| 	
		 Models:   
					QV32B-A   
					QV36B-A   
					Installers Guide   
					Underwriters   
					Laboratories Listed   
					READ THIS MANUAL BEFORE INSTALLING OR   
					OPERATING THIS APPLIANCE. THIS INSTALLERS   
					GUIDE MUST BE LEFT WITH APPLIANCE FOR   
					FUTURE REFERENCE.   
					WARNING: IMPROPER INSTALLA-   
					TION, ADJUSTMENT, ALTERATION,   
					SERVICE OR MAINTENANCE CAN   
					CAUSE INJURY OR PROPERTY DAM-   
					AGE. REFER TO THIS MANUAL. FOR   
					ASSISTANCE ORADDITIONAL INFOR-   
					MATION CONSULT A QUALIFIED IN-   
					STALLER, SERVICE AGENCY, OR THE   
					GAS SUPPLIER.   
					WARNING: IF THE INFORMATION   
					IN THESE INSTRUCTIONS IS NOT   
					FOLLOWED EXACTLY, A FIRE OR   
					EXPLOSION MAY RESULT CAUS-   
					ING PROPERTY DAMAGE, PER-   
					SONAL INJURY, OR DEATH.   
					In the Commonwealth of Massachusetts:   
					- Do not store or use gasoline or other flam-   
					mable vapors and liquids in the vicinity of this   
					or any other appliance.   
					• installation must be performed by a licensed   
					plumber or gas fitter;   
					See Table of Contents for location of additional   
					Commonwealth of Massachusetts requirements.   
					- What to do if you smell gas   
					• Do not try to light any appliance.   
					• Do not touch any electrical switch.   
					• Do not use any phone in your building.   
					1. This appliance may be installed in an af-   
					termarket, permanently located, manufac-   
					tured (mobile) home, where not prohibited   
					by local codes.   
					• Immediately call your gas supplier from a   
					neighbor's phone. Follow the gas supplier's   
					instructions.   
					• If you cannot reach your gas supplier, call   
					the fire department.   
					2. This appliance is only for use with the type   
					of gas indicated on the rating plate. This   
					appliance is not convertible for use with   
					other gases, unless a certified kit is used.   
					- Installation and service must be performed by a   
					qualified installer, service agency, or the gas   
					supplier.   
					Please contact your Quadra-Fire dealer   
					Quadra-Fire, a brand of Hearth & Home Technologies   
					1445 North Highway, Colville, WA 99114   
					with any questions or concerns. For the   
					number of your nearest Quadra-Fire   
					
					Printed in U.S.A. Copyright 2006   
					This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471,   
					5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165,   
					6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426, 6774802,   
					6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250,   
					780403, 1418504 or other U.S. and foreign patents pending.   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					1 
				TABLE OF CONTENTS   
					Safety and Warning Information ......................................................... 2   
					Service Parts Lists ................................................................................. 4   
					Section 1: Approvals and Codes .......................................................... 9   
					Appliance Certification ............................................................................. 9   
					Installation Codes .................................................................................... 9   
					HighAltitude Installations ........................................................................ 9   
					Requirements for the Commonwealth of Massachusetts........................ 10   
					Section 2: Getting Started .................................................................. 11   
					Introducing the Village Collection Gas Fireplaces .................................. 11   
					Pre-installation Preparation .................................................................... 11   
					Section 3: Installing the Fireplace..................................................... 14   
					Constructing the Fireplace Chase .......................................................... 14   
					Step 1   
					Step 2   
					Step 3   
					Locating the Fireplace........................................................... 14   
					Framing the Fireplace ........................................................... 15   
					Installing the Vent System .................................................... 18   
					A. Vent System Approvals ................................................... 18   
					B. Installing Vent Components ............................................. 28   
					C. Vent Termination.............................................................. 31   
					Positioning, Leveling, and   
					Step 4   
					Securing the Fireplace .......................................................... 34   
					The Gas Control Systems ..................................................... 34   
					The Gas Supply Line............................................................. 35   
					Gas Pressure Requirements ................................................. 35   
					Wiring the Fireplace .............................................................. 36   
					Finishing ............................................................................... 37   
					Step 5   
					Step 6   
					Step 7   
					Î 
					Í 
					Step 8   
					Step 9   
					Step 10 Installing Trim, Logs, and Ember Material ............................. 37   
					Shutter Settings .................................................................... 37   
					Placing the Ember Material................................................... 38   
					Step 11   
					Before Lighting the Fireplace................................................. 38   
					Step 12 Lighting theAppliance ........................................................... 39   
					After the Installation ............................................................................... 39   
					Section 4: Maintaining and Servicing Your Fireplace .................... 40   
					Section 5: Troubleshooting ............................................................... 41   
					Limited Lifetime Warranty ...................................................................... 43   
					Î = Contains updated information.   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					3 
				QV32B-A   
					Beginning Manufacturing Date: 6-03   
					Ending Manufacturing Date: ______   
					Service Parts   
					(NG, LP) Exploded Parts Diagram   
					Î 
					4 
					1 
					5 
					3 
					2 
					6 
					7 
					8 Log Set Assembly   
					13   
					12   
					11   
					9 
					10   
					Part number list on following page.   
					4 
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				(NG, LP) Service Parts List   
					QV32B-A   
					AVAILABLE   
					TO SHIP IN   
					24 HOURS   
					IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your   
					dealers VIP site. When ordering, supply serial and model numbers to ensure correct service parts.   
					Î 
					ITEM   
					STANDING PILOT IGNITION   
					SERIAL #   
					PART NUMBER   
					Burner Orifice NG (#38C)   
					582-838   
					Y 
					Y 
					Burner Orifice LP (1.55mmC)   
					Andirons, Cast   
					582-8155   
					80784   
					1 
					Pre 10-06   
					Post 10-06   
					2014-004   
					2014-014   
					2 
					3 
					4 
					5 
					Burner   
					Y 
					Y 
					Glass Door Assembly   
					Log Grate   
					GLA-550TRS   
					2014-001   
					Base Pan NG, LP   
					2014-100   
					6 
					7 
					Refractory Kit (Sold as set only)   
					BRICK-293-2   
					100-250A   
					Junction Box   
					Log Set Assembly   
					Log 1   
					Y 
					Y 
					8 
					LOGS-2014   
					SRV2014-701   
					SRV2014-703   
					SRV2014-702   
					SRV780-707   
					SRV2014-704   
					9 
					10   
					11   
					12   
					13   
					Log 2   
					Log 3   
					Log 4   
					Log 5   
					Pre 10-06   
					Post 10-06   
					Pre 10-06   
					Post 10-06   
					Pre 10-06   
					Post 10-06   
					446-505   
					2103-116   
					446-517   
					2103-117   
					446-511   
					2103-511   
					Pilot Orifice NG   
					Pilot Orifice LP   
					Thermocouple   
					Y 
					Y 
					Y 
					Pre 10-06   
					Post 10-06   
					060-512   
					2103-512   
					Thermopile   
					Y 
					Lava Rock   
					060-721   
					050-721   
					530-299   
					386-122A   
					Mineral Wool   
					Exhaust Restrictor   
					Glass Latch Assembly   
					Y 
					Y 
					Y 
					Y 
					Pre 10-06   
					Post 10-06   
					Pre 10-06   
					Post 10-06   
					060-518   
					230-1570   
					060-519   
					230-1520   
					Regulator NG   
					Regulator LP   
					Y 
					ACCESSORIES   
					Fan Kit   
					GFK-160A   
					Wall Switch Kit, Off-white   
					Wall Switch Kit, White   
					WSK-21-HTI   
					WSK-21-W-HTI   
					Pre 10-06   
					Post 10-06   
					Pre 10-06   
					Post 10-06   
					NGK-2014   
					NGKS-2014   
					LPK-2014   
					LPKS-2014   
					Conversion Kit NG   
					Conversion Kit LP   
					Y 
					Y 
					Door Front - Remington Ave.   
					Door Front - Remington Ave.   
					DF-32RA-BK   
					DF-32RA-HP   
					DF-32SPO-BK   
					DF-32SPO-HP   
					DF-32SPO-VC   
					DF-32TS-BK   
					DF-32TS-HP   
					DF-32HH-BK   
					Door Front - Sun Prairie Operable   
					Door Front - Sun Prairie Operable   
					Door Front - Sun Prairie Operable   
					Door Front - Town Square   
					Door Front - Town Square   
					Door Front - Harmony Hall   
					Hood, Black   
					SRV550-175   
					Hood, Hammered Pewter   
					Hood, Hammered Pewter   
					SRV550-175-HP   
					SRV550-175-HP   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					5 
				QV36B-A   
					Beginning Manufacturing Date: 6-03   
					Ending Manufacturing Date: ______   
					Service Parts   
					(NG, LP) Exploded Parts Diagram   
					Î 
					2 
					1 
					3 
					4 
					7 
					6 
					5 
					8 Log Set Assembly   
					12   
					13   
					11   
					9 
					10   
					6 
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				(NG, LP) Service Parts List   
					QV36B-A   
					AVAILABLE   
					TO SHIP IN   
					24 HOURS   
					IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your   
					dealers VIP site. When ordering, supply serial and model numbers to ensure correct service parts.   
					ITEM   
					STANDING PILOT IGNITION   
					SERIAL #   
					PART NUMBER   
					Î 
					Burner Orifice NG (#38C)   
					582-838   
					Y 
					Y 
					Burner Orifice LP (1.55mmC)   
					Andirons, Cast   
					582-8155   
					80784   
					1 
					2 
					3 
					4 
					5 
					Pre 10-06   
					Post 10-06   
					2014-004   
					2014-014   
					Burner   
					Y 
					Y 
					Glass Door Assembly   
					Log Grate   
					GLA-550TRS   
					2014-001   
					Base Pan NG, LP   
					2014-100   
					6 
					7 
					Refractory Kit (Sold as set only)   
					BRICK-293-2   
					100-250A   
					Junction Box   
					Log Set Assembly   
					Log 1   
					Y 
					Y 
					8 
					LOGS-2014   
					SRV2014-701   
					SRV2014-703   
					SRV2014-702   
					SRV780-707   
					SRV2014-704   
					9 
					10   
					11   
					12   
					13   
					Log 2   
					Log 3   
					Log 4   
					Log 5   
					Pre 10-06   
					Post 10-06   
					Pre 10-06   
					Post 10-06   
					Pre 10-06   
					Post 10-06   
					446-505   
					2103-116   
					446-517   
					2103-117   
					446-511   
					2103-511   
					Pilot Orifice NG   
					Pilot Orifice LP   
					Thermocouple   
					Y 
					Y 
					Y 
					Pre 10-06   
					Post 10-06   
					060-512   
					2103-512   
					Thermopile   
					Y 
					Lava Rock   
					060-721   
					050-721   
					530-299   
					386-122A   
					Mineral Wool   
					Exhaust Restrictor   
					Glass Latch Assembly   
					Y 
					Y 
					Y 
					Y 
					Pre 10-06   
					Post 10-06   
					Pre 10-06   
					Post 10-06   
					060-518   
					230-1570   
					060-519   
					230-1520   
					Regulator NG   
					Regulator LP   
					Y 
					ACCESSORIES   
					Fan Kit   
					GFK-160A   
					Wall Switch Kit, Off-white   
					Wall Switch Kit, White   
					WSK-21-HTI   
					WSK-21-W-HTI   
					Pre 10-06   
					Post 10-06   
					Pre 10-06   
					Post 10-06   
					NGK-2014   
					NGKS-2014   
					LPK-2014   
					LPKS-2014   
					Conversion Kit NG   
					Conversion Kit LP   
					Y 
					Y 
					Door Front - Remington Ave.   
					Door Front - Remington Ave.   
