Sanyo Refrigerator CHDX07263 User Guide

SERVICE MANUAL  
2-WAY ECO-i  
MULTI SYSTEM  
CHDX07263  
CHDXR07263*  
CHDX09663  
CHDXR09663*  
Outdoor Units  
Class  
ECO-i W-2WAY  
72  
96  
CHDX07263  
CHDXR07263  
CHDX09663  
CHDXR09663  
C
*
*
Refrigerant R410A is used in the outdoor units.  
* Salt-Air Damage Resistant Specifications.  
Indoor Units  
Class  
7
9
12  
15  
18  
19  
24  
36  
48  
54  
4-Way Air Discharge  
Semi-Concealed  
4-Way Air Discharge  
Mini Semi-Concealed  
1-Way Air Discharge  
Semi-Concealed  
X
XM  
A
XHX1252  
XHX1852  
XHX2452 XHX3652  
XMHX1252  
AHX0752 AHX0952 AHX1252  
XMHX1852  
U
Concealed Duct Type UHX0762 UHX0962 UHX1262 UHX1562 UHX1862  
UHX2462 UHX3662 UHX4862 UHX5462  
Slim Concealed  
UM  
D
UMHX0762UMHX0962UMHX1262UMHX1562UMHX1862  
Duct Type  
Concealed-Duct High  
Static Pressure  
DHX3652 DHX4852  
THX2452  
T
Ceiling-Mounted  
THX1252  
THX1852  
K
Wall-Mounted Type  
KHX0752 KHX0952 KHX1252  
KHX1862 KHX1962**KHX2452  
F
Floor-Standing Type FHX0762 FHX0962 FHX1262 FHX1562 FHX1862  
Concealed-Floor  
FHX2462  
FMHX0762  
FMHX0962  
FMHX1262 FMHX1562  
FMHX2462  
FMHX1862  
FM  
Standing Type  
** Necessary to install the External Electronic Expansion Valve Kit (Optional:ATK-SVRK56BA).  
85464849280000  
REFERENCE NO.  
SM830180-00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check of Density Limit  
The room in which the air conditioner is to be  
installed requires a design that in the event of refrig-  
erant gas leaking out, its density will not exceed a set  
limit.  
The refrigerant (R410A), which is used in the aircondition-  
er, is safe, without the toxicity or combustibility of ammonia,  
and is not restricted by laws imposed to protect the ozone  
layer. However, since it contains more than air, it poses the  
risk of suffocation if its density should rise excessively. Suf-  
focation from leakage of refrigerant is almost non-existent.  
With the recent increase in the number of high density  
buildings, however, the installation of multi air conditioner  
systems is on the increase because of the need for effec-  
tive use off loor space, individual control, energy conserva-  
tion by curtailing heat and carrying power, etc.  
Most importantly, the multi air conditioner system is able  
to replenish a large amount of refrigerant compared to  
conventional individual air conditioners. If a single unit of  
the multi air conditioner system is to be installed in a  
small room, select a suitable model and installation pro-  
cedure so that if the refrigerant accidentally leaks out, its  
density does not reach the limit (and in the event of an  
emergency, measures can be made before injury can  
occur).  
ASHRAE and the International Mechanical Code of the  
ICC as well as CSA provide guidance and define safe-  
guards related to the use of refrigerants, all of which define  
a Refrigerant Concentration Level (RCL) of 25 pounds  
per 1,000 cubic feet for R410A refrigerant.  
For additional guidance and precautions related to  
refrigerant safety, please refer to the following documents:  
International Mechanical Code 2009 (IMC-2009)  
(or more recently revised)  
ASHRAE 15  
ASHRAE 34  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTENTS  
Section 1: CONTROL FUNCTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1  
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2  
2. Selecting Outdoor Unit for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3  
3. Compressor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4  
4. Special Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9  
5. Other Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14  
6. Operation of Solenoid Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15  
7. Outdoor Unit Electronic Thermostatic Expansion Valves [MOV1, MOV2 & MOV4] . . . . . 1-17  
8. Outdoor Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-19  
9. Demand Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-20  
10. Indoor Unit Control of the Electronic Control Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-21  
11. Rap Valve Kit Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23  
12. Indoor Unit Refrigerant Oil Self Recovery Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-24  
13. Discharge Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-25  
14. Current Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-26  
15. Pressure Sensor Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-27  
16. Backup Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-28  
17. Service Maintenance Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-30  
18. Other Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-32  
Section 2: OUTDOOR UNIT REPAIR PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1  
1. Removing Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2  
2. Removing Electrical Component Box and Duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3  
3. Discharging Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5  
4. Backup Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6  
5. Recovering Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9  
6. Checking for Leakage After Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14  
7. Evacuating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15  
8. Charging Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16  
9. Pumping Out Refrigerant from Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20  
10. Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23  
11. High and Low Pressure Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-35  
12. Replacing 4-way Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-36  
Section 3: OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER . . . . . . . . . . . . 3-1  
1. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2  
2. Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3  
3. Ordinary Display Controls and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4  
4. Monitoring Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9  
5. Outdoor Unit Alarm History Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11  
6. Mode Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12  
Section 4: REMOTE CONTROLLER FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1  
1. Simple Settings Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2  
2. Detailed Settings Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4  
3. Remote Controller Servicing Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5: TROUBLE DIAGNOSIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1  
1. Contents of Remote Controller Switch Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2  
2. Outdoor Unit Control Panel LED Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4  
3. Remote Controller Servicing Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5  
4. W-2WAY ECO-i Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7  
5. Blinking Inspection Display on the Remote Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-27  
6. Inspection of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28  
7. Test Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29  
8. Thermister Characteristics Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
Contents  
1. CONTROL FUNCTIONS  
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2  
2. Selecting Outdoor Unit for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3  
3. Compressor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4  
4. Special Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9  
5. Other Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14  
6. Operation of Solenoid Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15  
7. Outdoor Unit Electronic Thermostatic Expansion Valves [MOV1, MOV2 & MOV4] . . . 1-17  
8. Outdoor Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-19  
9. Demand Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-20  
10. Indoor Unit Control of the Electronic Control Valve . . . . . . . . . . . . . . . . . . . . . . . . . 1-21  
11. Rap Valve Kit Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23  
12. Indoor Unit Refrigerant Oil Self Recovery Control . . . . . . . . . . . . . . . . . . . . . . . . . . 1-24  
13. Discharge Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-25  
14. Current Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-26  
15. Pressure Sensor Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-27  
16. Backup Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-28  
17. Service Maintenance Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-30  
18. Other Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-32  
1
1 - 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
1. Introduction  
The W-2WAY ECO-i is a system that allows multiple outdoor units to be connected. The outdoor units all contain  
inverter compressors, and the system does not utilize the sub units that were used in earlier systems.  
The outdoor unit where the unit No. is set to “1” includes the CCU (command controller unit) functions that are  
used to control the entire system. As a result, the system will not operate if no outdoor unit has been set as unit  
No. “1.”  
Required settings for Test Run  
Outdoor unit No.1  
On-site setting  
Outdoor unit No. 2  
1
On-site setting  
Not necessary  
At time of shipment  
At time of shipment  
1
System address  
No. of indoor units  
No. of outdoor units  
Unit No.  
1
System 1 ~ 30  
1 ~ 40 units  
1 ~ 3 units  
Not necessary  
Not necessary  
Unit No. 2  
1
1
1
1
1
1
Unit No. 1  
This system can be expanded to connect a maximum of 3 outdoor units. (The max. system capacity shall be within  
24 Ton.)  
The CCU functions are disabled at all units except the unit that is set as unit No. 1. Therefore no problems will  
result even if the system address, No. of indoor units, and No. of outdoor units settings are made at the other units.  
However, making these settings may be convenient for manual backup operation, as it eliminates the necessity of  
making the settings again if unit No. 1 fails.  
1 - 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
2. Selecting an Outdoor Unit for Operation  
2-1. Outdoor Unit Operating Rules  
Because in this system all outdoor units contain an inverter compressor, ordinarily there is no absolute order of  
priority for compressor operation. Therefore there is no order of priority for the outdoor units.  
However, it is possible to operate the outdoor units in sequence, beginning with unit No. 1, by using the outdoor  
unit maintenance remote controller to change the outdoor unit EEPROM settings.  
* For information concerning EEPROM settings, refer to the field application functions.  
1
2-2. Delayed Start of Outdoor Units  
(1) Delayed start of outdoor units in the same system  
If it is necessary to operate the compressors simultaneously at multiple outdoor units, each outdoor unit will  
start, beginning with unit No. 1, after a delay of a number of seconds equivalent to the outdoor unit address.  
The units do not start simultaneously.  
This is in order to reduce the load on the power receiving equipment.  
Outdoor unit  
address 1  
Outdoor unit  
address 2  
Starts after 1 second  
Starts after 2 seconds  
(2) Delayed start for each system  
At the time of factory shipment, delayed start for each system is not set to occur. Therefore when systems are  
linked and multiple systems are selected for start simultaneously by the central control device, all systems will  
begin operating simultaneously. For this reason, a function is included to delay the start time for each system  
address when systems are linked and multiple systems are selected for start by the central control device.  
In order to enable this delay time, it must be set in the EEPROM for each system. Those systems where this  
setting has been made will start after a delay according to their system addresses.  
* For information concerning EEPROM settings, refer to the field application functions.  
2-3. Outdoor Unit Stop Rules  
(1) Simultaneous stop of multiple outdoor units  
When all outdoor units, or multiple outdoor units, must stop, the units stop at the same time. However, depend-  
ing on the communications timing, a difference of approximately 10 seconds may occur.  
(2) Stopping individual outdoor units  
The last unit to stop operating is the outdoor unit that contains the inverter compressor with the shortest  
amount of operating time.  
In cooling mode, all inverter compressors in the outdoor units are designed to operate simultaneously.  
Therefore, all the outdoor units will stop at a time when any one unit is stopped. In heating mode, the out-  
door unit which has the inverter compressor with the shortest amount of operating time continues to run and  
rest of the other outdoor units may be stopped.  
1 - 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
3. Compressor Control  
3-1. Compressors Mounted in the Outdoor Units  
[CHDX07263, CHDX09663]  
Capacity  
72  
96  
DC Inverter  
DC Inverter  
Compressor 1  
Rotary  
Scroll  
Installed  
compressor  
Compressor 2  
5 hp  
–––  
hp = horsepower  
1
Constant  
speed INV  
INV  
Compressor 2  
Compressor 1  
Type 72  
Compressor 1  
Type 96  
3-2. Compressor Selection Rules  
In cooling mode, all inverter compressors in the outdoor units are designed to operate simultaneously. All the  
inverter compressors will stop at a time when the outdoor is stopped accordingly. Constant-speed compressors  
run in order of the shortest amount of operating time. In heating mode, the inverter compressor with the shortest  
amount of operating time runs at first followed by the compressors in order of the shortest amount of operating  
time including inverter units.  
* Immediately after installation, all compressors have an operating time of zero. In this case, the compressors  
start in the following sequence: Inverter compressor > Constant-speed compressor 1 > Constant-speed com-  
pressor 2.  
Examples of accumulated operating time: ODU=Outdoor Unit  
Suppose the following tentative system.  
ODU 1  
100 hrs.  
150 hrs.  
ODU 2  
70 hrs.  
Comp 1  
Comp 2  
160 hrs.  
Compressor Selection Sequence in Cooling Mode:  
All the inverter compressors are firstly selected simultaneously.  
ODU 1  
1st  
ODU 2  
1st  
Comp 1  
Comp 2  
3rd  
4th  
Compressor Selection Sequence in Heating Mode:  
First, the inverter compressor with the shortest amount of operating time is selected. And then, the remained  
other compressors are selected and start in the order of shortest amount of operating time  
.
ODU 1  
3rd  
ODU 2  
1st  
Comp 1  
Comp 2  
4th  
2nd  
1 - 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
3. Compressor Control  
3-3. Compressor Capacity Control  
The compressor operating conditions vary depending on the indoor unit operating conditions and the effects of  
indoor heat load, outdoor temperature and other factors. Unit No. 1 (CCU) calculates the required capacity accord-  
ing to these operating conditions, and allocates the capacity requirement among the outdoor units, according to the  
compressor start/stop rules. Fine adjustments to system capacity control are made by the inverter compressors.  
(Depending on the conditions, all inverter compressors may be operating for fine adjustment.)  
3-4. Inverter Compressor Capacity Control  
1
(1) The inverter compressor has a center limit value and upper limit value for the operating frequency. These limits  
are set for each outdoor unit capacity.  
(2) The inverter frequency during operation may be lower than the frequency listed above due to overload current  
protection control.  
* If Quiet mode is selected, the inverter may stabilize at a frequency lower than those stated above.  
For information about Quiet mode, refer to the field application functions.  
* If the Power Demand Mode is selected, the inverter may stabilize at a frequency lower than those stated  
above. Refer to the Field Application Function for the detail.  
3-5. Forced Compressor Stop  
Once a compressor stops, it will not start for a period of 3 minutes (3-minute forced OFF). However, this does not  
apply when the compressor was forced to stop as the result of a control operation during the special controls (start  
control, defrost control, refrigerant oil recovery control, etc.) which are described later.  
3-6. Roadmap Control  
(1) The below mentioned Roadmap Control are performed according to the pressure sensor on the outdoor unit,  
and the 2 temperature sensors attached to the indoor unit heat exchanger coil.  
* With the roadmap control in heating mode, the pressure detected by the pressure sensor at high pressure  
side is converted to the saturation temperature. This converted saturation temperature is called the “High  
Pressure Saturated Temperature”.  
(2) This control is performed every 15 seconds.  
(3) The evaporation temperature control and the temperature used to determine the area (A, AB, B, C) for the con-  
densation control shown in the figure on the next page, may vary depending on the relationships among factors  
including the difference between the room temperature setting and the air intake temperature (=air intake tem-  
perature difference) and the difference between the air discharge temperature setting and the air discharge  
temperature (=air discharge temperature difference).  
(4) Definitions of evaporation temperature and condensation temperature  
Evaporation temperature (Te): Lowest heat exchanger temperature (E1, E3) at any indoor unit  
Condensation temperature (Tc): Highest temperature among the outdoor unit pressure sensor temperature and  
the heat exchanger temperatures (E1) at all indoor units where the heating  
thermostat is ON.  
Ordinarily, this is the outdoor unit pressure sensor temperature. (If multiple  
outdoor units are connected, this is the highest outdoor unit pressure sensor  
temperature. )  
* E3 temperature in heating mode is not used for the condensation temperature detection, because it may indi-  
cate the temperature of superheated gas.  
1 - 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
3. Compressor Control  
3-6-1. Evaporation Temperature (Te) Control: Control of Indoor Units Operating in Cooling Mode  
60.8  
°F  
Horsepower increase  
53.6  
permitted  
Area A  
51.9  
51.8  
51.8  
Horsepower increase  
permitted  
Area AB  
1
45.5  
41.1  
41.0  
41.0  
35.6  
Horsepower increase  
prohibited  
Area B  
Area C  
35.6  
35.4 Horsepower decrease  
30  
0
15  
Maximum requirement level [L]  
* Depending on the maximum requirement level of the indoor unit, the judgement  
temperatures for each area may vary as shown in the figure.  
(1) For indoor units that are operating in Cooling Mode, if one unit is selected for a test run mode, the room temper-  
ature control by the set temperature cannot be performed. Areas B and C are assumed to be area A for control  
purposes, instead. By this reason, the compressor continues its operation regardless of the low evaporation  
temperature (This is used for additional charging of refrigerant, test run checking etc.) Vapor may be discharged  
if the test run continues for a long time. However, this does not indicate problems.  
(2) Even within the same area, the compressor capacity varies depending on the refrigerant temperature.  
(3) For 6 minutes after the compressors start, area C is considered to be area B for control purposes.  
(4) During special control, control of the compressor capacity according to Te is not performed.  
(5) If the thermostat turns OFF while Te is within area C, the next time the compressor starts it may restart from a  
lower capacity.  
(6) When the area changes to area C, area C is considered to be area B for control purposes for the first 6 min-  
utes, even if the horsepower is the minimum value within the range where capacity control is possible (opera-  
tion with inverter frequency of 25 Hz only). Subsequently if C area continues, the thermostat turns OFF.  
1 - 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
3. Compressor Control  
3-6-2. Condensation Temperature (Tc) Control:  
Control of Indoor Units Operating either in Cooling Mode or Heating Mode  
PX=125.6°F  
Thermostat OFF  
Area D  
Area C  
PX –0.1  
Horsepower decrease  
118.5  
118.4  
118.4  
116.6  
1
Horsepower increase  
prohibited  
Area B  
116.6  
116.4  
Area AB  
Area A  
Horsepower increase  
permitted  
109.4  
107.6  
113.0  
112.8  
100.4  
98.6  
Horsepower increase  
permitted  
* Depending on the maximum requirement level  
of the indoor unit, the judgment temperatures  
for each area may vary as shown in the figure  
(example).  
15  
30  
0
Maximum requirement level [L]  
(1) For indoor units which are operating in Heating mode, if one unit is selected for a test run, the air intake tem-  
perature difference is ignored, however Tc control is performed according to the figure above in order to pre-  
vent excessive load. (This is used for test run checks, etc.)  
(2) Even within the same area, the compressor capacity varies depending on the refrigerant temperature.  
(3) Temperature PX is the coefficient value used to correct for any deviation with the high pressure or condensa-  
tion temperature. It may vary. (At the time of shipment it is 127°F.)  
(4) If the condensation temperature (Tc) enters area D and the thermostat turns OFF, the next time the compressor  
starts it may restart from a lower capacity.  
3-6-3. Protection control  
Protection control consists of 2 types of protection: discharge temperature protection and current protection. The limit  
values from this protection control are incorporated into the output compressor capacity increase/decrease values that  
were calculated from control based on the temperature at the indoor unit heat exchanger coil (roadmap control).  
* In some cases, the control shown below may stop the compressor, issue a warning, or reduce the compressor  
capacity.  
(1) Discharge Temperature Protection  
During operation when only a single outdoor unit is installed, the air discharge temperature level is determined  
(the highest value is used), and the compressor capacity is limited, by using the air discharge temperature of  
the operating compressor (as shown in the tables below).  
Air discharge temperature level: Highest level among the air discharge temperature levels of all compressors  
Discharge temp. °F  
Air discharge temp. level  
Horsepower limit  
Decrease by 2 horsepower  
Decrease by 1 horsepower  
Decrease by 0.5 horsepower  
5
4
3
2
1
0
221  
219  
217  
212 ~ Less than 217  
208 ~ Less than 212 Permit horsepower increase (slowly)  
Prohibit horsepower increase  
Less than 208 No control  
The values shown in the table above are reduced to the values calculated by roadmap control.  
1 - 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
3. Compressor Control  
(2) Current Protection  
Inverter compressor current control is composed of primary current control and secondary current control.  
Current protection control for the inverter compressor is performed by self-protection in the inverter circuit, and  
does not increase or decrease the compressor capacity.  
Secondary current  
75.0A or (302°F)  
Control  
Primary current  
-
Inverter compressors stop (HIC auto. protection)  
1
Inverter compressors stop (When 100ms is detected,  
current protection works.)  
16.0A~  
16.5A  
Hz decrease in the inverter compressor  
14.5A~  
13.5A~  
13.5A  
13.0A  
12.5A  
12.0A  
Prohibit Hz increase in the inverter compressor  
Permit Hz increase in the inverter compressor  
80Hz  
90Hz  
3-6-4. Roadmap Control after Trip  
When restarting after the trip stop occurs, the horsepower may increase slowly depending on the trip counter value.  
(1) If trip counter =1, the horsepower increases at a speed that is 1/2 of ordinary roadmap control.  
(2) If trip counter =2, the horsepower increases at a speed that is 1/3 of ordinary roadmap control.  
The trip counter will be cleared if no trip occurs within 10 minutes after operation starts.  
1 - 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
4. Special Controls  
In addition to ordinary heating and cooling operation, this system also includes the following 3 types of special con-  
trols for control of the system as a whole.  
1. 4-way Valve Adjustment Control  
2. System refrigerant oil recovery control  
3. Defrost control  
4-1. 4-way Valve Adjustment Control  
1
When the microcomputer is initialized immediately after power-ON, after warning output, and all outdoor units are  
kept stopped for a preset period (standard = 60 minutes) , the 4-way Valve Adjustment Control will be performed.  
This control is intended to changeover the 4-way valve of outdoor unit. When the unit has been stopped for long  
period, and if refrigerant has accumulated somewhere in the tubing, recovery of the refrigerant is performed. This  
control can also compensate for tubing thermal loss by radiation during heating start as well as for oil recovery.  
(1) Cooling control when the outdoor unit heat exchanger is acting as a condenser  
Control time  
60 seconds  
Outdoor units  
All outdoor units operate at the maximum horsepower.  
Electronic Thermostat  
Expansion Valve  
Valves at all indoor units operate at a fixed pulse according to the indoor unit capacity.  
Valve kits at all indoor units operate in Cooling mode (OFF status).  
Indoor  
units  
RAP valve kit  
Fan  
Fan operates at the set fan speed or stops, depending on the indoor unit operation  
mode.  
*
When the above operation is finished, normal operation starts at the horsepower determined by the indoor units where  
thermostats are ON.  
(2) Heating control when outdoor unit heat exchanger is acting as an evaporator  
Control time  
Minimum 1 min - Maximum 10 min [until max (pressure sensor temp., E1)  
All outdoor units operate at the maximum horsepower.  
95°F ]  
Outdoor units  
Electronic Thermostat  
Expansion Valve  
Valves at all indoor units operate at 250 pulses as a default.  
Valve kits at all indoor units operate in heating mode (ON status).  
Indoor  
units  
RAP valve kit  
Fan  
Fan operates at the set fan speed, stops or operates at a very low speed,  
depending on the indoor unit operation mode.  
*
When the above operation is finished, normal operation starts at the horsepower determined by the indoor units  
where thermostats are ON  
.
4-2. System Refrigerant Oil Recovery Control  
4-2-1. System refrigerant oil recovery cycle  
This control is performed using the cooling cycle during cooling operation and using the heating cycle during heat-  
ing operation.  
4-2-2. Start of System Refrigerant Oil Recovery Control  
When the oil level in an operating compressor is detected as 0 (zero), the compressor stops in 120 seconds. If this  
compressor repeats this operation 3 times and the oil level does not reach 2, system refrigerant oil recovery con-  
trol is started.  
* When the compressor has stopped because the oil level is 0, a count is added to the alarm counter. The counter  
for this compressor is not cleared unless the oil level for that compressor reaches 2, or else alarm output occurs.  
1 - 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
4. Special Controls  
4-2-3. Refrigerant Oil Recovery Control between Systems  
(1) Simplified flow of system refrigerant oil recovery control  
Refrigerant oil recovery control between systems shall be performed as the flow mentioned below.  
Normal operation  
3-minute stop  
Refrigerant oil recovery control between systems (Max. 3 minutes)  
3-  
minute stop  
Normal operation  
(2) Cooling cycle  
Control time  
Maximum 3 minutes (Stops once before and once after control.)  
All outdoor units operate at maximum horsepower.  
1
Outdoor units  
Electronic Thermostat  
Expansion Valve  
Valves at all indoor units operate at a fixed pulse according to the indoor unit capacity.  
Indoor  
units  
RAP valve kit  
Fan  
Valve kits at all indoor units operate in Cooling mode (OFF status.)  
Fan operates at the set fan speed, or stops depending on the operation mode of the  
indoor unit.  
(3) Heating cycle  
Control time  
Maximum 3 minutes (Stops once before and once after control.)  
All outdoor units operate at maximum horsepower.  
Outdoor units  
Electronic Thermostat  
Expansion Valve  
Valves at all indoor units operate at 480 pulse.  
Indoor  
units  
RAP valve kit  
Fan  
Valve kits at all indoor units operate in Heating mode (ON status.)  
Fan operates at the set fan speed, stops or operates at a very low speed.  
4-3. Defrost Control  
4-3-1. Defrost Methods  
This system uses the following 2 defrosting systems.  
System employs  
Defrost control method  
1 outdoor unit in the refrigerant system  
2 outdoor units in the refrigerant system  
4-3-2. Constraint conditions  
Reverse cycle defrost  
Outdoor unit cycle defrost  
(1) Frost detection does not occur for 5 minutes after operation starts.  
(2) Defrost does not begin again for 35 minutes of A/C operation after defrost was once completed.  
(3) If all indoor units are stopped while defrost control is in effect, or if the outdoor unit is stopped due to protection  
control or another reason, then defrost control will not start for a minimum of 10 minutes after restart occurs.  
1 - 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
4. Special Controls  
4-3-3. Frost detection  
(A) Frost detection does not occur for 5 minutes after operation starts.  
(B) Frost is detected when either condition 1 or 2 below is met.  
Condition 1: L2 line or below is detected twice, each time continuously for 4 minutes, when the compressor is  
operating.  
Condition 2: L1 line or below is detected for a total of 60 minutes when the compressor is operating.  
Heat exchange liquid temperature °F  
1
Defrosting operation  
end temperature  
(The end temperature  
is different from the  
above detection  
50  
temperature.)  
External temperature °F  
50  
–6.5  
30  
L1  
L2  
26  
17  
14  
The frost detection area is  
located under the thick lines  
–9  
–13  
4-3-4. Outdoor units where defrost occurs  
Even if the total time has not reached 35 minutes, if there is 1 or more outdoor units that fulfills the defrost detec-  
tion conditions, all operating outdoor units perform defrost control at the same time.  
* Defrost control is also performed at outdoor units where the outdoor unit heat exchanger is not functioning as an  
evaporator (such as stopped outdoor units).  
4-3-5. Reverse Cycle Defrost  
If there is 1 outdoor unit and no thermal storage tank in a refrigerant system, a reverse cycle defrost will be carried out.  
• Defrost flow  
E: Evaporator operation  
C: Condenser operation  
E
C
C: Switching from evaporator operation to condenser operation  
E: Switching from condenser operation to evaporator operation  
Defrost preparation  
Defrost in progress  
Defrost end  
Outdoor unit status  
Stopped indoor units  
E
C
C
E
E
C
C
E
E
E
E
E
E
E
C
C
C
C
C
C
C
E
E
E
E
E
E
E
E
E
E
E
Indoor units where fan is operating  
C
C
C
C
C
E
E
E
E
E
Defrost  
end  
judgment  
Thermostat ON  
Cooling mode  
Thermostat OFF  
Thermostat ON  
Thermostat OFF  
indoor units  
Heating mode  
indoor units  
E
Compressor  
Time  
Stopped  
Operating  
Stopped  
Operating  
1 min  
1 min  
Max. 10 min  
1 min  
1 - 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
4. Special Controls  
4-3-6. Outdoor unit cycle defrost  
Outdoor unit cycle defrost is performed in systems where 2 outdoor units are connected to the refrigerant system.  
(1) Description of outdoor unit cycle defrost  
With this defrost method, when 1 outdoor unit operates in defrost mode (heat exchanger operating as a con-  
denser), another outdoor unit operates as an evaporator in the same way as in ordinary heating mode.  
In this way, the other outdoor unit is heating the unit where defrost is occurring. When 1 outdoor unit completes  
defrost, the other outdoor unit performs defrost in the same way.  
Because the amount of time that the unit operates as an evaporator is very short, there is little danger of frost  
forming again quickly. Rather, because the heat source is very powerful, it is possible to shorten the defrost  
operating time.  
1
(2) Defrost sequence  
Outdoor unit cycle defrost is always completed in 2 defrost operations.  
(A) When there are 2 outdoor units  
Switch  
Defrost  
outdoor unit  
Evaporator  
outdoor unit  
Evaporator  
outdoor unit  
Defrost  
outdoor unit  
First operation  
Second operation  
• Defrost flow  
E: Evaporator operation  
C: Condenser operation  
S: Shut off  
E
C
C: Switching from evaporator operation to condenser operation  
E: Switching from condenser operation to evaporator operation  
Defrost in  
progress  
Defrost in  
progress  
Defrost  
preparation  
Defrost  
preparation  
Switch  
C
Outdoor unit(s) where defrost occurs first  
Outdoor compressor(s) where defrost occurs first  
Outdoor unit(s) where defrost follows later  
Outdoor compressor(s) where defrost follows later  
Stopped indoor unit(s)  
C
E
E
ON  
C
ON  
S
S
E or S  
OFF  
E or S  
OFF  
E
OFF  
C
ON  
E
ON  
S
S
OFF  
E
OFF  
C
C
E
ON  
S
Defrost  
end  
judgment  
Defrost  
end  
judgment  
S
S
S
S
Indoor units where fan is operating  
S
Thermostat ON  
C
C
C
C
C
Heating mode indoor  
units  
Thermostat OFF  
C
C
C
C
C
1 min  
Time  
Max. 6 min  
1 min  
Max. 6 min  
1 min  
1 - 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
4. Special Controls  
4-3-7. Defrost end judgment conditions  
Defrost ends when either of the below defrost end judgment conditions is met.  
Condition 1: The temperatures are 50°F or higher at all temperatures sensors installed on the outdoor unit heat  
exchanger coils.  
However, if there is any other outdoor unit where the defrost end condition has not been met, defrost  
control continues for all outdoor units, and system defrost control is not ended.  
Condition 2: The maximum defrost time listed in the table above has elapsed.  
1
4-3-8. System defrost end  
When all outdoor units where defrost control is in effect have met the defrost end conditions, defrost control is  
ended for the system.  
1 - 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
5. Other Controls  
5-1. Oil Control  
5-1-1. Oil level  
Oil level  
Meaning  
Conditions of oil  
Judgement  
The compressor contains oil more than  
the oil level which is necessary and  
sufficient for normal operation.  
There is no problem.  
2
Sufficient  
1
The compressor contains sufficient oil  
but there is a possibility of shortage  
against the required oil level.  
Confirm that oil is returned after  
performing the oil control operation.  
1
0
Slightly low  
The compressor oil is short against  
the required oil level sufficient for normal  
operation.  
Confirm that oil level is recovered to the  
required level after performing the oil  
recovery control between systems.  
Extremely low  
At the time immediately after the oil level changes from 2 to 1, there is a specified amount of oil in the compressor.  
Namely, soon after the oil level is changed to 1, the oil in the compressor is not empty. If the oil level “0” indication  
continues for more than 5 to 10 minutes, it seems short of oil in the system. Check for any oil leakage as well as the  
refrigerant tubing.  
5-1-2. Oil level detection  
Excess oil in the compressor is sent by bypass via a capillary tube to the low-pressure circuit. The temperature  
detected by a temperature sensor is used to determine whether it is oil (warm) or refrigerant (cold).  
5-1-3. Self-separator oil recovery control  
* When a low oil level is detected, this control recovers the oil which has accumulated in that oil separator and  
sends it to the compressor.  
(1) Operation when oil level is not 2.  
30 seconds after the oil level changes from 2 to 1, the recovery valves turn ON.  
However, if the oil level becomes 2, this control is stopped.  
5-1-4. Unit refrigerant oil recovery control – utilizing balance tubes  
* If the low oil level continues, that outdoor unit (oil-receiving outdoor unit) receives a supply of oil from operating  
outdoor units where the oil level is not low (oil-supply outdoor units).  
(1) Control at the oil-supply outdoor unit begins 3 minutes after the oil level at the outdoor unit dose not become 2.  
Oil supply is performed for a maximum of 5 minutes from each unit.  
(2) When oil supply is ended, oil supply from that outdoor unit will not occur again for a period of [(No. of outdoor  
units minus1) x 5 minutes]. In addition, oil supply is ended if the oil-receiving outdoor unit oil level changes to 2,  
or if the oil-supply outdoor unit oil level becomes low.  
(3) The supply of oil is received from 1 unit at a time, in sequence, according to the order of priority of their inverter  
compressors.  
(4) Operation during unit refrigerant oil recovery  
(A) Oil-receiving outdoor unit  
The recovery valve turns ON and remains ON.  
(B) Oil-supply outdoor unit  
The balance valve turns ON and remains ON.  
The bypass valve repeatedly turns ON and OFF according to a constant cycle.  
5-1-5. Indoor unit refrigerant oil self-recovery control  
Refer to the items concerned with indoor unit special control.  
1 - 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
6. Operation of Solenoid Valves  
6-1. Refrigerant Control Valve [RCV]  
The main purpose of this valve is to detect the flow of refrigerant (refrigerant volume) on the indoor-unit side when  
the outdoor unit heat exchanger is functioning as a condenser. When the valve determines that there are signs of  
a low refrigerant level, refrigerant is supplied from the receiver tank to the system.  
(1) The OFF conditions take priority over the ON conditions for this valve.  
(2) This valve is OFF when the outdoor unit is stopped.  
(3) This valve is ON when special control is in progress.  
Hp  
1
(4) Control during normal operation  
(A) Cooling operation  
This valve turns ON when symptoms of insufficient refrigerant gas occur at an  
indoor unit.  
This valve turns ON when the outdoor air temperature is 59°F or below. (Under  
these conditions the high pressure is low and refrigerant flow becomes poor.)  
This valve turns OFF when symptoms of refrigerant overcharge are detected at  
the outdoor unit.  
(B) Mixed cooling/heating operation  
The RCV turns ON at stopped outdoor units when the heat exchanger at anoth-  
er outdoor unit is functioning as a condenser.  
6-2. Refrigerant Balance Valve [RBV] – Gas Purge Valve  
The main purpose of this valve is to detect the flow of refrigerant (refrigerant volume) on the indoor-unit side when  
the outdoor unit heat exchanger is functioning as an evaporator. When the valve determines that there are signs of  
excess refrigerant, refrigerant is recovered at the receiver tank.  
This valve is ON during heating operation and when the outdoor unit heat exchanger is functioning as an evapora-  
tor during mixed heating/cooling operation. It also turns ON in order to recover refrigerant at the outdoor unit after  
heating operation is stopped.  
* This valve is never turned ON at the same time with the RCV.  
(1) The OFF conditions take priority over the ON conditions for this valve.  
(2) This valve turns ON for 30 – 50 seconds after the outdoor unit stops, and then turns OFF.  
(3) This valve turns ON once after the outdoor unit starts.  
(A) Heating operation  
This valve is ON during heating operation and when it turns ON for the purpose  
Lp  
of recovering refrigerant in the outdoor unit at the end of the heating operation.  
After the valve turns from ON to OFF, it will not turn ON again for 15 minutes.  
This valve turns ON when poor refrigerant flow at an indoor unit is detected,  
and when symptoms of overcharge are detected, if the heat exchanger at the  
outdoor unit is functioning as an evaporator.  
(4) This valve turns OFF when an abnormal drop in discharge gas temperature is detected.  
(5) This valve turns OFF when a drop in the detected receiver tank temperature contin-  
ues for a set length of time, and when liquid back-flow is judged to be occurring.  
1 - 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
6. Operation of Solenoid Valves  
6-3. Recovery Valve (ORVR)  
This valve recovers refrigerant oil from the balance tube to the compressor.  
(1) When unit is stopped  
This valve is always OFF.  
(2) When unit is operating  
(A) This valve turns ON when separator oil self-recovery control is in progress.  
(B) This valve is ON when unit refrigerant oil recovery control is in progress (oil-receiving unit).  
(C) This valve is ON when control the system in case of insufficient refrigerant gas.  
(D) This valve turns ON for 60 seconds after a constant-speed compressor starts.  
(E) This valve turns ON for 120 seconds after defrost control ends.  
1
(F) This valve turns ON for 10 seconds after the outdoor unit stops.  
(G) This valve remains OFF at all times other than (A) through (F) above.  
6-4. Bypass Valve (BPV)  
This valve flushes the oil from the balance tubes. In addition, it is used for recovering refrigerant from stopped out-  
door units during cooling operation.  
(1) When unit is stopped  
This valve is always OFF.  
(2) When unit is operating  
This valve is ON at the oil-supply outdoor unit when unit refrigerant oil recovery control is in progress.  
* This valve repeatedly turns ON/OFF at regular intervals during unit refrigerant oil recovery control. (It is not  
constantly ON.)  
1 - 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
7. Outdoor Unit Electronic Thermostatic Expansion Valves  
[MOV1, MOV2 & MOV4]  
7-1. Types of Electronic Thermostatic Expansion Valves  
[CHDX07263, CHDX09663]  
Capacity  
72  
96  
Heat exchanger  
1 valve  
Heat exchanger  
1 valve  
Electronic  
control valve 1  
Electronic  
control valve  
Heat exchanger  
2 valve  
Heat exchanger  
2 valve  
Electronic  
control valve 2  
Electronic  
control valve 4  
1
For SC circuit  
For SC circuit  
7-2. Power Initialization  
If no indoor units have started (even once) after the power was turned ON, the outdoor unit electronic control valve  
operates at 480 pulses.  
7-3. Heat Exchangers which are controlled by each Electronic Thermostatic Expansion Valve  
The configuration of heat exchangers is as shown in the figure below. MOV3 is excluded.  
Heat  
exchanger 1  
Heat exchanger 2  
Front  
Operation of Electronic Thermostatic Expansion Valve during normal unit operation  
If any one compressor in the outdoor unit is operating, the outdoor heat exchanger coil is used.  
In cooling operation, all the inverter compressors are designed to operate, therefore, all the outdoor heat  
exchangers in the outdoor units will be used.  
SH control controls the difference between the liquid temperature and gas temperature to 2°F ~ 10°F.  
During heating mode SH operation in the heat exchanger 2 side, in order to prevent a liquid-back or high load  
operation from occurring a control may be implemented so that refrigerant may not flow intentionally to the heat  
exchanger.  
1 - 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
7. Outdoor Unit Electronic Thermostatic Expansion Valves  
[MOV1, MOV2 & MOV4]  
7-4. SC Circuit Electronic Control Valve [MOV4]  
(1) SC Control (Cooling Mode only)  
During cooling operation, the liquid refrigerant which condenses at the outdoor unit heat exchanger flows into  
the receiver tank, and SC (sub-cool = supercooling) approaches 0°F. When SC is small and the length of the  
tubing connecting the indoor and outdoor units is long, the refrigerant flow in the indoor unit will be reduced sig-  
nificantly. To prevent this trouble from occurring, MOV4 operates so as to increase supercooling in the double  
tube coil near the outlet of the outdoor unit.  
MOV4 controls refrigerant so that it will not flow back to the compressor in the liquid state with a suction tem-  
perature sensor near the accumulator and a low pressure sensor.  
1
Liquid refrigerant (SC = 0°F)  
Gas refrigerant returns  
to the accumulator.  
Refrigerant on the outer side evaporates,  
cooling the liquid refrigerant on the inner side.  
Liquid refrigerant  
(large SC)  
Electronic control valve 4  
(expansion valve) controls the flow.  
(2) Operation when discharge temperature is high  
When the discharge temperature increases, the SC circuit electronic thermostatic expansion valve opens to  
480 pulses to cool down the compressor. This operation takes priority over operation intended to increase SC.  
It is performed at top priority in all operating modes. In addition, the valve opening adjustment will be made  
when the discharge temperature falls.  
Liquid refrigerant  
Liquid refrigerant returns  
to the accumulator.  
Does not fully evaporate,  
resulting in liquid back-up.  
Liquid refrigerant  
Electronic control valve  
4 opens to 480 pulses.  
1 - 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
8. Outdoor Fan Control  
8-1. Fan mode  
These outdoor units utilize a DC fan motor that can be controlled in a maximum of 16 steps (16 modes).  
However, fan modes 15 and 16 can only be used if high static-pressure mode has been set.  
* For information concerning EEPROM settings, refer to the field application functions.  
8-2. Outdoor Fan Min. Fan Mode and Max. Fan Mode  
Max. fan mode  
Min. fan mode  
1
Outdoor air temp. > 59°F: 1  
Cooling operation  
Heating operation  
14  
14  
Outdoor air temp.  
<
59°F: 0  
1
* Even if the fan mode is 0 during cooling operation, the fan mode may change to 1 at regular intervals for tem-  
perature protection of the inverter hybrid IC.  
8-3. Fixed Initial Fan Mode  
For the first 30 seconds after operation starts, the mode is fixed at the initial mode which was calculated from the  
relationship between the outdoor air temperature and the outdoor unit horsepower.  
If the outdoor unit horsepower changes dramatically, say for about 2 hp, the initial mode may be recalculated and  
may be again fixed for 30 seconds.  
8-4. Operation after Fixed Initial Fan Mode  
After the fixed initial fan mode, the fan mode is increased or decreased according to the operating conditions.  
(1) When all indoor units are operating in cooling mode  
(A) Fan mode is increased when the high pressure satulation temperature sensed by the pressure sensor is  
high, and is decreased when the pressure sensor temperature is low.  
* The fan mode is always increased when the high pressure satulation temperature sensed by the pressure  
sensor is 113°F or higher.  
(B) The fan mode may be decreased when symptoms of insufficient refrigerant gas are detected at an indoor unit.  
(2) When all indoor units are operating in heating mode  
(A) If the condensation temperature is low, the fan mode is increased at regular intervals.  
(B) If the condensation temperature is high, the fan mode is decreased in order to prevent excessive loads.  
(C) The fan mode may be increased when the outdoor liquid temperature drops to 44°F or below.  
8-5. Snow Removal Control  
(1) When the outdoor air temperature is 50°F or below, the fan operates for 30 seconds every 2 hours in fan mode  
8, even when the outdoor unit is stopped or the heat exchanger is not in use. This control is intended to prevent  
snow from accumulating on stopped fans. (Because the outdoor air temperature cannot be accurately detected  
when the unit is stopped, a higher outdoor air temperature is used for the control condition, in order to ensure  
correct operation.)  
(2) If the fan mode becomes 0 during cooling operation, the fan mode is changed to 1.  
* This control is predictive control. Use a snowfall sensor as necessary according to the installation conditions.  
8-6. When the Compressor Magnet Switch Seizing Alarm Occurs  
Because there is the possibility that the high pressure has increased, the fan operates in Max. fan mode.  
8-7. Other  
This unit includes settings for high static-pressure and for Quiet mode.  
For information about these settings, refer to the field application functions.  
1 - 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
9. Demand Control  
Serial-parallel I/O must be connected in order to perform demand control. The below input is received by serial-  
parallel I/O, and demand control is performed.  
The demand values can be set as needed with this device. For more information, refer to the field application func-  
tions.  
Demand setting  
Demand meaning  
Control  
Contact 1  
Contact 2  
No control  
Operates to maximum capacity.  
1
-
-
-
Operates to the upper limit for the rated current.  
Operates to 70% of the upper limit for the rated current.  
Always in stop condition.  
Input not present  
:
:
Input present  
* The rated current indicates the current value that is listed in the catalog or similar material.  
1 - 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
10. Indoor Unit Control of the Electronic ControlValve  
10-1. Normal Control  
(1) Cooling operation  
Position of electronic control valve  
Outdoor unit operating  
Outdoor unit  
stopped  
Stopped  
Fan  
20  
20  
20  
20  
Thermostat  
1
20  
20  
OFF  
Thermostat  
ON  
Cooling  
Performs SH control in the range of 55 – 480  
pulses.  
* The SH target value is controlled so that the E3 - E1 becomes between 2°F to 6°F, depending on the operating  
conditions.  
However, a decline in the required level may cause the SH target value to increase. Be aware that in this case, the  
electronic control valve closes slightly. This can be easily identified incorrectly as insufficient gas.  
(2) Heating operation  
(A) Except Type D  
Position of electronic control valve  
Outdoor unit  
Outdoor unit operating  
stopped  
Liquid refrigerant is gradually returned to the outdoor unit  
at pulses ranging from 55 to 80.  
Liquid refrigerant is gradually returned to the outdoor unit  
at pulses ranging from 55 to 80.  
Liquid refrigerant is gradually returned to the outdoor unit  
at pulses ranging from 55 to 80.  
Stopped  
Fan  
85  
85  
85  
Thermostat  
OFF  
Thermostat  
ON  
Heating  
Performs SC distribution control within the range of 55–  
480 pulses.  
* The SC target value is controlled so that the high pressure saturated temp. - E1 becomes between 10°F to  
40°F , depending on the operating conditions.  
(B) Type D  
Position of electronic control valve  
Outdoor unit  
Outdoor unit operating  
stopped  
Stopped  
Fan  
20  
20  
20  
20  
Thermostat  
20  
20  
OFF  
Thermostat  
ON  
Heating  
Performs SC distribution control within the range of 55 –  
480 pulses.  
* The SC target value is controlled so that the high pressure saturated temp. - E1 becomes between 10°F to  
40°F, depending on the operating conditions.  
However, if installation is combined with except Type D, the high pressure saturated temp. - E1 may be  
controlled between 10°F to 80°F.  
1 - 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
10. Indoor Unit Control of the Electronic ControlValve  
10-2. Special Control  
Operating  
Control  
Subject indoor units  
Position of electronic control valve  
mode  
Cooling  
Heating  
Fixed pulse for cooling, according to indoor unit  
capacity  
4-way valve  
adjustment control  
All indoor units  
All indoor units  
Stopped  
Fan  
250  
Cooling control, according to indoor unit capacity  
Cooling control, according to indoor unit capacity  
1
Thermostat  
ON  
