Use & Care Manual
With Installation Instructions for the Installer
Commercial Indoor and Outdoor Gas
Tankless Water Heater
!
Warning: This water heater is not suitable
for use in manufactured (mobile) homes!
The purpose of this manual is twofold: one, to provide the installer with
the basic directions and recommendations for the proper installation and
adjustment of the water heater; and two, to the owner–operator, to
explain the features, operation, safety precautions, maintenance and
troubleshooting of the water heater. This manual also includes a parts
list.
It is imperative that all persons who are expected to install, operate or
adjust this water heater read the instructions carefully so they may
understand how to perform these operations. If you don’t understand
these instructions or any terms within it, seek professional advice.
Any questions regarding the operation, maintenance, service or
warranty of this water heater should be directed to the seller from whom
it was purchased. If additional information is required, refer to the
section on If You Need Service
Do not destroy this manual. Please read carefully and keep in a safe
place for future reference.
Recognize this symbol as an indication of Important Safety
Information!
!
Indoor Water Heater
California Proposition 65 Warning: This product contains
!
Outdoor Water Heater
chemicals known to the State of California to cause cancer, birth
defects or other reproductive harm.
WARNING: If the information in these instructions is not followed exactly,
a fire or explosion may result causing property damage, personal injury or death.
!
!
FOR YOUR SAFETY!
● If you cannot reach your gas supplier, call
— Do not store or use gasoline or other
flammable vapors or liquids or other
combustible materials in the vicinity of this or
any other appliance. To do so may result in an
explosion or fire.
the fire department.
● Do not return to your home until authorized
by the gas supplier or fire department.
— Improper installation, adjustment,
alteration, service or maintenance can cause
property damage, personal injury, or death.
Refer to this manual. Installation and service
must be performed by a qualified installer,
service agency or the gas supplier.
— WHAT TO DO IF YOU SMELL GAS
● Do not try to light any appliance.
● Do not touch any electrical switch; do not
use any phone in your building.
● Immediately call your gas supplier from a
neighbor’s phone. Follow the gas
supplier’s instructions.
S
I
N
31-52756
D
CERTIFIED
Printed in Japan
I
AP13731 (03/05)
T
®
R
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING.
Be sure to read and understand the entire Use and Care Manual before attempting to install or operate
this water heater. It may save you time and money. Pay particular attention to the Safety Instructions.
Failure to follow these warnings could result in serious bodily injury or death. Should you have
problems understanding the instructions in this manual, or have any questions, STOP, and get help
from a qualified service technician, or the local gas utility.
DANGER!
INSTALL AND PROPERLY VENT THE WATER HEATER…
Failure to install and properly vent the water heater to the outdoors as outlined in the
Venting Section of the Installation Instructions in this manual can result in unsafe
operation of the water heater. To avoid the risk of fire, explosion, or asphyxiation from
carbon monoxide, never operate this water heater unless it is properly vented and has an
adequate air supply for proper operation.
Be sure to inspect the vent outlet on the OUTDOOR water heater, or the vent terminal
and the vent system on the INDOOR water heater for proper installation at initial start-
up; and at least annually thereafter. Refer to the Care and Cleaning section of this
manual for more information regarding vent system inspection.
WARNING!
Gasoline, as well as other flammable materials and liquids (adhesives, solvents, paint
thinners etc.), and the vapors they produce are extremely dangerous. DO NOT handle,
use or store gasoline or other flammable or combustible materials anywhere near or in the
vicinity of a water heater or any other appliance. Be sure to read and follow the labels on
the water heater, as well as the warnings printed in this manual. Failure to do so can
result in property damage, bodily injury or death.
D A N G E R
FLAMMABLES
Flammable Vapors
Vapors from flammable
liquids will explode and
catch fire causing death or
severe burns.
Do not use or store flammable
products such as gasoline,
solvents or adhesives in the
same room or area near the
water heater.
Water heater has a main
burner flame.
The main burner flame:
1. which can come on
at any time and
2. will ignite flammable
vapors.
Vapors:
1. cannot be seen,
2. are heavier than air,
3. go a long way on the
floor and
4. can be carried from
other rooms to the
main burner flame by
air currents.
Keep flammable products:
1. far away from heater,
2. in approved containers,
3. tightly closed and
4. out of children's reach.
Installation:
Do not install water heater
18" above the floor. This will
where flammable products will reduce, but not eliminate, the
be stored or used unless the
main burner flame is at least
risk of vapors being ignited
by the main burner flame.
Read and follow water heater warnings and instructions. If
owners manual is missing, contact the retailer or manufacturer.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING.
!
DANGER!
WATER TEMPERATURE SETTING
Safety and energy conservation are factors to be considered when selecting the water
temperature setting of a water heater’s remote control. Water temperatures above
125°F (52°C) can cause severe burns or death from scalding. Be sure to read and follow the
warnings outlined on the label pictured below.
Time/Temperature Relationship in Scalds
!
D A N G E R
Water Temperature
Time To Produce a Serious Burn
120°F (49°C)
125°F (52°C)
More than 5 minutes
11/2 to 2 minutes
130°F (54°C)
135°F (57°C)
140°F (60°C)
145°F (63°C)
150°F (66°C)
155°F (68°C)
About 30 seconds
About 10 seconds
Less than 5 seconds
Less than 3 seconds
About 11/2 seconds
About 1 second
HOT
Table courtesy of Shriners Burn Institute
The chart shown above may be used as a guide
in determining the proper water temperature for your
home.
BURN
!
DANGER: Households with small children,
Water temperature over 125°F can
cause severe burns instantly or
death from scalds.
disabled, or elderly persons may require a
120°F (49°C) or lower temperature setting to
prevent contact with “HOT” water.
Children, disabled and elderly are
at highest risk of being scalded.
Maximum water temperature occurs while burner is
on. To find water temperature being delivered, turn
on a hot water faucet and place a thermometer in the
water stream and read the thermometer.
See instruction manual before
setting temperature at water
heater.
Feel water before bathing or
showering.
(See page 27 & 28 for more details.)
Temperature limiting valves are
available, see manual.
The temperature of the water at the outlet of the
water heater can be regulated by setting the
temperature on Remote Control. The remote control
was set at 100°F (38°C) before it was shipped from
the factory.
Notice:
The illustration to the bottom left illustrates the
Remote Control and how to adjust the water
temperature.
Display
shows
°F only.
PRIORITY
Notice: The factory setting allows operating
°F
temperatures between 100°F (38°C) and 120°F
(49°C). Temperatures of up to 180°F (82°C) can be
achieved with the MAIN (UMC-117) remote control
and a dip switch adjustment. Only qualified service
personnel should perform this adjustment. Only
factory authorized remote control(s) should be used.
POWER
ON/OFF
Notice: When this water heater is supplying general
purpose hot water requirements for use by
individuals, a thermostatically controlled mixing
valve for reducing point of use water temperature is
recommended to reduce the risk of scald injury.
Contact a licensed plumber or the local plumbing
authority for further information.
Higher (Hotter)
Lower (Cooler)
100 102 104 106 108 110 112 114 116 118 120* 125 130 135 140 150 160 170 180 °F
38 39 40 41 42 43 44 46 47 48 49* 52 54 57 60 66 71 77 82 °C
* Temperatures above 120°F (49°C) can be achieved
by adjusting the dip switch. See page 35 for dip
switch adjustment.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
DANGER!
NATURAL GAS AND LIQUEFIED PETROLEUM MODELS
Both LP and natural gas have an odorant added to aid in detecting a gas leak. Some
people may not physically be able to smell or recognize this odorant. If you are unsure or
unfamiliar with the smell of LP or natural gas, ask the gas supplier. Other conditions, such
as “odorant fade”, which causes the odorant to diminish in intensity, can also hide or
camouflage a gas leak.
Notice: If a gas leak is present or suspected:
● Do not attempt to find the cause yourself.
● Do not try to light any appliance.
● Water heaters utilizing LP gas are
different from natural gas models. A
natural gas water heater will not function
safely on LP gas and vice versa.
● Do not touch any electrical switch.
● Do not use any phone in your building.
● No attempt should ever be made to
convert the water heater from natural
gas to LP gas. To avoid possible
● Leave the building immediately and
make sure your family and pets leave
also.
equipment damage, personal injury or
fire, do not connect the water heater to a
fuel type not in accordance with the unit
data plate; propane for propane units
and natural gas for natural gas units.
These units are not certified for any
other fuel type.
● Leave the doors open for ventilation and
contact the gas supplier, a qualified
service agency or the fire department.
● Stay away from the building until the
service call has been made, the leak is
corrected and a qualified agency has
determined the area to be safe.
● LP appliances should not be installed
below grade (for example, in a basement)
if such installation is prohibited by
federal, state and/or local laws, rules,
regulations or customs.
● Propane or LP gas must be used with
great caution. It is heavier than air and
will collect first in lower areas making it
hard to detect at nose level.
● Before attempting to light the water
heater, make sure to look and smell for
gas leaks. Use a soapy solution to check
all gas fittings and connections. Bubbling
at a connection indicates a leak that must
be corrected. When smelling to detect a
gas leak, be sure to sniff near the floor
also.
● Gas detectors are recommended in LP
and natural gas applications and their
installation should be in accordance with
the detector manufacturer’s
recommendations and/or local laws,
rules, regulations or customs.
● It is recommended that more than one
method, such as soapy solution, gas
detectors, etc., be used to detect leaks in
gas applications.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING.
!
WARNING!
For your safety, the information in this manual must be followed to minimize the risk of
fire or explosion, electric shock, or to prevent property damage, personal injury, or loss of
life.
FOR INSTALLATIONS IN THE STATE OF CALIFORNIA
California Law requires that residential water heaters must be braced, anchored or
strapped to resist falling or horizontal displacement due to earthquake motions. For
residential water heaters up to 52 gallon capacity, a brochure with generic earthquake
bracing instructions can be obtained from: Office of the State Architect, 1102 Q Street,
Suite 5100, Sacramento, CA 95814 or you may call 916-445-8100 or ask a water heater
dealer.
However, applicable local codes shall govern installation. For residential water heaters
of a capacity greater than 52 gallons or tankless-style, consult the local building
jurisdiction code for acceptable bracing procedures.
SAFETY PRECAUTIONS
Have the installer show you the location of the gas shut-off valve and how to shut it off if
necessary. Turn off the manual shut-off valve if the water heater has been subjected to
overheating, fire, flood, physical damage or if the gas supply fails to shut off.
● Read this manual entirely before
● Do not attempt to repair or replace any
part of your water heater unless it is
specifically recommended in this
installing or operating the water heater.
● Use this appliance only for its intended
purpose as described in this Use and
Care Manual.
manual. All other servicing should be
referred to a qualified technician.
● Be sure your appliance is properly
installed in accordance with local codes
and the provided installation
instructions.
READ AND FOLLOW THIS SAFETY INFORMATION
CAREFULLY.
SAVE THESE INSTRUCTIONS
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the (INDOOR) water heater :
This water heater must be installed in accordance with these instructions, local codes, utility company
requirements, and/or in the absence of local codes, use the latest edition of the American National
Standard/National Fuel Gas Code. A copy can be purchased from either the American Gas Association,
400 North Capitol Street Northwest, Washington, DC 20001 as ANSI standard Z223.1 or National Fire
Protection Association, 1 Batterymarch Park, Quincy, MA 02269 as NFPA 54. In Canada, the latest
edition of the CSA B149.1 Natural Gas and Propane Installation, and the Canadian Electrical Code,
CSA C22.1 Part 1, in the absence of local codes.
Location of INDOOR Water Heater
The water heater should not be located
in an area where leakage of the heat
exchanger or connections will result in
damage to the area adjacent to it or to
lower floors of the structure.
● The water heater should be installed as
close as practical to the vent termination
to minimize vent length and the number
of elbows required for venting.
● The water heater should be installed with
the proper venting materials and
termination suitable for Category III
venting.
