and pre-wired. Re-  
move the shipping carton, exposing the front  
glass door. Remove the top panel. Remove  
the cardboard from underneath the pressure  
relief plates. Gently depress the outer top  
corners of the access panel until the catches  
"pop"thepanelfree, allowingittoswingoutand  
down to open. Open the two latches (located  
under the firebox floor) securing the glass  
door. Remove the door by tilting it outward at  
the bottom and lifting it up. Set the door aside  
protecting it from inadvertent damage. See  
Figure 50 on page 21. Remove the two card-  
board pad strips from between the firebox  
subfloor and the firebox sides.  
All appliances are factory-equipped with a flex-  
ible gas line connector and ¹⁄₂ inch shutoff  
valve. (See step 6 on page 20).  
TYPICAL INSTALLATION SEQUENCE  
The typical sequence of installation follows,  
however, each installation is unique resulting  
in variations to those described.  
See the page numbers references in the follow-  
ing steps for detailed procedures.  
Right Side  
Front Corner of  
Fireplace Framing  
3"  
Step 1. (page 5) Construct the appliance  
framing. Position the appliance within the  
framing and secure with nailing brackets.  
(76 mm)  
6 ¹⁄₂"  
(152 mm)  
Figure 7  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS  
*
See Item D in the Text Below.  
Center Line  
Exterior Wall  
of Termination  
Inside  
Corner Detail  
*18”  
Horizontal  
Termination  
G
18”  
V
Ventilated Soffit  
A
Inside Corner  
= 9in U.S.  
= 12in Canada  
A
Detail D  
H
3 ft.  
X
B
B
B
E
D
C
C
A
A
V
V
V
Fixed  
Closed  
Window  
Operable  
Window  
L
V
3 ft.  
V
F
V
J
M
C
B
B
C
V
I
A
X
V
= Air Supply Inlet  
= Vent Terminal  
= Area where Terminal is not Permitted  
Canadian Installation*  
12 inches (30cm)*  
US Installation**  
12 inches (30cm)**  
A = Clearance above grade, veranda, porch,  
deck, or balcony.  
B = Clearance to window or door that may be  
opened.  
6 in (15cm) for appliances  
< 10,000 Btuh (3kW), 12 in (30cm)  
6 in (15cm) for appliances  
< 10,000 Btuh (3kW), 9 in (23cm)  
for appliances > 10,000 Btuh (3kW) and  
< 50,000 Btuh (15kW), 12 inches (30cm)  
for appliances > 50,000 Btuh (15kW)**  
9" (229mm) recommended to prevent  
window condensation  
for appliances > 10,000 Btuh (3kW) and  
< 100,000 Btuh (30kW), 36 inches (91cm)  
for appliances > 100,000 Btuh (30kW)*  
12" (305mm) recommended to prevent  
window condensation  
C = Clearance to permanently closed window  
D = Vertical clearance to ventilated soffit  
located above the terminal within a horizontal  
distance of 18 inches (458mm) from the center  
line of the terminal  
18" (458mm)  
18" (458mm)  
E = Clearance to unventilated soffit  
12" (305mm)  
12" (305mm)  
F = Clearance to outside corner  
G = Clearance to inside corner  
5" (12.7cm) minimum  
6" (15.2cm) minimum  
5" (12.7cm) minimum  
6" (15.2cm) minimum  
H = Clearance to each inside of center line  
extended above meter/regulator assembly  
I = Clearance to service regulator vent outlet  
3 feet (91cm) within a height of 15 feet  
above the meter/regulator assembly*  
3 feet (91cm)*  
3 feet (91cm) within a height of 15 feet  
above the meter/regulator assembly**  
3 feet (91cm)**  
J = Clearance to nonmechanical air supply inlet 6 in (15cm) for appliances  
6 in (15cm) for appliances  
to building or the combustion air inlet to any  
other appliance  
< 10,000 Btuh (3kW), 12 in (30cm)  
for appliances > 10,000 Btuh (3kW) and  
< 100,000 Btuh (30kW), 36 inches (91cm)  
for appliances > 100,000 Btuh (30kW)*  
6 feet (1.83m)*  
< 10,000 Btuh (3kW), 9 in (23cm)  
for appliances > 10,000 Btuh (3kW) and  
< 50,000 Btuh (15kW), 12 inches (30cm)  
for appliances > 50,000 Btuh (15kW)**  
3 feet (91cm) above if within 10 feet (3m)  
horizontally**  
K = Clearance to a mechanical air supply inlet  
L = Clearance above paved sidewalk or paved  
diveway located on public property  
M = Clearance under veranda, porch, deck or  
balcony  
7 feet (2.13m)‡  
7 feet (2.13m)‡  
12 inches (30cm)*‡  
12 inches (30cm)‡  
* In accordance with the current CSA-B149.1 National Gas And Propane Installation Code.  
** In accordance with the curent ANSI SZ223.1/NFPA 54 National Fuel Gas Codes.  
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves  
both dwellings.  
*Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:  
Figure 8  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIREPLACE FRAMING SPECIFICATIONS  
**FRAMING WITH SQUARE HORIZONTAL TERMINATIONS (SV4.5HTSSL, SV4.5HTSS or SV4.5HTS)  
AND ROUND HORIZONTAL TERMINATION (SV4.5HTR)  
VENT FRAMING -  
TOP VENT WITH ONE  
90° ELBOW  
10¹⁄₂  
(267)  
VENT FRAMING -  
REAR VENT WITH  
NO ELBOWS  
7
(178)  
5¹⁄₈  
(130)  
12¹⁄₈  
(308)  
Framing should be constructed of  
2x4 or larger lumber.  
7
*12⁷⁄₈ inches (327 mm) is the required  
framing depth dimension when the finish  
material (drywall) thickness is 1/2 in.  
(13mm).  
(178)  
37¹⁄₈  
(943)  
5¹⁄₈  
12¹⁄₈  
(308)  
(130)  
33¹⁄₄  
(845)  
** See the horizontal venting Figures 35  
and 36 on page 16 for restrictions on the  
use of the round termination (SV4.5HTR)  
19⁵⁄₈  
(498)  
*12⁷⁄₈  
(327)  
16⁵⁄₈  
(422)  
33¹⁄₄  
(845)  
Inches (mm)  
Note-  
Figure 9  
Venting requirements for rear vent applications in corner installations -  
- the round termination (SV4.5HTR) may not be used  
- the horizontal vent length ato b,must not exceed 28 inches (711 mm)  
SV4.5HTS Termination  
b
Framing should be constructed of  
2x4 or larger lumber.  
SV4.5HTSS & SV4.5HTSSL  
7 (178)  
Termination  
*These dimensions occur when one 45  
degree elbow is connected directly to the  
*F = 5 in.  
b
appliance collar and the unit moved ¹⁄₂ in.  
(127 mm)  
(13 mm) into the room. This ¹⁄₂ in.  
movement is required to achieve a min. of  
5 in (127 mm) in the F dimension.  
8³⁄₁₆ (208)  
*34⁵⁄₁₆  
(872)  
*24¹⁄₄  
(616)  
*17³⁄₁₆  
(437)  
a
33¹⁄₈  
(841)  
Inches  
(millimeters)  
*48¹⁄₂  
(1232)  
Back wall of chase/enclosure (including any finishing materials)  
CORNER FRAMING WITH SQUARE HORIZONTAL  
TERMINATIONS (SV4.5HTSSL, SV4.5HTSS or SV4.5HTS)  
Figure 10  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIREPLACE SPECIFICATIONS  
21¹⁄₂  
(546)  
(Louvered Front Model Shown)  
FRAMING  
SPACERS  
(Top and Sides  
and Rear)  
10³⁄₄  
(273)  
*CONCENTRIC FLUE  
FLUE - 4¹⁄₂ (114)  
COMBUSTION AIR - 7¹⁄₂ (190)  
Inches (millimeters)  
*DR models have only a rear vent  
*DT models have only a top vent  
6¹³⁄₁₆  
(173)  
Top View  
13  
(330)  
NOTE - Eyebrow  
3 (76)  
33¹⁄₈  
(841)  
hood shown as positioned  
in louvered front model.  
¹⁄₂ (13)  
ELECTRICAL INLET  
2³⁄₄ x 2 (70 x 51)  
COVER PLATE with  
KNOCKOUT)  
1
(25)  
1 (25)  
30¹⁄₈  
(765)  
17  
(432)  
33¹⁄₈  
(841)  
GAS INLET  
(Either Side  
and bottom)  
8¹¹⁄₃₂  
(212)  
27¹⁄₂  
(699)  
**19⁵⁄₈  
(498)  
1⁵⁄₈  
(42)  
3 (76)  
2³⁄₄  
(70)  
**Rear vent models only  
Front View  
Right Side View  
Figure 11  
Step 3. INSTALL THE VENT SYSTEM  
General Information  
DONOTuseanyothermanufacturer's  
vent components with these appli-  
ances. These fireplaces must be vented  
directly to the outside.  
VENT RESTRICTOR INSTALLATION  
(TOP VENT)  
In all venting applications using the top vent of  
the appliance, a vent restrictor may be  
needed. Install the vent restrictor in the top  
vent of the appliance outlet.  
These instructions should be used as a guide-  
line and do not supersede local codes in any  
way. Install vent according to local codes,  
these instructions, the current National Fuel  
Gas Code (ANSI-Z223.1) in the USA or the  
current standards of CAN/CGA-B149.1 and -  
B149.2 in Canada.  
The vent system may not service multiple  
appliances, and must never be connected to a  
flue serving a solid fuel burning appliance. The  
vent pipe is tested to be run inside an enclos-  
ing wall (such as a chase). There is no require-  
ment for inspection openings in the enclosing  
wall at any of the joints in the vent pipe.  
If needed, install the restrictor orientated as  
shown, either from inside or outside the unit,  
in the inner fireplace collar.  
RESTRICTOR  
Thesefireplacesaredesigned,testedand  
listed for operation and installation with,  
and only with, Secure Vent(SV 4.5)  
Direct Vent System Components, Secure  
FlexFlexible Vent Components manu-  
factured by Security Chimneys Interna-  
tional. These approved vent system com-  
ponents are labeled for identification.  
Preparing the Appliance Top Vent Outlet in  
All Venting Applications Using the Appliance  
Top Vent Outlet  
INNER  
FIREPLACE  
COLLAR  
APPLIANCE TOP VENT OUTLET  
A vent restrictor may be needed with this  
appliance. Installtheventrestrictor(provided)  
in the appliance top flue outlet as shown in  
Figure 12. It is held in place by friction, only.  
Figure 12  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Select Venting System - Horizontal or Vertical  
VENT SECTION LENGTH CHART  
VENT SECTION LENGTH CHART  
Nominal  
T
O
T
A
L
T
O
T
A
L
Nominal Section  
With the appliance secured in framing, deter-  
mine vent routing and identify the exterior  
termination location. The following sections  
describe vertical (roof) and horizontal (exterior  
wall) vent applications. Refer to the section  
relating to your installation. A list of approved  
venting components is shown in the tables on  
pages 24 and 25.  
6
12  
24  
36  
48  
Section Length  
6
12  
24  
36  
48  
Length (inches)  
(inches)  
Net Section  
4-1/2 10-1/2 22-1/2 34-1/2 46-1/2  
Number of Vent Sections  
Net Section  
Length (inches)  
4-1/2 10-1/2 22-1/2 34-1/2 46-1/2  
Number of Vent Sections  
Length (inches)  
Height of Vent  
Height of Vent  
Q
T
Q
T
inches  
144  
ft  
inches  
4.5  
ft  
Y
Y
0.375  
0.75  
1
2
0
1
0
0
1
1
0
0
0
0
0
0
0
0
0
0
0
1
2
1
2
12  
1
0
1
0
0
1
0
0
1
0
0
0
1
0
1
1
2
0
0
1
0
0
1
1
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
5
5
5
0
0
0
5
6
6
3
3
3
3
0
0
0
4
4
4
0
0
0
4
4
5
5
5
6
6
4
5
5
7
6
7
9
150  
12.5  
10.5 0.875  
15 1.25  
19.5 1.625  
21 1.75  
154.5 12.875  
160.5 13.375  
172.5 14.375  
0
0
VERTICAL TERMINATION SYSTEMS (ROOF)  
2
1
0
0
3
Figures 13, and Figures 23 through 27 on  
pages 12 to 13 and their associated  
Vertical Vent Tables illustrate the various ver-  
tical venting configurations that are possible  
for use with these appliances. Secure Vent  
pipe applications are shown in these figures;  
Secure Flex pipe may also be used. A Vertical  
Vent Table summarizes each systems mini-  
mum and maximum vertical and horizontal  
length values that can be used to design and  
install the vent components in a variety of  
applications. Both these vertical vent systems  
terminate through the roof. The minimum  
vent height above the roof and/or adjacent  
walls is specified in ANSI Z223.1-(latest edi-  
tion) (In Canada, the current CAN-1 B149  
installation code) by major building codes.  
Always consult your local codes for specific  
requirements. A general guide to follow is the  
Gas Vent Rule (refer to Figure 4 on page 5).  
