Powerware Power Supply 30 160kVA User Manual

315  
9
Maintenance Bypass  
Module  
30--160kVA  
Installation/Operation  
Manual  
164201177 Rev. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
For More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2
2
3
3
2 Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5
Preparing the Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Creating an Installation Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Preparing for Wiring the Maintenance Bypass Module . . . . . . . . . . . . .  
Inspecting and Unpacking the Maintenance Bypass Module . . . . . . . .  
Unloading the MBM from the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
6
6
6
6
7
9
3 Installing and Wiring the Maintenance Bypass Module . . . .  
11  
13  
Line and Load Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
4 Maintenance Bypass Module Operation . . . . . . . . . . . . . . . . . .  
15  
Preliminary Checks and Startup for UPS Equipped with  
Maintenance Bypass Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
15  
15  
16  
17  
17  
17  
19  
19  
19  
Maintenance Bypass Module Operation . . . . . . . . . . . . . . . . . . . . . . . . .  
MBM Operation Without Kirk Key Interlocks . . . . . . . . . . . . . . . . . . . . . .  
MBM Operation With Kirk Key Interlocks (Optional) . . . . . . . . . . . . . . . .  
Kirk Key Solenoid Release Unit (SKRU) . . . . . . . . . . . . . . . . . . . . . . . . . .  
MBM Transfer Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Short Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Maintenance Bypass Module Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . .  
Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A---1  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
List of Figures  
Figure 1. Typical 30---160kVA MBM with Isolation Transformer . . . . . . . .  
1
Figure 2. Front and Side View of Typical Maintenance Bypass  
Module on Shipping Pallet (30---160kVA w/XFMR) . . . . . . . . . .  
5
7
Figure 3. MBM as Shipped, with Outer Packaging and Pallet . . . . . . . . .  
Figure 4. Detail of Shipping Supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
10  
Figure 5. Top, Bottom, and Front View of Maintenance Bypass Module  
(30---160kVA w/XFMR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
11  
13  
Figure 6. Typical Power Wiring Terminations of UPS Module  
and Maintenance Bypass Module (30---160kVA) . . . . . . . . . . . .  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
iv  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
The Powerware 9315 Maintenance Bypass Module (MBM) is a  
floor-mounted, enclosed cabinet containing a UPS module, Maintenance  
Isolation circuit breaker (MIS), and a maintenance Bypass circuit breakr  
(MBP). An optional UPS Module Input Bypass circuit breaker (BIB) is available. The MBM  
can be either free-standing or line-up-and-match. Figure 1 shows a typical MBM cabinet  
with isolation transformer for a Powerware 9315 30---160kVA UPS and MBM cabinet  
without isolation transformer for a Powerware 9315 30---160kVA UPS.  
The equipment and devices described in this manual are provided for operation with the  
specific UPS Modules (model and rating) described in the appendix.  
BREAKER ANNUNCIATION  
UTILITY INPUT,  
IF BIB BREAKER  
IS NOT  
INSTALLED  
CRITICAL LOAD  
CONNECTIONS  
MBP  
UPS/PTC OUTPUT  
CONNECTION  
NEUTRAL  
CONNECTIONS  
MIS  
OPTIONAL UPS  
BYPASS  
INPUT CONNECTIONS  
BIB1  
UTILITY INPUT,  
IF BIB BREAKER  
INSTALLED  
BIB2  
Figure 1. Typical 30---160kVA MBM with or without Isolation Transformer.  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Using This Manual  
This manual contains installation and operation procedures for the MBM. Before  
installation and operation, read through each procedure.  
· Chapter 1 provides an overview of this manual and references for further  
information.  
· Chapter 2 tells you how to prepare your site for the installation of the MBM.  
It discusses equipment environmental requirements, inspecting, and unpacking  
cabinets.  
· Chapter 3 describes how to install the MBM cabinet.  
· Chapter 4 contains operating information for the MBM.  
· Appendix A contains important information for planning and installing the MBM,  
including wiring data and illustrations of cabinets.  
Conventions Used in This Manual  
This manual contains installation and operation procedures for the Maintenance  
Bypass module.  
· Bold type highlights important concepts in discussions, key terms in  
procedures, and menu options.  
· Italic type highlights notes, references to other system manuals, references  
to other sections of this manual, and new terms where they are defined.  
· Rectangular boxes containing bold type are warnings or cautions that pertain  
to the system or its electrical connections. This important information indicates  
possible dangers pertaining to personnel safety, equipment damage, critical  
load protection, or operational concerns.  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
2
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For More Information  
For more information on the installation and operation of the UPS system and its  
accessories, refer to the following:  
164200252  
Powerware9315 30---160 kVA UPS Operation  
Each manual describes the UPS cabinet, Control Panel, and  
Monitor Panel, and explains the functions of the UPS; discusses  
the standard features of the UPS and optional accessories;  
provides procedures for starting and stopping the UPS, and  
information about maintenance and responding to system events.  
These also describe the RS --- 485 and RS --- 232 serial  
communications capabilities of the UPS system; discuss the two  
communications ports on the Customer Interface Panel inside the  
UPS and how to connect optional remote accessories to your  
UPS system; and provide information about enabling, disabling,  
and customizing building alarms.  
164200253  
164200292  
Powerware9315 30---80 kVA UPS Installation  
Powerware9315 100---160 kVA UPS Installation  
Each manual contains the following information: how to prepare  
the site and plan for installation, detailed step-by-step procedures  
for installing each component of your system, how to join  
cabinets in a line-up-and-match system, detailed illustrations of  
cabinets and optional accessories, including dimensions and  
connection points.  
Contact the local Powerware Field Service office for information on how to obtain  
copies of these manuals.  
Getting Help  
If you have a question about any of the information in this manual, or if you have a  
question this manual does not answer, please call Powerware Field Service:  
United States  
Canada  
1-800-843-9433  
1-800-461-9166  
Outside the U.S.  
Call your local representative  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
This Page Intentionally Left Blank.  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
164201177 Rev. C 041500  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting Started  
This section describes how to install the Powerware 9315 Maintenance  
Bypass Module (MBM). It contains instructions for installing the MBM and  
basic site preparation procedures. Figure 2 shows the front and side view of the  
MBM with or without transformer for a Powerware 9315 30---160kVA module.  
The MBM is shipped as a separate item. Use a forklift or pallet jack to move the  
packaged cabinet to the installation site, or as close as possible to the site, before  
unloading.  
The basic sequence of the installation steps is:  
1. Prepare the site for the MBM installation.  
2. Inspect, unpack, and unload the MBM.  
3. Create an installation plan for wiring the MBM to the UPS system.  
4. Prepare for wiring.  
5. Complete the installation checklist from the PowerwareR 9315 Installation manual.  
6. Have authorized service personnel perform preliminary checks and startup.  
NOTE: Startup and operational checks should be performed only by authorized  
service personnel. This service is usually offered as part of the sales  
contract for your UPS system.  
Figure 2. Front and Side View of Typical Maintenance Bypass Module on  
Shipping Pallet (30---160kVA with or without XFMR)  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preparing the Site  
For the MBM to operate at peak efficiency, the installation site should meet the  
environmental parameters outlined in the PowerwareÒ 9315 Operation manual  
provided with the UPS system. The operating environment must meet the size and  
weight requirements supplied in the PowerwareÒ 9315 Installation manual provided  
with the UPS system. If the MBM is to be operated at an altitude higher than 1500  
meters (5000 feet), contact the local sales or service office for important information  
about high altitude operation.  
