$30.00
Operation and Installation Manual
SSC Series
Central Chilling Stations
Important! Read Carefully Before Attempting to Install or Operate Equipment
Part No. A0551797
Revision: NEW
Bulletin No. SC3-630
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Considerations
Sterling central chilling stations are designed to provide safe and
reliable operation when installed and operated within design
specifications, following national and local safety codes.
To avoid possible personnel injury or equipment damage when
installing, operating, or maintaining this equipment, use good
judgment and follow these safe practices:
þ Only PROPERLY TRAINED personnel familiar with the
information within this manual should work on this equipment.
þ Follow all local SAFETY CODES.
þ Wear SAFETY GLASSES and WORK GLOVES.
þ Disconnect and/or lock out power before servicing or
maintaining the chiller.
þ Use care when LOADING, UNLOADING, RIGGING, or
MOVING this equipment.
þ Operate this equipment within design specifications.
þ OPEN, TAG, and LOCK ALL DISCONNECTS before
working on equipment. Sterling recommends following OSHA
Lock-Out/Tag-Out Standard 29 CFR 1910.147.
þ Make sure the unit is properly GROUNDED before switching
power on.
þ When welding or brazing in or around this equipment, be sure
VENTILATION is ADEQUATE. PROTECT adjacent
materials from flame or sparks by shielding with sheet metal.
An approved FIRE EXTINGUISHER should be close at hand
and ready for use if needed.
þ Do not jump or bypass any electrical safety control.
þ Do not restore power until all tools, test equipment, etc. and
chiller and related equipment have been removed.
SSC Series Central Chilling Stations
Page 3 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
1 General Information................................................. 7
1-1
1-2
1-3
1-4
1-5
Introduction......................................................................................7
Necessary Documents ....................................................................7
Models Covered ..............................................................................8
Standard Features...........................................................................8
Available Options.............................................................................9
2 Shipping Information............................................. 15
2-1
2-2
2-3
2-4
2-5
2-6
Unpacking and Inspection .............................................................15
In the Event of Shipping Damages................................................15
If the Shipment is Not Complete....................................................16
If the Shipment is Not Correct .......................................................16
Returns..........................................................................................16
Uncrating Your New Chiller ...........................................................17
3 Installation.............................................................. 19
3-1
3-2
3-3
3-4
3-5
3-6
3-7
3-8
3-9
Installation Location Considerations..............................................19
Making Electrical Connections ......................................................19
Piping Considerations....................................................................21
Making Process Water Connections..............................................21
Making Tank Piping Connections..................................................22
Water Connection Sizing Considerations ......................................23
Galvanic Corrosion Considerations...............................................23
Water Treatment Considerations...................................................23
Making Water-Cooled Condenser Connections ............................23
3-10 Installing the Remote Air-Cooled Condenser ................................24
3-11 Checking Motor Direction ..............................................................25
4 Sequence Of Operation......................................... 26
4-1
4-2
4-3
4-4
4-5
4-6
4-7
4-8
4-9
Staging ..........................................................................................27
Alarms ...........................................................................................27
Lead-Lag Compressors.................................................................27
Lead-Lag Pumps...........................................................................27
Chilled Water Circuit......................................................................28
Refrigeration Circuit.......................................................................28
Freezestat Control.........................................................................28
High Pressure Cutout ....................................................................30
Low Pressure Cutout.....................................................................30
4-10 Flow Switch ...................................................................................30
4-11 Control Nipple................................................................................31
4-12 Control Probe ................................................................................31
4-13 Chilled Water Manifold ..................................................................31
4-14 Condenser Water Manifold............................................................31
Page 4 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
5 Startup Checklists ................................................. 33
5-1
5-2
5-3
5-4
5-5
5-6
5-7
Introduction....................................................................................33
Water-Cooled SSC Series Startup Checklist.................................33
Water-Cooled SSC Series Startup ................................................35
Remote Air-Cooled SSC Series Startup Checklist ........................35
Remote Air-Cooled SSC Series Startup........................................37
Determining Flow Rate..................................................................38
Shutdown ......................................................................................38
6 Graphic Panel Devices .......................................... 41
6-1
Indicator Lights and Control Switches (MMI).................................41
7 Using the Standard Touchscreen Interface......... 43
7-1
7-2
7-3
7-4
7-5
7-6
7-7
Touchscreen Interface Introduction (MMI).....................................43
Using the SSC Series Standard Touchscreen Interface................44
Getting Started on the SSC Series Standard Touchscreen Interface45
Viewing and Operating Chiller Compressors.................................46
Viewing and Operating Chiller Pumps...........................................50
Viewing Active Alarms and Handling Alarm Conditions.................53
Viewing and Setting System Temperatures...................................55
8 Using the Advanced Touchscreen Interface ....... 57
8-1
8-2
8-3
Touchscreen Interface Introduction (MMI).....................................57
Using the SSC Series Advanced Touchscreen Interface ..............58
Getting Started on the SSC Series Advanced Touchscreen
Interface..............................................................................59
Viewing and Operating Chiller Compressors.................................60
Viewing and Operating Chiller Pumps...........................................64
Viewing Active Alarms and Handling Alarm Conditions.................68
Viewing and Setting System Temperatures...................................71
8-4
8-5
8-6
8-7
9 Routine Maintenance............................................. 73
9-1
9-2
9-3
9-4
9-5
9-6
9-7
Lubrication.....................................................................................73
Condenser Maintenance ...............................................................73
Evaporator Maintenance ...............................................................74
Pump Motor Seal...........................................................................74
Makeup Valve................................................................................74
Recommended Pump Tank Spare Parts.......................................74
Preventive Maintenance Service...................................................75
10 Troubleshooting .................................................... 77
I Index ....................................................................... 81
SSC Series Central Chilling Stations
Page 5 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Charts and Figures
1
2
3
4
5
6
7
8
Typical Two-Circuit 60-100 Ton Water Cooled Chiller
11
13
29
39
39
44
58
59
61
62
64
65
66
68
69
71
72
Typical Two-Circuit 60-100 Ton Remote Air Cooled Chiller
Freezing Protection Curve
SSC Series Standard Control Panel
SSC Series Advanced Control Panel
SSC Series Standard Control Panel
SSC Series Advanced Control Panel
Main Menu Screen (Advanced Control Panel)
9
Chiller Status Screen (Advanced Control Panel)
10
11
12
13
14
15
16
17
Chiller Configuration Screen (Advanced Control Panel)
Compressor Run Time Display Screen (Advanced Control Panel)
Pump Status Screen
Pump Enables Screen
Pump Run Time Display Screen
Alarm Condition Screen
System Status Screen
Temperature Input Display Screen
Page 6 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
1
General Information
1-1 Introduction
Sterling SSC Series central water chilling stations are available in
water-cooled and remote air-cooled designs. They differ only in
the condensing media used. The SSC Series units are configured
with two independent circuits using multiple compressors for each
circuit. This manual lists information for these units.
SSC Series chilling stations may be configured with stainless steel
pump tanks for use as reservoirs for chilled water processes. These
dual-well models hold hot and cold water before and after it is
pumped through the chiller. Tanks have recirculation pump(s) to
send return water to the chiller and process pump(s) to pump
cooled water directly to process. Standby pumps may be utilized to
distribute pump service or to allow uninterrupted chiller operation
during pump maintenance.
Properly installed, operated, and maintained SSC Series chilling
stations provide many years of reliable operation. To get the most
satisfaction from your new chiller, read and follow the
instructions in this manual.
1-2 Necessary Documents
The following documents are necessary for the operation,
installation, and maintenance of Sterling SSC Series central
chillers. Additional copies are available from Sterling.
Familiarize the appropriate personnel with these documents:
þ This manual.
þ The schematic and connection diagram in the control
enclosure.
þ Operation and installation manuals for accessories and options
selected by the customer.
þ The Customer Parts List included in the information packet.
SSC Series Central Chilling Stations
Page 7 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
1-3 Models Covered
This manual provides operation, installation, and maintenance
instructions for the SSC Series central chilling stations.
Model numbers are listed on the serial tag. A model number
followed by Q indicates a specially constructed unit, and not all
information in this manual may apply. Make sure that you know
the model number, serial number, and operating voltage of your
chiller if you contact Sterling.
1-4 Standard Features
·
Two independent refrigeration circuits
·
·
·
·
·
High-efficiency scroll compressors
Stainless steel brazed plate evaporators
Cleanable shell and tube condensers (water-cooled models)
Two-way water regulating valve (water-cooled models)
2 remote single circuit condensers with variable speed lead
fans and fan cycling (air-cooled models)
·
·
NEMA 12 electrical enclosure
Allen Bradley Micrologix 1500 PLC control with PanelView
300 Micro monochrome/key pad interface
·
·
·
High and low refrigerant pressure safeties
Touch-safe branch circuit fusing
Evaporator water piping manifold (Condenser manifold
optional)
·
·
·
·
·
·
·
HCFC-22 refrigerant
Digital low temperature freezestat
Liquid line solenoid and shut-off valves
Chilled water flow switches
Auto/Manual control mode switch for emergency operation
1 year warranty on parts and labor
3 year warranty on controller
Page 8 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
1-5 Available Options
SSC Series central chillers are available with options to tailor the
unit to your requirements. Some are factory installed; some can be
retro-fitted in the field. Consult Sterling sales for more
information. Available SSC Series options include:
·
Advanced control package including: AB SLC 5/04 PLC with
PanelView 1000 color touch screen, control of up to nine
additional chillers, cooling tower system, water treatment
system, and DH+ communication capabilities
·
·
·
General Fault audible/visual alarm with elevated light stack
Non-fused rotary thru-the-door disconnect switches
Electrical operation available in 208, 460, and 575 volts, 60
Hz; 200, 380, and 415 volts, 50 Hz
·
·
·
UL/CUL-listed electrical subpanel
Water cooled condenser manifold
Onsite startup
Standard Features on Remote Condensers
·
·
·
Direct-drive 3-phase fan motors with ball bearings and internal
overload protection
Electronic variable-speed control of lead fan and fan cycling
for constant condenser head pressure control
Fans are 30” (76 cm) in diameter and have PVC-coated steel
fan guards; 1½ hp (1.12 kW) variable-speed fans are 26” (66
cm) in diameter
·
·
·
·
·
Internal baffles between fan cells
UL listed in the United States and Canada
Patented floating tube coil to eliminate tube sheet leaks
Copper tube condenser coils have corrugated aluminum fins
Weather-proof control panel with factory-mounted door
interrupt switch
·
·
High-efficiency condenser coil, designed for optimum
performance
Aluminum housing provides corrosion protection for outdoor
applications
SSC Series Central Chilling Stations
Page 9 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Model Number Nomeclature
SSC
W
060
SSC – Scroll Compressor Central Chiller
Condenser Type
R – Remote Air Cooled
W – Water Cooled
Nominal Unit Size – Tons (kW)
030 – 30 (105.4)
040 – 40 (140.6)
050 – 50 (175.7)
060 – 60 (210.9)
070 – 70 (246.0)
080 – 80 (281.2)
090 – 90 (316.3)
100 – 100 (351.5)
Page 10 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 1
Typical Two-Circuit 60-100 Ton Water Cooled Chiller
SSCW-xxx
Model
30
40
50
60
Cooling Capacity (tons) @ 50°F (10°C) LWT •
Capacity stages (qty.)