0
0
1
0
0
1
2
0
2
3
0
1
0
1
0
0
0
1
0
0
0
0
1
0
0
0
0
0
0
0
2
1
3
3
1
3
177  
183  
186  
14.75  
15.25  
15.5  
22.5 1.875  
25.5 2.125  
31.5 2.625  
34.5 2.875  
37.5 3.125  
190.5 15.875  
196.5 16.375  
205.5 17.125  
43.5 3.625  
0
0
0
1
2
0
0
0
1
2
0
2
0
0
0
0
0
0
1
0
3
2
1
3
207  
17.25  
45  
3.75  
211.5 17.625  
46.5 3.875  
49.5 4.125  
217.5 18.125  
229.5 19.125  
232.5 19.375  
0
0
0
1
0
1
0
0
0
0
1
1
0
0
0
1
0
1
0
0
1
0
1
0
0
1
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
6
6
0
0
5
5
0
0
0
0
0
6
0
6
6
6
0
0
7
7
7
0
0
8
8
0
9
9
7
7
51  
4.25  
1
0
0
0
0
0
1
1
0
0
0
0
0
1
1
0
1
0
2
0
0
0
0
1
0
2
0
0
0
0
0
2
1
2
3
0
3
0
0
0
1
2
0
1
0
0
0
1
0
0
2
0
2
2
1
0
0
0
2
0
1
0
0
0
0
0
0
0
0
1
1
1
2
0
2
2
3
2
4
3
2
4
3
3
2
4
3
2
4
3
0
5
55.5 4.625  
237  
19.75  
0
6
57  
66  
4.75  
5.25  
241.5 20.125  
7
7
246  
252  
264  
276  
279  
20.5  
21  
7
8
67.5 5.625  
7
8
69  
72  
5.75  
6
22  
7
8
23  
8
8
73.5 6.125  
79.5 6.625  
Vertical (Straight) Installation  
23.25  
0
6
Determine the number of straight vent sections  
required. 4 ¹⁄₂" (114 mm), 10 ¹⁄₂" (267 mm), 22  
¹⁄₂"(572mm),34¹⁄₂"(876mm)and46¹⁄₂"(1181  
mm) net section lengths are available. Plan the  
ventlengthssothatajointdoesnotoccuratthe  
intersection of ceiling or roof joists. Refer to  
the Vent Section Length Chart.  
280.5 23.375  
283.5 23.625  
289.5 24.125  
301.5 25.125  
310.5 25.875  
8
9
81  
90  
6.75  
7.5  
0
7
0
7
91.5 7.625  
0
7
93  
96  
7.75  
8
9
9
315  
26.5  
9
10  
7
97.5 8.125  
102 8.5  
103.5 8.625  
325.5 27.125  
0
2
0
1
0
0
0
0
0
0
0
3
3
2
0
0
4
3
4
330  
336  
345  
27.5  
28  
0
8
SV4.5CGV-1  
SV4.5FA OR  
Termination  
0
8
SV4.5FB Flashing  
AND SV4.5SC  
108  
114  
117  
9
28.75  
10  
10  
0
10  
11  
8
STORM COLLAR  
9.5  
9.75  
0
1
1
0
1
0
0
0
1
2
0
1
0
0
0
0
0
0
0
5
0
1
1
6
0
0
0
0
0
3
3
3
0
4
0
4
2
0
0
0
0
0
0
3
0
4
6
5
4
5
6
4
3
5
349.5 29.125  
372 31  
118.5 9.875  
126 10.5  
130.5 10.875  
376.5 31.375  
379.5 31.625  
418.5 34.875  
0
9
1" (25.4 mm)  
Minimum  
Clearance to  
Combustibles  
11  
0
11  
9
135  
138  
11.25  
11.5  
423  
465  
35.25  
38.75  
0
10  
*SV4.5BF  
Firestop/Spacer  
0
10 10  
139.5 11.625  
142.5 11.875  
40' Max  
(12.2 M)  
SV4.5L6/12/24/36/48  
Vent Sections  
*When using Secure Flex,  
use Firestop/Spacer  
SF4.5BF  
Figure 13  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vertical (Offset) Installation  
All of the appliances covered in this document  
are fitted with collars having locking inclined  
channels. The dimpled end of the vent compo-  
nents fit over the appliance collar to create the  
positive twist lock connection.  
To add another vent component to a length of  
vent run, align the dimpled end over the inclined  
channel end of the previously installed section,  
adjusting the radial alignment until the four  
locking dimples are aligned with the inlets of the  
four incline channels of the previous section.  
Analyze the vent routing and determine the  
quantities of vent sections and number of el-  
bows required. Refer to Vertical Vent Figures  
andTablesonpage12and13toselectthetype  
of vertical installation desired. Vent sections  
are available in net lengths of 4 ¹⁄₂" (114 mm),  
10 ¹⁄₂" (267 mm), 22 ¹⁄₂" (572 mm), 34 ¹⁄₂" (876  
mm) and 46 ¹⁄₂" (1181 mm). Refer to the Vent  
Section Length Chart on page 9 for an aid in  
selectinglengthcombinations.Elbowsareavail-  
able in 90° and 45° configurations. Refer to  
Figure 18 for the SV4.5E45 and SV4.5E90  
elbow dimensional specifications.  
First Vent  
Component  
Align the dimple (four places)  
with the opening of the locking  
incline channel on appliance  
collar. Twist vent component  
clockwise to engage and seal.  
Push the vent component against the previous  
section until it fully engages, then twist the  
componentclockwiserunningthedimplesdown  
and along the incline channels until they seat at  
the end of the channels.This seating position  
is indicated by the alignment of the arrow and  
dimple as shown in Figure 16.  
Dimple  
Locking  
Incline Channel  
Appliance collar  
D. Install firestop/spacer at ceiling - Use a  
SV4.5BF firestop/spacer at ceiling joists. If  
there is living space above the ceiling level, the  
firestop/spacer must be installed on the bot-  
tom side of the ceiling. If attic space is above  
the ceiling, the firestop/spacer must be in-  
stalled on the top side of the joist. Route the  
vent sections through the framed opening and  
secure the firestop/spacer with 8d nails or  
other appropriate fasteners at each corner.  
Remember to maintain 1" (25 mm) clear-  
ance to combustibles, framing members,  
and attic or ceiling insulation when running  
vertical chimney sections.  
Vent / Appliance Collar  
Connection  
Where required, a telescopic vent section  
(SV4.5LA) may be used to provide the installer  
withanoptionininstallingintightand confined  
spaces or where the vent run made up of fixed  
length pieces develops a joint in a undesirable  
location, or will not build up to the required  
length. The SV4.5LA Telescopic Vent Section  
has an effective length of from 1 ¹⁄₂" (38 mm) to  
7 ¹⁄₂" (191 mm). The SV4.5LA is fitted with a  
locking inclined channel end (identical to a  
normal vent section component) and a plain  
endwith3pilotholes.Sliptheplainendoverthe  
locking channel end of a standard SV4.5 vent  
component the required distance and secure  
with three screws.  
Figure 15  
Arrow  
Align the dimple (four places) of the  
upper vent section with the opening of  
the locking incline channel on the  
lower vent section. Twist vent  
component clockwise to engage and  
seal until arrow and dimple align.  
Dimple  
Locking  
Incline Channel  
Connected  
Vent Sections  
Arrow  
E. Support the vertical vent run sections -  
Note - Proper venting support is very impor-  
tant. The weight of the vent must not be sup-  
ported by the firplace in any degree.  
Vent / Vent Section  
Connection  
Arrow  
Maintain a minimum 1" (25 mm) clearance to  
combustiblematerialsforallverticalelements.  
Clearances for all horizontal elements are 3"  
(76 mm) on top, 1" (25 mm) on sides and 1"  
(25 mm) on the bottom.  
Figure 16  
To attach a vent component to the appliance  
collar, align the dimpled end over the collar,  
adjusting the radial alignment until the four  
lockingdimplesarealignedwiththeinletofthe  
four inclined channels on the collar (refer to  
Figure 15 ). Push the vent component against  
the collar until it fully engages, then twist the  
component clockwise, running the dimples  
down and along the incline channels until they  
seat at the end of the channels. The unitized  
design of the Secure Vent components will  
engage and seal both the inner and outer pipe  
without the need for sealant or screws. If  
desired, a #6 x ¹⁄₂" screw may be used at the  
joint, but is not required as the pipe will se-  
curely lock when twisted.  
Support the vertical portion of the venting sys-  
temevery8feet(2.4m)abovethefireplacevent  
outlet. One method of support is by utilizing  
field provided support straps (conventional  
plumber's tape). Secure the plumber's tape to  
the framing members with nails or screws.  
A. Frame ceiling opening - Use a plumb line  
from the ceiling above the appliance to lo-  
cate center of the vertical run. Cut and/or  
frame an opening, 10¹⁄₂" x 10¹⁄₂" (267mm x  
267mm) inside dimensions, about this cen-  
ter mark (Figure 14).  
10¹⁄₂Min.  
(267 mm)  
Blocking  
10¹⁄₂Min.  
(267 mm)  
Support Straps  
(Plumbers tape)  
Note: An elbow may also be attached to the  
appliancecollar. Attachinthesamemanneras  
you would a vent section.  
8 feet (2.4 m)  
Maximum  
C. Attach vent components to each other -  
Other vent sections may be added to the pre-  
viously installed section in accordance with  
the requirements of the vertical vent figures  
and tables.  
Figure 14  
1 inch  
B. Attach vent components to appliance -  
Secure Vent SV4.5 direct vent system compo-  
nents are unitized concentric pipe components  
featuring positive twist lock connections (see  
Figure 15 ).  
(25.4 mm)  
minimum  
clearance to  
combustibles  
Figure 17  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Loop the tape around the vent, securing the  
ends of the tape to the framing. If desired,  
sheet metal screws #6 x ¹⁄₂" length may be  
used to secure the support straps to the vent  
pipe. Refer to Figure 17.  
Storm  
Collar  
C
F.Changeventdirectiontohorizontal/inclined  
run - At transition from or to a horizontal/  
inclinedrun,installtheSV4.5E45andSV4.5E90  
elbows in the same manner as the straight vent  
sections. The elbows feature a twist section to  
allow them to be routed about the center axis of  
their initial collar section to align with the re-  
quired direction of the next vent run element.  
Twist elbow sections in a clockwise direction  
onlysoastoavoidthepossibilityofunlocking  
any of the previously connected vent sec-  
tions. See Figure 18.  
D
Framing Dimensions for Roof  
Pitch  
0/12  
C
D
10¹⁄₂ in.  
10¹⁄₂ in.  
Figure 21  
(267 mm) (267 mm)  
10¹⁄₂ in. 12 in.  
(267 mm) (305 mm)  
10¹⁄₂ in. 17 ³⁄₄ in.  
(267 mm) (451 mm)  
K. Install the vertical termination - The final  
step involves installation of the SV4.5CGV-1  
VerticalTermination. Extendtheventsectionsto  
theheightasshowninthe"Verticalventtermina-  
tion section" on page 5. The SV4.5CGV-1 Verti-  
cal Termination (Figure 22 ) installs in the exact  
same fashion as any other Secure Vent section.  
Align the termination over the end of the previ-  
ouslyinstalledsection,adjustingtheradialalign-  
ment until the four locking dimples of the termi-  
nation are aligned with the inlets of the four  
inclinechannelsofthelastventsection. Pushthe  
terminationdownuntilitfullyengages,thentwist  
the termination clockwise running the dimples  
down and along the incline channels until they  
seat at the end of the channels.  
6/12  
12/12  
8 ¹⁄₈"  
4 ¹³⁄₁₆"  
(206 mm)  
Figure 19  
(122 mm)  
Swivel Joint  
Swivel Joint  
I. Install the roof flashing - Extend the vent  
sections through the roof structure. Install the  
roof flashing over the vent section and posi-  
tion such that the vent column rises vertically  
(use carpenters level) (Figure 20 ). Nail along  
perimeter to secure flashing or adjust roofing  
to overlap the flashing edges at top and sides  
only and trim where necessary. Seal the top  
and both sides of the flashing with waterproof  
caulking.  
(360° swivel)  
(360° swivel)  
SV4.5E45  
SV4.5E90  
(45° Elbow)  
(90° Elbow)  
Figure 18  
G.Continueinstallationofhorizontal/inclined  
sections - Continue with the installation of the  
straight vent sections in horizontal/inclined run  
as described in Step C. Install support straps  
every 5' (1.52 m) along horizontal/inclined vent  
runs using conventional plumbers tape. It is  
very important that the horizontal/inclined  
run be maintained in a straight (no dips) and  
recommended to be in a slightly elevated  
plane, in a direction away from the fireplace  
of ¹⁄₄" rise per foot (20 mm per meter) which is  
ideal, though rise per foot run ratios that are  
smaller are acceptable all the way down to at or  
near level. Use a carpenters level to measure  
from a constant surface and adjust the support  
straps as necessary.  
Figure 20  
It is important to maintain the required clear-  
ancestocombustibles:1"(25mm)atallsides  
for all vertical runs; and 3" (76 mm) at the top,  
1" (25 mm) at sides, and 1" (25 mm) at the  
bottom for all horizontal/inclined runs.  
