®
Altivar 61 / 71
®
User's manual
30072-452-37
Modbus TCP/IP Daisy Chain Ethernet Card
VW3A3310d
Retain for future use
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of contents
Important Information _________________________________________________________________________________________ 5
Before you begin_____________________________________________________________________________________________ 6
Documentation structure_______________________________________________________________________________________ 7
Introduction_________________________________________________________________________________________________ 8
Presentation _____________________________________________________________________________________________ 8
Notation ________________________________________________________________________________________________ 8
Hardware setup _____________________________________________________________________________________________ 9
Receipt _________________________________________________________________________________________________ 9
Hardware description ______________________________________________________________________________________ 9
Installing the card in the drive________________________________________________________________________________ 9
Connecting to the Ethernet network _____________________________________________________________________________ 10
Card RJ45 connector pinout________________________________________________________________________________ 10
Example of connection to an Ethernet network _________________________________________________________________ 10
Ethernet network connection elements________________________________________________________________________ 11
Ethernet menu _____________________________________________________________________________________________ 12
Access to Ethernet menu via graphic display terminal ____________________________________________________________ 12
Access to Ethernet menu via the integrated display terminal_______________________________________________________ 12
Ethernet menu parameters_________________________________________________________________________________ 13
Configuration ______________________________________________________________________________________________ 16
List of functions to be configured ____________________________________________________________________________ 16
Configuring IP addresses __________________________________________________________________________________ 17
Reserving control ________________________________________________________________________________________ 19
Configuring IO Scanning___________________________________________________________________________________ 19
Configuring the control ____________________________________________________________________________________ 20
Configuring the fault management ___________________________________________________________________________ 23
Configuring monitored parameters ___________________________________________________________________________ 25
Diagnostics ________________________________________________________________________________________________ 26
Signalling LEDs _________________________________________________________________________________________ 26
Available information _____________________________________________________________________________________ 27
Monitoring the control _____________________________________________________________________________________ 27
Troubleshooting communication interruptions __________________________________________________________________ 28
Troubleshooting the card __________________________________________________________________________________ 29
Software setup _____________________________________________________________________________________________ 30
List of services supported__________________________________________________________________________________ 30
TCP connections ________________________________________________________________________________________ 30
Modbus TCP server _________________________________________________________________________________________ 31
Modbus TCP frames______________________________________________________________________________________ 31
Drive Modbus servers_____________________________________________________________________________________ 31
Ethernet card parameters__________________________________________________________________________________ 32
List of Modbus functions supported __________________________________________________________________________ 35
“Read Holding Registers” (3) function ________________________________________________________________________ 35
“Write Single Register” (6) function___________________________________________________________________________ 36
“Write Multiple Registers” (16 = 16#10) function ________________________________________________________________ 37
“Read/Write Multiple Registers” (23 = 16#17) function____________________________________________________________ 38
“Read Device Identification” (43 = 16#2B) function ______________________________________________________________ 39
IO Scanning service _________________________________________________________________________________________ 40
Presentation ____________________________________________________________________________________________ 40
Periodic variables ________________________________________________________________________________________ 40
Address table ___________________________________________________________________________________________ 41
FDR service _______________________________________________________________________________________________ 42
Presentation ____________________________________________________________________________________________ 42
Local configuration _______________________________________________________________________________________ 43
Downloaded configuration _________________________________________________________________________________ 44
Periodic saving __________________________________________________________________________________________ 46
Other commands ________________________________________________________________________________________ 46
Configuration file_________________________________________________________________________________________ 46
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of contents
Standard Web server ________________________________________________________________________________________ 47
Web server functions _____________________________________________________________________________________ 47
Applets ________________________________________________________________________________________________ 48
Access to the Web server__________________________________________________________________________________ 49
Web server user interface__________________________________________________________________________________ 50
“Home” menu ___________________________________________________________________________________________ 50
“Monitoring” menu________________________________________________________________________________________ 50
“Altivar Viewer” page _____________________________________________________________________________________ 51
“Data Viewer” page_______________________________________________________________________________________ 52
“Altivar Chart” page_______________________________________________________________________________________ 53
“Diagnostics” menu_______________________________________________________________________________________ 53
“Ethernet Statistics” page __________________________________________________________________________________ 54
“Setup” menu ___________________________________________________________________________________________ 54
“HTTP password” and “Data write password pages” _____________________________________________________________ 55
“FDR Agent” page________________________________________________________________________________________ 56
“IO Scanner” page _______________________________________________________________________________________ 58
"E-mail" page ___________________________________________________________________________________________ 61
“Documentation” menu ____________________________________________________________________________________ 62
FTP server ________________________________________________________________________________________________ 63
Downloading from the Web server ______________________________________________________________________________ 65
SNMP agent _______________________________________________________________________________________________ 68
Setup using PL7 ____________________________________________________________________________________________ 70
Setup using Concept ________________________________________________________________________________________ 76
Setup using ProWORX NxT ___________________________________________________________________________________ 77
4
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain
it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call
attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or
equipment damage.
WARNING
Warning indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment
damage.
PLEASE NOTE:
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this material.
© 2008 Schneider Electric. All Rights Reserved.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Before you begin
Read and understand these instructions before performing any procedure with this drive.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this manual before installing or operating the Altivar 61 (ATV61) or Altivar 71 (ATV71) drive
controller. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical code requirements with respect to
grounding of all equipment.
• Many parts of this drive controller, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use
only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Before servicing the drive controller
- Disconnect all power, including external control power that may be present.
- Place a “DO NOT TURN ON” label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement
procedure given in the Installation Manual to verify that the DC voltage is less than 42 V. The drive LED is not an
indicator of the absence of DC bus voltage.
• Install and close all covers before applying power or starting and stopping the drive controller.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED EQUIPMENT
Do not install or operate any drive or drive accessory that appears damaged.The relays, inputs, or outputs of a damaged
drive may not operate in a normal manner, leading to unintended equipment operation.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical
control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control
functions are emergency stop and overtravel stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated
transmission delays or failures of the link.*
• Each implementation of an Altivar 71 Modbus TCP/IP Ethernet card must be individually and thoroughly tested for proper
operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
* For additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and
Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for
Selection, Installation and Operation of Adjustable-Speed Drive Systems.”
6
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Documentation structure
delivered with each drive controller.
bInstallation Manual
This manual describes:
• How to assemble the drive controller
• How to connect the drive controller
bProgramming Manual
This manual describes:
• The drive controller functions
• The drive controller parameters
• How to use the drive display terminal (integrated display terminal and graphic display terminal)
Installation and Programming Manuals
Drive
Family
Range
(hp)
Installation Manual
Module No.
Programming Manual
Module No.
ATV61
0.5–100 1760643
(atv61s_installation_manual)
1760649
(atv61_programming_manual)
75–800 1760655
(atv61e_installation_manual)
ATV71
0.5–100 1755843
(atv71s_installation_manual)
1755855
(atv71_programming_manual)
75–700 1755849
(atv71e_installation_manual)
7
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Introduction
4. 1. Presentation
The Ethernet card (catalog number VW3A3310d) is used to connect an Altivar 61 / 71 drive to an Ethernet network using the Modbus
TCP/IP protocol and Transparent Ready services.
The VW3A3310d card is equipped with two shielded RJ45 Ethernet connectors.
The accessories for connection to the Ethernet network must be ordered separately.
The data exchanges permit the following drive functionality:
• Configuration
• Adjustment
• Control
• Monitoring
• Diagnostics
The standard web server (English only) provides access to the following pages:
• Altivar Viewer
• Data Viewer
• Ethernet
• Security
The standard web server can be adapted or replaced by a customized server depending on the requirements of the application.
The graphic display terminal or the integrated display terminal can be used to access numerous functions for communication diagnostics.
4. 2. Notation
Drive terminal displays
The graphic display terminal menus are shown in square brackets.
Example: [1.9 COMMUNICATION].
The integrated 7-segment display terminal menus are shown in parentheses.
Example: (COM-).
The parameter names displayed on the graphic display terminal are shown in parentheses.
Example: [Fallback speed].
The parameter codes displayed on the integrated 7-segment display terminal are shown in round brackets.
Example: (LFF).
Formats
Hexadecimal values are written as follows: 16#
Binary values are written as follows: 2#
8
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Hardware setup
5. 1. Receipt
• Check that the card catalog number marked on the label is the same as that on the delivery note corresponding to the purchase order.
• Remove the option card from its packaging and check that it has not been damaged in transit.
CAUTION
STATIC SENSITIVE COMPONENTS
Avoid damage to the Modbus TCP/IP card by electrostatic discharge. Observe the electrostatic precautions below when handling
controller circuit boards or when testing components.
Failure to follow these instructions can result in injury or equipment damage.
Observe the following precautions for handling static-sensitive components:
• Keep static-producing material such as plastic, upholstery, and carpeting out of the immediate work area.
• Store the Modbus TCP/IP card in its electrostatic protective packaging when it is not installed in the drive controller.
• When handling the Modbus TCP/IP card, wear a conductive wrist strap connected to the card through a minimum of 1 megohm
resistance.
• Avoid touching exposed conductors and component leads with skin or clothing.
5. 2. Hardware description
LEDs
Shielded female RJ45
Ethernet connector
(Port 1)
Shielded female RJ45
Ethernet connector
(Port 2)
MAC address label
on the Ethernet card
5. 3. Installing the card in the drive
See the ATV61 or ATV71 Installation Manual.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Connecting to the Ethernet network
6. 1. Card RJ45 connector pinout
The Ethernet card is equipped with a shielded RJ45 connector. The shielding is connected to the drive ground.
Use STP (shielded twisted pair) Ethernet cable.
Pin
1
Signal
TD+
2
TD-
3
RD+
4
5
6
RD-
7
8........................1
8
The transmission speed is detected automatically by the card (10 Mbps or 100 Mbps).
The card can operate in half duplex or full duplex mode, whether connected to a hub or switch, regardless of the transmission speed
(10 Mbps or 100 Mbps).
The card supports the ETHERNET 2 frame format (IEEE 802-3 not supported).
6. 2. Example of connection to an Ethernet network
PLC
Daisy chain and/or star topology (1)
ATV61/71 ATV61/71 ATV61/71 ATV61/71 ATV61/71
Ethernet switch
(1)When the topology is a daisy chain, if one drive is turned off, the other drive(s) stop in response to a communication network fault (CNF).
Redundancy can be added by connecting the first and last drive in the daisy chain to a hub or switch to create a loop.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Connecting to the Ethernet network
6. 3. Ethernet network connection elements
Please consult our catalog “Ethernet TCP/IP and the Web” (available on the web site www.telemecanique.com).
Connecting cables
Description
Use
Length
Catalog number
From
To
m
2
Straight shielded twisted pair cables
2 RJ45 connectors
ATV71
Hubs
490 NTW 000 02
490 NTW 000 05
490 NTW 000 12
490 NTW 000 40
490 NTW 000 80
(+ VW3A3310d card)
499 NpH 1pp 10
Switches
499 NpS 171 00
5
12
40
80
Hubs and switches
Description
Hubs
Characteristics
Catalog number
499 NEH 104 10
499 NEH 141 10
499 NOH 105 10
4 × 10BASE-T ports
4 × 100BASE-TX ports
3 × 10BASE-T ports
2 × 10BASE-FL ports, multimode fiber, ST (BFOC) connectors
Switches
5 × 10BASE-T/100BASE-TX ports
Unmanaged basic
499 NES 251 00
499 NMS 251 01
4 × 10BASE-T/100BASE-TX ports
1 × 100BASE-FX port, multimode fiber, SC connectors
Unmanaged
3 × 10BASE-T/100BASE-TX ports
2 × 100BASE-FX port, multimode fiber, SC connectors
Unmanaged
499 NMS 251 02
499 NSS 251 01
499 NSS 251 02
4 × 10BASE-T/100BASE-TX ports
1 × 100BASE-FX port, monomode fiber, SC connectors
Unmanaged
3 × 10BASE-T/100BASE-TX ports
2 × 100BASE-FX port, monomode fiber, SC connectors
Unmanaged
8 × 10BASE-T/100BASE-TX ports
Unmanaged
499 NES 181 00
499 NES 271 00
499 NOS 271 00
7 × 10BASE-T/100BASE-TX ports
Managed
5 × 10BASE-T/100BASE-TX ports
2 × 100BASE-FX port, multimode fiber, SC connectors
Managed
5 × 10BASE-T/100BASE-TX ports
2 × 100BASE-FX port, monomode fiber, SC connectors
Managed
499 NSS 271 00
11
Download from Www.Somanuals.com. All Manuals Search And Download.
7. Ethernet menu
7. 1. Access to Ethernet menu via graphic display terminal
The [ETHERNET] submenu is used to configure and display the Ethernet card parameters and can be accessed via the
[1.9 - COMMUNICATION] menu.
If you are using the FDR (Faulty Device Replacement) function, you must also configure the device name in the [7. DISPLAY CONFIG.]
menu, [7.1 USER PARAMETERS] submenu, [DEVICE NAME] submenu.
This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).
RDY
NET +0.00 Hz
1 DRIVE MENU
0A
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
RUN
NET
+50.00 Hz 80A
1.4 MOTOR CONTROL
1.5 INPUTS/OUTPUTS CFG
1.9 COMMUNICATION
COM. SCANNER OUTPUT
MODBUS HMI
Code
<<
>>
Quick
1.6 COMMAND
MODBUS NETWORK
CANopen
RDY
NET +0.00 Hz
MAIN MENU
0A
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
ENT
ENT
ETHERNET
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
Code
Code
<<
>>
Quick
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
Quick
1.14 PROGRAMMABLE CARD
7. 2. Access to Ethernet menu via the integrated display terminal
The (EtH-) submenu is used to configure and display the Ethernet card parameters. It can be accessed via the (COM-) menu.
Note: The device name required for the FDR (Faulty Device Replacement) function cannot be configured via the integrated display terminal.