32.4
41.4
50.2
64.8
2
4
EER (BTUH/W)
Nominal water flow (gpm)
[lpm]
Condenser connection (no manifold) Flange Conn. (in.)
Evaporator manifold connection Victaulic
Amp draw, nameplate (460/3/60 V) „
Height
15.65
78 [295.3]
97 [367.2]
(2) 2
3
14.91
99 [374.8]
124 [469.4]
(2) 2
15.35
120 [454.2]
151 [571.6]
(2) 2
15.66
156 [590.5]
194 [734.4]
(2) 2 1/2
3
Evaporator ‚
Condensers ƒ
3
70
3
88
56
111
85 [215.9]
45 [114.3]
Dimensions (in.)[cm]
Width
Depth
66 [167.6]
94 [238.8]
Shipping weight (lbs)[kg]
1,520 1,900
2,120
[961.6]
2,260
2,700
[1224.7]
2,870
[689.5]
1,610
[861.8]
2,010
Max operating weight (lbs.)[kg]
[730.3]
[911.7]
[1025.1]
[1301.8]
SSC Series Central Chilling Stations
Page 11 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
SSCW-xxx
Model
70
80
90
100
Cooling Capacity (tons) @ 50°F (10 °C) LWT •
Capacity stages (qty.)
73.1
81.4
90.3
99.2
4
EER (BTUH/W)
15.15
175 [662.4]
219
[829.0]
(2) 2 1/2
3
14.63
196 [741.9]
244
[923.6]
(2) 2 1/2
3
14.90
217 [821.4]
271
[1025.8]
2 1/2 / 3
4
15.16
238 [900.9]
298
[1128.1]
(2) 3
4
Evaporator ‚
Condensers ƒ
Nominal water flow (gpm)
[lpm]
Condenser connection (no manifold) Flange Conn. (in.)
Evaporator manifold connection Victaulic
Amp draw, nameplate (460/3/60 V) „
Height
124
138
156
174
75 [190.5]
45 [114.3]
Dimensions (in.)[cm]
Width
Depth
94 [238.8]
115 [292.1]
Shipping weight (lbs)[kg]
3,000
[1360.8]
3,200
3,300
[1496.9]
3,520
3,580
[1623.9]
3,830
3,880
[1759.9]
4,160
Max operating weight (lbs.)[kg]
[1541.5]
[1596.6]
[1737.3]
[1886.9]
•
‚
ƒ
„
Based on 50ºF (10ºC) chilled water supply temperature and 85ºF (29ºC) tower water.
Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW).
Based on availability of 85ºF (29ºC) tower water at 25 psi (172.4 kPa/1.7 bars) minimum.
Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages; multiply by 1.2 for 380/3/60 amperages; multiply by 0.8 for
575/3/60 amperages
Page 12 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 2
Typical Two-Circuit 60-100 Ton Remote Air Cooled Chiller
SSCR-xxx
40
Model
30
50
60
Cooling Capacity (tons) @ 50°F LWT •
Capacity stages (qty.)
29.8
38.4
46.2
59.6
2
4
EER (BTUH/W)
Nominal water flow (gpm)
Evaporator ‚
[lpm]
Evaporator manifold connection Victaulic
No. of condenser fans per condenser
11.36
72
[272.5]
10.84
92
[348.3]
11.29
111
[420.2]
3
11.11
143
[541.3]
3
3
3
3
2
2
3
Chiller
Condensers (per
condenser)
56
70
88
111
Amp draw, nameplate
(460/3/60 V) ƒ
3.9
7
7
10.5
Dimensions (in.) [cm] of
chiller
Height
Width
Depth
Height
Width
Depth
Chiller
85 [215.9]
60 [152.4]
83 [210.8]
45 [114.3]
50 [127.0]
42.5 [108.0]
125 [317.5] 125 [317.5]
1,530
[694.0]
770
Dimensions (in.) [cm] of
each condenser
130 [330.2]
1,340
[607.8]
180 [457.2]
2,120
[961.6]
Shipping weight (lbs) [kg]
1,730
[784.7]
790
Condensers (per
condenser)
Chiller
550
1190
[249.5]
1,350
[612.3]
[349.3]
1,550
[703.1]
845
[358.3]
1,760
[798.3]
945
[539.8]
2,150
[975.2]
Max operating weight
(lbs.) [kg]
Condensers (per
condenser)
610
1420
[276.6]
[383.3]
[428.6]
[644.1]
SSCR-xxx
Model
70
80
90
100
Cooling Capacity (tons) @ 50°F LWT •
Capacity stages (qty.)
67.5
75.4
83.5
91.6
4
EER (BTUH/W)
Nominal water flow (gpm)
Evaporator ‚
[lpm]
Evaporator manifold connection Victaulic
No. of condenser fans per condenser
10.84
162
[613.2]
3
3/4
10.64
181
[685.2]
3
10.93
200
[757.1]
4
11.19
220
[832.8]
4
4
4
4
Chiller
Condensers (per
condenser)
124
138
156
174
Amp draw, nameplate
(460/3/60 V) ƒ
10.5/14
14
14
14
Dimensions (in.) [cm] of
chiller
Height
Width
Depth
Height
Width
Depth
75 [190.5]
86 [218.4]
45 [114.3]
50 [127.0]
42.5 [108.0]
235 [596.9]
Dimensions (in.) [cm]of
each condenser
180 [457.2]
2,360
[1070.5]
1190/1580
[539.8/716.7]
2,400
[1088.6]
1420/1805
[644.1/818.7]
Shipping weight (lbs) [kg]
2,600
[1179.3]
1580
[716.7]
2,640
2,870
[1301.8]
1580/1650
[716.7/748.4]
2,910
3,170
[1437.9]
1650
[748.4]
3,220
[1460.6]
1895
[859.6]
Chiller
Condensers (per
condenser)
Max operating weight
(lbs.) [kg]
Chiller
[1197.5]
1805
[818.7]
[1320.0]
1805/1895
[818.7/859.6]
Condensers (per
condenser)
•
‚
Based on 50ºF (10ºC) chilled water supply temperature and 95ºF (35ºC) ambient air.
Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW)
ƒ
Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages; multiply by 1.2 for 380/3/60 amperages; multiply by 0.8 for
575/3/60 amperages
SSC Series Central Chilling Stations
Page 13 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
SSCR Series Remote Condenser Models
Fan(s)
Refrigeration ‚
Each
Connections
Charge
Model
Number
SSCR30
SSCR40
SSCR50
SSCR60
Dia.
in.
26
Motor
hp •
¾ hp 3 ø
Amps
460V Fans cfm ƒ
Air flow Discharge Liquid
R-22
lbs. ƒ
ODS(in.) ODS(in.)
5
1
3.9
3
2
2
3
3
4
4
4
4
4
20,500
23,200
21,900
34,800
34,800
46,400
46,400
46,400
42,400
42,400
1 /8
1 /8
5
5
30 1 ½ hp 3 ø 7.0
30 1 ½ hp 3 ø 7.0
30 1 ½ hp 3 ø 10.5
1 /8
1 /8
12
12
19
19
22
22
22
27
27
5
5
1 /8
1 /8
1
1
2 /8
2 /8
1
1
SSCR70 a 30 1 ½ hp 3 ø 10.5
2 /8
2 /8
1
1
b
30 1 ½ hp 3 ø 14.0
30 1 ½ hp 3 ø 14.0
2 /8
2 /8
1
1
SSCR80
2 /8
2 /8
1
1
SSCR90 a 30 1 ½ hp 3 ø 14.0
2 /8
2 /8
1
1
b
30 1 ½ hp 3 ø 14.0
30 1 ½ hp 3 ø 14.0
2 /8
2 /8
1
1
SSCR100
2 /8
2 /8
•
‚
ƒ
ø represents electrical phase; all motors are 1,140 rpm. Multiply hp by 0.746 to convert to kW.
Refrigeration charge is for remote condenser only!
To convert cfm to cmh, multiply by 1.699. To convert lbs. to Kg, multiply by 0.454.
Page 14 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
2
Shipping Information
2-1 Unpacking and Inspection
You should inspect your central chilling station for possible
shipping damage. If the container and packing materials are in re-
usable condition, save them for reshipment if necessary.
Thoroughly check the equipment for any damage that might have
occurred in transit, such as broken or loose wiring and
components, loose hardware and mounting screws, etc. In case of
breakage, damage, shortage, or incorrect shipment, refer to the
following sections.
2-2 In the Event of Shipping Damages
Important!
According to the contract terms and conditions of the Carrier,
the responsibility of the Shipper ends at the time and place of shipment.
þ Notify the transportation company’s local agent if you discover
damage.
þ Hold the damaged goods and packing material for the
examining agent’s inspection. Do not return any goods to
Sterling before the transportation company inspection and
authorization.
þ File a claim against the transportation company. Substantiate
the claim by referring to the agent’s report. A certified copy of
our invoice is available upon request. The original Bill of
Lading is attached to our original invoice. If the shipment was
prepaid, contact Sterling at (414) 354-0970 for a receipted
transportation bill.
þ Advise Sterling regarding your request for replacement
and to obtain an RMA (return material authorization)
number.
SSC Series Central Chilling Stations
Page 15 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
2-3 If the Shipment is Not Complete
Check the packing list. The apparent shortage may be intentional.