J. Install the storm collar - Install the storm  
collar, supplied with the flashing, over the vent/  
flashing joint. See Figure 21. Loosen the storm  
collarscrew. Slidecollardownuntilitmeetsthe  
topoftheflashing. Tightentheadjustingscrew.  
Apply non-combustible caulking or mastic  
around the circumference of the joint to pro-  
vide a water tight seal.  
Figure 22  
If the vent system extends more than 5' (1.5 m)  
above the roof flashing, stabilizers may be  
necessary. Additional screws may be used at  
section joints for added stability. Guide wires  
may be attached to the joint for additional  
support on multiple joint configurations.  
H. Frame roof opening - Identify location for  
vent at the roof. Cut and/or frame opening per  
Roof Framing Chart and Figure 19.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VERTICAL VENT FIGURES/TABLES  
Note: Secure Vent (rigid vent pipe) is shown  
in the figures; Secure Flex (flexible vent pipe)  
may also be used.  
*When using Secure Flex,  
use Firestop/Spacer  
SF4.5BF  
**When using Secure  
Flex, use Firestop/Spacer  
SF4.5HF  
TABLE A  
*Ceiling  
V MINIMUM  
H Maximum  
Firestop/Spacer  
(SV4.5BF)  
feet  
(m)  
feet  
2
(m)  
(0.61)  
(1.222)  
(1.86)  
(2.4)  
WARNING:UNDERNOCIRCUMSTANCES  
MAY SEPARATE SECTIONS OF CONCEN-  
TRIC FLEXIBLE VENT PIPE BE JOINED  
TOGETHER.  
**Wall  
1
2
3
4
(0.305)  
(0.61)  
Firestop/Spacer  
(SV4.5HF)  
4
(0.914)  
(1.22)  
6
V
8
Note: It is very important that the horizontal/  
inclined run be maintained in a straight (no  
dips) and recommended to be in a slightly  
elevated plane, in a direction away from the  
fireplace of ¹⁄₄" rise per foot (20 mm per  
meter) which is ideal, though rise per foot run  
ratios that are smaller are acceptable all the  
way down to at or near level.  
V + H = 40 feet (12.4 m) Max.  
H = 8 feet (2.4 m) Max.  
H
Figure 24 - Rear Vent - ONE 90 DEGREE ELBOW  
Note: SV4.5BF (Secure Vent), SF4.5BF (Secure  
Flex) firestop/spacer must be used anytime vent  
pipe passes through a combustible floor or ceil-  
ing. SV4.5HF (Secure Vent), SF4.5HF (Secure  
Flex)firestop/spacer must be used anytime vent  
pipe passes through a combustible wall.  
TABLE B  
V MINIMUM  
H Maximum  
feet (meters) feet (meters)  
Note: Two 45 degree elbows may be used in  
place of one 90 degree elbow. The same rise to  
run ratios, as shown in the venting figures for  
90 elbows, must be followed if 45 degree  
elbows are used.  
H
1
2
3
4
(0.305)  
(0.610)  
(0.914)  
(1.22)  
5
(1.52)  
(3.1)  
10  
15  
20  
*Ceiling  
Firestop/Spacer  
(SV4.5BF)  
(4.65)  
(6.2)  
V + V1+ H = 40 feet (12.4 m)  
Max.  
H = 20 feet (6.2 m) Max.  
*When using Secure Flex,  
use Firestop/Spacer  
V1  
SF4.5BF  
40 feet (12.2 meters)  
V
*Ceiling  
Firestop/Spacer  
(SV4.5BF)  
Maximum  
**Wall  
Firestop/Spacer  
(SV4.5HF)  
*Ceiling  
Firestop/Spacer  
(SV4.5BF)  
**When using Secure  
Flex, use Firestop/Spacer  
SF4.5HF  
*When using  
Secure Flex, use  
Firestop/Spacer  
SF4.5BF  
Figure 25 - Top Vent - TWO 90 DEGREE ELBOWS  
Figure 23 - Top Vent - STRAIGHT  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VERTICAL VENT FIGURES/TABLES  
(continued)  
TABLE D  
V Minimum H Maximum H+H1 Maximum  
H1  
*When using Secure Flex,  
use Firestop/Spacer  
SF4.5BF  
**When using Secure  
Flex, use Firestop/Spacer  
SF4.5HF  
feet  
1
(m)  
feet  
2
(m)  
feet  
5
(m)  
(1.52)  
(3.1)  
*Ceiling  
Firestop/Spacer  
(SV4.5BF)  
(0.305)  
(0.610)  
(0.914)  
(1.22)  
(0.610)  
(1.22)  
(1.86)  
(2.48)  
2
4
10  
15  
20  
A Vent Restrictor, as  
shown in Figure 18,  
page 10, must be used  
in this application  
3
6
(4.65)  
(6.2)  
**Wall  
4
8
Firestop/Spacer  
(SV4.5HF)  
V+V1+H+H1 = 40 feet (12.4 m) Max.  
H = 8 feet (2.48 m) Max.  
H + H1 = 20 feet (6.2 m) Max.  
V1  
*Ceiling  
Firestop/Spacer  
(SV4.5BF)  
V
H
Figure 26 - Rear Vent - THREE ELBOWS  
TABLE E  
*Ceiling  
Firestop/Spacer  
(SV4.5BF)  
V MINIMUM  
H + H1 Maximum  
**Wall  
V
1
Firestop/Spacer  
(SV4.5HF)  
feet  
(m)  
feet  
5
(m)  
(1.52)  
(3.1)  
1
2
3
4
(0.305)  
(0.610)  
(0.914)  
(1.22)  
H
10  
15  
20  
(4.65)  
(6.2)  
H
1
H +H1= 20 feet (6.2 m) Max.  
V+V1+H+H1 = 40 feet (12.4 m) Max.  
V
*When using Secure Flex,  
use Firestop/Spacer  
SF4.5BF  
**When using Secure  
Flex, use Firestop/Spacer  
SF4.5HF  
Figure 27 - Top Vent - THREE ELBOWS  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HORIZONTAL (OUTSIDE WALL)  
TERMINATION SYSTEM  
TYPICAL HORIZONTAL VENT INSTALLATION  
Support  
Building  
Support  
Framing  
Horizontal / Inclined Run  
SV4.5HTSSL  
Termination  
Shown  
Brackets  
Figures 28, and Figures 34 to 41 on pages 16 to  
18 and their associated Horizontal Vent Table  
illustrate the various horizontal venting configura-  
tions that are possible for use with these appli-  
ances. SecureVentpipeapplicationsareshownin  
these figures; Secure Flex pipe may also be used.  
AHorizontalVentTablesummarizeseachsystems  
minimum and maximum vertical and horizontal  
lengthvaluesthatcanbeusedtodesignandinstall  
the vent components in a variety of applications.  
Both of these horizontal vent systems terminate  
through an outside wall. Building Codes limit or  
prohibit terminating in specific areas. Refer to  
Figure 8 on page 6 for location guidelines.  
SV4.5E90  
Elbow  
Firestop/Spacer  
Exterior  
Wall  
SV4.5L6/12/24/36/48  
Ceiling  
Vent Sections  
*Ceiling  
Firestop/Spacer  
(SV4.5BF)  
SV4.5HTSSL  
Termination  
Shown  
Vertical  
Rise  
Support Bracket Spacing  
Every 5 ft (1.52 m)  
*When using Secure Flex  
use Firestop/Spacer  
(SF4.5BF)  
See Figure 17 on page 10  
for vertical vent section  
support.  
Fireplace  
Fireplace  
Exterior  
Wall  
Figure 28  
Secure Vent SV4.5 direct vent system compo-  
nents are unitized concentric pipe components  
featuring positive twist lock connection, (refer to  
Figure 15 on page 10). All of the appliances  
covered in this document are fitted with collars  
having locking inclined channels. The dimpled  
endoftheventcomponentsfitovertheappliance  
collartocreatethepositivetwistlockconnection.  
Sealant and securing screws are not required.  
H. Change vent direction - At transition from  
or to a horizontal/inclined run, install the  
SV4.5E45 and SV4.5E90 elbows in the same  
manner as the straight vent sections. The  
elbows feature a twist section to allow them  
to be routed about the center axis of their  
initial collar section to align with the required  
direction of the next vent run element. Twist  
elbow sections in a clockwise direction only  
so as to avoid the possiblity of unlocking  
any of the previously connected vent sec-  
tions. See Figure 18 on page 11.  
Note: An elbow may also be attached to the  
appliancecollar. Attachinthesamemanneras  
you would a vent section.  
E. Attach vent components to each other -  
Other vent sections may be added to the previ-  
ously installed section in accordance with the  
requirements of the vent tables. To add another  
vent component to a length of vent run, align the  
dimpled end of the component over the inclined  
channel end of the previously installed section,  
adjusting the radial alignment until the four  
locking dimples are aligned with the inlets of the  
four incline channels of the previous section.  
Push the vent component against the previous  
section until it fully engages, then twist the  
componentclockwiserunningthedimplesdown  
and along the incline channels until they seat at  
the end of the channels.This seating position is  
indicated by the alignment of the arrow and  
dimple as shown in Figure 16 on page 10.  
A. Plan the vent run -  
Analyze the vent routing and determine the  
types and quantities of sections required  
4 ¹⁄₂" (114 mm), 10 ¹⁄₂" (267 mm), 22 ¹⁄₂" (572  
mm), 34 ¹⁄₂" (876 mm) and 46 ¹⁄₂" (1181 mm)  
net section lengths are available. Make allow-  
ances for elbows as indicated in Figure 18 on  
page 10. Maintain a minimum 1" (25 mm)  
clearance to combustibles on the vertical  
sections. Clearances for the horizontal runs  
are; 3" (76 mm) on top, 1" (25 mm) on sides,  
and 1" (25 mm) at the bottom.  
I. Continueinstallationofhorizontal/inclined  
sections - Continue with the installation of the  
straight vent sections in horizontal/inclined  
run as described in Step E. Install support  
straps every 5 ft. (1.52 m) along horizontal/  
inclinedventrunsusingconventionalplumbers  
tape. See Figure 28. It is very important that  
the horizontal/inclined run be maintained in a  
straight (no dips) and recommended to be in  
a slightly elevated plane, in a direction away  
from the fireplace of ¹⁄₄" rise per foot (20 mm  
per meter) which is ideal, though rise per foot  
run ratios that are smaller are acceptable all the  
way down to at or near level. Use a carpenters  
level to measure from a constant surface and  
adjust the support straps as necessary.  
B. Frame exterior wall opening -  
Locatethecenteroftheventoutletontheexteriorwall  
according to the dimensions shown in Figure 9 on  
page 7. Cut and/or frame an opening, 10¹⁄₂" x 12¹⁄₈"  
(267 mm x 308mm) inside dimensions, about this  
center.  
F. Install firestop/spacer at ceiling -  
When using Secure Vent, use SV4.5BF fir-  
estop/spacer at ceiling joists; when using Se-  
cure Flex, use SF4.5BF firestop/spacer. If there  
is living space above the ceiling level, the fir-  
estop/ spacer must be installed on the bottom  
side of the ceiling. If attic space is above the  
ceiling, the firestop/ spacer must be installed  
on the top side of the joist. Route the vent  
sections through the framed opening and se-  
cure the firestop/spacer with 8d nails or other  
appropriate fasteners at each corner.  
C. Frame ceiling opening - If the vertical  
route is to penetrate a ceiling, use plumb line  
to locate the center above the appliance. Cut  
and/or frame an opening, 10¹⁄₂" x 10¹⁄₂" (267  
mm x 267 mm) inside dimensions, about this  
center (refer to Figure 14 on page 10 ).  
It is important to maintain the required clear-  
ancestocombustibles:1"(25mm)atallsides  
for all vertical runs; and 3" (76 mm) at the top,  
1" (25 mm) at sides, and 1" (25 mm) at the  
bottom for all horizontal/inclined runs.  
D. Attach vent components to appliance - To  
attach a vent component to the appliance collar,  
align the dimpled end over the collar, adjusting  
theradialalignmentuntilthefourlockingdimples  
are aligned with the inlets of the four incline  
channels on the collar (refer to Figure 15 on  
page 10). Push the vent component against the  
collar until it fully engages, then twist the com-  
ponent clockwise, running the dimples down  
and along the incline channels until they seat at  
the end of the channels. The unitized design of  
the Secure Vent components will engage and  
seal both the inner and outer pipe elements with  
the same procedure.  
Remember to maintain 1" (25 mm) clearance  
to combustibles, framing members, and attic  
or ceiling insulation when running vertical  
chimney sections.  
J. Assemble vent run to exterior wall - If not  
previously measured, locate the center of the  
vent at the exterior wall. Prepare an opening as  
described in Step B  
G. Support the vertical run sections -  
Whenusingsquare(SV4.5HTS),shortsquare  
(SV4.5 HTSS) or round (SV4.5HTR) horizon-  
tal termination -  
Assemble the vent system to point where the  
terminus of the last section is within 6 in. (152  
mm) to 10¹⁄₄ in. (260 mm) inboard of the  
exterior surface to which the termination is to  
be attached, see Figure 31 on page 15.  