Fixed pulse for heating, according to indoor unit  
capacity  
Reverse cycle  
defrost control  
Heating  
Heating control, according to indoor unit capacity  
However, position is 20 pulses for Type D.  
Thermostat  
OFF  
Stopped  
Fan  
60 pulses  
60 pulses  
Thermostat  
ON  
Outdoor cycle  
defrost control  
Cooling/  
heating  
60 pulses  
Thermostat  
OFF  
60 pulses  
Fixed pulse for cooling, according to indoor unit  
capacity  
250  
System refrigerant  
oil recovery control  
Cooling  
Heating  
All indoor units  
All indoor units  
1 - 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
11. Rap Valve Kit Control  
A gas tube valve kit may be connected to the Type D indoor unit. When the gas tube valve kit is connected,  
operations of gas tube valve kit and indoor unit electronic thermostatic expansion valve are as shown in the  
table.  
Electronic thermostatic  
Gas tube valve  
expansion valve  
Stopped  
Fan  
20 pulses  
20 pulses  
OFF  
OFF  
Thermostat  
ON  
Thermostat  
OFF  
Thermostat  
ON  
Thermostat  
OFF  
1
ON  
20 pulses  
ON  
Superheat control (65 – 480)  
20 pulses  
OFF  
OFF  
Superheat control (50 – 480)  
1 - 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
12. Indoor Unit Refrigerant Oil Self Recovery Control  
This control is carried out regularly in cooling mode only.  
(1) During stopped, fan or thermostat OFF condition, indoor unit expansion valve is opened regularly for 1 to 2 min-  
utes regularly (at an interval of once every 2 hours.)  
(2) During the thermostat ON, the indoor unit electronic thermostatic expansion valve is opened about 10 pulses  
from the current status.  
1
1 - 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
13. Discharge Temperature  
<Alarm Information>  
(1) Discharge temperature protection alarm  
This device sets an upper limit discharge temperature of 222°F for all compressors. When the discharge tem-  
perature reaches 222°F, that compressor is stopped and restarted. If the same high discharge condition occurs  
4 times, then an alarm occurs.  
After a compressor has stopped, that compressor will not operate until the temperature has dropped to or  
below the start-prohibit temperature.  
1
Discharge temperature protection list  
Compressor No.  
Type  
Compressor 1  
Inverter  
222°F  
Compressor 2  
Constant-speed  
222°F  
Stop temp.  
Start-prohibit temp.  
Alarm display  
158°F  
P03  
158°F  
P17  
(2) Discharge sensor trouble detection control  
An alarm occurs if the discharge temperature remains abnormally high (above 158°F), when the system has  
been stopped for 60 minutes.  
* In this case, possible causes include sensor failure and compressor overheating caused by an insufficient  
level of refrigerant.  
The alarm also occurs if the sensor temperature is at or above the abnormal temperature (176°F) when 20 min-  
utes have passed after the compressor stopped.  
* In this case, it is possible that the discharge temperature from a different outdoor unit is being detected, due  
to an error in the installation of the discharge thermistor.  
Discharge sensor failure list  
Compressor No.  
Type  
Alarm display  
Compressor 1  
Inverter  
Compressor 2  
Constant-speed  
F05  
F04  
1 - 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
14. Current Protection  
(1) Fan motor  
Alarm  
Description  
P22  
Occurs when the fan motor detects over current, or when the motor is locked and  
does not turn.  
(2) Inverter compressor  
Alarm  
Description  
P16  
P26  
Occurs during ordinary operation when overcurrent (27 A) is detected.  
Occurs under the same conditions as P16 when the inverter compressor is operating  
at or above 80 Hz.  
1
Occurs when missing phase or overcurrent (48 A) is detected at inverter compressor  
start. (the alarm at frequencies below 25 Hz)  
Occurs when HIC detects overcurrent (75 A), or when an abnormal high temperature  
P29  
H31  
(302°F) is reached.  
The inverter current includes a primary current and secondary current. The alarm judgment utilizes both cur-  
rents. Generally, the secondary current is larger that the primary current.  
(3) Constant-speed compressor  
An alarm occurs when overcurrent or lock current is detected.  
List of overcurrent and lock currents  
Outdoor unit  
Constant-speed  
compressor  
Compressor 2  
Overload  
current [A]  
23.1  
Lock current  
[A]  
type  
96  
27.3  
List of Alarms  
Compressor  
No.  
Compressor 2  
Detected  
current  
Alarm display  
Lock  
current  
H12  
Overcurrent  
H11  
(4) CT circuit detection trouble  
Alarm  
Description  
Compressor 1 (inverter  
compressor)  
H03  
Occurs when an open CT circuit is detected in the inverter  
compressor.  
Compressor 2 (constant-  
speed compressor)  
H13  
Occurs when a current value of 1.5 A or less is detected  
when the constant-speed compressor is operating.  
If the inverter compressor operating frequency is low, the current value is also low. Therefore this alarm is  
detected only when the compressor is stopped.  
The operating current of the constant-speed compressors is always higher than 1.5 A. Therefore, this alarm  
occurs as the result of an open circuit or failure.  
1 - 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
15. Pressure Sensor Failure  
This system contains 2 types of pressure sensors: a high-pressure sensor and a low-pressure sensor.  
(1) High-pressure sensor failure  
Alarms are emitted when the high-pressure sensor becomes an electrical open-circuit or a short-circuit condi-  
tions, and a broken wiring, short-circuit or poor connection to the PCB in the high-pressure sensor circuit.  
(2) Low-pressure sensor failure  
Alarms are emitted when the low-pressure sensor becomes an electrical open-circuit or a short-circuit condi-  
tions, and a broken wiring, short-circuit or poor connection to the PCB in the low-pressure sensor circuit.  
1
High-pressure sensor failure  
Low-pressure sensor failure  
Alarm display  
F16  
F17  
1 - 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
16. Backup Operation  
<Field Application Functions>  
Backup Operation  
16-1. Automatic Backup Operation  
This system includes a function for automatic backup operation. An alarm is also displayed to inform the operator  
that a failure has occurred.  
(1) Alarms that result in automatic backup operation  
1
When compressor trouble or fan motor trouble makes emergency continued operation impossible, automatic  
backup operation mode is engaged. Automatic backup mode is not engaged in cases of communications  
alarms, automatic reset alarms, and other instances when emergency operation is possible by pressing the  
remote controller buttons or changing other conditions.  
The alarms that result in automatic backup mode are P16, P22, P26, P29, H11, H12, and H31.  
(2) Start of automatic backup operation  
If the above alarms occur, the alarm is displayed on the control device. Pressing the control device button again  
starts automatic backup mode.  
(3) Operation  
[1] When 1 outdoor unit is installed  
When 1 compressor has failed, backup operation is possible using the other compressors (only in the 09663  
model (8 Ton)). However, operation does not occur when the outdoor fan is unable to operate as a result of  
alarm P22.  
[2] When multiple outdoor units are installed  
When automatic backup mode is engaged, the outdoor unit where the above alarm occurred stops operating.  
However, if one or more of the compressors is able to operate, then this outdoor unit operates only when the  
operation of all outdoor units is required for special control (such as 4-way valve adjustment) or other system  
purposes.  
(4) Alarm display  
If a wired remote controller is present,  
display blinks during operation.  
(5) Canceling automatic backup operation  
Repair the outdoor unit where the failure occurred. When repairs are completed, reset the power on outdoor  
unit No.1.  
<Caution>  
After automatic backup mode has been engaged, it will not be canceled automatically when the repair of the  
failed outdoor unit is completed. Automatic backup mode will be canceled only when the power on outdoor unit  
No.1 is reset. Therefore, after repair work is completed, be sure to check whether or not automatic backup  
mode has been canceled.  
How to check: [1] Use test run or other means to verify that all outdoor units operate continuously.  
[2] If a wired remote controller is present, check that  
display has disappeared.  
16-2. Manual Backup  
If an alarm that does not result in automatic backup occurs frequently, possible causes include failure (such as  
refrigerant leakage) of a functional part at an outdoor unit other than the unit where the alarm occurs.  
In this case, because the outdoor unit service valve must be closed, backup operation must be performed manually.  
(1) Backup operation procedure  
[1] Disconnecting the failed outdoor unit  
(A) Reduce the number of outdoor units set at outdoor unit No.1 by the number of failed outdoor units.  
(B) At the S010 switch on the PCB of the failed outdoor unit, turn ON the switch for the compressor to dis  
able, and turn ON the “backup” switch.  
1 - 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
16. Backup Operation  
Outdoor unit tonnage  
Switches to turn ON  
8 Ton  
INV+AC1+BU  
(C) Close all service valves at the failed outdoor units.  
(D) Reset the power at outdoor unit No.1.  
* When the PCB of the main unit is normal, by implementing the above settings while leaving the communica-  
tion lines between indoor and outdoor units as they are, backup operation of units are possible. In this case,  
the outdoor unit that backed up all compressors is not identified as an outdoor unit, however, it can work as  
the command controller.  
1
[2] Disabling operation of 1 compressor  
At the S010 switch on the PCB of the failed outdoor unit, turn ON the switch for the compressor to disable, and  
turn ON the “backup” switch.  
<S010 switch>  
( * )  
INV  
AC1  
AC2  
Backup  
ON  
OFF  
ON  
S010  
(A) Compressor 1 backup  
OFF  
ON  
(B) Compressor 2 backup  
OFF  
* AC2 switch is not available.  
1 - 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
17. Service Maintenance Functions  
The outdoor unit EEPROM settings can be used for the following functions.  
17-1. Outdoor Unit Noise Countermeasure: EEPROM 05 (set at each outdoor unit)  
This unit includes 3 types of Quiet modes. (However, when they are engaged, operation is in Quiet mode 24 hours  
a day.) Selecting a Quiet mode results in operation that gives priority to reducing noise. Because these modes  
involve restrictions on outdoor unit fan modes and the operation frequency, the capacity will be somewhat reduced.  
Setting  
Max. fan mode  
Amount of capacity reduction  
Effect  
1
Normal operation (setting at time of  
factory shipment)  
0
14  
0
Noise reduced by approx. 1 – 2 dB from  
the catalog value.  
1
2
3
12  
11  
10  
Approx. 0.5 hp  
Approx. 1.2 hp  
Approx. 1.8 hp  
Noise reduced by approx. 2 – 3 dB from  
the catalog value.  
Noise reduced by approx. 5 dB from the  
catalog value.  
* If Quiet mode is set, the capacity will begin to decrease during heating operation at low outdoor temperatures,  
when the outdoor air temperature is below standard conditions.  
17-2. Anti-slime countermeasures ... EEPROM setting 0C (set only on the main unit)  
This setting controls the operation of the drain pump.  
Setting  
Description  
Normal control (setting at time of factory ship ment)  
The drain pump operates for 20 minutes at 2-hour intervals.  
The drain pump operates for 20 minutes at 20-minute intervals.  
The drain pump operates constantly.  
0
1
2
3
17-3. Delayed Start for Each System: Outdoor EEPROM 3E (set only on outdoor unit No. 1)  
The operation start time can be delayed according to the set system addresses.  
This setting reduces the voltage drop by preventing multiple systems from starting at the same time when opera-  
tion is restarted after multiple operating systems were stopped due to a power outage or other cause.  
Effect  
No delayed start (setting at time of factory shipment)  
Start begins after [1 second x System address]  
Setting  
0
1
2
3
Start begins after [2 seconds x System address]  
Start begins after [3 seconds x System address]  
17-4. Automatic Backup: Outdoor EEPROM 48 (set only on outdoor unit No. 1)  
Automatic backup is set to occur at the time the unit is shipped from the factory. However, the automatic backup  
function can be disabled by changing this setting to 1.  
1 - 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
17. Service Maintenance Functions  
17-5. Optional Solenoid Valve Control Operation Setting:  
Outdoor EEPROM C0 (set at each outdoor unit)  
Operation  
Setting  
0
1
No output (setting at time of factory shipment)  
Refrigerant shut-off valve control  
(for cooling when the outdoor air temperature is below standard conditions)  
1
2
External liquid valve control  
(used in special cases when the discharge gas temperature is especially likely to rise)  
17-6. High Static Pressure Mode: Outdoor EEPROM 8F (set at each outdoor unit)  
This product can be made compatible with high static pressure by changing the settings.  
By changing the setting item 8F to “6,” this product can be made compatible with outdoor unit static pressure of  
approximately 0.0085 psi (10 hp type only).  
Setting No.  
0
2
3
6
1
4
5
Compatible static  
pressure (psi)  
0.0014  
600  
0.0026  
630  
0.0037  
670  
0.0050  
710  
0.0061  
740  
0.0074  
0.0085  
800  
770  
Speed  
17-7. Compressor Operating Sequence: Outdoor EEPROM 46  
(set at outdoor units which include CCU functions)  
When this setting is set to “1,” the compressors start in sequence beginning from the No. 1 outdoor unit.  
(The setting is “0” at the time of shipment. With this setting, compressors with lower operating time are started  
first in order to balance the compressor operating times.)  
17-8. Demand Value Setting: Outdoor EEPROM 1A, 1B  
(set at outdoor units that include CCU functions)  
Demand setting  
Control  
Demand meaning  
Contact 1  
Contact 2  
Operates to the maximum  
capacity.  
No limit  
Demand can be set from 40 – 200% at  
EEPROM 1A.  
Current is limited to the set  
values.  
Demand can be set from 40 – 200 % at  
EEPROM 1B.  
Current is limited to the set  
values.  
Remains stopped.  
1 - 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
18. Other Functions  
18-1. Snowfall Sensor Functions: Outdoor EEPROM 04  
A unit identified as having a snowfall sensor attached will periodically send a signal indicating the snowfall sensor  
input status to all outdoor units in the same system (or all wired outdoor units in the case of linked systems). It is  
therefore unnecessary to install and wire multiple snowfall sensors.  
(1) Snow fall sensor settings  
Operation  
Setting  
0
1
2
3
Sensor input not present. Control is performed. (Setting at time of factory shipment)  
Sensor input present. Control is performed.  
1
Sensor input not present. Control is not performed.  
Sensor input present. Control is not performed.  
* If the snowfall sensor is used, then depending on the circumstances it is necessary to make the correct setting at  
all outdoor units in the system.  
* If “control is not performed” is set, control by the above signal is ignored. This setting is used in order to conserve  
energy at outdoor units that include a snowfall-protection hood.  
Recommended: If a low-speed fan mode is required (for all-year cooling or other reasons), install a snowfall-pro-  
tection hood and set this setting to ON  
.
(2) Control operation  
[1] Outdoor units where “sensor input present” is set send the snowfall sensor input information every 10 min-  
utes to all linked systems if the system wiring is linked.  
[2] At systems where “control is performed” is set, the above information is used to control operation of the out  
-
door fan.  
[3] At systems where “control is not performed” is set, the snowfall sensor input and above information ignored,  
and the outdoor fan does not operate.  
[4] In case of W-2WAY ECO-i system, control can be performed when snowfall sensor input is connected to  
any outdoor unit.  
<Caution>  
Snowfall sensor input information is detected once every 10 minutes. Therefore, the outdoor fan may continue  
operating for up to 10 minutes even when there is no snowfall sensor input.  
In addition, the outdoor fan may remain stopped for up to 10 minutes when snowfall sensor input is present.  
18-2. Function for Automatic Judgment of Insufficient Refrigerant Gas and Overcharg e  
This system includes a simple function for judging the level of refrigerant. However, be aware that false judgments  
may occur if the control elements of the outdoor unit or indoor unit fail.  
(1) Starting refrigerant level judgment mode  
Short-circuit the CHECK pin on the No. 1 outdoor for 4 seconds or longer to engage this mode. (The LED on  
the outdoor unit PCB begins blinking.)  
(2) Conditions for refrigerant level judgment  
After judgment mode starts, judgment occurs when all outdoor units in the system have been operating contin-  
uously for 30 minutes or longer.  
* Refrigerant level judgment requires that all outdoor units operate continuously for 30 minutes or longer. This is  
in order to prevent incorrect adjustment of the refrigerant level based on false detection caused by refrigerant  
accumulation or recovery at stopped outdoor units, which is due to failures of functional elements.  
After the judgment is displayed, repeated judgment will occur under new operating conditions if all outdoor  
units continue operating. Therefore, the judgment display may change when later judgments occur.  
* Judgment mode is automatically canceled after 4 hours.  
1 - 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Control Functions  
18. Other Functions  
(3) Outdoor unit PCB LED indications in judgment mode  
Judgment items  
Judgment mode  
Normal  
LED1  
Blinking  
ON  
Recommended response  
LED2  
Blinking  
ON  
-
-
Insufficient gas  
Overcharge  
Blinking  
OFF  
OFF  
Charge with refrigerant a little at a time.  
Recover refrigerant a little at a time.  
Blinking  
1
Judgment not  
possible  
Blinking alternately  
-
When judgment mode is not engaged, the LED indicates the normal display (OFF), or else indicates alarms or  
other information.  
If the insufficient gas or overcharge judgment is not stable, then recover refrigerant a little at a time when the  
overcharge display appears. End refrigerant adjustment when the normal or insufficient gas display appears.  
(4) Canceling judgment mode  
When judgment mode is cancelled, the LED returns to the standard status display (OFF unless an alarm or  
other event has occurred).  
[1] Automatic cancel  
Judgment mode is canceled automatically when 4 hours have passed after it was started.  
[2] Forced cancel  
Short-circuit the CHECK pin while the judgment mode display is active in order to cancel judgment mode.  
<Reference> General Guidelines for Insufficient Gas and Overcharge  
Judgment in automatic judgment mode can be problematic in some cases. Therefore, the following guidelines  
are provided for general judgment of the refrigerant amount.  
• Symptoms of insufficient gas  
There is an indoor unit where the position of the electronic control valve is much higher (open by  
300 pulses or more) than it was at start, and the difference [E3 – E1] at that indoor unit is large  
(30°F or more).  
Cooling  
operation  
There is an outdoor unit where the position of the electronic control valve is much higher (open by  
300 pulses or more) than it was at start, and the difference [Liquid temp. – Gas temp.] at that  
outdoor unit is large (30°F or more).  
Heating  
operation  
• Symptoms of overcharge  
The high-pressure sensor temperature is 134°F or higher, and the difference [Pressure sensor  
temp. – Liquid temp.] at that outdoor unit is large (30°F or more).  
Cooling  
operation  
There is an indoor unit where the position of the electronic control valve is much higher (open by  
300 pulses or more) than it was at start, and the difference [Pressure sensor temp. – E3] at that  
indoor unit is large (50°F or more).  
Heating  
operation  
These are only guidelines, therefore the judgment may vary depending on the installation conditions, load char-  
acteristics, and other elements.  
1 - 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
– MEMO –  
1 - 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
Contents  
2. OUTDOOR UNIT REPAIR PROCEDURES  
1. Removing Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2  
2. Removing Electrical Component Box and Duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3  
3. Discharging Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5  
4. Backup Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6  
5. Recovering Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9  
6. Checking for Leakage After Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14  
7. Evacuating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15  
8. Charging Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16  
9. Pumping Out Refrigerant from Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20  
10. Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23  
11. High and Low Pressure Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-35  
12. Replacing 4-way Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-36  
2
2 - 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
1. Removing Panels  
Procedures:  
1. Removing Panels  
2. Removing Electrical Component Box and Duct  
3. Discharging Compressor Oil  
4. Backup Operation  
5. Recovering Refrigerant  
6. Checking for Leakage After Repair  
7. Evacuating System  
8. Charging Compressor Oil  
9. Pumping Out Refrigerant from Outdoor Unit (when repairing parts other than compressor)  
10. Compressor  
11. High and Low Pressure Sensors  
12. Replacing the 4-way Valve  
2
(1) Front panel removal (Fig. 1)  
• Remove the front panel (remove 11 screws).  
Front panel  
Fig. 1  
(2) Power outlet panel & valve cover removal (Fig. 2)  
• Remove the power outlet panel (remove 2 screws).  
• Remove the tubing cover (remove 2 screws).  
Power outlet panel  
Tubing cover  
Fig. 2  
2 - 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
2. Removing Electrical Component Box and Duct  
Be sure to turn off the power before removing the electrical component box. Then check that the power LED (D53)  
on the control PCB of the outdoor unit is not lit.  
(1) Remove the electrical component box cover  
(remove 6 screws). (Fig. 3)  
• When closing the cover after the repair work,  
set the upper fringe of the cover should come  
to align inside the electrical component box.  
(Fig. 3A)  
A
2
Electrical component  
box cover  
Fig. 3A  
Fig. 3  
(2) Remove power and control wires from terminals.  
(3) Remove internal wires with extended connectors  
on the outdoor control PCB.  
(Solenoid valves, thermistors, crankcase heaters  
and others)  
(4) Disconnect power lines connected to the sec-  
ondary terminals of the magnetic contactor for  
the compressor.  
(5) Remove the electrical component box (remove 2  
screws). (Fig. 4)  
Electrical  
component box  
Fig. 4  
CAUTION  
Be sure to release the locking mechanism  
before disconnecting each connector.  
Upper duct  
Center duct  
(6) Remove the center duct. (Fig. 5)  
• The center duct is fitted into the upper and lower  
ducts, and held in place by the electrical component  
box, an arrangement that makes possible indepen-  
dent removal of the center duct.  
Lower duct  
Fig. 5  
2 - 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
2. Removing Electrical Component Box and Duct  
(7) Remove the lower duct: (remove 2 screws, and  
a hook)  
Lower duct  
2
Fig. 6  
(8) Remove the upper duct: (remove 3 screws)  
(Fig. 7)  
Upper duct  
Fig. 7  
2 - 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
3. Discharging Compressor Oil  
Discharged oil can be used for checking the condition of the system. Based on the appearance and color of the  
discharged oil, a judgment can be made on whether the system is operating normally or not.  
3-1. Discharging Oil from Oil Separator  
Recover the refrigerant from the outdoor unit following the procedure given in “5. Recovering Refrigerant.” Install  
hoses as indicated on the equipment and feed nitrogen gas gradually to provide pressure to the system from the  
low-pressure outlet and collect oil in a pan or container. (Fig. 8)  
• The low-pressure outlet port is at the Lo side of the right side.  
CAUTION  
• A faulty outdoor unit may remain pressurized. The oil outlet port employs a  
Schrader-type push-to-release valve. Be careful to avoid accidental oil release  
when using the port.  
2
Packless valve or the like  
Container  
Oil outlet port  
(For 1/4" (6.35mm)  
-dia. connector)  
Manifold gauge  
Lo  
Hi  
Nitrogen gas  
Low-pressure outlet port  
(For 5/16" (7.94mm)-dia. connector)  
Fig. 8  
3-2. Discharging Oil in Compressor  
Recover the refrigerant in the outdoor unit following the procedures in “5. Recovering Refrigerant.” Remove the  
compressor and discharge the oil in it. Refer to “10. Compressor” for detailed procedures.  
3-3. Checking the Oil  
Acceptance/rejection criteria for the oil  
Judgment criteria for changing oil*  
Condition of oil  
Odor  
Condition of  
refrigeration cycle  
Color  
Total acid value  
0.02 or less  
Hue  
Normal  
Yellowish  
None  
3.5 or less  
4.0 or over  
0.06 or over  
Abnormal overheat-  
operation  
Smells somewhat  
(not as strong as below)  
Brownish  
Changing the oil and system cleaning  
with dry-cores are necessary.  
Brownish /  
blackish  
Changing the oil and system cleaning  
with dry-cores are necessary.  
Motor burnout  
Pungent / burnt odor  
* It is difficult to measure the total acid value in the field, therefore oil hue and odor are the rule of thumb. Checking  
for carbon deposits and abrasive metal powder can additionally be used to assess the system condition.  
2 - 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
4. Backup Operation  
This system includes an emergency automatic backup function that allows the A/C to operate during the period  
after trouble occurs until repairs are made. However, during repair and at other times, use manual backup opera-  
tion.  
4-1. Automatic Backup  
For details, refer to the control functions section.  
After the alarm details are sent to the control device, control for automatic backup operation begins when the  
ON/OFF button of the wired remote controller is pressed again (operation is started after the alarm is cleared).  
During this operating mode, “CHECK” flashes on the wired remote controller only to inform the user that operation  
is in backup mode. However this is not displayed on any other control devices.  
• In order to cancel automatic backup mode, it is necessary to reset the power on the control PCB of the outdoor  
unit where the outdoor unit No. setting (S007) on the control PCB is set to No. 1 (main unit).  
(It is also available by resetting power of all the outdoor units.)  
2
If the power is not reset on the control PCB of the No. 1 outdoor unit (main unit),  
CAUTION  
backup mode operation will continue after the repairs are completed.  
Backup operation is intended as emergency operation until repairs are made. Have repairs made as soon as pos-  
sible.  
4-2. Manual Backup  
This backup operation is the conventional method of backup operation. It involves disconnecting the failed outdoor  
unit from the system, and operating only the normal outdoor units.  
4-2-1. Backup operation by disconnecting the outdoor unit  
(1) Changing the outdoor unit control PCB settings  
<If the failed outdoor unit is not the No. 1 unit>  
• Settings at No. 1 unit (main unit)  
Switch on outdoor unit control PCB  
System address (S003, S002)  
No. of indoor units (S005, S004)  
No. of outdoor units (S006)  
Action  
No change  
No change  
Subtract the number of failed units from the current setting.  
No change  
Outdoor unit No. (S007)  
• Settings at normal outdoor units other than the No. 1 unit  
No particular changes  
• Settings at the failed outdoor unit  
No particular changes  
However, close all service valves (gas tubes, liquid tube, and balance tube) at the failed outdoor unit, and dis-  
connect the wiring between the outdoor units.  
2 - 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
4. Backup Operation  
<If the failed unit is the No. 1 outdoor unit (main unit)>  
If the No. 1 unit (main unit) has failed, a different outdoor unit must be set as the No. 1 unit (main unit).  
• Settings at the failed No. 1 outdoor unit  
– No particular changes  
– However, close all service valves (gas tube, liquid tube, balance tube) at the failed outdoor unit, and dis-  
connect the wiring between the outdoor units.  
• Settings at No. 1 unit (main unit)  
Switch on outdoor unit control PCB  
System address (S003, S002)  
No. of indoor units (S005, S004)  
No. of outdoor units (S006)  
Action  
Make the same settings as on the failed No. 1 unit.  
Make the same settings as on the failed No. 1 unit.  
Subtract the number of failed units from the current setting.  
Change to “1.”  
2
Setting outdoor unit No. (S007)  
To this outdoor unit, connect the inter-unit communication line which was previously connected to the  
No. 1 unit (main unit).  
After recovery work is completed, wire the communication lines between  
indoor and outdoor units again. If it not finished yet, an alarm is emitted  
immediately.  
CAUTION  
• Settings at other outdoor units  
No particular changes.  
(2) Adjusting the refrigerant for backup operation  
During backup operation, all of the service valves on the failed unit are closed. However, if a check of the  
backup operating conditions shows that the level of gas is low, recover the refrigerant from the failed outdoor  
unit. If the level of gas is too high, collect refrigerant at the failed outdoor unit.  
Recovering refrigerant  
With the normal outdoor units operating, monitor the operating condition and open/close the gas tube ser-  
vice valve on the failed outdoor unit where all the service valves were closed. In this way, recover refriger-  
ant from the failed outdoor unit in order to adjust the amount of refrigerant in the system.  
After adjusting the amount of refrigerant, close the gas tube valve at the failed outdoor unit.  
Collecting refrigerant in the failed outdoor unit  
• Short-circuit the vacuum application pin (CN102) on the control PCB of the failed outdoor unit where the  
service valves are closed, then turn the power ON. Also disconnect the wiring between the outdoor units.  
• With the normal outdoor units operating, monitor the operating condition and open/close the liquid tube ser-  
vice valve on the failed outdoor unit where all the service valves were closed. In this way, collect refrigerant  
in the failed outdoor unit in order to adjust the amount of refrigerant in the system.  
• After adjusting the amount of refrigerant, turn OFF the power at the failed outdoor unit, release the short-  
circuit at the vacuum application pin, and close the liquid tube valve at the failed outdoor unit.  
* Refrigerant recovery is not affected by the power status of the failed outdoor unit. However, collecting  
refrigerant in the failed outdoor unit is affected by whether the power at that outdoor unit can be turned ON.  
If the power cannot be turned ON, use a refrigerant recovery device and recover the refrigerant into a  
recovery cylinder in order to adjust the amount of refrigerant in the system.  
2 - 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
4. Backup Operation  
4-2-2. Backup operation by setting the failed compressor not to operate  
Backup operation settings for each compressor  
INV compressor  
AC1 compressor  
Setting for backup operation  
DIP switch S010:  
OK  
Failed  
Turn BACK UP and AC1 ON.  
DIP switch S010:  
Turn BACK UP and INV ON.  
Failed  
Failed  
OK  
DIP switch S010:  
Turn BACK UP, INV, and AC1 ON.  
Failed  
2
2 - 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
5. Recovering Refrigerant  
The following equipment and tools are required:  
Jumper wire with clips, adjustable wrench, set of manifold gauge valves specially designed for refrigerant R410A  
only, vacuum pump, refrigerant recovery unit, pre-purged refrigerant cylinder for recovery, flathead screwdriver, and  
outdoor unit maintenance remote controller.  
5-1. Refrigerant Recovery Procedures (from outdoor unit)  
(1) Turn off the power of the outdoor unit beforehand (at power mains).  
(2) Fully close each service valve on the liquid tube, gas tubes, and the balance tube of the outdoor unit.  
(3) Connect the outdoor unit’s high-pressure and low-pressure outlet ports with the Hi and Lo sides of the manifold  
gauge valves using hoses. (Fig. 9)  
The remaining refrigerant in the faulty outdoor unit may create internal pressure.  
Before connecting hoses, be sure to confirm that each of the manifold gauge  
valves is tightly closed. Note that the connection ports employ Schrader-type  
push-to-release valves.  
CAUTION  
2
(4) Connect the manifold gauge valves, refrigerant recovery unit, and recovery cylinder using hoses. To avoid the  
entry of air into the refrigerant tubing, carry out this connection work carefully. (Fig. 9)  
For detailed procedures such as connecting the refrigerant recovery unit with the  
recovery cylinder and methods used for recovery, follow the specific instructions  
that came with the refrigerant recovery unit.  
CAUTION  
(5) Locate the AP (Air Purge) pins on the control PCB in the faulty outdoor unit and short them using the clips of  
the jumper wire. Then restore electrical power to the outdoor unit.  
By short-circuiting the AP pins, each solenoid valve in the outdoor unit is forcibly  
opened as soon as power comes on, which releases all remaining refrigerant into  
the recovery cylinder. Since neglecting this procedure may leave some refrigerant  
in the system, it is important that you carry out this step.  
CAUTION  
(6) Carry out refrigerant recovery.  
To determine the completion of refrigerant recovery, follow the instructions that  
CAUTION  
came with the refrigerant recovery unit.  
Manifold  
High-pressure outlet  
port (For 5/16" (7.94mm)  
-dia. connector)  
gauge  
Lo  
Hi  
Refrigerant  
recovery unit  
Refrigerant recovery cylinder  
Low-pressure outlet port  
(For 5/16" (7.94mm)-dia. connector)  
Fig. 9  
2 - 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
5. Recovering Refrigerant  
5-2. Refrigerant Recovery Procedures (Indoor Unit)  
The flowchart below shows the refrigerant recovery procedures you must follow when replacing or repairing the  
indoor unit due to trouble in the refrigerant circuit.  
START  
5-2-1. Cooling operation (for all units)  
Ball valve is provided in the indoor unit  
Turn off all equipment in system  
5-2-3. Refrigerant recovery  
procedures (2)  
NO  
YES  
5-2-2. Refrigerant recovery  
procedures (1)  
Replace or repair faulty unit  
Check for leakage in repaired unit  
Evacuate air from repaired unit  
Turn off all equipment in system  
When replacing or repairing a faulty  
unit, let other normal indoor units run  
(excluding indoor unit where refrigerant  
is recovered)  
Fig.8  
NO  
NO  
Charge refrigerant in repaired unit  
(Amount of charge should equal that  
recovered by refrigerant recovery unit)  
2
YES  
Power can independently be turned off  
for indoor unit where refrigerant is  
Modify power to permit turning off  
power to refrigerant-recovered  
indoor units independently  
Ready for operation  
END  
recovered  
YES  
Change controllable number of indoor  
units (including changes in group  
control and integrated-control settings)  
Other indoor units can operate normally  
Replace or repair faulty unit  
Check for leakage in repaired unit H  
Evacuate air from repaired unit H  
Replace or repair faulty unit  
Check for leakage in repaired unit H  
Evacuate air in repaired unit H  
Charge refrigerant in repaired unit H  
(Amount of charge should equal that  
recovered by refrigerant recovery unit)  
Charge refrigerant in repaired unit H  
(Amount of charge should equal that  
recovered by refrigerant recovery unit)  
Change controllable number of indoor  
units (including changes in group  
control and integrated-control settings)  
Open the ball valve  
Ready for normal operation  
END  
Open ball valve  
Ready for normal operation  
END  
Service work performed on indoor units is done simultaneously using the service ports at the liquid (narrow tube) side  
and the gas (wide tube) side ball valves. Refer to each section in the “Installation Instructions” on refrigerant charging,  
leak checking, and evacuation procedures.  
5-2-1. Cooling operation (for all units)  
(1) If the remote controller (RCS-TM80BG) is used for maintenance of the outdoor unit  
1
Connect the outdoor unit maintenance remote controller to the RC connector (CN006) (3P) (BLU) on any  
one of the outdoor unit control PCBs. Then start a test run of all units. (Press and hold the  
button for 4 seconds or longer.)  
(CHECK)  
2
Press the  
(MODE) button and change to cooling operation and ensure that the cooling is performed.  
Refer to the test run service manual for the detail of the outdoor maintenance remote controller operation.  
It may be possible to determine whether operation is cooling or heating by touching the gas tubing.  
Cooling : low temperature (68 °F or lower)  
Heating : high temperature (140 °F or higher)  
The gas tubing becomes hot (140 °F or higher) in heating mode. Be careful so as  
not to be burnt when touching the tubing.  
CAUTION  
2 - 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
5. Recovering Refrigerant  
(2) If the remote controller (RCS-TM80BG) is not available for maintenance of the outdoor unit  
1
Determine the outdoor unit where the unit No. setting (S007) (3P DIP switch) (Blue) on the outdoor unit  
control PCB is set to No. 1.  
2
3
Short-circuit the test-run pin (CN023) on the PCB to start test run operation.  
Leave the unit running for a while, and touch the gas tubing with fingers to determine whether the unit is  
running in cooling or heating mode.  
If it is in heating, follow the step 4 and later procedures.  
Cooling : low temperature (68 °F or lower)  
Heating : high temperature (140 °F or higher)  
The gas tubing becomes hot (140 °F or higher) in heating mode. Be careful so as  
not to be burnt when touching the tubing.  
CAUTION  
4
5
Release the short-circuit at the test-run pin (CN023) on the outdoor unit control PCB of the No. 1 unit. Then  
short-circuit the stop pin (CN104) to stop operation.  
2
Short-circuit the mode-change pin (CN101) on the outdoor unit control PCB of the No. 1 unit.  
* Switching of the 4-way valve occurs immediately before operation starts. Therefore it does not change at  
this time. (Mode change cannot be judged from the sound.)  
6
Short-circuit the test-run pin (CN023) on the PCB to start test run operation. Leave the unit running for a  
while, and touch the gas tubing with fingers to determine that the unit is running in cooling mode.  
5-2-2. Refrigerant recovery procedures (1) (using indoor unit ball valve)  
(1) If a ball valve with a service port has been provided in the indoor unit as shown in Fig. 10, follow the instructions  
given in (2) through (6) below. If the service port is instead located in the outdoor side, follow the instructions in  
“5-2-3. Refrigerant recovery procedures (2).”  
(2) After running the unit in Cooling mode for about 5 minutes as described in “5-2-1. Cooling operation (for all  
units),” fully close the liquid tube ball valve.  
(3) Run the unit in Cooling mode for 10 to 20 minutes more.  
(4) Fully close the gas tube ball valve, and stop the operation of all units.  
(5) Use hoses to connect the manifold gauge valves, refrigerant recovery unit, and refrigerant recovery cylinder  
with each other. (Fig. 10)Do each connection quickly to prevent air from entering the tubing.  
Remaining refrigerant may create internal pressure, therefore care should be  
taken when connecting the hoses.  
CAUTION  
(6) Recover the remaining refrigerant from the indoor unit using the refrigerant recovery unit.  
NOTE  
Manifold  
gauge  
Hi  
Lo  
To determine completion of refrigerant  
recovery, follow the instructions that  
came with the refrigerant recovery unit.  
Refrigerant  
recovery  
unit  
Refrigerant recovery cylinder  
Ball valve (separately purchased)  
Gas tube  
Service port  
Outdoor  
unit  
Indoor unit  
side  
Liquid tube  
Fig. 10  
2 - 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
5. Recovering Refrigerant  
5-2-3. Refrigerant recovery procedures (2): Indoor unit with no ball valve equipped  
Refrigerant in all indoor units and the refrigerant tubing circuit must be pumped into the outdoor unit. The maximum  
refrigerant storage capacity per a single outdoor unit is approx. 529 oz. Thus, in order to collect all refrigerant from  
the system, a separate refrigerant recovery unit is necessary. Follow these procedures to correctly perform pump  
down.  
Perform work correctly, according to the work procedures given below.  
1
Connect the manifold gauge to the high- and low-pressure outlet ports on the outdoor unit where pump down  
will be performed. Be sure that no air enters the tubing at this time.  
2
Follow the instructions in “5-2-1. Cooling operation (for all units)” and operate all units in Cooling mode for  
approximately 5 minutes. Then fully close the liquid tube valve on the outdoor unit where pump down will be  
performed.  
3
When the high-pressure gauge reaches 406.1 psi or higher, or the low-pressure gauge reaches 72.5 psi or  
below, at the outdoor unit where pump down is being performed, press the ON/OFF button on the outdoor unit  
maintenance remote controller to stop operation at all units. Then immediately fully close the suction tube valve  
on the outdoor unit where pump down is being performed.  
2
* If the outdoor unit maintenance remote controller is unavailable, follow the procedure below to stop all of the  
units.  
Pull out the SCT connector (2P) (YEL) (CN231) on the outdoor unit control PCB of the unit where pump down  
is being performed. When the SCT connector is pulled out, immediately alarm F12 (sensor trouble) occurs  
and all outdoor units stop operating. Be sure that you do NOT grasp the lead wire when pulling out the con-  
nector. Removing any other connector may not cause the units to stop. Therefore be sure to pull out the SCT  
connector only.  
It is not necessary to recover the refrigerant from the balance tube. Therefore do  
not operate the balance tube valve.  
CAUTION  
4
5
Turn off power to all equipment in the system. Then pull out the RC1 connector (4P) (BLU) (CN106) on the out-  
door control PCB in the outdoor unit for which pump down has been completed.  
* By pulling out the RC1 connector, communication between the main and the sub outdoor units will be isolated.  
Change the setting of controllable outdoor unit numbers (reduce by 1 unit).  
* If the setting is incorrect, the E30 alarm (outdoor unit serial communication signal error) occurs and the unit  
will not operate.  
6
7
8
Turn on power for all equipment in the system and let the remaining outdoor units run in Cooling mode.  
2
Repeat steps  
1
and  
and complete pump down for all outdoor units.  
Using hoses with Schrader-type push-to-release valves, connect the manifold gauge valves to the suction line  
service port, the discharge line service port and the liquid line service port in the next outdoor unit to undergo  
pump down. (Fig. 11)  
Remaining refrigerant in the system may cause internal pressure. Check that each  
valve on the manifold gauge is tightly closed. A Schrader-type push-to-release  
CAUTION  
valve is provided for each connection port.  
9
Use hoses to connect the manifold gauge valves, refrigerant recovery unit, and refrigerant recovery cylinder.  
Quickly connect each part to prevent air from entering the tubing.  
10  
Recover remaining refrigerant from the inter-unit tubing and indoor units using the refrigerant recovery unit.  
NOTE  
To determine the completion of refrigerant recovery, follow the instructions that came with the refrigerant recovery  
unit.  
2 - 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
5. Recovering Refrigerant  
Manifold  
gauge  
Liquid tube service port  
(For 5/16" (7.94mm)-dia.  
connector)  
Lo  
Hi  
Refrigerant  
recover unit  
2
Refrigerant  
recovery cylinder  
Gas tube service port  
(For 5/16" (7.94mm)-dia. connector)  
Fig. 11  
5-3. Recovery of Refrigerant from Entire System  
(1) Turn off power to the entire outdoor system.  
(2) Short-circuit the AP (Air Purge) pins (CN102) on the outdoor control PCB of all outdoor units, then supply power  
to the outdoor units.  
* By short-circuiting the AP pins and supplying power to the outdoor units, the solenoid valve in each unit is  
forcibly opened and all remaining refrigerant can be recovered.  
(3) If any unit has encountered a power failure, follow the instructions in “5-1. Refrigerant Recovery Procedures  
(from Outdoor Units)” and perform refrigerant recovery for the faulty outdoor unit.  
(4) Connect the manifold gauge to the high- and low-pressure outlet ports (Schrader-type valves) on any outdoor  
unit. (Fig. 11)  
Remaining refrigerant may cause internal pressure. Check that each valve on the  
manifold gauge valves is tightly closed. The connection port uses a Schrader-type  
CAUTION  
push-to-release valve.  
(5) Connect the manifold gauge valves, refrigerant recovery unit, and refrigerant recovery cylinder. Quickly connect  
each part to prevent air from entering the tubing.  
(6) Check that each service valve of the gas tubes, liquid tube, and the balance tube for the outdoor unit has opened,  
then perform refrigerant recovery.  
* If only a single outdoor unit is installed, the balance tube is not used. Therefore, leave this valve closed.  
NOTE  
To determine the completion of refrigerant recovery, follow the instructions that came with the refrigerant recovery  
unit.  
2 - 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
6. Checking for Leakage After Repair  
6-1. Pressure Check for Leakage of Outdoor Unit  
After completing repair of the outdoor unit, carry out the following leakage check.  
(1) Check that all service valves for gas tubes, liquid tube, and balance tube in the repaired outdoor unit (units  
necessary to carry out the pressurized leak check) are fully closed.  
(2) Connect the manifold gauge valves to the high- and low-pressure outlet ports of the outdoor unit.  
(3) Feed nitrogen gas into the circuit until 72.5 psi pressure is reached. If it is apparent that the nitrogen gas is not  
entering the repaired section, interrupt the feeding. Short-circuit the AP pins (CN102) on the outdoor unit control  
PCB, turn on power to run the outdoor unit, then resume feeding nitrogen.  
(4) Apply soapy water to the repaired part (such as a newly brazed part), and briefly inspect for any leakage. If there  
are any leaks, bubbles will show on the tubing surface.  
* To continue the air-tight check after the brief leak inspection, turn on power while short-circuiting the AP pins.  
Again feed nitrogen gas to obtain a system pressure of 72.5 psi. Then measure both the outdoor ambient  
temperature and the pressure in the system. Leave the system in this state for 1 full day and night, and again  
measure the outdoor ambient temperature and pressure (to determine any reduced values). During the  
inspection, it is recommended that an awning or cover be used to shield the unit in case of rain. If no problem  
is found, purge all nitrogen from the system.  
2
Manifold  
gauge  
Lo  
Hi  
High-pressure outlet port  
(For 5/16" (7.94mm)-dia.  
connector)  
Nitrogen gas  
Low-pressure outlet port  
(For 5/16" (7.94mm)-dia. connector)  
Fig. 12  
6-2. Checking for Leakage in Refrigerant Tubing Between Indoor and Outdoor Units  
Refer to the “Installation Instructions” that came with the outdoor unit.  
2 - 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
7. Evacuating System  
This procedure is carried out to ensure there is no remaining refrigerant or other gases (nitrogen, etc.) in the  
repaired outdoor unit and tubing.  
7-1. Evacuating Repaired Outdoor Unit  
(1) Check that each service valve of the gas tubes, liquid tube, and balance tube in the outdoor unit are fully closed.  
(2) Connect the manifold gauge valves to the high-pressure and low-pressure sensor outlets of the outdoor unit.  
(Fig. 13)  
(3) Connect the manifold gauge valves to the vacuum pump.  
* If the AP pins (CN102) on the outdoor control PCB have already been short-circuited, step (4) is not neces-  
sary.  
(4) Turn off power to the repaired outdoor unit and short-circuit the AP (Air Purge) pins on the outdoor control PCB.  
By short-circuiting the AP pins and turning on power to the outdoor unit, all elec-  
tronic valves in the outdoor unit are forcibly opened and any remaining nitrogen  
CAUTION  
2
gas can be recovered. Failure to perform this procedure may result in nitrogen gas  
remaining in the refrigerant circuit and causing operating problems. Therefore,  
never skip this step.  
(5) Turn the power ON at the outdoor unit where vacuum will be applied. Then run the vacuum pump and continue  
evacuation until the vacuum condition falls to less than –14.7 psig (5 Torr).  
To ensure proper evacuation, refer to the operating instructions that came with the  
vacuum pump.  
CAUTION  
Manifold  
gauge  
Lo  
Hi  
High-pressure outlet port  
(For 5/16" (7.94mm)-dia.  
connector)  
Vacuum pump  
Low-pressure outlet port  
(For 5/16" (7.94mm)-dia. connector)  
Fig. 13  
7-2. Evacuating Refrigerant Tubing Between Indoor and Outdoor Units  
Refer to the “Installation Instructions” that came with the outdoor unit.  
2 - 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
8. Charging Compressor Oil  
8-1. If Refrigerant Has Already Been Charged to Outdoor Unit  
Be sure to use an exclusive oil-charging tank for charging compressor oil. Prior to charging, carry out vacuum drying  
inside the tank and take care that no air (in the form of bubbles) is permitted to enter the tank.  
The oil charging procedures are given below.  
* The receiver tank used for maintenance may be used as an exclusive oil-charging tank.  
When installing the oil-charging  
(DPR : 623-081-7937)  
tank to the refrigerant system to  
serve as a safety bypass circuit for  
refrigerant, connect it to the gas  
tube service port carefully to  
avoid releasing refrigerant into the  
atmosphere.  
Nipple  
2
(Receiver-tank:  
638-015-2988)  
Perform oil charging  
CAUTION  
work carefully so that no  
liquid refrigerant enters  
the charging tank.  
Packless valve  
Fig. 14  
(1) Evacuation drying in oil-charging tank  
With the lower side valve fully closed, open the upper side valve and connect it to the vacuum pump via the  
manifold gauge valves as shown below. Run the vacuum pump and evacuate the tank until the pressure falls to  
below –14.7 psig (5 Torr) for the evacuation drying. After the evacuation drying is finished, fully close the upper  
valve. Next, fully close the manifold gauge valves and stop the vacuum pump.  
