Schneider Electric Gas Grill 20A User Guide

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip  
Units  
Unidades de disparo electrónico Micrologic™ 2.0A, 3.0A,  
5.0A y 6.0A  
MC  
Déclencheurs électroniques Micrologic 2.0A, 3.0A, 5.0A et  
6.0A  
Instruction Bulletin  
Boletín de instrucciones  
Directives d'utilisation  
48049-136-05  
Rev. 01, 04/2012  
Retain for Future Use. /  
Conservar para uso futuro. / ꢀ  
À conserver pour usage ultérieur.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A  
Electronic Trip Units  
Instruction Bulletin  
48049-136-05  
Rev. 01, 07/2012  
Retain for future use.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
48049-136-05  
Rev. 01, 07/2012  
Hazard Categories and Special  
Symbols  
Read these instructions carefully and look at the equipment to become  
familiar with the device before trying to install, operate, service or maintain  
it. The following special messages may appear throughout this bulletin or on  
the equipment to warn of potential hazards or to call attention to information  
that clarifies or simplifies a procedure.  
The addition of either symbol to a “Danger” or “Warning” safety label  
indicates that an electrical hazard exists which will result in personal injury if  
the instructions are not followed.  
This is the safety alert symbol. It is used to alert you to potential personal  
injury hazards. Obey all safety messages that follow this symbol to avoid  
possible injury or death.  
ANSI  
DANGER  
DANGER indicates a hazardous situation which, if not avoided, will result  
in death or serious injury.  
IEC  
WARNING  
WARNING indicates a hazardous situation which, if not avoided, can  
result in death or serious injury.  
CAUTION  
CAUTION indicates a hazardous situation which, if not avoided, can  
result in minor or moderate injury.  
NOTICE  
NOTICE is used to address practices not related to physical injury. The  
safety alert symbol is not used with this signal word.  
NOTE: Provides additional information to clarify or simplify a procedure.  
Please Note  
FCC Notice  
Electrical equipment should be installed, operated, serviced, and  
maintained only by qualified personnel. No responsibility is assumed by  
Schneider Electric for any consequences arising out of the use of this  
material.  
This equipment has been tested and found to comply with the limits for a  
Class A digital device, pursuant to part 15 of the FCC Rules. These limits  
are designed to provide reasonable protection against harmful interference  
when the equipment is operated in a commercial environment. This  
equipment generates, uses, and can radiate radio frequency energy and, if  
not installed and used in accordance with the instruction manual, may cause  
harmful interference to radio communications. Operation of this equipment  
in a residential area is likely to cause harmful interference in which case the  
user will be required to correct the interference at his own expense. This  
Class A digital apparatus complies with Canadian ICES-003.  
2-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic® 2.0A, 3.0A, 5.0A and 6.0A Electronic Trip Units  
Table of Contents  
Table of Contents  
SECTION 1:  
GENERAL INFORMATION  
...................................................................................................................... 5  
Introduction ................................................................................................. 5  
Communications ......................................................................................... 5  
Trip Unit Settings ........................................................................................ 5  
Micrologic 2.0A Trip Unit ....................................................................... 6  
Micrologic 3.0A Trip Unit ....................................................................... 6  
Micrologic 5.0A Trip Unit ....................................................................... 7  
Micrologic 6.0A Trip Unit ....................................................................... 8  
Zone-Selective Interlocking ......................................................................... 9  
Trip Unit Switches ..................................................................................... 10  
Long-Time Protection .......................................................................... 10  
Short-Time Protection ......................................................................... 11  
Instantaneous Protection ..................................................................... 12  
Ground-Fault Protection ...................................................................... 13  
Indicator Lights .......................................................................................... 13  
Overload Indicator Light ...................................................................... 13  
Trip Indicator Lights ............................................................................. 14  
Ammeter ................................................................................................... 14  
Trip Unit Testing ........................................................................................ 14  
Micrologic Trip Unit Configuration ............................................................. 14  
Control Power ...................................................................................... 14  
External Power Supply ........................................................................ 15  
SECTION 2:  
SECTION 3:  
AMMETER  
.................................................................................................................... 16  
Display ...................................................................................................... 16  
Ammeter Measurements ........................................................................... 16  
Accessing Information ............................................................................... 16  
Current Menu ...................................................................................... 17  
Peak Menu .......................................................................................... 18  
Switch Settings Menu .......................................................................... 19  
OPERATION  
.................................................................................................................... 20  
Switch Setting Adjustment ........................................................................ 20  
Examples .................................................................................................. 20  
Micrologic 2.0A Trip Unit ..................................................................... 20  
Micrologic 3.0A Trip Unit ..................................................................... 21  
Micrologic 5.0A Trip Unit ..................................................................... 21  
Micrologic 6.0A Trip Unit ..................................................................... 22  
Zone-Selective Interlocking (ZSI) .............................................................. 23  
Communication Module values ................................................................. 24  
Trip Unit Settings Check ........................................................................... 26  
Trip Unit Operation Verification ................................................................. 26  
Equipment Ground-Fault Trip Functions Testing ...................................... 27  
Trip Unit Resetting .................................................................................... 27  
Trip Unit Status Check .............................................................................. 27  
SECTION 4:  
TRIP UNIT REPLACEMENT  
.................................................................................................................... 28  
Required Tools .......................................................................................... 28  
Preparation ............................................................................................... 28  
Record Switch Settings ....................................................................... 28  
Circuit Breaker Disconnection ............................................................. 28  
Circuit Breaker Accessory Cover Removal ......................................... 28  
Rating Plug Removal ........................................................................... 29  
Trip Unit Removal ................................................................................ 29  
© 1999–2012 Schneider Electric All Rights Reserved  
3-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Table of Contents  
48049-136-05  
Rev. 01, 07/2012  
Trip Unit Replacement ..............................................................................29  
Battery Installation ...............................................................................29  
Trip Unit Installation .............................................................................30  
Circuit Breaker Accessory Cover Replacement ........................................31  
Trip Unit Installation Check .......................................................................32  
Secondary Injection Testing ................................................................32  
Primary Injection Testing .....................................................................32  
Check Accessory Operation ................................................................32  
Trip Unit Setup ..........................................................................................32  
Circuit Breaker Reconnection ...................................................................32  
SECTION 5:  
SECTION 6:  
ADJUSTABLE RATING PLUG REPLACEMENT ..............................................................................................33  
Rating Plug Removal ................................................................................33  
New Rating Plug Installation .....................................................................33  
BATTERY REPLACEMENT  
....................................................................................................................34  
Circuit Breaker Disconnection ...................................................................34  
Circuit Breaker Accessory Cover Removal ...............................................34  
Withstand Module Shifting ........................................................................34  
Battery Replacement .................................................................................34  
Withstand Module Replacement ...............................................................35  
Circuit Breaker Accessory Cover Replacement ........................................35  
Circuit Breaker Reconnection ...................................................................35  
APPENDIX A: REGISTER LIST  
....................................................................................................................36  
List of Registers ........................................................................................36  
4-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
Section 1—General Information  
Figure 1:  
Micrologic Trip Unit  
Introduction  
A—Micrologic Trip Unit  
B—Product Name  
C—Switch Cover  
D—Switch Cover Opening Slot  
E—Adjustable Rating Plug  
Micrologic™ trip units (A) provide adjustable  
tripping functions on electronic trip circuit  
breakers. The product name (B) specifies the  
level of protection provided by the trip unit.  
A
A
7.0  
ic  
g
o
l
ro  
ic  
M
B
Micrologic 3.0A  
%
%
0
0
0
1
Type of protection  
2—Basic IEC protection (LS0)  
3—Basic UL protection (LI)  
5—Selective protection (LSI)  
6—Selective protection plus ground fault  
protection for equipment (LSIG)  
E
4
m
lar  
a
u
n
e
m
e
m
ti  
8
r
12  
ng  
t
lo  
)
4
6
1
(
s
.8  
Ir  
.9  
.9  
.9  
2
1
20  
24  
.7  
5
8
.6  
.5  
.4 In  
.5  
Ir  
6
@
1
x
D
Trip unit series  
0—Indicates the first version  
C
Type of measurement  
None—Provides protection only  
A—Provides protection plus ammeter measurements  
Micrologic trip units are field replaceable to allow  
for upgrading of the trip unit in the field. For  
complete information on available circuit breaker  
models, frame sizes, interrupting ratings, sensor  
plugs, rating plugs and trip units, see the product  
catalog.  
Communications  
Micrologic trip units can communicate with other devices if the optional  
Circuit Breaker Communication Module (BCM) is installed. For information  
on the communication module, see the product catalog and Modbus™  
Communications System, Data Bulletin 0613IB1201.  
Trip Unit Settings  
On the face of the trip unit are adjustable switches to allow changing of trip  
characteristics. Trip units are shipped with the long-time pickup switch set at  
1.0 and all other trip unit adjustments set at their lowest settings.  
© 1999–2012 Schneider Electric All Rights Reserved  
5-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
48049-136-05  
Rev. 01, 07/2012  
NOTE: For use with IEC circuit breakers only.  
Micrologic 2.0A Trip Unit  
Figure 2:  
2.0A Trip Unit  
The Micrologic 2.0A trip unit provides basic IEC  
(LS0) protection and a built-in ammeter.  
M
N
L
A
A. Trip unit name  
Micrologic 2.0 A  
K
B. Alphanumeric display  
C. Three-phase bar graph  
D. Scroll button  
B
C
E. Menu button  
F. Long-time pickup (Ir) switch  
G. Long-time delay (tr) switch  
H. Short-time pickup (Isd) switch*  
I. Test plug receptacle  
J. Overload indicator light  
K. Reset button for battery status check and trip  
indicator LED  
L. Self-protection indicator light  
t
F
G
D
E
H
menu  
J
I
0
Ir  
Isd  
I
long time  
alarm  
Ir  
tr  
(s)  
.8  
8
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.6  
.5  
.4  
2
1
F
M. Short-time or instantaneous trip indicator  
light  
N. Long-time trip indicator light  
1
.5  
x In  
instantaneous  
Isd  
@ 6 Ir  
4
G
H
3
5
2.5  
6
8
10  
2
1.5  
x Ir  
setting  
Figure 3:  
3.0A Trip Unit  
Micrologic 3.0A Trip Unit  
N M  
L
A
The Micrologic 3.0A trip unit provides basic UL  
(LI) protection and a built-in ammeter.  