Power-up
Displays the drive state
XXX
ENT
ESC
SIM-
ESC
ESC
ESC
FLt-
CON-
FCS-
ENT
EtH-
ESC
ESC
LAC-
12
Download from Www.Somanuals.com. All Manuals Search And Download.
7. Ethernet menu
7. 3. Ethernet menu parameters
Code
Description
(bdr)
M[Bit rate]
Transmission speed detected on the network by the Ethernet card
Type:
Display (read-only)
Possible
values:
[0 Mbps] (0M): Automatic detection of the Ethernet network speed
[10 Mbps] (10M): 10 Mbps
[100 Mbps] (100M): 100 Mbps
Default value:
[0 Mbps] (0M)
(PAn-)
b [DEVICE NAME]
Device name used by FDR service. Accessible with an ATV71 from V1.2 and a ATV61 from V1.3 version.
Use the navigation selector button to increment the character (alphabetical order) and << and >> (F2 and F3) to switch
to the next or previous character respectively. Use F1 to change to ABC, abc, 123, *[-.
Type:
Configuration (read and write)
Display (read-only)
Possible values: 16 characters on 1 or 2 lines.
Default value: [0]
(IPC-)
b[IP card]
(IPC1)
(IPC2)
(IPC3)
(IPC4)
M[139.160.069.241] (139) (160) (069) (241)
Ethernet card IP address
Type:
Configuration (read and write)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
Possible
values:
• 0 to 255 for each of fields IPC1, IPC2, IPC3 and IPC4.
• If the value is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for an address from a BOOTP
or DHCP server.
Note: If you enter a value other than [0.0.0.0] (0) (0) (0) (0), dynamic addressing by a BOOTP
or DHCP server is disabled.
Note: After dynamic addressing by a BOOTP or DHCP server, the value [0.0.0.0] (0) (0) (0) (0)
is replaced by the address supplied.
Default value:
[0.0.0.0] (0) (0) (0) (0)
(IPM-)
b[IP Mask]
(IPM1)
(IPM2)
(IPM3)
(IPM4)
M[255.255.254.0] (255) (255) (254) (0)
Subnet mask
Type:
Configuration (read and write)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
Possible
values:
• 0 to 255 for each of fields IPM1, IPM2, IPM3 and IPM4.
• If the value of the IP address [IP card] is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for
a mask from a BOOTP or DHCP server.
Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the
address supplied.
Default value:
[0.0.0.0] (0) (0) (0) (0)
(IPG-)
b[IP Gate]
(IPG1)
(IPG2)
(IPG3)
(IPG4)
M[0.0.0.0] (0) (0) (0) (0)
Gateway IP address
Type:
Configuration (read and write)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
Possible
values:
• 0 to 255 for each of fields IPG1, IPG2, IPG3 and IPG4.
• If the value of the IP address [IP card] is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for
a mask from a BOOTP or DHCP server.
Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the
address supplied.
Default value:
[0.0.0.0] (0) (0) (0) (0)
13
Download from Www.Somanuals.com. All Manuals Search And Download.
7. Ethernet menu
Code
Description
(IPP-)
b[IP Master]
(IPP1)
(IPP2)
(IPP3)
(IPP4)
M[0.0.0.0] (0) (0) (0) (0)
IP address of the device that retains control
Type:
Configuration (read and write)
Display (read-only) if the address is supplied by a DHCP server
Possible
values:
• 0 to 255 for each of fields IPP1, IPP2, IPP3 and IPP4.
• If the value is [0.0.0.0] (0) (0) (0) (0), writing of the control word (CMd) is accepted
by the Ethernet card regardless of which device has sent it.
• If the value is other than [0.0.0.0] (0) (0) (0) (0) only the device which has the IP address
[IP Master] is authorized to write the control word (CMd).
Note: This configuration also affects the type of communication monitoring.
Default value:
[0.0.0.0] (0) (0) (0) (0)
(IPF-)
b[IP FDR]
(IPF1)
(IPF2)
(IPF3)
(IPF4)
M[0.0.0.0] (0) (0) (0) (0)
IP address of the FDR server
Type:
Display (read-only)
Possible
values:
• 0 to 255 for each of fields IPF1, IPF2, IPF3 and IPF4.
• If the value is [0.0.0.0] (0) (0) (0) (0), there is no server.
Default value:
[0.0.0.0] (0) (0) (0) (0)
(ISA)
(tOUt)
(FdrU)
(LCFG)
(FdrF)
M[IO Scan.activ.]
Enable IO Scanner
Type:
Configuration (read and write)
Possible
values:
• [No] (nO): IO Scanner disabled.
• [Yes] (YES): IO Scanner enabled.
Default value:
[Yes] (YES)
M[time out]
Ethernet communication monitoring time out
Type:
Configuration (read and write)
Possible
values:
• [0] (0): Monitoring disabled.
• [0.5 s] (0.5) to [60.0 s] (60.0): Time out value (unit: 0.1 s).
Default value:
[2.0 s] (2.0)
M[FDR validation]
Enable FDR service
Type:
Configuration (read and write)
Possible
values:
• [No] (nO): FDR service disabled.
• [Yes] (YES): FDR service enabled.
Default value:
[Yes] (YES)
M[FDR Local Config.]
Selection of local or server configuration
Type:
Configuration (read and write)
Possible
values:
• [No] (nO): The drive configuration is downloaded from an FDR server.
• [Yes] (YES): The drive configuration is local and saved in a FDR server.
Default value:
[No] (nO)
M[FDR Error Mgt.]
Enable FDR file error detection
Type:
Configuration (read and write)
Possible
values:
In the event of a problem with the FDR file (missing or invalid):
• [No] (nO): The Ethernet card does not trigger an [FDR fault] (Fdrd).
• [Yes] (YES): The Ethernet card triggers an [FDR fault] (Fdrd).
Default value:
[Yes] (YES)
14
Download from Www.Somanuals.com. All Manuals Search And Download.
7. Ethernet menu
Code
Description
(FdrA)
M[FDR Action]
FDR service command
Type:
Command (read and write)
Possible
values:
• [IDLE] (IdLE): No command.
• [SAVE] (SAUE): Command: save.
• [REST] (rESt): Command: download.
• [DEL] (dEL): Command: delete.
The command remains displayed during the action then reverts to the value [IDLE] (IdLE).
Default value:
[IDLE] (IdLE)
(FdrS)
(Fdrt)
(FdrE)
M[FDR autosave]
Enable periodic saving of the FDR service
Type:
Configuration (read and write)
Possible
values:
• [No] (nO): Automatic saving disabled.
• [Yes] (YES): Automatic saving enabled.
Default value:
[No] (nO)
M[FDR t.autosave]
Interval for periodic saving of the FDR service
Type:
Configuration (read and write)
Possible
values:
• [2] (2) to [9999] (9999): 2 min to 9999 min.
Default value:
[10] (10)
M[FDR state]
FDR service state
Type:
Display (read-only)
Possible
values:
• [IDLE] (IdLE): “Idle”.
• [INIT] (INIt): Initialization.
• [CONF] (CONF): Configuration.
• [RDY] (rdY): Ready.
• [GET] (GEt): Download the current configuration.
• [SET] (SEt): Save the current configuration.
• [APP] (APP): Write the FDR server configuration to the drive.
• [OPE] (OPE): Operational.
• [UCFG] (UCFG): Not configured.
Default value:
[IDLE] (IdLE)
(Fdrd)
M[FDR Error Code]
FDR service status code
Type:
Display (read-only)
Possible
values:
• [0] (0): No communication interruption
• [2] (2): The FDR configuration file is not compatible with the drive type
(example: the drive is not the same rating as that defined in the FDR file).
• [3] (3): Error reading the FDR configuration file on the server.
• [4] (4): Error writing the FDR configuration file to the server.
• [7] (7): Time-out for receipt of the FDR configuration file from the server.
• [9] (9): Duplication of IP address.
• [12] (12): The FDR configuration file is missing.
Default value:
[0] (0)
15
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Configuration
8. 1. List of functions to be configured
The table below gives the list of configuration functions and how they can be accessed:
Graphic
display
Integrated
display
PowerSuite
software
Standard
web
Functions
terminal
terminal
workshop
server
Entering the IP addresses
p
p
p
p
p
p
p
p
p
Entering the device name
Configuration (time delay, etc.)
Commands (save, etc.)
FDR
p
p
p
p
p
p
p
p
p
(Faulty Device Replacement)
Enable IO Scanner
p
p
p
p
p
IO Scanning
Configuring the IO Scanner variables
Reserving control (IP master)
Communication monitoring
p
p
p
p
Changing the “username”
Security of access
to the standard web server
Changing the “HTTP password”
Changing the “Write password”
p
p
p
Configuration using the drive graphic display terminal or the integrated display terminal is explained in the “Configuration” section.
Configuration using the standard web server is explained in the “Standard web server” section.
For configuration using the PowerSuite software workshop, refer to the PowerSuite online help.
Notes:
• The Ethernet card saves its configuration (IP address, mask, gateway, etc.) to the EEPROM each time the configuration is modified.
• For performance reasons, Schneider Electric recommends using the Ethernet IO Scanner, not the drive communication scanner.
• Configuration must be performed with the motor stopped.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Configuration
8. 2. Configuring IP addresses
bAssigning IP addresses
The drive needs 3 IP addresses:
• The drive IP address.
• The subnet mask.
• The gateway IP address (not always required).
®
®
Note: Some controllers, such as Prosoft and DeltaV modules, require a Modbus address to be set in addition to the IP address. This
address must be set in menu 1.9 of the drive, as well as in the software for the master device.
These IP addresses can be entered:
• Using the integrated display terminal.
• Using the graphic display terminal.
• Using the PowerSuite software workshop.
They can be provided by:
• A BOOTP server (correspondence between the MAC address and the IP addresses).
• A DHCP server (correspondence between Device Name [DEVICE NAME] and the IP addresses).
If an IP address other than 0.0.0.0 has been entered using the display terminal or the PowerSuite software workshop, assignment using
a server is disabled.
The BOOTP service is enabled:
• When no IP address other than 0.0.0.0 has been entered and
• The FDR service has not been enabled ([FDR validation] parameter = [No] or a [DEVICE NAME] has not been entered).
The DHCP service is enabled:
• When no IP address other than 0.0.0.0 has been entered and
• The FDR service has been enabled ([FDR validation] parameter = [Yes] and a [DEVICE NAME] has been entered).
Power-up
An address has been entered
Static
addressing
Initialization
[IP card] <> 0.0.0.0
No address has been entered
[IP card] = 0.0.0.0
Dynamic
addressing
[FDR validation] = [No]
BOOTP
[FDR validation] = [Yes]
[DEVICE NAME] blank
FDR
[DEVICE NAME] has been
entered
DHCP
17
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Configuration
bEntering IP addresses in the terminal
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu, enter the following IP addresses:
- [IP card] (IPC1) (IPC2) (IPC3) (IPC4).
- [IP Mask] (IPM1) (IPM2) (IPM3) (IPM4).
- [IP Gate] (IPG1) (IPG2) (IPG3) (IPG4) (not always required).
®
®
Note: Some controllers, such as Prosoft and DeltaV modules, require a Modbus address to be set in addition to the IP address. This
address must be set in menu 1.9 of the drive, as well as in the software for the master device.
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the IP addresses are not
taken into account.
Note: Before entry begins, the IP address displayed is the active IP address.
If this address is modified, the new IP address entered is displayed. This IP address will be effective the next time the drive is turned on.
bConfiguring BOOTP
The BOOTP service is used to assign IP addresses from the MAC address. The MAC address consisting of 6 octets (00-80-F4-80-xx-yy)
must be entered in the BOOTP server. The MAC address appears on the label attached to the Ethernet card.
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Do not enable the FDR service: [FDR validation] (FdrU) = [No] (nO).
bConfiguring FDR
The FDR service (based on DHCP) is used to assign the IP addresses and other parameters from the device name that must be entered
in the drive and in the FDR server (DHCP).
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES).
For the FDR function, select the drive configuration as either:
• Local: [FDR Local Config.] (LCFG) = [Yes] (YES).
• Downloaded. In this case, it is essential to consult the “FDR Service” section.
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu.
This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken
into account.
Note: The FDR function cannot be fully configured using the integrated display terminal as it does not provide access to the device name.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Configuration
8. 3. Reserving control
It is strongly recommended that control should be reserved for a single master device.
If control were not to be reserved for a master device (for example a PLC):
• Any other Modbus TCP Ethernet client could send unwanted commands.
• Other clients could use the 8 available TCP connections and prevent the master from having control.
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that a valid address for the IP master device has been specified.
Failure to follow this instruction will result in death, serious injury, or equipment damage.
Use the [IP Master] (IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified
using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended operation.
To configure this reservation, enter an IP address other than [0.0.0.0] (0) (0) (0) (0) in the [1.9 COMMUNICATION] (COM-) menu,
[ETHERNET] (EtH-) submenu, [IP Master] submenu.
• If control has been reserved:
Only the control word (CMd) written by the master with control will be accepted via IO Scanning or via Modbus TCP messaging.
2 TCP connections are reserved for this device. In this way, you avoid other TCP clients using all the available connections
(8 maximum) and the control master no longer being able to access the drive Modbus TCP server.
Other parameters written from other IP addresses are accepted (for example, adjustments or writing a setpoint).
When control has been reserved and another device attempts to write the control word (CMd):
- via IO Scanning: The Modbus TCP connection for this client is immediately reinitialized.
- via Modbus TCP messaging: Control is denied.
• If control has not been reserved ([IP Master] = [0.0.0.0] (0) (0) (0) (0)), control can come from any IP address.
8. 4. Configuring IO Scanning
Refer to the “IO Scanning Service” section.
The drive IO Scanning service can be enabled or disabled in the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-)
submenu via parameter [IO Scan.activ.] (IOSA).
