Spectrum Brands Power Supply 72A 190BQREM Series User Manual

27-0027-0111  
June 2, 2008  
Rev-01  
Installation and Operation  
Manual  
72A-196BAREM Series  
72A-190BQREM Series  
3-Phase Power Monitoring and  
Distribution Unit  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27-0027-0111  
Installation and Operation Manual  
Introduction & Safety Information  
The Spectrum Control PDU is an AC power distribution unit designed to  
distribute power for up to eighteen (18) AC loads. The PDU distributes 3  
phase power to six individual, over current protected, output banks. The  
unit has multiple alarm capabilities and includes an audible alarm circuit.  
Voltage and current are monitored and displayed locally on a liquid crys-  
tal display and remotely through a LAN connection. Operation/control is  
accomplished by use of 16A breaker actuators.  
Introduction  
This product complies with FCC, CE, TUV, UL60950-1 and IEC60950  
requirements.  
LCD – Liquid Crystal Display  
LED – Light Emitting Diode  
Related Terms  
LL – Lower Limit  
PDU – Power Distribution Unit.  
BANK – Any power source entering a PDU that is then distributed to an  
output.  
UL – Upper Limit  
Manual Conventions  
The following actions should be taken when these symbols are present in  
various instructions throughout the manual:  
Symbol  
Action  
Example  
Click on the items contained within these symbols <Start>  
with your mouse.  
< >  
Press all keys that are contained within these brack- [Ctrl]  
ets.  
[ ]  
Type all characters that are placed between quota-  
tions  
“1234”  
“ ”  
This installation and operation manual contains information about the  
Power Distribution Unit and basic installation instructions. The person  
installing or integrating the PDU into an electronic system must be sup-  
plied with this manual and read it to become familiar with the installation  
precautions. Spectrum Control, Inc. cannot be held liable for any dam-  
age to persons or property if the safety information in the installation and  
operation manual is not followed.  
Safety Information  
If the safety information is not observed, personnel could be put at risk.  
Only authorized personnel who have been properly trained may operate  
the device. There are no user serviceable parts inside. Therefore, any  
modifications made to the unit by any organization or persons other than  
the factory are not permitted.  
The general regulations governing the use of electricity in the country in  
which the device or integrated system is installed must be observed.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
27-0027-0111  
Installation and Operation Manual  
Technical Specifications  
Global  
Domestic  
Input  
Power Entry  
Connector  
IEC 309, 4pole, 5 wire, 32A, NEMA L21-30P  
WYE connected  
5 pin, Delta connected  
Nominal Input  
Voltage  
3 400/230VAC ±10%  
3 208/208VAC ±10%  
Input Frequency 50 – 60 Hz  
Input Current 72A maximum  
50 – 60 Hz  
41.6A maximum  
Output  
Global  
Domestic  
(18) IEC C13  
Outlet Connectors (18) IEC C13  
Load Current per 16A maximum  
Bank  
13.9A maximum  
Load Current per 10A maximum  
Output Connector  
10A maximum  
Load Current per 72A maximum  
PDU  
41.6A maximum  
Operating temperature: 0-55°C (32-131°F)  
Operating humidity: 0-95% (non condensing)  
Operating elevation: 0-10,000 ft (0-3000 m)  
Environmental  
Unit height: 0U, 55.5 inches (141 cm)  
Unit width: 1.75 inches (4.45 cm)  
Unit depth: 5.2 inches (13.3 cm)  
Unit weight: 32.5 pounds (14.74 kg)  
Cord length: 10 feet (Approx. 3 m)  
Rack mountable  
Physical  
Finish: Black powder coat  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
27-0027-0111  
Installation and Operation Manual  
Declaration of Conformity  
Manufacturer’s Name:  
Manufacturer’s Address:  
Spectrum Power Management Systems, a Spectrum  
Control Business  
1900 West College Avenue  
State College, PA 16801  
Declares that the product:  
Product Name:  
3-Phase Power Monitoring and Distribution Unit  
Model Number:  
72A-196BAREM-01  
72A-190BQREM-01  
Conforms to the following Product Specifications:  
Safety:  
UL 60950-1 File E149758-A8 Volume X3, First Edition;  
CSA C22.2 No. 60950-1-03, First Edition; IEC 60950-  
1, First Edition.  
