Schneider Electric Indoor Furnishings iEM3100 User Guide

iEM3100 / iEM3200 / iEM3300 series  
Energy meters  
User manual  
DOCA0005EN-04  
04/2014  
www.schneider-electric.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
The information provided in this documentation contains general descriptions and/or technical  
characteristics of the performance of the products contained herein. This documentation is not  
intended as a substitute for and is not to be used for determining suitability or reliability of these  
products for specific user applications. It is the duty of any such user or integrator to perform the  
appropriate and complete risk analysis, evaluation and testing of the products with respect to the  
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or  
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have  
any suggestions for improvements or amendments or have found errors in this publication, please  
notify us.  
No part of this document may be reproduced in any form or by any means, electronic or mechanical,  
including photocopying, without express written permission of Schneider Electric.  
All pertinent state, regional, and local safety regulations must be observed when installing and using  
this product. For reasons of safety and to help ensure compliance with documented system data, only  
the manufacturer should perform repairs to components.  
When devices are used for applications with technical safety requirements, the relevant instructions  
must be followed.  
Failure to use Schneider Electric software or approved software with our hardware products may  
result in injury, harm, or improper operating results.  
Failure to observe this information can result in injury or equipment damage.  
© 2014 Schneider Electric. All rights reserved.  
DOCA0005EN-04  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Safety information  
Important information  
Read these instructions carefully and look at the equipment to become familiar with the device  
before trying to install, operate, service or maintain it. The following special messages may  
appear throughout this bulletin or on the equipment to warn of potential hazards or to call  
attention to information that clarifies or simplifies a procedure.  
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical  
hazard exists which will result in personal injury if the instructions are not followed.  
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all  
safety messages that follow this symbol to avoid possible injury or death.  
DANGER  
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or  
serious injury.  
WARNING  
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or  
serious injury.  
CAUTION  
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or  
moderate injury.  
NOTICE  
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not  
be used with this signal word.  
Please note  
Electrical equipment should be installed, operated, serviced and maintained only by qualified  
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the  
use of this material.  
A qualified person is one who has skills and knowledge related to the construction, installation, and  
operation of electrical equipment and has received safety training to recognize and avoid the hazards  
involved.  
4
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Notices  
FCC Part 15 notice  
This equipment has been tested and found to comply with the limits for a Class B digital device,  
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection  
against harmful interference in a residential installation. This equipment generates, uses, and can  
radiate radio frequency energy and, if not installed and used in accordance with the instructions, may  
cause harmful interference to radio communications. However, there is no guarantee that interference  
will not occur in a particular installation. If this equipment does cause harmful interference to radio or  
television reception, which can be determined by turning the equipment off and on, the user is  
encouraged to try to correct the interference by one or more of the following measures:  
Reorient or relocate the receiving antenna.  
Increase the separation between the equipment and receiver.  
Connect the equipment to an outlet on a circuit different from that to which the receiver is  
connected.  
Consult the dealer or an experienced radio/TV technician for help.  
This Class B digital apparatus complies with Canadian ICES-003.  
DOCA0005EN-04  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
About the book  
Document scope  
This manual is intended for use by designers, system builders and maintenance technicians with an  
understanding of electrical distribution systems and monitoring devices.  
Validity note  
The meters are used to measure the amount of active energy consumed by an installation or a part of  
an installation.  
This function meets the requirements for:  
consumption monitoring,  
evaluation of energy items (cost, accounting, etc.).  
This function may also satisfy the power-saving incentives implemented by many countries.  
Related documents  
Title of documentation  
Reference number  
Installation sheet: iEM3100 / iEM3110 / iEM3115  
Installation sheet: iEM3150 / iEM3155  
Installation sheet: iEM3200 / iEM3210 / iEM3215  
Installation sheet: iEM3250 / iEM3255  
Installation sheet: iEM3135  
S1B46581 / S1B62907  
S1B46583 / S1B62908  
S1B46598 / S1B62910  
S1B46602 / S1B62911  
HRB68964 / HRB72100  
HRB68991 / HRB72106  
HRB68988 / HRB72103  
HRB68995 / HRB72108  
HRB69003 / HRB72111  
HRB68999 / HRB72109  
HRB91204 / HRB91205  
HRB91202 / HRB91203  
Installation sheet: iEM3165  
Installation sheet: iEM3175  
Installation sheet: iEM3235  
Installation sheet: iEM3265  
Installation sheet: iEM3275  
Installation sheet iEM3310 / iEM3350  
Installation sheet iEM3335 / iEM3355 / iEM3365 / iEM3375  
You can download these technical publications and other technical information from www.schneider-  
electric.com.  
6
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Contents  
DOCA0005EN-04  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
8
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Safety precautions  
Chapter 1  
Safety precautions  
Installation, wiring, testing and service must be performed in accordance with all local and national  
electrical codes.  
Carefully read and follow the safety precautions outlined below.  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices.  
See NFPA 70E in the USA or applicable local standards.  
• This equipment must only be installed and serviced by qualified electrical personnel.  
• Turn off all power supplying this device and the equipment in which it is installed before working  
on the device or equipment.  
• Always use a properly rated voltage sensing device to confirm power is off.  
• Before performing visual inspections, tests, or maintenance on this equipment, disconnect all  
sources of electric power. Assume that all circuits are live until they have been completely  
de-energized, tested and tagged. Pay particular attention to the design of the power system.  
Consider all power supply sources, particularly the potential for backfeed.  
• Replace all devices, doors and covers before turning on power to this equipment.  
• Do not exceed the device’s ratings for maximum limits.  
Failure to follow these instructions will result in death or serious injury.  
WARNING  
UNINTENDED OPERATION  
Do not use the meter for critical control or protection applications where human or equipment safety  
relies on the operation of the control circuit.  
Failure to follow these instructions can result in death, serious injury or equipment damage.  
WARNING  
INACCURATE DATA RESULTS  
• Do not rely solely on data displayed on the front panel or in software to determine if the device is  
functioning correctly or compliant with all applicable standards.  
• Do not use data displayed on the front panel or in software as a substitute for proper workplace  
practices or equipment maintenance.  
Failure to follow these instructions can result in death, serious injury or equipment damage.  
DOCA0005EN-04  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Safety precautions  
iEM3100 / iEM3200 / iEM3300 series user manual  
10  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Overview  
Chapter 2  
Overview  
What is in this chapter?  
This chapter contains the following topics:  
Overview of meter functions  
The meters provide the essential measurement capabilities (for example, current, voltage, and  
energy) required to monitor a 1- or 3-phase electrical installation.  
The key features of the meters are:  
measurement of active and reactive energy,  
Multi Tariffs (up to 4) controlled by internal clock, digital inputs or communication,  
MID compliance for many of the meters,  
pulse outputs,  
display (current, voltage, and energy measurements),  
communications via Modbus, LonWorks, M-Bus or BACnet protocols.  
Main characteristics  
63 A meters  
Function  
Direct measurement (up to 63 A)  
Active Energy measurement accuracy class (total and  
partial kWh)  
1
1
1
1
1
1
1
1
3
3
4
4
3
4
2
4
3
3
4
2
4
3
4
2
4
3
4
2
4
3
Four Quadrant Energy measurements  
Electrical measurements (I, V, P, ...)  
Controlled by internal clock  
Multi Tariff  
Controlled by digital input(s)  
Controlled by communications  
Measurement display (number of lines)  
Programmable (status, tariff  
2
1
1
1
1
1
1
1
control, or input monitoring)  
Digital inputs  
Tariff control only  
Programmable (energy pulsing  
or overload alarm)  
Digital outputs  
Overload alarm  
5
1
5
5
5
5
5
5
5
Pulse output only  
Modbus  
LonWorks  
M-Bus  
Communications  
MID compliant  
BACnet  
Width (18 mm module in DIN rail mounting)  
DOCA0005EN-04  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Overview  
iEM3100 / iEM3200 / iEM3300 series user manual  
125 A meters  
Function  
Direct measurement (up to 125 A)  
Active Energy measurement accuracy class (total and partial  
kWh)  
1
1
1
1
1
1
1
3
3
4
2
4
3
3
4
2
4
3
4
2
4
3
4
2
4
3
Four Quadrant Energy measurements  
Electrical measurements (I, V, P, ...)  
Controlled by internal clock  
Multi Tariff  
Controlled by digital input(s)  
Controlled by communications  
Measurement display (number of lines)  
Digital inputs (programmable for status, tariff control, or input  
monitoring)  
1
1
1
1
1
1
1
Programmable (energy pulsing or  
overload alarm)  
Digital outputs  
7
1
7
7
7
7
7
7
Pulse output only  
Overload alarm  
Modbus  
LonWorks  
Communications  
M-Bus  
BACnet  
MID compliant  
Width (18 mm module in DIN rail mounting)  
1 A / 5 A meters  
Function  
Measurement inputs through CTs (1 A, 5 A)  
Measurement inputs through VTs  
Active Energy measurement accuracy class (total and  
partial kWh)  
0.5S 0.5S 0.5S 0.5S 0.5S 0.5S 0.5S 0.5S  
3
3
4
4
3
4
2
4
3
3
4
2
4
3
4
2
4
3
4
2
4
3
Four Quadrant Energy measurements  
Electrical measurements (I, V, P, ...)  
Controlled by internal clock  
Multi Tariff  
Controlled by digital input(s)  
Controlled by communications  
Measurement display (number of lines)  
Programmable (status, tariff  
1
2
1
1
1
1
1
1
1
control, or input monitoring)  
Digital inputs  
Tariff control only  
Programmable (energy pulsing  
or overload alarm)  
Digital outputs  
Pulse output only  
12  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Overview  
Function  
5
5
5
5
5
5
5
5
Overload alarm  
Communications  
MID compliant  
Modbus  
LonWorks  
M-Bus  
BACnet  
Width (18 mm module in DIN rail mounting)  
Typical applications  
This range is a cost effective solution to monitor feeder circuits. These meters can monitor energy  
consumption by usage, by zone or by feeder in the cabinet. They can be used to monitor feeders in a  
main switchboard or to monitor the main in a distribution cabinet.  
iEM31•• and iEM33•• series  
Functions  
Advantages  
Can directly measure feeders up to:  
iEM31••: 63 A  
Saves installation time and space in the cabinet  
No wiring to manage  
iEM33••: 125 A  
Clear distribution network  
Embedded current transformers (CTs)  
Adapted to be installed with Acti9 iC65 (iEM31••) or Acti9 C120  
(iEM33••) circuit breakers  
Can be used in three-phase systems with or without neutral  
3 single feeders can be monitored with a single meter  
Can be used for single-phase multi-circuit monitoring  
iEM32•• series  
Functions  
Advantages  
CT and VT connection  
Flexible configuration  
Can be used in low or medium voltage applications  
Can be adapted to any distribution network with or without neutral  
Typical applications  
The following table presents some of the functions of the different meters, the advantages and main  
applications.  
Functions  
Advantages  
Applications  
Meter  
Sub-billing management  
Metering applications  
Provides the timestamp of the last reset of the All (except iEM3100 /  
Total and partial energy counters Energy usage monitoring  
All  
Internal clock  
Saves the date and time of last reset  
partial energy accumulation  
iEM3200 / iEM3300)  
Remote monitoring of energy consumption  
Pulse output with a configurable  
pulse weight of up to 1 pulse per  
1 Wh  
Collect pulses from the meter with a Smartlink  
system, PLC or any basic acquisition system  
iEM3110 / iEM3310 /  
iEM3210  
Integrate the meter in to a system monitoring of  
a large number of devices  
iEM3115 / iEM3135 /  
iEM3155 / iEM3165 /  
iEM3175  
Energy demand management  
Sub-billing management  
Manages up to four tariffs,  
controlled by the digital input(s), Peak, working days and weekends, or by different  
internal clock or communications electricity sources (for example, from the utility and  
Categorize energy consumption into On Peak and Off  
iEM3215 / iEM3235 /  
iEM3255 / iEM3265 /  
iEM3275  
Identification of local energy consumption  
behavior by zone, by usage or by feeder  
(depending on meter model)  
an electrical generator)  
iEM3335 / iEM3355 /  
iEM3365 / iEM3375  
iEM3135 / iEM3155 /  
iEM3165 / iEM3175  
Instantaneous measurements help you monitor the  
imbalance between phases.  
Measures essential electrical  
parameters like current, average  
voltage and total power.  
iEM3235 / iEM3255 /  
iEM3265 / iEM3275  
Monitoring of feeders or any sub-cabinet  
Total power allows you to monitor the feeder load  
level.  
iEM3335 / iEM3355 /  
iEM3365 / iEM3375  
DOCA0005EN-04  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Overview  
iEM3100 / iEM3200 / iEM3300 series user manual  
Functions  
Advantages  
Applications  
Meter  
Communicate advanced parameters using  
M-Bus protocol  
iEM3135 / iEM3235 /  
iEM3335  
M-Bus communications  
M-Bus network integration  
iEM3150 / iEM3155  
iEM3250 / iEM3255  
iEM3350 / iEM3355  
Communicate advanced parameters using Modbus  
protocol  
Modbus communications  
Modbus network integration  
Communicate advanced parameters using BACnet  
MS/TP protocol  
iEM3165 / iEM3265 /  
iEM3365  
BACnet communications  
LonWorks communications  
BACnet network integration  
LonWorks network integration  
Communicate advanced parameters using LonWorks  
communications  
iEM3175 / iEM3275 /  
iEM3375  
Identification of imported and exported active and  
reactive energy allows you to monitor energy flow in  
both directions: delivered from the utility and  
produced on-site  
Ideal for facilities with back-up generators or  
green power capabilities (for example, solar  
panels or wind turbines)  
Four quadrant calculation  
iEM3135 / iEM3155 /  
iEM3165/ iEM3175  
Manage energy consumption and make  
informed investment to reduce your energy bill  
or penalties (for example, installing capacitor  
banks)  
Measurement of active, reactive Allows you to monitor energy consumption and  
and apparent energy.  
production  
iEM3235 / iEM3255 /  
iEM3265 / iEM3275  
Can be programmed to:  
This allows for monitoring of:  
WAGES  
iEM3335 / iEM3355 /  
iEM3365 / iEM3375  
Count pulses from other meters (gas, water, etc.)  
Monitor an external status  
Programmable digital input  
Intrusion (for example, doors opening) or  
equipment status  
Reset the partial energy accumulation and start a  
new period of accumulation  
Energy usage  
This allows you to:  
iEM3135 / iEM3155 /  
iEM3165  
Can be programmed to:  
Collect pulses from the meter with a Smartlink  
system, PLC or any basic acquisition system  
be an active energy (kWh) pulse output, with a  
configurable pulse weight  
iEM3235 / iEM3255 /  
iEM3265  
Programmable digital output  
Monitor power levels at a detailed level and to  
help detect an overload before the circuit  
breaker trips  
Alarm on a power overload at a configurable pickup  
setpoint  
iEM3335 / iEM3355 /  
iEM3365  
14  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Hardware and installation  
Chapter 3  
Hardware and installation  
What is in this chapter?  
This chapter contains the following topics:  
Dimensions  
iEM31•• and iEM32•• meters  
A
B
Without communications  
With communications  
mm  
in  
87  
3.43  
ON  
500  
/kWh  
45  
1.77  
95.0  
3.74  
101.5  
4.00  
OK  
ESC  
Reset  
Config  
63.5  
2.50  
90  
3.54  
69  
2.71  
iEM33•• meters  
A
B
Without communications  
With communications  
mm  
in  
93.8  
3.70  
ON  
200  
/kWh  
45  
1.77  
103.2  
4.06  
108.4  
4.27  
OK  
ESC  
Reset  
Config  
63.8  
2.51  
126.0  
4.96  
69.3  
2.73  
DOCA0005EN-04  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Hardware and installation  
iEM3100 / iEM3200 / iEM3300 series user manual  
Hardware overview  
All meters: Meter sealing points  
All meters have sealing covers and sealing points to help prevent access to inputs and outputs and  
current and voltage connections.  
A
B
Sealing points  
Sealable covers  
ESC  
OK  
iEM3100 / iEM3110 / iEM3115 - Direct measurement up to 63 A  
The various features of the iEM3100 / iEM3110 / iEM3115 are shown in the diagram below:  
A
B
C
D
E
F
G
H
I
Digital inputs for tariff control (iEM3115)  
Display for measurement and configuration  
Pulse output for remote transfer (iEM3110)  
Cancel  
Confirm  
Scroll  
C/- T1 T2  
S0+ S0-  
Current and voltage inputs (direct measurement up to 63 A)  
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
ON  
500  
/kWh  
OK  
ESC  
Reset  
Config  
N
N’  
L1  
L1’  
L2  
L2’  
L3  
L3’  
16  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
iEM3100 / iEM3200 / iEM3300 series user manual  
Hardware and installation  
iEM3135 - Direct measurement up to 63 A and M-Bus communications  
The various features of the iEM3135 are shown in the diagram below:  
A
B
C
D
E
F
G
H
I
Digital input  
Digital output  
Communication port  
Communications LED  
Display for measurement and configuration  
M-Bus  
C/- DI  
C
DO  
Cancel  
Confirm  
Scroll  
ON  
500  
/kWh  
Current and voltage inputs (direct measurement up to 63 A)  
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
J
K
OK  
ESC  
Reset  
Config  
N
N’  
L1  
L1’  
L2  
L2’  
L3  
L3’  
iEM3150 / iEM3155 / iEM3165 - Direct measurement up to 63 A and Modbus or  
BACnet communications  
The various features of the iEM3150 / iEM3155 / iEM3165 are shown in the diagram below:  
A
B
C
D
E
F
G
H
I
Digital input (iEM3155/iEM3165)  
Digital output (iEM3155/iEM3165)  
Communication port  
Communications LED  
Display for measurement and configuration  
Cancel  
0V  
D0/- D1/+  
RS485  
C/- DI N.C.  
C
DO N.C.  
Confirm  
Scroll  
ON  
500  
/kWh  
Current and voltage inputs (direct measurement up to 63 A)  
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
J
K
OK  
ESC  
Reset  
Config  
N
N’  
L1  
L1’  
L2  
L2’  
L3  
L3’  
DOCA0005EN-04  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware and installation  
iEM3100 / iEM3200 / iEM3300 series user manual  
iEM3175 - Direct measurement up to 63 A and LonWorks communications  
The various features of the iEM3175 are shown in the diagram below:  
A
B
C
D
E
F
G
H
I
Digital input  
Communication port  
Communications / LonWorks operations LED  
Service pin  
Display for measurement and configuration  
LON  
Cancel  
C/- DI  
Service  
Confirm  
Scroll  
ON  
Current and voltage inputs (direct measurement up to 63 A)  
Neuron ID  
500  
/kWh  
J
K
L
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
OK  
ESC  
Reset  
Neuron ID: 000000000000  
S/N:0000000000  
Config  
N
N’  
L1  
L1’  
L2  
L2’  
L3  
L3’  
iEM3200 / iEM3210 / iEM3215 - Measurement with CTs  
The various features of the listed meters (CTs 1 A or 5 A) are shown in the diagram below:  
A
B
C
D
E
F
G
H
I
Digital inputs for tariff control (iEM3215)  
Display for measurement and configuration  
Pulse out for remote transfer (iEM3210)  
Current inputs (CTs 1 A or 5 A)  
Cancel  
C/- T1 T2  
S0+ S0-  
Confirm  
Scroll  
ON  
Voltage inputs  
5000  
/kWh  
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
J
OK  
ESC  
Reset  
Config  
(I1)  
(I2)  
S1  
(I3)  
V1  
V2  
V3 Vn  
S1  
S2  
S2  
S1  
S2  
18  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Hardware and installation  
iEM3235 - Measurement with CTs and M-Bus communications  
The various features of the iEM3235 (CTs 1 A or 5 A with M-Bus communications) are shown in the  
diagram below:  
A
B
C
D
E
F
G
H
I
Digital input  
Digital output  
Communication port  
Communications LED  
Display for measurement and configuration  
Current inputs (CTs 1 A and 5 A)  
Cancel  
M-Bus  
C/- DI  
C
DO  
Confirm  
ON  
5000  
/kWh  
Scroll  
J
Voltage inputs  
K
L
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
OK  
ESC  
Reset  
Config  
(I1)  
(I2)  
S1  
(I3)  
V1  
V2  
V3 Vn  
S1  
S2  
S2  
S1  
S2  
iEM3250 / iEM3255 / iEM3265 - Measurement with CTs and Modbus or BACnet  
communications  
The various features of the iEM3250 / iEM3255 / iEM3265 (CTs 1 A or 5 A with Modbus or BACnet  
communication) are shown in the diagram below:  
A
B
C
D
E
F
G
H
I
Digital input (iEM3255/iEM3265)  
Digital output (iEM3255/iEM3265)  
Communication port  
Communications LED  
Display for measurement and configuration  
Current inputs (CTs 1 A and 5 A)  
Cancel  
0V  
D0/- D1/+  
RS485  
C/- DI N.C.  
C
DO N.C.  
Confirm  
ON  
/kWh  
Scroll  
5000  
J
Voltage inputs  
K
L
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
OK  
ESC  
Reset  
Config  
(I1)  
(I2)  
S1  
(I3)  
V1  
V2  
V3 Vn  
S1  
S2  
S2  
S1  
S2  
DOCA0005EN-04  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware and installation  
iEM3100 / iEM3200 / iEM3300 series user manual  
iEM3275 - Measurement with CTs and LonWorks communications  
The various features of the iEM3275 (CTs 1 A or 5 A with LonWorks communications) are shown in  
the diagram below:  
A
B
C
D
E
F
G
H
I
Digital input  
Communication port  
Communications / LonWorks operation LED  
Service pin  
Display for measurement and configuration  
LON  
Current inputs (CTs 1 A and 5 A)  
C/- DI  
Cancel  
Confirm  
ON  
Scroll  
5000  
/kWh  
J
Voltage inputs  
K
L
Neuron ID  
OK  
ESC  
Reset  
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
Neuron ID: 000000000000  
S/N: 0000000000  
Config  
M
(I1)  
(I2)  
S1  
(I3)  
V1  
V2  
V3 Vn  
S1  
S2  
S2  
S1  
S2  
iEM3300 / iEM3310 - Direct measurement up to 125 A  
The various features of the iEM3300 / iEM3310 are shown in the diagram below:  
A
B
C
D
E
F
Display for measurement and configuration  
Pulse output for remote transfer (iEM3310)  
Cancel  
Confirm  
S0+ S0-  
Scroll  
Current and voltage inputs (direct measurement up to 125 A)  
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
ON  
200  
/kWh  
G
H
OK  
ESC  
Reset  
Config  
N
N’  
L1  
L1’  
L2  
L2’  
L3  
L3’  
20  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Hardware and installation  
iEM3335 - Direct measurement up to 125 A and M-Bus communications  
The various features of the iEM3335 are shown in the diagram below:  
A
B
C
D
E
F
G
H
I
Digital input  
Digital output  
Communication port  
Communications LED  
Display for measurement and configuration  
Cancel  
C/- DI  
C
DO  
Confirm  
Scroll  
ON  
200  
/kWh  
Current and voltage inputs (direct measurement up to 125 A)  
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
J
OK  
ESC  
Reset  
Config  
K
N
N’  
L1  
L1’  
L2  
L2’  
L3  
L3’  
iEM3350 / iEM3355 / iEM3365 - Direct measurement up to 125 A and Modbus  
or BACnet communications  
The various features of the iEM3350 / iEM3355 / iEM3365 are shown in the diagram below:  
A
B
C
D
E
F
G
H
I
Digital input (iEM3355 / iEM3365)  
Digital output (iEM3355 / iEM3365)  
Communication port  
Communications LED  
0V  
D0/- D1/+  
RS485  
Display for measurement and configuration  
Cancel  
C/- DI  
C
DO  
Confirm  
ON  
200  
/kWh  
Scroll  
Current and voltage inputs (direct measurement up to 125 A)  
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
OK  
ESC  
Reset  
Config  
J
N
N’  
L1  
L1’  
L2  
L2’  
L3  
L3’  
K
DOCA0005EN-04  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware and installation  
iEM3100 / iEM3200 / iEM3300 series user manual  
iEM3375 - Direct measurement up to 125 A and LonWorks communications  
The various features of the iEM3375 are shown in the diagram below:  
A
B
C
D
E
F
G
H
I
Digital input  
Communication port  
Communications / LonWorks operations LED  
Service pin  
Display for measurement and configuration  
C/- DI  
Service  
Cancel  
Confirm  
ON  
200  
/kWh  
Scroll  
Current and voltage inputs (direct measurement up to 125 A)  
Neuron ID  
OK  
ESC  
Reset  
Neuron ID: 000000000000  
S/N:0000000000  
Config  
J
K
L
Energy pulsing LED (used to verify accuracy)  
Status LED: on/off, error  
N
N’  
L1  
L1’  
L2  
L2’  
L3  
L3’  
DIN rail mounting and dismounting  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices.  
