Direct Vent Tankless Water Heater
Operation and Installation Manual
Table of Contents ....................2
Consumer Safety Information..4
Operating Instructions..............5
Maintenance............................12
Error Codes .............................13
Installation Instructions ............17
Consumer Support...................40
French Version ........................42
call 1-866-RINNAI1 (746-6241)
ANS Z21.10.3
●
CSA 4.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Model
RC80HPi
RC80HPe
RC98HPi
RC98HPe
Minimum Gas Consumption Btu/h
Maximum Gas Consumption Btu/h
Hot water capacity (Min - Max) *
9,500 for Natural Gas
157,000
/
10,300 for Propane Gas
199,000
0.4 - 8.0 GPM (1.5 - 30 L/min)
6.6 GPM (25 L/min)
0.4 - 9.8 GPM (1.5 - 37 L/min)
8.5 GPM (32 L/min)
Hot water capacity (45°F rise)
Default Temperature Setting (no controller)
Temperature Controller Default Setting
Maximum Temp Setting (commercial **)
120º F (49º C)
104º F (40º C)
185º F (85º C)
Maximum Temp Setting (residential)
Selectable at 120º F (49º C) or at 140º F (60º C)
see Temperature Ranges for more information
Minimum Temperature Setting
Weight
98º F (37º C)
63.9 lb (29 kg)
70.5 lb (32 kg)
Efficiency Rating
Noise level
95.0%
50 dB
Normal
63 W
44 W
80 W
59 W
Electrical
Consumption
Standby
2 W
Anti-frost Protection
By-Pass Control
220 W
172 W
220 W
172 W
Electronic
Natural Gas
Propane
5.0 inch W.C.
8.0 inch W.C.
10.5 inch W.C.
13.5 inch W.C.
Minimum Gas Supply
Pressure
Natural Gas
Propane
Maximum Gas Supply
Pressure
Type of Appliance
Operation
Condensing, Tankless, Temperature controlled continuous flow gas hot water system.
With or without remote controls, mounted in kitchen, bathroom, etc.
Natural Gas or Propane - Ensure unit matches gas type supplied at the installation location.
Gas Supply: 3/4" MNPT, Cold Water Inlet: 3/4" MNPT, Hot Water Outlet: 3/4" MNPT
Direct Electronic Ignition
Approved Gas Type
Connections
Ignition System
Electric Connections
Appliance: AC 120 Volts, 60Hz. Remote Control: DC 12 Volts (Digital)
Simulation Feedforward and Feedback.
Water Temperature Control
Water Supply Pressure
Minimum Water Pressure: 50 PSI (Recommended 60-80 PSI for maximum performance)
150 PSI
Maximum Water Supply Pressure
Remote Control Cable
Non-Polarized Two Core Cable (Minimum 22 AWG)
Yes
Energy Star Qualified
* Minimum flow may vary slightly depending on the temperature setting and the inlet water temperature.
** for commercial and hydronic applications requiring higher temperatures
Rinnai is continually updating and improving products. Therefore, specifications are subject to change without
prior notice.
The maximum inlet gas pressure must not exceed the value specified by the manufacturer. The minimum value
listed is for the purpose of input adjustment.
Manual - Rinnai Condensing Water Heaters
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Consumer Safety Information
Safety Definitions
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and
others.
Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
DANGER
Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
WARNING
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in minor or
moderate injury. It may also be used to alert against unsafe practices.
Safety Behavior and Practices
Safety Features
• Overheat: The appliance will automatically shut
down when the appliance exceeds a predetermined
temperature.
• Power Surge Fuse: A glass fuse protects against
overcurrent. If the fuse blows then all indicator
lamps will be off.
• Flame Failure: The appliance will automatically
• Fusible Link: In case the overheat feature does
not prevent the temperature from rising then the
fusible link will break shutting off the appliance.
shut down if the burner flame is extinguished.
• Power Failure: The appliance will cut off the gas if
it loses electrical power.
4
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Description of Operation
The Rinnai water heater is one of the most advanced
water heaters available. It provides a continuous
supply of hot water at a preset temperature.
Ignition is electronic. There is no pilot light consuming
gas while the water heater is not being used. The gas
burner lights automatically when the hot water tap is
opened and goes out when the tap is closed.
This appliance is a condensing tankless, direct vent
appliance where air is brought in from the outside and
combustion gases are exhausted to the outside. This
appliance uses a concentric vent where the outer
passage way brings in air from the outside, and the
inner passage way expels the combustion gases.
Installation of the temperature controller is highly
recommended. The temperature controller can set the
temperature within a specific range and can provide
error codes to diagnose any problems.
The temperature of the outgoing hot water is constantly
monitored. The Rinnai water heater may adjust the
water flow in order to maintain the temperature setting.
The water flow may vary from summer to winter due to
the difference in ground water temperature.
While electricity, water, and gas supplies are
connected, the Rinnai water heater produces hot water
whenever a hot water tap is open.
Operating Instructions
Features Available on Temperature Controllers
The MC-91 temperature controller is supplied with the appliance. Additional functions are available through the
use of optional controllers.
Description
Features
Call
Sends a short series of beeps to all controllers in the system. It is
not an intercom.
Clock
12 hour AM/PM clock.
Error Codes
When a fault is detected an error code flashes at the temperature
display on models MC-91, MCC-91, and MC-502; and flashes at
the clock display on models MC-100 and BC-100.
Function
Used on this model to set the clock or sound volume.
In Use Indicator
Indicates that hot water is being supplied (i.e. a hot water tap is
open).
ON/OFF Button
Power Save
Used to turn the water heater ON or OFF.
Allows the temperature controller to be in an energy saving
mode.
Priority Button /
Indicator
Indicates that this controller is setting the temperature . Priority
can be switched to another controller by pressing its Priority
Button when no hot water is running.
Sound Volume
Temperature Display
Thermostat
Used to adjust the voice prompt volume.
Shows the temperature setting.
Increases or decreases the temperature setting.
Water Smart / Bath Fill
Button / Indicator
Used to select the Water Smart / Bath Fill Function to fill a bath
with a predetermined volume of water.
Water Volume
Used to select the water volume for the Water Smart / Bath Fill
Function.
Manual - Rinnai Condensing Water Heaters
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Temperature Controllers - Models
MC-91-1US & MCC-91-1US
Dimensions (inches): 3.5 W x 4.75 H x 0.75 D
The MC-91 controller is the standard temperature controller that is supplied with the water heater. On indoor
models it is integrated into the front panel. The MCC-91 controller is for commercial and hydronic applications
requiring higher temperatures. When the MCC-91 controller is connected, these higher temperatures are
available on all controller models in the system. Refer to the section on temperature ranges.
In Use
Indicator
Priority
Indicator
Temperature
Display
Priority
Button
Temperature
Selection
ON/OFF
Button
MC-502RC-1US-S * (Wireless)
Dimensions (inches): 4.33 W x 5.90 H x 1.16 D
Priority
Indicator
Temperature
Display
In Use
Indicator
Temperature
Selection
Priority
Button
ON/OFF
Button
* Requires the
transceiver,
MC-502RC-
Refer to the MC-502RC-1US-S manual and the Wireless Controller Installation Instructions for complete details
on features, operation, and installation.
6
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Temperature Controllers - Models
BC-100V-1US
Dimensions (inches): 8.0 W x 4.125 H x 0.875 D
Temperature
Display
Water Smart
Bath Fill Indicator
In Use
Indicator
ON/OFF
Button
Priority
Button and
Indicator
Water Smart
Bath Fill
Call
Button
Power Save
Clock
Water Volume
Temperature
Selection
Sound Volume
MC-100V-1US
Dimensions (inches): 5.0 W x 4.75 H x 0.75 D
Temperature
Selection
In Use
Indicator
Function
Temperature
Display
Priority Button
and Indicator
Clock
Call
ON/OFF
Button
Manual - Rinnai Condensing Water Heaters
7
Download from Www.Somanuals.com. All Manuals Search And Download.
How to Set the Temperature
1. If the water heater is off, press
the ON/OFF button to turn on.
2. Press the “Priority button” on the
temperature controller. The
green Priority light will glow
indicating that this controller is
controlling the temperature and
that the Rinnai water heater is
ready to supply hot water.
The priority can only be changed
while no hot water is running.
3. Press the ▲ or ▼ buttons to
obtain the desired temperature
setting.
All hot water sources are able to
provide water at this temperature
setting until it is changed again at
this or another temperature
controller.
Temperature Controller Settings
This water heater will attempt to provide hot water at the temperature setting even when the water flow is varied
or when more than 1 tap is in use. The water heater can deliver water at only one temperature setting at a time.
The available temperatures for a given model are provided below.
Model
Temperature Settings Available (ºF)
RC80HPi
RC80HPe
RC98HPi
RC98HPe
125 130 135 140 150 160 185
98 100 102 104 106 108 110 115 120
*
*
*
*
**
**
**
Temp in Celsius ºC 37 38 39 40 41 42 43 46 49 52 54 57 60 66 71 85
8
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Temperature Controller Settings
Maximum Temperature
* Re-setting the Maximum Temperature
These units have a default maximum temperature of 120º F (49º C) and
an option to increase the maximum temperature to 140 ºF (60 ºC).
Temperature settings from 125-140 ºF (52-60 ºC) are available by
setting dip switch 6 to ON in the SW1 bank of 8 dip switches.
120º F (49º C)
140 ºF (60 ºC)
Switch No.
Switch No.
ON
ON
O
F
F
O
F
F
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
** MCC-91 Temperature Controller
These settings require the MCC-91 controller. When the MCC-91
controller is connected, these higher temperatures are available on all
controller models in the system. Use of an MCC-91 controller in a
residential dwelling will reduce the warranty coverage to that of a
commercial warranty application.
The MCC-91 controller is intended for commercial and hydronic
applications only. If an MCC-91 controller is used in a residential
dwelling for a hydronics application, a mixing valve must also be
installed to limit the potable hot water temperature to a safe
temperature. Water temperatures over 125º F (51º C) can cause severe
burns or scalding. Refer to the Danger Alert on water temperatures.
Rinnai shall not, in any event, be liable for damages resulting from such
misuse or misapplication.
A temperature lower than 98º F (37º C) can be
obtained at the tap by mixing with cold water.
Suggested temperatures are
•
•
•
Kitchen 120 ºF (49º C)
Shower 98º - 110º F (37º - 43º C)
Bath Fill 102º - 110º F (39º - 43º C)
To change the temperature scale from Celsius to
Fahrenheit or vice versa, press and hold the “On/Off”
button for 5 seconds while the water heater is OFF.
These temperatures are suggestions only.
Temperature Options Without a Temperature Controller
The default temperature setting for this appliance installed without a temperature controller is 120º F (49º C). If
desired, the temperature setting can be changed to 140º F (60º C) by adjustment of a dip switch.
In the SW1 bank of 8 dip switches, set dip switch 5 to ON to obtain 140º F (60º C) water temperature setting. Set
dip switch 5 to OFF (default) to obtain 120º F (49º C) water temperature setting.
If a temperature controller is installed, then dip switch 5 has no effect on temperature settings.
Setting the Sound Volume (Voice Prompt)
MC-100V Press the “Function” button to
adjust the voice prompt
BC-100V Press the “Sound Vol.” button to
adjust the voice prompt volume.
The default sound volume is set
to Medium. Each subsequent
press of the button cycles
volume. The default sound
volume is set to Medium.
Each subsequent press of the
▲ or ▼ button cycles through
the volume levels in the order
below.
through the volume levels in the
order below.
e
Manual - Rinnai Condensing Water Heaters
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Using the Water Smart / Bath Fill Function
Overview
This function is exclusive to the BC-100V temperature
controller. The bath fill function allows the consumer
to fill a tub with a preset volume of water at a preset
temperature. This is done by pressing the bath fill
button on the BC-100V controller while no hot water is
flowing and then opening only the hot water tap. The
water heater will stop the hot water flow when the
preset volume has been reached. The hot water tap
should then be closed and the bath fill button pressed.
The temperature settings for the bath fill function are
limited to those in the table below.
Bath Fill Temperature Settings Available
ºF 98 100 102 104 106 108
ºC 37 38 39 40 41 42
ºF 110 112 114 116 118 120
ºC 43 44 46 47 48 49
Setting the Water Volume
The default volume is set to 25 gallons. The volume
can be set between 10 and 120 gallons.
1. Press the “Priority” button.
5. Press the “Water Vol.”▲ or ▼
buttons to obtain the desired
water volume in gallons.
2. Press the “Water Smart Bath Fill”
button to set the water volume
and temperature.
6. Press the “Water Smart Bath Fill”
button.
3. Press the “Priority” button on the
temperature controller. The
green Priority light will glow
indicating that this controller is
controlling the temperature and
that the Rinnai water heater is
ready to supply hot water.
4. Press the “Temp” ▲ or ▼ buttons
to obtain the desired temperature
setting.
10
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Using the Water Smart / Bath Fill Function
Filling the Tub
1. Press the “Water Smart / Bath Fill”
button once. The button will
illuminate, and a tone will sound.
2. The voice prompt will announce
“The hot water system is ready.
Open the hot water tap.”
ON!
HOT
COLD
Make sure the water volume is set.
Refer to “Setting the Water
Volume” on the previous page.
Open the hot water tap. The “In
Use” indicator will illuminate on
MC-100V and BC-100V controllers.
The hot water will begin to flow.
ON!
HOT
COLD
3. When the preset volume of water
has been produced then
•
•
the water flow will cease
the “Water Smart / Bath Fill”
button will flash
•
•
a tone will sound
the voice prompt will
announce, “Bath fill is
complete. Turn off the bath
hot water tap and push the
Bath Fill button.”
4. Turn off the bath hot water tap and
push the Bath Fill button. The
water heater will not allow hot
water to flow from any source until
the “Water Smart / Bath Fill” button
is pushed.
The button light will go out.
Setting Controller to Mute
Models MC-91 and MCC-91
To eliminate the beeps when keys are pressed or to turn the beeps back on, press and hold both the ▲and ▼
buttons until a beep is heard (approximately 5 seconds).
Setting the Clock
MC-100V Press the “Function” button twice within 10 seconds to set the clock. Press the ▲ or
▼ button to reach the desired time. The clock on the BC-100V automatically shows
the time which has been set on the MC-100V.
Manual - Rinnai Condensing Water Heaters
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Snow Accumulation
Keep the area around flue terminal free of snow and
ice. The appliance will not function properly if the
intake air or exhaust is impeded (blocked or partially
blocked) by obstructions.
Repairs and maintenance should be performed by a
qualified service technician. The appliance should be
inspected annually by a qualified service technician.
Verify proper operation after servicing.
Visual Inspection of Flame
The burner must flame evenly over the entire surface
when operating correctly. The flame must burn with a
clear, blue, stable flame. See the parts breakdown of
the burner for the location of the view ports.