					DF-32RA-BK   
					DF-32RA-HP   
					DF-32SPO-BK   
					DF-32SPO-HP   
					DF-32SPO-VC   
					DF-32TS-BK   
					DF-32TS-HP   
					DF-32HH-BK   
					Door Front - Sun Prairie Operable   
					Door Front - Sun Prairie Operable   
					Door Front - Sun Prairie Operable   
					Door Front - Town Square   
					Door Front - Town Square   
					Door Front - Harmony Hall   
					Hood, Black   
					SRV550-175   
					Hood, Hammered Pewter   
					Hood, Hammered Pewter   
					SRV550-175-HP   
					SRV550-175-HP   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					7 
				QV32B-A, QV36B-A   
					Service Parts   
					(NG, LP) Exploded Parts Diagram   
					Beginning Manufacturing Date: 6-03   
					Ending Manufacturing Date: ______   
					Î 
					6 
					5 
					Standing Pilot Ignition   
					Valve Assembly   
					8 
					9 
					4 
					13   
					10   
					3 
					2 
					11   
					12   
					7 
					1 
					AVAILABLE   
					TO SHIP IN   
					24 HOURS   
					ITEM   
					DESCRIPTION   
					SERIAL #   
					PART NUMBER   
					1 
					ON/OFF Rocker Switch   
					Valve NG   
					060-521A   
					Y 
					Y 
					PRE 10-06   
					POST 10-06   
					060-522   
					230-0710   
					2 
					2 
					PRE 10-06   
					POST 10-06   
					060-523   
					230-0720   
					Valve LP   
					Y 
					Y 
					3 
					4 
					5 
					Flexible Gas Connector   
					Valve Plate Gasket   
					Burner Neck Gasket   
					530-302A   
					530-431   
					2046-407   
					PRE 10-06   
					POST 10-06   
					PRE 10-06   
					POST 10-06   
					530-510A   
					2103-010   
					530-511A   
					2103-011   
					6 
					Pilot Assembly NG   
					Y 
					Y 
					6 
					7 
					8 
					Pilot Assembly LP   
					Wire Assembly   
					Valve Bracket   
					049-552a   
					PRE 10-06   
					POST 10-06   
					2025-101   
					2025-101, 2044-155   
					9 
					Flex Ball Valve Assembly   
					Piezo Ignitor   
					302-320A   
					Y 
					Y 
					10   
					291-513   
					PRE 10-06   
					POST 10-06   
					PRE 10-06   
					POST 10-06   
					PRE 10-06   
					POST 10-06   
					291-530   
					571-531   
					291-531   
					571-534   
					291-119   
					291-125   
					11   
					12   
					Pilot Control Knob   
					Flame Control Knob   
					13   
					14   
					Control Panel   
					Shutter Bracket Assembly   
					Pilot Bracket   
					2026-017   
					Y 
					PRE 10-06   
					POST 10-06   
					2065-117   
					N/A   
					Shutter Sleeve   
					2026-130   
					8 
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Approvals and   
					Codes   
					1 
					Appliance Certification   
					High Altitude Installations   
					U.L. Listed gas appliances are tested and approved without   
					requiring changes for elevations from 0 to 2,000 feet in the   
					U. S. A. and in Canada.   
					The Village Collection fireplace models discussed in this   
					Installers Guide have been tested to certification standards   
					and listed by the applicable laboratories.   
					When installing this appliance at an elevation above 2,000   
					feet, it may be necessary to decrease the input rating by   
					changing the existing burner orifice to a smaller size. Input   
					rate should be reduced by 4% for each 1000 feet above a   
					2000 foot elevation in the U.S.A. or 10% for elevations   
					between 2000 and 4500 feet in Canada. If the heating value   
					of the gas has been reduced, these rules do not apply. To   
					identify the proper orifice size, check with the local gas   
					utility.   
					Certification   
					MODELS: QV32B-A, QV36B-A   
					LABORATORY: Underwriters Laboratories   
					TYPE: Vented Gas Fireplace Heater   
					STANDARD: ANSI Z21.88•CSA2.33•UL307B   
					NOTE: THESE MODELS ARE UL LISTED TO UL307B,   
					THE STANDARD FOR GAS-BURNING HEATINGAPPLI-   
					ANCES FOR MANUFACTURED HOMES AND RECRE-   
					If installing this appliance at an elevation above 4,500 feet   
					(in Canada), check with local authorities.   
					ATIONAL VEHICLES.   
					Installation Codes   
					The fireplace installation must conform to local codes. Before   
					installing the fireplace, consult the local building code   
					agency to ensure that you are in compliance with all   
					applicable codes, including permits and inspections.   
					In the absence of local codes, the fireplace installation must   
					conform to the National Fuel Gas Code ANSI Z223.1 (in   
					the United States) or the CAN/CGA-B149 Installation Codes   
					(in Canada). The appliance must be electrically grounded   
					in accordance with local codes or, in the absence of local   
					codes with the National Electric Code ANSI/NFPA No. 70   
					(in the United States), or to the CSAC22.1 Canadian Electric   
					Code (in Canada).   
					These models may be installed in a bedroom or bed-sitting   
					room in the U.S.A. and Canada.   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					9 
				Inspection   
					NOTE: The following requirements reference various   
					Massachusetts and national codes not contained in   
					this document.   
					The state or local gas inspector of the side wall horizontally   
					vented gas fueled equipment shall not approve the installa-   
					tion unless, upon inspection, the inspector observes carbon   
					monoxide detectors and signage installed in accordance with   
					the provisions of 248 CMR 5.08(2)(a)1 through 4.   
					Requirements for the Commonwealth of   
					Massachusetts   
					Exemptions   
					The following equipment is exempt from 248 CMR 5.08(2)(a)1   
					through 4:   
					For all side wall horizontally vented gas fueled equipment   
					installed in every dwelling, building or structure used in   
					whole or in part for residential purposes, including those   
					owned or operated by the Commonwealth and where the   
					side wall exhaust vent termination is less than seven (7)   
					feet above finished grade in the area of the venting, includ-   
					ing but not limited to decks and porches, the following re-   
					quirements shall be satisfied:   
					• 
					The equipment listed in Chapter 10 entitled “Equipment   
					Not Required To Be Vented” in the most current edition   
					of NFPA 54 as adopted by the Board; and   
					• 
					Product Approved side wall horizontally vented gas fu-   
					eled equipment installed in a room or structure sepa-   
					rate from the dwelling, building or structure used in whole   
					or in part for residential purposes.   
					Installation of Carbon Monoxide Detectors   
					At the time of installation of the side wall horizontal vented   
					gas fueled equipment, the installing plumber or gasfitter   
					shall observe that a hard wired carbon monoxide detector   
					with an alarm and battery back-up is installed on the floor   
					level where the gas equipment is to be installed. In addi-   
					tion, the installing plumber or gasfitter shall observe that a   
					battery operated or hard wired carbon monoxide detector   
					with an alarm is installed on each additional level of the   
					dwelling, building or structure served by the side wall hori-   
					zontal vented gas fueled equipment. It shall be the respon-   
					sibility of the property owner to secure the services of qual-   
					ified licensed professionals for the installation of hard wired   
					carbon monoxide detectors.   
					MANUFACTURER REQUIREMENTS   
					Gas Equipment Venting System Provided   
					When the manufacturer of ProductApproved side wall hor-   
					izontally vented gas equipment provides a venting system   
					design or venting system components with the equipment,   
					the instructions provided by the manufacturer for installa-   
					tion of the equipment and the venting system shall include:   
					• 
					Detailed instructions for the installation of the venting   
					system design or the venting system components; and   
					• 
					A complete parts list for the venting system design or   
					venting system.   
					In the event that the side wall horizontally vented gas fu-   
					eled equipment is installed in a crawl space or an attic, the   
					hard wired carbon monoxide detector with alarm and bat-   
					tery back-up may be installed on the next adjacent floor   
					level.   
					In the event that the requirements of this subdivision can   
					not be met at the time of completion of installation, the   
					owner shall have a period of thirty (30) days to comply with   
					the above requirements; provided, however, that during said   
					thirty (30) day period, a battery operated carbon monoxide   
					detector with an alarm shall be installed.   
					Gas Equipment Venting System NOT Provided   
					When the manufacturer of a Product Approved side wall   
					horizontally vented gas fueled equipment does not provide   
					the parts for venting the flue gases, but identifies “special   
					venting systems”, the following requirements shall be sat-   
					isfied by the manufacturer:   
					• 
					The referenced “special venting system” instructions shall   
					be included with the appliance or equipment installation   
					instructions; and   
					Approved Carbon Monoxide Detectors   
					Each carbon monoxide detector as required in accordance   
					with the above provisions shall comply with NFPA720 and   
					be ANSI/UL 2034 listed and IAS certified.   
					• 
					The “special venting systems” shall be ProductApproved   
					by the Board, and the instructions for that system shall   
					include a parts list and detailed installation instructions.   
					A copy of all installation instructions for all Product Ap-   
					proved side wall horizontally vented gas fueled equipment,   
					all venting instructions, all parts lists for venting instruc-   
					tions, and/or all venting design instructions shall remain   
					with the appliance or equipment at the completion of the   
					installation.   
					Signage   
					A metal or plastic identification plate shall be permanently   
					mounted to the exterior of the building at a minimum height   
					of eight (8) feet above grade directly in line with the ex-   
					haust vent terminal for the horizontally vented gas fueled   
					heating appliance or equipment. The sign shall read, in   
					print size no less than one-half (1/2) inch in size, “GAS   
					VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-   
					STRUCTIONS”.   
					See Gas Connection section for additional Common-   
					wealth of Massachusetts requirements.   
					10   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Getting Started   
					2 
					Introducing the Village Collection   
					Gas Fireplaces   
					The Quadra-Fire Warranty will be voided by, and Hearth &   
					Home Technologies disclaims any responsibility for, the   
					following actions:   
					The Village Collection direct vent gas fireplaces are designed   
					to operate with all combustion air siphoned from outside of   
					the building and all exhaust gases expelled to the outside.   
					• 
					Installation of any damaged fireplace or vent system   
					component.   
					• 
					• 
					Modification of the fireplace or direct vent system.   
					The information contained in this Installers Guide, unless   
					noted otherwise, applies to all models and gas control   
					systems. Gas fireplace diagrams, including the dimensions,   
					are shown in this section.   
					Installation other than as instructed by Hearth & Home   
					Technologies .   
					• 
					• 
					Improper positioning of the gas logs or the glass door.   
					Installation and/or use of any component part not manu-   
					factured and approved by Hearth & Home Technologies,   
					not withstanding any independent testing laboratory or   
					other party approval of such component part or acces-   
					sory.   
					Pre-install Preparation   
					This gas fireplace and its components are tested and safe   
					when installed in accordance with this Installers Guide.   
					Report to your dealer any parts damaged in shipment,   
					particularly the condition of the glass. Do not install any   
					unit with damaged, incomplete, or substitute parts.   
					ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE   
					HAZARD.   
					The vent system components and trim doors are shipped   
					in separate packages. The gas logs are packaged   
					separately and must be field installed.   
					When planning a fireplace installation, it’s necessary to   
					determine:   
					• Where the unit is to be installed.   
					• The vent system configuration to be used.   
					• Gas supply piping.   
					Read all of the instructions before starting the   
					installation. Follow these instructions carefully during   
					the installation to ensure maximum safety and benefit.   
					Failure to follow these instructions will void the   
					owner’s warranty and may present a fire hazard.   
					• Electrical wiring.   
					• Framing and finishing details.   
					• Whether optional accessories—devices such as a fan,   
					wall switch, or remote control—are desired.   