On the vertical run, support the venting system  
every 8 feet (2.4m) above the fireplace vent  
outlet with field provided support straps  
(Plumber's tape). Attach the straps to the vent  
pipe and secure to the framing members with  
nails or screws. See Figure 17 on page 10.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the terminus of the last section is not within  
this distance, use the telescopic vent section  
SV4.5LA, as the last vent section. For wall  
thicknesses greater than that shown in Figure  
31, refer to table 3 on page 16. This table lists  
the additional venting components needed (in  
addition to the termination and adapter) for a  
particular range of wall thicknesses.  
*Firestop/Spacer (SV4.5HF) shown  
on the exterior side of the wall. It  
may also be installed on the  
interior side.  
*Note - Firestop/Spacer integral  
with round termination  
(SV4.5HTR)  
SV4.5 HTSS  
Termination  
Shown.  
10¹⁄₂"  
(267 mm)  
*Note - When using Secure Flex  
use Firestop/Spacer SF4.5HF  
See Venting Figures for Use  
Restrictions on the Horizontal  
Round Termination (SV4.5HTR).  
3"  
(76 mm)  
When using long square (SV4.5HTSSL)  
horizontal termination -  
Assemble the vent system to point where the  
terminus of the last section is within 0 in. (0  
mm) to 9³⁄₄ in. (248 mm) inboard of the  
exterior surface to which the termination is to  
be attached, see Figure 32.  
6 to 48 inch Vent Section,  
Telescopic vent section,  
Elbow or Appliance Collar  
1"  
(25.4 mm)  
7"  
(178)  
5¹⁄₈"  
(130 mm)  
Adapter  
SV4.5RCH  
12¹⁄₈"  
(308 mm)  
Note: Centerline of Vent  
Piping is NOT the Same as  
the Centerline of the  
Framed Opening.  
See Figure 9 on page  
7 for Min. Distance to  
Base of Appliance.  
K. When using square (SV4.5HTS) or short  
square (SV4.5 HTSS) horizontal termination  
- attach termination adapter -  
Attach the adapter (adapter - SV4.5RCH - pro-  
videdwiththe termination)totheventsectionor  
telescoping vent section), elbow or appliance  
collarasshowninFigure29 inthesamemanner  
as any SV4.5 vent component (refer to Step E).  
Base of Appliance  
Installing Square HorizontalTermination (SV4.5HTS) Short Square Horizontal  
Termination (SV4.5HTSS) Round Horizontal Termination (SV4.5HTR)  
Figure 29  
*Firestop/Spacer (SV4.5HF) shown  
on the exterior side of the wall. It  
may also be installed on the  
interior side.  
SV4.5 HTSSL  
Termination  
Note: Centerline of Vent Piping is  
NOT the Same as the Centerline of  
the Framed Opening.  
L. Install Firestop/Spacer at exterior wall -  
When using either of the square terminations,  
install SV4.5HF (Secure Vent), or SF4.5HF  
(Secure Flex) firestop/spacer over the opening  
at the exterior side of the framing, long side up,  
with the 3 inch spacer clearance at the top as  
shown in Figure 29 or 30, and nail into place.  
(The Firestop/Spacer may be installed over the  
opening at the interior side of the framing.)  
When using the round termination, a separate  
firestop/spacer is not required since this termi-  
nation has integral spacers which provide the  
same function as a separate firestop/spacer.  
10¹⁄₂"  
(267 mm)  
3"  
See Figure 9 on page 7  
for Min. Distance to  
Base of Appliance.  
(76 mm)  
Base of Appliance  
1"  
(25.4 mm)  
6 to 48 inch Vent Section,  
Elbow or Appliance Collar  
7"  
(178)  
5¹⁄₈"  
(130 mm)  
12¹⁄₈"  
(308 mm)  
*When using Secure Flex, use  
Firestop/Spacer (SF4.5HF)  
Figure 30  
Installing Long Square HorizontalTermination (SV4.5HTSSL)  
Minimum wall thickness  
*6 in. (152 mm)  
*Note - Firestop/Spacer  
(SV4.5HF) required, but  
not shown for clarity.  
Minimum wall thickness  
*Cut termination collar  
for wall thicknesses  
*10³⁄₄ in. (273 mm)  
less than 10³⁄₄ in. (273 mm).  
Maximum wall thickness  
Maximum wall thickness  
20 in. (508 mm)  
10¹⁄₄ in. (260 mm)  
Interior Surface of Finished Wall  
Interior Surface of  
Finished Wall  
Exterior Surface of Siding  
Exterior Surface of Framing  
Maximum Extent of  
Vent Run Sections  
Relative to Exterior  
Surface of Framing  
Exterior Surface of Siding  
Exterior Surface of Framing  
Maximum Extent of  
Vent Run Sections  
Relative to Exterior  
Surface of Framing  
6 in. to 10¹⁄₄ in.  
(152 mm to 260 mm)  
10³⁄₄ to 20 in.  
Last Vent Section. Use  
Telescopic Vent Section  
(SV4.5LA), If Necessary  
(273 to 508 mm)  
*Cut termination collar  
for wall thicknesses  
less than 6 in. (152 mm).  
Last Vent Section  
Termination Securing  
Screw  
SV4.5HTSSL Long  
Square Termination  
Adapter  
SV4.5RCH  
SV4.5HTSS Short  
Square Termination  
Shown  
Siding  
Siding  
1¹⁄₄" Maximum Recess of Square  
Termination into Exterior Finishing  
Material. Round Termination may  
not be recessed at all.  
1¹⁄₄" Maximum Recess of  
Square Termination into  
Exterior Finishing Material  
*Note - Firestop/Spacer  
(SV4.5HF) required, but not  
shown for clarity.  
*When using Secure Flex, use  
Firestop/Spacer SF4.5HF  
*When using Secure Flex, use  
Firestop/Spacer SF4.5HF.  
Connecting/Recessing  
Square (SV4.5HTS)  
Short Square (SV4.5HTSS)  
or Round (SV4.5HTR)  
Horizontal Termination  
SV4.5HTSS Short Square  
Termination Shown  
SV4.5HTSSL Long  
Connecting/Recessing  
Long Square Horizontal  
Termination (SV4.5HTSSL)  
Square Termination  
Stucco  
Stucco  
Figure 31  
Figure 32  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M. Install the desired termination - See the  
horizontal venting figures for application re-  
strictionsontheroundtermination(SV4.5HTR).  
Orient the housing of the termination with the  
arrow pointed upwards. Secure the termina-  
tion to the exterior wall. The horizontal termi-  
nation must not be recessed into the exterior  
wall or siding by more than the 1 ¹⁄₄" (32 mm)  
as shown in Figure 32.  
The SV4.5HTR Round Termination may not  
be used when the appliance is vented di-  
rectly out the wall from the rear as shown in  
Figures 34 and 35.  
1.Installthesquare(SV4.5HTS)orshortsquare  
termination (SV4.5HTSS) - For the last step ,  
from outside the exterior wall, slide the collars of  
the termination into the adapter (see Figure 31)  
untiltheterminationseatsagainsttheexteriorwall  
surface to which it will be attached. Orient the  
housingoftheterminationwiththearrowpointed  
upwards. Secure the termination to the exterior  
wall. The horizontal termination must not be  
recessedintotheexteriorwallorsidingbymore  
than the 1 ¹⁄₄" (32 mm) as shown in Figure 31.  
Do Not recess the SV4.5HTR round termina-  
tion at all.  
3. Install the round termination (SV4.5HTR)  
See Figure 33 for an illustration of the round  
termination. For the last step, from outside the  
exterior wall, slide the collars of the termina-  
tion onto the adapter (same as shown in Fig-  
ure 31 for the SV4.5HTSS short square termi-  
nation) until the termination seats against the  
exterior wall surface to which it will be at-  
tached. Orient the housing of the termination  
with the arrow pointed upwards. Secure the  
termination to the exterior wall.  
SeeHorizontalVenting  
Figures and Tables for  
Use Restrictions  
SV4.5HTR Horizontal  
Round Termination  
Figure 33  
2. Install the long square termination  
(SV4.5HTSSL) - For the last step , from outside  
the exterior wall, slide the collars of the termi-  
nationontothelastventsection(seeFigure32)  
until the termination seats against the exterior  
wall surface to which it will be attached.  
SFHRK Snorkel Cap The snorkel cap is de-  
signed to be fitted into a basement window  
box. The SFHRK cap is for use with flex vent  
The vertical distance between the inlet and  
outlet of the cap is 28 in. (711 mm). pipe.  
Note: Secure Vent components (rigid vent pipe and terminal) are shown in  
the figures; Secure Flex components (flexible vent pipe and terminal) may also  
be used.  
HORIZONTAL VENT FIGURES/TABLES  
TABLE 3 - Venting Components Required for Various Exterior  
Wall Thicknesses, When Using Any of These Termination Kits -  
Square Termination (SV4.5HTS) Small Square Termination  
(SV4.5HTSS) Round Termination (SV4.5HTR)  
Note: SV4.5BF (Secure Vent), SF4.5BF (Secure Flex) firestop/spacer must be  
used anytime vent pipe passes through a combustible floor or ceiling. SV4.5HF  
(Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used anytime  
vent pipe passes through a combustible wall.  
Venting Components  
Required  
Termination Kit Only  
Exterior Wall Thicknesses  
inches (mm)  
6 to 10 1/4 (152 to 260)  
Note: Two45degreeelbowsmaybeusedinplaceofone90degreeelbow.Thesame  
rise to run ratios, as shown in the venting figures for 90 elbows, must be followed if  
45 degree elbows are used.  
Termination Kit and 6 in. vent  
section (SV4.5L6)  
Termination Kit and12 in. vent  
section (SV4.5L12)  
10 1/4 to 14 3/4 (260 to 375)  
16 3/4 to *20 3/4 (425 to *527)  
Note: It is very important that the horizontal/inclined run be maintained  
in a straight (no dips) and recommended to be in a slightly elevated  
plane, in a direction away from the fireplace of ¹⁄₄" rise per foot (20 mm  
per meter) which is ideal, though rise per foot run ratios that are smaller are  
acceptable all the way down to at or near level.  
Termination Kit and Telescopic  
section (SV4.5LA) and 6 in.  
vent section (SV4.5L6)  
11 3/4 to *21 3/4 (298 to *552)  
*Note: See Figure 35 for wall thickness range reductions when using  
SV4.5HTSandSV4.5HTSSterminations.  
WARNING: UNDERNOCIRCUMSTANCESMAYSEPARATESECTIONS  
OF CONCENTRIC FLEXIBLE VENT PIPE BE JOINED TOGETHER.  
28 in. (711 mm)  
Maximum  
20 in. (508 mm)  
Maximum  
28 in. (711 mm)  
Maximum.  
10³⁄₄ to 20 in.  
(273 to 508 mm)  
*When using Secure Flex,  
use Firestop/Spacer  
(SF4.5HF)  
*Wall Firestop/Spacer  
(SV4.5HF)  
*Wall Firestop/Spacer  
(SV4.5HF)  
SV4.5HTSS Termination Shown  
*When using Secure flex,  
12 in. Vent Section  
Note - In applications where the wall thickness is less than 6 inches  
(152 mm), field shortening of the termination collar may be required.  
use Firestop/Spacer  
(SV4.5L12)  
SF4.5HF)  
See Table 3 as an aid in venting component selection for a particular  
range of exterior wall thicknesses.  
The round horizontal termination (SV4.5HTR) may not be used.  
Note - It may be necessary to cut the termination collar  
in some applications.  
The round horizontal termination (SV4.5HTR) may not be used.  
Rear Vent - NO ELBOWS - with SV4.5HTSSL  
Figure 35 -  
Rear Vent - NO ELBOWS - with SV4.5HTS SQUARE OR  
SV4.5HTSS SHORT SQUARE TERMINATION  
Figure 34 -  
LONG SQUARE TERMINATION  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HORIZONTAL VENT FIGURES/TABLES (CONTINUED)  
TABLE F  
V = 0ne 90 degree elbow  
H = 3 feet (0.914 m) Max.  
H
V
Refer to Table 3 on page 16 for an aid in venting component selection for a  
particularrangeofexteriorwallthicknesseswhenusingthesquare(SV4.5HTS),  
small square (SV4.5HTSS) or the round (SV4.5HTR) termination .  
Short Square Termination (SV4.5HTSS) shown;  
Long Square Termination (SV4.5HTSSL) may also be used;  
Square Termination (SV4.5HTS) may also be used  
Round Termination (SV4.5HTR) may also be used.  
*Wall Firestop/Spacer  
(SV4.5HF)  
*When using Secure Flex, use Wall Firestop/Spacer SV4.5HF.  
Figure 36 - Top Vent - ONE 90 DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE  
TABLE G  
TABLE H  
V Minimum  
H Maximum H+H1 Maximum  
V Minimum  
H Maximum  
feet  
(m)  
feet  
2
(m)  
feet  
5
(m)  
(1.52)  
(3.1)  
feet  
(m)  
feet  
5
(m)  
(1.52)  
(3.1)  
1
2
3
4
(0.305)  
(0.610)  
(0.914)  
(1.22)  
(0.610)  
(1.22)  
(1.86)  
(2.48)  
1
2
3
4
(0.305)  
(0.61)  
4
10  
15  
20  
10  
6
(4.65)  
(6.2)  
(0.914) 15  
(1.22) 20  
(4.65)  
(6.2)  
8
V+H+H1 = 40 feet (12.4 m) Max.  
