Operator Manual, Supercharger 60
R3.0
TABLE OF CONTENTS
1. INTRODUCTION AND SYSTEM DESCRIPTION ..................................................................5
2. CONDENSED OPERATING INSTRUCTIONS.......................................................................8
2.1 Constant Current Charge (normal mode)...............................................................................................8
2.2 Constant Voltage........................................................................................................................................9
2.3 Peak Voltage Charge ...............................................................................................................................10
2.4 Discharge..................................................................................................................................................11
3. SPECIFICATIONS................................................................................................................12
3.1 CHARGE..................................................................................................................................................12
3.2 DISCHARGE...........................................................................................................................................14
3.3 TIMER......................................................................................................................................................15
3.4 LINE INPUT VOLTAGE:......................................................................................................................16
3.5 DIGITAL PANEL METERS..................................................................................................................17
3.6 FUSES and BREAKERS (Other than charge and discharge current limiters) .................................17
4. CONTROLS AND DISPLAYS ..............................................................................................18
4.1 M1 - Ammeter..........................................................................................................................................18
4.2 M1 - Voltmeter.........................................................................................................................................18
4.3 R1 - Main Charge Current Selector.......................................................................................................18
4.4 R2 - Topping/Discharge Current Selector.............................................................................................18
4.5 SW1 - Main Time selector switch...........................................................................................................18
4.6 SW2 - Total Time selector switch...........................................................................................................18
4.7 SW3 – Keypad..........................................................................................................................................18
4.8 SW4 - CELL SELECTOR:.....................................................................................................................19
4.9 SW5 - DIGITAL VOLTMETER INPUT SELECTOR: ......................................................................19
4.10 SW6 - VOLTAGE MODE SELECTOR:...............................................................................................19
4.11 SW7 - TIMER SPEED SELECTOR: ....................................................................................................19
4.12 DS1A - RESET:........................................................................................................................................21
4.13 DS1B - CYC END:...................................................................................................................................21
4.14 DS2A - DUAL: .........................................................................................................................................21
4.15 DS2B - MAIN:..........................................................................................................................................21
4.16 DS3A - SINGLE:......................................................................................................................................21
4.17 DS3B - TOP:.............................................................................................................................................21
4.18 DS4A - AUTO:.........................................................................................................................................21
4.19 DS4B - DISCH: ........................................................................................................................................21
Page 1 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
8.8 DISCHARGE VOLTAGE CUT-OFF....................................................................................................38
8.9 FULL DISCHARGE. ..............................................................................................................................39
8.10 CURRENT TRACKING.........................................................................................................................39
8.11 VOLTAGE CONTROL. .........................................................................................................................39
8.12 FLOAT VOLTAGE: ...............................................................................................................................40
8.13 PEAK VOLTAGE:..................................................................................................................................40
8.14 METERS ..................................................................................................................................................41
9. CALIBRATION .....................................................................................................................42
9.1 CIRCUIT BOARD ADJUSTMENTS AND CALIBRATION.............................................................42
9.2 DIGITAL METERS (see [Figure 6])......................................................................................................42
10. TROUBLESHOOTING AND REPAIRS................................................................................53
10.1 TROUBLESHOOTING..........................................................................................................................53
10.2 FINDING A SHORTED DISCHARGE TRANSISTOR......................................................................55
11. REPLACEABLE MODULES AND PARTS ..........................................................................59
11.1 CIRCUIT BOARDS ................................................................................................................................59
11.2 PARTS......................................................................................................................................................59
11.3 OTHER.....................................................................................................................................................59
12. BATTERY TESTING NOTES ...............................................................................................60
13. DISCLAIMER........................................................................................................................61
14. REVISION INDEX.................................................................................................................62
Page 3 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
TABLE OF FIGURES
Figure 1 - Block Diagram...................................................................................................................................... 7
Figure 2 - Front Panel.......................................................................................................................................... 20
Figure 3 - Line Voltage Wiring, 115V ................................................................................................................ 33
Figure 4 - Line Voltage Wiring, 208/230V ......................................................................................................... 34
Figure 5 - Line Voltage Wiring, 230/245V ......................................................................................................... 34
Figure 6 - Meters Board Adjustments.................................................................................................................. 44
Figure 7 - Control Switch Board Adjustments .................................................................................................... 45
Figure 8 - Current Control Board Adjustments ................................................................................................... 47
Figure 9 - Monitor Board Adjustments................................................................................................................ 48
Figure 10 - Voltage Control Board Adjustments................................................................................................. 50
Figure 11 - Circuit Board Sequence .................................................................................................................... 52
Figure 12 - Measuring for a shorted transistor..................................................................................................... 56
Figure 13 - Location of Current Limiters ............................................................................................................ 57
Figure 14 - Power Block Diagram....................................................................................................................... 58
TABLE OF TABLES
Table 1 - Constant Voltage and Peak Voltage Chart ........................................................................................... 31
Table 2 - Index of Revisions................................................................................................................................ 62
Page 4 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
1. INTRODUCTION AND SYSTEM DESCRIPTION
Congratulations! You now own the finest battery Charger-Analyzer available today. The
Supercharger is a precision instrument designed to charge and analyze NICKEL-CADMIUM,
LEAD-ACID and other rechargeable batteries exactly as recommended by the battery
manufacturers.
The simple to set controls plus the condensed operating procedure found on the front panel
makes the Supercharger a very easy to operate CHARGER/ANALYZER, which combined with
easy to read CURRENT, VOLTAGE, TIME and STATUS indicators, makes it also a very
simple unit to monitor.
The Supercharger is also designed for speed, for it can charge two batteries, (actually, any
number of batteries where the total number of cells is 50 or less), at maximum currents, and it
can also discharge two batteries at reduced currents, or one battery (25 cells or less) at
maximum current.
The Supercharger also provides a Voltage Control enhancement that allows the Charger-
Analyzer, originally designed for Constant Current operation on Nickel-Cadmium batteries to
also be able to handle Lead-Acid and other type of rechargeable batteries, where the end
voltage is a more reliable indicator of the state of charge (as opposed to Nickel-Cadmium
batteries).
Dependability is another great plus of the Supercharger. 100% SOLID STATE circuitry
requires no scheduled maintenance. No relay contacts to inspect and clean. No high current
carrying contacts to arc and burn. A simple performance verification procedure is all it takes to
determine if the instrument requires re-calibration or repair.
This instrument is also protected against certain internal performance deviations and
programming errors, plus it is also designed to sense certain battery abnormalities to protect the
instrument and battery from possible damage. In the event that any malfunction takes place,
VISUAL and AUDIBLE indicators will turn on, alerting the operator and preventing any
further operation of the unit.
The Supercharger Battery Charger-Analyzer System is comprised of the Charger-Analyzer, the
Temp-plate, the Battery Cable and several accessories.
The Charger-Analyzer is basically a precision programmable constant current source (for
charge) and a programmable constant current sink (for discharge) combined with voltage and
temperature sensing circuits for total battery monitoring.
The specially designed circuitry provides a performance not achieved by any of the older
conventional battery charging methods. The Supercharger will deliver current into a short
circuit or a battery or combination of batteries totaling 50 cells, within ±1% of the programmed
value, independent of line voltage variations (within ±10% of the nominal line voltage).
The control circuitry of the Charger-Analyzer consists of a CONTROL SWITCH, a CLOCK, a
TIMER, a CURRENT CONTROL, a SYSTEM MONITOR, a POWER REGULATOR and a
VOLTAGE CONTROL CIRCUIT. See Figure 1
The CONTROL SWITCH receives the function commands from the function selector switch
on the front panel and outputs control signals to the rest of the circuit boards as well as to the
charge SCR'S and discharge transistors.
Page 5 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
The TIMER provides all the required timing functions related to the charge and discharge
durations. Digital time and speed selectors provide the external inputs, while the four digit
readout of the CLOCK provides the elapsed time display.
The CURRENT CONTROL interprets the programmed current values and controls the angle of
firing of two SCR's to maintain a constant current in accordance to the feedback received from
a precision shunt.
Display of current is provided by an independent Digital Ammeter that uses the same shunt
used by the CURRENT CONTROL circuit.
Inputs from the TIMER, the SYSTEM MONITOR and the CONTROL SWITCH, determine
the operating mode of the CURRENT CONTROL circuit.
The SYSTEM MONITOR provides several safeguarding functions. It compares the measured
current against the programmed value and if they differ by more than one ampere, operation is
halted and a current malfunction is indicated.
It measures the battery voltage and compares it with the programmed number of cells. From
there, it determines during charge if the total voltage exceeds the equivalent of 1.75 V per cell,
indicating an Overvoltage condition, or during discharge if the total voltage is below the
equivalent of 1 volt per cell, indicating the end of the discharge cycle.
It checks for polarity reversal at voltages as low as .25V, as well as an absolute Overvoltage at
85 volts, both generating a voltage malfunction indication that prevents any further operation of
the unit.
It measures the temperature of the discharge heat dissipators and signals an overheat
malfunction if the internal temperature exceeds 90oC, as it could be caused by a fan failure or
an installation with restricted air flow. It also monitors the temperature of the batteries being
charged (via the TEMP-PLATE) and terminates the charge, indicating battery Overtemp, in the
event of battery overheating that may lead to thermal runaway.
The POWER REGULATOR provides all regulated voltages and power amplification as
required by the various circuits.
The VOLTAGE CONTROL CIRCUIT provides the functions that regulate the charging current
in the Constant Voltage (float) mode and in the Peak Voltage mode, transfers from Main to
Topping charge on a voltage peak or ends charging on a voltage peak (new feature).
The DIGITAL VOLTMETER provides internal battery voltage readings with resolutions of
0.1V and 0.01V, while a selectable external position allows single cell measurements to a
resolution of 0.001V.
Additional protection is provided by a high speed current limiter for the discharge transistor
bank, a slow speed current limiter for the charge circuit and a magnetic circuit breaker capable
of tripping under fast high current overload conditions.