Cleaning
It is imperative that control compartments, burners,
and circulating air passageways of the appliance be
kept clean.
The flame pattern should be as shown in the figures
below.
Clean as follows:
1. Turn off and disconnect electrical power. Allow to
cool.
2. Remove and clean the water inlet filter.
3. Remove the front panel by removing 4 screws.
4. Use pressurized air to remove dust from the main
burner, heat exchanger, and fan blades. Do not
use a wet cloth or spray cleaners on the burner.
Do not use volatile substances such as benzene
and thinners. They may ignite or fade the paint.
5. Use soft dry cloth to wipe cabinet.
Vent System
The vent system should be inspected at least annually
for blockages or damage.
Motors
Motors are permanently lubricated and do not need
periodic lubrication. Keep fan and motor free of dust
and dirt by cleaning annually.
Temperature Controller
Use a soft damp cloth to clean the temperature
controller. Do not use solvents.
Lime / Scale Build-up
If you receive Error Code “LC”, refer to the procedure,
Flushing the Heat Exchanger. Refer to the section on
Water Quality to see if your water needs to be treated
or conditioned. (When checking maintenance code
history, “00” is substituted for “LC”.)
12
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Error Codes
The Rinnai water heater has the ability to check its own operation continuously. If a fault occurs, an error code
will flash on the Display of the temperature controller. This assists with diagnosing the fault and may enable you
to overcome a problem without a service call. Please identify the code displayed when inquiring about service.
Code
03
Fault
Remedy
Turn off all hot water taps. Press ON/OFF twice.
Power interruption during
Bath Fill (Water will not flow
when power returns).
Ensure Rinnai approved venting materials are being used.
Check that nothing is blocking the flue inlet or exhaust.
Check all vent components for proper connections.
Ensure vent length is within limits.
10
Air Supply or Exhaust
Blockage
Ensure condensation collar was installed correctly.
Verify dip switches are set properly.
Check fan for blockage.
Burner Sensor Error (see code 31)
Check the fins in the heat exchanger.
Check that the gas is turned on at the water heater, gas meter, or cylinder.
Ensure gas type and pressure is correct.
11
No Ignition
Ensure gas line, meter, and/or regulator is sized properly.
Bleed all air from gas lines.
Verify dip switches are set properly.
Ensure appliance is properly grounded.
Disconnect EZConnect™ or MSA controls to isolate the problem.
Ensure igniter is operational.
Check igniter wiring harness for damage.
Check gas solenoid valves for open or short circuits.
Remove burner cover and ensure all burners are properly seated.
Remove burner plate and inspect burner surface for condensation or debris.
Check that the gas is turned on at the water heater and gas meter. Check for obstructions in
the flue outlet.
12
Flame Failure
Ensure gas line, meter, and/or regulator is sized properly.
Ensure gas type and pressure is correct.
Bleed all air from gas lines.
Ensure proper Rinnai venting material was installed.
Ensure condensation collar was installed properly.
Ensure vent length is within limits.
Verify dip switches are set properly.
Ensure appliance is properly grounded.
Disconnect keypad.
Disconnect EZConnect™ or MSA controls to isolate the problem.
Check power supply for loose connections.
Check power supply for proper voltage and voltage drops.
Ensure flame rod wire is connected.
Check flame rod for carbon build-up.
Disconnect and reconnect all wiring harnesses on unit and PC board.
Check for DC shorts at components.
Check gas solenoid valves for open or short circuits.
Remove burner plate and inspect burner surface for condensation or debris.
Check the ground wire for the PC board.
Check gas type of unit and ensure it matches gas type being used.
Check for restrictions in air flow around unit and vent terminal.
Check for low water flow in a circulating system causing short-cycling.
Ensure dip switches are set to the proper position.
Check for foreign materials in combustion chamber and/or exhaust piping.
Check heat exchanger for cracks and/or separations.
Check heat exchanger surface for hot spots which indicate blockage due to scale build-up.
Refer to instructions in manual for flushing heat exchanger.
Measure resistance of safety circuit.
14
Thermal Fuse
Ensure high fire and low fire manifold pressure is correct.
Check for improper conversion of product.
Manual - Rinnai Condensing Water Heaters
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Code
16
Fault
Remedy
Check for restrictions in air flow around unit and vent terminal.
Check for low water flow in a circulating system causing short-cycling.
Check for foreign materials in combustion chamber and/or exhaust piping.
Check for clogged heat exchanger.
Over Temperature
Warning
Condensate container is full.
Check condensate drain for blockage.
Replace condensate trap.
25
Condensate Trap Error
Burner Sensor Error
Measure resistance of sensor.
Replace sensor.
31
32
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Replace sensor.
Outgoing Water
Temperature Sensor
Fault
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Replace sensor.
33
Heat Exchanger
Outgoing Temperature
Sensor Fault
Check modulating gas solenoid valve wiring harness for loose or damaged terminals.
Measure resistance of valve coil.
52
61
Modulating Solenoid
Valve Signal Abnormal
Combustion Fan
Failure
Ensure fan will turn freely.
Check wiring harness to motor for damaged and/or loose connections.
Measure resistance of motor winding.
The water flow control valve has failed to close during the bath fill function. Immediately turn off
the water and discontinue the bath fill function. Contact a state qualified or licensed contractor to
service the appliance.
65
71
72
Water Flow Control
Fault
Replace the PC board.
SV0, SV1, SV2, SV3
and SV4 Solenoid
Valve Circuit Fault
Flame Sensing Device
Fault
Ensure flame rod is touching flame when unit fires.
Check all wiring to flame rod for damage.
Remove flame rod and check for carbon build-up; clean with sand paper.
Check inside burner chamber for any foreign material blocking flame at flame rod.
Measure micro amp output of sensor circuit with flame present.
Replace flame rod.
Check sensor wiring and PC board for damage.
Replace sensor.
73
Burner Sensor Circuit
Error
Flush heat exchanger. Refer to instructions in manual.
Replace heat exchanger.
NOTE: The LC code is the only error code that will allow the unit to keep running. The display will
alternate between the LC code and the temperature setting. The controller will continue to beep.
The LC code will reset if power is turned off and then on.
LC
Scale Build-up in Heat
Exchanger (when
checking maintenance
code history, “00” is
substituted for “LC”)
Nothing happens when
water flow is activated.
Clean inlet water supply filter.
No
code
On new installations ensure hot and cold water lines are not reversed.
Check for bleed over. Isolate unit from building by turning off hot water line to building. Isolate the
circulating system if present. Open your pressure relief valve; if water is flowing, there is bleed
over in your plumbing.
Ensure you have at least the minimum flow rate required to fire unit.
Ensure turbine spins freely.
Measure the resistance of the water flow control sensor.
Check for DC shorts at components.
14
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Trouble Shooting for Common Issues
When I open a hot tap, I do not immediately get hot
water.
I don’t have any hot water when I open the tap.
Make sure there is gas, water, and electricity to the
Rinnai water heater (power is turned on and the gas is
turned on).
Hot water must travel through your plumbing from the
Rinnai water heater to the faucet. The time period for
hot water to reach your fixture is determined by the
amount of water in the plumbing system between the
water heater and the fixture, water pressure, and the
flow rate of the fixture.
When I was using the hot water, the water got cold.
If you adjusted the flow from the tap to lessen it, you
may have gone below the minimum flow required. The
Rinnai water heater requires a minimum flow rate to
operate. (See the specification page for the flow rate
of your model.) Decrease the temperature setting at
the temperature controller or increase the water flow.
After I turn off the hot water tap, the fan on the
Rinnai water heater continues to run.
The fan is designed to continue running for a short time
after the flow of water stops. This is to ensure constant
water temperatures during rapid starting and stopping,
as well as exhausting any residual gas flue products
from the unit.
White smoke comes out of the exhaust.
During colder weather when the exhaust temperature
is much hotter than the outside air, the exhaust fumes
condense producing water vapor.
Accessing Operating Information
Models MC-91 and MCC-91
To display the most recent error codes press and hold the “On/Off” button for 2 seconds. While holding the “On/
Off” button press the ▲ button. The last 9 error codes will flash one after the other. To exit this mode press the
“On/Off” and ▲ button as before.
To display the water flow through the water heater press and hold the ▲ button for 2 seconds and without
releasing the ▲ button press the “On/Off” button.
To display the outlet water temperature press and hold the ▼ button for 2 seconds and without releasing the ▼
button press the “On/Off” button.
Water Quality
Consideration of care for your water heater should
include evaluation of water quality. If the water quality
exceeds the target levels provided in the table, you
may want to treat or condition the water.
Maximum Level
Up to 200 mg / L
Up to 0.2 mg / L
Up to 250 mg / L
Up to 1.0 mg / L
Up to 0.3 mg / L
Up to 0.05 mg / L
6.5 to 8.5
Total Hardness
Aluminum *
Chlorides *
Copper *
•
Source: Part 143 National Secondary Drinking
Water Regulations
Component failure resulting from water quality issues
is not covered under the Rinnai product warranty.
Iron *
Manganese *
pH *
TDS (Total Dissolved
Solids) *
Up to 500 mg / L
Zinc *
Up to 5 mg / L
Manual - Rinnai Condensing Water Heaters
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Flushing the Heat Exchanger (Error Code: LC or 00)
An “LC” or “00” error code indicates the unit is beginning to lime up and must be flushed. Failure to flush the
appliance will cause damage to the heat exchanger. Damage caused by lime build-up is not covered by the unit’s
warranty. After flushing, reset the LC fault code by turning off the power to the unit and turning the power back
on.
KEY
1. Disconnect electrical power to the water heater.
2. Close the shutoff valves on both the hot water and
cold water lines (V3 and V4).
Pressure Regulator
Circulating Pump
3/4" Ball Valve
3/4" Union
3. Connect pump outlet hose (H1) to the cold water
line at service valve V2.
Check Valve
Boiler Drain Valve
Solenoid Valve
4. Connect drain hose (H3) to service valve V1.
S
Pressure Relief Valve
5. Pour 4 gallons of undiluted virgin, food grade,
white vinegar into pail.
6. Place the drain hose (H3) and the hose (H2) to
the pump inlet into the cleaning solution.
7. Open both service valves (V1 and V2) on the hot
water and cold water lines.
8. Operate the pump and allow the cleaning solution
to circulate through the water heater for 1 hour at
a rate of 4 gallons per minute (15.1 liters per
minute).
Water Heater
9. Turn off the pump.
10. Rinse the cleaning solution from the water heater
as follows:
a. Remove the free end of the drain hose (H3)
from the pail.
b. Close service valve, (V2), and open shutoff
valve, (V4). Do not open shutoff valve, (V3).
c. Allow water to flow through the water heater for
5 minutes
In-line
Filter
d. Close service valve, (V1), and open shutoff
valve, (V3).
Gas Supply
11. Disconnect all hoses.
12. With (V4) closed, remove the in-line filter at the
cold water inlet and clean out any residue. Place
filter back into unit and open (V4).
V2
V1
13. Restore electrical power to the water heater.
H3
V4
V3
Cold Water Line
Hot Water Line
Cleaning solution is 4 gallons of
undiluted virgin, food grade,
white vinegar.
H2
H1
Circulating Pump
16
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Instructions
Only properly trained and qualified installers
should install this appliance. The warranty may
be voided due to improper installation or
installation by a non-qualified installer.
Rinnai highly recommends all installers attend a
product knowledge class.
For information on a Rinnai Training Course or
for questions on installation call 1-800-621-
9419.
General Instructions
• The appliance must be isolated from the gas supply
piping system by closing its individual manual
shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psi (3.5 kPa) (13.84 in W.C.).
Do not use substitute materials.
Use only parts certified with the appliance.
• Follow the installation instructions and those in Care
• This appliance must be installed by a state qualified
or licensed contractor. It is the responsibility of the
person having the water heater installed to ensure
the installing contractor has proper licenses and
permits for installing water heaters in your location.
Rinnai highly recommends that installers attend a
product knowledge class to ensure customer
satisfaction and warranty coverage. Failure to
comply with state and local codes pertaining to
water heater installations may void the warranty.
and Maintenance for adequate combustion and
ventilation air.
• The appliance should be located in an area where
water leakage of the unit or connections will not
result in damage to the area adjacent to the
appliance or to lower floors of the structure. When
such locations cannot be avoided, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance. The pan
must not restrict combustion air flow.
• The RC80HPi (REU-KA2530FFUD-US) and
RC98HPi (REU-KA3237FFUD-US) are not to be
installed outdoors.
• The flow of combustion and ventilation air shall not
be obstructed.
• This appliance is not suitable for use in an
application such as a pool or spa heater that uses
chemically treated water . (This appliance is
suitable for filling large or whirlpool bath tubs with
potable water.)
• The RC80HPe (REU-KA2530WD-US) and
RC98HPe (REU-KA3237WD-US) are not to be
installed indoors.
• A qualified installer or service technician should
install the appliance, inspect it, and leak test it
before use.
• If a water heater is installed in a closed water supply
system, such as one having a backflow preventer in
the cold water supply line, means shall be provided
to control thermal expansion. Contact the water
supplier or local plumbing inspector on how to
control thermal expansion.
• The installation must conform with local codes or, in
the absence of local codes, with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, or the Natural
Gas and Propane Installation Code, CSA B149.1.
• The appliance, when installed, must be electrically
grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical
Code, ANSI/NFPA 70, or the Canadian Electrical
Code, CSA C22.1.
• Should overheating occur or the gas supply fail to
shut off, turn off the manual gas control valve to the
appliance.
• Keep the air intake location free of chemicals such
as chlorine or bleach that produce fumes. These
fumes can damage components and reduce the life
of your appliance.
• The appliance and its appliance main gas valve
must be disconnected from the gas supply piping
system during any pressure testing of that system at
test pressures in excess of 1/2 psi (3.5 kPa) (13.84
in W.C.).
• Component damage resulting from chemical fumes
is not covered under the Rinnai product warranty.
Manual - Rinnai Condensing Water Heaters
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Clearances from Appliance
RC80HPi, RC98HPi
RC80HPe, RC98HPe
to Non-
to Com-
to Non-
Combus-
tibles
to Com-
bustibles
Combus-
bustibles
to top
tibles
Top of
Heater
12 inches
(305 mm)
2 inches
(51 mm)
Top of
Heater
12 inches
(305 mm)
2 inches
(51 mm)
Back of
Heater
0 (zero)
0 (zero)
Back of
Heater
0 (zero)
0 (zero)
Front of
Heater
6 inches
(152 mm)
6 inches
(152 mm)
Front
(Panel)
24 inches
(610 mm)
0 inches
(0 mm)
to side
Sides of
Heater
2 inches
(51 mm)
1/2 inch
(13 mm)
Front
(Exhaust)
24 inches
(610 mm)
24 inches
(610 mm)
Floor/
Ground
12 inches
(305 mm)
2 inches
(51 mm)
Sides of
Heater
6 inches
(152 mm)
1/8 inch
(3.2 mm)
to front
to floor/ground
Floor/
Ground
12 inches
(305 mm)
2 inches
(51 mm)
Vent
4 inches * 0 (zero)
* 4 inches (102 mm) for enclosed area; 1 inch (26 mm) for unenclosed area.