					If the fireplace is to be installed on carpeting or tile, or on   
					any combustible material other than wood flooring, the   
					fireplace should be installed on a metal or wood panel that   
					extends the full width and depth of the fireplace.   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					11   
				30-11/16   
					(779mm)   
					1/2   
					(13mm)   
					15-5/16   
					(389mm)   
					16-3/8   
					(414mm)   
					15-7/8   
					(402mm)   
					8-3/4   
					(223mm)   
					Ø 6-5/8   
					(168mm)   
					Ø 8   
					(203mm)   
					ELECTRICAL   
					ACCESS   
					37-3/4   
					(960mm)   
					25   
					(635mm)   
					40   
					35-5/8   
					(905mm)   
					(1016mm)   
					3-9/16   
					(90mm)   
					2-1/8   
					(55mm)   
					36-1/8   
					(917mm)   
					GAS LINE   
					ACCESS   
					6-7/8   
					(174mm)   
					5-1/16   
					(129mm)   
					40-15/16   
					(1040mm)   
					TOP   
					STANDOFFS   
					GAS   
					CONTROLS   
					ELECTRICAL   
					ACCESS   
					GAS   
					ACCESS   
					RATING PLATE/   
					LABELS   
					Figure 1. Diagram of the QV36B-A   
					12   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				25-11/16   
					(653mm)   
					12-7/8   
					(326mm)   
					1/2   
					(13mm)   
					16-3/8   
					(414mm)   
					15-7/8   
					(402mm)   
					8-13/16   
					(223mm)   
					Ø8   
					(203mm)   
					Ø6-5/8   
					(168mm)   
					35-7/16   
					32-9/16   
					(901mm)   
					(828mm)   
					21-7/16   
					(545mm)   
					32-1/8   
					(815mm)   
					3-1/3   
					(90mm)   
					2-1/8   
					(55mm)   
					31-1/8   
					(790mm)   
					ELECTRICAL   
					ACCESS   
					GAS LINE   
					ACCESS   
					5-1/16   
					(129mm)   
					36   
					(913mm)   
					6-7/8   
					(174mm)   
					TOP   
					STANDOFFS   
					GAS   
					CONTROLS   
					ELECTRICAL   
					ACCESS   
					GAS   
					ACCESS   
					RATING PLATE/   
					LABELS   
					Figure 2. Diagram of the QV32B-A   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					13   
				3” MIN. (76mm)   
					B 
					Installing the Fireplace   
					A 
					3 
					Constructing the Fireplace Chase   
					A chase is a vertical box-like structure built to enclose the   
					gas fireplace and/or its vent system. Vertical vents that run   
					on the outside of a building may be, but are not required to   
					be, installed inside a chase.   
					E 
					D 
					CAUTION: TREATMENT OF FIRESTOP SPACERS AND   
					CONSTRUCTION OF THE CHASE MAY VARY WITH THE   
					TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT   
					SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL   
					BUILDING CODES. THEREFORE, YOUR LOCAL BUILD-   
					ING CODES MUST BE CHECKED TO DETERMINE THE   
					REQUIREMENTS FOR THESE STEPS.   
					C 
					1/2 “ MIN. (13mm)   
					A 
					42”   
					37”   
					B 
					C*   
					D*   
					45”   
					E*   
					63 3/4”   
					QV36B-A   
					QV32B-A   
					16 1/4” 31 7/8”   
					16 1/4” 29 3/8” 41 1/2” 58 3/4”   
					*If venting with (2) 900 elbows off rear of unit   
					the dimensions C, D and E will change.   
					Factory-built fireplace chases should be constructed in the   
					manner of all outside walls of the home to prevent cold air   
					drafting problems. The chase should not break the outside   
					building envelope in any manner.   
					Figure 4. Fireplace Dimensions, Locations,   
					and Space Requirements   
					Minimum Clearances   
					from the Fireplace to Combustible Materials   
					This means that the walls, ceiling, base plate and cantilever   
					floor of the chase should be insulated. Vapor and air infiltra-   
					tion barriers should be installed in the chase as per regional   
					codes for the rest of the home. Additionally, the inside sur-   
					faces may be sheetrocked and taped for maximum air tight-   
					ness.   
					Inches   
					mm   
					Glass Front...................................... 36 ........ 914   
					Floor .................................................0........... 0   
					Rear ................................................ 1/2 ........ 13   
					Sides .............................................. 1/2 ........ 13   
					Top (QV36B-A) ............................. 3 1/4 ....... 83   
					(QV32B-A) ............................. 1 1/2 ....... 38   
					Ceiling* ............................................ 31 ........ 787   
					To further prevent drafts, the firestops should be caulked to   
					seal gaps. Gas line holes and other openings should be   
					caulked or stuffed with insulation. If the unit is being in-   
					stalled on a cement slab, a layer of plywood may be placed   
					underneath to prevent conducting cold up into the room. Be   
					sure to include spark arrestors for woodburning units if they   
					are required.   
					* The clearance to the ceiling is measured from the top   
					of the unit, excluding the standoffs (see Figure 37).   
					The distance from the unit to combustible construction is to   
					be measured from the unit outer wrap surface to the com-   
					bustible construction, NOT from the screw heads that se-   
					cure the unit together.   
					THE CHASE SHOULD BE CONSTRUCTED SO THATALL   
					CLEARANCES TO THE FIREPLACE ARE MAINTAINED   
					AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.   
					Minimum Clearances   
					from the Vent Pipe to Combustible Materials   
					Step 1.   
					Locating the Fireplace   
					The following diagram shows space and clearance require-   
					ments for locating a fireplace within a room.   
					Inches   
					mm   
					Vertical Sections. ............. 1 ................ 25   
					Clearance Requirements   
					Horizontal Sections   
					Top ..................................... 3 ................ 75   
					Bottom ............................... 1 ................ 25   
					Sides ................................. 1 ................ 25   
					The top and back of the fireplace are defined by stand-offs.   
					The minimum clearance to a perpendicular wall extending   
					past the face of the fireplace is 3 inches (76mm). The back   
					of the fireplace may be recessed 16 1/4 inches (413mm)   
					into combustible construction.   
					At Wall Firestops   
					Top ..................................... 3 ................ 75   
					Bottom ............................... 1 ................ 25   
					Sides ................................. 1 ................ 25   
					For minimum clearances, see the direct vent termination   
					clearance in Figures 30 and 31.   
					14   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Step 2. Framing the Fireplace   
					CAUTION: MEASURE FIREPLACE DIMENSIONS AND   
					VERIFY FRAMING METHODS AND WALL COVERING   
					DETAILS BEFORE FRAMING.   
					Fireplace framing can be built before or after the fireplace   
					is set in place. Framing should be positioned to accommo-   
					date wall coverings and fireplace facing material. The dia-   
					gram below shows framing reference dimensions.   
					NON-COMBUSTIBLE ZONE   
					IS DEFINED BY 3” ABOVE THE   
					ELBOW FOR THE ENTIRE   
					WIDTH AND DEPTH (BEHIND THE   
					FRONT HEADER) OF THE FIREBOX.   
					3”   
					WALL STUD   
					3 1/2”   
					B 
					C 
					WARNING:   
					A 
					To ensure proper clearances the front   
					framing header must be installed on its   
					narrow edge and to the front of the frame.   
					VENT   
					FRAMING   
					HOLE   
					Framing should be   
					constructed of 2 X 4   
					lumber or heavier.   
					The framing headers may rest   
					on the fireplace stand-offs.   
					*The center of the framing hole is one (1)   
					inch (25.4mm) above the center of the   
					horizontal vent pipe.   
					D 
					Model   
					A 
					B 
					C 
					D 
					E*   
					E 
					QV36B-A   
					QV32B-A   
					42” 38-1/4” 16-1/4”   
					37”   
					41”   
					27-7/8”   
					33” 16-1/4” 36-1/2” 24-3/8”   
					Figure 5. Framing Dimensions   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					15   
				4 
					6 
					12   
					DVP4   
					DVP6   
					DVP12   
					14-1/4   
					12-3/16   
					MAX.   
					2 
					MIN.   
					24   
					36   
					DVP12A   
					48   
					9-7/8   
					DVP24   
					45.0O   
					10-1/4   
					DVP45   
					DVP36   
					11-1/4   
					7-1/4   
					1-1/4 TYP   
					DVP48   
					1/2 TYP   
					8-9/16   
					12-9/16   
					NOTE: PIPES OVERLAP 1-1/4 INCHES   
					(34.93mm) AT EACH JOINT.   
					DVP   
					90ST   
					Figure 6. DVP-Series Direct Vent Component Specifications (5-inch inner pipe / 8-inch outer pipe)   
					16   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				6 1/2   
					6 3/8   
					9 1/4   
					6 5/8   
					6 1/2   
					9 5/8   
					6 3/8   
					SL-45D   
					6 5/8   
					9 5/8   
					SL-90D   
					SL-09D   
					SL-12/17D (SL12-17D)   
					SL-24D   
					SL-48D   
					SL-36D   
					8 3/4   
					12-17   
					23 3/4   
					35 3/4   
					47 3/4   
					17-24   
					6 1/2   
					11 3/4   
					5 3/4   
					6 5/8   
					SL-17/24D   
					(SL17-24D)   
					SL-12D   
					SL-06D   
					SL-FLEX-10   
					120”   
					(3048mm)   
					SL-FLEX-2   
					SL-FLEX-5   
					SL-FLEX-3   
					60”   
					(1524mm)   
					24”   
					(610mm)   
					NOTE: PIPES OVERLAP 1-3/8 INCHES   
					(34.93mm) AT EACH JOINT.   
					36”   
					(914mm)   
					Figure 7. SL D-Series Direct Vent Component Specifications (4-inch inner pipe / 6 5/8-inch outer pipe)   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					17   
				Step 3. Installing the Vent System   
					WARNING: YOU MUST NOT MIX DVP-SERIES   
					AND SL D-SERIES COMPONENTS IN ANY VENT   
					SYSTEM CONFIGURATION.   
					! 
					A. Vent System Approvals   
					These models have vent starting collars on both the top   
					and the back of the unit. Depending upon the installation,   
					decide which ONE set of starting collars will be used to   
					attach the vent system. The starting collar sealing cap must   
					remain on the starting collar NOT used.   
					Identifying Vent Components   
					Approved vent system components are labeled for identifi-   
					cation. NO OTHER VENTING SYSTEMS OR COMPO-   
					NENTS MAY BE USED. Detailed installation instructions   
					are included with each vent termination kit and should be   
					used in conjunction with this Installers Guide. Figure 8   
					shows vent system components and terminations.   
					These models use SL-D-series, direct vent components   
					when using the TOP vent collars. This pipe is tested and   
					listed as an approved component of the fireplace. The pipe   
					is tested to be run inside an enclosed wall. There is no   
					requirement for inspection openings at each joint within the   
					wall. There is no required pitch for horizontal vent runs.   
					The vent systems installed on this gas fireplace may in-   
					clude one, two, or three 90° elbow assemblies. The rela-   
					tionships of vertical rise to horizontal run in vent configura-   
					tions using 90° elbows MUST BE strictly adhered to. The   
					rise to run relationships are shown in the venting drawings   
					and tables. Refer to the diagrams on the next several pages.   
					These models also use DVP-series direct vent components   
					when using the REAR vent collars.   
					NOTE: Two 45° elbows may be used in place of one   
					90° elbow. Maximum and minimum rise to run ratios   
					must always be maintained in the vent system when   
					using 45° elbows.   
					The flame and ember appearance may vary based on the   
					type of fuel burned and the venting configuration used.   
					Vent System Components   
					Vent System Termination Kits   
					VERTICAL   
					TERMINATION   
					DVP-SERIES   
					STORM COLLAR   
					DVP-TVHW   
					DVP-TV   
					ROOF FLASHING   
					HORIZONTAL PIPE   
					DVP-TRAP   
					HORIZONTAL   
					TERMINATION   
					SUPPORT   
					(SL-Series)   
					WALL   
					FIRESTOP   
					DVP-TB1   
					(Required   
					to have a   
					minimum of 3   
					feet of vertical   
					in the vent   
					system)   
					PIPE LENGTH   
					WALL BRACKET   
					(SL-Series)   
					90 DEGREE   
					ELBOW   
					CEILING   
					FIRESTOP   
					SL D-SERIES   
					SLK-01TRD   
					SLK-01TRF   
					SL-FLEX2-01TRF   
					SLK-SNKD   
					* 
					SLK-991DA   
					(There MUST be a 25%   
					reduction in total H   
					when using the snorkel   
					cap except when using   
					the simple up and out   
					installation (see Fig. 9)   
					* For use with flex vent only.   
					Figure 8. Vent System Components and Termination Kits   
					18   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Flex Vent   
					CAP   
					The flex vent must be supported with the spacing between   
					support intervals not exceeding 4 feet, with no more than ½   
					inch sag between supports.   
					STRAIGHT UP   
					VERTICAL VENTING   
					V (FT.)   