Micrologic 3.0 A  
K
A. Trip unit name  
B. Alphanumeric display  
C. Three-phase bar graph  
D. Scroll button  
B
C
E. Menu button  
t
F
F. Long-time pickup (Ir) switch  
G. Long-time delay (tr) switch  
H. Instantaneous pickup (Ii) switch  
I. Test plug receptacle  
J. Overload indicator light  
G
D
E
H
menu  
J
K. Reset button for battery status check and trip  
indicator LED  
0
Ir  
Ii  
I
long time  
alarm  
Ir  
tr  
(s)  
.8  
8
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.6  
.5  
.4  
2
1
F
L. Self-protection indicator light  
1
.5  
x In  
@ 6 Ir  
instantaneous  
M. Short-time or instantaneous trip indicator  
light  
N. Long-time trip indicator light  
Ii  
G
5
4
6
3
2
8
10  
1.5  
x In  
setting  
12  
H
I
*Short-time delay is factory set at 0 (no delay), thus short-time  
pickup provides instantaneous protection.  
6-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
Figure 4:  
5.0A Trip Unit  
P O  
Micrologic 5.0A Trip Unit  
N
A
The Micrologic 5.0A trip unit provides selective  
(LSI) protection and a built-in ammeter.  
Micrologic 5.0 A  
M
A. Trip unit name  
B. Alphanumeric display  
C. Three-phase bar graph  
D. Scroll button  
B
C
E. Menu button  
t
F. Long-time pickup (Ir) switch  
G. Long-time delay (tr) switch  
H. Short-time pickup (Isd) switch  
I. Short-time delay (tsd) switch  
J. Instantaneous pickup (Ii) switch  
K. Test plug receptacle  
L. Overload indicator light  
F
G
H
D
E
I
menu  
J
L
long time  
alarm  
Ir  
tr  
(s)  
0
Ir  
Isd Ii  
I
.8  
8
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.6  
.5  
2
1
F
G
H
.4  
1
.5  
M. Reset button for battery status check and trip  
indicator LED  
N. Self-protection indicator light  
x In  
@
6 Ir  
short timee  
instantaneous  
Isd  
tsd  
I i  
.4 .4  
4
8
(s)  
.3  
.2  
.3.2  
3
5
6
10  
12  
15  
off  
x In  
2.5  
6
8
4
3
.1  
2
.1  
0
off  
1.5  
10  
2
2
x Ir  
setting  
on  
I
t
delay  
O. Short-time or instantaneous trip indicator  
light  
P. Long-time trip indicator light  
I
K
J
© 1999–2012 Schneider Electric All Rights Reserved  
7-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
48049-136-05  
Rev. 01, 07/2012  
Figure 5:  
6.0A Trip Unit  
Micrologic 6.0A Trip Unit  
R Q  
T S  
The Micrologic 6.0A trip unit provides selective  
and ground-fault protection for equipment  
(ꢁꢀ1200 A) (LSIG) and a built-in ammeter.  
A
Micrologic 6.0 A  
t
F
P
A. Trip unit name  
G
B. Alphanumeric display  
H
I
B
C
C. Three-phase bar graph  
D. Scroll button  
E. Menu button  
J
0
Ir  
Isd Ii  
I
100%  
F. Long-time pickup (Ir) switch  
G. Long-time delay (tr) switch  
H. Short-time pickup (Isd) switch  
I. Short-time delay (tsd) switch  
J. Instantaneous pickup (Ii) switch  
K. Ground-fault pickup (Ig) switch  
L. Ground-fault delay (tg) switch  
M. Test plug receptacle  
N. Ground fault push-to-trip button  
O. Overload indicator light  
P. Reset button for battery status check and trip  
indicator LED  
%
40  
t
D
E
menu  
O
I2t on  
I2t off  
long time  
alarm  
K
Ir  
tr  
(s)  
.8  
8
.7  
.9  
.95  
.98  
4
12  
16  
20  
.6  
.5  
2
1
F
24  
.4  
1
.5  
L
x In  
@
6 Ir  
G
short time  
instantaneous  
Isd  
tsd  
I i  
(s)  
.4 .3  
6
4
5
.4  
3
5
10  
12  
15  
off  
.3  
.2  
.1  
6
8
4
3
2.5  
H
J
.2  
.1  
2
0
2
1.5  
10  
2
0
Ig  
I
x Ir  
on  
I
t
off  
x In  
setting  
delay  
I
test  
N
Ig  
tg  
(s)  
.3  
.2  
.4 .4  
E
.3.2  
D
F
G
H
C
K
.1  
B
A
M
.1  
0
J
2
on  
I
t
off  
ground fault  
L
Q. Self-protection indicator light  
R. Ground-fault trip indicator light  
S. Short-time or instantaneous trip indicator  
light  
T. Long-time trip indicator light  
8-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
Zone-Selective Interlocking  
2
2
Short-time and ground-fault protection can be  
interlocked to provide zone-selective  
interlocking.  
NOTE: Use I t off with ZSI for proper coordination. Using I t on with ZSI is  
not recommended as the delay in the upstream device receiving a restraint  
signal could result in the trip unit tripping in a time shorter than the published  
trip curve.  
Control wiring links several trip units in the  
distribution network and in the event of a fault, a  
trip unit will obey the set delay time only if  
receiving a signal from a downstream trip unit.  
NOTE: Setting short-time delay (tsd) or ground-fault delay (tg) to the 0  
setting will eliminate selectivity for that circuit breaker.  
If the trip unit does not receive a signal, tripping  
will be instantaneous (with no intentional delay).  
The fault is cleared instantaneously by the  
nearest upstream circuit breaker.  
2
Thermal stresses (I t) in the network are  
minimized without any effect on the correct  
time delay coordination of the installation.  
Figure 6 shows circuit breakers 1 and 2 zone-  
selective interlocked.  
Figure 6:  
Zone-Selective Interlocking  
A fault at A is seen by circuit breakers 1 and  
2. Circuit breaker 2 trips instantaneously and  
also informs circuit breaker 1 to obey set  
delay times. Thus, circuit breaker 2 trips and  
clears the fault. Circuit breaker 1 does not  
trip.  
A fault at B is seen by circuit breaker 1.  
Circuit breaker 1 trips instantaneously since  
it did not receive a signal from the  
downstream circuit breaker 2. Circuit breaker  
1 trips and clears the fault. Circuit breaker 2  
does not trip.  
1
B
A
2
© 1999–2012 Schneider Electric All Rights Reserved  
9-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
48049-136-05  
Rev. 01, 07/2012  
Trip Unit Switches  
NOTE: Micrologic trip units are powered from the circuit to always provide  
fault protection. All other functions (display, metering, communications, etc.)  
require external power. See 15 for more information.  
Long-Time Protection  
Long-time protection protects equipment against  
overloads.  
Figure 7:  
Long-Time Protection Switches  
Long-time protection is standard on all trip  
units.  
Micrologic 2.0A Trip Unit  
Micrologic 3.0A Trip Unit  
A
B
C
A
B
C
The long-time pickup (Ir) (A) sets the  
maximum current level (based on sensor  
plug rating In) which the circuit breaker can  
continuously carry. If current exceeds this  
value, circuit breaker will trip after the preset  
time delay. The long-time pickup (Ir) is  
adjustable from 0.4–1.0 times the sensor  
plug rating (In).  
long time  
long time  
alarm  
Ir  
tr  
(s)  
alarm  
Ir  
tr  
(s)  
8
.8  
8
.8  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.6  
.5  
.4  
2
1
.6  
.5  
.4  
2
1
1
.5  
1
.5  
x In  
@ 6 Ir  
x In  
@ 6 Ir  
instantaneous  
instantaneous  
Isd  
Ii  
4
5
3
5
4
6
2.5  
2
6
8
3
2
8
10  
1.5  
10  
1.5  
12  
x Ir  
x In  
setting  
setting  
The long-time delay (tr) (B) sets the length of  
the time that the circuit breaker will carry an  
overcurrent (below the short-time or  
instantaneous pickup current level) before  
tripping. See Table 1 for delay settings.  
Both long-time pickup and long-time delay  
are on the field-replaceable adjustable rating  
plug. To change settings to more precisely  
match the application, various rating plugs  
are available. For instructions on replacing  
the rating plug, see Section 5 —Adjustable  
Rating Plug Replacement.  
Micrologic 5.0A Trip Unit  
Micrologic 6.0A Trip Unit  
A
B
C
A
B
C
long time  
long time  
alarm  
Ir  
tr  
alarm  
Ir  
tr  
8
.8  
8
.8  
(s)  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
(s)  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.6  
.5  
.4  
2
1
.6  
.5  
2
1
1
.5  
@ 6 Ir  
.4  
1
.5  
@ 6 Ir  
x In  
x In  
short time  
instantaneous  
short time  
instantaneous  
tsd  
I i  
Isd  
tsd  
(s)  
I i  
Isd  
4
8
.4  
.4 .4  
(s)  
.3  
0
4
8
.
4
.3  
5
6
2
10  
12  
15  
off  
x In  
3
3
5
5
10  
12  
15  
off  
4
3
6
8
.
3
.
2
1
2.5  
2
.3  
.2  
.2  
.1  
2.5  
2
6
8
4
3
.
2
.
.
1
0
off  
.1  
2
2
1.5  
10  
1.5  
10  
2
on  
I
t
off  
x Ir  
on  
I
t
x In  
x Ir  
setting  
delay  
setting  
delay  
test  
Ig  
tg  
(s)  
.
4
E
.
4
.3  
D
F
For Masterpact™ NT and NW circuit  
.
.
3
.
2
1
C
B
G
H
2
.
breakers, the In value can be changed by  
replacing the sensor plug below the trip unit.  
For further information, see the instructions  
packed with the sensor plug replacement kit.  
.1  
0
off  
A
J
2
on  
I
t
ground fault  
The overload indicator light (C) indicates that  
the Ir long-time pickup threshold has been  
exceeded.  
Long-time protection uses true RMS  
measurement.  
