Smart-UPS® RT
Uninterruptible Power Supply
SURTD 3000/5000 VA 200-240 VAC
Tower/Rack-Mount 3U
English
2010 APC by Schneider Electric. APC, the APC logo, Smart-UPS and PowerChute are owned by Schneider Electric
Industries S.A.S., American Power Conversion Corporation, or affiliated companies. All other trademarks are the property of
their respective owners.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring and Connecting the UPS
5000 VA XLI MODELS ONLY: HARDWIRING INSTRUCTIONS
•
•
•
•
Wiring must be performed by a qualified electrician.
Install a high magnetic 30/32 A utility circuit breaker.
Adhere to all national and local electrical codes.
Use #10 AWG gauge (5 mm2) wire.
1. Switch the utility circuit breaker OFF.
2. Remove the input access panel.
3. Remove circular knockout.
4. Run #10 AWG gauge (5 mm2) wire through the access panel, and connect the wires to the
terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief (not
included).
5. Switch the utility circuit breaker ON.
6. Check line voltages.
7. Replace the access panel.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
CONNECTING THE BATTERY MODULES AND ATTACHING THE FRONT BEZEL
ꢀ
4
Download from Www.Somanuals.com. All Manuals Search And Download.
BASIC CONNECTORS
The serial connector is to be used for interfacing with APC PowerChute
software and terminal emulation software.
serial com
Use only cables approved by APC.
Any other interface cable will be incompatible with the UPS
connector.
Manual bypass enables the user to manually put connected equipment into
bypass mode.
normal bypass
Emergency Power Off terminal allows the user to connect the UPS to the
central EPO system.
EPO terminal
TVSS screw
The UPS features a transient voltage surge-suppression (TVSS) screw for
connecting the ground lead on surge suppression devices such as telephone
and network line protectors.
When connecting grounding cable, disconnect the unit from the utility
power outlet.
Optional external battery packs provide extended run time during power
outages. These units support up to ten external battery packs.
external battery
pack connector
battery pack, SURT192XLBP.
5000 VA
XLI models
output circuit
breakers
3000/5000VA
XLJ/XLT/XLTW
models
output circuit
breakers
5
Download from Www.Somanuals.com. All Manuals Search And Download.
CONNECTING EQUIPMENT AND POWER TO THE UPS
1. Connect equipment to the UPS (cables not included for XLJ/XLT/XLTW models).
2. Avoid using extension cords.
•
3000 VA XLJ/XLT/XLI/XLTW and 5000 VA XLJ/XLT/XLTW models: Using a power cord,
plug the UPS into a two-pole, three-wire, grounded receptacle only.
•
5000 VA XLJ models: To draw full 5000 VA from the UPS have a qualified electrician cut
off the input plug and hardwire the UPS to the appropriate power panel.
3. Turn on all connected equipment. To use the UPS as a master ON/OFF switch, ensure all
connected equipment is switched ON. The equipment will not be powered until the UPS is
turned on.
4. To power up the UPS press the
button on the front panel.
•
The UPS battery charges when it is connected to utility power. The battery charges to 90%
capacity during the first three hours of normal operation. Do not expect full battery run
capability during this initial charge period.
5. For additional computer system security, install PowerChute® Server Smart-UPS monitoring
software.
OPTIONS
External Battery Pack SURT192XLBP
Rail Kit SURTRK2
Isolation Transformer
Service Bypass Panel
6
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
SMART-UPS RT FRONT DISPLAY
Load
Battery Charge
Indicator
Description
The Online LED illuminates when the UPS is drawing utility power and performing
double conversion to supply power to connected equipment.
Online
The UPS is supplying battery power to the connected equipment.
On Battery
Bypass
The Bypass LED illuminates indicating that the UPS is in bypass mode. Utility
power is sent directly to connected equipment during bypass mode operation.
Bypass mode operation is the result of an internal UPS fault, an overload condition
or a user initiated command either through an accessory or the manual bypass
switch. Battery operation is not available while the UPS is in bypass mode. Refer to
Troubleshooting in this manual.
