TM
Owners &
LIBERTY L676E Gas Fireplace
Installation Manual
Unit requires 120V to
operate. See “Wiring Diagram”
section in manual for more
details. Receptacle is included
with manual package.
MODELS: L676E-NG Natural Gas L676E-LP Propane
FOR YOUR SAFETY
WARNING:
What to do if you smell gas:
Iftheinformationintheseinstructionsarenotfollowedexactly,
a fire or explosion may result causing property damage,
personal injury or loss of life.
ꢀ Do not try to light any appliance
ꢀ Do not touch any electrical switch:
do not use any phone in your
building.
ꢀ Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
ꢀ If you cannot reach your gas
supplier, call the fire department.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
03/14/08
918-621a
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
High Elevation .............................................................26
Gas Line Installation....................................................26
Pilot Adjustment...........................................................26
Gas Pipe Pressure Testing..........................................26
SIT 845 Valve Description ...........................................26
Aeration Adjustment ....................................................26
Back-Up Battery Installation........................................27
Brick Panel Installation................................................28
Log Set Installation......................................................30
Wiring Diagram ...........................................................32
SAFETY LABEL
Copy of Safety Decal.....................................................4
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)............................5
UNIT DIMENSIONS
OPERATING INSTRUCTIONS
Unit Dimensions ............................................................6
Gas Control Valve........................................................33
Matching Remote Handset & Control Box ID Code ....33
Operating Instructions .................................................33
First Fire ......................................................................33
Lighting Procedure ......................................................34
Shutdown Procedure...................................................34
Normal Operating Sounds of Gas Appliances.............34
Operation During Power Outage.................................34
Backup Battery............................................................34
Copy of Lighting Plate Instructions..............................35
Maintenance Instructions ............................................36
General Vent Maintenance..........................................36
Log Replacement ........................................................36
Glass Gasket...............................................................36
INSTALLATION
Important Message ......................................................7
Before You Start ............................................................7
General Safety Information ...........................................7
Installation Checklist......................................................7
Manufactured Mobile Home Additional Requirements ..8
Locating Your Gas Fireplace .........................................8
Heatwave Duct Kit ........................................................8
Heat Release Kit ..........................................................8
Hearth Requirements ....................................................8
Clearances ....................................................................9
Mantel Clearances ......................................................10
Mantel Leg Clearances ...............................................10
Framing & Finishing ....................................................11
Unit Assembly Prior To Installation ..............................12
Top Standoff Assembly ........................................12
Side Nailing Strips ...............................................12
Finishing Template.......................................................12
Venting Introduction.....................................................13
Vent Restrictor Position...............................................13
Exterior Vent Termination Requirements.....................14
Venting Arrangements ................................................15
Horizontal Termination (Flex)...............................15
Rigid Pipe Venting Systems ........................................16
Basic Horizontal & Vertical Terminations .............16
5” x 8” Rigid Pipe Cross Reference Chart...................17
Venting Arrangements ................................................19
Allowable Horizontal Terminations.......................19
Venting Arrangements ................................................22
Allowable Vertical Terminations ...........................22
Unit Installation with Horizontal Termination................23
Unit Installation with Vertical Termination ....................24
Horizontal Termination with Flex Vent System ............25
MAINTENANCE
Door Glass ..................................................................36
Glass Replacement .............................................36
Back-Up Battery Replacement....................................37
Control Box Replacement ...........................................37
Valve Tray Replacement..............................................39
PARTS LIST
Main Assembly ............................................................42
Burner & Log Assembly...............................................43
WARRANTY
The Warranty: Limited Lifetime ...................................47
Regency® L676E Direct Vent Gas Fireplace
3
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY LABEL
This is a copy of the label that accompanies
each L676E-NG and L676E-LP Direct Vent
Gas Fireplace. We have printed a copy of the
contents here for your review. The safety label
is located on the right hand side of the unit,
visible when the exterior right side brick panel
is removed.
NOTE: Regency® units are constantly being
improved. Check the label on the unit and if
there is a difference, the label on the unit is
the correct one.
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfitter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, flexible
connectors shall not exceed 36 inches in
length.
For the State of Massachusetts, the appli-
ances individual manual shut-off must be a
t-handle type valve.
The State of Massachusetts requires the
installation of a carbon monoxide alarm in
accordance with NFPA720 and a CO alarm
withbatterybackupinthesameroomwhere
the gas appliance is installed.
Regency® L676E Direct Vent Gas Fireplace
4
Download from Www.Somanuals.com. All Manuals Search And Download.
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
Regency® L676E Direct Vent Gas Fireplace
5
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT DIMENSIONS
Regency® L676E Direct Vent Gas Fireplace
6
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
12) Installationandanyrepairstothisappliance
should be done by an authorized service
person.Aprofessionalservicepersonshould
be called to inspect this appliance annually.
Make it a practice to have all of your gas
appliances checked annually.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN
THEY ARE IN THE SAME ROOM AS
THE APPLIANCE.
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The L676E Direct Vent Fireplace must be
installed in accordance with these instructions.
Carefully read all the instructions in this manual
first.Consultthe"authorityhavingjurisdiction"to
determine the need for a permit prior to starting
the installation. It is the responsibility of the
installer to ensure this fireplace is installed in
compliancewithmanufacturersinstructionsand
all applicable codes.
CLOTHINGOROTHERFLAMMABLE
MATERIALSHOULDNOTBEPLACED
ON OR NEAR THE APPLIANCE.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
15) The appliance area must be kept clear and
free of combustible materials, (gases and
other flammable vapours and liquids).
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform
with local codes or, in the absence of local
codes,withthecurrentCanadianorNational
Gas Codes, CAN1-B149 or ANSI Z223.1
Installation Codes.
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
BEFORE YOU START
Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of
the following:
2) The appliance when installed, must be
electrically grounded in accordance with
localcodes, orintheabsenceoflocalcodes
with the current National Electrical Code,
ANSI/NFPA 70 or CSA C22.1 Canadian
Electrical Code.
INSTALLATION
CHECKLIST
INSTALLATION AND REPAIR SHOULD
BE DONE BY AN AUTHORIZED
SERVICE PERSON. THE APPLIANCE
SHOULD BE INSPECTED BEFORE
USE AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON.
MORE FREQUENT CLEANING MAY
BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, BEDDING
MATERIAL, ETC. IT IS IMPERATIVE
THAT CONTROL COMPARTMENTS,
BURNERS AND CIRCULATING AIR
PASSAGEWAYS OF THE APPLIANCE
BE KEPT CLEAN.
1) Locate appliance
3) See general construction and assembly
instructions. The appliance and vent should
be enclosed.
a) Room location (Refer to "Locating Your
Gas fireplace" section)
b) Clearances to Combustibles (Refer to
"Clearances" section)
4) This appliance must be connected to the
specified vent and termination cap to the
outsideofthebuildingenvelope. Nevervent
to another room or inside a building. Make
sure that the vent is fitted as per Venting
instructions.
c) Mantel Clearances (Refer to "Mantel
Clearances" section)
d) Framing & Finishing Requirements
(Refer to "Framing & Finishing"
section)
e) Venting Requirements (Refer to
"Venting" section)
5) Inspect the venting system annually for
blockage and any signs of deterioration.
2) Assemble Top Standoffs (Refer to "Unit
Assembly Prior to Installation).
6) Venting terminals shall not be recessed into
a wall or siding.
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES.
3) Install back-up battery. Refer to "Back-up
7) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
Battery Installation" section.
4) Slide unit into place.
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fireplace.
WARNING: FAILURE TO INSTALL THIS
APPLIANCE CORRECTLY WILL VOID
YOUR WARRANTY AND MAY CAUSE
A SERIOUS HOUSE FIRE.
5) Installvent(Referto"Venting Arrangement"
sections).
6) Make gas connections (Refer to "Gas Line
9) Wearglovesandsafetyglassesforprotection
Installation section).
while doing required maintenance.
CHILDREN AND ADULTS SHOULD BE
ALERTED TO THE HAZARDS OF HIGH
SURFACE TEMPERATURES, ESPE-
CIALLY THE FIREPLACE GLASS, AND
SHOULDSTAYAWAYTOAVOIDBURNS
OR CLOTHING IGNITION.
7) Makeelectricalconnections(Referto"Wiring
Diagram" section). NOTE: Unit requires
120V to operate.
10) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for
termination.
8) Test the pilot (Refer to "Pilot Adjustment"
11) Under no circumstances should this
appliancebemodified. Partsthathavetobe
removed for servicing should be replaced
prior to operating this appliance.
section).
9) Test Gas Pressure (Refer to "Gas Pipe
Pressure Testing" section).
Regency® L676E Direct Vent Gas Fireplace
7
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
10) Install standard and optional features. Refer
HEAT RELEASE KIT
to the following sections:
The Heat Release Kit expels warm air from the
fireplace to the outside of the building, allowing
thefireplacetobeoperatedwithlessheatentering
the room. The kit may be used on either the left
or right side.
a)
b)
c)
d)
Interior Brick Panels
Log Set
Exterior Brick Panels
Remote Control - refer to "Matching
Remote Handset & Control Box
ID Code" section.
A) Flat on Wall
B) Flat on Wall Corner
C) Recessed into
Wall/Alcove
SeeHeatReleaseinstallationmanualforcomplete
details and clearances from side only.
11) Final check.
D) Corner
Before leaving this unit with the customer, the
installer must ensure that the appliance is firing
correctly and operation fully explained to
customer.
HEARTH
REQUIREMENTS
Diagram 1
Aminimum29-1/8"(737mm)widex12"(305mm)
deep x 2" (51mm) thick non-combustible hearth
isrequiredifthefinishedfloorisnotflushwiththe
base of the unit. The maximum height between
the finished floor and sub-floor is 1" (25mm).
This includes:
4) This appliance is Listed for bedroom
installations using the standard FireWizard
Remote. Some areas may have further
requirements, check local codes before
installation.
1) Clocking the appliance to ensure the correct
firing rate (rate noted on label 42,000 (NG)
Btu/h, 40,000 (LP) Btu/h) after burning
appliance for 15 minutes.