** 0 inches from vent components and condensate drain line.
The clearance for servicing is 24 inches in front of the water heater.
For closet installation: clearance is 6 inches (152 mm) from the front.
Attachment of the Water Heater
1. Identify the installation location and confirm that
the installation will meet all required clearances.
2. Securely attach the water heater to the wall using
any of the holes in the wall installation brackets
which are at the top and bottom of the water
heater. Ensure that the attachment strength is
sufficient to support the weight. Refer to the
weight of the water heater in the Specifications
section.
wall installation
brackets
18
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical Connection
The water heater requires 120 VAC, 60 Hz power from a properly grounded circuit.
If using the 6 foot long power cord, plug it into a standard 3 prong 120 VAC, 60 Hz properly grounded wall outlet.
The wiring diagram is located on the Technical Sheet attached to the inside of the front cover.
The water heater must be electrically grounded in accordance with local codes, or in the absence of local codes
with the National Electrical Code, ANSI/NFPA 70 and/or the CSA C22.1, Canadian Electrical Code.
Gas Piping
General Instructions
including soap and water, may cause corrosion or
stress cracking, the piping shall be rinsed with water
after testing, unless it has been determined that the
leak test solution is non-corrosive.)
• A manual gas control valve must be placed in the
gas supply line to the Rinnai water heater. A union
can be used on the connection above the shut off
valve for the future servicing or disconnection of the
unit.
• Always use approved connectors to connect the unit
to the gas line. Always purge the gas line of any
debris before connection to the water heater.
• Check the type of gas and the gas inlet pressure
before connecting the Rinnai water heater. If the
Rinnai water heater is not of the gas type that the
building is supplied with, DO NOT connect the water
heater. Contact the dealer for the proper unit to
match the gas type.
• The gas supply line shall be gas tight, sized, and so
installed as to provide a supply of gas sufficient to
meet the maximum demand of the heater and all
other gas consuming appliances at the location
without loss of pressure.
• Check the gas supply pressure immediately
upstream at a location provided by the gas
company. Supplied gas pressure must be within the
limits shown in the Specifications section.
• Any compound used on the threaded joint of the gas
piping shall be a type which resists the action of
liquefied petroleum gas (propane / LPG).
• Before placing the appliance in operation all joints
including the heater must be checked for gas
tightness by means of leak detector solution, soap
and water, or an equivalent nonflammable solution,
as applicable. (Since some leak test solutions,
• Refer to an approved pipe sizing chart if in doubt
about the size of the gas line.
Manual - Rinnai Condensing Water Heaters
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Piping
Pipe Sizing Procedure - Example
The gas supply must be capable of handling the entire gas load at the location. Gas line sizing is based on gas
type, the pressure drop in the system, the gas pressure supplied, and gas line type. For gas pipe sizing in the
United States, refer to the National Fuel Gas Code, NFPA 54. For Canadian gas pipe sizing, refer to the Natural
Gas and Propane Installation Code CAN/CSA B149.1. The below information is provided as an example. The
appropriate table from the applicable code must be used.
1. Determine the cubic feet per hour of gas required by dividing the gas input (on the rating plate) by the heating
value of the gas (available from the local gas company). The gas input needs to include all gas products at
the location and the maximum BTU usage at full load when all gas products are in use.
Gas Input of Rinnai water heater (BTU / HR)
Cubic Feet per Hour (CFH) =
Heating Value of Gas (BTU / FT 3 )
2. Use the table for your gas type to find the pipe size required for your cubic feet per hour of gas and your pipe
length.
Example: The heating value of propane gas for your location is 2516 BTU / FT 3. The gas input of the R94LSi is
190,000 BTU/HR. Additional appliances at the location require 75,000 BTU/HR.
Therefore the cubic feet per hour = (190,000+75,000) / 2516 = 105.3 FT 3/ HR.
If the pipe length is 100 ft then the 3/4 inch pipe size capable of supplying 197 FT 3/ HR of propane gas
will be adequate.
Pipe Size (inches)
Length
Pipe Size (inches)
Length
3/4
273
188
151
129
114
104
95
1
1 1/4
1060
726
583
499
442
400
368
343
322
304
269
244
224
209
1 1/2
1580
1090
873
747
662
600
552
514
482
455
403
366
336
313
1/2
291
200
160
137
122
110
101
94
3/4
608
418
336
287
255
231
212
197
185
175
155
140
1
1 1/4
2350
1620
1300
1110
985
10
20
514
353
284
243
215
195
179
167
157
148
131
119
109
102
10
20
1150
787
632
541
480
434
400
372
349
330
292
265
30
30
40
40
50
50
60
60
892
70
80
821
80
89
100
125
150
175
200
763
90
83
89
716
100
125
150
175
200
79
84
677
70
74
600
63
67
543
58
54
20
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Piping
General Instructions
• A manual water control valve must be placed in the
water inlet connection to the Rinnai water heater
before it is connected to the water line. Unions may
be used on both the hot and cold water lines for
future servicing and disconnection of the unit.
• Toxic chemicals such as those used for boiler water
treatment are not to be introduced to the potable
water used for space heating.
• If the appliance will be used as a potable water
source, it must not be connected to a system that
was previously used with a nonpotable water
heating appliance.
• The piping (including soldering materials) and
components connected to this appliance must be
approved for use in potable water systems.
• Ensure that the water filter on the Rinnai water
• Purge the water line to remove all debris and air.
heater is clean and installed.
Debris will damage the Rinnai water heater.
Pressure Relief Valve
• An approved pressure relief valve is required by the
American National Standard (ANSI Z21.10.3) /
Canadian Standard (CSA 4.3) for all water heating
systems.
• The relief valve should be added to the hot water
outlet line according to the manufacturer’s
instructions. DO NOT place any other type valve or
shut off device between the relief valve and the
water heater.
• The relief valve must comply with the standard for
Relief Valves and Automatic Gas Shutoff Devices
for Hot Water Supply Systems ANSI Z21.22 and /or
the standard Temperature, Pressure, Temperature
and Pressure Relief Valves and Vacuum Relief
Valves, CAN1-4.4.
• Do not plug the relief valve and do not install any
reducing fittings or other restrictions in the relief line.
The relief line should allow for complete drainage of
the valve and the line.
• If a relief valve discharges periodically, this may be
due to thermal expansion in a closed water supply
system. Contact the water supplier or local
plumbing inspector on how to correct this situation.
Do not plug the relief valve.
• The relief valve must be rated up to 150 psi and to
at least the maximum BTU/hr of the appliance.
• The discharge from the pressure relief valve should
be piped to the ground or into a drain system to
prevent exposure or possible burn hazards to
humans or other plant or animal life. Follow local
codes. Water discharged from the relief valve could
cause severe burns instantly, scalds, or death.
• Neither Rinnai nor the American National Standard
(ANSI Z21.10.3) / Canadian Standard (CSA 4.3)
requires a combination temperature and pressure
relief valve for this appliance. However, local codes
may require a combination temperature and
pressure relief valve.
• The pressure relief valve must be manually
operated once a year to check for correct operation.
Freeze Protection
The freeze protection features include electrical
heating elements. Freeze protection may be disabled
if electricity is not supplied, or if there is an error
preventing the water heater from functioning. Loss of
freeze protection may result in water damage from a
burst heat exchanger or water lines.
The condensate trap drain plug and water drain plug
are not affected by the auto drain down solenoid valves
and will have to be manually opened.
The freeze protection features will not prevent the
external piping from freezing. Rinnai recommends
heat tracing and insulating hot and cold water pipes
connecting units. Pipe cover enclosures may be
packed with insulation for added freeze protection.
The installation of auto drain down solenoid valves is
optional. However, Rinnai strongly recommends that
these valves be installed to prevent damage from
freezing in case the normal freeze protection should
become disabled. Any product damage due to
freezing will not be covered by the warranty.
With electrical power supplied, Rinnai condensing
water heaters will not freeze when the outside air
temperature is as cold as –22ºF (-30ºC) for indoor
models or is as cold as –4ºF (-20ºC) for outdoor
models, when protected from direct wind exposure.
Because of the “wind-chill” effect, any wind or
circulation of the air on the unit will reduce its ability to
freeze protect.
In addition, the solenoid valves should be connected
electrically to a surge protector with terminals. This
allows the solenoid valves to operate if the water
heater is disabled due to an error code.
The solenoid valves and surge protector with terminals
are available for purchase at Rinnai.
Manual - Rinnai Condensing Water Heaters
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Freeze Protection Piping
Manual draining of the water heater
If the water heater is not going to be used during a period of possible freezing weather, it is recommended that the
water inside the water heater be drained.
To manually drain the water:
1. Shut off cold water supply and gas supply.
2. Turn off the temperature controller.
3. Disconnect the power to the water heater.
Hot water
outlet
Hot water
drain plug*
Water
filter
4. Open hot water tap or open hot water drain plug at the
hot water outlet.
Water
drain
plug
5. Remove water filter to drain the cold water.
6. Unscrew the water drain plug from the drain line next
to the hot water outlet.
7. Remove the condensate trap drain plug and allow to
drain.
To resume normal operation:
1. Confirm that all water drain plugs are removed, that the
gas supply is turned off, and that all taps are closed.
Condensate
trap drain plug
Cold water
inlet
2. Insert the condensate trap drain plug.
3. Screw in the water drain plugs.
4. Screw in the water filter in the cold water inlet.
5. Open the cold water supply.
* Use a wrench or other
tool to unscrew the hot
water drain plug.
6. Open a tap and confirm that water flows, and then
close.
7. Turn on the power.
8. After confirming that the temperature controller is off,
turn on the gas supply.
9. Turn on the temperature controller.
Running a low volume of water through the water heater to prevent freezing
If the temperature exceeds the ability of the water heater to freeze
protect itself, or if power is lost, the following steps may prevent the
ON!
water heater and external piping from freezing. (Units connected with
MSA or EZConnect should be drained to prevent freezing if not in
use.)
COLD
0.1 gal/min or
about 0.2 inch
thick
1. Turn the water heater off.
2. Close the gas supply valve.
HOT
3. Reduce the flow to about 0.1 gal/min or to where the stream is
about 0.2 inches thick.
When the water heater or external piping has frozen
1. Do not operate the water heater if it or the external piping is frozen.
2. Close the gas and water valves and turn off the power.
3. Wait until the water thaws. Check by opening the water supply valve.
4. Check the water heater and the piping for leaks.
22
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Recommended Piping for Basic Installation
Hot water
drain plug
Water
drain
plug
Condensate
trap drain plug
Rinnai
Equipment List
QTY
Condensate
drain line
Rinnai
Water Heaters
1
1
RIK-KIT (Optional)
(3/4" Fittings Include:
2 Unions, 2 Ball Valves,
2 Drain Valves and
1 Pressure Relief Valve.)
Refer to the Condensate
section in the venting
instructions
3/4" Gas Connection
Condensate drain line
Condensate
drain
Gas Supply
3/4" Hot Water Supply Line
3/4" Cold Water Supply
Line
For Building Fixtures
KEY
This is not an engineered drawing. It is intended only as a guide and not
as a replacement for professionally engineered project drawings. This
drawing is not intended to describe a complete system. It is up to the
contractor/engineer to determine the necessary components and
configuration of the particular system being installed. This drawing does
not imply compliance with local building code requirements. It is the
responsibility of the contractor/engineer to ensure installation is in
accordance with all local building codes. Confer with local building
officials before installation.
Pressure Regulator
Circulating Pump
3/4" Ball Valve
3/4" Union
Check Valve
Boiler Drain Valve
Solenoid Valve
S
Pressure Relief Valve
Manual - Rinnai Condensing Water Heaters
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Recommended Piping for Circulation Systems
NOTE:
For residential and commercial
applications, this piping arrange-
ment maintains full warranty.
Rinnai
Equipment List
QTY
1
For this application:
Rinnai
Water Heaters
Pump should be controlled by an
Aquastat, Timer or Combination Aquastat
and Timer.
RIK-KIT (Optional)
1
(3/4" Fittings Include:
2 Unions, 2 Ball Valves,
2 Drain Valves and
Pump to be sized to maintain circulation
loop temperature.
1 Pressure Relief Valve.)
The pump should be sized to overcome
the pressure loss through the tank water
heater, and supply and return plumbing.
Reference the Rinnai Hot Water System
Design Manual, Pump Sizing for Circula-
tion.
3/4" Gas Connection
Gas Supply
Pump to be of bronze or stainless
construction.
Condensate drain line
Minimum 3/4" Cold Water Supply Line
Tank Water Heater to be Sized for
Heat Loss of Circulation Loop.
Condensate
drain
Building Supply
IMPORTANT: Connect the building
return line to the hot water supply line
as close as possible to the Rinnai Water
Heater.
Electric Water
Heater
Building
Fixtures
k
an
n T
sio
an
Exp
KEY
This is not an engineered drawing. It is intended only as a guide and not
as a replacement for professionally engineered project drawings. This
drawing is not intended to describe a complete system. It is up to the
contractor/engineer to determine the necessary components and
configuration of the particular system being installed. This drawing does
not imply compliance with local building code requirements. It is the
responsibility of the contractor/engineer to ensure installation is in
accordance with all local building codes. Confer with local building
officials before installation.
Pressure Regulator
Circulating Pump
3/4" Ball Valve
3/4" Union
Check Valve
Boiler Drain Valve
Solenoid Valve
S
Pressure Relief Valve
24
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Piping for Circulation Systems
NOTE:
For residential and commercial
applications, this piping
arrangement reduces the warranty
to the following:
For this application:
Pump should be controlled by an Aquastat,
Timer or Combination Aquastat and Timer.
3 years on heat exchanger
3 year on parts
Pump to be sized to maintain circulation
loop temperature.
Full warranty will be maintained if
an on-demand recirculation
system in incorporated. Refer to
the Limited Warranty.
A minimum of 3 GPM flow is recommended
for the circulation system.
The pump should be sized to overcome the
pressure loss through the Rinnai water
heater, supply and return plumbing. Refer-
ence the Rinnai Hot Water System Design
Manual, Pump Sizing for Circulation.
Rinnai
Equipment List
QTY
Rinnai
Water Heaters
1
1
Pump to be of bronze or stainless construc-
tion.
RIK-KIT (Optional)
(3/4" Fittings Include:
2 Unions, 2 Ball Valves,
2 Drain Valves and
1 Pressure Relief Valve.)
3/4" Gas Connection
Condensate drain line
Gas Supply
Note:
Condensate
drain
Water heater outlet temperature
cannot be adjusted when
circulation pump is running.