Product Category: NWGQ-INFORMATION TECH-  
NOLOGY EQUIPMENT INCLUDING ELECTRICAL  
BUSINESS EQUIPMENT - COMPONENT  
Emissions per:  
EN 55022 (1998): Class A  
FCC P.15  
EMC:  
ANSI C63.4  
Immunity per :  
EN 55024  
EN 61000-4-2: Criteria B  
EN 61000-4-3: Criteria A (@ 10V/m)  
EN 61000-4-4: Criteria B  
EN 61000-4-5: Criteria B  
EN 61000-4-6: Criteria A (Power @ 10V/m)  
Chuck Drew  
Lead Engineer  
Mike Esposit  
Quality Engineer  
Spectrum Control, Inc.  
Power Management Systems  
1900 West College Avenue  
State College, PA 16801  
814-272-2700  
11/16/2007  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
27-0027-0111  
Installation and Operation Manual  
Connections and Installation  
Locate PDU in dry area.  
Operating  
Environment  
Rack Mount in equipment rack using mounting brackets.  
Restricted Access Location not required.  
This PDU relies on protective devices in the building installation  
for short circuit and over current protection.  
Elevated Operating Ambient- If installed in a closed or multi-unit  
rack assembly, the operating ambient temperature of the rack  
environment may be greater than room ambient. Therefore,  
consideration should be given to installing the equipment in an  
environment compatible with the maximum ratings of the product.  
Reduced Air Flow- Installation of the equipment should be such  
that the amount of airflow required for safe operation of the  
equipment is not compromised.  
Mechanical Loading- Mounting of the equipment in the rack should  
be such that a hazardous condition is not achieved due to uneven  
mechanical loading.  
Circuit Overloading- Consideration should be given to the  
connection of the equipment to the supply circuit and the effect  
that overloading the circuits might have on over current protection  
and supply wiring. Appropriate consideration of equipment  
nameplate ratings should be used when addressing this concern.  
Reliable earthing of equipment should be maintained. Particular  
attention should be given to supply connections other than direct  
connections to the branch circuit (e.g. use of power strips).  
Consult the local electrical code for additional information.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
27-0027-0111  
Installation and Operation Manual  
Connections and Installation  
Depress rocker handle of all circuit breakers to “off” position.  
Electrical  
Connections  
Example: Breaker Off  
Example: Breaker On  
Connect input supply cord to a grounded power source rated for  
the input voltage and current of the PDU.  
Connect equipment to AC output connectors. Continuous  
current draw for all connected units must not exceed the current  
rating per output.  
CAUTION:  
Power source for PDU must be properly grounded.  
Total current for all connected units must not exceed the  
current rating per input.  
Current must not exceed the current rating per output.  
Do not conduct any DWV testing greater than 300 VAC.  
Input cord and output connections are located on the front side of the  
unit. Pluggable mating connectors are not supplied with the unit.  
Input and Output  
Connections  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
27-0027-0111  
Installation and Operation Manual  
Connections and Installation  
LAN Module and  
Communications  
RJ45  
LAN Connection  
The LAN Module provides an interface between a computer  
LAN Module  
Interface  
network and the power distribution unit using the front RJ-45 jack.  
Communications between the PDU and a computer can take place via a  
Telnet session or SNMP manager. If you are connecting the PDU directly  
to a PC without a router, a crossover cable is required. The module oper-  
ates at 10/100MB/sec via an Ethernet communication for both of these  
configurations and uses a RJ45 connector for the interface jack.  
Crossover Cable  
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
LAN LED Status  
LED  
Description  
Guide  
Top left  
(Yellow)  
Network link status:  
Off - no link has been detected.  
On - a link has been detected.  
Top right  
(Green)  
Serial port activity/Network activity:  
Off - the serial channel is idle.  
Blinking - serial data is transmitted or received.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
27-0027-0111  
Installation and Operation Manual  
Connections and Installation  
The LAN module consists of integrated hardware and a network agent  
software program. These components provide the ability to configure,  
control, and monitor aspects of multiple units using a standard web  
browser. The network interface can operate using Telnet and SNMP.  
The LAN module is configured at the factory to an IP Address of  
192.168.1.110 and subnet mask of 255.255.255.0. A default gateway ad-  
dress of 192.168.1.1 and a SNMP trap address of 192.168.1.200 are also  
provided.  