Page 6 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 1 - Block Diagram
Page 7 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
2. CONDENSED OPERATING INSTRUCTIONS
CAUTION: Disconnect power and batteries before performing any internal maintenance.
Failure to observe this caution may result in serious damage to the unit and injury to the
operator.
NOTE 1: Depress the RESET button before turning the power on, or before connecting or
disconnecting the battery.
NOTE 2: The current selector potentiometers display three digits indicating XX.X AMPS.
e.g.: in order to select 4A dial 040 (04.0A), and for 20A dial 200 (20.0A).
2.1 Constant Current Charge (normal mode)
2.1.1. Number of Cells
2.1.1.1. Enter the number of cells
2.1.1.2. NOTE: when charging more than one battery enter the total number of
cells.
2.1.2. Main Charge Time
2.1.2.1. Enter the MAIN CHARGE TIME and TOTAL TIME if in the TWO
RATE mode, or enter the TOTAL CHARGE TIME only if in the
SINGLE RATE mode.
2.1.2.2. Verify that the Timer Speed is consistent with the required elapsed
time (hours or minutes).
2.1.2.3. Enter the MAIN and TOPPING CHARGE CURRENTS, if in the
TWO RATE mode, or enter the TOPPING CURRENT only if in the
SINGLE RATE mode.
2.1.2.4. Place batteries on the TEMP-PLATE. When working with only one
battery, connect the free plug into the shorted receptacle provided in
the TEMP-PLATE. Verify also that the small cable is connected to the
TEMP-PLATE (the red "BATTERY OVERTEMP" INDICATOR will
be on if not connected).
2.1.2.5. Depress the CONTROL BUTTON corresponding to the desired mode
(white for TWO RATE and yellow for SINGLE RATE).
2.1.2.6. The charge will terminate automatically (CYCLE END) when the
TOTAL TIME selected is reached.
2.1.2.7. The charge will terminate as a FAULT if the MONITOR CIRCUIT
detects that:
• Battery temperature exceeds 45oC/113oF (BATTERY
OVERTEMP FAULT).
• Battery voltage exceeds the equivalent of 1.75V/cell (VOLTAGE
FAULT).
• The actual charge current deviates from the programmed value by
more than 1 AMP (CURRENT FAULT).
Page 8 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
2.2 Constant Voltage
2.2.1. Battery Voltage
2.2.1.1. Enter the nominal battery voltage using the cell selector (see chart on
page 19).
2.2.1.2. Program the charge (maximum) current in the Topping Current
selector.
2.2.1.3. Program sufficient time in the Total Time selector to allow the battery
to reach the required charge under constant voltage charge (consult
battery manufacturers specifications). Verify that the Timer Speed is
consistent with the required elapsed time.
2.2.1.4. Start the Charger-Analyzer in the Single Rate mode. The charger will
begin to reduce the charging current when the battery voltage is within
0.5V of the float level.
2.2.1.5. The charge will terminate automatically (CYCLE END) when the
TOTAL TIME selected is reached.
2.2.1.6. The charge will terminate as a FAULT if the MONITOR CIRCUIT
detects that:
• Battery temperature exceeds 45oC/113oF (BATTERY
OVERTEMP FAULT).
• The actual charge current deviates from the programmed value by
more than one AMP (CURRENT FAULT). Note: this will occur
only before the Charger-Analyzer switches from constant current
to constant voltage.
Page 9 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
2.3 Peak Voltage Charge
2.3.1. Nominal Battery Voltage
2.3.1.1. Enter the nominal battery voltage using the cell selector (see chart on
page xxx).
2.3.1.2. Select transfer from Main to Topping on Peak or stop on Peak.
2.3.1.3. Program the Main and Topping Charge currents as required.
2.3.1.4. Program the Main and Total Time selectors to allow the battery to
reach the required charge level (consult battery manufacturers
specifications). Verify that the Timer Speed is consistent with the
required elapsed time.
2.3.1.5. Start the Charger-Analyzer in the Dual Rate mode. The charger will
transfer from Main to Topping charge when the battery reaches the
peak voltage or Start in the Dual or Single Rate mode and the Charger-
Analyzer will stop on peak (at any part of the cycle).
2.3.1.6. The charge will terminate automatically (CYCLE END) when the
TOTAL TIME selected is reached.
2.3.1.7. The charge will terminate as a FAULT if the MONITOR CIRCUIT
detects that:
• Battery temperature exceeds 45oC/113oF (BATTERY
OVERTEMP FAULT).
• The actual charge current deviates from the programmed value by
more than one AMP (CURRENT FAULT).
Page 10 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
2.4 Discharge
NOTE 1: Do not place batteries on the Temp-Plate during discharge. Due to the normal
heating of the battery a false Overtemp may be generated later during the charge
process.
NOTE 2: Do not attempt to discharge with the voltage mode selector in the Float or Peak
voltage modes. Voltage and current faults will occur depending on the battery voltage
and the cell selector setting.
2.4.1. Number of Cells
2.4.1.1. Enter the number of cells.
2.4.1.2. Ignore this step if FULL DISCHARGE is to be selected.
2.4.2. Total Time
2.4.2.1. Enter the TOTAL TIME.
2.4.2.2. Verify that the Timer Speed is consistent with the required elapsed
time.
2.4.2.3. Enter the DISCHARGE CURRENT.
2.4.2.4. Depress the Blue button for DISCHARGE with automatic cut-off
(ANALYSIS), or the RED button for FULL DISCHARGE (DEEP
CYCLE).
2.4.2.5. DISCHARGE will terminate automatically (CYCLE END) when the
(TOTAL) time selected is reached or (CAPACITY FAILURE) if the
BATTERY voltage reaches the equivalent of ONE VOLT per CELL
prior to the selected time.
2.4.2.6. NOTE: Battery voltage is ignored during Full Discharge.
2.4.2.7. Discharge will terminate as a FAULT if the MONITOR CIRCUIT
detects:
• An overheating of the discharge transistors (OVERHEAT
FAULT).
• That the discharge current differs from the programmed value by
more than one AMP (CURRENT FAULT).
• That the programmed current exceeds 30A for a battery voltage in
excess of 32V.
Page 11 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
3. SPECIFICATIONS
3.1 CHARGE
3.1.1. CONTROL: SCR, air cooled.
3.1.2. MAXIMUM CURRENT: 50 AMPS.
3.1.3. MINIMUM INCREMENT: 0.1 AMP.
3.1.4. ACCURACY and STABILITY of settings: ±1% of reading, ±0.1 AMP.
3.1.4.1. FLOAT:
• The reference voltage is set at the equivalent of 2.33V/cell (Lead-
Acid).
• The Cell Selector provides the basic reference as nominal battery
voltage, e.g.: a 24V battery is entered as 24 on the Cell Selector.
• Current reduction from within 0.5V of the float voltage, with an
accuracy of ±0.5%, ±0.1A
3.1.4.2. PEAK:
• The reference voltage is set at the equivalent of 2.45V/cell (Lead-
Acid).
• The Cell Selector provides the basic reference as nominal battery
voltage, e.g.: a 24V battery is entered as 24 on the Cell Selector.
• Voltage transfer or stop within " 1% of the Peak Voltage.
• Note: Due to cable/connector losses the peak voltage registered by
the Charger-Analyzer will be higher than the actual battery voltage
(up to 0.2V depending on current).
Page 12 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
3.1.5. MODES:
3.1.5.1. Main and topping for Constant Current
3.1.5.2. Constant Voltage
3.1.5.3. Peak Voltage.
3.1.6. TIMER:
3.1.6.1. 1 to 9 hours for MAIN charge time and 1 to 60 hours for TOTAL time.
3.1.6.2. Time can also be programmed in minutes by selecting the FAST mode
in the TIMER SPEED selector switch (Front Panel).
3.1.6.3. NOTE 1: Topping charge time equals the total charge time minus the
main charge time (TOTAL = MAIN + TOP).
3.1.6.4. NOTE 2: Newer instruments may have a new version of the Timer
(Identified by an external Timer Speed Switch) that has a maximum of
79 (hours or minutes) in Total Time.
3.1.7. OVERTEMP PROTECTION:
3.1.7.1. Four thermistors on the TEMP-PLATE measure the battery
temperature.
3.1.7.2. The charge is terminated when the surface temperature of the TEMP-
PLATE reaches 39oC (102oF).
3.1.8. OVER/UNDER CURRENT PROTECTION:
3.1.8.1. A Monitor circuit continuously compares the actual charge current
with the programmed value.
3.1.8.2. Operation is terminated if they differ by more than 1 AMP.
3.1.9. OVERVOLTAGE PROTECTION:
3.1.9.1. Programmable, in accordance with the number of cells selected, at the
equivalent of 1.75 volts/cell (TOLERANCE: ±1%, ±0.1V).
3.1.9.2. Absolute maximum internal limit set at 85 VOLTS.
3.1.9.3. NOTE: Does not apply in the Float and Peak voltage modes. (Voltage
is controlled in those modes).
3.1.10. REVERSE POLARITY PROTECTION:
3.1.10.1. Operation of the unit is inhibited for reverse voltages greater than 0.5
VOLTS.
3.1.11. FUSING:
3.1.11.1. Aircraft type current limiter, ANL-60 (slow).
3.1.12. AC LINE CURRENT:
Page 13 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
3.1.12.1. 3 AMPS idling plus ½ the value of the charging current; e.g. when
charging 40 AMPS the line current is 23 AMPS (Note: nominal values,
line voltage and frequency dependent).
3.2 DISCHARGE
3.2.1. CONTROL: Transistors, air cooled.
3.2.2. MAXIMUM CURRENT:
3.2.2.1. 60 AMPS. Total power dissipation must not exceed 1.2KW (1200
watts, the product of battery voltage and battery current).