The basic environmental requirements for operation of the MBM are:  
Ambient Temperature Range  
Recommended Operating Range 20---25˚C (68---77˚F)  
Maximum Relative Humidity 95%  
0 --- 40˚C (32---104˚F)  
The MBM uses convection cooling to regulate internal component temperature. Air  
inlets are in the front of the cabinet, and outlets are in the top. Clearance in front of  
and above each cabinet for proper air circulation is essential.  
Creating an Installation Plan  
Before beginning to install the MBM, read and understand how this manual applies  
to the system being installed. It is important to note that UPS module installation  
procedures are contained in the PowerwareÒ 9315 Installation manual provided  
with the UPS system. It is recommended to first understand how to install the UPS  
modules. The information in Chapter 2 of this manual is a guide for installation of  
the MBM to the UPS modules.  
Environmental Considerations  
The life of the maintenance bypass module is adversely affected if the installation  
does not meet the following guidelines:  
1. The MBM must be installed on a sealed concrete pad or floor.  
2. The MBM must be installed in a dust-free environment.  
3. The MBM must be installed in a humidity-controlled environment.  
Preparing for Wiring the Maintenance Bypass Module  
See Tables A-1 through A-6 in Appendix A of this manual for wiring requirements.  
The power wiring for this equipment is rated at 90_C. If wire is run in an ambient  
temperature greater than 30_C, higher temperature rating and/or larger size wire  
may be necessary. Wiring should be installed through the bottom or top entry of  
the module. For UPS external wiring requirements, including minimum AWG size  
of external wiring, see the PowerwareÒ 9315 Installation manual provided with the  
UPS system.  
NOTE: Material and labor for external wiring are to be provided by designated  
personnel.  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
6
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inspecting and Unpacking the Maintenance Bypass Module  
The first task in preparing for installation of the MBM is inspecting and unpacking  
the unit. The MBM arrives covered with protective packaging material as shown in  
Figure 3.  
OUTER  
PACKAGING  
LAMINATED PLYWOOD  
AND POLYFOAM SKIDS  
Figure 3. MBM as Shipped, with Outer Packaging and Pallet  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Carefully inspect the outer packaging for evidence of damage during transit.  
CAUTION:  
Do not install a damaged MBM. Report any damage to the carrier and contact  
the local sales or service office immediately.  
2. Use a forklift or other material handling equipment to move the MBM to a  
convenient unpacking area. Insert the forklift jacks between the laminated  
plywood/polyfoam skids on the bottom of the unit.  
CAUTION:  
Do not tilt unit more than 10 degrees from vertical.  
3. Set the pallet on a firm, level surface, allowing a minimum clearance of  
4.6m (15 ft) on each side for removing the MBM from the pallet.  
4. Cut the steel bands around the MBM.  
5. Remove the protective cardboard covering from the MBM, cutting where  
indicated, using a knife blade no longer than 25 mm (1 in.).  
NOTE: Do not discard the packaging material. Instructions for unloading the MBM  
from the pallet are printed on the cardboard. Please to refer to them.  
6. Remove the plastic bag and foam packing material. Please discard or recycle  
them in a responsible manner.  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
8
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unloading the MBM from the Pallet  
The MBM pallet consists of four metal angle supports secured to plywood/polyfoam  
laminated skids. The skids act as shock absorbers for the MBM during shipment.  
WARNING:  
Unit is extremely heavy. If unloading instructions are not closely  
followed, the unit may tip and cause serious injury.  
Turning the jacking bolts unevenly may cause the unit to become  
unbalanced. To prevent tipping, raise and lower the jacking bolts  
evenly and sequentially. The unit should only be raised approximately  
3 mm (1/8 in.) above the floor (just enough to remove polyfoam skids).  
1. Remove the doors. Remove the retaining screw located inside each door at  
the bottom hinge pivot point, then lift off the door. Save the retaining screws  
for reinstallation of the doors.  
2. Locate the field kit packed inside the unit. Locate the four ½-in. jacking bolts  
and install them in the threaded holes in the front and rear supports. Place a  
floor protector underneath each jacking bolt, and screw the bolts down until  
they contact the floor protectors. The floor protectors prevent the floor from  
being damaged by the jacking bolts.  
WARNING:  
Module may fall. Do not loosen hardware attaching the side or front/rear  
shipping supports to the module base. Also, do not loosen the shipping  
supports from each other. The module must be lowered using jacking  
bolts before the shipping supports can be removed.  
3. Loosen, but do not remove the hardware holding the plywood/polyfoam skids  
to the front and rear supports (labeled “1” in Figure 4 --- 8 places).  
4. Turn each jacking bolt clockwise sequentially, no more than two full turns each,  
until the foam cushions clear the floor by approximately 3 mm (1/8 in.).  
5. After the plywood/polyfoam skids clear the floor, remove the hardware  
loosened in step 3. Pull the skids out from under the MBM. Discard or recycle  
them in a responsible manner.  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
DOOR  
REAR  
POLYFOAM  
SKID  
SUPPORT  
2
FRONT  
SIDE  
SUPPORT  
2
SUPPORT  
1
FLOOR  
PROTECTOR  
(4 PLACES)  
1
POLYFOAM  
SKID  
JACKING BOLT  
(USE FRONT AND REAR)  
1
Figure 4. Detail of Shipping Supports  
6. Carefully and evenly lower the MBM by turning each jacking bolt  
counterclockwise in sequence no more than two full turns each (maximum)  
until the supports contact the floor, and the module is no longer supported by  
the jacking bolts.  
7. When the module is resting on the floor, remove the jacking bolts. Discard or  
recycle them in a responsible manner.  
8. Remove the hardware labeled “2” in Figure 4, holding the front, rear and side  
supports to the module base (14 places). Discard or recycle the hardware and  
support brackets in a responsible manner.  
9. Install the doors removed in step 1. The MBM is now ready to be rolled to its  
final location.  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
10  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing and Wiring the  
Maintenance Bypass Module  
When the maintenance bypass module (MBM) has been moved to its installed  
location, unpacked, and inspected, it is ready for installation. This section  
discusses the typical process of installing the MBM in both the line-up and match  
and free-standing situations. The MBM is shown in Figure 5.  
Cooling Air Inlets  
(Front)  
Cable Entry, Top Plan View  
(Front)  
Cable Entry, Bottom Plan View  
Figure 5. Top, Bottom, and Front View of Maintenance Bypass Module  
(30---160kVA with or without XFMR)  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refer to the following while installing the MBM:  
· Dimensions in this manual are in millimeters and (inches).  
· Do not tilt the unit more than 10˚ during installation.  
· Remove the conduit landing plates to add conduit landing holes as required.  
Plate material is 16 gauge steel (0.06 in. thick).  
· Terminals are UL and CSA rated at 90˚C. A hex key tool is required to attach  
wires to the terminals.  
· Details about power wiring are provided in the tables of Appendix A of this  
manual.  
Figure 6 shows typical power wiring terminations of the UPS module and  
Maintenance Bypass Module (30---160kVA). Refer to the Powerware 9315  
Installation manual provided with the UPS system for location of UPS module  
cabinet wiring terminations.  
NOTE: Material and labor for external wiring are to be provided by designated  
personnel.  