When such areas cannot be avoided it is
recommended that a suitable catch pan,
adequately drained, must be installed
under the water heater.
● Failure to install and properly vent the
water heater to the outdoors as outlined
in the Venting Section of this manual can
result in unsafe operation.
The pan must not restrict combustion air
flow.
A gas fired water heater or any other
appliance should not be installed
in a space where liquids which give off
flammable vapors are to be used or stored.
Such liquids include gasoline, LP gas
(butane or propane), paint or adhesives and
their thinners, solvents or removers.
!
WARNING: Combustible
● Long hot water lines should be insulated to
conserve water and energy.
construction refers to
adjacent walls and ceilings
and should not be confused
with combustible or
● The water heater and water lines should
be protected from exposure to freezing
temperatures.
flammable products and
materials. Combustible
and/or flammable products
and materials should never
be stored in the vicinity of
this or any gas appliance.
● Do not install the water heater in
bathrooms, bedrooms, any occupied
rooms normally kept closed, or in
outdoor areas.
Because of natural air movement in a room
or other enclosed space, flammable vapors
can be carried some distance from where
their liquids are being used or stored. The
open flame of the water heater’s main
burner can ignite these vapors causing an
explosion or fire which may result in severe
burns, death or property damage.
● Do not install the water heater in small,
poorly ventilated rooms, or in air tight
rooms with air-conditioning.
Minimum Clearance from
Combustible and
Non-Combustible
Construction.
● Do not install water heater where subject
to vibrations.
The water heater must be located so it is not
subject to physical damage, for example, by
moving vehicles, area flooding, etc.
min.
1/2 "
(1.3 cm)
min.
min. 2"
(5 cm)
(m5inc.m2")
● Do not install the water heater in
Recreational Vehicles, Mobile Homes,
Boats and other Watercrafts.
1/2 "
(1.3 cm)
(30 cm)
min. 12"
(24" (60 cm) minimum is
recommended for service)
If the water heater is installed in a garage, it
should be installed so that the direct
ignition system and main burner are no less
than 18 inches (45 cm) above the garage
floor.
Top = 12"(30 cm) Back = 0" *
(1.3 cm)
● Do not install the water heater near vents
for heating or cooling. A minimum of 4
feet (1.2 m) should be maintained.
(5 cm)
Vent = 2"
Front = 12"(30 cm) Bottom = 12"
(with support bracket)
Side = 1/2"
(30 cm)
*
!
WARNING: Follow vent
● Minimum clearance from combustible
and non-combustible construction is 1/2”
(1.3 cm) sides, 0” rear (with support
bracket); 12” (30 cm) from the bottom;
12” (30 cm) from the front of the water
heater; and 12” (30 cm) from the top
(24” (61 cm) from front and top is
recommended for servicing purposes).
Maintain a minimum clearance of
2” (5 cm) around the vent pipe to
Raising the gas fired water heater will
reduce BUT NOT eliminate the possibility
of lighting the vapor of any flammable
liquids which may be improperly stored or
accidentally spilled.
manufacturers
instructionwhile installing
vent. If required, provide
additional clearances from
vent to combustibles per
vent manufacturers
instruction.
combustible or non-combustible
Vent Pipe
3" (8 cm) min
2" (5 cm) min
construction. If the clearances stated on
the Instruction/Warning Label, located
on the front panel of the heater differ,
install the water heater according to the
clearances stated on the label.
2" (5 cm) min
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the (OUTDOOR) water heater:
This water heater must be installed in accordance with these instructions, local codes, utility company
requirements, and/or in the absence of local codes, use the latest edition of the American National
Standard/National Fuel Gas Code. A copy can be purchased from either the American Gas Association, 400
North Capitol Street Northwest, Washington, DC 20001 as ANSI standard Z223.1 or National Fire Protection
Association, 1 Batterymarch Park, Quincy, MA 02269 as NFPA 54. In Canada, the latest edition of the CSA
B149.1 Natural Gas and Propane Installation, and the Canadian Electrical Code, CSA C22.1 Part 1, in the
absence of local codes.
Location of the OUTDOOR water heater
This water heater is for OUTDOOR
installation ONLY!
● The water heater should be installed
vertically with the water, gas, and power
connections on the underside pointing
toward the ground.
This water heater is an outdoor model
and must be mounted vertically. It
must not be installed indoors or in a
confined space.
● Failure to properly install the water
heater outdoors as outlined in this
manual can result in unsafe operation.
The water heater should be installed
close to the most frequently used outlet
and its position chosen with safety and
service in mind.
● Hot and cold water lines should be
insulated to conserve water and energy.
● The water heater and water lines should
be protected from exposure to freezing
temperatures.
Make sure people (particular children,
disabled, and elderly) will not touch the
hot water outlet or the flue terminal.
The flue terminal and air inlet must be
clear of obstruction and shrubbery.
● Do not install water heater where
subject to vibrations.
● Do not install the water heater in
Recreational Vehicles, Mobile Homes,
Boats and other Watercrafts.
The water heater should not be located
in an area where leakage of the heat
exchanger or connections will result in
damage to the area adjacent to it or to
lower floors of the structure.
● Do not install the water heater near
vents for heating or cooling. A
minimum of 4 feet should be
maintained.
!
WARNING: Combustible
construction refers to
adjacent walls and ceilings
and should not be confused
with combustible or
A gas fired water heater or any other
appliance should not be installed
in a space where liquids which give off
flammable vapors are to be used or stored.
Such liquids include gasoline, LP gas
(butane or propane), paint or adhesives and
their thinners, solvents or removers.
● Minimum clearance from combustible
and noncombustible construction is
1/2” (1.3 cm) sides, 0” rear (with
support bracket); 12” (30 cm) from the
bottom; 12” (30 cm) from the front of
the water heater; and 12” (30 cm) from
the top (24” (61 cm) from front and top
is recommended for servicing
purposes). If the clearances stated on
the Instruction/Warning Label, located
on the front panel of the heater differ,
install the water heater according to the
clearances stated on the label.
flammable products and
materials. Combustible
and/or flammable products
and materials should never
be stored in the vicinity of
this or any gas appliance.
Because of natural air movement in a
room or other enclosed space, flammable
vapors can be carried some distance from
where their liquids are being used or
stored. The open flame of the water
heater’s main burner can ignite these
vapors causing an explosion or fire which
may result in severe burns, death or
property damage.
Minimum Clearance from
Combustible and
Non-Combustible
Construction.
min.
1/2 "
(1.3 cm)
min.
1/2 "
(1.3 cm)
The water heater must be located so it is
not subject to physical damage, for example,
by moving vehicles, area flooding, etc.
min. 12" (30 cm)
(24" (61 cm) minimum is
recommended for service)
Top = 12" (30 cm)
Front = 12" (30 cm)
Back = 0" (with support bracket)
Side = 1/2" (1.3 cm)
Bottom = 12" (30 cm)
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the water heater:
Proper operation of the water heater requires air for combustion and ventilation. Provisions for
combustion and ventilation air must comply with referenced codes and standards.
Combustion and Ventilation Air (Indoor Water Heater Only)
NOTICE: If the water heater is installed in
an unconfined space within a building of
conventional frame, masonry or metal
construction, infiltration air is normally
adequate for proper combustion and
ventilation. If the water heater is installed in
a confined space, provisions for combustion
and ventilation air must be made.
ventilated attic or crawl space.
If air is supplied from outdoors, directly or
through vertical ducts, there must be two
openings located as specified above and
each must have a minimum net free area
of not less than one square inch
(6.5 sq cm) per 4000 Btuh of the total
input rating of all the appliances in the
enclosure.
Air Openings
Min. 200 Sq. In.
(1290 cm2
)
A confined space is one having a volume
of less than 50 cubic feet (1.4 cubic
meters) per 1000 Btuh of the aggregate
input of all appliances within that space.
If horizontal ducts are used to
communicate with the outdoors, each
opening must have a minimum net free
area of not less than one square inch
(6.5 sq cm) per 2000 Btuh of the total
input rating of all the appliances in the
enclosure. If ducts are used, the minimum
dimensions of rectangular air ducts shall
not be less than 3” (7.6 cm).
Min. 3" (7.6 cm)
The air must be supplied through two
permanent openings of equal area. One
is to be located within 12” (30 cm) above
the floor and the other is to be located
within 12” (30 cm) below the ceiling.
DANGER: OUTDOOR
water heaters must not
be installed indoors or
in a confined space.
The minimum net free area of each opening
must not be less than one square inch (6.5
sq cm) per 1000 Btuh of the total input
rating of all the appliances in the
enclosure (but not less than 100 square
inches (650 cm2),) if each opening
communicates with other unconfined areas
inside the building.
Install outdoor water
heaters outdoors only.
NOTICE: If the duct openings which supply
combustion and ventilation air are to be
covered with a protective screen or grill, the
net free area (openings in the material) of
the covering material must be used in
determining the size of the openings.
Protective screening for the openings MUST
NOT be smaller than 1/4” (0.64 cm) mesh to
prevent clogging by lint or other debris.
Buildings of unusually tight construction
shall have the combustion and ventilation
air supplied from outdoors, or a freely
NOTICE: The water heater
should not be installed near
an air supply containing
halogenated hydrocarbons.
Corrosive Atmospheres
The air in beauty shops, dry cleaning
establishments, photo processing labs,
and storage areas for liquid and powdered
bleaches or swimming pool chemicals
often contain such halogenated
hydrocarbons.
Propellants from common spray cans or
gas leaks from A/C and refrigeration
equipment are highly corrosive after
passing through a flame.
The water heater warranty is voided when
failure of the heater is due to operation in
a corrosive atmosphere.
An air supply containing halogenated
hydrocarbons may be safe to breathe,
but when it passes through a gas flame
corrosive elements are released that
will shorten the life of any gas burning
appliance.
Inspect Shipment
Inspect the water heater for possible damage. Check the markings on the rating plate of
the water heater to be certain the type of gas supplied corresponds to the water heater
requirements. Verify all included parts are present (see below).
Use
&
Care Manual
W
ith Installation Instructions for the Installer
Certificate of
Limited
Residential
Tankless WateGrasHeaters
Warranty
Warning: This water heater is not suitable for
use in manufactured (mobile) homes!
®
The purpose of this manual is twofold: one, to provide the installer with
the basic directions and recommendations for the proper installation and
adjustment of the water heater; and two, to the owner–operator to
,
explain the features, operation, safety precautions, maintenance and
troubleshooting of the water heater This manual also includes parts
list.
PRIORITY
.
a
COMMERCIAL
W
A
T
E
R
H
E
A
T
E
R
S
It is imperative that all persons who are expected to install, operate or
adjust this water heater read the instructions carefully so they may
understand how to perform these operations. If you don’t understand
these instructions or any terms within it, seek professional advice.
Any questions regarding the operation, maintenance, service or
warranty of this water heater should be directed to the seller from whom
it was purchased. If additional information is required, refer to the
section on How to Obtain Service Assistance.
°F
Do not destroy this manual. Please read carefully and keep in
place for future reference.
a
safe
Wood Screw x 5pcs.
Washer x 4 pcs.
COMMERCIAL
GAS TER HEATERS
YEAR HEA EXCHANGER AND
YEAR ARTS LIMITED ARRANTY
T
ANKLESS
!
!
Recognize this symbol as an indication of Important Safety
nformation!
WA
WITH
1
A
3
T
California Proposition 65 Warning: This product contains
P
W
chemicals known to the State of California to cause cancer birth
,
defects or other reproductive harm.
W
ARNING: If the information in these instructions is not followed exactly,
AP13487-1 (03/05)
!
a
fire or explosion may result causing property damage, personal injury or death.
POWER
ON/OFF
!
FOR YOUR SAFETY!
—
Do not store or use gasoline or other
flammable vapors or liquids or other
combustible materials in the vicinity of this or
●
●
—
If you cannot reach your gas supplier call
,
the fire department.