3.2.2.2. NOTE: Discharge current is automatically limited to 30 AMPS for
battery voltages in excess of 32 VOLTS. A current fault will be
generated if attempting to discharge at more than 30 AMPS.
3.2.3. MINIMUM INCREMENT:
3.2.3.1. 0.1 AMP.
3.2.4. ACCURACY and STABILITY of settings:
3.2.4.1. ±1% of reading, ±0.1AMP.
3.2.5. MODES:
3.2.5.1. Analysis (automatic cut-off)
3.2.5.2. Deep cycle (full discharge).
Page 14 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
3.2.6. TERMINAL VOLTAGE:
3.2.6.1. Programmable, in accordance with the number of cells selected, at the
equivalent of 1 VOLT/cell.
3.2.6.2. TOLERANCE: ±1% ±0.1 VOLT.
3.2.6.3. NOTE 1: Due to cable/connector losses the voltage registered by the
Charger-Analyzer will be lower than the actual battery voltage (up to
0.2V depending on current).
3.2.6.4. NOTE 2: Terminal voltage is ignored in the full discharge mode.
3.2.7. OVERHEAT PROTECTION:
3.2.7.1. Two thermistors measure the temperature of the bank of discharge
transistors.
3.2.7.2. Operation is terminated if the transistors surface temperature exceeds
90oC.
3.2.8. OVER/UNDER CURRENT PROTECTION:
3.2.8.1. A Monitor circuit continuously compares the actual discharge current
with the programmed value
3.2.8.2. Operation is terminated if they differ by more than 1 AMP.
3.2.8.3. NOTE: Undercurrent monitoring is disabled in the full discharge
mode for battery voltages below 2.5V.
3.2.9. REVERSE POLARITY PROTECTION:
3.2.9.1. Operation of the unit is inhibited for reverse voltages greater than 0.5V
3.2.10. FUSING:
3.2.10.1. Aircraft type current limiter, ANN-80(fast).
3.2.10.2. NOTE: The type of limiter and current rating are critical for proper
protection of the discharge circuits. Failure to replace the discharge
current limiter with the proper type/value may result in catastrophic
damage of the load banks.
3.3 TIMER
3.3.1. TIME BASE:
3.3.1.1. Microprocessor Controlled
3.3.2. MODES:
3.3.2.1. NORMAL: Timer advances at the rate of one count per minute
(HH:MM).
3.3.2.2. FAST: Timer advances at the rate of one count per second (MM:SS).
3.3.2.3. TEST: Timer advances at the rate of 60 counts per second (SS:SS/60).
Page 15 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
3.3.2.4. NOTE: The colon flashes at the rate of one cycle per second regardless
of the selected mode.
3.3.3. ACCURACY AND STABILITY:
3.3.3.1. ±0.01%
3.3.4. POWER FAILURE PROTECTION:
3.3.4.1. An internal rechargeable battery maintains (for several hours) the clock
and other vital circuits for a dependable resumption of operation after a
power failure.
3.3.4.2. The colon will be lit in case of a power failure.
3.3.4.3. NOTE: Do not operate the Charger-Analyzer without this battery or
with a battery in bad condition. Replace only with the same type, 7 or 8
cells (8.4V or 9.6V), rechargeable).
3.3.5. TIME LIMITS:
3.3.5.1. 0 to 9 in Main
3.3.5.2. 0 to 79 in Total
3.3.5.3. NOTE: The time limit in Total is dependent on the type of Timer.
Newer instruments, characterized by a Timer Speed Switch mounted
on the Front Panel have a limit of 79 (hours or minutes) while older
units have a limit of 60.
3.4 LINE INPUT VOLTAGE:
3.4.1. 115V(*), 208V, 230V, 245V
Note: For proper operation of this instrument, power line voltages must be
within ±10% of the nominal.
3.4.2. The instrument is normally wired for 230V operation.
3.4.3. A terminal block at the transformer inputs allows field re-wiring for 245V, 208V
or 115V operation. See figs 3, 4 and 5.
3.4.4. For operation at line voltages in excess of 220V at 50Hz, it is required that the
245V tap be used.
3.4.5. NOTE (*): Operation at 115V is not recommended at battery charging currents
above 15A due to the increased line current.
Page 16 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
3.5 DIGITAL PANEL METERS
3.5.1. VOLTMETER:
3.5.1.1. Accuracy (system): ±0.25% of reading, ±0.1V in the 200V scale,
±0.01V in the 20V scale, ±0.005V in the 2V scale.
3.5.1.2. Input impedance: 1 M-OHM.
3.5.1.3. Scale 2V, 20V and 200V (1.999V, 19.9V and 199.9V) for external
measurements and 20V and 200V for internal (battery) measurements.
3.5.2. AMMETER:
3.5.2.1. Accuracy (system): ±0.5% of reading, ±0.1A
3.5.2.2. Scale: 200A (199.9A)
3.5.3. SHUNT:
3.5.3.1. Accuracy: ±0.25%
3.5.3.2. Output: 1mV/A (100mV / 100A)
3.6 FUSES and BREAKERS (Other than charge and discharge current limiters)
3.6.1. Mains: Dual Magnetic Circuit Breaker
3.6.2. Electronics and digital panel meters: 1/4A SLO BLO.
Page 17 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
4. CONTROLS AND DISPLAYS
4.1 M1 - Ammeter
4.1.1. 0 to 199.9ADC DIGITAL PANEL METER.
4.1.2. Positive sign indicates charge current.
4.1.3. Minus sign indicates discharge current.
4.2 M1 - Voltmeter
4.2.1. 0 to 1.999VDC, 0 to 19.99VDC and 0 to 199.9VDC DIGITAL PANEL METER.
4.2.2. Indicates battery voltage in the internal (20/200V) position and voltage present at
the RED (+) and BLK (-) jacks in the 2/20/200V external positions. Positive sign
indicates proper battery connection. Minus sign indicates reversed polarity
connection.
4.3 R1 - Main Charge Current Selector
4.3.1. Ten turn potentiometer with digital readout to program: current
4.3.1.1. MAIN charge current, 0 to 50.0 AMPS.
4.4 R2 - Topping/Discharge Current Selector
4.4.1. Ten turn potentiometer with digital readout to program:
4.4.1.1. TOPPING charge current, 0 to 50.0 AMPS
4.4.1.2. DISCHARGE current, 0 to 60.0 AMPS
4.5 SW1 - Main Time selector switch
4.5.1. 0 to 9 hours (or minutes), to determine the duration of the main charge.
4.6 SW2 - Total Time selector switch
4.6.1. 0 to 60 hours (or minutes), to determine the total charge or discharge duration.
4.7 SW3 – Keypad
Five station membrane push button control switch to select and control the mode of
operation, as follows:
4.7.1. GREEN: Stop/reset, cycle end.
4.7.2. WHITE: Two rate charge mode (main and topping).
4.7.3. YELLOW: Single rate charge mode.
4.7.4. BLUE: Auto cut-off discharge (analysis).
4.7.5. RED: Full discharge (deep cycle).
Page 18 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
4.8 SW4 - CELL SELECTOR:
4.8.1. Two digit selector to program the battery terminal voltage as a function of the
number of cells.
4.8.2. Rate: 1.75 volts per cell for charge and 1.0 volts per cell for discharge.
4.8.3. Used also in the Float and Peak Voltage modes to enter nominal battery voltage.
4.9 SW5 - DIGITAL VOLTMETER INPUT SELECTOR:
4.9.1. External, 2/20/200V scale.
4.9.2. Internal, 20/200V scale.
4.10 SW6 - VOLTAGE MODE SELECTOR:
4.10.1. Four position switch to select Normal, Float and Peak Voltage modes.
4.11 SW7 - TIMER SPEED SELECTOR:
4.11.1. Three position switch to select
4.11.1.1. Normal (HH:MM)
4.11.1.2. FAST (MM:SS)
4.11.1.3. TEST (SS:S/60).
Page 19 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 2 - Front Panel
Page 20 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
4.12 DS1A - RESET:
4.12.1. Indicates that the unit is in standby.
4.13 DS1B - CYC END:
4.13.1. Flashing (with pulsating beeper) cycle end. Indicates that the unit has completed
its cycle.
4.14 DS2A - DUAL:
4.14.1. Indicates that the DUAL rate mode (MAIN and TOPPING) is selected.
4.15 DS2B - MAIN:
4.15.1. Indicates that the unit is in MAIN charge.
4.16 DS3A - SINGLE:
4.16.1. Indicates that the SINGLE rate mode (Topping) is selected.
4.17 DS3B - TOP:
4.17.1. Indicates that the unit is in TOPPING charge.
4.18 DS4A - AUTO:
4.18.1. Indicates that the AUTO (analysis) mode is selected.
4.19 DS4B - DISCH:
4.19.1. Indicates that the unit is in AUTO discharge.
4.20 DS5A - FULL:
4.20.1. Indicates that the FULL (deep cycle) mode is selected.
4.21 DS5B - DISCH:
4.21.1. Indicates that the unit is in FULL discharge.
4.22 DS6A - CAP FAIL:
4.22.1. Indicates that the battery has failed to meet capacity.
4.23 DS6B - OPEN LIM:
4.23.1. Indicates that either the charge or discharge limiters are open.
4.24 DS7A - OVR TEMP:
Indicates Overtemp fault.
4.24.1. Continuous (no beeper): Indicates that the TEMP-PLATE is not connected (or
open).
4.24.2. Flashing: Indicates battery temperature in excess of 45oC).
Page 21 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
4.25 DS7B - OVR HEAT:
4.25.1. Indicates that the discharge bank is overheated.
4.26 DS8A - VOLT FLT:
Indicates voltage fault.
4.26.1. Continuous: battery connected with polarity reversed.
4.26.2. Flashing: (during charge) battery voltage in excess of 1.75 volts per cell or in
excess of 85 volts, or open circuit.
4.27 DS8B -CURR FLT:
4.27.1. Indicates that the actual current differs from the programmed value by more than
1A.