Table 1:  
Setting1  
Micrologic Trip Unit Long-Time Delay Values  
Long-Time Delay in Seconds2  
tr at 1.5 x Ir  
tr at 6 x Ir  
12.5  
0.5  
25  
1
50  
2
100  
4
200  
8
300  
12  
400  
16  
500  
20  
600  
24  
Thermal imaging provides continuous  
temperature rise status of the wiring, both before  
and after the device trips. This allows the circuit  
breaker to respond to a series of overload  
conditions which could cause conductor  
overheating, but would go undetected if the  
long-time circuit was cleared every time the load  
dropped below the pickup setting or after every  
tripping event.  
3
tr at 7.2 x Ir  
0.34  
0.69  
1.38  
2.7  
5.5  
8.3  
11  
13.8  
16.6  
1
Ir = In x long-time pickup. In = sensor rating. Trip threshold between 1.05 and 1.20 Ir.  
Time-delay accuracy +0/-20%  
For Micrologic 5.0A and 6.0A trip units, when tsd is set to 0.4 on or 4.0 off, then tr = 0.5 instead of 0.34.  
2
3
NOTE: If checking trip times, wait a minimum of 15 minutes after circuit  
breaker trips before resetting to allow the thermal imaging to reset  
completely to zero or use a full-function test kit to defeat the thermal  
imaging.  
10-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
Figure 8:  
Short-Time Protection Switches  
Short-Time Protection  
Micrologic 5.0A Trip Unit  
Micrologic 6.0A Trip Unit  
Short-time protection protects equipment  
against short circuits.  
long time  
long time  
alarm  
Ir  
tr  
(s)  
alarm  
Ir  
tr  
(s)  
8
.8  
8
.8  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.6  
.5  
2
1
.6  
.5  
2
1
Short-time protection is standard on 2.0A,  
5.0A and 6.0A trip units. It is not available on  
3.0A trip units.  
.4  
1
.5  
.4  
1
.5  
x In  
@ 6 Ir  
x In  
@ 6 Ir  
short time  
instantaneous  
short time  
instantaneous  
tsd  
I i  
Isd  
tsd  
I i  
Isd  
4
8
.4  
.4 .4  
(s)  
.3  
0
4
8
(s)  
.
4
.3  
5
6
2
10  
12  
15  
off  
x In  
3
3
5
5
10  
12  
15  
off  
4
3
6
8
.
3
.
2
1
2.5  
2
.3  
.2  
.2  
.1  
2.5  
2
6
8
4
3
.
2
.
.
1
0
off  
.1  
2
2
1.5  
10  
1.5  
10  
2
Short-time protection is based on the long-  
time pickup (Ir).  
The short-time pickup (Isd) (A) sets current  
level (below instantaneous trip level) at  
which circuit breaker will trip after the preset  
time delay.  
on  
I
t
off  
x Ir  
on  
I
t
x In  
x Ir  
setting  
delay  
A
B
A
B
setting  
delay  
test  
Ig  
tg  
(s)  
.
4
E
.
4
.3  
D
F
.
.
3
.
2
1
C
B
G
H
2
.
.1  
0
off  
A
J
2
on  
I
t
ground fault  
The short-time delay (tsd) (B) sets the length  
of time that the circuit breaker will carry an  
overcurrent above the short-time pickup  
current level before tripping. It is adjustable  
on the 5.0A and 6.0A trip unit and factory set  
to zero on the 2.0A trip unit.  
The I t on/I t off option provides improved  
selectivity with downstream protective  
devices:  
Table 2:  
Micrologic Trip Unit Short-Time Delay Values  
Short-Time Delay  
Setting  
2
I t off (Isd at 10 Ir) (seconds)  
0
0.1  
0.1  
80  
0.2  
0.2  
140  
200  
0.3  
0.4  
0.4  
350  
500  
2
2
2
I t on (Isd at 10 Ir) (seconds)  
0.3  
tsd (min. trip) (milliseconds)  
tsd (max. trip) (milliseconds)  
20  
80  
230  
320  
140  
2
— With I t off selected, fixed time delay is  
provided.  
2
2
— With I t on selected, inverse time I t  
protection is provided up to 10 x Ir.  
Above 10 x Ir, fixed time delay is  
provided.  
Intermittent currents in the short-time tripping  
range which do not last sufficiently long to  
trigger a trip are accumulated and shorten  
the trip delay appropriately.  
Short-time protection can be zone-selective  
interlocked (ZSI) with upstream or  
downstream circuit breakers.  
2
2
NOTE: Use I t off with ZSI for proper coordination. Using I t on with ZSI is  
not recommended as the delay in the upstream device receiving a restraint  
signal could result in the trip unit tripping in a time shorter than the  
published trip curve.  
Setting tsd to the 0 setting turns off zone-  
selective interlocking.  
Short-time protection uses true RMS  
measurement.  
Short-time pickup and delay can be adjusted  
to provide selectivity with upstream or  
downstream circuit breakers.  
© 1999–2012 Schneider Electric All Rights Reserved  
11-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
48049-136-05  
Rev. 01, 07/2012  
Figure 9:  
Instantaneous Protection Switches  
Instantaneous Protection  
Micrologic 2.0A Trip Unit  
Micrologic 3.0A Trip Unit  
Instantaneous protection protects equipment  
against short circuits with no intentional time  
delay.  
long time  
long time  
alarm  
Ir  
tr  
(s)  
alarm  
Ir  
tr  
(s)  
8
.8  
8
.8  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.6  
.5  
.4  
2
1
.6  
.5  
.4  
2
1
1
.5  
1
.5  
x In  
@ 6 Ir  
x In  
@ 6 Ir  
instantaneous  
instantaneous  
Instantaneous protection (Ii) (A) is standard  
on the 3.0A, 5.0A and 6.0A trip units.  
Instantaneous protection on 2.0A trip units is  
achieved by using short-time protection (Isd)  
with the short-time delay factory set to 0  
(zero).  
Isd  
Ii  
4
5
3
5
4
6
2.5  
2
6
8
3
2
8
10  
1.5  
10  
1.5  
12  
x Ir  
x In  
A
A
setting  
setting  
Instantaneous protection on the 3.0A, 5.0A  
and 6.0A trip units is based on the circuit  
breaker sensor rating (In).  
Micrologic 5.0A Trip Unit  
Micrologic 6.0A Trip Unit  
long time  
long time  
alarm  
Ir  
tr  
(s)  
alarm  
Ir  
tr  
(s)  
8
.8  
8
.8  
Instantaneous protection on the 2.0A trip unit  
is based on the long-time pickup setting (Ir).  
Circuit breaker open command is issued as  
soon as threshold current is exceeded.  
Instantaneous protection uses peak current  
measurement.  
When instantaneous protection switch is set  
to off, the instantaneous protection is  
disabled.  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.6  
.5  
2
1
.6  
.5  
2
1
.4  
1
.5  
.4  
1
.5  
x In  
@ 6 Ir  
x In  
@ 6 Ir  
short time  
instantaneous  
short time  
instantaneous  
tsd  
I i  
Isd  
tsd  
I i  
Isd  
4
8
.4  
.4 .4  
(s)  
.3  
0
4
8
(s)  
.4  
.3  
5
6
2
10  
12  
15  
off  
x In  
3
3
5
5
10  
12  
15  
off  
4
3
6
8
.
.
3
.
2
1
2.5  
2
.3  
.2  
.2  
.1  
2.5  
2
6
8
4
3
2
.
.
1
0
off  
.1  
2
1.5  
10  
2
1.5  
10  
2
A
A
on  
I
t
off  
x Ir  
on  
I
t
x In  
x Ir  
setting  
delay  
setting  
delay  
test  
Ig  
tg  
(s)  
.4  
E
.4  
.3  
D
F
.
.
3
.
2
1
C
B
G
H
2
.
.
1
0
off  
A
J
2
on  
I
t
ground fault  
Table 3:  
Setting  
Micrologic Instantaneous Values  
Interruption Current  
2.0A Isd (= Ir x..)  
3.0A Ii (= In x..)  
5.0A Ii (= In x..)  
6.0A Ii (= In x..)  
1.5  
1.5  
2
2
2
3
3
2.5  
3
3
4
6
6
4
5
8
8
5
6
8
8
10  
12  
off  
off  
6
10  
15  
15  
4
10  
10  
12  
12  
2
4
Ii = UL and ANSI instantaneous  
Isd = IEC instantaneous (short-time with zero delay)  
In = sensor rating  
Ir = long-time pickup  
12-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
Figure 10: Ground-Fault Protection Switches  
Ground-Fault Protection  
Micrologic 6.0A Trip Unit  
Equipment ground-fault protection protects  
conductors against overheating and faults from  
ground-fault currents (ꢁꢀ1200 A).  
long time  
alarm  
Ir  
tr  
(s)  
8
.8  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.6  
.5  
2
1
.4  
1
.5  
x In  
@ 6 Ir  
short time  
instantaneous  
Isd  
tsd  
I i  
Equipment ground-fault protection is  
standard on 6.0A trip units.  
.
4
4
8
(s)  
.
4
.3  
3
5
5
10  
12  
15  
off  
.
3
.
2
1
2.5  
2
6
8
4
3
.
2
.
.
1
0
off  
2
1.5  
10  
2
x Ir  
on  
I
t
x In  
Ground-fault pickup (Ig) (A) sets ground  
current level where circuit breaker will trip  
after the preset time delay.  
Ground-fault delay (tg) (B) sets the length of  
time that the circuit breaker will carry a  
ground-fault current above the ground-fault  
pickup current level before tripping.  
Equipment ground-fault protection can be  
zone-selective interlocked (ZSI) with  
upstream or downstream circuit breakers.  
Setting the ground-fault delay (tg) to the 0  
setting turns off zone-selective interlocking.  
setting  
delay  
test  
Ig  
tg  
(s)  
.
4
E
.
4
.3  
D
F
.
.
3
.
2
1
C
B
G
H
2
.
.1  
0
off  
A
J
2
on  
I
t
ground fault  
A
B
Table 4:  
Micrologic Trip Unit Ground-Fault Pickup Values  
Ig (= In x....)  
A
B
C
D
E
F
G
H
J
1
1
In 400 A  
0.3  
0.2  
0.3  
0.3  
0.4  
0.4  
0.5  
0.5  
0.6  
0.6  
0.7  
0.7  
0.8  
0.8  
0.9  
0.9  
400 A < In 1200 A  
In > 1200 A  
500 A 640 A 720 A 800 A 880 A 960 A 1040 A 1120 A 1200 A  
Neutral protection and equipment ground-  
fault protection are independent and can  
operate concurrently.  