BREAKER ANNUNCIATION  
RIGHT DOOR  
REMOVED  
FOR  
UTILITY INPUT,  
IF BIB BREAKER  
IS NOT  
CLARITY  
INSTALLED  
CRITICAL LOAD  
CONNECTIONS  
MBP  
MIS  
UPS/PTC OUTPUT  
CONNECTION  
LEFT DOOR  
NEUTRAL  
CONNECTIONS  
OPTIONAL UPS  
BYPASS  
INPUT CONNECTIONS  
A/C Output  
E9, E10, E11  
Output  
BIB1  
BIB2  
Neutral  
Connection  
(E12)  
UTILITY INPUT,  
IF BIB BREAKER  
INSTALLED  
TB1  
TB2  
UPS MODULE (30 -160kVA UPS Shown)  
Maintenance Bypass Module  
Figure 6. Typical Power Wiring Terminations of UPS Module and  
Maintenance Bypass Module (30---160kVA)  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
164201177 Rev. C 041500  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The recommended location, for the Maintenance Bypass Module, is as close to the  
installed UPS module as possible. Refer to the tables in Appendix A for wire rating  
and sizing information  
The MBM is packaged in a module similar to the UPS modules (same height,  
width, depth). The MBM is designed as a standard line-up-and-match accessory  
for the 30---160 KVA rated modules.  
Wiring harness assemblies for connecting the UPS module bypass input and  
output to the MBP are provided in separate shipping containers, if applicable. The  
wiring harness assemblies are passed through the 3-inch wiring feed-through hole  
located at the lower right side of the MBM cabinet, for connecting to the UPS input  
and output terminals. Refer to Appendix A for UPS module to MBM wiring terminal  
locations.  
Line up and match connection (cables sold separately by Powerware)  
· From the UPS to the MBM, the power cables are connected by mechanical  
pressure lugs.  
· From the UPS to the MBM, the control cables are connected to terminal blocks.  
Remote connection (cables, lugs, and hardware supplied by others)  
· All cables are terminated to MBM mechanical pressure lugs.  
Line and Load Wiring  
The Maintenance Bypass Module provides a means to manually transfer the Critical  
load from the UPS module via the UPS Module Bypass to a Maintenance Bypass  
Module as may be necessary for shutting down the UPS Module for maintenance  
or testing. The proper operation of the transfer is accomplished without interrupting  
the load power.  
The UPS Module Bypass AC Input and the Maintenance Bypass AC Input must be  
from the same or synchronized AC sources. The UPS Module Bypass Input is  
connected through the MBP cabinet via an optional Bypass Input Breaker (BIB), if  
installed. The Maintenance Bypass Breaker (MBP) is placed in the secondary of the  
stepdown transformer (480:208 VAC or 600:208 VAC) or connected directly to the  
Maintenance Bypass source if the Isolation Transformer is not required.  
UPS Module AC output connects through the MBM cabinet via isolation breaker  
MIS. Critical Load terminals are located on the load side of breakers MBP and MIS.  
The Critical Load may be transferred in a Make-Before-Break transfer sequence  
between the UPS Bypass Source and the Maintenance Bypass source after UPS  
output has been transferred from the UPS module and UPS bypass operating  
mode. The MBP must first be closed to prevent power interruption and MIS opened  
to provide UPS isolation from the Critical Load bus. Refer to the Transfer Sequence  
placard affixed to the front of the MBM cabinet.  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This Page Intentionally Left Blank.  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
164201177 Rev. C 041500  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Bypass Module Operation  
This chapter provides preliminary checks, maintenance operations and a  
schematic diagram of the maintenance bypass module.  
Preliminary Checks and Startup for UPS Equipped with  
Maintenance Bypass Module (MBM)  
Installation inspection and startup procedures must be performed only by a  
Powerware Corporation authorized service person. The procedure is normally part  
of the sales contract for the UPS system.  
WARNING:  
Attempts to startup the UPS system yourself may damage equipment and/or  
your critical load. Such attempts may also invalidate your system warranty.  
Maintenance Bypass Module Operation  
The MBM is provided for use with the Powerware 9315 (30---160kVA) UPS module.  
WARNING:  
Only persons familiar with the operation of this equipment should transfer loads.  
Failure to follow the transfer sequence exactly may cause loss of power to the  
critical load or may cause overload protection devices to function.  
Operator Note:  
MIS is to be OPENED only after MBP is CLOSED  
MBP is to be OPENED only after MIS is CLOSED  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MBM Operation Without Kirk Key Interlocks  
The following transfer sequence is the recommended procedure for the  
step-by-step load transfer from and back to the UPS when required. This  
information is provided on a label located on the deadfront panel behind  
the right front door of the MBM.  
From UPS Bypass to Maintenance Bypass:  
1. Confirm BIBs, if installed, are closed.  
2. Transfer UPS from Normal to Bypass mode (see UPS Operation manual).  
NOTE: For Parallel Redundant systems, transfer both UPS modules to  
Bypass mode.  
3. Close MBP breaker.  
CAUTION:  
Failure to close MBP breaker results in loss of power to the critical load.  
4. Open MIS breaker.  
5. Deenergize UPS before servicing unit (see UPS operation manual).  
CAUTION:  
For UPS electrical isolation, BIB breaker (if applicable) must be opened.  
From Maintenance Bypass to UPS Bypass:  
1. Confirm BIBs, if installed, are closed.  
2. Transfer UPS from Normal to Bypass mode (see UPS Operation manual).  
NOTE: For Parallel Redundant systems, transfer both UPS modules to  
Bypass mode.  
3. Close MIS breaker.  
CAUTION:  
Failure to close MIS breaker results in loss of power to the critical load.  
4. Open MBP breaker.  
5. To place UPS in Normal Mode, see UPS operation manual.  
NOTE: While the UPS is in Normal Mode and the MIS breaker is closed, the MBP  
breaker always trips OFF. Likewise, while the UPS is in Normal Mode and the  
MBP is closed, the MIS breaker always trips OFF.  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
16  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MBM Operation With Kirk Key Interlocks (Optional)  
The following transfer sequence is the recommended procedure for the  
step-by-step load transfer from and back to the UPS when required. This  
information is provided on a label located on the deadfront panel behind  
the right front door of the MBM.  
Kirk Key Solenoid Release Unit (SKRU)  
The 120 VAC operating power for the Kirk Key Solenoid Release Unit (SKRU) is  
derived from the Maintenance Bypass source.  
The Kirk Key SKRU is provided to prevent access to the key, which is necessary to  
initiate the transfer sequence. The operator must observe the instructions on the  
Transfer Sequence nameplate mounted on the MBP Panelboard.  
Electrical interlocks inhibit key release until UPS is in the Bypass mode.  
MBM Transfer Sequences  
From UPS Bypass to Maintenance Bypass:  
1. Confirm BIBs, if installed, are closed.  
2. Transfer UPS from Normal to Bypass mode (see UPS Operation manual).  
NOTE: For Parallel Redundant systems, transfer both UPS modules to  
Bypass mode.  
3. Depress pushbutton on the solenoid key release unit (SKRU). Turn and  
remove key A. Key A” may be removed when UPS system is in Bypass  
mode as indicated by illuminated pilot light.  
4. Insert key A” into MBP lock, retract bolt, close MBP breaker. Remove key “B”.  
CAUTION:  
Failure to close MBP breaker results in loss of power to the critical load.  
5. Insert key “B’ into MIS lock, open MIS breaker, extend bolt. Remove key A.  
6. Insert key A” into solenoid and turn key to LOCK position.  
7. Deenergize UPS before servicing (see UPS Operation manual).  
CAUTION:  
For UPS electrical isolation, BIB breaker (if applicable) must be opened.  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
From Maintenance Bypass to UPS Bypass:  
1. Confirm BIBs, if installed, are closed.  
2. Transfer UPS to Bypass mode (see UPS Operation manual).  
NOTE: For Parallel Redundant systems, transfer both UPS modules to  
Bypass mode.  