The Login dialog box requests a username and password. The factory  
default username and password are “root” and “1234”, respectively. This  
username has full privileges to set up, maintain, and control the unit.  
Other Factory Defaults:  
SNMP  
Enabled  
SNMP Community Name Public  
Telnet Setup  
FTP Download  
Web Server  
Enabled  
Enabled  
Disabled - Can enable with  
future Firmware Update  
Web Setup  
ECHO  
Disabled  
Disabled  
The LAN module supports three IP assignment methods: Static IP ad-  
dress, DHCP, and Auto-IP. If a static address is enabled, it will be used.  
If a static address is not enabled, and Auto-IP is enabled, it will be used  
to generate an address ONLY if DHCP is disabled, or if DHCP is enabled  
and a DHCP server has not responded to the DHCP query. If both are  
enabled, Auto-IP has assigned an address, and then a DHCP server  
responds. The Auto-IP address will be discarded and the DHCP address  
will be used.  
LAN Module IP  
Address, DHCP, and  
Auto IP  
AutoIP allows the unit to obtain an address in a network that does not  
have a DHCP server. AutoIP assigns a random valid address to the LAN  
module in the range of 169.254.x.x to 169.254.x.x where x is between 0  
and 255 and a Netmask of 255.255.0.0.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
27-0027-0111  
Installation and Operation Manual  
Connections and Installation  
The discovery tool “digi_dev_disc.exe” has the following:  
1. “Configure Network Settings” is to configure the IP/Subnet/Gateway.  
2. “Restart Device” is to reboot the PDU after assigning the new network  
configuration .  
Device Discovery  
3. “Refresh View” is to search again.  
4. “Open Web Interface” is to launch the web page.  
This program is part of the PDU tools and should be placed in  
C:\Program Files  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10  
27-0027-0111  
Installation and Operation Manual  
Connections and Installation  
Once the IP address is assigned, you should test the IP address  
configuration to be sure it works as configured.  
Testing the IP  
Address  
Configuration  
Prerequisite  
This procedure assumes that you have configured the device server with  
an IP address.  
Procedure  
1.  
2.  
Access the command line of a PC or other networked device.  
Issue the following command: ping ip-address (where ip-address  
is the address you assigned to the device server).  
Example:  
ping 192.168.1.110  
A reply should be returned.  
Setting the Telnet configuration password prevents unauthorized access  
of the setup menu via a Telnet connection to port 9999. The password  
is limited to 32 characters. Option 7 allows the user to change the telnet  
configuration password.  
Telnet Configuration  
Password  
LAN Module  
Configuration Using  
a Telnet Connection  
To configure the LAN Module over the network, establish a Telnet  
connection to port 9999. From the Windows Start menu, click Run and  
type the following command, where x.x.x.x is the IP address and 9999 is  
the LAN Module’s fixed network configuration port number.  
telnet x.x.x.x 9999  
Note: Be sure to include a space between the IP address and 9999.  
The default IP Address is 192.168.1.110, so the command should look  
like “telnet 192.168.1.110 9999”. At login, type “root” for the username  
and “1234” for the password. This command will launch the configuration  
menu. After the first sentence appears, press [Enter] to go into the setup  
mode.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
27-0027-0111  
Installation and Operation Manual  
Connections and Installation  
Menu option 8 restores all PDU and LAN module defaults back to the  
factory settings. This command will ensure that both the LAN module  
and internal PDU microprocessor are returned to identical  
communication settings. PDU with LAN modules should have all configu-  
ration changes made using the LAN module configuration menu selec-  
tions.  
Set PDU and LAN  
Module to Factory  
Defaults  
Items that get restored back to default settings:  
• snmpReadCommunityName  
• snmpRead-WriteCommunityName  
• SNMP TRAP_IP  
• TRAPDSTPORT  
• HTTPPORT  
• USER NAME  
• PASSWORD  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12  
27-0027-0111  
Installation and Operation Manual  
Connections and Installation  
Select 9 to exit the configuration mode without saving any changes, or  
select 10 to exit and save all changes. All values are stored in  
nonvolatile RAM. The LAN Module will automatically reset, but the state  
of the PDU outputs will not be affected.  
Exit Configuration  
Mode  
Run “digi_dev_disc.exe” utility to set up unit’s IP, if necessary. These are  
part of the LAN tools.  