In = sensor rating.  
Ig = ground-fault pickup.  
Table 5:  
Micrologic Trip Unit Ground-Fault Delay Values  
Ground-Fault Delay  
Setting  
2
I t off (ms at In) (seconds)  
0
0.1  
0.1  
80  
0.2  
0.2  
140  
200  
0.3  
0.3  
230  
320  
0.4  
2
I t on (ms at In) (seconds)  
0.4  
tsd (min. trip) (milliseconds) 20  
350  
500  
tsd (max. trip) (milliseconds) 80  
140  
2
2
NOTE: Use I t off with ZSI for proper coordination. Using I t on with ZSI is  
not recommended as the delay in the upstream device receiving a restraint  
signal could result in the trip unit tripping in a time shorter than the  
published trip curve.  
Indicator Lights  
Figure 11: Overload Indicator Light  
Overload Indicator Light  
long time  
alarm  
Ir  
tr  
(s)  
The overload indicator light (A) lights when the Ir  
long-time pickup level has been exceeded (over  
100% on the bar graph).  
8
.8  
.7  
.9  
.95  
.98  
4
12  
16  
20  
24  
.6  
.5  
2
1
A
.4  
1
.5  
x In  
@ 6 Ir  
short time  
instantaneous  
Isd  
tsd  
I i  
%
%
100  
40  
.
4
4
4
.
4
.3  
3
5
3
5
2.5  
2
.
3
.
2
1
2.5  
2
6
8
6
8
.
2
.
.
1
0
1.5  
10  
1.5  
10  
x In  
2
on  
x Ir  
I
t
setting  
delay  
test  
IΔn  
ΔI  
(ms)  
(A)  
5
230  
140  
60  
3
7
350  
800  
2
1
10  
20  
.5  
30  
earth leakage  
© 1999–2012 Schneider Electric All Rights Reserved  
13-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
48049-136-05  
Rev. 01, 07/2012  
Figure 12: Trip Indicator Lights  
Trip Indicator Lights  
C D  
A B  
The Ir trip indicator light (A) lights when a trip  
occurs because the Ir long-time pickup level was  
exceeded.  
Micrologic 6.0 A  
The Isd/Ii trip indicator light (B) lights when a trip  
occurs because the Isd short-time pickup or the  
Ii instantaneous pickup was exceeded.  
The Ig trip indicator light (C) lights when a trip  
occurs because the Ig ground fault pickup was  
exceeded.  
The Ap self-protection indicator light (D) lights  
when the trip unit overheats, the instantaneous  
override level is exceeded, or a trip unit power  
supply failure occurs.  
Figure 13: Ammeter  
Ammeter  
The ammeter monitors and displays the circuit  
breaker currents. An alphanumeric screen (A)  
continuously displays the phase at the highest  
load. Navigation buttons (B) can be pressed to  
display the various monitored currents.  
A
B
100%  
The process of checking the ammeter values  
can be stopped at any time. After several  
seconds, Micrologic trip units automatically  
return to displaying the phase at the highest  
load.  
%
40  
menu  
See the following section for addition information  
concerning the ammeter.  
Trip Unit Testing  
Trip unit functions can be tested using primary injection testing or secondary  
injection testing.  
Micrologic Trip Unit Configuration  
Control Power  
The A trip unit was designed to be used with or without an external 24 Vdc  
power supply.  
Table 6:  
Pickup Values  
The following will be powered and functional even if the trip unit is not  
externally powered:  
Sensor Plug Value Minimum Ground-Fault  
(In)  
Pickup  
Fault protection for LSIG functions. The A trip unit is fully circuit powered  
for fault protection.  
LED trip indication (powered by an onboard battery). The battery’s only  
function is to provide LED indication if all other power is off  
All display functions and trip unit features power-up with current flow on  
one phase greater than or equal to the values in Table 6.  
Ground-fault push-to-trip button works for testing ground fault with  
current flow on one phase greater than or equal to the values in Table 6.  
100–250 A  
30% of Sensor Rating  
20% of Sensor Rating  
500 A  
400–1200 A  
1600–6300 A  
The ground-fault push-to-trip is also functional if a Hand-Held Test Kit or  
Full-Function Test Kit is powering the trip unit.  
14-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 1—General Information  
The following will be powered and functional with external power:  
All of the above functions which are functional without external power.  
Ammeter and bar graph displays are functional with or without current  
flowing through the circuit breaker. With current flow between 0 and 20%  
of sensor value, the ammeter may not be accurate.  
Trip settings and max. current readings can be accessed on the display  
be pressing the navigation buttons with or without current flowing  
through the circuit breaker.  
Ground-fault push-to-trip button works for testing ground fault with or  
without current flowing through the circuit breaker.  
Optional Modbus communications are functional, using a separate 24  
Vdc power supply for the circuit breaker communications module. This  
separate 24 Vdc power supply is required to maintain the isolation  
between the trip unit and communications.  
The ground-fault push-to-trip is also functional if a Hand-Held Test Kit or  
Full-Function Test Kit is powering the trip unit.  
External Power Supply  
The trip unit display can be powered by a 24 Vdc external power supply.  
CAUTION  
HAZARD OF SHOCK, ARC FLASH OR  
EQUIPMENT DAMAGE  
Table 7:  
Function  
Power Supply Specifications  
Specification  
Power for Trip Unit Alone  
24 Vdc, 50 mA  
2400 V  
Minimum Input-to-Output Isolation  
Output (Including Max. 1% Ripple)  
Dielectric Withstand (Input/Output)  
Trip unit and communication module must use  
separate power supplies.  
5%  
3 kV rms  
Failure to follow this instruction can result  
in personal injury or equipment damage.  
Connections UC3  
F1 (-)  
Connections  
24 Vdc  
F2 (+)  
Power supply is used for graphic scree display when the circuit breaker is  
open or not carrying current.  
© 1999–2012 Schneider Electric All Rights Reserved  
15-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 2—Ammeter  
48049-136-05  
Rev. 01, 07/2012  
Section 2—Ammeter  
Display  
NOTE: The ammeter display will function only if the trip unit is powered. The  
trip unit is powered by the circuit breaker carrying more than 0.20 x In of  
load current, by being connected to a 24 Vdc external power supply, or by  
having the Full-Function Test Kit or Hand-Held Test Kit connected and on.  
Even with external power supplied, current through the circuit breaker must  
exceed 0.20 x In for the ammeter reading to be accurate to within 1.5%.  
A. Alphanumeric screen: Displays ammeter  
information  
B. Bar graph: Displays currents using an LED  
bar graph  
Figure 14: Ammeter  
A
C. Menu button: Used to navigate between the  
various menus  
D. Scroll button: Used to scroll to the next  
screen in the menus  
B
100%  
The default display is the current value of the  
phase at the highest load.  
%
40  
C
D
If no information is displayed, contact the local  
field office.  
menu  
Ammeter Measurements  
Micrologic A trip units measure the true RMS  
value of currents. They provide continuous  
current measurement from 0.2 to 20 x In with an  
accuracy of 1.5% (including sensors). No  
auxiliary source is needed where I > 0.2 x In.  
The optional external power supply (24 Vdc)  
makes it possible to display currents where  
I < 0.2 x In and to store values of the interrupted  
current.  
A digital LCD screen continuously displays the  
most heavily loaded phases (Imax) or displays  
the Ia, Ib, Ic, Ig, and (on 4-pole circuit breakers  
only) In stored current and setting values by  
successively pressing the navigation button.  
Figure 15: Menus  
Accessing Information  
B–Peak Currents  
C–Switch Settings  
A–Currents  
Three different menus can be accessed:  
Max  
Ir=  
A. Current measurements  
B. Stored peak current measurements  
C. Switch settings  
A
A
A
In addition, the ammeter can be used to address  
the circuit breaker communication module  
(BCM) in circuit breakers which have the  
optional circuit breaker communication module  
installed.  
1.125 x Ir  
1 x Ir  
0.8 x Ir  
0.6 x Ir  
0.4 x Ir  
%
%
100  
40  
%
%
100  
40  
%
100  
%
40  
16-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 2—Ammeter  
To access the next menu, press the menu  
button (A). To access the next screen in a menu,  
press the scroll button (B).  
Figure 16: Navigation Buttons  
A
B
menu  
Figure 17: Current Menus  
A–A-Phase Current (IA)  
Current Menu  
B–B-Phase Current (IB)  
The current (default) menu displays:  
A. Phase current (IA) in A phase  
B. Phase current (IB) in B phase  
C. Phase current (IC) in C phase  
A
A
D. Ground-fault current (Ig) (Micrologic 6.0A trip  
units only)  
E. Neutral current (In)  
To display next current, press scroll button.  
%
%
100  
40  
%
%
100  
40  
NOTE: Neutral current is only displayed with a  
4-pole circuit breaker with the neutral protection  
set to half or full. Refer to bulletin 48041-082-03  
for NC CT wiring guidelines.  
C–C-Phase Current (IC)  
D–Ground-Fault Current (Ig)  
A
A
%
%
100  
40  
%
%
100  
40  
Return to A-Phase Current  
E–Neutral Current (In)  
A
A
%
%
%
%
100  
40  
100  
40  
© 1999–2012 Schneider Electric All Rights Reserved  
17-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 2—Ammeter  
48049-136-05  
Rev. 01, 07/2012  
Figure 18: Access the Peak Menu  
Current Menu  
Peak Menu  
Peak Menu  
To access the peak menu:  
Max  
menu  
1. Current menu is displayed.  
2. Press menu button.  
A
A
3. Peak menu appears.  
To access menu screens, press scroll button.  
%
%
100  
40  
%
%
100  
40  
The peak menu displays:  
Figure 19: Peak Menus  
A–Peak A-Phase Current (IpA)  
B–Peak B-Phase Current (IpB)  
A. Peak current (IpA) in A phase  
B. Peak current (IpB) in B phase  
C. Peak current (IpC) in C phase  
Max  
A
Max  
A
D. Peak ground-fault current (Ipg) (Micrologic  
6.0A trip unit only)  
E. Peak neutral current (Ipn)  
To display next peak current, press scroll button.  