3. Depress pushbutton on the Solenoid Key Release Unit (SKRU). Turn and  
remove key A.  
4. Insert key A” into MIS lock, retract bolt, close MIS breaker. Remove key “B”.  
CAUTION:  
Failure to close MBP breaker results in loss of power to the critical load.  
5. Insert key “B” into MBP lock, open MBP breaker, extend bolt. Remove key A.  
6. Insert key A” into solenoid and turn key to LOCK position.  
7. See UPS Operation manual to place UPS in Normal mode.  
WARNING:  
Dangerous and potentially lethal voltages are present within the UPS enclosure.  
When maintenance or repair activities are to be performed, the UPS and the UPS  
Bypass power sources should be deenergized and verified with a meter before  
working in the required area.  
WARNING:  
UPS equipment has power feeds that are derived from two or more power  
sources.  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
18  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Maintenance should be scheduled on a periodic basis, recommended not to  
exceed one year. More frequent intervals are recommended if the equipment is  
subjected to highly repetitive operations.  
CAUTION:  
Refer to Section 9 -- Maintaining the UPS System of the Powerware 9315  
30--160kVA Operation manual, Powerware part number 164200252, before  
beginning maintenance or repairs on the UPS equipment.  
WARNING:  
Dangerous and life-threatening voltages are present when the UPS is  
operating. De-energize all equipment before physically touching potentially  
live parts.  
Periodic inspections of the maintenance bypass module should be made to  
determine if components, wiring, and connections exhibit evidence of overheating.  
Particular attention should be given to bolted connections. Maintenance  
procedures should specify that the bolted connections be retorqued to values  
listed on labels posted on the equipment.  
CAUTION:  
Overtightening of bolted connections containing compression washers  
decreases the washer’s ability to maintain compression during heating and  
cooling cycles.  
Refer to circuit breaker manufacturer’s application and maintenance literature for  
recommended maintenance practices and procedures.  
Short Circuits  
Short circuits are not considered normal phenomena in UPS applications. Tripping  
of protective devices due to low impedance short circuits should be thoroughly  
investigated for damage to conductors, insulation, and the protective devices in  
accordance with the manufacturer’s recommendations.  
Maintenance Bypass Module Diagrams  
See Appendix A for onelines and system configuration schematics  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This Page Intentionally Left Blank.  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
164201177 Rev. C 041500  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A --- Customer Information  
The information in this appendix will help you plan for and install your Maintenance Bypass  
Module cabinet. This appendix contains the following:  
· 164201177---1  
· 164201177---2  
· 164201177---3  
· 164201177---4  
Installation Notes  
Typical MBM Cabinet --- 30-160kVA with or without XFMR  
Typical UPS System with MBM  
Oneline --- 30-160kVA, Reverse Transfer (RT), 480:480VAC,  
600:600VAC, 400:400VAC  
· 164201177---5  
Oneline --- 30-160kVA, Reverse Transfer (RT), 480:208VAC,  
600:208VAC  
· 164201177---6  
Oneline --- 30-160kVA, Reverse Transfer (RT), 208:208VAC,  
· 164201177---7  
Oneline --- 30-160kVA, Parallel, 480:480VAC, 600:600VAC,  
400:400VAC  
· 164201177---8  
Oneline --- 30-160kVA, Parallel, 480:208VAC, 600:208VAC  
Oneline --- 30-160kVA, Parallel, 208:208VAC  
· 164201177---9  
· 164201177---10 UPS Module Line Up and Match 1 through 3  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A --- 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table A--1. Ratings & External Wiring Requirements for Powerware 9315  
M B M 3 0 --- 1 6 0 kVA, 480:208VAC/600:208VAC  
Rating and External Wiring Requirement  
Units  
Rating 60 Hz  
Basic unit rating at  
0.8 lagging PF load  
KVA  
KW  
160  
128  
130  
104  
100  
80  
80  
64  
UPS Input Voltage/Bypass Input  
VOLTS  
VOLTS  
480  
208  
600  
208  
480  
208  
600  
208  
408  
208  
600  
208  
480  
208  
600  
208  
UPS Output Voltage  
AC Input to Maintenance Bypass  
(3) Phases, (1) Ground  
AMPS  
192  
153  
156  
125  
120  
96  
96  
77  
A
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
1
(1)  
1
(1)  
AC Input to UPS Bypass  
(3) Phases, (1) Ground  
AMPS  
192  
153  
156  
125  
120  
96  
96  
77  
B
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
1
(1)  
1
(1)  
AC Output to Critical Load  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
444  
444  
361  
361  
278  
278  
222  
222  
C
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
400  
(2)  
400  
(2)  
400  
(2)  
400  
(2)  
400  
(2)  
400  
(2)  
300  
(1)  
300  
(1)  
UPS/PTC Output to MBM Cabinet (MIS)  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
444  
444  
361  
361  
278  
278  
222  
222  
D
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
400  
(2)  
400  
(2)  
400  
(2)  
400  
(2)  
400  
(2)  
400  
(2)  
300  
(1)  
300  
(1)  
Control Wiring to UPS  
VOLTS  
AMPS  
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
E
(2) Conductors  
Basic unit rating at  
0.8 lagging PF load  
KVA  
KW  
65  
52  
50  
40  
40  
32  
30  
24  
UPS Input Voltage/Bypass Input  
VOLTS  
VOLTS  
480  
208  
600  
208  
480  
208  
600  
208  
480  
208  
600  
208  
480  
208  
600  
208  
UPS Output Voltage  
AC Input to Maintenance Bypass  
(3) Phases, (1) Ground  
AMPS  
78  
63  
60  
48  
48  
38  
36  
29  
A
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
AC Input to UPS Bypass  
(3) Phases, (1) Ground  
AMPS  
78  
63  
60  
48  
48  
38  
36  
29  
B
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
AC Output to Critical Load  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
180  
180  
139  
139  
111  
111  
83  
83  
C
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
UPS/PTC Output to MBM Cabinet (MIS)  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
180  
180  
139  
139  
111  
111  
83  
83  
D
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
Control Wiring to UPS  
VOLTS  
AMPS  
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
E
(2) Conductors  
Note:  
Callout letters  
A, B, C, D,  
and  
E
map to drawing 164201177---5 (Reverse Transfer Connection) and  
164201177---8 (Parallel Connection). Read and understand the notes on drawings when planning your installation.  