H = 8 feet (2.48 m) Max.  
H + H1 = 20 feet (6.2 m) Max.  
V + H = 40 feet (12.4 m) Max.  
H = 20 feet (6.2 m) Max.  
RefertoTable3onpage16 foranaidinventingcomponentselection  
for a particular range of exterior wall thicknesses when using the  
square (SV4.5HTS), small square (SV4.5HTSS) or the round  
(SV4.5HTR) termination .  
Refer to Table 3 on page 16 for an aid in venting component selection for a  
particularrangeofexteriorwallthicknesseswhenusingthesquare(SV4.5HTS),  
small square (SV4.5HTSS) or the round (SV4.5HTR) termination .  
Short Square Termination (SV4.5HTSS) shown;  
Long Square Termination (SV4.5HTSSL) may also be used;  
Square Termination (SV4.5HTS) may also be used  
Round Termination (SV4.5HTR) may also be used.  
Short Square Termination (SV4.5HTSS) shown;  
Long Square Termination (SV4.5HTSSL) may also be used;  
Square Termination (SV4.5HTS) may also be used  
Round Termination (SV4.5HTR) may also be used.  
H
H
1
*When using Secure Flex,  
use Wall Firestop/Spacer  
SF4.5HF.  
H
*Wall  
Firestop/Spacer  
(SV4.5HF)  
V
**Ceiling  
Firestop/Spacer  
(SV4.5BF)  
*When using Secure  
*Wall  
Firestop/Spacer  
(SV4.5HF)  
Flex, use Wall  
Firestop/Spacer  
SF4.5HF.  
V
*Wall Firestop/Spacer  
(SV4.5HF)  
**Ceiling Firestop/Spacer  
(SV4.5BF)  
**When using Secure  
Flex, use Ceiling  
Firestop/Spacer  
SF4.5BF.  
**When using Secure Flex, use Ceiling  
Firestop/Spacer SF4.5BF.  
Figure 37 - Top Vent - ONE 90 DEGREE ELBOW -  
ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE  
Figure 38- Rear Vent - TWO 90 DEGREE ELBOWS  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HORIZONTAL VENT FIGURES/TABLE (CONTINUED)  
Refer to Table 3 on page 16 for an aid in venting component selection for a particular range of exterior  
wall thicknesses when using the square (SV4.5HTS), small square (SV4.5HTSS) or the round (SV4.5HTR)  
TABLE J  
V MINIMUM  
H + H1 Maximum  
termination .  
*Wall Firestop/Spacer  
(SV4.5HF)  
feet  
(m)  
feet  
(m)  
(1.52)  
(3.1)  
1
2
3
4
(0.305)  
(0.610)  
(0.914)  
(1.22)  
5
H
10  
15  
20  
(4.65)  
(6.2)  
H
1
V
V + H+ H1 = 40 feet (12.4 m) Max.  
H + H1= 20 feet (6.2 m) Max.  
*When using Secure Flex,  
use Wall Firestop/Spacer  
SF4.5HF.  
*Wall Firestop/Spacer  
(SV4.5HF)  
Short Square Termination (SV4.5HTSS) shown;  
Long Square Termination (SV4.5HTSSL) may also be used;  
Square Termination (SV4.5HTS) may also be used  
Round Termination (SV4.5HTR) may also be used.  
**Ceiling  
Firestop/Spacer  
(SV4.5BF)  
**When using Secure  
Flex, use Ceiling  
Firestop/Spacer  
SF4.5BF.  
Figure 39- Top Vent - TWO 90 DEGREE ELBOWS  
TABLE K  
*Wall Firestop/Spacer  
(SV4.5HF)  
H+H1+H2  
Maximum  
V Minimum  
H Maximum  
H
1
feet  
(m)  
feet  
2
(m)  
feet  
(m)  
(1.52)  
(3.1)  
H
2
1
2
3
4
(0.305)  
(0.610)  
(0.914)  
(1.22)  
(0.610)  
(1.22)  
(1.86)  
(2.48)  
5
4
10  
15  
20  
*When using Secure Flex,  
use Wall Firestop/Spacer  
SF4.5HF.  
6
(4.65)  
(6.2)  
**Ceiling Firestop/Spacer  
(SV4.5BF)  
8
V+H+H1+H2 = 40 feet (12.4 m) Max.  
H = 8 feet (2.48 m) Max.  
H+H1+H2= 20 feet (6.2 m) Max.  
**When using Secure Flex,  
use Ceiling Firestop/Spacer  
SF4.5BF.  
V
Refer to Table 3 on page 16 for an aid in venting component selection for a  
particularrangeofexteriorwallthicknesseswhenusingthesquare(SV4.5HTS),  
small square (SV4.5HTSS) or the round (SV4.5HTR) termination .  
Short Square Termination (SV4.5HTSS) shown;  
Long Square Termination (SV4.5HTSSL) may also be used;  
Square Termination (SV4.5HTS) may also be used  
Round Termination (SV4.5HTR) may also be used.  
H
Figure 40 - Rear Vent - THREE 90 DEGREE ELBOWS  
*When using Secure Flex,  
use Wall Firestop/spacer  
SF4.5HF.  
TABLE L  
V MINIMUM  
H Maximum  
H
**When using Secure flex,  
use Ceiling Firestop/spacer  
SF4.5BF.  
1
feet  
(m)  
feet  
5
(m)  
(1.52)  
(3.1)  
1
2
3
4
(0.305)  
(0.610)  
(0.914)  
(1.22)  
**Ceiling Firestop/spacer  
(SV4.5BF)  
10  
15  
20  
(4.65)  
(6.2)  
H
H +H1= 20 feet (6.2 m) Max.  
V+V1+H+H1 = 40 feet (12.4 m) Max.  
V
*Wall Firestop/spacer  
(SV4.5HF)  
1
V
Refer to Table 3 on page 16 for an aid in venting component selection for a  
particularrangeofexteriorwallthicknesseswhenusingthesquare(SV4.5HTS),  
small square (SV4.5HTSS) or the round (SV4.5HTR) termination .  
Short Square Termination (SV4.5HTSS) shown;  
Long Square Termination (SV4.5HTSSL) may also be used;  
Square Termination (SV4.5HTS) may also be used  
Round Termination (SV4.5HTR) may also be used.  
*Wall Firestop/spacer  
(SV4.5HF)  
Figure 41 - Top Vent - THREE 90 DEGREE ELBOWS  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VERTICAL OR HORIZONTAL VENTING USING  
SECURE FLEX KITS AND COMPONENTS  
FLEX VENT  
NOTE: OUTER PIPE IS PULLED AWAY TO  
SHOW THE DETAIL OF THE INNER PIPE  
Secure Flex venting kits and components may  
be used in any venting application where rigid  
Secure Vent (SV4.5) direct vent components  
can be used. All restrictions, clearances and  
allowances that pertain to the rigid piping apply  
to the flexible venting. Secure Flex kits may  
notbemodified;also,undernocircumstances  
may separate sections of flex pipe be joined  
together. Secure Flex kits may be added to the  
end of a vent run made up of rigid Secure Vent  
(SV4.5) vent sections provided that doing so  
does not violate any of the venting length,  
height, routing, horizontal to vertical ratio re-  
quirements or clearance considerations de-  
tailed in this manual.  
SECURING SCREW  
(3 PLACES EQUIDISTANT  
JUST BELOW GEAR CLAMP)  
Apply ONLY MIL-PAC BLACK HIGH  
TEMPERATURE SEALANT (Catalog No.  
10K81) to the outside surface of both  
collars of the adapter (be especially  
careful to fill the grooves of the outer  
collar to be covered by the flexible  
pipe) and slide flexible pipe over  
inner and outer adapter collars.  
GEAR  
CLAMPS  
1³⁄₄ in. (44 mm)  
Flexible Pipe and  
Adapter Outer  
1³⁄₄ in. (44 mm)  
Flexible Pipe and  
Adapter Inner  
Collar Overlap  
Collar Overlap  
SecureFlexkitscomewithanincludedadapter  
that can be fitted to the appliance collar or the  
inclined channel end of the last Secure Vent  
(SV4.5) vent section in a rigid system in the  
exact same fashion as any other Secure Vent  
section. Align the dimpled end of the adapter  
over the previously installed section or appli-  
ance collar, adjusting the radial alignment until  
the four locking dimples of the adapter are  
aligned with the inlets of the four incline chan-  
nels of the last vent section or collar. Push on  
the adapter until it fully engages, then twist the  
adapter clockwise running the dimples down  
and along the incline channels until they seat at  
the end of the channels.  
Adapter  
(SV4.5RF)  
SECURING SCREW  
(3 PLACES EQUIDISTANT  
JUST BELOW GEAR CLAMP)  
Attach Adapter to Appliance  
Collar, or Secure Vent Sections  
Figure 42  
B. Install the Outer Flex Pipe -  
1. Install the large gear clamp loosely around  
the outer flexible vent pipe, push it back out of  
the way.  
D. Install Firestop/Spacers at ceilings and walls -  
When Secure Flex penetrates a wall or ceiling,  
a firestop/spacer is required: use the SF4.5 BF  
firestop/spacer for ceilings and the SF4.5 HF  
firestop/spacer for walls. See the appropriate  
sections and figures shown throughout the  
ventingsectionfortheirinstallationrequirments.  
2. ApplyabeadofMill-PacBlack(700°F)high  
temperature sealant - Catalog No. 10K81) to  
the outer adapter collar; to the grooves of the  
collar which extend approximately 1 inch from  
the end and to the flat surface, approximately  
1³⁄₈ inches from the end.  
SF-12 or SF-18 Flexible Vent Section  
Attach the flexible vent to the adapter as  
follows (see also Figure 42):  
3. Pull and extend the outer flexible vent pipe.  
A. Install the Inner Flex Pipe -  
1. Install the small gear clamp loosely around  
the inner flexible vent pipe, push it back out of  
the way.  
4. Slide the outer flex pipe over the adapter  
collar. Ensure the flexible vent pipe completely  
engages the adapter collar to a distance of 1³⁄₄  
inches from the end, and that it is free from  
damage or tears.  
5" (127 mm)  
Radius Minimum  
2. Apply a bead of Mill-Pac Black (700°F)  
high temperature sealant - Catalog No.  
10K81) to the inner adapter collar, approxi-  
mately ¹⁄₂ inch from the end.  
Figure 43  
5. Slide the gear clamp down and tighten it  
fully to secure the flexible vent to the adapter  
outer collar approximately ³⁄₄ inch from the  
end of the flex.  
E. Attach Flex Vent to Termination -  
Secure Flex components can be purchased  
separately and attached to bulk lengths of  
Secure Flex flexible tubing cut to size at the  
job site. Secure the flexible vent to the Secure  
Flex terminations in the same manner (see  
Figure 42) as it was attached to the adapter.  
3. Pull and extend the inner flexible vent pipe.  
4. Slide the inner flex pipe over the adapter  
collar. Ensure the flexible vent pipe completely  
engages the adapter collar to a distance of 1³⁄₄  
inches from the end, and that it is free from  
damage or tears.  
6. Install three screws 120 degrees apart  
through the flexible vent pipe and into the  
adapter collar just below the gear clamp to  
provide additional security to the connection.  
Note: Secure Flex vent must be attached to  
Secure Flex terminations only. DO NOT  
substitute Secure Vent terminations or the  
Secure Vent adapter for Secure Flex compo-  
nents. The collars of Secure Flex termina-  
tions and adapters have a different circum-  
ference than that used with the Secure Vent  
pipe. Additionally, Secure Flex components  
have an extended length center tube for use  
in attaching the flexible vent.  
C. Route Flex Vent -  
5. Slide the gear clamp down and tighten it fully to  
secure the flexible vent to the adapter inner collar  
approximately ³⁄₄ inch from the end of the flex.  
Ensure that the flex vent is properly routed to  
provide the required clearance. Do Not allow  
the flexible vent to bend in a radius tighter than  
5" (127 mm). Refer to Figure 43. Support  
horizontal sections of flex with metal straps at  
2 foot (0.61 m) intervals.  
6. Install three screws 120 degrees apart  
through the flexible vent pipe and into the  
adapter collar just below the gear clamp to  
provide additional security to the connection.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: The supplied 15 feet of 2 conductor wire  
has one end of each conductor connected to  
the gas valve circuit and the other end of each  
conductor placed loose inside the bottom  
compartment.  
4. Connect the ground supply wire to the  
outlet's green ground screw.  
Step 4. FIELD WIRING  
The gas valve is set in place and pre-wired at  
the factory on both models.  
5. Reinstall the outlet box.  
6. Insert the blower plug into the top outlet.  
A. SIT and Honeywell Millivolt Wiring  
(See Figure 44 ) –  
B. Electronic Wiring (See Figure 45 ) –  
(The bottom outlet is unused on millivolt units,  
while the burner control circuit plugs into the  
bottom outlet on electronic units.)  
1. Select any of the following optional con-  
trols: appliance-mounted (rocker switch) or  
wall-mounted switch, thermostat, oroneofthe  
optional remote control kits. If appliance-  
mountedON/OFFcontrolisselectedmountitin  
the gas valve mounting bracket.  