Do not return to your home until authorized
by the gas supplier or fire department.
any other appliance.
explosion or fire.
T
o
do so may result in an
Improper installation, adjustment,
—
WHA
T
TO DO IF YOU SMELL GAS
alteration, service or maintenance can cause
property damage, personal injury, or death
Refer to this manual. Installation and service
.
●
Do not try to light any appliance.
●
Do not touch any electrical switch; do not
use any phone in your building.
Warranty
must be performed by
a
qualified installer
,
service agency or the gas supplier
.
●
Immediately call your gas supplier from
neighbor’ phone. Follow the gas
supplier’ instructions.
a
s
s
D
E
S
I
Printed in USA
Tankless Unit
E
TIFI
E
D
®
Remote Control
Assembly Kit
Manual Appliance
Gas Shut-off Valve
Use & Care Manual
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Mounting the Water Heater
Make sure the location of the appliance
allows for easy access and operation.
Using a wood screw and a washer, affix
the lower bracket to the wall (Left and
Right). Repeat to affix the top bracket.
CAUTION:
Reinforcement of the wall is
required in case the wall is
not strong enough to hold
the appliance.
Wall studs should be utilized when
mounting the water heater to the wall.
Alternately, a suitable piece of wood may
be placed inside or outside of the wall to
span the distance between the wall studs.
Fasten the water heater mounting brackets
to the wood.
The brackets can be adjusted to change
the distance between the back of the
appliance and the wall within the range of
3/8” (.95 cm) to 1½” (3.8 cm).
Loosen the adjustment screws of both the
top and the bottom brackets to adjust the
distance. (See diagram below)
In case of dry wall or concrete wall use
dry wall anchors or lag bolts.
1/8" (.32 cm)
Clearance
Wood Screw
Upper Bracket
TOP
The water heater requires 120VAC/60Hz.
Have a receptacle with ground terminal
near the water heater. The length of the
power supply cord is 10 feet (3 m),
(Indoor water heater only.)
Adjustment Screws
Bracket
Washer
Washer
Wood Screw
Washer
Install a wood screw for the upper bracket
with a clearance of 1/8” (.32 cm) between
the wall and the screw head. Hang the
center of the upper bracket on the screw.
Adjustment Screws
Wood Screw
Lower Bracket
BOTTOM
Bracket
IMPORTANT: Do not
Water Supply Connections
Plumbing should be carried out by a
qualified plumber in accordance with local
codes.
apply heat to the HOT or
COLD water connections. If
sweat connections are used,
sweat tubing to adapter
before fitting adapter to the
water connections on
additional water pressure (0.44 psi/ft)
(10 kPa/m) must be ensured. The
measurement should be calculated by
the distance between the water inlet of
the water heater (ground level) to the
hot water faucet (upper floor level).
Use approved plumbing materials only.
heater. Any heat applied to
the water supply fittings
will permanently damage
the internal components of
the water heater.
The diameter of the pipe lines should be a
minimum of 3/4”.
● Well water systems should be set to
ensure a minimum system pressure of
40 psi (276 kPa).
To conserve energy and to prevent
freezing, insulate both cold and hot water
supply lines. DO NOT cover the drain or
pressure relief valve.
● When the water is supplied from a
water supply tank, the height of the
tank and the diameter of the pipes and
their relation to water pressure, should
be taken into consideration. Gravity
water pressure is not recommended.
To ensure proper operation of the water
heater, the following water pressure
guidelines should be followed:
CAUTION: This water
heater must only be used
with the following water
supply system conditions:
● Operation of the water heater requires
the minimum water pressure of 14 psi
(97 kPa) and a minimum water flow
rate of 0.66 gpm (2.5 lpm).
Notice: If the water flow resistance of a
shower head is too high, the burner in the
water heater will fail to ignite. Keep the
shower head clean from debris that could
cause additional pressure drop.
● With clean, potable water
free of corrosive
chemicals, sand, dirt, or
other contaminates.
● A water pressure of 40 psi (276 kPa) is
required to achieve maximum flow rate.
● With inlet water
temperatures above
32°F (0°C), but not
exceeding 140°F (60°C).
Notice: If using mixing valves on the
outlet, choose one which prevents cold
water pressure from overcoming hot water
line pressure.
● To maintain proper performance, ensure
sufficient water supply pressure. The
Required Water Pressure = Min.
Operating Water Pressure
(14 psi) (97 kPa) + Pipe Pressure Loss
+ Faucet and Shower Pressure Loss +
Safety Margin (more than 5 psi)
(34 kPa).
● Free of lime and scale
deposits.
Notice: If multiple water heaters are
installed in a manifold system, the
water piping must be in “Parallel”. A
water pressure of 40 psi (276 kPa) is
recommended for each water heater for
proper operation of the water heaters.
● DO NOT reverse the hot
and cold water
connections. The water
heater will not operate.
● To supply hot water to upper floors,
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the water heater:
Water Supply Connections Continued
Water Filter
Install a shutoff valve near the inlet of the Install a Check Valve between the water
water heater for service and draining
purposes.
heater and the water shutoff valve. (See
illustration the top left).
It is not recommended to use pipes with
smaller diameters than the water supply
connection of the water heater.
The following should be addressed in
regards to the HOT WATER OUTLET:
Clean the
Water Filter
Water Inlet
Check Valve
● Connections between the water heater
and point(s) of use should be as short
and direct as possible.
Before connecting the water supply pipe
to the water heater, open the shutoff valve
and clean out sand, debris, air, caulking
material, etc. inside the pipe. Connect to
the water inlet, then check water flow.
Close the shutoff valve and clean the
water filter.
Nipple
● DO NOT use lead or plastic pipe.
Water
● To conserve energy and minimize heat
loss, insulation of hot water piping is
recommended. (See Hot and Cold Pipe
Insulation Installation on page 24).
Notice: Use only teflon tape on cold
and hot water connections and
lines.
Be sure to connect the water inlet and the
hot water outlet as shown on the water
heater. If reversed, the water heater will
not function.
Notice: The flow rate of hot water may
vary when more than two faucets
(appliances, fixtures, etc.) are being used
simultaneously.
Hot
Water
Tap
Installation of unions or flexible copper
connections are recommended on the
HOT and COLD water lines, so that the
water heater may disconnect easily for
servicing if necessary.
Notice: The pipes MUST be completely
drainable. If the hot water faucets are
located at a point higher than the water
heater, place a drain valve at the lowest
point (see diagram to the left).
Drain Valve
Relief Valve
A new pressure relief valve, complying
with the Standard for Relief Valves and
Automatic Gas Shut-Off Devices for Hot
Water Supply Systems, ANSI Z21.22/
CSA 4.4, must be installed at the hot
water outlet connection of the water
heater at the time of installation. Local
codes shall govern the installation of
relief valves.
● The discharge line must be NO
SMALLER than the outlet of the relief
valve and must pitch downward to
allow complete drainage (by gravity) of
the relief valve and discharge line.
Pressure
Relief Valve
● The end of the discharge line should not
be threaded or concealed and should be
protected from freezing. No valve of
any type, restriction or reducer coupling
should be installed in the discharge line.
For safe operation of the water heater, be
sure that:
Water
Notice: Local codes govern the
installation of relief valves. If local codes
require that a temperature and pressure
relief valve should be installed the
manufacturer recommends a type 40XL
Watts T&P relief valve or an equivalent
model be used.
Shutoff
Valve
● The pressure rating of the relief valve
must not exceed 150 psi (1034 kPa), the
maximum working pressure of the
water heater as marked on the rating
plate.
Union
Cold
Water
Supply
Inlet
Relief
Valve
Discharge
Line
● The BTUH rating of the relief valve
must equal or exceed the BTUH input
of the water heater as marked on its
rating plate.
Notice: Manual operation of relief valves
should be performed at least once a year.
Turn off the electrical power and gas
shutoff valve. Lift and release lever on the
relief valve and check the manual
operation of the relief valve. You should
take precaution to avoid contact with the
hot water coming out of the relief valve
and to prevent water damage.
Hot Water
Supply
Outlet
Notice: The above illustrates a
pressure only relief valve. If local
codes require a combination
● No valve of any type should be
installed between the relief valve and
the water heater
temperature and pressure relief
valve be installed, an extension
piece may be needed. (Refer to
page 22 or 23 for example of
extension piece for T&P relief
valve installation.) The T&P relief
valve probe should not be directly
in the flow path of the water.
● Discharge from the relief valve should
be piped to a suitable drain to eliminate
potential water damage. Piping used
should be of a type approved for the
distribution of hot water.
Notice: If the relief valve on the system
discharges periodically, a problem exists
and service to the water system is
required.
● Hot and cold water lines should be
insulated up to the water heater. Refer
to page 24 for details.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Do not attempt to convert this water heater for use with a different type of gas other than the type
shown on the rating plate. Such conversion could result in hazardous operating conditions.
Gas Supply
The supplied Manual Gas Appliance
Shutoff Valve must be installed at the gas
connection of the water heater at the time
of installation (see diagram to the left).
A sediment trap should be installed at the
bottom of the gas line.
Manual
Gas
Supply
Line
Shut-off
Valve
Do not use excessive force
(over 31.5 ft lbs.) (42.7 Nm) in tightening
the pipe, particularly if teflon pipe
compound is used, as the unit may be
damaged.
The branch gas supply line to the water
heater should be a minimum of 3/4” black
steel pipe or other approved gas piping
material.
The inlet gas pressure to the water heater
must not exceed 10.5” w.c. (2.6 kPa) for
natural or 14” w.c. (3.5 kPa) for LP gas.
For purposes of input adjustment, the
minimum inlet gas pressure (with main
burner on) is shown on the water heater
rating plate. If high or low gas pressures
are present, contact your gas supplier for
correction.
A ground joint union or ANSI design
certified semi-rigid or flexible gas
Manual Gas
Appliance
appliance connector should be installed in
the gas line close to the water heater. The
National Fuel Gas Code (NFGC) ANSI
Z223.1 and CAN B149 code mandates a
manual gas shut-off valve: See NFGC &
B149 for complete instructions.
Shut-off
(Supplied)
Union
If flexible connectors are used, the
maximum length shall not exceed
36” (91 cm).
NOTICE: To ensure proper operation
of the heater the gas pipe and gas
meter must be sized correctly.
Sediment
Trap
Cap
If lever type gas shut offs are used, they
shall be T-Handle type.
Gas piping shall be in accordance
with local, utility company require-
ment and/or in the absence of local
codes, use the latest edition of the
National Fuel Gas Code. In Canada
the latest edition of CSA B149.1 Nat-
ural Gas and Propane installation
code.
Compound used on the threaded joints of
the gas piping must be of the type
resistant to the action of LP gas. Use
compound sparingly on male threads only.
Leak Testing
WARNING: Never use
an open flame to test for
gas leaks, as property
damage, personal injury, or
death could result.
The water heater and its gas connections
must be leak tested at normal operating
pressures before it is placed in operation.
Use a soapy water solution to test for
leaks at all connections and fittings.
Bubbles indicate a gas leak that must
be corrected.
Turn on the gas shut-off valve(s) to
the water heater.
The factory connections should also be
leak tested after the water heater is placed
in operation.
Pressure Testing the Gas Supply System
WARNING: Install a
gas pressure regulator, in
the gas supply line, which
does not exceed the
The water heater and its manual gas shut-
off valve must be disconnected from the
gas supply piping system during any
pressure testing of the system at
pressures in excess of 1/2 psi (14” w.c.)
(3.5 kPa).
The water heater must be isolated from
the gas piping system by closing the
manual gas shut-off valve during any
pressure testing of the gas supply piping at
pressures equal to or less than
maximum supply pressure.
DO NOT use an industrial
type gas regulator.
1/2 psi (14” w.c.) (3.5 kPa).
High Altitude
Input rating of this water heater is
based on sea level operation. At
higher elevations the actual input
rate may be lower than the value list-
ed on the rating label. This water
heater can be installed at elevations
up to 3,280 feet (1000 m)without any
change or modification.