5) The L676E Direct Vent Gas Fireplace
is approved for alcove installations, see
"Clearances" section for details.
2) Ifrequired,adjustingtheprimaryairtoensure
that the flame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
6) We recommendthatyouplanyourinstallation
on paper using exact measurements for
clearances and floor protection before
actually installing this appliance. Have an
authorized inspector, dealer, or installer
review your plans before installation.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
MANUFACTURED
MOBILE HOME
ADDITIONAL
Note: For vent terminations refer to
"ExteriorVent TerminationLocations"
section.
REQUIREMENTS
HEATWAVE
DUCT KIT
1) Ensure that structural members are not cut
or weakened during installation.
The HeatWave Air Duct Kit increases the
effectiveness of your fireplace by dispersing
warmairfromthefireplacetoremotelocationsin
the same room or other rooms in your home.
2) Ensure proper grounding using the #8
ground lug provided. See "Wiring Diagram"
section.
Up to two kits may be installed on the fireplace.
Please Note: Only 1 HeatWave kit may be
operated at one time.
NOTE:Nohearthisrequiredwhentheunitisflush
LOCATING YOUR
GAS FIREPLACE
with the finished floor as shown below.
The minimum floor clearance must be maintained
from the top surface of the carpet, etc. to the
unit base.
See HeatWave installation manual for complete
details and clearances from side only.
1) When selecting a location for your fireplace,
ensure that the clearances are met.
2) The appliance must be installed on a flat,
solid, continuous surface (e.g. wood, metal,
concrete). This may be the floor, or raised up
on a platform to enhance its visual impact.
The appliance must be installed on a metal
or wood panel extending the full width and
depth of the appliance.
The HeatWave Duct Kit has different
clearance and framing requirements,
check the HeatWave manual for details.
3) The L676E Direct Vent Gas Fireplace can
be installed in a recessed position or framed
out into the room as in A, B, C and D. See
Diagram 1.
Regency® L676E Direct Vent Gas Fireplace
8
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
Clearance to Combustibles from:
Back
Side
Floor
0"
0"
0"
(0mm)
(0mm)
(0mm)
Minimum Clearance from Top of Front Facing:
Mantel min. 16-1/2" (419mm)
Ceiling
52"
(813mm) from top of front facing
Side Wall to Unit:
15"*
(381mm)
Horizontal Vent Clearances to Combustibles:
Top
3"
2"
2"
(76mm)
(51mm)
(51 mm)
Side
Bottom
Vertical Vent Clearances to Combustibles:
All Sides
2"
(51mm)
Alcove Clearances:
Min. Depth
36"
(914mm)
(2134mm)
(2032mm)
Min. Width* 84"
Min. Height 84"
* Alcove side wall must have a minimum of 15" (381mm) clearance on one side.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials
are not adhered to. It is of greatest importance that this
fireplace and vent system be installed only in
accordance with these instructions.
Regency® L676E Direct Vent Gas Fireplace
9
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
MANTEL CLEARANCES
Because of the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing
are shown in the diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible
board.
Note: Ensure the paint that is used
on the mantel and the facing is
"heat resistant" or the paint may
discolour.
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram:
MANTEL LEG
L676 UNIT
Non-combustible
Facing
9" (229mm)
Allowable mantel
leg projection
11" (279mm)
Side wall
15” (381mm)
Regency® L676E Direct Vent Gas Fireplace
10
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
FRAMING & FINISHING
1) Frame in the enclosure for the unit with framing material. The framed
opening for the assembled kit is 45-7/8" high x 48" wide x 24-1/4"
deep (1143mm x H 1219mm W x 616mm D). See Diagram 1. Also
see Diagram 2 for corner installations.
IMPORTANT: Header must be metal stud.
Diagram 1
Diagram 3
2) For exterior walls, insulate the enclosure to the same degree as the rest
of the house, apply vapour barrier and drywall, as per local installation
codes. (Do not insulate the fireplace itself.)
3) The unit does not have to be completely enclosed in a chase. You
must maintain clearances from the vent to combustible materials: See
"Clearances" section. Combustible materials can be laid against the
side and back standoffs and the stove base.
Diagram 2
Non-Combustible Requirements
Regency® L676E Direct Vent Gas Fireplace
11
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
SIDE NAILING STRIPS
UNIT ASSEMBLY
PRIOR TO
FINISHING TEMPLATE
Thesidenailingstripscomeattachedtotheunit.
There are 3 plates, one on the top and bottom
that can be folded out as required.
In order to maintain a clean face; the L676E
allows for a 1/8” in overlap of finishing material,
such as rock or tile, on both the left and right
hand sides of the unit (top and bottom sides do
not allow for an overlap), this overlap must not
be exceeded or the glass door will no longer
open properly.
INSTALLATION
TheTopFacingSupport, theSideNailingStrips
and the 2 Top Standoffs must be correctly
positioned and attached to the top before unit
is slipped into position.
Non-combustible wall board is installed up
to the flanges on all sides of the unit. When
installing any additional facing material use
the Finishing Template (included with the unit)
to ensure that the finishing material does not
exceed the allowable overlap.
TOP STANDOFF ASSEMBLY
The top standoffs are shipped in a flat position
and must be folded into shape and attached.
1) Remove the standoffs from the fireplace
The Finishing Template uses two magnets to
attach itself to the flange on the left or right side
oftheunit(seediagrambelow).Installthefacing
material up to the outside edge (when facing
theunit)ofthefinishingtemplate. Thistemplate
may be discarded after the facing material has
been installed.
top.
2) Takeeachstandoffandbendintothecorrect
shape. Bend up at the bend lines until the
screw holes in the standoff and the pre-
punched screw holes on the fireplace top
line up.
3) Attach the standoff securely to the top
with 2 screws per standoff (on opposite
corners).
Side Nailing Strips shown folded out.
Regency® L676E Direct Vent Gas Fireplace
12
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
To set the vent restriction as indicated in the
venting arrangements diagrams, refer to the
instructions below;
Screws for plugging the holes.
VENTING
(all holes must be plugged with a screw).
INTRODUCTION
Screw holes for fixing the restrictor plate.
1) Remove the glass door.
The L676E uses the "balanced flue" technology
CoAxial system. The inner liner vents products
of combustion to the outside while the outer
liner draws outside combustion air into the
combustion chamber thereby eliminating the
needtouseheatedroomairforcombustionand
losing warm room air up the chimney.
a. Release the 2 door latches on the left
and right side at the top of the firebox.
Note: These flue pipes must not be
connected to any other appliance.
Latch Location
The gas appliance and vent system must be
vented directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Eachdirectventgasappliancemustuseit'sown
separate vent system. Common vent systems
are prohibited.
(factory set for NG units)
Latch
VENT RESTRICTOR
POSITION
Vent restriction is required for certain venting
installations, see the diagrams in the "Venting
Arrangements" section to determine if they are
required for your installation.
b. Swingthedooroutfromthetopandrelease
the hinges on the left and right side of the
door by lifting them up.
(factory set for LP units)
TheVentRestrictorplateislocatedontheinside
top of the firebox.
Hinge
Vent Restrictor Plate
Door
2) Removethescrewsthatholdtheventrestric-
tor plate in place.
3) Adjusttheventrestrictorplatetotherequired
vent restrictor position as per the diagrams
shown.
4) Oncetheventrestrictorplateisintherequired
position, secure with screws.
Regency® L676E Direct Vent Gas Fireplace
13
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
A= Clearance above grade, veranda
, porch, deck, or balcony
*(min. 12"/30cm)
B= Clearance to window or door t
hat may be opened
ly closed window
*(12"/30cm) #(
9"/23cm)
C= Clearance to permanent
D= Vertical
*(min. 12"/30cm)
fit located above the terminal within a h
clearance to
ventilated sof
24"/60cm) check with local code.
E= Clearance to un
orizontal distance of
(24"/60cm) from the centerline of the terminal
(min.
ventilated sof
fit (min. 24"/60cm)
F= Clearance to outside c
G= Clearance to inside
orner: with AstroCa
p Termination
Cap (min. 13"), with Dura-V
ent Termination
Cap (13")
Cap (13")
corner: with
AstroCap T
ermination Cap (min. 13
"), with Dura-V
ent Termination
(3'/90cm) horizontally from the centerline of the regulator
H= Not to be installed abo
ve a meter/regulator a
ssembly within
.
J= Clearance to ser
vice regulator
vent outlet *(min. 36"/90cm)
al air supply inlet to building or
K= Clearance to non-mechanic
L= Clearance to a mechanical
the combustion air inlet
to any other app
liance *(12"/30cm) #(9"/23cm)
air supply inlet
*(min. 72"/1.8m)
#3' (91cm) above if within 10' (3m) horizontally
M= Clearance above paved sidewalk or a pa
.
ved driveway located on public propert
y *(min. 84"/2.1m)
N= Clearance under veranda, porch, deck
, or balcony *(min. 24
"/60cm)
Note:
- Excluding direct vent or non-condensing appliances
, a vent shall not terminate directly abo
ve a sidewalk or pa
ved driveway which is located
between
two single family
- Only permitted
dwellings and ser
ves both dwellings.
if veranda, porch, deck
, or balcony is fully open on a minimum of two sides beneath the
ed guard shall be installed.
Code. Note: Local c
floor.
- If the vent termination is acc
essible, a certifi
* As specified in CGA
B149 Installation
odes or regulations may re
quire different clearances.
# In accordance with the
current ANSI Z223.1/NFP
A 54, Natioinal
Fuel Gas Code.
Regency® L676E Direct Vent Gas Fireplace
14
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
VENTING ARRANGEMENTS
HORIZONTAL TERMINATION (FLEX)
Regency® Direct Vent System
These venting systems, in combination with the L676E, have been tested and listed as a direct vent heater system by Intertek. The location of the
termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the
parts needed to install the L676E using a flexible vent.