%
%
100  
40  
%
%
100  
40  
To reset a max value, scroll to the particular max  
value screen to be reset and hold the scroll  
button for three seconds.  
C–Peak C-Phase Current (IpC)  
D–Peak Ground-Fault Current (Ipg)  
Max  
A
Max  
A
%
%
%
%
100  
40  
100  
40  
E–Peak Neutral Current (Ipn)  
Return to Peak A-Phase Current  
Max  
A
Max  
A
%
%
%
%
100  
40  
100  
40  
18-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 2—Ammeter  
Figure 20: Access the Switch Settings Menu  
Switch Settings Menu  
Peak Menu  
Switch Settings Menu  
The switch settings menu displays the values at  
which the switches are set.  
Max  
menu  
Ir=  
A
A
To access the switch settings menu:  
1. Peak menu is displayed.  
2. Press menu button.  
3. Switch settings menu will appear.  
To access menu screens, press scroll button.  
%
100  
%
100  
The switch settings menu displays:  
Figure 21: Trip Unit Switch Settings  
A–Ir Setting  
A. Long-time pickup (Ir) setting  
B. Long-time delay (tr) setting  
C. Short-time pickup (Isd) setting  
D. Short-time delay (tsd) setting  
E. Instantaneous pickup (Ii) setting  
B–tr Setting  
tr=  
s
Ir=  
A
F. Ground-fault pickup (Ig) setting (6.0A trip  
units only)  
G. Ground-fault delay (tg) setting (6.0A trip  
units only)  
C–Isd Setting  
D–tsd Setting  
tsd=  
Isd=  
s
A
To display next switch setting, press scroll  
button.  
E–Ii Setting  
F–Ig Setting  
Ii=  
A
A
Ig=  
G–tg Setting  
A–Ir Setting  
s
Ir=  
A
tg=  
To return to the current menu:  
Figure 22: Return to Current Menu  
1. Switch settings menu is displayed.  
2. Press menu button.  
Switch Settings Menu  
Current Menu  
menu  
3. Current menu will appear.  
Ir=  
A
A
Or wait several seconds and ammeter will  
automatically return to the current (i.e., default)  
menu.  
%
%
100  
100  
© 1999–2012 Schneider Electric All Rights Reserved  
19-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 3—Operation  
48049-136-05  
Rev. 01, 07/2012  
Section 3—Operation  
Figure 23: Adjust Switch Settings  
Switch Setting Adjustment  
1. Open switch cover (A).  
2. Adjust the appropriate switches (B) to  
desired values.  
3. Replace switch cover. Use wire seal  
MICROTUSEAL (C, not provided), if  
necessary, to provide tamper evidence.  
A
C
B
Figure 24: Circuit Breaker Rating  
Examples  
Circuit breaker is rated 2000 A.  
In 2000 A  
Figure 25: Set Pickup Levels  
Micrologic 2.0A Trip Unit  
In = 2000 A  
long time  
1. Set pickup levels.  
alarm  
Ir  
.8  
.7  
.9  
.95  
.98  
t
Ir = 0.7 x In = 1400 A  
Isd = 2 x Ir = 2800 A  
.6  
.5  
.4  
1
x In  
instantaneous  
Isd  
4
5
3
2.5  
2
6
8
10  
1.5  
x Ir  
setting  
0
Ir  
Isd  
20-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 3—Operation  
2. Set time delay.  
Figure 26: Set Time Delay  
tr = 1 s (at 6 x Ir)  
long time  
alarm  
tr  
(s)  
8
4
12  
16  
20  
24  
2
1
t
.5  
@ 6 Ir  
1 s  
tr  
0
I
Figure 27: Set Pickup Levels  
Micrologic 3.0A Trip Unit  
In = 2000 A  
long time  
alarm  
Ir  
1. Set pickup levels.  
.8  
.7  
.9  
.95  
.98  
Ir = 0.7 x In = 1400 A  
Ii = 3 x In = 6000 A  
t
.6  
.5  
Ir  
.4  
1
x In  
instantaneous  
Ii  
5
6
4
3
2
8
10  
12  
1.5  
setting  
x In  
Ii  
0
I
2. Set time delay.  
Figure 28: Set Time Delay  
tr = 1 s (at 6 x Ir)  
long time  
alarm  
tr  
8
(s)  
4
12  
16  
20  
24  
2
1
t
.5  
@ 6 Ir  
1 s  
tr  
0
I
Figure 29: Set Pickup Levels  
Micrologic 5.0A Trip Unit  
In = 2000 A  
long time  
1. Set pickup levels.  
alarm  
Ir  
.8  
.7  
.9  
.95  
.98  
Ir = 0.7 x In = 1400 A  
Ii = 6 x In = 12000 A  
Isd = 2 x Ir = 2800 A  
t
.6  
.5  
Ir  
.4  
1
x In  
short time  
instantaneous  
Isd  
I i  
8
4
5
6
10  
12  
15  
off  
x In  
3
2.5  
2
4
3
6
8
Isd  
2
1.5  
10  
off  
x Ir  
setting  
Ii  
0
I
© 1999–2012 Schneider Electric All Rights Reserved  
21-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 3—Operation  
48049-136-05  
Rev. 01, 07/2012  
2. Set time delay.  
Figure 30: Set Time Delays  
long time  
tr = 1 s (at 6 x Ir)  
alarm  
tr  
(s)  
8
4
12  
16  
20  
24  
2
1
t
2
tsd = 0.2 s I t on  
.5  
@ 6 Ir  
short time  
tr  
tsd  
1 s  
.
4
.
4
.3  
.
.
2
1
I2t on  
I2t off  
.
3
2
.
.
1
0
2
on  
I
t
tsd  
delay  
0.2 s  
0
Figure 31: Set Pickup Levels  
Micrologic 6.0A Trip Unit  
t
Ir  
1. Set pickup levels.  
long time  
alarm  
Ir  
.8  
.7  
.9  
.95  
.98  
In = 2000 A  
.6  
.5  
Ir = 0.7 x In = 1400 A  
.4  
1
Isd  
x In  
short time  
instantaneous  
Is  
I
4
8
3
5
6
10  
12  
Ii = 6 x In = 12000 A  
Isd = 2 x Ir = 2800 A  
Ii  
2.5  
2
6
8
4
3
15  
off  
1.5  
1
2
0
t
I
x Ir  
x In  
setting  
Ig  
E
D
F
G
BIg = 640 A  
C
H
B
J
A
ground fault  
Ig  
0
t
I
2. Set time delays.  
Figure 32: Set Pickup Levels  
long time  
tr  
alarm  
tr  
1 s  
8
(s)  
tr = 1 s (at 6 x Ir)  
4
12  
16  
20  
24  
2
1
.5  
@ 6 Ir  
tsd  
0.2 s  
short time  
instantaneous  
tsd  
.4 .4  
.3.2  
2
(s)  
tsd = 0.2 s I t on  
.3  
.2  
.1  
0
I
.1  
0
off  
2
I2t on  
I2t off  
on  
I
t
delay  
tg  
(s)  
.4 .3  
t
.4  
.3  
.2  
.1  
on  
.2  
.1  
2
0
2
off  
tg = 0.2 s I t on  
I
t
ground fault  
tg  
0.2 s  
0
I
22-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 3—Operation  
Table 8:  
ZSI Combinations  
Zone-Selective Interlocking (ZSI)  
The number of devices which can be interlocked  
are shown in Table 8.  
Upstream Device  
(receives input from RIM)  
Downstream Device  
(sends output to RIM)  
Micrologic #.0x Trip Units  
15  
R
R
R
R
15  
R
15  
R
R
26  
15  
Square D Micrologic Series B Trip Units  
Square D GC-100 Ground-Fault Relay  
for Equipment Protection  
R
R
R
7
R
R
R
R
Square D GC-200 Ground-Fault Relay  
for Equipment Protection  
15  
R
15  
15  
15  
15  
R
R
R
R
15  
15  
15  
15  
R
R
Merlin Gerin STR58 Trip Units  
Merlin Gerin STR53 Trip Units  
Federal Pioneer USRC and USRCM Trip  
Units  
R
R
15  
5
R
R
R
R
R
R
15  
R
Square D Add-On Ground Fault Module  
for Equipment Protection  
R—RIM module is required to restrain any devices.  
Numerical References—Maximum number of upstream circuit breakers which can be restrained  
without requiring a RIM Module.  
Circuit breaker terminals are shipped with  
terminals Z3, Z4 and Z5 jumpered to self-  
restrain the short-time and ground-fault  
functions. Remove the jumpers when activating  
zone-selective interlocking.  
Figure 33: Jumpered Terminals  
UC1  
Z5  
Z3  
Z1  
M1  
Z4  
Z2  
Auxiliary Connections  
© 1999–2012 Schneider Electric All Rights Reserved  
23-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 3—Operation  
48049-136-05  
Rev. 01, 07/2012  
Wire circuit breakers for zone-selective  
interlocking.  
Figure 34: ZSI Wiring Example  
UC1  
Z5  
M1  
Z4  
Z2  
Z3  
Z1  
UC1  
Z5  
Auxiliary  
M1  
Z4  
Z2  
Connections 1  
Z3  
Z1  
UC1  
Secondary  
Connector  
Position  
Auxiliary  
Connections 2  
Z5  
M1  
Z4  
Z2  
Z3  
Z1  
Description  
ZSI out signal  
ZSI out  
ZSI in signal  
ZSI in short time  
ZSI in ground fault  
Z1  
Z2  
Z3  
Z4  
Z5  
Auxiliary  
Connections 3  
Figure 35: Access Communication Module Menu  
Communication Module values  
Current Menu  
Communications Address  
If the optional circuit breaker communication  
module (BCM) is installed, use the ammeter to  
set communication module values.  
menu  
A
To access the communication module menu:  
1. Current menu is displayed.  
2. Simultaneously press both menu button and  
scroll button down for three seconds.  
%
100  
%
100  
3. Communication module addressing menu  
will appear.  
24-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 3—Operation  
Set communication module values:  
Figure 36: Set Communication Module Values  
Communications Address  
1. Press and release scroll button to sequence  
addresses (1 through 47). When the correct  
address number is reached, enter the value  
by pressing and holding scroll button until  
the display stops flashing.  