NOTICE: For installations above
3,280 feet (1000 m) elevation, the
connector on the PC board must be
replaced. Do not install this water
heater at elevations above 3,280 feet
(1000 m) without installing the proper
high altitude connector. Please contact
your local distributor, dealer, or Rheem
for replacement connector.
NOTICE:
Select models may be available preset
for operations at elevations up to 6,560
feet (2000 m).
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the water heater:
The water heater must be installed with a RTG20002B vent adapter or a UL approved Category III Stainless
Steel equivalent.
Venting
DANGER: Failure to
The installation of venting must comply with Vent pipe runs must be adequately supported
install the vent adapter and
properly vent the water
heater to the outdoors as
outlined in the Venting
section of this manual will
result in unsafe operation of
the water heater causing
death, serious injury,
national codes, local codes, and the vent
manufacturer’s instructions.
along both horizontal and vertical runs.
The maximum recommended unsupported
span should be no more than five (5) feet
(1.5 m) Support isolation hanging bands
should be used. DO NOT use wire. (See
The water heater must be vented to the
outdoors as described in these instructions.
DO NOT connect this water heater to a
Chimney. It must be vented separately from
all other appliances.
NO!
YES!
explosion, or fire. To avoid
the risk of fire, explosion,
or asphyxiation from
All vent components (adapters, pipe, elbows,
terminals, etc.) should be UL1738 Certified
Stainless Steel Venting Material
(e.g. AL29-4C).
carbon monoxide, NEVER
operate the water heater
unless it is properly vented
and has adequate air supply
for proper operation as
outlined in the Venting
section of this manual.
diagram below).
The specified vent termination must be used.
The termination should be a 90° elbow type
with screen. (Refer to page 17)
Notes on pre-existing vent:
If the water heater is being installed as a
replacement for an existing water heater, a
thorough inspection of the existing venting
system must be performed prior to any
installation work. Verify that the correct
materials, vent lengths and terminal locations
as detailed in this Use and Care manual have
been met. Carefully inspect the entire
Use a vent pipe with an anti-disconnection
structure.
The use of a High Temperature Silicone
(500°F) (260°C) may be required to seal vent
connections. To prevent accidental gas
exhaust leakage, apply a 1/4” (6 mm) wide
bead approximately 1/4” (6 mm) from the
end and another bead against the joint side of
the stop bead.
WARNING: Use UL
approved Category III
Stainless Steel vent material
only. No other vent
venting system for any signs of cracks or
fractures, particularly at the joints between
elbows or other fittings and the straight runs
of vent pipe. Check the system for signs of
sagging or other stresses in the joints as a
result of misalignment of any components in
the system. If any of these conditions are
found, they must be corrected in accordance
with the venting instructions in this manual
before completing the installation and
material is permitted.
Follow vent manufacturer’s installation
instructions.
WARNING: Refer to
page 7 for clearances to
combustible material.
The unit can be vented either horizontally or
vertically.
putting the water heater into service.
Venting Lengths
Number of
90° elbows
(bends)
Maximum
Length of
MAXIMUM VENT LENGTH - The
system will not operate if there is excessive
restriction (pressure drop) in the venting
system. A maximum of 47 feet 6 inches
(14.4 m) of vent pipe may be used provided
there is only one 90° elbow in the system. If
additional elbows are required: two elbows
horizontal run toward the vent terminal (see
diagram below). This ensures that any
condensate formed during operation of the
unit is evacuated from the appliance.
Straight Pipe
1
2
3
47’ 6”
(14.4 m)
A 1/4” per foot upward slope is acceptable
when it is not possible to vent with a
downward slope, however, a UL approved
Category III Stainless Steel condensate trap
MUST be installed at the beginning of the
horizontal run (See page 17 “Typical
Horizontal Termination
can be used with 42 feet 6 inches (13 m)
and three elbows can be used with 37 feet 6
inches (11.4 m) of vent pipe.
,
42’ 6”
(13 m)
A 90° elbow is equivalent to 5 feet (1.5 m)
37’ 6”
(11.4 m)
to straight pipe. A 45° elbow is equivalent to w/ 1/4” per foot UPWARD Slope” or
2 feet 6 inches (76 cm) of straight pipe.
page 18, “Standard Vertical Vent
Termination” for examples).
The termination elbow does not count as an
elbow when determining total vent lengths.
MINIMUM VENT LENGTH - The
venting may be as short as 12” (30 cm),
provided one vent termination is installed to
the outdoors through a sidewall, one 90°
elbow is included in the installation, and the
wall thimble is installed.
The vent can be installed with a slight
downward slope of 1/4” per foot of
Vent Seam
1/4" per foot
downward slope.
Notice: Make sure that the seam of the vent
pipe in horizontal runs is toward the top of
the installation (see illustration to the far
left).
Min. 3"
(8 cm)
Max. 3 feet (91 cm)
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting Through Closed Spaces
If the vent piping passes through a closed space, a minimum
clearance of 8” (20 cm) when installed horizontally, 6” (15 cm)
when installed vertically should be maintained between the vent
pipe and combustibles and noncombustibles. Be sure to follow
local codes.
1/4” per foot
downward slope
Wall Thimble
For maintenance and inspection purposes, the following access
panels are required.
● Two (2) inspection access panels large enough to allow
access for venting inspection. One (1) of these access
panels should be close to where the vent pipe enters the
ceiling. The other access panel should be near the vent
termination.
● A ventilation access panel with a 16 in2 (103 cm2) opening
should be provided every 10 ft (3 m).
Vent Pipe
Ceiling
Board
Inspection
Access Panel #1
Inspection
Access Panel#2
Vent Adapter
A UL 1738 approved stainless steel vent
adapter is required for vent connection.
● Tighten the clamp around the collar.
● Inspect the inside of the adapter to
verify that the collar and adapter are
sealed. If more sealant is required,
apply sealant to a flat tool, then spread
around the collar edge on inside of
adapter.
Exhaust
Flow
Read the following instructions before
installation.
● Test fit the adapter over the water
heater collar before proceeding. Adjust
clamp as needed.
Vent Adapter
RTG20002B
Clamp
A
● Ensure that the clamp does not interfere
with the damper shaft.
High Temp.
Sealant
● With an alcohol wipe, clean inside
surface "A" of adapter and outside
surface of "B" of heater collar.
Collar
B
NOTICE: Follow the vent adapter
manufacturer’s instructions
Water Heater
● Apply 1/4" (6 mm) wide bead of high
temperature silicone (500°F) (260°C)
around outside of heater collar "B".
● Slide adapter end "A" down over heater
collar "B" as far as it will go.
Draining the Condensate
In order to prevent condensate from
draining back into the water heater, a
condensate trap and drain must be
installed in a horizontal vent section as
close as practical to the water heater vent
connection, uless the water heater is
vented horizontally with a 1/4” per foot
DOWNWARD slope towards the vent
terminal as shown below.
Condensate is known to be acidic; refer to
local, state (provincial) or federal codes
for proper handling and discharge
methods.
1/4” per foot downward slope
3” (8 cm) Clearance
3’
(91 cm)
Max
Support
Hanger
Vent
Adapter
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the water heater.
AREA WHERE TERMINAL IS NOT PERMITTED
AIR SUPPLY INLET
VENT TERMINAL
V
X
Horizontal Vent Terminal Location
The following information should be used for determining the proper location of the vent terminal
for indoor and outdoor tankless water heaters.
1
2
Canadian Installations
US Installations
A= Clearance above grade, veranda,
porch, deck or balcony.
12 inches (30 cm) above anticipated
snow level.
12 inches (30 cm) above anticipated
snow level.
B= Clearance to window or door that
may be opened.
6 inches (15 cm) for appliances < 10,000
Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (30 cm) for
appliances > 10,000 Btuh (30kW), 36
inches (91 cm) for appliances > 100,000
Btuh (30kW).
4 feet (1.2 m) below or to side of
opening; 1 foot (300 mm) above opening.
C= Clearance to permanently closed
window.
*
*
D= Vertical Clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm)
from the center line of the terminal.
4 feet (1.2 m)
4 feet (1.2 m)
E= Clearance to unventilated soffit.
F= Clearance to outside corner.
G= Clearance to inside corner.
*
*
*
*
*
*
M = Clearance under veranda, porch,
deck or balcony.
3 feet (91 cm)
3 feet (91 cm)
1 In accordance with current CAN/CGA-B149 Installation Codes.
2 In accordance with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code.
1
2
Canadian Installations
US Installations
H = Clearance to each side of center line
*
3 feet (91 cm) within a height 15 feet
(4.57 m) above the meter/regulator
assembly.
extended meter/regulator assembly.
above
I = Clearance to service regulator vent
outlet.
3 feet (91 cm)
*
J = Clearance to nonmechanical air
supply inlet to the combustion air
inlet to any building or other
appliance.
4 feet (1.2 m) below or to side of
opening; 1 foot (300 mm) above opening.
6 inches (15 cm) for appliances < 10,000
Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (30 cm) for
appliances > 10,000 Btuh (30kW), 36
inches (91 cm) for appliances > 100,000
Btuh (30kW).
6 feet (1.83 m)
3 feet (91 cm) above if within 10 feet (3
m) horizontally.
K = Clearance to mechanical air supply
inlet.
L = Clearance above paved side walk or
7 feet (2.13 m)
7 feet (2.13 m)
paved driveway located on public
property.
M = Clearance under veranda, porch,
deck or balcony.
Not Allowed
Not Allowed
+
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and
serves both dwellings.
*
If clearances are not specified then follow local installation codes and the requirement of the gas supplier.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the water heater:
Additional Considerations
Outdoor Water Heater
Do Not install vent terminal under any patio or deck.
To help prevent moisture from freezing on walls and under
eaves, do not locate vent terminal on the side of a building
with prevailing winter winds.
Caulk
Rising moisture will collect under eaves
(1.8 m)
To help prevent water lines from freezing do not locate vent
terminal on the side of a building with prevailing winter
winds.
6'
If soffit vent is too close,
6' (1.8 m)
block off and install new
caulk zone or
vent at another location
to edge of
window etc., starting
within 6' (1.8 m)
Inside
corner
6' (1.8 m) caulk
zone
Do Not terminate vent directly on brick or masonry surfaces.
A rust-resistant sheet metal backing plate
(2 x 2 feet) (60 x 60 cm) is recommended behind vent. (See
illustration.)
Caulk
Caulk
Do Not locate vent terminal too close to shrubbery, as flue
gasses may damage them.
4'
(1.2 m)
Caulk all cracks, seams and joints within six (6) feet (1.8 m)
of vent terminal.
Caulk around thimble face plate for weather tight seal.
Indoor Water Heater
All painted surfaces should be primed to lessen the chance of
physical damage. Painted surfaces will require maintenance.
Caulk
Insulate vent pipe of indoor water heaters exposed to cold
conditions (attics, crawl spaces, etc.) with inflammable
material to help prevent moisture from accumulating in vent
pipe.
Rising moisture will
collect under eaves.
If soffit vent is too close,
block off and install new
6’
Do Not extend exposed vent pipe of indoor water heaters
outside of building.
vent at another location.
(1.8 m)
Inside
Corner
Caulk
6’ (1.8 m)
Caulk
6’ (1.8 m)
zone or to edge of window
Caulk Zone
Guard vent against accidental contact with people and pets.
etc.,starting within 6’ (1.8 m).
Caulk
RTV silicone caulk
2 ft. sq. (60 x 60 cm) sheet metal plate on
brick or masonary surface, recommended.
4’
(1.2 m)
WARNING: Moisture in the flue gas will condense as it
leaves the vent terminal. In cold weather this condensate can
freeze on the exterior wall, under the eaves and on
surrounding objects. Some discoloration to the exterior of
the building is to be expected. However, improper location
or installation can result in severe damage to the structure
or exterior finish of the building
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Vent Horizontal Wall Thimble Installation
Outer Thimble
Section
Inner Thimble
Section
An approved 4 inch (10 cm) Vent
more caulking.