FPI Kit #
Length Contains:
#946-618
6 Feet
1) 8” flexible liner (Kit length)
2) 5” flexible liner (Kit length)
3) spring spacers (3)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
#946-616
10 Feet
7) tube of Mill Pac (1)
8) plated screws (8)
9) S.S. screws #8 x 1-1/2” drill point, (4)
10) vinyl siding standoff
* A Vent Guard is required when the AstroCap
is installed above grade at 7 feet or lower.
Notes:
1) Liner sections should be continuous
without any joints or seams.
2) Only Flex pipe purchased from FPI may
be used for Flex installations.
3) Horizontalventmustbesupportedevery
3 feet.
4) A wall thimble is mandatory for all
horizontal terminations due to high
temperatures.
Regency® L676E Direct Vent Gas Fireplace
15
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
RIGID PIPE VENTING SYSTEMS
BASIC HORIZONTAL & VERTICAL TERMINATIONS
Rigid Pipe Vent Systems offer a complete
line of component parts for installation of both
horizontalandverticalinstallations. Manyitems
are offered in decorative black, as well as gal-
vanized finish.
The minimum components required for a basic
horizontal termination are:
1
1
1
1
1
Horizontal Termination Cap
90o Elbow
Rigid Pipe Adaptor
Wall Thimble
Length of pipe to suit wall thickness
The minimum components required for a basic
vertical termination are:
1
1
1
Vertical Termination Cap
Rigid Pipe Adaptor
Lengths of pipe to adequately
penetrate roof
1
1
1
Ceiling Firestop
Flashing
Storm Collar
Wall thickness is measured from the back
standoffs to the inside mounting surface of
termination cap. For siding other than vinyl
furring strips may be used, instead of the vinyl
siding standoff, to create a level surface to
mount the vent terminal. The Terminal must
not be recessed into siding. Measure the wall
thickness including furring strips.
* A Vent Guard is required when the AstroCap
is installed above grade at 7 feet or lower.
If a Vinyl Siding Standoff is required (it must
be used with vinyl siding), measure to outside
surface of wall without siding and add 2
inches.
WARNING:
IMPORTANT NOTE
• The Simpson Dura-Vent and Selkirk Direct
Temp horizontal termination caps cannot
be used in any applications.
Do not combine venting components from
different venting systems.
Alternate
Horizontal Termination
Caps
TM
• Only the AstroCap XL and Snorkels are
certified for horizontal terminations.
Use of the the AstroCap XL is acceptable
with all systems.
ThisproducthasbeenevaluatedbyIntertekfor
using a Rigid Pipe Adaptor in conjunction with
Duravent Direct-Vent GS and Selkirk Direct-
Temp systems. Use of these systems with
the Rigid Pipe adaptor is deemed acceptable
and does not affect the Intertek WHI listing of
components.
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
The FPI AstroCap XLTM is certified for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent GS and Selkirk Direct-Temp.
AstroCap XLTM is a proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary
trademarks of Simpson Dura-Vent Co. Inc.
Regency® L676E Direct Vent Gas Fireplace
16
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
5” X 8” RIGID PIPE CROSS REFERENCE CHART
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Simpson
Simpson
Metal-Fab®
Sure Seal
Selkirk
Direct Vent GS®
Discontinued
Description
Direct Vent Pro®
Direct-Temp™
6” Pipe Length, Galvanized
6” Pipe Length, Black
58DVA-06
1208
5DT-6
5D6
58DVA-06B
58DVA-09
1208B
1207
5DT-6B
5DT-9
5D6B
N/A
9” Pipe Length, Galvanized
9” Pipe Length, Black
58DVA-09B
58DVA-12
1207B
1206
5DT-9B
5DT-12
5DT-12B
5DT-18
5DT-18B
5DT-24
5DT-24B
5DT-36
5DT-36B
5DT-48
5DT-48B
N/A
N/A
12” Pipe Length, Galvanized
12” Pipe Length, Black
5D12
5D12B
5D18
5D18B
5D24
5D24B
5D36
5D36B
5D48
5D48B
N/A
58DVA-12B
58DVA-18
1206B
18” Pipe Length, Galvanized
18” Pipe Length, Black
58DVA-18
58DVA-18B - N/A from FPI
58DVA-18B - N/A from FPI
24” Pipe Length, Galvanized
24” Pipe Length, Black
58DVA-24
1204
58DVA-24B
58DVA-36
1204B
36” Pipe Length, Galvanized
36” Pipe Length, Black
1203
58DVA-36B
58DVA-48
1203B
48” Pipe Length, Galvanized
48” Pipe Length, Black
1202
58DVA-48B
58DVA-60
1202B
60” Pipe Length, Galvanized
60” Pipe Length, Black
58DVA-60
58DVA-60B - N/A from FPI
58DVA-60B - N/A from FPI
N/A
N/A
Adjustable Length 3”-10”, Galvanized
Adjustable Length 3”-10”, Black
Adjustable Length 11”-14”, Galvanized
Adjustable Length 11”-14”, Black
Adjustable Length 17”-24”, Galvanized
Adjustable Length 17”-24”, Black
Extension Pipe 8-1/2”, Galvanized
Extension Pipe 8-1/2”, Black
N/A
N/A
N/A
5DAL
5DALB
N/A
N/A
N/A
N/A
Disc - See 58DV-08A
Disc - See 58DV-08AB
Disc - See 58DV-16A
Disc - See 58DV-16AB
58DVA-08A - N/A from FPI
Disc - See 58DV-08A
Disc - See 58DV-08AB
Disc - See 58DV-16A
Disc - See 58DV-16AB
58DVA-08A - N/A from FPI
5DT-AJ
5DT-AJB
N/A
N/A
N/A
N/A
N/A
N/A
N/A
58DVA-08AB
58DVA-08AB
N/A
N/A
58DVA-16A - N/A from FPI
58DVA-16A - N/A from FPI
Extension Pipe 16”, Galvanized
Extension Pipe 16”, Black
N/A
N/A
58DVA-16AB
58DVA-16AB
N/A
N/A
45º Elbow, Galvanized
45º Elbow, Black
58DVA-E45
1245
5DT-EL45
5DT-EL45B
N/A
N/A
58DVA-E45B
Disc - See 58DVA-E45
Disc - See 58DVA-E45B
58DVA-E90
1245B
N/A
45º Elbow, Swivel, Galvanized
45º Elbow, Swivel, Black
90º Elbow, Galvanized
90º Elbow, Black
1245G
5D45L
5D45LB
N/A
1245BG
N/A
58DVA-E90
58DVA-E90B
Disc - See 58DVA-E90
Disc - See 58DVA-E90B
N/A
5DT-EL90S
5DT-EL90SB
N/A
58DVA-E90B
Disc - See 58DVA-E90
Disc - See 58DVA-E90B
N/A
N/A
90º Elbow, Swivel, Galvanized
90º Elbow, Swivel, Black
90º Starter Elbow, Swivel, Galvanized*
Adaptor*
5D90L
5D90LB
5D90A
5DDA
N/A
N/A
N/A
N/A
N/A
Ceiling Support
58DVA-DC
1240
1241
1288
N/A
5DT-CS
5DT-CSS
5DT-WS/B
5DT-OS
5DT-WT
N/A
5DSP
5DRS
5DWS
N/A
Cathedral Support Box
Wall Support/Band
58DVA-CS
58DVA-WS
58DVA-ES - N/A from FPI
58DVA-WT
Offset Support
Wall Thimble, Black
Wall Thimble Support Box/Ceiling Support
Firestop Spacer
1247
N/A
5DWT
N/A
58DVA-DC - N/A from FPI
58DVA-FS
1263
1242
5DT-FS
5DT-TP
5DFS
5DCP
Trim Plate, Black
58DAV-WFS
Regency® L676E Direct Vent Gas Fireplace
17
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Simpson
Simpson
Metal-Fab®
Sure Seal
Selkirk
Direct Vent GS®
Discontinued
Description
Direct Vent Pro®
Direct-Temp™
Round Support / Radiation Sheild
Flat Flashing
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Attic Insulation Shield 12”
58DVA-IS - N/A from FPI
58DVA-IS - N/A from FPI N/A
N/A
Basic Horizontal Termination Kit (A)
Horizontal Termination Kit (B)
Vertical Termination Kit
N/A
N/A
5DT-HKA
5DT-HKB
N/A
N/A
N/A
58DVA-KHA
58DVA-VCH
N/A
1291
5DT-VKC
High Wind Vertical Cap
High Wind Horizontal Cap
Horizontal Square Termination Cap
Vertical Termination Cap
Storm Collar
N/A
N/A
N/A
N/A
DISC.
N/A
1285
1284
N/A
N/A
N/A
5DT-HHC
5DT-HVC
5DT-SC
5DHT
5DVT
5DSC
N/A
58DVA-SC
1253
Adjustable Flashing, 0/12-6/12
Adjustable Flashing, 6/12-12/12
58DVA-F6
1243
5DT-AF6
5DF
58DVA-F12
1243S
5DT-AF12
5DF-12
Vinyl Siding Standoff
58DVA-VSS
N/A
1250
N/A
5DT-VS
5DVS
N/A
Vinyl Siding Shield Plate
5DT-VSP
Snorkel Termination 14”
Snorkel Termination 36”
58DVA-SNK14
N/A
1282
1281
5DT-ST14
5DT-ST36
5DST14
5DST36
Restrictor Disk
58DVA-RD
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Colinear Flex Liner Adapter (3” Ø)
FPI
946-604/P
770-994
Simpson Direct Vent Vent Guard (Optional)
Rigid Pipe Adapter (Must use with all Rigid Piping)
946-623/P
946-506/P
946-625
AstroCap XL Horizontal Cap
Vent Guard (Optional)
Vinyl Siding Standoff - AstroCap XL
*NOTE: When using Metal-Fab Sure Seal Rigid Piping please note that either the Adaptor (5DDA) or 90º Starter Elbow
(5D90A) must be used in conjunction with FPI Rigid Pipe Adaptor (770-994).
L676 & L900 Direct Vent Fireplace
IMPORTANT NOTE
• A Vent Guard is required when the AstroCap is installed above grade at 7 feet or lower.
• The Simpson Dura-Vent and Selkirk Direct Temp horizontal termination caps cannot be used in any applications.