It is not possible to modify the assignment of the IO Scanning periodic variables using the display terminal (integrated or graphic).
To configure IO Scanning, use the standard web server or the PowerSuite software workshop.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Configuration
8. 5. Configuring the control
Numerous configurations are possible. For more information, refer to the Programming Manual and the Communication parameters
Manual.
The following configurations are just some of the possibilities available.
bControl via Ethernet in I/O profile
The command and setpoint come from Ethernet.
The command is in I/O profile.
Configure the following parameters:
Parameter
Value
Comment
Profile
I/O profile
The run command is simply obtained by bit 0 of the control word.
Setpoint 1 configuration
Command 1 configuration
Network card The setpoint comes from Ethernet.
Network card The command comes from Ethernet.
Configuration via the graphic display terminal or the integrated display terminal:
Menu
Parameter
Value
[1.6 - COMMAND] (CtL-)
[Profile] (CHCF)
[Ref.1 channel] (Fr1)
[Cmd channel 1] (Cd1)
[I/O profile] (IO)
[Com. card] (nEt)
[Com. opt card] (nEt)
bControl via Ethernet or the terminals in I/O profile
Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet
and the terminals.
The command is in I/O profile.
Configure the following parameters:
Parameter
Value
Comment
Profile
I/O profile
Network card
The run command is simply obtained by bit 0 of the control word.
Setpoint 1 comes from Ethernet.
Setpoint 1 configuration
Setpoint 1B configuration
Setpoint switching
Command 1 configuration
Command 2 configuration
Command switching
Analog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.
Input LI5
Input LI5 switches the setpoint (1 ↔1B).
Command 1 comes from Ethernet.
Command 2 comes from the terminals.
Input LI5 switches the command.
Network card
Terminals
Input LI5
Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
Menu
Parameter
Value
[1.6 - COMMAND] (CtL-)
[Profile] (CHCF)
[I/O profile] (IO)
[Com. card] (nEt)
[Com. card] (nEt)
[Terminals] (tEr)
[LI5] (LI5)
[Ref.1 channel] (Fr1)
[Cmd channel 1] (Cd1)
[Cmd channel 2] (Cd2)
[Cmd switching] (CCS)
[Ref.1B channel] (Fr1b)
[Ref 1B switching] (rCb)
[1.7 APPLICATION FUNCT.] (FUn-)
[REFERENCE SWITCH.]
[Ref. AI1] (AI1)
[LI5] (LI5)
20
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Configuration
bControl via Ethernet in CiA402 (Drivecom) profile
The command and setpoint come from Ethernet.
The command is in CiA402 profile.
Note: The term Drivecom has been in use since 1991. Recently, the term has changed to DSP402, and currently is CiA402. This profile
requires a specific sequence of commands to control the drive. The profile is a standard that is available for use by many brands and
products to facilitate interchangeability of similar products from different manufacturers. Refer to the Communications Parameters and
Programming guides for additional details.
Configure the following parameters:
Parameter
Value
Comment
Profile
Not separate
The run commands are in CiA402 profile, the command and the setpoint come
from the same channel.
Setpoint 1 configuration
Network card
The command comes from Ethernet.
Configuration via the graphic display terminal or the integrated display terminal:
Menu
Parameter
Value
[1.6 - COMMAND] (CtL-)
[Profile] (CHCF)
[Ref.1 channel] (Fr1)
[Not separ.] (SIM) (factory setting)
[Com. card] (nEt)
bControl via Ethernet or the terminals in CiA402 profile
Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet
and the terminals.
The command is in CiA402 profile.
Configure the following parameters:
Parameter
Value
Comment
Profile
Not separate
The run commands are in CiA402 profile, the command and the setpoint
come from the same channel.
Setpoint 1 configuration
Setpoint 2 configuration
Setpoint switching
Network card
Setpoint 1 comes from Ethernet.
Analog input 1 on the terminals
Input LI5
Setpoint 2 comes from input AI1 on the terminals.
Input LI5 switches the setpoint (1 ↔ 2) and the command.
Note: Setpoint 2 is directly connected to the drive setpoint limit. If switching is performed, the functions that affect the setpoint (summing,
PID, etc.) are disabled.
Configuration via the graphic display terminal or the integrated display terminal:
Menu
Parameter
Value
[1.6 - COMMAND] (CtL-)
[Profile] (CHCF)
[Ref.1 channel] (Fr1)
[Ref.2 chan] (Fr2)
[Ref. 2 switching] (rFC)
[Not separ.] (SIM)
[Com. card] (nEt)
[Ref. AI1] (AI1)
[LI5] (LI5)
21
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Configuration
bCommand in CiA402 (Drivecom) profile via Ethernet and setpoint switching at the terminals
The command comes from Ethernet.
The setpoint comes either from Ethernet or from the terminals. Input LI5 at the terminals is used to switch the setpoint between Ethernet
and the terminals.
The command is in CiA402 profile.
Configure the following parameters:
Parameter
Value
Comment
Profile
Separate
The run commands are in CiA402 profile, the command and the setpoint
can come from different channels.
Setpoint 1 configuration
Setpoint 1B configuration
Setpoint switching
Network card
Setpoint 1 comes from Ethernet.
Analog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.
Input LI5
Input LI5 switches the setpoint (1 ↔1B).
Command 1 comes from Ethernet.
Channel 1 is the command channel.
Command 1 configuration
Command switching
Network card
Channel 1
Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
Menu
Parameter
Value
[1.6 - COMMAND] (CtL-)
[Profile] (CHCF)
[Separate] (SEP)
[Com. card] (nEt)
[Com. card] (nEt)
[Ch1 active] (Cd1)
[Ref. AI1] (AI1)
[LI5] (LI5)
[Ref.1 channel] (Fr1)
[Cmd channel 1] (Cd1)
[Cmd switching] (CCS)
[Ref.1B channel] (Fr1b)
[Ref 1B switching] (rCb)
[1.7 APPLICATION FUNCT.] (FUn-)
[REFERENCE SWITCH.]
22
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Configuration
8. 6. Configuring communication interruption management
bCommunication monitoring
The Ethernet card can detect 2 types of communication interruptions:
- Network management (server missing, duplication of IP address, etc.).
- Communication (time out on the master traffic, etc.).
The associated information is:
Ethernet interruption type
Network management
Communication
Associated drive parameter
Code:
Code:
[External fault com.] (EPF2)
[Com. network] (CnF)
Configuring the communication
interruption or file error detection
settings
Parameter:
[FDR Error Mgt.] (FdrF)
Menu:
Parameter:
[time Out] (tOUt)
Menu:
[1.9 COMMUNICATION] (COM-)
Submenu:
[1.9 COMMUNICATION] (COM-)
Submenu:
[ETHERNET] (EtH-)
[ETHERNET] (EtH-)
Configuring the drive’s
response
Parameter:
[External fault mgt] (EPL)
Parameter:
[COM. fault mgt] (CLL)
Menu:
Menu:
[1.8 FAULT MANAGEMENT] (FLt-)
Submenu:
[1.8 FAULT MANAGEMENT] (FLt-)
Submenu:
[EXTERNAL FAULT] (EtF-)
[COM. FAULT MANAGEMENT] (CLL-)
bNetwork management
The IP address duplication management detection cannot be configured.
If the FDR (Faulty Device Replacement) service has been configured, the FDR communication interruption detection can be disabled via
the [FDR Error Mgt.] (FdrF) parameter, which can be accessed via the [1.9 COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-)
submenu.
In factory settings mode, a network management interruption will trigger a resettable drive stop condition [External fault com.] (EPF2) and
initiate a freewheel stop.
bCommunication
It is strongly recommended that control should be reserved for a single master device.
Monitoring begins when the first control word is received.
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that a valid address for the IP master device has been specified.
Failure to follow this instruction will result in death, serious injury, or equipment damage.
Use the [IP MASTER] (IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified
using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended equipment
operation.
• If control has been reserved:
A communication interruption is triggered if the Ethernet card does not receive a Modbus TCP request within a predefined period
of time (time out).
Any type of Modbus request from the master device [IP Master] is taken into account (write operation, read operation, etc.).
• If control has not been reserved:
A communication interruption is triggered if the Ethernet card does not receive a control word write request (CMd) within a predefined
period of time (time out).
Receipt of the command (CMd) is taken into account regardless of the sender’s IP address.
The “time out” can be set to between 0.5 and 60 s via the graphic display terminal or integrated display terminal in the
[1.9 COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu via the [time Out] (tOUt) parameter. The default value is 2 s.
In factory settings mode, if Ethernet is involved in the command or setpoint, a communication interruption will trigger a resettable stop
condition [Com. network] (CnF) and initiate a freewheel stop.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Configuration
bDrive response
The drive response to an Ethernet communication interruption can be configured via the graphic display terminal or the integrated display
terminal from the [1.8 FAULT MANAGEMENT] (FLt-) menu:
RDY
NET
+0.00Hz
0A
COM. FAULT MANAGEMENT
For communication faults
in the [COM. FAULT MANAGEMENT] (CLL-) submenu
via parameter [COM. fault mgt] (CLL)
Network fault mgt
CANopen fault mgt
Modbus fault mgt
:
:
:
Freewheel
Freewheel
Freewheel
Code
Quick
RDY
NET
EXTERNAL FAULT
External fault mgt
+0.00Hz
0A
For network management faults
in the [EXTERNAL FAULT] (EtF-) submenu
via the [External fault mgt] (EPL) parameter
:
Freewheel
Code
Quick
The values of parameters: [COM. fault mgt] (CLL) that will trigger a stop response from the drive [Com. network] (CnF)
and [External fault mgt] (EPL) that will trigger a stop response from the drive [External fault com.] (EPF2) are:
[Freewheel] (YES): Freewheel stop (factory setting).
[Ramp stop] (rMP): Stop on ramp.
[Fast stop] (FSt): Fast stop.
[DC injection] (dCI): DC injection stop.
The values of parameters [COM. fault mgt] (CLL) and [External fault management] (EPL) which will not trigger a stop response from the
drive are:
[Ignore] (nO): Communication interruption detection is disabled.
[Per STT] (Stt): Stop according to configuration of [Stop type] (Stt).
[fallback spd] (LFF): Change to fallback speed, maintained as long as the communication interruption persists and the run command has
not been removed.
[Spd maint.] (rLS): The drive maintains the speed at the time the communication interruption occurred, as long as the interruption persists
and the run command has not been removed.
The fallback speed can be configured in the [1.8 - FAULT MANAGEMENT] (FLt-) menu via the [Fallback speed] (LLF) parameter.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Configuration
8. 7. Configuring monitored parameters
It is possible to select up to 4 parameters to display their values in the [1.2 - MONITORING] menu on the graphic display terminal.
The selection is made via the [6 - MONITORING CONFIG.] menu, [6.3 - COM. MAP CONFIG.] submenu.
Each parameter in the range [Address 1 select.] … [Address 4 select.]
is used to select the parameter logic address. Select an address of zero
to disable the function.
RDY
NET
+0.00Hz
0A
6.3 COM. MAP CONFIG.
Word 1 add. select.
Format word 1
Word 2 add. select.
Format word 2
Word 3 add. select.
Code
:
:
:
:
:
3204
Signed
3205
In the example given here, the monitored words are:
• Parameter 1 = Motor current (LCR): logic address 3204;
signed decimal format.
• Parameter 2 = Motor torque (OTR): logic address 3205;
signed decimal format.
• Parameter 3 = Last fault occurred (LFT): logic address 7121;
hexadecimal format.
Signed
7121
Quick
Format word 3
:
Hex
• Disabled parameter: address 0; default format: hexadecimal format.
Word 4 add. select.
Format word 4
:
:
0
Hex
One of the three display formats below can be assigned to each monitored word:
Format
Range
Terminal display
[Hex]
Hexadecimal
Signed decimal
Unsigned decimal
0000 … FFFF
-32,767 … 32,767
0 … 65,535
[Signed]
[Unsigned]
25
Download from Www.Somanuals.com. All Manuals Search And Download.
9. Diagnostics
9. 1. Signalling LEDs
The VW3A3310d Ethernet card features 5 LEDs, which are visible through the Altivar 61 / 71 cover.
1.1
1.2
1.3
1.4
1.5
Port 1 activity
2.1
Port 2 activity
Link status
NS “Network status”
MS “Module status”
2.2
2.3
2.4
2.5
The first 2 LEDS are respectively dedicated to each Ethernet port.
The third LED is relative to the IP level.
The last 2 LEDs are specific to EtherNet/IP and CIP communication protocol.
LED
Color/ state
Description
2.1
Off
No link
Flashing Green/yellow Power up testing.
Green ON
Link at 100 Mbps.
Link at 10 Mbps.
Yellow ON
Green BLINK
Yellow BLINK
Activity at 100 Mbps.
Activity at 10 Mbps.
2.2
Off
No link
Flashing Green/yellow Power up testing.
Green ON
Link at 100 Mbps.
Link at 10 Mbps.
Yellow ON
Green BLINK
Yellow BLINK
Activity at 100 Mbps.
Activity at 10 Mbps.
2.3
Off
Physical connections unplugged - No IP address obtained
Power up testing.
Flashing Green/red
Green ON
At least one port is connected and an IP address has been obtained.
Green flashing 3 times All ports are unplugged, but the card has an IP address.
Green flashing 4 times Error: Duplicated IP address (1)
Green flashing 5 times The card is performing a BOOTP or DHCP sequence
2.4
Off
The device does not have an IP address or powered off.
“NS”
Flashing Green/red
Green ON
Power up testing.
The device has at least one established Modbus connection (even to the Message Router).
The device has not established Modbus connections, but has obtained an IP address.
Green flashing
2.5
Off
No power is supplied to the device
“MS”
Flashing Green/red
Green ON
Power Up testing.
The device is ready.
Green flashing
Red flashing
Red ON
The device is not ready (waiting for cable connection, ...).
The device has detected a [Network fault] (CnF).