Note: The electronic appliance must be con-  
nected to the main power supply.  
IMPORTANT: Ground lead must be con-  
nected to the green screw located on the  
outlet box. See Figure 45. Failure to do  
so will result in a potential safety hazard.  
The appliance must be electrically  
grounded in accordance with local codes  
or, in the absence of local codes, the  
National Electrical Code, ANSI/NFPA 70-  
(latest edition). (In Canada, the current  
CSA C22-1 Canadian Electrical Code.)  
1. Route a 3-wire 120Vac 60Hz 1ph power  
supply to the appliance junction box.  
2. Removetheoutletboxfromthejunctionbox  
by removing two screws .  
2. Ifwall-mountedON/OFFcontrolorthermo-  
statisselectedmountitinaconvenientlocation  
on a wall near the fireplace.  
3. Connect the black power supply wire to the  
lower outlet's red pigtail lead and the white  
power supply wire to the common terminal of  
the outlet as shown in Figure 46.  
3. Wire the control switch within the millivolt  
control circuit using the 15 feet of 2 conductor  
wire supplied with the unit. Caution: do not  
connect the optional wall switch to a 120V  
power supply.  
4. Connect the ground supply wire to the  
outlet's green ground screw.  
Electronic Wiring Diagram (Honeywell)  
Showing the Blower Wiring for the Optional  
FBK-100 and FBK-200 Kits  
1. If any of the original wire as supplied must be replaced,  
1. it must be replaced with Type AWM 105°C 18 GA. wire.  
2. 120V, 60Hz Less than 3 amps.  
5. Locate and install a low voltage (24V) wall  
switch or thermostat (not supplied) in the  
desired location.  
4. Alternatively, the appliance may be operated  
without the use of the controls indicated in step  
1, solely by manipulating the gas valve control  
knob. In order to use this method, twist the free  
ends of the two conductor wire (located inside  
thebottomcompartmentof theunit)togetheras  
shown in Figure 44.  
**Leave the ON/OFF switch, which is integral  
**ON/OFF Switch (Integral  
with the gas valve, in the ON position.  
with Gas Valve)  
6. Connect the low voltage wire to this switch  
or thermostat.  
*OPTIONAL  
ACCESSORY  
SWITCH  
Gas Valve  
PILOT  
ASSEMBLY  
BK  
W
G
BK  
7. Insert the control circuit plug into the lower  
outlet box.  
120  
VAC.  
R
Note: The supplied 15 feet of 2 conductor wire  
has one end of each conductor connected to the  
gas valve circuit and the other end of each  
conductor placed loose inside the bottom com-  
partment of the unit.  
BL  
Outlet Box  
Green Ground  
Screw  
8. After wiring is complete, replace the outlet box.  
OPT  
BLOWER  
Black  
G
pigtail  
Break Off  
Tab  
Note: The gas valve-mounted ON/OFF switch  
isshowninFigure45. Itisintegralwiththegas  
valve.  
Red  
pigtail  
White Wire  
to Opposite  
Side  
Junction Box  
W
Transf.  
B
120 V.  
Millivolt Wiring Diagram  
G
Step 5. WIRING - OPTIONAL FORCED AIR  
BLOWER KIT (See Figure 45 )  
Hot side of Outlet  
BL  
If any of the original wire as supplied must be replaced,  
it must be replaced with Type AWM105°C 18 GA. wire.  
24 V  
R
An electrical outlet box is provided for the instal-  
lation of the FBK-100, FBK-200 forced air blower  
kits (optional). Electrical power must be pro-  
vided to this box to operate these blowers.  
W
BK  
OPTIONAL APPLIANCE-MOUNTED ON/OFF SWITCH  
OR OPTIONAL WALL SWITCH  
OR OPTIONAL THERMOSTAT  
OR OPTIONAL REMOTE RECEIVER  
1. Route a 3-wire, 120Vac 60Hz 1ph power line  
with control switch to the lower right rear  
corner of the appliance.  
*Blower speed control switch is provided in FBK200 blower kit.  
Thermopile  
Factory Wired  
Field Wired  
Schematic Representation Only  
A
B
2. Remove the outlet box by removing two  
screws.  
Figure 45  
*OPTIONAL ON/OFF SWITCH,  
WALL SWITCH, THERMOSTAT  
OR REMOTE CONTROL RECEIVER  
3. Connect the supply wires to the blower  
controlswitch.Thenconnectthewiresfromthe  
blower control switch to the outlet box' pigtail  
leads as shown in Figure 45.  
*TWIST WIRES AAND BTOGETHER TO OPERATE UNIT  
SOLELY BY MANIPULATING THE GAS VALVE CONTROL KNOB;  
OR CONNECT WIRES TO OPTIONAL ON/OFF SWITCH OR WALL  
SWITCH OR THERMOSTAT TO OPERATE UNIT.  
Figure 44  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FBK-250 Blower Kit (See Figure 46)  
Turn on gas supply and test for gas leaks using  
a soapy water solution. Never use an open  
flame to check for leaks.  
Step 6. CONNECTING GAS LINE  
An electrical outlet box is provided for the instal-  
lation of the FBK-250 forced air blower kit.  
Electrical power must be provided to this box to  
operate these blowers. Install the blower kit  
according to the installation instructions pro-  
vided with the kit.  
Make gas line connections. All codes re-  
quire a shut-off valve mounted in the supply  
line. Figure 47 illustrates two methods for  
connecting the gas supply. The flex-line  
method is acceptable in the U.S., however,  
Canadian requirements vary depending on  
locality. Installation must be in compliance  
with local codes.  
Open the lower panel or louver assembly by  
gently depressing the outer top corners of the  
panel until the catches popthe panel free,  
allowing it to swing out and down to open.  
1. Routea3-wire, 120Vac 60Hz 1ph powerline  
to the lower right rear corner of the appliance.  
Control  
Valve  
2. Remove the outlet box by removing two  
screws.  
These appliances can be equipped with a gas  
flex line for use (where permitted) in connect-  
ing the unit to the gas line. The gas flex line  
(not provided) is to aid in attaching the direct  
vent appliance to the gas supply. The gas flex  
line can only be used where local codes per-  
mit. See Figure 47 for flex line description.  
The flex line is rated for both natural and  
propane gas. The optional gas flex line is  
equipped with a manual shut off valve.  
Lower Control  
Compartment  
Door  
3. Connect the black supply wire to both of the  
outlet box' pigtail leads and the white supply  
wire to the common terminal of the outlet box  
as shown in Figure 46.  
Opening Control Compartment Door  
Figure 48  
4. Connect the ground supply wire to the  
outlet's green ground screw.  
A. Mix a 50% dish soap, 50% water solution.  
5. Reinstall the outlet box.  
B. Light the appliance (refer to the lighting  
instructionsprovidedintheHomeowner'sCare  
and Operation Instructions).  
Open the control compartment access panel  
(Figure 48) by actuating the spring-loaded  
magnetic catches securing the panel, gently  
depressing the outer top corners of the panel  
until the catches "pop" the panel free, allowing  
it to swing out and down to open.  
6. Insert the kit-provided module plug into the  
top outlet.  
(The bottom outlet is unused on millivolt  
units, while the burner control circuit plugs  
into the bottom outlet on electronic units.)  
C. Brush all joints and connections with the  
soapy water solution to check for leaks. If  
bubbles are formed, or gas odor is detected,  
turn the gas control knob to the OFFposition.  
Either tighten or refasten the leaking connec-  
tion and retest as described above.  
The millivolt control valve has a ³⁄₈"  
(10 mm) NPT thread inlet port.  
7. Insert the blower plug into the module's  
receptacle.  
Secure all joints tightly using appropriate  
tools and sealing compounds (ensure pro-  
pane resistant compounds are used in pro-  
pane applications).  
Electronic Wiring Diagram (Honeywell)  
Showing the Blower Wiring for the Optional  
FBK-250 Kits  
D. When the gas lines are tested and leak free,  
observe the individual tongues of flame on the  
burner. Make sure all ports are open and pro-  
ducing flame evenly across the burner. If any  
ports are blocked, or partially blocked, clean  
out the ports.  
1. If any of the original wire as supplied must be replaced,  
1. it must be replaced with Type AWM 105°C 18 GA. wire.  
2. 120V, 60Hz Less than 3 amps.  
*Leave the ON/OFF switch, which is integral  
with the gas valve, in the ON position.  
*ON/OFF Switch (Integral  
with Gas Valve)  
Outlet Box Green  
Ground Screw  
Gas Valve  
PILOT  
ASSEMBLY  
G
120  
VAC.  
BK  
W
BK  
Optional Gas Flex Line Connector  
Optional FBK-250  
Module  
R
³ꢀ₈" NPT x ³ꢀ₈  
Flare Fitting  
BL  
¹ꢀ₂" x ³ꢀ₈" Flare  
Shut-Off Valve  
Gas  
Valve  
OPT  
BLOWER  
G
White Wire  
To Opposite  
Side  
³ꢀ₈" Flex Tubing  
W
B
Transf.  
120 V.  
G
Gas  
Stub  
Hot side of Outlet  
¹ꢀ₂ x ³ꢀ₈ "  
Reducer  
24 V  
BL  
³ꢀ₈" Nipple  
³ꢀ₈" Union  
³ꢀ₈" Close Nipple  
R
WH  
BK  
OPTIONAL APPLIANCE-MOUNTED ON/OFF SWITCH  
OR OPTIONAL WALL SWITCH  
³ꢀ₈" Shut-Off Valve  
OR OPTIONAL THERMOSTAT  
OR OPTIONAL REMOTE RECEIVER  
Factory Wired  
Field Wired  
Figure 47 - GAS CONNECTION  
Schematic Representation Only  
Figure 46  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Replace logs if removed for pilot inspection.  
Step7. INSTALLINGLOGS ANDGLOWING  
EMBERS  
Step 9. INSTALLING THE GLASS DOOR  
To light the burner; turn ONthe remote wall  
switch and rotate the gas valve control knob  
counterclockwise to the ONposition.  
Retrieve the glass door. Visually inspect the  
gasket on the backside of the frame. Gasket  
surface must be clean, free of irregularities and  
seated firmly.  
The logs are packaged in a carton which is  
shrink-wrapped to the front glass enclosure  
panel. The glowing embers are packaged sepa-  
rately inaplasticbaglocatedinthecontrolarea  
of the fireplace.  
Hood Ignitor Rod  
SIT MILLIVOLT  
Thermocouple  
Positionthedoorinfrontofthefireboxopening  
with the bottom of the door held away from the  
fireplace (Figure 53 ). Hook the top flange of  
thedoorframeoverthetopofthefireboxframe.  
Refer to the homeowner's care and operation  
instructions for detailed placement instruc-  
tions for the logs and glowing embers.  
Let the bottom of the door frame swing gently  
in towards the fireplace ensuring that the gas-  
ket seats evenly as the door frame draws shut.  
Fasten the two latches located underneath the  
firebox floor to the door's vee-flange. Close  
both the latches securely.  
³⁄₈" Min  
(9 mm)  
Step 8. CHECKING APPLIANCE OPERATION  
Pilot  
Withgaslineinstalledruninitialsystemcheckout  
before closing up the front of the unit. Follow the  
pilot lighting instructions provided in the  
Homeowner's Care and Operation Instructions.  
For piezo ignitor location see Figure 49 (SIT and  
Honeywell millivolt appliances only).  
Nozzels  
Thermopile  
Figure 50  
Top Flange  
Door Frame  
HONEYWELL MILLIVOLT  
Thermocouple  
Note: Instructions are also found on the litera-  
ture tag attached to the gas valve train.  
Ignitor Rod  
¹⁄₈" Min  
(3 mm)  
Hood  
Glass Door  
Whenfirstlightingtheappliance, itwilltakeafew  
minutes for the line to purge itself of air. Once  
purgingiscomplete,thepilotandburnerwilllight  
andoperateasindicatedintheinstructionmanual.  
Subsequent lightings of the appliance will not  
require such purging. Inspect the pilot flame  
(remove logs, if necessary, handling carefully).  
Latch  
³⁄₈" Min  
(9 mm)  
Pilot  
Nozzels  
Thermopile  
Figure 51  
Electronic Appliance Checkout  
Bottom Vee-flange  
Door Frame  
Latch  
SIT Gas Valve  
To light the burner, turn ONthe optional  
remote wall switch and turn the gas control  
switch to the ONposition. Ensure the ignitor  
lights the pilot. The pilot flame should engulf  
the flame rod as shown in Figure 52.  
Firebox Floor  
Honeywell  
Gas Valve  
Figure 53 - INSTALLING THE GLASS DOOR  
Piezo  
Ignitor  
WARNING: HANDLE THIS GLASS WITH  
EXTREME CARE! THE GLASS PANEL IS  
SUSCEPTIBLE TO DAMAGE DO NOT  
SCRATCH WHILE HANDLING OR WHILE  
RE-INSTALLINGTHEGLASSDOORFRAME.  