Minimum 3/4" Hot Water
Supply Line
Minimum 3/4 “ Cold Water Supply Line
(Optional)
2-6 Gallon
Storage Tank
(To eliminate cold water
sandwich effect caused by
frequent On/Off operation)
nk
Ta
ion
ans
Exp
Building Fixture Outlets
KEY
This is not an engineered drawing. It is intended only as a guide and not
as a replacement for professionally engineered project drawings. This
drawing is not intended to describe a complete system. It is up to the
contractor/engineer to determine the necessary components and
configuration of the particular system being installed. This drawing does
not imply compliance with local building code requirements. It is the
responsibility of the contractor/engineer to ensure installation is in
accordance with all local building codes. Confer with local building
officials before installation.
Pressure Regulator
Circulating Pump
3/4" Ball Valve
3/4" Union
Check Valve
Boiler Drain Valve
Solenoid Valve
S
Pressure Relief Valve
Manual - Rinnai Condensing Water Heaters
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting Instructions
Refer to the specific instructions on your vent product for
additional installation requirements.
Intake / Exhaust Guidelines
•
This water heater is a direct vent water heater and
therefore is certified and listed with the vent
system. You must use vent components that are
certified and listed with the water heater model.
•
•
•
•
Do not common vent with the vent pipe of any
other water heater or appliance.
Vent connections must be firmly pressed together
so that the gaskets form an air tight seal.
•
•
•
•
Do not combine vent components from different
manufacturers.
Refer to the instructions of the vent system
manufacturer for component assembly instructions.
The vent system must vent directly to the outside
of the building and use outside air for combustion.
If the vent system is to be enclosed, it is suggested
that the design of the enclosure shall permit
inspection of the vent system. The design of such
enclosure shall be deemed acceptable by the
installer or the local inspector.
Venting should be as direct as possible with a
minimum number of pipe fittings.
Avoid dips or sags in horizontal vent runs by
installing supports per the vent manufacturer’s
instructions.
•
Support horizontal vent runs every four feet and all
vertical vent runs every six feet or in accordance
with local codes.
•
•
Vent diameter must not be reduced.
Do not connect the venting system with an existing
vent or chimney.
Condensate
The Rinnai RC80HPi and RC98HPi condensing
tankless water heaters are factory equipped with a
condensate trap and drain line.
• Use only vent that is approved and identified as
acceptable for condensing appliances.
The condensate trap must be primed before operation
to prevent exhaust gases from entering the building
• Do not use aluminum, PVC, CPVC, ABS or
galvanized material to vent this appliance.
• Slope the venting toward the appliance according to
the vent manufacturers installation instructions.
• All condensate must drain and dispose of per local
codes.
• The drain pipe should be as short as possible and
have a downward pitch.
• If the condensate drain gets blocked, an error code
will display on the controller. If this occurs, the
condensate drain must be cleaned.
• The end of the drain pipe should be open to the
atmosphere. The end should not be under water or
other substances.
• The condensate trap will automatically prime (self-
prime) during operation of the unit as condensate
forms. Condensate draining from the unit indicates
that the trap is full and that there is no blockage in
the condensate drain. It is not necessary to add
water to the condensate trap.
• Do not connect the drain pipe directly to the rain
sewer.
• Do not connect the condensate drain line with an
air conditioning evaporator coil drain.
• To minimize freezing of the condensate, run the
condensate drain line through an interior wall or
between insulation and an interior wall.
• Use only PVC or CPVC pipe for the condensate
drain line.
• The drain pipe (along its entire length) must be at
least the same diameter as the drain line, (1/2 inch
NPT).
26
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Maximum Vent Length
1. Determine the number of 90 degree elbows in the vent system. Two 45 degree elbows count as one 90
degree elbow.
2. Refer to the table to find the maximum vent length based on the number of elbows.
3. Follow the applicable note.
Example: If you have one elbow then your maximum vent length is 35 feet (10.7 m). If your actual length is
greater than 15 ft (4.6 m) then move dip switch no. 1 (SW1) to OFF.
Number of 90° Elbows
0
1
2
3
4
5
6
41 ft 1
35 ft 2
29 ft 3
23 ft 4
17 ft 4
11 ft 4
5 ft 4
(12.5 m) (10.7 m)
(8.8 m)
(7.0 m)
(5.2 m)
(3.4 m)
(1.5 m)
Switch No.
1If the length is greater than 21 ft (6.4 m) then move
ON
dip switch no. 1 (SW1) to OFF.
O
F
F
1
2
3
4
5
6
7
8
Notes 1234
2If the length is greater than 15 ft (4.6 m) then move
dip switch no. 1 (SW1) to OFF.
3If the length is greater than 9 ft (2.7 m) then move
dip switch no. 1 (SW1) to OFF.
4Move dip switch no. 1 (SW1) to OFF.
Vent Products
Listed and Tested Vent Products for RC80HPi ................. REU-KA2530FFUD-US
RC98HPi ................. REU-KA3237FFUD-US
Manufacturer
Product
Parts
Rinnai/Ubbink
Rolux Condensing Vent
System
Refer to the manufacturer’s technical literature for
specific part numbers and instructions.
Selkirk / Heat-Fab
Metal-Fab
Saf-T Vent SC system
Corr/Guard Vent/Air
Intake System
Vent Manufacturer Contact Information for Installation Instructions and Parts Lists:
Rinnai/Ubbink
Heat-Fab
Metal-Fab Inc.
Telephone: 800-621-9419
Telephone: 800-772-0739
Telephone: 800-835-2830
Fax:
678-829-1666
Fax:
413-863-4803
316-943-2351
E-mail:
Fax:
316-943-2717
E-mail:
Manual - Rinnai Condensing Water Heaters
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Flue Terminal Clearances (ANS Z21.10.3 ● CSA 4.3)
INSIDE
CORNER DETAIL
G
H
A
I
M
B
FIXED
CLOSED
D
K
B
OPERABLE
E
B
C
J
FIXED
B
CLOSED
B
A
X
AIR SUPPLY INLET
VENT TERMINAL
OPERABLE
L
V
F
AREA WHERE
TERMINAL IS NOT
PERMITTTED
B
Description
Canadian Installations
12 inches (30 cm)
36 inches (91 cm)
*
US Installations
12 inches (30 cm)
12 inches (30 cm)
*
Ref
A
Clearance above grade, veranda, porch, deck, or balcony
Clearance to window or door that may be opened
Clearance to permanently closed window
B
C
Vertical clearance to ventilated soffit, located above the terminal
within a horizontal distance of 2 feet (61 cm) from the center line
of the terminal
D
*
*
E
F
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
*
*
*
*
*
*
G
3 feet (91 cm) within a height
15 feet (4.5 m) above the
meter/regulator assembly
Clearance to each side of center line extended above meter/
regulator assembly
H
*
I
Clearance to service regulator vent outlet
36 inches (91 cm)
36 inches (91 cm)
*
Clearance to nonmechanical air supply inlet to building or the
combustion air inlet to any other appliance
J
12 inches (30 cm)
3 feet (91 cm) above if within
10 feet (3 m) horizontally
K
Clearance to a mechanical air supply inlet
6 feet (1.83 m)
Clearance above paved sidewalk or paved driveway located on
public property
L
7 feet (2.13 m) 1
*
*
M
Clearance under veranda, porch, deck, or balcony
12 inches (30 cm) 2
1
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves
both dwellings.
2
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
∗
For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances are in accordance with local installation codes and the
requirements of the gas supplier.
Clearance to opposite wall is 24 inches (60 cm) for Canada and US.
28
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Additional Clearances - Vent Terminal (RC80HPi, RC98HPi)
Local codes supersede these clearances.
• Avoid termination locations near a dryer vent.
• Avoid termination locations near commercial cooking exhaust.
• For air intake position, follow the ANS Z21.10.3 ● CSA 4.3 requirements on the previous page.
Vent terminal (represents concentric vent terminal or exhaust only vent terminal)
V
(1.52 m) vertically
between Rinnai terminals
60"
(0.91 m) to ventilated
or unventilated soffit
36" or eve vent; or to a
deck or porch
V
12"
V
V
(0.30 m ) to an
inside corner
12"
(0.61 m) to wall or parapet
V
24"
(0.30 m) between
Rinnai terminals at
same level
INSIDE
CORNER
(1.52 m) between
Rinnai terminals
at different levels
60"
V
V
12"
(0.30 m) between
Rinnai terminals at
same level
V
V
Manual - Rinnai Condensing Water Heaters
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Additional Clearances (RC80HPe, RC98HPe)
Local codes supersede these clearances.
• Avoid termination locations near a dryer vent.
• Avoid termination locations near commercial cooking exhaust.
(0.91 m) to ventilated or unventilated soffit or eve vent; or
36" to a deck or porch
12"
(0.30 m) to an
inside corner
2"
(50 mm) between Rinnai terminals at same level
INSIDE
CORNER
30
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Flue Installation (RC80HPi, RC98HPi)
Slope the venting toward the appliance according to
the vent manufacturers installation instructions.
Dispose of condensate per local codes.
Slope the venting toward the appliance according to
the vent manufacturers installation instructions.
Dispose of condensate per local codes.
Securing
Manual - Rinnai Condensing Water Heaters
31
Download from Www.Somanuals.com. All Manuals Search And Download.
High Altitude Installations
Set dip switches 2 and 3 to the values shown in table
below for your altitude. The default setting for the
appliance is 0-2000 ft (0-610 m) with switches No. 2
and No. 3 in the OFF position.
0-2000 ft
(0-610 m)
2001-5200 ft
(610-1585 m)
5201-7700 ft
(1585-2347 m)
7701-10200 ft
(2347-3109 m)
Switch No. 2
Switch No. 3
OFF
OFF
OFF
ON
ON
ON
ON
OFF
Switch No.
ON
Switch No.
ON
Switch No.
ON
Switch No.
ON
O
F
F
O
F
F
O
F
F
O
F
F
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Connecting Multiple Water Heaters
The EZConnect™ cable is an optional accessory that
connects 2 water heaters and allows them to function
as one hot water source.
Guidelines
• Do not install both the EZConnect™ and the MSA
packs because they are not designed to operate
together.
The MSA-2M and MSA-2S packs are optional
accessories that connect 2 to 5 water heaters and
allow them to function as one hot water source.
• Water heaters connected with the EZConnect™
Cable or the MSA-2M and MSA-2S packs cannot be
used for the bath fill function.
Refer to the instructions that come with the accessory
for complete installation information.
• Water heaters should be installed less than 18
inches apart so that the cables will reach between
units and to prevent temperature fluctuations (cold
water sandwich effect) when the water is shut off
and turned back on.
• Temperature settings can only be changed on the
controller for the primary unit.
Number of Connected Water Heaters:
Accessories Necessary:
(1) EZConnect™ Cable or (1) MSA-2M
(1) MSA-2M and (1) MSA-2S
(1) MSA-2M and (2) MSA-2S
(1) MSA-2M and (3) MSA-2S
2
3
4
5
32
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Temperature Controller Installation
Indoor models have their controller built into the front panel. A kit is available that allows the integrated controller
to be removed and used as a remote controller. Additional controllers can also be installed.
Location
•
•
•
The controller should be out of reach of small
children.
•
•
Avoid locations where the temperature controller
could be splashed with liquids.
Avoid locations where the controller may become
hot (near the oven or radiant heater).
Do not install in locations where it can be adjusted
by the public.
Avoid locations in direct sunlight. The digital
display may be difficult to read in direct sunlight.
Configurations
A maximum of 4 temperature controllers, including
wired and wireless, can be installed for a water heater
or bank of water heaters. Controllers can only be
wired in parallel. Controllers cannot be wired in
series.
Controllers
The 4 temperature controllers can consist of multiple
MC-91’s or MC-502RC’s but only 1 BC-100V and only
1 MC-100V.
Any one of the 5 types of controllers can be installed
by itself and still operate the water heater. All
functions will be available with the exception that the
clock function on the BC-100V will only be available if
an MC-100V is also connected.
Wire controllers in parallel
If 4 MC-91’s are installed, simultaneously press the
Priority and On/Off buttons on the fourth controller
until a beep sounds.
MC-91
MC-91
+
+
MC-91
+
MCC-91
+ MC-502RC
MCC-91 + MC-502RC + MC-502RC
The table to the right shows some of the possible
combinations of controllers.
MCC-91 + MC-502RC + BC-100V
MC-91 + MC-502RC + BC-100V
+
+
MC-100V
MC-100V
MC-91
+
MC-91
+ MC-502RC + BC-100V
MC-91 + MC-502RC + MC-502RC + MC-100V
Cable Lengths and Size
Number of Wired Maximum Cable Length for each
The cable for the temperature controller should be a
non-polarized two-core cable with a minimum gauge
of 22 AWG. The maximum cable length from each
controller to the water heater depends on the total
number of wired controllers connected to the water
heater.
Controllers
Controller to Water Heater
1
2
328 ft (100 m)
164 ft (50 m)
3 or 4
65 ft (20 m)
Manual - Rinnai Condensing Water Heaters
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Temperature Controller Installation
Mounting the Controller
Follow the procedure below to install MC-91 or
MCC-91 temperature controllers.
1. Determine a suitable location for the
controller.
2. Make three holes in the wall as shown.
3. Run the cable between the controller and the
Rinnai water heater or the controller and the
other controller.
4. Remove the face plate from the temperature
controller using a screwdriver.
5. Connect the cable to the temperature
controller.
6. Mount the controller to the wall using the
holes drilled in step 2.
Outline of Remote
7. Disconnect the power from the Rinnai water
heater.
8. Remove the cover of the Rinnai water heater.
securing screw
9. Remove the plastic cover from the PC board
and electrical connections.
1-21/32"
wiring hole
10. Thread the cable through the access hole at
the base of the unit and connect the wires to
the controller terminals on the right hand side
bottom of the PC board.
3-5/16"
securing screw
11. Secure the controller cable using the clamp
provided.
12. Replace plastic cover over PC board and then
replace the cover of the Rinnai water heater.
34
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is
equipped with an ignition device which
automatically lights the burner. Do not try to light
the burner by hand.
• If you cannot reach your gas supplier, call the
fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not
push in or turn by hand, do not try to repair it, call a
qualified service technician. Force or attempted
repair may result in a fire or explosion.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than air and
will settle on the floor.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas control
which has been under water.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
OPERATING INSTRUCTIONS
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you smell
gas, STOP! Follow “B” in the safety information
above. If you don’t smell gas, go to the next step.
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance using
the ON/OFF button.
7. Turn the manual gas valve counterclockwise to the
full ON position.
4. This appliance is equipped with an ignition device
which automatically lights the burner. Do not try to
light the burner by hand.
8. Turn on all electric power to the appliance using
the ON/OFF button.