To ensure proper evacuation, refer to the operating instructions that came with the  
vacuum pump.  
CAUTION  
Open Close  
Manifold  
gauge  
Upper side  
valve  
Lo  
Hi  
Close  
Lower side  
valve  
Vacuum pump  
Fig. 15  
2 - 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
8. Charging Compressor Oil  
(2) Charging compressor oil into oil-charging tank  
Connect a piece of pipe to the lower valve and then insert the other end deeply into the bottom of the oil con-  
tainer. Make sure you avoid letting any air be sucked into the tube. Next, run the vacuum pump and open the  
manifold gauge valves, then open the upper and lower valves to begin charging oil into the charging tank.  
Close Open  
Manifold  
gauge  
Upper valve  
Close Open  
2
Lower valve  
Vacuum pump  
Oil  
Fig. 16  
When the predetermined amount of oil has been charged into the oil-charging tank, immediately close the lower  
valve. Next, run the vacuum pump until the system pressure reaches lower than -14.7 psig (5 Torr).  
Close the upper valve and then, stop the vacuum pump.  
Do this operation quickly because compressor oil easily absorbs moisture from  
the air.  
CAUTION  
(3) Charging compressor oil into outdoor unit  
Connect the lower valve to the low-pressure outlet (with Schrader-type push-to-release valve) in the outdoor  
unit to be oil-charged, and then connect the high-pressure outlet (with push-to-release valve) to the upper valve  
via the manifold gauge valves (at Hi-pressure gauge side). In addition, connect the gas tube service port (with  
push-to-release valve) to the DPR (Discharge Pressure Regulator). Carry out the connection work quickly to  
avoid letting air enter.  
The hoses may be subject to internal pressure from the refrigerant inside the out  
door unit. A Schrader-type push-to-release valve is provided at each connection  
port.  
CAUTION  
• Since the DPR valve opens at pressures of 362.6 psi and above, be sure to con-  
nect the DPR to the gas tube service port (low-pressure side).  
Low-pressure  
outlet port  
High-pressure  
outlet port  
(For 5/16"  
DPR  
(7.94mm)-  
dia. connector)  
(For 5/16"  
(7.94mm)-  
dia. connector)  
Gas tube  
Upper valve  
service port  
(For 5/16"  
(7.94mm)-  
dia. connector)  
Manifold  
gauge  
Lo  
Hi  
Lower valve  
Fig. 17  
2 - 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
8. Charging Compressor Oil  
Next follow the instructions in “5-2-1. Cooling operation (for all units)” at the outdoor unit where oil will be charged,  
and start cooling operation at all units. When the operating conditions have stabilized, perform steps 1, 2, and 3 in  
sequence and open the valves. When this is done, the refrigerant pressure from operation forces the oil out of the  
oil charge tank, and oil is charged into the outdoor unit from the low-pressure outlet port. From time to time close  
the upper valve on the top of the oil charge tank (only this valve) and shake the tank to check the amount of  
remaining oil.  
Low-pressure  
outlet port  
High-pressure  
(For 5/16"  
DPR  
outlet port  
(7.94mm)-  
(For 5/16"  
dia. connector)  
(7.94mm)-  
dia. connector)  
Gas tube  
Upper valve  
service port  
(For 5/16"  
2
(7.94mm)-  
dia. connector)  
Manifold  
gauge  
Lo  
Hi  
Procedure 2: Open  
Procedure 1: Open  
Lower valve  
Procedure 3: Open  
Connect from here to  
refrigerant recovery unit  
Fig. 18  
To terminate the oil charging work, do as follows:  
To end the charge process, first close the valve on the high-pressure side of the manifold gauge. Then wait several  
tens of seconds after the pressure display on the manifold gauge low-pressure gauge stabilizes (in order to equalize  
the pressure with the low-pressure outlet port and to vaporize the refrigerant in the charge tank). Then perform steps  
1 and 3 in sequence and fully close the valves. Finally, connect the refrigerant recovery unit to the Lo-gauge side,  
shut down all indoor and outdoor units, and then recover the remaining refrigerant in the oil-charging tank, manifold  
gauge valves, and connecting hoses. Perform these procedures quickly and securely so that no air can enter.  
After, charge the necessary amount of new refrigerant by referring to the “Installation Instructions” that came with the  
outdoor unit.  
NOTE  
To determine the completion of refrigerant recovery, follow the instructions that came with the refrigerant recovery  
unit.  
8-2. If Outdoor Unit Has Not Been Charged with Refrigerant  
When a compressor has been replaced or in any other case where the outdoor unit has not been charged with  
refrigerant, first charge with refrigerant then follow the instructions in “8-1. If Refrigerant Has Already Been  
Charged to Outdoor Unit” and charge with oil.  
Or, alternatively, follow the procedure below.  
(1) Connect a tube to the oil outlet port on the outdoor unit to be charged with oil. Insert the other end of the tube  
into the oil container.  
(2) Follow the instructions in “7. Evacuating System,” and apply vacuum to the outdoor unit to be charged with oil.  
When this is done, oil is charged into the outdoor unit through the oil outlet port.  
(3) When the unit has been charged with the designated amount of oil, stop the vacuum pump.  
CAUTION  
The oil absorbs moisture readily. This work must be completed quickly.  
2 - 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
8. Charging Compressor Oil  
Oil tube outlet port  
(For 1/4" (6.35mm)-dia. connector)  
Oil  
Manifold  
gauge  
Lo  
Hi  
Vacuum pump  
2
Low-pressure outlet port  
(For 5/16" (7.94mm)-dia. connector)  
Fig. 19  
8-3. Charging Additional Compressor Oil (after replacing compressor)  
The rated amount of oil is pre-charged in the compressors as given below:  
Model name  
CHDX07263  
Compressor model  
Q'ty  
Pre-charged amount of oil (liters)  
C-9RVN273H0S  
1
1.9  
(Inverter-controlled rotary compressor)  
CHDX09663  
C-9RVN273H0S  
(Inverter-controlled rotary compressor)  
1
1
1.9  
2.1  
JT160G-KTTJ  
(Constant-speed scroll compressor)  
When replacing a faulty compressor, be sure to first measure the amount of remaining oil in the compressor.  
Charge additional new oil equal to the difference in the remaining oil and the rated amount as listed above.  
For example: Type of replaced compressor: JT160G-KTTJ  
Remaining oil in the removed compressor: 0.58 gal  
Additional oil to be charged:  
0.58 gal (remaining oil in the removed compressor) – 0.55 gal (rated oil amount) = 0.026 gal  
* If the result is a negative amount (remaining oil in the removed compressor is less than the rated amount), it is  
not necessary to discharge the extra oil from the system.  
For the method used for additional oil charging after compressor replacement, refer to “8-1. If Refrigerant Has  
Already Been Charged to Outdoor Unit.”  
2 - 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
9. Pumping Out Refrigerant from Outdoor Unit  
Required equipment and tools: Jumper wire with clips, adjustable wrench, set of manifold gauge valves for the  
refrigerant R410A, refrigerant recovery unit, pre-purged refrigerant cylinder for  
recovery, flat-head screwdriver, and outdoor unit maintenance remote controller.  
This work is performed in order to collect the refrigerant from an outdoor unit where repairs (other than compressor  
replacement) will be performed into other outdoor units and indoor units, and the refrigerant tubing.  
9-1. If Remote Controller (RCS-TM80BG) is Used for Maintenance of Outdoor Unit  
(1) Refer to “4. Backup Operation” and perform backup operation.  
(2) Connect the manifold gauge valves at the Lo side to the low-pressure outlet port of the outdoor unit to be  
repaired. Also connect the refrigerant recovery cylinder to any one of the normal outdoor units at the liquid line  
service port (Schrader-type push-to-release valve). Perform the connection work quickly so that no air is  
allowed to enter. (Fig. 20)  
* Connecting the refrigerant recovery cylinder is done to prevent pressure from rising excessively during backup  
operation by recovering the refrigerant from the outdoor unit to be repaired.  
(Measure the weight of the refrigerant and cylinder itself beforehand and provide sufficient safety measures,  
such as installing a high-pressure cutout in the circuit.)  
2
The hoses may be subject to internal pressure from the refrigerant inside the out-  
door unit. Check that the manifold gauge valves are fully closed beforehand.  
CAUTION  
A Schrader-type push-to-release valve is provided at each connection port.  
(3) Connect the outdoor unit maintenance remote controller to the RC connector (CN006) (3P) (BLU) on the out-  
door unit control PCB of the outdoor unit to be repaired. Then start a test run of all units. (Press and hold the  
(CHECK) button for 4 seconds or longer.)  
(4) Use the outdoor unit maintenance remote controller to check the operating status of the indoor units. Check  
that all units are operating in Heating mode. For details concerning operation of the outdoor unit maintenance  
remote controller, refer to the “Outdoor unit maintenance remote controller” item. It is also possible to check the  
operating conditions either in cooling or heating mode by touching the gas tube.  
Cooling mode : low temperature (68 F or lower)  
Heating mode : high temperature (140 F or higher)  
The gas tubing becomes hot (140 F or higher) in heating. Be careful so as not to be  
burnt when touching the tubing.  
CAUTION  
(5) Close the suction tube and balance tube on the outdoor unit to be repaired. Then slowly close the liquid tube  
service valve.  
(6) When the low pressure at the outdoor unit to be repaired reaches 72.5 psi or below, press the ON/OFF button  
on the outdoor unit maintenance remote controller to stop all the units. Then immediately fully close the gas  
tube valve on that outdoor unit.  
While closing the valves, the rise in discharge temperature or another factor may  
cause a protective device to activate, stopping the operation of the outdoor unit.  
If this occurs, immediately fully close the gas tube valve on the outdoor unit to be  
repaired.  
CAUTION  
(7) Connect the high-pressure gauge side of the manifold gauge to the high-pressure outlet port on the outdoor unit  
to be repaired, and connect the manifold gauge to the refrigerant recovery device. Be sure that no air enters the  
tubing at this time.  
2 - 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
9. Pumping Out Refrigerant from Outdoor Unit  
(8) Short-circuit the vacuum application pin on the outdoor unit control PCB of the unit to be repaired. Then turn ON  
the outdoor unit power.  
When the vacuum application pin is short-circuited and the power is turned ON, all  
solenoid valves in the outdoor unit are forced open, allowing the refrigerant to be  
CAUTION  
recovered from all tubes which are separated by solenoid valves. If this work is not  
performed, it will not be possible to recover all of the refrigerant at the refrigerant  
recovery device. Be sure to perform this step.  
Open both Hi- and Lo-side valves on the manifold gauge valves, and recover the refrigerant remaining in  
the outdoor unit. After that, measure the amount of recovered refrigerant.  
NOTE  
To determine the completion of refrigerant recovery, follow the instructions that came with the refrigerant recovery  
unit.  
2
9-2. If Remote Controller is Not Available for maintenance of Outdoor Unit  
(1) Refer to “4. Backup Operation” and perform backup operation.  
(2)  
Connect the manifold gauge valves at the Lo side to the low-pressure outlet port of the outdoor unit to be  
repaired. Also connect the refrigerant recovery cylinder to any one of the normal outdoor units at the liquid line  
service port (Schrader-type push-to-release valve). Perform the connection work quickly so that no air is  
allowed to enter. (Fig. 20)  
* Connecting the refrigerant recovery cylinder is done to prevent pressure from rising excessively during the  
backup operation by recovering the refrigerant from the outdoor unit to be repaired.  
(Measure the weight of the refrigerant and cylinder itself beforehand and provide sufficient safety measures,  
such as installing a high-pressure cutout in the circuit.)  
The hoses may be subject to internal pressure from the refrigerant inside the out-  
door unit. Check that the manifold gauge valves are fully closed beforehand.  
CAUTION  
A Schrader-type push-to-release valve is provided at each connection port.  
(3) Determine the outdoor unit where the unit No. setting (S007)(3P DIP switch)(BLU) on the outdoor unit control  
PCB is set to No.1.  
(4) Short-circuit the test-run pin (CN023) to start operation.  
(5) Leave the unit running for a while, and then touch the gas tubing with fingers to determine whether the unit is  
running in cooling or heating mode. If it is in heating, follow the step (6) and later procedures.  
Cooling : low temperature (68 F or lower)  
Heating : high temperature (140 F or higher)  
The gas tubing becomes hot (140 F or higher) in heating mode. Be careful so as  
not to be burnt when touching the tubing.  
CAUTION  
(6) When the unit is operating in heating mode, release the short-circuit at the test-run pin on the outdoor unit con-  
trol PCB of the No. 1 unit. Then short-circuit the stop pin (CN104) to stop operation.  
(7)  
Short-circuit the mode-change pin (CN101) on the outdoor unit control PCB of the No. 1 unit.  
* Switching of the 4-way valve occurs immediately before operation starts. Therefore it does not change at this  
time. (Mode change cannot be judged from the sound.)  
(8) Short-circuit the test-run pin (CN023) to start operation, leave the unit running for a while. Touch the gas tubing  
with fingers to determine whether the unit is running in cooling.  
2 - 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
9. Pumping Out Refrigerant from Outdoor Unit  
(9) Close the gas tube and balance tube on the outdoor unit to be repaired. Then slowly close the liquid tube ser-  
vice valve.  
* When the low pressure at the outdoor unit to be repaired reaches 72.5 psi or below, pull out the SCT connec-  
tor (2P) (YEL) (CN231) from the outdoor unit control PCB of that outdoor unit. Then immediately fully close  
the gas tube valve on that outdoor unit.  
* Pulling out the SCT connector immediately stops all of the outdoor units.  
While closing the valves, the rise in discharge temperature or another factor may  
cause a protective device to activate, stopping the operation of the outdoor unit.  
CAUTION  
If this occurs, immediately fully close the gas tube valve on the outdoor unit to be  
repaired.  
(10) Connect the high-pressure gauge side of the manifold gauge to the high-pressure outlet port on the outdoor  
unit to be repaired, and connect the manifold gauge to the refrigerant recovery device. Be sure that no air  
enters the tubing at this time.  
2
(11) Open both Hi- and Lo-side valves on the manifold gauge valves, and recover the refrigerant remaining in the  
outdoor unit. After that, measure the amount of recovered refrigerant.  
NOTE  
To determine the completion of refrigerant recovery, follow the instructions that came with the  
refrigerant recovery unit.  
Faulty outdoor unit  
Other outdoor unit  
Low-pressure outlet port  
(For 5/16" (7.94mm)-dia.  
connector)  
Liquid tube service port  
(For 5/16" (7.94mm)-dia.  
connector)  
High-pressure outlet port  
(For 5/16" (7.94mm)-dia.  
connector)  
Manifold  
gauge  
Refrigerant  
recovery  
cylinder  
Measuring scale  
Connect from here to  
refrigerant recovery unit  
Fig. 20  
2 - 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
10-1. Compressor Trouble Diagnosis and Check Methods  
Generally, compressor failures can be classified into the following categories.  
(1) Mechanical trouble  
(2) Electrical trouble  
(A) Locking (intrusion of foreign objects, galling, etc.)  
(B) Pressure rise failure (damaged valve, seal, bearing, or other component)  
(C) Noise (damaged stator rotor, valve, or other component)  
(A) Coil burning  
(B) Open circuit  
(C) Insulation failure  
(D) Short circuit  
Trouble diagnosis is based on the following remote controller displays: [H03] (Compressor 1: INV compressor,  
center), [H11] [H12] [H13] (Compressor 2: constant-speed compressor 1, left side when viewed from front), [H21]  
[H22] [H23] (Compressor 3: constant-speed compressor 2, right side when viewed from front (not present in type  
90). A judgment is made based on factors that include the following: coil resistance (varies depending on the  
compressor), insulation resistance, current, leakage breaker operation, oil and refrigerant fouling, odor, pressure,  
and noise.  
2
Reference: Insulation resistance (Use a DC 500 V insulation resistance meter and measure the insulation resis-  
tance between the electrified and non-electrified parts.)  
(a) Motor  
Min. 300 M  
(b) Compressor  
(c) Unit  
Min. 100 M (servicing part)  
Min. 10 M (This is due to the presence of refrigerant, which decreases the  
insulation resistance.)  
* Minimum insulation resistance as required by generally accepted requirements is 1 M .  
JUDGMENT START  
Is there burning of the failed  
compressor motor?  
Follow the instructions in  
“3. Discharging Compressor Oil”  
and drain the oil from the failed  
compressor. Then inspect.  
NO  
YES  
Follow the instructions in  
“3. Discharging Compressor Oil” and  
drain the oil from all compressors in the  
same system. Then inspect.  
Is the color phase 4.0 or above, or is a  
sharp odor present?  
YES  
NO  
Are there 2 or more outdoor units where  
the compressor oil color phase is 4.0 or  
higher or where a sharp odor is  
present?  
NO  
YES  
Go to “10-2-3. Replacing all  
compressors in a system.”  
Go to “10-2-2. Replacing all  
compressors in a failed unit.”  
Go to “10-2-1. Replacing only the  
failed compressor.”  
Follow the instructions in “10-2-4. Dry  
core cleaning” and perform dry core  
cleaning of all outdoor units.  
Follow the instructions in  
“10-2-4. Dry core cleaning” and  
perform dry core cleaning of the  
failed outdoor unit.  
Reference: Symptoms of motor burning  
1. Ground fault results in breaker operation.  
2. Short circuit results in different coil resistance at different phases.  
3. Open circuit  
2 - 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
10-2. Replacing the Compressor(s)  
10-2-1. Replacing only the failed compressor  
(1) If backup operation is required, follow the instructions in “4. Backup Operation” and engage backup operation.  
(2) Follow the instructions in “10-3. Removing and Installing Compressors” and replace the failed compressor.  
(3) Fully close the high- and low-pressure gauge valves on the manifold gauge, then stop the vacuum pump.  
(4) Disconnect the manifold gauge from vacuum pump. Connect the manifold gauge to the cylinder where the  
refrigerant was recovered. At this time, be careful that air does not enter the tubing.  
(5) Open the valve on the refrigerant recovery cylinder and the high-pressure gauge valve on the manifold gauge  
to charge with refrigerant. At this time, the low-pressure gauge valve on the manifold gauge remains fully  
closed.  
If the recovered refrigerant becomes mixed with another refrigerant or another gas  
(such as nitrogen or air), do not use the recovered refrigerant for charging. Charge  
CAUTION  
2
with the designated amount of new refrigerant.  
(6) When charging has been completed with an amount of new refrigerant equal to the amount of recovered  
refrigerant, or when charging with the same amount of new refrigerant has not been completed but no more  
refrigerant will enter the unit, fully close the high-pressure gauge valve on the manifold gauge. Next, turn the  
power OFF at the repaired outdoor unit, then remove the short circuit at the AP pin (CN102). Finally, fully  
open all valves on the gas tube, liquid tube, and balance tube.  
However, leave the balance tube fully closed if only a single outdoor unit is installed.  
(7) If backup operation was engaged, follow the instructions in “4. Backup Operation” and perform backup opera-  
tion recovery.  
(8) If charging with an amount of new refrigerant equal to the amount of recovered refrigerant was not possible,  
fully close the high-pressure gauge valve on the manifold gauge. Then, while the unit is operating in “5-2-1.  
Cooling operation (for all units)”, open the low-pressure gauge valve on the manifold gauge and charge with  
the designated amount of refrigerant.  
When charging with liquid refrigerant, add refrigerant a little at a time in order to  
prevent liquid back-flow.  
CAUTION  
(9) Fully close the low-pressure gauge valves on the manifold gauge, follow the instructions in “8. Charging Com-  
pressor Oil,” and charge with oil if necessary.  
(10) Remove the manifold gauge.  
The connecting port employs a Schrader-type push-to-release valve. When discon-  
necting the hose, pressure will be applied from the refrigerant in the outdoor unit.  
CAUTION  
2 - 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
10-2-2. Replacing all compressors in a failed unit  
(1) Follow the instructions in “3. Discharging Compressor Oil” and drain the oil from the oil separator in the failed  
unit. Measure the amount of drained oil.  
(2) If backup operation is required, follow the instructions in “4. Backup Operation” and engage backup operation.  
(3) Follow the instructions in “10-3. Removing and Installing Compressors” and replace all compressors in the  
failed unit.  
(4) Fully close the high- and low-pressure gauge valves on the manifold gauge, then stop the vacuum pump.  
(5) Disconnect the manifold gauge from the vacuum pump. Connect the manifold gauge to the refrigerant cylinder.  
At this time, be careful that air does not enter the tubing.  
CAUTION  
Do not reuse the recovered refrigerant. Use a refrigerant cylinder that contains new  
refrigerant.  
2
(6) Open the valve on the refrigerant cylinder, and open the high-pressure gauge valve on the manifold gauge (with  
the low-pressure gauge valve closed). When charging has been completed with an amount of new refrigerant  
equal to the amount of recovered refrigerant, or when charging with the same amount of new refrigerant has  
not been completed but no more refrigerant will enter the unit, fully close the high-pressure gauge valve on the  
manifold gauge. Next, turn the power OFF at the repaired outdoor unit, then remove the short circuit at the AP  
pin (CN102). Finally, fully open all valves on the gas tube, liquid tube, and balance tube.  
However, leave the balance tube fully closed if only a single outdoor unit is installed.  
(7) If backup operation was engaged, follow the instructions in “4. Backup Operation” and perform backup opera-  
tion recovery.  
(8) If charging with an amount of new refrigerant equal to the amount of recovered refrigerant was not possible,  
fully close the high-pressure gauge valve on the manifold gauge. Then, while the unit is operating according  
to “5-2-1. Cooling operation (for all units),” open the low-pressure gauge valve on the manifold gauge and  
charge with the designated amount of refrigerant.  
When charging with liquid refrigerant, add refrigerant a little at a time in order to  
CAUTION  
prevent liquid back-flow.  
(9) Fully close the low-pressure gauge valves on the manifold gauge, follow the instructions in “8. Charging Com-  
pressor Oil,” and charge with the necessary amount of oil. Also add an amount of oil that is equivalent to the  
amount that was drained from the oil separator.  
(10) Remove the manifold gauge.  
The connecting port employs a Schrader-type push-to-release valve. When discon-  
CAUTION  
necting the hose, pressure will be applied from the refrigerant in the outdoor unit.  
(11) Follow the instructions in “10-2-4. Dry core cleaning” and perform dry core cleaning of the outdoor unit that  
failed.  
2 - 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
10-2-3. Replacing all compressors in a system  
(1) Follow the instructions in “3. Discharging Compressor Oil” and drain the oil from the oil separators in all out-  
door units. Measure the amount of drained oil.  
(2) Follow the instructions in “10-3. Removing and Installing Compressors” and replace all compressors in the  
system.  
(3) Follow the instructions in “6. Checking for Leakage After Repair” and check for leaks at all outdoor units and  
in the tubing.  
(4) Follow the instructions in “7. Evacuating System” and apply vacuum to all outdoor units and tubing.  
(5) Fully close the high- and low-pressure gauge valves on the manifold gauge, then stop the vacuum pump.  
(6) Disconnect the manifold gauge from vacuum pump. Connect the manifold gauge to the refrigerant cylinder.  
Be especially careful that air does not enter the tubing.  
2
Do not reuse the recovered refrigerant. Use a refrigerant cylinder that contains un-  
used refrigerant.  
CAUTION  
(7) Open the valve on the refrigerant cylinder, and open the high-pressure gauge valve on the manifold gauge.  
When charging has been completed with an amount of new refrigerant equal to the amount of recovered refrig-  
erant, or when charging with the same amount of new refrigerant has not been completed but no more refriger-  
ant will enter the unit, first turn the power OFF at the repaired outdoor unit, then remove the short circuit at the  
AP pin (CN102). Then fully open all valves on the gas tube, liquid tube, and balance tube.  
However, leave the balance tube fully closed if only a single outdoor unit is installed.  
(8) If backup operation was engaged, follow the instructions in “4. Backup Operation” and perform backup opera-  
tion recovery.  
(9) If charging with an amount of new refrigerant equal to the amount of recovered refrigerant was not possible,  
fully close the high-pressure gauge valve on the manifold gauge. Then, while the unit is operating in Cooling  
mode, open the low-pressure gauge valve on the manifold gauge and charge with the designated amount of  
refrigerant.  
When charging with liquid refrigerant, add refrigerant a little at a time in order to  
CAUTION  
prevent liquid back-flow.  
(10) Fully close the low-pressure gauge valves on the manifold gauge, follow the instructions in “8. Charging Com-  
pressor Oil,” and charge with the necessary amount of oil. Also add an amount of oil that is equivalent to the  
amount that was drained from the oil separators.  
(11) Remove the manifold gauge.  
The connecting port employs a Schrader-type valve. When disconnecting the hose,  
CAUTION  
pressure will be applied from the refrigerant in the outdoor unit.  
(12) Follow the instructions in “10-2-4. Dry core cleaning” and perform dry core cleaning of all outdoor units.  
2 - 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
10-2-4. Dry core cleaning  
If burning or other failures occur repeatedly at compressors within the same system, in many cases the cause is  
acid, sludge, carbon, or other substances that remain in the refrigeration cycle as the result of insufficient cleaning.  
If, when the oil is inspected, there is an outdoor unit where the oil color phase is 4.0 or higher, or where a sharp  
odor is present, carry out all steps below to perform dry core cleaning.  
And use the bidirectional dry core for refrigerant R410A.  
(A) If a ball valve is installed on the outdoor unit  
(1) Refer to “5-2-1. Cooling operation (for all units)” and operate all outdoor units in either Heating or Cooling mode.  
(2) If all units are operated in Cooling mode, close first the liquid tube service valve then the ball valve on all out-  
door units where dry cores will be attached.  
If all units are operated in Heating mode, close first the ball valve then the liquid tube service valve on all out-  
door units where dry cores will be attached.  
* This step is performed in order to expel refrigerant from the tubing between the liquid tube service valve and  
the ball valve. Approximately 4 – 5 seconds is a sufficient interval between closing each of the 2 valves.  
2
ON/OFF  
(3) Press the  
button on the outdoor unit maintenance remote controller to stop the operation of all units.  
* If the outdoor unit maintenance remote controller is not available, use the following method to stop the oper-  
ation of all units:  
Pull out the SCT connector (2P) (YEL) (CN231) from the outdoor unit control PCB of the unit where pump-down  
is being performed. When the SCT connector is pulled out, alarm F12 (sensor trouble) immediately occurs and  
all outdoor units stop operating. Be sure that you do NOT grasp the lead wire when pulling out the connector.  
Removing any other connector may not cause the units to stop. Therefore be sure to pull out only the SCT  
connector.  
(4) Connect a refrigerant recovery device to the liquid tube service port (Schrader-type valve) of all outdoor units  
where dry cores will be attached, then recover the refrigerant from the tubing. Be sure that no air enters the  
tubing at this time.  
When the hose is connected, internal pressure is applied by the remaining refriger-  
ant in the inter-unit tubing. The connection port employs a Schrader-type valve. To  
determine when refrigerant recovery is compete, follow the instructions in the  
instruction manual of the refrigerant recovery device.  
CAUTION  
(5) As shown in Fig. 21, disconnect the tube that runs from the liquid tube valve to the ball valve on all outdoor  
units where dry cores will be attached. Then attach the dry cores.  
(6) At all outdoor units where dry cores are attached, pressurize with 478.6 psi of nitrogen from the liquid tube  
service port and check for leaks.  
(7) After evacuating all nitrogen gas from the tubing, apply vacuum from the liquid tube service port to all outdoor  
units where dry cores are attached until the pressure is –14.7 psig (5 Torr) or less.  
(8) Fully open the liquid tube valve and ball valve on all outdoor units where dry cores are attached.  
(9) Operate all outdoor units for approximately 3 hours (in either Heating or Cooling mode or mixed Cooling and  
Heating mode).  
(10) Follow the above procedure, and replace all dry cores with new dry cores.  
(11) Operate all outdoor units for approximately 20 minutes (in either Heating or Cooling mode or mixed Cooling  
and Heating mode).  
(12) Follow the instructions in “3. Discharging Compressor Oil” and drain a small amount of the oil from the oil  
separators of all outdoor units where dry cores are attached. Check the color phase, odor, and other  
characteristics.  
(13) If the results show that dry core cleaning is still necessary (for example, a color phase of 4.0 or higher)*,  
return to Step 11 and repeat until the results are normal (including a color phase of 3.5 or less)*.  
* Color sample sheet for degree of stain  
Perform another dry core replacement after approximately 30 hours of system  
CAUTION  
operation.  
2 - 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
(14) Perform steps (1) – (4), and remove all dry cores. Then connect the tubing between the liquid (narrow) tube  
valves and the ball valves.  
(15) At all outdoor units where dry cores were removed, pressurize with 478.6 psi of nitrogen from the liquid tube  
service port and check for leaks.  
(16) After evacuating all nitrogen gas from the tubing, apply vacuum to all outdoor units where dry cores were  
removed until the pressure is –14.7 psig (5 Torr) or less.  
(17) INSTALLATION: Refer to the “Information for the Person in Charge of Installation” items. Charge with an  
amount of refrigerant equal to the amount that was recovered.  
(B) If a ball valve is not installed on the outdoor unit  
(1) Refer to “5-2-3. Refrigerant recovery procedures (2) : Indoor unit with no ball valve equipped.” Perform  
pump down of the refrigerant from all indoor units and inter-unit tubing to the outdoor unit side.  
2
(2) Cut the liquid (narrow) tube at all outdoor units where dry cores will be attached, then attach the dry cores  
and ball valves as shown in Fig. 21.  
(3) For the next steps, refer to (6) – (17) in (A) on the previous page.  
Cleaning dry core  
Liquid tube service valve  
Normal unit  
Outdoor unit  
Gas tube  
Balance tube  
Dry core (bidirectional:  
)
for R410A refrigerant  
Ball valve  
Liquid tube  
Fig. 21  
2 - 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
10-3. Removing and Installing Compressors  
When removing and installing compressors, use sufficient caution to ensure that moisture or other substances do  
not enter the refrigerant tubing system.  
10-3-1. Replacing compressors  
* For all types 90 and 140, follow the replacement procedure below.  
(A) Replacing the inverter compressor (Compressor 1 on remote controller alarm display)  
Removal  
(1) Connect a manifold gauge to the high- and low-pressure outlet ports at the outdoor unit where the compressor  
will be replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas replacement in  
the outdoor unit tubings.  
(2) Follow the instructions in “1. Removing Panels” and “2. Removing Electrical Component Box and Duct” and  
remove the corresponding parts from the outdoor unit where the compressor will be replaced.  
(3) Remove the cap at the compressor terminal plate. Disconnect the power terminal.  
(4) Remove the crankcase heater.  
2
(5) Remove the 3 bolts, and remove the washers and rubber washers (quantities indicated in the figure below).  
(6) Disconnect the tube-with-flare-nut using two adjustable wrenches. At this time, cover the tube in place with  
waste cloth while watching out for oil leaks. Then cap the disconnected tube and mount the flare nut on the  
compressor. Tighten the flare nut with a seal bonnet (1/4") in it.  
If oil remaining in the compressor reaches the equalized oil level, oil will come pouring out when the  
tube-with-flare-nut is removed.  
NOTE  
(7) Prepare to disconnect the 2 brazed locations shown in the figure.  
Protect the sensors and the surrounding plates, rubber, lead wires, clamps, and  
other items. Remove the discharge sensor shown in the figure 22.  
CAUTION  
(8) Disconnect the 2 brazed locations shown in the figure below.  
(9) Pull the compressor toward you.  
When pulling the compressor toward you, be careful not to cause any abnormal  
deformation of the tube-with-flare-nut.  
CAUTION  
Remove the  
discharge sensor  
Inverter compressor  
Bolt  
Brazed locations (2)  
Tube-with-flare-nut  
Washer (1)  
Rubber washer (1)  
Bolt  
Washer (1)  
Rubber washer (1)  
Bolt  
Washer (1)  
Rubber washer (1)  
Crankcase heater  
Front view  
Fig. 22  
2 - 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
Installation  
(1) Remove the rubber stopper and tube cap (brazed) from the new compressor.  
(2) Install the crankcase heater onto the new compressor.  
(3) Place the 2 pieces of cushioning rubber in the designated positions on the compressor.  
(4) Place the 2 pieces of cushioning rubber onto the legs of the new compressor.  
When setting the compressor into the unit, be careful not to cause any abnormal  
CAUTION  
deformation of the tube-with-flare-nut.  
(5) Place the remaining cushioning rubber onto the new compressor, at the position shown in the figure below.  
(6) Remove the bolts that are temporarily fastening the pieces of cushioning rubber (inner 2 legs), and anchor  
the 3 compressor legs using the bolts, washers, and rubber washers.  
(7) Remove the flare nut from the new compressor, and connect the tube-with-flare-nut.  
(8) Shape the tubes and insert them at the 2 brazing locations.  
2
(9) Connect a manifold gauge to the high- and low-pressure outlet ports at the outdoor unit where the compres-  
sor was replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas replacement.  
(10) Perform copper brazing at the 2 brazing locations.  
(11) Follow the instructions in “6. Checking for Leakage After Repair” and check for leaks at the outdoor unit  
where the compressor was replaced.  
CAUTION  
At this time, also check for leaks at the flare nut connection on the tube-with-flare-nut.  
(12) Re-install all components that were removed. Re-install the electrical component box in the same position as  
it was before.  
Be sure to check for looseness of the power terminal connection at the compressor  
terminal plate, and to check by pulling vertically on the connections. If the termi-  
CAUTION  
nals become disconnected easily, replace the wiring Assy.  
(13) Follow the instructions in “7. Evacuating System” and apply vacuum to the outdoor unit where the compres-  
sor was replaced.  
Brazed  
locations (2)  
Tube-with-flare-nut  
Front view  
Cushioning rubber  
(Temporary fastening  
bolts - 2 inner legs)  
Crankcase  
heater  
Cushioning rubber  
(Inner 1 leg)  
Bolt  
Washer (1)  
Rubber washer (1)  
Fig. 23  
Fig. 24  
2 - 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
(B) Replacing the constant-speed compressor 1  
(Compressor 2 on remote controller alarm display)  
Removal  
(1) Connect the manifold gauge to the high- and low-pressure outlet ports at the outdoor unit where the compres-  
sor will be replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas replacement.  
(2) Follow the instructions in “1. Removing Panels” and “2. Removing Electrical Component Box and Duct” and  
remove the corresponding parts from the outdoor unit where the compressor will be replaced.  
(3) Remove the cap at the compressor terminal plate. Disconnect the power terminal.  
(4) Remove the crankcase heater.  
(5) Remove the bolts(3 locations), washers, and spacers (1 each at the 3 locations shown in the figure).  
* The compressor rear leg is not anchored.  
(6) Prepare to disconnect the 3 brazed locations shown in the figure.  
2
Constant-speed  
compressor  
(left side)  
Brazed locations (3)  
Remove  
discharge sensor  
Protect the oil  
equalizer tube  
connector  
Bolt  
Washer: 1  
s
Rubber washer: 1  
(1 each at the 3 locations)  
Crankcase heater  
Front view (Type 96)  
Fig. 25  
• Protect the sensors and surrounding plates, rubber, lead wires, clamps, and  
other items.  
Pay particular attention to protection of the oil equalizer tube connector parts,  
and removal of the discharge sensor.  
CAUTION  
An O-ring is mounted inside the oil equalizer tube connector parts. It must be  
protected and do not lose it.  
(7) Disconnect the 3 brazed locations shown in the figure 25.  
* First disconnect the ø1/4" (ø6.35 mm) tube, then disconnect the ø1/2" (ø12.7 mm) and ø7/8" (ø22.22 mm)  
tubes.  
(8) Pull the compressor toward you.  
2 - 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
Installation  
(1) Remove the 2 brazed tube caps (2 pieces) from the compressor.  
(2) Remove hexagonal caps from the compressor.  
* When removing the hexagonal caps, hold the fixing nut at the main unit side so as not to loose it with a  
wrench or spanner. And then, loosen and remove the hexagonal cap.  
Hexagonal cap  
Oil equalizer tube  
connector parts  
2
Fixing nut  
at the main unit side  
O-ring  
Fig. 26  
(3) Remove the oil equalizer tube connector parts along with the O-ring from the removed compressor and  
mount them on the replaced new compressor.  
(4) Install the crankcase heater onto the new compressor.  
(5) Temporary mount 2 cushion rubbers with bolts at the position as shown in the figure 27.  
Set up the leg of the new compressor onto the 2 cushion rubbers.  
Cushion rubbers  
Bolts  
(Temporary mounting: 2 locations  
at back side, each 1 piece)  
Front view  
Fig. 27  
2 - 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
Brazing  
locations (3)  
Bolt  
Washer: 1  
Rubber washer: 1  
(1 each at the 3 locations)  
Protect the oil  
equalizer tube  
connectors  
Cushioning  
rubber guide  
2
Front view  
Fig. 28  
(6) Set the remaining cushioning rubber beneath the new compressor leg at the locations shown in the figure 28.  
(7) Remove the bolts which are temporarily fastening the 2 pieces of cushioning rubber, and anchor the 3 com-  
pressor legs using the bolts, washers, and rubber washers.  
(8) Insert the pre-shaped tube assembly at the 3 brazing locations indicated.  
(9) Connect the manifold gauge to the high- and low-pressure outlet ports at the outdoor unit where the compres-  
sor was replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas replacement.  
(10) Perform copper brazing at the 3 brazing locations.  
In the same way as during removal, pay particular attention to protection of the oil  
equalizing tube connector parts shown in the figure 28.  
CAUTION  
An O-ring is mounted inside the oil equalizer tube connector parts. It must be pro-  
tected and do not lose it.  
(11) Follow the instructions in “6. Checking for Leakage After Repair” and check for leaks at the outdoor unit  
where the compressor was replaced.  
(12) Re-install all components that were removed. Re-install the electrical component box in the same position as  
it was before.  
Be sure to check for looseness of the power terminal connection at the compress or  
terminal plate, and to check by pulling vertically on the connections. If the termi-  
CAUTION  
nals become disconnected easily, replace the wiring Assy.  
(13) Follow the instructions in “7. Evacuating System” and apply vacuum to the outdoor unit where the compres-  
sor was replaced.  
2 - 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
10. Compressor  
(C) Replacing multiple compressors  
Removal  
(1) Follow the instructions in “(A) Replacing the inverter compressor,” “(B) Replacing constant-speed compressor,”  
and remove the compressors.  
* There is no predetermined sequence for removal; any compressor may be removed first.  
Installation  
(1) Follow the instructions in “(A) Replacing the inverter compressor,” “(B) Replacing constant-speed compressor,”  
and install the compressors.  
* There is no predetermined sequence for installation; any compressor may be installed first.  
2
2 - 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
11. High and Low Pressure Sensors  
The outdoor unit connection ports for the high and low pressure sensors employ Schrader-type push-to-release  
valves. Therefore it is not necessary to recover refrigerant when removing and installing them.  
11-1. Removing the High and Low Pressure Sensor  
(1) Follow the instructions in “1. Removing Panels” and “2. Removing Electrical Component Box and Duct” and  
remove the corresponding components from the outdoor unit where the high pressure sensor will be  
removed.  
(2) Disconnect the high & low pressure sensor connector socket (3P) (BLK) & (WHT) from terminals CN009 and  
CN024 on the outdoor unit control PCB of the outdoor unit where the high & low pressure sensor will be  
removed.  
(3) Use 2 adjustable wrenches in combination to remove the high & low pressure sensors.  
When removing the high & low pressure sensors, internal pressure will be applied by  
the refrigerant in the outdoor unit. The high & low pressure sensor connection ports on  
CAUTION  
2
the outdoor unit employs a Schrader-type valve.  
11-2. Installing the High and Low Pressure Sensors  
(1) Use 2 adjustable wrenches in combination to install the high and low pressure sensors.  
High pressure  
sensor  
Low pressure  
sensor  
Fig. 29  
2 - 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
12. Replacing 4-way Valve  
When replacing 4-way valve of type 96 (for type with 1 or 2 compressor), be sure to protect check valves, which are  
located adjacent to the 4-way valve, while performing replacement work. Type 72 (for type with 1 compressor) is  
not located near to the check valves, therefore no protection is necessary.  
12-1. When the replacement is available from the right side of the unit  
(1) Remove the front panel of the outdoor unit, then remove the right side panel of the unit.  
(2) Follow the instructions in “9. Pumping Out Refrigerant from Outdoor Unit”, recover the refrigerant of the out-  
door unit where the 4-way valve is located.  
(3) Connect the manifold gauge to the high and low-pressure outlet ports at the outdoor unit where the 4-way  
valve will be replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas replace-  
ment.  
(4) Prepare the brazing kit to disconnect the brazed parts (4 locations).  
2
CAUTION  
Protect the check valves as shown in the figure 30.  
Check valve  
4-way valve  
Brazed parts  
(4 locations)  
Fig. 30  
(5) After replacing the 4-way valve, follow the instructions in “6. Checking for Leakage After Repair”, and “7.  
Evacuating System”. The outdoor unit after replaced 4-way valve shall be checked for gas leakage and per-  
form system evacuation.  
(6) Fully open service valves on the outdoor unit.  
However, if only one outdoor unit is installed, leave the balance tube kept closed.  
(7) Charge the recovered refrigerant with the Refrigerant Recovery Unit by referring to the Installation Instruc-  
tions that came with the outdoor unit and the refrigerant recovery unit.  
2 - 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Repair Procedures  
12. Replacing 4-way Valve  
12-2. When the replacement is not available from the right side of the unit  
(1) Follow the instructions of “10. Compressor” and remove the constant-speed compressor 2.  
(2) Connect the manifold gauge to the high and low-pressure outlet ports at the outdoor unit where the 4-way valve  
will be replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas replacement.  
(3) Prepare the brazing kit to disconnect the brazed parts (4 locations).  
CAUTION  
Protect the check valves as shown in the figure 31.  
Check valve  
2
4-way valve  
Brazed parts  
(4 locations)  
Fig. 31  
(4) After replacing the 4-way valve, follow the instructionsin “10. Compressor”, and reinstall the removed constant-  
speed compressor 2 in the outdoor unit.  
2 - 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
– MEMO –  
2 - 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
Contents  
3. OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER  
1. Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2  
2. Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3  
3. Ordinary Display Controls and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4  
4. Monitoring Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9  
5. Outdoor Unit Alarm History Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11  
6. Mode Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12  
3
3 - 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
1. Overview  
[Service Checker Section]  
OUTDOOR UNIT MAINTENANCE REMOTE  
CONTROLLER (RCS-TM80BG) for W-2WAY  
ECO-i  
About the outdoor unit maintenance remote controller  
N
The outdoor unit utilizes nonvolatile memory (EEPROM) on  
its PCB. This allows EEPROM data to replace the setting  
switches that were present on previous PCBs. The outdoor  
unit maintenance remote controller is used to set and change  
these EEPROM data.  
In addition to setting and checking the outdoor unit EEPROM  
data, this remote controller can also be used to monitor the  
outdoor unit alarm history, monitor the various indoor and  
outdoor temperatures, and check the indoor unit connection  
status (number of units, operating mode, etc.).  
NOTE  
RCS-TM80BG  
Outdoor unit maintenance remote controller does not function as an  
ordinary remote controller. It is therefore only used for test runs and during servicing.  
Outdoor unit maintenance  
System diagram  
remote controller  
3
Outdoor unit  
Special service checker wiring  
Inter-unit control wiring  
(Servicing No.: 6231785082)  
Outdoor unit  
control PCB  
Indoor  
unit  
Indoor  
unit  
Remote controller Ass’y  
Remote  
controller  
Remote  
controller  
Operation manual included in package.  
L
The special service checker wiring is required in order to connect the outdoor unit maintenance remote controller  
to the outdoor unit PCB.  
Ordinary remote controllers or other controller are still required for the indoor units, even when the outdoor unit  
maintenance remote controller is connected.  
L
3 - 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
2. Functions  
Functions on the ordinary display  
N
(1) Functions: Button operations can be used to perform the following functions.  
• Start/stop of all indoor units  
• Switching between cooling and heating  
Test run of all indoor units  
• Double-speed operation of indoor units (Do not use for actual operation. Doing so may damage the devices.)  
(2) Display: The following can be displayed.  
• Alarm details display  
• No. of indoor/outdoor units  
• Unit Nos. of connected indoor/outdoor units  
• Indoor/outdoor unit operating status (blinks when an alarm occurs)  
• Indoor unit thermostat ON  
• Display of individual outdoor unit alarms  
Total operating time of outdoor unit compressors  
• Oil level of the outdoor unit oil sensor  
Total outdoor unit power ON time  
• Outdoor unit microcomputer version, other information  
Temperature monitor  
• Displays the indoor/outdoor unit sensor temperatures.  
N
N
N
3
Outdoor unit alarm history monitor  
• Displays the outdoor unit alarm history.  
Mode settings  
• Setting mode 1 and setting mode 2 are used to make the outdoor EEPROM setting.  
3 - 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
3. Ordinary Display Controls and Functions  
Functions on the ordinary display  
N
Connect the special service checker wiring to the outdoor unit PCB.  
The connection is shown in the figure below.  
Outdoor unit PCB  
RC (3P, BLU)  
PCB connector (3P, BLU)  
Special service checker wiring  
Relay connector (2P, WHT)  
Remote controller Ass’y  
3
L
L
If the communications line in the inter-unit control wiring is connected, it can be left as-is.  
In case of an independent outdoor unit (1 maintenance remote controller connected to 1 outdoor unit, automatic  
address setting for indoor units not completed), both setting mode 1 and setting mode 2 can be used.  
The overall system status for that refrigerant system is displayed.  
L
3 - 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
3. Ordinary Display Controls and Functions  
L
All units start/stop (Fig. 1)  
<Operation>  
The  
(ON/OFF operation) button can be used to  
start and stop all the indoor units.  
• The LED illuminates if any indoor units is operating.  
• The LED blinks if an alarm at any of the operating indoor  
units occurs.  
LED  
L
Cooling/heating change (Fig. 1)  
<Operation>  
The  
(MODE) button can be used to change  
between heating and cooling operation.  
• The display indicates the operating mode of the indoor  
unit with the lowest unit No.  
Fig. 1  
L
All units test run (Fig. 2)  
<Operation>  
The  
(CHECK) button can be used to start and stop a  
test run for all indoor units.  
3
• Press and hold for 4 seconds to turn ON.  
During the test run “TEST” is displayed.  
• The status of test runs performed from the indoor unit  
remote controller is not displayed on the outdoor unit  
maintenance remote controller.  
Fig. 2  
L
Double-speed  
• Do not use for actual operation.  
(Doing so may damage the devices.)  
<Operation>  
The timer button  
can be used to change between  
double-speed and normal operation.  
• During double-speed operation, the SLEEPING MODE  
mark is displayed.  
3 - 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
3. Ordinary Display Controls and Functions  
Display (functions)  
N
Use the temperature setting  
and  
buttons to change the item code.  
Item code  
Item  
Remarks  
Alarm code display  
Outdoor unit alarm  
Œ