Horizontal Wall Thimble must be used.
Use 4 hollow wall anchors, at least
1/8” (.32 cm) in diameter and of
The Wall Thimble requires mechanical
support from the wall sufficient to support
any incidental loads on the system. If the
wall is not sufficient enough to support the
Wall Thimble, then appropriate additional
framing and/or blocking is required.
appropriate length for the thickness of
the sheathing, if sheathing is particle
board or other composite material. Use
4 #10x1-1/4” wood screws for plywood,
solid wood sheathing or members. Use
suitable masonry anchors when passing
through solid masonry walls. Reinstall
the decorative sheathing around the
Wall Thimble. This assembly may be
painted to match the exterior decor.
Side View
Inner Wall
INSTALLATION PROCEDURE:
Prepare an opening for the Wall Thimble
in the wall. The opening must be
6-1/2 inches (16 cm) in diameter for a
4 inch (10 cm) vent system.
Outer Thimble
Section
Inner Thimble
Section
90° Elbow
Vent
Pipe
● Attach a screened 4 inch (10 cm)
termination fitting to the female end of
a vent section or slip connector. Use the
method described in the Venting
installation instructions (page 13). Slide
the vent in through the outside of the
Thimble and seal the annular space
with a thick bead of caulk.
90° termination
with screen
Outer
Wall
If there are not sufficient support members
to secure the Wall Thimble or if there is a
semirigid foam insulation layer under the
sheathing, appropriate fasteners must be
used to secure the Wall Thimble to the
support members.
Caulk for
weather seal
Water
Heater
Outside Wall
The Wall Thimble is designed to adapt to
any wall thickness from 3-1/2” (9 cm) to
6” (15 cm) thick. If the wall is thicker
than 6” (15 cm) the Wall Thimble may be
extended using a piece of 6” (15 cm)
diameter snaplock or welded seam
● Slide the interior portion of the Thimble
into the inside hole. Be certain the
interior and exterior Thimble halves
overlap at least 1” (2.5 cm). If
insufficient overlap exists, extend the
interior portion with single wall
galvanized pipe.
Mounting
Brackets
Side View
galvanized pipe up to 6” (15 cm) long.
Select the larger diameter half of the Wall
Thimble for the outside of the wall.
WARNING: Use UL
approved Category III vent
material only. No other
vent material is permitted.
● Secure the Wall Thimble to the interior
sheathing using suitable fasteners.
● Apply a continuous bead of high
quality silicone or silicone/latex caulk
on the inside of the outer flange. This
will be the only weather seal to keep
moisture outside the building. Ensure a
sufficient seal is made.
● Secure the vent section or slip
connector that protrudes through the
Wall Thimble to the rest of the vent
system as described in the Venting
installation instructions (page 13).
CAUTION: Follow the
vent manufacturers
installation instructions as
design might vary from
manufacturer to
● Position this portion of the Wall
Thimble into the prepared hole from the
outside. Secure the assembly into the
prepared opening using fasteners as
indicated by sheathing or structural
members, sealing the screw heads with
manufacturer.
1/4” per foot upward slope
1/4” per foot downward slope
3” (8 cm) Clearance
3” (8 cm) Clearance
3’
(91 cm)
Max
3’
(91 cm)
Max
Support
Hanger
Support
Hanger
Condensate
Trap
To Drain. Dispose of
Vent
Adapter
Vent
Adapter
condensate in accordance
to local codes
Typical Horizontal Termination
w/ ¼” per foot DOWNWARD Slope
Typical Horizontal Termination
w/ ¼” per foot UPWARD Slope
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the water heater.
Vertical Vent Termination Location
The location of the vent terminal depends on the following
Small (6” min) (15 cm)
minimum clearances and considerations (see illustration):
section of vent
Elbow
Minimum twelve (12) inches (30 cm) above roof.
Minimum twelve (12) inches (30 cm) above
anticipated snow level.
Maximum twenty-four (24) inches (60 cm) above
roof level without additional support for vent.
Vent Pipe
Through Roof
Min. 12" (30 cm)
Above Roof
Four (4) feet (1 m) from any gable, dormer or other
roof structure with building interior access (i.e., vent,
window, etc.).
Min. 12" (30 cm)
Above Anticipated
Snow Level.
Termination Elbow
w/ Protective Screen
Ten (10) feet (3 m) from any forced air inlet to the
building. Any fresh or make-up air inlet such as a
dryer or furnace area is considered to be a forced air
inlet.
Max. 24" (60 cm)
Above Roof (Without
Additional Support)
Vertical Vent Installation
Once the vent terminal location has been
determined, make a hole through the roof
and interior ceiling to accommodate the
vent pipe. Complete the vent pipe
Install adequate flashing where the vent
pipe passes through the roof. Determine
the vent terminal height and install the
vent pipe accordingly. Refer to the
installation to the water heater's vent
connector fitting on the water heater vent
illustration above for proper vent terminal
height. Connect vent elbow on to vertical
collar outlet. Support vertical or horizontal pipe through roof. Connect short piece of
runs as previously mentioned. If required,
use silicone sealant at the point the vent
connector joins the water heater.
vent pipe (approximately 6" long (15 cm))
to elbow, and the terminal elbow with the
protective screen.
Rain Cap
Storm
Storm
Collar
Collar
Adjustable
Adjustable
Roof Flashing
Roof Flashing
Roof Jack
Roof Jack
Support
Clamp
Firestop
Support
Clamp
Firestop
Chase Requires
6” (15 cm) Clearance
to Combustibles
Chase Requires
6” (15 cm) Clearance
to Combustibles
1/4” per foot upward slope
1/4” per foot upward slope
3” (8 cm) Clearance
3” (8 cm) Clearance
Firestop
Firestop
3’
3’
(91 cm)
Max
Support
Hanger
(91 cm)
Max
Support
Hanger
Condensate
Trap
Condensate
Trap
To Drain. Dispose of
condensate in accordance
to local codes
To Drain. Dispose of
condensate in accordance
to local codes
Vent
Vent
Adapter
Adapter
Alternate
Vertical Vent Termination with Rain Cap
Standard Vertical Vent Termination
18
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Field wiring connections and electrical grounding must comply with local
codes, or in the absence of local codes, with the latest edition of the National Electrical Code,
ANSI/NFPA 70, or in Canada, Canadian Electrical Code, CSA C22.1 Part 1.
Remote Control Installation
One (1) remote control is provided with
the water heater.
● The MAXIMUM distance between the
water heater and the remote control
installation location is limited to 195
feet (59 m) of wire.
NOTICE: The provided
remote control will allow
a maximum temperature
setting of 120°F (49°C).
Temperatures of up to
180°F (82°C) can be
achieved with dip switch
adjustment. Only qualified
service personnel should
perform this adjustment.
The following are considerations for
determining the location of the remote
control(s):
NOTICE: Only main remote control
(UMC-117) and manifolding control can
be connected to the water heater.
● DO NOT install any remote control
outdoors or areas were it can come in
contact with water.
No other manufacturer’s controls are
suitable for use with this water heater.
●
●
Place remote control out of children’s reach.
DO NOT attempt to disassemble the
remote control.
The remote control can be installed in
convenient locations such as the kitchen,
laundry room, utility room, or directly beside
the indoor water heater.
● Avoid areas where the remote control
may be exposed to heat, e.g. stove
ranges or heaters.
● Avoid areas where the remote control
may be subjected to oil and/or steam
from cooking.
● Avoid areas where chemical agents
(such as thinner, benzine and alkaline)
are used.
● Avoid areas of direct sunlight.
Base Plate
MAIN
Control
PRIORITY
°F
PO
WER
ON/OFF
Mounting Screw x 2
Control screw
Remote Control
Model Number
Remote Control
Description
Temperature
Availability
Set Point Range
100°F - 120°F
Factory Default
(38°C)-(49°C)
UMC-117
MAIN
125°F - 180°F
(52°C)-(82°C)
With Dip Switch
Adjustment
NOTICE:
Manifolding Applications: Certain Commercial installations may require more than
one water heater piped together in a manifold to supply enough capacity for high
temperature and/or water flow applications. Special manifolding control kits are
available for operating multiple heaters together. Contact your dealer for details.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the Main Remote Control.
WARNING: Field wiring connections and electrical grounding must comply with local
codes, or in the absence of local codes, with the latest edition of the National Electrical Code,
ANSI/NFPA 70, or in Canada, Canadian Electrical Code, CSA C22.1 Part 1.
Remote Control Installation
NOTICE: Extension cable
Connecting the MAIN (UMC-117 )
remote control to the water heater:
Connecting the remote control to the
water heater:
can be any Type-T 18 AWG
wire similar to a thermostat
wire and need not be
● Drill a 1” (2.5 cm) to 1.5” (4 cm) hole
at the proposed control location.
● Ensure that the power to the water
heater has been disconnected.
polarity sensitive.
● Install the extension cable between the
location of the remote control and the
water heater.
● Remove the front cover of the water
Do Not apply sealant to the
remote control cable.
heater.
● Insert the remote control extension
cable throught the hole at the bottom
right hand corner of the water heater.
● Remove the base plate from the control.
It is not recommended to
have wiring exposed.
● Draw the remote control extension
cable through the central in the base
plate.
● Connect the wires to the terminals on
the top right hand side of the Printed
Circuit Board (PCB) as shown in
illustration to the left.
Remote Control
● Fix the base plate to the wall using
Connection Terminals
suitable screws and wall anchors.
PCB
Ensure the projections on the base plate NOTICE: The remote control wire
are pointing upwards.
connection terminals are not polarity
sensitive.
● Connect the remote control cables to
the extension cable from the water
heater.
● Firmly tighten the terminal screws.
● Secure the remote control extension
cable using the appropriate clamp.
● Place the remote control over the base
plate. Ensure the projections in the
base plate fit into the housings in the
remote control.
● Replace the front cover of the water
heater.
● Switch on the power supply to the
water heater.
● Fix the control to the base plate at the
bottom of the remote control using the
screw provided.
● Ensure proper operation of the remote
control and water heater.
● Proceed to “Connecting the remote
control to the water heater”, to
complete installation.
Clamp
NOTICE: If water heaters are in a
manifold system the main remote control
connected to the mainfold controller
(MIC-180) has priority over remote controls
connected to the water heaters.
18 AWG
Gas Valve
Extension
Cable
Projections
Remote
Control
Extension
Cable
Wall
Penetration
Suitable
Wall Anchors
Control
Screw
Base Plate
Screws
20
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: Field wiring connections and electrical grounding must comply with local
codes, or in the absence of local codes, with the latest edition of the National Electrical Code,
ANSI/NFPA 70, or in Canada, Canadian Electrical Code, CSA C22.1 Part 1.
Electrical Connection
POWER CORD (Indoor water heaters
only):
HARDWIRING THE ELECTRICAL
CONNECTIONS (Indoor or Outdoor
water heaters):
WARNING: Shock
hazard line voltage is
present. Before servicing
the water heater, turn off
the electrical power to the
water heater at the main
disconnect or circuit
● The electric power supply requirement
for this water heater is 120 VAC/60HZ,
2 Amps.
● Wiring should be carried out by a
qualified electrician in accordance with
local codes.
● The water heater comes with a three (3)
pin power supply cord (INDOOR
MODELS ONLY). Use only a power
outlet with a ground terminal.
● The water heater requires 120 VAC/60Hz
and should be properly grounded.
breaker. Failure to do so
could result in severe
personal injury or death.
● DO NOT connect grounding wire to
water pipes, gas pipes, telephone
cables, lightning conductor circuits and
to grounding circuit of other equipment
that carry a ground-fault interrupter.
● The installation of an electric leakage
breaker is recommended.
CAUTION: Label all
wires prior to
disconnection when
servicing controls. Wiring
errors can cause improper
and dangerous operation.