ELECTRONIC  
Sit and Honeywell Millivolt Gas Valve  
Showing Piezo Ignitor Location (Each Unit is  
Equipped with Only One of these Gas Valves)  
3/8 To 1/2 Inch  
(9 mm to 13 mm)  
Proper Flame  
Adjustment  
Figure 49  
Pilot  
Nozzle  
Ground  
Electrode  
SIT and Honeywell Millivolt Appliance Checkout  
WARNING: NEVER OPERATE THE APPLI-  
ANCE WITHOUT THE FRONT GLASS EN-  
CLOSURE PANEL IN PLACE AND SECURE.  
The pilot flame should be steady, not lifting or  
floating. Flame should be blue in color with  
traces of orange at the outer edge. The top ³⁄₈"  
(10 mm) at the pilot generator (thermopile)  
and the top ¹⁄₈" min (tip) of the quick drop out  
thermocouple should be engulfed in the pilot  
flame. The flame should project 1" (25 mm)  
beyond the hood at all three ports (Figure 50  
- SIT, Figure 51 - Honeywell )  
Flame Rod  
Hot Surface  
Igniter  
Figure 52  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Allow the burner to operate for at least 15 min-  
utes. Observe the flame continuously. If it ap-  
pears weak or sooty as previously described,  
adjusttheairshutterbypushingorpullingonthe  
adjustment rod until the flame appearance is as  
desired.  
Step 10. BURNER ADJUSTMENTS  
Flame Appearance and Sooting  
Step 11. HOOD INSTALLATION  
All of these appliances must have hoods  
installed prior to operating.  
Proper flame appearance is a matter of taste.  
Generally, mostpeoplepreferthewarmglowof  
a yellow to orange flame. Appliances operated  
with air shutter openings that are too large will  
exhibit flames that are blue and transparent.  
These weak, blue and transparent flames are  
termed anemic. If the air shutter opening is too  
small sooting may develop.  
On all clean face units, slide the hood into the slots  
on the lower edge of the radiant panel (Figure 55 ).  
Theadjustmentrodandassociatedadjustableair  
shutter is patented technology. Flame adjust-  
ments can be made quickly and accurately to  
taste without the need of disassembling the  
appliance and waiting for 30 minutes after each  
adjustment.  
On louvered face units, slide the hood into the slots  
on the lower edge of the cabinet top (Figure 56 ).  
FINISHING REQUIREMENTS  
Wall Details  
Sooting is indicated by black puffs developing  
at the tips of very long orange flames. Sooting  
results in black deposits forming on the logs,  
appliance inside surfaces and on exterior sur-  
faces adjacent to the vent termination. Sooting  
is caused by incomplete combustion in the  
flames and lack of combustion air entering the  
air shutter opening. To achieve a warm yellow  
to orange flame with an orange body that does  
not soot, the shutter opening must be adjusted  
between these two extremes.  
Complete finished interior wall. To install the  
appliance facing flush with the finished wall,  
position framework to accommodate the thick-  
ness of the finished wall (Figures 55 and 56 ).  
Note:Iftheflamestillappearsanemicwiththe  
air shutter closed all the way against the stop  
(usually a result of lengthy vertical runs), turn  
the appliance off, turn the gas supply off, wait  
for the parts to cool, remove the glass door and  
logs to access the air shutter. The shutter is  
prevented from actually closing all the way by  
an adjustment set screw (see Figure 54). Re-  
move this screw using a ¹⁄₄ inch nut driver.  
Reinstall the logs and glass door, turn the gas  
backonandthenrestarttheappliance.After30  
minutes, reobserve the flame. Adjust the air  
shutter as previously described.  
Combustible  
Finished Wall  
This Area Must Remain  
Clear of Combustible  
Materials  
Materials  
1" Min  
(25 mm)  
Combustible  
material  
No smokeorsootshouldbepresent. Reposition  
the logs if flames impinge on any of them.  
If the logs are properly positioned and sooting  
conditions exist, the air shutter opening on the  
main burner tube should be adjusted. Normally,  
the more offsets in the vent system, the greater  
the need for the air shutter to be opened further.  
Spacer  
may touch the  
appliance top.  
When satisfied that the appliance operates  
properly, proceed to finish the installation.  
Leave the control knob in the ON position  
and the remote switch OFF. Close the lower  
control compartment door.  
Combustible  
materials not  
allowed below  
this point on  
the face of the  
appliance.  
Top of Appliance  
Radiant panel  
Top of Door Frame  
Burner Adjustment  
Hood must be installed as shown.  
Clean Face Models  
WARNING: AIR SHUTTER ADJUST-  
MENT SHOULD ONLY BE PERFORMED  
BY A QUALIFIED PROFESSIONAL  
SERVICE TECHNICIAN.  
Adjusting Set Screw  
Adjustment Rod Up  
(Fully Open Position)  
Figure 55  
Burner Tube  
Air Shutter  
Combustible  
IMPORTANT: ENSURE THAT THE  
FRONT GLASS PANEL IS IN PLACE  
AND SEALED DURING ADJUSTMENT.  
Finished Wall  
Materials  
This Area Must Remain  
Clear of Combustible  
Materials  
Adjustment Rod Down  
(minimum air  
Combustible  
1" Min  
material  
(25 mm)  
opening position)  
may touch the  
appliance top.  
CAUTION: THE AIR SHUTTER DOOR AND  
NEARBYAPPLIANCESURFACESAREHOT.  
EXERCISE CAUTION TO AVOID INJURY  
WHILEADJUSTINGFLAMEAPPEARANCE.  
Spacer  
FACTORY AIR  
SHUTTER SETTING  
Natural Gas Propane Gas  
Combustible  
materials not  
allowed below  
this point on  
the face of the  
appliance.  
Models  
inches  
(mm)  
1/32  
inches  
(mm)  
5/16  
To adjust the flame, move the adjustment rod  
(located in the lower control area) up or down  
to increase or reduce the air shutter opening,  
respectively. Initially, always position the air  
shuttertothefactorysetting(theminimumair  
opening position) as shown in Figure 54. This  
can be done by pulling the adjustment rod all  
the way down.  
Top of Appliance  
Louvers  
DT-400  
DR-400  
(0.8)  
(8.0)  
Top of Door Frame  
Figure 54  
Hood must be installed as shown.  
Louver Face Models  
Figure 56  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A hearth extension is not required with this appliance. If a hearth extension is used, do not block the lower control compartment door. Any hearth  
extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.  
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet  
metal). Never allow combustible materials to be positioned in front of or overlapping the appliance front face. See Figures 55 and 56 on page 23.  
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they  
must not cover any portion of the glass or louvers; they may cover any portion of the top radiant panel or the air gaps surrounding the top radiant  
panel up to the installed hood.  
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. (See Figure 58 ). Mantels constructed of non-  
combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the hood.  
Combustible materials may project beyond the  
MANTEL CLEARANCES  
Inches (mm)  
sides of the fireplace opening as long as they  
are kept within the shaded areas illustrated in  
Figure 57.  
12 (305) MANTEL  
10 (254) MANTEL  
8 (203) MANTEL  
Combustible Materials  
Allowed In Shaded  
Top View Of  
Area Safe Zone”  
Fireplace  
6 (152) MANTEL  
4 (102) MANTEL  
12"  
14  
(356)  
12  
(305)  
10  
(254)  
TOP OF  
APPLIANCE  
5"  
45°  
8
2 (51) MANTEL  
6
(203)  
17"  
(152)  
4
(102)  
Min. Distance  
8 ¹⁄₄"  
To Protected  
Side Wall  
Side  
Wall  
NOTE - Hood shown as positioned  
in louvered front model. The hood  
position in the flush faced front model  
is lower than shown.  
Side  
Wall  
Min. Distance To  
14"  
Unprotected Side Wall  
Figure 57  
COLD CLIMATE INSULATION  
Figure 58  
Ifyouliveinacoldclimate, sealallcracksaroundyourappliancewithnoncombustiblematerialandwherevercoldaircouldentertheroom. Itisespecially  
important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level.  
INSTALLATION ACCESSORIES  
Listed Secure VentComponents  
Listed Secure FlexComponents  
Cat.  
No.  
86L95  
Cat.  
No.  
Model  
No.  
Model No. Description  
Description  
These termination kits include firestop/spacer, gear clamps and flex adapter.  
SV4.5HTR Horizontal Round Termination  
with Firestop/Spacer (96K80)  
and Adapter (74L61)  
86L94 SF-HTR  
Horizontal Round Termination  
without Flex  
77L82 SFKIT12R Flex Round Term. with 12 in.  
(305 mm) of *compressed Flex  
98L27  
SV4.5HTSSL Horizontal Long Small Square  
Termination with  
77L83 SFKIT18R Flex Round Term. with 18 in.  
(457 mm) of *compressed Flex  
Firestop/Spacer (96K80) and  
12 in. (305 mm) vent section  
(77L71)  
77L84 SFKIT24R Flex Round Term. with 24 in.  
(610 mm) of *compressed Flex  
77L85 SFKIT36R Flex Round Term. with 36 in.  
(914 mm) *compressed Flex  
86L97  
94L10  
H2152  
SV4.5HTS Horizontal Square Termination  
with Firestop/Spacer (96K80)  
and Adapter (74L61)  
77L86 SFKIT48R Flex Round Term. with 48 in.  
(1219 mm) of *compressed Flex  
87L01 SFHRK  
Snorkel Riser Kit with Flex  
Adapter, a section of Flex, and  
Gear Clamps  
SV4.5HTSS Horizontal Short Square  
Termination with  
Firestop/Spacer (96K80) and  
Adapter (74L61)  
SV4.5CGV-1 Vertical Termination  
19M40 SF4.5HF  
19M41 SF4.5BF  
Firestop/Spacer-  
Horizontal (3-1-1 spacing)  
Firestop/Spacer-  
Vertical (1-1-1 spacing)  
*All compressed flex vents can be expanded up to two times.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION ACCESSORIES (Continued)  
Listed Secure VentComponents  
Listed Secure FlexComponents  
Cat.  
No.  
Cat.  
Model No. Description  
Model No.  
SV4.5L6  
Description  
No.  
These termination kits include firestop/spacer, gear clamps and flex adapter.  
77L70  
6 inch (152 mm) Vent Section  
12 inch (305 mm) Vent Section  
24 inch (610 mm) Vent Section  
36 inch (914 mm) Vent Section  
48 inch (1219 mm) Vent Section  
94L09 SF-HTSS  
Horizontal Short Small Square  
Termination without Flex  
SV4.5L12  
SV4.5L24  
SV4.5L36  
SV4.5L48  
SV4.5LA Telescopic Section  
SV4.5E45 45 Degree Elbow  
77L71  
77L72  
77L73  
77L74  
77L75  
77L76  
94L04 SFKIT12S- Flex Short Small Square Term.  
S
with 12 in. (305 mm of  
*compressed Flex  
94L05 SFKIT18S- Flex Short Small Square Term.  
S
with 18 in. (457 mm) of  
*compressed Flex  
94L06 SFKIT24S- Flex Short Small Square Term.  
S
with 24 in. (610 mm) of  
*compressed Flex  
77L77  
SV4.5E90 90 Degree Elbow  
94L07 SFKIT36S- Flex Short Small Square Term.  
S
with 36 in. (914 mm) of  
*compressed Flex  
The following flashings come packaged with a storm collar.  
94L08 SFKIT48S- Flex Short Small Square Term.  
SV4.5F-B  
91L01  
91L02  
91L03  
77L81  
Flat Roof Flashing  
SV4.5FA-B 1/12 to 7/12 Adjust. Flashing  
SV4.5FB-B  
S
with 48 in. (1219 mm ) of  
*compressed Flex  
7/12 to 12/12 Adjust. Flashing  
These termination kits include firestop/spacer, gear clamps and flex adapter.  
SV4.5SC6 Storm Collars (6 collars/box)  
86L96 SF-HTS  
Horizontal Square Termination  
without Flex  
96K80  
96K87  
96K93  
SV4.5HF Firestop/Spacer -  
Horizontal (3-1-1 spacing)  
SV4.5BF Firestop/Spacer -  
Vertical (1-1-1 spacing)  
77L87 SFKIT12S  
Flex Square Term. with 12 in.  
(305 mm of *compressed Flex  
77L88 SFKIT18S  
77L89 SFKIT24S  
77L90 SFKIT36S  
77L91 SFKIT48S  
Flex Square Term. with 18 in.  
(457 mm) of *compressed  
Flex  
Flex Square Term. with 24 in.  
(610 mm) of *compressed  
Flex  
Flex Square Term. with 36 in.  
(914 mm) of *compressed  
Flex  
Flex Square Term. with 48 in.  
(1219 mm ) of *compressed  
Flex  
Vertical Termin. for Flex (flat  
to 6/12) with Flex Adapter,  
section of rigid vent, roof  
support collar assembly, roof  
flashing and storm collar.  
SV4.5SU Support Strap  
96K94  
SV4.5RSA Attic Insulation Shield  
96K92  
97K00  
SV4.5SP Support Plate  
SV4.5HGR Heat Guard Round  
56L74 SFVT30  
87L02  
SV4.5HGS Heat Guard Square  
56L75 SFVT45  
Vertical Termin. for Flex (6/12  
to 12/12) with Flex Adapter  
section of rigid vent, roof  
support collar assembly, roof  
flashing and storm collar.  