					A support is required at each change in venting direction,   
					and in any location where it is necessary to maintain the   
					necessary clearance to combustibles.Asimple “up and out”   
					installation (Figure 9) requires only enough support to main-   
					tain the necessary clearance to combustibles. However, the   
					vent attachment point and the firestop location are consid-   
					ered to be supports.   
					45' MAX.   
					NOTE: For vertical venting   
					over 20 feet a restrictor   
					plate is recommended for   
					improvedflameappearance.   
					V 
					TERMINATION   
					CAP   
					3” CLEARANCE   
					Use SL D-Series   
					components only.   
					FLEX-VENT   
					1”   
					CLEARANCE   
					Figure 10.   
					Straight up Vertical Venting   
					Figure 9.   
					STRAIGHT OUT HORIZONTALVENTING   
					H 
					90-DEGREE   
					ELBOWS   
					Max. Run   
					36" (914 mm)   
					Use DVP-Series   
					components only.   
					Use two 900 elbows for corner installations.   
					The use of two 900 elbows in a corner installa-   
					tion will affect space requirements (see Fig. 4)   
					H 
					Figure 11. Straight Out Horizontal Venting   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					19   
				V 
					H 
					1' MIN. (305mm)   
					2' MIN. (610mm)   
					3' MIN. (914mm)   
					4' MIN. (1.22m)   
					V+H=40' MAX. (12.4m)   
					H = 8' MAX. (2.4m)   
					2' MAX. (610mm)   
					4' MAX. (1.22m)   
					6' MAX. (1.86m)   
					8' MAX. (2.4m)   
					V 
					Use DVP-Series   
					H 
					components only.   
					Figure 12. Venting with One 90° Elbow   
					H 
					V 
					Use SL D-Series   
					components only.   
					VENTING WITH ONE (1) 90o ELBOW   
					NATURAL GAS   
					V (MIN.)   
					H (MAX.)   
					90o Elbow on Top   
					1 FT (305mm)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					5 FT (1.52m)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					H MAX. = 16 FT (4.8m)   
					V + H MAX. = 40 FT (12.2m)   
					VENTING WITH ONE (1) 90o ELBOW   
					PROPANE   
					V (MIN.)   
					H (MAX.)   
					NOTALLOWED   
					2 FT (610mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					NOTE: There MUST be a 25%   
					reduction in total H when using   
					flex vent except when using   
					the simple up and out installa-   
					tion (see Figure 9).   
					90o Elbow on Top   
					1 FT (305mm)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					5 FT (1.52m)   
					H MAX. = 16 FT (4.8m)   
					V + H MAX. = 40 FT (12.2m)   
					Figure 13. Venting with One 90° Elbow   
					20   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				V 
					H 
					H + H1   
					1' MIN. (305 mm)   
					2' MIN. (610 mm)   
					3' MIN. (914 mm)   
					4' MIN. (1.22 m)   
					2' MAX. (610 mm)   
					4' MAX. (1.22 m)   
					6' MAX. (1.86 m)   
					8' MAX. (2.48 m)   
					4' MAX. (1.22m)   
					8' MAX. (2.4m)   
					12' MAX. (3.6m)   
					16' MAX. (4.8m)   
					V+H+H1 = 40' MAX. (12.4 m)   
					H = 8' MAX. (2.48 m)   
					H+H1 = 16' MAX. (4.8m)   
					H 
					1 
					V 
					Use DVP-Series   
					components only.   
					H 
					V (FT)   
					H + H1 (FT)   
					1' MIN. (305 mm)   
					2' MIN. (610 mm)   
					2' MAX. (610 mm)   
					4' MAX. (1.22 m)   
					3' MIN. (914 mm)   
					4' MIN. (1.22 m)   
					6' MAX. (1.86 m)   
					8' MAX. (2.48 m)   
					V 
					H + H1= 8' MAX. (2.48 m)   
					V + H + H1= 40' (12.2m) MAX.   
					H 
					1 
					H 
					Figure 14. Venting with Two 90° Elbows   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					21   
				VENTING WITH TWO (2) 90o ELBOWS   
					NATURAL GAS   
					V (MIN.)   
					H + H1 (MAX.)   
					90o Elbow on Top   
					1 FT (305mm)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					5 FT (1.52m)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					H + H1 MAX. = 16 FT (4.8m)   
					V + H + H1 MAX. = 40 FT (12.2m)   
					VENTING WITH TWO (2) 90o ELBOWS   
					PROPANE   
					V (MIN.)   
					H + H1 (MAX.)   
					NOTALLOWED   
					2 FT (610mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					90o Elbow on Top   
					1 FT (305mm)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					5 FT (1.52m)   
					H + H1 MAX. = 16 FT (4.8m)   
					V + H + H1 MAX. = 40 FT (12.2m)   
					H1   
					V 
					H 
					NOTE: There MUST be a 25% reduction   
					in total H when using flex vent except   
					when using the simple up and out   
					installation (see Figure 9).   
					Use SL D-Series   
					components only.   
					Figure 15. Venting with Two 90° Elbows   
					22   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				VENTING WITH TWO (2) 90o ELBOWS   
					NATURAL GAS   
					V (MIN.)   
					H (MAX.)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					90o Elbow on Top   
					1 FT (305mm)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					5 FT (1.52m)   
					H MAX. = 16 FT (4.8m)   
					V + V1 + H MAX. = 40 FT (12.2m)   
					VENTING WITH TWO (2) 90o ELBOWS   
					PROPANE   
					V (MIN.)   
					H (MAX.)   
					90o Elbow on Top   
					1 FT (305mm)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					5 FT (1.52m)   
					NOTALLOWED   
					2 FT (610mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					H MAX. = 16 FT (4.8m)   
					V + V1 + H MAX. = 40 FT (12.2m)   
					H 
					V1   
					V 
					NOTE: There MUST be a 25%   
					reduction in total H when using   
					flex vent except when using   
					the simple up and out installa-   
					tion (see Figure 9).   
					Use SL D-Series components only.   
					Figure 16. Venting with Two 90° Elbows   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					23   
				V 
					H 
					H + H1   
					1'MIN. (305mm)   
					2'MIN. (610mm)   
					3'MIN. (914mm)   
					4' MIN. (1.22 m)   
					2' MAX. (610mm)   
					4' MAX. (1.22m)   
					6' MAX. (1.86m)   
					8' MAX. (2.48m)   
					4' MAX. (1.22m)   
					8' MAX. (2.48m)   
					12' MAX. (3.72m)   
					16' MAX. (4.8m)   
					V1+V+H+H1 = 40' MAX. (12.4m)   
					H = 8' MAX. (2.48m) H+H1 =16' MAX. (4.8m)   
					V 
					1 
					V 
					H 
					1 
					H 
					V 
					H 
					H + H1 + H2   
					1' MIN. (305 mm)   
					2' MIN. (610 mm)   
					3' MIN. (914 mm)   
					4' MIN. (1.22 m)   
					2' MAX. (610 mm)   
					4' MAX. (1.22 m)   
					6' MAX. (1.86 m)   
					8' MAX. (2.48 m)   
					4' MAX. (1.22m)   
					8' MAX. (2.48m)   
					12' MAX. (3.72m)   
					16' MAX. (4.8m)   
					1 
					2 
					V+H+H +H = 40' MAX. (12.4 m)   
					1 
					2 
					H = 8' MAX. (2.48m)   
					H + H + H = 16' MAX. (4.8m)   
					V 
					H 
					2 
					H 
					1 
					Use DVP-Series   
					components only.   
					H 
					Figure 17. Venting with Three 90° elbows   
					24   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				VENTING WITH THREE (3) 90o ELBOWS   
					NATURALGAS   
					VENTING WITH THREE (3) 90o ELBOWS   
					PROPANE   
					V (MIN.)   
					H(MAX.)   
					H + H1(MAX.)   
					V (MIN.)   
					H(MAX.)   
					H + H1(MAX.)   
					90o Elbow on Top   
					1 FT (305mm)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					5 FT (1.52m)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					12 FT (3.72m)   
					16 FT (4.8m)   
					16 FT (4.8m)   
					90o Elbow on Top   
					1 FT (305mm)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					5 FT (1.52m)   
					NOT ALLOWED NOT ALLOWED   
					2 FT (610mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					4 FT (1.22m)   
					8 FT (2.48m)   
					12 FT (3.72m)   
					16 FT (4.8m)   
					16 FT (4.8m)   
					V + H + V1 + H1 MAX. = 40 FT (12.2m)   
					V + H + V1 + H1 MAX. = 40 FT (12.2m)   
					H 
					H1   
					V1   
					V 
					Use SL D-Series   
					components only.   
					NOTE: There MUST be a 25% reduction in total H when   
					using flex vent except when using the simple up and   
					out installation (see Figure 9).   
					Figure 18. Venting with three 90° elbows   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					25   
				VENTING WITH THREE (3) 90o ELBOWS   
					Model: QV32B-A   
					NATURAL GAS   
					Model: QV36B-A   
					H + H1 (MAX.)   
					V (MIN.)   
					H + H1 (MAX.)   
					90o Elbow on Top   
					1 FT (305mm)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					5 FT (1.52m)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					H + H1 MAX. = 16 FT (4.8m)   
					V + V1 + H + H1 MAX. = 40 FT (12.2m)   
					VENTING WITH THREE (3) 90o ELBOWS   
					PROPANE   
					V (MIN.)   
					H + H1 (MAX.)   
					90o Elbow on Top   
					1 FT (305mm)   
					2 FT (610mm)   
					3 FT (914mm)   
					4 FT (1.22m)   
					5 FT (1.52m)   
					NOTALLOWED   
					2 FT (610mm)   
					4 FT (1.22m)   
					6 FT (1.86m)   
					8 FT (2.48m)   
					16 FT (4.8m)   
					H + H1 MAX. = 16 FT (4.8m)   
					V + V1 + H + H1 MAX. = 40 FT (12.2m)   
					V 
					1 
					V 
					H 
					H 
					1 
					Use SL D-Series   
					components only.   
					NOTE: There MUST be a 25% reduction in   
					total H when using flex vent except when   
					using the simple up and out installation   
					(see Figure 9).   
					Figure 19. Venting with three 90° elbows   
					26   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				VENTING WITH FOUR (4) 90° ELBOWS   
					NATURAL AND PROPANE GAS   
					H1   
					V (MIN.)   
					H (MAX.)   
					V1 (MIN.)   
					H1 (MAX.)   
					V2 (MIN.)   
					2' (609mm) 5' (1.52m)   
					5' (1.52m)   
					5' (1.52m)   
					4.5' (1.37m)   
					V + V1 + V2 + H + H1 MAX. = 40' (12.2m)   
					V2   
					V1   
					H 
					Use SL D-Series   
					components only.   
					V 
					NOTE: There MUST be a 25%   
					reduction in total H when using   
					flex vent except when using   
					the simple up and out installa-   
					tion (see Figure 9).   
					Figure 20. Venting with Four 90° elbows   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					27   
				B. Installing Vent Components   
					After determining which set of starting collars will be used   
					(top or rear), follow venting instructions accordingly.   
					DVP Series Venting Only:   
					1. Attaching the Venting to the Fireplace   
					Refer to Cinch Pipe and Termination Cap installation in-   
					structions.   
					Venting Out the Rear Vent (See Figure 21)   
					Remove the installed rear seal cap from the rear starting collars   
					by cutting the strap at each end. Remove the insulation inside   
					the 5” collar. Follow the vent configuration tables accordingly.   
					WARNING: ENSURE THAT THE FIBERGLASS   
					! 
					GASKET SUPPLIED WITH THE FIREPLACE SEALS   
					Remove the 5” diameter heat shield from the 5” diameter collar   
					by sliding it out.   
					BETWEEN THE FIRST VENT COMPONENT AND   
					THE OUTER FIREPLACE WRAP.   
					If the installation is for a termination cap attached directly   
					to the fireplace, skip to the sections, Install Firestops and   
					Vent Termination.   
					WARNING: THE TOP HEAT SHIELD (INSIDE   
					THE FIREBOX) MUST REMAIN ATTACHED IF   
					THE VENT SYSTEM IS ATTACHED TO THE   
					REAR STARTING COLLARS. SEE FIGURE 21.   
					! 