DESCRIPTION:  
INSTALLATION NOTES  
DRAWING NO:  
SHEET:  
164201177---1  
1 of 4  
REVISION:  
DATE:  
C
041500  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 2  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table A--2. Ratings & External Wiring Requirements for Powereware 9315  
M B M 3 0 --- 1 6 0 kVA, 480:480VAC/600:600VAC  
Rating and External Wiring Requirement  
Units  
Rating 60 Hz  
Basic unit rating at  
0.8 lagging PF load  
KVA  
KW  
160  
128  
130  
104  
100  
80  
UPS Input Voltage/Bypass Input  
VOLTS  
VOLTS  
480  
480  
600  
600  
480  
480  
600  
600  
480  
480  
600  
600  
UPS Output Voltage  
AC Input to Maintenance Bypass  
(3) Phases, (1) Ground  
AMPS  
192  
153  
156  
125  
120  
96  
A
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
AC Input to UPS Bypass  
(3) Phases, (1) Ground  
AMPS  
192  
153  
156  
125  
120  
96  
B
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
AC Output to Critical Load  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
192  
153  
156  
125  
120  
96  
C
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
UPS/PTC Output to MBM Cabinet (MIS)  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
192  
153  
156  
125  
120  
96  
D
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
Control Wiring to UPS  
VOLTS  
AMPS  
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
E
(2) Conductors  
Basic unit rating at  
0.8 lagging PF load  
KVA  
KW  
80  
64  
65  
52  
50  
40  
40  
32  
30  
24  
UPS Input Voltage/Bypass Input  
VOLTS  
VOLTS  
480  
480  
480  
480  
480  
480  
480  
480  
480  
480  
UPS Output Voltage  
AC Input to Maintenance Bypass  
(3) Phases, (1) Ground  
AMPS  
96  
78  
60  
48  
36  
A
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
AC Input to UPS Bypass  
(3) Phases, (1) Ground  
AMPS  
96  
78  
60  
48  
36  
B
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
AC Output to Critical Load  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
96  
78  
60  
48  
36  
C
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
UPS/PTC Output to MBM Cabinet (MIS)  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
96  
78  
60  
48  
36  
D
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
1
(1)  
Control Wiring to UPS  
VOLTS  
AMPS  
120  
1
120  
1
120  
1
120  
1
120  
1
E
(2) Conductors  
Note:  
Callout letters  
A, B, C, D,  
and  
E
Map to drawing 164201177---4 (Reverse Transfer Connection) and  
164201177---7 (Parallel Connection). Read and understand the notes on drawings when planning your installation.  
DESCRIPTION:  
INSTALLATION NOTES  
DRAWING NO:  
SHEET:  
164201177---1  
2 of 4  
REVISION:  
DATE:  
C
041500  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A --- 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table A--3. Ratings & External Wiring Requirements for Powerware 9315  
M B M 3 0 --- 1 6 0 kVA, 208:208VAC  
Rating and External Wiring Requirement  
Units  
Rating 60 Hz  
Basic unit rating at  
0.8 lagging PF load  
KVA  
KW  
160 130 100  
80  
64  
65  
52  
50  
40  
40  
32  
30  
24  
128 104  
80  
UPS Input Voltage/Bypass Input  
VOLTS  
VOLTS  
208  
208  
208  
208  
208  
208  
208  
208  
208  
208  
208  
208  
208  
208  
208  
208  
UPS Output Voltage  
AC Input to Maintenance Bypass  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
444  
361  
278  
222  
180  
139  
111  
83  
A
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
400  
(2)  
400  
(2)  
400  
(2)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
AC Input to UPS Bypass  
(3) Phases, (1) Ground  
AMPS  
444  
361  
278  
222  
180  
139  
111  
83  
B
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
400  
(2)  
400  
(2)  
400  
(2)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
AC Output to Critical Load  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
444  
361  
278  
222  
180  
139  
111  
83  
C
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
400  
(2)  
400  
(2)  
400  
(2)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
UPS/PTC Output to MBM Cabinet (MIS)  
(3) Phases, (1) Neutral, (1) Ground  
AMPS  
444  
361  
278  
222  
180  
139  
111  
83  
D
Conductor Size  
Number per Phase  
AWG/MCM  
(each)  
400  
(2)  
400  
(2)  
400  
(2)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
Control Wiring to UPS  
VOLTS  
AMPS  
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
E
(2) Conductors  
Note:  
Callout letters  
A, B, C, D,  
and  
E
map to drawing 164201177---6 (Reverse Transfer Connection) and  
164201177---9 (Parallel Connection). Read and understand the notes on drawings when planning your installation.  
DESCRIPTION:  
INSTALLATION NOTES  
DRAWING NO:  
SHEET:  
164201177---1  
3 of 4  
REVISION:  
DATE:  
C
041500  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 4  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table A--4. Rating and External Wiring Requirements for Powerware 9315  
M B M 5 0 --- 1 6 0 KVA, 380:380VAC, 400:400VAC, 415:415VAC  
RATING AND EXTERNAL WIRING REQUIREMENT  
UNITS  
RATING 50/60 HZ  
BASIC UNIT RATING AT  
0.8 LAGGING PF LOAD  
KVA  
KW  
160  
128  
130  
104  
100  
80  
80  
64  
65  
52  
50  
40  
40  
32  
30  
24  
UPS INPUT VOLTAGE  
BYPASS INPUT/UPS OUTPUT VOLTAGE  
VOLTS  
VOLTS  
380/400/415  
380/400/415  
AC INPUT TO MAINTENANCE BYPASS  
(3) PHASES, (1) GROUND  
AMPS  
231  
188  
146  
115  
97  
74  
60  
45  
A
CONDUCTOR SIZE  
NUMBER PER PHASE  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
1
(1)  
1
(1)  
1
(1)  
AC INPUT TO UPS BYPASS  
(3) PHASES, (1) GROUND  
AMPS  
231  
188  
146  
115  
97  
74  
60  
45  
B
CONDUCTOR SIZE  
NUMBER PER PHASE  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
1
(1)  
1
(1)  
1
(1)  
AC OUTPUT TO CRITICAL LOAD  
(3) PHASES, (1) NEUTRAL, (1) GROUND  
AMPS  
231  
188  
146  
115  
97  
74  
60  
45  
C
CONDUCTOR SIZE  
NUMBER PER PHASE  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
1
(1)  
1
(1)  
1
(1)  
UPS/PTC OUTPUT TO MBM CABINET (MIS)  
(3) PHASE, (1) NEUTRAL, (1) GROUND  
AMPS  
231  
188  
146  
115  
97  
74  
60  
45  
D
CONDUCTOR SIZE  
NUMBER PER PHASE  
AWG/MCM  
(each)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
300  
(1)  
1
(1)  
1
(1)  
1
(1)  
CONTROL WIRING TO UPS  
(2) CONDUCTORS  
VOLTS  
AMPS  
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
120  
1
E
Note:  
Callout letters  
A, B, C, D,  
and  
E
map to drawing 164201177---4 (Reverse Transfer Connection) and  
164201177---7 (Parallel Connection). Read and understand the notes on drawings when planning your installation.  
DESCRIPTION:  
INSTALLATION NOTES  
DRAWING NO:  
SHEET:  
164201177---1  
4 of 4  
REVISION:  
DATE:  
C
041500  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A --- 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table B. Circuit Breaker Requirements for Powerware 9315  
M B M 3 0 --- 1 6 0 KVA, 380:380VAC, 400:400VAC, 415:415VAC, 600:600VAC,  
480:208VAC, 600:208VAC, 208:208VAC, 480:480VAC.  
BIB1 & BIB2  
MBP & MIS  
MBM  
FAMILY  
MBM  
Model No.  