Back-ordered items are noted on the packing list. You should have:
þ Sterling SSC Series central chilling station
þ Bill of lading
þ Packing list
þ Operating and Installation packet
þ Electrical schematic and panel layout drawings
þ Component instruction manuals
þ Parts list
Re-inspect the container and packing material to see if you missed
any smaller items during unpacking. Determine that the item was
not inadvertently taken from the area before you checked in the
shipment. Notify Sterling immediately of the shortage.
2-4 If the Shipment is Not Correct
If the shipment is not what you ordered, contact Sterling
immediately. Include the order number and item. Hold the items
until you receive shipping instructions.
2-5 Returns
Important!
Do not return any damaged or incorrect items
until you receive shipping instructions from Sterling.
Page 16 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
2-6 Uncrating Your New Chiller
! WARNING !
DUE TO THE SIZE AND WEIGHT OF SSC SERIES CHILLERS,
STERLING RECOMMENDS USING BONDED PROFESSIONAL
MILLWRIGHTS TO UNLOAD AND MOVE SSC SERIES CHILLERS.
Rig the chiller from the frame only, using spreader bars to prevent
load transfer to any chiller components. Rig the frame from at least
four points and balance the load before lifting to clear the skid. Use
a forklift of adequate size when lifting the chiller by the fork
pockets.
Insert the forks all the way into the pockets and be sure to balance
the load before lifting the chiller to clear the skid. Lift only as high
as necessary. Use a pry bar to free the skid if necessary. Lower
slowly. Retain the crating in case reshipment is necessary due to
hidden shipping damage.
Caution!
Due to the weight of these units, use extreme caution
when moving and placing SSC Series chillers.
.
SSC Series Central Chilling Stations
Page 17 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
- Notes -
Page 18 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
3-1 Installation Location Considerations
As with all equipment installations, follow all applicable codes and
regulations.
þ Locate close to the process to reduce piping expense.
þ Locate adjacent to drain and city water sources.
þ Consult a structural engineer to assure that the floor, mounting
pad or structural steel support is of adequate strength.
þ Allow for required service clearances necessary for condenser
maintenance and easy access to all components.
3-2 Making Electrical Connections
SSC Series systems are designed for three-phase voltage operation.
Refer to the unit nameplate for proper voltage and amperage
requirements.
Make sure you provide a correctly sized and protected supply of
electrical power to the unit.
Important!
Refer to National Electric Code (NEC) Article 430-24 through 430-26
for proper feeder conductor and supply disconnect sizing.
Maintain a safe ground and disconnect the power supply before
servicing the unit. A qualified electrician should make electrical
connections, and disconnect and lock out electricity using OSHA
29CFR 1910.147 standards when you need a service call.
Check serial tag voltage and amperage requirements and make sure
your electrical service conforms before making any electrical
connections. Total running amps for the SSC Series systems are
listed on the nameplate. Customer connections can be run to the
supply terminals from either side of the unit. Make sure that all
three phases are wired correctly. If not wired properly, the unit will
run backwards. Again, check the unit nameplate for correct
voltage and amperage.
SSC Series Central Chilling Stations
Page 19 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
! DANGER
Improper electrical connections
can damage the unit and cause
serious operator injury or death!
Bring properly sized power leads and ground from a fused
disconnect (installed by your electrician) to the unit. Provide
external overcurrent protection to the unit, using circuit breakers or
fuses. If you use fuses, make sure that they are dual-element time-
delay fuses, sized according to your electrical code. Make sure that
all electrical connections are tight.
Important!
1. Electrical connections must comply with all applicable electrical codes.
2. The chiller must be grounded in accordance with NEC Article 250.
3. Voltage must be within plus or minus ten percent (±10%) of the nameplate
rating.
4. Make sure your installer provides external protection.
Check the electrical wiring schematic
provided in your Customer Information packet
for additional information.
Page 20 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Note:
·
Never switch contactor leads or motor leads for reversing
rotation.
·
·
Do not use contactor or motor leads for phase matching.
Compressor noise from reverse rotation is noticeable. Do not
run in this mode for more than ten (10) seconds. The
compressor shuts off if it is run longer in this mode.
·
·
Reverse rotation can cause suction and discharge pressures to
be approximately equal; amp draws will be lower than normal.
If you discover that compressor rotation is reversed, correct it
by switching any two main power leads into the disconnect
switch or distribution block on the unit.
Check your work and proceed to the following Piping Considerations section.
3-3 Piping Considerations
Piping systems vary with process application and pump tank
configuration. Typical system configuration drawings are provided
in this manual; the details may or may not apply to your
application. Piping systems must be designed by a person
knowledgeable in piping system design and configuration.
Sterling’s Contracting Department can design and install a piping
system tailored to your process.
·
All piping returning to the pump tank must be equipped with
an inverted trap with a vacuum breaker at the high point of the
system to prevent mains from siphoning into the pump tank.
·
Run mains full size in order to reduce pressure drop in the
system and provide maximum pressures at the ends of the
mains.
3-4 Making Process Water Connections
All Models
All SSC Series chilling stations have two chilled water connections
per unit, and on water-cooled models, one more set of water
connections for condenser water:
SSC Series Central Chilling Stations
Page 21 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
To Process
The chilled water supply outlet leading to the process being
controlled.
From Process
The chilled water return for water returning back to the chiller
from the process to be cooled and recirculated.
3-5 Making Tank Piping Connections
If you have purchased the SSC Series central chilling station with
the integral pump tank, please proceed with this section.
Return
Bring the chilled water returning from the process to the pump
tank warm From Process side. This line is sized according to the
flow rate from the process to the pump tank. See Section 3-3 on
Page 21 for more information on piping considerations.
Important!
Do not use the SSC Series unit to support piping.
Makeup
Connect a city water source to maintain water level in the pump
tank.
Overflow
Connect the OVERFLOW outlet to an approved, trapped drain to
permit excess water in the pump tank to overflow to the drain. The
overflow line is sized according to the size of the pump tank.
To Drain
Connect to a 1½” line (approx. 63 mm) leading to an approved,
trapped drain. You can drain the pump tank if necessary.
Page 22 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
3-6 Water Connection Sizing Considerations
Important!
·
·
·
Run all external chilled water connections with adequate size to the
process.
Provide the largest possible openings and passages for the flow of chilled
water through platens, dies, molds, or other pieces of equipment.
Minimum external pressure drop is critical for proper operation.
3-7 Galvanic Corrosion Considerations
Water circuit piping components are primarily ferrous (iron) and
react electro-chemically with non-ferrous metallic materials such
as copper. Some water has dissolved minerals that will greatly
accelerate the reaction between dissimilar metals.
Use PVC or ferrous piping to minimize galvanic action. If piping
must be copper, use dielectric unions at the chiller.
3-8 Water Treatment Considerations
Water treatment is important in any piping system. In some
locations, raw water may be used in the system without problem;
in other locations, it will result in large deposits of scale and
corrosion.
Sterling offers a complete line of water treatment equipment.
Contact your Sterling sales representative for water testing and
treatment options.
3-9 Making Water-Cooled Condenser Connections
SSC Series water-cooled chilling stations use city or tower water
as a cooling medium. All external condenser supply and discharge
piping and connections should be of adequate size.
SSC Series Central Chilling Stations
Page 23 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Two connections are made to each SSC Series unit:
Condenser Water In
Condenser Water Out
The city or tower water supply inlet is located at the side or rear of
the chiller.
·
·
Water pressure ³ 25 psi (³ 172.4 kPa/³ 1.72 bars)
Water temperature £85°F (£29ºC)
The return outlet, located at the chiller side or rear is connected to
a cooling tower inlet, a sewer or other approved discharge receiver.
·
A water regulating valve is a standard feature in the condenser
water out line.
Caution!
The water regulating valve is set at the factory.
It must not be adjusted except by a qualified refrigeration technician.
3-10 Installing the Remote Air-Cooled Condenser
SSC Series models use the surrounding air to cool the remote
condenser. All models have variable speed fans and low ambient
controls to allow proper operation down to -20°F (-29ºC) outdoor
air temperature.
Install the remote air cooled condenser where there is:
·
·
·
·
·
·
Greater than or equal to -20°F (-29ºC) air temperature.
Free passage of air for condensing.
Adequate structural support.
Protection from strong winds and drifting snow.
Provisions for removal of heated air from the area.
No steam, hot air or fume exhausts drawn into the condenser
coils.
·
Service accessibility.
Page 24 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
SSC Series condensing pressure
with 95ºF (35ºC) condenser air
R-22 = 260 psi (1,793 kPa/17.93 bars)
Note: Due to the variables involved in remote air-cooled condenser installations, no set or
standard piping procedure exists. Each installation must be designed and installed by
qualified persons. Follow the instructions supplied with the condenser.
3-11 Checking Motor Direction
Compressor
Note:
·
Never switch contactor leads or motor leads for reversing
rotation.
·
·
Do not use contactor or motor leads for phase matching.
Compressor noise from reverse rotation is noticeable. Do not
run in this mode for more than ten (10) seconds. The
compressor shuts off if run longer in this mode.
·
·
Reverse rotation can cause suction and discharge pressures to
be approximately equal; amp draws will be lower than normal.
If you discover that compressor rotation is reversed, correct it
by switching any two main power leads into the disconnect
switch or distribution block on the unit.
Water Pump
A positive pressure of 20 to 30 psi (137.9 to 206.8 kPa/1.38 to 2.07
bars) on the TO PROCESS line indicates correct pump rotation.
Condenser Fan
On SSC Series remote air-cooled units, air should draw through
the condenser and discharge up from the condenser.
Changing fan rotation direction
·
·
Disconnect and lock out power at the fused disconnect.
If all fans are going backwards, reverse any two main power
leads.
·
If only some of the fans are going backwards, switch any two of
their respective motor leads.
SSC Series Central Chilling Stations
Page 25 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
-Notes-
Page 26 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
4
Sequence Of Operation
4-1 Staging
1. The system uses a PID control algorithm to regulate the
chilled water temperature. As the required control effort
increases or decreases, the system compressors are turned
on or off to keep the temperature at the specified set-point
2. Compressor anti-recycle time is three (3) minutes.
4-2 Alarms
If a fault occurs, that compressor or circuit is deactivated. The
load will automatically shift to any other compressors that are
currently ON-LINE, but not running. Lead/Lag rotation will
continue to function. Compressors that are faulted will be
removed from the rotation order.