Verify correct operation
after servicing.
● Keep any excess of the power supply
cord on the outside of the water heater.
● An ON/OFF switch must be provided
and installed for the incoming
120VAC power.
● If local codes require hardwiring, see
instructions for “Hardwiring the
Electrical Connections”.
● Wire the water heater exactly as shown
below. A wiring diagram is also found
inside of the cover panel.
● A green screw is provided in the
junction box for grounding connection.
● Connect the live wire to black leg wire
and the neutral wire to the white neutral
wire.
WATER VOLUME
CONTROL MOTOR
Ground Screw
WIRING DIAGRAM
AIR
MAIN
REMOTE
CONTROL
(UMC-117)
BATH
REMOTE
CONTROL1
(USC1-117)
BATH
REMOTE
CONTROL2
(USC2-117)
LIMITER
MOTOR
INTAKE
FILTER
SWITCH
COLOUR CODE
R:RED
W:WHITE
SW1
SW2
B
R
GR
Y
B
O
W
BR
MAX
BR:BROWN
BK:BLACK
B:BLUE
MIN
BUTTON
W
W
BUTTON
8
FAN
FM
SW3
MOTOR
ON
OFF
DIP SWITCH
8
BK
R
GY:GRAY
7
6
5
4
3
2
1
5
4
3
2
1
ADJUSTER
BUTTON
A
D
2
E
GR:GREEN
O:ORANGE
Y:YELLOW
G/Y:GREEN/YELLOW
GR
Y
F
1
3
2
4
6
W
B
5
4
3
2
1
B
B
R
O
Y
O
G
O
W
2
BR
P
1
LED
M
L
FLAME ROD1
FLAME ROD2
FLAME ROD3
W
R
B
CONNECTOR FOR CHECKING
T
THERMOELECTROMOTIVE FORCE
2
7
6
5
4
3
2
1
1
B
W
1U
GR
WATER BY-PASS
WV
Y
Q
3
GR
SOLENOID VALVE
R
OVER HEAT
LIMITER
W
2
2
BK
BK
R
H
W
3 6
2 5
1
IGNITER
IG
1
1
BKELECTRODE
R
GY
GY
WATER
FLOW
FOR INDOOR
S
4
BK
BR
MODEL ONLY
R
SENSOR
TRANSFORMER
R
4
1
B
Y
W
FUSE(3A)
CIRCUIT
BOARD
I
5 2
6 3
Junction
Box
BK
AC
BK
G/Y
W
BK
W
BK
W
BK
G/Y
100V
FUSE
J
W
(5A)
R
K
GND
R
AC
(BLUE)W
GND
T
H
E
120V
Wire
Connections
W
R
W
W
BK
R
M
O
C
O
U
P
BK
BK
R2
BK
R1
BK
BK
BK
BK
(REDW)
BK
R3
BK
BK
-
+
PSV
W
R4
W
W
SV3
SV2
SV1
SV0
FROST
OHT
UOH
TTE
AAT WIT
MIH ANH
BRE
TLE
EER
HET
EXH
ACE
THR
AM
NI
(REDW)
ANTI-FROST
HEATER
PROTECTION
THERMOSTAT
V
S
S
S
G S
W
W
A
L
V
E
L
O
O
O
AO
L
R
I
R
E
BK
L V
E A
N L
OV
I E
D
L V L V
E A E A
N L N L
OV OV
S L V
E A
EWM
TAI
TS
E M RTM
THE CONNECTORS OF DUAL AND MULTIPLE
ARE INTERAPPLICABLE TO THE BODY
CONNECTORS EACH OTHER.(RED)
N
T
I
S
T
O
R
I
S
T
O
R
I N L
NOV
L I E
E D
On/Off
Switch
GS
FOR INDOOR
MODEL ONLY
ET
RO
R
ET
RO
I E
I E
D
D
R
1
3
2
T
0
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the water heater.
Typical Installation of Indoor Water Heater
Outside Wall
1/4" Per Foot Downward Pitch
90° Elbow
Wall Thimble
Vent Termination
With Protective
Screen
Vent Adapter
PRIORITY
°F
POWER
ON/OFF
Outside Wall
Remote
Control
Manual
Gas Supply Line
Shut-off
Power
Supply
Cord
To Hot Water
Faucet(s)
Valve
Union
Manual Gas
Appliance
Check
Valve
Shut-off
(supplied)
Union
Water Filter
Drain Valve
Relief
Valve
Vacuum Relief Valve
(Not Supplied)
Sediment
Trap
Cap
Cold Water
Supply
Shut-off
Valve
Discharge
Line
(To Suitable Drain)
If required, install per local codes
and valve manufacturer’s
instructions.
6" (15 cm) Air Gap
NOTICE: The National Fuel Gas Code (NFGC) and B149 mandates a manual gas shut-off valve:
See NFGC/B149 for complete instructions. Local codes or plumbing authority requirements may
vary from the instructions or diagrams provided and take precedent over these instructions.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the water heater:
Typical Installation of Outdoor Water Heater
To Hot Water
Faucet(s)
Union
Relief
Valve
Drain Valve
Discharge
Line
(To Suitable Drain)
6" (15 cm) Air Gap
23
Insulation Blankets
Insulation blankets, available to the general
public, for external use on gas water heaters
are not necessary. The purpose of an
insulation blanket is to reduce the standby
heat loss encountered with storage tank
heaters. This water heater does not store
water making an insulation blanket
unnecessary.
shorten the life of the water heater and may
endanger life and property.
WARNING: If local
codes require external
application of insulation
blanket kits the
The manufacturer disclaims any responsibility
for such loss or injury resulting from the use
of such unauthorized devices.
manufacturer’s instructions
included with the kit must
be carefully followed.
CAUTION: If local codes require the
application of an external insulation
blanket to this water heater, pay careful
attention to the following so as not to
restrict the proper function and operation
of the water heater:
The manufacturer’s warranty does not cover
any damage or defect caused by installation,
attachment or use of
any type of energy saving or other
● Do not cover the air inlet, flue outlet, or
operating and warning labels attached to
the water heater or attempt to relocate them
on the exterior of insulation blanket.
unapproved devices (other than those
authorized by the manufacturer) into, onto or
in conjunction with the water heater. The use
of unauthorized energy saving devices may
Hot and Cold Pipe Insulation Installation
Insulate all the
way to the top
NOTICE: The hot and cold
pipes should be insulated as
shown to provide additional
freeze protection.
Gas Inlet
ck Valve
Inlet Pipe
Ht
Waer
Cold Water
For increased energy efficiency, use pipe
insulation. Please install the insulation,
according to the illustrations above,
making sure to insulate all the way to the
top. Do not cover any drain or pressure
relief valve(s).
During Installation of this water heater...........
Do’s
Don’ts
❑
Do follow all installation instructions
❑
Don’t block or restrict Air Intake
convered in this manual.
Opening located bottom left corner of the
water heater.
❑
Do check inlet gas pressure to ensure that
it is within the range specified on the rating
❑
Don’t remove the front cover unless
plate.
absolutely necessary. This should only be
done after being examined by a qualified
service technician.
❑
Do provide adequate air for combustion
and ventilation as discussed in the Use &
Care Manual and the National Fuel Gas
Code (CAN/CGA B149 in Canada).
❑
Don’t install this product where standing
water may occur.
❑
Do maintain proper clearances to
❑
Don’t use pipe dope on water line
combustibles and non-combustibles as
connections and fittings.
specified on the nameplate.
❑
Do ensure that the venting system
complies with the guidelines found in the
Use & Care Manual and National Fuel Gas
Code (CAN/CGA B149 in Canada).
❑
Do contact local gas company to ensure
gas meter and gas piping are adequately
sized.
❑
Do use teflon tape on water line
connections and fittings.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing the water heater:
Installation Check List
E. Gas Supply
A. Outdoor Water Heater Location
❑
Gas type matches rating plate.
❑
❑
Outdoor water heaters must be installed outdoors.
Protected from freezing temperatures.
❑
Gas supply pressure is sufficient for the water
heater.
B. Indoor Water Heater Location
❑
Gas line equipped with shut-off valve, union and
sediment trap.
❑
❑
Close to area of vent termination.
❑
❑
Approved pipe joint compound used.
Indoors and protected from freezing temperatures .
Soap and water solution used to check all
connections and fittings for possible gas leak.
C. Outdoor and Indoor Water Heater Location
❑
Gas Company inspected installation (if required).
❑
Proper clearance from combustible surfaces
observed.
F. Relief Valve
❑
❑
❑
Sufficient fresh air supply for proper operation of
water heater.
❑
Pressure Relief Valve properly installed and
discharge line run to open drain
Air supply free of corrosive elements and
flammable vapors.
❑
Discharge line protected from freezing.
G. Venting (Indoor Water Heaters Only)
Provisions made to protect area from water
damage.
❑
❑
Materials used are as instructed in the manual.
Vent connector(s) pitched downward to termination
(¼" per foot of length minimum) See page 13.
❑
❑
Sufficient room to service heater.
Combustible materials, such as clothing, cleaning
materials, rags, etc. clear of the heater and vent
piping.
❑
Vent connector(s) securely fastened together with
high temperature silicone (500°F) (260°C) and air-
tight.
❑
Water heater is properly attached to the wall.
❑
❑
❑
All vent runs are properly supported.
Vent terminal is properly installed.
Sufficient combustion air is available.
D. Water Supply
❑
❑
❑
❑
❑
❑
Water supply has sufficient pressure.
❑
Maximum and minimum vent lengths are
observed.
Air purged from water heater and piping.
Water connections tight and free of leaks
Water filter is clean and in place.
H. Electrical Wiring
❑
❑
❑
Voltage matches rating plate.
Materials used are as instructed in this manual.
Water heater is properly grounded.
Water pipes are insulated and protected from
freezing.
Supply cord and/or wiring meets all local codes.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Lighting the water heater:
Before operating this water heater, be sure to read and follow the instructions on the label pictured
below and all other labels on the water heater, as well as the warnings printed in this manual. Failure to
do so can result in unsafe operation of the water heater resulting in property damage, personal injury,
or death . Should you have any problems reading or following the instructions in this manual, STOP,
and get help from a qualified person.
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING : If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
OPERATING INSTRUCTIONS
1.STOP! Read the safety information above on this label.
GAS SHUTOFF
VALVE
2.Turn off all electric power to the appliance.
3.Do not attempt to light the burner by hand.
4.Turn the Gas Shutoff Valve located on the outside of the unit
to the "OFF" position.
OPEN
CLOSE
clockwise
5.Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in
the safety information above on this label. If you don't smell gas, go to the next step.
6.Turn the Gas Shutoff Valve located on the outside of the unit counterclockwise
the "ON" position.
7.Turn on all electric power to the appliance.
to
8.If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance"
and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
Turn off all electric power to the appliance if service is to be performed.
Turn the Gas Shutoff Valve located on the outside of the unit clockwise
1
2
.
.
to the "OFF" position.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating the water heater:
Safety Precautions
Do turn off manual gas shut-off valve if water heater
has been subjected to over heating, fire, flood,
physical damage or if the gas supply fails
to shut off.
Do Not store or use gasoline or other flammable
vapors and liquids, such as adhesives or paint thinner,
in vicinity of this or any other appliance.
If such flammables must be used, open doors
and windows for ventilation, and all gas burning
appliances in the vicinity should be shut off including
their pilot lights, to avoid vapors lighting.
Do Not turn on water heater unless water and gas
supplies are fully opened.
Do Not turn on water heater if cold water supply
shut-off valve is closed.
NOTICE: Flammable vapors can be drawn by air
currents from surrounding areas to the water heater.
Do Not allow combustible materials such as
newspaper, rags or mops to accumulate near
water heater.
If there is any difficulty in understanding or following
the Operating Instructions or the Care and Cleaning
section, it is recommended that a qualified person or
serviceman perform the work.