Locate the update file.  
LAN Module Reflash  
Instructions  
A.  
If any network setting(s) on the LAN module are changed, you  
must click <Restart device> to apply the changes.  
Place the update file “image.bin” in C:\release.  
In command window, navigate to C:\release directory.  
Type “ftp <IP Address>”.  
B.  
C.  
D.  
E.  
F.  
Then log-in (User name is “root”, and password default is “1234”.)  
Type “binary” and press [Enter].  
Type “put image.bin” and press [Enter]. **Wait for the  
completion message** Do not interrupt download.  
Type “quit” after the “Transfer Complete” message appears. It may  
take up to 1 minute, including PDU reboot.  
G.  
H.  
In “C:\release\bin”, type “ping <IP Address> -t” until the  
communication is re-established. Press [Ctrl+C] to exit ping.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
27-0027-0111  
Installation and Operation Manual  
Operational Control of PDU  
The unit’s LCD is used to monitor incoming power and configure the  
software. The LCD has two modes of operation: Monitor or Menu. The  
system menu is organized in a top down tree structure. The unit has  
four buttons that are used to navigate through the menu system. The  
buttons are labeled with universal symbols for Menu, Select, Left, and  
Right as shown in the following figure.  
Front Panel Menu  
MENU - Enters the menu system or moves one level up the tree.  
SELECT - Moves one level down the tree or accepts a parameter input.  
LEFT, RIGHT - Moves horizontally through menu items or parameters.  
Alarm Acknowledgment – Silences audible alarm.  
Selecting the MENU button while the unit is in monitor mode will bring  
up the system top level menu. The top level menu contains parameters  
for Alarm Acknowledgement, Incoming Power Peak Readings, Incoming  
Power Limit Settings, and System Configuration.  
Menu Navigation  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14  
27-0027-0111  
Installation and Operation Manual  
Operational Control of PDU  
Menu Tree  
Alarm Acknowledgment  
Incoming Power Peaks  
Incoming Power Limits  
System Configuration  
None  
Minimum Current Channel A  
Maximum Current Channel A  
Minimum Current Channel B  
Maximum Current Channel B  
Minimum Current Channel C  
Maximum Current Channel C  
Minimum Current All Channel Total  
Maximum Current All Channel Total  
Minimum Voltage Channel A  
Maximum Voltage Channel A  
Minimum Voltage Channel B  
Maximum Voltage Channel B  
Minimum Voltage Channel C  
Maximum Voltage Channel C  
Reset All Peaks  
Minimum Current Channel A  
Maximum Current Channel A  
Minimum Current Channel B  
Maximum Current Channel B  
Minimum Current Channel C  
Maximum Current Channel C  
Minimum Current All Channel Total  
Maximum Current All Channel Total  
Minimum Voltage Channel A  
Maximum Voltage Channel A  
Minimum Voltage Channel B  
Maximum Voltage Channel B  
Minimum Voltage Channel C  
Maximum Voltage Channel C  
Monitor Display Mode  
Display Cycle time  
Voltage Calibration Step 1 Chan A  
Voltage Calibration Step 2 Chan A  
Voltage Calibration Step 1 Chan B  
Voltage Calibration Step 2 Chan B  
Voltage Calibration Step 1 Chan C  
Voltage Calibration Step 2 Chan C  
Current Calibration Step 1 Chan A  
Current Calibration Step 2 Chan A  
Current Calibration Step 1 Chan B  
Current Calibration Step 2 Chan B  
Current Calibration Step 1 Chan C  
Current Calibration Step 2 Chan C  
Number of Channels  
Contrast  
Software Rev  
PEAKS - MAX, MIN, RESET  
Selecting PEAKS in the menu system allows the user to view the  
maximum and minimum values that have been recorded for both voltage  
and current for each distribution bank. This feature also gives the user  
the option to reset these values.  
LIMITS - MAX, MIN  
Selecting LIMITS in the menu system allows the user to set the desired  
maximum and minimum values to monitor for each bank. These values  
will be used by the unit as comparison limits while monitoring bank  
voltage and current levels. Decisions concerning minor and major  
alarms will be based on this comparison.  