5. Locate the manual gas valve on the side of the
heater. Turn the manual valve
9. Set the thermostat to desired setting.
clockwise to the full OFF position.
10. Open a hot water tap. If the appliance will not
operate, follow the instructions “To Turn Off Gas
To Appliance” and call your service technician or
gas supplier. See manual for additional
information.
Manual Valve
CLOSE
OPEN
TO TURN OFF GAS TO APPLIANCE
1. Turn off all electric power to the appliance using
3. Locate the manual gas valve on the side of the
heater. Turn the manual valve clockwise to the full
OFF position.
the ON/OFF button.
2. Set the thermostat to lowest setting.
Manual - Rinnai Condensing Water Heaters
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Technical Data
Pressure Drop Curve
RC80HP
RC98HP
Water Flow (gpm)
Outlet Flow Data
RC98HP
RC80HP
delta T - Temperature Rise (ºF)
36
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Space Heating
If the water heater is to be used for both water (potable) heating and space heating then the following apply.
•
•
•
The piping and components connected to the water heater shall be suitable for use with potable water.
Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water.
The water heater shall not be connected to any heating system or components previously used with a
nonpotable water heating appliance.
•
When the system requires water for space heating at temperatures higher than required for other uses, a
means such as a mixing valve shall be installed to temper the water for other uses in order to reduce the
scald hazard potential.
Space heating applications are considered commercial applications for warranty purposes.
Temperature Setting
When using this appliance to provide domestic hot water it is recommended that the domestic hot water
temperature be reduced to acceptable temperatures in accordance with local codes. In the absence of local
codes it is recommended that the domestic hot water temperature be set to 140º F (60º C) or lower in accordance
with UPC 501.6 by using mixing valves or the temperature controller for the water heater.
Pumps
Only use pumps of brass or stainless steel construction. Do not use pumps of iron construction as they will
oxidize and clog the inlet filter on the appliance.
Pumps circulating water through the water heater must be sized to overcome the pressure loss through the water
heater, the heating system, and any additional plumbing pressure losses. The pressure drop curve based on the
water heater model is provided in this manual.
Replacement
When replacing an existing space heating application’s water heating source (boiler, tank water heater, tankless
water heater, etc.) with Rinnai water heaters, ensure that the water heaters are sized to adequately provide the
necessary BTU input for the desired space heating application. Rinnai water heaters are designed to maintain a
constant outlet temperature and will supply only the necessary amount of BTU’s to maintain that temperature.
Depending on the application the maximum BTU rating of the unit may not be achieved. Contact Rinnai’s
Applications Engineering Department for assistance at (800) 621-9419 ext. 4490.
Iron Components
Do not use Rinnai water heaters directly for space heating applications involving iron radiators or applications with
any iron components. Iron components may oxidize creating rust that will clog the inlet filter of the Rinnai water
heater.
Manual - Rinnai Condensing Water Heaters
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
RC80HPi, RC98HPi
RC80HPe, RC98HPe
RC80HPi, RC80HPe
RC98HPi, RC98HPe
G
I
E
L
H
J
F
M
DI
M
DESCRIPTION
RC80HPi
in (mm)
RC98HPi
in (mm)
RC80HPe
in (mm)
RC98HPe
in (mm)
A
B
C
D
E
F
Width
Depth
18.5 (470)
10.5 (266.9) *
26.4 (670)
28.5 (723.2)
4.3 (110) *
3.9 (100)
18.5 (470)
10.5 (266.9) *
26.4 (670)
28.5 (723.2)
4.3 (110) *
3.9 (100)
18.5 (470)
10.7 (271.9)
26.4 (670)
28.4 (721.6)
4.5 (115)
18.5 (470)
10.7 (271.9)
26.4 (670)
28.4 (721.6)
4.5 (115)
Height - Unit
Height - with brackets
Hot Water Outlet - from wall
Hot Water Outlet - from
center
3.9 (100)
3.9 (100)
G
H
I
Cold Water Inlet - from wall
Cold Water Inlet - from center
Gas Connection - from wall
Gas Connection - from center
From base to gas connection
From base to cold connection
From base to hot connection
Condensate Dain - from wall
2.8 (70.0) *
0.5 (12.8)
3.9 (99) *
2.9 (74.6) *
1.1 (27.7)
3.9 (99) *
3.0 (75.0)
0.5 (12.8)
4.1 (104)
4.1 (103.2)
1.6 (40.2)
2.0 (50.2)
1.6 (41.2)
5.4 (137.6)
7.7 (195)
3.1 (79.6)
1.1 (27.7)
4.1 (104)
4.1 (103.2)
1.6 (40.2)
2.0 (50.2)
1.6 (41.2)
5.4 (137.6)
7.7 (195)
J
4.1 (103.2)
1.6 (40.2)
2.0 (50.2)
1.6 (41.2)
5.2 (132.6) *
7.7 (195)
4.1 (103.2)
1.6 (40.2)
2.0 (50.2)
1.6 (41.2)
5.2 (132.6) *
7.7 (195)
K
L
Condensate Drain - from
center
M
* This is the minimum dimension from the wall. The wall bracket is adjustable to allow an additional 1.57 inches
(40 mm).
38
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Ladder Diagram
TWIN
THERMISTOR
WATER
LEVEL
DETECTING
CIRCUIT
WATER
LEVEL
ELECTRODE
Manual - Rinnai Condensing Water Heaters
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Consumer Support
Warranty Information
The installer is responsible for your water heater’s correct installation.
Please complete the information below to keep for your records:
Purchased from: _________________________________________________________________
Address: _____________________________ Phone: _________________________________
_____________________________
Date of Purchase: __________________________________
Model No.: ________________________________________
Serial No.: ________________________________________
Installed by: ___________________________ Installer’s License No.: _____________________
Address: _____________________________ Phone: _________________________________
Date of Installation: __________________________________
Limited Warranty
What is covered?
This Warranty covers any defects in materials or workmanship when the product is installed and operated according to Rinnai
written installation instructions, subject to the terms within this Limited Warranty document. This Warranty applies only to
products that are installed correctly. Improper installation may void this Warranty. Rinnai strongly suggests that you use a
state qualified or licensed installer who has attended a Rinnai product knowledge class before installing this water heater. This
Warranty extends to the original purchaser and subsequent owners, but only while the product remains at the site of the
original installation. This Warranty only extends through the first installation of the product and terminates if the product is
moved or reinstalled at a new location.
How long does coverage last?
RC Series Period of Coverage (from date of purchase)
Item
Used with Rinnai Air Handler
for domestic heating and water
Commercial Applications
including radiant heating
Residential Applications
Heat Exchanger
All Other Parts and Components
Reasonable Labor
12 years *
5 years *
10 years * †
5 years * †
1 year
5 years *
5 years *
* Note: Period of coverage is reduced to 3 years from date of purchase when used as a circulating water heater within a hot
water circulation loop, where the water heater is in series with a circulation system and all circulating water flows
through the water heater, and where an on-demand recirculation system is not incorporated.
On-demand recirculation is defined as a hot water recirculating loop or system that utilizes existing hot and cold lines
or a dedicated return line, and only activates when hot water is used. It can be activated by a push button, motion
sensor, or voice activation but not by a temperature sensor. A timer added to a standard recirculating pump is not
considered as on-demand.
There is no warranty coverage on product installed in a closed loop application, commonly associated with space
heating only applications.
Use of an MCC-91 controller in a residential dwelling will reduce the warranty coverage to that of a commercial
warranty application (except when an MCC-91 is used with a Rinnai Hydronic Air Handler).
The integrated controller on indoor models has a 1 year warranty on parts.
† Note: Period of coverage is reduced to 3 years from date of purchase if the Rinnai water heater temperature setting
exceeds 160º F (71º C).
40
Manual - Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Limited Warranty Continued
What will Rinnai do?
Rinnai will repair or replace the covered product or any part or component that is defective in materials or workmanship as set
forth. Rinnai will pay reasonable labor charges associated with the repair or replacement of any such part or component. All
repair parts must be genuine Rinnai parts. All repairs or replacements must be performed by an individual or servicing
company that is properly trained, state qualified or licensed to do the type of repair.
Replacement of the product may be authorized by Rinnai only. Rinnai does not authorize any person or company to assume
for it any obligation or liability in connection with the replacement of the product. If Rinnai determines that repair of a product is
not possible, Rinnai will replace the product with a comparable product at Rinnai’s discretion. If a component or product
returned to Rinnai is found to be free of defects in material or workmanship, or damaged by improper installation or damaged
during return shipping, the warranty claim for product, parts and labor may be denied.
How do I get service?
You must contact a state qualified/licensed contractor or authorized service provider for the repair of a product under this
Warranty. For the name of a qualified/authorized service provider please contact your place of purchase, visit the Rinnai
30269.
Proof of purchase is required to obtain warranty service. You may show proof of purchase with a dated sales receipt, or by
registering within 30 days of purchasing the product. To register your tankless water heater, please visit
www.rinnairegistration.com. For those without internet access, please call 1-866-RINNAI1 (746-6241). Receipt of Registration
by Rinnai will constitute proof-of-purchase for this product. However, Registration is not necessary in order to validate this
Warranty.
What is not covered?
This Warranty does not cover any failures or operating difficulties due to the following:
•
•
•
•
•
accident, abuse, or misuse
alteration
misapplication
force majeure
improper installation (such as but not limited to inadequate water quality, condensate damage, improper venting, incorrect
gas type, incorrect gas or water pressure, or absence of a drain pan under the appliance)
•
•
•
•
improper maintenance (such as but not limited to scale build-up, freeze damage, or vent blockage)
incorrect sizing
component damage resulting from chemical fumes
any other causes other than defects in materials or workmanship
This Warranty does not apply to any product whose serial number or manufacture date has been defaced. This Warranty does
not cover any product used in an application that uses chemically treated water such as a pool or spa heater. This appliance is
suitable for filling large or whirlpool bath tubs with potable water. Refer to the Water Quality Section in the Operation and
Installation Manual.
Limitation on warranties
No one is authorized to make any other warranties on behalf of Rinnai America Corporation. Except as expressly provided
herein, there are no other warranties, expressed or implied, including, but not limited to warranties of merchantability or fitness
for a particular purpose, which extend beyond the description of the warranty herein and further Rinnai shall not be liable for
indirect, incidental, special, consequential or other similar damages that may arise, including lost profits, damage to person or
property, loss of use, inconvenience, or liability arising from improper installation, service or use. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you.
Any implied warranties of merchantability and fitness arising under state law are limited in duration to the period of coverage
provided by this limited Warranty, unless the period provided by state law is less. Some states do not allow limitations on how
long an implied Warranty lasts, so the above limitation may not apply to you.
This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Manual - Rinnai Condensing Water Heaters
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Instructions d'utilisation
Chauffe-eau d’intérieur sans
réservoir à ventilation directe
Comportements et pratiques de sécurité ...........42
Réglage de température ................................... 43
Plages de température avec un contrôleur
de température...................................................44
Options de température sans
Manuel d'installation et d'utilisation
contrôleur à distance..........................................44
Entretien.............................................................45
Instructions d’installation
Instructions générales........................................46
Écartements par rapport à l'appareil..................47
Fixation du chauffe-eau .....................................47
Installation à altitude élevée...............................48
Tuyauterie de gaz ..............................................48
Tuyauterie d'eau ................................................49
Qualité de l'eau ..................................................49
Tuyauterie recommandée pour
installation de base.............................................50
Instructions de ventilation
Enregistrer votre produit à
ou l'appel 1-866-RINNAI1 (746-6241)
Consignes pour aspiration/évacuation .......51
Condensat ..................................................51
Longueur de ventilation maximum...............52
Produits de ventilation .................................53
Espacement pour terminaison de cheminée .....54
Installation de conduit de cheminée ..................55
Instructions d'utilisation......................................56
Diagramme en escalier.......................................57
Support à la clientele ......................................58, 59
Pour une traduction complète du manuel en français,
vous pouvez le télécharger du site Web de
42
Manuel – Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Instructions d'utilisation
Comportements et pratiques de sécurité
Réglage de température
Chaud
Brûlure
1. Si le chauffe-eau est éteint, appuyez
sur le bouton ON/OFF pour activer.
2. Appuyez sur le “ priorité bouton ” du
contrôleur de température. La
lumière verte de priorité s'allume en
indiquant que ce contrôleur est
contrôlant la température et la Rinnai
de l'eau poêle est prête à fournir de
l'eau chaude. La priorité peut être
modifiée pendant l'exécution sans
eau chaude.
3. Appuyez sur les boutons ▲ ou ▼
pour obtenir le réglage de
température désirée.
Toutes les sources d'eau chaude
sont capables de fournir de l'eau à
cette température définition jusqu'à
ce qu'il est modifié à nouveau au
contrôleur de température ce ou un
autre.
Manuel – Rinnai Condensing Water Heaters
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Plages de température avec un contrôleur de température
Ce chauffe-eau va tenter de fournir de l'eau chaude à température stable malgré les variations de débit ou quand plus d'un
robinet est ouvert. La chauffe-eau ne peut délivrer de l'eau qu'à une seule température de consigne à la fois. Les températures
de consigne disponibles pour un modèle donné sont fournies ci-dessous :
Model
Plages de température disponible (ºF)
125 130 135 140 150 160 185
RC80HPi
RC80HPe
RC98HPi
RC98HPe
98 100 102 104 106 108 110 115 120
*
*
*
*
**
**
**
Temp in Celsius ºC 37 38 39 40 41 42 43 46 49 52 54 57 60 66 71 85
* Remettre à l'état initial la Température Maximum Si le nom modèle sur le côté des
fins de chauffe-eau avec « -UC » (ex. « REU-VA2535FFUD-UC »), alors ces unités
ont une température maximum implicite de 120º F (49º le C) et une option pour
augmenter la température maximum à 140 ºF (60 ºle C). Les cadres de température
de 125-140 ºF (52-60 ºle C) sont disponible en réglant le commutateur de baisse 6 à
SUR dans le SW1 banque de 8 commutateurs de baisse. Les unités avec les noms
modèles terminant dans « -US » a une température maximum implicite de 140 ºF
(60 ºle C).
Température Maximum
120º F (49º C) 140 ºF (60 ºC)
cotateur comeur
N° de micro- N° demicro-
m
mu
m
u
tat
ON
ON
O
F
F
O
F
F
1
1
2
3
4
5
6
7
8
2
3
4
5
6
7
8
** MCC-91 Contrôleur de Température Ces cadres exigent le MCC-91 contrôleur. Quand
le MCC-91 contrôleur est connecté, ces plus hautes températures sont disponibles sur
tous modèles de contrôleur dans le système. L'usage d'un MCC-91 contrôleur dans une
demeure résidentielle réduira la couverture de garantie à cela d'une application de
garantie commerciale.