V /V  
in out  
I /I  
in out  
Instantaneous  
Instantaneous  
Frame/Trip  
Frame/Trip  
Trip Range  
150---1200A  
150---1200A  
150---1200A  
375---3000A  
150---1200A  
150---1200A  
150---1200A  
150---1200A  
150---1200A  
150---1200A  
375---3000A  
150---1200A  
150---1200A  
150---1200A  
150---1200A  
150---1200A  
150---1200A  
375---3000A  
Trip Range  
375---3000A  
150---1200A  
375---3000A  
375---3000A  
150---1200A  
150---1200A  
150---1200A  
375---3000A  
150---1200A  
375---3000A  
375---3000A  
150---1200A  
150---1200A  
150---1200A  
375---3000A  
150---1200A  
375---3000A  
375---3000A  
MBM 50/30---48/20  
MBM 50/30---48/48  
MBM 50/30---60/20  
MBM 50/30---20/20  
MBM 50/30---38/38  
MBM 50/30---40/40  
MBM 50/30---41/41  
MBM 50/40---48/20  
MBM 50/40---48/48  
MBM 50/40---60/20  
MBM 50/40---20/20  
MBM 50/40---38/38  
MBM 50/40---40/40  
MBM 50/40---41/41  
MBM 50/50---48/20  
MBM 50/50---48/48  
MBM 50/50---60/20  
MBM 50/50---20/20  
480V/208V  
480V/480V  
600V/208V  
208V/208V  
380V/380V  
400V/400V  
410V/410V  
480V/208V  
480V/480V  
600V/208V  
208V/208V  
380V/380V  
400V/400V  
415V/415V  
480V/208V  
480V/480V  
600V/208V  
208V/208V  
36A/83A  
36A/36A  
29A/83A  
83A/83A  
45A/45A  
45A/45A  
45A/45A  
48A/111A  
48A/48A  
38A/111A  
111A/111A  
60A/60A  
60A/60A  
60A/60A  
60A/139A  
60A/60A  
48A/139A  
139A/139A  
100A/40A  
100A/40A  
100A/40A  
250A/100A  
100A/50A  
100A/50A  
100A/50A  
100A/50A  
100A/50A  
100A/40A  
250A/125A  
100A/70A  
100A/70A  
100A/70A  
100A/70A  
100A/70A  
100A/50A  
250A/150A  
250A/100A  
100A/40A  
250A/100A  
250A/100A  
100A/50A  
100A/50A  
100A/50A  
250A/125A  
100A/50A  
250A/125A  
250A/125A  
100A/70A  
100A/70A  
100A/70A  
250A/150A  
100A/70A  
250A/150A  
250A/150A  
MBM 50  
30KVA  
40KVA  
50KVA  
MBM 80/50---48/20  
MBM 80/50---48/48  
MBM 80/50---60/20  
MBM 80/50---38/38  
MBM 80/50---40/40  
MBM 80/50---41/41  
MBM 80/50---20/20  
MBM 80/65---48/20  
MBM 80/65---48/48  
MBM 80/65---60/20  
MBM 80/65---38/38  
MBM 80/65---40/40  
MBM 80/65---41/41  
MBM 80/65---20/20  
480V/208V  
480V/480V  
600V/208V  
380V/380V  
400V/400V  
415V/415V  
208V/208V  
480V/208V  
480V/480V  
600V/208V  
380V/380V  
400V/400V  
415V/415V  
208V/208V  
60A/139A  
60A/60A  
48A/139A  
74A/74A  
74A/74A  
74A/74A  
139A/139A  
78A/180A  
78A/78A  
63A/180A  
97A/97A  
97A/97A  
94A/94A  
180A/180A  
100A/70A  
100A/70A  
100A/50A  
100A/80A  
100A/80A  
100A/80A  
250A/150A  
100A/80A  
100A/80A  
100A/70A  
250A/100A  
250A/100A  
250A/100A  
250A/200A  
150---1200A  
150---1200A  
150---1200A  
150---1200A  
150---1200A  
150---1200A  
375---3000A  
150---1200A  
150---1200A  
150---1200A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
250A/150A  
100A/70A  
250A/150A  
100A/80A  
100A/80A  
100A/80A  
250A/150A  
250A/200A  
100A/80A  
250A/200A  
250A/100A  
250A/100A  
250A/100A  
250A/200A  
375---3000A  
150---1200A  
375---3000A  
150---1200A  
150---1200A  
150---1200A  
375---3000A  
375---3000A  
150---1200A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
MBM 80  
50KVA  
65KVA  
NOTE: See Sheet 2 For Model Number Legend.  
DESCRIPTION:  
DRAWING NO:  
REVISION:  
INSTALLATION NOTES  
SHEET:  
164201177---1  
1 of 2  
DATE:  
C
041500  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 6  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table B. Circuit Breaker Requirements for Powerware 9315  
M B M 3 0 --- 1 6 0 KVA, 380:380VAC, 400:400VAC, 415:415VAC, 600:600VAC,  
480:208VAC, 600:208VAC, 208:208VAC, 480:480VAC.  
BIB1 & BIB2  
MBP & MIS  
MBM  
FAMILY  
MBM  
Model No.  
V /V  
in out  
Ii /I  
n
out  
Instantaneous  
Instantaneous  
Frame/Trip  
Frame/Trip  
Trip Range  
Trip Range  
MBM 80/50---48/20  
MBM 80/80---48/20  
MBM 80/80---48/48  
MBM 80/80---60/20  
MBM 80/80---38/38  
MBM 80/80---40/40  
MBM 80/80---41/41  
MBM 80/80---20/20  
480V/208V  
480V/208V  
480V/480V  
600V/208V  
380V/380V  
400V/400V  
415V/415V  
208V/208V  
60A/139A  
96A/222A  
96A/96A  
100A/70A  
150---1200A  
150---1200A  
150---1200A  
150---1200A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
900---7200A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
900---7200A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
250A/150A  
250A/237A  
100A/100A  
250A/237A  
250A/125A  
250A/125A  
250A/125A  
250A/237A  
600A/300A  
250A/125A  
600A/300A  
250A/100A  
250A/150A  
250A/150A  
250A/150A  
600A/300A  
600A/420A  
250A/175A  
600A/420A  
250A/150A  
250A/200A  
250A/200A  
250A/200A  
600A/420A  
600A/480A  
250A/200A  
600A/480A  
250A/175A  
250A/237A  
250A/237A  
250A/237A  
600A/480A  
375---3000A  
375---3000A  
150---1200A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
900---7200A  
375---3000A  
900---7200A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
900---7200A  
900---7200A  
375---3000A  
900---7200A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
900---7200A  
900---7200A  
375---3000A  
900---7200A  
375---3000A  
375---3000A  
375---3000A  
375---3000A  
900---7200A  
MBM 80  
100A/100A  
100A/100A  
100A/80A  
77A/222A  
115A/115A  
115A/115A  
115A/115A  
222A/222A  
120A/278A  
120A/120A  
96A/278A  
96A/96A  
80KVA  
250A/125A  
250A/125A  
250A/125A  
250A/237A  
250A/125A  
250A/125A  
250A/100A  
250A/100A  
250A/150A  
250A/150A  
250A/150A  
600A/300A  
250A/175A  
250A/175A  
250A/150A  
250A/150A  
250A/200A  
250A/200A  
250A/200A  
600A/420A  
250A/200A  
250A/200A  
250A/175A  
250A/175A  
250A/237A  
250A/237A  
250A/237A  
600A/480A  
MBM 160  
MBM 160/100---48/20 480V/208V  
MBM 160/100---48/48 480V/480V  
MBM 160/100---60/20 600V/208V  
MBM 160/100---60/60 600V/600V  
MBM 160/100---38/38 380V/380V  
MBM 160/100---40/40 400V/400A  
MBM 160/100---41/41 415V/415V  
MBM 160/100---20/20 208V/208A  
MBM 160/130---48/20 480V/208V  
MBM 160/130---48/48 480V/480V  
MBM 160/130---60/20 600V/208V  
MBM 160/130---60/60 600V/600V  
MBM 160/130---38/38 380V/380V  
MBM 160/130---40/40 400V/400V  
MBM 160/130---41/41 415V/415V  
MBM 160/130---20/20 208V/208V  
MBM 160/160---48/20 480V/208V  
MBM 160/160---48/48 480V/480V  
MBM 160/160---60/20 600V/208V  
MBM 160/160---60/60 600V/600V  
MBM 160/160---38/38 380V/380V  
MBM 160/160---40/40 400V/400V  
MBM 160/160---41/41 415V/415V  
MBM 160/160---20/20 208V/208V  
100KVA  
130KVA  
160KVA  
146A/146A  
146A/146A  
146A/146A  
278A/278A  
156A/361A  
156A/156A  
125A/361A  
125A/125A  
188A/188A  
188A/188A  
188A/188A  
361A/361A  
192A/444A  
192A/192A  
153A/444A  
153A/153A  
231A/231A  
231A/231A  
231A/231A  
444A/444A  
NOTE: Model Number Legend  
1. MBM 50/30---20/20 means MBM cabinet,  
Family 50, 208V (input) and 208V (output),  
model 30 (30kVA).  