4.28 DS9 - CC
4.28.1. Indicates that the charger is in the basic Constant Current mode.
4.29 DS10 - CV
4.29.1. Indicates that the charger is in the Constant Current/Float mode.
4.30 DS11 - PEAK
4.30.1. Indicates that the charger is in the Constant Current/Peak mode.
4.31 AUDIBLE ALARM:
4.31.1. Continuous: turns on with any of the faults.
4.31.2. Pulsating: turns on with cycle end.
Page 22 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
5. MODES OF OPERATION
5.1 CONSTANT CURRENT CHARGE
5.1.1. DUAL RATE:
5.1.1.1. The battery is charged at the main rate for a preset time, at the end of
which, the current is switched automatically to the topping rate for the
remainder of the total time selected.
5.1.1.2. Charging is automatically terminated at the end of the total time
selected (cycle end), or as a fault if:
• Battery overtemperature is detected (Overtemp fault).
• Battery voltage is in excess of 1.75V/cell as determined by the
number of cells programmed, or if battery voltage is in excess of
85V (voltage fault).
• Actual charging current differs from the programmed value by
more than 1 AMP (current fault).
5.1.1.3. Charge operation may be terminated at any time by depressing the
RESET (green) button.
5.1.2. SINGLE RATE:
5.1.2.1. The battery is charged at the topping rate for a preset time.
5.1.2.2. Charging is automatically terminated at the end of the total time
selected (cycle end), or as a fault if:
• Battery overtemperature is detected (Overtemp fault).
• Battery voltage is in excess of 1.75V/cell as determined by the
number of cells programmed, or if battery voltage is in excess of
85V (voltage fault).
• Actual charging current differs from the programmed value by
more than 1 AMP (current fault).
5.1.2.3. Charge operation may be terminated at any time by depressing the
(green) reset button.
Page 23 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
5.2 CONSTANT VOLTAGE CHARGE.
5.2.1. The battery is charged at the topping rate for a preset time.
5.2.2. When the battery voltage is within 0.5V of the selected float voltage, the
charging current begins to diminish, and settles to the level of current required to
maintain the battery at the selected float voltage.
5.2.3. Charging is automatically terminated at the end of the total time selected (cycle
end), or as a fault if:
• Battery overtemperature is detected (Overtemp fault).
• Battery voltage is in excess of 85V (voltage fault).
• Actual charging current differs from the programmed value by more than 1
AMP (current fault). Note: applicable only before the charger switches from
constant current to constant voltage.
5.2.4. Charge operation may be terminated at any time by depressing the (green) reset
button.
Page 24 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
5.3 PEAK CHARGE.
5.3.1. Transfer from Main to Topping on Peak voltage.
5.3.1.1. The battery is charged at the main rate for a preset time.
5.3.1.2. When the battery voltage reaches the programmed peak voltage, the
charging current transfers from main to topping.
5.3.1.3. Charging is automatically terminated at the end of the total time
selected (cycle end), or as a fault if:
• Battery overtemperature is detected (Overtemp fault).
• Battery voltage is in excess of 85V (voltage fault).
• Actual charging current differs from the programmed value by
more than 1 AMP (current fault).
• NOTE: Charge operation may be terminated at any time by
depressing the (green) reset button.
5.3.2. Stop on Peak Voltage.
5.3.2.1. The battery is charged at the main rate for a preset time.
5.3.2.2. When the battery voltage reaches the programmed peak voltage, the
charging current stops.
5.3.2.3. Charging is automatically terminated at the end of the total time
selected (cycle end), or as a fault if:
• Battery overtemperature is detected (Overtemp fault).
• Battery voltage is in excess of 85V (voltage fault).
• Actual charging current differs from the programmed value by
more than 1 AMP (current fault).
• NOTE: Charge operation may be terminated at any time by
depressing the (green) reset button.
Page 25 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
5.4 DISCHARGE.
NOTE: For battery voltages greater than 32V, the discharge current is automatically
limited to 30A. A current fault condition will result if more than 30A is programmed.
5.4.1. ANALYSIS (AUTO CUT-OFF):
5.4.1.1. The battery is discharged at the selected rate for a preset time.
5.4.1.2. Discharge is automatically terminated (cycle end), at the end of the
time selected or if the battery voltage reaches the equivalent of 1
VOLT/cell (capacity failure), as determined by the number of cells
programmed, or it is terminated as a fault, if:
• The actual discharge current differs from the programmed value by
more than 1 AMP (current fault).
• Overheating of the transistor heat sinks is detected (overheat fault).
• NOTE: Discharge operation can be terminated at any time by
depressing the (green) reset button.
5.4.2. DEEP CYCLE (FULL DISCHARGE):
5.4.2.1. The battery is discharged at the selected rate for a preset time.
5.4.2.2. Discharge is automatically terminated (cycle end) at the end of the time
selected, or as a fault, if:
• The actual discharge current differs from the programmed value by
more than 1 AMP (current fault). NOTE: Undercurrent fault
monitoring is disabled at battery voltages below 2V.
• Overheating of the transistor heat sinks is detected (overheat fault).
Page 26 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
6. OPERATING INSTRUCTIONS
6.1 GENERAL
6.1.1. Verify RESET
6.1.1.1. Verify that the reset button is depressed before turning power on.
6.1.2. Connect the Battery
6.1.2.1. Connect the battery cable to the batteries and the Temp-Plate.
6.1.2.2. If only one battery is used, connect the free plug to the shorted
receptacle provided in the Temp-Plate.
6.1.2.3. Observe polarity when using the single cell adaptor.
6.1.2.4. If battery polarity is reversed, a voltage fault condition will be
indicated and further operation of the instrument will be inhibited.
6.1.3. Verify Voltmeter
6.1.3.1. The digital voltmeter will read battery voltage if the selector switch is
in the internal position.
6.1.3.2. Select the scale consistent with the battery voltage.
6.1.4. Program the number of cells.
6.1.4.1. Enter the number of cells of the battery
6.1.4.2. When working with more than one battery enter the TOTAL number of
cells.
6.1.4.3. Note 1: In the full discharge mode the number of cells is ignored.
6.1.4.4. Note 2: In the Float and Peak voltage modes, the cell selector becomes
a nominal battery voltage selector. See xxx
Page 27 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
6.2 CONSTANT CURRENT CHARGE.
6.2.1. Main Charge
6.2.1.1. Program Main charging rate and time duration.
6.2.1.2. Verify that the Timer Speed is consistent with the required elapsed
time.
6.2.2. Topping Charge
6.2.2.1. Program Topping charging rate and total time of charge (Total time =
Main + Topping Times).
6.2.2.2. Start in Dual Rate
6.2.2.3. Depress the Two Rate (white) control button.
6.2.2.4. DUAL and MAIN indicators will turn on and current will rise to the set
rate in about three to five seconds.
6.2.2.5. Verify colon(:)
• The colon in the digital time display will flash a the rate of one
cycle per second.
6.2.3. Single Rate Charge
6.2.3.1. For a single rate, program the current using the Topping selector
6.2.3.2. Set the required (total) time and depress the single rate (yellow) control
button.
6.2.3.3. The SING and TOP indicators will turn on and battery current will rise
to the set rate in about three to five seconds.
6.3 CONSTANT VOLTAGE CHARGE
6.3.1. Nominal Battery Voltage
6.3.1.1. Enter the nominal battery voltage using the cell selector (see chart on
page 19).
6.3.2. Maximum Charge Current
6.3.2.1. Program the maximum charge current using the Topping Current
selector.
6.3.3. Time
6.3.3.1. Program sufficient time in the Total Time selector to allow the battery
to reach the required charge level (consult battery manufacturers
specifications).
6.3.3.2. Verify that the Timer Speed is consistent with the required elapsed
time.
Page 28 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
6.3.4. RUN
6.3.4.1. Start the Charger-Analyzer in the Single Rate mode. The charger will
start to reduce the charging current when the battery voltage is within
0.5V of the float level.
6.3.4.2. The charge will terminate automatically (CYCLE END) when the
TOTAL TIME selected is reached.
6.3.4.3. The charge will terminate as a FAULT if the MONITOR CIRCUIT
detects that:
• Battery temperature exceeds 45oC/113oF (BATTERY
OVERTEMP FAULT).
• The actual charge current deviates from the programmed value by
more than 1A (CURRENT FAULT).
6.4 PEAK VOLTAGE CHARGE:
6.4.1. Nominal Battery Voltage
6.4.1.1. Enter the nominal battery voltage using the Cell selector (see chart on
page 19).
6.4.1.2. Select transfer from Main to Topping on Peak Voltage or stop on Peak
Voltage.
6.4.2. Charge Currents
6.4.2.1. Program the Main and Topping Charge currents as required.
6.4.3. Time
6.4.3.1. Program the Main and Total Time selectors to allow the battery to
reach the required charge level (consult battery manufacturers
specifications).
6.4.3.2. Verify that the Timer Speed is consistent with the required elapsed
time.
6.4.4. RUN
6.4.4.1. Start the Charger-Analyzer in the Dual Rate mode. If transfer on peak
is selected, the charger will transfer from Main to Topping charge
when the battery reaches the peak voltage. If stop on peak is selected,
the Charger stop upon reaching the peak voltage.
6.4.4.2. The charge will terminate automatically (CYCLE END) when the
TOTAL TIME selected is reached.
6.4.4.3. The charge will terminate as a FAULT if the MONITOR CIRCUIT
detects that:
• Battery temperature exceeds 45oC/113oF (BATTERY
OVERTEMP FAULT).
• The actual charge current deviates from the programmed value by
more than 1A (CURRENT FAULT).
Page 29 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
6.5 DISCHARGE
NOTE: Do not discharge batteries on the Temp-Plate. Normal battery heating of the
Temp-Plate during discharge will generate a false battery Overtemp fault when
attempting to recharge it.