4-3 Lead-Lag Compressors
The system automatically rotates the compressor order to generate
a Lead/Lag rotation. Any time a compressor is faulted or manually
taken OFF-LINE, it will be removed from the Lead/Lag rotation.
Once the fault is cleared or manually put ON-LINE, the
compressor is returned to the Lead/Lag rotation at the end of the
rotation order.
4-4 Lead-Lag Pumps
The system automatically rotates the pump order to generate a
Lead/Lag rotation. Any time a pump is faulted or manually taken
OFF-LINE, it will be removed from the Lead/Lag rotation. Once
the fault is cleared or manually put ON-LINE, the pump is returned
to the Lead/Lag rotation at the end of the rotation order.
SSC Series Central Chilling Stations
Page 27 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
4-5 Chilled Water Circuit
If your central chilling station is equipped with the optional
integral pump tank, make the process cooling water supply
connection at the P1 manifold at the left side of the pump tank at
the exposed connection. Bring the process cooling water return
connection to the Hot well of the tank on the right side at the
flanged connection.
Warm coolant (water and ethylene glycol mixture) returns from the
process to the tank, then gets pumped through the evaporator
where it is cooled. The coolant flows to the process and returns to
repeat the cycle.
4-6 Refrigeration Circuit
·
SSC Series chilling station air- and water-cooled unit
refrigeration cycles differ only in the way the compressed gas
is condensed to a liquid.
·
·
Liquid refrigerant from the condenser passes through a shut-off
valve into a filter/dryer.
The refrigerant then passes through the sight glass and solenoid
valves into the thermal expansion valve which regulates flow;
the valve lowers pressure and boiling point. Heat from the fluid
causes the refrigerant to boil off into a vapor.
·
·
The refrigerant vapor flows through the suction line back into
the compressor.
The refrigerant gives up heat as it re-condenses to a liquid in
the condenser.
4-7 Freezestat Control
The freezestat shuts down the compressor if the chilled water
temperature approaches the freezing point. The chilled water pump
on the system will continue to run. It is factory-set at 40°F (4ºC) or
10°F (6ºC) below the rated capacity operating temperature of 50°F
(10ºC).
Page 28 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
If you want lower chilled water temperatures, you’ll need to mix
process water with industrial- (not automotive) grade ethylene or
propylene glycol with rust inhibitor to provide protection down to
20°F (12ºC) below the operating temperature you want. Figure 3
below shows the proper mixtures needed to provide protection to
20°F (12ºC) below the operating temperature you want. You can
then reset the freezestat cutout temperature to a temperature 10°F
(6ºC) below the operating temperature you selected.
Caution!
Make sure all freezestat adjustments are performed
by a qualified refrigeration service technician.
The Sterling product warranty does not cover system freeze-up!
Figure 3
Freezing Protection Curve
Ethylene glycol required for evaporator freeze protection
60
50
40
Ethylene
glycol
30
percent by
volume
20
10
0
-50ºF -40ºF -30ºF -20ºF -10ºF 0ºF 10ºF 20ºF 30ºF 40ºF 50ºF 60ºF
-46ºC -40ºC -34ºC -29ºC -23ºC -18ºC -12ºC -7ºC -1ºC 4ºC 10ºC 16ºC
Chilled water operating temperature ºF / ºC
SSC Series Central Chilling Stations
Page 29 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
4-8 High Pressure Cutout
This electro-mechanical safety feature opens the control circuit if
the system condensing pressure exceeds a safe level.
High pressure cutout setting
Model
psi
kPa
bars
SSC Series water-cooled chilling stations
SSC Series remote air-cooled chilling stations
290 psi
375 psi
2,000 kPa
2,586 kPa
20 bars
26 bars
Important!
The high pressure cutout is a manual reset control,
so you should reset it once.
If the problem persists, call a refrigeration service technician
to analyze the problem and to reset the control.
4-9 Low Pressure Cutout
This encapsulated switch safety feature prevents the compressor
suction pressure from dropping below a pre-set point. It is factory
set to open the control circuit when pressure drops below a safe
level. The chiller will need to be restarted when the suction
pressure reaches above 65 psi (448.2 kPa/4.5 bars).
Opens control circuit @
psi kPa bars
Resets control circuit @
psi kPa bars
Model
SSC Series water-cooled chilling stations
SSC Series remote air-cooled chilling
stations
15 psi 103.4 kPa 1.0 bars 30 psi 206.9 kPa 2.1 bars
15 psi 103.4 kPa 1.0 bars 30 psi 206.9 kPa 2.1 bars
4-10 Flow Switch
The flow switch shuts down the chiller if the evaporator water flow
falls below a safe operating gallons-per-minute (liters-per-minute)
flow rate.
Page 30 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
4-11 Control Nipple
All SSC Series chilling station evaporators have two control
nipples. The flow switch, freezestat, and flush port are located in
the control nipple. Optional pressure gages can be mounted in the
control nipples to aid in achieving proper flow through the
evaporator and balancing flows.
Coupling mounts for customer-installed pressure gauges are
included on both control nipples. Pressure drop between
evaporator entering water pressure and evaporator leaving water
pressure can be converted to gallons per minute using the pressure
drop charts provided.
4-12 Control Probe
Two control probes sense temperatures. One probe measures the
temperature of the hot well and the other does the same for the
cold well of the reservoir. These temperatures are used by the PLC
controller to sequence the compressors, based on load.
4-13 Chilled Water Manifold
The chilled water manifold allows one-point connections of TO
PROCESS piping. The Sch. 40 steel piping includes butterfly
valves at each evaporator for flow balancing and circuit isolation;
optional pressure gauges can be installed.
4-14 Condenser Water Manifold
The condenser water manifold allows one-point connection of TO
TOWER (drain) and FROM TOWER (city water) piping. Sch. 40
steel include butterfly valves for each condenser. Drain points are
at the bottom of the header.
SSC Series Central Chilling Stations
Page 31 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
- Notes -
Page 32 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
5
Startup Checklists
5-1 Introduction
Important!
These lists assume the installation information
in this manual has been read and followed.
Have new chillers started up and checked
by a qualified refrigeration service technician.
Sterling offers factory startup for SSC Series Series chilling stations.
Call the Sterling Service Department
at 1 (800) 233-4819 for more details.
5-2 Water-Cooled SSC Series Startup Checklist
þ Check the shipping papers against the serial tag to be sure
chiller size, type and voltage is correct for the process.
þ Check the transformer primary voltage connections to be sure
they are configured for the electrical power you are using.
þ The voltage at the main power connection must be within plus
or minus ten percent (±10%) of the voltage listed on the serial
tag.
þ Phase imbalance must be less than two percent (<2%).
þ Electrical connections must conform to all applicable codes.
þ Complete the chilled water TO and FROM PROCESS
connections.
þ The optional or field installed chilled water supply and return
valves on the chiller must be open.
þ Be sure the pump tank and chilled water circuit are filled with a
water/glycol mixture that provides freeze protection to 20°F
(12ºC) below the leaving water temperature you want.
þ Complete the tower or city condenser WATER IN and WATER
OUT connections. Provide an adequate condenser water
supply; 2 gpm per ton for city water or 3 gpm per ton for tower
water operation.
þ Remove all tools, foreign matter and debris from the pump
tank reservoir and piping.
SSC Series Central Chilling Stations
Page 33 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
þ Complete all piping leading to and from the pump tank.
Observe all applicable codes.
þ Complete all electrical wiring. Observe all applicable codes.
þ Prepare all related equipment in the system for operation.
Note:
·
Never switch contactor leads or motor leads for reversing
rotation.
·
·
Do not use contactor or motor leads for phase matching.
Compressor noise from reverse rotation is noticeable. Do
not run in this mode for more than ten (10) seconds. The
compressor shuts off if run longer in this mode.
·
·
Reverse rotation can cause suction and discharge pressures
to be approximately equal; amp draws are lower than
normal.
If you discover that compressor rotation is reversed, correct
it by switching any two main power leads into the
disconnect switch or distribution block on the unit.
þ Open the 1” (approx. 25 mm) makeup water valve and allow
the tank to fill until the automatic float valve shuts off. The
float level should be adjusted so the standing water level is 8”
(20 cm) from the top of the tank.
þ Check for proper pump rotation direction. To confirm proper
rotation:
1. Observe a pump pressure gauge connected to the
suction and discharge sides of the pump casing through
two ¼” (approx. 6.4 mm) gauge cocks.
2. Close the gauge cock leading to the pump suction and
open the gauge cock leading to the pump discharge.
3. Close the discharge butterfly valve, crack it open, then
start the pump and observe the gauge.
·
·
·
If the gauge indicates within 15 psi (103.4 kPa/1.03
bars) below the pump curve, pump rotation is
correct. Pump rotation is clockwise opposite the
shaft end.
If the gauge indicates 20 psi (137.9 kPa/1.38 bars)
or more below the pump curve, the pump is running
backwards. Reverse rotation by interchanging any
two power mains to the pump motor or starter.
Recheck the pressure to be sure it increased.
Page 34 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
þ Check the water level in the pump tank to be sure the pump
does not run dry while the system piping is being filled.
þ Check your work and proceed to the Startup procedure.
5-3 Water-Cooled SSC Series Startup
1. Start the chiller by pushing the Start button on the control
panel of the unit.
2. The touchscreen will display the Main Menu screen.
3. If your chiller has been setup to control the pump tank, the
recirculation pump will turn on first, then after 5 seconds
the process pump will turn on. If configured with a standby
pump, the lead/lag will control which pump turns on.
4. Fifteen (15) seconds after the last pump turns on the first
compressor will turn on. Based on the temperature of the
water the controller will turn on compressors every 15
seconds.
5. Adjust the Freezestat cut-out, located in the main electrical
enclosure, to 10°F (6ºC) below the process temperature set
point you want.
Note: If the recirculation pump does not turn on (or that the flow switch is not satisfied) the
compressors will not be allowed to turn on.
6. Check the pump(s) amp draws and pressures. The amp
draws must be within the pump(s) running load and service
factor amps.
7. Operate the chiller, looking for leaks and listening for
unusual noises or vibrations that could indicate improper
operation.
5-4 Remote Air-Cooled SSC Series Startup Checklist
þ Check the shipping papers against the serial tag to be sure
chiller size, type and voltage is correct for the process.