See NFPA 70E in the USA or applicable local standards.  
• This equipment must only be installed and serviced by qualified electrical personnel.  
• Turn off all power supplying this device and the equipment in which it is installed before working  
on the device or equipment.  
• Always use a properly rated voltage sensing device to confirm power is off.  
• Replace all devices, doors and covers before turning on power to this equipment.  
• Do not exceed the device’s ratings for maximum limits.  
Failure to follow these instructions will result in death or serious injury.  
Mounting the meter on a DIN rail  
1. Position the 2 upper slots on the rear of the meter onto the DIN rail.  
2. Press the meter against the DIN rail until the locking mechanism engages. The meter is now  
attached to the rail. Make sure that the device is not tilted following installation.  
22  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Hardware and installation  
Click!  
Dismounting the meter from a DIN rail  
1. Use a flat-tip screwdriver (6.5 mm / 0.25 in) to lower the locking mechanism and release the  
meter.  
2. Lift the meter out and up to free it from the DIN rail.  
DOCA0005EN-04  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware and installation  
iEM3100 / iEM3200 / iEM3300 series user manual  
Input, output and communications wiring  
This section describes the wiring of the digital inputs, digital and pulse outputs and the  
communications (as applicable).  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices.  
See NFPA 70E in the USA or applicable local standards.  
• This equipment must only be installed and serviced by qualified electrical personnel.  
• Turn off all power supplying this device and the equipment in which it is installed before working  
on the device or equipment.  
• Always use a properly rated voltage sensing device to confirm power is off.  
• Replace all devices, doors and covers before turning on power to this equipment.  
• Do not exceed the device’s ratings for maximum limits.  
Failure to follow these instructions will result in death or serious injury.  
WARNING  
UNINTENDED OPERATION  
Do not use the meter for critical control or protection applications where human or equipment safety  
relies on the operation of the control circuit.  
Failure to follow these instructions can result in death, serious injury or equipment damage.  
Related topics  
connections.  
Pulse output wiring: iEM3110 / iEM3210 / iEM3310  
Rin  
Radd  
5 – 30 V DC  
+
-
S0+ S0-  
The pulse output is compatible with S0 format.  
The pulse output can be directly connected to a 24 V DC (< 30 V DC) input on a Zelio or  
Twido PLC.  
The pulse output indicates the primary consumption with consideration of transformer ratios.  
For other concentrators, if V DC/Rin > 15 mA, add a resistor Radd = (V DC/0.01) - Rin Ω  
Digital input wiring: iEM3115 / iEM3215  
11 – 40 V DC  
- +  
C/- T1 T2  
24  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
iEM3100 / iEM3200 / iEM3300 series user manual  
Hardware and installation  
Digital input wiring: iEM3135 / iEM3155 / iEM3165 / iEM3175 / iEM3235 /  
iEM3255 / iEM3265 / iEM3275 / iEM3335 / iEM3355 / iEM3365 / iEM3375  
11 – 40 V DC  
-
+
C/- DI N.C.  
The digital input and output are electrically independent.  
Digital output wiring: iEM3135 / iEM3155 / iEM3165 / iEM3235 / iEM3255 /  
iEM3265 / iEM3335 / iEM3355 / iEM3365  
5 – 40 V DC  
-
-
/+ +/  
Load  
C
DO N.C.  
The programmable digital output is compatible with S0 format when configured as a pulse output.  
The digital output is polarity-independent.  
The digital input and output are electrically independent.  
Modbus RS-485 communications wiring: iEM3150 / iEM3155 / iEM3250 /  
iEM3255 / iEM3350 / iEM3355  
0 V  
D0 = A’ / Rx-, A / Tx-  
D1 = B’ / Rx+, B / Tx+  
0V  
D0/- D1/+  
BACnet RS-485 communications wiring: iEM3165 / iEM3265 / iEM3365  
0 V  
D0 = A’ / Rx-, A / Tx-  
D1 = B’ / Rx+, B / Tx+  
0V  
D0/- D1/+  
M-Bus communications wiring: iEM3135 / iEM3235 / iEM3335  
The M-Bus communications connection is polarity-independent.  
DOCA0005EN-04  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware and installation  
iEM3100 / iEM3200 / iEM3300 series user manual  
LonWorks communications wiring: iEM3175 / iEM3275 / iEM3375  
Service  
The LON communications connection is polarity-independent.  
Power system wiring  
The diagrams below illustrate how to connect the meters to a single-phase or three-phase 3-wire or  
4-wire power system.  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices.  
See NFPA 70E in the USA or applicable local standards.  
• This equipment must only be installed and serviced by qualified electrical personnel.  
• Turn off all power supplying this device and the equipment in which it is installed before working  
on the device or equipment.  
• Always use a properly rated voltage sensing device to confirm power is off.  
• Replace all devices, doors and covers before turning on power to this equipment.  
• Do not exceed the device’s ratings for maximum limits.  
Failure to follow these instructions will result in death or serious injury.  
Voltage input protection  
The meter’s voltage inputs must be wired to fuses/breakers and a disconnect switch. If using a voltage  
transformer (VT), both primary and secondary sides of the VT must be fused and switched.  
Clearly label the device’s disconnect circuit mechanism and install it within easy reach of the  
operator.  
Fuses / circuit breakers must be:  
— installed in accordance with all local and national electrical codes and standards, and  
— rated for the installation voltage, available fault current, and sized for connected loads.  
Fuse for neutral is required if the source neutral connection is not grounded.  
Current input protection for 1 A and 5 A meters  
For all connected current inputs on 1 A and 5 A meters with external CTs, use a CT shorting block to  
short-circuit the secondary leads of the CTs before removing the current input connections to the  
meter.  
NOTE: Ground any unused current inputs on 1 A and 5 A meters.  
iEM31•• and iEM33•• devices associated with a contactor  
Connection requirements for iEM3100 / iEM3110 / iEM3115 / iEM3135 / iEM3150 / iEM3155 /  
iEM3165 / iEM3175 / iEM3300 / iEM3310 / iEM3335 / iEM3350 / iEM3355 / iEM3365 / iEM3375:  
When the meter is associated with a contactor, connect the meter upstream of the contactor.  
The meter must be protected by a circuit breaker.  
26  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Hardware and installation  
L
L
iEM  
iEM  
Load  
Load  
Related topics  
inputs, digital or pulse outputs and communications for your device.  
63 A direct measurement meter wiring  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Do not allow the total additive current flowing through the device to exceed 63 A.  
Failure to follow these instructions will result in death or serious injury.  
Fuses and disconnect switch  
Power system  
Wiring  
N
N’ L1 L1’ L2 L2’ L3 L3’  
N
N’ L1 L1’ L2 L2’ L3 L3’  
1PH2W L-N  
L
N
L
N
277 V L-N  
277 V L-N  
N
N’ L1 L1’ L2 L2’ L3 L3’  
1PH2W L-L  
L1  
L2  
480 V L-L  
N
N’ L1 L1’ L2 L2’ L3 L3’  
N
N’ L1 L1’ L2 L2’ L3 L3’  
L1  
L2  
N
L1  
L2  
N
1PH3W L-L-N  
277 V L-N  
277 V L-N  
480 V L-L  
480 V L-L  
N
N’ L1 L1’ L2 L2’ L3 L3’  
L1  
L2  
L3  
3PH3W  
480 V L-L  
N
N’ L1 L1’ L2 L2’ L3 L3’  
N
N’ L1 L1’ L2 L2’ L3 L3’  
L1  
L1  
L2  
L3  
N
L2  
L3  
N
3PH4W  
277 V L-N  
277 V L-N  
480 V L-L  
480 V L-L  
DOCA0005EN-04  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware and installation  
iEM3100 / iEM3200 / iEM3300 series user manual  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Do not connect N’ to the load when setting the wiring type on the meter to 1PH4W Multi L-N.  
Failure to follow these instructions will result in death or serious injury.  
Power system  
Wiring  
N
N’ L1 L1’ L2 L2’ L3 L3’  
1
1PH multiple loads with neutral (1PH4W Multi L-N)  
1
The 1PH4W Multi L-N wiring type is only available on the iEM3135, iEM3150, iEM3155, iEM3165 and iEM3175.  
125 A direct measurement meter wiring  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Do not allow the total additive current flowing through the device to exceed 125 A.  
Failure to follow these instructions will result in death or serious injury.  
Fuses and disconnect switch  
Power system  
Wiring  
N
N’ L1 L1’ L2 L2’ L3 L3’  
N
N’ L1 L1’ L2 L2’ L3 L3’  
1PH2W L-N  
L
N
L
N
277 V L-N  
277 V L-N  
N
N’ L1 L1’ L2 L2’ L3 L3’  
1PH2W L-L  
L1  
L2  
480 V L-L  
N
N’ L1 L1’ L2 L2’ L3 L3’  
N
N’ L1 L1’ L2 L2’ L3 L3’  
L1  
L2  
N
L1  
L2  
N
1PH3W L-L-N  
277 V L-N  
277 V L-N  
480 V L-L  
480 V L-L  
N
N’ L1 L1’ L2 L2’ L3 L3’  
L1  
L2  
L3  
3PH3W  
480 V L-L  
28  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Hardware and installation  
Power system  
Wiring  
N
N’ L1 L1’ L2 L2’ L3 L3’  
N
N’ L1 L1’ L2 L2’ L3 L3’  
L1  
L2  
L3  
N
L1  
L2  
L3  
N
3PH4W  
277 V L-N  
277 V L-N  
480 V L-L  
480 V L-L  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Do not connect N’ to the load when setting the wiring type on the meter to 1PH4W Multi L-N.  
Failure to follow these instructions will result in death or serious injury.  
Power system  
Wiring  
N
N’ L1 L1’ L2 L2’ L3 L3’  
1
1PH multiple loads with neutral (1PH4W Multi L-N)  
1
The 1PH4W Multi L-N wiring type is only available on the iEM3335, iEM3350, iEM3355, iEM3365 and iEM3375.  
5 A / 1 A meter wiring  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Never short the secondary of a voltage transformer (VT).  
• Never open circuit a current transformer (CT); use the shorting block to short circuit the leads of  
the CT before removing the connection from the meter.  
• Always use grounded external CTs for current inputs.  
Failure to follow these instructions will result in death or serious injury.  
Single-phase systems with CTs  
250 mA fuses and disconnect switch  
Shorting block  
Power system  
Wiring  
(I1) (I2) (I3)  
V1V2V3Vn  
1PH2W L-N  
S1  
S2  
277 V L-N  
DOCA0005EN-04  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware and installation  
iEM3100 / iEM3200 / iEM3300 series user manual  
Power system  
Wiring  
(I1) (I2) (I3)  
V1V2V3Vn  
1PH2W L-L  
S1  
S2  
L1  
L2  
480 V L-L  
(I1) (I2) (I3)  
V1V2V3Vn  
1PH3W L-L-N  
S1  
S2  
S1  
L1  
L2  
N
S2  
277 V L-N  
480 V L-L  
2CTs  
3CTs  
(I1) (I2) (I3)  
(I1) (I2) (I3)  
V1V2V3Vn  
V1V2V3Vn  
1PH multiple loads with neutral  
1
(1PH4W Multi L-N)  
277 V L-N  
277 V L-N  
1
The 1PH4W Multi L-N wiring type is only available on the iEM3235, iEM3250, iEM3255, iEM3265 and iEM3275  
Three-phase systems with CTs  
250 mA fuses and disconnect switch  
Shorting block  
indicates wiring for a balanced system  
Power system  
Wiring  
1 CT  
2CTs  
3CTs  
V1V2V3Vn  
V1V2V3Vn  
V1V2V3Vn  
3PH3W  
480 V L-L  
480 V L-L  
480 V L-L  
1 CT  
2 CTs  
3CTs  
V1V2V3Vn  
V1V2V3Vn  
V1V2V3Vn  
3PH4W  
277 V L-N  
277 V L-N  
277 V L-N  
30  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Hardware and installation  
Three-phase systems with CTs and VTs  
250 mA fuses and disconnect switch  
Shorting block  
VT primary fuses and disconnect switch  
indicates wiring for a balanced system  
Power system  
Wiring  
2 VTs, 1 CT  
2 VTs, 2 CTs  
2 VTs, 3 CTs  
V1V2V3Vn  
V1V2V3Vn  
V1V2V3Vn  
3PH3W  
3 VTs, 1 CTs  
3 VTs, 2 CTs  
3 VTs, 3 CTs  
V1V2V3Vn  
V1V2V3Vn  
V1V2V3Vn  
3PH4W  
DOCA0005EN-04  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware and installation  
iEM3100 / iEM3200 / iEM3300 series user manual  
32  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Front panel display and meter setup  
Chapter 4  
Front panel display and meter setup  
What is in this chapter?  
This chapter contains the following topics:  
Overview  
The meter features a front panel with signaling LEDs, a graphical display, and menu buttons that allow  
you to access the information required to operate the meter and modify parameter settings.  
The front panel also allows you to display, configure and reset parameters.  
Some meters have the Multi Tariff feature, which allows you to configure different tariffs.  
Data display  
Data display screen overview  
A
B
C
D
E
F
Measurement  
Ea / Er = active / reactive energy (if available)  
Value  
Active tariff (if applicable)  
Scroll through the available screens  
Total Ea Import  
View more screens related to the measurement category  
(if available)  
1234.5  
G
H
I
Go back to previous screen  
Date and time (if applicable)  
Unit  
T1 23 Apr 2011 12:00 kWh  
DOCA0005EN-04  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Front panel display and meter setup  
iEM3100 / iEM3200 / iEM3300 series user manual  
Example: navigating the display screens  
Partial Reactive E  
Tariffs  
OK  
T1  
T2  
T3  
T4  
V & I  
1. Press  
to scroll through the main display screens; in the image above, press  
to move from  
Partial Reactive E to Tariffs to V & I.  
OK  
OK  
2. Press  
press  
to access additional screens related to main screen (if available); in the image above,  
to access screens for each of the available tariffs.  
3. Press  
to scroll through these additional screens.  
Related topics  
model.  
Data display screens  
The following sections outline the data display screens available on the various meter models.  
Data display screens: iEM3100 / iEM3110 / iEM3115 / iEM3200 / iEM3210 / iEM3215 /  
iEM3300 / iEM3310  
A
B
C
Resets all energy measurements except total active energy  
iEM3115 / iEM3215  
Total Active E  
Partial Active E  
Diagnosis screen appears if there is a specific event  
Reset  
T1  
T2  
T3  
T4  
Tariffs  
Diagnosis  
Related topics  
diagnostic codes.  
34  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Front panel display and meter setup  
Data display screens: iEM3150 / iEM3250 / iEM3350  
A
B
Resets all energy measurements except total active energy  
Diagnosis screen appears if there is a specific event  
Total Active E  
Reset  
Partial Active E  
V & I  
Avg. L-L (L-N) Voltage  
Phase 1 Current  
Phase 2 Current  
Phase 3 Current  
Active Power  
Power Factor  
Diagnosis  
Related topics  
diagnostic codes.  
Data display screens: iEM3135 / iEM3155 / iEM3165 / iEM3175 / iEM3235 / iEM3255 /  
iEM3265 / iEM3275 / iEM3335 / iEM3355 / iEM3365 / iEM3375  
A
B
C
Import / export indicated for total active (Ea) and total reactive (Er)  
energy. Other energy measurements are import only.  
Total Ea Export  
Total Er Export  
Reset  
Total Ea Import  
Total Er Import  
Partial Active E  
Resets all energy measurements except total active energy and total  
reactive energy  
Diagnosis screen appears if there is a specific event  
Reset  
Partial Reactive E  
Tariffs  
T1  
T2  
T3  
T4  
Avg. L-L (L-N) Voltage  
Phase 1 Current  
Phase 2 Current  
Phase 3 Current  
V & I  
Active Power  
Reactive Power  
Apparent Power  
P, Q & S  
PF & F  
Power Factor  
Frequency  
Operation Time  
Diagnosis  
DOCA0005EN-04  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front panel display and meter setup  
iEM3100 / iEM3200 / iEM3300 series user manual  
Related topics  
diagnostic codes.  
Resets  
The following resets are available, depending on your meter model:  
Reset  
Description  
Clears all active and reactive energy accumulated since the last reset.  
NOTE: this does not reset the total active and reactive energy accumulation.  
Clears all input metering energy data.  
Partial energy  
Input metering  
NOTE: you can only reset the input metering accumulation using software.  
Resetting accumulated energy using the display  
1. Navigate to the Partial Active E or Partial Reactive E screen. The screen displays the date of the  
last reset. For example:  
A
Date of last reset  
Partial Active E  
876.2  
23-Apr-2012  
kWh  
2. Press and hold  
. The Reset screen appears.  
OK  
3. Press  
to confirm the reset and enter the meter password when prompted.  
NOTE: Regardless of the screen you use to access this reset, accumulations of both Partial Active  
Energy and the Partial Reactive Energy (if available) are cleared.  
Related topics  
See your software documentation for information on resetting the input metering accumulation.  
Multi Tariff feature  
The Multi Tariff feature is available on the following devices: iEM3115, iEM3135, iEM3155, iEM3165,  
iEM3175, iEM3215, iEM3235, iEM3255, iEM3265, iEM3275, iEM3335, iEM3355, iEM3365 and  
iEM3375.  
The following table illustrates how the tariffs operate according to the tariff selection (2, 3 or 4 tariffs).  
These tariffs are stored in 4 different registers: T1, T2, T3 and T4.  
2 tariffs  
3 tariffs  
T1  
4 tariffs  
T1  
T1  
T1  
Weekday  
Weekend  
T2  
T2  
T2  
T4  
T2  
24 H  
24 H  
24 H  
24 H  
24 H  
24 H  
T3  
T3  
NOTE: If the tariff Control Mode is set to by Internal Clock, the start time of the next tariff is the end  
time of the current tariff. For example, T2 start equals the end of T1.  
36  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
iEM3100 / iEM3200 / iEM3300 series user manual  
Front panel display and meter setup  
Meter status information  
Two LEDs on the front panel indicate the current status of the device: the green status LED and the  
yellow energy pulsing LED.  
The icons in the table below indicate the LED state as follows:  
= LED is off  
= LED is on  
= LED is flashing  
Status LED  
Energy pulsing LED  
Description  
Off  
On, no pulse counting  
1s >  
On, with pulse counting  
Error, pulse counting stopped  
Abnormal, with pulse counting  
Related topics  
See the section for the protocol of your device for information on the communication LED:  
The device clock  
This section does not apply to the iEM3100, iEM3200 or iEM3300.  
You must reset the time to account for any time change (for example, to switch the time from standard  
time to daylight savings time).  
Clock behavior on power interruption  
iEM3110, iEM3150, iEM3210, iEM3250, iEM3310 and iEM3350: When power is interrupted, the date  
and time are reset. When power is restored, the device automatically displays the screen to set Date  
and Time.  
iEM3115, iEM3135, iEM3155, iEM3165, iEM3175, iEM3215, iEM3235, iEM3255, iEM3265, iEM3275,  
iEM3335, iEM3355, iEM3365 and iEM3375: When the power is interrupted, the device retains its date  
and time information for 3 days. If power is interrupted for longer than 3 days, the device automatically  
displays the screen to set Date and Time when power is restored.  
Date/time format  
The date is displayed in the following format: DD-MMM-YYYY.  
The time is displayed using the 24-hour clock in the following format: hh:mm:ss.  
DOCA0005EN-04  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Front panel display and meter setup  
iEM3100 / iEM3200 / iEM3300 series user manual  
Setting the clock initially  
The following diagram illustrates how to set the clock when you initially power up the device or after a  
power failure. To set the clock during normal operation, see the section on device configuration.  
Date & Time  
Password  
Date  
Time  
Date & Time  
Total Active E  
1234.5  
OK  
0010  
01-Jan-2000  
DD-MM-YYYY  
00:00  
hh:mm  
Set?  
Save Settings?  
OK  
OK  
OK  
OK  
OK  
kWh  
NOTE: Password entry is only required for meters that support a password.  
Related topics  
operation.  
Device configuration  
The default factory settings are listed in the following table:  
Menu  
Factory settings  
iEM31••: 3PH4W  
Wiring  
iEM32••: 3PH4W; 3 CTs on I1, I2, and I3; Direct-No VT  
iEM33••: 3PH4W  
CT Ratio  
CT Secondary = 5 A; CT Primary = 5 A  
CT Secondary = 5 A; CT Primary = 5 A  
CT & VT Ratio  
VT Secondary = 100 V; VT Primary = 100 V  
Frequency  
Date  
50 Hz  
1-Jan-2000  
Time  
00:00:00  
Multi Tariffs  
Overload Alarm  
Digital Output  
Digital Input  
Pulse Output  
Communication  
Com.Protection  
Contrast  
Disable  
Disable  
Disable  
Input Status  
100 imp / kWh  
Varies depending on protocol  
Enable  
5
Password  
0010  
Entering configuration mode  
1. Press and hold OK and ESC at the same time for about 2 seconds.  
2. Enter the meter password, if prompted. The Access Counter screen displays, indicating the  
number of times the configuration mode has been accessed.  
Config  
> 2s  
The front panel display in configuration mode  
The diagram below illustrates the various elements of the display in configuration mode:  
A
B
C
D
Parameter  
..\In. Pulse Const.  
Setting  
Configuration mode icon  
Indicates that the setting impacts the Multi Tariff feature  
00500  
Overriding!  
38  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
iEM3100 / iEM3200 / iEM3300 series user manual  
Front panel display and meter setup  
Related topics  
configure list and numeric value settings.  
Com. Protection setting  
For meters with communications capabilities, you can enable or disable the Com. Protection setting. If  
this setting is enabled, you must use the display to configure certain settings (for example, wiring or  
frequency, etc.) and perform resets; you cannot use communications.  