The device has detected a [internal com. link] (ILF) communication interruption.
(1)The Ethernet card detects IP address duplication each time it connects to the network (power-up or connection to the network).
If the card detects that another device is using the same IP address as itself, it abandons the use of the IP address and triggers the
status: [External fault com.] (EPF2).
If a device with an IP address identical to that of the drive is connected to the network during operation, the condition will not be detected
by the drive (it is the new station that has to disconnect).
26
Download from Www.Somanuals.com. All Manuals Search And Download.
9. Diagnostics
9. 2. Available information
In addition to the LEDs, the table below summarizes the diagnostic information available by various means.
Functions
Graphic display
terminal
Integrated display
terminal
PowerSuite software
workshop
Standard
web server
Control-signal diagnostics
• Control word
• Setpoint
• Active channel
• Etc.
p
p
p
p
p
p
Communication diagnostics
• Transmission counter
• Reception counter
• Collision counter
• Etc.
9. 3. Monitoring the control
On the graphic display terminal only, the [1.2 - MONITORING] menu, [COMMUNICATION MAP] submenu can be used to display control
signal diagnostic information between the drive and the Ethernet PLC:
Active command channel
Value of control word used
to send a command to the drive
(hexadecimal format)
Active setpoint channel
RUN
NET
+50.00 Hz
80A
Value of frequency setpoint
(unit 0.1 Hz) used to control the drive
COMMUNICATION MAP
Command Channel
Cmd value
Channel ref. active
Frequency ref.
Status word
Code
:
:
:
:
:
Com. card
000F
Hex
Value of status word
(hexadecimal format)
Com. card
500.0
Hz
Values of the four monitored words selected by the user.
The address and display format of these parameters
can be configured in the [6 - MONITORING CONFIG.] menu,
[6.3 - COM. MAP CONFIG.] submenu
8627
Hex
Quick
(see “Configuration” section on page 16).
The value of a monitored word is equal to “-----” if:
W3204
:
:
:
:
53
W3205
725
-
Monitoring has not been activated
(address equal to W0)
The parameter is protected
W7132
0000
Hex
Hex
-
-
W0
-----
The parameter is not known (e.g., W3200)
COM. SCANNER INPUT MAP
COM SCAN OUTPUT MAP
CMD. WORD IMAGE
Communication scanner:
Use not recommended for Ethernet
for performance reasons
FREQ. REF. WORD MAP
MODBUS NETWORK DIAG
MODBUS HMI DIAG
Control word from Ethernet
[COM. card cmd.] (CMd3)
CANopen MAP
SCANNER CARD PROG.
Frequency setpoint from Ethernet
[Com. card ref.] (LFr3)
27
Download from Www.Somanuals.com. All Manuals Search And Download.
9. Diagnostics
9. 4. Troubleshooting communication interruptions
bCommunication monitoring
Ethernet faults are indicated by the drive display and the Module Status LED on the Ethernet card.
The Ethernet card can detect 2 types of communication interruptions:
- Network management (server missing, duplication of IP address, etc.).
- Communication (time out on the master traffic, etc.).
In factory settings mode, a network management interruption will trigger a resettable drive stop response [External fault com.] (EPF2)
and initiate a freewheel stop.
In factory settings mode, if Ethernet is involved in the command or setpoint, a communication interruption will trigger a resettable drive stop
response [Com. network] (CnF) and initiate a freewheel stop.
The drive’s response in the event of an Ethernet communication interruption can be changed. Refer to the Configuration section beginning
on page 17.
The associated information is:
Ethernet communication interruption type
Network management
Communication
Associated drive parameter
Code:
[External fault com.] (EPF2)
Code:
[Com. network] (CnF)
Extended communication interruption [FDR fault] (Fdrd)
[Network fault] (CnF)
Menu:
code
Menu:
[1.9 COMMUNICATION] (COM-)
Submenu:
[1.10 DIAGNOSTICS] (dGt-)
Submenu:
[ETHERNET] (EtH-)
[MORE FAULT INFO] (AFI-)
Parameter [Network fault] (CnF) is used to obtain more detailed information about the origin of the last communication interruption
[Com. network] (CnF). It can be accessed on the graphic display terminal only, in the [1.10 DIAGNOSTICS] (dGt-) menu,
[MORE FAULT INFO] (AFI-) submenu.
Value
0
Description of the values of the [Network fault] (CnF) parameter
No communication interruption
Modbus TCP time out
1
10
11
Network overload
Loss of Ethernet carrier
The [FDR fault] (Fdrd) Ethernet communication interruption status is used to obtain more detailed information about the origin of the last
fault [External fault com.] (EPF2). It can be accessed on the graphic display terminal only, in the [1.9 COMMUNICATION] (COM-)
menu, [ETHERNET] (EtH-) submenu.
Value
Description of the values of the [FDR fault] (Fdrd) Ethernet communication interruption code parameter
No communication interruption
0
2
The FDR configuration file is not compatible with the drive type (example: the drive is not the correct rating).
Error reading the FDR configuration file on the server.
Error writing the FDR configuration file to the server.
Time-out for receipt of the FDR configuration file from the server.
Duplication of IP address (1).
3
4
7
9
12
203
FDR configuration file missing.
Inconsistent hardware configuration
(1)The Ethernet card detects IP address duplication each time it connects to the network (power-up or connection to the network).
If the card detects that another device is using the same IP address as itself, it abandons the use of the IP address and triggers the
status: [External fault com.] (EPF2).
If a device with an IP address identical to that of the drive is connected to the network during operation, the condition will not be detected
by the drive (it is the new station that has to disconnect).
28
Download from Www.Somanuals.com. All Manuals Search And Download.
9. Diagnostics
9. 5. Troubleshooting the card
The [internal com. link] (ILF) status appears when the following conditions occur:
- Hardware becomes inoperative on the Ethernet card.
- Dialog interruption between the Ethernet card and the drive.
The drive’s response in the event of an [internal com. link] (ILF) status cannot be configured, and the drive stops with a freewheel stop.
This event cannot be reset.
Two diagnostic parameters are used to obtain more detailed information about the origin of the [internal com. link] (ILF) status:
- [Internal link fault 1] (ILF1) if the interruption has occurred on option card no. 1 (installed directly on the drive).
- [Internal link fault 2] (ILF2) if the interruption has occurred on option card no. 2 (installed on option card no. 1).
The Ethernet card can be in position 1 or 2.
The [Internal link fault 1] (ILF1) and [Internal link fault 2] (ILF2) parameters can only be accessed on the graphic display terminal
in the [1.10 DIAGNOSTICS] (dGt-) menu, [MORE FAULT INFO] (AFI-) submenu.
Value
0
Description of the values of the [Internal link fault 1] (ILF1) and [Internal link fault 2] (ILF2) parameters
No communication interruption
1
Loss of internal communication with the drive
Error in the EEPROM checksum
3
101
102
103
Unknown card
Exchange problem on the drive internal bus
Time out on the drive internal bus (500 ms)
29
Download from Www.Somanuals.com. All Manuals Search And Download.
10. Software setup
10. 1. List of services supported
• Modbus TCP server, with the support of the “IO Scanning” periodic service.
• IP protocol (version 4).
• TCP and UDP protocol.
• HTTP server for configuring, adjusting and monitoring the drive.
• ICMP client for supporting certain IP services, such as the “ping” command.
• BOOTP client for assignment of an IP address by an address server.
• FTP protocol for file transfer.
• DHCP client for dynamic assignment of IP addresses by an address server.
• FDR service for replacement of a faulty device.
• SNMP protocol for network management.
• ARP protocol for detecting a competing IP address (IP address already in use).
10. 2. TCP connections
Number of simultaneous connections limited to 8 maximum (port 502).
The table below gives the number of connections consumed for each service:
Client
Service
Number of connections
IO Scanning
1
1
0
2
1
1
1
0
0
1
1
Controller (PLC)
Modbus messaging
“Home” page
“Monitoring\Altivar Viewer” page
“Monitoring\Data Viewer” page
“Monitoring\Altivar chart” page
“Diagnostics\Ethernet Statistics” page
“Setup\Security\HTTP password” page
“Setup\Security\Data write password” page
“Setup\FDR agent” page
“Setup\IO Scanner” page
Web browser
Example:
If the “Altivar Viewer” page is viewed in two different windows of a web browser, on the same PC, four connections are consumed.
If the drive is controlled by a PLC, two connections are consumed by IO Scanning and Modbus messaging, so the total number
of connections consumed is then six.
Two connections are still available, since the maximum number of simultaneous connections is eight.
If control is reserved for a device ([IP Master] (IPP-) configured), 2 connections are reserved for this device, even if it is not present
on the network.
If the maximum number of connections has been exceeded, any new connection attempt will be rejected by the Ethernet card.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Modbus TCP server
11. 1. Modbus TCP frames
Modbus TCP frames consist of a header and a Modbus request.
Header format:
Byte Description
Comments
0
high order
low order
high order
low order
high order
low order
Transaction identifier
1
2
3
4
5
6
7
Protocol identifier
Length of data
This identifier always equals 0.
Number of bytes in the Modbus request +1. The frame length is always less than
256 bytes, the value of the significant byte therefore equals 0.
Destination identifier (Unit ID)
Modbus request function code
The frame header returned by the Altivar 71 server is identical to that of the frame sent by the client.
11. 2. Drive Modbus servers
The destination identifier (Unit ID) is used to access 4 drive Modbus TCP servers:
Unit ID
Modbus TCP server
Accessible parameters
0
Variable speed drive
See the Altivar 71 Communication parameters Manual.
See the “Ethernet card parameters” section.
2048 words (%MW0 to %MW2047).
See the “IO Scanner” section.
251, AMOC Ethernet card
252, AMOA Controller Inside card
255
IO Scanner
31
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Modbus TCP server
11. 3. Ethernet card parameters
Comments:
• Parameters on 2 words are double words (low order in address word n, high order in address word n+1).
• Parameters 60 019 to 60 043 and 60 066 to 60 068 can be accessed in both read and write mode. They can be reset using
a write operation.
• The current IP addresses (60006 to 60017) are the ones displayed on the terminal.
The EEPROM IP addresses (60075 to 60079) are the ones used by the card.
Address Size
(in words)
Description
Access Possible values, comments
60 000
6
MAC address
R
00-80-F4-80-xx-yy
00: 60 000
80: 60 001
F4: 60 002
80: 60 003
xx: 60 004
yy: 60 005
60 006
60 010
60 014
60 018
4
4
4
1
Current value of IP Address
[IP card] (IPC-)
R/W
R/W
R/W
R
IPC1.IPC2.IPC3.IPC4
IPC1: 60 006
IPC2: 60 007
IPC3: 60 008
IPC4: 60 009
Current value of Subnet mask
[IP Mask] (IPM-)
IPM1.IPM2.IPM3.IPM4
IPM1: 60 010
IPM2: 60 011
IPM3: 60 012
IPM4: 60 013
Current value of Gateway Address
[IP Gate] (IPG-)
IPG1.IPG2.IPG3.IPG4
IPG1: 60 014
IPG2: 60 015
IPG3: 60 016
IPG4: 60 017
Transmission speed
[Bit rate] (bdr)
= 0: Speed not defined
= 10: 10 Mbps
= 100: 100 Mbps
60 019
60 021
60 022
60 023
60 024
60 026
60 027
60 028
60 029
60 030
60 031
60 032
60 034
60 036
60 037
60 039
60 041
60 042
60 043
60 044
2
1
1
1
2
1
1
1
1
1
1
2
2
1
2
2
1
1
1
1
OK transmission counter
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
Store-and-forward transmission counter
Late collision counter
Buffer (Tx) error counter
OK reception counter
CRC error counter
Frame error counter
Buffer (Rx) error counter
Collision counter
Multiple collision counter
OverRun counter
Sent Modbus TCP message counter
Received Modbus TCP message counter
Modbus TCP message error counter
Sent IO Scanning message counter
Received IO Scanning message counter
IO Scanning message error counter
Active traffic (msg/s)
IO Scanning messages not included
IO Scanning messages not included
IO Scanning messages not included
Max. traffic (msg/s)
Number of active TCP connections
8 maximum
32
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Modbus TCP server
Address Size
(in words)
Description
Access Possible values, comments
60 045
1
Communication monitoring
R/W
Unit: 0.1 s; min. = 5 (0.5 s); max. = 600 (60.0 s)
time out [time out] (tOUt)
60 046
60 047
60 048
1
1
1
Drive type
Reserved
R
= 2 ATV71
= 0
R
Enable IO Scanner
[IO Scan. activ.] (IOSA)
R/W
= 0 [No] (nO)
= 1 [Yes] (YES)
= 0
: IO Scanning disabled.
: IO Scanning enabled.
60 049
60 050
1
4
Reserved
R
IP address of Master [IP Master] (IPP-) R/W
IPP1.IPP2.IPP3.IPP4
IPP1 = 60 050
IPP2 = 60 051
IPP3 = 60 052
IPP4 = 60 053
60 054
4
IP address of DHCP-FDR server
[IP FDR] (IPF-)
R
IPF1.IPF2.IPF3.IPF4
IPF1 = 60 054
IPF2 = 60 055
IPF3 = 60 056
IPF4 = 60 057
60 058
60 059
1
1
Enable FDR service
[FDR validation] (FdrU)
R/W
R/W
0 = [No] (nO)
1 = [Yes] (YES)
0 = [No] (nO)
: FDR service disabled
: FDR service enabled
Select local configuration
: The drive configuration is
[FDR Local Config.] (LCFG)
downloaded from an FDR server
1 = [Yes] (YES)
: The drive configuration is local
60 060
1
Enable FDR file error detection
R/W
In the event of a problem with the FDR file (missing or invalid)
[FDR Error Mgt.] (FdrF)
0 = [No] (nO)
: The Ethernet card does not trigger
an Ethernet communication
interruption
1 = [Yes] (YES)
: The Ethernet card triggers an
Ethernet communication
interruption
60 061
60 062
1
1
FDR service command
[FDR Action] (FDrA)
R/W
R
0 = [IDLE] (IdLE) : No command
20 = [SAVE] (SAUE) : Command: save
21 = [REST] (rESt) : Command: download
22 = [DEL] (dEL)
: Command: delete
FDR service state
0 = [IDLE] (IdLE) : “Idle”
[FDR state] (FDrE)
1 = [INIT] (INIt) : Initialization
2 = [CONF] (CONF) : Configuration
3 = [RDY] (rDY)
4 = [GET] (GEt)
: Ready
: Downloading the current
configuration
5 = [SET] (SEt)
6 = [APP] (APP)
: Saving the current configuration
: Writing the FDR server
configuration to the drive
: Operational
7 = [OPE] (OPE)
8 = [UCFG] (UCFG) : Not configured
60 063
1
Ethernet communication interruption
[FDR fault] (Fdrd)
R
When an Ethernet communication interruption is present, this
parameter is used to determine the cause.