No. of connected indoor units  
Quantity  
Unit Nos. of connected indoor unit  
Operating status of indoor unit  
7-segment display  
7-segment display  
7-segment display  
1 – 2  
Thermostat ON status of indoor unit  
No. of connected outdoor units  
Unit Nos. of connected outdoor units  
Operating status of outdoor unit compressor  
7-segment display  
7-segment display  
Compressor 1 operating time  
Compressor 2 operating time  
Compressor 3 operating time  
Compressor 1 oil level  
0 – 99999999 hrs  
0 – 99999999 hrs  
3
0 = Empty 1 = Insufficient 2 = Sufficient  
0 = Empty 1 = Insufficient 2 = Sufficient  
Compressor 2 oil level  
Compressor 3 oil level  
Outdoor unit power ON time  
Compressor 1 operation count  
Compressor 2 operation count  
Compressor 3 operation count  
0 – 99999999 hrs  
0 – 65535 times  
0 – 65535 times  
Alarm history 1 (most recent)  
Alarm history 2  
Alarm history 3  
Display only. Alarm code and unit No. of unit  
where alarm occurred are displayed alternately.  
0 = CCU  
Alarm history 4  
Alarm history 5  
1 – 2 = Outdoor unit  
Alarm history 6  
Alarm history 7  
Alarm history 8 (oldest)  
Firmware version  
Program version  
Display the version No. × 100.  
Display the version No. × 100.  
3 - 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
3. Ordinary Display Controls and Functions  
(3) XX-YY R.C.  
Locations where  
as shown in Fig. 3.  
,
Œ   
, and  
2
are displayed  
1
Ž
Displays the outdoor unit sub-bus address which is  
currently selected.  
XX = Outdoor system address on main bus line (1 – 30)  
YY = Outdoor unit sub-bus address (1 – 8).  
“1” appears when there is only 1 outdoor unit.  
LED  
3
3
Fig. 3  
<Sample displays>  
01: <No. of connected indoor units>  
4 units connected  
02: <Unit Nos. 1, 2, 3, and 4 are  
connected>  
Fig. 4  
Fig. 5  
3 - 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
3. Ordinary Display Controls and Functions  
Concerning the 7-segment, 4-digit display remote controller timer display  
N
The unit Nos. of connected units are indicated by four 7-segment digits (  
) and a colon.  
L
Display of unit Nos. 1 − 20  
OFF  
OFF  
OFF  
OFF  
Meaning of display colon  
1
6
11  
16  
3
8
13  
18  
4
9
14  
19  
2
7
12  
17  
5
10  
15  
20  
1 ~ 20 21 ~ 40 41 ~ 60 61 ~ 80  
ON  
ON  
ON  
ON  
is not displayed.  
L
Display of unit Nos. 21 − 40  
OFF  
26 OFF  
31 OFF  
OFF  
Meaning of display colon  
21  
36  
23  
28  
33  
38  
24  
29  
34  
39  
22  
27  
32  
37  
25  
30  
35  
40  
1 ~ 20 21 ~ 40 41 ~ 60 61 ~ 80  
ON  
ON  
ON  
ON  
L
L
The meaning of the colon changes in the same way to indicate unit Nos. up to 80.  
Sample displays of the connected indoor unit Nos.:  
3
Display of unit No. 1  
Display of unit Nos. 1 and 2  
Display of unit Nos. 1, 2, and 3  
Display of unit Nos. 1, 2, 3, and 4  
NOTE  
The change of the colon display (between unit Nos. 1-20 to unit Nos. 21-40) occurs automatically  
every 10 seconds. (However the display does not change if there are no higher-number units connected.)  
To change the display to the higher-number units before 10 seconds have passed, press the  
(FLAP)  
button.  
(A)  
(B)  
The total compressor operating time is displayed  
(in 1-hour units) using 8 digits.  
N
• When the first 4 digits are displayed, the top  
dot of the colon is illuminated. (Figure (A))  
• When the last 4 digits are displayed, the colon  
dot is OFF. (Figure (B))  
• The display of the first 4 digits and last 4 digits  
changes automatically after 10 seconds. The display  
can also be changed by pressing the  
button.  
(FLAP)  
10: <Compressor’s total operating time>  
(A) and (B) are displayed alternately.  
(The example here (0000, 0062) indicates 62 hours.)  
NOTE  
With the outdoor unit maintenance remote controller (when connected to the outdoor unit), the unit remote  
controller check functions will not operate.  
3 - 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
4. Monitoring Operations  
Display the indoor unit and outdoor unit sensor  
temperatures.  
<Operating procedure>  
Press and hold the  
(CHECK) button and  
Œ
buttons simultaneously for 4 seconds or longer to  
engage temperature monitor mode.  
During temperature monitoring,  
is illuminates.  
(The display and operations are the same as  
for monitor mode using the indoor unit remote  
controller.)  
4
Press the  
to monitor.  
button and select the indoor unit  
3