The protected settings and resets are:  
Power system settings (for example, wiring, frequency, CT ratios)  
Date and time settings  
Multi-tariff settings  
Communications settings  
Partial energy reset  
Modifying parameters  
There are two methods for modifying a parameter, depending on the type of parameter:  
selecting a value in a list (for example, selecting 1PH2W L-N from a list of available power  
systems), or  
modifying a numerical value, digit by digit (for example, entering a value for the date, time or VT  
primary).  
NOTE: Before you modify any parameters, ensure that you are familiar with the HMI functionality and  
navigation structure of your device in configuration mode.  
Related topics  
menus on your device.  
Selecting a value from a list  
1. Use the down button to scroll through the parameter values until you reach the desired value.  
2. Press OK to confirm the new parameter value.  
Example: Configuring a list value  
To set the nominal frequency of the meter:  
1. Enter configuration mode and press the down button until you reach Frequency then press OK to  
access the frequency configuration.  
2. Press the down button to select the frequency you want then click OK. Press OK again to save  
your changes.  
Modifying a numerical value  
When you modify a numerical value, the digit on the far right side is selected by default (except for  
Date/Time).  
DOCA0005EN-04  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Front panel display and meter setup  
iEM3100 / iEM3200 / iEM3300 series user manual  
The parameters listed below are the only ones for which you set a numerical value (if the parameter is  
available on your device):  
Date  
Time  
Pick Up Value for an overload alarm  
Voltage Transformer (VT) Primary  
Current Transformer (CT) Primary  
Password  
Address of the meter  
To modify a numerical value:  
1. Use the down button to modify the selected digit.  
2. Press OK to shift to next digit. Modify the next digit, if needed, or press okay to move to the next  
digit. Continue to move through the digits until you reach the last digit then press OK again to  
confirm the new parameter value.  
If you enter an invalid setting for the parameter, when you press OK after setting the left-most  
number, the cursor shifts back to the right-most number so you can enter a valid value.  
Example: configuring a numeric value  
To set the password:  
1. Enter configuration mode and press the down button until you reach Password then press OK to  
access the password configuration.  
2. Press the down button to increment the selected digit or press OK to move to the next digit to the  
left. When you reach the left-most digit, press OK to move to the next screen. Press OK again to  
save your changes.  
Canceling an entry  
To cancel the current entry, press the ESC button  
. The change is canceled and the screen  
reverts to the previous display.  
Configuration mode menus  
The diagrams below show the configuration navigation for each device.  
Related topics  
40  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
iEM3100 / iEM3200 / iEM3300 series user manual  
Front panel display and meter setup  
Configuration menu for iEM3100 / iEM3110 / iEM3115 / iEM3300 / iEM3310  
A
B
C
iEM3110 / iEM3115 / iEM3310  
iEM3110 / iEM3310  
iEM3115  
Type  
Wiring  
Frequency  
Date  
Frequency  
Date  
Time  
Time  
Pulse Constant  
Pulse Width  
Pulse Output  
Multi Tariffs  
Control mode  
Disable  
Schedule  
by 2 Tariffs  
by Internal Clock  
by Digital Input  
by Communications  
by 3 Tariffs  
by 4 Tariffs  
Contrast  
Contrast  
Password  
Password  
Reset Config  
Reset Config  
Section  
Parameter  
Options  
Description  
3PH3W  
3PH4W  
Wiring  
Type  
1PH2W L-N  
1PH2W L-L  
1PH3W L-L-N  
50  
Select the power system type the meter is wired to.  
Frequency  
Frequency  
Select the frequency of the electrical power system, in Hz.  
60  
Date (iEM3110 / iEM3115 /  
iEM3310)  
Date  
Time  
DD-MMM-YYYY  
hh:mm  
Set the current date using the specified format.  
Use the 24-hour format to set the time.  
Time (iEM3110 / iEM3115 /  
iEM3310)  
100  
200  
1000  
1
Pulse Constant  
(imp/kWh)  
Set the pulses per kWh for the pulse output.  
10  
Pulse Output  
20  
50  
Pulse Width  
(ms)  
100  
200  
300  
Set the pulse width (ON time).  
Select the tariff control mode:  
Disable: the Multi Tariff function is disabled.  
by Digital Input: the digital input is associated with the multi-tariff function. A  
signal to the digital input changes the active tariff.  
by Internal Clock: the device clock controls the active tariff. If you set the  
Control Mode to by Internal Clock, you must also configure the schedule.  
Set the time when each tariff period starts, using the 24 hour clock format  
(00:00 to 23:59). The start time of the next tariff is the end time of the current  
tariff. For example, T2 start equals the end of T1.  
Disable  
Multi Tariffs (iEM3115)  
Control Mode  
by Digital Input  
by Internal Clock  
Contrast  
Contrast  
1-9  
Increase or decrease the value to increase or decrease the display contrast.  
Sets the password for accessing the meter configuration screens and resets.  
Settings are reset to their defaults, except for Password. Meter restarts.  
Password  
(iEM3110 / iEM3115 /  
iEM3310)  
Password  
Reset Config  
0-9999  
Reset Config  
DOCA0005EN-04  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front panel display and meter setup  
iEM3100 / iEM3200 / iEM3300 series user manual  
Configuration menu for iEM3150 / iEM3350  
Type  
Wiring  
Frequency  
Date  
Frequency  
Date  
Time  
Time  
Slave Address  
Baud Rate  
Parity  
Communication  
Contrast  
Contrast  
Reset Config  
Reset Config  
Section  
Parameter  
Options  
Description  
3PH4W  
1PH2W L-N  
1PH2W L-L  
1PH3W L-L-N  
3PH3W  
Wiring  
Type  
Select the power system type the meter is wired to.  
1PH4W Multi L-N  
50  
Frequency  
Frequency  
Select the frequency of the electrical power system, in Hz.  
60  
Date  
Time  
Date  
Time  
DD-MMM-YYYY  
hh:mm  
Set the current date using the specified format.  
Set the time using the 24-hour format.  
Set the address for this device. The address must be unique for each device in  
a communications loop.  
Slave Address  
1 - 247  
19200  
38400  
9600  
Even  
Odd  
Select the speed for data transmission. The baud rate must be the same for all  
devices in a communications loop.  
Baud Rate  
Communication  
Select None if the parity bit is not used. The parity setting must be the same for  
all devices in a communications loop.  
Parity  
NOTE: Number of stop bits = 1.  
None  
1-9  
Contrast  
Contrast  
Increase or decrease the value to increase or decrease the display contrast.  
Settings are reset to their defaults, except for Password. Meter restarts.  
Reset Config  
Reset Config  
42  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Front panel display and meter setup  
Configuration menus for iEM3135 / iEM3155 / iEM3165 / iEM3175 / iEM3335 /  
iEM3355 / iEM3365 / iEM3375  
Not available on iEM3175 /  
iEM3375  
A
Type  
Wiring  
B
C
D
iEM3155 / iEM3355  
iEM3135 / iEM3335  
iEM3165 / iEM3365  
Frequency  
Date  
Frequency  
Date  
Time  
Time  
Control mode  
Disable  
Multi Tariffs  
Schedule  
by 2 Tariffs  
by Internal Clock  
by Digital Input  
by Communications  
by 3 Tariffs  
by 4 Tariffs  
Alarm  
Overload Alarm  
Digital Output  
Disable  
Enable  
Pick Up Value  
DO Function  
Disable  
for Alarm  
for Pulse  
Pulse Constant  
Pulse Width  
DI Function  
Digital Input  
Input Status  
Tariff Control  
Input Metering  
Partial Reset  
In. Pulse Const.  
Slave Address  
Baud Rate  
Parity  
Primary Addr.  
Baud Rate  
MAC Addr.  
Baud Rate  
Device ID  
Communication  
Communication  
Communication  
Com.Protection  
Contrast  
Com.Protection  
Contrast  
Password  
Password  
Reset Config  
Reset Config  
Section  
Parameter  
Options  
Description  
3PH4W  
1PH2W L-N  
1PH2W L-L  
1PH3W L-L-N  
3PH3W  
Wiring  
Type  
Select the power system type the meter is wired to.  
1PH4W Multi L-N  
50  
Frequency  
Frequency  
Select the frequency of the electrical power system, in Hz.  
60  
Date  
Time  
Date  
Time  
DD-MMM-YYYY  
hh:mm  
Set the current date using the specified format.  
Set the time using the 24-hour format.  
DOCA0005EN-04  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front panel display and meter setup  
iEM3100 / iEM3200 / iEM3300 series user manual  
Section  
Parameter  
Options  
Description  
Select the tariff control mode:  
Disable: the Multi Tariff function is disabled.  
by Communication: the active tariff is control by communications. See  
the chapter for the applicable protocol for more information.  
Disable  
by Digital Input: the digital input is associated with the multi-tariff  
function. A signal to the digital input changes the active tariff.  
by Internal Clock: the device clock controls the active tariff. If you set the  
Control Mode to by Internal Clock, you must also configure the  
schedule. Set the time when each tariff period starts, using the 24 hour  
clock format (00:00 to 23:59). The start time of the next tariff is the end  
time of the current tariff. For example, T2 start equals the end of T1.  
by Communication  
by Digital Input  
Multi Tariffs  
Control Mode  
by Internal Clock  
Select whether or not the Overload Alarm is enabled:  
Disable  
Enable  
Disable: the alarm is disabled.  
Enable: the alarm is enabled. If you enabled the Overload Alarm, you  
must also configure the Pick Up Value in kW from 1 - 9999999.  
Overload Alarm  
Alarm  
Select how the digital output functions:  
Disable: the digital output is disabled.  
for Alarm: the digital output is associated with the overload alarm. The  
meter sends a pulse to the digital output port when the alarm is  
triggered.  
Disable  
Digital Output  
DO Function  
for Alarm  
for Pulse: The digital output is associated with energy pulsing. When  
this mode is selected, you must also configure the can select the energy  
parameter and the set the Pulse Constant (imp/kWh) and the Pulse  
Width (ms).  
for Pulse (kWh)  
NOTE: the iEM3175 and iEM3375 do not have a digital output.  
Select how the digital input functions:  
Input status: the digital input records the status of the input, for example,  
OF, SD of a circuit breaker.  
Input Status  
Tariff Control  
Input Metering  
Partial Reset  
Input Metering: the digital input is associated with input metering. The  
meter counts and records the number of incoming pulses. If you set the  
DI Function to Input Metering, you must also configure In. Pulse  
Constant.  
Tariff Control: the digital input is associated with the multi-tariff function.  
A signal to the digital input changes the active tariff.  
Partial Reset: a signal to the digital input initiates a partial reset.  
Digital Input  
DI Function  
Set the address for this device. The address must be unique for each  
device in a communications loop.  
Slave Address  
Baud Rate  
1 - 247  
19200  
38400  
9600  
Even  
Odd  
Select the speed for data transmission. The baud rate must be the same for  
all devices in a communications loop.  
Communication  
(iEM3155 / iEM3355)  
Select None if the parity bit is not used. The parity setting must be the same  
for all devices in a communications loop.  
Parity  
NOTE: Number of stop bits = 1.  
None  
Set the address for this device. The address must be unique for each  
device in a communications loop.  
Primary Addr.  
0 - 255  
2400  
4800  
9600  
300  
Communication  
(iEM3135 / iEM3335)  
Select the speed for data transmission. The baud rate must be the same for  
all devices in a communications loop.  
Baud Rate  
600  
1200  
Set the address for this device. The address must be unique for each  
device in a communications loop.  
MAC Addr.  
Baud Rate  
1 - 127  
9600  
19200  
38400  
57600  
76800  
Communication  
Select the speed for data transmission. The baud rate must be the same for  
all devices in a communications loop.  
(iEM3165 / iEM3365)  
Set the Device ID for this device. Make sure the Device ID is unique in your  
BACnet network.  
Device ID  
0 - 4194303  
Enable  
Disable  
Protects selected settings and resets from configuration via  
communications.  
Com.Protection  
Contrast  
Com.Protection  
Contrast  
Increase or decrease the value to increase or decrease the display  
contrast.  
1-9  
Sets the password for accessing the meter configuration screens and  
resets.  
Password  
Password  
0-9999  
Reset Config  
Reset Config  
Settings are reset to their defaults, except for Password. Meter restarts.  
44  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Front panel display and meter setup  
Configuration menus for iEM3200 / iEM3210 / iEM3215  
A
B
C
iEM3210 / iEM3215  
iEM3210  
Type  
CT  
Wiring  
iEM3215  
CT Secondary  
CT Primary  
CT Ratio  
Frequency  
Date  
Frequency  
Date  
Time  
Time  
Pulse Constant  
Pulse Width  
Pulse Output  
Multi Tariffs  
Control mode  
Disable  
Schedule  
by 2 Tariffs  
by Internal Clock  
by Digital Input  
by Communications  
by 3 Tariffs  
by 4 Tariffs  
Contrast  
Contrast  
Password  
Password  
Reset Config  
Reset Config  
Section  
Parameter  
Options  
Description  
3PH3W  
3PH4W  
Type  
1PH2W L-N  
Select the power system type the meter is wired to.  
1PH2W L-L  
Wiring  
1PH3W L-L-N  
3CTs on I1, I2, I3  
Define how many current transformers (CT) are connected to the meter and  
which terminals they are connected to.  
CT  
1 CT on I1  
2 CTs on I1, I3  
1
CT Secondary  
CT Primary  
Frequency  
Select the size of the CT secondary, in Amps.  
Enter the size of the CT primary, in Amps.  
5
CT Ratio  
1 - 32767  
50  
Frequency  
Select the frequency of the electrical power system, in Hz.  
60  
Date (iEM3210 / iEM3215)  
Time (iEM3210 / iEM3215)  
Date  
Time  
DD-MMM-YYYY  
Set the current date using the specified format.  
Set the time using the 24-hour format.  
hh:mm  
0.01  
0.1  
Pulse Constant  
(imp/kWh)  
1
Set the pulses per kWh for the pulse output.  
10  
100  
500  
50  
Pulse Output (iEM3210)  
Pulse Width  
(ms)  
100  
200  
300  
Set the pulse width (ON time).  
DOCA0005EN-04  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front panel display and meter setup  
iEM3100 / iEM3200 / iEM3300 series user manual  
Section  
Parameter  
Options  
Description  
Select the tariff control mode:  
Disable: the Multi Tariff function is disabled.  
by Digital Input: the digital input is associated with the multi-tariff  
function. A signal to the digital input changes the active tariff.  
by Internal Clock: the device clock controls the active tariff. If you set the  
Control Mode to by Internal Clock, you must also configure the schedule.  
Set the time when each tariff period starts, using the 24 hour clock format  
(00:00 to 23:59). The start time of the next tariff is the end time of the  
current tariff. For example, T2 start equals the end of T1.  
Disable  
Multi Tariffs (iEM3215)  
Control Mode  
by Internal Clock  
Contrast  
Contrast  
1-9  
Increase or decrease the value to increase or decrease the display contrast.  
Sets the password for accessing the meter configuration screens and resets.  
Settings are reset to their defaults, except for Password. Meter restarts.  
Password  
(iEM3210 / iEM3215)  
Password  
Reset Config  
0-9999  
Reset Config  
Configuration menus for iEM3250  
Type  
Wiring  
Frequency  
Date  
Frequency  
Date  
Time  
Time  
Slave Address  
Baud Rate  
Parity  
Communication  
Contrast  
Contrast  
Reset Config  
Reset Config  
Section  
Parameter  
Options  
Description  
3PH4W  
1PH2W L-N  
1PH2W L-L  
1PH3W L-L-N  
3PH3W  
Wiring  
Type  
Select the power system type the meter is wired to.  
1PH4W Multi L-N  
50  
Frequency  
Frequency  
Select the frequency of the electrical power system, in Hz.  
60  
Date  
Time  
Date  
Time  
DD-MMM-YYYY  
hh:mm  
Set the current date using the specified format.  
Set the time using the 24-hour format.  
Set the address for this device. The address must be unique for each device in  
a communications loop.  
Slave Address  
1 - 247  
19200  
38400  
9600  
Even  
Odd  
Select the speed for data transmission. The baud rate must be the same for all  
devices in a communications loop.  
Baud Rate  
Communication  
Select None if the parity bit is not used. The parity setting must be the same for  
all devices in a communications loop.  
Parity  
NOTE: Number of stop bits = 1.  
None  
1-9  
Contrast  
Contrast  
Increase or decrease the value to increase or decrease the display contrast.  
Settings are reset to their defaults, except for Password. Meter restarts.  
Reset Config  
Reset Config  
46  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Front panel display and meter setup  
Configuration menus for iEM3235 / iEM3255 / iEM3265 / iEM3275  
A
iEM3235 / iEM3255 / iEM3265  
iEM3255  
B
Type  
VT  
Wiring  
C
D
iEM3235  
iEM3265  
CT  
CT Secondary  
CT Primary  
CT & VT Ratio  
VT Secondary  
VT Primary  
Frequency  
Date  
Frequency  
Date  
Time  
Time  
Control mode  
Disable  
Multi Tariffs  
Schedule  
by 2 Tariffs  
by Internal Clock  
by Digital Input  
by Communications  
by 3 Tariffs  
by 4 Tariffs  
Alarm  
Overload Alarm  
Digital Output  
Disable  
Enable  
Pick Up Value  
DO Function  
Disable  
for Alarm  
for Pulse  
Pulse Constant  
Pulse Width  
DI Function  
Digital Input  
Input Status  
Tariff Control  
Input Metering  
Partial Reset  
In. Pulse Const.  
Slave Address  
Baud Rate  
Parity  
Primary Addr.  
Baud Rate  
MAC Addr.  
Baud Rate  
Device ID  
Communication  
Communication  
Communication  
Com.Protection  
Contrast  
Com.Protection  
Contrast  
Password  
Password  
Reset Config  
Reset Config  
DOCA0005EN-04  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front panel display and meter setup  
iEM3100 / iEM3200 / iEM3300 series user manual  
Section  
Parameter  
Options  
Description  
3PH3W  
3PH4W  
1PH2W L-N  
1PH2W L-L  
1PH3W L-L-N  
1PH4W Multi L-N  
Direct-NoVT  
Wye(3VTs)  
Delta(2VTs)  
3CTs on I1, I2, I3  
1 CT on I1  
2 CTs on I1, I3  
1
Type  
Select the power system type the meter is wired to.  
Wiring  
Select how many voltage transformers (VT) are connected to the electrical power  
system.  
VT  
CT  
Define how many current transformers (CT) are connected to the meter and which  
terminals they are connected to.  
CT Secondary  
CT Primary  
Select the size of the CT secondary, in Amps.  
Enter the size of the CT primary, in Amps.  
5
1 - 32767  
100  
CT & VT Ratio  
110  
VT Secondary  
Select the size of the VT secondary, in Volts.  
115  
120  
VT Primary  
Frequency  
1 - 1000000  
50  
Enter the size of the VT primary, in Volts.  
Frequency  
Select the frequency of the electrical power system, in Hz.  
60  
Date  
Time  
Date  
Time  
DD-MMM-YYYY  
hh:mm  
Set the current date using the specified format.  
Set the time using the 24-hour format.  
Select the tariff control mode:  
Disable: the Multi Tariff function is disabled.  
by Communication: the active tariff is control by communications. See the chapter  
for the applicable protocol for more information.  
Disable  
by Digital Input: the digital input is associated with the multi-tariff function. A signal to  
the digital input changes the active tariff.  
by Communication  
by Digital Input  
by Internal Clock  
Multi Tariffs  
Control Mode  
by Internal Clock: the device clock controls the active tariff. If you set the Control  
Mode to by Internal Clock, you must also configure the schedule. Set the time when  
each tariff period starts, using the 24 hour clock format (00:00 to 23:59). The start  
time of the next tariff is the end time of the current tariff. For example, T2 start  
equals the end of T1.  
Select whether or not the Overload Alarm is enabled:  
Disable  
Enable  
Disable: the alarm is disabled.  
Enable: the alarm is enabled. If you enabled the Overload Alarm, you must also  
configure the Pick Up Value in kW from 1 - 9999999.  
Overload Alarm  
Digital Output  
Alarm  
Select how the digital output functions:  
Disable: the digital output is disabled.  
for Alarm: the digital output is associated with the overload alarm. The meter sends  
a pulse to the digital output port when the alarm is triggered.  
for Pulse: The digital output is associated with energy pulsing. When this mode is  
selected, you must also configure the can select the energy parameter and the set  
the Pulse Constant (imp/kWh) and the Pulse Width (ms).  
Disable  
DO Function  
for Alarm  
for Pulse (kWh)  
NOTE: the iEM3275 does not have a digital output.  
Select how the digital input functions:  
Input status: the digital input records the status of the input, for example, OF, SD of  
a circuit breaker.  
Input Metering: the digital input is associated with input metering. The meter counts  
and records the number of incoming pulses. If you set the DI Function to Input  
Metering, you must also configure In. Pulse Constant.  
Tariff Control: the digital input is associated with the multi-tariff function. A signal to  
the digital input changes the active tariff.  
Partial Reset: a signal to the digital input initiates a partial reset.  
Input Status  
Tariff Control  
Input Metering  
Partial Reset  
Digital Input  
DI Function  
Set the address for this device. The address must be unique for each device in a  
communications loop.  
Slave Address  
Baud Rate  
1 - 247  
19200  
38400  
9600  
Even  
Odd  
Select the speed for data transmission. The baud rate must be the same for all devices  
in a communications loop.  
Communication (iEM3255)  
Select None if the parity bit is not used. The parity setting must be the same for all  
devices in a communications loop.  
Parity  
NOTE: Number of stop bits = 1.  
None  
48  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Front panel display and meter setup  
Section  
Parameter  
Options  
Description  
Set the address for this device. The address must be unique for each device in a  
communications loop.  
Primary Addr.  
0 - 255  
2400  
4800  
9600  
300  
Communication (iEM3235)  
Select the speed for data transmission. The baud rate must be the same for all devices  
in a communications loop.  
Baud Rate  
600  
1200  
Set the address for this device. The address must be unique for each device in a  
communications loop.  
MAC Addr.  
Baud Rate  
1 - 127  
9600  
19200  
38400  
57600  
76800  
Select the speed for data transmission. The baud rate must be the same for all devices  
in a communications loop.  
Communication (iEM3265)  
Set the Device ID for this device. Make sure the Device ID is unique in your BACnet  
network.  
Device ID  
0 - 4194303  
Enable  
Disable  
1-9  
Com.Protection  
Com.Protection  
Protects selected settings and resets from configuration via communications.  
Contrast  
Contrast  
Increase or decrease the value to increase or decrease the display contrast.  
Sets the password for accessing the meter configuration screens and resets.  
Settings are reset to their defaults, except for Password. Meter restarts.  
Password  
Reset Config  
Password  
Reset Config  
0-9999  
DOCA0005EN-04  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front panel display and meter setup  
iEM3100 / iEM3200 / iEM3300 series user manual  
50  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via Modbus RS-485  
Chapter 5  
Communications via Modbus RS-485  
What is in this chapter?  
This chapter contains the following sections:  
Modbus communication overview  
Modbus RTU protocol is available on the iEM3150, iEM3155, iEM3250, iEM3255, iEM3350 and  
iEM3355.  
The information in this section assumes that you have an advanced understanding of Modbus  
communications, your communications network and the power system that your meter is connected  
to.  