CONFIG - DISPLAY MODE  
While in Monitor Mode, the unit can display the incoming voltage and  
current readings. The menu system allows the user to select one of  
three display modes: CYCLE, FIXED, and BAR.  
Selecting CYCLE causes the system to cycle the display of channel  
measurements. Measurements will be shown in order of voltage  
channels and then current banks.  
Selecting FIXED turns off the measurement display cycle. Pressing the  
LEFT or RIGHT menu buttons while in FIXED mode moves to the next  
reading in the cycle list.  
In BAR mode, a bar graph is displayed to show all measured bank  
currents at the same time. The values are displayed on a 30 amp scale.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
27-0027-0111  
Installation and Operation Manual  
Operational Control of PDU  
CONFIG - CYCLE TIME  
The CYCLE TIME parameter sets the amount of time to wait before  
displaying the next bank measurement. The parameter can be set to  
FAST, MEDIUM, or SLOW.  
CONFIG - NUMBER OF CHANNELS  
The unit can be configured to work for 1, 2, or 3 power bank devices.  
Note that reducing the number of banks to 1 removes the total current  
monitoring processes.  
CONFIG - CONTRAST  
The CONTRAST feature allows the user to adjust the contrast of the LCD  
screen to a desired level.  
CONFIG – SOFTWARE REV  
Selecting the REV parameter will display the current revision of software  
loaded into the meter.  
CONFIG - METERING CALIBRATIONS  
The unit’s onboard voltage and current monitoring devices require a  
two-step calibration procedure to achieve maximum accuracy. Each  
power bank has adjustable parameters in the menu system for voltage  
and current. This calibration is performed at the factory before shipment.  
Each power bank has four major alarm thresholds that can be adjusted.  
There is an upper and lower limit for input voltage. There is also an  
upper and lower limit for distributed current. An alarm is also signaled  
if the current reaches two minor limits: 80% of upper limit, 90% of upper  
limits.  
Alarm Capabilities  
If a major alarm threshold is surpassed the unit will respond by setting  
the power bank indicator LED to red and setting the audible alarm  
buzzer.  
If a minor alarm threshold is surpassed the unit will toggle the LED  
indicator and audible alarm. The 80% alarm toggles the LED and buzzer  
once per second. The 90% alarm toggles twice per second.  
If an alarm condition exists and the PDU is in monitor mode, the audible  
alarm may be silenced by pressing the Alarm Acknowledge button. If the  
PDU is not in monitor mode and is in the system menu, select the Alarm  
Acknowledge menu item. The audible alarm will remain silenced until  
another alarm threshold is exceeded.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16  
27-0027-0111  
Installation and Operation Manual  
Networking Functions  
The PDU LAN Port supports the Telnet and SNMP networking functions,  
which allow remote monitoring through the network environment. Table  
1 lists the available Telnet commands. Table 2 lists the content of SNMP  
functions – Read/Set/Trap in detail. An SNMP Manager PC Tool is need-  
ed in order to implement the SNMP functions. To implement the Telnet  
and SNMP functions, the device must be configured properly, such as  
assigning a valid IP address or subnet mask by using the recommended  
device discovery tool.  
Introduction  
Telnet always has the higher priority than SNMP with the timeout value of  
30 seconds, which can be adjusted later.  
You can access the PDU by typing “telnet <IP> 10001” and entering the  
username and password (Default username is “root”. Default password is  
“1234”). The telnet session has a 30 second timeout.  
Telnet  
Communication  
A list of commands is in the following table.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
27-0027-0111  
Installation and Operation Manual  
Networking Functions  
telnet <IP Address> 10001 [space before and after address]  
Telnet Commands  
Table 1  
List of Commands:  
Command  
@AACK  
Description  
Response  
Alarm Acknowledgement  
Save settings to EEPROM  
Voltage Bank A  
#AACK  
@SYSF  
#SYSF OK  
#BNKV 120.2  
#BNKV 120.2  
#BNKV 120.2  
#BNKC 22.5  
#BNKC 22.5  
#BNKC 22.5  
#BNKC 65.3  
#MAXV 138  
#MAXV 138  
#MAXV 138  
#MINV 75.0  
#MINV 75.0  
#MINV 75.0  
#MAXV OK  
#MAXV OK  
#MAXV OK  
#MINV OK  
#MINV OK  
#MINV OK  
#BULV OK  
#BULV OK  
#BULV OK  
#BULC OK  
#BULC OK  
#BULC OK  
#BULC OK  
#BLLC OK  
#BLLC OK  
#BLLC OK  
#BLLC OK  
#BULV 135.3  
#BULV 135.3  
#BULV 135.3  
#BULC 22.5  
@BNKV A,?  