6.5.1. Current and Time
6.5.1.1. Program the discharge rate and time duration.
6.5.1.2. Verify that the Timer Speed is consistent with the required elapsed
time.
6.5.2. RUN
6.5.2.1. Depress auto discharge (BLUE) control button, for analysis to one volt
per cell.
6.5.2.2. Depress full discharge (RED) control button for battery deep cycling.
6.5.2.3. DISCHARGE will terminate automatically (CYCLE END) when the
(TOTAL) time selected is reached or (CAPACITY FAILURE) if the
BATTERY voltage reaches the equivalent of ONE VOLT per CELL
prior to the selected time.
6.5.2.4. NOTE: Battery voltage is ignored during full discharge.
6.5.2.5. Discharge will terminate as a FAULT if the MONITOR CIRCUIT
detects:
• An overheating of the discharge transistors (OVERHEAT
FAULT).
• That the discharge current differs from the programmed value by
more than one AMP (CURRENT FAULT).
• That the programmed current exceeds 30A for a battery voltage in
excess of 32V.
Page 30 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
6.6 Float/Peak Voltage Chart
CHART RELATING THE COMPUTED FLOAT AND PEAK VOLTAGES TO THE
SELECTED NOMINAL BATTERY VOLTAGE
6.6.1. The Cell Selector becomes a Nominal Battery Voltage selector in other than the
Constant Current settings of the Voltage Mode Selector.
6.6.2. NOTE: Nominal battery voltage is referenced on the basis of 1.2V/cell for
Nickel-Cadmium batteries and 2V/cell for Lead-Acid batteries. e.g.: a 20 cell
Nickel-Cadmium battery and a 12 cell Lead-Acid battery are both considered to
be 24V batteries. Consult manufacturers specifications for optimum float and
peak voltage charge levels.
Table 1 - Constant Voltage and Peak Voltage Chart
CELL
SELECTOR
1
FLOAT
PEAK
VOLTAGE
-----
CELL
SELECTOR
25
FLOAT
VOLTAGE
29.1
PEAK
VOLTAGE
30.6
-----
2
2.3
3.5
2.5
3.7
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
30.3
31.5
32.6
33.8
35.0
36.1
37.3
38.4
39.6
40.8
41.9
43.1
44.3
45.4
46.6
47.8
48.9
50.1
51.3
52.4
53.6
54.8
55.9
31.9
33.1
34.3
35.5
36.8
38.0
39.2
40.4
41.7
42.9
44.1
45.3
46.6
47.8
49.0
50.2
51.5
52.7
53.9
55.1
56.4
57.6
58.8
3
4
4.7
4.9
5
5.8
6.1
6
6.7
7.4
7
8.2
8.6
8
9.3
9.8
9
10.5
11.7
12.8
14.0
15.1
16.3
17.5
18.6
19.8
21.0
22.1
23.3
24.5
25.6
26.8
28.0
11.0
12.3
13.5
14.7
15.9
17.2
18.4
19.6
45.3
22.1
23.3
24.5
25.7
27.0
28.2
29.4
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Page 31 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
6.7 OPERATING NOTES AND PRECAUTIONS
6.7.1. Make sure that the instrument is in the reset position before turning power on or
off, or before connecting or disconnecting batteries.
6.7.2. When a cycle is terminated either automatically or by resetting, wait about two to
three seconds before re-starting in any mode (the control switch circuit has a time
delay that ignores switch selections during a 2 to 3 second interval).
6.7.3. It is possible to alternate between the two discharge modes or from the dual rate
to the single charge rate mode while the unit is in operation, but the charger must
be reset before switching to an opposite mode (e.g. from charge to discharge or
vice versa).
• NOTE: The control switch circuit ignores mode change requests without
previous resetting of the charger.
6.7.4. If the discharge current limiter opens it is still possible to operate in the charge
mode (by setting the switch in the Monitor board to Test), but if the charge
current limiter opens, the unit is rendered completely inoperative.
6.7.5. It is imperative that the current limiter and fuses be replaced with the same type
and value.
6.7.5.1. Failure to do so will result in serious damage to the control and power
circuitry of the instrument.
6.7.5.2. Failure to observe this requirement will void the warranty.
6.7.6. Do not block air circulation. A substantial amount of heat must be dissipated,
particularly in the discharge mode (up to 1KW).
• External heat removal (circulating fan) is required when operating in
confined spaces or hot environments.
6.7.7. Do not disconnect the battery cable while the unit is in operation.
• Large current surges can occur, with corresponding arcing, that can damage
the charger, the connectors and the battery.
6.7.8. Disconnect batteries and power from the instrument (remove the line cord from
the wall outlet) before changing circuit boards and current limiters or to perform
maintenance or repairs.
• Failure to do so can result in serious (lethal) personal injury and/or serious
damage to the instrument.
6.7.9. Do not exceed a setting of 79 in the total time selector.
• If exceeded, times will be inconsistent with the dialed settings.
6.7.10. Do not run the unit with the monitor switch in the test position (except for tests).
Loss of protection will occur.
6.7.11. Do not perform battery work on bare metal table tops.
6.7.12. Do not attempt to discharge with the Voltage Mode Selector in the CV or PEAK
positions.
• Voltage and currents faults will result depending on the battery voltage and
cell selector settings.
Page 32 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
7. INSTALLATION
7.1 BENCH SPACE.
7.1.1. The Charger-Analyzer system occupies 19" x 17" (48.3 cm x 43.2 cm) of table
top space for the charger and 10" x 25" (25 cm X 63.5 cm) for the Temp-Plate.
7.1.2. Allow also at least 6" (15.2 cm) of separation from the wall and adjacent
equipment, in order to maintain proper air flow (VITAL!).
7.1.3. NOTE 1: In non air-conditioned rooms or if other heat dissipating equipment are
nearby, it is recommended that circulating or extracting fans be used to aid in the
heated air removal.
7.1.4. NOTE 2: Operation in dusty or otherwise "dirty" air environments will severely
reduce the cooling capacity of the fans and lead to premature failure.
7.2 LINE VOLTAGE.
7.2.1.
Connect the unit to a wall receptacle NEMA 6-30R, 230V (re-wire the
transformers input for 240V or 208V operation) with a 30 AMP capacity. This
line must be a dedicated line, originating at the breakers box and must be
protected with a motor load rated circuit breaker. Sharing of the line with other
equipment may result in erratic operation of the Charger-Analyzer and the other
devices connected to the same line.
7.2.2. NOTE: Operation of this unit with a "soft" line or with a line voltage 10% above
or below the nominal 208/230/240VAC will result in erratic operation and may
also lead to equipment damage if large voltage surges occur.
7.2.3. Power (Mains) Wiring Diagram
Figure 3 - Line Voltage Wiring, 115V
Page 33 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 4 - Line Voltage Wiring, 208/230V
Figure 5 - Line Voltage Wiring, 230/245V
Page 34 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
8. VERIFICATION OF PERFORMANCE
The Charger-Analyzer has been designed, manufactured and tested to give thousands of hours
of trouble free operation, but if you find that your unit is not performing properly (or as
expected), please refer first to the operating instructions for re-assurance that proper procedures
are being followed.
If it is determined then, that your Charger-Analyzer is malfunctioning or appears to be
malfunctioning, please refer to the verification of performance, calibration and troubleshooting
sections which will show you how to use the various built-in test features to determine or
approximate the nature of the problem.
NOTE 1: The Charger-Analyzer is a precision instrument. Use only certified instrumentation
capable of accuracies of at least 0.25% on voltage and 0.5% on current.
• The CAL-100 Battery Charger-Analyzer Calibrator provides all necessary functions to
monitor, verify and calibrate the Charger-Analyzer.
NOTE 2: In the following tests make no connection to a battery unless specifically indicated.
Always start from reset and always reset at the conclusion of a test.
8.1 REQUIRED TEST EQUIPMENT AND ACCESSORIES.
8.1.1. CAL-100 Calibrator and one 20 to 50A-Hr 20 cell battery
8.1.2. IF a CAL-100 Calibrator is not available, the following items are required in
addition to the battery mentioned in (a) .
8.1.2.1. Power Supply capable of 60V output with very little current capability
(less than 20mA).
8.1.2.2. Ammeter or Shunt capable of at least 50A
8.1.2.3. Digital Voltmeter, 3-1/2 digits or better.
8.1.2.4. Four each of 16.5K, 17.5K and 30.1K 1% resistors (1/4W)
8.2 VISUAL VERIFICATION.
8.2.1. Set the Voltage Mode Selector to CC (first position).
8.2.2. Turn power on.
8.2.3. Verify the following:
8.2.3.1. Reset/cycle end (green) light must be on
8.2.3.2. The digital panel meters must read zero
8.2.3.3. The elapsed time display must read zero (colon must be off).
Page 35 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
8.3 TIMER VERIFICATION.
8.3.1. Settings:
8.3.1.1. Set the Main and Topping Charge Current Selectors to zero.
8.3.1.2. Set both Time Selectors to zero.
8.3.1.3. Set the Timer Speed Switch to the test (center) position.
8.3.2.
NOTE: Current and voltage readings must remain at zero during the following
tests. If voltage starts to rise, which may lead to voltage a fault, verify that the
current selectors are completely at zero.
8.3.3. Start the unit by depressing the two rate charge selector.
8.3.3.1. The unit will go immediately into Cycle End.
8.3.3.2. Reset.
8.3.4. Set the total time to 01 and start.
8.3.4.1. Unit will start in main charge and immediately transfer to topping,
going into cycle end after one second.
8.3.4.2. Reset.
8.3.5. Set the main time to 1, total time to 02 and start.
8.3.5.1. The unit will start in the main mode, transfer to topping after one
second and go into cycle end after two seconds.
8.3.5.2. Reset.
8.3.6. Repeat the above tests, each time advancing the main and total time selectors as
follows: 2/04, 4/08, 8/09, 9/10, 9/20, 9/40 and 9/79 (or 9/60 depending on the
type of Timer).