There are three different ways of using Modbus communication:  
Modbus communications settings  
Before communicating with the device using Modbus protocol, use the display to configure the  
following settings:  
Settings  
Possible values  
9600 Baud  
Baud rate  
19 200 Baud  
38 400 Baud  
Odd  
Even  
Parity  
None  
NOTE: number of stop bits = 1  
Address  
1–247  
Communications LED indicator for Modbus devices  
The yellow communications LED indicates the status of communication between the meter and the  
master as follows:  
If...  
Then...  
Communication with the device has been established.  
NOTE: If there is an error online, the LED also flashes.  
There is no active communication between the master and the slave  
The LED is flashing  
The LED is off  
Related topics  
For more information on the Modbus protocol, see the Modbus organization website at  
www.modbus.org.  
DOCA0005EN-04  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Communications via Modbus RS-485  
iEM3100 / iEM3200 / iEM3300 series user manual  
Modbus functions  
Function list  
The table below lists the supported Modbus functions:  
Function code  
Function name  
Decimal  
Hexadecimal  
3
0x03  
Read Holding Registers  
Write Multiple Registers  
Read Device Identification  
16  
0x10  
43/14  
0x2B/0x0E  
For example:  
To read different parameters from the meter, use function 3 (Read).  
To change the tariff, use function 16 (Write) to send a command to the meter.  
Table format  
Register tables have the following columns:  
Register Address  
Action (R/W/WC)  
Size  
Type  
Units Range  
Description  
Register Address: Modbus address of register encoded in the Modbus frame, in decimal (dec)  
Action: The read/write/write by command property of the register  
Size: The data size in Int16  
Type: The encoding data type  
Units: The unit of the register value  
Range: The permitted values for this variable, usually a subset of what the format allows  
Description: Provides information about the register and the values that apply  
Unit table  
The following data types appear in the Modbus register list:  
Type  
Description  
Range  
UInt16  
Int16  
16 bit unsigned integer  
16 bit signed integer  
32 bit unsigned integer  
64 bit unsigned integer  
8 bit field  
0 – 65535  
-32768 to +32767  
UInt32  
Int64  
0 – 4 294 967 295  
0 – 18 446 744 073 709 551 615  
UTF8  
multibyte character encoding for Unicode  
Float32  
Bitmap  
32 bit value  
Standard representation IEEE for floating number (with single precision)  
DATETIME See below  
52  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
DATETIME format:  
Communications via Modbus RS-485  
Bits  
Word  
15  
14  
13  
12  
11  
10  
9
8
7
6
5
4
3
2
1
0
1
Reserved (0)  
R4 (0)  
WD (0)  
iV  
Year (0 – 127)  
2
0
Month (1 – 12)  
Hour (0 – 23)  
Day (1 – 31)  
Minute (0 – 59)  
3
SU (0)  
0
0
4
Millisecond (0 – 59999)  
R4 :  
Reserved Bit  
Year :  
Month :  
Day :  
Hour :  
Minute :  
Millisecond :  
7 bits (year from 2000)  
4 bits  
5 bits  
5 bits  
6 bits  
2 octets  
WD (day of the week) :  
SU (summer time) :  
1–7: Sunday–Saturday  
Bit to 0 if this parameter is not used.  
Bit to 0 if this parameter is not valid or not used.  
iV (validity of received data) :  
Command interface  
Command interface overview  
The command interface allows you to configure the meter by sending specific command requests  
using Modbus function 16.  
Command request  
The following table describes a Modbus command request:  
Command block  
Slave  
Number  
Function  
Code  
CRC  
Register Address  
Command Description  
The command is made of a command number and a set of parameters. See the  
detailed description of each command in the command list.  
1–247  
16  
5250 (up to 5374)  
Checking  
NOTE: All the reserved parameters can be considered as any value, e.g. 0.  
The following table describes the command block:  
Register Address  
Content  
Size (Int16)  
Data (example)  
5250  
5251  
Command Number  
(Reserved)  
1
2008 (Set Tariff)  
1
0
4 (Tariff=4)  
5252–5374  
Parameter  
n
NOTE: Command number 2008 supports only  
one parameter with the size of 1.  
Command result  
The command result can be obtained by reading registers 5375 and 5376.  
The following table describes the command result:  
Register Address  
Content  
Size (Int16)  
Data (example)  
5375  
Requested Command Number  
Result  
1
2008 (Set Tariff)  
Command result codes:  
0 = Valid Operation  
3000 = Invalid Command  
3001 = Invalid Parameter  
3002 = Invalid Number of Parameters  
3007 = Operation Not Performed  
5376  
1
0 (Valid Operation)  
DOCA0005EN-04  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Communications via Modbus RS-485  
iEM3100 / iEM3200 / iEM3300 series user manual  
Command list  
Set Date/Time  
Command  
Number  
Action  
(R/W)  
Size  
Type  
Unit  
Range  
Description  
W
W
W
W
W
W
W
W
1
1
1
1
1
1
1
1
UInt16  
UInt16  
UInt16  
UInt16  
UInt16  
UInt16  
UInt16  
UInt16  
(Reserved)  
Year  
2000–2099  
1–12  
1–31  
23  
Month  
Day  
1003  
Hour  
0–59  
0–59  
Minute  
Second  
(Reserved)  
Set Wiring  
Command Action  
Size  
Type  
Unit  
Range  
Description  
Number  
(R/W)  
W
W
W
1
1
1
UInt16  
UInt16  
UInt16  
(Reserved)  
(Reserved)  
(Reserved)  
Power System Configuration  
0 = 1PH2W L-N  
1 = 1PH2W L-L  
2 = 1PH3W L-L-N  
3 = 3PH3W  
W
1
UInt16  
0, 1, 2, 3, 11,13  
11 = 3PH4W  
13 = 1PH4W L-N  
Nominal Frequency  
(Reserved)  
W
W
W
W
W
W
1
2
2
2
1
1
UInt16  
Float32  
Float32  
Float32  
UInt16  
UInt16  
Hz  
50, 60  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
VT Primary  
VT Secondary–  
1000000.0  
W
W
W
W
W
2
1
1
1
1
Float32  
UInt16  
UInt16  
UInt16  
UInt16  
V
V
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 /  
iEM3350 / iEM3355  
VT Secondary  
2000  
100, 110, 115, 120  
1, 2, 3  
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 /  
iEM3350 / iEM3355  
Number of CTs  
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 /  
iEM3350 / iEM3355  
CT Primary  
A
A
1–32767  
1, 5  
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 /  
iEM3350 / iEM3355  
CT Secondary  
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 /  
iEM3350 / iEM3355  
W
W
W
W
1
1
1
1
UInt16  
UInt16  
UInt16  
UInt16  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
VT Connection type:  
0 = Direct Connect  
1 = 3PH3W (2 VTs)  
2 = 3PH4W (3 VTs)  
W
1
UInt16  
0, 1, 2  
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 /  
iEM3350 / iEM3355  
54  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via Modbus RS-485  
Set Pulse Output (iEM3155 / iEM3255 / iEM3355)  
Command  
Number  
Action  
(R/W)  
Size  
Type  
Unit  
Range  
Description  
W
W
1
1
UInt16  
(Reserved)  
(Reserved)  
UInt16  
Pulse Output enable / disable  
0 = Disable  
W
1
UInt16  
0, 1  
1 = Enable  
iEM3155 / iEM3355:  
1, 10, 20, 100, 200,  
1000  
W
2
Float32  
pulse/kWh  
Pulse constant  
2003  
iEM3255: 0.01, 0.1,  
1, 10, 100, 500  
W
W
W
W
W
W
W
W
W
1
1
2
1
1
2
1
1
1
UInt16  
UInt16  
Float32  
UInt16  
UInt16  
Float32  
UInt16  
UInt16  
UInt16  
ms  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
Pulse width  
2038  
50, 100, 200, 300  
Set Tariff (iEM3155 / iEM3255 / iEM3355)  
Command  
Number  
Action  
(R/W)  
Size  
Type  
Unit  
Range  
Description  
W
W
W
1
1
1
UInt16  
(Reserved)  
Multi Tariff Mode  
0 = Disable Multi Tariff  
2060  
1 = Use COM as Tariff Control (maximum 4 tariffs)  
2 = Use Digital Input as Tariff Control (2 tariffs)  
UInt16  
UInt16  
0, 1, 2, 4  
4 = Use Internal Clock as Tariff Control (maximum 4  
tariffs)  
(Reserved)  
Tariff  
1 = T1  
2 = T2  
3 = T3  
4 = T4  
2008  
W
1
UInt16  
1–4  
NOTE: You can only set the tariff using this method if the  
Tariff Mode is set to by Communication.  
Set Digital Input as Partial Energy Reset (iEM3155 / iEM3255 / iEM3355)  
Command  
Number  
Action  
(R/W)  
Size  
Type  
Unit  
Range  
Description  
W
W
1
1
UInt16  
(Reserved)  
Digital Input to Associate:  
0 = Disable  
6017  
UInt16  
0, 1  
1 = Enable  
DOCA0005EN-04  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications via Modbus RS-485  
iEM3100 / iEM3200 / iEM3300 series user manual  
Input Metering Setup (iEM3155 / iEM3255 / iEM3355)  
Command  
Number  
Action  
(R/W)  
Size  
Type  
Unit  
Range  
Description  
W
W
W
W
W
1
UInt16  
1
(Reserved)  
1
UInt16  
UTF8  
Input Metering Channel  
Label  
20  
2
string size <= 40  
Float32  
UInt16  
1–10000  
Pulse Weight  
(Reserved)  
6014  
1
Digital Input Association:  
0 = Disable  
W
1
UInt16  
0, 1  
1 = Enable  
Overload Alarm Setup (iEM3155 / iEM3255 / iEM3355)  
Command  
Number  
Action  
(R/W)  
Size  
Type  
Unit  
Range  
Description  
W
W
W
W
W
1
1
1
1
1
UInt16  
9
(Reserved)  
Alarm ID  
UInt16  
UInt16  
UInt16  
UInt16  
(Reserved)  
(Reserved)  
(Reserved)  
0 = Disable  
1 = Enable  
Pickup value  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
W
1
UInt16  
0, 1  
W
W
W
W
W
W
W
W
W
W
W
2
2
2
2
1
4
1
1
1
2
2
Float32  
UInt32  
Float32  
UInt32  
UInt16  
UInt16  
UInt16  
UInt16  
UInt16  
Float32  
UInt32  
0.0–1e10  
7000  
20000  
20001  
Digital Output to Associate  
0 = Unassociated  
W
W
1
1
Bitmap  
UInt16  
0,1  
1 = Associated  
Acknowledge the Overload Alarm  
Communications Setup  
Command  
Number  
Action  
(R/W)  
Size  
Type  
Unit  
Range  
Description  
W
W
W
W
1
1
1
1
UInt16  
(Reserved)  
(Reserved)  
(Reserved)  
Address  
UInt16  
UInt16  
UInt16  
1–247  
Baud Rate  
0 = 9600  
1 = 19200  
2 = 38400  
Parity  
W
1
UInt16  
0, 1, 2  
5000  
0 = Even  
1 = Odd  
W
W
1
1
UInt16  
UInt16  
0, 1, 2  
2 = None  
(Reserved)  
56  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via Modbus RS-485  
Reset Partial Energy Counters  
Command  
Number  
Action  
(R/W)  
Size  
Type  
Unit  
Range  
Description  
(Reserved)  
iEM3150/iEM3250/iEM3350: Partial Active Energy and  
Phase Energy registers will be reset.  
2020  
W
1
UInt16  
iEM3155/iEM3255/iEM3355: Partial Active / Reactive  
Energy, Energy by tariff and Phase Energy registers will be  
reset.  
Reset Input Metering Counter (iEM3155 / iEM3255 / iEM3355)  
Command  
Number  
Action  
(R/W)  
Size  
Type  
Unit  
Range  
Description  
2023  
W
1
UInt16  
(Reserved)  
Modbus register list  
System  
Register  
Address (R/W/WC  
Action  
Size  
Type  
Units  
Description  
30  
R
R
R
R
R
R
R
20  
UTF8  
Meter Name  
50  
20  
20  
2
UTF8  
Meter Model  
70  
UTF8  
Manufacturer  
130  
132  
136  
1637  
UInt32  
DATETIME  
UTF8  
Serial Number  
4
Date of Manufacture  
Hardware Revision  
5
1
UInt16  
Present Firmware Version (DLF format): X.Y.ZTT  
Date/Time  
Reg. 1845: Year (b6:b0) 0–99 (year from 2000 to 2099)  
Reg. 1846: Month (b11:b8), Weekday (b7:b5), Day (b4:b0)  
Reg. 1847: Hour (b12:b8), Minute (b5:b0)  
Reg. 1848: Millisecond  
1845–1848 R/WC  
1 X 4  
UInt16  
Meter Setup and Status  
Register  
Address (R/W/WC)  
Action  
Size  
Type  
Units  
Description  
Meter Operation Timer  
2004  
R
2
UInt32  
Second  
Not applicable for iEM3150 / iEM3250 / iEM3350  
2014  
2015  
R
R
1
1
UInt16  
UInt16  
Number of Phases  
Number of Wires  
Power System  
0 = 1PH2W L–N  
1 = 1PH2W L–L  
2016  
R/WC  
1
UInt16  
2 = 1PH3W L–L with N  
3 = 3PH3W  
11 = 3PH4W  
13 = 1PH4W multi L with N  
2017  
2025  
R/WC  
R
1
1
UInt16  
UInt16  
Hz  
Nominal Frequency  
Number VTs  
Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355  
VT Primary  
2026  
2028  
2029  
2030  
R/WC  
R/WC  
R/WC  
R/WC  
2
1
1
1
Float32  
UInt16  
UInt16  
UInt16  
V
V
Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355  
VT Secondary  
Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355  
Number CTs  
Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355  
CT Primary  
A
Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355  
DOCA0005EN-04  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Communications via Modbus RS-485  
iEM3100 / iEM3200 / iEM3300 series user manual  
Register  
Address (R/W/WC)  
Action  
Size  
Type  
Units  
Description  
CT Secondary  
2031  
R/WC  
1
1
UInt16  
A
Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355  
VT Connection Type  
0 = Direct Connect  
2036  
R/WC  
UInt16  
1 = 3PH3W (2 VTs)  
2 = 3PH4W (3 VTs)  
Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355  
Energy Pulse Output Setup (iEM3155 / iEM3255 / iEM3355)  
Register  
Address (R/W/WC)  
Action  
Size  
Type  
Units  
Description  
2129  
2131  
2132  
R/WC  
R/WC  
R/WC  
1
1
2
UInt16  
Millisecond  
Energy Pulse Duration  
Digital Output Association  
0 = Disable  
UInt16  
1 = DO1 enable for active energy pulse output  
Pulse Weight  
Float32  
pulse/kWh  
Command Interface  
Register  
Address (R/W/WC)  
Action  
Size  
Type  
Units  
Description  
5250  
5252  
5374  
5375  
R/W  
R/W  
R/W  
R
1
1
1
1
UInt16  
UInt16  
UInt16  
UInt16  
Requested Command  
Command Parameter 001  
Command Parameter 123  
Command Status  
Command Result codes:  
0 = Valid Operation  
3000 = Invalid Command  
3001 = Invalid Parameter  
3002 = Invalid Number of Parameters  
3007 = Operation Not Performed  
Command Data 001  
5376  
R
1
UInt16  
5377  
5499  
R/W  
R
1
1
UInt16  
UInt16  
Command Data 123  
Communication  
Register  
Address (R/W/WC)  
Action  
Size  
Type  
Units  
Description  
Protocol  
6500  
6501  
R
1
1
UInt16  
UInt16  
0 = Modbus  
Address  
R/WC  
Baud Rate:  
0 = 9600  
6502  
R/WC  
R/WC  
1
UInt16  
1 = 19 200  
2 = 38 400  
Parity:  
0 = Even  
6503  
1
UInt16  
1 = Odd  
2 = None  
NOTE: number of stop bits = 1  
Input Metering Setup (iEM3155 / iEM3255 / iEM3355)  
Register  
Address (R/W/WC)  
Action  
Size  
Type  
Units  
Description  
7032  
R/WC  
20  
UTF8  
Label  
58  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via Modbus RS-485  
Register  
Address (R/W/WC)  
Action  
Size  
Type  
Units  
Description  
7052  
7055  
R/WC  
R/WC  
2
1
Float32  
pulse/unit Pulse Constant  
Digital Input Association  
0 = Disable for input metering  
1 = Enable for input metering  
UInt16  
Digital Input (iEM3155 / iEM3255 / iEM3355)  
Register  
Address (R/W/WC)  
Action  
Size  
Type  
Units  
Description  
Digital Input Control Mode:  
0 = Normal (Input Status)  
2 = Multi Tariff Control  
3 = Input Metering  
7274  
8905  
R
R
1
2
UInt16  
5 = All Energy Reset  
Digital Input Status (only Bit 1 is used):  
Bit 1 = 0, relay open  
Bitmap  
Bit 1 = 1, relay closed  
Digital Output (iEM3155 / iEM3255 / iEM3355)  
Register Action  
Address (R/W/WC)  
Size  
Type  
Units  
Description  
Digital Output Control Mode Status:  
2 = for Alarm  
9673  
R
1
UInt16  
3 = for Pulse (kWh)  
0xFFFF = Disable  
Meter Data  
Current, voltage, power, power factor and frequency  
Register Action  
Address (R/W/WC)  
Size  
Type  
Units  
Description  
Current  
3000  
3002  
3004  
3010  
R
R
R
R
2
Float32  
A
A
A
A
I1: phase 1 current  
I2: phase 2 current  
I3: phase 3 current  
Current Avg  
2
2
2
Float32  
Float32  
Float32  
Voltage  
3020  
3022  
3024  
3026  
3028  
3030  
3032  
3036  
R
R
R
R
R
R
R
R
2
2
2
2
2
2
2
2
Float32  
Float32  
Float32  
Float32  
Float32  
Float32  
Float32  
Float32  
V
V
V
V
V
V
V
V
Voltage L1–L2  
Voltage L2–L3  
Voltage L3–L1  
Voltage L–L Avg  
Voltage L1–N  
Voltage L2–N  
Voltage L3–N  
Voltage L–N Avg  
Power  
3054  
3056  
3058  
3060  
R
R
R
R
2
2
2
2
Float32  
Float32  
Float32  
Float32  
kW  
kW  
kW  
kW  
Active Power Phase 1  
Active Power Phase 2  
Active Power Phase 3  
Total Active Power  
Total Reactive Power  
3068  
3076  
R
R
2
2
Float32  
Float32  
kVAR  
kVA  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Total Apparent Power  
Not applicable for iEM3150 / iEM3250 / iEM3350  
DOCA0005EN-04  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications via Modbus RS-485  
iEM3100 / iEM3200 / iEM3300 series user manual  
Register Action  
Address (R/W/WC)  
Size  
Type  
Units  
Description  
Power Factor  
Total Power Factor:  
-2 < PF < -1 = Quad 2, active power negative, capacitive  
-1 < PF < 0 = Quad 3, active power negative, inductive  
0 < PF < 1 = Quad 1, active power positive, inductive  
1 < PF < 2 = Quad 4, active power positive, capacitive  
3084  
R
2
Float32  
Frequency  
3110  
R
2
Float32  
Hz  
Frequency  
Energy, energy by tariff and input metering  
Most energy values are available in both signed 64-bit integer and 32-bit floating point format.  
The energy and energy by tariff measurements listed below are preserved through power failures.  
Energy reset and active tariff information  
Register Action  
Size  
Type  
Units  
Description  
Address (R/W/WC)  
3252  
3554  
R
R
4
DATETIME  
DATETIME  
Energy Reset Date and Time  
Input Metering Accumulation Reset Date and Time  
Not applicable for iEM3150 / iEM3250 / iEM3350  
MultiTariffs Energy Active Rate  
4
1
0: multi tariff disabled  
1 to 4: rate A to rate D  
4191  
R/WC  
UInt16  
Not applicable for iEM3150 / iEM3250 / iEM3350  
NOTE: You can only set the tariff using this method if the Tariff Mode  
is set to by Communication.  
Energy values – 64-bit integer  
Units  
Register Action  
Address (R/W/WC)  
Size  
Type  
Description  
Total Energy (cannot be reset)  
3204  
3208  
R
R
4
4
Int64  
Int64  
Wh  
Wh  
Total Active Energy Import  
Total Active Energy Export  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Total Reactive Energy Import  
3220  
3224  
R
R
4
4
Int64  
Int64  
VARh  
VARh  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Total Reactive Energy Export  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Partial Energy  
3256  
3272  
R
R
4
4
Int64  
Int64  
Wh  
Partial Active Energy Import  
Partial Reactive Energy Import  
VARh  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Phase Energy  
3518  
3522  
3526  
R
R
R
4
4
4
Int64  
Int64  
Int64  
Wh  
Wh  
Wh  
Active Energy Import Phase 1  
Active Energy Import Phase 2  
Active Energy Import Phase 3  
Input Metering Counter  
Input Metering Accumulation  
3558  
R
4
Int64  
Unit  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Energy by Tariff (iEM3155 / iEM3255 / iEM3355 only)  
4196  
4200  
4204  
4208  
R
R
R
R
4
4
4
4
Int64  
Int64  
Int64  
Int64  
Wh  
Wh  
Wh  
Wh  
Rate A Active Energy Import  
Rate B Active Energy Import  
Rate C Active Energy Import  
Rate D Active Energy Import  
60  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via Modbus RS-485  
Energy values – 32-bit floating point  
Type Units  
Register Action  
Address (R/W/WC)  
Size  
Description  
Total Energy (cannot be reset)  
45100  
45102  
R
R
2
2
Float32  
Float32  
Wh  
Total Active Energy Import  
Total Active Energy Export  
Wh  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Total Reactive Energy Import  
45104  
45106  
R
R
2
2
Float32  
Float32  
VARh  
VARh  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Total Reactive Energy Export  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Partial Energy  
45108  
45110  
R
R
2
2
Float32  
Float32  
Wh  
Partial Active Energy Import  
Partial Reactive Energy Import  
VARh  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Phase Energy  
45112  
45114  
45116  
R
R
R
2
2
2
Float32  
Float32  
Float32  
Wh  
Wh  
Wh  
Active Energy Import Phase 1  
Active Energy Import Phase 2  
Active Energy Import Phase 3  
Input Metering Counter  
Input Metering Accumulation  
45118  
R
2
Float32  
Unit  
Not applicable for iEM3150 / iEM3250 / iEM3350  
Energy by Tariff (iEM3155 / iEM3255 / iEM3355 only)  
45120  
45122  
45124  
45126  
R
R
R
R
2
2
2
2
Float32  
Float32  
Float32  
Float32  
Wh  
Wh  
Wh  
Wh  
Rate A Active Energy Import  
Rate B Active Energy Import  
Rate C Active Energy Import  
Rate D Active Energy Import  
Overload Alarm (iEM3155 / iEM3255 / iEM3355)  
Register Action  
Address (R/W/WC)  
Size  
Type  
Units  
Description  
Overload Alarm Setup:  
0x0000 = Disabled  
0x0100 = Enabled  
45001  
45002  
45004  
R/WC  
R/WC  
R/WC  
1
Bitmap  
2
1
Float32  
Bitmap  
kW  
Pickup Setpoint  
Digital Output to Associate:  
0x0000 = Digital Output unassociated to overload alarm  
0x0100 = Digital Output associated to overload alarm  
Activated Status:  
45005  
45006  
R
R
1
1
Bitmap  
Bitmap  
0x0000 = Alarm is inactive  
0x0100 = Alarm is active  
Unacknowledged Status:  
0x0000 = Historic alarm is acknowledged by the user  
0x0100 = Historic alarm is unacknowledged by the user  
Last Alarm - Time Stamp  
45007  
45011  
R
R
4
2
DATETIME  
Float32  
kW  
Last Alarm - Value  
Read Device Identification  
The meters supports the Read Device Identification function with the mandatory objects  
VendorName, ProductCode and Revision Number.  