þ Check the transformer primary voltage connections to be sure
they are configured for the electrical power you are using.
þ The voltage at the main power connection must read within
plus or minus ten percent (±10%) of the voltage listed on the
serial tag.
þ Phase imbalance must be less than two percent (<2%).
SSC Series Central Chilling Stations
Page 35 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
þ Electrical connections must conform to all applicable codes.
þ Complete the chilled water TO and FROM PROCESS
connections.
þ The optional or field installed chilled water supply and return
valves must be open.
þ Be sure the tank and chilled water circuit piping are filled with
a water/glycol mixture. The water/glycol mix should provide
freeze protection to 20°F below the leaving water temperature
you’ve selected.
þ The air cooled condenser should have an adequate supply of air
for proper operation.
þ Connect the main power to the unit and bump-start it to check
for proper rotation direction. If the fans are operating
backwards, reverse any two main power leads at the incoming
terminal block.
þ Remove all tools, foreign matter and debris from the pump
tank reservoir and piping.
þ Complete all piping leading to and from the pump tank.
Observe all applicable codes.
þ Complete all electrical wiring. Observe all applicable codes.
þ Prepare all related equipment in the system for operation.
Note:
·
Never switch contactor leads or motor leads for reversing
rotation.
·
·
Do not use contactor or motor leads for phase matching.
Compressor noise from reverse rotation is noticeable. Do
not run in this mode for more than ten (10) seconds. The
compressor shuts off if run longer in this mode.
·
·
Reverse rotation can cause suction and discharge pressures
to be approximately equal; amp draws are lower than
normal.
If you discover that compressor rotation is reversed, correct
it by switching any two main power leads into the
disconnect switch or distribution block on the unit.
þ Open the 1” (approx. 25 mm) makeup water valve and allow
the tank to fill until the automatic float valve shuts off. The
float level should be adjusted so the standing water level is 8”
(20 cm) from the top of the tank.
Page 36 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
þ Check for proper pump rotation direction. To confirm proper
rotation:
1. Observe a pump pressure gauge connected to the
suction and discharge sides of the pump casing through
two ¼” (approx. 6.4 mm) gauge cocks.
2. Close the gauge cock leading to the pump suction and
open the gauge cock leading to the pump discharge.
3. Close the discharge butterfly valve, crack it open, then
start the pump and observe the gauge.
·
·
·
If the gauge indicates within 15 psi (103.4 kPa/1.03
bars) below the pump curve, pump rotation is
correct. Pump rotation is clockwise opposite the
shaft end.
If the gauge indicates 20 psi (137.9 kPa/1.38 bars) or
more below the pump curve, the pump is running
backwards. Reverse rotation by interchanging any
two power mains to the pump motor or starter.
Recheck the pressure to be sure it increased.
þ Check the water level in the pump tank to be sure the pump
does not run dry while the system piping is being filled.
þ Check your work and proceed to the Startup procedure in the
following section.
5-5 Remote Air-Cooled SSC Series Startup
1. Start the chiller by pushing the Start button on the control
panel of the unit.
2. The touchscreen will display the Main Menu screen.
3. If your chiller has been setup to control the pump tank, the
recirculation pump will turn on first, then after 5 seconds
the process pump will turn on. If configured with a standby
pump, the lead/lag will control which pump turns on.
4. Fifteen (15) seconds after the last pump turns on the first
compressor will turn on. Based on the temperature of the
water, the controller will turn on compressors every 15
seconds.
5. Adjust the Freezestat cut-out, located in the main electrical
enclosure, to 10°F (6ºC) below the process temperature set
point you want.
SSC Series Central Chilling Stations
Page 37 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Note: If the recirculation pump does not turn on (or that the flow switch is not satisfied) the
compressors will not be allowed to turn on.
6. Check the pump(s) amp draws and pressures. The amp
draws must be within the pump(s) running load and service
factor amps.
7. Operate the chiller, looking for leaks and listening for
unusual noises or vibrations that could indicate improper
operation.
8. Check condenser fans for pressure switch settings as shown
in the table below:
Fan
number
Set on
kPa
Set off
kPa
psi
bars
psi
bars
1
2
3
4
5
not applicable; Fan 1 is a variable-speed fan
240
265
285
305
1,654.8
1,827.2
1,965.1
2,102.9
16.5
18.3
19.7
21.1
190
215
235
255
1,310.1
1,482.4
1,620.3
1,758.2
13.1
14.8
16.2
17.6
5-6 Determining Flow Rate
To determine flow:
1. Close the gauge cock leading to the pump suction side and
open the gauge cock leading to the pump discharge.
2. Start the pump and make note of the discharge pressure in
psi (kPa/bars).
3. Check the pump curve for the appropriate horsepower
pump at the discharge pressure psi.
4. Project this point down to find the flow in gpm (lpm).
5. Process pumps can be left wide open if running amps are
below full load amps.
5-7 Shutdown
1. Ready process and related equipment for shut down.
2. Turn off main power.
3. Close the water make up valve.
4. If the system is to be drained, open the 2” drain valve.
Page 38 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 4
SSC Series Standard Control Panel
Figure 5
SSC Series Advanced Control Panel
SSC Series Central Chilling Stations
Page 39 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
-Notes-
Page 40 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
6
Graphic Panel Devices
6-1 Indicator Lights and Control Switches (MMI)
System On
The green System On indicator lights when the main power
switch is on and the control circuit is energized.
Start
The Start push-button lets you energize the unit.
Stop
The Stop push-button lets you de-energize the unit.
Touchscreen Interface
The color touchscreen interface gives you control over the chilling
station. It has an easy-to-use control menu that lets you quickly
change or adjust chiller settings and also gives you all the
operation information you need to control the unit effectively.
See Chapter 7 on Page 42 for more information on the Standard
touchscreen interface operation. See Chapter 8 on Page 57 for
more information on the Advanced touchscreen interface
operation.
SSC Series Central Chilling Stations
Page 41 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
-Notes-
Page 42 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Using the Standard
7
Touchscreen Interface
7-1 Touchscreen Interface Introduction (MMI)
The Standard touchscreen interfaces let you control your SSC
Series central chilling station. You can do such things as:
·
·
Control compressors and optional pumps
View current statuses of operation, such as pressures,
temperatures, and capacities
·
Handle alarm conditions
The sections in this chapter list special instructions for operating
either touchscreen interfaces.
Note: The screens shown in this chapter are sample screens.
Actual screen representations may be slightly different in
appearance, but are no different in operation.
On all screens in this controller, the F4 button is reserved for the
previous screen function. Some screens, such as the chiller status
screen, do not have sufficient space to display a prompt that the F4
performs this function. However, the F4 button will always move
to the previous screen and will eventually return to the Main Menu.
SSC Series Central Chilling Stations
Page 43 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 6
SSC Series Standard Control Panel
7-2 Using the SSC Series Standard Touchscreen
Interface
The SSC Series Standard touchscreen interface is the “manager” of
your SSC Series central chilling station. The screen contains screen
buttons you can press to control system operation.
For example, if you need to resolve an alarm condition, press the
or
buttons on the right side of the screen to highlight
“ACTIVE ALARM LIST”. The screen will tell you what alarm is active
and you may clear the alarm by touching the F1 button located to
the lower left of the terminal.
To return to the Main Menu screen at this point, press the F4
button of the terminal, located in the lower right corner. The Main
Menu screen then displays.
Some screens let you directly control the operation of the chilling
station, while others are for information purposes and are “display-
only” screens. This chapter distinguishes between operation and
display screens.
Page 44 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
7-3 Getting Started on the SSC Series Standard
Touchscreen Interface
To start the SSC Series Standard touchscreen interface:
n Push the ON/OFF button on the cabinet.
The SSC Series control panel energizes and the System On
indicator turns on.
The Main Menu screen displays:
Main Menu Screen
The Main Menu screen lets you gain access to:
·
·
“COMPRESSOR STATUS” contains the compressor status display
screen
If the chiller was configured to operate the chilled water pump
tank, the “PROC PUMP STATUS” is displayed. This screen
contains the process pump status.
·
·
“RECIRC PUMP STATUS” contains the recirculation pump status
if the chiller was configured to operate the chilled water pump
tank.
“ACTIVE ALARM LIST” shows all of the active alarms. Those
alarms which are currently preventing the chiller from
functioning, if fatal alarm, or those that show a condition which
needs to be looked at in a short period of time.
·
“ALARM HISTORY” contains the last twenty-five (25) alarms that
were activated.
SSC Series Central Chilling Stations
Page 45 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
·
“CONFIGURATION MENU” contains the chiller setup parameters
(i.e. chiller setpoint, and high and low temperature alarm
setpoints)
The following sections in this chapter list the information you need
to navigate through these screens for operating and monitoring
your SSC Series central chilling station with the Standard Control
Package.
7-4 Viewing and Operating Chiller Compressors
Viewing Compressor Status
To view the status of the chiller compressors, start at the Main
Menu screen, then:
n Press the
or
buttons on the right side of the screen
to highlight “COMPRESSOR STATUS”
n Press ¿
The compressor status screen displays:
Compressor Status Screen
The Compressor Status screen shows the status for compressors
within the system. Only compressors that are included in the
system will be shown on this screen. Compressors will display one
of the following states:
1. OFFLINE – This indicates that the compressor has been turned
off in the compressor enable/disable screen. The compressor
will not be called to operate until it has been re-enabled.
Page 46 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
2. READY – Indicates that the compressor is enabled and ready
to run. However, the current loading does not require the
compressor to be running. This compressor will be
automatically started when needed.
3. RUNNING – Compressor is currently running.
4. FAULT – A safety on the compressor indicates a fault
condition and the compressor has been deactivated. Once the
problem is remedied, the compressor will return to a READY
state unless it is put in the OFFLINE state.
Operating the chiller compressors
To enable or disable the individual compressors, start at the Main
Menu, then:
n Press the
or
buttons on the right side of the screen
to highlight “CONFIGURATION MENU”
n Press the ¿ button
The configuration menu screen displays:
Chiller Configuration Screen
n Press the
or
button to highlight either “CIR 1 COMP
ENABLES” or “CIR 2 COMP ENABLES”
n Press the ¿
SSC Series Central Chilling Stations
Page 47 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
The compressor enable screen displays:
Compressor Enable Screen
These screens allow the customer to toggle the compressors
between ON-LINE and OFF-LINE. As the operator presses the F1
or F2 button, the corresponding compressor state changes between
ON-LINE and OFF-LINE.