The UPS detects an internal fault.
Refer to Troubleshooting in this manual.
Fault
An overload condition exists. See Troubleshooting.
Overload
The battery is disconnected or must be replaced. See Troubleshooting.
Replace
Battery
Feature
Function
Press this button to turn on the UPS. (See below for additional capabilities.)
Power On
Press this button to turn off the UPS.
Power Off
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Feature
Function
Cold Start
When there is no utility power and the UPS is off, press and hold the
power up the UPS and connected equipment.
button to
The UPS will emit two beeps. During the second beep, release the button.
Self-Test
Automatic: The UPS performs a self-test automatically when turned on, and every
two weeks thereafter (by default). During the self-test, the UPS briefly operates the
connected equipment on battery.
Manual: Press and hold the
button for a few seconds to initiate the self-test.
The UPS has a diagnostic feature that displays the utility voltage. Plug
the UPS into the normal utility power.
Diagnostic Utility Voltage
The UPS starts a self-test as part of this procedure. The self-test
does not affect the voltage display.
Press and hold the
button to view the utility voltage bar graph
display. The five-LED, Battery Charge
display on the right of the
front panel shows the utility input voltage.
Refer to the figure at left for the voltage reading (values are not listed
on the UPS).
The display indicates the voltage is between the displayed value on the
list and the next higher value.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT
ACCESSORY CARDS, OR TERMINAL MODE.
FACTORY
DEFAULT
USER SELECTABLE
CHOICES
FUNCTION
DESCRIPTION
Automatic Self-Test
On start-up and
every 14 days,
thereafter
On start-up and every 7
days thereafter
Set the interval at which the
UPS will execute a self-test.
On start-up and every 14
days thereafter
On start-up only
No self-test
Date of Last Battery
Replacement
Manufacture date Date of
battery replacement
Reset this date when you replace
the battery modules.
Specify the minimum run time
following a low battery
shutdown, before powering
connected equipment.
Minimum Run time
Before Return from
Shutdown
0 seconds
0 to 3600 s of run time
Audible Alarm
Setting
ON
ON, OFF
Enable or disable all alarms
permanently.
Simple Shutdown
Delay
90 seconds
0 to 1800 s
Set the interval between the time
when the UPS receives a simple
shutdown command and the
actual shutdown.
Simple Low Run
Time Warning
150 seconds
0 to 1800 s
Change the warning interval
default to a higher setting if the
operating system requires a
longer interval for shutdown.
The low battery warning beeps
are continuous when 150
seconds of run time remain.
High Bypass Point
Output Voltage Setting
Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
255 VAC
200 VAC:
210 - 280 VAC
208 VAC:
220 - 280 VAC
220 VAC:
235 - 280 VAC
230 VAC:
245 - 280 VAC
240 VAC:
255 - 280 VAC
9
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT
ACCESSORY CARDS, OR TERMINAL MODE.
FACTORY
DEFAULT
USER SELECTABLE
CHOICES
FUNCTION
DESCRIPTION
Low Bypass Point
Output Voltage Setting
Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
160 VAC
200 VAC:
160 - 185 VAC
208 VAC:
160 - 190 VAC
220 VAC:
160 - 195 VAC
230 VAC:
160 - 200 VAC
240 VAC:
160 - 205 VAC
Output Voltage
XLJ models:
200 VAC
200, 208, 220,
230, 240 VAC
Allows the user to select the on
on-line output voltage.
XLT models:
208 VAC
XLTW models:
220 VAC
XLI models:
230 VAC
Output Frequency
Automatic
50 ± 3 Hz
50 ± 1 Hz
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 1 Hz
60 ± 0.1 Hz
Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.
50 ± 3 Hz or
60 ± 3 Hz
50 ± 3 Hz or 60 ± 3 Hz
Number of External
Battery Packs
0
0 to 100
Defines the number of external
connected battery packs for
proper run time prediction.