DOCA0005EN-04  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Communications via Modbus RS-485  
iEM3100 / iEM3200 / iEM3300 series user manual  
Object ID Name/Description  
Length Value  
Note  
0x00  
0x01  
0x02  
VendorName  
16  
09  
04  
SchneiderElectric  
A9MEM3150  
A9MEM3155  
A9MEM3250  
A9MEM3255  
A9MEM3350  
A9MEM3355  
V1.0  
The ProductCode value is identical to the catalog number  
of each device.  
ProductCode  
MajorMinorRevision  
Equivalent to X.Y in register 1637  
The Read Device ID codes 01 and 04 are supported:  
01 = request to get basic device identification (stream access)  
04 = request to get one specific identification object (individual access)  
The Modbus request and response are compliant with the Modbus Application Protocol Specification.  
62  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via LonWorks  
Chapter 6  
Communications via LonWorks  
What is in this chapter?  
This chapter contains the following sections:  
Standard network variable types (SNVTs) and configuration properties for  
reading data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
LonWorks communications overview  
LonWorks communications is available on the iEM3175, iEM3275 and iEM3375.  
The information in this section assumes that you have an advanced understanding of LonWorks  
communications, your communications network and the power system that your device is connected  
to.  
Related topics  
See the LonMark International website at www.lonmark.org for more information on LonTalk  
protocol or LonWorks communications.  
LonWorks communication implementation  
External interface file (XIF)  
The variables and configuration properties for the meter are documented in the external interface file  
(XIF). The XIF file is loaded onto the meter where your LNS (LonWorks Network Services) software  
can download it. You can also download the XIF file from www.schneider-electric.com if you need to  
manually add the XIF file to your software.  
The LonMaker plug-ins  
The plug-ins allow you to configure the meter and view meter data in Echelon LonMaker.  
LED indicators for LonWorks meters  
The LonWorks meters have two LonWorks status LEDs: the red service LED and the green  
communications LED.  
Red service LED  
This LED provides the status of LonWorks operations.  
LED state  
Description  
The LED is off  
The meter is configured. It may be online or offline.  
The LED is flashing The meter is unconfigured but has an application.  
The meter is unconfigured and without an application, or  
There is a defective internal memory issue.  
The LED is on  
DOCA0005EN-04  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Communications via LonWorks  
iEM3100 / iEM3200 / iEM3300 series user manual  
Green communications LED  
This LED provides the status of the meter’s communications with the network.  
LED state  
Description  
The LED is off  
Communication is not active.  
The LED is flashing Communication is active.  
Location of the service pin and Neuron ID  
The service pin is located on the front panel. Press this when requested by your LNS software in order  
to identify the meter to your LonWorks network.  
You can also find the Neuron ID on the meter label if you need to manually enter it into your LNS  
software.  
A
B
Service pin  
Location of the Neuron ID on the front panel  
LON  
C/- DI  
OK  
ESC  
Reset  
Neuron ID: 000000000000  
S/N: 0000000000  
Config  
Related topics  
communications.  
instructions on installing and using the LonMaker plug-in.  
Standard network variable types (SNVTs) and configuration properties for reading data  
The following sections outline the standard network variable types (SNVTs), the standard  
configuration property types (SCPTs), and user configuration property types (UCPTs) that you can  
access to read data from the meter.  
Related topics  
LonWorks.  
General variables  
Network variable label  
Type  
Description  
nviRequest  
nvoStatus  
SCPTpartNumber  
SCPToemType  
For LonWorks internal communication.  
For LonWorks internal communication.  
System variables  
Network variable label  
Type  
Description  
nvoFileDirectory  
nvoResponse  
SNVT_address  
SNVT_count  
Configuration parameter file directory address (LonMark)  
Command result (LonMark)  
64  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via LonWorks  
Network variable label  
Type  
Description  
Device error status  
Error bitmap: each bit of the bitmap provides error information about  
the device. If value of the bit = 1, that error is active.  
Bit0 = Code 101: EEPROM error  
Bit1 = Code 102: No calibration table  
Bit2 = Code 201: mismatch between frequency settings and  
frequency measurements  
Bit3 = Code 202: mismatch between wiring settings and wiring inputs  
Bit4 = Code 203: phase sequence reversed  
Bit5 = Not used  
nvoErrors  
SNVT_state  
Bit6 = Code 205: Date and time have been reset due to a power  
failure  
Bit7 = Not used  
Bit8 = Code 207: Abnormal internal clock function  
Bit9 = Internal data bus communications error  
Bit10 - 15: Not used  
SNVT_str_asc  
(SCPTpartNumber)  
nciMeterModel  
nciMeterManf  
Device model, stored as an ASCII string (for example, iEM3275)  
Manufacturer name (Schneider Electric)  
Device serial number  
SNVT_str_asc  
(SCPToemType)  
SNVT_str_asc  
(SCPTserialNumber)  
nciSerialNumber  
nciManfDateTime  
SNVT_time_stamp  
(SCPTmanfDate)  
Date of manufacture  
LonWorks firmware major version (for example, 2.xx)  
nciDevMajVer  
SCPTdevMajVer  
SCPTdevMinVer  
This variable functions with nciDevMinVer to provide the device’s  
LonWorks firmware version  
LonWorks firmware minor version (for example, x.34)  
nciDevMinVer  
This variable functions with nciDevMajVer to provide the device’s  
LonWorks firmware version  
SNVT_str_asc  
(UCPTMeterVersion)  
nciMeterVersion  
Device firmware version, stored as an ASCII text string  
Related topics  
network update rate.  
Energy and energy by tariff measurements  
Most energy values are available in both signed 32-bit integer and floating point format. The SNVT is  
appended with _l for 32-bit integer values and _f for floating point values.  
For example, the SNVTs for total active energy import are as follows:  
32-bit integer: SNVT_elec_kwh_l  
Floating point: SNVT_elec_whr_f  
The energy and energy by tariff measurements listed below are preserved through power failures.  
Network variable label Type  
Description  
nvoTotkWhImp  
nvoTotkWhExp  
nvoTotkVARhImp  
nvoTotkVARhExp  
nvoTotWhImp  
SNVT_elec_kwh_l  
Total active energy import  
Total active energy export  
Total reactive energy import  
Total reactive energy export  
Total active energy import  
Total active energy export  
Total reactive energy import  
Total reactive energy export  
Partial active energy import  
Partial reactive energy import  
Partial active energy import  
Partial reactive energy import  
SNVT_elec_kwh_l  
SNVT_elec_kwh_l  
SNVT_elec_kwh_l  
SNVT_elec_whr_f  
SNVT_elec_whr_f  
SNVT_elec_whr_f  
SNVT_elec_whr_f  
SNVT_elec_kwh_l  
SNVT_elec_kwh_l  
SNVT_elec_whr_f  
SNVT_elec_whr_f  
nvoTotWhExp  
nvoTotVARhImp  
nvoTotVARhExp  
nvoPartialkWh  
nvoPartialkVARh  
nvoPartialWh  
nvoPartialVARh  
DOCA0005EN-04  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications via LonWorks  
iEM3100 / iEM3200 / iEM3300 series user manual  
Network variable label Type  
Description  
nvoPh1kWh  
nvoPh2kWh  
nvoPh3kWh  
nvoPh1Wh  
nvoPh2Wh  
nvoPh3Wh  
SNVT_elec_kwh_l  
SNVT_elec_kwh_l  
SNVT_elec_kwh_l  
SNVT_elec_whr_f  
SNVT_elec_whr_f  
SNVT_elec_whr_f  
Active energy import phase 1  
Active energy import phase 2  
Active energy import phase 3  
Active energy import phase 1  
Active energy import phase 2  
Active energy import phase 3  
Active tariff  
0 = Multi Tariff feature is disabled  
1 = rate A (tariff 1) active  
nvoTariffActRate  
SNVT_count  
2 = rate B (tariff 2) active  
3 = rate C (tariff 3) active  
4 = rate D (tariff 4) active  
nvoTariffAkWh  
nvoTariffBkWh  
nvoTariffCkWh  
nvoTariffDkWh  
nvoTariffAWh  
nvoTariffBWh  
nvoTariffCWh  
nvoTariffDWh  
nvoInMeterAcc  
nvoRstEnergyDT  
SNVT_elec_kwh_l  
SNVT_elec_kwh_l  
SNVT_elec_kwh_l  
SNVT_elec_kwh_l  
SNVT_elec_whr_f  
SNVT_elec_whr_f  
SNVT_elec_whr_f  
SNVT_elec_whr_f  
SNVT_count_f  
Rate A (tariff 1) active energy import  
Rate B (tariff 2) active energy import  
Rate C (tariff 3) active energy import  
Rate D (tariff 4) active energy import  
Rate A (tariff 1) active energy import  
Rate B (tariff 2) active energy import  
Rate C (tariff 3) active energy import  
Rate D (tariff 4) active energy import  
Input metering accumulation  
Date and time of last energy reset  
SNVT_time_stamp  
Related topics  
network update rate.  
Instantaneous (RMS) measurements  
Network variable label Type  
Description  
nvoActPowerPh1  
nvoActPowerPh2  
nvoActPowerPh3  
nvoActPowerSum  
nvoRctPowerSum  
nvoAppPowerSum  
nvoVoltsL1N  
SNVT_power_f  
Active power Phase 1  
Active power Phase 2  
Active power Phase 3  
Total active power  
Total reactive power  
Total apparent power  
Voltage L1-N  
SNVT_power_f  
SNVT_power_f  
SNVT_power_f  
SNVT_power_f  
SNVT_power_f  
SNVT_volt_f  
SNVT_volt_f  
SNVT_volt_f  
SNVT_volt_f  
SNVT_volt_f  
SNVT_volt_f  
SNVT_volt_f  
SNVT_volt_f  
SNVT_amp_f  
SNVT_amp_f  
SNVT_amp_f  
SNVT_amp_f  
SNVT_count_inc_f  
SNVT_freq_f  
nvoVoltsL2N  
Voltage L2-N  
nvoVoltsL3N  
Voltage L3-N  
nvoVoltsLNAvg  
nvoVoltsL1L2  
Average voltage line-to-neutral  
Voltage L1-L2  
nvoVoltsL2L3  
Voltage L2-L3  
nvoVoltsL3L1  
Voltage L3-L1  
nvoVoltsLLAvg  
nvoCurrentPh1  
nvoCurrentPh2  
nvoCurrentPh3  
nvoCurrentAvg  
nvoAvgPwrFactor  
nvoFrequency  
Average voltage line-to-line  
Phase 1 current  
Phase 2 current  
Phase 3 current  
Average current  
Total power factor  
Frequency  
Related topics  
network update rate.  
66  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via LonWorks  
Meter status information  
You can read the following network variables to obtain configuration and status information about the  
meter. For information on configuring the meter, see the sections on meter configuration properties  
and the LonWorks plug-in.  
Network variable label SNVT / UCPT type  
Basic information and meter configuration  
Description  
nvoDateTime  
nvoOpTimer  
SNVT_time_stamp  
SNVT_count_32  
Meter date and time (DD/MM/YYYY hh:mm:ss)  
Meter operation timer: the time in seconds since the meter was last  
powered up  
System configuration information  
Power system configuration:  
0 = 1PH2W L-N  
1 = 1PH2W L-L  
nciSystemType  
SNVT_count  
2 = 1PH3W L-L with N  
3 = 3PH3W  
11 = 3PH4W  
13 = 1PH4 wire multi L-N  
Number of wires  
nciWireNum  
SNVT_count  
SNVT_count  
2, 3, 4  
Number of phases  
1, 3  
nciPhaseNum  
Number of CTs  
nciCtNum  
nciVtNum  
SNVT_count  
SNVT_count  
1, 2, 3  
NOTE: only applies to the iEM3275  
Number of VTs  
0-10  
NOTE: only applies to the iEM3275  
VT Primary  
nciVtPrimary  
SNVT_count_32  
SNVT_count  
SNVT_count  
SNVT_count  
NOTE: only applies to the iEM3275  
VT Secondary  
nciVTSecondary  
nciCtPrimary  
NOTE: only applies to the iEM3275  
CT Primary  
NOTE: only applies to the iEM3275  
CT Secondary  
nciCtSecondary  
NOTE: only applies to the iEM3275  
VT connection type  
0 = Direct connection, no VTs  
1 = 3PH3W (2VTs)  
2 = 3PH4W (3VTs)  
System frequency  
50, 60  
nciVtConnType  
SNVT_count  
nciNominalFreq  
SNVT_freq_hz  
Digital input configuration and status information  
Digital input control mode  
0 = Normal (input status)  
nciDICtrMode  
SNVT_count  
2 = Multi Tariff control  
3 = Input metering  
5 = All partial energy reset (configure to reset all partial energy logs)  
Pulse constant (pulses/unit)  
Digital input status (only Bit 1 is used)  
0 = relay open  
nciDIPulseConst  
nvoDIStatus  
SNVT_count_32  
SNVT_count  
1 = relay closed  
NOTE: The information provided by this variable only applies if the  
digital input control mode is set to Input Status.  
Alarm status  
Alarm status (only Bit 1 is used)  
0 = Alarm is inactive  
nvoAlmStatus  
SNVT_count  
1 = Alarm is active  
DOCA0005EN-04  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications via LonWorks  
iEM3100 / iEM3200 / iEM3300 series user manual  
Network variable label SNVT / UCPT type  
Description  
Acknowledgement status (only Bit 1 is used):  
0 = historic alarm is acknowledged by the user  
1 = historic alarm is unacknowledged by the user  
Timestamp of last alarm (DD/MM/YYYY hh:mm:ss)  
Value at last alarm  
nvoAlmUnAckState  
SNVT_count  
nvoAlmLastTime  
nvoAlmLastValue  
SNVT_time_stamp  
SNVT_power_f  
Overload alarm configuration:  
nciAlmEnable  
SNVT_count  
0 = disabled  
1 = enabled  
nciAlmPkUpSetPt  
Related topics  
SNVT_power_f  
Active power alarm pickup setpoint in kW  
can use to configure the meter.  
instructions on using the LNS plug-in to configure the meter.  
Resets  
Network variable label  
Type  
Description  
Action  
Resets all partial energy accumulators to 0:  
Partial active energy import (nvoPartialkWh, nvoPartialWh)  
Partial reactive energy import (nvoPartialkVARh, nvoPartialVARh)  
Rate A active energy import (nvoTariffAkWh, nvoTariffAWh)  
Rate B active energy import (nvoTariffBkWh, nvoTariffBWh)  
Rate C active energy import (nvoTariffCkWh, nvoTariffCWh)  
Rate D active energy import (nvoTariffDkWh, nvoTariffDWh)  
Active energy import phase 1 (nvoPh1kWh, nvoPh1Wh)  
Active energy import phase 2 (nvoPh2kWh, nvoPh2Wh)  
Active energy import phase 3 (nvoPh3kWh, nvoPh3Wh)  
nciRstPartEnergy  
SNVT_switch  
SNVT_swtich  
To reset, set the state field to 1.  
To reset, set the state field to 1.  
nciRstInMeterAcc  
Resets input metering accumulation (nvoInMeterAcc) to 0  
Meter configuration properties  
You can configure the meter using the configuration properties listed in this section. However, it is  
recommended that you use the Echelon LonMaker plug-in if you are configuring the meter using  
LonWorks communications.  
NOTE: If Com. Protection is enabled, you may receive an error response when you try to configure  
the meter over communications.  
Related topics  
instructions on using the LNS plug-in to configure the device.  
Date/time setup  
Function profile UCPT  
Struct Members Range / options  
year  
2000 - 2099  
1 - 12  
month  
day  
1 - 31  
nciCfgDateTime  
UCPTDateTime  
hour  
0 - 23  
minute  
second  
0 - 59  
0 - 59  
68  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via LonWorks  
Basic setup  
Function profile UCPT  
Struct Members  
Range / options  
Description  
0 = 1PH2W L-N  
1 = 1PH2W L-L  
2 = 1PH3W L-L with N  
3 = 3PH3W  
SystemType  
0, 1, 2, 3, 11, 13  
11 = 3PH4W  
13 = 1PH4 wire multi L with N  
Nominal frequency in Hz  
NominFreq  
VtPrimary  
50, 60  
The minimum value for VtPrimary  
must be equal to or greater than  
the value set for VtSecondary.  
0 - 1000000.0  
nciCfgWiring  
UCPTWiring  
VtSecondary  
CtNum  
100, 110, 115, 120  
1, 2, 3  
CtPrimary  
CtSecondary  
1 - 32767  
1, 5  
VT connection type  
0 = Direct connection  
1 = 3PH3W (2VTs)  
2 = 3PH4W (3VTs)  
VtConnType  
0, 1, 2  
Digital input setup  
Function profile UCPT  
Struct Members Range / options Description  
Associates the digital input to reset partial  
energy data:  
0 = Digital input is not associated with the  
partial energy reset.  
1 = Digital input is associated with the partial  
energy reset.  
nciCfgDigitInpt  
UCPTDigitalInput  
0, 1  
Setting this property to 1 also updates  
nciDICtrlMode (UCPTDiCtrlMode) to All  
Energy Reset.  
Input metering setup  
Function profile UCPT  
Struct Members Range / options Description  
Sets the pulse weight (1 - 10000 ms)  
Setting this property also sets  
nciDIPulseConst (UCPTDiPulseConst) to  
the same value.  
PulseWeight  
1 - 10000  
Associates the digital input with input  
metering:  
0 = Digital input is not associated with input  
metering.  
nciCfgInptMetAcc UCPTInputMetering  
1 = The digital input is associated with input  
metering.  
DigitalAssociation  
0, 1  
Setting this property to 1 also updates  
nciDICtrlMode (UCPTDiCtrlMode) to Input  
Metering.  
DOCA0005EN-04  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications via LonWorks  
iEM3100 / iEM3200 / iEM3300 series user manual  
Overload alarm setup  
Function profile UCPT  
Struct Members Range / options Description  
Enable or disable the overload alarm:  
0 = Disabled  
AlmEnable  
0, 1  
nciCfgOvLoadAlm UCPTOverLoadAlarm  
1 = Enabled  
PkUpSetpoint  
1 - 9999999  
The pickup value for the overload alarm  
Acknowledgement status (only Bit 1 is  
used):  
0 = historic alarm is acknowledged by  
the user  
nciCfgOvLoadAck UCPTOverLoadAlmAck —  
0, 1  
1 = historic alarm is unacknowledged by  
the user  
Multi Tariff setup  
Function profile UCPT  
Struct Members Range / options Description  
Set Multi Tariff control mode to Disabled or by  
Communication  
0 = Disabled  
nciCfgCommTariff UCPTTariffMode  
0, 1  
1 = by Communication  
NOTE: To configure the Multi Tariff feature to  
be controlled by the digital input or device  
clock, use the HMI.  
Set the active tariff  
1 = Rate A (tariff 1)  
2 = Rate B (tariff 2)  
3 = Rate C (tariff 3)  
4 = Rate D (tariff 4)  
nciCfgTariffSel  
UCPTTariffSelect —  
1, 2, 3, 4  
NOTE: You can only set the tariff using this  
method if the Tariff Mode is set to by  
Communication.  
Network propagation rate setup  
The following configuration properties help control network traffic by controlling the rate at which  
variable values are sent to your LNS.  
nci variable  
UCPTs/SCPTs  
Applies to...  
Description  
nciErrors  
nciAllEnergy  
nciAllPower  
nciAllVoltage  
nciAllCurrent  
nciAllPowerFactor  
nciFrequency.  
Limits the total number of updates sent per second for listed nci variables.  
If more than the specified number of updates are queued to be sent out in any 1  
second period, the excess updates are delayed until the next second to reduce  
network traffic. The number of updates sent per second varies depending on  
the connection type updates from network variables that are not controlled by  
this configuration property.  
nciMaxNvSntPerSec  
UCPTNVUpdtLimit  
Maximum interval, in seconds, between transmissions of error values to the  
network.  
nciErrors  
SCPTmaxSendTime  
nvoErrors  
The value of the applicable variable is sent after the interval has elapsed,  
regardless of whether or not the value of the variable has changed. The counter  
is reset to 0.  
70  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via LonWorks  
nci variable  
UCPTs/SCPTs  
Applies to...  
Description  
Floating-point energy values:  
nvoTotWhImp  
nvoTotWhExp  
nvoTotVARhImp  
nvoTotVARhExp  
nvoPartialWh  
nvoPartialVARh  
nvoPh1Wh  
nvoPh2Wh  
nvoPh3Wh  
nvoTariffAWh  
nvoTariffBWh  
nvoTariffCWh  
nvoTariffDWh  
nciAllEnergy  
SCPTminSendTime  
nvoActPowerPh1  
nvoActPowerPh2  
nvoActPowerPh3  
nvoActPowerSum  
nvoRctPowerSum  
nvoAppPowerSum  
The minimum interval, in seconds, between consecutive transmissions of the  
listed variable values to the network.  
nciAllPower  
SCPTminSendTime  
No updates to the value of the applicable variables are sent over the network  
until the minimum interval has elapsed, regardless of whether or not the value of  
the variable has changed.  
After an update is sent, the counter is reset to 0.  
nvoVoltsL1N  
nvoVoltsL2N  
nvoVoltsL3N  
nvoVoltsLNAvg  
nvoVoltsL1L2  
nvoVoltsL2L3  
nvoVoltsL3L1  
nvoVoltsLLAvg  
nciAllVoltage  
nciAllCurrent  
SCPTminSendTime  
SCPTminSendTime  
nvoCurrentPh1  
nvoCurrentPh2  
nvoCurrentPh3  
nvoCurrentAvg  
nciAllPowerFactor  
nciFrequency  
SCPTminSendTime  
SCPTminSendTime  
nvoAvgPwrFactor  
nvoFrequency  
Echelon LonMaker plug-in for data display and meter configuration  
The information in this section assumes that you have an advanced understanding of system  
administration using Echelon LonMaker.  
The LonMaker plug-in provides a graphical user interface where you can view meter values and  
configure meter settings. Once you install and register the plug-in with LonMaker, it opens instead of  
the default LonMaker browser when you browse the meter in LonMaker.  
To add devices to LonMaker, you need access to the device service pin when commissioning the  
device or your need the device Neuron ID recorded in an accessible location.  
Related topics  
Refer to http://www.echelon.com/products/tools/integration/lonmaker/ and the LonMaker  
documentation for more information on using LonMaker.  
Neuron ID.  
Installing and registering the LonMaker plug-in  
Before you install the plug-in:  
Download the plug-in and XIF file for your device from www.schneider-electric.com or contact your  
sales representative to obtain these files.  
Make sure Echelon LonMaker is closed.  