Setting Compressor Lead/Lag Times and Activating Compressor
Lead/Lag Operation
While in the Configuration Menu, the compressor lead/lag screen
allows the customer to enable or disable the Lead/Lag rotation of
compressors. While viewing the screen for the applicable rotation,
pressing F1 will toggle the rotation function On or Off. Pressing
the F2 button will present an entry screen which will allow the
entry of a rotation interval. Acceptable range is 50-200 hours.
The compressor lead/lag screen displays:
Compressor Lead/Lag Screen
Page 48 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Viewing Compressor Run Times
From the Main Menu, use the
or
buttons to highlight
the “HOURMETERS” menu. Scroll to select the compressors. Then
press ¿ to display the hourmeter.
Note: this is a complete list of all components that may be
included in the system. Any component that is not
included in the system will not accumulate time.
The Compressor Run Time screen displays:
Compressor Run Time Display Screen
Two hourmeters are kept for each compressor in the system. The
first is a lifetime meter. This measures the total time that the
compressor has been operational in the lifetime of the chiller. The
second is a resettable hourmeter. This hourmeter can be cleared to
monitor run time on specific intervals. In order to clear the
resettable hourmeter, press the F1 button (as prompted on the
screen)
SSC Series Central Chilling Stations
Page 49 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
7-5 Viewing and Operating Chiller Pumps
If your chiller system was configured to operate the pump(s) of the
chilled water pump tank the user may view the status of the
process and recirculation pumps.
Viewing Chiller Pump Status
To view the status of the pumps, start from the Main Menu, then:
n Press the
or
buttons to highlight either “PROC
PUMP STATUS”or “RECIRC PUMP STATUS”.
n Press ¿
The Pump Status Screen appears
Pump Status Screen
Only pumps that are included in the system will be shown on this
screen. Pumps will display one of the following states:
1. OFFLINE – This indicates that the pump has been turned off in
the pump enable/disable screen. The pump will not be called
to operate until it has been re-enabled.
2. READY – Indicates that the pump is enabled and ready to run.
However, the current number of pumps specified to run does
not require this pump to operate.
3. RUNNING – Pump is currently running.
4. FAULT – A safety on the pump indicates a fault condition and
the pump has been deactivated. Once the problem is remedied,
the pump will return to a READY state unless it is put in the
OFFLINE state.
Page 50 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Chiller Pumps
To turn on and off the pumps, start from the Main Menu, then:
n Press the
or
buttons to highlight either
“CONFIGURATION MENU”.
n Press ¿
n Highlight “PUMP ENABLES”
n Press ¿
n Highlight the pump you want to operate.
The Pump Enables Screen appears
Pump Enables Screen
Any pump that is disabled to the OFF-LINE position will not be
called to operate. Simply toggle the F1 key on the enable/disable
screen to toggle the state of the pump from the ON-LINE to OFF-
LINE state.
Setting Pump Lead/Lag Times and Activating Pump Lead/Lag
Operation
While in the Configuration Menu, the pump lead/lag screen allows
the customer to enable or disable the Lead/Lag rotation of
compressors. While viewing the screen for the applicable rotation,
pressing F1 will toggle the rotation function On or Off. Pressing
the F2 button will present an entry screen which will allow the
entry of a rotation interval. Acceptable range is 50-200 hours.
SSC Series Central Chilling Stations
Page 51 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
The compressor lead/lag screen displays:
Pump Lead/Lag Screen
Viewing Pump Run Times
From the Main Menu, use the
or
buttons to highlight
the “HOURMETERS” menu. Scroll to select the pump. Then press
¿ to display the hourmeter.
Note: this is a complete list of all pumps that may be included in
the system. Any pump that is not included in the system
will not accumulate time.
The Pump Run Time screen displays:
Pump Run Time Display Screen
Page 52 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Two hourmeters are kept for each compressor in the system. The
first is a lifetime meter. This measures the total time that the pump
has been operational in the lifetime of the chiller. The second is a
resettable hourmeter. This hourmeter can be cleared to monitor
run time on specific intervals. In order to clear the resettable
hourmeter, press the F1 button (as prompted on the screen)
7-6 Viewing Active Alarms and Handling Alarm
Conditions
These two screens let you view any active alarm conditions as well
as the alarm history for the entire history. The list of system
alarms that are tracked are as follows:
n Chilled Water High Temperature Alarm
n Chilled Water Low Temperature Alarm
n Compressor Motor Protector Fault (One for each compressor)
n Chilled Water Circuit Low Flow (One per chilled water circuit)
n Chilled Water Circuit Freezestat (One per chilled water circuit)
n Chilled Water Circuit High Pressure (One per chilled water
circuit)
n Chilled Water Circuit Low Pressure (One per chilled water
circuit)
n Pump motor overload (One per system pump)
If an alarm conditions occurs the follow screen is displayed:
Alarm Condition Screen
SSC Series Central Chilling Stations
Page 53 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
To acknowledge the alarm, press F1 to clear the alarm. It will then
appear in the alarm history screen. Except for High and Low
Water Temperature, and Low Refrigerant Pressure, these alarms
are considered fatal and maintenance must be preformed in order
to allow the chiller to fully run. Should a compressor or pump turn
off from an alarm condition, the remaining will shut down and
display FAULT in the status screen for the device.
Once a device has gone offline you will need to contact a licensed
professional (electrician or refrigeration sevice company) to bring
the device back online.
! CAUTION
Never attempt to service a unit until a qualified
electrician has opened and locked out the main
disconnect using OSHA 1910.147 standards.
All electrical connections must be done by a qualified
electrician.
! WARNING
Disconnect all power to the unit, let the unit
cool down, and turn off the water prior to any
servicing.
Failure to do so can result in SERIOUS INJURY
OR DEATH!
Page 54 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
7-7 Viewing and Setting System Temperatures
To view the actual process temperature select any of the status
screens from the main menu. The process temperature is located
on the bottom of the screen.
For example, the compressor status displays:
Compressor Status Screen
Note: If you have a metric version of the SSC Series controller, the screens display in converted
metric values.
Setting System Temperatures
The chiller setpoints are set through the configuration menu.
Starting from the Main Menu:
n Press the
or
buttons to highlight “CONFIGURATION
MENU”
n Press ¿
n Highlight “CW TEMP SETPOINT”, “CW TEMP HIGH LIMIT”, or “CW
TEMP LOW LIMIT”
n Press ¿
n While on the parameter screen, simply press the F1 button to
make the parameter change. A numeric entry screen will
appear. Use the
the and
and
buttons to select the digit, and
buttons to increase and decrease that digit.
SSC Series Central Chilling Stations
Page 55 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Once the value is correct, press the ¿ button to make the
change. In the event that the value is outside the range
specified by MAX or MIN, the value entered will be the
corresponding MAX or MIN.
Page 56 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Using the Advanced
8
Touchscreen Interface
8-1 Touchscreen Interface Introduction (MMI)
The Advanced touchscreen interfaces let you control your SSC
Series central chilling station. You can do such things as:
·
·
Control compressors and optional pumps
View current statuses of operation, such as pressures,
temperatures, and capacities
·
Handle alarm conditions
The sections in this chapter list special instructions for operating
either touchscreen interfaces.
Note: The screens shown in this chapter are sample screens.
Actual screen representations may be slightly different in
appearance, but are no different in operation. Also, the
PLC is configured based on options and system
configuration at the time of order. These screens are the
basic ones to startup the chiller.
SSC Series Central Chilling Stations
Page 57 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 7
SSC Series Advanced Control Panel
8-2 Using the SSC Series Advanced Touchscreen
Interface
The SSC Series Advanced touchscreen interface is the “manager”
of your SSC Series central chilling station. This screen contains
screen buttons you can press to control system operation.
For example, if you need to resolve an alarm condition, press the
Up or Down arrow buttons on the right side of the screen to
highlight “ACTIVE ALARMS”. The screen will tell you what alarm is
active and you may clear the alarm by touching the F1 button
located on the lower left of the terminal.
To return to the Main Menu screen at this point, press the Main
Menu button on the screen, located in the lower right corner. The
Main Menu screen then displays.
Some screens let you directly control the operation of the chilling
station, while others are for information purposes and are “display-
only” screens. This chapter distinguishes between operation and
display screens.
Page 58 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
8-3 Getting Started on the SSC Series Advanced
Touchscreen Interface
To start the SSC Series Standard touchscreen interface:
n Push the ON/OFF button on the cabinet.
The SSC Series control panel energizes and the System On
indicator turns on.
The Main Menu screen displays:
Figure 8
Main Menu Screen
The Main Menu screen lets you gain access to:
·
·
“Active Alar ms” contains the current alarm(s) of the system
“Al;ar m Histor y” contains the last thirty (30) alarms that were
activated.
SSC Series Central Chilling Stations
Page 59 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
·
·
“Compr essor Hour meter s” contains the lifetime and resettable
hour meters to show the number of hours that the compressors
have been running
If the chiller was configured to operate the chilled water pump
tank, there are three screens to configure and view the pump
tank setup. The configuration screen allows for the user to turn
on or off any of the pumps as well as configuring the lead/lag
rotation (if multiple pumps were configured)
·
·
“Chiller Configur ation” shows the configuration of the chiller
itself including the chiller temperature setpoint, temperature
alarm settings, as well as setting up the lead/lag rotation, and
the ability to turn on and off the compressors.
“PanelView Utilities” and “ACS Ser vice” are both password
protected sections of the PLC that are used to configure the
display and the initial configuration of the chiller and system.
The following sections in this chapter list the information you need
to navigate through these screens for operating and monitoring
your SSC Series central chilling station with the Standard Control
Package.
8-4 Viewing and Operating Chiller Compressors
Viewing Compressor Status
To view the status of the chiller compressors, start at the Main
Menu screen, then:
n Press the Up or Down buttons on the right side of the screen to
highlight “System Infor mation”
n Press ¿
The chiller status screen displays:
Page 60 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 9
Chiller Status Screen
The Chiller Status screen shows the status for compressors within
the system. Only compressors that are included in the system will
be shown on this screen. Compressors will display one of the
following states:
1. OFFLINE – This indicates that the compressor has been turned
off in the compressor enable/disable screen. The compressor
will not be called to operate until it has been re-enabled. The
color code for this indication is black.