Bypass Acceptable
Not required
Required/ Not required
Phase and frequency lock
required/not required before the
UPS will switch to bypass.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
CONNECTING THE EPO (EMERGENCY POWER OFF) OPTION
The output power can be disabled in an emergency by closing a switch connected to the EPO.
Adhere to National and local electrical codes when wiring the EPO.
EPO
switch
The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers.
The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and a SELV circuit (IEC
standard).
Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any
circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV.
If circuit standard cannot be confirmed, use a contact closure switch.
Use one of the following cable types to connect the UPS to the EPO switch:
•
•
•
•
•
CL2: Class 2 cable for general use
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
CL2R: Riser cable for use in a vertical run in a floor to floor shaft.
CLEX: Limited use cable for use in dwellings and for use in raceways.
For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).
11
Download from Www.Somanuals.com. All Manuals Search And Download.
TERMINAL MODE TO CONFIGURE UPS PARAMETERS
3000 VA models:
Terminal Mode is a menu driven interface that enables configuration of the UPS by users not wishing
to use PowerChute® software or an optional Network Management Card.
Connect the serial cable to the serial com connector on the back of the UPS.
If PowerChute software is not installed do not perform steps 1 and 7.
1. For Windows users: STOP the PowerChute Server using the following steps:
•
From the Desktop, go to Start => Settings => Control Panel =>
Administrative Tools => Services.
•
Select APC PowerChute Server – right click the mouse and select Stop.
1a. For Linux users: STOP the PowerChute Server using the following steps:
•
•
Change directory to /etc/init.d.
Initiate the command ./PowerChute stop.
2. Open a terminal program. Example: HyperTerminal
•
From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.
3. Double-click on the HyperTerminal icon.
•
Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.
•
Select the COM port that is connected to your UPS. The port settings are:
9
9
9
9
9
bits per second - 9600
data - bits 8
parity - none
stop bit - 1
flow control - none
•
Press ENTER
4. Press 1 to modify the UPS parameters.
5. Follow the prompts.
6. Exit the terminal program.
7. For Windows users: START the PowerChute® Server using the following steps:
•
From the Desktop, go to Start => Settings => Control Panel =>
Administrative Tools => Services.
•
Select APC PowerChute Server – right click the mouse and select Start.
7a. For Linux users: START the PowerChute Server using the following steps:
•
•
Change directory to /etc/init.d.
Initiate the command ./PowerChute start.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
5000 VA models:
Terminal Mode is a menu driven interface that enables configuration of the UPS by users not using
PowerChute software or the installed Network Management Card interfaces.
Connect the serial cable to the serial port on the back of the UPS.
If PowerChute software is not installed do not perform steps 1 and 5.
1. For Windows users: STOP the PowerChute® Server using the following steps:
•
From the Desktop, go to Start => Settings => Control Panel =>
Administrative Tools => Services.
•
Select APC PowerChute Server – right click the mouse and select Stop.
1a. For Linux users: STOP the PowerChute Server using the following steps:
•
•
Change directory to /etc/init.d.
Initiate the command ./PowerChute stop.
2. Open a terminal program. Example: HyperTerminal
•
From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.
3. Double-click on the HyperTerminal icon.
•
Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.
•
Select the COM port that is connected to your UPS. The port settings are:
9
9
9
9
9
bits per second - 9600
data - bits 8
parity - none
stop bit - 1
flow control - none
•
Press ENTER
4. Example for setting the number of external battery packs (SURT192XLBP):
Once the blank terminal window is open, follow these steps to enter the number of battery packs:
•
Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User
Name: is displayed. Follow the prompts. Type slowly, waiting until each character appears
on the screen prior to typing the next character.
Network Management Card defaults:
•
User Name: apc
Password: apc
•
•
Press 1 and ENTER to select Device Manager.
Select the model by entering the corresponding number, then press ENTER.
•
•
•
Press 3 and ENTER to select Configuration.
Press 1 and ENTER to select Battery.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
•
Press 2 and ENTER to change the Battery Settings.
•
Type in the number of external battery packs (four battery modules per pack), and
press ENTER.
(Number of packs: 1 = 1 SURT192XLBP, 2 = 2 SURT192XLBP etc.)