The code remains saved after the disappearance of the
condition.
2 = The FDR configuration file is not compatible with the
drive type
(example: the drive is not the correct rating)
3 = Error reading the FDR configuration file on the server
4 = Error writing the FDR configuration file to the server
7 = Time out for receipt of the FDR configuration file from the
server
9 = Duplication of IP address
12 = The FDR configuration file is missing
33
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Modbus TCP server
Address Size
(in words)
Description
Access Possible values, comments
60 064
1
Enable periodic saving
of the FDR service
[FDR autosave]
(FdrS)
R/W 0 = [No] (nO)
: Periodic saving is disabled
: Periodic saving is enabled
1 = [Yes] (YES)
60 065
1
Interval for saving
the FDR service
[FDR t. autosave]
(Fdrt)
R/W 2 to 9999, unit: min
60 066
60 067
1
1
Number of FDR save
operations
R/W
R/W
Number of FDR restore
operations
60 068
60 069
60 070
60 075
1
1
5
4
Number of FDR deletions R/W
FDR file checksum
Reserved
R
R
R
IP address
IPC1.IPC2.IPC3.IPC4
IPC1 = 60 075
(EEPROM value)
IPC2 = 60 076
IPC3 = 60 077
IPC4 = 60 078
60 079
60 083
4
4
Subnet mask
(EEPROM value)
R
R
IPM1.IPM2.IPM3.IPM4
IPM1 = 60 079
IPM2 = 60 080
IPM3 = 60 081
IPM4 = 60 082
Gateway
(EEPROM value)
IPG1.IPG2.IPG3.IPG4
IPG1 = 60 083
IPG2 = 60 084
IPG3 = 60 085
IPG4 = 60 086
60 087
60 107
20
1
Reserved
R
R
Method of assigning IP
addresses
0 = Configuration via the display terminal or PowerSuite
1 = Configuration via BOOTP
2 = Configuration via DHCP
60 108
60112
4
1
Adresse IP serveur
E-mail
R/W
E-mail activation
R/W Bit 0: Error detected by drive actuation (ETA.3)
Bit 1: Drive alarm activation (ETA.7)
Bit 2: Ethernet error activation
Bit 3: Controller Inside message activation
60113
60114
1
1
E-mail status (of the
option board)
R
E-mails number
successfully sent
R/W
60115
60116
60117
1
1
Number of errors
Last error code
R/W
R
85
E-mail address of the
destination
R/W
60202
85
E-mail address of the
sender
R/W
34
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Modbus TCP server
11. 4. List of Modbus functions supported
Code
(decimal)
3 = 16#03
Modbus name
Description
Read N output words
Size of data
63 words max.
Read Holding Registers
Write Single Register
6 = 16#06
16 = 16#10
23 = 16#17
43 = 16#2B
Write one output word
Write N output words
Read/write N words
Identification
-
Write Multiple Registers
Read/Write Multiple Registers
Read Device Identification
61 words max.
20/20 words max.
-
11. 5. “Read Holding Registers” (3) function
This Modbus request is used to read the values of a number (No. of Points) of adjacent words starting at the address indicated (Starting
Address). The values read are restored one after another, at the end of the response (First Point Data →Last Point Data).
Request format:
Byte
Meaning
0
1
2
3
4
Function Code = 16#03
Starting Address Hi
Starting Address Lo
No. of Points Hi (0)
No. of Points Lo (1 - 125)
Response format:
Byte
0
Meaning
Function Code = 16#03
Byte Count (B = 2 × No. of Points)
First Point Data Hi
First Point Data Lo
………………………
Last Point Data Hi
1
2
3
…
B
B+1
Last Point Data Lo
Exception response format:
Byte
Meaning
With the VW3A3310d Ethernet card
0
Function Code = 16#83
01 (Illegal Function)
02 (Illegal Data Address)
03 (Illegal Data Value)
04 (Illegal Response Length)
1
Exception Code
35
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Modbus TCP server
11. 6. “Write Single Register” (6) function
This Modbus request is used to write a given value (Preset Data) to the address supplied (Register Address).
Request format:
Byte
Meaning
0
1
2
3
4
Function Code = 16#06
Register Address Hi
Register Address Lo
Preset Data Hi
Preset Data Lo
Response format:
Byte
Meaning
0
1
2
3
4
Function Code = 16#06
Register Address Hi
Register Address Lo
Preset Data Hi
Preset Data Lo
Exception response format:
Byte
Meaning
With the VW3A3310d Ethernet card
0
Function Code = 16#86
01 (Illegal Function)
02 (Illegal Data Address)
03 (Illegal Data Value)
04 (Illegal Response Length)
1
Exception Code
36
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Modbus TCP server
11. 7. “Write Multiple Registers” (16 = 16#10) function
This Modbus request is used to write a number (No. of Registers) of adjacent words starting at a given address (Starting Address).
The values to be written are supplied one after another (First Register Data V Last Register Data).
Request format:
Byte
0
Meaning
Function Code = 16#10
Starting Address Hi
1
2
Starting Address Lo
3
No. of Registers Hi (0)
No. of Registers Lo (1 - 100)
Byte Count (B = 2 × No. of Registers)
First Register Data (Hi)
First Register Data (Lo)
……………
4
5
6
7
…
B+4
B+5
Last Register Data (Hi)
Last Register Data (Lo)
Response format:
Byte
Meaning
0
1
2
3
4
Function Code = 16#10
Starting Address Hi
Starting Address Lo
No. of Registers Hi (0)
No. of Registers Lo (1 - 100)
Exception response format:
Byte
Meaning
With the VW3A3310d Ethernet card
0
Function Code = 16#90
01 (Illegal Function)
02 (Illegal Data Address)
03 (Illegal Data Value)
04 (Illegal Response Length)
1
Exception Code
37
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Modbus TCP server
11. 8. “Read/Write Multiple Registers” (23 = 16#17) function
The “Read/Write Multiple Registers” service is reserved for setting up the IO Scanning service (see “IO Scanning” section).
Request format:
Byte
0
Meaning
With the VW3A3310d Ethernet card
Function Code = 16#17
Read Reference Address Hi
Read Reference Address Lo
Quantity to Read Hi (0)
Quantity to Read Lo (1 - 125)
Write Reference Address Hi
Write Reference Address Lo
Quantity to Write Hi (0)
Quantity to Write Lo (1 - 100)
Byte Count (2 × Quantity to Write)
Write Data 01 (Hi)
16#17
1
0 (not handled)
2
0 (not handled)
3
0
4
32
5
0 (not handled)
6
0 (not handled)
7
0
8
32
64
9
10
11
…
72
73
Value of 1st IO Scanner output register
(by default: value of the control word (CMd))
Write Data 01 (Lo)
……………………
……………………
Write Data 32 (Hi)
PKW output: PKE (Hi)
PKW output: PKE (Lo)
Write Data 32 (Lo)
Response format:
Byte
0
Meaning
With the VW3A3310d Ethernet card
Function Code = 16#17
Byte Count (2 × Quantity to Write)
Read Data 01 (Hi)
Read Data 01 (Lo)
……………………
Read Data 32 (Hi)
Read Data 32 (Lo)
16#17
1
64
2
Value of 1st IO Scanner input register
(by default: value of the status word (EtA))
3
…
64
65
……………………
PKW input: PKE (Hi)
PKW input: PKE (Lo)
Exception response format:
Byte
Meaning
With the VW3A3310d Ethernet card
0
Function Code = 16#97
01 (Illegal Function)
02 (Illegal Data Address)
03 (Illegal Data Value)
04 (Illegal Response Length)
1
Exception Code
38
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Modbus TCP server
11. 9. “Read Device Identification” (43 = 16#2B) function
Request format:
Byte
Meaning
With the VW3A3310d Ethernet card
0
1
Function Code = 16#2B
Type of MEI
16#2B
16#0E
16#01: Basic
2
3
Read Device ID code
Object ID
16#02: Regular
16#03: Extended
16#00
Response format:
Byte(s)
Meaning
With the VW3A3310d Ethernet card
0
1
2
3
4
5
Function code = 16#2B
Type of MEI
16#2B
16#0E
ReadDeviceId code
Degree of conformity
Number of additional frames
Next object ID
16#01
16#02
16#00 (a single frame)
16#00
3 for Basic
4 for Regular or Extended
6
Number of objects
7
8
Object no. 1 ID
16#00 = Vendor Name
Length of object no. 1 (A)
Value of object no. 1 (A ASCII characters)
Object no. 2 ID
13
9…21
22
“Telemecanique”
16#01 = Product Code
23
Length of object no. 2 (B)
Value of object no. 2 (B ASCII characters) (1)
Object no. 3 ID
11 (for the following example only)
Example: “ATV71HU15M3”
16#02 = Major.Minor Revision
4
24…23+B
24+B
25+B
Length of object no. 3 (C)
26+B…29+B Value of object no. 3 (C ASCII characters)
Example: “0201” for version 2.1
16#06 = Application Name (2)
8 (for the following example only) for Regular and Extended
Example: “MACHINE 4”
30+B
31+B
Object no. 4 ID
Length of object no. 4 (D)
32+B…31+B+D Value of object no. 4 (D ASCII characters) (1)
(1)The length of this field is variable. Use the “Length of object no. X” field associated with it to determine the length.
(2)In the case of the drive, this data item corresponds to [DEVICE NAME].
The response to a “drive identification” request does not cause an exception response.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
12. IO Scanning service
12. 1. Presentation
The IO Scanning service is used to exchange periodic I/O data between:
• A controller or PLC (IO Scanner).
• Devices (IO Scanning servers).
This exchange is usually performed by implicit services, thus avoiding the need to program the controller (PLC).
The IO Scanner periodically generates the Read/Write Multiple Registers (23 = 16#17) request.
The IO Scanning service operates if it has been enabled in the PLC and the drive.
The drive parameters assigned to IO Scanning have been selected by default. This assignment can be modified by configuration.
The table below indicates the tools which can be used to modify these configurations:
Functions
Graphic display
terminal
Integrated
display
PowerSuite
software
Standard
web server
terminal
workshop
Enable IO Scanning
p
p
p
p
p
p
Configuring the IO Scanning variables
The drive IO Scanning service can also be configured by the Ethernet card Modbus server.
When the IO Scanning service has been enabled in the Altivar 61/71 drive:
• A TCP connection is assigned to it.
• The parameters assigned in the periodic variables are exchanged cyclically between the Ethernet card and the drive.
• The parameters assigned to the periodic output variables are reserved for IO Scanning. They cannot be written by other Modbus services,
even if the IO Scanner is not sending its periodic output variables.
12. 2. Periodic variables
Output variables (written by IO Scanner)
No. Meaning/default assignment Configurable
Input variables (read by IO Scanner)
No. Meaning/default assignment Configurable
0
1
2
3
4
5
6
7
8
9
Reserved
no
0
1
2
3
4
5
6
7
8
9
Reserved
no
Control word (CMd)
Speed setpoint (LFrd)
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
no
Status word (EtA)
Output speed (rFrd)
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
no
10 Not assigned
11-31 Reserved
10 Not assigned
11-31 Reserved
It is possible to configure the assignment of periodic variables 1 to 10.
Note: • Avoid configuring the drive configuration parameters as periodic output variables because they cannot be modified with the
motor running (DSP 402 state 5—"Operation Enabled”).
• Monitoring parameters must not be configured as periodic output variables, because they cannot be written.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
12. IO Scanning service
The values of the periodic variables are listed in a table.
This table can be accessed in read-only mode by the Ethernet card Modbus server (Unit ID = 251).
Address Description
Default value
Address Description
Default value
40 001
Value of output variable 1
Value of the
control word
(CMd)
40 017
Value of read register 1
Value of the status
word (EtA)
40 002
Value of output variable 2
Value of the speed
setpoint (LFrd)
40 018
Value of read register 2
Value of the output
speed (rFrd)
40 003
40 004
40 005
40 006
40 007
40 008
40 009
40 010
Value of output variable 3
Value of output variable 4
Value of output variable 5
Value of output variable 6
Value of output variable 7
Value of output variable 8
Value of output variable 9
Value of output variable 10
40 019
40 020
40 021
40 022
40 023
40 024
40 025
40 026
Value of input variable 3
Value of input variable 4
Value of input variable 5
Value of input variable 6
Value of input variable 7
Value of input variable 8
Value of input variable 9
Value of input variable 10
12. 3. Address table
The periodic variables are defined in the address table.
This table can be accessed in read-write mode by the Ethernet card Modbus server (Unit ID = 251).