Le MCC-91 contrôleur est l'intention eu pour les applications de publicité et hydronic
seulement. Si un MCC-91 contrôleur est utilisé dans une demeure résidentielle pour
une application de hydronics, une soupape mélangeant doit être aussi installée pour
limiter la température d'eau chaude potable à une température sûre. Arroser des
températures plus de 125º F (51º le C) peut causer des brûlures ou scalding sévère.
Se référer à l'Alerte de Danger sur les températures d'eau. Rinnai ne fait pas, en tout
cas, être responsable des dommages qui résultent de tel usage impropre ou tel
mauvais usage.
Une température inférieure à 98º F (37 ºC) peut s'obtenir par
ajout d'eau froide avec un robinet mitigeur.
Les températures suggérées sont de :
•
•
•
Cuisine
Douche
Baignoire
120º F (49º C)
98º - 110º F (37º - 43º C)
102º - 110º F (39º - 43º C)
Pour passer l'affichage de température de Celsius à
Fahrenheit ou vice versa, actionnez et maintenez enfoncé le
bouton M/A pendant 5 secondes avec le chauffe-eau en
position d'arrêt.
Ces températures ne sont que des suggestions.
Options de température sans contrôleur à distance
Le réglage de température de consigne par défaut pour cet appareil sans un contrôleur à distance est de 120º F (49 ºC). On
peut, si on le souhaite, la passer sur 140º F (60 ºC) en modifiant la position d'un seul micro-commutateur DIP.
À la banque SW1 de 8 interrupteurs à positions multiples, le micro-commutateur 5 donne un réglage à 120°F (49 ºC) s'il est
sur OFF (valeur automatique) mais à 140°F (60 ºC) s'il est sur ON.
Si un contrôleur de température est installé, alors le contact DIP 5 n'a aucun effet sur des arrangements de température.
44
Manuel – Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Entretien
Accumulation de neige
Maintenez la zone autour de la terminaison de cheminée
libre de toute neige et glace. Cet appareil ne peut pas bien
fonctionner si ses bouches d'aspiration et d'évacuation d'air
sont entravées (blocage total ou même partiel) par des
obstacles quelconques.
Les réparations ne doivent être effectuées que par un
technicien de service qualifié. Cet appareil doit être inspecté
annuellement par un technicien de service qualifié. Vérifiez
le bon fonctionnement après chaque intervention.
Inspection visuelle de flamme
Le brûleur doit être allumé de façon régulière sur toute sa
surface quand il fonctionne correctement. La flamme doit
être claire, bleutée et stable. Reportez-vous à la
décomposition par pièces du brûleur pour l'emplacement
des hublots d'inspection.
Nettoyage
Il est impératif de contrôler compartiments, brûleurs et
passages pour la circulation de l'air sur l'appareil à nettoyer.
La configuration de flamme est illustrée ci-dessous :
Procédez au nettoyage comme ceci :
1. Coupez et débranchez l'alimentation électrique. Laissez
refroidir le chauffe-eau.
CORRECT
2. Démontez et nettoyez le filtre d'arrivée d'eau.
VUE DE FACE
3. Démontez le panneau frontal en enlevant ses 4 vis.
FLAMME
BLEUE
4. Utilisez de l'air comprimé pour dépoussiérer brûleur
principal, échangeur thermique et pales de ventilateur.
N'utilisez pas de chiffon mouillé ou de nettoyants à
pulvériser sur le brûleur. N'utilisez pas de substances
volatiles comme benzène ou diluants. Ils pourraient
s'enflammer ou décolorer la peinture.
ÉLECTRODE DE
DÉTECTION
5. Utilisez un chiffon doux sec pour essuyer le boîtier.
Système de ventilation
INCORRECT
Les conduites de prise d'air et d'évacuation doivent être
inspectées au moins tous les ans pour y détecter des
blocages ou dommages éventuels.
VUE DE FACE
Moteurs
FLAMME JAUNE
Les moteurs sont lubrifiés à vie et ne demandent pas de
lubrification périodique. Maintenez ventilateur et moteur
sans poussière ou saleté en les nettoyant tous les ans.
ÉLECTRODE DE
DÉTECTION
Contrôleur à distance
Utilisez un chiffon humide pour nettoyer les contrôleurs à
distance. N'employez pas de solvants.
Accumulation de calcaire et de tartre
Si vous recevez le code d'erreur « LC », reportez-vous à la
procédure de rinçage de l'échangeur thermique. Voyez
aussi la section sur la qualité de l'eau pour savoir si votre
eau a besoin d'un traitement ou conditionnement en amont.
(Lors de la vérification de l'historique des anomalies pour
l'entretien, le code « 00 » aura remplacé « LC ».)
Manuel – Rinnai Condensing Water Heaters
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation Instructions
Seuls des installateurs qualifiés avec une formation
adéquate peuvent installer cet appareil. La garantie
peut être annulée suite à une installation incorrecte
ou réalisée par un installateur non qualifié.
Rinnai recommande fortement que les installateurs
suivent une classe pour la connaissance des
produits. Pour vous informer sur les cours de
formation de Rinnai, appelez :
1-800-621-9419.
Instructions générales
• L'appareil doit être isolé du système de conduite
d'alimentation en gaz en fermant sa vanne individuelle de
coupure durant les essais du système en pression
inférieurs ou égaux à 1/2 psi (3.5 kPa ou 13,84 pouces de
hauteur de colonne d'eau).
N'utilisez pas de matériaux de substitution.
N'utilisez sur cet appareil que des pièces certifiées
• Suivez les instructions d'installation et les conseils de
soins et entretien pour avoir de l'air de combustion et de
ventilation de façon adéquate.
• Cet appareil doit être installé par un sous-traitant qualifié
ou agréé. Il est de la responsabilité de la personne devant
faire installer un chauffe-eau de s'assurer que ce sous-
traitant installateur possède les autorisations et permis
adéquats pour installer des chauffe-eau dans votre
région. Rinnai recommande fortement que les
• L'appareil doit être placé à un endroit où des fuites d'eau
venant de l'unité ou des raccordements n'entraîneront pas
de dommages dans les environs immédiats de l'appareil
ou aux étages inférieurs de la structure. Si un endroit
idéal n'est pas disponible, il est recommandé d'installer un
bac de récupération bien drainé sous l'appareil. Ce bac
ne doit pas freiner le flux de l'air de combustion.
installateurs suivent une classe de connaissance de ses
appareils pour assurer la satisfaction du client et la
couverture par la garantie. Le non respect de
• Le flux d'air de combustion et de ventilation ne doit pas
réglementations d'état ou de province relatifs à
l'installation de chauffe-eau peut annuler la garantie.
être obstrué.
• Cet appareil ne convient pas pour une utilisation dans une
application comme le chauffage d'eau de piscine ou de
spa utilisant de l'eau chimiquement traitée (cet appareil
peut par contre remplir de grandes baignoires ou bains à
tourbillon avec de l'eau potable chaude).
• Le RC80HPi (REU-KA2530FFUD-US) et RC98HPi (REU-
KA3237FFUD-US) ne doivent pas être installé à
l'extérieur.
• Le RC80HPe (REU-KA2530WD-US) et RC98HPe (REU-
KA3237WD-US) ne doivent pas être installé à l'intérieur.
• Si un chauffe-eau est installé dans un système fermé
d'alimentation en eau, ayant par exemple un dispositif anti
-refoulement dans la conduite d'alimentation en eau
froide, il faut fournir les moyens de contrôler l'expansion
thermique. Contactez le fournisseur d'eau ou un
inspecteur en plomberie local sur la façon de gérer cette
situation.
• C'est un installateur ou un technicien de service qualifié
qui doit installer, inspecter et vérifier l'absence de fuites
de cet appareil avant sa mise en service.
• L'installation doit être en conformité avec les normes
locales, et en leur absence avec la norme américaine sur
le gaz combustible, ANSI Z223.1/NFPA 54, ou la norme
canadienne sur les installations au gaz naturel et
propane, CSA B149.1.
• En cas de surchauffe, ou si la coupure du gaz ne se fait
pas, fermez l'arrivée de gaz au niveau de la vanne de
contrôle manuelle alimentant l'appareil.
• L'appareil, quand il est installé, doit être électriquement
relié à la terre en conformité avec la norme américaine
électrique, ANSI/NFPA 70, ou la norme canadienne
électrique, CSA C22.1.
• Gardez la zone d'aspiration d'air exempte de produits
chimiques comme chlore ou agent de blanchiment qui
produisent des fumées. Ces fumées pourraient
endommager des composants et réduire la durée de
service de votre appareil.
• L'appareil et sa vanne de gaz doivent être débranchés de
la conduite d'alimentation en gaz durant les essais du
système en pression dépassant 1/2 psi (3.5 kPa ou 13,84
pouces de hauteur de colonne d'eau).
46
Manuel – Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Écartements par rapport à l'appareil
RC80HPi, RC98HPi
RC80HPe, RC98HPe
Jusqu'à Jusqu'à
matières matières
combus- combus-
Jusqu'à Jusqu'à
matières matières
combus- combus-
Vers le haut
tibles
tibles
tibles
tibles
Dessus du
chauffe-eau
12 inches
(305 mm)
2 inches
(51 mm)
Dessus du
chauffe-eau (305 mm)
12 inches
2 inches
(51 mm)
Arrière du
chauffe-eau
0 (zero)
0 (zero)
Arrière du
0 (zero)
0 (zero)
chauffe-eau
Sur le côté
Avant du
chauffe-eau
6 inches
(152 mm)
6 inches
(152 mm)
Le devant
24 inches
(le Pan-
(610 mm)
neau)
0 inches
(0 mm)
Côtés du
chauffe-eau
2 inches
(51 mm)
1/2 inch
(13 mm)
Le devant
(l'Echappem
ent)
24 inches 24 inches
(610 mm) (610 mm)
Par rapport
au plancher/
sol
12 inches
(305 mm)
2 inches
(51 mm)
to front
Vers l'avant
Vers le sol
Côtés du
6 inches
1/8 inch
(3.2 mm)
Ventilation
chauffe-eau (152 mm)
4 inches * 0 (zero)
Par rapport
12 inches
au plancher/
(305 mm)
sol
2 inches
(51 mm)
* 4 pouces (102 mm) pour zone confinée ; 1 pouce (26 mm) pour zone ouverte.
** 0 pouces des composants de ventilation et de la canalisation de vidange condensat.
L'espacement pour des interventions doit faire 24 pouces (61 cm) sur l'avant du chauffe-eau.
Pour installation en placard : espacement de 6 pouces (152 mm) à l'avant.
Fixation du chauffe-eau
1. Identifiez l'emplacement d'installation et confirmez que
là les espacements requis seront respectés.
2. Fixez bien le chauffe-eau au mur en utilisant n'importe
lesquels des trous des supports d'installation murale
placés en haut et en bas du chauffe-eau. Assurez-vous
que la résistance des fixations est suffisante pour
supporter le poids de l'appareil. Reportez-vous au
poids des modèles de chauffe-eau dans la section des
spécifications.
Supports
d'installation
murale
Manuel – Rinnai Condensing Water Heaters
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Installations à haute altitude
Disposez les micro-commutateurs N° 2 et N° 3 sur les
positions montrées dans le tableau qui suit en fonction
de votre altitude d'installation.
Micro-commutateur
0-2000 ft
(0-610 m)
2001-5200 ft
(610-1585 m)
5201-7700 ft
(1585-2347 m)
7701-10200 ft
(2347-3109 m)
N° 2
N° 3
OFF
OFF
OFF
ON
ON
ON
ON
OFF
N° de micro-
N° de micro-
N° de micro-
N° de micro-
commutateur
commutateur
commutateur
commutateur
ON
ON
ON
ON
O
F
F
O
F
F
O
F
F
O
F
F
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Tuyauterie de gaz
Instructions générales
pour détection de fuites de gaz, incluant l'eau
• Une vanne manuelle de coupure de gaz doit être placée
sur la conduite d'alimentation en gaz en amont du chauffe
-eau Rinnai. Un raccord union peut être utilisé sur la
connexion au-dessus de la vanne de coupure pour
pouvoir ultérieurement intervenir sur l'unité en la
déconnectant.
savonneuse, peuvent causer corrosion ou fissuration par
contrainte, la tuyauterie doit être rincée avec de l'eau
après le test, sauf si vous avez pu déterminer que la
solution de détection utilisée n'était pas corrosive).
• Utilisez toujours des connecteurs approuvés pour
raccorder l'unité sur la conduite de gaz. Purgez toujours la
conduite de gaz de tous débris éventuels avant son
branchement sur le chauffe-eau;
• Vérifiez le type de gaz d'arrivée et sa pression avant de
raccorder le chauffe-eau Rinnai. Si l'appareil a besoin
d'un gaz qui n'est pas celui disponible localement, NE
branchez PAS le chauffe-eau Rinnai. Contactez votre
revendeur pour obtenir le bon modèle correspondant à
votre type de gaz.
• La conduite d'alimentation en gaz doit être étanche au
gaz, du bon calibre et installée d'une façon permettant de
fournir assez de gaz pour satisfaire la demande maximale
du chauffe-eau et de tous les autres appareils
fonctionnant au gaz du lieu sans qu'il y ait de chute de
pression.
• Vérifiez la pression du gaz d'alimentation immédiatement
en amont à l'arrivée de la régie fournissant le gaz. La
pression d'arrivée du gaz doit être dans la fourchette de
limites montrée dans la section de spécifications.
• Tout composé utilisé sur la jonction filetée du tuyau de
gaz doit être d'un type qui résiste à l'action du gaz
propane ou naturel.
• Avant de mettre l'appareil en service, tous les joints, y
compris sur le chauffe-eau, doivent avoir leur étanchéité
vérifiée, au moyen d'une solution de détection de fuites à
l'eau savonneuse, ou une solution ininflammable
• Reportez-vous à un tableau de calibrage approuvé de
tuyauterie de gaz si vous avez un doute sur la taille de
votre conduite.
équivalente éventuellement (comme certaines solutions
48
Manuel – Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Tuyauterie d'eau
Instructions générales
• Une vanne manuelle de coupure d'eau doit intercalée sur
la conduite en amont sur l'arrivée d'eau au chauffe-eau
Rinnai. Des raccords union peuvent s'utiliser sur les
conduites d'eau froide et d'eau chaude pour faciliter les
interventions ultérieures avec déconnexion de l'unité.
• Des produits chimiques toxiques, comme ceux utilisés
pour le traitement d'eau de chaudière, ne doivent pas être
utilisés dans l'eau potable utilisée pour le chauffage des
locaux.
• Si l'appareil doit être utilisé comme source d'eau potable,
il ne doit pas être connecté à un appareil utilisé
auparavant comme chauffage et fourniture d’eau non
potable.
• La tuyauterie (incluant les matériaux de soudage) et les
composants connectés à cet appareil doivent être approuvés
pour une utilisation sur des systèmes à eau potable.