2. All breakers are 100% UL rated with  
Interrupting Capacity (IC) of 65kAIC@480VAC.  
DESCRIPTION:  
DRAWING NO:  
REVISION:  
INSTALLATION NOTES  
SHEET:  
164201177---1  
2 of 2  
DATE:  
C
041500  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A --- 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table C -- 1. Power Cable Terminations  
With Optional BIB  
Without Optional BIB  
Tightening  
Int.  
Hex  
Size  
(In.)  
Tightening  
Int.  
Hex  
Size  
(In.)  
Terminal  
Function  
Size of  
Presure  
Terminal  
Size of  
Presure  
Terminal  
Powerware 9315  
UPS Model in KVA  
(see note below)  
Terminal Function  
Torque  
N --- M  
( lb --- in )  
Torque  
N --- M  
( lb --- in )  
2 --- #6 - 3 5 0  
kcmil  
1 --- #6 - 3 5 0  
kcmil  
30---160KVA,  
38/38, 48/48, 60/60  
30---80KVA, 20/20  
31.1 (275)  
31.1 (275)  
56.5 (500)  
31.1 (275)  
3/8  
3/8  
1/2  
3/8  
31.1 (275)  
31.1 (275)  
3/8  
3/8  
(Note 2)  
(Note 3)  
2 --- #6 - 3 5 0  
kcmil  
(Note 2)  
2 --- #6 - 3 5 0  
kcmil  
(Note 2)  
E1,  
E2,  
E3  
Phase A,  
Phase B,  
Phase C  
30---160KVA,  
48/20, 60/20  
AC Input to  
MBM  
4 --- #2 - 6 0 0  
kcmil  
(Note 2)  
3 --- #3 / 0 - 4 0 0  
kcmil  
(Note 3)  
42.4 (375) 5/16  
100---160KVA, 20/20  
30---160KVA,  
38/38, 48/48, 60/60, 48/20, 60/20  
30---80KVA, 20/20  
1 --- #6 - 3 5 0  
kcmil  
AC Input to  
UPS Bypass  
(BIB breaker  
Load side)  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
B IB --- 2 ,  
BIB---4,  
B IB --- 6  
Phase A,  
Phase B,  
Phase C  
3 --- #3 / 0 - 4 0 0  
kcmil  
42.4 (375) 5/16  
100---160KVA, 20/20  
30---160KVA,  
38/38, 48/48, 60/60  
30---80KVA,  
1 --- #6 - 3 5 0  
kcmil  
1 --- #6 - 3 5 0  
kcmil  
UPS Output  
to MBM  
(MIS breaker  
Line side)  
311 (275)  
3/8  
311 (275)  
3/8  
MIS --- 1 ,  
MIS --- 3 ,  
MIS --- 5  
Phase A,  
Phase B,  
Phase C  
48/20, 60/20, 20/20  
3 --- #3 / 0 - 4 0 0  
kcmil  
3 --- #3 / 0 - 4 0 0  
kcmil  
100---160KVA,  
48/20, 60/20, 20/20  
42.4 (375) 5/16  
42.4 (375) 5/16  
30---160KVA,  
38/38, 48/48, 60/60  
30---80KVA,  
2 --- #6 - 3 5 0  
kcmil  
2 --- #6 - 3 5 0  
kcmil  
31.1 (275)  
3/8  
31.1 (275)  
3/8  
MBM Output  
to Critical  
Load  
E13,  
E14,  
E15  
Phase A,  
Phase B,  
Phase C  
48/20, 60/20, 20/20  
4 --- #2 - 6 0 0  
kcmil  
4 --- #2 - 6 0 0  
kcmil  
100---160KVA,  
48/20, 60/20, 20/20  
56.5 (500)  
56.5 (500)  
31.1 (275)  
1/2  
1/2  
3/8  
56.5 (500)  
56.5 (500)  
31.1 (275)  
1/2  
1/2  
3/8  
12---#2-500  
kcmil  
12---#2-500  
kcmil  
Neutral Lug  
E12  
Neutral  
Ground  
30---160KVA, all voltages  
30---160KVA, all voltages  
Customer  
Ground Lug  
2 --- #6 - 3 5 0  
kcmil  
2 --- #6 - 3 5 0  
kcmil  
Ground  
NOTES: Model Number Legend  
1. 38/38: 380VAC in---380VAC out; 48/48: 480VAC in---480VAC out; 60/60: 600VAC in---600VAC out  
48/20: 480VAC in---208VAC out; 60/20: 600VAC in---208VAC out; 20/20: 208VAC in---208VAC out  
2. AC input wiring is connected to input lugs E1---E3. Lugs are located on the right side of BIB breaker.  
3. A C inp ut w iring is connected directly to the line sid e of M BP b reaker (M BP --- 1, M BP --- 3, and M BP --- 5).  
4. AC input wiring is connected to input lugs E1---E3.  
DESCRIPTION:  
INSTALLATION NOTES  
DRAWING NO:  
SHEET:  
164201177---1  
1 of 2  
REVISION:  
DATE:  
C
041500  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 8  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table C--2. Control Wiring Requirements and Termination Requirement for  
Reverse Transfer (RT) System.  
Size of  
Pressure  
Termination  
(lb-in)  
Size of  
Pressure  
Termination  
(lb-in)  
Maximum  
Voltage and  
Current  
Connecting Point  
in MBM Cabinet  
Connection  
Point in UPS  
Recommended  
Wire Size  
Remarks  
TB1 --- 12  
TB1 --- 14  
TB6 --- 1  
TB6 --- 2  
#18---#8  
(55)  
#18---#8  
(55)  
120VAC  
1.0A  
See Fig 1.  
(Twisted Pair)  
#18---#14  
Table C--3. Control Wiring Requirements and Termination Requirement for  
Parallel Redundant System.  
Size of  
Pressure  
Termination  
(lb-in)  
Size of  
Pressure  
Termination  
(lb-in)  
Maximum  
Voltage and  
Current  
Connecting Point  
in MBM Cabinet  
Connection Point  
in UPS  
Recommended  
Wire Size  
Remarks  
TB1 --- 12  
TB1 --- 13  
TB1 --- 13  
TB1 --- 14  
TB6 --- 1 (UPS1)  
TB6 --- 1 (UPS2)  
TB6 --- 2 (UPS1)  
TB6 --- 2 (UPS2)  
#18---#8  
(55)  
#18---#8  
(55)  
120VAC  
1.0A  
See Fig 2.  
