AdvantagePlus
Sealed-Combustion Gas-Fired Commercial Water Heaters
Available in Sizes Ranging From 45 - 119 Gallon Models
ꢀ
100,000 BTU/Hr. thru 199,000 BTU/Hr.
Rheem-Ruud AdvantagePlusTM Gas Commercial Water Heaters are
specifically designed to provide customers with maximum savings on
operation, space and installation. Designed with the most advanced
technology available, these products optimize efficiency and operating
reliability.
Construction Features:
• 316L stainless steel tank
construction (requires no
anode rods).
• Temperature range from 70°F to
160°F (maximum temperature
setting of 180°F available on
HE45-160 and HE45-199
• No chimney required; direct
booster models only).
vent using plastic pipe.
• Zero clearance to all
• Thermal efficiency of 95%
dramatically reduces
operating costs.
combustible surfaces.
• Factory installed AGA/ASME
rated T&P relief valve.
• 85 equivalent feet of vent length.
• Booster installation kit provided
with HE45-160 and HE45-199
booster models.
• Low NO emissions. Meets
x
SCAQMD Rule 1146.2.
• High impact plastic jacket
eliminates dents.
• 2” of non-CFC, polyurethane
No Chimney Required
foam insulation.
Vents Up To 40 Feet
Using 3" Schedule 40
PVC, CPVC or ABS Pipe
• Less than 1/2 degree per
hour heat loss (R17).
Heat Exchanger/
• Corrosion resistant, high
efficiency 90/10 cupronickel
heat exchanger.
Combustion Chamber
100,000 BTU and
130,000 BTU Models
Are Certified To
Control Well and E.C.O.
Air Inlet Connector
Gas Valve
Combustion Blower
Gas Burner
Vent With 2"
• Self-diagnostic electronic
control with digital readout for
water temperature, set point
and differential.
Gas Inlet Nipple 1/2”
Hot Surface Ignitor
Flame Probe
Schedule 40 PVC,
CPVC or ABS Pipe
Exhaust Outlet Connector
Control Board
Vent Over-Temp
Reset Switch
• Removable front cover allows
easy access to equipment
(24" service clearance
recommended).
Exhaust Elbow and Drain
Pressure Switch
Transformer
®
Condensate Connector
Hose
Condensate Connector
Certifications and Ratings:
The water heaters are UL/ULC listed and exceed the minimum efficiency
requirements of ASHRAE/IES 90.1b-2001. All water heaters are supplied
with an AGA/ASME rated temperature and pressure relief valve. The control
panel is an integrated solid state temperature and ignition control device
with integral diagnostics, LED fault display capability and a digital display of
temperature settings. All models are North Carolina Code compliant.
CERTIFIED FOR A 150 PSI MAXIMUM WORKING PRESSURE.
Continued next page.
Download from Www.Somanuals.com. All Manuals Search And Download.
AdvantagePlus Gas continued.
DIMENSIONAL INFORMATION
B
HOT OUT
T&P
72°
54°
39°
60°
CONTROL
GAS INLET
5.0"
A
TOP VIEW SHOWN
WITHOUT CABINET
AND IS THE SAME
D
FOR ALL TANKS SHOWN
ELECTRICAL
CONNECTION
INTAKE
F
G
EXHAUST
3.0"
COLD IN
H
3.75”
E
CONDENSATE
CONNECTION
C
VENTING OPTIONS
*
(SP12161)
*
SIDE VENTING W/ CONCENTRIC VENT KIT
SIDE VIEW
VERTICAL ROOF VENTING W/ CONCENTRIC VENT KIT
FRONT VIEW
NOTE: An aluminum outside vent termination kit is also available. (SP12162)
* HE80 and HE119 have 7" solid core ABS factory supplied.
BOOSTER FOR HIGH TEMPERATURE SANITATION RINSE
Download from Www.Somanuals.com. All Manuals Search And Download.
AdvantagePlus Gas continued.
The HE45-160 and HE45-199 Booster models are the only models equipped with a 180°F thermostat.
Models with 180°F thermostats come standard with the Booster Installation Kit which includes all
necessary components for an approved installation.
Booster Installation Kit includes:
• Nibco Tee – 1" x 1" x 1/2" (2 pieces)
• Female Adapter – 1" (2 pieces)
• Dial Thermometer (2 pieces)
• Expansion Tank – 4-1/2 gallon
• Grundfos 3 Speed Pump with Check Valve
• Nibco 1.2" x 12" Fitting Air Chamber
• Vacuum Relief Valve
• Pressure Gauge – 0-200 PSI
• Nibco Tee 712R – 1" x 1" x 3/4" (2 pieces)
• Nibco Tee 714RR – 1" x 1/2" x 1"
• Nibco Tee – 1" x 1/2" x 1" Copper
• Reducing Coupling
• Pressure Reducing Valve
• Nibco Male Adapter – 1"
Recommended Specifications (for trade reference only)
The Water Heaters shall be Rheem-Ruud model number HE- _________. The Water Heaters shall be a sealed
combustion system, taking only outside air for combustion and exhausting the flue gas with plastic pipe. The intake
air shall be piped with plastic PVC or ABS pipe, 3" in diameter (2" in diameter for 100,000 BTU and 130,000 BTU)
and the exhaust gas shall be piped with CPVC or ABS solid NON FOAM CORE for the first 7' only, with the
remaining pipe being sch 40 or 80 CPVC solid - solid PVC NON FOAM CORE - ABS solid NON FOAM CORE.
All related intake air and exhaust gas shall be approved for zero clearance to any combustible surface.
The heaters shall be constructed of 316L stainless steel. The primary condensing heat exchanger shall be
constructed of 90/10 cupronickel. The insulation is a water blown foam and shall be 2" thick with rating of R14.2
and 3" on the top of the heater rated at R21.3. Insulation shall be enclosed in a plastic shell. All components shall
be located in the front of the heater for easy access for serviceability. All related hardware shall be constructed of
stainless steel studs and brass nuts for serviceability.
Limited Warranty
This product features a three year limited warranty against tank leaks. Please refer to Commercial Warranty
Information brochure for complete warranty information.
C O M M E R C I A L
W A T E R H E A T E R S
In keeping with its policy of continuous progress and product improvement, Rheem-Ruud reserves the right to make changes without notice.
Rheem Canada Ltd./Ltée,128 Barton Street West, Hamilton, Ontario L8N 3P3
PRINTED IN U.S.A
02/05 WP
Form No. RR102C-8 Rev. 9
Download from Www.Somanuals.com. All Manuals Search And Download.
|