1. Navigate to the location where you saved the plug-in. Extract the files if they are in a .zip file.  
2. Double-click setup.exe. A welcome screen appears. Click Next.  
3. Select the installation folder where you want to install the plug-in. Click Browse if you want to  
select a different location. Click Next. A confirmation screen appears.  
4. Click Next to begin the installation.  
NOTE: If LonMaker is open, a message appears instructing you to close LonMaker and restart the  
plug-in installation.  
DOCA0005EN-04  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Communications via LonWorks  
iEM3100 / iEM3200 / iEM3300 series user manual  
A screen appears when the installation is complete. Click Close.  
5. Navigate to Start > Programs > Schneider Electric and select the registration entry for the plug-  
in you installed (for example, Schneider Electric iEM3275 Plugin Registration). The LNS  
Plugin Registration dialog box appears, indicating that registration is complete.  
Make sure that the plug-in appears in the list of registered plug-ins in LonMaker before you try to  
connect to a meter using the plug-in. If it does not appear, you may need to re-register the plug-in.  
Once the plug-in is installed and registered, add the meter to LonMaker. You can either read the  
template (.XIF) from the device during commissioning or select the EnergyMeter5A or  
EnergyMeter63A template when you add the device to LonMaker.  
Related topics  
Refer to the Echelon LonMaker documentation for information on registering the plug-in.  
Browsing the meter using the LonMaker plug-in  
In order to use the plug-in to view data and configure the meter:  
The plug-in must be installed and registered.  
The meter must be added to LonMaker and commissioned.  
1. Open LonMaker.  
2. Right-click the meter icon and select Browse. The meter plug-in appears.  
NOTE: If the meter-specific plug-in does not open, the plug-in may not be correctly registered or  
the meter may not be properly commissioned in LonMaker. Double-check the registration and  
meter commissioning. Refer to the Echelon LonMaker documentation for more information.  
LonMaker plug-in interface  
The plug-in has the following tabs:  
Tab name  
Description  
Meter Info  
This tab provides basic information about the meter (for example, model and serial  
number) and any active error codes.  
Energy Measure  
RMS Measure  
This tab provides total and partial energy values as well as energy per phase and  
energy by tariff information. You can also reset energy and input metering  
accumulations on this tab.  
This tab provides power, current, and voltage values as well as frequency and power  
factor information.  
72  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via LonWorks  
Tab name  
Description  
Meter Status  
This tab provides information on the settings and status of the digital input and alarms  
as well as existing power system settings.  
Meter Config  
Diagnostics  
This tab provides access to the meter configuration properties, allowing you to  
configure power system, digital input, alarm, Multi Tariff and time settings.  
NOTE: If you see a message that the configuration was unsuccessful, make sure: 1) the meter is  
properly commissioned in LonMaker and the plug-in is communicating with the meter, and 2)  
that Com. Protection is disabled on the meter.  
This tab provides LonMaker diagnostics information related to the meter.  
DOCA0005EN-04  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications via LonWorks  
iEM3100 / iEM3200 / iEM3300 series user manual  
74  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via M-Bus  
Chapter 7  
Communications via M-Bus  
What is in this chapter?  
This chapter contains the following sections:  
M-Bus communications overview  
M-Bus is a master / slave communications protocol where the master initiates transactions and the  
slave(s) respond with the requested information or action. Data is transferred using hexadecimal  
telegrams.  
Communications via M-Bus protocol is available on the iEM3135, iEM3235 and iEM3335.  
The information in this section is intended for users with an advanced understanding of M-Bus  
protocol, their communications network and their power system.  
Configuring basic communications settings  
Before communicating with the meter via M-Bus protocol, use the HMI to configure the following  
settings:  
Setting  
Possible values  
300  
600  
1200  
2400  
4800  
9600  
1–250  
Baud rate  
Primary address  
Key terms  
Term  
Definition  
The control or function field of the telegram. It provides information about the telegram, such as the  
direction of data flow (master to slave or slave to master), the status of the data flow and the  
function of the message.  
C-Field  
The control information field of the telegram. It defines the type and sequence of data to be  
transmitted.  
CI-Field  
Fixed data header  
DIF  
Contains device and manufacturer identification information.  
Data information field. The DIF contains information about the function of the data (for example,  
instantaneous versus maximum) and the data format (for example, 16-bit integer).  
Data information field extension. A DIFE contain additional information about the data, such as tariff  
and subunit.  
DIFE  
A device that issues commands and receives responses from slave devices. There can be only one  
master per serial network.  
Master  
Slave  
A device that provides information or performs actions in response to requests from the master.  
Value information field and value information field extension. The VIF and VIFE contain information  
about the value (for example, whether it is an energy or power value).  
VIF / VIFE  
The meter uses both primary VIFE (as detailed in the M-Bus protocol documentation) and  
manufacturer-specific VIFE.  
DOCA0005EN-04  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Communications via M-Bus  
iEM3100 / iEM3200 / iEM3300 series user manual  
Related topics  
See the M-Bus organization website at www.m-bus.com for more information on the M-bus  
protocol.  
telegram.  
M-Bus protocol support  
The meter supports the M-Bus protocol as follows:  
Mode 1 communications (least significant bit first).  
Telegram formats:  
— Single character  
— Short frame  
— Long frame  
Function codes (C-field bits 3-0):  
— SND_NKE: Initiates of communications between the master and slave.  
— SND_UD: The master sends user data to the slave.  
— REQ_UD2: The master requests Class 2 user data from the slave.  
— RSP_UD: The slave sends requested data to the master.  
Secondary addressing in accordance with the M-Bus standard.  
Broadcast telegrams.  
Related topics  
See the M-Bus organization website at www.m-bus.com for more information on the M-Bus  
protocol, including secondary addressing procedures.  
addressing (for example, identification number, manufacturer and medium).  
M-Bus protocol implementation  
M-Bus tool for viewing data and configuring the meter  
The M-Bus tool provides a graphical user interface where you can view meter data and configure  
meter settings. To obtain the tool, go to www.schneider-electric.com and search for your meter model  
then select Downloads or contact your local Schneider Electric representative.  
Communications LED indicator for M-Bus meters  
The communications LED indicates the status of the communications between the meter and the  
network as follows:  
LED state  
Description  
Communication with the meter has been established.  
NOTE: The LED flashes even if there is a communications error.  
There is no active communication.  
The LED is flashing  
The LED is off  
Related topics  
and using the M-Bus tool.  
76  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via M-Bus  
Variable data structure telegram information  
Fixed data header  
Byte 1-4  
Identification No.  
Byte 5-6  
Manufacturer  
Byte 7  
Version  
Byte 8  
Medium  
Byte 9  
Access No.  
Byte 10  
Status  
Byte 11-12  
Signature  
Serial number of the meter in an  
8-digit, BCD coded format  
Firmware version of the  
communications board  
4CA3 hex =  
Schneider Electric  
Counter of successful Indicates M-Bus  
02 hex (electricity)  
Not used  
access attempts  
application errors  
The serial number can also be  
found on the meter front panel.  
10 = version 1.0  
Data record header information  
Data formats used by the meter (DIF bits 3-0)  
NOTE: x in the hex value is determined by bits 7-4 of the DIF.  
Format  
bin  
hex  
No data  
0000  
0001  
0010  
0011  
0100  
0101  
0110  
0111  
1101  
x0  
x1  
x2  
x3  
x4  
x5  
x6  
x7  
xD  
8-bit integer  
16-bit integer  
24-bit integer  
32-bit integer  
32-bit real  
48-bit integer  
64-bit integer  
Variable length  
Data function types used by the meter (DIF bits 5-4)  
Function type  
bin  
Instantaneous  
Maximum  
00  
01  
Primary VIF used by the meter  
NOTE: E denotes the extension bit; x in the hex value is determined by bits 7-4 of the VIF.  
Primary VIF  
bin  
hex  
Description  
0
Energy  
Power  
E000 0011  
E000 1110  
x3  
Wh with a resolution of 10  
3
xE  
kW with a resolution of 10  
Date and time in data type F, as detailed in the M-Bus  
protocol documentation  
Time point  
E110 1101  
xD  
xA  
Data type C (unsigned integer), as detailed in the M-Bus  
protocol documentation  
Bus address  
Primary VIFE  
E111 1010  
1111 1101  
FD  
FF  
Indicates that the first VIFE is a primary VIF extension  
Indicates that the next VIFE is manufacturer specific  
Manufacturer-specific VIFE 1111 1111  
Primary VIFE codes used by the meter  
The primary VIFE codes in the table below are used by the meter when the VIF equals FD hex  
(1111 1101 bin).  
NOTE: E denotes the extension bit; x in the hex value is determined by bits 7-4 of the VIFE.  
Primary VIFE codes bin  
hex  
Additional information  
Manufacturer  
Model  
E000 1010  
xA  
xC  
x9  
E000 1100  
E100 1001  
E101 1100  
E001 1010  
E001 1011  
0
Voltage  
Volts with a resolution of 10  
0
Current  
xC  
xA  
xB  
Amps with a resolution of 10  
Digital output  
Digital input  
DOCA0005EN-04  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Communications via M-Bus  
iEM3100 / iEM3200 / iEM3300 series user manual  
Primary VIFE codes bin  
hex  
Additional information  
Cumulation counter  
Error flag  
E110 0001  
E001 0111  
x1  
x7  
Input metering accumulation  
Manufacturer-specific VIFE codes  
The manufacturer-specific VIFE codes in the table below are used by the meter when the VIF equals  
FF hex (1111 1111 bin).  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Description  
bin  
hex  
L1 value  
L2 value  
L3 value  
E000 0001  
E000 0010  
E000 0011  
E000 1001  
E000 1101  
E000 0000  
E000 0100  
E000 0101  
E000 0110  
E000 0111  
E000 1000  
E000 1010  
E000 1011  
E000 1100  
E000 1110  
E000 1111  
E001 0000  
E001 0001  
E010 0000  
E010 0001  
E010 0010  
E010 0011  
E010 0100  
E010 0101  
E010 0110  
E010 0111  
E010 1000  
E010 1001  
E010 1010  
E010 1011  
E010 1100  
01  
02  
03  
09  
0D  
00  
04  
05  
06  
07  
08  
0A  
0B  
0C  
0E  
0F  
10  
11  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
2A  
2B  
2C  
2D  
2E  
2F  
30  
32  
34  
35  
36  
37  
38  
39  
3A  
Export energy value  
Partial energy value  
Average current  
L-N Avg  
L1-L2  
L2-L3  
L3-L1  
L-L Avg  
Power Factor  
Frequency  
Energy reset date and time  
Input metering reset date and time  
Input metering accumulation  
Active tariff (Energy active rate)  
Tariff control mode  
Meter operation timer  
Number of phases  
Number of wires  
Power system configuration  
Nominal frequency  
Number of VTs  
VT primary  
VT secondary  
Number of CTs  
CT Primary  
CT Secondary  
VT connection type  
Energy pulse duration  
Digital output association with active energy pulsing E010 1101  
Pulse weight  
E010 1110  
E010 1111  
E011 0000  
E011 0010  
E011 0100  
E011 0101  
E011 0110  
E011 0111  
E011 1000  
E011 1001  
E011 1010  
Pulse constant  
Digital input association  
Digital input status  
Overload alarm setup  
Pickup setpoint  
Digital output association with overload alarm  
Activated status  
Acknowledgement  
Date and time of last alarm  
Value at last alarm  
78  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via M-Bus  
Telegram information for data records  
The following sections outline the telegram information used in data records. The tables contain the  
following information (if applicable):  
Data format in hex (for example, 16-bit integer)  
Primary VIF in hex  
Primary VIFE codes in bin and hex  
Manufacturer-specific VIFE codes in bin and hex  
Meter information  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Primary VIF Extension  
Data format  
Description  
bin  
hex  
Manufacturer  
0D  
0D  
E000 1010  
E000 1100  
0A  
0C  
18-bit ASCII = Schneider Electric  
Model  
Meter error codes:  
0 = Code 101: EEPROM error  
1 = Code 102: No calibration table  
2 = Code 201: Mismatch between frequency settings and frequency measurements  
3 = Code 202: Mismatch between wiring settings and wiring inputs  
4 = Code 203: Phase sequence reversed  
03  
E0001 0111 17  
5 = Code 204: Total active energy negative due to incorrect voltage or current  
connections  
6 = Code 205: Date and time are reset due to a power failure  
7 = Code 206: Pulse missing due to overspeed of energy pulse output  
8 = Code 207: Abnormal internal clock function  
9 = Internal data bus communications error  
Related topics  
Energy and energy by tariff measurements  
The energy and energy by tariff measurements listed below are preserved through power failures.  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Primary VIFE  
bin hex  
Manufacturer-specific VIFE  
bin hex  
Data format DIFE Primary VIF  
Description  
07  
07  
87  
87  
07  
87  
07  
07  
07  
40  
40  
40  
03  
83  
03  
83  
83  
83  
83  
83  
83  
Total active energy import  
E000 1001  
09  
Total active energy export  
Total reactive energy import  
Total reactive energy export  
Partial active energy import  
Partial reactive energy import  
Active energy import phase 1  
Active energy import phase 2  
Active energy import phase 3  
Active tariff  
E000 1001  
E000 1101  
E000 1101  
E000 0001  
E000 0010  
E000 0011  
09  
0D  
0D  
01  
02  
03  
0 = Multi Tariff feature is disabled  
1 = rate A (tariff 1) active  
03  
E001 0000  
10  
2 = rate B (tariff 2) active  
3 = rate C (tariff 3) active  
4 = rate D (tariff 4) active  
87  
87  
87  
10  
20  
30  
03  
03  
03  
Rate A (tariff 1) active energy import  
Rate B (tariff 2) active energy import  
Rate C (tariff 3) active energy import  
DOCA0005EN-04  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Communications via M-Bus  
iEM3100 / iEM3200 / iEM3300 series user manual  
Primary VIFE  
bin hex  
Manufacturer-specific VIFE  
bin hex  
Data format DIFE Primary VIF  
Description  
87  
07  
04  
04  
80 10  
03  
61  
Rate D (tariff 4) active energy import  
Input metering accumulation  
E110 0001  
ED  
ED  
E000 1100  
E000 1110  
0C  
0E  
Date and time of last partial energy reset  
Date and time of last input metering reset  
Instantaneous measurements  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Primary VIFE  
bin hex  
Manufacturer-specific VIFE  
Data format DIFE Primary VIF  
Description  
bin  
hex  
05  
05  
05  
05  
85  
85  
05  
05  
05  
05  
05  
05  
05  
05  
05  
05  
05  
05  
05  
05  
40  
80 40  
AE  
AE  
AE  
2E  
2E  
2E  
E000 0001  
E000 0010  
E000 0011  
01  
02  
03  
Active power Phase 1  
Active power Phase 2  
Active power Phase 3  
Total active power  
Total reactive power  
Total apparent power  
Voltage L1-N  
E100 1001  
E100 1001  
E100 1001  
E100 1001  
E100 1001  
E100 1001  
E100 1001  
E100 1001  
E101 1100  
E101 1100  
E101 1100  
E101 1100  
C9  
C9  
C9  
C9  
C9  
C9  
C9  
C9  
DC  
DC  
DC  
DC  
E000 0001  
E000 0010  
E000 0011  
E000 0100  
E000 0101  
E000 0110  
E000 0111  
E000 1000  
E000 0001  
E000 0010  
E000 0011  
E000 0000  
E000 1010  
E000 1011  
01  
02  
03  
04  
05  
06  
07  
08  
01  
02  
03  
00  
0A  
0B  
Voltage L2-N  
Voltage L3-N  
Average voltage line-to-neutral  
Voltage L1-L2  
Voltage L2-L3  
Voltage L3-L1  
Average voltage line-to-line  
Phase 1 current  
Phase 2 current  
Phase 3 current  
Average current  
Total power factor  
Frequency  
Meter status information  
Use the following information to read system and status information from the meter. See the section  
regarding telegram information for meter configuration for more information on writing to the meter.  
Date and time information  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Manufacturer-specific VIFE  
Description  
Data format Primary VIF  
bin  
hex  
04  
06  
6D  
Meter date and time (DD/MM/YYYY hh:mm:ss)  
E010 0000  
20  
Meter operation timer: the time in seconds since the device was last powered up  
80  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via M-Bus  
Power system configuration information  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Manufacturer-specific VIFE  
Data format  
Description  
bin  
hex  
Power system configuration:  
0 = 1PH2W L-N  
1 = 1PH2W L-L  
03  
E010 0011  
23  
2 = 1PH3W L-L with N  
3 = 3PH3W  
11 = 3PH4W  
13 = 1PH4 wire multi L with N  
Number of wires  
03  
03  
E010 0010  
E010 0001  
22  
21  
2, 3, 4  
Number of phases  
1, 3  
Number of CTs  
03  
03  
E010 1000  
E010 0101  
29  
25  
1, 2, 3  
NOTE: only applies to the iEM3235  
Number of VTs  
0-10  
NOTE: only applies to the iEM3235  
VT Primary  
05  
03  
03  
03  
E010 0110  
E010 0111  
E010 1001  
E010 1010  
26  
27  
29  
2A  
NOTE: only applies to the iEM3235  
VT Secondary  
NOTE: only applies to the iEM3235  
CT Primary  
NOTE: only applies to the iEM3235  
CT Secondary  
NOTE: only applies to the iEM3235  
VT connection type  
0 = Direct connection, no VTs  
1 = 3PH3W (2VTs)  
2 = 3PH4W (3VTs)  
Nominal frequency  
50, 60  
03  
03  
E010 1011  
E010 0100  
2B  
24  
Digital input and output status information  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Primary VIFE  
Manufacturer-specific VIFE  
bin hex  
Data format  
Description  
bin  
hex  
Digital input control mode:  
0 = Normal (Input Status)  
2 = Multi Tariff control  
3 = Input metering  
03  
E001 1011  
1B  
5 = All partial energy logs reset  
Pulse constant (pulses/unit)  
Digital input status:  
05  
02  
E010 1111  
E011 0010  
2F  
32  
0 = relay open  
1 = relay closed  
NOTE: This information only applies if the digital input control mode is set  
to Input Status.  
Digital input association with partial energy data reset  
0 = Digital input is not associated with the partial energy reset  
1 = Digital input is associated with the partial energy reset  
Energy pulse duration in milliseconds  
03  
03  
E011 0000  
E010 1100  
30  
2C  
NOTE: This information only applies if the digital output mode is set to  
energy pulsing.  
DOCA0005EN-04  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications via M-Bus  
iEM3100 / iEM3200 / iEM3300 series user manual  
Primary VIFE  
bin hex  
Manufacturer-specific VIFE  
Data format  
Description  
bin  
hex  
Pulse weight of the digital output  
05  
E010 1110  
2E  
NOTE: This information only applies if the digital output mode is set to  
energy pulsing.  
Digital output control mode  
2 = for Alarm  
03  
E001 1010  
1A  
3 = for Pulse (kWh)  
0xFFFF = Disabled  
Digital output association with energy pulsing:  
0 = Digital output disabled  
03  
02  
E010 1101  
E011 0110  
2D  
36  
1 = for Pulse (digital output is associated with active energy pulse output)  
Digital output association with overload alarm:  
0x0000 = digital output disabled  
0x0100 = for Alarm (digital output is associated with the overload alarm)  
Alarm status information  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Manufacturer-specific VIFE  
Data format Primary VIF  
Description  
bin  
hex  
Alarm status:  
02  
02  
E011 0111  
37  
38  
0x0000 = Alarm is inactive  
0x0100 = Alarm is active  
Acknowledgement status:  
E011 1000  
0x0000 = historic alarm is acknowledged by the user  
0x0100 = historic alarm is unacknowledged by the user  
Timestamp of last alarm (DD/MM/YYYY hh:mm:ss)  
Value at last alarm  
04  
05  
ED  
E011 1001  
E011 1010  
39  
3A  
Overload alarm configuration:  
02  
05  
E011 0100  
E011 0101  
34  
35  
0x0000 = disabled  
0x0100 = enabled  
The pickup setpoint in kW for the overload alarm  
Telegram information for meter configuration  
You can use the information provided in this section to write to the meter using a SND_UD function.  
NOTE: If Com. Protection is enabled, you may receive an error response when you try to configure  
the meter over communications.  
You can also configure the meter using the M-Bus tool available from www.schneider-electric.com.  
Supported VIFE codes for meter configuration  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
VIFE code  
Action  
Description  
bin  
hex  
E000 0000  
E000 0111  
00  
07  
Write and replace  
Clear  
Replaces the old value with the new value.  
Resets an accumulated value to 0 (zero).  
Related topics  
Com. Protection.  
M-Bus tool.  
82  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via M-Bus  
Date/time setup  
Data format Primary VIF  
Description  
Type F data type, as described in the M-Bus protocol documentation.  
Supports the date and time in the following format YYYY:MM:DD hh:mm:ss.  
04  
6D  
Power system setup  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Manufacturer-specific VIFE  
Range/options  
SND_UD  
code  
Data format  
Description  
bin  
hex  
Power system configuration:  
0 = 1PH2W L-N  
1 = 1PH2W L-L  
00  
02  
E010 0011  
23  
0, 1, 2, 3, 11, 13  
2 = 1PH3W L-L with N  
3 = 3PH3W  
11 = 3PH4W  
13 = 1PH4 wire multi L with N  
Nominal frequency  
00  
00  
00  
00  
00  
00  
02  
05  
02  
02  
02  
02  
E010 0100  
E010 0110  
E010 0111  
E010 1000  
E010 1001  
E010 1010  
24  
26  
27  
28  
29  
2A  
50, 60  
VT Secondary - 1000000.0  
VT Primary (iEM3235 only)  
VT Secondary (iEM3235 only)  
Number of CTs (iEM3235 only)  
CT Primary (iEM3235 only)  
CT Secondary (iEM3235 only)  
VT Connection Type (iEM3235 only)  
0 = direct connect  
100, 110, 115, 120  
1, 2, 3  
1-32767  
1, 5  
00  
02  
E010 1011  
2B  
0, 1, 2  
1= 3PH3W (2 VTs)  
2 = 3PH4W (3 VTs)  
Multi Tariff setup  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Manufacturer-specific VIFE  
Range/options  
SND_UD  
code  
Data format  
Description  
bin  
hex  
Set Multi Tariff control mode to Disabled or by  
Communication:  
0 = Disabled  
00  
00  
02  
E001 0001  
11  
10  
0,1  
1 = by Communication  
NOTE: To configure the Multi Tariff feature to be controlled  
by the digital input or device clock, use the HMI.  
Set the active tariff:  
1 = Rate A (tariff 1)  
2 = Rate B (tariff 2)  
3 = Rate C (tariff 3)  
4 = Rate D (tariff 4)  
02  
E001 0000  
1, 2, 3, 4  
NOTE: You can only set the tariff using this method if the  
Tariff Mode is set to by Communication.  