Ž
Press the temperature setting  
buttons and select the item code of the temperature  
to monitor.  
and  
1
2
The unit No. of the selected indoor unit, and the  
temperature data, are displayed.  
To end monitoring, press the  
The display returns to the normal display.  
(CHECK) button.  

3
NOTE  
The display does not blink.  
3 - 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
4. Monitoring Operations  
Display of unit No. 1 (main unit)  
N
DN  
Description  
Remarks  
Intake temp.  
°F  
E1  
E2  
E3  
°F  
°F  
°F  
Indoor unit  
Discharge temp.  
Discharge temp. setting  
Indoor unit electronic control valve position  
Discharge temp. 1  
Discharge temp. 2  
High-pressure sensor temp.  
Heat exchanger gas 1  
Heat exchanger liquid 1  
Heat exchanger gas 2  
Heat exchanger liquid 2  
Outdoor air temp.  
Not used  
°F  
°F  
STEP  
°F  
°F  
°F  
°F  
°F  
°F  
°F  
°F  
Inverter primary current  
CT2  
A
3
A
Outdoor unit  
MOV1 pulse  
STEP  
STEP  
°F  
MOV2 pulse  
Discharge temp. 3  
CT3  
A
MOV3 pulse  
STEP  
STEP  
°F  
MOV4 pulse  
Heat exchanger gas 3  
Heat exchanger liquid 3  
Low-pressure sensor temp.  
Suction temp.  
°F  
°F  
°F  
Oil 1  
°F  
Oil 2  
°F  
Oil 3  
°F  
Actual operating frequency  
Hz  
NOTE  
0A and subsequent items are outdoor unit data. 0A – 22 are for unit No. 1.  
2A – 42 are for unit No. 2.  
3 - 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
5. Outdoor Unit Alarm History Monitor  
Displays outdoor unit alarms only.  
Check the indoor unit alarm histories separately using the  
indoor unit remote controllers or other control device.  
<Operating procedure>  
Press and hold the  
(CHECK) button and  
Œ
button simultaneously for 4 seconds or longer to engage  
outdoor unit alarm history mode.  
During temperature monitoring,  
illuminates.  
The display and operations are the same as for the  
alarm history monitor performed from the indoor unit  
remote controller. However the “unit No.display shows  
the outdoor unit address.  
3
Press the  
which to monitor the alarm history.  
button and select the outdoor unit for  

Ž
1
5
4
2
Press the temperature setting  
and  
buttons and select the item code for the alarm history.  
The select outdoor unit address, the item code, and the  
alarm history (alarm data) are displayed.  
3
The outdoor unit address is displayed as R.C. XX-YY.  
System XX = Outdoor unit system address  
R.C. XX = Outdoor unit system address  
YY = Outdoor unit sub-bus address  
Item codes 01-08 are displayed. 01 indicates the most  
recent alarm.  
The alarm history displays the alarm code. (If no alarm  
are present, then -- -- is displayed.)  
To clear the alarm history, press the  
outdoor unit alarm history will be cleared.)  
button. (The  


To exit, press the  
(CHECK) button. The display  
returns to the normal display.  
3 - 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
6. Mode Settings  
Setting mode 1  
<Operating procedure>  
N
A
Display of first 4 digits  
Press and hold the  
(CHECK) button and  
(VENTILATION) button simultaneously for 4  
seconds or longer.  
Œ

Press the temperature setting  
and  
buttons to change the item code. The item codes  
and setting data are shown in the table of “List of  
Item Codes” on the next page.  
Press the timer time  
change the setting data.  
and  
buttons to  
Ž

5
To confirm the changed setting data, press the  
button.  
2
(At this time, all displays stop blinking and remain  
lit.)  
1
3
During this mode, “  
” is displayed, blinking.  
B
Display of last 4 digits  
The outdoor unit address display section displays  
“ALL,the item code and number (DN value in the  
table), and the setting data (8 digits).  
3
(The setting data is displayed in 8 digits. The  
A
display changes between the first 4 digits (Fig.  
)
B
and the last 4 digits (Fig.  
).  
When the first 4 digits are displayed, the top dot of  
the colon is illuminated.)  
To exit the setting mode, press the  
button.  
(CHECK)  

5
2
1
3
A
B
and  
are displayed alternately.  
(Example shows display of 0000 0001.)  
DN  
Parameter  
Description  
0 = Sensor input not present. Control is performed.  
1 = Sensor input present. Control is performed.  
2 = Sensor input not present. Control is not performed.  
3 = Sensor input present. Control is not performed.  
Snowfall sensor usage  
0 = Disabled  
2 = Quiet mode 2  
4 = Quiet mode 4  
1 = Quiet mode 1  
3 = Quiet mode 3  
Outdoor unit fan Quiet  
mode  
0 = None  
1 = Discharge temp. control only (Mode 3)  
2 = Demand only (Mode 2)  
Energy saving mode  
3 = Discharge temp. control + Demand (Mode 1)  
Energy saving operation  
plug  
0 = Independent  
1 = All indoor units linked  
0 = 0% 1 = 40 … 4 = 70 7 = 100 8 = 120  
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)  
0 = 0% 1 = 40 … 4 = 70 7 = 100 8 = 120  
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)  
Demand 1 current  
Demand 2 current  
3 - 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Outdoor Unit Maintenance Remote Controller  
6. Mode Settings  
Setting mode 2  
N
<Operating procedure>  
Press and hold the  
simultaneously for 4 seconds or longer.  
(CHECK) button,  
button, and  
button  
Œ

Ž
Press the temperature setting and  
code. The item codes and setting data are shown in the table below.  
Press the timer time and buttons to change the setting data.  
To confirm the changed setting data, press the button.  
(At this time, all displays stop blinking and remain lit.)  
buttons to change the item  
5
2
During this mode, “  
” is displayed, blinking. The display shows the set  

3
1
outdoor unit address “System XX-YY” (System XX = System address, YY =  
Address at outdoor unit sub-bus), item code number (DN value in the table  
below), and the setting data (8 digits).  
Fig. 7  
A
(The setting data is displayed in 8 digits. The display changes between the first 4 digits (Fig.  
) and the last 4  
B
digits (Fig.  
). When the first 4 digits are displayed, the top point of the colon is lit.)  
To exit setting mode, press the  
(CHECK) button. Returns to the normal display mode.  