• Only the AstroCap XL and Snorkels are certified for horizontal terminations.
Offset Pipe Selection:
Use this table to determine offset pipe lengths.
Forspecificinstructionsordetailsonparticular
venting components please visit the following
websites:
5” x 8” Venting
Pipe Length
Run (X)
Rise (Y)
0”(0mm)
5-11/16”(144mm)
8-13/16”(224mm)
10-15/16”(278mm)
13”(330mm)
15-5/16”(389mm)
18-7/16”(468mm)
20-9/16”(522mm)
22-11/16”(576mm)
31-1/16”(789mm)
39-7/16”(1002mm)
47-7/8”(1216mm)
6”(152mm)
9”(229mm)
12”(305mm)
24”(610mm)
36”(914mm)
48”(1219mm)
L
Y
21-7/16”(697mm)
29-13/16”(757mm)
38-1/4”(972mm)
X
NOTE: Horizontal runs of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards
the termination. Never allow the vent to run downward. This could cause high temperatures and
may present a possible fire hazard.
Regency® L676E Direct Vent Gas Fireplace
18
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
VENTING ARRANGEMENTS
ALLOWABLE HORIZONTAL TERMINATIONS
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o two 45o elbows equal one 90o elbow).
Note: Must use optional rigid pipe adapter (Part# 770-994) when using Rigid Pipe Venting Systems.
VENT RESTRICTOR SETTING:
NG Units; Vent restrictor at Set 0 - factory set, no adjustment required unless otherwise indicated.
LP Units; Vent restrictor at Set 1 - factory set, no adjustment required unless otherwise indicated.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor to Set 1, Set 2 or Set 3 if required.
A vent guard maybe required as per local codes, refer to "Exterior Vent Termination Requirements" section for details.
Note: Regency® Direct Vent System (Flex) is only approved for horizontal terminations.
•
•
•
•
Maintain clearances to combustibles as listed in "Clearances" section
Horizontal vent must be supported every 3 feet.
Firestops are required at each floor level and whenever passing through a wall.
A wall thimble is mandatory for all horizontal terminations due to high temperatures.
Regency® L676E Direct Vent Gas Fireplace
19
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
Option
A)
V
H + H1 With these options, maximum total
pipe length is 30 feet with minimum
of6feettotalverticalandmaximum
8 feet total horizontal.
2' Min.
3' Min.
4' Min.
5' Min.
6' Min.
4' Max.
5' Max.
6' Max.
7' Max.
8' Max.
B)
C)
D)
E)
Please note minimum 1 foot
between 90o elbows is required.
VENT RESTRICTOR SETTING:
Vent restrictor must be at Set 0 for both NG and LP.
Horizontal Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
With these options, max.
total pipe length is 30 feet
with min. of 11 feet total
verticalandmax. 9feettotal
Option
A)
V
H
V + V1 H + H1
2' Min. 1' Max. 3' Min. 2' Max.
2' Min. 2' Max. 5' Min. 4' Max.
B)
C)
D)
E)
3' Min. 2' Max. 7' Min. 5' Max. horizontal.
4' Min. 3 Max. 9' Min. 6' Max.
Please note min. 1 foot
5' Min. 4' Max. 10' Min. 7' Max.
6' Min. 6' Max. 11' Min. 9' Max.
between 90o elbows is
required.
F)
VENT RESTRICTOR SETTING:
Vent restrictor must be at Set 0 for both NG and LP.
Regency® L676E Direct Vent Gas Fireplace
20
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Vertical Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
Withtheseoptions,max.totalpipe
length is 30 feet with min. of 6 feet
totalverticalandmax. 10feettotal
horizontal.
Option V
H
V + V1
A)
B)
C)
D)
E)
2' Min. 2' Max. 3' Min.
2' Min. 10' Max. 6' Min.
3' Min. 6' Max. 4' Min.
4' Min. 7' Max. 5' Min.
5' Min. 8' Max. 6' Min.
Pleasenotemin.1footbetween
90o elbows is required.
VENT RESTRICTOR SETTING:
Vent restrictor must be at Set 0 for both NG and LP.
Vertical Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Withtheseoptions,max.total
Option
A)
V
H + H1 V + V1
pipelengthis30feetwithmin.
of9feettotalverticalandmax.
8 feet total horizontal.
2' Min. 2' Max. 4' Min.
3' Min. 4' Max. 6' Min.
4' Min. 5' Max. 7' Min.
5' Min. 6' Max. 8' Min.
6' Min. 8' Max. 9' Min.
B)
C)
D)
E)
Please note min. 1 foot
between 90o elbows is
required.
VENT RESTRICTOR SETTING:
Vent restrictor must be at Set 0 for both NG and LP.
Regency® L676E Direct Vent Gas Fireplace
21
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
VENTING ARRANGEMENTS
ALLOWABLE VERTICAL TERMINATIONS
The shaded area in the diagram shows all allowable
combinationsofstraightverticalandoffsettovertical
terminations, using two 90o elbows, with Rigid Pipe
Venting Systems for Propane and Natural Gas.
Two 45o elbows equal to one 90o elbow. Maximum
of four 45o elbows allowed.
•
•
Vent must be supported at offsets.
Firestops are required at each floor level and
whenever passing through a wall.
•
•
Maintainclearancestocombustiblesaslisted
in the "Clearances" section.
Referto"VentRestrictorPosition"sectionfor
details on how to change the vent restrictor
to Set 1, Set 2 or Set 3 if required.
Note: Mustuseoptionalflueadapterwhenusing
Rigid Pipe (Part # 770-994).
Regency® L676E Direct Vent Gas Fireplace
22
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Horizontal runs of vent must be supported 7) Ensure that the pipe clearances to
UNIT INSTALLATION
WITH HORIZONTAL
every 3 feet (0.9meter). Wall straps are
available for this purpose.
combustible materials are maintained
(Diagram 5). Install the termination cap.
TERMINATION
Note: If installing termination on a vinyl
siding covered wall, a vinyl siding
standofforfurringstripsmustbeused
to ensure that the termination is not
recessed into the siding.
6) Mark the wall for a 11" x 11" (279mm x
279mm) square hole. The center of the
square hole should line up with the center-
line of the horizontal pipe. Cut and frame the
11 inch (279mm) square hole in the exterior
wall where the vent will be terminated. See
diagram 2 for center line requirements.
(Rigid Vent Systems)
Note: A top clearance of 3"(76mm) and
side & bottom clearance of 2"(51mm)
must be maintained; except when
passing through a wall, ceiling, or at
the termination where the use of a
firestop or wall thimble reduces the
required clearance to 1-1/2" (38mm).
Werecommendframinga11"(279mm)
x 11"(279mm) (inside dimensions)
hole to give structural rigidity for
mounting the termination.
If the wall being penetrated is constructed of
non-combustiblematerial,i.e.masonryblock
or concrete, an 8" (203mm) diameter hole
is acceptable.
Install the vent system according to the
manufacturer's instructions included with the
components.
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are in
thewaywhentheventingsystemisattached.
If this is the case, you may want to adjust
the location of the unit. Rough in the gas
preferably on the right side of the unit and
the electrical (junction block is on the left
side) on the left.
Diagram 5
Thefourwoodscrewsprovidedshouldbere-
placedwithappropriatefastenersforstucco,
brick, concrete, or other types of sidings.
8) Before connecting the horizontal run of vent
pipe to the vent termination, slide the Wall
Thimble over the vent pipe. The wall thimble
is required for all horizontal terminations.
2) DirectVentpipeandfittingsaredesignedwith
specialtwist-lockconnectionstoconnectthe
venting system to the appliance flue outlet.
A twist-lock appliance adaptor is required.
9) Slide the appliance and vent assembly
towards the wall carefully inserting the vent
pipeintotheventcapassembly.Itisimportant
that the vent pipe extends into the vent cap
sufficientdistancesoastoresultinaminimum
pipeoverlapof1-1/4inches(32mm). Secure
the connection between the vent pipe and
the vent cap.
3) In conjunction with the Simpson Dura-Vent
Direct Vent GS system. Install the adaptor
after the unit is set in its desired location.
Put a bead of high temperature silicone
inside the outer section of the adapter and
a bead of Mill Pack on the inner collar. Slip
the adapter over the existing inner and outer
fluecollar. Fastentotheoutercollaronlywith
the 3 supplied screws (drilling pilot holes will
make this easier).
Diagram 2
Note:
a) The horizontal run of vent must be level,
or have a 1/4 inch rise for every 1 foot
of run towards the termination. Never
allow the vent to run downward. This
could cause high temperatures and may
present the possibility of a fire.
10) Install wall thimble in the center of the 11"
(279mm)squareandattachwithwoodscrews
(Diagram 7).
4) Levelthefireplaceandfastenittotheframing
using nails or screws through the top and
side nailing strips.
b) The location of the horizontal vent
terminationonanexteriorwallmustmeet
all local and national building codes, and
must not be blocked or obstructed. See
"Exterior Vent Termination Locations"
section for more details.
5) Assemble the desired combination of pipe
and elbows to the appliance adaptor and
twist-lock for a solid connection.
Note: For best results and optimum perfor-
mance with each approved venting system,
it is highly recommended to apply “Mill-Pac”
sealant(supplied)toeveryinnerpipeconnec-
tion. Failure to do so may result in drafting
or performance issues not covered under
warranty. Silicone (red RTV) is optional.
Diagram 7
NOTE: A Vent Guard is required when
the AstroCap is installed above grade
at 7 feet or lower.
Diagram 1
Regency® L676E Direct Vent Gas Fireplace
23
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
4) Assemble the desired lengths of pipe and
elbows. Ensure that all pipes and elbow
connections are in the fully twist-locked
position and sealed.
UNIT INSTALLATION
WITH VERTICAL
TERMINATION
Note: For best results and optimum
performance with each approved venting
system, it is highly recommended to apply
“Mill-Pac” sealant (supplied) to every inner
pipe connection. Failure to do so may
result in drafting or performance issues not
covered under warranty. Silicone (red RTV)
is optional.