					2. Continue Adding Vent Components   
					Venting Out the Top Vent   
					Refer to Cinch Pipe and Termination Cap installation in-   
					structions.   
					Remove the top vent collar seal cap by cutting the strap at   
					each end. Remove the insulation inside BOTH the 4”   
					diameter and 6 5/8” diameter collars. (See Figure 21).   
					• Continue adding vent components, locking each succeed-   
					ing component into place.   
					Remove the 4” diameter heat shield from the 4” diameter   
					collar by sliding it out.   
					• Ensure that each succeeding vent component is secure-   
					ly fitted and locked into the preceding component in the   
					vent system.   
					You have to take the glass off for positioning the logs when the   
					unit is finally installed in place and finished around it. Attach   
					vent system to the top starting collars.   
					• 90° elbows may be installed and rotated to any point   
					around the preceding component’s vertical axis. If an el-   
					bow does not end up in a locked position with the pre-   
					ceding component, attach with a minimum of two (2)   
					sheet metal screws.   
					WARNING: THE REAR VENT COLLAR SEAL   
					CAP MUST REMAINATTACHED TO THE REAR   
					VENT COLLARS IF THE VENT SYSTEM ISATTACHED   
					TO THE TOP STARTING COLLARS. SEE FIGURE 21.   
					! 
					3. Install Support Brackets   
					Refer to Cinch Pipe and Termination Cap installation in-   
					structions.   
					WARNING: FAILURE TO REMOVE INSULATION   
					IN THE SET OF COLLARS YOU ARE USING   
					COULD NEGATIVELY AFFECT FIREPLACE   
					PERFORMANCE.   
					! 
					Go to Step 4 Install Firestops.   
					WARNING: YOU MUST LEAVE THE INSULA-   
					TION IN PLACE IN THE SET OF COLLARS YOU   
					! 
					ARE NOT USING. FAILURE TO DO THIS COULD   
					CAUSE A FIRE.   
					Insert screwdriver   
					or similar object   
					here to remove cap.   
					Venting   
					Out Top   
					Venting   
					Out Rear   
					SEAL   
					CAP   
					INSULATION,   
					DISCARD   
					BOTH   
					SEAL   
					CAP   
					PIECES   
					HEAT   
					SHIELD   
					HEAT   
					SHIELD   
					DISCARD   
					INSULATION   
					CUT HERE   
					Figure 21.   
					28   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SL-D and SL-Flex Series Venting Only:   
					1. Attach the First Vent Component to the   
					Starting Collars   
					To attach the first vent component to the starting collars   
					of the fireplace:   
					• Lock the vent components into place by sliding the con-   
					centric pipe sections with four (4) equally spaced interior   
					beads into the fireplace collar or previously installed com-   
					ponent end with four (4) equally spaced indented sections.   
					Figure 22. Adding Venting Components   
					3. Install Support Brackets   
					• When the internal beads of each outer pipe line up, ro-   
					tate the pipe section clockwise about one-quarter (1/4)   
					turn. The vent pipe is now locked together.   
					For Horizontal Runs - The vent system must be supported   
					every five (5) feet of horizontal run by a horizontal pipe support.   
					• Slide the ceramic fiber pad over the first vent section and   
					place it flush to the fireplace (see Figure 1). This will   
					prevent cold air infiltration. High temp caulk may be used   
					to hold the part in place. Continue to add vent compo-   
					nents.   
					To install support brackets for horizontal runs:   
					• Place the pipe supports around the vent pipe.   
					• Nail the pipe supports to the framing members.   
					If the installation is for a termination cap attached directly   
					to the fireplace, skip to the sections, Install Firestops and   
					Vent Termination.   
					For Vertical Runs - The vent system must be supported   
					every eight (8) feet (2.4m) above the fireplace flue outlet by   
					wall brackets. To install support brackets for vertical runs:   
					• Attach wall brackets to the vent pipe and secure the wall   
					bracket to the framing members with nails or screws.   
					2. Continue Adding Vent Components   
					• Continue adding vent components, locking each succeed-   
					ing component into place.   
					WALL BRACKET   
					WALL STUD   
					• Ensure that each succeeding vent component is secure-   
					ly fitted and locked into the preceding component.   
					• 90° elbows may be installed and rotated to any point   
					around the preceding component’s vertical axis. If an el-   
					bow does not end up in a locked position with the pre-   
					ceding component, attach with a minimum of two (2)   
					sheet metal screws.   
					8 FT. (2.4m)   
					FLUE   
					OUTLET   
					1 INCH MIN.   
					(25.4mm)   
					Figure 23. Installing Support Brackets   
					Go to Step 4 Install Firestops.   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					29   
				For Vertical Runs - One ceiling firestop is REQUIRED at   
					the hole in each ceiling through which the vent passes.   
					DVP, SL-D and SL-Flex Series Venting:   
					STEP 4. Install Firestops   
					To install firestops for vertical runs that pass through ceilings:   
					For Horizontal Runs - Firestops are REQUIRED on both   
					• Position a plumb bob directly over the center of the verti-   
					cal vent component.   
					sides of a combustible wall through which the vent passes.   
					NOTE: Model DVP-TRAP or SLK-01TRD does not need   
					an exterior firestop on an exterior combustible wall.   
					• Mark the ceiling to establish the centerpoint of the vent.   
					• Drill a hole or drive a nail through this centerpoint.   
					To install firestops for horizontal runs that pass through   
					either interior or exterior walls:   
					Cut a 12” x 10“ (305mm x 25mm) hole through the wall for   
					DVP-series or a 10” x 10” (254mm x 254mm) hole for SL-D-   
					series pipe. The center of the framing hole is one (1) inch   
					(25.4mm) above the center of the horizontal vent pipe.   
					• Check the floor above for any obstructions, such as wir-   
					ing or plumbing runs.   
					• Reposition the fireplace and vent system, if necessary,   
					to accommodate the ceiling joists and/or obstructions.   
					• Position the firestops on both sides of the hole previ-   
					ously cut and secure the firestops with nails or screws.   
					• Cut a 10-inch X 10-inch (254mm X 254mm) hole through   
					the ceiling, using the centerpoint previously marked.   
					• The heat shields of the firestops MUST BE placed to-   
					wards the top of the hole.   
					• Frame the hole with framing lumber the same size as the   
					ceiling joists.   
					• Continue the vent run through the firestops.   
					NOTE: There must be NO INSULATION or other   
					combustibles inside the framed firestop opening.   
					NOTE: There must be NO INSULATION or other   
					combustibles inside the framed firestop opening.   
					10"   
					(254mm)   
					10" (254mm)   
					10" (254mm)   
					1" (25.4 mm)   
					12"(DVP) or 10" (SL)   
					(305mm or 254mm)   
					CHIMNEY   
					HOLE   
					VENT PIPE   
					EXISTING CEILING   
					JOISTS   
					NEW   
					FRAMING   
					MEMBERS   
					CEILING   
					Figure 24. Hole and Vent Pipe   
					Figure 26. Hole & New Framing Members   
					HEAT SHIELD   
					TRIM HEAT   
					SHIELD IF TOO   
					LONG, ADD TO   
					SHIELD IF TOO   
					SHORT   
					EXTERIOR   
					FIRESTOP   
					INTERIOR   
					FIRESTOP   
					Figure 25. Heat Shield, Interior & Exterior Firestops   
					30   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				If the area above the ceiling is NOT an attic, position and   
					secure the ceiling firestop on the ceiling side of the previously   
					cut and framed hole.   
					C. Vent Termination   
					SL-Series Venting Only:   
					For Horizontal Terminations - To attach and secure the   
					termination to the last section of horizontal vent:   
					• Rotate and interlock the ends as described at the begin-   
					ning of the Installing Vent Components section.   
					JOIST   
					• The termination kit should pass through the wall firestops   
					from the exterior of the building.   
					• Adjust the termination cap to its final exterior position on   
					the building.   
					For trapezoidal cap termination kits:   
					• Using screws secure the cap to the exterior wall through   
					the flanges in the cap.   
					CEILING   
					NAILS (3 REQUIRED)   
					For DVP Venting Only:   
					CEILING FIRESTOP   
					Refer to Cinch Pipe and Termination Cap installation in-   
					structions.   
					Figure 27. Ceiling Firestop (Ceiling Side)   
					If the area above the ceiling IS an attic, position and secure   
					the firestop on top of the previously framed hole.   
					For All Venting:   
					WARNING: THE TERMINATION CAPMUST BE   
					POSITIONED SO THAT THEARROW IS POINT-   
					ING UP.   
					NOTE: Keep insulation away from the vent pipe at least   
					1 inch (25mm).   
					! 
					NAILS (3 REQUIRED)   
					WARNING: VENTING TERMINALS SHALL   
					NOT BE RECESSED INTO AWALL OR SID-   
					! 
					ING. VENT TERMINATION CLEARANCES MUST   
					BE FOLLOWED TO AVOID FIRE DANGER. SEE   
					VENT TERMINATION MINIMUM CLEARANCES DI-   
					AGRAM ON FOLLOWING PAGE.   
					RAFTER   
					CEILING   
					CEILING FIRESTOP   
					Figure 28. Attic Firestop   
					7 1/4"   
					(184mm)   
					Figure 29. Trapezoid Termination Cap   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					31   
				O 
					N 
					P 
					G 
					R 
					v 
					A 
					H 
					D 
					Q 
					(See Note 2)   
					v 
					V 
					B 
					L 
					U.S.   
					(3 FT)   
					B 
					T 
					v 
					v 
					v 
					B 
					v 
					S 
					S 
					Electrical   
					Service   
					V 
					V 
					F 
					v 
					M 
					I 
					D*   
					V 
					v 
					X 
					A 
					J or K   
					X 
					= VENT TERMINAL   
					=AIR SUPPLY INLET   
					= AREA WHERE TERMINAL IS NOT PERMITTED   
					V 
					A 
					B 
					= 12" ....................... clearances above grade, veran-   
					K 
					= 3 ft. (U.S.A.)   
					(See Note 1)   
					da, porch, deck or balcony   
					6 ft. (Canada) ......... clearance to a mechanical   
					air supply inlet   
					= 12" ....................... clearances to window or door   
					that may be opened, or to per-   
					L** = 7 ft. ......................... clearance above paved   
					(See Note 1)   
					sidewalk or a paved driveway   
					located on public property   
					manently closed window.   
					D*   
					= 18" ....................... vertical clearance to unventilat-   
					ed soffit or to ventilated soffit lo-   
					M*** = 18" ......................... clearance under veranda,   
					porch, deck or balcony   
					cated above the terminal   
					N 
					O 
					P 
					= 6” ........................... non-vinyl sidewalls   
					12” ......................... vinyl sidewalls   
					*30” min. .............. for vinyl clad soffits and below   
					electrical service   
					= 18” ......................... non-vinyl soffit and overhang   
					42” ......................... vinyl soffit and overhang   
					F 
					= 
					9" ........................ clearance to outside corner   
					G 
					H 
					= 6" ......................... clearance to inside corner   
					= 8 ft.   
					= 3 ft. (Canada) ...... not to be installed above a gas   
					meter/regulator assembly within   
					______________________________Q___M_I_N___________________________________   
					_____1___c__a_p__________________3___f_e_e__t_________________2__x__Q____A_C_T_U_A_L____   
					______2__c__a_p__s________________6___f_e_e__t_________________1__x__Q____A_C_T_U_A_L____   
					______3__c__a_p__s_________________9__f_e_e__t_______________2_/_3__x___Q___A_C_T_U_A__L___   
					4 caps 12 feet 1/2 x Q ACTUAL   
					RMAX   
					3 feet (90cm) horizontally from the   
					center-line of the regulator   
					I 
					= 3 ft. (U.S.A.)   
					6 ft. (Canada) ...... clearance to gas service regu-   
					lator vent outlet   
					= 9" (U.S.A.)   
					QMIN = # termination caps x 3   
					RMAX = (2 / # termination caps) x QACTUAL   
					J 
					12" (Canada) ........ clearance to non-mechanical air   
					supply inlet to building or the   
					combustion air inlet to any other   
					appliance   
					S = 6" MIN................... clearance from sides of elec-   
					(See Note 5)   
					trical service   
					T 
					= 12" MIN. ................ clearance above electrical   
					(See Note 5)   
					service   
					NOTE 3: Local codes or regulations may require different   
					clearances.   