3
A
Display of first 4 digits  
B
Display of last 4 digits  
5
2
1
3
<Refrigerant type> A and B are displayed alternately. (Example  
shows 0000 0410 (R410A).)  
List of Item Codes  
DN  
Parameter  
Description  
81  
Outdoor unit capacity  
0 = Disabled 224 = 72 Type 280 = 96 Type  
3 - 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
– MEMO –  
3 - 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
Contents  
4. REMOTE CONTROLLER FUNCTIONS  
1. Simple Settings Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2  
2. Detailed Settings Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4  
3. Remote Controller Servicing Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15  
4
4 - 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
1. Simple Settings Function  
This allows the filter lifetime, operating mode  
priority change, central control address, and other  
settings to be made for an individual or group-  
control indoor unit to which the remote controller  
used for simple settings is connected.  
[Remote Controller Functions Section]  
2
When simple settings mode is engaged, operation  
stops at the individual or group-control indoor unit  
to which the remote controller for simple settings is  
connected.  
<Procedure>  
3
4
Press and hold the  
and  
buttons  
Œ
simultaneously for 4 seconds or longer.  
7
,” unit No. “  
” (or “  
” in the case of  

group control), item code “  
,” and settings data  
” are displayed blinking on the remote  
controller LCD display (Fig. 1). At this time, the  
indoor unit fan (or all indoor unit fans in the case of  
group control) begins operating.  
RCS-TM80BG  
1
5
6
If group control is in effect, press the  
button and select the address (unit No.) of the  
indoor unit to set. At this time, the fan at the indoor  
unit begins operating.  
Ž
Fig. 1  
* If unit No. “  
” is displayed, the same setting  
4
will be made for all indoor units.  
Press the temperature setting  
/


buttons to select the item code to change.  
Press the timer time  
desired setting data.  
/
buttons to select the  
* For item codes and setting data, refer to the  
following page.  
Press the  
button. (The display stops blinking  
and remains lit, and setting is completed.)  
Press the  
button to return to normal remote  
controller display.  
4 - 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
1. Simple Settings Function  
List of Simple Setting Items  
Setting data  
Description  
Item code  
Item  
No.  
0000 Not displayed  
0001 150 hours  
0002 2,500 hours  
0003 5,000 hours  
0004 10,000 hours  
Filter sign ON time  
(fitlter life time)  
0005 Use the filter clogging sensor.  
0000 Standard (setting at time of shipping)  
Degree of filter fouling  
Highly fouled  
0001  
(Filter sign ON time is reduced to one-half the set time.)  
0001 Central control address 1  
0002 Central control address 2  
0003 Central control address 3  
Central control  
address  
0064 Central control address 64  
0099 No central control address set (setting at time of shipping)  
0000 Normal (setting at time of shipping)  
0001 Priority  
Operating mode  
priority change  
Compressor ON  
Compressor OFF  
0000  
0001  
0002  
0004  
0005  
0006  
MED 1 min., LO 3 min.  
LO  
LO  
LO  
MED  
MED  
MED  
MED  
LO  
Fan speed when  
heating thermostat is  
OFF  
MED 1 min., LO 3 min.  
MED  
LO  
0000 No shift  
4
0001 Shifts intake temperature 2°F down.  
0002 Shifts intake temperature 4°F down.  
0003 Shifts intake temperature 6°F down.  
0004 Shifts intake temperature 8°F down.  
0005 Shifts intake temperature 10°F down.  
Heating intake  
temperature shift  
0006 Shifts intake temperature 12°F down.  
0000 No heater  
0001 Heater installed  
Electric heater  
installation  
Humidifying when  
heater thermostat is  
OFF  
0000 No (setting at time of shipping)  
0001 Yes  
Permit/prohibit  
automatic  
heating/cooling  
0000 Permit  
0001 Prohibit  
0000 Normal  
0001 Cool only (Set “1” for item code OD.)  
Cool-only  
NOTE  
• In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF unless a  
vaporizing humidifier is used.  
• Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.  
• Do not change any setting data that does not appear in this list.  
• The 10-hp 4-way ceiling cassette has 2 indoor unit addresses. Set both of them.  
4 - 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
This allows the system address, indoor unit  
address, and other settings to be made for the  
individual or group-control indoor unit to which  
the remote controller used for detailed settings is  
connected.  
2
When detailed settings mode is engaged,  
operation stops at the individual or group-control  
indoor unit where the remote controller used for  
detailed settings is connected. Simple settings  
items can also be set at this time.  
<Procedure>  
3
Press and hold the  
and  
buttons  
Œ
,
simultaneously for 4 seconds or longer.  
,” unit No. “  
of group control), item code “  
data “  
” (or “  
” in the case  
7

,” and settings  
” are displayed blinking on the  
4
remote controller LCD display (Fig. 2).  
At this time, the indoor unit fan (or all indoor unit  
fans in the case of group control) begins operating.  
RCS-TM80BG  
1
6
1
5
If group control is in effect, press the  
button and select the address (unit No.) of the  
indoor unit to set. At this time, the fan at the indoor  
unit begins operating.  
Ž
Fig. 2  
4
Press the temperature setting  
/


buttons to select the item code to change.  
Press the timer time  
desired setting data.  
/
buttons to select the  
* For item codes and setting data, refer to the  
following page.  
Press the  
button. (The display stops blinking  
and remains lit, and setting is completed.)  
Press the  
button to return to normal remote  
controller display.  
4 - 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
List of Detailed Setting Items  
Setting data  
Description  
Item code  
Item  
No.  
Description  
No.  
No.  
Description  
4-Way Air Discharge (Mini)  
Semi-Concealed (X, XM)  
Slim Concealed-Duct  
(U, UM)  
1-Way Air Discharge  
Semi-Concealed (A)  
0000  
0001  
0005  
Concealed-Duct High  
Static Pressure (D)  
0006  
0007  
Ceiling-Mounted (T)  
0008  
Wall-mounted (K)  
Type  
Concealed Floor  
Standing (FM)  
0010  
0001  
0007  
Wall-mounted (F)  
22 (Type 7)  
0011  
0003  
28 (Type 9)  
0005  
0011  
36 (Type 12)  
71 (Type 24) For  
FHX2462 and FMHX2462  
0009  
0015  
45 (Type 15)  
80 (Type 24)  
56 (Type 18, 19)  
Indoor unit  
capacity  
0012 (Except FHX2462,  
112 (Type 36)  
0017  
140 (T  
ype 48)  
FMHX2462)  
0018  
160 (Type 54)  
0001 Unit No. 1  
0002 Unit No. 2  
0003 Unit No. 3  
System  
address  
0030 Unit No. 30  
0099 Not set  
0001 Unit No. 1  
0002 Unit No. 2  
0003 Unit No. 3  
Indoor unit  
address  
4
0064 Unit No. 64  
0099 Not set  
0000 Individual (1:1 = Indoor unit with no group wiring)  
0001 Main unit (One of the group-control indoor units)  
0002 Sub unit (All group-control indoor units except for main unit)  
0099 Not set  
Group control  
address  
–010 Shifts intake temperature by –20°F.  
–009 Shifts intake temperature by –18°F.  
Cooling  
intake  
temperature  
shift  
–001 Shifts intake temperature by –2°F.  
0000 No intake temperature shift  
0001 Shifts intake temperature by +2°F.  
0009 Shifts intake temperature by +18°F.  
0010 Shifts intake temperature by +20°F.  
0000 Function disabled  
Automatic  
stop time  
after  
operation  
start  
0001 Stops automatically 5 minutes after operation starts.  
0002 Stops automatically 10 minutes after operation starts.  
0123 Stops automatically 615 minutes after operation starts.  
*Can be set  
in 5-minute 0124 Stops automatically 620 minutes after operation starts.  
units.  
0125 Stops automatically 625 minutes after operation starts.  
4 - 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
Setting data  
Description  
Item code  
Item  
No.  
0000 5 minutes  
0001 4 minutes  
–010 –20°F  
–009 –18°F  
–008 –16°F  
(1B)  
Forced thermostat ON time  
Cooling discharge  
temperature shift  
0010 20°F  
–010 –20°F  
–009 –18°F  
–008 –16°F  
Heating discharge  
temperature shift  
0010 20°F  
0001  
0002  
0003  
2°F  
4°F  
6°F  
Temperature shift for  
cooling/heating change in  
auto heat/cool mode  
0007  
14°F  
0018 64°F (Lower limit at shipment)  
0019 66°F  
(Upper limit)  
(Lower limit)  
(Upper limit)  
(Lower limit)  
(Upper limit)  
0029 84°F  
0030 86°F (Upper limit at shipment)  
0016 60°F (Lower limit at shipment)  
0017 62°F  
4
0029 84°F  
0030 86°F (Upper limit at shipment)  
Change to remote  
control temperature  
setting range  
0018 64°F (Lower limit at shipment)  
0019 66°F  
0029 84°F  
(Lower limit)  
(Upper limit)  
(Lower limit)  
0030 86°F (Upper limit at shipment)  
0017 62°F (Lower limit at shipment)  
0018 64°F  
0026 78°F  
0027 80°F (Upper limit at shipment)  
0000 Normal  
0001 Ignore heat exchanger temperature conditions.  
0000 Filter input (differential pressure switch input)  
Humidifier operation  
Filter (CN70) input  
switching  
0001 Alarm input (for trouble input about air cleaner or similar device)  
Humidifier input (Operates linked with drain pump when humidifier is  
0002  
ON.)  
0000 Present (Setting at shipment)  
0002 None  
Indoor unit electronic  
control valve  
0000 Normal (Used as optional relay PCB or JEMA standard HA terminal.)  
0001 Used for OFF reminder  
T10 terminal switching  
0002 Fire prevention input  
4 - 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
Setting data  
Description  
Item code  
Item  
No.  
0000 No forced operation  
0001 Forced operation for 1 minute  
Automatic drain pump  
operation  
0060 Continuous operation  
0000 None  
0001 Ventilation fan operated by remote controller.  
0000 Not used. (Body sensor is used.)  
0001 Remote control sensor is used.  
Ventilation fan operation  
Wired remote controller  
sensor  
“Operation change  
control in progress”  
display  
0000 Normal (displayed)  
0001 Not displayed  
OFF reminder function  
for when weekly timer is  
used  
0000 None  
0001 Only stop time setting is enabled.  
0000 Discharge temperature control OFF  
0001 Discharge temperature control ON  
Discharge temperature  
control  
0013 Control temperature 55°F  
0014 Control temperature 57°F  
Heat exchanger  
temperature for cold air  
discharge  
(Heat exchanger control  
point for control to  
prevent cold air)  
0025 Control temperature 77°F  
0026 Control temperature 78°F  
0000 Output linked with fan. (ON when indoor unit fan is operating.)  
0001 Fan mode operation output  
0000 No delayed start  
Fan output switching  
0001 1 sec. delayed start  
0002 2 sec. delayed start  
Drain pump delayed  
start time  
4
0058 58 sec. delayed start  
0059 59 sec. delayed start  
0060 60 sec. delayed start  
0000 Humidifier output OFF. Drain pump stopped.  
0001 Humidifier output ON. Drain pump operates.  
Humidifier setting  
Humidifier output ON. Drain pump operates for 1 minute when total humidifier  
operating time reaches 60 minutes.  
0002  
0003 Humidifier output ON. Drain pump stopped.  
0000 Standard setting  
0001 Draft reduction mode (Flap lower-limit position is shifted upwards.)  
0000 Smudging reduction mode (Flap swing upper-limit position is shifted downwards.)  
0001 Normal mode  
Flap operation mode  
Flap swing mode  
0002 Draft reduction mode (Flap swing lower-limit position is upwards.)  
4 - 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
Setting data  
Description  
Item code  
Item  
No.  
DC fan tap operating  
mode  
Purpose  
0000 Standard  
High ceiling use  
For low  
Standard (setting at shipment)  
High ceiling setting 1 (with standard panel)  
Ultra long-life filter, oil guard panel, ammonia deodorizing  
0001  
static-pressure filter filter, optical regenerative deodorizing filter  
Fan tap setting  
(Fan tap change in order  
to prevent drop in air  
discharge caused by  
filter installation)  
High ceiling use  
High ceiling setting 2 (with standard panel)  
(Antibacterial) high-performance filter (90%)  
(Antibacterial) high-performance filter (65%)  
For low  
0003 static-pressure filter Air-cleaning unit, air-cleaning unit + optical regenerative  
deodorizing filter, deodorant (activated charcoal) filter  
For air-blocking  
For 3-way discharge, when discharge duct is connected  
material  
For air-blocking  
material  
0006  
For 2-way discharge  
0000 No humidifier output  
0001 1 sec.  
0002 2 sec.  
Humidifier ON time  
(ON time per 60  
seconds)  
0058 58 sec.  
0059 59 sec.  
0060 Continuously ON  
0000 Function disabled  
Repeat timer switching  
0001 Function enabled  
0000 Function disabled  
0001 Function enabled  
Timer function change  
prohibit  
Smudging control  
0000 No smudging control  
4
4 - 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
Simple setting items  
Item code  
Item  
Description  
Filter sign ON time setting  
(filter lifetime)  
Changes the indoor unit filter lifetime when a high-performance filter or other  
optional product is installed.  
01  
Reduces the filter sign ON time to 1/2 of the standard time (setting at the time of  
shipping) for cases when filter fouling is more severe than normal.  
02  
Degree of filter fouling  
Filter sign ON times for each model  
Filter sign ON time  
High  
High  
Super  
long-life  
Standard  
Long-life  
performance performance  
Model  
Model  
data  
Pressure  
differential  
switch  
65  
90  
1-Way Air Discharge  
0000  
×
75  
2500 1250  
×
×
×
×
×
×
×
×
×
Semi-Concealed (A)  
4-Way Air Discharge  
0001  
×
×
×
×
×
×
2500 1250 5000 2500 2500 1250  
×
×
×
(Mini)Semi-Concealed (X, XM)  
0005 (Slim)Concealed Duct (U, UM))  
×
×
1250 5000 2500 2500 1250 5000 2500  
Concealed Duct  
0006  
1250  
×
×
2500 1250 5000 2500  
High Static Pressure (D)  
0007 Ceiling-Mounted (T)  
0008 Wall-Mounted (K)  
0010 Floor-Standing (F)  
×
×
2500 1250  
×
×
×
×
×
×
×
×
2500 1250  
×
×
×
×
×
×
×
×
×
×
×
4
150  
150  
75  
75  
75  
×
×
×
×
×
×
×
×
×
×
×
×
0011 Concealed-Floor Standing (FM) 150  
×
Unit: hour  
NOTE  
indicates that there is no corresponding filter.  
150 indicates the filter sign ON time that is set at shipment.  
×
• High fouling: Set when  
is selected for the degree of filter fouling (item code  
).  
4 - 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
Item code  
Item  
Description  
Set when using a central control device.  
Used when setting the central control address manually from the  
remote controller.  
03  
04  
Central control address  
Operating mode priority change  
Note (1)  
NOTE  
(1) Explanation of operation mode priority change  
Enabled only in 2WAY MULTI heat-pump models.  
<Function>  
With indoor units that are installed in combination with an outdoor unit model where either heating or cooling  
operation can be selected, the operating mode of the indoor unit that starts first takes priority. The first indoor unit  
to operate can select any operating mode. When any mode other than fan mode is selected, then the operating  
modes that cannot be selected are not displayed on all remote controllers that are subsequently operated.  
“Operation change control in progress” is displayed, indicating that there are restrictions on the operating  
modes that can be selected.  
Controlling the operating mode from a specific remote controller  
- When there are multiple remote controllers in the same refrigerant system, it is possible to set one remote  
controller as the priority remote controller (the remote controller which is given priority for selecting the  
operating mode). (If 2 or more remote controllers are set as priority remote controllers, an alarm will occur at  
the remote controllers, and operation will not be possible.)  
- When the priority remote controller is set to the operating mode for control, then all other remote controllers can  
select only the permitted operating mode, regardless of whether the priority remote controller is operating or  
stopped.  
4
- When a controlled remote controller is operated, “Operation change control in progress” is displayed.  
Set mode at priority remote controller  
Cooling or dry  
Heating  
Modes that can be selected at other remote controllers  
Cooling, dry, fan  
Heating, fan  
Fan  
Whichever mode (heating/cooling) is selected first  
NOTE  
There are other methods to avoid control in which the mode selected first takes priority.  
Methods of remotely controlling the operating mode  
(1) Use the central functions of a central control device.  
(2) Use a remote control relay PCB at the outdoor unit.  
4 - 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
When the operating mode at the priority remote controller is changed, the operating modes of other remote  
controllers change as shown below.  
Mode change at priority remote controller Operating modes at other remote controllers  
Current mode  
New mode  
Current mode  
Cooling or dry  
Fan  
New mode  
Heating  
Cooling or dry  
Heating  
Fan (not changed)  
Cooling  
Heating  
Fan  
Heating  
Cooling  
Heating  
Cooling  
Dry  
Fan (not changed)  
Cooling (not changed)  
Dry (not changed)  
Cooling  
Cooling  
Dry  
Heating  
Fan  
Dry  
Fan (not changed)  
Cooling (not changed)  
Dry (not changed)  
Fan (not changed)  
Heating (not changed)  
Fan (not changed)  
Cooling  
Dry  
Cooling or dry  
Heating  
Fan  
Fan  
Fan  
Heating  
Fan  
Item code  
05  
Item  
Description  
Fan speed setting when  
heating thermostat is OFF  
Changes the fan speed setting when the heating thermostat is OFF.  
Heating intake temperature  
shift  
Shifts the intake temperature during heating.  
Can be set when the body thermostat is used.  
06  
07  
Set when cost distribution is performed using an AMY central control system  
or similar system, and when an optional electric heater is installed.  
(This is unrelated to control of the electric heater.)  
Electric heater installation  
4
Normally humidifying does not occur when the thermostat is OFF during  
heating operation. However, this setting can be changed in order to increase  
the amount of humidifying.  
Caution: In order to avoid water leakage and damage to the fan, do not use  
this setting unless a vaporizing humidifier is used.  
Humidifying when heater  
thermostat is OFF  
08  
This setting can be used to prevent the automatic heating/cooling display on  
the remote control if the unit configuration permits automatic heating/cooling  
operation.  
Permit/prohibit automatic  
heating/cooling  
0D  
0F  
This setting allows a heat pump indoor unit to be operated as a cooling-only  
unit.  
Cooling-only  
4 - 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
Item code  
Item  
Description  
10  
11  
Unit type  
Set when the indoor unit EEPROM memory is replaced during servicing.  
Indoor unit capacity  
System (outdoor unit)  
address  
12  
These are not set at the time of shipping from the factory.  
These must be set after installation if automatic address setting is not  
performed.  
13  
14  
Indoor unit address  
Group address  
Shifts the intake temperature during cooling and dry operation.  
(Enabled only when the body thermostat is used.)  
Increase this value when it is difficult to turn the thermostat ON.  
Cooling intake temperature  
shift  
17  
18  
1b  
Automatic stop time after  
operation start  
The time at which an indoor unit is automatically stopped after operation starts  
can be set in increments of 5 minutes.  
Use this setting to change the time for forced operation at installation or  
servicing from 5 minutes to 4 minutes.  
Forced thermostat ON time  
(Enabled only with PAC-i models.)  
Cooling discharge  
temperature shift  
1C  
1d  
Shifts the set value for models which perform discharge temperature control.  
(Discharge temperature control models: Floor discharge, wall built-in, direct  
expansion coil outdoor air treatment, high-fresh)  
Heating discharge  
temperature shift  
“Auto heat/cool” selects the operating mode automatically based on the  
difference between the room temperature and the temperature set on the  
remote controller. This setting establishes a shift temperature for the heating/  
cooling temperature setting relative to the remote controller temperature  
setting.  
Temperature shift for  
cooling/heating change in  
“auto heat/cool” mode  
1E  
4
Cooling temperature setting  
Shift temperature  
(+)  
Remote controller temperature setting  
Heating temperature setting  
Shift temperature  
(–)  
4 - 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
Item code  
Item  
Description  
1F (Upper limit)  
20 (Lower limit)  
Cooling  
Heating  
Drying  
21 (Upper limit)  
22 (Lower limit)  
This setting changes the temperature range (upper limit and lower limit)  
which is set from the remote controller or central control device.  
The set upper limit must be greater than or equal to the lower limit. If the  
temperature setting is to be a single point, set the upper limit and lower  
limit to the same temperature.  
Change to the remote  
control temperature  
setting range  
23 (Upper limit)  
24 (Lower limit)  
25 (Upper limit)  
Auto  
26 (Lower limit)  
heat/cool  
During heating operation, the humidifier operates when the heat  
Humidifier operation which ignores exchanger temperature is suitable for humidifying. This setting is  
29  
2A  
2C  
the heat exchanger temperature  
used to ignore this condition for humidifier operation and operate the  
humidifier more.  
Filter input switching  
This setting switches the filter input according to the purpose of use.  
This setting indicates whether or not an indoor unit electronic control  
valve is present.  
At the time of shipping, this setting is set according to the conditions of  
the indoor unit.  
Indoor unit electronic control valve  
T10 terminal input switching  
Ordinarily, the T10 terminal is used as the HA terminal at the time of  
shipping. However, this setting is used when the T10 terminal is used  
for OFF reminder or for fire prevention input.  
2E  
31  
It is possible to install a total heat exchanger and ventilation fan in  
the system, which can be started and stopped by the wired remote  
controller. The ventilation fan can operate linked with the start and  
stop of the indoor unit, or can be operated even when the indoor  
unit is stopped.  
4
Ventilation fan operation from  
remote controller  
Use a ventilation fan that can accept the no-voltage A contact as  
the external input signal.  
In the case of group control, the fans are operated together. They  
cannot be operated individually.  
This setting is used to switch from the body sensor to the remote  
controller sensor.  
Check that “remote controller sensor” is displayed.  
Do not use this setting with models that do not include a remote  
controller sensor.  
Switching to remote controller  
sensor  
32  
Do not use this setting if both the body sensor and remote sensor  
are used.  
In a MULTI system with multiple remote controllers, switching  
between heating and cooling is restricted, and “Operation change  
control in progress” is displayed.  
This setting is used to prevent this display from appearing.  
Refer to the item concerned with operating mode priorities.  
ON/OFF of “Operation change  
control in progress” display  
34  
35  
This setting switches the operation when the weekly timer is  
connected to the remote controller.  
This can be used to prevent cases in which the unit is accidentally  
left ON. There is no change when this setting is ON, however it is  
necessary to set the weekly timer ON time.  
OFF reminder function for weekly  
timer  
(Continued)  
4 - 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
2. Detailed Settings Function  
(Continued from previous page)  
Item code  
3C  
Item  
Description  
Heat exchanger temperature for  
cold air discharge  
The heat exchanger temperature control point for prevention of cold air  
discharge during heating operation can be changed.  
The indoor unit PCB optional output for the fan can be switched  
according to the purpose of use.  
3d  
3E  
Fan output switching  
The drain pump starts after the set time delay after cooling operation  
stops.  
Drain pump delayed start time  
40  
45  
46  
5d  
Humidifier drain pump setting  
DC flap operation mode  
DC flap swing mode  
This specifies the humidifier and drain pump setting.  
Changes flap operation to draft reduction mode.  
Selects the swing operation mode for the flap.  
Sets the DC fan tap according to the purpose of use.  
Change the settings data at the same time.  
DC fan tap setting  
Sets the humidifier output ON time for when the humidifier is operating.  
ON/OFF control is performed during humidifier operation.  
This setting therefore sets the ON time per 60-second interval.  
5E  
5F  
Humidifier ON time  
This setting enables a function that stops operation when the amount  
of time set for the OFF timer has passed after remote controller  
operation was started.  
Stop at time set for OFF timer after  
operation starts  
This function prohibits changes from being made to the remote  
controller time setting.  
60  
62  
Timer function change prohibit  
Smudging control  
4
Smudging control is disabled when 0000 is set.  
4 - 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
3. Remote Controller Servicing Functions  
The remote controller includes a number of servicing functions. Use these as needed for test runs and  
inspections.  
List of Servicing Functions  
Functions Description  
Button operation  
Press and hold the  
Reset operation  
Unit status  
Operation with  
forced thermostat  
ON  
button  
Test run  
for 4 seconds or longer.  
Press and hold the  
and  
Sensor  
temperature  
display  
Temperature  
display from each  
sensor  
Current operation is  
maintained.  
buttons for 4 seconds or  
longer.  
Press and hold the  
buttons for 4 seconds or  
longer.  
and  
Servicing check  
display  
Alarm history  
display  
Press the  
button.  
Filter life time,  
Press and hold the  
buttons for 4 seconds or  
longer.  
and  
operating mode  
priority, central  
Simple settings  
When settings are made  
from a remote controller,  
the indoor unit where that  
remote controller is  
control address,  
and other settings  
System address,  
indoor unit address,  
Press and hold the  
,
connected stops.  
Detailed settings central control  
address, and other  
settings  
and  
buttons for 4 seconds  
or longer.  
Automatic address  
setting based on  
Press and hold the  
and  
Automatic  
address  
command from  
the wired remote  
controller  
Automatic reset  
the timer operation  
buttons  
for 4 seconds or longer.  
Entire system stops.  
4
Press and hold the  
and  
Change of indoor  
Address change  
Press the  
button.  
the timer operation  
for 4 seconds or longer.  
buttons  
unit address  
4 - 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
3. Remote Controller Servicing Functions  
Test Run Function  
Operates the unit with the thermostat forced ON.  
<Procedure>  
2
3
Press and hold the  
longer.  
button for 4 seconds or  
Œ
Test” appears on the remote controller LCD  
display (Fig. 3).  

Start operation.  
Ž

Press the  
button to return to normal remote  
controller display.  
1 4  
RCS-TM80BG  
Fig. 3  
4
4 - 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
3. Remote Controller Servicing Functions  
Sensor Temperature Display Function  
(displayed regardless of whether unit is  
operating or stopped)  
2
N
The procedure below displays the sensor  
temperatures from the remote controller, indoor unit,  
and outdoor unit on the remote controller.  
<Procedure>  
Press and hold the  
and  
buttons  
Œ
simultaneously for 4 seconds or longer.  
The unit No. “X-X” (main unit No.), item code “XX”  
(sensor address), and servicing monitor “  

(sensor temperature) are displayed on the remote  
controller LCD display. (See Fig. 4 at right.)  
3
Press the temperature setting  
/
Ž
buttons and select the item code to the address of  
the sensor to monitor.  
RCS-TM80BG  
4
5
1
* Display shows a discharge temperature of 00XX at  
unit No. 1-1.  
(For the relationships between the sensor  
addresses and sensor types, refer to the table of  
temperature sensors and addresses on the next  
page.)  
In case, for example, the display shows “0185” in  
the figure above, a discharge temperature from the  
outdoor unit stands for 185°F.  
If group control is in effect, press the  
button to select the unit to monitor.  
Press the temperature setting buttons to select the  
item code to change.  


Fig. 4  
4
NOTE  
The temperature display appears as “- - - -” for units  
that are not connected.  
Press the  
button to return to normal remote  
controller display.  
* If monitor mode is engaged while normal operation  
is in progress, only the parts of the LCD display  
shown in the figure will change. Other parts continue  
to display the same information as during normal  
operation.  
4 - 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Remote Controller Functions  
3. Remote Controller Servicing Functions  
Outdoor unit sensors  
Indoor unit sensors  
Unit No.1  
0A  
0B  
0C  
0D  
0E  
0F  
Unit No.2  
02  
03  
04  
05  
06  
07  
Intake temp.  
2A  
2B  
2C  
2D  
2E  
2F  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
3A  
3B  
3C  
3D  
3E  
3F  
40  
41  
42  
Discharge temp. 1  
E1  
Discharge temp. 2  
High-pressure sensor temp.  
E2  
Heat exchanger gas 1  
E3  
Heat exchanger liquid 1  
Heat exchanger gas 2  
Discharge temp.  
Discharge temp. setting  
10  
Heat exchanger liquid 2  
11  
Outdoor air temp.  
Position of indoor unit electronic  
control valve  
12  
08  
13  
For inspection  
14  
CT2  
15  
For inspection  
16  
For inspection  
17  
18  
19  
For inspection  
1A  
1B  
1C  
1D  
1E  
1F  
For inspection  
Low-pressure sensor temp.  
Suction temp.  
Oil 1  
20  
Oil 2  
21  
22  
For inspection  
4
4 - 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
Contents  
5. TROUBLE DIAGNOSIS  
1. Contents of Remote Controller Switch Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . 5-2  
2. Outdoor Unit Control Panel LED Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4  
3. Remote Controller Servicing Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5  
4. W-2WAY ECO-i Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7  
5. Blinking Inspection Display on the Remote Controller . . . . . . . . . . . . . . . . . . . . . . . . 5-27  
6. Inspection of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28  
7. Test Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29  
8. Thermister Characteristic Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30  
5
5 - 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
1. Contents of Remote Controller Switch Alarm Display  
ON: Blinking:  
Wired  
OFF:  
Wireless  
remote  
control  
display  
remote controller  
receiver display  
Possible cause of malfunction  
Serial  
Remote controller is detecting Error in receiving serial communication signal. (Signal from  
communication error signal from indoor unit.  
errors  
Mis-setting  
main indoor unit in case of group control) Outdoor system  
address, indoor unit address, or indoor unit address  
independent/main/sub unit setting has not been made.  
(Auto address is not completed.)  
Operating lamp  
blinking  
<E01>  
Error in transmitting serial communication signal.  
<E02>  
Indoor unit is detecting error signal from remote controller and system controller.  
<<E03>>  
Indoor unit is detecting error  
signal from outdoor unit.  
• Error in receiving serial communication signal.  
• When turning on the power supply, the number of  
connected indoor units does not correspond to the number  
set. (Except R.C. address is “0.)  
Heating ready lamp  
blinking  
E04  
Group wiring failure of indoor units in the refrigerant system  
(occurring when remote controller is operated immediately  
after automatic address setting)  
Outdoor unit is detecting error  
signal from indoor unit.  
• Error in receiving serial communication signal.  
• There is an indoor unit which does not send signals when  
the power is ON.  
E06  
Improper setting  
Improper setting  
• Indoor unit address setting is duplicated.  
• Duplicated remote controller “main” setting.  
Automatic address setting start is prohibited.  
AP pin was short-circuited at time when automatic address  
setting was started.  
<<E08>>  
<<E09>>  
Operating lamp  
blinking  
E12  
Indoor unit communication  
error of group control wiring.  
Error of main indoor unit in receiving serial communication  
signal from sub indoor units.  
E18  
During auto. address setting, Number of connected indoor units is less than the number set.  
E15  
E16  
E20  
E24  
E25  
E26  
number of connected units  
does not correspond to number  
set.  
Number of connected indoor units is more than the number set.  
No indoor unit is connected during auto. address setting.  
Main outdoor unit is detecting error signal from sub outdoor unit.  
Duplicated outdoor unit address.  
Heating ready lamp  
blinking  
Mismatch in “No. of outdoor units” setting.  
Error of sub outdoor unit in receiving serial communication  
signal from main outdoor unit.  
E29  
Improper setting  
Connected indoor unit is not a multi unit.  
Duplication of main indoor unit address setting in group control.  
Duplicated indoor unit priority (priority indoor unit).  
<<L02>>  
<L03>  
L05  
5
Operating and heating  
ready lamps blinking  
simultaneously  
Duplicated indoor unit priority (non-priority indoor unit) and  
outdoor unit.  
L06  
Group control wiring is connected to individual control indoor unit.  
Indoor unit address is not set.  
L07  
L08  
Capacity code of indoor unit is not set.  
Mismatch of outdoor unit type.  
Duplication of outdoor R.C. address setting.  
Capacity code of outdoor unit is not set.  
<<L09>>  
L17  
L04  
Operating and heating  
ready lamps blinking  
simultaneously  
L10  
L18  
4-way valve operation failure  
Thermistor  
fault  
Indoor unit  
Indoor coil temp. sensor (E1)  
Indoor coil temp. sensor (E3)  
<<F01>>  
<<F03>>  
<<F10>>  
<<F11>>  
F04  
Operating and  
timer lamps blinking  
alternately  
Indoor suction air (room) temp. sensor  
Indoor discharge air temp. sensor  
Compressor 1 (INV) discharge temp. sensor  
Compressor 2 (constant speed) discharge temp. sensor  
Outdoor air temp. sensor  
Thermistor fault Outdoor unit  
Operating and timer  
lamps blinking  
altemately  
F05  
F08  
Heat exchanger 1 liquid temp. sensor  
Heat exchanger 1 gas temp. sensor  
F07  
F06  
Continued  
5 - 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
1. Contents of Remote Controller Switch Alarm Display  
ON: Blinking:  
OFF:  
Wired  
Wireless  
remote  
remote controller  
control  
display  
receiver display  
Possible cause of malfunction  
Thermistor fault Outdoor unit  
Ceiling panel connection failure  
Compressor intake temp. sensor (suction temp)  
High-pressure sensor  
F12  
F16  
Operating and timer  
lamps blinking  
altemately  
Low-pressure sensor  
F17  
Heat exchanger 2 liquid temp. sensor  
Heat exchanger 2 gas temp. sensor  
F24  
F23  
Timer and heat  
ready lamp blinking  
altemately  
<<P09>>  
<<P01>>  
<<P10>>  
<<P12>>  
P14  
Protective  
device  
Indoor unit  
Thermal protector in indoor unit fan motor is activated.  
Float switch is activated.  
Fan inverter protection function activated.  
Oxygen (O2) gas sensor activated.  
Outdoor unit  
Compressor 1 (INV) discharge temp. trouble  
High-pressure switch or Overload Protector (OLR)  
Reverse phase (missing phase) detected.  
DCCT, ACCT overcurrent (compressor less than 80 Hz)  
Compressor 2 (constant speed) discharge temp. trouble  
Outdoor unit fan trouble  
P03  
P04  
Operating and heat  
ready lamp blinking  
altemately  
P05  
P16  
P17  
P22  
DCCT, ACCT over current (80 Hz or more)  
INV compressor start failure. (Missing phase or lock alarm)  
P26  
P29  
Failure of nonvolatile memory IC (EEPROM) on indoor unit control PCB  
Operating and timer  
lamp blinking  
F29  
F31  
simultaneously  
Failure of nonvolatile memory IC (EEPROM) on outdoor unit control PCB  
Operating and timer  
lamp blinking  
simultaneously  
Protective  
device  
Overload current detected.  
Lock current detected.  
Compressor 2 (constant speed)  
Compressor 2 (constant speed)  
Compressor 1 (INV)  
H11  
H12  
H03  
H13  
H15  
H06  
H31  
H07  
H08  
H27  
No current detected when  
compressor was ON.  
Compressor 2 (constant speed)  
Discharge temp. sensor trouble Compressor 2 (constant speed)  
5
Outdoor unit protection  
Outdoor unit protection  
Low-pressure trouble  
HIC trouble alarm  
Timer lamp blinking  
(No display changes)  
Low oil alarm  
Connection failure of oil detection sensor  
Compressor 1 (INV)  
Compressor 2 (constant speed)  
Fusing of electromagnetic contact (Current detected when compressor was OFF)  
Automatic backup operation  
CHECK  
only blinking  
<< >> alarm indication: Does not affect the operation of other indoor units.  
<
> alarm indication: In some cases may affect the operation of other indoor units.  
5 - 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
2. Outdoor Unit Control Panel LED Display  
(
: ON  
: Blinking  
: OFF)  
LED (RED)  
Display meaning  
1
2
After the power is turned ON (and automatic address setting is not in progress), no communication  
with the indoor units in that system is possible.  
(Both ON)  
After power is turned ON (and automatic address setting is not in progress), one or more indoor  
units are confirmed in that system; however, the number of indoor units does not match the number  
that was set.  
(OFF)  
(ON)  
Automatic address setting was completed successfully. (After the power is turned ON, and  
automatic address setting is not in progress, the number of detected indoor units connected to that  
system matches the number that was set, and regular communications are occurring.)  
(Both OFF)  
Automatic address setting is in progress.  
(Blinking alternately)  
At time of automatic address setting, the number of indoor units did not match the number that was  
set.  
(Both blinking)  
Alarm display  
LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.  
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm  
N = Alarm No.  
(Blinking alternately)  
Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats.  
Alarm is “P17.”  
5
5 - 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
3. Remote Controller Servicing Functions  
Sensor temperature display function (displayed  
both when unit is running and stopped)  
Use the following check procedure to display the  
sensor temperatures from the remote controller,  
indoor unit, and outdoor unit sensors on the remote  
controller display.  
<Check procedure>  
Press and hold the  
(CHECK) button and  
button simultaneously for 4 seconds or  
longer.  
Œ
The following appears on the remote controller  
LCD display: unit No. X – X (main unit No.), item  
code XX (sensor address), and service monitor  
00XX (sensor temperature).  