Page 36 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
8.4 BATTERY OVERTEMP CUT-OFF.
8.4.1. Settings:
8.4.1.1. Set current selectors to zero.
8.4.1.2. Set the timer speed switch in the normal position (to the right).
8.4.1.3. Set time selectors to 1/01 and cell selector to 20.
8.4.1.4. Connect the battery cable to the unit but make no battery or Temp-
Plate connections. The red Overtemp light will be on.
8.4.2. Temp-Plate simulations resistors:
8.4.2.1. Connect one 16.5 K-OHM (1%) resistor between pins D and B
8.4.2.2. Connect one each 30.1 K-OHM (1%) resistors between pins D and C,
D and E, and D and H.
8.4.2.3. The red light will turn off.
8.4.3. Start in either of the charge modes.
8.4.3.1. The unit will start and immediately go into Overtemp fault (red light
flashing and alarm on).
8.4.3.2. Reset.
8.4.4. Repeat the previous test by rotating the 16.5 K-OHM resistor in all four
positions.
8.4.5. Repeat the first test using four 17.5 K-OHM (1%) resistors.
8.4.5.1. The unit must not show Overtemp fault.
8.5 VOLTAGE FAULT TEST.
8.5.1. Disconnect battery cable from any external devices.
8.5.2. Settings:
8.5.2.1. Set the Current Selectors (both) to 010.
8.5.2.2. Set the Time Selectors to 1/01.
8.5.2.3. Set the Cell Selector to 20.
8.5.3. Start in either of the charge modes.
8.5.3.1. The unit will start and the output voltage will slowly rise.
8.5.3.2. The unit will stop, indicating a voltage fault.
8.5.3.3. Reset.
Page 37 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
8.6 REVERSE POLARITY TEST.
8.6.1. Connect the battery cable to a voltage source (CAL-100 or low current power
supply and reverse the polarity). Start at zero and advance towards -0.5V
8.6.2. The unit will show a fault through the alarm and the voltage fault light at about -
0.25V (-0.20V to -0.35V).
8.6.3. Alternatively, connect the battery cable, with the single cell adaptor, to one cell
with the polarity reversed or to a standard 1.5V battery (size is unimportant).
8.7 OVERVOLTAGE CUT-OFF.
8.7.1. Set the Current selectors to zero and Time selectors to 1/01. Set the Cell selector
to 20.
8.7.2. Connect the battery cable to an adjustable voltage source (CAL-100 or low
current power supply), set to approximately 34V and start the unit in either
charge mode.
8.7.3. Slowly increase the voltage. Unit will stop and indicate a voltage fault at 35V
±0.5V. Reset.
8.7.4. (See 8.2.5 for adjustments)
8.8 DISCHARGE VOLTAGE CUT-OFF.
8.8.1. Settings:
8.8.1.1. Set the Current selectors to zero and the Time selectors to 1/01.
8.8.1.2. Set the Cell selector to 20.
8.8.2. Connect the battery cable to a voltage source (CAL-100 or low current power
supply), set to approximately 21V and start the unit in the auto discharge mode
(blue).
8.8.3. Slowly decrease the voltage. Unit will go into cap fail at 20V ±0.3V. Reset.
8.8.4. (See 8.2.1 for adjustments)
Page 38 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
8.9 FULL DISCHARGE.
8.9.1. Settings:
8.9.1.1. Set the Current selectors to zero.
8.9.1.2. Set the Time selectors to 1/01.
8.9.1.3. Set the Cell selector to 20.
8.9.2. Start the unit in the full discharge mode (red). Unit will run. Increase the
discharge current selector to any value above 1 AMP (010). Unit will continue to
run.
8.9.3. Switch to Auto discharge. Unit will go to Capacity Failure. Disconnect from the
voltage source. Reset.
8.10 CURRENT TRACKING.
8.10.1. Settings:
8.10.1.1. Set the Time selectors to 1/01 and the Cell selector consistent with the
battery.
8.10.1.2. Set the main charge current selector to 25 AMPS (250)
8.10.1.3. Set the topping charge current selector to 1 AMP (010).
8.10.2. Connect the Battery Cable to the battery.
8.10.3. Start the unit in the two rate mode. Current will rise to 25.0A ±0.35A.
8.10.4. Switch to the single rate mode. Current will drop to 1.0A ±0.2A. Reset.
8.10.5. Repeat this test for other high and low settings.
8.10.6. Repeat also for the discharge mode.
8.10.7. NOTE: In discharge, the readings may be lower by 0.1A to 0.2A.
8.10.8. See 8.2.4 for adjustments
8.11 VOLTAGE CONTROL.
8.11.1. See 8.2.7 for adjustments.
Page 39 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
8.12 FLOAT VOLTAGE:
8.12.1. Settings:
8.12.1.1. Set the Voltage Control Selector to Float
8.12.1.2. Set the Current Selectors to zero.
8.12.2. Connect the Battery Cable to the battery and note the battery voltage.
8.12.3. Using the chart in figure 3 (page 19) find in the FLOAT column the closest
higher voltage (by at least 1V) to the observed voltage on the battery. Set the cell
selector to the value indicated in the Cell Selector column.
8.12.4. Start the Charger-Analyzer in Single Rate an advance the Topping current to 1A
8.12.5. Observe that the current will start to be reduced as the battery voltage approaches
the corresponding float voltage.
8.12.6. Example: for 24V measured on the battery set the cell selector to 22. This will
result in a float voltage of 25.6. As long at the voltage at the battery is less than
25.1, the charge current will be as programmed. As the voltage rises towards the
expected 25.6, the current will start to decrease and will settle on a value of
current to maintain the battery at 25.6
8.12.7. Depending on the condition of the battery, a charge current higher than the initial
1A may be required for the battery to rise to the expected float voltage.
Conversely, if the voltage rises too fast it will be necessary to select the next
higher reading (23 for 26.8V) and /or a lower charge current.
8.12.8. Verify that the Charger-Analyzer maintains the battery at the expected voltage
±0.2AV
8.13 PEAK VOLTAGE:
8.13.1. Settings:
8.13.1.1. Set the Voltage Control Mode to Peak.
8.13.1.2. Set both current selectors to zero
8.13.1.3. Program for a nominal battery voltage of 24V on the cell selector
(setting = 24).
8.13.2. Connect the CAL-100 Calibrator or a power supply (capable of producing at least
35V with very little current) in place of the battery.
8.13.3. Set the calibrator/power supply to 28.5V
8.13.4. Start the Charger-Analyzer in Dual rate. The current will rise to the programmed
value.
8.13.5. Increase the power supply/calibrator towards 29.4V. The Charger-Analyzer will
switch from Main to Topping at a battery voltage of 29.4V ±0.5V.
8.13.6. Return the Voltage Control Mode to CC.
Page 40 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
8.14 METERS
8.14.1. Verify the battery voltage and charge/discharge current readings by comparing
against a CAL-100 Calibrator or a reference voltmeter and a reference ammeter
(or reference shunt).
8.14.2. See 8.1 for adjustments.
Page 41 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
9. CALIBRATION
• NOTE 1: The Charger-Analyzer must be verified (and calibrated if required) at least once
every 12 months, or earlier if deviation from performance is observed. (see first note on
section 7).
• NOTE 2: Perform adjustments only when changing parts and components that require re-
calibration.
• NOTE 3: Perform a Verification of Performance prior to attempting a calibration (see
Section 7, page 25). If the Charger-Analyzer does not perform in accordance to what is
called for in Verification of Performance, then, and only then, proceed with an actual
calibration (adjustments).
9.1 CIRCUIT BOARD ADJUSTMENTS AND CALIBRATION
WARNING! The ground of the electronics circuitry floats on the battery voltage. Make
no connections between the electronics ground and the battery or chassis ground.
Serious damage to the wiring and control circuits will occur if any part of the circuitry
becomes in contact with the chassis while a battery is connected.
NOTE: Most adjustments are performed with no current (no battery required) and
require the use of a voltage source to simulate battery voltages such as the CAL-100
Calibrator or a Power Supply. A battery is required for the adjustments of current output.
9.2 DIGITAL METERS (see [Figure 6]).
NOTE: Digital meters are adjusted by means of multi-turn trimming potentiometers
(trimpots) located on the rear (solder side) of the METERS board.
9.2.1. AMMETER.
9.2.1.1. NOTE 1: Newer versions of this circuit board no longer have a zero
adjustment.
9.2.1.2. NOTE 2: Modified versions of this circuit board may not have a zero
adjustment. (not required).
9.2.1.3. ZERO:
• Adjust the zero with R3 for a reading of 00.0 (the exact point is
when the + - signs alternate).
9.2.1.4. SCALE:
• This meter has a full scale of 199.9 millivolts to read a 100 AMP
shunt with an output of one millivolt per AMP.
• Verify and calibrate using an external ammeter with digital
readout. Adjust R10 at a minimum of 25.0A for a reading within
±0.1A of the reference ammeter.
Page 42 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
• NOTE 3: Insert an external shunt/ammeter in series with any of the
battery leads (Use the Single Cell adaptor to facilitate the
connection or simply use the CAL-100 which is a calibrator
designed specifically to test and certify Charger-Analyzer Battery
Charger-Analyzers.
• NOTE 4: The charge output current wave is in the form of short
pulses (at twice the line frequency). The use of clamp-on meters
and moving magnet meters will yield erroneous readings. Verify in
discharge (pure DC) if better meters are not available.
9.2.2. VOLTMETER.
9.2.2.1. ZERO: No zero adjustments.
9.2.2.2. SCALE:
• This meter has a full scale of 1.999 volts, but an attenuator on the
board converts it to a full scale of 1.999, 19.99 or 199.9 volts, as
selected by the DPM selector switch.
• Verify and calibrate using a voltage source (Power Supply or
CAL-100, as a battery voltage simulator) between 10 and 20 volts
in the "EXTERNAL 20V" position.