(Rigid Vent Systems)
Diagram 5
Note: A clearance of 2"(51mm) must be
maintained; except when passing
through a wall, ceiling, or at the
terminationwheretheuseofafirestop
or wall thimble reduces the required
clearance to 1-1/2" (38mm). We
recommend framing a 11"(279mm) x
11"(279mm) (inside dimensions) hole
togivestructuralrigidityformounting
the termination.
Minimum Vent
Height
Roof Pitch
Feet
2
Meters
0.61
0.61
0.61
0.76
0.99
1.22
1.52
1.83
2.13
2.29
flat to 7/12
over 7/12 to 8/12
over 8/12 to 9/12
over 9/12 to 10/12
over 10/12 to 11/12
over 11/12 to 12/12
over 12/12 to 14/12
over 14/12 to 16/12
over 16/12 to 18/12
over 18/12 to 20/12
2
2
1) Maintain the 2" (51mm)
clearances (air spaces)
to combustibles when
passing through ceilings,
walls, roofs, enclosures,
attic rafter, or other nearby
combustible surfaces.
Do not pack air spaces
with insulation. Check
"Venting Arrangemnt
- Vertical Termination"
2.5
3.25
4
5
6
5) Cut a hole in the roof centered on the small
drilled hole placed in the roof in Step 2. The
hole should be of sufficient size to meet
the minimum requirements for clearance to
combustiblesof1-1/2"(38mm).Sliptheflashing
under the shingles (shingles should overlap
half the flashing) as per Diagram 4.
7
7.5
s e c t i o n
f o r
t h e
A poor draft, or down drafting can result from
highwindconditionsnearbigtreesoradjoining
roof lines, in these cases, increasing the vent
height may solve the problem.
maximum vertical rise
of the venting system and
the maximum horizontal
offset limitations.
Diagram 1
2) Setthegasappliance
initsdesiredlocation.
Drop a plumb bob
downfromtheceiling
to the position of the
appliance flue exit,
andmarkthelocation
where the vent will
penetratetheceiling.
Drill a small hole at
his point. Next, drop
a plumb bob from
the roof to the hole
previously drilled in
theceiling, andmark
the spot where the
7) Ensure vent is vertical and secure the base
of the flashing to the roof with roofing rails,
slide storm collar over the pipe section and
seal with a mastic.
8) Install the vertical termination cap by twist-
locking it.
Note: Anyclosetsorstoragespaces,which
the vent passes through must be
enclosed.
Diagram 4: The upper half of the flashing is
installed under the roofing material and not
nailed down until the chimney is installed.
This allows for small adjustments.
Offset Chart
Diagram 2
ventwillpenetratetheroof.Determineifceiling
joists,roofraftersorotherframingwillobstruct
the venting system. You may wish to relocate
theapplianceortooffset,asshowninDiagram
2 to avoid cutting load bearing members.
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic
to avoid obstructions, it is important
to support the vent pipe every 3
feet (0.9 meter), to avoid excessive
stress on the elbows, and possible
separation. Wall straps are available
for this purpose
3) AFirestop spacer must be installed in the floor
or ceiling of every level.
(Diagram 2).
Galvanizedpipeisdesirableabovetheroofline
duetoitshighercorrosionresistance.Continue
to add pipe sections through the flashing until
the height of the vent cap meets the minimum
heightrequirementsspecifiedinDiagram5or
local codes. Note that for steep roof pitches,
the vertical height must be increased.
Diagram 3
Regency® L676E Direct Vent Gas Fireplace
24
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
4) Separatethe2halvesofthewallthimbleand
securely fasten the one with the tabs to the
outside wall making sure that the tabs are
on top and bottom. Fasten the other thimble
half to the inside wall. The thimble halves
slip inside each other and can be adjusted
for 2 x 4 or 2 x 6 walls.
IMPORTANT: Do not locate termination
hood where excessive snow or ice
buildup may occur. Be sure to check vent
terminationareaaftersnowfalls, andclear
to prevent accidental blockage of venting
system. When using snow blowers, make
sure snow is not directed towards vent
termination area.
UNIT INSTALLATION
HORIZONTAL TERMINATION
WITH FLEX VENT SYSTEM
Note: A top clearance of 3"(76mm) and
side&bottomclearanceof2"(51mm)
must be maintained; except when
passing through a wall, ceiling, or
at the termination where the use of
afirestoporwallthimblereducesthe
required clearance to 1-1/2" (38mm).
Werecommendframinga11"(279mm)
x 11"(279mm) (inside dimensions)
hole to give structural rigidity for
mounting the termination.
5) Slip the assembled liner and termination
assembly through the thimble making sure
the termination cap faces up (there are
markings on the cap that show which way
is up). This will position the termination cap
with proper down slope for draining water.
Fasten the cap to the outer wall with the 4
supplied screws.
ASTROCAP XL
DIMENSIONS (946-623/P)
1) Locate the unit in the framing, rough in the
gas (preferably on the right side of the unit)
and the electrical (Junction block is on the
left side) on the left. Locate the centerline of
the termination and mark wall accordingly.
Cut an 11"(279mm) hole in the wall (inside
dimension).
6) Pull the centre 5"(127mm) liner and outer
8"(203mm) liner out enough to slip over
the flue collars of the fireplace. (You may
wish to cut the liner shorter to make it more
workable.) Do not bend liner more than 90o.
The liners must slip over the collars a
minimum of 1-3/8".
7) Apply Mill Pac over the fireplace inner collar
and slip the 5"(127mm) liner down over it
and attach with 3 supplied screws.
8) Do the same with the 8"(203mm) liner.
9) Applyabeadofsiliconebetweenthethimble
and termination and around the outer edge
of the terminal at the wall in order to keep
the water out.
Note: If installing termination on a siding
covered wall, a vinyl siding standoff
or vinyl furring strips must be used
to ensure that the termination is not
recessed into the siding.
2) Level the fireplace and fasten it to the fram-
ing using nails or screws through the nailing
strips.
3) Assemble the vent assembly by applying
Mill Pac to the 5"(127mm) inner collar of
theterminationand slippingthe5"(127mm)
liner over it at least 1-3/8" (35mm). Fasten
with the 3 screws (drilling pilot holes will
make this easier). Apply Mill Pac or high
temperature silicone to the 8"(203mm) flex
pipe and slip it over the 8" outer collar of
the vent terminal at least 1-3/8"(35mm) and
fasten with the 3 screws.
NOTE: Horizontal sections must be sup-
ported at intervals not exceeding 3
feet (0.9 meter). (Flame picture and
performance will be affected by sags
in the liner).
Regency® L676E Direct Vent Gas Fireplace
25
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
SIT 845 VALVE DESCRIPTION
PILOT ADJUSTMENT
L676E-NG SYSTEM DATA
Min. Supply Pressure 5" WC (1.25 kpa)
Periodically check the pilot flames. Correct
flame pattern has three strong blue flames:
1 flowing around the pilot, 1 flowing around
the flame sensor and 1 flowing across the
burner (it does not have to be touching the
burner).
1) On-Off Solenoid Valve EV1
2) On-Off Solenoid Valve EV2
3) Inlet Pressure Test Point
4) Outlet Pressure Test Point
5) Connection for Pressure Regulator /
Combustion Chamber Compensation
6) Pressure Regulator for Minimum and
Maximum Outlet Pressure
7) Gas Outlet Pressure Electric Modulator
8) Pilot Outlet
9) Main Gas Outlet
10) Side Outlet
11) Main Gas Inlet
Low Setting Man.
Pressure
1.6" WC (0.39 kpa)
3.5" WC (0.87 kpa)
#48 DMS
Max. Manifold
Pressure
Orifice Size (Front
Burner)
Orifice Size (Back
Burner)
#34 DMS
Minimum Input
11,000 Btu/h
(3.22 kW)
Maximum Input
42,000 Btu/h
(12.3 kW)
Note: Ifyouhaveanincorrectflamepattern,
contact your Regency® dealer for
further instructions.
L676E-LP SYSTEM DATA
Min. Supply Pressure 12" WC (2.98 kpa)
11
Low Setting Man.
Pressure
3.6" WC (2.49 kpa)
10" WC (2.98 kpa)
#56 DMS
Incorrect flame pattern will have small,
probably yellow flames, not coming into
proper contact with the rear burner or flame
sensor.
3
Max. Manifold
Pressure
1
Orifice Size (Front
Burner)
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 1/2 psig.
7
Orifice Size (Back
Burner)
#53 DMS
M D
6
10
Minimum Input
9,000 Btu/h
(2.64 kW)
2
Maxiumm Input
40,000 Btu/h
(11.72 kW)
4
5
8
HIGH ELEVATION
This unit is approved in Canada for altitude 0
to 4500 ft. (CAN1 2.17-M91).
9
Themanifoldpressureiscontrolledbyaregulator
builtintothegascontrol, andshouldbechecked
at the pressure test point.
AERATION
ADJUSTMENT
The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude. Open the air shutter for a blue flame or
close for a more yellow flame.
Note: Toproperlycheckgaspressure,both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
GAS LINE
INSTALLATION
1) Make sure the unit is turned OFF.
Since some municipalities have additional
local codes it is always best to consult with
your local authorities and the CAN/CGA B149
installation code.
2) Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a
1/8" wide flat screwdriver.
In order to adjust the aeration, the logs, grate
and burners will need to be removed to be able
to access the shutters.
For USA installations follow local codes and/or
the current National Fuel Gas Code, ANSI
Z223.1.
3) Attach manometer to "IN" and/or "OUT"
Minimum Air Shutter Opening:
pressure tap(s) using a 5/16" ID hose.
NG
Front Burner
Rear Burner
1/4"
1/8"
4) Turn the unit ON.
When using copper or flex connectors use only
approved fittings. Always provide a union so
that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and flex
connectors are usually considered to meet this
requirement.
LP
Front Burner
Rear Burner
5/16"
1/4"
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specified on the safety
label.
CAUTION: Carbonwillbeproducedifairshutter
is tightly closed.
6) When finished reading manometer, turn off
theunit,disconnectthehoseandtightenthe
screw(clockwise)witha1/8"flatscrewdriver.
Note: Screw should be snug, but do not
over tighten.