Address Description
Default value
Address Description
Default value
50 001
50 002
50 003
50 004
50 005
50 006
50 007
50 008
50 009
50 010
Logic address
of output variable 1
Address of the control word
(CMd) = 8501
50 017
50 018
50 019
50 020
50 021
50 022
50 023
50 024
50 025
50 026
Logic address
of input variable 1
Address of the status
word (EtA) = 3201
Logic address
of output variable 2
Address of the speed setpoint
(LFrd) = 8602
Logic address
of input variable 2
Address of the output
speed (rFrd) = 8604
Logic address
of output variable 3
0
0
0
0
0
0
0
0
Logic address
of input variable 3
0
0
0
0
0
0
0
0
Logic address
of output variable 4
Logic address
of input variable 4
Logic address
of output variable 5
Logic address
of input variable 5
Logic address
of output variable 6
Logic address
of input variable 6
Logic address
of output variable 7
Logic address
of input variable 7
Logic address
of output variable 8
Logic address
of input variable 8
Logic address
of output variable 9
Logic address
of input variable 9
Logic address
Logic address
of output variable 10
of input variable 10
To modify the address table, IO Scanning must be disabled (only when the motor is stopped).
41
Download from Www.Somanuals.com. All Manuals Search And Download.
13. FDR service
13. 1. Presentation
The Faulty Device Replacement (FDR) service is used to simplify the maintenance or replacement of drives connected on the Ethernet
network. Not all PLCs and control system devices are able to use the FDR service. Consult the appropriate documentation for the
associated controller devices.
If a drive controller is replaced, this service quickly reconfigures its replacement.
The new drive (FDR client) retrieves:
• Its IP addresses and the FDR file path from a DHCP server.
• The FDR file from an FTP server, if the drive is not configured in local configuration.
In practice, the DHCP server and the FTP server are the same device (TSX Premium or Quantum PLC).
The FDR file contains:
• The Ethernet parameters (configuration of IO Scanning, FDR etc.).
• The drive parameters (drive, functions, application, etc.).
The FDR service is based on identification of the device by a “Device Name”. In the case of the Altivar 71 drive, this is represented
by the [DEVICE NAME] parameter.
Configuration using the drive graphic display terminal or the integrated display terminal is explained in the “Configuration” section.
Configuration using the standard web server is explained in the “Standard web server” section.
For configuration using the PowerSuite software workshop, refer to the software online help.
Note: Check that each network device has a unique “Device Name”.
The FDR server controls duplication of “Device Names” (it does not assign an IP address that has already been assigned and is active).
If the same IP address is supplied on 2 devices, the 2nd should trigger an IP address duplication [External fault com.] (EPF2).
If the FDR service has been enabled, the Ethernet card attempts to restore its IP addresses on each power-up. Each time the procedure is
unsuccessful, the Ethernet card reiterates its FDR requests (DHCP).
Where the configuration also needs to be downloaded by the FDR server:
After assigning the Ethernet card IP addresses, if the configuration download is unsuccessful, the Ethernet card detects a network
management interruption [External fault com.] (EPF2).
42
Download from Www.Somanuals.com. All Manuals Search And Download.
13. FDR service
13. 2. Local configuration
IP assignment
Save
If the drive parameter configuration is local, the FDR server only assigns the IP addresses:
• Card IP address.
• Subnet mask.
• Gateway IP address.
On connection to the network, the drive automatically saves its parameters in the FDR server.
To make the system operational, it is necessary to:
• Configure the FDR server.
• Configure the drive.
• Turn off the drive.
• Connect the drive to the network.
MConfigure the FDR server
See the PLC manual or the section on software setup using PL7.
MConfigure the drive
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0)
• Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES)
• Select local drive configuration: [FDR Local Config.] (LCFG) = [Yes] (YES)
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu.
This menu can only be accessed in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).
MTurn the drive off and then back on again
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken
into account.
MConnect the drive to the network
43
Download from Www.Somanuals.com. All Manuals Search And Download.
13. FDR service
13. 3. Downloaded configuration
IP assignment
Save
Downloading
If the drive parameter configuration has been downloaded, the FDR server assigns:
MThe IP addresses
• Card IP address.
• Subnet mask.
• Gateway IP address.
• FDR server IP address.
MDrive parameters (configuration)
bFirst use
Procedure:
• Configure the drive.
• Turn off the drive.
• Connect the drive to the network.
• Configure the FDR server (see the PLC manual).
• Supply the FDR server with the configuration file.
• Check that the system is operational.
In the procedure described below, the configuration file is supplied to the FDR server, via the Ethernet network, using a save command
performed on the drive graphic display terminal.
Note: This procedure can also be performed using a web browser, which is more user-friendly than the drive graphic display terminal
(see the “Standard web server” section).
MConfigure the drive
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES).
• Caution, before the first connection, you must select local drive configuration: [FDR Local Config.] (LCFG) = [Yes] (YES).
The drive must first supply the configuration to the server.
If this option is not selected, an invalid or null configuration file may be uploaded to the FDR server. Subsequent drives would then receive
incorrect configuration files, leading to unexpected behavior.
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that the local configuration option [FDR Local Config.] (LCFG)=[Yes] (YES) is selected when configuring the first drive.
Failure to follow this instruction will result in death, serious injury, or equipment damage.
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu.
This menu can only be accessed in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).
MTurn the drive off and then back on again
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken
into account.
MConnect the drive to the network
44
Download from Www.Somanuals.com. All Manuals Search And Download.
13. FDR service
MDownload the IP addresses
• Connect the drive and the FDR server (PLC) to the Ethernet network.
• The server downloads the IP addresses to the Ethernet card.
Check that the operation has proceeded correctly:
• The “STS” LED should be on.
You can also check, in the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu whether the [IP card] (IPC1)
(IPC2) (IPC3) (IPC4), [IP Mask] (IPM1) (IPM2) (IPM3) (IPM4) and [IP Gate] (IPG1) (IPG2) (IPG3) (IPG4)
parameters have values other than [0.0.0.0] (0) (0) (0) (0).
MSave the drive configuration parameters in the FDR server
• Configure the drive parameters.
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Specify that the drive configuration is to be downloaded from the FDR server on each power-up: [FDR Local Config.] (LCFG) = [No] (nO).
• Send a save command to the FDR server: [FDR Action] (FdrA) = [SAVE] (SAUE).
After execution of the command, the [FDR Action] (FdrA) parameter reverts to the value [IDLE] (IdLE).
MCheck that the system is operational
Check that the operation has proceeded correctly:
• The “STS” LED should be on.
• The [FDR state] (FdrE) parameter should be at the value [OPE] (OPE).
If the save operation has not been successful, the card triggers a drive status [External fault com.] (EPF2).
bReplacing a drive
Procedure:
• Configure the drive.
• Turn off the drive.
• Connect the drive to the network.
• Check that the drive is operational.
MConfigure the drive
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES).
• Specify that the drive configuration is to be downloaded from the FDR server on each power-up:
[FDR Local Config.] (LCFG) = [No] (nO).
These configurations are the default values.
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu.
This menu can only be accessed in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).
MTurn the drive off and then back on again
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken
into account.
MConnect the drive to the network
MCheck that the system is operational
Check that the operation has proceeded correctly:
• The “STS” LED should be on.
• The [FDR state] (FdrE) parameter should be at the value [OPE] (OPE).
If downloading has not been possible after a period of 2 min following assignment of the IP addresses, the card triggers a drive status
[External fault com.] (EPF2).
45
Download from Www.Somanuals.com. All Manuals Search And Download.
13. FDR service
13. 4. Periodic saving
Periodic saving of the drive configuration can be configured on the FDR server in either local configuration or downloaded
configuration mode.
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Select: [FDR autosave] (FdrS) = [Yes] (YES).
• Set the [FDR t.autosave] (Fdrt) parameter.
Note: Saving too often risks overburdening the network and adversely affecting its performance (factory setting: 10 min).
13. 5. Other commands
On request, the configuration saved in the FDR server can be downloaded to the drive using the [FDR Action] (FdrA)
command = [REST] (rESt).
The saved configuration can be deleted from the FDR server using the [FDR Action] (FdrA) command = [DEL] (dEL).
13. 6. Configuration file
The configuration file, XXXX.prm where XXXX is the DeviceName, is an HTML file which contains the entire drive configuration
as a comment.
The HTML format is a simple way of providing the user with a summary of the configuration. An example appears below:
FDR Configuration File
File Revision: 2
ATV Revision: 1.0IE1.0
Catalog number: ATV-71HU15M3
CheckSum File: SE92
b Limitations
• The FDR configuration file XXXX.prm coming from an Ethernet V2.1 or V3.0 option board cannot be applied on a V1.1 option board. If
applied, an ILF fault will appear.
• The FDR service is able to store the current configuration of the drive, but does not provide the possibility to store multi-configurations or
multi-parameters configurations.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 1. Web server functions
Menu
Page
Function
HOME
English
Home page
Altivar Viewer
Data Viewer
Display of the main drive parameters (motor speed, state of drive logic and analog IO, status)
Display and modification (password-protected) of the drive parameters, arranged by category
MONITORING
DIAGNOSTICS
Display of two drive parameters (speed, voltage, etc.) in the form of an oscilloscope type
time chart
Altivar Chart
Display and resetting of the communication statistics
Drive identification
Ethernet Statistics
[Security]
HTTP password
Changing the HTTP password used to access the web server
[Security]
Data write password
Changing the Write password that allows modification of the parameters
Display of the state and management of the Ethernet card FDR agent
FDR Agent
IO Scanner
References
SETUP
Display and modification (password-protected) of the assignment of the IO Scanning
periodic variables
Enabling and disabling of IO Scanning (password-protected)
Setting (password-protected) of the IO Scanning and Modbus TCP messaging time outs
Link to the site http://www.telemecanique.com
DOCUMENTATION
“Home” menu
“Monitoring” menu
“Altivar Viewer” page
A
“Data Viewer” page
A
“Altivar Chart” page
A
“Diagnostics” menu
“Setup” menu
“Ethernet Statistics” page
A
“Security” submenu
“Data write password” page
“HTTP password” page
“FDR Agent” page
A
“IO Scanner” page
A
“Documentation” menu
Pages which contain applets are marked “A”. See page 48 for more information.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 2. Applets
The web server downloads Java programs called “applets” to your computer. These applets communicate with the drive using Modbus
services (on port 502), thus establishing one or more connections between the computer and the drive. Until an applet has been fully
transmitted from the drive to the browser, a gray rectangle appears in the place reserved for it in the page.
The applet connects when the page is opened and remains connected until the page is closed.
Display problems can appear with the SUN “Java virtual machine” (JVM). Use the Internet Explorer default JVM. Consult your internet
browser’s Help files for assistance with configuring your browser’s Java settings.
The applets associated with the web pages monitor communication with the drive. When the drive no longer responds to requests to update
the data, the message “Link down” is displayed in one field and the other field contents are emptied.
Subsequently, the description of each page indicates the data refresh period requested by the applet loaded on the computer. The refresh
period actually observed depends on:
• The performance of the computer on which the web browser is running.
• The communication system response time.
• The amount of data to be refreshed on the page.
48
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 3. Access to the web server
Number of Modbus TCP connections
0
To connect to the web server of a drive located, for example, at IP address 139.160.69.241 enter the URL
“http://139.160.69.241/” in the address bar of a web browser.
When the browser first connects to the drive web server, it requests entry of a username and a password (HTTP password).
14. 4. Username and password
By default, the username and the password (HTTP password) are both “USER” (upper case).
If authentication is accepted, the home page is displayed. If not, after three attempts, access to this page is denied as illustrated below:
To attempt a new connection to the drive server home page, simply refresh the web browser display (F5 key or “Refresh” button,
for example).
49
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 5. Web server user interface
The drive web server pages have the same appearance:
1 A bar at the top containing links to HTML pages for the main menus: “Home”, “Documentation”, “Monitoring”, “Control”, etc.
This bar is the same regardless of which HTML page is being viewed.
Note: The “Control” and “Maintenance” menus are disabled. They only appear because of the “Transparent Ready” common interface.
2 A menu down the left-hand side which displays links to the HTML pages available in the selected menu.
3 The center part of the window displays the information for the selected page.
1
1
2
3
14. 6. “Home” menu
Number of Modbus TCP connections used
0
The home page or “Home” menu contain the following items:
• A “Languages” submenu containing:
- A link to the “English” page
The only link in the “Languages” submenu sends the user to the home page in English and configures the web browser to open the HTML
case of English).
14. 7. “Monitoring” menu
Number of Modbus TCP connections used
0
The “Monitoring” menu contains the following items:
• A link to the “Altivar Viewer” page.
• A link to the “Data Viewer” page.
• A link to the “Altivar Chart” page.
50
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 8. “Altivar Viewer” page
Number of Modbus TCP connections used
This page gives an overview of the drive state.
2
Refresh period
0.5 s
The state indicated in the “Altivar State” field corresponds to the display on the drive integrated display terminal. A delay may sometimes
be noticed between the displays on the web server and the display terminal, depending on the performance of the computer used to display
the pages using a web browser and the communication system performance.
The motor speed displayed on the “Motor Speed” gauge is calibrated according to the maximum frequency [Max frequency] (tFr)
and the number of pairs of poles [Pr] (PPn).
The LI… area gives the state of the drive terminals (logic inputs LI1 to LI14, logic outputs LO1 to LO4, relay outputs R1 to R4, analog inputs
AI1 to AI4 and analog outputs AO1 to AO3). When a logic input is active, the LED is green. When a logic output is active, the LED is red.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 9. “Data Viewer” page
This page is used to display the drive parameters and modify their values.
The parameters are arranged in groups, and consistent with the keypad and user manuals
The display mode for each value depends on the nature of the parameter.
• The unit for the physical values is displayed in the “Unit” column.
• The registers (bit fields) are displayed in hexadecimal format (16#xxxx).
• Signed values are displayed as such.
To begin monitoring, click the “Start animation” button:
To modify the parameter value, click the “Write value of selected row” button then select the parameter to modify
It is only possible to modify the parameter values after entering the “Write password” (see “HTTP password” and “Data write password
pages” section on page 55). Click on the “Password” button to enter this password. An entry field then appears in the parameter table, and
also a “Cancel” button, for canceling the password entry. After entering the password, press the Enter key so that it is taken into account
by the web browser.