RCS-TM80BG  
(See figure at right.  
)

Press the temperature setting  
and  
Ž
Example  
buttons to change the item code to the  
:
:
Unit No.  
sensor address of the sensor you wish to monitor.  
Item code (sensor address)  
Discharge temp. (TD)  
(For the relationship between the sensor address  
and sensor type, refer to the sensor temperature  
relationship table on next page.)  
:
If group control is in effect, press the  
button to change to the unit you wish to monitor.  


Press the  
(CHECK) button to return to normal  
remote controller operation.  
<Note> The temperature display for units that are not  
connected appears as “- - - -.”  
If monitor mode is engaged during ordinary  
operation, the only parts of the LCD display that  
5
change are those shown in  
in the figure.  

The other parts remain unchanged during normal  
operation.  
5 - 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
3. Remote Controller Servicing Functions  
Sensor Temperature Relationship Table  
Location where sensor  
Sensor address  
Sensor type  
Sensor address  
Sensor type  
is installed  
Remote controller temperature  
Indoor unit intake temperature  
Discharge temperature sensor  
Indoor unit heat exchanger  
temperature (E1)  
Indoor unit electronic expansion  
valve position  
Indoor unit  
Indoor unit heat exchanger  
temperature (E3)  
Unit No. Unit No.  
Unit No. Unit No.  
1
2
1
2
Discharge temperature 1  
Discharge temperature 2  
High-pressure sensor temperature  
Heat exchanger gas 1  
Outside air temperature  
CT2  
Low-pressure sensor temperature  
Detected reservoir tank temp.  
Detected oil temp. 1  
Detected oil temp. 2  
Outdoor unit  
Heat exchanger liquid 1  
Heat exchanger gas 2  
Heat exchanger liquid 2  
5
5 - 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
With type 96, the INV compressor is compressor 1, and the constant-speed  
compressor is compressor 2.  
With type 72, the INV compressor is compressor 1.  
Alarm code  
Alarm meaning  
Page  
E06  
E12  
E15  
E16  
E20  
E24  
Outdoor unit failed to receive serial communication signals from indoor unit.  
Automatic address setting start is prohibited.  
Automatic address setting alarm (too few units)  
Automatic address setting alarm (too many units)  
No indoor units at automatic address setting.  
5-9  
5-9  
5-9  
5-10  
5-10  
5-10  
Outdoor unit (INV) failed to receive communications from another outdoor  
unit (constant-speed).  
E25  
E26  
E29  
Outdoor unit address setting failure (duplication)  
Mismatch in outdoor unit quantity  
Outdoor unit failed to receive communication from outdoor unit (main)  
5-11  
5-11  
5-11  
F04  
F05  
F06  
F07  
F08  
F12  
F16  
F17  
F23  
F24  
F31  
Compressor 1 discharge temperature sensor trouble  
Compressor 2 discharge temperature sensor trouble  
Gas temperature sensor trouble at outdoor heat exchanger 1 (In)  
Liquid temperature sensor trouble at outdoor heat exchanger 1 (Out)  
Outdoor air temperature sensor trouble  
Compressor intake temperature sensor trouble  
High-pressure sensor trouble  
Low-pressure sensor trouble  
5-12  
5-12  
5-13  
5-13  
5-14  
5-14  
5-15  
5-16  
5-13  
5-13  
5-16  
Gas temperature sensor trouble at outdoor heat exchanger 2 (In)  
Liquid temperature sensor trouble at outdoor heat exchanger 2 (Out)  
Outdoor unit non-volatile memory (EEPROM) trouble  
H11  
H12  
H03  
H06  
H07  
H08  
H13  
H15  
H27  
H31  
Constant speed compressor 2 overcurrent alarm  
Constant speed compressor 2 lock current alarm  
Compressor 1 CT sensor disconnected or short-circuit  
Low-pressure switch activated  
5-17  
5-17  
5-18  
5-19  
5-20  
5-21  
5-18  
5-18  
5-21  
5-21  
No-oil alarm  
Compressor 1 oil detection sensor (connection) trouble  
Compressor 2 CT sensor disconnected or short-circuit  
Compressor 2 discharge temperature sensor disconnected  
Compressor 2 oil detection sensor (connection) trouble  
HIC trouble alarm  
5
L04  
L10  
L17  
L18  
Outdoor system address duplication  
Outdoor unit capacity not set  
Outdoor unit model mismatch  
4-way valve operation failure  
5-22  
5-22  
5-22  
5-22  
5 - 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
P03  
P04  
P05  
P16  
P17  
P22  
P26  
P29  
Compressor 1 discharge temperature trouble  
High-pressure switch activated  
5-23  
5-24  
5-24  
5-25  
5-23  
5-25  
5-26  
5-26  
Reverse phase (or missing phase) detected  
Compressor 1 (INV) overcurrent alarm  
Compressor 2 discharge temperature trouble  
Fan motor trouble  
Inverter compressor high-frequency overcurrent alarm  
Inverter compressor missing phase or lock alarm  
Blinking Inspection Display on the remote  
controller  
CHECK blinking (1)  
CHECK blinking (2)  
5-26  
5-27  
5
5 - 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
E06 Alarm  
Alarm code  
E06  
Alarm meaning  
Alarm conditions  
Probable cause  
Outdoor unit failed to receive serial communication signals from indoor unit.  
Outdoor unit failed to receive serial communication signals from indoor unit.  
(1) The indoor unit power was cut OFF after initial communications were completed.  
(2) An open circuit or short circuit occurred in the inter-unit control wiring after initial  
communications were completed.  
Check  
Check the power at the indoor and outdoor units, and check the inter-unit control wiring.  
This alarm is detected after initial communications are completed. Therefore, it does not occur in  
cases of “disconnected serial connector,no terminal unit set,or other trouble that occurs  
before initial communications are completed. If initial communications have not been completed,  
alarm E04 occurs.  
Correction  
Example  
Notes  
E12 Alarm  
Alarm code  
E12  
Alarm meaning  
Alarm conditions  
Automatic address setting start is prohibited.  
Automatic address setting was started when automatic address setting was in progress at  
another outdoor unit in the same link.  
Probable cause  
Check  
Automatic address setting is in progress at another outdoor unit.  
This alarm is not displayed on the remote controller. Therefore check the blinking on the outdoor  
unit PCB.  
Correction  
Wait for automatic address setting to be completed at the outdoor unit where it is currently in  
progress. Then start automatic address setting again.  
Example  
Notes  
E15 Alarm  
Alarm code  
E15  
Alarm meaning  
Alarm conditions  
Probable cause  
Automatic address setting alarm (too few units)  
The number of indoor units was too few when automatic address setting was performed.  
(1) The number of indoor units set at the indoor unit quantity setting SW (S004, S005) on the  
outdoor unit PCB is too many.  
(2) The inter-unit control wiring between indoor units has been cut.  
(1) Refer to the test run servicing materials and check the indoor unit quantity setting SW (S004,  
S005).  
Check  
5
(2) Check the inter-unit control wiring at the indoor and outdoor units.  
After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic  
address setting again.  
Correction  
Example  
Notes  
W-2WAY ECO-i switch position  
S004  
S005  
5 - 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
E16 Alarm  
Alarm code  
E16  
Alarm meaning  
Alarm conditions  
Automatic address setting alarm (too many units)  
• The number of indoor units was too many when automatic address setting was performed.  
• After initial communications were completed, an unrecognized unit was detected.  
(1) The number of indoor units set at the indoor unit quantity setting SW (S004, S005) on the  
outdoor unit PCB is less than the number set.  
Probable cause  
(2) The inter-unit control wiring is wired incorrectly.  
Check  
(1) Refer to the test run servicing materials and check the number of indoor units that is set.  
(2) Check the inter-unit control wiring at the indoor and outdoor units.  
After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic  
address setting again.  
Correction  
Example  
Notes  
E20 Alarm  
Alarm code  
E20  
Alarm meaning  
Alarm conditions  
Probable cause  
No indoor units at automatic address setting.  
When automatic address setting was performed, no indoor units were recognized.  
(1) The inter-unit control wiring from the outdoor unit to the indoor units has been cut.  
(2) Serial connector 1 (CN001) is disconnected at the outdoor unit.  
(3) The power is OFF at all indoor units in the system.  
Check  
(1) Check whether the inter-unit control wiring from the outdoor unit to the indoor units is cut.  
(2) Check whether serial connector 1 (CN001) is disconnected at the outdoor unit.  
(3) Check the power at the indoor units.  
Correction  
Example  
Notes  
(1) Reconnect the inter-unit control wire from the outdoor unit to the indoor unit.  
Position of serial connector CN001 on W-2WAY ECO-i  
CN001  
5
E24 Alarm  
Alarm code  
E24  
Alarm meaning  
Alarm conditions  
Probable cause  
Outdoor unit (INV) failed to receive communications from other outdoor unit (constant-speed).  
After initial communications were completed, communications from an outdoor unit stopped.  
(1) After initial communications were completed, the control wiring between main and sub  
outdoor units was cut.  
(2) After initial communications were completed, the outdoor unit power was turned OFF.  
Check  
Correction  
Example  
Notes  
5 - 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
E25 Alarm  
Alarm code  
E25  
Alarm meaning  
Alarm conditions  
Outdoor unit address setting failure (duplication)  
Communication by outdoor unit main-sub control wiring was received that contained the same  
address as that unit 5 times or more within 3 minutes.  
The unit number is set incorrectly.  
Probable cause  
Check  
Check the unit number again.  
Correction  
Example  
Notes  
Correct the incorrect unit number setting.  
Recovery from this alarm occurs automatically (when communication that contains the same  
address is not received for 3 minutes).  
E26 Alarm  
Alarm code  
E26  
Alarm meaning  
Alarm conditions  
Mismatch in outdoor unit quantity  
After power initialization, the set outdoor unit quantity did not match the number of outdoor units  
detected on the outdoor unit main-sub control wiring for 3 minutes or longer.  
(1) The outdoor unit quantity is set incorrectly.  
(2) The outdoor unit main-sub control wiring is cut.  
(1) Check the outdoor unit quantity setting again.  
Probable cause  
Check  
(2) Check the outdoor unit main-sub control wiring.  
Correction  
(1) Correct the incorrect outdoor unit quantity setting.  
(2) Repair the outdoor unit main-sub control wiring.  
Example  
Notes  
Recovery from this alarm occurs automatically (when the set outdoor unit quantity matches the  
number of outdoor units detected on the outdoor unit main-sub control wiring).  
E29 Alarm  
Alarm code  
E29  
Alarm meaning  
Alarm conditions  
Probable cause  
Outdoor unit failed to receive communication from outdoor unit (main).  
Outdoor unit communications from outdoor unit (main) were interrupted for 3 minutes or longer.  
(1) After initial communications were completed, the outdoor unit main-sub control wiring was  
cut.  
5
(2) After initial communications were completed, the RC connector became disconnected.  
(3) The power at the outdoor unit (main unit) is turned OFF.  
(1) Check the outdoor unit main-sub control wiring.  
(2) Check the RC connectors.  
Check  
(3) Check the power at the outdoor unit (main).  
(1) Repair the outdoor unit main-sub control wiring.  
(2) Correct the RC connector connection.  
Correction  
(3) Turn ON the outdoor unit (main) power.  
Example  
Notes  
5 - 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
F04, F05 Alarm  
Alarm code  
F04, F05  
Alarm meaning  
Compressor 1 discharge temperature sensor trouble, compressor 2 discharge temperature  
sensor trouble.  
Alarm conditions  
(1) Discharge temp. of 212°F or higher was detected 20 minutes or more after that compressor  
stopped operating.  
(2) Discharge temp. of 158°F or higher was detected after all compressors had been stopped for  
60 minutes or longer.  
(3) A/D step is 10 steps or less (short circuit).  
Probable cause  
(1) Sensor malfunction  
• Sensor element malfunction  
• Sensor wiring is partially disconnected, resulting in increased electrical resistance.  
This alarm does not occur when the wiring is cut or when the connector is not connected to  
the outdoor unit PCB.  
(2) Crossed wiring or installation error  
• The discharge temperature sensor of that compressor is connected to the discharge tube  
of the other compressor.  
• The connector for the discharge temperature sensor of the problem compressor is  
connected to the outdoor unit PCB connector for the other compressor.  
(3) Outdoor unit PCB failure  
(4) The check valve on the discharge tube for that compressor is wet.  
(5) An air short blockage in the area around the outdoor unit has increased the outdoor unit  
ambient temperature, reducing the cooling effects after the compressor stops.  
(6) There is a cause that results in P03, P17, or P02 alarm.  
(7) Electrical noise  
Check  
(1) Sensor malfunction and outdoor unit PCB failure  
Trouble: • Constantly indicates a high temperature.  
• When monitoring software or other means are used for monitoring, the discharge  
temperature at times fluctuates suddenly and wildly.  
• In some cases, the precise temperature may not be known, even when monitoring  
software is used.  
Check: • Wiggle the sensor and check whether the trouble continues.  
• Check whether the connector is partially disconnected from the PCB.  
An F04 alarm will not result if the connector is completely disconnected (circuit is  
open).  
• If the cause is still uncertain, check the following to determine whether a sensor or  
PCB failure has occurred.  
Step 1: Connect the other compressor discharge sensor, or a discharge sensor where  
the F04 alarm has not occurred, to the connector for this compressor on the  
PCB. Measure the temperature at the same point (a location where temperature  
fluctuations are small), and check whether there is a temperature difference.  
5
Difference  
A PCB or sensor failure is possible.  
¡
No difference PCB and sensor are normal.  
¡
Step 2: If an abnormality was found at Step 1, connect the problem compressor  
sensor to the other compressor connector on the PCB, or to the PCB  
connector of a device where the F04 alarm has not occurred. Measure the  
temperature at the same point (a location where temperature fluctuations are  
small), and check whether there is a temperature difference.  
Difference  
Sensor failure.  
¡
No difference PCB failure.  
¡
It is convenient at this time to have a discharge temperature sensor on hand.  
(2) Crossed wiring or installation error  
Trouble: Although the other compressor is operating and this compressor is stopped, the  
discharge temperature of the other compressor does not increase and the discharge  
temperature of this compressor rises.  
* The discharge temperature remains high immediately after the compressor stops. Wait  
for some time after the compressor stops and observe.  
Check: Check for crossed wiring and installation errors.  
Continued  
5 - 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
Check  
(3) Leakage from the discharge tube check valve  
Trouble: Although the other compressor is operating and this compressor is stopped, the  
discharge temperature of this compressor rises together with the temperature of the  
other compressor.  
(4) The ambient temperature around the outdoor unit when it is stopped is 109°F or higher.  
(5) If the cause is still unknown after checking the above, then it is possible that electrical noise is  
the cause of the trouble. It is necessary to provide a line filter or carry out other noise  
countermeasures.  
Correction  
(1) Replace the sensor.  
(2) Replace the outdoor unit PCB.  
(3) Carry out noise countermeasures.  
(4) Repair the refrigerant tubing.  
(5) Adjust the amount of refrigerant.  
(6) Correct the trouble.  
Example  
Notes  
(1) Sensor wiring is partially cut.  
This alarm does not indicate that the sensor is disconnected.  
In order to prevent overheating during operation, the outdoor units in this system will not allow a  
compressor to start if the discharge temperature does not decrease while the compressor is  
stopped. If a sensor malfunction results in continuous detection of a high discharge temperature,  
then the compressor may stop for no apparent reason. The purpose of this alarm is to facilitate  
identification of the problem in this case.  
F06, F23 Alarm  
Alarm code  
F06, F23  
Alarm meaning  
Gas temperature sensor trouble at outdoor heat exchanger 1; Gas temperature sensor trouble at  
outdoor heat exchanger 2  
Alarm conditions  
Probable cause  
Check  
(1) A/D step is 10 steps or less (short circuit).  
(2) A/D step is 1014 steps or more (open circuit).  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by  
the microcomputer.  
Correction  
Example  
Notes  
5
F07, F24 Alarm  
Alarm code  
F07, F24  
Alarm meaning  
Liquid temperature sensor trouble at outdoor heat exchanger 1; Liquid temperature sensor trouble  
at outdoor heat exchanger 2  
Alarm conditions  
Probable cause  
Check  
(1) A/D step is 10 steps or less (short circuit).  
(2) A/D step is 1014 steps or more (open circuit).  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by  
the microcomputer.  
Correction  
Example  
Notes  
5 - 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
F08 Alarm  
Alarm code  
F08  
Alarm meaning  
Alarm conditions  
Outdoor air temperature sensor trouble  
(1) A/D step is 10 steps or less (short circuit).  
(2) A/D step is 1014 steps or more (open circuit)  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
Probable cause  
Check  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by  
the microcomputer.  
Correction  
Example  
Notes  
F12 Alarm  
Alarm code  
F12  
Alarm meaning  
Alarm conditions  
Compressor intake temperature sensor trouble  
(1) A/D step is 10 steps or less (short circuit).  
(2) A/D step is 1014 steps or more (open circuit)  
Probable cause  
Check  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by  
the microcomputer.  
Correction  
Example  
Notes  
5
5 - 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
F16 Alarm  
Alarm code  
F16  
Alarm meaning  
High-pressure sensor trouble (abnormal rise in high pressure) (In some cases this may not be  
the result of a high-pressure sensor malfunction.)  
Alarm conditions  
Probable cause  
• High-pressure SW activated although the detected pressure was lower (439.4 psi or below)  
than the high-pressure SW activation pressure: Undershift  
• High-pressure SW failed to activate although the detected pressure was higher (497.5 psi or  
above) than the high-pressure SW activation pressure: Overshift  
• The saturation temperature at the detected pressure is 10°F or more below the highest indoor-  
unit E1 temperature continuously for 30 minutes.  
• High-pressure sensor disconnected or open circuit.  
(1) High-pressure sensor malfunction  
(2) Failure to connect the connector to the outdoor unit PCB  
(3) Failure to open the service valve  
(4) Clogged tubing  
(5) Valve leakage  
(6) Over-charging  
(7) Outdoor unit PCB failure  
(8) Electrical noise  
Check  
(1) High-pressure sensor failure  
• Check the sensor resistance value. (Use a tester and measure the resistance between  
sensor No. 1 and No. 3)  
Resistance of less than 10k indicates a short circuit or other trouble.  
Ω
Resistance of 10k - 200k is normal. Resistance of more than 200k indicates  
Ω
Ω
Ω
an open circuit or other trouble.  
• Connect a gauge to the high-pressure outlet and check for changes in the value  
dispalyed by the monitoring software, and for large deviation of the gauge pressure.  
• During heating, check whether the temperature is lower than the highest indoor-unit E1  
temperature.  
* The pressure detected by the high-pressure sensor is the highest pressure in the system.  
Therefore during heating the converted saturation temperature will never be lower than  
any indoor-unit E1 temperature. During cooling this temperature will never be lower  
than the outdoor unit liquid temperature.  
(2) Failure to open the service valve, clogged tubing, valve leakage, over-charging.  
In all of these cases an alarm occurs when there are rapid pressure fluctuations and tracking  
of the detected pressure is poor.  
• Check the open/closed status of the valve.  
• Check for clogging of the tubing.  
To check for clogging, disconnect the high-pressure sensor from the PCB and check  
whether the high-pressure SW activates.  
• Check for valve leakage and over-charging  
5
When valve leakage or over-charging occurs, refrigerant is likely to accumulate in the  
outdoor units or indoor units, resulting in a sudden rise in pressure at start that occurs  
before the refrigerant in the heat exchanger is discharged.  
* The representative valves to check are the liquid valves and mechanical valves.  
(3) Outdoor unit PCB failure  
• The check items are the same as for a high-pressure sensor malfunction.  
A normal PCB is needed to determine whether the problem is a PCB failure or a pressure  
sensor malfunction. If an abnormality was found at the check items for a high-pressure  
sensor malfunction, first try replacing the PCB and check again.  
Trouble is corrected: Outdoor unit PCB failure  
Trouble is not corrected: High-pressure sensor malfunction  
Continued  
5 - 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
Correction  
(1) Replace the high-pressure sensor.  
Caution: Because the high-pressure sensor connection employs a Schrader-type valve, it can  
be removed and replaced. However, the high-pressure sensor can be easily  
damaged by high voltage; therefore use sufficient caution with regard to static  
electricity.  
(2) Replace the PCB.  
(3) Correct the locations of problems in the refrigeration cycle.  
• Correct locations where clogging or leakage has occurred.  
• In the case of over-charging, recover refrigerant. (Adjust the amount of refrigerant).  
Guide for over-charging  
Be sure to connect the gauge to the high-pressure outlet when checking for over-charging.  
During cooling: The following does not apply when outdoor air temperature is low or when fan  
speed is controlled. When both compressor 1 and compressor 2 are  
operating, and the fan mode is 14 (maximum fan speed), then the high  
pressure saturation temperature should be approximately 30°F above the  
outdoor air temperature. If it is 10°F or more above this level, then it is  
possible that over-charging may have occurred.  
During heating: There is an indoor unit where refrigerant flow is poor (E1 temperature and  
discharge temperature are low), and the mechanical valve of that unit is  
opened to 300 pulses or more, and the E1 temperature is close to room  
temperature. However be aware that this kind of data results often when  
there is a height difference between indoor units. Reducing the amount of  
refrigerant will improve the refrigerant flow, however reducing it too much will  
increase the likelihood of alarms related to low oil level (scroll-side), the low  
pressure SW, and discharge temperature. Use caution.  
Example  
This alarm may result when the service valve is closed or when valve leakage (particularly from  
the mechanical valve) occurs.  
F17 Alarm  
Alarm code  
F17  
Alarm meaning  
Alarm conditions  
Low-pressure sensor trouble  
(1) Sensor short circuit  
(2) Sensor open circuit  
Probable cause  
Check  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote monitor or a PC monitor to check the temperature that is recognized  
5
by the microcomputer.  
Correction  
Example  
Notes  
F31 Alarm  
Alarm code  
F31  
Alarm meaning  
Alarm conditions  
Outdoor unit non-volatile memory (EEPROM) trouble  
(1) Non-volatile memory is not present when power initialization occurs.  
(2) Read values do not match after writing to non-volatile memory is complete.  
Probable cause  
(1) Memory was not inserted after the PCB was replaced.  
(2) The lifetime of the non-volatile memory has been reached.  
(3) Non-volatile memory is installed incorrectly (wrong direction, bent pins, etc.).  
Check  
(1) Check the non-volatile memory on the PCB.  
Correction  
Example  
Notes  
5 - 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
H11, H12 Alarm  
Alarm code  
H11, H12  
Alarm meaning  
H11: Constant speed compressor 2 overcurrent alarm  
H12: Constant speed compressor 2 lock current alarm  
Alarm conditions  
Probable cause  
H11: During operation, the compressor current value exceeded 20 A for 30 seconds or longer.  
However this alarm is not detected for 4 seconds after the compressor starts.  
H12: During operation, the compressor current value exceeded 29 A for 4 seconds or longer.  
However this alarm is not detected for 2 seconds after the compressor starts.  
(1) Compressor failure (locked or partially locked)  
(2) CT circuit failure (including cut wiring)  
(3) Missing power phase  
(4) Low power voltage  
(5) PCB failure  
Check  
(1) Compressor failure (partially locked)  
Trouble: Current value during operation greatly exceeds the value shown above.  
Check: When the current for each phase is measured with a clamp meter or similar  
instrument, check that the current value for all phases is not high. If MG was forced  
ON (use caution), check that compressor noise will not occur or the compressor will  
not run with a groaning sound.  
(2) CT circuit failure, PCB failure  
Trouble:  
Check: • Check for poor connector contact.  
• Check the continuity of the CT circuit.  
• Install a normal CT in place of this CT and check. If current is detected, then the  
PCB can be jedged OK.  
CT circuit failure  
• Check that current is flowing in the phase where the CT circuit is connected.  
Check voltage and current.  
(3) Missing power phase  
Trouble: This alarm primarily occurs when the T-phase is missing. When the R-phase or  
S-phase is missing, CT trouble or PCB continuity trouble occur. However this may not  
be true in the case of a missing phase caused by magnet SW trouble.  
Check: There is the possiblility of a magnet SW failure. Therefore, check the phase voltage at  
a location that is as close to the compressor as possible.  
(4) Low power voltage  
Trouble: In most cases, this occurs when another constant-speed compressor (including  
compressors in other units) or other dvice starts. It also occurs when the power  
wiring is extremely long.  
Check: Check the voltage between each of the phases. However if this troube occors when  
other devices or compressors start, then an oscilloscope is required.  
(5) PCB failure  
5
Trouble:  
Check: Check that the current value measured with the clamp meter is not lower than the  
value measured with the PC or remote controller.  
(6) If the cause is still unknown after checking the above, then it is possible that noise is the  
cause of the trouble. It is necessary to connect a PC or other instrument.  
(1) Replace the compressor.  
Correction  
(2) Replace the CT circuit.  
(3) Repair the power circuit.  
(4) Adjust the primary-side power. Repair the power wiring.  
(5) Replace the outdoor unit PCB.  
(6) Correct the trouble.  
* In the case of a compressor failure, it is likely that steps must be taken to correct the cause  
of the compressor failure (such as liquid back-up) in order to prevent recurrence. Be sure to  
check that there is no cause which may resuit in compressor locking.  
Example  
5 - 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
H03, H13 Alarm  
Alarm code  
H03, H13  
Alarm meaning  
H03: Compressor 1 CT sensor disconnected or short-circuit  
H13: Compressor 2 CT sensor disconnected or short-circuit  
Alarm conditions  
Probable cause  
Compressor 1: Current value of more than 18.0 A is detected while the compressor 1 is stopped.  
Compressor 2: Current value at compressor 2 is less than 2.0 A when 2 seconds or more had  
passed after the compressors began operation and output.  
* No current is detected even though the compressor is operating.  
(1) CT circuit failure (including cut wiring, etc.)  
(2) Disconnected CT circuit connector  
(3) Missing phase where CT circuit is connected  
(4) This CT circuit is connected to the connector of the other CT circuit.  
(5) PCB failure  
(6) Electrical noise  
Check  
(1) CT circuit failure, PCB failure  
Trouble: • Current value during compressor operation is below the threshold value.  
Check: • Check that the connector is not disconnected.  
• Check the continuity of the CT circuit.  
• Install a normal CT in place of this CT and check. If current is detected, then the  
PCB can be judged OK.  
CT circuit failure  
• Check that current is flowing in the phase where the CT circuit is connected.  
Check voltage and current.  
(2) Crossed wiring or installation error  
Trouble: When the compressor is stopped, the current value at the other compressor is high.  
When this type of condition occurs, seizing-detection control takes priority.  
(3) If the cause is still unknown after checking the above, then it is possible that noise is the  
cause of the trouble. It is necessary to connect a PC or other instrument.  
(1) Replace the CT circuit.  
Correction  
(2) Replace the outdoor unit PCB.  
(3) Correct the problem.  
Example  
Notes  
(1) The connector was not inserted after the PCB was replaced.  
Use a normal CT as a tool to determine whether the trouble is a PCB failure or CT failure.  
H15 Alarm  
Alarm code  
H15  
Alarm meaning  
Compressor 1 discharge temperature sensor disconnected; Compressor 2 discharge temperature  
sensor disconnected  
5
Alarm conditions  
This alarm occurs when the discharge sensor temperature detector is not inserted into the tube’s  
sensor holder, or when the sensor itself has suffered some kind of malfunction other than a cut  
wire.  
• When outdoor air temperature is 50°F or higher:  
Alarm occurs if the temperature detected by the discharge sensor has changed by less than  
4°F when the compressor has operated for 10 minutes immediately after start.  
• When outdoor air temperature is below 50°F:  
Alarm occurs if the temperature detected by the discharge sensor has changed by less than  
4°F when the compressor has operated for 30 minutes immediately after start.  
(1) Discharge sensor temperature detector is not inserted into the tube’s sensor holder.  
(2) Discharge sensor itself has suffered some kind of malfunction other than a cut wire.  
(1) Check that the discharge temperature sensor is inserted into the sensor holder.  
(2) Check that sufficient heat-conducting putty is applied.  
Probable cause  
Check  
(3) Remove the discharge sensor from the sensor holder and expose the sensor to the outside  
air for approximately 5 minutes. Check that the temperature detected by the sensor changes  
to match the outside air temperature. (However the sensor cannot detect temperatures at or  
below 32°F.)  
Correction  
Example  
(1) Install the sensor into the holder, and apply sufficient heat-conducting putty.  
(2) If the sensor is malfunctioning, replace it.  
5 - 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
H06 Alarm  
Alarm code  
H06  
Alarm meaning  
Alarm conditions  
Low-pressure switch activated  
A report occurs during A/C operation when the low-pressure sensor installed at constant  
low-pressure parts detects a pressure of 7.3 psi or less continuously for 2 minutes,  
or an instantaneous pressure of 2.9 psi or less. (These values represent abnormal low pressure  
which may damage the compressor.)  
However, the alarm does not actually occur the first 2 times that the above operation takes place.  
At these times, the outdoor unit is stopped and the conditions are monitored. The alarm occurs  
when the above operation occurs for the fifth time. The first 4 times before the alarm occurs are  
called “pre-trip.After pre-trip occurs, if the low-pressure sensor detects a pressure of 21.8 psi or  
more for 3 minutes of continuous operation, the pre-trip count is reset to 0.  
If the low-pressure sensor detects a pressure of 23.2 psi or less continuously for 30 minutes  
when the compressor is stopped, an alarm occurs immediately (no pre-trip).  
The A/C unit low pressure has dropped to a level that does not occur under ordinary conditions.  
(1) The absolute amount of gas in the system is too low (as a result of insufficient refrigerant  
charge or leak).  
Probable cause  
(2) The refrigerant has accumulated in the circuit and has not returned to the compressor.  
Refrigerant has accumulated in a location of one-way flow and cannot escape.  
High-pressure level is low, resulting in poor flow of refrigerant in the circuit. (A lower high-  
pressure level results in a smaller difference between low pressure and high pressure, that  
may be insufficient to cause refrigerant flow.)  
(3) The refrigerant circuit has become closed, and refrigerant has not returned to the  
compressor. In some cases when moisture enters the refrigerant circuit, it can freeze at the  
low-pressure locations and the resulting ice can block the circuit.  
If the alarm occurs when there is sufficient refrigerant in the system ((1) and (3)), liquid  
refrigerant has definitely accumulated somewhere in the system. Liquid refrigerant generally  
accumulates in high-pressure locations. In this case the high pressure gradually increases  
(however it may not increase if the location where the liquid accumulates is sufficiently  
large). Depending on the refrigerant saturation temperature, it may also accumulate in low  
pressure locations. In this case the high pressure is unlikely to increase.  
(1) Check that the service valve is open.  
Check  
(2) Check that none of the valves (solenoid valves, mechanical valves) in the main refrigerant  
circuit is closed due to an operation failure.  
(3) Check that there is no possibility of foreign objects or water having entered the refrigerant  
circuit.  
(4) Check that valve leakage at a stopped sub unit has not resulted in accumulation of  
refrigerant at that sub unit.  
(5) Check that no refrigerant leakage has occurred.  
Correction  
(1) If there was a valve operation failure, in general it is necessary to replace the valve.  
(2) If a foreign object or moisture has entered the circuit, install a strainer or dry core (depending  
on the degree of the problem).  
5
(3) If refrigerant has leaked into stopped sub units, it is likely that valve leakage has occurred.  
The valve must be replaced.  
Example  
Notes  
5 - 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
H07 Alarm  
Alarm code  
H07  
Alarm meaning  
Alarm conditions  
No-oil alarm  
This alarm occurs when oil does not flow for a specified amount of time in tubing where oil  
flow constantly. (The presence of oil is detected by a temperature sensor.)  
Judgment method:  
Tcal (calculated by the formula below from the oil temperature) is compared with the discharge  
temperature. If Tcal is higher than the discharge temperature then oil is judged to be present.  
If Tcal is lower than the discharge temperature, oil is judged to be not present.  
Tcal={(0.0254 · T_oil · LP2 +0.0298 · T_oil · LP +0.8842 · T_oil –2.9953 · LP2 –11.091 · LP +436.94)  
+2.9953 · HP2 +11.091 · HP –436.94}/(0.0254 · HP2 +0.0298 · HP +0.8842)  
These points are calculated from the oil temperature and compared  
with the discharge temperature  