Important:Alwayscheckforgasleakswitha
soapandwatersolutionorgasleakdetector.
Do not use open flame for leak testing.
Note: Any damage due to carboning
resulting from improperly setting
the aeration controls is NOT covered
under warranty.
Regency® L676E Direct Vent Gas Fireplace
26
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
BACK-UP BATTERY INSTALLATION
1) Unsecure the battery from the outer firebox base flange by cutting the
6) Connect the red and black wires to the battery accordingly.
cable tie and remove from protective wrapping.
2) Remove the plastic pin protectors from the battery.
3) Loosen the 2 screws that hold the right side heat shield in place.
Note - Battery Hookup
Ensure that the black wire is connected to the black spade
and the red wire is connected to the red spade.
Heat
Shield
7) Place the battery into position at the base of the firebox as shown.
4) Lift the heat shield up and pull out slightly to clear the head screws
and then hang it on the top bracket (located directly above the heat
shield, close to the top of the firebox).
5) Pull out the black and red battery wires from the right side of the
firebox.
Battery
Wires
8) Re-install the heat shield.
Regency® L676E Direct Vent Gas Fireplace
27
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
BRICK PANEL INSTALLATION
IMPORTANT: Must install 1 set of brick panels. The operation of this unit without the brick panels is prohibited.
Dangerous operating conditions may occur if the panels are broken.
Handle with care. DO NOT FORCE INTO POSITION.
3) Remove the 2 brick panel clips on the inside left and right side of the
Interior Brick Panel Installation:
firebox by removing the screw.
1) Remove the glass door.
a. Release the 2 door latches on the left and right side at the top of
the firebox.
Brick
Panel
Clip
Screw
Latch Location
Latch
4) Place the 2 small back brick panels at the base of the firebox on the
left and right side of the rear log tray.
Note: The left and right side back brick panels are different.
b. Swing the door out from the top and release the hinges on the left
and right side of the door by lifting them up.
Left Side Back
Brick Panel
Right Side Back
Brick Panel
Hinge
Door
c. Place the door on a soft surface to prevent scratching.
2) Unwrap the brick panels from the protective wrapping.
Note: The logs must not be in the unit.
Right Side
Back Brick
Panel
Left Side
Back Brick
Panel
Regency® L676E Direct Vent Gas Fireplace
28
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
5) Install the back brick panel by carefully placing it against the back
7) Slide the left side brick panel into position and secure in place with
wall of the firebox.
the brick panel clip that was removed in step 3.
L e f t
Side
Brick
Panel
Back Brick Panel
Exterior Brick Panel Installation:
1) Ensure installation of the logs and glass door has been completed
before installing the exterior brick panels.
2) Line up the pins in the exterior base brick panel with the holes on
the outerbox of the firebox and fit in place.
6) Place the top brick panel into position and hold it in place while slid-
ing the right side brick panel into position and secure using the brick
panel clip that was removed in step 3.
Top Brick Panel
Outerbox of Firebox
3) Install the right side exterior brick panel by placing the bottom tab
into the slot of the exterior base brick panel.
The top of the brick panel is held in place by a magnet that sits
against the bracket as shown in the image below.
Top Brick Panel
Repeat for left side exterior brick panel.
Right Side
Brick Panel
Bracket
Brick
Panel
Clip
Tab
Base Brick Panel Slot
Regency® L676E Direct Vent Gas Fireplace
29
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
LOG SET INSTALLATION
Installation of Interior Brick Panels must be completed before installing the log set.
Read the instructions below carefully and refer to the diagrams.
If the logs are broken do not use the unit until they are replaced.
Broken logs can interfere with pilot operation.
3) Place log 03-27 on the front left side of the burner. Place the right
end of the log into the pin and rest the left end of the log inbetween
the rear and front burner tubes.
Log kit (Part No. 521-930 and 521-935) contain the following pieces:
a) 03-25
b) 03-26
c) 03-27
d) 03-28
Log Rear
Log Top
Log Front Left
Log Front Right
03-27
e) 902-154 Embers Lava
f) 902-179 Vermiculite
g) 946-669 Platinum Embers (supplied with packaged manual)
Rear
Burner
Tube
03-25
Front Burner Tube
4) Place the left end of log 03-28 into the pin while resting the right end
of the log on the grate. Slide the right end of the log forward until it
is approximately 3/8" away from the back side of the grate.
03-27
03-28
03-28
03-26
The "03" reference numbers (i.e. 03-25) are
molded into the rear of each log.
1) Carefully remove the logs from the box and unwrap them. The logs
are fragile, handle with care - do not force into position.
2) Place log 03-25 on the rear log support pins.
Backside of Grate
5) Line up the two holes on the underside of log 03-26 with the pins on
logs 03-25 and 03-27 and fit in place.
03-26
03-25
03-25
03-27
Regency® L676E Direct Vent Gas Fireplace
30
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
6) Spread all of the Embers on the bottom brick panel around the burner
tube and inbetween the front burner tube and the grate as shown.
Separateplatinumembersandplaceontheembersaroundtheburner
tube and inbetween the front burner tube and grate. Avoid stacking
platinum embers.
Embers in between front burner tube and grate.
7) Spreadthevermiculiteonthebasebrickpanelcoveringtheremaining
exposed base brick.
Embers on bottom brick panel.
Complete Log Set Installation
03-25
03-26
03-28
03-27
Regency® L676E Direct Vent Gas Fireplace
31
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
WIRING DIAGRAM
A receptacle is provided on the left hand side
of the unit. 120 Volt AC power must be wired to
the receptacle and the control module plugged
in for the unit to operate fully. The front and
rear burners will operate on low, when the unit
is running on battery back-up.
Caution: Ensure that the wires do
not touch any hot surfaces and are
away from sharp edges.
CAUTION: Label all wires prior
to disconnection when servicing
controls. Wiring errors can
cause improper and dangerous
operation.
(Do not cut the ground terminal off under
any circumstances.)
Black
Orange
Lockout Led
Black
Reset Button
Green
Flame Sensor
1
2
white
black
J7
NG/LP
jumper
ECS MODULE
yellow
green
Spark Ignitor
white
white
black
orange
E
A
D
B
C
B
120V Power Source
NEUTRAL (white)
LIVE (black)
red
black
MODULATING
COIL
(REAR)
MAIN
BURNER
(EMBER)
red
SECONDARY
BURNER
black
Battery
Pin
3
P.OUT
4
2
1
VENT
EV1
EV2
R.Q.
ADJ.
red
red
black
black
9V SOLENOID
VALVE
Regency® L676E Direct Vent Gas Fireplace
32
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
5) Verify that the venting and cap are
GAS CONTROL VALVE
MATCHING REMOTE
unobstructed.
HANDSET & CONTROL
BOX ID CODE
The gas control knob is located on the
righthandsideofthefireboxbehindthe
right side exterior brick panel.
6) Ensure that the brick panels are installed.
7) Verify log placement. If the pilot cannot be
seen when lighting the unit, the logs have
been incorrectly positioned.
TheRemoteControlHandsethasasetofunique
IDcodesthatispre-programmedintoitsmemory.
This set of ID codes helps to differentiate one
Remote Control Handset from another so that
only the control box with a matching ID code
will respond to the appropriate Remote Control
Handset.
1) Remove the right side exterior brick panel.
8) The unit should never be turned off, and on
again without a minimum of a 60 second
wait.
To ensure the remote control is matched to
the receiver correctly, please follow the steps
below:
FIRST FIRE
TheFIRSTFIREinyourheaterispartofthepaint
curing process. To ensure the paint is properly
cured,it is recommendedyou burnyourfireplace
for at least four (4) hours the first time.
1. Install the 2 x AAA alkaline batteries into the
Remote Control.
2. Unplug and re-plug the power cord. The
power cord is located on the left hand side
of the appliance and will be plugged into the
receptacle.
When first operated, the unit will release an
odour caused by the curing of the paint and the
burning off of any oils remaining from manufac-
turing. Smoke detectors in the house may go off
at this time. Open a few windows to ventilate
the room for a couple of hours. The glass may
require cleaning.
3. Press and hold the PROG and FAN buttons
simultaneously for up to 20 seconds. During
this time, the remote will display LC while it
is transmitting codes to the receiver.
NOTE: The main burner will always start on
"HIGH" and resume it's last setting after
20 seconds of operation.
4. Once it is successfully transmitted, wait for
20 seconds and press the ON/OFF button
on the remote control once and the burners
will come on.
Right Side Exterior Brick Panel
NOTE: Whentheglassiscoldandtheappliance
is lit, it may cause condensation and fog
the glass. This condensation is normal
and will disappear in a few minutes as
the glass heats up.
2) Loosen the 2 screws that hold the right side
heat shield in place.
If is does not work the first time, repeat steps
2 and 3.
5. The remote control is now programmed to
the receiver and the appliance can now be
operated with it.
DO NOT BURN THE APPLIANCE
WITHOUT THE GLASS FRONT IN
PLACE.
The control box will only learn the Remote ID
codes during the first 30 seconds after power is
appliedandwillignorethisspecialcommandfrom
the Remote after the first 30 seconds.
DO NOT ATTEMPT TO CLEAN THE
GLASS WHILE IT IS STILL HOT!
Heat
Shield
NOTE: This must only be performed by a quali-
fied installer.
During the first few fires, a white film
may develop on the glass front as part of
the curing process. The glass should be
cleaned after the unit has cooled down
or the film will bake on and become very
difficult to remove. Use a non-abrasive
cleanerandDONOTATTEMPTTOCLEAN
THE GLASS WHILE IT IS HOT.
OPERATING
INSTRUCTIONS
1) Read and understand these instructions
before operating this appliance.
3) Lift the heat shield up and pull out slightly to
clear the head screws and then hang it on
the top bracket (located directly above the
heat shield, close to the top of the firebox).
2) Check to see that all wiring is correct and
enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the door frame is
properly positioned. Never operate the
appliance with the glass removed.
Regency® L676E Direct Vent Gas Fireplace
33
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
LIGHTING
NORMAL OPERATING
OPERATION DURING
POWER OUTAGE
PROCEDURE
SOUNDS OF
GAS APPLIANCES
1) Plug the power cord into a power outlet.
