				Features   
					/ 
					/ 
					AV Air Movement System   
					n Streamlined eased inlet fan cylinder   
					assures full area, low turbulence airflow   
					through the cylinder.   
					n Heavy duty aluminum alloy fan–   
					adjustable pitch blades.   
					n 7.5 hp and larger fans are driven by a   
					high quality, solid backed, multi-grooved   
					neoprene and polyester v-belt thru a   
					corrosion resistant aluminum alloy fan   
					sheave.   
					n Heavy duty, self-aligning, grease   
					lubricated roller bearings selected with   
					an L design life of 50,000 to 100,000   
					10   
					hours support the fan and shaft.   
					n TEFC fan motor, 1.15 service factor,   
					variable torque design, specially insulated   
					for cooling tower duty.   
					n The AV air movement system is   
					guaranteed against failure for a period   
					of five full years from date of shipment.   
					Includes fan, fan shaft, bearings and   
					mechanical equipment support.   
					AVWater Distribution System   
					AV Structure   
					n Gravity flow distribution system. Easy, nonrestrictive   
					maintenance. Basin covers are standard.   
					n Crossflow configuration — easier and safer to inspect,   
					service and maintain.   
					n Marley SpiralTarget polypropylene nozzles for   
					consistent, predictable water distribution.   
					n G-235 heavy galvanized steel. Also available in 300   
					stainless steel.   
					n Marley MX thermoformed PVC film fill is suspended   
					from the upper tower structure by heavy galvanized   
					steel support members providing clearance between fill   
					and sloping self-cleaning collection basin floor for easy   
					basin cleaning. Integral eliminators and louvers keep   
					circulating water confined to fill over a wide range of air   
					flow rates.   
					n Factory-assembled modules, including fan cylinders   
					— makes final field installation hassle-free.   
					n Large Access Doors—the generous plenum region in   
					the AV tower is nonconfining, permitting quick visual   
					inspection of cold water basin, internal structure, drift   
					eliminators and mechanical equipment.   
					Note: For economical transportation, AV towers are also   
					available unassembled and crated for export.   
					For Safety Reasons—always shut down and lock out the   
					fan motor before entering the plenum.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Optional Equipment and Accessories   
					/ 
					/ 
					Enhance your AV tower installation with options and accessories that will improve the operation, longevity,   
					maintenance, and accessibility of your cooling tower.   
					n 
					n 
					Stainless Steel Distribution Basin   
					Corrosion is usually most aggressive in the   
					hot water distribution basins—stainless steel   
					provides assurance of long, trouble-free service   
					life.   
					External Service Platform   
					Provides easy access to distribution system   
					without increasing installed height of tower.   
					Platform with OSHA guardrails is Factory   
					Mounted, eliminating installation labor cost and   
					time. Field-installed ladder with optional safety   
					cage for easy access.   
					n 
					Marley Control System Package   
					Factory-wired, factory-installed, factory-tested   
					control center in NEMA 3R enclosure mounted   
					on tower casing near access door. Complete   
					with thermostat controller for single or two-   
					speed motors to maintain chosen cold water   
					temperature.   
					n 
					Stainless Steel Collection Basin   
					All collection basin parts in the wetted area—   
					including structural members projecting in the   
					basin, assembly and attaching hardware, and   
					all basin options, are heavy-gauge Series 300   
					stainless steel.   
					n 
					InletTrash Screens   
					Factory-installed, U-edged, galvanized wire mesh   
					screens work in concert with the internal cellular   
					louvers.   
					The AV Engineering Data and Specifications   
					Manual AV-TS provides engineering sche-   
					matics, data, and information necessary for   
					initial tower layout and details the tower in   
					the form of specification language, providing   
					technical as well as common-sense informa-   
					tion on the importance of your specifica-   
					tions. Available on the web at spxcooling.   
					com or see your Marley sales representative   
					for a copy.   
					The Marley UPDATE™ web-based application   
					software provides model selections perfectly   
					tuned to your cooling water system. Func-   
					tions include model selection, specifications,   
					model optimization, performance curves,   
					engineering data, and free cooling applica-   
					tions. Available to both registered customers   
					and guests at spxcooling.com.   
					If we can help in any way, feel free to call.   
					To find the Marley representative nearest   
					you call 1 800 462 7539 or check the web at   
					spxcooling.com.   
					7401 WEST 129 STREET   
					OVERLAND PARK, KANSAS 66213   
					UNITED STATES   
					913 664 7400   
					
					spxcooling.com   
					In the interest of technological progress,   
					all products are subject to design and/or   
					material change without notice.   