Gas Fireplaces
P48 Gas Fireplace
P48 Zero Clearance Direct Vent Gas Fireplace
Model
P48-NG2
P48-LP2
Fuel Type
Natural Gas
Propane
Minimum Supply Pressure
Manifold Pressure - High
Manifold Pressure - Low
Orifice Size
5” W.C. (1.25 kPa)
3.8” W.C. (0.95 kPa)
1.1” W.C. (0.27 kPa)
#27 DMS - 0-4500ft
29,000 BTU/h (8.49 kW)
51,000 BTU/h (14.94 kW)
5” Inner / 8” Outer
12” W.C. (3.00 kPa)
11” W.C. (2.74 kPa)
3.3” W.C. (0.82 kPa)
#47 DMS
Minimum Input
26,000 BTU/h (3.07 kW)
48,000 BTU/h (6.30 kW)
5” Inner / 8” Outer
Maximum Input
Vent Sizing
Approved Venting Systems
Flex Vent Systems:
FPI AstroCap™ Flex Vent
Rigid Pipe Vent Systems:
Simpson Dura-Vent® Direct Vent GS
B
A
L
C D
F
Top Header
Drywall
(or other
facing)
H
E
A
11" (279mm)
dia. Hole through
wall Vent.
Unit Dimensions
Description
P33
A
B
C
D
E
F
Front Face Width
Rear Firebox Width
Front Face Height
Height w/ Standoff
Unit Depth
48” (1219mm)
34-1/2” (876mm)
41” (1041mm)
47” (1193mm)
23-1/4” (324mm)
40” (1016mm)
G
I
M
Firebox Height
Framing Dimensions Description
P33
J
G
Framing Width
48-1/2” (1232mm)
47-1/2” (1207mm)***
H***
Framing Height***
29-3/4” (756mm) Vertical Rise
I
Framing Depth
26-1/4” (667mm) No Vertical Rise
N
J
Corner Wall Length
57-5/8” (1464mm)
81-1/2” (2070mm)
K
Corner Facing Wall Width
Framed Chase Ceiling
O
P
K
N/A - Vertical Rise
50” (1270mm) No Vertical Rise
Opening for gas
connection
L
M
Vent Centerline Height
43” (1092mm)
N
O
P
Gas Connection Height
Gas Connection Inset
Gas Connection Width
2” (51mm)
3-3/4” (95mm)
5” (127mm)
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
***Important: Framing height requires consideration of the hearth
depth. Dimension H = H + the thickness of installed hearth.
June 2007 Regency Product Specifications Book
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Fireplaces
P48 Gas Fireplace
Regency Direct Vent System (Flex)
Snorkel Terminations
Horizontal Terminations Only
Snorkel Terminations:
These venting systems, in combination with the P48 Direct Vent Gas
Fireplace, have been tested and listed as a direct vent heater system
by Warnock Hersey. The location of the termination cap must conform
to the requirements in the Vent Terminal Locations diagram.
For installations requiring a vertical rise on the exterior of the building, 14-
inch and 36-inch tall Snorkel Terminations are available. Follow the same
installation procedures as used for standard Horizontal Termination.
NEVER install the snorkel upside down.
FPI Direct Vent (Flex) System Termination Kits include all the parts
needed to install the P48 using a flexible vent.
FPI Kit #
Length Contains:
#946-618
6 Feet
1) 6-5/8” flexible liner (Kit length)
2) 4” flexible liner (Kit length)
3) spring spacers (3)
Dura-Vent
Snorkel
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
#946-616
10 Feet
7) tube of Mill Pac (1)
8) plated screws (8)
Min. 12"*
(305mm)
9) S.S. screws #8 x 1-1/2” drill point, (4)
10) vinyl siding standoff
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency may be used for Flex
installations.
3) Horizontal sections must be supported every 3 feet.
AstroCap XL
(Part# 946-623/P)
Below Grade Snorkel Installation (Dura-Vent Only)
If the Snorkel Termination must be installed below grade, i.e. basement
application, proper drainage must be provided to prevent water from
entering the Snorkel Termination. Refer to Rigid Pipe Installation
instructions for details. Do not attempt to enclose the Snorkel within the
wall, or any other type of enclosure.
Vinyl Siding
Standoff
Wall Thimble
5” dia.
Flue pipe
8" dia.