Intheeventofapowerfailure, theunitwillbefully
functional for approximately the first 45 minutes
using the backup battery system.
Itispossiblethatyouwillhearsomesoundsfrom
yourgasappliance.Thisisperfectlynormaldueto
the fact that there are various gauges and types
of steel used within your appliance. Listed below
2) Press and release the ON/OFF button once
on the Remote Control.
If power resumes within the first 45 minutes you
3) After approximately 3 seconds the spark
ignition system will spark for 30 seconds to
light the main burner.
are some examples. All are normal operating can continue using the unit as normal.
soundsandshouldnotbeconsideredasdefects
in your appliance.
If power is restored after 45 minutes you will
need to reset the unit as follows;
4) The unit will turn on.
Burner Tray:
The burner tray is positioned directly under the
burner tube and logs and is made of a different
gauge material from the rest of the firebox and
body.Therefore, thevaryingthicknessesofsteel
will expand and contract at slightly different
rates which can cause "ticking" and "cracking"
sounds. You should also be aware that as there
are temperature changes within the unit these
sounds will likely re-occur. Again, this is normal
for steel fireboxes.
a) Remove the left side exterior brick panel.
NOTE:
If the unit does not turn on within 90 seconds
of pressing the ON/OFF button on the Remote
Control, this means that the system is in lockout
mode.
b) Hold the reset button for 3 to 5 seconds or
until the LED stops blinking.
c) Press and release the ON/OFF button once
on the Remote Control.
The unit will need to be reset as follows;
a) Remove the left side exterior brick panel.
Reset Button
b) Hold the reset button for 3 to 5 seconds or
until the LED stops blinking.
Pilot Flame:
While the pilot flame is on it can make a very
slight "whisper" sound.
c) Repeat step 2.
For all other Remote Control features, see
FireWizard remote control operation manual.
Gas Control Valve:
As the gas control valve turns ON and OFF, a
dull clicking sound may be audible, this is normal
operation of a gas regulator or valve.
SHUTDOWN
PROCEDURE
Unit Body/Firebox:
Different types and thicknesses of steel will
expand and contract at different rates resulting
in some "cracking" and "ticking" sounds will be
heard throughout the cycling process.
Located on the left hand side of the
firebox behind the exterior brick panel.
1) Press and release the ON/OFF button once
on the Remote Control.
2) If service is to be preformed, you must
disconnectbothsourcesofpowertotheunit;
main power and the battery.
BACKUP BATTERY
Listedbelowareapprovedbatterytypesthatcan
be used for replacement:
a) Powersonic 1.3AH
b) Panasonic 1.3AH
c) Henda 1.3AH
d) Magnacharge 1.3AH
CAUTION:
Risk of Energy Hazard, 12V, 1.3 Amphere-hour
battery. Before replacing batteries, remove con-
ductivejewelrysuchaschains,wristwatches,and
rings. High energy through conductive materials
could cause severe burns.
Dispose of batteries at an authorized battery
disposal site. Do not dispose of batteries in a
fire. The batteries may explode.
Do not open or mutilate batteries. Released
material is harmful to the skin and eyes. It may
be toxic.
Regency® L676E Direct Vent Gas Fireplace
34
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
COPY OF LIGHTING PLATE INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
This appliance must be installed in accordance with local codes, if any;
if none, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or
Natural Gas and Propane Installation Codes, CSA B149.1.
WARNING: If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life. Improper
installation, adjustment, alteration, service or maintenance can cause injury
or property damage. Refer to the owner’s information manual provided with
this appliance. For assistance or additional information consult a qualified
installer, service agency or gas supplier.
A) BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance.
- Do not touch any electric switch, do not use any phone in your building.
- Immediately call your gas supplier from a neighbours phone. Follow the gas supplier’s
instructions.
- If you cannot reach your gas supplier, call the fire department.
B) Do not use this appliance if any part has been under water. Immediately call a qualified service
technician to inspect the appliance and to replace any part of the control system and any gas
control which has been under water.
C) This appliance needs fresh air for safe operation and must be installed so there are provisions for
adequate combustion and ventilation air.
CAUTION: Hot while in operation. Do not touch. Severe Burns may result. Due
to high surface temperatures keep children, clothing and furniture, gasoline and
otherliquidshavingflammablevaporsaway.Keepburnerandcontrolcompartment
clean. See installation and operating instructions accompanying appliance.
LIGHTING INSTRUCTIONS
STOP! Read the safety information above on this label.
1) Plug the power cord into a power outlet.
2) Press and release the ON/OFF button once on the Remote Control.
3) After approximately 3 seconds the spark ignition system will spark for 30
seconds to light the main burner.
4) If the main burner does not light within 90 seconds, you must reset the
unit. See instruction manual for details.
TO TURN OFF GAS APPLIANCE
1) Press the ON/OFF button once on the Remote Control.
2) If service is to be performed, you must disconnect both sources of power
to the unit; main power and the battery.
918-628
DO NOT REMOVE THIS INSTRUCTION PLATE
Regency® L676E Direct Vent Gas Fireplace
35
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
DOOR GLASS
MAINTENANCE
INSTRUCTIONS
1) Alwaysturnoffthegasvalvebeforecleaning.
For relighting, refer to lighting instructions.
Keep the burner and control compartment
clean by brushing and vacuuming at least
once a year. When cleaning the logs, use a
soft clean paint brush as the logs are fragile
and easily damaged.
GENERAL VENT
MAINTENANCE
Conduct an inspection of the venting system
semiannually. Recommended areas to inspect
as follows:
Your Regency® fireplace is supplied with high
temperature 5mm-Ceramic glass. If your glass
requires cleaning, we recommend using an
approvedglasscleaneravailableatallauthorized
dealers. Do not use abrasive materials.
1) Check the Venting System for corrosion in
areas that are exposed to the elements.
These will appear as rust spots or
streaks, and in extreme cases, holes.
These components should be replaced
immediately.
CAUTION & WARNINGS:
*
Do not clean when the glass is hot.
* Theuseofsubstituteglasswillvoidallproduct
2) Clean appliance and door with a damp
cloth (never when unit is hot). Never use
an abrasive cleaner. The glass should be
cleaned with a gas fireplace glass cleaner.
The glass should be cleaned when it
starts looking cloudy.
warranties.
* Care must be taken to avoid breakage of the
glass.
2) Remove the Cap, and shine a flashlight
down the Vent. Remove any bird nests, or
other foreign material.
*
Do not strike or abuse the glass.
* Do not operate this fireplace without the
glass front or with a cracked or broken glass
front.
3) Check for evidences of excessive
condensation,suchaswaterdropletsforming
in the inner liner, and subsequently dripping
outthejoints,Continuouscondensationcan
cause corrosion of caps, pipe, and fittings.
It may be caused by having excessive
lateral runs, too many elbows, and exterior
portions of the system being exposed to
cold weather.
3) The heater is finished in a heat resistant
paintandshouldonlyberefinishedwithheat
resistant paint. Regency® uses StoveBright
Paint - Metallic Black #6309.
* Wear gloves when removing damaged or
broken glass.
* Replacement of the glass panel(s) should be
done by a licensed or qualified service per
son.
4) Make a periodic check of burner for proper
position and condition. Visually check the
flameoftheburnerperiodically,makingsure
the flames are steady; not lifting or floating.
If there is a problem, call a qualified service
person.
GLASS REPLACEMENT
Intheeventthatyoubreakyourglassbyimpact,
purchase your replacement from an authorized
Regency® dealer only.
4) Inspect joints, to verify that no pipe
sections or fittings have been disturbed,
and consequently loosened. Also check
mechanical supports such as Wall Straps,
or plumbers' tape for rigidity.
5) The appliance and venting system must be
inspected before use, and at least annually,
byaqualifiedfieldserviceperson, toensure
that the flow of combustion and ventilation
air is not obstructed.
Replacement glass is shipped already installed
into the door frame.
LOG REPLACEMENT
CAUTION: Wear gloves when
removing damaged or broken
glass.
Note: Never operate the appliance without
the glass properly secured in place.
The unit should never be used with broken logs.
Turn off the gas valve and allow the unit to cool
before opening door and carefully remove the
logs. (The pilot light generates enough heat to
burn someone.) If for any reason a log should
need replacement, you must use the proper
replacement log. The position of these logs
must be as shown in the diagrams under Log
Installation.
6) Donotusethisapplianceifanyparthasbeen
under water. Immediately call a qualified
service technician to inspect the appliance
andtoreplaceanypartofthecontrolsystem
and any gas control which has been under
water.
WARNING: Do not operate the
appliance with the glass panels
removed, cracked or broken.
Replacement of the glass panels
should be done by a licensed or
qualified service person.
7) In the event this appliance has been
serviced check that the vent-air system
has been properly resealed & reinstalled
in accordance with the manufacturer's
instructions.
Note: Improper positioning of logs may
create carbon build-up and will
severely alter the unit's performance
which is not covered under
warranty.
8) Verify operation after servicing.
GLASS GASKET
If the glass gasket requires replacement use a
tadpole glass gasket (Part # 936-155).
Regency® L676E Direct Vent Gas Fireplace
36
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
CONTROL BOX REPLACEMENT
BACK-UP BATTERY REPLACEMENT
1) Loosen the 2 screws that hold the right side heat shield in place.
1) Remove the exterior brick panels.
2) Remove the glass door.
a. Release the 2 door latches on the left and right side at the top of
the firebox.
Heat
Shield
Latch Location
Latch
2) Lift the heat shield up and pull out slightly to clear the head screws
and then hang it on the top bracket (located directly above the heat
shield, close to the top of the firebox).
3) Remove the battery by lifting off the velcro and bring out from the side
of the firebox.
b. Swing the door out from the top and release the hinges on the
left and right side of the door by lifting them up.
Backup
Battery
Hinge
Door
4) Disconnect the wires connected to the battery.
3) Loosen the 2 screws that hold the right side heat shield in place.
Heat
Shield
5) Replace with new battery and reconnect battery wires accordingly.