•
•
•
Press 3 and ENTER to accept the changes.
Press ESC multiple times (5) to return to the main menu.
Press 4 and ENTER to log out.
5. For Windows users: START the PowerChute® Server using the following steps:
•
From the Desktop, go to Start => Settings => Control Panel =>
Administrative Tools => Services.
•
Select APC PowerChute Server – right click the mouse and select Start.
5a. For Linux users: START the PowerChute Server using the following steps:
•
•
Change directory to /etc/init.d.
Initiate the command ./PowerChute start.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE AND TRANSPORT
Replacing the Battery Module
This UPS has an easy to replace, hot-swappable battery module. Replacement is a safe procedure,
isolated from electrical hazards. You may leave the UPS and connected equipment on during the
replacement battery modules.
The battery replacement procedure must include replacing all battery modules in the UPS and
connected external battery pack(s).
Once the battery(s) are disconnected, the connected equipment is not protected
from power outages.
Be careful during battery replacement, the battery modules are heavy.
Be sure to deliver spent batteries to a recycling facility or ship to the manufacturer
in the replacement battery packing material.
REMOVING BATTERY MODULES
X
Y
Z
[
\
15
Download from Www.Somanuals.com. All Manuals Search And Download.
REPLACING BATTERY MODULES
X
Y
Z
[
\
]
^
_
Disconnecting the Battery for Transport
Always DISCONNECT THE BATTERY(s) before shipping in compliance with U.S.
Department of Transportation (DOT) and IATA regulations.
The battery(s) may remain in the UPS.
1. Shut down and disconnect any equipment attached to the UPS.
2. Shut down and disconnect the UPS from the power supply.
3. Unplug the battery connectors. Refer to Replacing Battery modules in this manual.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING, SERVICE, AND WARRANTY INFORMATION
Use the table below to solve minor installation and operation problems. Refer to the APC Web site,
www.apc.com for assistance with complex UPS problems.
PROBLEM AND POSSIBLE
CAUSE
SOLUTION
UPS WILL NOT TURN ON
Battery not connected properly.
Check that the battery connectors are fully engaged.
button not pushed.
Press the
button once to power the UPS and the connected equipment.
UPS not connected to utility
power supply.
Check that the power cable from the UPS to the utility power supply is securely
connected at both ends.
Very low or no utility voltage.
Check the utility power supply to the UPS by plugging in a table lamp. If the
light is very dim, have the utility voltage checked.
UPS WILL NOT TURN OFF
button not pushed.
Internal UPS fault.
Press the
button once to turn the UPS off.
Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
UPS BEEPS OCCASIONALLY
Normal UPS operation when
running on battery.
None. The UPS is protecting the connected equipment.
UPS DOES NOT PROVIDE EXPECTED BACKUP TIME
The UPS battery(s) are weak
due to a recent outage or
battery(s) are near the end of
their service life.
Charge the battery(s). Battery modules require recharging after extended outages.
They wear faster when put into service often or when operated at elevated
temperatures. If the battery(s) are near the end of their service life, consider
replacing the battery(s) even if the Replace Battery LED is not illuminated.
FRONT PANEL LEDS FLASH SEQUENTIALLY
The UPS has been shut down
remotely through software or an
optional accessory card.
None. The UPS will restart automatically when utility power returns.
ALL LEDS ARE OFF AND THE UPS IS PLUGGED INTO A WALL OUTLET
The UPS is shut down and the
battery is discharged from an
extended outage.
None. The UPS will return to normal operation when the power is restored and
the battery has a sufficient charge.
BYPASS AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONE
The UPS is overloaded
The connected equipment exceeds the specified “maximum load” as defined in
The alarm remains on until the overload is removed. Disconnect nonessential
equipment from the UPS to eliminate the overload condition.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
PROBLEM AND POSSIBLE
CAUSE
SOLUTION
BYPASS LED ILLUMINATES
The bypass switch has been
turned on manually or through
an accessory.
If bypass is the chosen mode of operation, ignore the illuminated LED.