Water Temperature Setting
The temperature of the water in the water
scalding. Be sure to read and follow the
warnings outlined in this manual and on
the label located on the water heater.
!
DANGER: There is a
heater can be regulated by setting the
temperature on the front of the remote
control.
hot water scald potential
if the temperature is set
too high. Households with
small children, disabled, or
elderly persons may require
a 120°F (49°C) or lower
temperature setting to
prevent contact with HOT
water.
Mixing valves are available for reducing
point of use water temperature by mixing
hot and cold water in branch water lines.
Contact a licensed plumber or the local
plumbing authority for further
Safety factors should be considered when
selecting the water temperature setting of
the water heater’s remote control.
The remote control was set at 100°F
(38°C) before the water heater was shipped
from the factory. This is the
information. (See page 4 for more details.)
The chart below may be used as a guide in
determining the proper water temperature
for your home.
recommended starting point.
Water temperatures above 125°F (52°C)
can cause severe burns or death from
Time/Temperature Relationship in Scalds
Water Temperature
Time To Produce a Serious Burn
120°F (49°C)
125°F (52°C)
More than 5 minutes
11/2 to 2 minutes
130°F (54°C)
135°F (57°C)
140°F (60°C)
145°F (63°C)
150°F (66°C)
155°F (68°C)
About 30 seconds
About 10 seconds
Less than 5 seconds
Less than 3 seconds
About 11/2 seconds
About 1 second
Table courtesy of Shriners Burn Institute
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Temperature Setting…
Maximum water temperature occurs while The hottest temperature water will be at
the burner is on. To determine the water
temperature, turn on a hot water faucet
and place a thermometer in the water
stream. Water temperature at the faucet
may vary depending on season and length
of pipe from the water heater.
the hot water faucet closest to the water
heater.
Always remember to test the water
temperature with your hand before use and
remember that hotter water increases the
risk of scald injury.
The factory setting of the remote control
temperature range is between
100°F (38°C) and 120°F (49°C).
Always supervise young children or others
who are incapacitated.
The water heater is equipped with a device
that will shut off the gas supply to the
burner if the water heater exceeds normal
operating temperatures. Refer to the
(Before You Call For Service) section
located near the back of this manual, or
contact your dealer.
The remote control is factory preset to
100°F (38°C).
To turn the remote control ON or OFF,
press the POWER button.
To adjust the temperature to a required
setting , press the UP arrow temperature
button.
!
WARNING: Should overheating occur or
the gas supply fail to shut off, turn off the
manual gas control valve to the appliance.
Pressing the UP or DOWN temperature
adjustment buttons will change the
temperature set point.
If the water heater has been subjected to
fire, flood or physical damage, turn off the
manual gas shut-off valve(s), and do not
operate the water heater again until it has
been checked by qualified personnel.
The temperature set point on the remote
control cannot be increased above 112°F
(44°C) when a hot water faucet is in the
open position.
Notice: The water heater may not operate
with a small water flow. In such case,
increase the water flow. If water heater still
does not operate and hot water faucet is
completely open, increase the temperature
setting on the remote control.
Notice: The remote controller
cannot be turned on when
water is flowing or circulating
through the water heater.
Notice: The factory setting allows
operating temperatures between 100°F
(38°C) and 120°F (49°C). Temperatures
of up to 180°F (82°C) can be achieved
with the MAIN (UMC-117) remote
control and a dip switch adjustment. Only
qualified service personnel should perform
this adjustment. Only factory authorized
remote control(s) should be used.
Priority Indicator
In Use Indicator
(Lit during operation)
PRIORITY
Temperature
Adjustment
Buttons
LED Display
(Displays water
temperature and error
codes)
Notice: Display shows
°F
°F only.
ON/OFF
Indicator
POWER
ON/OFF
Higher (Hotter)
Lower (Cooler)
100 102 104 106 108 110 112 114 116 118 120* 125 130 135 140 150 160 170 180 °F
38 39 40 41 42 43 44 46 47 48 49* 52 54 57 60 66 71 77 82 °C
* Temperatures above 120°F (49°C) can be achieved by adjusting the
dip switch. See page 35 for dip switch adjustment.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Care and cleaning of the water heater:
Routine Preventative Maintenance
DANGER: Before
manually operating the
Properly maintained, your water heater
will provide years of dependable trouble-
free service.
Inspect the area around the water heater to
relief valve, make certain
no one will be exposed to
the danger of the hot water
released by the valve. The
water may be hot enough to
create a scald hazard. The
water should be released
into a suitable drain to
prevent injury or property
damage.
ensure a safe operating environment. Keep
appliance area clear and free from
combustible materials, gasoline, and other
flammable vapors and liquids.
It is recommended that a periodic
inspection of the burner, relief valve, air
intake filter, water filter and venting
system should be made by service
Ensure the unit has not been damaged. If
damage or denting is present, contact a
personnel qualified in gas appliance repair. service personnel to verify proper
operation.
It is suggested that a routine preventive
maintenance program be established and
followed by the user.
Check for any abnormal sounds during
normal operation of the water heater.
At least once a year, lift and release the
lever handle on the pressure relief valve,
located in the hot outlet piping of the
water heater, to make certain the valve
operates freely. Allow several gallons to
flush through the discharge line to an open
drain.
All piping should be checked for gas
and/or water leaks. Refer to page 12 of
this manual for instructions on leak
testing.
!
DANGER: Hotter water
increases the potential for
Hot Water Scalds.
The air intake and cold water supply
filters should be cleaned monthly. Refer to
the “Housekeeping” section for further
NOTICE: If the pressure relief valve on information.
the hot water heater discharges
periodically, this may be due to a
problem in the water system. Contact
the water supplier or your plumbing
contractor on how to correct this. DO
NOT plug the relief valve outlet.
DO NOT operate the water heater if you
feel something is wrong with the unit.
DANGER: Failure to
perform the recommended
Routine Preventative
Maintenance can harm the
proper operation of this
water heater, which can
cause carbon monoxide
dangers, excessive
DO NOT allow children to operate or
otherwise handle the unit.
Notice: After inspection, maintenance,
and/or cleaning, ensure proper operation
Rapid closing of faucets or solenoid
valves in automatic water using appliances by turning on a hot water faucet.
can cause a banging noise heard in a water
pipe. Strategically located risers in the
water pipe system or water hammer
hot water temperatures and
other potentially hazardous
conditions.
arresting devices can be used to minimize
the problem.
Housekeeping
Before performing Housekeeping tasks to
this water heater, turn the unit off and
disconnect the power supply.
HOW TO CLEAN THE WATER FILTER:
● Make sure the unit is OFF and the
electrical power supply has been
disconnected.
!
DANGER: Shock Hazard
Make sure the electrical
power to the water heater is
off to avoid potential serious
injury or damage to
Vacuum around the water heater for dust,
dirt and lint on a regular basis.
● Turn the water supply OFF to the
heater.
Clean the water heater and remote control
by using a damp soft cloth with a few
drops of mild detergent and gently wiping
the surfaces of the unit. Wipe any
components.
● Drain heater. See “Draining The
Water Heater” section on page 31.
● Unscrew the water filter, and slide the
remaining moisture with a dry soft cloth.
filter out.
To ensure sufficient ventilation and
combustion air supply, proper clearances
must be maintained.
● DO NOT tap the filter as it may
!
DANGER: Combustible
deform and/or damage the filter.
materials, such as clothing,
cleaning materials, or
● To remove severe sediment and dirt,
use a soft brush and wash with running
water.
DO NOT block or obstruct the air intake
opening located at the lower left corner of
the water heater. A minimum of 12”
(30 cm) is required between this
combustion air inlet opening and any
obstruction.
flammable liquids, etc., must
not be placed against or next
to the water heater.
● Return the filter to the water heater and
screw in the filter.
● Turn the electrical power supply and
cold water supply ON to the water
heater.
The Air Intake and Water filters should be
cleaned on a monthly basis.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Care and cleaning of the water heater:
Housekeeping continued
CLEANING THE AIR INTAKE
tightening the screw.
!
DANGER: DO NOT attempt
FILTER/AIR FILTER:
to operate the water heater
CLEANING THE WATER HEATER
AND REMOTE CONTROL(S):
without the air intake filter. DO
NOT alter the proving switch to
force the unit to operate without
the air intake filter.
● Make sure the unit is OFF and the
electrical power supply has been
disconnected.
● Make sure the unit is OFF and the
electrical power supply has been
disconnected.
● Unscrew the holding screw to the right
of the filter, and slide the filter down.
Notice: The water heater may
not work if the air intake filter
is severely clogged.
● DO NOT scrub the appliance with a
brush.
● Using a vacuum cleaner, remove any
loose dust particles. DO NOT tap the
filter as it may deform and/or damage
the filter.
● Use only mild soapy water, other
cleaners may damage the surface of the
water heater.
● To remove severe dust, use a soft brush
● DO NOT remove any label including
the rating plate while cleaning or
servicing.
and wash with running water.
● Allow the filter to dry completely
before reinstalling the filter on the
water heater. Be sure to secure the filter
by lining the guide tab in the hole and
● DO NOT splash water on the remote
controls when cleaning.
Venting System Inspection
The venting system of an indoor water
heater should be inspected annually to
ensure all of the vent sections are secure
and air-tight.
Bubbles around a joint connection
indicates a seal leak. Refer to page 13 for
vent sealing instructions.
DO NOT operate the unit if vent system
shows signs of leaking exhaust.
It is recommended that qualified service
personnel familiar with Category III
venting inspect the venting system.
Check to make sure that the air intake and
vent outlet on the OUTDOOR water
heater or the air intake filter and the vent
terminal on the INDOOR water heater has
not been blocked or contain debris.
Check vent connection joint sections with
a solution of soapy water to assure air-
tightness while the unit is operating.
Blue Flame
Burner Inspection
Visually inspect the main burners
annually.
!
CAUTION: For your safety, burner
inspection and cleaning should be
performed only by qualified service
personnel.
Through the sight glass, inspect the burner
flame with the main burner off and inspect
the main burner while firing.
For cleaning, a vacuum cleaner can be
used on the burner.
Proper burner pattern.
If any unusual burner operation is noted,
the water heater should be shut off until
qualified service assistance can be
obtained.
Vacation and Extended Shut-Down
NOTICE: Refer to the Freeze
Protection Section on page 31.
If the water heater is to remain idle for an
extended period of time, the power and
water to the appliance should be turned
off.
After a long shut-down period, the water
heater’s operation and controls should be
checked by qualified service personnel.
The water heater and piping should be
drained if they might be subjected to
freezing temperatures.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Care and cleaning of the water heater:
Draining the Water Heater
Below are instructions for draining water
out of the water heater.
To put the water heater back into
operation after draining, follow the steps
below.
Turn off the switch on the remote
control.
Reinstall the drain plug and water filter.
Close the hot water outlet drain valve.
PRIORITY
Close the gas shut-off valve(s).
°F
POWER
ON/OFF
Open the water shut-off valve and close
again after making sure that water
comes out from hot water faucets.
(This step is to remove air from the
water lines.)
Unplug the power supply cord (or
disconnect breaker) at least 10 seconds
after step #1.
To Hot Water
Faucet(s)
Open all hot water faucets. Before
proceeding to the next step, make sure
that COLD water is coming out of all
hot water faucets.
Plug into an electrical outlet, fully open
the gas shut-off valve and the water
shut-off valve.
Close the water shut-off valve.
NOTICE: The water heater may not
operate unless the above procedure is
followed correctly.
Using a suitable container to catch
Draining the water heater
water, remove the water filter from
heater. Attach a garden hose to the
drain valve installed in the hot water
outlet line and direct the stream of
water to a suitable drain where it will
cause no damage. Leave water heater
as is until next use.
WARNING: Failure
to follow these
instructions while
draining the water
heater can cause serious
damage to the water
heater as well as
personal injury
including scalding.