High pressure  
Lower than the discharge  
temperature: No oil  
Ž
Discharge  
temperature  
Higher than the discharge  

temperature: Oil present  
Low pressure  
Oil temperature  
Œ
Probable cause  
Insufficient amount of oil in the system  
(1) The length of system tubing exceeds the allowable tubing length.  
(2) The difference in height between system units exceeds the allowable value.  
(3) A large amount of oil was drained when a compressor was replaced.  
(4) Oil has accumulated in a stopped outdoor unit and has not returned, as a result of refrigerant  
circuit clogging or valve leakage at the stopped outdoor unit.  
(5) A valve (ORVR, BALV, BPB) in the oil circuit has malfunctioned, or there is clogging of the  
circuit (capillaries) which returns oil from the oil separator to the compressor.  
(6) If an excessive amount or liquid returns to the compressor, oil foaming may increase oil  
discharge. The same occurs when the refrigerant proportion in the compressor is high at start,  
due to an open circuit in the crank case heater.  
5
(7) Oil sensor disconnected or open circuit  
Check  
(1) Check the tubing length and height differences.  
(2) Check the operation of system circuit valves.  
(3) Check that there is not an excessive amount of liquid return. (Check that there is no  
mechanical valve leakage.)  
(4) Check the crank case heater (wintertime).  
(5) Check that the oil sensor is not disconnected, and that the circuit is not open.  
(1) If insufficient oil is a possibility, then charge with additional oil.  
(2) If it is clear that a valve failure has occurred, replace the valve.  
Correction  
Example  
Notes  
5 - 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
H08, H27 Alarm  
Alarm code  
H08, H27  
Alarm meaning  
Alarm conditions  
Trouble (open circuit) with the oil sensor (connection) at compressor 1, compressor 2  
This alarm occurs when a connector connection (pins 1 and 2 for compressor 1, pins 4  
and 5 for compressor 2) is open.  
Probable cause  
Check  
Correction  
Disconnected connector  
Check that the connector is securely connected.  
(1) Connect the connector.  
(2) Correct the connection at connector pins 4 and 5.  
Example  
Notes  
H31 Alarm  
Alarm code  
H31  
Alarm meaning  
Alarm conditions  
HIC trouble alarm  
This alarm occurs when the microcomputer identifies a trouble signal (indicating abnormal HIC  
temperature or other trouble) from the HIC.  
The HIC judges the current and temperature, and outputs the trouble signal. In general this  
indicates trouble with the HIC itself.  
Probable cause  
Check  
Overcurrent in HIC circuit, and the resultant abnormal heating, caused by HIC failure  
Check the power wiring and connector wiring. If the wiring and connectors are normal, use a  
tester to measure the resistance between the compressor HIC power (HIC+) and ground (HIC–).  
If there is a short circuit, there is an HIC malfunction.  
HIC -  
HIC +  
5
HIC PCB  
Correction  
Example  
Notes  
If an HIC failure is found, replace the PCB.  
Turn OFF the power, and check the continuity of HIC+ and HIC– on the HIC PCB.  
5 - 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
L04 Alarm  
Alarm code  
L04  
Alarm meaning  
Alarm conditions  
Outdoor system address duplication  
Communication by inter-unit control wiring was received that contained the same address as that  
unit 5 times or more within 3 minutes.  
Probable cause  
Check  
Incorrect outdoor system address settings  
Check the system address settings again.  
Correction  
Example  
Notes  
Correct the system address settings.  
Recovery from this alarm occurs automatically (when communication that contains the same  
address as that unit is not received for 3 minutes after detection).  
L10 Alarm  
Alarm code  
L10  
Alarm meaning  
Alarm conditions  
Probable cause  
Check  
Outdoor unit capacity not set  
The outdoor unit capacity has not been set, or the setting is not allowed by the system.  
This alarm occurs because the capacity has not been set.  
Connect the outdoor unit maintenance remote controller. On the outdoor unit EEPROM detailed  
setting mode screen, check the value for the outdoor unit capacity (item code 81). Check that it is  
not set to “0” or to a capacity that is not allowed.  
Correction  
If item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it  
correctly.  
* After changing the setting, be sure to reset both the indoor and outdoor power.  
Example  
Notes  
The outdoor unit maintenance remote controller is required in order to set the capacity in the  
outdoor unit EEPROM.  
L17 Alarm  
Alarm code  
L17  
Alarm meaning  
Alarm conditions  
Probable cause  
Outdoor unit model mismatch  
This alarm occurs when a unit other than a R410A refrigerant model is connected.  
(1) A unit that uses R407C refrigerant, or a R22 model unit, was connected by mistake.  
(2) The connected unit is correct, however the refrigerant type setting in the outdoor unit  
EEPROM (item code 80) is incorrect.  
Check  
(1) Check the refrigerant type at the connected unit.  
(2) Use the outdoor unit maintenance remote controller and check the item code 80 refrigerant  
type. If the setting is incorrect, change it to R410A.  
5
Correction  
Example  
Notes  
The outdoor unit maintenance remote controller is required in order to set the refrigerant type in  
the outdoor unit EEPROM.  
L18 Alarm  
Alarm code  
L18  
Alarm meaning  
Alarm conditions  
4-way valve operation failure  
During heating operation (Comp. ON), the highest detected temperature at an outdoor unit  
heat exchanger (EXG 1, EXG 2, EXL 1, or EXL 2) was 40°F or more above the outdoor air  
temperature (Air Temp.) continuously for 5 minutes or longer, or the detected suction temperature  
(SCT) was 40°F or more above the outdoor air temperature continuously for 5 minutes or longer.  
(1) The 4-way valve connector (20S CN060) has become disconnected from the control PCB.  
(2) The 4-way valve circuit is locked (malfunctioning).  
Probable cause  
Check  
(1) Check the 4-way valve connector (20S CN060).  
(2) If the connector is normal, check the 4-way valve wiring and the PCB circuit.  
If the connector is normal, correct or replace the problem locations.  
Correction  
Example  
Notes  
5 - 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
P03, P17 Alarm  
Alarm code  
P03, P17  
Alarm meaning  
Alarm conditions  
Compressor 1 discharge temperature trouble; Compressor 2 discharge temperature trouble  
Temperature is 222°F or higher and pre-trip stop has occurred.  
The alarm occurs when pre-trip stop occurs more than once. However the pre-trip counter is  
cleared if the compressor operates continuously for a specified length of time.  
Probable cause  
(1) Clogging of liquid valve capillaries  
(2) Insufficient amount of refrigerant (including trouble resulting from an insufficient initial charge  
and from gas leakage)  
(3) Blocking of low-pressure parts caused by intrusion of foreign objects (moisture, scale, etc.)  
(4) Crossing (tubing or PCB connectors) with the other compressor thermistor  
(5) Expansion valve operation failure  
(6) Accumulation of refrigerant at stopped outdoor units  
(7) Compressor discharge sensor failure  
(8) PCB failure (A/D conversion failure)  
(9) Electrical noise  
Check  
(1) Clogging of capillaries  
Trouble: Compressor discharge temperature does not decrease even when the liquid valve  
is ON.  
Check: When the liquid valve is operating and the liquid valve is ON, check that the  
secondary side of the liquid capillaries is cold.  
(2) Insufficient refrigerant  
Trouble: Liquid effectiveness is poor.  
Check: Check whether or not the superheating temperature is declining if the evaporator  
mechanical valve is opened to 300 pulses or more (after checking for foreign object  
intrusion).  
(3) Foreign object intrusion  
Trouble: Liquid valve effectiveness is poor.  
Check: Check that there is no difference in the condensation or frost conditions between  
the strainer primary-side and secondary-side tubing.  
(4) Crossed thermistor  
Trouble: The discharge temperature of the other compressor is high although only this  
compressor is operating.  
When the liquid valve turns ON, the discharge temperature of the other compressor  
decreases.  
(5) Accumulation of refrigerant in stopped outdoor units  
Trouble: • System is OK when all outdoor units are operating, however symptoms of  
insufficient gas occur when a certain outdoor unit is stopped.  
• Condensation or frost is visible up to the top of the accumulator of the stopped  
outdoor unit.  
• After an outdoor unit stops, there is the sound of refrigerant flowing into an outdoor  
unit that was stopped for a long time.  
• When an outdoor unit starts after being stopped for a long time, the start is  
accompanied by much vibration.  
Check: • Representative parts include the liquid capillaries (secondary side of capillaries will  
be cool during cooling operation), mechanical valve, mechanical valve bypass check  
valve (sound of refrigerant flow can be heard, and stops when the liquid valve is  
closed), hot gas defrost valve (if valve secondary side remains hot even after much  
time has passed, be careful not to mistake transmitted heat for a valve failure).  
• Ice is growing on the lower parts of some outdoor unit heat exchangers but not on  
others.  
5
Because this trouble may occur even in outdoor units with a high operating rate  
under conditions of insufficient gas, caution is needed.  
(6) Sensor failure  
Check: • This alarm is likely to occur when wiring is partially cut. (It is difficult to identify, even  
when continuity is checked.) The detected discharge temperature is high.  
• Although such conditions rarely occur, a P02 alarm is likely if the detected discharge  
temperature is low.  
• Replace the sensor with another discharge sensor and compare the temperature  
conditions.  
(7) If the cause is still unknown after checking the above, then it is possible that electrical noise  
is the cause of the trouble.  
Correction  
(1) Replace the sensor.  
(2) Replace the outdoor unit PCB.  
(3) Correct the problem locations.  
Example  
Notes  
All of the probable causes  
Operates continuously for a set length of time.  
Indicates 2.5 minutes or longer for an inverter unit and 30 seconds or longer for a constant-  
speed compressor.  
5 - 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
P04 Alarm  
Alarm code  
P04  
Alarm meaning  
Alarm conditions  
High-pressure switch activated.  
The operation of the electronic circuit in the high-pressure switch may short-circuit the terminal  
depending on the pressure. A pressure of 478.6 psi or above will short-circuit the terminal. Once  
the terminal is short-circuited, it will remain in that state until the pressure goes below 377.1 psi.  
(1) Failure of the check valve in the compressor discharge tube.  
(2) The service valve is closed.  
Probable cause  
(3) Clogging of the outdoor heat exchanger during cooling.  
(4) An air short in the outdoor unit during cooling.  
(5) Failure of the outdoor fan during cooling.  
(6) Clogging of the air filter in the indoor unit during heating.  
(7) An air short in the indoor unit during heating.  
(8) Failure of the indoor fan during heating.  
(9) Clogging of the refrigerant circuit.  
(10) Failure of the mechanical valve.  
(11) Failure of the solenoid valve kit.  
(12) Too much refrigerant has been charged.  
(13) Failure of the high-pressure switch.  
Check  
(1) Make sure that the high-pressure switch connector has been properly connected.  
(2) If the high-pressure switch is properly connected, connect a high-pressure gauge to the  
high-pressure outlet port and monitor the pressure during operation to check the pressure  
when the high-pressure switch is activated. Check valve failure is likely if the pressure is less  
than 478.6 psi. The following describes checks to be made when the pressure is high.  
(3) During cooling, check whether the outdoor unit heat exchanger is clogged. Remove any  
foreign material that prevents ventilation.  
(4) During cooling, check whether an air short blockage has occurred in the outdoor unit. The  
system is operating normally unless the temperature around the outdoor unit is excessively high.  
(5) During cooling, check for outdoor fan failure. Check whether the screws securing the fan are  
loose and whether the fan connector in the outdoor unit PCB is properly connected.  
(6) During heating, check whether the air filters in the indoor unit are clogged. If clogged, clean  
the filters.  
(7) During heating, check whether an air short blockage has occurred in the indoor unit. The  
system operates normally unless the temperature around the indoor unit is excessively high.  
(8) During heating, check for indoor fan failure.  
(9) Check whether the refrigerant circuit is clogged. Check that all service valves are closed.  
Check whether welded locations are clogged.  
(10) Check for mechanical valve failure. Check whether the mechanical valves make a clattering  
sound when the power is reset. Since the mechanical valve in the indoor unit is in a location  
that makes aural inspection difficult, use an electric means to check. Check that the  
connector pin of the mechanical valve on the PCB outputs 4 V. In addition, check that the coil  
5
resistance of the mechanical valve is several tens of Ohm (  
Ω)  
.
(11) Check for solenoid valve kit failure. Removing a coil that is on will result in a clicking sound.  
Also, removing a coil that is off will not produce such a sound.  
(12) Check whether too much refrigerant has been charged. Too much refrigerant has been  
charged if the sub-cool temperature of the condenser is 59°F or more.  
Replace damaged components and correct the amount of charged refrigerant.  
Correction  
Example  
Notes  
P05 Alarm  
Alarm code  
Alarm meaning  
Alarm conditions  
Probable cause  
Check  
P05  
Reverse phase (or missing phase) detected  
This alarm occurs when a reverse phase or missing phase is detected in the L1-L2-L3-N phases.  
Reverse phase or missing phase in the L1-L2-L3-N phases  
Check the wiring at the power terminal plate.  
Correction  
Example  
Notes  
Switch the phases and reinsert. Check if the result is OK.  
5 - 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
P16 Alarm  
Alarm code  
P16  
Alarm meaning  
Alarm conditions  
Compressor 1 (INV) overcurrent alarm  
This alarm occurs when current trouble or current detection trouble occur at an inverter frequency  
of less than 80 Hz after start (when trouble judgment current is detected in the primary or  
secondary current, or when an instantaneous secondary current of 13.5 A or higher is detected.  
There is a strong possibility of a compressor failure.  
Probable cause  
An alarm occurs for current detection trouble when it is judged that no current is flowing after  
start (DCCT is damaged). In this case, the cause is a DCCT failure.  
Check the power wiring and connector wiring.  
Check  
Correction  
Example  
Notes  
It is possible to resolve this trouble by limiting the maximum frequency.  
P22 Alarm  
Alarm code  
P22  
Alarm meaning  
Alarm conditions  
Probable cause  
Check  
Fan motor trouble  
Fan motor start failure, fan motor Hall IC input failure  
Possible causes are a Hall IC input circuit failure and a fan HIC failure.  
Check the fan motor wiring, the Hall IC wiring, and the connector connections. If the wiring and  
connectors are normal, then check that the capacitor of the Hall IC input circuit is securely  
soldered on the outdoor unit control PCB. Also use a tester and measure the resistance between  
fan HIC power (HIC+) and ground (HIC–). If there is a short circuit, there is an HIC malfunction.  
(+)  
(–)  
5
Fan circuit on the outdoor unit control PCB  
Correction  
If the fan does not start, the below corrections may be effective.  
(1) If there is a fan HIC failure or circuit failure, replace the PCB.  
(2) If the fan motor is locked, replace the fan motor.  
Example  
Notes  
Turn OFF the power, and check the continuity of “+” and “–” on the fan circuit PCB.  
5 - 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
4. W-2WAY ECO-i Alarm Codes  
P26 Alarm  
Alarm code  
P26  
Alarm meaning  
Alarm conditions  
Inverter compressor high-frequency overcurrent alarm  
This alarm occurs when current trouble or current detection trouble occurs at an inverter  
frequency of 80 Hz or higher after start (when trouble judgment current is detected in the  
primary or secondary current, or when an instantaneous secondary current of 13.5 A or higher is  
detected).  
Probable cause  
The detection methods are the same as for P16. However the fact that operation up to high  
frequencies is possible does not necessarily mean that a compressor failure is the cause of the  
trouble. Start the compressor several times. If alarm P26 occurs every time and alarm P16 does  
not occur at all, then the possibility of a compressor failure is low.  
Check  
Check the power wiring and connector wiring.  
Correction  
Example  
Notes  
It is possible to resolve this trouble by limiting the maximum frequency.  
P29 Alarm  
Alarm code  
P29  
Alarm meaning  
Alarm conditions  
Inverter compressor missing phase or lock alarm  
This alarm may occur at start, and occurs when missing phase or lock is detected, and when a  
DCCT failure occurs.  
Probable cause  
Generally this alarm occurs when the refrigerant pressure balance is uneven at start, or when  
inverter compressor lock occurs, there is a missing phase in the inverter compressor wiring, or a  
DCCT failure occurs. This can be judged to be starting trouble which is not caused by HIC.  
Check  
Check the power wiring and connector wiring.  
Correction  
Example  
Notes  
DCCT failure (replace PCB) or compressor failure  
Use a tester to measure the voltage between the DCCT output terminal on the rear of the PCB  
and the ground. If the voltage is not within 2 – 3 V, then the DCCT has malfunctioned.  
Currently the blinking inspection display can be displayed only on the wired remote controller  
and system remote controller.  
CAUTION  
Blinking inspection display (1) (Automatic backup)  
Alarm code  
(Blinking inspection display)  
5
Alarm meaning  
Automatic backup is in progress. A/C units can be operated.  
Status: The compressor at one of the outdoor units where the outdoor unit fan is running should  
be operating.  
* Blinking inspection display also occurs when seizing of the compressor magnet SW  
is detected. Because this may also be the case, refer to “Blinking inspection display  
(compressor magnet SW seizing detection).”  
Alarm conditions  
Probable cause  
When alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, correcting the control device  
(remote controller, etc.) input engages this mode.  
Because alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, check the alarm history  
then refer to the corresponding items.  
Correction  
Recovery  
Follow the instructions in the corresponding items to correct the trouble.  
After repairing the malfunctioning locations, reset the power for the system (all outdoor units).  
Caution: Automatic backup mode will not be canceled until the power is reset.  
Notes  
Automatic backup mode is not engaged in cases of alarms other than those listed above.  
Reasons: • There is no need for automatic backup if recovery is possible by correcting the  
remote controller input.  
• With alarms for which automatic recovery is possible (such as sensor alarms), the  
presence of electrical noise may result in a new alarm. However, it is believed that  
this occurs for a comparatively short time only. In these cases, a mode (automatic  
backup mode) that limits operation may be engaged.  
• Control is not possible when a communications system alarm has occurred.  
Automatic backup mode is not engaged in order to avoid causing secondary  
damage.  
5 - 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
5. Blinking Inspection Display on the Remote Controller  
Blinking inspection display (2) (compressor magnet SW seizing detection)  
Alarm code  
(Blinking inspection display)  
Alarm meaning  
Compressor magnet SW seizing detected  
Status: Although an outdoor unit exists where the outdoor unit fan is running, no compressors in  
the system are operating.  
Because the fan is running only at the outdoor unit where seizing was detected, check  
the corresponding outdoor unit.  
* The fan may also run on its own when fan cracking prevention control is in effect  
or when snowfall sensor input is present. Therefore monitor for approximately 10  
minutes if the outdoor unit fans are operating at multiple units.  
Current is detected in the CT circuit when the compressor is stopped.  
Alarm conditions  
(1) This control is not engaged for the first 30 seconds after the compressor turns ON OFF.  
¡
(2) For 1 minute following the first 30 seconds after the compressor turned ON OFF, the  
¡
threshold for the detected current is 10 A or more continuing for 2 seconds.  
(3) All times other than the above:  
• If the low-pressure SW has not activated, the threshold for the detected current is 7A or  
more continuing for 5 seconds.  
• If the low-pressure switch has activated, the threshold for the detected current is 7A or more  
continuing for 2 seconds.  
Probable cause  
(1) Magnet SW malfunction  
• The magnet SW has seized, and the compressor is continuing to run.  
Even when the power is turned OFF, the primary side and secondary side contacts  
remain together.  
¡
• The conditions of magnet SW operation are poor (difficult to open).  
When a magnet SW is used in a DC circuit, it may be difficult for the SW to open at times.  
In an AC circuit the magnet SW should open instantaneously as long as the current is  
within the allowable range. However, this kind of trouble can occur if excessive current  
flows, and may prevent the SW from opening.  
¡
(2) CT circuit failure or PCB failure (A/D failure)  
• CT circuit contact failure  
Check that the connector is not partially disconnected.  
Wiggle the connector to check the connection.*  
¡
* These symptoms will not occur if the connector is completely disconnected or the wire is  
cut. In these cases alarm Hx3 occurs.  
• Current of 7A or higher was detected although the compressor was stopped, or a higher  
current was detected at occasional intervals.  
• The compressor continues to operate at a time when the outdoor unit should be stopped  
(such as when all indoor units are stopped).  
Check whether or not 200 V is output from the PCB to the magnet SW. If the voltage is  
output, there is a PCB failure.  
(3) Installation error  
¡
5
• CT1 connector is connected to the compressor 2 side  
• CT1 circuit is connected to the compressor 2 side  
• CT2 connector is connected to the compressor 1 side  
• CT2 circuit is connected to the compressor 1 side  
(4) Electrical noise  
Correction  
Notes  
(1) Replace the CT circuit.  
(2) Replace the magnet SW.  
(3) Replace the PCB.  
If the above probable causes are not the cause of the alarm, it is possible that in rare cases  
the alarm may be caused by the effects of noise. See notes.  
The effects of electrical noise are difficult to identify unless a PC is connected and the conditions  
are monitored for a long period of time.  
5 - 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
6. Inspection of Parts  
(1) High-pressure switch (63PH1, 63PH2)  
63PH1: Disconnect the CN042 connector (3P, WHT) from the outdoor unit control panel. Measure the resis-  
tance between socket pins 1 and 3. The resistance is OK if the result is 0  
.
Ω
63PH2: Disconnect the CN044 connector (3P, RED) from the outdoor unit control panel. Measure the resis-  
tance between socket pins 1 and 3. The resistance is OK if the result is 0  
.
Ω
(2) Electronic control valve (MOV1, MOV2, MOV4)  
After removing the connector from the PCB, use the following methods to check the valves.  
MOV1: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN015 connector (6P, WHT) on  
the outdoor unit control PCB. (Because of the pulse output, a simplified measurement method is used. Set  
the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)  
When the voltage is normal, measure the resistance between each pair of pins on the electronic control valve  
connector. The connector is normal if all results (pin 5 – pin 1, pin 5 – pin 3, pin 6 – pin 2, pin 6 – pin 4) are  
approximately 46 . (If the results are 0 or , replace the coil.)  
Ω
Ω
MOV2: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN016 connector (6P, RED) on  
the outdoor unit control PCB. (Because of the pulse output, a simplified measurement method is used. Set  
the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)  
When the voltage is normal, measure the resistance between each pair of pins on the electronic control valve  
connector. The connector is normal if all results (pin 5 – pin 1, pin 5 – pin 3, pin 6 – pin 2, pin 6 – pin 4) are  
approximately 46 . (If the results are 0 or , replace the coil.)  
Ω
Ω
MOV4: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN230 connector (6P, BLU) on  
the outdoor unit control PCB. (Because of the pulse output, a simplified measurement method is used. Set  
the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)  
When the voltage is normal, measure the resistance between each pair of pins on the electronic control valve  
connector. The connector is normal if all results (pin 5 – pin 1, pin 5 – pin 3, pin 6 – pin 2, pin 6 – pin 4) are  
approximately 46 . (If the results are 0 or , replace the coil.)  
Ω
Ω
(3) Crank case heater  
Connect a clamp meter to 1 of the 2 crank case heater wires and measure the current. The current is normal  
if the result is 0.15 A or higher. (As a guide, the current should be 0.14 A (180 V) – 0.17 A (220 V).)  
5
5 - 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
7.Test Pin  
When the test pin on the outdoor unit control PCB is short-circuited, each part can be operated individually.  
After turning OFF the main unit power, short circuit the test pin (CN022, WHT), then turn the power back ON.  
Output is performed in the sequence shown in the table below, for 0.5 seconds each.  
Output  
Operation  
4-way valve (205)  
Output  
Operation  
Save valve (SAVE)  
1
2
3
4
5
6
7
8
9
Relay RY024  
11 Relay RY012  
12  
13 Relay RY003  
14 Relay RY002  
Crank case 2 (CH2)  
Crank case 1 (CH1)  
Relay RY005  
Relay RY007  
Bypass valve (BPV)  
Recovery valve (ORVR)  
Relay RY017  
Refrigerant balance valve (RBV)  
Refrigerant adjustment valve (RCV)  
10 Relay RY016  
5
5 - 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
8.Thermister Characteristics Curve  
8-1. Room temp.sensor  
Temperature sensor  
10  
9
8
7
6
5
4
3
2
1
10 15 20 25 30 35 40 45 50 55  
Temperature (˚C)  
8-2. Indoor heat exch. coil sensor (E1, E3)  
Indoor Heat Exchanger temperature sensor  
[E1, E3]  
40  
35  
30  
25  
20  
15  
10  
5
8
7
6
5
4
3
2
1
0
5
0
-20 -15 -10  
-5  
0
5
10  
15  
20  
20  
30  
40  
50  
60  
Temperature (˚C)  
Temperature (˚C)  
5 - 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W-2WAY ECO-i SYSTEM  
Trouble Diagnosis  
8.Thermister Characteristics Curve  
8-3. Outdoor temp. sensor, Compressor suction gas temp. sensor  
Outdoor heat exch. coil sensor (C1, C2)  
Outdoor temperature, Suction gas temperature (TS) sensor  
Heat exchanger temperature, Heat exchanger temperature sensor  
40  
8
7
6
5
4
3
2
1
0
35  
30  
25  
20  
15  
10  
5
0
20  
30  
40  
50  
60  
-20 -15 -10 -5  
0
5
10 15 20  
Temperature (°C)  
Temperature (°C)  
8-4. Compressor discharge gas temp. sensor  
Discharge gas temp. sensor  
7
6
5
4
3
2
1
5
80  
90  
100  
110  
125  
130  
Temperature (°C)  
5 - 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
– MEMO –  
5 - 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For Parts or Service Assistance please contact your local Sanyo HVAC Contractor or Distributor  
United States: SCS, HVAC Solutions  
Web: www.SanyoHVAC.com  
Parts: hvac.parts@sna.sanyo.com  
Service: hvac.service@sna.sanyo.com  
Canada: Sanyo Canada Inc.  
Web: www.SanyoHVAC.com  
Parts/Service: hvac@sci.sanyo.com  
201002  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Radio Shack Heart Rate Monitor 63 1520 User Guide
Raymarine GPS Receiver DSM30 User Guide
Raypak Swimming Pool Heater R185 User Guide
Razor Riding Toy 300001 SL User Guide
Rosewill Power Supply RU101 User Guide
RoyalTek Stereo Receiver RTA 2000 User Guide
Samsung Home Security System SVD 4120A AW User Guide
Samsung Tablet SM T520NZKAXAR User Guide
Sanyo Network Card POA PN40 User Guide
Sears Tiller 91729149 User Guide