• Adjust R17 for a reading within " 0.01V of the reference voltmeter.
• NOTE: individual scales cannot be adjusted.
Page 43 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 6 - Meters Board Adjustments
Page 44 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 7 - Control Switch Board Adjustments
9.2.3. CONTROL SWITCH (see fig 8).
NOTE: For voltage measurements use pin 14 on the Current Control Board as
reference common.
9.2.3.1. R10 - AMPLIFIER ZERO.
• Static test (no battery or Calibrator).
• Adjust a reading of 0.000V " 0.003V at E3 on the CONTROL
circuit board.
• NOTE 2: Newer versions of this circuit board no longer have a
zero adjustment.
• NOTE 3: Modified versions of this circuit board may not have a
zero adjustment. (not required).
9.2.3.2. R11 - DISCHARGE CELL CALIBRATE.
• No battery is required for this test.
Page 45 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
• Set the Cell Selector at 20, connect a voltage source set to
approximately 21V and start the Charger-Analyzer in AUTO
Discharge
• Adjust for a Discharge CUT-OFF (Capacity Failure) at 20.0 volts.
• NOTE: This step requires that the Overvoltage cut-off on the
MONITOR circuit board be previously calibrated.
9.2.3.3. CLOCK-TIMER
• No adjustments on this board.
• Older versions of the Charger-Analyzer use two circuit boards
associated with timer functions: The Timer Board 9879903010 and
the Clock Display Board 9879903009.
• Newer Superserseders use a single Clock-Timer Board
9879903109. In either case, there are no adjustments to perform.
9.2.3.4. (Blank)
9.2.3.5. CURRENT CONTROL (see fig 11).
NOTE: Use the hook at pin 14 as ground reference for voltage
measurements (test point E0).
9.2.3.5.1.
R29 - 10 VOLT ADJUSTMENT.
• Static test (no battery or Calibrator).
• Adjust for a reading of 10.000V ±0.003V at E7.
• NOTE: Newer versions of this circuit board have a
fixed 10V reference (no adjustment). Verify that it
reads 10V ±0.005V.
9.2.3.5.2.
R28 - LOW CURRENT CALIBRATE.
• Connect a battery and start the Charger-Analyzer in
Single Rate.
• Adjust for a reading of 0.9 to 1.0 AMP at the current
digital panel meter, with the topping charge current
potentiometer set for 1 AMP (010).
9.2.3.5.3.
R25 - HIGH CURRENT CALIBRATE
• Connect a battery and start the Charger-Analyzer in
Dual Rate.
• Adjust for a reading of 25.0 AMPS at the current
digital panel meter, with the main current
potentiometer set for 25.0 AMPS (250).
Page 46 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
• NOTE 1: Other currents can also be used for High
Current calibration (20A minimum).
• NOTE 2: Adjustments of R28 and R25 are
interactive. Therefore, It will be necessary to repeat
the adjustments once or twice to achieve exact
results.
• The Voltage reading at E3 (shunt amplifier output)
must correspond to the current as follows: voltage at
E3 = -0.1V/A ±2%.
• Examples:
40 A equals -4.00V ±0.08V
20 A equals -2.00V ±0.04V
10 A equals -1.00V ±0.02V
5 A equals -0.50V ±0.01V
Figure 8 - Current Control Board Adjustments
Page 47 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 9 - Monitor Board Adjustments
9.2.4. MONITOR (see fig 12)
NOTE:
Use pin 14 on the card connector (or the Test Point E0 on the
Control Board) as ground reference for voltage measurements.
9.2.4.1. U12 pin 1 - BATTERY VOLTAGE
• This point corresponds to one tenth of the battery voltage present
at the input terminals.
9.2.4.2. U12 pin 7 - CELL SELECTOR
• This point corresponds to one tenth volt per cell, e.g. 2.00V = 20
cells.
Page 48 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
9.2.4.3. R62 – OVERVOLTAGE
• (no battery)
• Set the Current Selectors to zero and set the Cell Selector to 20
(1.75V/cell)
• Connect an external voltage source (Power Supply or CAL-100) to
simulate the battery voltage, set at approximately 34V.
• Start the Charger-Analyzer in either of the Charge modes and
adjust this trimpot for an Overvoltage charge cut-off at 35.0V
±0.1V.
9.2.5. POWER
There are no adjustments in the Power circuit board, but the following voltages
must be measured at the card edge connection fingers (bottom), using a standard
digital voltmeter referenced to pin 14.
9.2.5.1. PIN # * VOLTAGE
• 10 to 11 * 36VAC (" 2V nominal, line dependent).
• NOTE: 10 to 14 or 11 to 14 will read ½ the total voltage (18V,
nominal).
• 12 * 12V"B" (11.4V "0.6V).
• NOTE: This is a battery backed-up source. During a power failure,
the voltage will drop to the backup battery voltage minus 0.6V
(approximately 7.8V for a 7 cell battery or 9.0V for an 8 cell
battery).
• 13 * COMMON (not chassis ground or battery negative!).
• 14 * COMMON (not chassis ground or battery negative!).
• 15 * +15V (+15.0V "0.75).
• 16 * -15V (-15.0V "0.75).
• 17 * 9V Battery (8.4V to 9.6, nominal for 7 or 8 cell batteries
respectively).
• 18 * 18V (17V +1, -2V nominal, line dependent).
• 21 * Timing pulse, twice the line frequency and about 11V and
1ms duration (will read 1.2V +0.1V, -0.2V with a DC meter)
• 22 * 12V"A" (11.4 "0.6V).
Page 49 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 10 - Voltage Control Board Adjustments
9.2.5.2. VOLTAGE CONTROL - See [Figure 10]
9.2.5.2.1.
R11, FLOAT VOLTAGE:
• Connect a CAL-100 Calibrator or a power supply
capable of producing at least 10V (very little current
required) to the CAL (-) and CAL (COMMON) test
points. The positive lead to COMMON and the
negative lead to CAL (-).
• Set the calibrator/power supply to 2.70V to simulate
a battery that has 27.0V.
• NOTE: The Calibrator voltage is 1/10 of the
simulated battery voltage.
• Connect a battery to the Charger-Analyzer.
• Set the Voltage Control Mode Switch to CV
(Constant Voltage)
• Program for 10A of Topping current.
• Enter 24 in the cell selector (nominal battery
voltage).
• Start the Charger-Analyzer in Single rate. The
current will rise to the programmed 10A.
• Increase the power supply voltage towards 2.8V and
observe the current.
• The charging current will begin to decrease at about
2.75V and should reach zero as the voltage is
advanced to 2.8V.
• NOTE: Ignore the actual battery voltage. The Float
voltage control circuit is responding to the simulated
battery voltage as provided by the power supply.
Page 50 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
• Adjust R11 as required to reduce the charging
current to zero at a simulated battery voltage of
28.0V
• Note: This test can also be performed directly on a
battery (no calibrator required), preferably one that
is “soft” (rapid voltage change). Adjust R11 as
necessary to maintain the battery at the required
voltage (see Verification of Performance, section 7,
page 27).
9.2.5.2.2.
R14, PEAK VOLTAGE:.
• Connect a CAL-100 Calibrator or a power supply
(capable of producing at least 35V with very little
current) in place of the battery.
• Set the calibrator/power supply to 28.5V
• Set the Voltage Control Mode to Peak (Transfer).
• Set both current selectors to zero
• Enter 24 in the cell selector (nominal battery
voltage).
• Start the Charger-Analyzer in Dual rate. The current
will rise to the programmed value.
• Increase the power supply/calibrator towards 29.4V.
The Charger-Analyzer will switch from Main to
Topping at a battery voltage of 29.4V
• Adjust R14 as required to switch at 29.4 ±0.1V
• Return the Voltage Control Mode to CC.
• Note: on newer models there is one extra Peak
position to STOP at the peak voltage.
• Set the Voltage Control Mode Switch to Peak Stop
• Verify that the Superseder will stop at the peak
voltage (as opposed to transfer from Main to
Topping).
Page 51 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 11 - Circuit Board Sequence
Page 52 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
10. TROUBLESHOOTING AND REPAIRS
10.1 TROUBLESHOOTING
The following are hints and directions to help you locate the most probable causes of
deviation of performance as established in the procedures of section 8.
10.1.1. UNIT CHARGES ON MAIN BUT DOES NOT CHARGE ON TOPPING AND
DOES NOT DISCHARGE.
Defective Topping/Discharge current selector or defective Control board.
10.1.2. UNIT CHARGES PROPERLY ONE BATTERY BUT CANNOT CHARGE
TWO BATTERIES AT HIGH RATES.
Low line voltage.
10.1.3. UNIT GOES INTO VOLTAGE FAULT IMMEDIATELY OR SHORTLY
AFTER STARTING UP (charge mode).
Open link or one or more cells developing a high voltage.
10.1.4. UNIT DISCHARGES CORRECTLY ONE BATTERY BUT RESULTS IN A
CURRENT FAULT WHEN DISCHARGING TWO BATTERIES.
Attempting to discharge more than 20A on a battery with more than 28V or
defective Monitor board.
10.1.5. THE UNIT CHARGES LOW CURRENT (BELOW 10 AMPS) PROPERLY
BUT HUMS NOTICEABLY AT HIGHER CURRENTS.
One of the SCR's is inoperative, or one of the rectifiers is open.
10.1.6. UNIT CHARGES ON TOPPING AND DISCHARGES CORRECTLY BUT
WILL NOT CHARGE IN MAIN.
Defective Main Current Selector or defective Control board.
10.1.7. UNIT STARTS IN THE DISCHARGE MODE BUT GOES INTO CAPACITY
FAILURE IMMEDIATELY.
Battery not properly connected. Open link. Open cable.
10.1.8. THE DISCHARGE CURRENT LIMITER OPENS THE MOMENT A
BATTERY IS CONNECTED TO THE CHARGER.