2. READY – Indicates that the compressor is enabled and ready
to run. However, the current loading does not require the
compressor to be running. This compressor will be
automatically started when needed. The color code for this
indication is yellow.
3. RUNNING – Compressor is currently running. The color code
for this indication is green.
4. FAULT – A safety on the compressor indicates a fault
condition and the compressor has been deactivated. Once the
problem is remedied, the compressor will return to a READY
SSC Series Central Chilling Stations
Page 61 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
state unless it is put in the OFFLINE state. The color code for
this indication is red.
Operating the chiller compressors
To enable or disable the individual compressors, start at the Main
Menu, then:
n Press the Up or Down buttons on the right side of the screen to
highlight “Chiller Configur ation”
n Press the ¿ button
The configuration menu screen displays:
Figure 10
Chiller Configuration Screen
n Touch the screen corresponding with the compressor you want
to bring On-Line or Off-Line. The background color of the
square turns green for On-Line and black for Off-line.
Page 62 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Setting Compressor Lead/Lag Times and Activating Compressor
Lead/Lag Operation
While in the Configuration Menu, the compressors can be setup in
a lead/lag configuration using interval hours. By pressing the
“Compr essor Rotation Inter val” button, a numeric keypad will be
displayed and allow the user to change the timeframe of the
interval.
To activate the Lead/Lag operation touch the “Compr essor
Rotation” button. The status of the button will change to Enabled
(green background), or Disabled (black background).
Viewing Compressor Run Times
From the Main Menu, use the Up or Down buttons to highlight the
“Compr essor Hour meter s” menu. Scroll to select the compressors.
Then press ¿ to display the hourmeters.
Note: this is a complete list of all compressors that may be
included in the system. Any compressor that is not
included in the system will not accumulate time.
The Compressor Run Time screen displays:
SSC Series Central Chilling Stations
Page 63 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 11
Compressor Run Time Display Screen
Two hourmeters are kept for each compressor in the system. The
first is a lifetime meter. This measures the total time that the
compressor has been operational in the lifetime of the chiller. The
second is a resettable hourmeter. This hourmeter can be cleared to
monitor run time on specific intervals. In order to clear the
resettable hourmeter, press the Hour Meter Reset button (as
prompted on the screen)
8-5 Viewing and Operating Chiller Pumps
If your chiller system was configured to operate the pump(s) of the
chilled water pump tank, the user may view the status of the
process and recirculation pumps.
Page 64 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Viewing Chiller Pump Status
To view the status of the pumps, start from the Main Menu, then:
n Press the Up or Down buttons to highlight either “System
Infor mation”.
n Press ¿
The Pump Status Screen appears
Figure 12
Pump Status Screen
Only pumps that are included in the system will be shown on this
screen. Pumps will display one of the following states:
1. OFFLINE – This indicates that the pump has been turned
off in the pump enable/disable screen. The pump will not
be called to operate until it has been re-enabled. The color
code for this indication is black.
SSC Series Central Chilling Stations
Page 65 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
2. READY – Indicates that the pump is enabled and ready to run.
However, the current number of pumps specified to run does
not require this pump to operate. The color code for this
indication is yellow.
3. RUNNING – Pump is currently running. The color code for
this indication is green.
4. FAULT – A safety on the pump indicates a fault condition and
the pump has been deactivated. Once the problem is remedied,
the pump will return to a READY state unless it is put in the
OFFLINE state. The color code for this indication is red.
Operating Chiller Pumps
To turn on and off the pumps, start from the Main Menu, then:
n Press the Up or Down buttons to highlight either “Chilled
Water Pump Tank Configur ation”.
n Press ¿
The Pump Enables Screen appears
Figure 13
Pump Enables Screen
Page 66 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Any pump that is disabled to the OFF-LINE position will not be
called to operate. Simply press the button of the desired pump to
toggle the state of the pump from the ON-LINE to OFF-LINE
state.
Setting Pump Lead/Lag Times and Activating Pump Lead/Lag
Operation
While in the Configuration Menu, the pump lead/lag (rotation) can
be enabled or disabled. Simply press the Process or Recirculation
Pump Interval button on the screen to toggle between Enabled and
Disabled.
The interval between rotating pumps may also be setup in this
screen. Press the CW Pump Rotation Interval button to bring up
the time entry screen. Acceptable range is 50-200 hours.
Viewing Pump Run Times
From the Main Menu, use the Up or Down buttons to highlight
either the “Chilled Water Pr ocess Pump Hour meter s” or “Chilled
Water Recir c Pump Hour meter s” menu. Then press ¿ to display
the hourmeters.
Note: this is a complete list of all pumps that may be included in
the system. Any pump that is not included in the system
will not accumulate time.
The Pump Run Time screen displays:
SSC Series Central Chilling Stations
Page 67 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 14
Pump Run Time Display Screen
Two hourmeters are kept for each compressor in the system. The
first is a lifetime meter. This measures the total time that the pump
has been operational in the lifetime of the chiller. The second is a
resettable hourmeter. This hourmeter can be cleared to monitor
run time on specific intervals. In order to clear the resettable
hourmeter, press the appropriate “Hour Meter Reset” button (as
prompted on the screen)
8-6 Viewing Active Alarms and Handling Alarm
Conditions
These two screens let you view any active alarm conditions as well
as the alarm history for the entire history. The list of system
alarms that are tracked are as follows:
n Chilled Water High Temperature Alarm
n Chilled Water Low Temperature Alarm
Page 68 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
n Compressor Motor Protector Fault (One for each compressor)
n Chilled Water Circuit Low Flow (One per chilled water circuit)
n Chilled Water Circuit Freezestat (One per chilled water circuit)
n Chilled Water Circuit High Pressure (One per chilled water
circuit)
n Chilled Water Circuit Low Pressure (One per chilled water
circuit)
n Pump motor overload (One per system pump)
If an alarm condition occurs the follow screen is displayed:
Figure 15
Alarm Condition Screen
To acknowledge the alarm, press the alarm silence button to clear
it. It will then appear in the alarm history screen. Except for High
and Low Water Temperature, and Low Refrigerant Pressure, these
alarms are considered fatal and maintenance must be preformed in
order to allow the chiller to fully run. Should a compressor or
SSC Series Central Chilling Stations
Page 69 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
pump turn off from an alarm condition the remaining will shut
down and display FAULT in the status screen for the device.
Once a device has gone offline you will need to contact a licensed
professional (electrician or refrigeration sevice company) to bring
the device back online.
! CAUTION
Never attempt to service a unit until a qualified
electrician has opened and locked out the main
disconnect using OSHA 1910.147 standards.
All electrical connections must be done by a qualified
electrician.
! WARNING
Disconnect all power to the unit, let the unit
cool down, and turn off the water prior to any
servicing.
Failure to do so can result in SERIOUS INJURY
OR DEATH!
Page 70 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
8-7 Viewing and Setting System Temperatures
To view the actual process temperature start at the Main Menu and
n Use the Up or Down arrows to highlight “System Infor mation”
n Press ¿
The system status displays:
Figure 16
System Status Screen
Note: If you have a metric version of the SSC Series controller, the screens display in converted
metric values.
SSC Series Central Chilling Stations
Page 71 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Setting System Temperatures
The chiller setpoints are set through the compressor configuration
menu. Starting from the Main Menu:
n Press the Up or Down buttons to highlight “Chiller
Configur ation”
n Press ¿
n Touch the “Process Set-point” button
The input display screen appears:
Figure 17
Temperature Input Display Screen
Page 72 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
9
Routine Maintenance
9-1 Lubrication
Grease all fan bearings, fan motors, and pump motors that do not
have permanently sealed bearings. Remove the grease relief plug
(motors only) before adding grease. Failure to do so may
dislodge the bearing grease retainer which will eventually
cause bearing failure.
Lubricate components regularly, based only on the component
manufacturer’s specifications for frequency and lubricant.
Compressors require a special scroll oil (Suniso 3GSA or
equivalent); failure to use this oil when lubricating will void the
warranty.
9-2 Condenser Maintenance
Dirty condenser heat exchange surfaces reduce system capacity.
Inspect and clean as needed.
Remote Air-Cooled
Brush or vacuum light dirt accumulations. Avoid bending or
damaging the fins. Heavy soil accumulations on the coil require
professional steam cleaning by a qualified refrigeration service
technician. Washing from the outside will only make matters
worse.
Water-Cooled
Proper water treatment will greatly reduce cleaning intervals.
Remove dirt in the condenser tubes with a nylon tube brush.
Mineral deposits can be removed by circulating Sterling Liquid
De-Scaling Solution (Sterling Model Number A0502600) through
the water side of the condenser. Follow the directions on the
container.
The refrigerant side is sealed and requires no routine maintenance.
SSC Series Central Chilling Stations
Page 73 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
9-3 Evaporator Maintenance
The evaporator(s) may be accessed for back-flushing by removal
of the 2” plug (approx. 51 mm) in the return control nipple and the
flow switch in the supply control nipple. If the suggested piping
recommendations have been followed, one circuit of a multiple
circuit chiller may be back-flushed without shutting down the
entire system. Check Y-strainer for any clogging.
9-4 Pump Motor Seal
Pump seals require water for lubrication, so the pump(s) must
never be run dry. Always fill the tank before attempting to operate
the pump(s). Seal failures usually follow a period of dry operation
of the pump.
9-5 Makeup Valve
Periodically inspect the water makeup valve assembly for proper
operation. If the valve no longer shuts off completely or reliably,
replace it. The plastic ball float should be buoyant for proper
operation.
9-6 Recommended Pump Tank Spare Parts
Part no.
Part description
Pressure gauge
Float valve, 1” (approx. 25 mm)
Plastic ball float, 6” (approx. 152 mm)
Float rod, 10” (25 cm)
Quantity
1 per pump
1 per tank
1 per tank
1 per tank
1 per pump
A0550190
A0102396
A0069538
A0102394
- Call Sterling
Parts -
Pump seal and casing gasket
Check your Customer Information Packet for a complete list of
spare parts and part numbers for your SSC Series chilling station.
Page 74 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
9-7 Preventive Maintenance Service
A systematic preventive maintenance program helps avoid costly
down time. Call the Service Department at Sterling to arrange a
schedule of inspections. This service, described in Sterling
Bulletin No. 10-106.3, is tailored to fit your maintenance
requirements.