Baud Rate  
Baud rate screen will appear after address  
has been entered.  
2. Press and release scroll button to sequence  
baud rates (4.8k, 9.6k or 19.2k). When the  
desired baud rate appears, enter the value  
by pressing and holding scroll button until  
the display stops flashing.  
Parity  
Baud Rate  
Parity screen will appear after baud rate has  
been entered.  
Language  
3. Press and release scroll button to sequence  
parities (E [even] or n [none]). When the  
desired parity appears, enter the value by  
pressing and holding scroll button until the  
display stops flashing.  
Parity  
Languages screen will appear after parity  
has been entered.  
4. Press and release scroll button to scroll  
through languages (French [Fr], US English  
[En US], UK English [En], German [d],  
Spanish [SP] or Italian [It]). When the  
desired language appears, enter the value  
by pressing and holding scroll button until  
the display stops flashing.  
Language  
Ammeter display will return to the default  
screen after language is entered.  
After the communication module values have  
been set, ammeter will automatically return to  
the current (i.e., default) menu.  
After setting circuit breaker communication  
module values, drawout circuit breakers must  
have the cradle communication module, if  
available, activated. For drawout circuit  
breakers, refer to the cradle communication  
module instructions to complete setup.  
© 1999–2012 Schneider Electric All Rights Reserved  
25-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 3—Operation  
48049-136-05  
Rev. 01, 07/2012  
Table 9:  
Trip Unit Settings  
Window  
Trip Unit Settings Check  
Setting  
2.0A 3.0A 5.0A 6.0A  
Use the ammeter switch setting menu to check  
the trip unit settings.  
menu  
menu  
1. Press menu button twice.  
2. Switch settings menu will appear.  
3. Press scroll button to advance to next  
screen.  
4. After checking trip unit settings, press menu  
button once to return to main menu.  
Long-Time  
Ir  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Ir=  
Pickup  
A
tr=  
Long-Time  
Delay  
s
tr  
Isd=  
Short-Time  
Pickup  
Isd  
tsd  
Ii  
A
tsd=  
s
Short-Time  
Delay  
Instantaneous  
Pickup  
X
Ii=  
A
Ground-Fault  
Pickup  
Ig  
tg  
A
s
Ig=  
Ground-Fault  
Delay  
tg=  
Figure 37: Verify Trip Unit Operation  
Trip Unit Operation Verification  
Use a test kit connected to the trip unit test plug  
receptacle (A) to verify trip unit is functioning as  
desired. See instructions shipped with test kit to  
perform verification tests.  
A
26-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 3—Operation  
NOTE: Trip unit must be powered to test ground-fault trip function. The trip  
unit is powered if the circuit breaker is carrying more than 0.20 x In of load  
current, if the 24 Vdc external power supply is connected or if the Full-  
Function Test Kit or Hand-Held Test Kit is connected and on.  
Equipment Ground-Fault Trip  
Functions Testing  
Paragraph 230-95 (c) of the National Electrical  
Code requires that all equipment ground-fault  
protection systems be tested when first installed.  
Figure 38: Test Equipment Ground-Fault Trip Function  
With the circuit breaker closed, test the ground-  
fault (Micrologic 6.0A trip unit only) trip  
6.0  
A
ic  
log  
o
icr  
M
functions. For instructions on how to close circuit  
breaker, refer to the circuit breaker installation  
instructions shipped with the circuit breaker.  
%
0
0
0
1
%
4
1. Press the ground-fault test button (A). Circuit  
breaker should trip.  
2. If circuit breaker does not trip, contact the  
local field office.  
u
men  
A
Figure 39: Reset Trip Unit  
Trip Unit Resetting  
A
Micrologic 6.0 A  
When the circuit breaker trips, the fault indicator  
will remain lit until the trip unit is reset.  
Press the reset/test button (A) to reset the trip  
unit after trip.  
Do not return circuit breaker to service until cause  
of trip is determined. For more information, refer  
to the circuit breaker installation instructions  
shipped with the circuit breaker.  
NOTE: Trip unit must be powered to test battery. The trip unit is powered if  
the circuit breaker is carrying more than 0.20 x In of load current, if the 24  
Vdc external power supply is connected or if the Full-Function Test Kit or  
Hand-Held Test Kit is connected and on.  
Trip Unit Status Check  
To check trip unit battery and trip indicators,  
press the test/reset button (A).  
Figure 40: Check Trip Unit Status  
B
Charged  
A
All trip indicators (B) will light up  
Battery status will be displayed  
If no battery status is displayed, there is no  
battery installed.  
Half-Charged  
Micrologic 6.0 A  
Change Battery  
The battery bar graph reading is valid after  
the reset button has been released.  
If the battery bar graph shows the battery  
needs to be changed, use Square D battery  
catalog number S33593:  
— lithium battery  
— 1.2AA, 3.6 V, 800 ma/h  
For instructions on replacing battery, see  
Section 6—Battery Replacement.  
© 1999–2012 Schneider Electric All Rights Reserved  
27-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 4—Trip Unit Replacement  
48049-136-05  
Rev. 01, 07/2012  
Section 4—Trip Unit Replacement  
Trip unit replacement must be done by qualified  
persons, as defined by the National Electric  
Code, who are familiar with the installation and  
maintenance of power circuit breakers.  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Failure to follow these instructions for installation, trip test and primary  
injection testing may result in the failure of some or all protective function.  
• Apply appropriate personal protective equipment (PPE) and follow safe  
electrical work practices. See NFPA 70E or CSA Z462.  
• Replacement/upgrading of a trip unit in the field must be done by  
qualified persons, as defined by the National Electric Code, who are  
familiar with the installation and maintenance of power circuit breakers.  
Before replacing trip unit, confirm that the circuit  
breaker is in good working condition. If the  
condition of the circuit breaker is unknown, do  
not proceed. For assistance in evaluating the  
condition of the circuit breaker, call Technical  
Support.  
Read this entire section before starting the  
replacement procedure.  
• Before replacing/upgrading trip unit, confirm that the circuit breaker is in  
good working condition. If the condition of the circuit breaker is unknown,  
do not proceed. For assistance in evaluating the condition of the circuit  
breaker, call Technical Support.  
• If the circuit breaker fails to function properly in any manner upon  
completion of the trip unit installation, immediately remove the circuit  
breaker from service and call Field Services.  
NOTE: If trip unit being replaced is a Micrologic  
2.0, 3.0 or 5.0 trip unit, order connector block  
S33101 and circuit breaker or cradle wiring  
harness if necessary.  
• Turn off all power supplying this equipment before working on or inside  
equipment. Follow instructions shipped with circuit breaker to disconnect  
and reconnect circuit breaker.  
• Replace all devices, doors and covers before returning equipment to  
service.  
Failure to follow this instruction will result in death or serious injury.  
Required Tools  
Preparation  
Torque-controlled screwdriver, set at 7 in-lbs (0.8 N•m) 10%  
(Lindstrom torque driver MAL500-2 or equivalent)  
Micrologic Full-Function Test Kit (part number S33595)  
Record Switch Settings  
Record all trip unit switch settings for later use.  
Circuit Breaker Disconnection  
Disconnect circuit breaker as directed in the circuit breaker instruction  
bulletin shipped with the circuit breaker. The circuit breaker must be  
completely isolated. (For a drawout circuit breaker, place circuit breaker in  
the disconnected position. For a fixed-mounted circuit breaker, all voltage  
sources, including auxiliary power, must be disconnected.)  
Circuit Breaker Accessory Cover  
Removal  
Remove circuit breaker accessory cover as directed in the Install  
Accessories section of the circuit breaker instruction bulletin shipped with  
the circuit breaker.  
28-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 4—Trip Unit Replacement  
Figure 41: Remove Adjustable Rating Plug  
Rating Plug Removal  
B
C
A small Phillips screwdriver is needed to remove  
the adjustable rating plug.  
1. Open switch cover (A).  
m
ar  
al  
e
m
8
ti  
g
r
2
2. Unscrew adjustable rating plug mounting  
screw (B).  
on  
t
1
l
)
4
(s  
1
6
0
.8  
Ir  
.9  
.9  
.9  
2
1
.7  
2
4
5
8
2
.6  
.5  
s
u
eo  
n
ta  
.5  
6
I
r
@
an  
st  
in  
1
ous  
.
4
I
n
ane  
nt  
x
a
st  
i
I
4
5
in  
e
m
3
.5  
ti  
6
8
t
or  
4
.
.
3
I
i
sh  
t
sd  
4
5
.
4
2
.
.
2
e
3
m
6
8
ti  
d
rt  
4
Is  
4
2
1.  
.
.
3
sho  
5
3
.
.
.5  
2
0
1
4
2
1
.
3
3
6
8
5
.
2
.
1
m
alar  
2
In  
d
Is  
0
x
4
.5  
2
2
5
.
.
0
1
.
1
2
3
6
8
5
.
t
1
e
m
I
ti  
8
2
.
g
0
In  
t
r
2
1
n
.5  
0
x
1
o
y
2
lon  
.8  
a
.5  
d
el  
)
4
1
1
(s  
6
0
2
1
Ir  
x
2
1
t
y
ela  
Ir  
.9  
.95  
.98  
I
g
tt  
in  
0
2
1
1
n
se  
o
.7  
2
4
.5  
d
Ir  
x
2
.6  
.5  
.4  
ing  
ett  
.5  
Ir  
3. Remove adjustable rating plug (C). Save for  
installation in replacement trip unit.  
s
@
6
1
In  
x
A
Figure 42: Remove Existing Trip Unit  
A
Trip Unit Removal  
1. Remove connector block (A) from top of trip  
unit, if present.  
2. Loosen two trip unit screws (B).  
3. Slide out trip unit (C).  
B
C
Trip Unit Replacement  
NOTE: Battery holder with battery is located under the side flap in the  
cardboard box the trip unit is shipped in.  
Battery Installation  
If a new trip unit is being installed, install the trip  
unit battery.  
Figure 43: Install Battery  
Install battery holder with battery (A) in trip unit,  
observing the correct polarity as indicated on the  
battery compartment.  