• Purgez la conduite d'eau pour en éliminer les débris et
l'air. Des débris entrant dans le chauffe-eau Rinnai
pourraient l'endommager.
• Le filtre d’eau du chauffage Rinnai dout être propre et
installé.
Soupape de sûreté
• Une soupape de sûreté est nécessaire, d'un type
approuvé par les normes américaines (ANSI Z21.10.3) et
canadiennes (CSA 4.3) pour tous les systèmes de
chauffage par eau.
• La soupape de sûreté doit être actionnée manuellement
au moins une fois par an pour vérifier qu'elle est toujours
fonctionnelle.
• La soupape de sûreté doit être insérée dans la conduite
de sortie d'eau chaude en suivant les instructions du
fabricant. N'intercalez PAS n'importe quel autre type de
vanne ou dispositif de coupure entre la soupape de sûreté
et le chauffe-eau.
• La soupape de sûreté doit être compatible avec les
normes ANSI Z21.22 (soupapes de sûreté et dispositifs
de coupure automatique de gaz pour systèmes de
fourniture d'eau chaude) et/ou CAN1-4.4 (soupapes de
sûreté combinées à pression et à température et
soupapes casse-vide).
• Ne bouchez pas la soupape de sûreté, et n'installez
aucun raccord réducteur ou autre restriction dans la
conduite de déversement. Elle doit permettre un drainage
complet de la soupape et de la conduite.
• La soupape de sûreté doit être homologuée pour 150 PSI
(1034 kPa) et au moins la valeur maximum de BTU/H de
l'appareil.
• Si une soupape de sûreté déverse périodiquement, cela
peut venir d'une expansion thermique dans un système
d'eau fermé. Contactez votre fournisseur d'eau ou votre
inspecteur de plomberie local pour voir comment régler
cette situation. Mais ne bouchez pas la soupape.
• Le déversement venant de la soupape de sûreté doit être
amené par tuyau au sol ou dans un système de drainage
pour éviter une exposition avec possibilité de brûlure pour
humains, végétaux ou animaux. Conformez-vous aux
normes locales. L'eau chaude sortant de la soupape de
sûreté peut causer des brûlures sévères et des
• Ni Rinnai ni la norme nationale américaine (ANSI
Z21.10.3) ou canadienne (CSA 4.3) n'exigent d'utiliser
une soupape de sûreté combinée à pression et à
température pour cet appareil. Cependant des normes
locales peuvent le demander.
échaudages pouvant même provoquer la mort.
Qualité de l'eau
Parmi les soins à apporter à votre chauffe-eau il y a
l'évaluation de la qualité de l'eau consommée. Si les
paramètres de votre eau dépassent les limites fournies dans
ce tableau, il vous faudra traiter ou conditionner cette eau.
Niveau maximum
Dureté totale
Aluminium*
Chlorures*
Cuivre*
Jusqu'à 200 mg/L
Jusqu'à 0,2 mg/L
Jusqu'à 250 mg/L
Jusqu'à 1,0 mg/L
Jusqu'à 0,3 mg/L
Jusqu'à 0,05 mg/L
6,5 à 8,5
* Source : Part 143 National Secondary Drinking Water
Regulations (normes américaines sur les réseaux
d'alimentation secondaires en eau potable)
Fer*
Manganèse*
pH *
Matières dissoutes
totales (MDT)*
Jusqu'à 500 mg/L
Zinc *
Jusqu'à 5 mg/L
Manuel – Rinnai Condensing Water Heaters
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Tuyauterie recommandée pour installation de base
Liste d'équipement
Rinnai
Qté
1
Chauffe-eau Rinnai
Kit RIK (optionnel)
1
(raccords 3/4 po (19 mm)
comprenant :
2 unions, 2 vannes à boisseau
sphérique, 2 électrovannes de
drainage, 1 soupape de sûreté)
Connexion de gaz en 3/4 po
(19 mm)
e
Canalisation condensat
e
Vidange condensat
Alimentation en gaz
Conduite de sortie d'eau chaude en 3/4 po
(19 mm)
Conduite d'alimentation en eau froide en 3/4 po (19 mm)
Appareils du bâtiment
Légende
Ceci n'est pas un schéma technique, son but n'est que de vous guider, et il ne tient
pas lieu de dessin industriel professionnel pour un projet. Ce schéma n'a pas l'ambi-
tion de décrire un système au complet. C'est la responsabilité du concepteur ou de
Vanne à tournant sphérique
Régulateur de pression
l'ingénieur de déterminer les composants nécessaires et la configuration pour le
3/4 po (19 mm)
système spécifique à installer. Ce schéma n'implique aucune conformité avec les
Pompe de circulation
exigences des normes de construction locales. C'est la responsabilité du concepteur
ou de l'ingénieur de s'assurer que l'installation sera en conformité avec toutes les
Raccord union 3/4 po (19 mm)
Vanne de purge de
chaudière
normes locales de construction applicables. Consultez les autorités compétentes dans
Clapet anti-retour
ce domaine avant l'installation.
S
Soupape de décharge
Électrovanne
50
Manuel – Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Instructions de ventilation
Consignes pour aspiration/évacuation
Référez-vous aux instructions spécifiques sur votre produit de ventilation pour les exigences supplémentaires
•
Ce chauffe-eau est un modèle à ventilation directe, et de
ce fait est certifié et listé avec son système de
ventilation. Vous devez utiliser des composants de
ventilation qui sont certifiés et listés avec le modèle de
chauffe-eau. Ne combinez pas de composants de
ventilation venant de constructeurs différents.
•
•
Ne partagez pas la ventilation avec le tuyau de
ventilation de tout autre chauffe-eau ou appareillage.
Les connexions de ventilation doivent être fermement
pressées ensemble de façon à ce que leurs jonctions
forment une bonne étanchéité à l'air.
•
•
Reportez-vous aux instructions du constructeur de la
ventilation pour les instructions d'assemblage des
différents éléments.
•
•
Le système doit ventiler directement vers l'extérieur du
bâtiment et utiliser de l'air extérieur pour la combustion.
Évitez les abaissements et fléchissements sur les
tronçons de ventilation horizontaux en installant des
supports en suivant les installations du fabricant de la
ventilation.
Si le circuit de mise à l'air libre doit être enfermé, on le
suggère que la conception de la clôture permette
l'inspection du circuit de mise à l'air libre. La conception
d'une telle clôture sera considérée acceptable par
l'installateur ou l'inspecteur local.
•
Supportez les tronçons de ventilation horizontaux tous
les 4' (1,2 m) et les tronçons verticaux tous les 6' (1,8
m), ou en conformité avec les normes locales.
•
•
•
La ventilation doit être aussi directe que possible avec
un minimum de raccords de tuyauterie.
Le diamètre de ventilation ne doit pas comporter de
réductions.
Ne connectez pas le système de ventilation sur une
ventilation ou une cheminée existante.
Condensat
Le Rinnai RC80HPi et le RC98HPi condensant le
chauffe-eau tankless est usine équipée d'une
canalisation condensat de piège et de vidange.
• Employez seulement le passage qui est approuvé
et identifié comme acceptable pour les appareils de
condensation.
• N'employez pas l'aluminium, le PVC, le CPVC,
l'ABS ou le matériel galvanisé pour exhaler cet
appareil.
• Inclinent n'importe quelle mise à l'air libre
horizontale 1/4 pouce par pied (19 millimètres/m),
vers le réchauffeur. Débarassez-vous du condensat
par codes locaux.
• La conduite des cerveaux (le long de sa longueur
entière) doit être au moins le diamètre de même
que la ligne des cerveaux, (1/2 pouce NPT).
• La conduite des cerveaux devrait être aussi brève
• Tout le condensat doit s'écouler et se débarasser
que possible et avoir un terrain à la baisse.
par codes locaux.
• La fin de la conduite des cerveaux doit être ouverte
à l'atmosphère. La fin ne devrait pas être sous
l'eau ou d'autres substances.
• Si le drain condensat obtient bloqué, un code
d'erreur montrera sur le contrôleur. Si ceci se
produit, le drain condensat doit être nettoyé.
• Ne connectez pas la conduite des cerveaux
• Le piège de condensats sera automatiquement
prime (self-prime) lors d'opération de l'unité comme
formes de condensats. Condensat de purge de
l'unité indique que le piège est complète et qu'il
n'existe aucun blocage dans le drain de
directement à l'égout de pluie.
• Ne connectez pas la ligne des cerveaux condensat
avec une climatisation évaporateur bobine des
cerveaux.
condensats. Il n'est pas nécessaire ajouter l'eau
dans le piège de condensats.
• Pour minimiser les gel du condensat, exécuter la
ligne des cerveaux condensat grâce à un mur
intérieur ou entre l'isolation et un mur intérieur.
• Utiliser seul tube PVC ou CPVC pour la ligne des
cerveaux de condensats.
Manuel – Rinnai Condensing Water Heaters
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Longueur maximum de ventilation
1. Déterminez le nombre de coudes à 90° dans le système de ventilation (deux coudes à 45° comptent pour un coude à
90°).
2. Référez-vous au tableau pour trouver la longueur de ventilation maximum sur la base du nombre de coudes.
3. Suivez les recommandations de la note applicable.
Exemple : Si vous n'avez qu'un coude votre longueur de ventilation maximum est alors de 35 pieds (10,7 m). Si votre
longueur effective fait plus de 15 pieds (4,6 m) vous devez passer le microcommutateur DIP N° 1 (SW1) en
position OFF.
Nombre de coudes à 90°
0
1
2
3
4
5
6
41 ft 1
35 ft 2
29 ft 3
23 ft 4
17 ft 4
11 ft 4
5 ft 4
(12.5 m) (10.7 m)
(8.8 m)
(7.0 m)
(5.2 m)
(3.4 m)
(1.5 m)
1Si la longueur fait plus de 21' (6,4 m) passez le
Switch No.
ON
microcommutateur DIP N° 1 (SW1) en position OFF.
O
F
F
1
2
3
4
5
6
7
8
2Si la longueur fait plus de 15' (4,6 m) passez le
Notes 1234
microcommutateur DIP N° 1 (SW1) en position OFF.
3Si la longueur fait plus de 9' (2,7 m) passez le
microcommutateur DIP N° 1 (SW1) en position OFF.
4Passez le microcommutateur DIP N° 1 (SW1) en position
OFF.
52
Manuel – Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Produits de ventilation
Produits de ventilation listés et testés pour
RC80HPi ................. REU-KA2530FFUD
RC98HPi ................. REU-KA3237FFUD
Manufacturer
Product
Rolux Condensing Vent
Pièces
Rinnai/Ubbink
System
Référez-vous à la littérature technique du fabricant
pour les numéros de la pièce et les instructions
spécifiques.
Selkirk / Heat-Fab
Metal-Fab
Saf-T Vent SC system
Corr/Guard Vent/Air
Intake System
Contacts avec les constructeurs de ventilation pour des informations d'installation et de liste de pièces :
Rinnai/Ubbink
Heat-Fab
Metal-Fab Inc.
Téléphone : 800-621-9419
Téléphone : 800-772-0739
Téléphone : 800-835-2830
Fax :
678-829-1666
Fax :
413-863-4803
316-943-2351
Courriel :
Fax :
316-943-2717
Courriel :
Manuel – Rinnai Condensing Water Heaters
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Espacement pour terminaison de cheminée (ANS Z21.10.3 ï CSA 4.3)
DÉTAIL D'ANGLE
INTÉRIEUR
G
H
A
I
M
B
FIXED
PERMANENTE
D
FERMETURE
K
B
OUVRABLE
OPEABE
E
B
C
J
FERMETURE
B
PERMANENTE
B
A
ENTÉE D'ALIMENTATION
EN AIR
OUVRABLE
X
L
TERMINAISON DE
VENTILATION
V
F
B
ZONE OÙ LA TERMINAISON
N'EST PAS PERMISE
Description
Installations au Canada
Installations aux USA
Réf.
Espace au dessus de niveau du sol, véranda, porche, plate-forme
ou balcon
A
12" (30 cm)
12" (30 cm)
B
C
Écartement par rapport à fenêtre ou porte qui peut s'ouvrir
Écartement par rapport à fenêtre toujours fermée
36" (91 cm)
*
12" (30 cm)
*
Espacement vertical par rapport à combles ventilés, situés
au-dessus de la terminaison à une distance horizontale de
2 ' (61 cm) de la ligne centrale de terminaison
D
*
*
E
F
Espacement vertical par rapport à combles non ventilés
Écartement par rapport à un angle extérieur
Écartement par rapport à un angle intérieur
*
*
*
*
*
G
*
3 pieds (91 cm) avec une
Espacement par rapport à chaque côté d'une ligne centrale
prolongée au-dessus de l'ensemble de compteur/régulateur
hauteur de 15 pieds (4,5 m)
au-dessus de l'ensemble
de régulation
H
*
Écartement par rapport à la sortie de ventilation du régulateur
de service
I
36 " (91 cm)
36 " (91 cm)
6' (1,83 m)
*
Écartement par rapport à entrée d'alimentation d'air non
mécanique dans le bâtiment ou entrée d'air de combustion
vers tout autre appareil
J
K
12" (30 cm)
3' (91 cm) au dessus si à
10' (3 m) horizontalement
Écartement par rapport à entrée d'alimentation d'air mécanique
Espacement au dessus d' un trottoir ou passage pavé situé dans
le domaine public
L
7' (2,13 m) 1
*
*
M
Espacement sous véranda, porche, plate-forme ou balcon
12" (30 cm) ) 2
1
Une ventilation ne doit pas se terminer directement au-dessus d'un trottoir ou passage pavé situé entre deux habitations familiales et les desservant toutes
les deux.
2
*
Permis uniquement si véranda, porche, plate-forme ou balcon est entièrement ouvert au moins sur deux côtés en dessous du plancher.
Pour les espacements non spécifiés dans ANSI Z223.1/NFPA 54 ou CSA B149.1, il faut appliquer les valeurs conformes aux normes locales d'installation et
aux exigences du fournisseur de gaz..
L'espacement par rapport au mur opposé est de 24" (60 cm) pour Canada et USA.
54
Manuel – Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation de conduit de cheminée (RC80HPi, RC98HPi)
Inclinent n'importe quelle mise à l'air libre horizontale
1/4 pouce par pied (19 millimètres/m), vers le
réchauffeur. Débarassez-vous du condensat par
codes locaux.
Inclinent n'importe quelle
mise à l'air libre horizontale
1/4 pouce par pied (19
millimètres/m), vers le
réchauffeur. Débarassez-
vous du condensat par
codes locaux.
Vis de fixation
Fixez la pièce de ventilation connectée sur le chauffe-eau
avec une vis autotaraudeuse dans le trou situé au dessus
du collecteur de condensat.