@BNKV B,?  
@BNKV C,?  
@BNKC A,?  
@BNKC B,?  
@BNKC C,?  
Voltage Bank B  
Voltage Bank C  
Current Bank A  
Current Bank B  
Current Bank C  
@BNKC T,?  
@MAXV A,?  
@MAXV B,?  
@MAXV C,?  
@MINV A,?  
Total Current on PDU (All banks)  
Read Maximum Voltage Bank A  
Read Maximum Voltage Bank B  
Read Maximum Voltage Bank C  
Read Minimum Voltage Bank A  
Read Minimum Voltage Bank B  
Read Minimum Voltage Bank C  
Reset Maximum Voltage Bank A  
Reset Maximum Voltage Bank B  
Reset Maximum Voltage Bank C  
Reset Minimum Voltage Bank A  
Reset Minimum Voltage Bank B  
Reset Minimum Voltage Bank C  
@MINV B,?  
@MINV C,?  
@MAXV A,0  
@MAXV B,0  
@MAXV C,0  
@MINV A,999.9  
@MINV B,999.9  
@MINV C,999.9  
@BULV A,135.3 Set High Threshold Voltage Bank A  
@BULV B,135.3 Set High Threshold Voltage Bank B  
@BULV C,135.3 Set High Threshold Voltage Bank C  
@BULC A,22.5  
@BULC B,22.5  
@BULC C,22.5  
@BULC T,77.5  
@BLLC A,10.0  
@BLLC B,10.0  
@BLLC C,10.0  
@BLLC T,10.0  
@BULV A,?  
Set High Threshold Current Bank A  
Set High Threshold Current Bank B  
Set High Threshold Current Bank C  
Set High Threshold Current Bank T  
Set Low Threshold Current Bank A  
Set Low Threshold Current Bank B  
Set Low Threshold Current Bank C  
Set Low Threshold Current Bank T  
Read High Threshold Voltage Bank A  
Read High Threshold Voltage Bank B  
Read High Threshold Voltage Bank C  
Read High Threshold Current Bank A  
@BULV B,?  
@BULV C,?  
@BULC A,?  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18  
27-0027-0111  
Installation and Operation Manual  
Networking Functions  
@BULC B,?  
@BULC C,?  
@BULC T,?  
@BLLV A,?  
Read High Threshold Current Bank B  
#BULC 22.5  
#BULC 22.5  
#BULC 77.5  
#BLLV 135.3  
#BLLV 135.3  
#BLLV 135.3  
#BLLC 10.0  
#BLLC 10.0  
#BLLC 10.0  
#BLLC 22.0  
#MAXC 22.5  
#MAXC 22.5  
#MAXC 22.5  
#MAXC 90.0  
#MINC 15.0  
#MINC 15.0  
#MINC 15.0  
#MINC 45.0  
#MAXC OK  
#MAXC OK  
#MAXC OK  
#MAXC OK  
#MINC OK  
#MINC OK  
#MINC OK  
#MINC OK  
Read High Threshold Current Bank C  
Read High Threshold Current Bank T  
Read Low Threshold Voltage Bank A  
Read Low Threshold Voltage Bank B  
Read Low Threshold Voltage Bank C  
Read Low Threshold Current Bank A  
Read Low Threshold Current Bank B  
Read Low Threshold Current Bank C  
Read Low Threshold Current Bank T  
Read Maximum Current Bank A  
@BLLV B,?  
@BLLV C,?  
@BLLC A,?  
@BLLC B,?  
@BLLC C,?  
@BLLC T,?  
@MAXC A,?  
@MAXC B,?  
@MAXC C,?  
@MAXC T,?  
@MINC A,?,  
@MINC B,?  
@MINC C,?  
@MINC T,?  
