FORCE 90
90% EFFICIENT
Power-Vent Commercial Gas Water Heater
The 50-gallon, 76,000 BTU Force 90 light-duty commercial gas water heater is equipped with a fully submerged, spiral-shaped condensing heat
exchanger. This design provides much greater heat transfer surface than a standard straight flue tube, resulting in 90% thermal efficiency and
higher hot water output than comparable 80% efficient water heaters. With 22" diameter, the 50-gallon Force 90 can be installed in less space than
a 75-gallon unit and delivers greater recovery and lower operating costs.
Power-Vent Design for Installation Versatility
• Modular blower, with 120 volt, 60Hz electrical system (5 amps or less), 6-foot cord with
standard 3-prong connector
• Combined horizontal and vertical vent runs terminating through outside wall,
using Schedule 40 PVC pipe as follows:
- 2" pipe allows vent runs up to 25 equivalent feet
- 3" pipe allows vent runs up to 65 equivalent feet
- 4" pipe allows vent runs up to 128 equivalent feet
• Supplied with PVC pipe and elbows to connect heat exchanger outlet to blower,
including condensate elbow and drain
• PVC Vent Attenuation Assembly (VAA) supplied to help ensure extra-quiet operation
Side-Mounted Taps for Recirculating Systems
• Hot and cold “side taps” allow Force 90 to be used for “combination” systems
for water heating plus space heating, radiant floor heating or other applications
requiring a recirculating hot water loop
• Plugs for recirculating taps are factory installed
Intelli-Vent®* Gas Control with Silicon Nitride Hot Surface Ignitor
• Premium-grade hot surface ignitor eliminates standing pilot
• Electronic circuitry provides superior system diagnostic capabilities plus extremely
precise temperature control
• 180°F maximum temperature setting
Glass Lined Tank with Two Magnesium Anode Rods
• Provides superior protection against corrosion
• Glass lining protects all “water side” tank surfaces plus inside of internal heat
exchanger exposed to condensate
Low-NOx Green Choice® Burner
• Reduces NOx emissions up to 33%, complies with Southern California and Texas
requirements
PEXAN™ Diffuser Dip Tube
• Helps reduce lime and sediment buildup, maximize hot water output
• PEXAN cross-link polymer withstands long-term exposure to temperatures up to 400°F
Factory-Installed Temperature and Pressure Relief Valve
Maximum Hydrostatic Working Pressure: 150 psi
Meets ASHRAE/IESNA 90.1-1999
• Design-certified by UL (Underwriters Laboratories) according to ANSI Z21.10.3-CSA4.3
standards governing storage-type water heaters
Three-Year Limited Tank Warranty
• Consult written warranty shipped with water heater or contact State for complete
warranty information
* Intelli-Vent is a registered trademark of the Emerson Electric Company
FPoHr AOddNitEion8al0Te0ch-n3ic6al5In-f0or0m2at4ion,
State Industries, Inc.
500 Tennessee Waltz Parkway, Ashland City, TN 37015
Page 1 of 2
SCGSS00806
Download from Www.Somanuals.com. All Manuals Search And Download.
™
FORCE 90
90% EFFICIENT
Power-Vent Commercial Gas Water Heater
SPECIFICATIONS
RECOVERY – GALLONS
BTU
PER HOUR
TANK
SIZE
SHIPPING
WEIGHT
LBS.
MODEL
NUMBER
INPUT
PER
AT DEGREE RISE
GALLONS
40°F
22°C
100°F
56°C
140°F
78°C
HOUR
SHE50 76NE
76,000
50
206
83
59
210
Manifold Pressure: 4.0 inches n.c. (.99 kPa); All models–Maximum Supply Pressure: 14 inches w.c. (3.48 kPa)
Minimum Supply Pressure Natural Gas: 5.0 inches w.c. (1.24 kPa); Minimum Pressure must be maintained under both load and no-load (static and dynamic) conditions
DIMENSIONS
SHE50 76NE
A
B
C
D
E
F
G
H
J
K
INCHES
70-5/8
68-1/4
52
21
9-1/8
12
22
8
15-3/4
27
Top inlet and outlet: 3/4" male NPT
Side inlet and outlet: 3/4" female NPT
Gas inlet: 1/2" NPT
INLET (L)
OUTLET(L)
SIDE OUTLET
T & P VALVE
(H)
ANODE
(K)
HOT
COLD
(A)
(B)
(J)
(G)
DIAMETER
(C)
TOP VIEW
SIDE INLET
THERMOSTAT
* INSTALL IN ACCORDANCE WITH LOCAL CODES
DRAIN
VALVE
(D)
(E)
(F)
FRONT VIEW
SUGGESTED SPECIFICATION
(Natural or Propane) gas water heater(s) shall be State Force 90 model # SHE50 76NE, with 90% thermal efficiency, a storage capacity of 50 gallons, an input rating of 76,000
BTUs per hour, a recovery rating of 83 gallons per hour at 100ºF rise and a maximum hydrostatic working pressure of 150 psi. Water heater(s) shall be of power-vent design,
using 2", 3" or 4" PVC pipe for horizontal and/or vertical vent runs. Water heater(s) shall have: 1: Seamless, glass lined steel tank construction and a spiral-shaped heat
exchanger placed entirely inside the tank, which shall be glass lined on the flue gas side to protect against acidic condensate. 2: An Intelli-Vent gas control system with silicon
nitride hot surface ignitor. 3: A 3-year limited warranty against tank leaks. Water heater(s) shall meet or exceed ASHRAE/IESNA 90.1-1999, and be design-certified by UL
(Underwriters Laboratories) according to ANSI Z21.10.3-CSA4.3 standards governing storage tank water heaters.
For complete information on limited warranties, consult written warranty,
or contact the State Customer Care Center, 1-800-365-0024.
State Industries, Inc. reserves the right to make product changes or improvements without prior notice.
FPoHr AOddNitEion8al0Te0ch-n3ic6al5In-f0or0m2at4ion,
State Industries, Inc.
500 Tennessee Waltz Parkway, Ashland City, TN 37015
Page 2 of 2
SCGSS00806
SWHC-111787-10M
© 2006 State Industries, Inc.
Printed in U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Soleus Air Refrigerator JC 128E User Manual
Sony Camera Lens SEL 1018 User Manual
Sony Car Stereo System CDX GT828U User Manual
Sony Mouse PCGA UMS3 User Manual
Sony MP3 Player ZS YN7 User Manual
SoundCraft Power Supply CPS250 User Manual
SSD COMPANY LIMITED Computer Drive 637f User Manual
Stiga Lawn Mower 13 2557 13 User Manual
Sunbeam Coffee Grinder EM0415 User Manual
Sunpentown Intl Air Conditioner WA 7500M User Manual