17M52  
17M53  
96K98  
SV4.5 Heat Guard Square (1 - Pack)  
HGS-1  
SV4.5 Heat Guard Square (12 - Pack)  
HGS-12  
60L10 SF-18  
98K03 SF-12  
10K81 SFMP  
18 ft. (5.49 m) *compressed  
SV4.5HDR Heat Deflector for Round  
Termination  
Flex  
12 ft.(3.66 m) *compressed  
86L98  
SV4.5RFF Adapter - Crimped Fireplace  
Collar to Secure Vent  
Flex  
t
n
a
Mil Pac Black Hi-Temperature  
Sealant  
l
a
e
S
99L03 SV4.5HRK36 Horizontal Riser Kit 36"  
99L02 SV4.5HRK14 Horizontal Riser Kit 14"  
88J01 SF-GC4  
83J00 SF-GC7  
87L00 SF4.5RF  
Gear Clamp 4.5in. (114 mm)  
for Flex  
Gear Clamp 7.5 in. (190.5  
mm) for Flex  
Flex Adapter  
*All compressed flex vents can be expanded up to two times.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS CONVERSION KITS  
WARNING: THIS CONVERSION KIT SHALL BE  
INSTALLED BY A QUALIFIED SERVICE AGENCY IN  
ACCORDANCE WITH THE MANUFACTURER'S IN-  
STRUCTIONS AND ALL APPLICABLE CODES AND  
REQUIREMENTS OF THE AUTHORIZED AGENCY  
HAVING JURISDICTION. IF THE INFORMATION IN  
THESE INSTRUCTIONS IS NOT FOLLOWED EX-  
ACTLY, A FIRE, EXPLOSION OR PRODUCTION OF  
CARBON MONOXIDE MAY RESULT CAUSING  
PROPERTYDAMAGE,PERSONALINJURYORLOSS  
OFLIFE. THEINSTALLATIONISNOTPROPERAND  
COMPLETE UNTIL THE OPERATION OF THE CON-  
VERTEDAPPLIANCEISCHECKEDASSPECIFIEDIN  
THEOWNERINSTRUCTIONSSUPPLIEDWITHTHE  
KIT.THEQUALIFIEDSERVICEAGENCYPERFORM-  
ING THIS INSTALLATION ASSUMES RESPONSI-  
BILITY FOR THIS CONVERSION.  
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION  
SERAINSTALLÉPARUNEAGENCEQUALIFIÉEDESERVICE  
CONFORMÉMENT AUX INSTRUCTIONS DU FABRICANT ET  
TOUTES EXIGENCES ET CODES APPLICABLES DE  
L'AUTORISÉSAVOIRLAJURIDICTION. SIL'INFORMATION  
DANS CETTE INSTRUCTION N'EST PAS SUIVIE  
EXACTEMENT, UN FEU, EXPLOSION OU PRODUCTION DE  
PROTOXYDEDECARBONEPEUTRÉSULTERLEDOMMAGES  
CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE  
PERSONNELLEDEVIE. L'AGENCEQUALIFIÉEDESERVICE  
EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET  
ÉQUIPMENT. L'INSTALLATION N'EST PAS PROPRE ET  
COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL  
CONVERTI EST CHÉQUE SUIVANT LES CRITÈRES ÉTABLIS  
DANS LES INSTRUCTIONS DE PROPRIÉTAIRE  
PROVISIONNÉES AVEC L'ÉQUIPEMENT.  
In Canada:  
Natural To Propane Gas Conversion Kit  
(SIT Systems)  
Models No. Unit Type  
Natural To Propane Gas Conversion Kit  
(Honeywell Systems)  
THE CONVERSION SHALL BE CARRIED OUT  
INACCORDANCEWITHTHEREQUIREMENTS  
OF THE PROVINCIAL AUTHORITIES HAVING  
JURISDICTION AND IN ACCORDANCE WITH  
THE REQUIREMENTS OF THE CAN1-B149.1  
AND .2 INSTALLATION CODE.  
Catalog No.  
H1594  
Models No. Unit Type  
Catalog No.  
26M51  
26M51  
99L90  
DT-400  
DR-400  
DT-400  
DR-400  
millivolt  
millivolt  
DT-400  
DR-400  
DT-400  
DR-400  
millivolt  
millivolt  
H1594  
electronic  
electronic  
99L90  
electronic  
electronic  
LA CONVERSION DEVRA ÊTRE EFFECTUÉE  
CONFORMÉMENT AUX RECOMMANDATIONS  
DES AUTORITÉS PROVINCIALES AYANT  
JURIDICTION ET CONFORMÉMENT AUX  
EXIGENCES DU CODE D'INSTALLATION CAN1-  
B149.1 ET.2.  
99L90  
99L90  
Propane to Natural Gas Conversion Kit  
(Honeywell Systems)  
Propane to Natural Gas Conversion Kit  
(SIT Systems)  
Model No.  
DT-400  
DR-400  
DT-400  
DR-400  
Unit Type Catalog No.  
Model No.  
DT-400  
DR-400  
DT-400  
DR-400  
Unit Type Catalog No.  
millivolt  
millivolt  
H1595  
H1595  
99L91  
99L91  
millivolt  
millivolt  
26M55  
26M55  
99L91  
99L91  
Gas conversion kits are available to adapt your  
appliance from the use of one type of gas to the  
useofanother. Thesekitscontainalltheneces-  
sary components needed to complete the task  
including labeling that must be affixed to en-  
sure safe operation.  
electronic  
electronic  
electronic  
electronic  
Step 4. Millivolt Appliances - SIT Systems  
SIT Millivolt Gas Valve  
Kit part numbers are listed here and the follow-  
ing steps detail the conversion procedure.  
a. See Figure 59 and the instructions provided  
with the kit. Using a Torx T20, remove and  
discard the three pressure regulator mounting  
screws. Removethepressureregulator,spring,  
poppet, diaphragm and bushing. Discard all  
removed components. Ensure the rubber gas-  
ket installed on the back of the replacement  
pressure regulator is properly positioned and  
install the new pressure regulator using the  
new screws supplied with the kit. Tighten  
screws to 25 In. lb. torque.  
Step 1. Turn off the gas supply to the appliance.  
Remove the front glass door/frame from the  
appliance. Access the control compartment.  
Pressure  
Regulator  
Step 2. Carefully remove the logs. Exercise  
care as not to break the logs.  
Remove  
These  
Components  
Step 3. Locate the screws securing the burner  
(tray) to the appliance. Remove the burner and  
retain the securing screws.  
Figure 59  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pilot for Honeywell Millivolt Gas Valve  
(Loosening of Hex Fitting For Orifice Strip Tab Positioning)  
Pilot for SIT Millivolt Gas Valve  
Hood Alignment  
Hood  
7/16 in. Open End Wrench  
Pilot  
Orifice  
Figure 60  
Orifice Strip Tab  
b. Attach manometer to the manifold side  
pressure test fitting and verify manifold pres-  
sure reads 3.5 inches water column (0.87 kPa)  
for natural gas, and 10.0 inches water column  
(2.49 kPa) for propane gas.  
Take Care Not to Contact the Orifice Strip Tab  
with the Hex Fitting Wrench - Distortion of the Tab  
May Render the Pilot Inoperative.  
Figure 62  
Pilot for Honeywell Millivolt Gas Valve  
c. Refer to Figure 60 and remove the pilot  
hood assembly to access the hexed pilot ori-  
fice. Remove and replace the orifice with the  
one provided with the kit.  
Orifice Strip Tab Position Identification  
For LP/Propane and Natural Gas  
LP/Propane Gas Position -  
Natural Gas Position -  
NAT shown on tab  
1/16 in. Hole, LP and  
Step 5. Millivolt Appliances -  
Honeywell Systems  
Red Color shown on tab  
L
a.Convertthegasvalveasfollows(seeFigure61):  
Removetheplasticprotectingcap. Removethe  
gas type setting screw by turning it counter-  
clockwise. Obtain the replacement gas type  
setting screw from the kit and screw it into  
place(redforpropaneandbluefornaturalgas).  
Tighten the gas type setting screw by turning it  
clockwise. Replace the plastic protecting cap.  
NAT  
Top View of Hex Fitting and Orifice Strip Tab  
Figure 63  
Pilot for Honeywell Millivolt Gas Valve Orifice Strip Tab Positioning  
Pilot Hood Position After  
Loosening Hex Fitting 1/4 Turn  
Honeywell Millivolt Gas Valve  
Orifice Strip Tab  
Push Tab to Set  
Gas Type Usage  
Adjusting Knob  
Regulator Cap  
Conversion screw  
(blue natural gas;  
red LP/propane gas)  
Note - Orifice Strip Tab May  
Be Randomly Located On Any  
Side Of The Hex Fitting  
Figure 61  
Figure 64  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b. Attach manometer to the manifold side  
pressure test fitting and verify manifold pres-  
sure reads 3.5 inches water column (0.87 kPa)  
for natural gas, and 10.0 inches water column  
(2.49 kPa) for propane gas.  
All Models  
Inlet Pressure Test Port  
Step 7. Remove the orifice from the mani-  
fold and replace it with the one provided with  
the kit. See the following table for orifice sizes  
for natural and propane models. Figure 67  
illustrates the orifice.  
Manifold  
Pressure  
Test Port  
c. Convert the pilot orifice as follows (refer to  
Figures 62, 63 and 64 ):  
Note - Use extra care not to engage the orifice  
strip with the 7/16" open end wrench (contact-  
ing the orifice strip could cause strip distortion  
rendering the pilot inoperative). Also avoid  
wrench contact to any of the other pilot parts.  
Slotted  
Cap  
Orifice size  
Model No.  
Spring  
Natural Propane  
Adjusting  
Screw  
DT-400  
0.048  
#45  
Use a 7/16" open end wrench and turn the pilot  
hex fitting counter-clockwise 1/4 turn. (refer  
to Figure 62 ).  
inch  
Figure 65  
DR-400  
Removethescrewsecuringthepilotassembly  
to its mounting bracket. Back off the flare nut  
at the end of the pilot gas line to free the pilot  
assembly from the gas line.  
Note - The orifice strip tab may be randomly  
located on any side of the hex fitting.  
d. Push the orifice strip tab all the way against  
the hex fitting to align the appropriate gas type  
orifice (refer to Figures 63 and 64). The type  
of gas for which the pilot is set, is, the gas type  
shown on the tab.  
Remove the pilot orifice and replace it with the  
one provided with the conversion kit. Reinstall  
the pilot assembly by reversing the steps de-  
tailed here.  
Figure 67  
Step 8. Reassembleallremovedcomponents  
by reversing the procedures outlined in the  
preceding steps. Use pipe joint compound or  
Teflon tape on all pipe fittings before installing  
(ensurepropaneresistantcompoundsareused  
in propane applications, do not use pipe joint  
compounds on flare fittings).  
e. Retighten, clockwise, the pilot hex fitting  
until the pilot hood aligns with the thermo-  
couple and thermopile as indicated by the  
arrows shown in Figure 62.  
When reinstalling the ignitor assembly, use  
extreme care to prevent damage and break-  
age. Do not apply any leverage to the ignitor  
assembly while restoring the retainer clip to  
its original position.  
Step 6. Electronic Appliances -  
Honeywell Systems  
Step 9. Attach the conversion label provided  
in the conversion kit to the rating plate on the  
appliance.  
Pilot  
Assembly  
Pilot  
Orifice  
See Figure 65 and the instructions provided  
with the kit. Remove the slotted cap screw, o-  
ring, pressure-regulating adjusting screw and  
spring. Retain all parts for possible later use.  
Install new components from the kit. Black cap  
and red spring for propane gas units. Silver cap  
and stainless steel spring for natural gas units.  
Before installing the cap, attach manometer to  
the manifold side pressure test fitting and adjust  
screw until pressure reads 3.5 inches water  
column (0.87 kPa) for natural gas, and 10.0  
incheswatercolumn(2.49kPa)forpropanegas.  
Ignitor  
Assembly  
Step 10. Turn on gas supply and test for gas  
leaks.  
Retaining  
Clip  
Flare Nut  
Note: If the ignitor is damaged, a replacement  
kit is available - order Catalog Number 87L54.  
See Figure 66 and replace the pilot orifice as  
follows: Remove the ignitor assembly retainer  
clip, andcarefullyremovetheignitorassembly.  
Exercise extreme care to prevent damage to  
or breakage of the ignitor assembly.  
Figure 66  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products.  
Consult your local distributor for fireplace code information.  
Printed in U.S.A. © 2002 by Lennox Hearth Products  
LHP  
P/N 700,020M REV. M 11/2004  
1110 West Taft Avenue Orange, CA 92865  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Shark Iron GI472H User Manual
Sonic Alert Clock SBP100 User Manual
Sony Bluetooth Headset DR BT160IK User Manual
Sony Cassette Player TCM 343 User Manual
Sony Portable Stereo System ZS SN10 User Manual
SPX Cooling Technologies Humidifier Evaporative Cooling User Manual
Star Micronics Printer SP320S User Manual
Sterling Compact Loader SSIL Series User Manual
Stiga Lawn Mower PRO 51 S User Manual
Sylvania Clock Radio SCR2608 User Manual