					** a vent shall not terminate directly above a sidewalk or paved   
					driveway which is located between two single family dwellings   
					and serves both dwellings.   
					NOTE 4: Termination caps may be hot. Consider their proximity to   
					doors or other traffic areas.   
					*** only permitted if veranda, porch, deck or balcony is fully open on   
					a minimum of 2 sides beneath the floor.   
					NOTE 5: Location of the vent termination must not interfere with   
					access to the electrical service.   
					NOTE 1: On private property where termination is less than 7 feet   
					above a sidewalk, driveway, deck, porch, veranda or balcony, use of   
					a listed cap shield is suggested.   
					WARNING: In the U.S: Vent system termination is NOT permitted   
					in screened porches. You must follow side wall, overhang and   
					ground clearances as stated in the instructions.   
					NOTE 2: Termination in an alcove space (spaces open only on one side   
					and with an overhang) are permitted with the dimensions specified for   
					vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum   
					between termination caps. 2. All mechanical air intakes within 10 feet   
					of a termination cap must be a minimum of 3 feet below the termination   
					cap. 3. All gravity air intakes within 3 feet of a termination cap must be   
					a minimum of 1 foot below the termination cap.   
					In Canada: Vent system termination is NOT permitted in screened   
					porches. Vent system termination is permitted in porch areas   
					with two or more sides open. You must follow all side walls,   
					overhang and ground clearances as stated in the instructions.   
					Heat-N-Glo assumes no responsibility for the improper perfor-   
					mance of the fireplace when the venting system does not meet   
					these requirements.   
					Figure 30. Vent Termination Minimum Clearances   
					CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE   
					INSTALLED.   
					32   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				To seal the roof hole, and to divert rain and snow from the   
					vent system:   
					For Vertical Terminations - To locate the vent and install   
					the vent sections:   
					• Locate and mark the vent centerpoint on the underside   
					of the roof, and drive a nail through the centerpoint.   
					• Attach a flashing to the roof using nails, and use a non-   
					hardening mastic around the edges of the flashing base   
					where it meets the roof.   
					• Make the outline of the roof hole around the centerpoint   
					nail.   
					• Attach a storm collar over the flashing joint to form a   
					water-tight seal. Place non-hardening mastic around the   
					joint, between the storm collar and the vertical pipe.   
					• The size of the roof hole framing dimensions depend on the   
					pitch of the roof. There MUST BE a 1-inch (25.4mm) clear-   
					ance from the vertical vent pipe to combustible materials.   
					• Slide the termination cap over the end of the vent pipe   
					and snap into place.   
					• Mark the roof hole accordingly.   
					• Cover the opening of the installed vent pipes.   
					• Cut and frame the roof hole.   
					HORIZONTAL   
					OVERHANG   
					2 FT. MIN.   
					2 FT.   
					20” MIN.   
					MIN.   
					VERTICAL   
					WALL   
					(DVP PIPE)   
					• Use framing lumber the same size as the roof rafters   
					and install the frame securely. Flashing anchored to the   
					frame must withstand heavy winds.   
					LOWEST   
					DISCHARGE   
					OPENING   
					TERMINATION   
					CAP   
					• Continue to install concentric vent sections up through   
					the roof hole and up past the roof line until you reach the   
					appropriate distance above the roof.   
					X 
					12   
					ROOF PITCH   
					IS X/ 12   
					WARNING: MAJOR U.S. BUILDING CODES   
					! 
					SPECIFY MINIMUM CHIMNEY AND/OR   
					VENT HEIGHTABOVE THE ROOF TOP. THESE MIN-   
					IMUM HEIGHTS ARE NECESSARY IN THE INTER-   
					EST OF SAFETY. SEE THE FOLLOWING DIAGRAM   
					FOR MINIMUM HEIGHTS, PROVIDED THE TERMI-   
					NATION CAP IS AT LEAST TWO (2) FEET (20 INCH-   
					ES FOR DVP PIPE) FROMAVERTICAL WALLAND   
					2-FEET BELOWAHORIZONTAL OVERHANG.   
					H (MIN.) - MINIMUM HEIGHT FROM ROOF   
					TO LOWEST DISCHARGE OPENING   
					Roof Pitch   
					H (min.) ft.   
					flat to 6/12   
					6/12 to 7/12   
					1.0   
					1.25   
					1.5   
					2.0   
					over 7/12 to 8/12   
					over 8/12 to 9/12   
					NOTE: This also pertains to vertical vent systems in-   
					stalled on the outside of the building.   
					over 9/12 to 10/12   
					over 10/12 to 11/12   
					over 11/12 to 12/12   
					over 12/12 to 14/12   
					over 14/12 to 16/12   
					over 16/12 to 18/12   
					over 18/12 to 20/12   
					over 20/12 to 21/12   
					2.5   
					3.25   
					4.0   
					5.0   
					6.0   
					7.0   
					7.5   
					8.0   
					Figure 31. Minimum Height from Roof to   
					Lowest Discharge Opening   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					33   
				Step 4. Positioning, Leveling, and   
					Securing the Fireplace   
					Step 5. The Gas Control System   
					WARNING: THIS UNIT IS NOT FOR USE WITH   
					SOLID FUEL.   
					The diagram below shows how to properly position, level,   
					and secure the fireplace.   
					! 
					The type of gas control system used with this model is   
					Standing Pilot Ignition.   
					WARNING:   
					To ensure proper clearances   
					the front framing header   
					must be installed on its   
					narrow edge and to the   
					front of the frame.   
					Standing Pilot Ignition System   
					This system includes millivolt control valve, standing pilot,   
					thermopile/thermocouple flame sensor, and piezo ignitor.   
					WARNING: 110-120 VAC MUST NEVER BE   
					CONNECTED TO A CONTROL VALVE IN A   
					! 
					MILLIVOLT SYSTEM.   
					STANDING PILOT   
					NAILING TABS   
					(BOTH SIDES)   
					Figure 32. Proper Positioning, Leveling, and   
					Securing of a Fireplace   
					Figure 33. Gas Control System   
					• Place the fireplace into position.   
					• Level the fireplace from side to side and from front to   
					back.   
					• Shim the fireplace with non-combustible material, such   
					as sheet metal, as necessary.   
					• Secure the fireplace to the framing using nails or screws   
					through the nailing tabs.   
					34   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Step 6. The Gas Supply Line   
					NOTE: Have the gas supply line installed in accordance   
					with local building codes by a qualified installer   
					approved and/or licensed as required by the locality.   
					(In the Commonwealth of Massachusetts installation   
					must be performed by a licensed plumber).   
					NOTE: Before the first firing of the fireplace, the gas   
					supply line should be purged of any trapped air.   
					FLEX CONNECTOR   
					NOTE: Consult local building codes to properly size   
					the gas supply line leading to the 1/2 inch (13mm)   
					hook-up at the unit.   
					MANUAL   
					SHUT-OFF VALVE   
					GAS VALVE   
					This gas fireplace is designed to accept a 1/2 inch (13mm)   
					gas supply line. To install the gas supply line:   
					USE WRENCH ON SHUT-OFF   
					VALVE WHEN TIGHTENING GAS LINE   
					• A listed (and Commonwealth of Massachusetts approved)   
					1/2 inch (13mm) tee-handle manual shut-off valve and a   
					listed flexible gas connector are connected to the 1/2   
					inch (13mm) inlet of the control valve. NOTE: If substi-   
					tuting for these components, please consult local codes   
					for compliance.   
					Figure 34. Gas Supply Line   
					Step 7. Gas Pressure Requirements   
					Pressure requirements for these gas fireplaces are shown   
					in the table below.   
					• Locate the gas line access hole in the outer casing of   
					the fireplace.   
					Pressure   
					Natural Gas   
					Propane   
					• The gas line may be run from either side of the fireplace   
					provided the hole in the outer wrap does not exceed 2” in   
					diameter and it does not penetrate the actual firebox.   
					Minimum   
					Inlet Pressure   
					5.0 inches   
					w.c.   
					11.0 inches   
					w.c.   
					Maximum Inlet   
					Gas Pressure   
					14.0 inches   
					w.c.   
					14.0 inches   
					w.c.   
					• Open the fireplace lower grille, insert the gas supply line   
					through the gas line hole, and connect it to the shut-off valve.   
					Manifold   
					Pressure   
					3.5 inches   
					w.c.   
					10.0 inches   
					w.c.   
					• When attaching the pipe, support the control so that the   
					lines are not bent or torn.   
					• After the gas line installation is complete, use a soap   
					solution to carefully check all gas connections for leaks.   
					A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is   
					provided on the inlet and outlet side of the gas control for a   
					test gauge connection to measure the manifold pressure.   
					Use a small flat blade screwdriver to crack open the screw   
					in the center of the tap. Position a rubber hose over the tap   
					to obtain the pressure reading.   
					WARNING: DO NOT USE AN OPEN FLAME   
					TO CHECK FOR GAS LEAKS.   
					! 
					• Insert insulation from the outside of the fireplace and   
					pack the insulation tightly to totally seal between the   
					pipe and the outer casing.   
					The fireplace and its individual shut-off valve must be   
					disconnected from the gas supply piping system during   
					any pressure testing of the system at test pressures in   
					excess of one-half (1/2) psig (3.5 kPa).   
					• At the gas line access hole the gap between the supply   
					piping and gas access hole can be plugged with non-   
					combustible insulation to prevent cold air infiltration.   
					The fireplace must be isolated from the gas supply piping   
					system by closing its individual shut-off valve during any   
					pressure testing of the gas supply piping system at test   
					pressures equal to or less than one-half (1/2) psig (3.5 kPa).   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					35   
				STANDING   
					PILOT   
					REMOTE SWITCH   
					PIGTAIL   
					ON   
					OFF   
					ON/OFF   
					SWITCH   
					VALVE   
					WHT   
					RED   
					OPTIONAL WALL SWITCH,   
					THERMOSTAT OR REMOTE   
					Figure 35. Standing Pilot Ignition Wiring Diagram   
					Î 
					Step 8. Wiring the Fireplace   
					Optional Accessories   
					NOTE: Electrical wiring must be installed by a licensed   
					electrician.   
					Optional fan and remote control kits require that 110-120   
					VAC be wired to the factory installed junction box before   
					the fireplace is permanently installed.   
					CAUTION: DISCONNECT REMOTE CONTROLS IF AB-   
					SENT FOR EXTENDED TIME PERIODS. THIS WILL PRE-   
					VENTACCIDENTAL FIREPLACE OPERATION.   
					Wall Switch   
					For Standing Pilot Ignition Wiring   
					Position the wall switch in the desired position on a wall.   
					Run a maximum of 25 feet (7.8 m) or less length of 18   
					A.W.G. minimum wire and connect it to the fireplace ON/   
					OFF switch pigtails.   
					Appliance Requirements   
					• This appliance DOES NOT require 110-120 VAC to operate.   
					WARNING: DO NOT CONNECT 110-120 VAC TO   
					THE GAS CONTROL VALVE OR WALL SWITCH   
					OR THE APPLIANCE WILL MALFUNCTION   
					AND THE VALVE WILL BE DESTROYED.   
					CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-   
					TION WHEN SERVICING CONTROLS. WIRING ERRORS   
					CAN CAUSE IMPROPERAND DANGEROUS OPERATION.   
					VERIFY PROPER OPERATION AFTER SERVICING.   
					! 
					ROMEX   
					CONNECTOR   
					14/2WG   
					COVER PLATE   
					OUTSIDE FIREBOX   
					T 
					H 
					W 
					K 
					L 
					SENSOR   
					SWITCH   
					B 
					BLOWER   
					W 
					H 
					T 
					B 
					L 
					K 
					COPPER   
					GROUND ATTACHED   
					TO GRN SCREW WITH   
					GRN WIRE   
					GRN WIRE   
					INSIDE BOX   
					FAN   
					RECEPTACLE   
					SPEED   
					CONTROL   
					Figure 36. Fan Wiring Diagram   
					Î 
					36   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Hearth Extensions   
					Step 9. Finishing   
					A hearth extension may be desirable for aesthetic reasons.   