Manuel – Rinnai Condensing Water Heaters
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Instructions d'utilisation
À LIRE AVANT LA MISE EN SERVICE POUR VOTRE SÉCURITÉ
Si vous ne suivez pas exactement ces instructions, il peut en
résulter un départ d'incendie ou une explosion, causant dégâts
A. Cet appareil ne comporte pas de veilleuse. Il est muni
d’un dispositif d’allumage qui allume automatiquement le
brûleur. Ne tentez pas d’allumer le brûleur
manuellement.
• Si vous ne pouvez rejoindre le fournisseur, appelez le
service des incendies.
C. Ne poussez ou tournez la manette d’admission du gaz
qu’à la main ; ne jamais utiliser d’outil. Si la manette
reste coincée, ne pas tenter de la réparer ; appelez un
technicien qualifié. Le fait de forcer la manette ou de la
réparer peut déclencher une explosion ou un incendie.
B. AVANT DE FAIRE FONCTIONNER, reniflez tout autour
de l’appareil pour déceler une odeur de gaz. Reniflez
près du plancher, car certains gaz sont plus lourds que
l’air et peuvent s’accumuler au niveau du sol.
D. N’utilisez pas cet appareil s’il a été plongé dans l’eau,
même partiellement. Faites inspecter l’appareil par un
technicien qualifié et remplacez toute partie du système
de contrôle et toute commande qui ont été plongés dans
l’eau.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur ; ne pas vous servir
des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du
fournisseur.
INSTRUCTIONS DE MISE EN MARCHE
1. ARRÊTEZ ! Lisez les instructions de sécurité sur la
portion supérieure (à gauche) de cette étiquette.
6. Attendre cinq (5) minutes pour laisser échapper tout le
gaz. Reniflez tout autour de l’appareil, y compris près du
plancher, pour déceler une odeur de gaz. Si vous sentez
une odeur de gaz, ARRÊTEZ ! Passez à l’étape B des
instructions de sécurité sur la portion supérieure (à
gauche) de cette étiquette. S’il n’y a pas d’odeur de gaz,
passez à l’étape suivante.
2.Réglez le thermostat sur la consigne la plus basse.
3.Coupez l'alimentation électrique de l'appareil en utilisant
son bouton M/A.
4.L'appareil est équipé d'un dispositif d'allumage qui allume
automatiquement le brûleur. N'essayez pas de l'allumer
manuellement.
7.Ouvrez l'arrivée de gaz en tournant la vanne manuelle de
gaz en sens antihoraire (position ON).
5.Repérez la vanne de gaz manuelle sur le côté du chauffe-
eau. Fermez-la en la tournant à fond dans le sens
horaire (position OFF).
8.Rétablissez l'alimentation électrique de l'appareil avec son
bouton M/A.
9.Passez le thermostat sur le réglage de consigne souhaité.
10.Ouvrez un robinet d'eau chaude du circuit. Si l'appareil ne
démarre pas, suivez les instructions ci-dessous relatives
à la coupure du gaz vers l'appareil et appelez un
technicien de service ou votre fournisseur de gaz.
Reportez-vous au manuel pour plus d'informations.
Vanne manuelle
FERMÉEOUVERTE
COMMENT COUPER L’ADMISSION DE GAZ DE L’APPAREIL
1.Coupez l'alimentation électrique de l'appareil en utilisant
3.Repérez la vanne de gaz manuelle sur le côté du chauffe-
eau. Fermez-la en la tournant à fond dans le sens
horaire (position OFF).
son bouton M/A.
2.Réglez le thermostat sur la consigne la plus basse.
56
Manuel – Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Diagramme en escalier
PHASE
NEUTRE
CONTACT DE
DÉTECTION DE GEL
FUSIBLE 7 A
ANTI-FOUDRE
ANTI-FOUDRE
TERRE
RELAIS 1
ALLUMAGE
ALIMENTATION
D'ÉNERGIE DE
COMMUTATION
12 V CC
40 V CC
170 V CC
12,6 V
5 V CC
DÉTECTEUR
D'ÉCOULEMENT
ÉLECTRO-
VANNE À
MODULATION
CIRCUIT
DÉTECTEUR
D'ÉCOULEMENT
CIRCUIT D'ALIMENTA-
TION D'ÉLECTRO-
VANNE À
DISPOSITIF DE CONTRÔLE
D'ÉCOULEMENT
MODULATION
CIRCUIT DISPOSITIF
DE CONTRÔLE
D'ÉCOULEMENT
VEBTILATEUR DE
COMBUSTION
CIRCUIT DE CONTRÔLE D'É-
COULEMENT DE DÉRIVATION
CIRCUIT DE
COMMANDE DE
VENTILATEUR
UNITÉ
CENTRALE
DE TRAITE-
MENT
DISPOSITIF DE CON-
TRÔLE DÉCOULEMENT
DE DÉRIVATION
VENTI-
LATEUR
CIRCUIT DE
RELAIS 1
COMMANDE
DE RELAIS
ÉLECTRODE DE
FLAMME 1
CIRCUIT DE
DÉTECTION DE
FLAMME
CIRCUIT DE
COMMANDE
D'ÉLECTRO-
VANNE
FUS THER.
ÉLECTRODE DE
FLAMME 2
INTER-
RUPTEUR DE
SURCHAUFFE
CIRCUIT DE
CONTRÔLEUR À
DISTANCE
THERMISTANCE DE
SORTIE D'EAU 1
CONTRÔLEUR À
DISTANCE
JUMEAU
THERMISTOR
THERMISTANCE DE
SORTIE D'EAU 2
THERMISTANCE D'É-
CHAGEUR THERMIQUE
CIRCUIT DE
THERMIS-
TANCE
NIVEAU D'EAU
DÉTECTANT LE
CIRCUIT
NIVEAU D'EAU
DÉTECTANT LE
CIRCUIT
THERMISTANCE DE
BRÛLEUR
MODÈLE D'INTÉRIEUR UNIQUEMENT
Manuel – Rinnai Condensing Water Heaters
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Support à la clientèle
Informations sur la garantie
L'installateur est responsable de l'installation correcte de votre chauffe-eau.
Veuillez fournir les informations demandées ci-dessous et les archiver :
Appareil acheté chez :: _________________________________________________________________
Adresse : _____________________________ Téléphone : _________________________________
_____________________________
Date de l'achat : __________________________________
Référence de modèle : ________________________________________
Numéro de série : ________________________________________
Installé par : ___________________________ N° d'immatriculation de l'installateur :
_____________________
Adresse : _____________________________ Téléphone : _________________________________
Garantie limitée
Qu'est-ce qui est couvert ?
Cette garantie couvre tous défauts dus aux matériaux et à la main d'œuvre quand le produit a été installé et utilisé en suivant
les instructions écrites d'installation de Rinnai, dans les termes décrits dans ce document de garantie limitée. Cette garantie
s'applique seulement aux produits qui sont installés correctement. Une installation incorrecte pourrait annuler cette garantie.
Rinnai vous recommande fortement d'employer un installateur qui aura suivi une classe Rinnai pour la connaissance des
produits avant d'installer le chauffe-eau. Cette garantie couvre l'acheteur d'origine uniquement tant que le produit reste sur le
site de son installation initiale. Cette garantie ne joue qu'après la toute première installation du produit et se termine s'il est
déplacé ou réinstallé à un autre emplacement.
Combien de temps dure la couverture ?
Période de couverture (à partir de la date d'achat) pour Séries RC
Avec traitement d'air
Rinnai pour chauffage et
eau domestiques
Applications
commerciales incluant
chauffage radiant
Élément
Applications
domestiques
Échangeur thermique
Autre pièces et composants
12 ans*
5 ans*
10 ans* †
5 ans* †
1 an
5 ans*
5 ans*
Main d'œuvre dans la limite du raisonnable
* Note : La période de couverture est réduite à 3 ans à partir de la date d'achat quand le chauffe-eau est utilisé comme chauffage
d'eau circulante dans une boucle de circulation d'eau chaude, où il est utilisé en série avec un système de circulation, et que
toute l'eau qui circule passe au travers de lui, et où un système de recirculation à la demande n'est pas incorporé.
Une recirculation à la demande est définie comme une boucle de recirculation d'eau chaude ou un système qui utilise des
conduites d'eau chaude et froide existantes, ou une conduite de retour dédiée, et qui ne s'active que lorsque de l'eau chaude
est utilisée. L'activation peut se faire par bouton poussoir, détecteur de mouvement ou activation vocale, mais pas par un
capteur de température. Une minuterie ajoutée sur une pompe de recirculation standard n'est pas considérée comme
donnant un système à la demande.
L'utilisation d'un contrôleur MCC-91 dans une habitation résidentielle réduira la couverture de garantie au niveau de la
garantie pour une application commerciale
† Note : La période de garantie est réduite à 3 ans à partir de la date d'achat si le réglage de température du chauffe-eau Rinnai
dépasse 160°F (71 °C).
58
Manuel – Rinnai Condensing Water Heaters
Download from Www.Somanuals.com. All Manuals Search And Download.
Garantie limitée
Que fait Rinnai pour exercer la garantie ?
Rinnai va réparer ou remplacer le produit, ou toute partie ou tout composant défectueux pour cause de matériaux ou de main
d'œuvre, dans les conditions définies plus loin. Rinnai remboursera des charges de main d'œuvre raisonnables associées
avec la réparation ou le remplacement de toute pièce ou tout composant. Toutes les pièces utilisées pour la réparation doivent
être des pièces Rinnai d'origine. Toutes les réparations et tous les remplacement doivent être effectués par un artisan ou du
personnel de société de service qui aura été convenablement formé et sera administrativement agréé pour effectuer ce type
de travail.
Le remplacement du produit complet ne peut être autorisé que par Rinnai. Rinnai n'autorise aucune personne ou entité à
assumer pour elle toute obligation ou responsabilité en relation avec le remplacement du produit. Si Rinnai détermine que la
réparation d'un produit n'est pas possible, Rinnai le remplacera par un produit comparable, à sa discrétion. Si un composant
ou un produit retourné à Rinnai est trouvé sans défaut du aux matériaux ou à la main d'œuvre, ou qu'il est déterminé qu'il a été
mal installé ou endommagé pendant l'expédition de retour, la réclamation au titre de la garantie pourra être rejetée.
Comment obtenir le service au titre de la garantie ?
Vous devez contacter un fournisseur de service qualifié/agréé pour la réparation d'un produit dans le cadre de cette garantie.
Pour trouver les coordonnées d'un tel fournisseur local, veuillez contacter votre point d'achat, ou allez sur le site Web de
Peachtree City, Georgia 30269, USA.
La preuve de votre achat est nécessaire pour bénéficier du service dans le cadre de la garantie. Vous pouvez montrer la
preuve de l'achat avec une facture ou un ticket de caisse datés, ou en vous enregistrant dans les 30 jours suivant l'achat du
d'enregistrement de l'appareil à Rinnai (adresse imprimée sur la carte). Pour thos sans l'accès à Internet, s'il vous plaît appeler
1-866-RINNAI1 (746-6241) La réception de cette carte d'enregistrement servira de preuve de l'achat du produit. Cependant la
démarche d'enregistrement n'est pas une obligation pour valider cette garantie.
Qu'est-ce qui n'est pas couvert ?
Cette garantie ne couvre pas routes pannes ou difficultés de fonctionnement découlant de :
•
•
•
•
•
accident, abus, mauvais usage
altération
application non prévue
cas de force majeure
installation incorrecte (comme sans y être limité mauvaise qualité de l'eau, dommages dus à la condensation, mauvaise
ventilation, type de gaz ou pression d'eau inadéquats, absence de bac de drainage sous l'appareil)
•
•
•
entretien inadéquat (comme sans y être limité accumulation de tartre, dommages dus au gel, blocage de ventilation)
mauvais dimensionnement de l’installation.
ou pour toutes autres causes autres que des défauts dans les matériaux et la main d'œuvre
Cette garantie ne s'applique pas pour tout produit sur lequel numéro de série ou date de fabrication auraient été effacés. Cette
garantie ne couvre pas tout produit utilisé dans une application qui gère de l'eau traitée chimiquement, comme le chauffage de
piscine ou de spa. Cette appareil reste utilisable pour remplir de baignoires de grande contenance avec de l'eau potable.
Reportez-vous à la section relative à la qualité de l'eau dans le manuel d'installation et d'utilisation.
Limitation sur les garanties
Personne n'est autorisé a offrir toute autre garantie au nom de Rinnai America Corporation. Sauf pour ce qui est expressément
communiqué ici, il n'y a aucune autre garantie, explicite ou implicite, y compris sans y être limité les garanties de valeur
marchande ou d'adéquation à une finalité particulière, qui s'étendrait au-delà de la description de garantie fournie ici. De plus
Rinnai n'est pas responsable de tous dommages spéciaux, accessoires, indirects ou consécutifs qui peuvent survenir, y
compris les dommages aux personnes et aux biens, la perte d'usage, les désagréments ou les conséquences de mauvaise
qualité d'installation,entretien ou utilisation. Certains états ne permettent pas l'exclusion ou la limitation des dommages
annexes ou consécutifs, de ce fait la limitation qui précède peut ne pas être applicable à votre cas.
Toutes garanties implicites de valeur marchande et d'adéquation à une finalité spécifique autorisées par la législation locale
seront de toutes façons limitées en durée à la période de couverture offerte par cette garantie limitée, sauf si la période légale
locale d'application est plus courte. Certains états ne permettent pas de limitations sur le temps que durent les garanties
implicites, de ce fait la limitation qui précède peut ne pas être applicable à votre cas.
Cette garantie vous donne des droits légaux spécifiques, et vous pouvez également avoir d'autres droits qui peuvent varier
d'un état à l'autre.
Manuel – Rinnai Condensing Water Heaters
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Rinnai America Corporation
103 International Drive
Peachtree City, GA 30269
TOLL FREE: 1-800-621-9419
FAX: 678-829-1666
Rinnai’s other fine products
Tankless Water Heaters
• Residential and Commercial Applications
• Continuous Hot Water
• Up to 9.8 GPM
• High Energy Efficiency
• Propane or Natural Gas
• Internal or External Installation
• Digital Temperature Control
• Small, Compact Design
Direct Vent Furnaces
• High Efficiency
• Cool-to-the-touch Cabinet
• Blower Included
• Vent Terminal A Included
• 556 and 1004 Models Available in Beige, White and Silver
• Gas Conversion Kit Included
Direct-Vent Fireplace, RHFE-750ETRA
• Up to 83% AFUE Energy Efficiency
• Zero-Clearance Installation
• Available in Four Options of Fronts
• Remotes and Fan Included
• Gas Conversion Kit Available
Hydronic Air Handler
•
•
•
•
•
Designed for Use with Rinnai Systems
Domestic Hot Water Priority
Optional Programmable Thermostat
Zero Clearance to Combustibles
Accommodates Standard Cased-Coils
or call 1-866-RINNAI1 (746-6241)
U290-665X01
Printed in Japan 09.06
© 2009 Rinnai America Corporation