When the value of a parameter cannot be modified, a message box appears: “This parameter can't be written!”
This is the case for any parameter until you have correctly entered the Password. If IO Scanning has been enabled, modifying the value of
a parameter assigned to periodic output variables will have no effect since this value is updated cyclically by the PLC. The same applies if
a parameter is written periodically by a Modbus service.
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that an IP Master has been configured before modifying values with the Data Viewer.
Failure to follow this instruction will result in death, serious injury, or equipment damage.
It is possible to write the command word using the Data Viewer. It is mandatory to configure an IP master in order to avoid undesired action.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 10. “Altivar Chart” page
Number of Modbus TCP connections used
1
Refresh period
1 s
This page is used to monitor two drive parameters simultaneously.
Two parameters can be selected and displayed simultaneously. To do this, select them in the Trace1 and Trace2 list.
To change the display range, you can modify the curve minimum and maximum points by entering the values directly in fields Min and Max
for each trace.
To speed up sampling, enter a value of 0 in the interval Intv(s) field.
Note: Entering a value of 0 in the Intv(s) field increases the traffic on the Ethernet network and can cause collision problems if there is too
much traffic, thereby reducing the overall network performance. If this problem occurs, increase the sampling period.
To start the oscilloscope function, press the Run/Stop button. Pressing the button again stops the sampling and updates the screen.
Reset: clears the active traces.
14. 11. “Diagnostics” menu
Number of Modbus TCP connections used
0
The “Diagnostics” menu contains the following item:
• A link to the “Ethernet Statistics” page.
53
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 12. “Ethernet Statistics” page
Number of Modbus TCP connections used
1
Refresh period
0.5 s
This page provides the Ethernet statistics and the drive identification data.
14. 13. “Setup” menu
Number of Modbus TCP connections used
0
The “Setup” menu contains the following items:
• A “Security” submenu containing:
- A link to the ”HTTP password” page.
- A link to the ”Data write password” page.
• A link to the ”FDR Agent” page.
• A link to the ”IO Scanner” page.
• A link to the ”E-mail” page.
54
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 14. “HTTP password” and “Data write password pages”
Number of Modbus TCP connections used (for each page)
0
These two pages are used to modify the two web server passwords.
By default, the username and both passwords are: “USER” (upper case).
The username can only be modified using the PowerSuite software workshop.
The username and the “HTTP password” are used to access the web server in display mode.
The “Write password” is used to access the web server in modification mode.
When the value of a parameter cannot be modified, the background of the corresponding cell appears grayed-out. This is the case for any
parameter until you have correctly entered the “Write password”.
Note: Do not lose the username or the passwords. If they are lost, the card must be rest. Contact you Schneider Electric representative for
instructions.
55
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 15. “FDR Agent” page
Number of Modbus TCP connections
1
Refresh period
1s
This page displays the main parameters used by the VW3A3310d Ethernet card FDR function and is used to configure these parameters.
See the “FDR Service” section.
Information
on the FDR
Agent page
Corresponding
terminal display
Description/Possible values
IP Address
[IP card]
(IPC-)
Ethernet card IP address
Subnet mask
NetMask
[IP Mask]
(IPM-)
Gateway
[IP Gate]
Gateway IP address
(IPG-)
FTP Server
[IP FDR]
(IPF-)
Indicates the IP address of the FDR server that has supplied the Ethernet card
configuration, in particular its IP addresses.
This is the server which also supplies the drive configuration file, if [FDR Local Config.]
(LCFG) = [No] (nO).
DeviceName
Device File
[DEVICE NAME]
Not accessible
Used by the DHCP server to assign the Ethernet card IP addresses dynamically
(example: Machine 157).
Name of FDR configuration file.
The file name is consistent with the DeviceName (in our example: Machine 157.prm).
If the FDR server file has not been downloaded to the drive, “Local” is displayed in this field.
Device Reference -
Drive catalog number.
Checksum File
Not accessible
Drive configuration Checksum value. Whenever a drive parameter is modified, this value
changes.
56
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
Information
on the FDR
Agent page
Corresponding
terminal display
Description/Possible values
Validation
Local Config
File Error
[FDR validation]
(FdrU)
Enables the FDR function
• Off = [No] (nO): FDR service disabled.
• On = [Yes] (YES): FDR service enabled.
[FDR Local Config.]
(LCFG)
Selection of local or server configuration
• Off = [No] (nO): The drive configuration is downloaded from an FDR server.
• On = [Yes] (YES): The drive configuration is local.
[FDR Error Mgt.]
Enables the FDR file error detection.
(FdrF)
• Off = [No] (nO): In the event of a problem with the FDR file (missing or invalid),
the Ethernet card does not trigger an Ethernet [FDR fault] (Fdrd).
• On = [Yes] (YES): In the event of a problem with the FDR file (missing or invalid),
the Ethernet card triggers an [FDR fault] (Fdrd).
AutoSave
[FDR autosave]
(FdrS)
Enables periodic saving of the FDR service.
• Off = [No] (nO): Automatic saving disabled.
• On = [Yes] (YES): Automatic saving enabled.
Period
[FDR t.autosave]
(Fdrt)
Interval for periodic saving of the FDR service.
2 min to 9999 min
FDR State
[FDR state]
FDR service state.
(FdrE)
• Idle = [IDLE] (IdLE): FDR service inactive.
• Initialization = [INIT] (InIt): Initialization of the current Ethernet card.
• Configuration = [CONF] (COnF): Configuration of the current Ethernet card.
• Ready = [RDY] (rdY): Ethernet card ready.
• Get Conf = [GET] (GEt): Downloads the current configuration from the FDR server.
• Store Conf = [SET] (SEt): Saves the current configuration to the FDR server.
• Apply Conf = [APP] (APP): Writes the FDR server configuration to the drive.
• Operational = [OPE] (OPE): Operational.
• Unconfigured = [UCFG] (UCFG): FDR service interruption.
Error Code
[FDR fault]
Ethernet error code.
(Fdrd)
• = [0]: No communication interruption
• Service Unavailable = The FDR server is not available.
• = [2]: The FDR configuration file is not compatible with the drive type
(example: the drive is not the same rating as that defined in the FDR file).
• = [3]: Error reading the FDR configuration file on the server.
• = [4]: Error writing the FDR configuration file to the server.
• = [7]: Time out for receipt of the FDR configuration file from the server.
• = [9]: Duplication of IP address.
• File Not Found = [12]: The FDR configuration file is missing.
• = [203]: Inconsistent hardware configuration.
Save Counter
Not accessible
Number of times the configuration has been saved to the FDR server.
This counter is incremented even if the drive configuration is identical to that of the server.
Restore Counter Not accessible
Number of times the configuration has been downloaded from the FDR server.
This counter is not incremented if the drive configuration is identical to that of the server
(comparison of checksums).
Delete Counter
Save File
Not accessible
Number of times the configuration file has been deleted in the FDR server.
[FDR Action]
Command to save the configuration to the FDR server.
(FdrA)
Corresponds to the display terminal command: [SAVE] (SAUE).
Restore File
Delete File
[FDR Action]
(FdrA)
Command to download the configuration from the FDR server.
Corresponds to the display terminal command: [REST] (rESt).
[FDR Action]
Command to delete the configuration file in the FDR server.
(FdrA)
Corresponds to the display terminal command: [DEL] (dEL).
Reset counter
Not accessible
Command to reset the “Save counter”, “Restore counter” and “Delete counter” counters.
57
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 16. “IO Scanner” page
Number of Modbus TCP connections
1
Refresh period
1s
This page is used to:
• Enable or disable IO Scanning.
• Display and modify assignment of the IO Scanning periodic variables.
• Set the communication monitoring time out.
The default configuration is described in the screen below:
Modifications are protected by the “Write password” modification password. Click on the “PassWord” button to enter the
“Write password”. After correctly entering the password, you can access “IoScanner”, “Time Out (s)”, “Master”, “Output parameters”,
“Input parameters” and the “Save” and “Abort” buttons.
By default, the password is “USER”. It can be modified in the “Data write password” page.
58
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
bEnabling IO Scanning
Control by the IO Scanner is enabled if the “IoScanner” field is set to “Yes” and disabled if the “IoScanner” field is set to “No”.
The “IoScanner” field corresponds to the parameter [IO Scan.activ.] (IOSA).
DANGER
UNINTENDED EQUIPMENT OPERATION
• Do not disable a drive's IO scanning support when the PLC is using the IO scanner to monitor/control client devices.
• Do not modify the assignment of the periodic variables if the PLC is using IO scanning to monitor/control client devices.
Disabling a drive's IO Scanning or modifying the assignment of periodic variables can result in a loss of control via the network, and could
result in unintended equipment operation.
Failure to follow these instructions will result in death, serious injury, or equipment damage.
Disabling a drive's IO Scanning or modifying the assignment of periodic variables can result in a loss of control via the network, and could
result in unintended equipment operation.
Note: Disabling IO Scanning results in loss of control if a PLC is using the IO Scanner.
Before disabling IO Scanning, you must disable the time out (set the value to 0). However, communication monitoring remains active and
the card will detect a communication interruption at the end of the period defined by the time out. In factory settings mode, a communication
interruption will trigger a resettable stop condition [Com. network] (CnF) and initiate a freewheel stop.
Once the value in the “IoScanner” field has been modified, it may take a while to update the page, depending on the capacity of your
computer and network.
The “IoScanner” field corresponds to the parameter [IO Scan.activ.] (IOSA).
bAssigning the IO Scanning periodic variables
Note: Modifying the assignment of the periodic variables can result in loss of control if a PLC is using the IO Scanner.
To modify the IO Scanning periodic variables, proceed as follows:
1 Enter “No” in the “Io Scanner” field.
2 Modify the assignment of periodic variables.
3 Apply these modifications using the “Save” button.
4 Enter “Yes” in the “Io Scanner” field.
Once the value in the “IoScanner” field has been set to “No”, it may take a while to update the page, depending on the capacity of your
computer.
A drop down menu is used to modify the assignment of each of the periodic variables.
Click on the periodic variable whose assignment you wish to modify, then choose the code corresponding to the drive parameter to be
assigned.
Modifications to “Output parameters” and/or “Input parameters” can be confirmed by clicking the “Save” button or canceled by clicking the
“Abort” button.
Each time the “Save” button is pressed the address table will be saved to an EEPROM on the Ethernet card.
The assignments are now saved, even if the power is turned off.
59
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
bTime out
This page can also be used to modify the communication monitoring “time out”. Entries must be confirmed by pressing “Enter”.
The accepted values are as follows:
0: No communication check.
0.5 to 60.0 s: Time out value.
See the “Configuration - Communication faults” section.
The default time out value is 2 s (display: “2.0”).
The “Time Out” field corresponds to the [time out] (tOUt) parameter.
bMaster
See the “Reserving control” section.
To configure reservation, enter an IP address other than [0.0.0.0] in the “Master” field. This field is equivalent to the [IP Master] (IPP-)
parameter.
60
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 17. “E-mail” page
The configuration page of the E-mail service is available in the setup menu VE-mail of the option board web page, only for V2.1 version
and above.
This service is able to generate and send e-mails to a predefined address in case of alarms or drive detected faults. The controller inside
option board can also initiate the sending of an e-mail.
It is possible to configure the E-mail service after entering the “Write password” (see “HTTP password” and “Data write password pages”
section on page 55).
Enter the following information to configure the E-mail service:
E-mail IP Server: IP address of the E-mail server that will process the message (SMTP server)
E-mail Dest @: E-mail address of the E-mail recipient
E-mail From @: E-mail address of the Ethernet option board which will send the e-mail (this is a virtual address since the option board
does not provide any incoming e-mail box)
Configure the triggering mode for sending E-mail:
Drive Fault: an E-mail is sent when a drive detects a fault (triggered by ETA status word bit 3)
Drive alarm: an E-mail is sent when a drive generates an alarm (triggered by ETA status word bit 7)
Eth. Board fault: an E-mail is sent if an ethernet board becomes inoperative
PLC Board status: an E-mail is sent on demand from the application of the Controller Inside Card.
E-mail example sent on CNF fault of the Ethernet board:
From:
Subject:
Date:
Error CNF on Altivar Drive
Wed, 14 Dec 2005 14:55:32 +0100
Fault occurred on Ethernet Board's Drive:
DeviceName: ATV
IP Address: 139.160.69.241
Reference: ATV71H037M3
Description: TimeOut TCP/Modbus (CNF)
IMPORTANT NOTICE
This E-mail has been automatically generated. Please do not reply.
Copyright © 2005, Schneider Automation. All rights reserved
Service diagnostic:
• E-mail Status
- 0 VIdle
- 1 VOperational
- 2 VStopped
• SentCount: number of e-mails successfully sent
• ErrorCount: number of errors occurred
• LastError: last error code
61
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Standard web server
14. 18. “Documentation” menu
Number of Modbus TCP connections used
0
The “Documentation” menu contains a link to the “References” page.
62
Download from Www.Somanuals.com. All Manuals Search And Download.
15. FTP server
bAccess
The Ethernet card has a structured FTP server which is used to:
• Access the embedded web server resource files.
• Store the FDR (Faulty Device Replacement) service configuration files.
Access to the FTP server is restricted. To access it, the user has to enter a username and a password:
• The username is USER.
• The default HTTP password is USER. It can be changed by the standard web server.
Username
HTTP password
IP address
To obtain this display in Internet Explorer, first activate the “Enable folder view for FTP sites” option (located in Tools, Internet Options …,
Advanced, Browsing).
The FTP server accepts up to 2 FTP clients connected at the same time.
The FTP server content cannot be modified if the motor is running.
63
Download from Www.Somanuals.com. All Manuals Search And Download.