DOCA0005EN-04  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications via M-Bus  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications setup  
SND_UD code Data format Primary VIF  
Range/options  
Description  
00  
01  
7A  
0-250  
Primary address  
To change the baud rate via communications, send a telegram to the meter with the appropriate value  
in the CI-field:  
Baud rate Hex value for CI-field  
300  
B8  
B9  
BA  
BB  
BC  
BD  
600  
1200  
2400  
4800  
9600  
Digital input setup  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Manufacturer-specific VIFE  
SND_UD  
code  
Data format  
Range/options  
Description  
bin  
hex  
Digital input control mode  
0 = Normal (Input Status)  
3 = Input metering  
00  
00  
02  
05  
E001 1011  
1B  
2F  
0, 3, 5  
5 = Partial energy reset  
Pulse constant (pulses/unit; applicable when the digital  
input is used for input metering)  
E010 1111  
1-10000  
Digital output setup  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Manufacturer-specific VIFE  
Range/options  
SND_UD  
code  
Data format  
Description  
bin  
hex  
Digital output control mode  
2 = Alarm  
00  
02  
E001 1010  
1A  
2, 3, 0xFFFF  
3 = Energy (energy pulsing)  
0xFFFF = Disable  
iEM3135 / iEM3335: 1, 10, 20, 100, Pulse constant  
200, 1000  
00  
00  
05  
02  
E010 1110  
E010 1100  
2E  
2C  
NOTE: This information only applies if the digital output  
iEM3235: 0.01, 0.1, 1, 10, 100, 500 control mode is set to for Pulse.  
Pulse width in ms  
50, 100, 200, 300  
NOTE: This information only applies if the digital output  
control mode is set to for Pulse.  
Overload alarm setup and acknowledgment  
Use the information in the table below to configure the overload alarm.  
NOTE: E denotes the extension bit; the hex value assumes E = 0.  
Manufacturer-specific VIFE  
SND_UD  
Data format  
Range/options  
Description  
code  
bin  
hex  
The pickup setpoint in kW for the  
overload alarm  
00  
00  
05  
02  
E011 0101  
35  
34  
0 - 9999999  
Overload alarm setup:  
0 = Disable  
E011 0100  
0,1  
1 = Enable  
84  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via M-Bus  
Use the information in the table below to acknowledge the overload alarm.  
NOTE: E denotes the extension bit; the hex value assumes E = 1.  
Manufacturer-specific VIFE  
SND_UD  
Data format  
Range/options  
Description  
code  
1
bin  
hex  
07  
00  
E011 1000  
B8  
Acknowledge alarm  
Resets  
NOTE: E denotes the extension bit; the hex value assumes E = 1.  
Primary VIFE  
bin hex  
Manufacturer-specific VIFE  
SND_UD  
code  
Data format  
Description  
bin  
hex  
07  
07  
00  
00  
E000 1101  
8D  
Resets partial energy accumulation to 0.  
Resets input accumulation to 0.  
E110 0001 E1  
M-Bus tool for data display and meter configuration  
The M-Bus tool provides a graphical user interface where you can view meter data and configure  
meter settings. To obtain the tool, go to www.schneider-electric.com and search for your meter model  
then select Downloads or contact your local Schneider Electric representative.  
If you access a different meter without closing and re-opening the M-Bus tool, the fields displayed in  
the tool may not match the device you are accessing. The M-Bus tool may indicate a setting was  
changed without the setting on the meter actually changing.  
NOTICE  
INACCURATE DEVICE SETTINGS  
Do not rely on the configuration information displayed in the M-Bus tool to determine if the  
associated device is correctly configured.  
Failure to follow these instructions can result in inaccurate device settings and data results.  
Installing the M-Bus tool  
Before you install the tool, you need to download it from www.schneider-electric.com or obtain it from  
your sales representative.  
1. Navigate to the location where you saved the installation files.  
2. Double-click setup.exe. A welcome screen appears. Click Next.  
3. Confirm the installation location for the tool. Click Browse if you want to select a different location.  
Click Next. A confirmation screen appears.  
4. Click Next to begin the installation. A screen appears when the installation is complete.  
5. Click Close.  
Accessing the meter using the tool  
Before you access the meter using the M-Bus tool, make sure that you:  
connect the meter to a level converter (for a direct serial connection) or a level converter and  
gateway (for connection via a serial or Ethernet network).  
set the address of the device to a value other than 0 (zero) using the HMI.  
install the M-Bus tool on your computer.  
1. Select Start > Programs > Schneider Electric > Mbus config tool (or navigate to the location  
where you installed the program) and click SE_iEM3135_3235_3335 Mbus Tool to open the tool.  
The login screen appears.  
DOCA0005EN-04  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Communications via M-Bus  
iEM3100 / iEM3200 / iEM3300 series user manual  
2. Select the port on your computer that you are using to connect to the meter and select the baud  
rate that matches the meter’s configuration.  
3. Click Test Com to open the communications port.  
4. Type the device address in the Address field.  
5. Select the communications mode that you want the tool to start in:  
Monitor(Automatic): The tool automatically sends read requests to and receives data from  
the meter. You can set the interval at which these read requests are sent.  
Monitor(Manual): You must manually send a read request to get data from the meter.  
Config: The tool opens in configuration mode.  
You can change the mode from within the tool, if needed.  
6. Click OK to start the M-Bus tool and access the meter.  
Viewing meter data using the M-Bus tool  
You can use two modes to view data from the device:  
Automatic mode: Select the update interval from the Interval dropdown list.  
Manual mode: Press Req_UD2 to request data from the meter.  
To switch modes, select Setup > Monitor then select the mode you want to use.  
The tool has the following tabs for viewing meter information:  
Tab name  
Description  
This tab provides basic information about the meter (for example, model and serial number) and any  
active error codes. Click Clear to remove the error codes from the display.  
Meter Info  
This does not resolve the errors.  
This tab provides total and partial energy, energy per phase and energy by tariff information, as well as  
input accumulations and the date and time of the last input metering and partial energy resets.  
Energy Measure  
86  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via M-Bus  
Tab name  
Description  
RMS Measure  
This tab provides power, current, and voltage values as well as frequency and power factor information.  
This tab provides information on the settings and status of the digital input, digital outputs and alarms as  
well as existing power system settings.  
Meter Status  
Configuring the meter using the M-Bus tool  
1. Select Setup > Config to switch to configuration mode.  
2. Set the values that you want to change then click Send for that value or section. For example, to  
change the nominal frequency, select a different value from the list then click Send in Set Wiring.  
Some values may be unavailable based on existing settings.  
NOTE: If Com. Protection is enabled, you may receive a message that the configuration failed.  
Use the HMI to either: 1) configure the meter, or 2) disable Com. Protection then configure the  
meter using the tool.  
The configuration screen has the following sections:  
Section  
Description  
Configure power system settings (for example, power system configuration and nominal  
frequency).  
Set Wiring  
Set Digital Input  
Set the digital input mode and pulse constant.  
Set Digital Output  
Enable / disable the digital output and set the control mode, pulse weight and duration.  
Disable the Multi Tariff feature or set the control mode to by Communication and set the active tariff  
if the control mode is set to by Communication.  
Set Multi Tariff  
Set Power Alarm  
Reset  
Enable / disable to the overload alarm, enter the setpoint, and acknowledge alarms.  
Reset partial energy and input metering accumulations.  
Set the date and time or send a time synchronization signal to set the meter to the computer time.  
Set the baud rate.  
Set Date Time  
Set Baudrate  
Set Address  
Set the meter address.  
DOCA0005EN-04  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications via M-Bus  
iEM3100 / iEM3200 / iEM3300 series user manual  
88  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via BACnet  
Chapter 8  
Communications via BACnet  
What is in this chapter?  
This chapter contains the following sections:  
BACnet communications overview  
Communications via BACnet MS/TP protocol is available on the iEM3165, iEM3265 and iEM3365.  
The information in this section is intended for users with an advanced understanding of BACnet  
protocol, their communications network and their power system.  
Key terms  
Term  
Definition  
APDU  
Application protocol data unit, that data portion of a BACnet message.  
A message for which the device expects an answer.  
Confirmed message  
COV  
Change of value, sets the amount by which a value has to change in order for the meter to send a  
subscription notification.  
A BACnet device is a unit that is designed to understand and use BACnet protocol (for example, a  
BACnet-enabled meter or software program). It contains information about the device and device  
data in objects and object properties. Your meter is a BACnet device.  
Device  
MS/TP  
Master-slave/token-passing over RS-485.  
Represents the device and device data. Each object has a type (for example, analog input or binary  
input) and has a number of properties.  
Object  
Present value  
Property  
Service  
The current value of an object.  
The smallest piece of information in BACnet communications, it consists of a name, data type and  
value.  
Messages from one BACnet device to another.  
Creates a relationship between the server and the meter, so that when the present value property  
Subscription  
of an object changes by more than the configured COV threshold (COV_Increment), a notification is  
sent.  
Subscription notification  
Unconfirmed message  
The message the meter sends to indicate a COV event has occurred.  
A message for which the device does not expect an answer.  
Related topics  
See www.bacnet.org for more information on the BACnet protocol.  
BACnet protocol support  
Go to www.schneider-electric.com and search for your meter model to access the PICS (Protocol  
Implementation Conformance Statement) for your meter.  
The meter supports the BACnet protocol as follows:  
BACnet component  
Description  
Protocol version  
1
Protocol revision  
6
Standardized device profile (Annex L)  
BACnet Application Specific Controller (B-ASC)  
DOCA0005EN-04  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Communications via BACnet  
iEM3100 / iEM3200 / iEM3300 series user manual  
BACnet component  
Description  
DS-RP-B (Data Sharing - Read Property - B)  
DS-RPM-B (Data Sharing - Read Property Multiple - B)  
DS-WP-B (Data Sharing - Write Property - B)  
BACNet Interoperability Building Blocks (Annex K) DS-COV-B (Data Sharing - COV - B)  
DM-DDB-B (Device Management - Dynamic Device Binding - B)  
DM-DOB-B (Device Management - Dynamic Object Binding - B)  
DM-DCC-B (Device Management - Device Communication Control - B)  
MS/TP master (clause 9)  
Data link layer options  
Character set  
Baud rates 9600, 19200, 38400, 57600, 76800  
ANSI X3.4  
subscribeCOV  
readProperty  
readPropertyMultiple  
writeProperty  
deviceCommunicationControl  
Supported services  
who-HAS  
who-Is  
I-Am  
I-Have  
Confirmed COV notification  
Unconfirmed COV notification  
The meter does not support segmentation  
The meter does not support static device address binding  
None  
Segmentation  
Static device address binding  
Networking options  
The following standard object types are supported:  
Object type  
Optional properties supported Writable properties supported Proprietary properties  
Max_Master  
Max_Info_Frames  
Description  
Location  
Object_Name  
Max_Master  
Max_Info_Frames  
Description  
ID_800  
ID_801  
ID_802  
Device Object  
Local_Date  
Local_Time  
Active_COV_Subscriptions  
Profile Name  
COV_Increment  
Location  
APDU_Timeout  
Number_Of_APDU_Retries  
Analog Input Object  
Analog Value Object  
Binary Input Object  
COV_Increment  
Present_Value  
Related topics  
BACnet communications implementation  
Configuring basic communication parameters  
Before communicating with the meter via BACnet protocol, use the front panel to configure the  
following settings:  
Setting  
Possible values  
9600  
19200  
Baud rate  
38400  
57600  
76800  
Mac Address  
Device ID  
1 - 127  
0 - 4194303  
90  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via BACnet  
Make sure that the Mac Address is unique on the serial loop and the Device ID is unique in your  
BACnet network.  
Communications LED indicator for BACnet meters  
The LED indicates the status of the meter’s communications with the network.  
LED state  
Description  
The LED is off  
Communication is not active.  
Communication is active.  
The LED is flashing  
NOTE: The LED flashes even if there is a communications error.  
Change of Value (COV) subscriptions  
The meter supports up to 14 COV subscriptions. You can add COV subscriptions to Analog Input and  
Binary Input objects using your BACnet-compatible software.  
Related topics  
panel.  
BACnet object and property information  
The following sections outline the supported objects and properties available on the meter.  
Device object  
The following table outlines the properties of the Device object, whether a property is read-only or  
read-write, and if the value of the property is stored in the meter’s non-volatile onboard memory.  
Device object property  
R/W Stored Possible values  
Description  
The unique device ID number for the meter, in the format of <device, #>.  
NOTE: You must use the front panel to configure the device ID number.  
A configurable name for the meter.  
Object_Identifier  
R
configurable  
configurable  
Object_Name  
R/W  
The meter ships from the factory with a name of <model name>_<serial number>  
(for example, iEM3265_0000000000).  
Object_Type  
R
R
R
R
Device  
The object type for the meter  
System_Status  
Vendor_Name  
Vendor_Identifier  
Operational  
Schneider Electric  
10  
This value of this property is always Operational.  
Meter manufacturer  
The BACnet vendor identifier for Schneider Electric  
iEM3165, iEM3265,  
iEM3365  
Device model (for example, iEM3265) and serial number in the format <model  
name>_<serial number> (for example, iEM3265_0000000000).  
Model_Name  
R
Firmware_Revision  
Application_Software_Version  
Description  
R
varies  
BACnet firmware version, stored in an x.x.x format (for example, 1.7.2).  
Meter firmware version, stored in an x.x.xxx format (for example, 1.0.305).  
Optional description of the meter, limited to 64 characters.  
Optional description of the meter’s location, limited to 64 characters.  
BACnet protocol version (for example, version 1)  
R
varies  
R/W  
R/W  
R
configurable  
configurable  
varies  
Location  
Protocol_Version  
Protocol_Revision  
R
varies  
BACnet protocol revision (for example, revision 6)  
0000 0100 0000 1011 The BACnet services supported by the meter: subscribeCOV, readProperty,  
0100 0000 0000 0000 readPropertyMultiple, writeProperty, deviceCommunicationControl, who-HAS,  
Protocol_Services_Supported  
R
R
0110 0000  
who-Is  
1011 0000 1000 0000 The BACnet object types supported by the meter: analog input, analog value,  
0000 0000 0000 0000 binary input, device  
Protocol_Object_Types_Supported  
List of objects in the meter:  
Object_list  
R
varies  
iEM3165 / iEM3365: DE1, AI0-AI48, AV0, BI0-BI6  
iEM3265: DE1, AI0-AI55, AV0, BI0-BI6  
The maximum packet size (or application protocol data unit) that the meter can  
accept, in bytes  
Max_APDU_Length_Accepted  
Segmentation_Supported  
R
R
480  
0x03  
The meter does not support segmentation.  
Date  
Local_Date  
R
configurable  
NOTE: You must use the front panel to set the meter’s date.  
DOCA0005EN-04  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Communications via BACnet  
iEM3100 / iEM3200 / iEM3300 series user manual  
Device object property  
R/W Stored Possible values  
Description  
Time  
Local_Time  
R
configurable  
NOTE: You must use the front panel to set the meter’s time.  
The amount of time (in milliseconds) before the meter tries to resend a confirmed  
message that has not been answered.  
APDU_Timeout  
R/W  
R/W  
R/W  
R/W  
R
1000 - 30000  
1 - 10  
The number of times the meter tries to resend an unanswered confirmed  
request.  
Number_Of_APDU_Retries  
Max_Master  
The highest master address the meter will try to discover when the next node is  
unknown.  
1 - 127  
1 - 14  
Maximum number of messages the meter can send before it must pass the  
token.  
Max_Info_Frames  
Device_Address_Binding  
Device address binding table is always blank because the meter does not initiate  
the who-Is service.  
A number that increments when the object database on the meter changes (for  
example, when an object is created or deleted or the ID of an object changes).  
Database_Revision  
Active_COV_Subscriptions  
Profile_Name  
R
R
R
varies  
varies  
varies  
List of COV subscriptions currently active on the meter.  
Device identifier, used on these meters to record the meter manufacturer, the  
meter family and the specific meter model (for example, 10_iEM3000_iEM3265).  
ID 800  
ID 801  
ID 802  
R
R
R
varies  
varies  
varies  
Date and time of last energy reset  
Date and time of last input metering accumulation reset  
Date and time of the last alarm (DD/MM/YYYY hh:mm:ss)  
Related topics  
panel.  
Analog Input objects  
The following tables list the Analog Input (AI) objects along with the units and default COV value for  
each AI object (if applicable).  
NOTE: The Value Type for all AI objects is Real.  
Energy and energy by tariff measurements  
The energy and energy by tariff measurements listed below are preserved through power failures.  
Object ID Units Default COV Object name / description  
27  
Wh  
Wh  
Wh  
Wh  
Wh  
Wh  
Wh  
Wh  
Wh  
100  
100  
100  
100  
100  
100  
100  
100  
100  
AI27 - Total active energy import  
AI28 - Total active energy export  
AI29 - Total reactive energy import  
AI30 - Total reactive energy export  
AI31 - Partial active energy import  
AI32 - Partial reactive energy import  
AI33 - Active energy import phase 1  
AI34 - Active energy import phase 2  
AI35 - Active energy import phase 3  
AI36 - Accumulation  
28  
29  
30  
31  
32  
33  
34  
35  
36  
10  
Input metering accumulation  
AI37 - Tariff Energy Active Rate  
Denotes the active tariff:  
0 = Multi Tariff feature is disabled  
1 = rate A (tariff 1) active  
37  
1
2 = rate B (tariff 2) active  
3 = rate C (tariff 3) active  
4 = rate D (tariff 4) active  
38  
39  
40  
41  
Wh  
Wh  
Wh  
Wh  
100  
100  
100  
100  
AI38 - Rate A (Tariff 1) active energy import  
AI39 - Rate B (Tariff 2) active energy import  
AI40 - Rate C (Tariff 3) active energy import  
AI41 - Rate D (Tariff 4) active energy import  
92  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via BACnet  
Instantaneous (RMS) measurements  
Object ID Units Default COV Object name / description  
7
A
50  
50  
50  
50  
10  
10  
10  
10  
10  
10  
10  
10  
10  
10  
10  
10  
AI07 - Current Phase 1  
AI08 - Current Phase 2  
AI09 - Current Phase 3  
AI10 - Current Average  
AI11 - Voltage L1-L2  
8
A
9
A
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
A
V
V
AI12 - Voltage L2-L3  
V
AI13 - Voltage L3-L1  
V
AI14 - Voltage Average L-L  
AI15 - Voltage L1-N  
V
V
AI16 - Voltage L2-N  
V
AI17 - Voltage L3-N  
V
AI18 - Voltage Average L-N  
AI19 - Active Power Phase 1  
AI20 - Active Power Phase 2  
AI21 - Active Power Phase 3  
AI22 - Active Power Total  
AI23 - Reactive Power Total  
AI24 - Apparent Power Total  
AI25 - Power Factor Total  
AI26 - Frequency  
kW  
kW  
kW  
kW  
kVAR 10  
kVA  
10  
0.2  
10  
Hz  
Meter information  
The following AI objects display information about the meter and its configuration.  
NOTE: You can access the meter’s configuration information over BACnet communications.  
However, you must use the front panel to configure the meter’s settings.  
Object ID Units  
Default COV Object name / description  
AI44 - Meter operation time  
10  
44  
45  
46  
Seconds  
The time in seconds since the meter was last powered up  
AI45 - Number of phases  
1, 3  
1
1
AI46 - Number of wires  
2, 3, 4  
AI47 - Power system type  
0 = 1PH2W L-N  
1 = 1PH2W L-L  
47  
1
2 = 1PH3W L-L with N  
3 = 3PH3W  
11 = 3PH4W  
13 = 1PH4 wire multi L-N  
AI48 - Nominal frequency  
50, 60  
48  
49  
Hz  
1
1
AI49 - Number of VTs  
0 - 10  
NOTE: only applies to the iEM3265  
AI50 - VT Primary  
50  
51  
V
V
1
1
NOTE: only applies to the iEM3265  
AI51 - VT Secondary  
NOTE: only applies to the iEM3265  
AI52 - Number of CTs  
1, 2, 3  
52  
53  
A
1
1
NOTE: only applies to the iEM3265  
AI53 - CT Primary  
NOTE: only applies to the iEM3265  
DOCA0005EN-04  
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications via BACnet  
iEM3100 / iEM3200 / iEM3300 series user manual  
Object ID Units  
Default COV Object name / description  
AI54 - CT Secondary  
54  
A
1
NOTE: only applies to the iEM3265  
AI55 - VT connection type  
0 = Direct connection, not VTs  
1 = 3PH3W (2VTs)  
55  
1
2 = 3PH4W (3VTs)  
Communications settings information  
The following AI objects display information about the meter’s communications settings.  
NOTE: You can access the meter’s communications configuration information over BACnet  
communications. However, you must use the front panel to configure the meter’s settings.  
Object ID Units  
Default COV Object name / description  
00  
01  
1
1
AI00 - BACnet MAC Address  
AI01 - BACnet Baud Rate  
Digital input and output setting information  
The following AI objects display information about the meter’s I/O settings.  
NOTE: You can access the meter’s I/O configuration information over BACnet communications.  
However, you must use the front panel to configure the meter’s settings.  
Object ID Units  
Default COV Object name / description  
AI02 - Pulse Duration  
The energy pulse duration (or pulse width), in milliseconds, of the digital  
output.  
02  
ms  
1
NOTE: This information only applies if the digital output mode is set to  
energy pulsing.  
AI03 - Pulse Weight  
The pulses/unit setting of the digital input when it is configured for input  
metering.  
03  
04  
1
1
NOTE: This information only applies if the digital input mode is set to  
Input Metering.  
AI04 - Pulse Constant  
The pulses/kWh setting of the digital output.  
NOTE: This information only applies if the digital output mode is set to  
energy pulsing.  
AI05 - Digital Input Mode  
0 = Normal (input status)  
2 = Multi Tariff control  
3 = Input metering  
05  
06  
1
1
5 = All partial energy logs reset  
AI06 - Digital Output Mode  
2 = Alarm  
3 = Energy  
0xFFFF (65535 dec) = Disabled  
AI42 - Pickup Setpoint  
Active power alarm pickup setpoint in kW  
AI43 - Last Alarm Value  
42  
43  
kW  
kW  
10  
10  
Related topics  
panel.  
and alarm.  
94  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Communications via BACnet  
Analog Value object  
There is one Analog Value (AV) object available on the meter, named AV00 - Command. The  
available commands are listed in the following table. Enter the number in the Present_Value column  
in the Present_Value property of the AV object to write the associated command to the meter.  
Command  
Present_Value entry Object name / description  
Acknowledge an overload alarm.  
The alarm indicator disappears from the front panel display after you  
acknowledge the alarm; however, this does not address the state that  
caused the alarm.  
Acknowledge Overload Alarm 20001.00  
Reset partial energy accumulation to 0.  
Reset Partial Energy Counter 2020.00  
Reset Input Metering Counter 2023.00  
Partial Active / Reactive Energy, Energy by Tariff and Phase Energy  
registers are reset.  
Resets input metering accumulation to 0.  
Binary Input objects  
The following table lists the Binary Input (BI) objects available on the meter.  
NOTE: The Value Type for all BI objects is Boolean.  
Object ID Object name / description  
BI00 - Digital Output Enable  
Indicates whether or not the digital output functions as an energy pulse output:  
0
0 = Digital output disabled  
1 = Digital output is associated with active energy pulse output  
BI01 - Digital Input Association Enable  
Indicates whether or not the digital input is associated with input metering:  
1
0 = Digital input is not associated with input metering.  
1 = Digital input is associated with input metering.  
BI02 - Digital Input Status  
0 = relay open  
2
1 = relay closed  
NOTE: This information only applies if the digital input is set to Input Status.  