					However,ANSI or CAN/CGAtesting standards do not require   
					hearth extensions for gas fireplace appliances.   
					Figure 37 shows the minimum vertical and corresponding   
					maximum horizontal dimensions of fireplace mantels or other   
					combustible projections above the top front edge of the   
					fireplace. See Figures 3 and 4 for other fireplace clearances.   
					Only non-combustible materials may be used to cover the   
					black fireplace front.   
					Step 10. Installing Trim, Logs and   
					Ember Material   
					WARNING: WHEN FINISHING THE FIREPLACE,   
					NEVER OBSTRUCT OR MODIFY THE AIR IN-   
					Installing the Trim   
					! 
					Combustible materials may be brought up to the specified   
					clearances on the side and top front edges of the fireplace,   
					but MUST NEVER overlap onto the front face. The joints   
					between the finished wall and the fireplace top and sides   
					can only be sealed with a 300° F. (149° C) minimum sealant.   
					LET/OUTLET GRILLES IN ANY MANNER.   
					CEILING   
					WARNING: WHEN FINISHING THE FIREPLACE,   
					NEVER OBSTRUCT OR MODIFY THE AIR INLET/   
					OUTLET GRILLES IN ANY MANNER.   
					12"   
					11"   
					10"   
					! 
					9"   
					31”   
					8"   
					Install optional marble and brass trim surround kits as   
					desired. Marble, brass, brick, tile, or other non-combustible   
					materials can be used to cover up the gap between the   
					sheet rock and the fireplace.   
					7"   
					6"   
					12”   
					11”   
					5"   
					10”   
					4"   
					2”   
					9”   
					3"   
					8”   
					7”   
					2"   
					6”   
					5”   
					Do not obstruct or modify the air inlet/outlet grilles. When   
					overlapping on both sides, leave enough space so that the   
					bottom grille can be opened and the trim door removed.   
					4"   
					3”   
					1”   
					1”   
					Positioning the Logs   
					TOP FRONT EDGE   
					OF FIREPLACE   
					If the gas logs have been factory installed they should not   
					need to be positioned. If the logs have been packaged   
					separately, refer to the instructions that accompany the   
					logs. Save the log instructions with this manual.   
					Figure 37.   
					Minimum Vertical and Maximum Horizontal   
					Dimensions of Combustibles above Fireplace   
					If sooting occurs, the logs might need to be repositioned   
					slightly to avoid excessive flame impingement.   
					CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS   
					AND THE FIREPLACE SURROUND (TOP AND SIDES)   
					ARE SEALED, A 300° F. MINIMUM SEALANT MATE-   
					RIAL MUST BE USED. THESE JOINTS ARE NOT RE-   
					QUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE   
					MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF   
					NEEDED) CAN BE APPLIED AS FACING TO THE FIRE-   
					PLACE SURROUND (SEE FIGURE 38).   
					Shutter Settings   
					Model   
					NG   
					LP   
					___________________________________________   
					QV32B-A   
					1/16”   
					3/8”   
					___________________________________________   
					QV36B-A   
					1/16”   
					3/8”   
					FINISH MATERIAL   
					MAY BE COMBUSTIBLE   
					- TOP AND SIDES   
					OF UNIT   
					TOP SEAL   
					JOINT   
					SIDE SEAL   
					JOINT   
					0”   
					0”   
					Figure 38. Sealant Material   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					37   
				Step 11. Before Lighting the Fireplace   
					Placing the Ember Material   
					Ember material is shipped with this gas fireplace. The bag   
					labeled Glowing Embers (050-721) is standard glowing   
					ember material. To place the ember material:   
					Before lighting the fireplace, be sure to do the following:   
					Remove all paperwork from underneath the fireplace.   
					Review safety warnings and cautions   
					• 
					• 
					• 
					• 
					Remove the door bylifting it up and away from the unit.   
					Unlatch the latches at the top and bottom of the glass.   
					Remove the glass from the unit (see Figure 44).   
					• Read the Safety and Warning Information section at   
					the beginning of this Installers Guide.   
					Double-check for gas leaks   
					Place dime size pieces of ember material about 1/2 inch   
					apart near port holes in burner top. Do NOT press em-   
					bers into burner ports. Cover the top of the burner with a   
					single layer of ember material. For best performance do   
					NOT place embers on the ports at the rear of the burner   
					(see Figure 45).   
					• Before lighting the fireplace, double-check the unit for   
					possible gas leaks.   
					Double-check vent terminations and front grilles for   
					obstructions.   
					• Before lighting the fireplace, double-check the unit for   
					possible obstructions that could be blocking the vent ter-   
					minations or the front grilles.   
					• 
					• 
					Save the remaining ember materials for use during fire-   
					place servicing. The bag of embers provided is sufficient   
					for 3 to 5 applications.   
					Double-check for faulty components   
					Reinstall and latch the glass and door on the unit.   
					• Any component that is found to be faulty MUST BE re-   
					placed with an approved component. Tampering with the   
					fireplace components is DANGEROUS and voids all war-   
					ranties.   
					CAUTION: THE GLASS MUST BE SECURELY LATCHED   
					BEFORE OPERATING THE UNIT.   
					A small amount of air will be in the gas supply lines. When   
					first lighting the fireplace, it will take a few minutes for the   
					lines to purge themselves of this air. Once the purging is   
					complete, the fireplace will light and will operate normally.   
					Subsequent lightings of the fireplace will not require this   
					purging of air from the gas supply lines, unless the gas   
					valve has been turned to the OFF position, in which   
					case the air would have to be purged.   
					LATCHES   
					(BOTH TOP   
					AND BOTTOM)   
					NOTE: The fireplace should be run for 3 to 4 hours on the   
					initial start-up. Turn it off and let it cool completely. Remove   
					and clean the glass. Replace the glass and run the fireplace   
					for an additional 8 hours. This will help to cure the products   
					used in the paint and logs.   
					GLASS   
					ASSEMBLY   
					Figure 44. Glass Assembly   
					During this break-in period it is recommended that some   
					windows in the house be opened for air circulation. This will   
					help avoid setting off smoke detectors, and help eliminate   
					any odors associated with the fireplace’s initial burning.   
					GLASS SPECIFICATIONS:   
					QV32B-A and QV36B-A CERAMIC   
					WARNING: PLEASE REFER TO THE USER’S   
					! 
					MANUAL FOR ALL CAUTIONS, SAFETY, AND   
					WARNING INFORMATION PERTAINING TO THE   
					LIGHTINGAND OPERATION OF THE FIREPLACE.   
					Figure 45. Placement of the Ember Material   
					38   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Step 12. Lighting the Appliance   
					unobstructed, and you’ve checked for faulty components.   
					Now you’re ready to light the appliance.   
					You’ve reviewed all safety warnings, you’ve checked the   
					appliance for gas leaks, you know the vent system is   
					LIGHTING INSTRUCTIONS   
					STANDING PILOT CONTROLS   
					FOR YOUR SAFETY   
					READ BEFORE LIGHTING   
					1. To access controls, open the lower grille.   
					WARNING: IF YOU DO NOT FOLLOW THESE   
					INSTRUCTIONS EXACTLY, A FIRE OR   
					EXPLOSION MAY RESULT CAUSING   
					PROPERTYDAMAGE, PERSONALINJURY, OR   
					LOSS OF LIFE.   
					2. Turn the gas control valve knob to the OFF position. To do this, you   
					must turn the knob clockwise   
					press in and continue turning clockwise   
					to the PILOT position, and then   
					to the OFF position.   
					NOTE: Knob cannot be turned from “PILOT” to “OFF” unless knob is   
					pushed in slightly. Do not force.   
					3. WAIT AT LEAST FIVE (5) MINUTES TO CLEAR OUT ANY GAS. If   
					you have unsuccessfully tried to light the fireplace, wait longer, espe-   
					cially if you are using LP gas. Then smell for gas, including near the   
					floor. If you then smell gas, STOP! Follow "B" in the safety informa-   
					tion on previous page. If you don't smell gas, go to the next step.   
					STANDING PILOT IGNITION   
					A. This appliance (standing pilot version) has a pilot   
					that must be lighted by hand. When lighting the   
					pilot, follow these instructions exactly.   
					4. The pilot should not require accessing for lighting   
					purposes. The pilot is located inside the combustion   
					chamber. If it is necessary to access the pilot, re-   
					move the trim door and glass door.   
					B. BEFORE LIGHTING smell all around the appli-   
					ance area for gas. Be sure to smell next to the   
					floor because some gas is heavier than air and   
					will settle to the floor.   
					THERMOCOUPLE PILOT THERMOPILE   
					5. To put the control in the PILOT position, turn the control knob counter-   
					clockwise   
					to the PILOT position.   
					6. To light the pilot press the control knob and then press the red or black   
					piezo button once every second. The piezo makes a clicking sound. It   
					may be necessary to repeat this step. If the pilot does not light after   
					10 seconds, go back to step 2. The control knob should be held down   
					for a MINUTE after pilot ignition.   
					WHAT TO DO IF YOU SMELL GAS   
					• Do not try to light any appliance.   
					• Do not touch any electric switch; do not use any   
					phone in your building.   
					• If the control knob does not pop out when released, STOP! Shut off   
					the gas supply to the fireplace control valve, and IMMEDIATELY call   
					your service technician or gas supplier.   
					• Immediately call your gas supplier from a neigh-   
					bor’s phone. Follow the gas supplier’s instruc-   
					tions.   
					• If the pilot will not stay lit after two tries, turn the control knob to the   
					“OFF” position and call your service technician or gas supplier.   
					7. After the pilot has been lit, the burner can be turned on by turning the   
					• If you cannot reach your gas supplier, call the fire   
					department.   
					knob counter-clockwise   
					to the “ON” position.   
					8. Set the ON/OFF switch to the “ON” position.   
					9. Close the lower grille.   
					C. Use only your hand to push in or turn the gas   
					control knob. Never use tools. If the knob will not   
					push in or turn by hand, don’t try to repair it, call   
					a qualified service technician. Force or attempt-   
					ed repair may result in a fire or explosion.   
					TO TURN OFF   
					GASAPPLIANCE   
					1. Open the lower grille.   
					D. Do not use this appliance if any part has been   
					under water. Immediately call a qualified service   
					technician to inspect the appliance and to replace   
					any part of the control system and any gas con-   
					trol which has been under water.   
					2. Set ON/OFF switch to “OFF”.   
					3. Turn the valve control knob clockwise   
					to the “Pilot” position,   
					then depress knob and continue turning to “OFF” position.   
					4. Close the lower grille.   
					Additionally, for the first few minutes after each lighting, vapor   
					may condense and fog the glass and flames may be blue.   
					After a few minutes this moisture will disappear and within   
					15-30 minutes the flames should become yellow.   
					When you light your fireplace, you may notice:   
					This gas appliance produces heat which does have an associ-   
					ated odor or smell. If you feel this odor is excessive it may   
					require the initial 3-4 hour continuous burn on high followed by   
					a second burn up to 12 hours to fully drive off any odor from   
					paint and lubricants used in the manufacturing process.   
					Noise caused by metal expanding and contracting as it heats   
					up and cools down, similar to the sound produced by a furnace   
					or heating duct. This noise does not affect the operation or   
					longevity of your fireplace.   
					During this break-in period it is recommended that some   
					windows in the house be opened for air circulation. This will   
					help avoid setting off smoke detectors, and help eliminate   
					any odors associated with the fireplace’s initial burning.   
					After the Installation   
					LEAVE THIS INSTALLATION MANUALWITH THE   
					APPLIANCE FOR FUTURE REFERENCE.   
					! 
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					39   
				Maintaining and Servicing Your Fireplace   
					4 
					Fireplace Maintenance   
					Checking Vent System   
					Frequency: Before initial use and at least annually   
					thereafter, more frequently if possible.   
					By: Qualified service technician/Home owner.   
					Task: Inspect the external vent cap on a regular basis to   
					ensure that no debris is interfering with the flow of air. Inspect   
					entire vent system for proper function.   
