Print Form
™
ECO-i Submittal Data
CHX05252
Heat Pump: 52,000 btu VRF Outdoor Unit
Job Name:
Location:
Approval:
Date:
Engineer:
Construction:
Unit #:
Drawing #:
Submitted to:
Submitted by:
Reference:
Compressor Warranty: 6 Years
Parts Warranty: 1 Year
Coil Coated to Protect Against Corrosion
Salt Protection also available
Capacities:
Cooling: Btu/h
SEER
Power Input Ducted Non-Ducted
Mix
51,500
16
Fan
2 Propeller
4.57 KW
51,500
14.6
52,000
17.3
Quantity/Type:
Fan Motor Output (KW):
90
Heating: Btu/h
HSPF
4.58 KW
57,500
7.7
58,000
9.5
58,500
8.6
Power Supply
208-230 / 1 / 60
V/PH/Hz.
29
50
Cooling Mode Nominal Conditions
Indoor: °F DB/°F WB
Outdoor: °F DB
Minimum circuit Amps (MCA): Amps
Max. Overcurrent Protection (MOCP):
80/67
95
229
25
Pipe Length (feet):
Weight (lbs):
Level Difference (feet):
0
410A
Refrigerant:
Heating Mode Nominal Conditions
Indoor: °F DB
Outdoor: °F DB/ °F WB
Pipe Length (feet):
70
47/43
25
Coil
11.7
3
Coil Face Area (sq. ft.):
Number of Rows:
Level Difference (feet):
0
Protection Devices
High Pressure Switch:
Overcurrent (CT Method):
Crankcase Heaters (W):
Yes
Yes
30
Operating Range
Cooling: °F DB:
Heating: °F WB:
14 to 109
-4 to 59
Electrostatic Powder Coating
Compressor
External Finish:
Quantity/Type:
1 Inverter driven rotary
Capacity Control Range:
Starting Amps:
10-100%
1
Download from Www.Somanuals.com. All Manuals Search And Download.
|