A
Y
TRE  
LHTIUMBA  
36.VL-50/S  
OCSHEIN  
Press test/reset button (A). All four indicator  
lights (B) should light. If they do not light, check  
polarity of battery and retest. If indicator lights  
still do not light up when test/reset button is  
pressed, stop installation and contact the local  
sales office for factory authorized service  
Figure 44: Trip Indicator Lights  
B
A
Micrologic 6.0 A  
© 1999–2012 Schneider Electric All Rights Reserved  
29-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 4—Trip Unit Replacement  
48049-136-05  
Rev. 01, 07/2012  
Trip Unit Installation  
1. Inspect trip unit connector pins and surfaces.  
If there is any damage, misaligned pins, or  
contamination, stop installation and contact  
the local sales office for factory authorized  
service.  
2. Inspect trip unit mounting base on the circuit  
breaker. Clear any debris from area and  
check that all accessory wiring is properly  
routed for the trip unit being installed. If there  
is any damage or contamination, stop  
installation and contact the local sales office  
for factory authorized service.  
Figure 45: Install Trip Unit  
Masterpact NW Circuit Breaker  
3. For Masterpact NW circuit breaker only:  
Manually depress trip unit interlock (A) and  
hold it in place during steps 4–6 below.  
4. Align guide rail (B) on bottom of trip unit with  
guide rail slot (C) on trip unit mounting base  
in circuit breaker and gently slide the trip unit  
in until it stops.  
NOTE: The Masterpact NT and NW trip unit  
mounting bases are shock mounted and  
therefore can flex slightly.  
C
A
B
NOTICE  
HAZARD OF EQUIPMENT DAMAGE  
Check installation of trip unit to assure proper  
connections and seating.  
Failure to follow this instruction can result  
in equipment damage or improper circuit  
breaker tripping.  
30-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 4—Trip Unit Replacement  
5. Align the trip unit so top mounting screw (A)  
aligns with the top threaded insert and start  
the screw by turning the screw two full  
rotations.  
Figure 46: Install Trip Unit  
A
6. Use a torque-controlled screwdriver to drive  
the bottom screw (B) to 7 in-lbs (0.8 N•m)  
10%. The back of the trip unit must be flush  
with the trip unit mounting base.  
7. Use a torque-controlled screwdriver to drive  
the top screw to 7 in-lbs (0.8 N•m) 10%.  
Mounting tab must be flush with the mounting  
standoff and sensor plug.  
Must be  
seated  
7 lb-in  
[0.8 N•m]  
B
NOTE: The face of the closed switch cover must  
be flush with adjoining mounting base surfaces.  
If these surfaces are not flush, stop installation  
and contact the local sales office for factory  
authorized service.  
Must be flush  
C
NOTE: If you are upgrading from a Micrologic  
2.0, 3.0 or 5.0 trip unit, the connector block must  
be ordered separately (Part Number S33101).  
See instructions shipped with the connector  
block for installation into circuit breaker.  
8. Install connector block (C) into top of trip  
unit.  
9. Install adjustable rating plug into the trip unit.  
a. Open switch cover (A) on new trip unit.  
Figure 47: Install Adjustable Rating Plug  
C
b. Inspect mounting area for debris and  
contamination.  
c. Gently push adjustable rating plug (B)  
into new trip unit.  
d. Tighten adjustable rating plug mounting  
screw (C). The plug will be drawn into  
position flush with front face as screw is  
tightened.  
B
m
ar  
al  
e
m
ti  
8
g
n
r
2
t
1
lo  
4
6
0
(
s)  
1
.8  
Ir  
.9  
2
1
.7  
2
4
5
8
.9  
.9  
2
.6  
.5  
s
u
eo  
n
ta  
.5  
6
I
r
@
an  
st  
in  
1
.
4
I
n
x
i
I
4
5
us  
o
e
n
e
t
im  
3
6
8
ta  
n
t
r
ho  
d
.
4
ta  
.
3
s
t
s
ins  
.5  
.
4
2
.
.
2
d
Is  
i
I
4
4
2
1.  
5
5
.
.
3
1
10  
3
3
6
8
5
6
8
t
rt  
sho  
3
7 lb-in  
[0.8 N•m]  
t
.
2
0
x
In  
.5  
2
2.5  
2
1
.
.
1
2
t
2
1
m
d
lar  
2
1.  
Is  
4
a
I
d
e
5
3
10  
n
.
.
o
0
y
la  
1
5
3
6
8
5
.
Ir  
8
x
2
.
g
time  
In  
tr  
1
2
.5  
2
1
0
x
lon  
.8  
g
2
tt  
in  
1
st  
(s  
)
4
6
0
se  
2
te  
1
t
Ir  
.9  
.9  
.98  
I
10  
n
2
1
o
y
.7  
2
4
5
.5  
ela  
r
I
x
2
.6  
.5  
.4  
g
d
tin  
.5  
Ir  
6
set  
@
1
In  
x
A
A
10. Set trip unit switches to values recorded  
above or per coordination study results.  
11. Close switch cover (A).  
Circuit Breaker Accessory Cover  
Replacement  
Replace circuit breaker accessory cover as directed in the Install  
Accessories section of the circuit breaker instruction bulletin shipped with  
the circuit breaker.  
© 1999–2012 Schneider Electric All Rights Reserved  
31-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 4—Trip Unit Replacement  
48049-136-05  
Rev. 01, 07/2012  
Trip Unit Installation Check  
Field installation of a trip unit requires secondary injection testing with the  
Full-Function Test Kit. to ensure that the newly-installed trip unit is  
functioning properly. The test will require opening and closing the circuit  
breaker. Follow the procedures outlined in the instruction bulletins shipped  
with the circuit breaker and the test kit.  
Secondary Injection Testing  
1. Make sure the circuit breaker is isolated from all upstream and  
downstream devices.  
2. Perform secondary injection testing as outlined in the instruction bulletin  
shipped with the test kit. Verify that all applicable trip unit functions are  
operating properly.  
3. Repeat step 2 with the circuit breaker in the open position.  
NOTE: The test kit states that the circuit breaker should be closed when  
performing the test. Do not close the circuit breaker for this step.  
4. If any test fails, do not put the circuit breaker into service and contact the  
local sales office for factory authorization service.  
Primary injection testing is recommended to ensure that all trip system  
connections have been correctly made. Perform primary injection testing  
per the instructions in the Field Testing and Maintenance Guide, bulletin  
number 0600IB1201.  
Primary Injection Testing  
1. Installed accessories – Validate the proper operation of all installed  
accessories. See the corresponding accessory instruction bulletins for  
operational testing procedures.  
Check Accessory Operation  
2. Zone selective interlocking – If the circuit breaker is part of a ZSI system,  
follow the zone selective interlocking test procedures as outlined in the  
Full Function Test Kit instruction bulletin.  
3. Communications – If communication modules exist, validate circuit  
breaker has re-established communications with the supervisor.  
Trip Unit Setup  
1. If an auxiliary power supply is being used for the Micrologic trip unit,  
reconnect the auxiliary power supply.  
2. Reset the trip unit switches to original values, as recorded at the  
beginning of this section.  
Circuit Breaker Reconnection  
Reconnect circuit breaker as directed in the circuit breaker instruction  
bulletin shipped with the circuit breaker.  
32-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 5—Adjustable Rating Plug Replacement  
Section 5—Adjustable Rating Plug Replacement  
NOTE: To select correct replacement rating  
DANGER  
plug, see the product catalog.  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
NOTE: If adjustable rating plug is removed, the  
circuit breaker will default to a long-time pickup  
rating of 0.4 x In and a long-time delay at  
whatever setting was selected before the rating  
plug was removed.  
• Apply appropriate personal protective equipment (PPE) and follow safe  
electrical work practices. See NFPA 70E or CSA Z462.  
• This equipment must be installed and serviced only by qualified electrical  
personnel.  
• Turn off all power supplying this equipment before working on or inside  
equipment. Follow instructions shipped with circuit breaker to disconnect  
and reconnect circuit breaker.  
• Replace all devices, doors and covers before returning equipment to  
service.  
Failure to follow this instruction will result in death or serious injury.  
Figure 48: Remove Adjustable Rating Plug  
Rating Plug Removal  
B
C
1. Open circuit breaker contacts:  
— For Masterpact NT and NW circuit  
breakers, press the “Push to open”  
button on the circuit breaker.  
— For other circuit breakers, move handle  
to the off (O) position.  
m
ar  
al  
e
m
8
ti  
g
r
2
n
t
1
lo  
)
4
(s  
1
6
0
.8  
Ir  
.9  
.9  
.9  
2
1
.7  
2
4
5
8
2
.6  
.5  
.4 In  
s
u
eo  
n
ta  
.5  
6
I
r
@
an  
st  
in  
1
ous  
tane  
n
x
a
st  
i
I
4
5
in  
e
m
3
ti  
6
8
rt  
.
4
o
sd  
.
3
I
i
s
h
t
4
5
.5  
.
4
2
.
.
2
e
3
m
6
8
ti  
d
rt  
ho  
4
Is  
4
2
1.  
.
.
3
s
5
3
.
.
.5  
2
0
1
4
2
1
.
3
3
6
8
5
.
2
.
1
m
alar  
2
In  
d
Is  
0
x
4
.5  
2
2
5
.
.
0
1
.
1
2
3
6
8
5
.
t
1
e
m
I
ti  
8
2
.
g
0
In  
t
r
)
(s  
2
1
n
.5  
0
x
1
o
y
2
lon  
.8  
a
.5  
d
el  
4
1
1
2
16  
0
Ir  
x
se  
2
1
t
Ir  
.9  
.9  
.98  
I
g
tt  
in  
0
2
1
1
n
o
y
.7  
2
4
5
.5  
d
ela  
Ir  
x
2
.6  
.5  
.4  
ing  
tt  
.5  
Ir  
se  
@
6
1
In  
x
2. Open switch cover (A).  
3. Unscrew adjustable rating plug mounting  
screw (B).  
4. Remove adjustable rating plug (C).  
A
Figure 49: Install New Adjustable Rating Plug  
A
New Rating Plug Installation  
B
1. Inspect mounting area for debris and  
contamination.  
2. Gently push in new adjustable rating plug  
(A).  