6) Re-install the battery to the right side of the firebox.
7) Re-install the right side heat shield.
Regency® L676E Direct Vent Gas Fireplace
37
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
4) Disconnect both sources of power; the power cord, located on the
left hand side of the firebox and the wires connected to the back-up
battery located on the right side of the firebox.
7) Disconnect the spark cable and flame sensor wires from the control
board.
Back-up
Battery
Power
Receptacle
8) Remove the cable tie from control box to release the wires. Do not
discard cable tie.
5) Remove the control box by carefully lifting off the velcro and sliding it
out from the side of the firebox.
NOTE: The control box will need to be flipped as it is being brought
out from the side of the firebox.
9) Remove the ground screw from the side of the control box. Do not
discard the ground screw.
6) Disconnect the wire harnesses from the control board labelled A, C,
D, E & F. Do not disconnect the the jumper cables labelled B.
F
10) Replace the control box.
11) Re-connect wires harnesses. Ensure that the cables match the letters
labelled on the control box and are securely connected.
12) Reinstall the ground screw.
13) Reverse steps 8 to 1.
A
D
E
C
Regency® L676E Direct Vent Gas Fireplace
38
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
VALVE TRAY REPLACEMENT
6) Remove the front burner by removing the screw.
1) Remove the exterior brick panels.
2) Remove the glass door.
a. Release the 2 door latches on the left and right side at the top of
the firebox.
Latch Location
Front Burner
Latch
b. Swing the door out from the top and release the hinges on the
left and right side of the door by lifting them up.
Front Burner Removed
Hinge
7) Remove the back burner by removing the screw.
Door
3) Remove the log set.
4) Remove the interior brick panels.
5) Remove the grate by undoing the 2 screws on the left and right
Back Burner
side.
8) Remove the rear log stand by removing the 4 screws.
Rear Log Stand
Grate
Regency® L676E Direct Vent Gas Fireplace
39
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
9) Carefully remove the bottom brick panel.
13) Disconnect the inlet gas line from the valve.
14) Disconnect the 2 connectors from the modulating coil and the wire
harness.
Wire Harness
Connectors
Bottom Brick Panel
10) Loosen the 2 screws that hold the right side heat shield in place.
Heat
Shield
11) Lift the heat shield up and pull out slightly to clear the head screws
and then hang it on the top bracket (located directly above the heat
shield, close to the top of the firebox).
Wire Harness Disconnected
12) Disconnect both sources of power; the power cord, located on the
left hand side of the firebox and the wires connected to the back-up
battery located on the right side of the firebox.
15) Remove the control box by carefully lifting off the velcro and sliding it
out from the side of the firebox.
NOTE: The control box will need to be flipped as it is being brought
out from the side of the firebox.
Back-up
Battery
shown
Regency® L676E Direct Vent Gas Fireplace
40
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
16) Disconnect the spark cable and valve sensor wires from the control
19) Replace the valve tray and reverse steps to re-install. Ensure to
board.
check the gasket around the valve tray opening.
20) Turn on the gas supply and check for gas leaks.
21) Plug in the power source.
22) Re-install the grate.
23) Re-install the interior brick panels.
24) Re-install the log set.
25) Re-install the glass door.
26) Check the inlet (12" WC) and outlet (10"WC).
27) Re-install the right heat shield.
28) Check operation of flame control.
29) Check for proper flame appearance.
30) Re-install the exterior brick panels.
17) Remove the 16 screws that hold the valve tray to the firebox and
carefully pull out the valve tray.
Valve Tray
18) Disconnect the black and red wires from the solenoid valve.
Regency® L676E Direct Vent Gas Fireplace
41
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
MAIN ASSEMBLY
Part #
Description
1) 521-527
2) 502-008
Flue Collar Inner Assembly
Flue Collar Outer
5) 904-751
6) W260280
7) 770-066F
8) 942-117
9) W260260
Cap Screws 1/4" x 4-1/2"
Gasket Top Relief Plate
Top Relief Plate
Top Relief Frame
Top Relief Frame Gasket
11) 521-528
12) 521-540
940-351/P
Base Brick Panel
Door Frame Assembly with Glass
Glass
13) 521-013
One Piece Faceplate
15) 521-079
16) 910-950
910-075
Valve Heat Shield
Control Box with Igniter & Battery Backup IPI
Backup Battery
17) 521-075
Outer Control Box Cover
20) 521-901
521-902
Brick Panel Set - Standard Brown
Brick Panel Set - Standard Red
*
*
*
*
Left Side Panel (Interior)
Top Panel (Interior)
Back Panel (Interior)
Right Side Panel (Interior)
*
*
*
Right Side Panel (Exterior)
Base Panel (Exterior)
Left Side Panel (Exterior)
521-930
521-935
Birch Log Set
Oak Log Set
946-556
946-570
Heat Wave Kit
Heat Release Kit
521-969E
LP Conversion Kit
918-621
910-960
918-619
Manual
FireWizardTM Remote Control
Manual FireWizard-E
* Not available as a replacement part.
Regency® L676E Direct Vent Gas Fireplace
42
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
BURNER & LOG ASSEMBLY
Part #
Description
30) 521-015
31) 521-016
32) 521-042
Bracket Log Tray
Log Tray
Deflector Log Tray
35) 948-455
36) 948-454
37) 521-050
Burner Rear NG/LP
Burner Front NG/LP
Grate
40) 521-063
41) 502-061
42) 380-013
43) W840470
Bracket Log Position
Pilot Shield
Pilot Holder
Gasket Pilot Assembly
46) 521-007
521-034
47) 521-025
48) 910-480
Valve Tray
Valve Tray Gasket
Valve Bracket
Valve 845 SIT Electric
521-574E/P
521-576E/P
Valve Assembly - NG
Valve Assembly - LP
910-952
910-953
904-617
904-622
904-241
904-345
910-937
Pilot Assembly - NG
Pilot Assembly - LP
NG - Orifice #34
NG - Orifice #48
LP - Orifice #56
LP - Orifice #53
Valve Solenoid
Regency® L676E Direct Vent Gas Fireplace
43
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
Regency® L676E Direct Vent Gas Fireplace
44
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
Regency® L676E Direct Vent Gas Fireplace
45
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
Regency® L676E Direct Vent Gas Fireplace
46
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
Regency® Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit
thoroughly before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of a
Regency® Product. This warranty is not transferable.
The Warranty: Limited Lifetime
The combustion chamber, heat exchanger, burner tubes, logs, brick panels (against defective manufacture only) are covered under the Limited Lifetime Warranty for five (5)
years for parts and subsidized labour* and parts only thereafter.
Glass is covered for lifetime against thermal breakage only, parts and subsidized labour* for five (5) years and parts only thereafter from date of purchase.
Electrical and mechanical components such as switches, wiring, FPI remote controls, pilot assembly components, control boards and gas valves are covered for two years
parts and one year subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are considered repairs and continue as if new with appliance.
ie. twelve (12) months from original purchase date of appliance with a minimum of three (3) months coverage from date of replacement.
FPI venting components are covered parts and subsidized labour* for three (3) years from date of purchase.
Simpson Dura-Vent venting components (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.
Repair/replacement parts purchased by the consumer from FPI after the original coverage has expired on the unit will carry a 90 day warranty, valid with a receipt only. Any
item shown to be defective will be repaired or replaced at our discretion. No labor coverage is included with these parts.
Conditions:
Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI's option, through an accredited distributor or agent provided
that the defective part be returned to the distributor or agent Transportation Prepaid, if requested.
It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated
for manufacturer defect.
The authorized selling dealer is responsible for all in-field service work carried out on your Regency® product. FPI will not be liable for results or costs of workmanship from
unauthorized service persons or dealers.
At all times FPI reserves the right to inspect product in the field which is claimed to be defective.
All claims must be submitted to FPI by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer name,
purchase date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim.
At no time will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufactured.
ie. as products evolve, field modifications or upgrades will not be performed.
FPI will not be liable for travel costs for service work.
Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.
Embers, gaskets, and paint are not covered under the terms of this warranty policy.
Any unit which shows signs of neglect or misuse is not covered under the terms of this warranty policy.
The warranty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, negligence
or accident, spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by mechanical
systems such as furnaces, fans, clothes dryer, etc.
Freight damage to stoves and replacement parts is not covered by warranty and is subject to a claim against the freight carrier by the dealer.
FPI will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.
Performance problems due to operator error will not be covered by this warranty policy.
Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from FPI, may nullify your warranty
on this product.
Any alteration to the unit which causes sooting or carboning that results in damage to the interior / exterior facia is not the responsibility of FPI.
* Subsidy according to job scale as predetermined by FPI.
Regency® L676E Direct Vent Gas Fireplace
47
Download from Www.Somanuals.com. All Manuals Search And Download.
FPI fireplaces are designed with reliability and simplicity
in mind. In addition, our internal Quality Assurance Team
carefully inspects each unit thoroughly before it leaves
our door.
FPI FireplaceProductsInternationalLtd.ispleasedtoextend
this Limited Lifetime Warranty to the original purchaser of
a FPI Product.
See the inside back cover for details.
Register your Regency® online at
Installer: Please complete the following information
Dealer Name & Address:______________________________________________
___________________________________________________________________
Installer: ___________________________________________________________
Phone #: ___________________________________________________________
Date Installed: ______________________________________________________
Serial No.:__________________________________________________________
Regency, Liberty, AstroCap, HeatWave, Heat Release and FireWizard are trademarks of FPI Fireplace Products International Ltd.
© Copyright 2008, FPI Fireplace Products International Ltd. All rights reserved.
Printed in Canada
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Radio Shack Amplified Phone ET 293 User Guide
RedMax Blower EBZ5100Q User Guide
Reliable Iron I60 User Guide
Roland Musical Instrument TD 6V User Guide
Samson Music Mixer Servo 4060 User Guide
Samsung Label Maker SLPD220 User Guide
Sanyo Microwave Oven EM S2588B User Guide
Savin All in One Printer 9220 User Guide
Seagate Computer Hardware ST410800N ND User Guide
Sears Humidifier 75814417 User Guide