					Although the frequency of your fireplace servicing and main-   
					tenance will depend on use and the type of installation, you   
					should have a qualified service technician perform an appli-   
					ance check-up at the beginning of each heating season.   
					See the table below for specific guidelines regarding each   
					fireplace maintenance task.   
					IMPORTANT: TURN OFF THE GAS BEFORE SERVICING   
					YOUR FIREPLACE.   
					Cleaning Glass   
					Frequency: After the first 3 to 4 hours of use.As necessary   
					after initial cleaning.   
					By: Home owner.   
					Replacing old ember material   
					Frequency: Once annually, during the checkup.   
					By: Qualified service technician.   
					Task: Remove and clean glass after the first 3 to 4 hours of   
					use.After the initial cleaning, clean as necessary, particularly   
					after adding new ember (flame colorant) material. Film   
					deposits on the inside of the glass should be cleaned off   
					using a household glass cleaner. NOTE: DO NOT handle   
					or attempt to clean the glass when it is hot and DO NOT   
					use abrasive cleaners.   
					Task: Brush away loose ember material near the burner.   
					Replace old ember material with pieces of Mystic Ember   
					following the directions in Placing Ember Material. New   
					ember material should be placed on top of the burner. Save   
					the remaining ember material and repeat this procedure at   
					your next servicing. For more information, see Placing   
					Ember Material.   
					Cleaning Burner and Controls   
					Frequency: Once annually.   
					By: Qualified service technician.   
					Task: Brush or vacuum the control compartment, fireplace   
					logs and burner areas surrounding the logs.   
					Checking Flame Patterns, Flame Height   
					Frequency: Periodically.   
					By: Qualified service technician/Home owner.   
					Task: Make a visual check of your fireplace’s flame patterns.   
					Make sure the flames are steady - not lifting or floating.   
					See Figure 46. The thermopile/thermocouple tips should   
					be covered with flame. See Figure 33.   
					MAKE SURE THE FLAMES   
					ARE STEADY—NOT   
					LIFTING OR FLOATING.   
					Figure 46. Burner Flame Patterns   
					40   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				With proper installation, operation, and maintenance your gas fireplace will   
					provide years of trouble-free service. If you do experience a problem, this   
					troubleshooting guide will assist a qualified service person in the diagnosis   
					of a problem and the corrective action to be taken. This troubleshooting   
					guide can only be used by a qualified service technician.   
					Troubleshooting   
					5 
					Symptom   
					Possible Cause   
					Corrective Action   
					1. After repeated   
					triggering of the red   
					or black piezo button,   
					the spark ignitor will   
					not light the pilot.   
					a. Defective ignitor.   
					Check the spark at the electrode and pilot. If no spark and electrode wire is   
					properly connected, replace the ignitor.   
					b. Defective pilot or   
					misaligned electrode   
					(spark at electrode).   
					Using match, light the pilot. If the pilot lights, turn off the pilot and trigger the red or   
					black piezo button again. If the pilot lights, an improper gas/air mixture caused the   
					bad lighting and a longer purge period is recommended. If the pilot will not light,   
					ensure the the gap at the electrode and pilot is one-eighth (1/8) inch to have a   
					strong spark. If the gap is OK, replace the pilot.   
					c. No gas or low gas   
					pressure.   
					Check the remote shut-off valvess from the fireplace. Usually, there is a valve near   
					the gas main. There can be more than one (1) valve between the fireplace and the   
					main.   
					d. No LP in tank.   
					Check the LP (propane) tank. You may be out of fuel.   
					2. The pilot will not   
					stay lit after carefully   
					following the lighting   
					instructions.   
					a. Defective   
					thermocouple.   
					Check that the pilot flame impinges on the thermocouple. Clean and/or adjust the   
					pilot for maximum flame impingement.   
					Ensure that the thermocouple connection at the gas valve is fully inserted and tight   
					(hand tighten plus 1/4 turn).   
					Disconnect the thermocouple from the valve, place one millivolt meter lead wire on   
					the tip of the thermcouple and the other meter lead wire on the thermocouple   
					copper lead. Start the pilot and hold the valve knob in. If the millivolt reading is less   
					than 15mV, replace the thermocouple.   
					b. Defective valve.   
					If the thermocouple is producing more than 15 millivolts, replace faulty valve.   
					3. The pilot is   
					a. ON/OFF switch or   
					wires defective.   
					Check the ON/OFF switch and wires for proper connections. Place the jumper   
					wires across the terminals at the switch. If the burner comes on, replace the   
					defective switch. If the switch is OK, place the jumper wires across the switch wires   
					at the gas valve. If the burner comes on, the wires are faulty or connections are   
					bad.   
					burning, there is no   
					gas burner, the valve   
					knob is in the ON   
					position, and the   
					ON/OFF switch is in   
					the ON position.   
					b. Thermopile may   
					not be generating   
					sufficient millivoltage.   
					If the pilot flame is not close enough physically to the thermopile, adjust the pilot   
					flame.   
					Be sure the wire connections from the thermopile at the gas valve terminals are   
					tight and that the thermopile is fully inserted into the pilot bracket.   
					Check the thermopile with a millvolt meter. Take the reading at TH-TP&TP   
					terminals of the gas valve. The meter should read 325 millivolts minimum, while   
					holding the valve knob depressed in the pilot position, with the pilot lit, and the   
					ON/OFF switch in the OFF position. Replace the faulty thermopile if the reading is   
					below the specified minimum.   
					With the pilot in the ON position, disconnect the thermopile leads from the valve.   
					Take a reading at the thermopile leads. The reading should be 325 millivolts   
					minimum. Replace the thermopile if the reading is below the minimum.   
					c. Defective valve.   
					Turn the valve knob to the ON position. Place the ON/OFF switch in the ON   
					position. Check the millivolt meter a the thermopile terminals. The millivolt meter   
					should read greater than 125mV. If the reading is acceptable, and if the burner   
					does not come on, replace the gas valve.   
					d. Plugged burner   
					orifice.   
					Check the burner orifice for stoppage. Remove stoppage.   
					e. Wall switch or   
					wires are defective.   
					Follow the corrective action in Symptom and Possible Cause 1.a above. Check   
					the switch and wiring. Replace where defective.   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					41   
				Troubleshooting (continued)   
					Symptom   
					Possible Cause   
					Corrective Action   
					3. (Continued)   
					f. High limit switch is defective or Allow the unit to cool. If the burner remains lit after the fireplace warms   
					has reached its maximum   
					temperature.   
					up, the switch is good.   
					4. Frequent pilot   
					outage problem.   
					a. Pilot flame may be too high or   
					too low, or blowing (high),   
					Clean and adjust the pilot flame for maximum flame impingement on   
					thermocouple. Follow lighting instructions carefully.   
					causing pilot safety to drop out.   
					5. The pilot and main a. No LP in tank.   
					Check the LP (propane) tank. Refill the fuel tank.   
					burner extinguish   
					while in operation.   
					b. Inner vent pipe leaking exhaust Check for gas leaks.   
					gases back into the system.   
					c. Horizontal vent improperly   
					pitched.   
					The horizontal vent cap should slope down only enough to prevent any   
					water from entering the unit. The maximum downwards lope is 1/4 inch.   
					d. Glass too loose and air tight   
					packet leaks in corners after   
					usage.   
					Tighten the corner.   
					e. Bad thermopile or   
					thermocouple.   
					Replace if necessary.   
					f. Improper vent cap installation.   
					a. Flame impingement.   
					Check for proper installation and freedom from debris or blockage.   
					Adjust the log set so that the flame does not excessively impinge on it.   
					Adjust the air shutter at the base of the burner.   
					6. Glass soots.   
					b. Improper venturi setting.   
					c. Debris around venturi.   
					Inspect the opening at the base of the burner. NO MATERIAL SHOULD   
					BE PLACED IN THIS OPENING.   
					7. Flame burns blue   
					and lifts off burner.   
					a. Insufficient oxygen being   
					supplied.   
					Ensure that the vent cap is installed properly and free of debris. Ensure   
					that the vent system joints are tight and have no leaks.   
					Ensure that no debris has been placed at the base of, or in the area of   
					the air holes in the center of the base pan beneath the burner.   
					Ensure that the glass is tightened properly on the unit, particularly on top   
					corners.   
					42   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Lifetime Warranty   
					LIMITED LIFETIME WARRANTY   
					The Hearth & Home Technologies limited Lifetime Warranty guarantees that the following components will work as   
					designed for the lifetime of the stove or Hearth & Home Technologies will repair or replace them. These items   
					include but are not limited to steel and cast iron components, all gas burners, gas logs, combustion chambers,   
					heat exchanger systems, stainless steel firebox components, plating, doors, glass damaged by thermal breakage,   
					steel baffle supports, steel and ceramic baffles and manifold tubes. Labor is for the first five years.   
					THREEYEAR WARRANTY   
					Our EZ Clean firepots are covered under Hearth & Home Technologies three-year warranty program. Labor is for   
					3 years.   
					TWO YEAR WARRANTY   
					All electrical components such as but not limited to blowers, wiring, vacuum switches, speed controls, control   
					boxes, thermodisc switches, igniters, pilot assembly, gas valves, thermostats and remotes are covered under   
					Hearth & Home Technologies two-year warranty program. Effective April, 2005 igniters are also covered under the   
					two year warranty. Labor is for two years.   
					ONEYEAR WARRANTY   
					Porcelain and powdercoat finishes are warranted against manufacturer defects for one year. Labor to repair or   
					replace these parts is covered for one year, reimbursed per our warranty service fee schedule.   
					CONDITIONS   
					This warranty is nontransferable and is made to the original retail purchaser only provided that the purchase was   
					made through an authorized dealer of Hearth & Home Technologies. It must be installed and operated at all times   
					in accordance with the Installation and Operating Instructions furnished with this product, as well as any applicable   
					local and national codes. Any alteration, willful abuse, accident, or misuse of the product shall nullify this warranty.   
					Labor to repair or replace items covered under the limited Lifetime Warranty will be covered for the first five years per   
					our warranty service fee reimbursement schedule. Parts covered under the limited Lifetime Warranty will be covered   
					for the lifetime of the appliance up to a maximum of ten (10) years after Hearth & Home Technologies discontinues   
					the model and two   
					(2) years for optional accessories. Adjustments, regular maintenance, cleaning and temporary repairs do not   
					qualify for a service call fee and will not be covered. The replacement of consumer replaceable items and installation   
					of upgraded component parts do not quality for a service call fee, and will not be covered.   
					This limited Lifetime Warranty does not extend to or include surface finish on the appliance, door gasketing, glass   
					gasketing, glass, firebrick, pellet logs, kaowool or other ceramic insulating materials. It does not cover installation   
					or operational-related problems such as overfiring, use of corrosive driftwood, downdrafts or spillage caused by   
					environmental conditions, nearby trees, buildings, hilltops, mountains, inadequate venting or ventilation, excessive   
					offsets, or negative air pressures caused by mechanical systems such as furnaces, fans, clothes dryers, etc.   
					Any installation, construction, transportation, or other related costs or expenses arising from defective part(s),   
					repair, replacement, etc., will not be covered by this warranty, nor will Hearth & Home Technologies assume   
					responsibility for them. Further, Hearth & Home Technologies will not be responsible for any incidental, indirect, or   
					consequential damages, except as results in damage to the interior or exterior of the building in which this appliance   
					is installed. This limited Lifetime Warranty does not apply to the venting components, hearth components or other   
					accessories used in conjunction with the installation of this product not manufactured by Hearth & Home   
					Technologies   
					This warranty is void if the stove has been overfired or operated in atmospheres contaminated by chlorine, fluorine,   
					or other damaging chemicals, the stove is subjected to prolonged periods of dampness or condensation, or there   
					is any damage to the stove or other components due to water or weather damage which is the result of, but not   
					limited to, improper chimney or venting installation. Hearth & Home Technologies may, at its discretion, fully   
					discharge all obligations with respect to this warranty by either repairing or replacing the unit, or refunding the   
					wholesale price of the defective part(s).   
					This limited Lifetime Warranty is effective on all appliances sold after May 1, 2002 and supersedes any and all   
					warranties currently in existence.   
					250-8620J   
					12/05   
					Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					43   
				 |