3. Tighten adjustable rating plug mounting  
screw (B).  
m
ar  
al  
e
m
8
ti  
g
r
2
n
t
1
lo  
(
s)  
4
6
1
0
.8  
Ir  
.9  
.9  
.9  
2
1
.7  
2
4
5
8
2
.6  
.5  
.4  
s
u
eo  
n
ta  
I
r
.5  
6
@
an  
st  
in  
1
n
I
x
i
I
4
5
us  
o
e
3
e
n
6
8
ta  
t
t
im  
n
r
.
4
ta  
ho  
.
3
s
t
sd  
ins  
.5  
.
3
4
2
.
.
2
d
Is  
i
I
4
4
2
1.  
5
5
.
.
0
1
1
3
e
3
6
8
5
6
8
t
rt  
ho  
3
2
In  
s
.5  
2
0
x
.5  
2
.
1
2
t
2
.
1
m
d
3
lar  
2
1.  
Is  
4
2
1
a
I
d
e
5
3
10  
n
o
.
.
0
y
la  
1
5
6
8
.
5
Ir  
8
x
2
.
n
time  
In  
ng  
tr  
1
2
.5  
2
1.  
0
x
lo  
g
2
tt  
in  
1
st  
(s  
)
4
6
0
se  
2
te  
1
.8  
t
Ir  
.9  
.9  
.98  
I
2
1
10  
o
y
.7  
2
4
5
5
d
ela  
r
I
x
2
.6  
.5  
.4  
g
tin  
set  
.5  
Ir  
6
@
1
In  
x
4. Set the switches on the trip unit (see Section  
3 —Operation).  
5. Close switch cover (C).  
C
© 1999–2012 Schneider Electric All Rights Reserved  
33-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 6—Battery Replacement  
48049-136-05  
Rev. 01, 07/2012  
Section 6—Battery Replacement  
Circuit Breaker Disconnection  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
Disconnect circuit breaker as directed in the  
circuit breaker instruction bulletin shipped with  
the circuit breaker.  
• Apply appropriate personal protective equipment (PPE) and follow safe  
electrical work practices. See NFPA 70E or CSA Z462.  
• This equipment must be installed and serviced only by qualified electrical  
personnel.  
• Turn off all power supplying this equipment before working on or inside  
equipment. Follow instructions shipped with circuit breaker to disconnect  
and reconnect circuit breaker.  
Circuit Breaker Accessory Cover  
Removal  
Remove circuit breaker accessory cover as  
directed in the Install Accessories section of the  
circuit breaker instruction bulletin shipped with  
the circuit breaker.  
• Replace all devices, doors and covers before returning equipment to  
service.  
Failure to follow this instruction will result in death or serious injury.  
Figure 50: Shift Withstand Module  
Withstand Module Shifting  
NOTE: R-frame and NS1600b–NS3200 circuit  
breakers only.  
Loosen screws (A) securing withstand module  
(B). Swing module to side to access trip unit  
battery cover. Do not remove withstand module  
connector.  
B
A
Figure 51: Remove Battery Cover  
Battery Replacement  
1. Insert small screwdriver blade into battery  
housing cover notch and rotate to slide  
battery housing cover (A) out of trip unit.  
A
2. Remove battery (A).  
Figure 52: Replace Battery  
3. Insert new battery (B). Make sure that the  
polarity is correct.  
Y
Y
TRE  
TRE  
4. Replace battery housing cover (C).  
Y
TRE  
LHTIUMBA  
LHTIUMBA  
36.VL-50/S  
36.VL-50/S  
OCSHEIN  
OCSHEIN  
A
B
LHTIUMBA  
36.VL-50/S  
OCSHEIN  
C
34-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Section 6—Battery Replacement  
Figure 53: Replace Withstand Module  
Withstand Module Replacement  
NOTE: R-frame and NS1600b–NS3200 circuit  
breakers only.  
Replace withstand module (A). Tighten screws  
(B) securing withstand module.  
B
4.4 lb-in  
[0.5 N•m]  
A
Circuit Breaker Accessory Cover  
Replacement  
Replace circuit breaker accessory cover as directed in the Install  
Accessories section of the circuit breaker instruction bulletin shipped with  
the circuit breaker.  
Circuit Breaker Reconnection  
Reconnect circuit breaker as directed in the circuit breaker instruction  
bulletin shipped with the circuit breaker.  
© 1999–2012 Schneider Electric All Rights Reserved  
35-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Appendix A—Register List  
48049-136-05  
Rev. 01, 07/2012  
Appendix A—Register List  
To access available registers, the following address scheme applies.  
List of Registers  
Module  
Module Name  
Equation  
Address Range  
The quantities are listed in alphabetical order  
according to the SMS topic name.  
BCM  
CCM  
PM  
Circuit Breaker Communication Module --  
1–47  
Cradle Communication Module  
BCM + 50  
51–97  
NOTE: A system scan rate of 500 ms or greater  
is recommended to minimize communications  
timeout issues.  
Protection Module (Internal to trip unit) BCM + 100  
101–147  
201–247  
MM  
Meter Module (Internal to trip unit)  
BCM + 200  
This is an abbreviated list of registers. For a  
complete list of registers, contact your local  
sales office.  
Table 10:  
Register List  
Number of  
Registers*  
SMS Topic Name User Description  
Register* Module*Units  
Scale/Bitmask  
810DBrkrStatus  
810DBrkrTripStat  
BCM_SN  
Circuit Breaker Status  
1
1
4
661  
661  
516  
BCM  
BCM  
BCM  
Bit 0; ON = closed, OFF = open  
Bit 2; ON = tripped, OFF = not tripped  
ASCII text  
Circuit Breaker Trip Unit Status  
BCM Serial Number  
Bit 8 = disconnected  
Bit 9 = connected  
BkrPos  
Circuit Breaker Position  
1
661  
CCM  
Bit 10 = test position  
DT_3Regs  
Device Clock Date/Time  
Remote Closing Enabled  
Remote Opening Enabled  
3
1
1
679  
669  
669  
BCM  
BCM  
BCM  
3-register date/time format  
EnableCloseBkr  
EnableOpenBkr  
Bit 2; ON = enabled, OFF = not enabled  
Bit 1; ON = enabled, OFF = not enabled  
Bit 3; ON = auto (enabled),  
OFF = manual (not enabled)  
EnableRemCtrl  
Remote Control Enabled  
1
669  
BCM  
IA  
Current A  
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
8821  
8837  
8822  
8838  
8823  
8839  
8825  
8841  
8842  
8826  
8820  
8824  
8840  
8756  
8827  
8828  
8829  
8831  
8832  
8830  
8750  
661  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
PM  
BCM  
A
%
A
%
A
%
A
%
%
A
A
A
%
A
A
A
A
A
A
A
A
Unity  
IA_PCT  
IB  
Current A % Load  
Current B  
Unity  
Unity  
IB_PCT  
IC  
Current B % Load  
Current C  
Unity  
Unity  
IC_PCT  
IG  
Current C % Load  
Current G  
Unity  
Unity  
IG_PCT  
IG_PCT_VIGI  
IG_VIGI  
IMax  
Current G % Load  
Current G (VIGI) % Load  
Current G (VIGI)  
Current Max Present  
Current N  
Unity  
Hundredths  
Thousandths  
Unity  
IN  
Unity  
IN_PCT  
LDPUValue  
MaxIA  
Current N % Load  
Long Delay Pickup Value  
Max Current A  
Unity  
**  
Modulo 10,000 format  
Unity  
MaxIB  
Max Current B  
Unity  
MaxIC  
Max Current C  
Unity  
MaxIG  
Max Current G  
Unity  
MaxIG_VIGI  
MaxIN  
Max Current G (VIGI)  
Max Current N  
Thousandths  
Unity  
NominalCurrent  
ReadyToClose  
Circuit Breaker Nominal Current  
Circuit Breaker Ready to Close  
Unity  
Bit 5; ON = yes, OFF = no  
Continued on next page  
36-EN  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48049-136-05  
Rev. 01, 07/2012  
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Appendix A—Register List  
Table 10:  
Register List (continued)  
Number of  
Registers*  
SMS Topic Name User Description  
Register* Module*Units  
Scale/Bitmask  
TU_BATT_PCT  
TU_SN  
Trip Unit % Battery  
1
4
1
8843  
8700  
552  
PM  
%
Unity  
Trip Unit Serial Number  
Trip Unit Internal Comms Status  
PM  
ASCII text  
TUCommStatus  
BCM  
Bit 11; ON = not responding, OFF = OK  
*
For register entries that are not listed, please refer to the Micrologic device type register list. Contact your local sales office.  
BCM = Circuit breaker communication module. CCM = Cradle communication module. PM = Trip unit protection module.  
3-register date/time format: register 1: month (byte 1) = 1–12, day (byte 2) = 1–31; register 2: year (byte 1) = 0–199 (add to 1900 to determine the actual year), hour  
(byte 2) = 0–23; register 3: minutes (byte 1) = 0–59, seconds (byte 2) = 0–59. Note: Bits 14 and 15 of the month/day register must be masked.  
**  
Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = –9,999 to +9,999). Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1]  
+ R1. Range is zero to 9,999,999,999,999,999.  
© 1999–2012 Schneider Electric All Rights Reserved  
37-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Micrologic® 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units  
Instruction Bulletin  
Electrical equipment should be installed, operated, serviced, and maintained only by qualified  
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of  
the use of this material.  
Square D™, Schneider Electric™, Micrologic™, Modbus, and Masterpact™ are trademarks or  
registered trademarks of Schneider Electric. Other trademarks used herein are the property of  
their respective owners.  
Schneider Electric  
3700 Sixth St SW  
Cedar Rapids, IA 52404 USA  
1-888-778-2733  
48049-136-05 Rev. 01, 07/2012  
Replaces 48049-136-05 ECN 725D, 07/2008  
© 1999–2012 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  

RCA Microwave Oven RMW743 User Guide
RCA Telephone 2 9480 User Guide
Roland Musical Instrument HP201 User Guide
Samsung Air Conditioner AM18B1C09 User Guide
Samsung Refrigerator DA99 01906A User Guide
Samsung Tablet SM P6000ZWYX User Guide
Sanyo CRT Television DS27425, DS32225 User Guide
Sanyo Digital Camera VPC E890 User Guide
Sanyo Vacuum Cleaner SC X90 User Guide
Seagate TV Cables 77767496 User Guide