Freeze Protection
Where the water heater may be exposed to Another method of freeze prevention is by
WARNING: Failure
to drain the water
heater can cause serious
damage to the water
heater as well as
running a small volume of water. Running
water will protect the water heater, piping
and valves.
freezing conditions, even for a short
period of time, be sure to drain all water
from the unit as instructed above.
Follow the steps below to ensure proper
water flow through the water heater and
piping:
Exposure to freezing conditions can occur
from down draft of venting system or
from installation in areas exposed to cold
air.
personal injury.
Turn off the switch on the remote
control.
The water heater is equipped with a Freeze
Protection Electric Heater. As long as the
electricity is supplied to the water heater, it
prevents freezing inside the water heater up
to an ambient temperature of approximately
minus 30°F (-34°C) (without wind
conditions)
NOTICE: DO NOT
unplug the electric
power supply cord for
freeze protection.
Close the gas shut-off valve.
Open the hot water faucet slightly until
a stream of approximately 1/8” (.32 cm)
is flowing. Be sure to check the flow
periodically.
This device only protects the internal
components of the water heater. It does
NOT protect piping and valves. Therefore,
piping and valves should be wrapped with
insulation material as instructed on page 24.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Before You Call For Service…
Troubleshooting Tips
Save time and money! Review the charts on the following pages first and you may not need to call for service.
Problem
Possible Cause
What To Do
Not enough or no hot water.
Water Shutoff valve is not fully
opened.
● Check shutoff valve and open fully.
Hot water faucet is not fully opened.
● Open how water faucet completely.
(The main burner goes off when
incoming water volume is
inadequate.)
Water piping is frozen.
● Allow piping to thaw.
No electricity or water supply is cut
off.
● Check that proper power is being
supplied and/or water supply is
adequate.
Unit is not "ON".
● Turn the unit "ON" by the button
on the remote control.
The temperature may be set too low.
● Increase the temperature setting.
Mixing Valve Malfunctions
(if applicable)
● Check and replace if necessary.
Error code displayed on remote
controller.
● See instructions for Error Code and
if required, contact a dealer for
service.
Not enough water demand.
Water inlet filter clogged.
Fixture aerator is clogged.
● Increase water flow.
● Clean water inlet filter.
● Clean aerator.
Scale build up in heat exchanger.
● Check for error code. If required,
contact a dealer for service.
Hot and cold water lines reversed.
The temperature may be set too low.
● Reverse water connections.
Water not hot enough.
● Check and open the gas valve fully.
The gas valve is not fully opened.
● Call your gas company to verify
the gas meter and gas piping size.
Gas supply pressure is low.
● Call dealer for service.
Bleed over in one of the hot water
fixtures.
● Decrease the temperature setting.
Water too hot.
Temperature is set too high.
● Check shutoff valve and open fully.
Water shutoff valve is not fully
opened.
● Allow more water to flow.
Small amount of water has been
heated.
● Normal operation. There is no need
to call for service.
Fan continues to rotate after hot water This function is to supply hot water
faucet is closed. when the hot water faucet is reopened.
● Normal operation. There is no
need to call for service.
CAUTION: Make certain power to water heater is “OFF” before removing protective cover FOR ANY REASON.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING.
CAUTION: For your safety DO NOT attempt repair of electrical wiring, gas piping, remote control, burners, vent
connectors or other safety devices. Refer repairs to qualified service personnel.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Error Code Guide
When an error code is displayed:
● Close the hot water faucet, turn off the switch on the
remote control.
If the error code is still shown:
● Turn off the hot water faucet and turn off the switch on
the remote control.
● Wait for about 5 minutes before turning the switch on
again.
● Take note of the error code displayed and call the
customer service assistance number in the “If You Need
Service” section of the manual on the back cover.
● Open the hot water faucet.
If the error code remains shown:
Notice: If an error code other than those listed below is
displayed, immediately turn off the hot water faucet, take
note of the error code, turn off the switch on the remote
control and call the customer assistance number.
● Close the hot water faucet and turn off the switch on the
remote control.
● Take the proper action shown below and attempt
operation of the appliance again.
Error Code
Possible Cause
What To Do
11
12
The Gas Shutoff Valve is not opened
completely.
● Open the Gas Shutoff Valve
completely.
Gas Service has been interrupted.
● Contact Gas Utility Company.
● Fill up LP Gas container or
LP Gas is running low. (LP models only)
replacewith a new cylinder of LP Gas.
15
16
The hot water faucet is not opened enough. ● Open the faucet more to secure
enough volume.
The method of restarting the unit after
draining the water from it was not performed
in sequesnce.
● See the section "Draining the Water
Heater"
21
Air intake filter may not be attached, or may ● See the section "Cleaning the Intake
Filter".
Indoor Water Heater Only not be firmly in place.
05
Air intake of the unit and/or vent termination ● Remove any obstructions of the air
may be blocked.
intake or vent termination.
(Every 60 seconds you hear
an alarm or when the faucet is
closed, the alarm stops.)
Ventilator or other vents of the room may be
blocked.
● Clean the air intake of any dust or
grease build up.
The air inside the room may be
contaminated due to long use of a fireplace
or spaceheater.
● Open a window or vent to keep the
air inside the room fresh.
Indoor Water Heater Only
● Lower the level of the ventilation of
Heavy ventilation by other equipment or
appliances causing the lack of air intake to
the water heater.
other equipment or appliances.
● Avoid direct contact from steam.
Air shortage may be caused by too much
steam in the unit.
● Clean the air intake filter.
Air intake filter is clogged.
13
If the error code is still displayed after
● Please contact a dealer for service.
Indoor Water Heater Only taking the above steps.
1L
Water heater has build up of lime deposits.
● Contact a dealer for service.
99
Decrease of blower motor ventilation
● Clean any blockage from heat
exchanger fins and/or blower motor
Outdoor Water Heater Only amount. (Operation Stops)
CAUTION: Make certain power to water heater is “OFF” before removing protective cover FOR ANY REASON.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING.
CAUTION: For your safety DO NOT attempt repair of gas piping, remote control, burners, vent connectors or other
safety devices. Refer repairs to qualified service personnel.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Replacement Parts.
Indoor Water Heater
Instructions For Placing a Parts Order
Address parts orders to the distributor or store
from where the water heater was purchased.
Part description (as noted below) and
number of parts desired.
WARNING: For your
safety, DO NOT attempt to
disassemble this unit for
any reason.
CAUTION: For your safety, DO
NOT attempt repair of electrical wiring,
gas piping, burners, vent connectors
or other safety devices. Refer repairs
to qualified service personnel.
All parts orders should include:
The model and serial number of the
water heater from the rating plate.
Specify type of gas (natural or LP) as
marked on the rating plate.
Unit Cover Panel
Heat Exchanger
Thermistor
Heat Exchanger
Burner Assembly
Cover
Burner
(w/ sight glass)
Assembly
(with ODS)
Ignitor
Flame Rod/
Electrodes
.
Water Flow
Solenoid
Proving Switch
Blower
Motor
Transformer
PC Board (PCB)
5A (250V) Fuse
3
2
3
4
Inlet Thermistor
Outlet
Thermistor
Gas Valve
Assembly
3A (250V)
Fuses
Water Filter
Outdoor Water Heater
Unit Cover Panel
Heat Exchanger
Thermistor
Heat Exchanger
Burner Assembly
Cover
Burner
Assembly
(w/ sight glass)
Ignitor
Flame Rod/
Electrodes
Water Flow
Solenoid
Blower
Motor
Transformer
N
PC Board (PCB)
5A (250V) Fuse
3
3
Inlet Thermistor
Outlet
Thermistor
Gas Valve
Assembly
3A (250V)
Fuses
Water Filter
34
Download from Www.Somanuals.com. All Manuals Search And Download.
The content on this page is intended for use by qualified
installation/service personnel ONLY.
WARNING: Improper adjustment, alteration,
!
DANGER: Hotter water increases
service or maintenance can cause property damage,
the potential for Hot Water SCALDS.
personal injury, or death.
Temperature Setting DIP Switch Adjustment
Required adjustment for up to 180°F (82°C) water temperature settings
Time/Temperature Relationship in Scalds
Water Temperature
Time To Produce a Seroius Burn
120°F (49°C)
125°F (52°C)
130°F (54°C)
135°F (57°C)
140°F (60°C)
145°F (63°C)
150°F (66°C)
More than 5 minutes
1 ½ to 2 minutes
About 30 seconds
About 10 seconds
Less than 5 seconds
Less than 3 seconds
About 1 ½ seconds
About 1 second
!
WARNING: Refer to scald potential warnings on page 4 before
making adjustment. Changing this setting is done at your own risk.
DO NOT alter the #4 DIP Switch if the setting of up to 180°F (82°C) is
not required.
Follow the instructions below if it is determined that a setting of up to
180°F (82°C) is required.
●
●
●
Turn off remote control. Turn off the gas and water shutoff valves.
Remove the front cover.
155°F (68°C)
Table courtesy of Shriners Burn Institute
Find the DIP Switch #4 located at the top left hand side of the PCB. (See
illustration to the right for DIP Switch location)
ON
2
3
4
1
●
●
●
Change the DIP Switch #4 setting to the “ON” position. DO NOT alter any
other DIP Switch. The LED on the PCB is flashing. At the same time, the
display of the Main Remote Control starts to flash.
2
3
4
1
SW1
SW2
ON
SW3
1
2
3
4
1
2
3
4
Press the “Max” button on the left hand side of the PCB for more than 1
second. The LED on the PCB starts illuminating continuously. At the same
time, the display of the Main Remote Control is on continuously.
Change the DIP Switch #4 setting back to the “OFF” position. DO NOT alter
any other DIP Switch. The LED on the PCB will stop illuminating. At the
same time, the display of the Main Remote Control will turn off.
Location of DIP Switches on PC Board.
ON
●
●
●
Attach the unit’s front cover.
4
2
3
1
Turn on the remote control, gas and water shutoff valves.
Check and ensure safe operation and performance of the water heater.
As set from factory
See steps below to LIMIT maximum water temperature setting to 120 (49°C).
Follow first four bullets points listed above, then continue as listed below:
ON
4
2
3
1
●
Press the “Min.” button on the left hand side of the PCB for more than 1
second. The LED on the PCB starts illuminating continuously. At the same
time, the display of the Main Remote Control is on continuously.
Setting during adjustment
to DIP Switch #4
for temperature.
●
Change the DIP Switch #4 setting back to the “OFF” position. DO NOT alter
any other DIP Switch. The LED on the PCB will stop flashing. At the same
time, the display of the Main Remote Control turn off.
ON
4
2
3
1
●
●
●
Attach the unit’s front cover.
Setting after adjustment
to DIP Switch #4
Turn on the remote control, gas and water shutoff valves.
“Max”
Button
for temperature.
Check and ensure safe operation and
performance of the water heater.
LED
SW1
SW2
ON
“Min.”
Button
SW3
1
2
3
4
1
2
3
4
DIP
Switches
35
Download from Www.Somanuals.com. All Manuals Search And Download.
IF YOU NEED SERVICE
1. Should you have any questions about your new water heater, or if it requires
adjustment, repair, or routine maintenance, it is suggested that you first contact
your installer, plumbing contractor or previously agreed upon service agency. In
the event the firm has moved, or is unavailable, refer to the telephone directory,
commercial listings or local utility for qualified service assistance.
2. Should your problem not be solved to your complete satisfaction, you should
then contact the Manufacturer’s National Service Department at the following
address:
2600 Gunter Park Drive
Montgomery, Alabama 36109-1413
Phone: 1-800-432-8373.
When contacting the manufacturer, the following information will be requested:
a. Model and serial number of the water heater as shown on the rating plate attached
to the front panel of the heater.
b. Address where the water heater is located and physical location.
c. Name and address of installer and any service agency who performed service on
the water heater.
d. Date of original installation and dates any service work was performed.
e. Details of the problem as you can best describe them.
f. List of people, with dates, who have been contacted regarding your problem.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
|