Flue pipe
Spring Spacer
Dura-Vent
Snorkel
Alternate Horizontal
Termination Caps
Alternate Snorkel
Termination Cap
Part #1282 (14”)
Part #1281 (36”)
Window
Well
Adequate
drainage
Gravel
If required by the external termination location the listed
alternate termination caps may be used. (Refer to Page 11)
June 2007 Regency Product Specifications Book
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Fireplaces
P48 Gas Fireplace
Rigid Pipe Venting
Horizontal or Vertical Terminations
Vertical
Terminal
2
4
8
14
0
6
10
12
Storm Collar
Flashing
Vinyl Siding
Standoff
40
38
36
34
32
Horizontal
Termination Cap
# 946-623/P
Ceiling Firestop
Wall Thimble
Adj.Pipe Length
Pipe Length
11" - 14-5/8”
Horizontal
Termination Cap
# 946-623/P
90o Elbow
24" Length
Vinyl Siding
Standoff
Wall Thimble
Adj.Pipe Length
30
28
11" - 14-5/8”
45o Elbow
Rigid Pipe Adapter
# 770-994
Alternate Horizontal
Termination Caps
26
24
Alternate Snorkel
Termination Cap
Part #1282 (14”)
Part #1281 (36”)
22
20
18
16
14
12
10
If required by the external termination location the listed
alternate termination caps may be used. (Refer to Page 11)
Venting Arrangements - Vertical
Terminations
Rigid Pipe System
(Propane & Natural Gas)
The P48 is approved for a maximum 40 ft. straight vertical, with Rigid
Pipe vent systems for Propane and Natural Gas.
The lightly shaded area,
, in the diagram shows allowable venting
configurations with a maximum two 45° elbows allowed.
The darker shaded area,
, in the diagram shows allowable venting
8
6
configurations using 45° and one 90° elbow.
•
•
•
Vent must be supported at offsets.
Horizontal sections must be supported every 3 feet.
Firestops are required at each floor level and whenever
passing through a wall.
4
2
0
•
•
Maintain clearances to combustible materials.
Minimum of 1’ pipe section between elbows.
Note: Must use optional flue adapter when using Rigid Pipe (Part
# 770-994).
Max. 10’ (3m)(centerline to centerline)
Minimum 12” (305mm)
64
June 2007 Regency Product Specifications Book
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Fireplaces
P48 Gas Fireplace
Vertical Venting with Two (2) 90° Elbows
- Initial vertical section.
Vertical Venting with Three (3) 90°
Elbows - Initial vertical section.
Two 45° elbows = One 90° elbow
Two 45° elbows = One 90° elbow
Option
A)
V
H
V+ V1
2’ Min.
3’ Min.
4’ Min.
5’ Min.
6’ Min.
Maximum total pipe: length, of
all sections, must not exceed
30 feet.
Option
A)
V
H + H1
3’ Max.
4’ Max.
5’ Max.
6’ Max.
7’ Max.
8’ Max.
V+ V1
4’ Min.
6’ Min.
7’ Min.
8’ Min.
9’ Min.
10’ Min.
Maximum total pipe: length, of
all sections, must not exceed
30 feet.
1’ Min.
2’ Min.
3’ Min.
4’ Min.
5’ Min.
4’ Max.
5’ Max.
6’ Max.
7’ Max.
8’ Max.
2’ Min.
3’ Min.
4’ Min.
5’ Min.
6’ Min.
7’ Min.
Total horizontal sections must
not exceed 8 feet.
Total horizontal sections must
not exceed 8 feet.
B)
B)
C)
C)
Minimum of 1 foot between
90° elbows is required.
Minimum of 1 foot between
90° elbows is required.
D)
D)
E)
E)
F)
Vertical Venting with Two (2) 90° Elbows
- Initial horizontal section.
Vertical Venting with Three (3) 90°
Elbows - Initial horizontal section.
Two 45° elbows = One 90° elbow
Two 45° elbows = One 90° elbow
Option
A)
H + H1
2’ Max.
3’ Max.
4’ Max.
5’ Max.
6’ Max.
V
Maximum total pipe: length, of
all sections, must not exceed
30 feet.
2’ Min.
3’ Min.
4’ Min.
5’ Min.
6’ Min.
Option
A)
H
V
H + H1
3’ Max.
4’ Max.
5’ Max.
6’ Max.
7’ Max.
V+ V1 Maximum total pipe:
Total horizontal sections must
not exceed 6 feet.
Minimum of 1 foot between
90° elbows is required.
B)
length, of all sections,
1’ Max.