If bypass is not the chosen mode of operation move the bypass switch on the
back of the UPS, to the normal position.
FAULT AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONE
The UPS has ceased sending
power to connected equipment.
The connected equipment exceeds the specified “maximum load” as defined in
Disconnect nonessential equipment from the UPS to eliminate the overload
condition.
Press the OFF button, then the ON button to restore power to connected
equipment.
FAULT LED ILLUMINATES
Internal UPS fault.
Do not attempt to use the UPS. Turn the UPS off and have it serviced
immediately.
REPLACE BATTERY LED ILLUMINATES
Replace Battery LED flashes and Check that the battery connectors are fully engaged.
short beep is emitted every two
seconds to indicate the battery is
disconnected.
Weak battery.
Allow the battery to recharge for 24 hours. Then, perform a self-test. If the
problem persists after recharging, replace the battery.
Failure of a battery self-test.
The UPS emits short beeps for one minute and the Replace Battery LED
illuminates. The UPS repeats the alarm every five hours. Perform the self-test
procedure after the battery has charged for 24 hours to confirm the Replace
Battery condition. The alarm stops and the LED clears if the battery passes the
self-test.
UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTS
Very high, low, or distorted line
voltage. Inexpensive fuel
powered generators can distort
the voltage.
Move the UPS to a different outlet on a different circuit. Test the input voltage
with the utility voltage display.
DIAGNOSTIC UTILITY VOLTAGE
All five LEDs are illuminated
The line voltage is extremely high and should be checked by an electrician.
There is no LED illumination
If the UPS is plugged into a properly functioning utility power outlet, the line
voltage is extremely low.
ONLINE LED
There is no LED illumination
The UPS is running on battery, or it is not turned on.
The UPS is running an internal self-test.
The LED is blinking
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Service
If the UPS requires service do not return it to the dealer. Follow these steps:
1. Review the problems discussed in the Troubleshooting section of this manual to eliminate
common problems.
2. If the problem persists, contact APC Customer Support through the
•
Note the model number of the UPS, the serial number located on the back of the unit, and the
date purchased. If you call APC Customer Support, a technician will ask you to describe the
problem and attempt to solve it over the phone. If this is not possible, the technician will
issue a Returned Material Authorization Number (RMA#).
•
•
If the UPS is under warranty, repairs are free.
Procedures for servicing or returning products may vary internationally. Refer to the APC
Web site for country specific instructions.
3. Pack the UPS in its original packaging.
•
information about obtaining a new set.
•
Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for
packaging. Damage sustained in transit is not covered under warranty.
Always DISCONNECT THE BATTERY(S) before shipping in compliance with U.S.
Department of Transportation (DOT) and IATA regulations.
The battery(s) may remain in the UPS.
4. Mark the RMA# on the outside of the package.
5. Return the UPS by insured, prepaid carrier to the address given to you by Customer Support.
Limited Warranty
American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of
two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole
option, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization
(RMA) number from customer support. Products must be returned with transportation charges prepaid and must be
accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does
not apply to equipment that has been damaged by accident, negligence, or misapplication or has been altered or modified in
any way. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of
purchase.
EXCEPT AS PROVIDED HEREIN, AMERICAN POWER CONVERSION MAKES NO WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s)
may not apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL APC BE LIABLE FOR DIRECT, INDIRECT, SPECIAL,
INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF
ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, APC is not liable for any costs, such as lost profits or
revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties,
or otherwise.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
RADIO FREQUENCY WARNINGS
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference. The user is responsible for correcting
the interference.
Shielded signal cables must be used with this product to ensure compliance with the Class A FCC limits.
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following
ways:
•
Refer to the APC Web site to access documents in the APC Knowledge Base and to submit
customer support requests.
•
www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer
support information.
•
Global support searching APC Knowledge Base and using e-support.
•
Contact an APC Customer Support center by telephone or e-mail.
Local, country-specific centers:
Contact the APC representative or other distributor from whom you purchased your APC product for
information on how to obtain local customer support.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
|