BI03 - Alarm Enable  
Indicates whether the overload alarm is enabled or disabled:  
3
0 = disabled  
1 = enabled  
BI04 - Digital Output Association Enable  
Indicates if the digital output is configured for alarming:  
4
0 = digital output disabled  
1 = for Alarm (digital output is associated with the overload alarm)  
BI05 - Alarm Status  
5
6
0 = Alarm is inactive  
1 = Alarm is active  
BI06 - Unacknowledged status  
0 = historic alarm is acknowledged  
1 = historic alarm is unacknowledged  
DOCA0005EN-04  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Communications via BACnet  
iEM3100 / iEM3200 / iEM3300 series user manual  
96  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Specifications  
Chapter 9  
Specifications  
What is in this chapter?  
This chapter contains the following sections:  
Electrical characteristics  
Power system inputs: iEM31•• meters  
Characteristic  
Value  
Wye: 100 - 277 V L-N, 173 - 480 V L-L ±20%  
Measured voltage  
Delta: 173 - 480 V L-L ±20%  
63 A  
Maximum current  
Measured current  
Overload  
0.5 A to 63 A  
332 V L-N or 575 V L-L  
3 MΩ  
Voltage impedance  
Current impedance  
Frequency  
< 0.3 mΩ  
50 / 60 Hz ±10%  
III  
Measurement category  
Minimum wire temperature rating required  
Burden  
90 °C (194 °F)  
< 10 VA at 63 A  
2
Wire  
16 mm / 6 AWG  
Wire strip length  
Torque  
11 mm / 0.43 in  
1.8 Nm / 15.9 in•lb  
Power system inputs: iEM33•• meters  
Characteristic  
Value  
Wye: 100 - 277 V L-N, 173 - 480 V L-L ±20%  
Measured voltage  
Delta: 173 - 480 V L-L ±20%  
125 A  
Maximum current  
Measured current  
Overload  
1 A to 125 A  
332 V L-N or 575 V L-L  
6 MΩ  
Voltage impedance  
Current impedance  
Frequency  
< 0.2 mΩ  
50 / 60 Hz ±10%  
III  
Measurement category  
Minimum wire temperature rating required  
Burden  
105 °C (221 °F)  
< 10 VA at 125 A  
2
Wire  
50 mm / 1 AWG  
Wire strip length  
Torque  
13 mm / 0.5 in  
3.5 Nm / 30.9 in•lb  
DOCA0005EN-04  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
iEM3100 / iEM3200 / iEM3300 series user manual  
Power system inputs: iEM32•• meters  
Characteristic  
Value  
Wye: 100 - 277 V L-N, 173 - 480 V L-L ±20%  
Measured voltage  
Delta: 173 - 480 V L-L ±20%  
332 V L-N or 575 V L-L  
3 MΩ  
Overload  
Impedance  
Frequency  
50 / 60 Hz ±10%  
III  
Measurement category  
Voltage inputs  
Minimum wire temperature rating required  
90 °C (194 °F)  
< 10 VA  
Maximum device consumption  
2
Wire  
2.5 mm / 14 AWG  
Wire strip length  
8 mm / 0.31 in  
Torque  
0.5 Nm / 4.4 in•lb  
1 A or 5 A  
Nominal current  
Measured current  
20 mA to 6 A  
Withstand  
10 A continuous, 20 A at 10 sec/hr  
90 °C (194 °F)  
Minimum wire temperature rating required  
Impedance  
Frequency  
Burden  
< 1 mΩ  
Current inputs  
50 / 60 Hz ±10%  
< 0.036 VA at 6 A  
2
Wire  
6 mm / 10 AWG  
Wire strip length  
Torque  
8 mm / 0.31 in  
0.8 Nm / 7.0 in•lb  
Inputs and outputs  
Characteristic  
Value  
Meters  
Number  
Type  
1
Form A  
5 – 40 V DC  
50 mA  
Load voltage  
Maximum load current  
iEM3135 / iEM3155 / iEM3165 /  
iEM3235/ iEM3255 / iEM3265 /  
iEM3335 / iEM3355 / iEM3365  
Programmable digital  
output  
Output resistance  
Isolation  
0.1 – 50 Ω  
3.75 kV rms  
2
Wire  
1.5 mm / 16 AWG  
6 mm / 0.23 in  
0.5 Nm / 4.4 in•lb  
1
Wire strip length  
Torque  
Number  
Type  
S0 form (IEC 62053-31 compatible)  
Configurable  
Pulses / kWh  
Voltage  
5 – 30 V DC  
Current  
1 – 15 mA  
Pulse output  
iEM3110 / iEM3210 / iEM3310  
Configurable  
Pulse width  
Minimum width is 50 ms  
3.75 kV rms  
Isolation  
Wire  
2
2.5 mm / 14 AWG  
Wire strip length  
Torque  
7 mm / 0.28 in  
0.5 Nm / 4.4 in•lb  
98  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Specifications  
Characteristic  
Value  
Meters  
2
1
iEM3115 / iEM3215  
iEM3135 / iEM3155 / iEM3165 /  
iEM3175 / iEM3235 / iEM3255 /  
iEM3265 / iEM3275 / iEM3335 /  
iEM3355 / iEM3365 / iEM3375  
Number  
Type  
Type 1 (IEC 61131-2)  
40 V DC  
Voltage  
Current  
Maximum input  
4 mA  
Programmable digital  
input  
Voltage OFF  
Voltage ON  
Nominal voltage  
Isolation  
0 - 5 V DC  
11 - 40 V DC  
24 V DC  
iEM3115 / iEM3135 / iEM3155 /  
iEM3165 / iEM3175 / iEM3215 /  
iEM3235 / iEM3255 / iEM3265 /  
iEM3275 / iEM3335 / iEM3355 /  
iEM3365 / iEM3375  
3.75 kV rms  
2
Wire  
1.5 mm / 16 AWG  
Wire strip length  
Torque  
6 mm / 0.23 in  
0.5 Nm / 4.4 in•lb  
Mechanical characteristics  
Characteristic  
Value  
Meters  
IP40  
IP20  
Front panel  
IP degree of protection  
Impact rating  
iEM31•• / iEM32•• / iEM33••  
Meter body  
IK08  
iEM31•• / iEM32•• / iEM33••  
iEM32••  
In kWh or MWh up to 99999999 MWh  
In kWh: 8 + 1 digits up to 99999999.9  
500 flashes / kWh  
Active energy display range  
iEM31•• / iEM33••  
iEM31••  
1
Energy pulsing LED (yellow)  
5000 flashes / kWh without consideration of transformer ratios  
200 flashes / kWh  
iEM32••  
iEM33••  
1
The pulses / kWh of the energy pulsing LED cannot be changed.  
Environmental characteristics  
Characteristic  
Value  
Meters  
Operating temperature  
-25 °C (-13 °F) to +55 °C (131 °F) (K55)  
-40 °C (-40 °F) to +85 °C (185 °F)  
2
Storage temperature  
Pollution degree  
5% – 95% RH non-condensing  
Maximum dewpoint 50 °C (122 °F)  
For indoor use only  
iEM31•• / iEM32•• / iEM33••  
Relative humidity  
Location  
Altitude  
Not suitable for wet locations  
< 2000 m (6561 ft) above sea level  
Measurement accuracy  
Characteristic  
Value  
Meters  
Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD):  
=63 A, I =10 A, and I =0.04 A  
iEM31••  
iEM31••  
I
max  
b
st  
Active energy  
Class B conforming to EN 50470-3: I  
=63 A, l =10 A, I =0.5 A, and  
ref min  
max  
63 A  
I =0.04 A  
st  
Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD):  
=63 A, I =10 A, and I =0.05 A  
Reactive energy  
Active energy  
iEM3135 / iEM3155 / iEM3165 / iEM3175  
I
max  
b
st  
Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD):  
=125 A, I =20 A, and I =0.08 A  
iEM33••  
I
max  
b
st  
Class B conforming to EN 50470-3: I  
=125 A, l =20 A, I =1 A, and  
ref min  
max  
125 A  
iEM33••  
I =0.08 A  
st  
Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD):  
=125 A, I =20 A, and I =0.1 A  
Reactive energy  
iEM3335 / iEM3355 / iEM3365 / iEM3375  
I
max  
b
st  
DOCA0005EN-04  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Specifications  
iEM3100 / iEM3200 / iEM3300 series user manual  
Characteristic  
Value  
Meters  
Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD):  
=1.2 A, l =1 A, and I =0.002 A  
iEM3200 / iEM3210 / iEM3215  
I
max  
n
st  
Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx):  
=1.2 A, l =1 A, and I =0.002 A  
iEM3235 / iEM3250 / iEM3255 / iEM3265 /  
iEM3275  
Active energy  
Reactive energy  
Active energy  
Reactive energy  
I
max  
n
st  
for x/1A current input  
Class B conforming to EN 50470-3: I  
=1.2 A, l =1 A, I =0.01 A, and  
min  
max  
n
iEM32••  
I =0.002 A  
st  
Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx):  
=1.2 A, l =1 A, and I =0.003 A  
iEM3235 / iEM3255 / iEM3265 / iEM3275  
iEM32••  
I
max  
n
st  
Class 0.5S conforming to IEC 62053-22 and IEC 61557-12 (PMD SD):  
=6 A, l =5 A, and I =0.005 A  
I
max  
n
st  
Class 0.5S conforming to IEC 62053-22 and IEC 61557-12 (PMD Sx):  
=6 A, l =5 A, and I =0.005 A  
iEM3235 / iEM3250 / iEM3255 / iEM3265 /  
iEM3275  
I
max  
n
st  
for x/5A current input  
Class C conforming to EN 50470-3: I  
=6 A, l =5 A, I =0.05 A, and  
min  
max  
n
iEM32••  
I =0.005 A  
st  
Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx):  
=6 A, l =5 A, and I =0.015 A  
iEM3235 / iEM3255 / iEM3265 / iEM3275  
I
max  
n
st  
MID  
Characteristic  
Value  
Meters  
Electromagnetic environmental class  
Mechanical environmental class  
E2  
iEM3110 / iEM3115 / iEM3135 / iEM3155 / iEM3165 / iEM3175 /  
iEM3210 / iEM3215 / iEM3235 / iEM3255 / iEM3265 / iEM3275 /  
iEM3310 / iEM3335 / iEM3355 / iEM3365 / iEM3375  
M1  
Complies with the European Measuring Instruments Directive (MID) 2004/22/CE when installed in a  
suitable switchboard in accordance with the instructions in DOCA0038EN, available on our website.  
The CE declaration document is also available; search for ECDiEM3000.  
Internal clock  
Characteristic  
Value  
Meters  
Quartz crystal based  
Type  
iEM3115 / iEM3135 / iEM3155 / iEM3165 /  
iEM3175 / iEM3215 / iEM3235 / iEM3255 /  
iEM3265 / iEM3275 / iEM3335 / iEM3355 /  
iEM3365 / iEM3375  
Backup by supercapacitor  
< 2.5 s/day (30 ppm) at 25°C (77°F)  
> 3 days at 25°C (77°F)  
Time error  
Backup time  
Modbus communications  
Characteristic  
Value  
Meters  
Number of ports  
Labels  
1
0V, D0/-, D1/+  
(shield)  
Parity  
Even, Odd, None  
Baud rate  
Isolation  
9600, 19200, 38400  
4.0 kV rms  
iEM3150 / iEM3155 / iEM3250 /  
iEM3255 / iEM3350 / iEM3355  
2
Wire  
2.5 mm / 14 AWG shielded twisted pair  
Wire strip length  
Torque  
7 mm / 0.28 in  
0.5 Nm / 4.4 in•lb  
Related topics  
communications.  
LonWorks communications  
Characteristic  
Value  
Meters  
Number of ports  
Isolation  
1
3.75 kV rms  
2
Wire  
2.5 mm / 14 AWG  
iEM3175 / iEM3275 / iEM3375  
Wire strip length  
Torque  
7 mm / 0.28 in  
0.5 Nm / 4.4 in•lb  
100  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
iEM3100 / iEM3200 / iEM3300 series user manual  
Specifications  
Related topics  
M-Bus communications  
Characteristic  
Value  
Meters  
Number of ports  
1
Parity  
Even, Odd, None  
Baud rate  
Isolation  
Wire  
300, 600, 1200, 2400, 4800, 9600  
3.75 kV rms  
iEM3135 / iEM3235 / iEM3335  
2
2.5mm / 14 AWG  
Wire strip length  
Torque  
7 mm / 0.28 in  
0.5 Nm / 4.4 in•lb  
Related topics  
BACnet communications  
Characteristic  
Value  
Meters  
Number of ports  
Labels  
1
0V, D0/-, D1/+  
(shield)  
Baud rate  
Isolation  
9600, 19200, 38400, 57600, 76800  
4.0 kV rms  
iEM3165 / iEM3265 / iEM3365  
2
Wire  
2.5mm / 14 AWG shielded twisted pair  
Wire strip length  
Torque  
7 mm / 0.28 in  
0.5 Nm / 4.4 in•lb  
Related topics  
DOCA0005EN-04  
101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
iEM3100 / iEM3200 / iEM3300 series user manual  
102  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iEM3100 / iEM3200 / iEM3300 series user manual  
Troubleshooting  
Chapter 10  
Troubleshooting  
The meter does not contain any user-serviceable parts. If the meter requires service, contact your  
local Schneider Electric representative.  
NOTICE  
RISK OF DAMAGE TO THE METER  
• Do not open the meter case.  
• Do not attempt to repair any components of the meter.  
Failure to follow these instructions can result in equipment damage.  
Do not open the meter. Opening the meter voids the warranty.  
Diagnosis screen  
The Diagnosis screen lists any current diagnostic codes.  
NOTE: The Diagnosis screen only appears if there is a specific event.  
A
B
Diagnostic code  
Existing events  
Diagnosis  
201  
1/2  
T1 23-Apr-2012  
1. Press the down button to scroll through the main display screens until you reach the Diagnosis  
screen.  
2. Press the  
button to scroll through any existing events.  
Related topics  
DOCA0005EN-04  
103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Troubleshooting  
iEM3100 / iEM3200 / iEM3300 series user manual  
Diagnostic codes  
If the diagnostics code persists after following the instructions below, please contact Technical  
Support.  
1
Diagnostic code  
Description  
Possible solution  
LCD display is not visible.  
Push buttons do not respond.  
Check and adjust LCD contrast.  
Restart the meter by powering off and powering on again.  
Metering stops due to an EEPROM error.  
Press OK to display total energy consumption.  
Metering stops due to a lack of a calibration table.  
Press OK to display total energy consumption.  
Metering continues.  
101  
102  
Enter configuration mode and select Reset Config.  
Enter configuration mode and select Reset Config.  
Correct the frequency settings according to the nominal frequency of  
the power system.  
201  
Mismatch between frequency settings and frequency  
measurements.  
Metering continues.  
202  
203  
Correct the wiring settings according to wiring inputs.  
Mismatch between wiring settings and wiring inputs.  
Metering continues.  
Check the wire connections and correct the wiring settings if needed.  
Phase sequence reversed.  
Metering continues.  
204  
Check the wire connections and correct the wiring settings if needed.  
Total active energy is negative due to incorrect voltage and  
current connections.  
Metering continues.  
205  
206  
207  
Set the Date and Time.  
Date and Time have been reset due to a loss of power.  
Metering continues.  
Check the energy pulse output settings and correct if needed.  
Pulse is missing due to overload on energy pulse output.  
Metering continues.  
Restart the meter by powering off and powering on again then reset the  
date and time.  
Abnormal internal clock function.  
1
Not all diagnostic codes apply to all devices.  
104  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Power, energy and power factor  
Chapter 11  
Power, energy and power factor  
NOTE: The descriptions in this section assume that you are an electrical energy consumer, not a  
supplier.  
What is in this chapter?  
This chapter contains the following sections:  
Power (PQS)  
A typical AC electrical system load has both resistive and reactive (inductive or capacitive)  
components. Resistive loads consume real power (P) and reactive loads consume reactive  
power (Q).  
Apparent power (S) is the vector sum of real power (P) and reactive power (Q):  
S = P2 + Q2  
Real power is measured in watts (W or kW), reactive power is measured in vars (VAR or kVAR) and  
apparent power is measured in volt-amps (VA or kVA).  
Power and the PQ coordinate system  
The meter uses the values of real power (P) and reactive power (Q) on the PQ coordinate system to  
calculate apparent power.  
+Q  
(+kVAR)  
Quadrant 1  
Quadrant 2  
S
S
Q (+)  
Q (+)  
P (-)  
P (-)  
P (+)  
P (+)  
-P  
+P  
(-kW)  
(+kW)  
Q (-)  
S
Q (-)  
S
Quadrant 3  
Quadrant 4  
-Q  
(-kVAR)  
Power flow  
Positive power flow P(+) and Q(+) means power is flowing from the power source towards the load.  
Negative power flow P(-) and Q(-) means power is flowing from the load towards the power source.  
DOCA0005EN-04  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Power, energy and power factor  
iEM3100 / iEM3200 / iEM3300 series user manual  
Energy delivered (imported) / energy received (exported)  
The meter interprets energy delivered (imported) or received (exported) according to the direction of  
real power (P) flow.  
Energy delivered (imported) means positive real power flow (+P) and energy received (exported)  
means negative real power flow (-P).  
Energy delivered (imported) or  
Quadrant  
Real (P) power flow  
received (exported)  
Quadrant 1  
Quadrant 2  
Quadrant 3  
Quadrant 4  
Positive (+)  
Negative (-)  
Negative (-)  
Positive (+)  
Energy delivered (imported)  
Energy received (exported)  
Energy received (exported)  
Energy delivered (imported)  
Power factor (PF)  
Power factor (PF) is the ratio of real power (P) to apparent power (S), and is a number between  
0 and 1.  
P
PF = --  
S
An ideal, purely resistive load has no reactive components, so its power factor is one (PF = 1, or unity  
power factor). A purely inductive or capacitive load no resistive components, so its power factor is  
zero (PF = 0).  
True PF and displacement PF  
The meter supports true power factor and displacement power factor values:  
True power factor includes harmonic content.  
Displacement power factor only considers the fundamental frequency.  
PF lead / lag convention  
The meter correlates leading power factor (PF lead) or lagging power factor (PF lag) with whether the  
current waveform is leading or lagging the voltage waveform.  
Current phase shift from voltage  
For purely resistive loads the current waveform is in phase with the voltage waveform. For capacitive  
loads, current leads voltage. For inductive loads, current lags voltage.  
Current lead / lag and load type  
Current and voltage in phase (resistive)  
Current leads voltage (capacitive)  
Current lags voltage (inductive)  
V
V
V
Vb  
Ib  
Vb  
Ib  
Vb  
Ib  
Ia  
Ia Va  
Va  
I
Va  
Ic  
Vc  
Ia  
I
Ic  
Vc  
I
Ic  
Vc  
270°  
90°  
270°  
90°  
270°  
90°  
106  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
iEM3100 / iEM3200 / iEM3300 series user manual  
Power, energy and power factor  
Power and PF lead / lag  
+Q  
(+kVAR)  
Quadrant 1  
Quadrant 2  
S
S
Q (+)  
Q (+)  
PF lead  
PF lag  
PF lag  
P (-)  
P (-)  
P (+)  
P (+)  
-P  
+P  
(-kW)  
(+kW)  
PF lead  
Q (-)  
S
Q (-)  
S
Quadrant 3  
Quadrant 4  
-Q  
(-kVAR)  
PF lead / lag summary  
Quadrant  
Current phase shift  
Load type  
PF lead / lag  
Quadrant 1  
Quadrant 2  
Quadrant 3  
Quadrant 4  
Current lags voltage  
Current leads voltage  
Current lags voltage  
Current leads voltage  
Inductive  
Capacitive  
Inductive  
PF lag  
PF lead  
PF lag  
Capacitive  
PF lead  
PF sign convention  
The meter shows positive or negative power factor according to IEC standards.  
PF sign in IEC  
The meter correlates power factor sign (PF sign) with the direction of real power (P) flow.  
For positive real power (+P), the PF sign is positive (+).  
For negative real power (-P), the PF sign is negative (-).  
+Q  
(+kVAR)  
Quadrant 1  
Quadrant 2  
S
S
Q (+)  
Q (+)  
PF sign -  
PF sign -  
PF sign +  
P (-)  
P (-)  
P (+)  
-P  
+P  
(-kW)  
(+kW)  
P (+)  
S
PF sign +  
Q (-)  
S
Q (-)  
Quadrant 3  
Quadrant 4  
-Q  
(-kVAR)  
DOCA0005EN-04  
107  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power, energy and power factor  
iEM3100 / iEM3200 / iEM3300 series user manual  
Power factor register format  
Each power factor value (PF value) occupies one floating point register for power factor (PF register).  
The meter performs a simple algorithm to the PF value then stores it in the PF register. The meter and  
software interpret the PF register for all reporting or data entry fields according to the following  
diagram:  
0
-0.5  
+0.5  
Quadrant 1  
0 PF +1  
Quadrant 2  
-1 PF 0  
-1  
+1  
Quadrant 3  
-1 PF 0  
Quadrant 4  
0 PF +1  
-0.5  
+0.5  
0
0 to -1  
Quadrant 3  
-2 to -1  
-1 to 0  
0 to +1  
PF value  
+1 to 0  
+1  
-1  
-1  
0
0
0
Quadrant 4  
Quadrant 1  
Quadrant 2  
+1  
0
+2  
-2  
+1 to +2  
-1 to 0  
0 to +1  
PF register  
0
0
-0.5  
+0.5  
Quadrant 2  
-1 PF register 0  
Quadrant 1  
0 PF register +1  
-1  
+1  
Quadrant 4  
+1 PF register +2  
Quadrant 3  
-2 PF register -1  
-1.5  
+1.5  
-2 +2  
108  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
iEM3100 / iEM3200 / iEM3300 series user manual  
Power, energy and power factor  
PF value is calculated from the PF register value using the following formulas:  
Quadrant  
PF range PF register range  
PF formula  
Quadrant 1  
Quadrant 2  
Quadrant 3  
Quadrant 4  
0 to +1  
-1 to 0  
0 to -1  
+1 to 0  
0 to +1  
-1 to 0  
PF value = PF register value  
PF value = PF register value  
-2 to -1  
+1 to +2  
PF value = (-2) - (PF register value)  
PF value = (+2) - (PF register value)  
Related topics  
See the section for the applicable protocol for more information on the registers for that protocol.  
DOCA0005EN-04  
109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power, energy and power factor  
iEM3100 / iEM3200 / iEM3300 series user manual  
110  
DOCA0005EN-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Schneider Electric  
35, rue Joseph Monier  
CS30323  
F - 92506 Rueil Malmaison Cedex  
www.schneider-electric.com  
As standards, specifications and designs change from time to  
time, please ask for confirmation of the information given in this  
publication.  
© 2014 Schneider Electric. All rights reserved.  
DOCA0005EN-04 – 04/2014  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Quantum Computer Hardware PlatiniX 2 User Guide
RCA Microcassette Recorder RP5030 User Guide
ResMed Portable Generator VPAP Adapt SV User Guide
Rheem Water Heater 92 103234 02 User Guide
Rotel Stereo Amplifier RA 1060 User Guide
Samsung Home Theater System HT Q100W User Guide
Samsung Projector Accessories S19A350B User Guide
Samsung Telephone ITP 5107SIP User Guide
Sanyo Air Conditioner C2432 User Guide
Sarlo Trimmer SS 18 User Guide