Read Maximum Current Bank B  
Read Maximum Current Bank C  
Read Maximum Current Bank T  
Read Minimum Current Bank A  
Read Minimum Current Bank B  
Read Minimum Current Bank C  
Read Minimum Current Bank T  
Reset Maximum Current Bank A  
Reset Maximum Current Bank B  
Reset Maximum Current Bank C  
Reset Maximum Current Bank T  
Reset Minimum Current Bank A  
Reset Minimum Current Bank B  
Reset Minimum Current Bank C  
Reset Minimum Current Bank T  
@MAXC A,0  
@MAXC B,0  
@MAXC C,0  
@MAXC T,0  
@MINC A,999.9  
@MINC B,999.9  
@MINC C,999.9  
@MINC T,999.9  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
27-0027-0111  
Installation and Operation Manual  
Networking Functions  
An SNMP-managed network consists of three key components:  
Simple Network  
Management  
Protocol (SNMP)  
1. Managed devices  
2. Agents  
3. Network Management Systems (NMSs)  
A managed device is a network node that contains an SNMP agent and  
that resides on a managed network. Managed devices collect and store  
management information and make this information available to NMSs  
using SNMP. Managed devices, sometimes called network elements, can  
be any type of network based device including this PDU.  
The agent running in this PDU has local knowledge of measurement  
information and translates that information into a form compatible with  
SNMP.  
An Network Manager system executes applications that monitor and con-  
trol managed devices. One or more NMSs may exist on any managed  
network.  
The model on the following page illustrates the basic elements of an  
SNMP-managed network.  
SNMP-Managed Network  
NMS  
User  
Interface  
Network  
Managment  
Application  
SNMP  
SNMP  
SNMP  
Agent  
Agent  
MIB  
Agent  
MIB  
MIB  
Managed  
Device  
Managed  
Device  
Managed  
Device  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
20  
27-0027-0111  
Installation and Operation Manual  
Networking Functions  
Interactions between the NMS and managed devices can be any of four  
different types of commands: reads, writes, traversal operations, and  
traps.  
Reads - To monitor managed devices, NMSs read variables main-  
tained by the devices.  
Writes - To control managed devices, NMSs write variables stored  
within the managed devices.  
Traversal operations - NMSs use these operations to determine  
which variables a managed device supports and to sequentially  
gather information from variable tables (such as IP routing tables) in  
managed devices.  
Traps - Managed devices use traps to asynchronously report certain  
events to NMSs.  
Accessing the SNMP interface requires a tool, such as a network man-  
agement station. The management station relies on an agent at a device  
to retrieve or update the information at the device, including device con-  
figuration, status, and statistical information. This information is viewed  
as a logical database, called a Management Information Base (MIB). MIB  
modules describe MIB variables for a variety of device types and com-  
puter hardware and software components.  
Accessing the SNMP  
Interface  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
27-0027-0111  
Installation and Operation Manual  
Networking Functions  
Key SNMP Settings  
SNMP read community name  
SNMP read/write name  
“public”  
“public”  
You can access the SNMP settings using Telnet <unit IP address> 9999.  
The default username and password is “root” and “1234”, respectively.  
Option 0 thru 3 on the Setup page:  
Option 0 - Up to three SNMP trap addresses may be entered.  
Option 1 - Read Community Name [default = “public”]  
Option 2 - Read-Write Community Name [default = “public”]  
Option 3 - SNMP Trap Destination Address  
SNMP Security  
Authorization: Changing public and private community  
names is recommended to prevent unauthorized access to  
the device.  
You can disable SNMP set commands to make use of  
SNMP read-only.  
SNMP MAX and MIN  
Data  
MAX and MIN data fields are calculated by the PDU.  
To reset a MAX field, write a “0” (zero) to the data location.  
To reset a MIN field, write “999” to the data location.  