Shorted discharge transistors(s).
10.1.9. BURNED RESISTOR(S) IN THE DISCHARGE HEATSINK(S).
Transistor(s) shorted and discharge current limiter did not open (wrong limiter
value or type).
10.1.10.RESET INDICATOR AND TIMER DISPLAY DO NOT TURN ON.
Open fuse to electronics card rack or problems with the Power circuit board or
the transformer feeding it.
10.1.11.DIGITAL VOLTMETER REGISTERS A VOLTAGE (APPROXIMATELY 36
VOLTS) WITH THE UNIT IN RESET AND THE BATTERY IS NOT
CONNECTED.
One or both SCR'S shorted.
Page 53 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Do not connect a battery under this condition!
10.1.12.9.1.12 CURRENT TRACKING IS OFF BY A SMALL CONSTANT
AMOUNT.
Amplifier zero or low current calibrate out of adjustment (CONTROL board).
10.1.13.9.1.13
CURRENT TRACKING IS OFF BY A SMALL AMOUNT
WHICH INCREASES AS THE PROGRAMMED VALUE IS INCREASED.
High current calibrate out of adjustment (CONTROL board).
10.1.14.9.1.15
THE UNIT STARTS BUT EXHIBITS A CURRENT FAULT
AFTER SOME TIME (from a few seconds to a few minutes).
a) Current tracking is off, exceeding 1 AMP: Verify Control board calibration.
See 8.2.5 and 8.2.2.
b) Current tracking is proper: Verify that the shunt amplifier in the Control
board reads properly. See 8.2.5 and 8.2.2.
10.1.15.FAULT LIGHT(S) ON AND NO AUDIBLE ALARM. UNIT RUNS
NORMALLY.
• Switch in the Monitor board is set in the test position.
• If the switch is in the correct position (run), turn power off and back on to
clear the condition and resume operation without resetting.
10.1.16.DIGITAL METERS DO NOT TURN ON.
Open fuse to digital panel meters.
10.1.17.OPEN LIMITER, SMALL CRACK.
Inconsequential opening. Replace and resume operation.
10.1.18.OPEN LIMITER, BLOWN ELEMENT (vaporized).
• Discharge transistors short.
• Perform test per 9.2.
10.1.19.CURRENT FAULT IN CV.
• Attempting to charge a battery with a voltage higher than the programmed
float voltage.
• Attempting to discharge a battery with a voltage lower than the float voltage.
10.1.20.VOLTAGE FAULT IN CV OR PEAK.
Attempting to discharge a battery with a voltage grater than the float voltage.
10.1.21.IMMEDIATE TRANSFER TO TOPPING IN PEAK.
Attempting to charge a battery with a voltage higher than the programmed peak
voltage.
10.1.22.IMMEDIATE STOPPPING IN PEAK.
Attempting to charge a battery with a voltage higher than the programmed peak
voltage.
Page 54 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
10.2 FINDING A SHORTED DISCHARGE TRANSISTOR
Since all discharge transistors are wired in parallel, a single shorted transistor will short
the entire bank.
The procedure that follows will allow the finding of the shorted transistor without
requiring removal and testing of each device individually.
10.2.1. EQUIPMENT REQUIRED
• Digital Voltmeter.
• Battery, 24V.
• Lamp, 24V (lamp must draw at least 0.5 A).
10.2.2. PROCEDURE
10.2.2.1. TURN UNIT OFF, DISCONNECT IT FROM THE WALL OUTLET.
10.2.2.2. Connect the lamp in place of the discharge current limiter (see fig 8).
10.2.2.3. Connect the charger to the battery.
10.2.2.4. If the lamp illuminates, it indicates that there is a short in the discharge
circuit, generated by one or more shorted transistors.
10.2.2.5. Measure the voltage across the individual .22 OHM emitter resistors
(RED-RED-GOLD-GOLD) (see fig 8).
• A non zero reading, approximately 0.1V for a lamp drawing .5A,
indicates current flow due to a transistor with a collector to emitter
short.
• NOTE: A non zero reading on all emitter resistors (0.02V approx
for a lamp drawing 0.5A) indicates a different failure mode
(collector to base short; refer to step 7).
10.2.2.6. Remove any shorted transistors and repeat steps 4 and 5 until a no
short reading is obtained. Replace defective devices only with
transistor type MJ15023.
10.2.2.7. If all transistors appear to be shorted (ALL emitter resistors reading a
voltage), then, one or more have failed with a collector to base short,
causing the remainder of the transistors to turn on. It will then be
necessary to check each transistor individually.
• This can be greatly facilitated by searching for a zero reading. This
will indicate the shorted device.
10.2.2.8. When replacing transistors, make sure that the base and emitter pins
engage properly in the socket contacts. Add heat sink compound and
torque the screws properly to insure a good thermal transfer.
• NOTE: If replacing any of the control transistors (Q1 and Q2),
note that they are mounted with a mica insulator.
Page 55 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 12 - Measuring for a shorted transistor
Page 56 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 13 - Location of Current Limiters
Page 57 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
Figure 14 - Power Block Diagram
Page 58 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
11. REPLACEABLE MODULES AND PARTS
11.1 CIRCUIT BOARDS
9879101001 - METERS (LED)
9879903004 - VOLTAGE CONTROL
9879960001 – CONTROL SWITCH
9879903009 – CLOCK (older units)
9879903010 – TIMER (older units)
9879903109 – CLOCK-TIMER (newer units)
9879903011 – CURRENT CONTROL
9879960012 – MONITOR
9879903013 – POWER
11.2 PARTS
30110003M0 – INSULATOR, MICA, TO-3
391207R110 – BATTERY, RECHARGEABLE, 7 cells, 100mA-Hr
4311R25SB0 – FUSE, ¼ W, Slow Blow
4317ANL060 – CURRENT LIMITER, ANL-60
4317ANN080 – CURRENT LIMITER, ANN-80
47412D1R00 – RESISTOR, POWER, 1 ohm, 2W, 5%
47130E10R0 – RESISTOR, POWER, 10 ohm, 1W, 5%
474120F1010 – RESISTOR, POWER, 100 ohm, 1/2W, 5%
47413CR33F – RESISTOR, POWER, 0.33 ohm, 3W, 5%, flameproof
4755101031 – POTENTIOMETER with DIAL, 10 turn
47562H1030 – CELL SELECTOR
4822J15001 – POWER TRANSISTOR, MJ15001
4822J15002 – POWER TRANSISTOR, MJ15002
4822J15023 – POWER TRANSISTOR, MJ15023
9811960461 – SCR
9811960463 – CHARGE DIODE
9811960462 – DISCHARGE DIODE
11.3 OTHER
Contact the factory at:
TEL 305-592-2272
TEL 305-599-6893
FAX 305-594-4933
Page 59 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
12. BATTERY TESTING NOTES
Note, hazardous condition: Handle batteries with extreme care as they are capable of very
high discharge rates if short circuited.
Check the Battery Manual, IMM or Aircraft Manufacturer Instructions for information on
charging, discharging and testing.
The Charge & Float and the Charge & Peak Stop modes are particularly useful with lead acid
batteries, where the battery voltage is a better indicator of the state of charge, as compared with
Nickel-Cadmium batteries where terminal voltage gives little information on the state of
charge.
Lead-Acid batteries are normally float charged (constant voltage) typically at 2.3V/cell. A 6
cell pack (12V) will then be float charged with the voltage selector at 13.8V. In this mode, the
charge current is set to the highest level that the cells will safely take (typically up to 1C
depending on the battery type and specific manufacturer’s instructions). This will be the charge
current until the float voltage is reached, at which time the current will diminish to the level
needed to maintain the float voltage.
Lead-Acid batteries can also be charged in a manner in which it is possible to know much
better the end of charge. When a Lead-Acid cell is charged with constant current at C/15 to
C/10, the end voltage will rise rapidly at about 90 to 95% of charge, which occurs at about 2.4
to 2.45V/cell. A 5A-hr, 6 cell pack, can be charged at 335mA to 500mA, with the voltage
selector at 14.7V. The CHARGER-ANALYZER will stop the charge operation when the rapid
rise of end-of-charge voltage is detected.
For Nickel-Cadmium batteries, the most effective charge method is constant current vs time. In
the absence of any particular instructions from the manufacturer, charging at c/10 for 12 to 16
hours will insure a complete charge.
The Nickel-Cadmium batteries can also be charged in the float mode, with a voltage of 1.4
V/cell (a 20 cell battery would be set to 28.0V).
NOTE: Prolonged use of the float (constant voltage) method on Nickel-Cadmium batteries will
result in cell imbalance, which could eventually lead to premature cell failure due to un-even
charge acceptance and un-even discharge capacity.
Page 60 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
13. DISCLAIMER
• The Supercharger is a precision system intended to be operated by personnel qualified in
the servicing of aircraft batteries.
• The end user must establish suitability in the intended application.
• JFM Engineering’s responsibility is limited to the repair/replacement of any malfunctioning
part of the system (not responsible for any losses incurred from the usage of the system).
• It is the user’s responsibility to verify the performance of the instruments and to operate
and maintain it in accordance with the above given instructions.
• It is the user’s responsibility to operate the Instrument within standard safety procedures
applicable to the operation of a Battery Test Facility.
• It is the user’s responsibility to install power receptacles and wiring in accordance with
local wiring codes.
Page 61 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Manual, Supercharger 60
R3.0
14. REVISION INDEX
Table 2 - Index of Revisions
NOTES
REVISION
DATE
1.0
2.0
2.1
21 January 2001
15 January 2003
23 July 2003
Release
New Clock-Timer Board and additional Peak function
Overvoltage is now set at 1.75V/cell (was 1.70). Numerous other text
updates (clarifications).
3.0
4 October 2007
Reformatted
Many text changes for clarification
Page 62 of 62
Download from Www.Somanuals.com. All Manuals Search And Download.
|