2’ Max.
3’ Max.
4’ Max.
5’ Max.
1’ Min.
2’ Min.
3’ Min.
4’ Min.
5’ Min.
3’ Min.
5’ Min.
7’ Min.
9’ Min.
11’ Min.
must not exceed 30
feet.
C)
B)
Total horizontal sections
must not exceed 7
feet.
D)
E)
C)
Minimum of 1 foot
between 90° elbows
is required.
D)
E)
June 2007 Regency Product Specifications Book
Download from Www.Somanuals.com. All Manuals Search And Download.
65
Gas Fireplaces
P48 Gas Fireplace
•
•
•
Maintain clearances to combustibles.
Venting Arrangements - Horizontal
Terminations
Horizontal vent must be supported every 3 feet.
Firestops are required at each floor level and whenever passing
through a wall.
This diagram shows all allowable combinations of vertical runs with
horizontal terminations, using one 45° and one 90° elbow (two 45º
elbows equal one 90° elbow).
Avent guard should be used whenever the termination is lower than the
specified minimum or as per local codes.
Note: Must use optional flue adapter (Part # 770-994) when using
Rigid Pipe.
Note: FPIDirectVentSystem(Flex)isonlyapprovedforhorizontal
terminations.
Horizontal (Feet)
8
0
2
4
6
18
20
16
10
12
14
16
14
12
10
8
6
4
43” (1092mm)
Minimum
Height
2
0
Requirement
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
66
June 2007 Regency Product Specifications Book
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Fireplaces
P48 Gas Fireplace
Horizontal Venting with Two (2) 90°
Horizontal Venting with Three (3) 90°
Elbows - Initial vertical section.
Elbows - Initial vertical section.
Two 45° elbows = One 90° elbow
Two 45° elbows = One 90° elbow
Option
A)
V
H+ H1
3’ Max.
4’ Max.
5’ Max.
6’ Max.
7’ Max.
8’ Max.
Maximum total pipe: length, of
all sections, must not exceed
30 feet.
Option
A)
V
H
V+ V1
3’ Min.
4’ Min.
6’ Min.
8’ Min.
10’ Min.
12’ Min.
H + H1
4’ Max.
5’ Max.
6’ Max.
7’ Max.
8’ Max.
9’ Max.
Maximum total
pipe: length, of
all sections, must
not exceed 30
feet.
Total horizontal
sections must not
exceed 8 feet.
Minimum of 1
foot between
90° elbows is
required.
1’ Min.
2’ Min.
3’ Min.
4’ Min.
5’ Min.
6’ Min.
2’ Min.
3’ Min.
4’ Min.
5’ Min.
6’ Min.
7’ Min.
1’ Max.
2’ Max.
3’ Max.
4’ Max.
5’ Max.
6’ Max.
Total horizontal sections must
not exceed 8 feet.
B)
B)
C)
C)
Minimum of 1 foot between
90° elbows is required.
D)
D)
E)
E)
F)
F)
Horizontal Venting with Two (2) 90°
Elbows - Initial horizontal section.
Two 45° elbows = One 90° elbow
Option
A)
H
V
H + H1
3’ Max.
5’ Max.
6’ Max.
7’ Max.
8’ Max.
Maximum total pipe: length, of
all sections, must not exceed
30 feet.
Horizontal Venting with Three (3) 90°
Elbows - Initial horizontal section.
Two 45° elbows = One 90° elbow
1’ Max.
2’ Max.
3’ Max.
4’ Max.
5’ Max.
1’ Min.
2’ Min.
4’ Min.
6’ Min.
8’ Min.
Total horizontal sections must
not exceed 8 feet.
B)
C)
Minimum of 1 foot between
90° elbows is required.
Option
A)
H
V
H + H1 + H2 Maximum total pipe:
D)
length, of all sections,
E)
1’ Max.
2’ Max.
3’ Max.
4’ Max.
5’ Max.
6’ Max.
1’ Min.
3’ Min.
5’ Min.
7’ Min.
9’ Min.
11’ Min.
3’ Max.
5’ Max.
6’ Max.
7’ Max.
8’ Max.
9’ Max.
must not exceed 30
feet.
B)
Total horizontal sections
must not exceed 7
feet.
C)
Minimum of 1 foot
between 90° elbows
is required.
D)
E)
F)
June 2007 Regency Product Specifications Book
Download from Www.Somanuals.com. All Manuals Search And Download.
67
|