Inspections include:
þ Check refrigerant suction and discharge pressures.
þ Check safety and operating controls.
þ Check voltage and amperage of all motors.
þ Check all electrical connections.
þ Check quantity of refrigerant.
þ Check compressor oil level.
þ Check lubrication of motor and pump bearings.
þ Check circulating pump operation.
þ Check flow through heat exchangers.
þ Check compressor efficiency.
þ Check noise levels.
þ Check cleanliness of equipment area.
.
SSC Series Central Chilling Stations
Page 75 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
- Notes -
Page 76 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
10
Troubleshooting
Problem
Possible Cause
No power.
Solution
Check main disconnect,
fuses, wiring, and power lead
to unit.
Voltage must be within plus
or minus ten percent (±10%)
of nameplate rating.
Wrong voltage supplied to
unit.
Defective On/Off switch.
Replace switch.
Replace fuse, check
transformer, check wiring for
loose wires, check for shorted
coils on contactors and
solenoids, check crankcase
heater.
Control circuit fuse blown.
Unit does not run.
Defective control transformer. Replace.
Check pump for proper
rotation.
Reset and test motor.
Check that the chiller pump is
running.
Flow switch circuit is open.
Pump motor off on overload.
Unit is off on flow switch or
pressure switch.
Check that all valves are
open.
Check for defective flow
switch or pressure switch.
Lower freeze control setting
to 10°F (6ºC) below the
leaving temperature you
want.
Freeze control set higher than
temperature of liquid in
system.
Air cooled units: Check and
clean air filters. Check
condenser fans for proper
rotation. Check for dirty
condenser. Check for
condenser air obstruction.
Check for tripped motor
overload, blown fuses, or bad
condenser fan motor.
Water cooled units: Check for
water valves turned on.
Check for dirty condenser.
Check water flow through
condenser.
Pump runs,
compressor does not.
High pressure refrigerant
cutout switch contacts open.
SSC Series Central Chilling Stations
Page 77 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Problem
Possible Cause
Solution
Allow time to cool and reset.
Check for high/low voltage.
Voltage must be within plus
or minus ten percent (±10%)
of nameplate rating.
Compressor internal overload
open.
Check for poor compressor
electrical connections.
Check compressor rotation
on scroll compressors.
Compressor contactor
holding coil open.
Repair or replace.
Pump runs,
Defective fan motor.
Fan motor out on overload.
Defective freezestat.
Refrigerant low.
Repair or replace.
Reset and test.
Replace.
Check the refrigerant charge.
Replace.
compressor does not
(cont’d).
Defective fan cycling control.
Sight glass should be clear
while comperssor runs. Call
for service if bubbling or
foaming.
Low refrigerant pressure
switch contact open.
Defective pump motor
interlock to compressor
control circuit.
Repair or replace.
Broken wire in the
compressor control circuit.
Locate and repair.
Lower set point to 10°F (6ºC)
below the leaving water
temperature you want with at
least 15 degrees differential.
Check refrigeration charge;
check refrigerant sight glass
for bubbles or a level in the
glass.
Freezestat control setting is
too high.
Pump runs, compressor
cycles at short intervals.
Refrigerant is too low.
Be sure the antifreeze
mixture protection is right for
the process.
Replace.
Call service to find and repair
the leak. Add refrigerant.
Improper water/glycol
mixture.
Leaving water temperature is
not at set point.
Defective freezestat control.
Refrigerant charge is low.
Check for partially closed
valves etc. Be sure all lines
are properly sized.
Pump pressure is too high.
Restricted water flow.
Page 78 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Problem
Possible Cause
Solution
Verify proper rotation; if
incorrect, see Changing
Rotation Direction on Page
25 for more information.
Clean the system. You may
also have to pull the pump
and inspect the impeller.
Check for foam in the water
circuit; add anti-foam if
needed.
Isolate evaporator, thaw out,
check for leaks. Check
coolant solution. Coolant
solution should be good for at
least 10ºF (6ºC) below
leaving water temperature.
Clean air filters, clean
condenser, check water flow.
Check superheat on
expansion valve.
Pump is running in reverse.
Pump pressure is too low.
Check for foreign matter.
Evaporator frozen.
Process water pressure low,
pressure at pump high.
Restricted condenser air flow.
Refrigerant not feeding.
Make sure that coolant
mixture protection is right for
the process.
Backflush and clean
evaporator.
Improper water/glycol
solution.
Unit runs continuously, but
not enough cooling
power.
Poor heat transfer in
evaporator.
Unit low on refrigerant.
Low water flow through
evaporator.
Call service.
Increase flow to design flow
of 2.4 gpm/ton.
Inefficient compressor.
Unit under-sized for
application.
Call service.
Call sales representative.
.
SSC Series Central Chilling Stations
Page 79 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Notes
Page 80 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
I
Index
Water-Cooled Condenser
Connections, 23
High Pressure Cutout, 30
Lead-lag Compressors, 27
Lead-Lag Pumps, 27
Low Pressure Cutout, 30
Refrigeration Circuit, 28
Shipping damages, 15
Shipping information, 15–17
Incomplete shipment, 16
Incorrect shipment, 16
Returns, 16
Shipping damages, 15
Uncrating, 17
Unpacking and inspection, 15
Specifications
Alarms
Advanced Controls, 68
Standard Controls, 53
Available options, 9
Location considerations, 19
Makeup Valve Maintenance, 74
Models covered, 8
Motors
Checking Motor Direction, 25
Chiller Pumps
Advanced Controls, 64
Chiller Shutdown, 38
Circuit Alarm Sequence, 27
Compressor Lead-Lag, 27
Compressor Staging Sequence,
27, 31
Condenser Maintenance, 73
Copyright information, 2
Checking Direction, 25
Necessary documents, 7
Operating Compressors
Advanced Controls, 60
Standard Controls, 46
Options, 9
SSCR, 13
SSCR Condensers, 14
SSCW, 12
Standard Controls Touchscreen,
44, 58
Determining Flow Rate, 38
Disclaimer information, 2
Piping Considerations, 21
Process Water Connections, 21
Pump Lead-Lag, 27
Pump Seal Maintenance, 74
Pump Tank Piping Connections,
22
Standard features, 8
Startup Checklist, 33–39
Chiller Shutdown, 38
Determining Flow Rate, 38
Introduction, 33
Electrical connections, 19
Electrical wiring schematics, 20
Evaporator Maintenance, 74
Remote Air-Cooled, 35
Remote Air-Cooled Startup,
37
Freezestat Control, 28
SSCR Condenser
Specifications, 14
Galvanic Corrosion
Considerations, 23
General information
Available options, 9
Models covered, 8
Necessary documents, 7
Standard features, 8
Graphic Panel Devices, 41
Indicator Lights and Control
Switches, 41
SSCR drawing, 13
SSCR specifications, 13
SSCW drawing, 11
SSCW specifications, 12
Remote Air-Cooled Condenser
Installation, 24
Remote Air-Cooled Startup, 37
Remote Air-Cooled Startup
Checklist, 35
Water Cooled, 33
Water Cooled Startup, 35
System Temperatures
Advanced Controls, 71
Troubleshooting, 73–75
Uncrating, 17
Unpacking and inspection, 15
Using the Advanced
Touchscreen Interface, 57–72
Alarms, 68
Returns, 16
Revision number, 2
Routine Maintenance, 73–75
Condensers, 73
Incomplete shipment, 16
Incorrect shipment, 16
Installation information, 19–25
Checking Motor Direction, 25
Connection Sizing
Chiller Pumps, 64
Getting Started, 59
Introduction, 57
Evaporators, 74
Lubrication, 73
Makeup Valve, 74
Pump Seals, 74
Operating Chiller
Considerations, 23
Electrical connections, 19
Galvanic Corrosion
Compressors, 60
System Temperatures, 71
Using the Standard Touchscreen
Interface, 44, 43–56, 58
Alarms, 53
Safety considerations, 3
Sequence of Operation, 25–31
Alarms, 27
Considerations, 23
Location considerations, 19
Piping Considerations, 21
Process Water Connections,
21
Chilled Water Circuit, 28
Chilled Water Manifold, 31
Compressor Staging, 27
Condenser Water Manifold,
31
Getting Started, 45
Introduction, 43
Operating Chiller
Remote Air-Cooled
Compressors, 46
Condensers, 24
Tank Piping Connections, 22
Water Treatment
Control Nipple, 31
Control Probe, 31
Flow Switch, 30
Freezestat Control, 28
Water Connection Sizing
Consideration, 23
Water Cooled Startup, 35
Considerations, 23
SSC Series Central Chilling Stations
Page 81 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Cooled Startup Checklist,
33
Water Treatment
Water-Cooled Condenser
Connections, 23
Considerations, 23
Page 82 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Notes
SSC Series Central Chilling Stations
Page 83 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Notes
Page 84 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Notes
SSC Series Central Chilling Stations
Page 85 of 86
Download from Www.Somanuals.com. All Manuals Search And Download.
Parts Department
[
]
[262]
Call toll-free 7am–6pm CST 800 423-3183 or call 641-8653
The Parts Department at Sterling is ready to provide the parts to keep your systems up and running. Sterling
replacement parts ensure operation at design specifications. Please have the model and serial number of your
equipment when you call. Consult the Customer Parts List included in your information packet for replacement part
numbers.
Service Department
[
]
[262]
[800]
Call toll-free 8am–5pm CST 800 423-3183 or call
Emergencies after 5pm CST, call
641-8600
423-3183
Sterling has a qualified service department ready to help. Service contracts are available for most Sterling products.
Sales Department
[262]
Call
641-8600 Monday–Friday, 8am–5pm CST
Sterling products are sold by a world-wide network of independent sales representatives. Contact our Sales
Department for the name of the sales representative nearest you.
Contract Department
[262]
Call
641-8600 Monday–Friday, 8am–5pm CST
Let Sterling install your system. The Contract Department offers any or all of these services: project planning; system
packages including drawings; equipment, labor, and construction materials; and union or non-union installations.
Sterling
2900 S. 160th Street
New Berlin, WI 53151
[262]
[262]
641-8653
641-8610 · Fax
Page 86 of 86
SSC Series Central Chilling Stations
Download from Www.Somanuals.com. All Manuals Search And Download.
|