The data location will then refresh with new calculated values.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
22  
27-0027-0111  
Installation and Operation Manual  
Networking Functions  
Table 2  
SNMP v2 Functions  
SNMP v2 Functions  
Variables  
SNMP v2 MIB  
READ & TRAP  
READ & TRAP  
READ & TRAP  
READ & TRAP  
READ & TRAP  
READ & TRAP  
READ & TRAP  
R/W  
Voltage Bank A  
Voltage Bank B  
Voltage Bank C  
Current Bank A  
Current Bank B  
Current Bank C  
Total Current on PDU (All banks)  
Maximum Voltage Bank A  
Maximum Voltage Bank B  
Maximum Voltage Bank C  
Minimum Voltage Bank A  
Minimum Voltage Bank B  
Minimum Voltage Bank C  
High Threshold Voltage Bank A  
High Threshold Voltage Bank B  
High Threshold Voltage Bank C  
High Threshold Current Bank A  
High Threshold Current Bank B  
High Threshold Current Bank C  
High Threshold Current Bank T  
Low Threshold Current Bank A  
Low Threshold Current Bank B  
Low Threshold Current Bank C  
Low Threshold Current Bank T  
Low Threshold Voltage Bank A  
Low Threshold Voltage Bank B  
Low Threshold Voltage Bank C  
Maximum Current Bank A  
Maximum Current Bank B  
Maximum Current Bank C  
Maximum Current Bank T  
Minimum Current Bank A  
Minimum Current Bank B  
Minimum Current Bank C  
Minimum Current Bank T  
Software Revision  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
READ  
READ  
READ  
TRAP  
PDU Model  
Number Of Banks  
Serial Communication Timeout  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23  
27-0027-0111  
Installation and Operation Manual  
Networking Functions  
This section addresses the loading and compiling of MIBS into Network  
Management Systems (NMS). Alternatively, you can consult the docu-  
mentation of other NMS on MIB loading and compilation. Below are the  
instructions for HP OpenView and IBM NetView, but you should still con-  
sult HP or IBM documentation, as the products may change.  
General MIB Usage  
From the GUI of HP OpenView or IBM NetView  
Follow these steps to load the PDU MIBt:  
Copy the files into the directory /usr/OV/snmp_mibs of the network man-  
agement station.  
This is the default directory where HP OpenView and IBM NetView look  
for MIB documents. If you place them elsewhere, specify the explicit path  
names in the loadmib graphical interface.  
Set the permissions so that you have read access to the MIBs.  
From the GUI menu, choose Options > Load/Unload MIBs.  
Follow the instructions in the platform documentation, to compile or load  
the PDU MIB.  
From the Command Line Interface of HP OpenView or IBM NetView  
Issue the /opt/OV/bin/xnmloadmib -load filename command, to load the  
MIB file.  
There is no need to compile MIBs for use with Vista Infrastructure Moni-  
toring (VIM) [formerly Enterprise Device Manager]. However, there are a  
few steps to take before VIM can communicate with a device, and these  
are mostly the same for every device.  
MIB Use With Vista  
Infrastructure  
Monitoring  
1.  
2.  
The device must be configured with network settings including an  
IP address, subnet mask, and default gateway.  
The device must be configured to allow the VIM software to be an  
SNMP manager. This usually involves entering the IP address of  
the VIM server into the device’s NMS list or device access list.  
3.  
The device must be configured to send traps to the VIM server.  
This involves entering the IP address of the VIM server into a  
table along with the SNMP community string.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
24  
27-0027-0111  
Installation and Operation Manual  
Maintenance & Warranty  
There are no user serviceable parts inside the PDU. In the event there is  
an electronic problem with the unit, please contact the factory.  
Maintenance and  
Replacement parts  
Under normal use and specified operation conditions the PDU is warrant-  
ed from the day of delivery for a period of three years. During this pe-  
riod, if the product should fail, the device can be sent back to the factory  
for repair or replacement at the discretion of Spectrum Control.  
Warranty  
If the device is misused or tampered with in any way, the warranty be-  
comes invalid. SCI is not liable for any damage caused by products that  
have been modified or serviced by other parties.  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
27-0027-0111  
Installation and Operation Manual  
PDU Front Panel  
IEC C13 Outlets  
20A Circuit Breakers  
SCI P/N: 72A-196BAREM Series  
72A-190BQREM Series  
Date: 6/02/2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
26  

Sharp Microwave Oven R 1505L User Manual
SIIG Computer Hardware 4110 User Manual
Snapper Lawn Mower ZF2100DKU ZF2300GKU ZF5200M ZF6100M User Manual
Sony CD Player CDP XE200 User Manual
Sony DVR DCR IP5 IP7BT User Manual
Sony Headphones MDR NC200D User Manual
Sony VCR GV D200E User Manual
Sterling Refrigerator 30RA010 055 User Manual
Swisher Lawn Mower ZT13536 ZT17542B ZT20050 User Manual
T+A Elektroakustik Stereo Amplifier P 10 User Manual