15. FTP server
bFunctions
The table below describes the functions available:
FTP functionality
Comment
Handled
Username check. Accepts or rejects connection
HTTP password check. Accepts or rejects
User output
Handled
Handled
Type of file system
Create a volume or disk
Change file name
Handled. “DOS”.
Not handled
Handled
Delete a file
Handled
Open a file
Handled in read/write mode
Handled
Read a file
Write a file
Handled
Close a file
Handled
Open a directory
Handled
Close a directory
Handled
Change directory
Handled
Current directory = parent directory
Delete a directory
Handled
Handled
Create a directory
Handled
Restore current directory
Read next directory input
Handled
Handled
bFile system
The FTP server “fdr” directory is fixed. The RD (remove directory) command therefore has no effect on this directory.
However, the whole “html” directory can be modified using the MD (make directory) and RD commands.
Note: Before modifying the content of this directory, remember to save it to the hard disk of your PC. Do not modify this saved directory
because in the event of a problem, you can use it to restore the original content of the FTP server “html” directory.
The file system is DOS type. The response to DIR or LS commands is as follows:
08-28-01 08:07AM
08-28-01 08:07AM
<DIR>
Java
57346
AtvSys.jar
The Ethernet card manages the time and date of web server file save operations.
But there is a specific procedure for starting the Ethernet card date/time function:
• Connect a browser to the standard web server.
• Open one of the pages containing a Java applet (Altivar Viewer, Data Viewer, Altivar chart, Ethernet Statistics, FDR agent, IO Scanner).
• On each connection, the applet sends the date and time present on the PC, from which it is executed.
The date/time function remains active until midnight. After midnight, it is automatically deactivated.
Note: If the date/time function has not been activated, the date and time used to date-stamp the web server files are those supplied by the
Ethernet card software.
64
Download from Www.Somanuals.com. All Manuals Search And Download.
16. Downloading from the web server
bPrinciple
PC
VW3A3310d Ethernet card
File system
Write to
Flash memory
FTP server
Read
Internet
Explorer
Read
HTTP server
The Ethernet card has an embedded FTP server which authorizes access to the various URLs available for the HTTP server. A browser
such as Internet Explorer can be used to display the URLs like a disk in the Windows explorer. This “disk” consists of various directories
containing the URL files. It is therefore possible to use the different commands managed by Windows explorer such as deletion, renaming
or writing (downloading) files (check that card IO Scanning has been disabled).
bFile management
The memory zone assigned to the web server URLs consists of 24 blocks:
• 23 sectors of 64 Kb for file storage.
• 1 sector of 64 Kb for the file table.
The web server storage capacity is 1.5 Mb, i.e. 1536 Kb.
The file table is used to make the link between the HTTP server, the FTP server and the various “URL” files. This table is dynamic and is
cleared and reprogrammed each time there is a change.
The maximum number of URL files is limited to 150.
The information relating to each file is as follows:
• File name (32 characters max.).
• Location address in the card memory.
• File size in bytes.
• “FTP” storage directory (html, html/lib/js etc.).
• URL processing function. (Access management, etc.). The URLs have a default function which requires a password (“HTTP password”)
in order to access them via HTTP, apart from a few exceptions (see below).
65
Download from Www.Somanuals.com. All Manuals Search And Download.
16. Downloading from the web server
Each URL in the HTTP server is stored in the file table. As a result, the user can easily change the standard web server by adding, deleting
or modifying the URL files.
However, some URLs are required and/or cannot be modified.
• The “index.htm”, “html/english/home/index.htm” and “html/english/home/home.htm” pages, which form the entry page to the web server, are
compulsory.
• The WebServer.htm page (see later), and the various HTML requests, such as password modification, are fixed and are not visible via
the FTP server.
The maximum file size is limited to 64 Kb. The size of the AtvSys.jar java archive file, containing the java applets, is almost 64 Kb.
If additional java applets are required, two archive files must be created.
bWeb server
The web server has a masked page, which cannot be accessed directly via a hyperlink, providing access to a summary of the memory
resources, sector by sector, used by the web server.
Example of access: http://192.168.1.23/WebServer.htm
Memory Sector
Sector 12
Sector 13
Sector 14
Sector 15
Sector 16
Sector 17
Sector 18
Sector 19
Sector 20
Sector 21
Sector 22
Sector 23
Sector 24
Sector 25
Sector 26
Sector 27
Sector 28
Sector 29
Sector 30
Sector 31
Sector 32
Sector 33
Sector 34
TOTAL
Free (bytes)
1,429
Max (bytes)
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
1,507,328
FastFree (bytes)
1,429
# File
44
01
02
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
47
237
237
18,516
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
1,330,902
18,516
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
65,536
1,330,902
66
Download from Www.Somanuals.com. All Manuals Search And Download.
16. Downloading from the web server
bStandard web server resources
The web server is version HTTP 1.1 and also supports HTTP 1.0.
The HTTP server provides access to the resources (URLs) in the Ethernet card:
• HTML pages
• Images
• Java applets
• Text file (Description of the drive parameters)
File name
(Complete URL)
Size
(bytes)
File name
(Complete URL)
Size
(bytes)
Type
Type
AtvChart.htm
AtvConf.htm
AtvFdr.htm
651
630
628
880
633
660
591
WebServer.htm
-
Special
HMTL
pages
Access not permitted
Pwd change OK
Pwd change NOK
-
-
AtvView.htm
DataEditor.htm
DocReferences.htm
index.htm
-
Parameter file fdr/Current.prm
altivar71.jpg
Variable
14,982
3,582
images/Telemecanique.gif
images/TelemecaniquePocketPC
.gif
SecurityData.htm
1,570
3,216
Images
SecurityHttp.htm
1,523
648
968
560
575
760
575
856
lib/images/left.gif
lib/images/moins.gif
lib/images/plus.gif
lib/images/right.gif
AtvChart.jar
870
866
Statistic.htm
html/english/header.htm
html/english/index.htm
883
882
html/english/control/index.htm
html/english/control/menu.htm
html/english/diagnostic/index.htm
html/english/diagnostic/menu.htm
15,479
64,736
42,196
418
Java
applets
AtvSys.jar
Text file
DataFile.txt
HTML pages
html/config.js
html/english/documentation/index
.htm
575
839
lib/js/header.js
lib/js/home.js
5,629
536
html/english/documentation/men
u.htm
JavaScript
scripts
html/english/home/home.htm
html/english/home/index.htm
html/english/home/menu.htm
698
575
830
lib/js/index.js
lib/js/menu.js
lib/js/tools.js
895
4,824
261
html/english/maintenance/index.h
tm
575
64
main.css
314
988
341
655
html/english/maintenance/menu.
htm
lib/css/header.css
lib/css/main.css
lib/css/menu.css
Cascaded
Style
Sheets
html/english/monitoring/index.ht
m
575
960
html/english/monitoring/menu.ht
m
html/english/setup/index.htm
html/english/setup/menu.htm
575
1,056
The total size is 176,426 bytes for a total of 47 files (excluding special HTML pages and parameters file).
The standard web server HTML pages have been designed for a 1024 × 768 minimum screen resolution.
67
Download from Www.Somanuals.com. All Manuals Search And Download.
17. SNMP agent
bPresentation
The SNMP protocol (Simple Network Management Protocol) is used to provide the data and services required for managing a network.
The data is stored in an MIB (Management Information Base).
The SNMP protocol is used to read or write MIB data.
Implementation of the Ethernet card SNMP services is minimal, as only the required objects are handled.
Note: An SNMP agent can be configured to generate TRAPS to the SNMP Manager.
TRAPS are used to signal a specific agent state (status, reset, etc.).
The VW3A3310d Ethernet card does not handle TRAPS.
bTree structure
68
Download from Www.Somanuals.com. All Manuals Search And Download.
17. SNMP agent
bObjects handled
Objects
Description
Access Default value
SysDescr
Text description of the device
R
SCHNEIDER ATV Altivar Fast
Ethernet TCP/IP Module
SysObjectID
SysUpTime
SysContact
Pointer to the product reference
in the private MIB
R
entreprises.3833.1.7.255.6
Time elapsed since the
Ethernet card was last turned on
R
-
-
Data item used to contact
the manager of this node
R/W
SysName
Node administrative name
R/W
R/W
R
ATV
-
SysLocation
SysService
Physical location of the product
Indicates the type of service
offered by this product
72
The SysContact, SysName and SysLocation objects can be modified by the user. The values written are saved to the Ethernet card via an
SNMP client not supplied with the VW3A3310d Ethernet card.
The size of these character strings is limited to 50 characters.
Using the “public” character string as a “community string” allows the user to access objects in “read only” mode, whereas the “schneider”
character string enables read access to “read only” objects and write access to “R/W” objects.
69
Download from Www.Somanuals.com. All Manuals Search And Download.
18. Setup using PL7
bDefining the hardware configuration
Configure an Ethernet module, then configure the module so that it can communicate with the drive. The example shows a TSX Premium
PLC equipped with a TSX ETY5103 module.
70
Download from Www.Somanuals.com. All Manuals Search And Download.
18. Setup using PL7
bBOOTP configuration
The BOOTP server function consists of allocating BOOTP clients their IP addresses.
The activation conditions for the drive BOOTP client are described in the “Configuration - IP Addresses” section.
This window is used to configure the BOOTP server.
The drive MAC address is given on a label attached to its VW3A3310d Ethernet card. The IP address assigned to the drive must be entered
in the table against the MAC address.
In this example, the Ethernet card MAC address is 00.80.F4.7D.00.A3, and its IP address is 139.160.69.242.
Each line in the “Table of supplied addresses” can accept both the MAC and IP addresses of a BOOTP client.
71
Download from Www.Somanuals.com. All Manuals Search And Download.
18. Setup using PL7
bConfiguring Modbus messaging
To use Modbus messaging in PL7, the “IP address”, “Subnet mask” and “Gateway address” parameters must be configured in the
“Messaging” tab in the PLC Ethernet module configuration screen.
Data entered in the “Connection configuration” box is used to manage the PLC Modbus messaging service, but has no effect on IO
Scanning which is an independent service.
Example:
PLC IP address
Subnet mask
139.160.69.245
255.255.254.0
139.160.68.1
Gateway address
Drive IP address
139.160.69.242
Xway address
IP address
139.160.69.242
Protocol
Access
Mode
1
1.101
MODBUS
MULTI
72
Download from Www.Somanuals.com. All Manuals Search And Download.
18. Setup using PL7
bConfiguring periodic variables
This window is used to configure the IO Scanning function, described in the IO Scanning Service section on page 40.
In this example:
• The periodic variables of the drive at IP address 139.160.69.242 are associated with PLC data words.
• The drive periodic output variables (control) are associated with the 32 words (WR count) starting at PLC address %MW550 (Write Ref.).
• The drive periodic input variables (monitoring) are associated with the 32 words (RD count) starting at PLC address %MW500 (Read Ref.).
73
Download from Www.Somanuals.com. All Manuals Search And Download.
18. Setup using PL7
The addresses for the PLC %MW words correspond to the configuration in the previous example.
PLC
address
Periodic output variable
(default assignment)
PLC
address
Periodic input variable
(default assignment)
Configurable
Configurable
%MW 550
%MW 551
%MW 552
%MW 553
%MW 554
%MW 555
%MW 556
%MW 557
%MW 558
%MW 559
%MW 560
Reserved
no
%MW 500
%MW 501
%MW 502
%MW 503
%MW 504
%MW 505
%MW 506
%MW 507
%MW 508
%MW 509
%MW 510
Reserved
no
Control word (CMd)
Speed setpoint (LFrd)
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
Status word (EtA)
Output speed (rFrd)
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
%MW 561
to
%MW 511
to
Reserved
no
Reserved
no
%MW 581
%MW 531
74
Download from Www.Somanuals.com. All Manuals Search And Download.
18. Setup using PL7
bConfiguring the DHCP address server (FDR)
The DHCP server function consists of allocating BOOTP clients an IP address.
The activation conditions for the drive DHCP (FDR) client are described in the “Configuration - IP Addresses” section.
This window is used to configure the DHCP server.
The user must enter the following fields:
• “Name” to indicate the device name. In our example the ATV name is “ATV_0004”. This “name” corresponds to the FDR function
DeviceName and the drive parameter [DEVICE NAME].
• “IP address” to indicate the device IP address. In our example the ATV IP address is “139.160.69.242”.
• “Netmask” to indicate the subnet mask. In our example the subnet mask is “255.255.254.0”.
• “Gateway” to indicate the gateway IP address. In our example the gateway IP address is “139.160.68.1”.
Each line in the “Table of supplied addresses” can accept both the names and IP addresses of a DHCP client.
75
Download from Www.Somanuals.com. All Manuals Search And Download.
19. Setup using Concept
bHardware configuration
bEthernet and I/O Scanner configuration
The screen illustrated below does not apply to the 140-NOE-771-10 master module. Note that the unit ID must be set to 251 for I/O scanner.
The screen capture illustrated below incorrectly shows a Unit ID of 1.
76
Download from Www.Somanuals.com. All Manuals Search And Download.
20. Setup using ProWORX NxT
bHardware configuration (Traffic Cop)
bNetwork configuration
77
Download from Www.Somanuals.com. All Manuals Search And Download.
20. Setup using ProWORX NxT
bTCP/IP configuration
bI/O Scanner configuration
Note that the unit ID must be set to 251 for I/O scanner. The screen capture illustrated below incorrectly shows a Unit ID of 1.
78
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
30072-452-37
2008-02
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Raypak Boiler 5042004 User Guide
RCA CRT Television 32V430T User Guide
RCA Portable CD Player RCD179 User Guide
Regency Stove U39 LP1 User Guide
Roland Universal Remote GR 33 User Guide
Rosewill Network Card RC 209 EX User Guide
Samsung Projection Television HL P5085W User Guide
Samsung Projection Television SP 50L7HR User Guide
Sansui Flat Panel Television SLED4650 User Guide
Saturn Automobile 2008 Aura Hybrid User Guide