(Twisted Pair)  
#18---#14  
NOTES FOR TABLES C--2 AND C--3:  
· Install the copper wiring in a conduit separate from the power wiring.  
· Control wiring is NEC Class 1.  
· Control wiring from each UPS Module should be twisted.  
UPS  
UPS1  
UPS2  
K3  
K3  
K3  
TB6  
TB6  
BLK  
TB6  
BLK  
--- 1  
--- 2  
--- 1  
--- 2  
--- 1  
WHT  
--- 2  
BLK  
WHT  
WHT  
Twist Pair  
Twist Pair  
Twist Pair  
--- 12 --- 13 --- 14  
TB1  
--- 12 --- 13  
TB1  
--- 14  
MBM  
MBM  
Figure 2. (Parallel Redundant)  
Figure 1. (Reverse Transfer)  
DESCRIPTION:  
DRAWING NO:  
REVISION:  
INSTALLATION NOTES  
SHEET:  
164201177---1  
2 of 2  
DATE:  
C
041500  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A --- 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DESCRIPTION:  
TYPICAL MBM CABINET --  
30-160kVA with or without XFMR  
DRAWING NO:  
REVISION:  
SHEET:  
164201177---2  
1 of 3  
Dimensions are in millimeters (inches)  
DATE:  
A
080498  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 10  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BREAKER ANNUNCIATION  
UTILITY INPUT,  
IF BIB  
BREAKER IS  
NOT  
INSTALLED  
CRITICAL LOAD CONNECTIONS  
MBP  
MIS  
UPS/PTC OUTPUT  
CONNECTION  
NEUTRAL CONNECTIONS  
OPTIONAL UPS BYPASS  
INPUT CONNECTIONS  
BIB1  
BIB2  
UTILITY INPUT,  
IF BIB  
BREAKER  
INSTALLED  
DESCRIPTION:  
TYPICAL MBM CABINET --  
30-160kVA with or without XFMR  
INTERIOR COMPONENTS  
DRAWING NO:  
REVISION:  
SHEET:  
164201177---2  
2 of 3  
DATE:  
A
080498  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A---11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOP VIEW  
BOTTOM VIEW  
DESCRIPTION: TYPICAL MBM CABINET --  
30-160kVA with or without XFMR  
TOP and BOTTOM VIEW  
DRAWING NO:  
SHEET:  
164201177---2  
3 of 3  
Dimensions are in millimeters (inches)  
REVISION:  
DATE:  
A
080498  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 12  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDM CABINET  
(optional)  
MBM CABINET  
(optional)  
INPUT  
TRANSFORMER  
CABINET  
UPS  
BATTERY CABINET  
(optional)  
CABINET  
(optional)  
30---160kVA UPS System with MBM  
DESCRIPTION:  
TYPICAL UPS SYSTEM WITH MBM  
DRAWING NO:  
REVISION:  
SHEET:  
164201177---3  
1 of 1  
DATE:  
A
080498  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A---13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Read and understand the following notes while planning your installation:  
1. Refer to national and local electric codes for acceptable external wiring practices.  
2. Material and labor for external wiring requirements are to be provided by others.  
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column  
in Table A-2 and A-4. The power wiring for this equipment is rated at 90 degrees Celsius.  
4. The output of the UPS is not a separately derived source. Output neutral is not bonded to equipment ground through the main  
bonding jumper. Refer to NEC and local codes for proper grounding practices.  
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full  
load input current in Table A-2 and A-4.  
6. The Bypass three-phase feeds should be symmetrical about ground.  
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.  
8. Control wiring must be installed in separate conduit from the power wiring.  
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with  
an optional (extra cost) mechanical interlock if required.  
10. Refer to UPS Installation Manual for proper Bypass terminating lugs at UPS cabinet or input transformer cabinet.  
11. Refer to Table C-2 for control wiring connections.  
12. A Maintenance Bypass neutral feeder must be supplied when the MBM output neutral is used. If no Maintenance Bypass  
neutral is supplied, the MBM output neutral is not to be used. In neither case shall the MBM output neutral be bonded to ground.  
LEGEND  
MIS:  
MAINTENANCE ISOLATION BREAKER  
MAINTENANCE BYPASS BREAKER  
BYPASS INPUT BREAKER  
SOLENOID KEY RELEASE UNIT  
(MECHANICAL INTERLOCK)  
REVERSE TRANSFER  
MBP:  
BIB:  
DESCRIPTION:  
ONELINE -- 30-160kVA, RT, 480:480VAC,  
SKRU:  
600:600VAC, 400:400VAC  
DRAWING NO:  
REVISION:  
SHEET:  
RT:  
164201177---4  
1 of 1  
DATE:  
110100057 D3  
A
080498  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 14  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Read and understand the following notes while planning your installation:  
1. Refer to national and local electric codes for acceptable external wiring practices.  
2. Material and labor for external wiring requirements are to be provided by others.  
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A---1.  
The power wiring for this equipment is rated at 90 degrees Celsius.  
4. The output of the UPS is a separately derived source. Output neutral is bonded to equipment ground through the main  
bonding jumper. Refer to NEC and local codes for proper grounding practices.  
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full  
load input current in Table A---1.  
6. The Bypass three-phase feeds should be symmetrical about ground.  
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.  
8. Control wiring must be installed in separate conduit from the power wiring.  
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with  
an optional (extra cost) mechanical interlock if required.  
10. Refer to UPS Installation Manual for proper Bypass terminating lugs.  
11. Refer to Table C-2 for control wiring connections.  
LEGEND  
MIS:  
MAINTENANCE ISOLATION BREAKER  
MAINTENANCE BYPASS BREAKER  
BYPASS INPUT BREAKER  
SOLENOID KEY RELEASE UNIT  
(MECHANICAL INTERLOCK)  
REVERSE TRANSFER  
MBP:  
BIB:  
DESCRIPTION:  
ONELINE -- 30-160kVA, RT,  
480:208VAC, 600:208VAC  
SKRU:  
DRAWING NO:  
REVISION:  
SHEET:  
RT:  
164201177---5  
1 of 1  
DATE:  
110100056 D1  
A
080498  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A---15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Read and understand the following notes while planning your installation:  
1. Refer to national and local electric codes for acceptable external wiring practices.  
2. Material and labor for external wiring requirements are to be provided by others.  
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A---3.  
The power wiring for this equipment is rated at 90 degrees Celsius.  
4. The output of the UPS is not a separately derived source. Output neutral is not bonded to equipment ground through the main  
bonding jumper. Refer to NEC and local codes for proper grounding practices.  
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full  
load input current in Table A---3.  
6. The Bypass three-phase feeds should be symmetrical about ground.  
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.  
8. Control wiring must be installed in separate conduit from the power wiring.  
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with  
an optional (extra cost) mechanical interlock if required.  
10. Refer to UPS Installation Manual for proper bypass terminating lugs at UPS cabinet or at input transformer cabinet.  
11. Refer to Table C-2 for control wiring connections.  
LEGEND  
MIS:  
MAINTENANCE ISOLATION BREAKER  
MAINTENANCE BYPASS BREAKER  
BYPASS INPUT BREAKER  
SOLENOID KEY RELEASE UNIT  
(MECHANICAL INTERLOCK)  
REVERSE TRANSFER  
MBM:  
BIB:  
SKRU:  
DESCRIPTION: ONELINE -- 30-160kVA, RT, 208:208VAC  
DRAWING NO:  
SHEET:  
RT:  
164201177---6  
1 of 1  
REVISION:  
DATE:  
A
080498  
110100058 D2  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 16  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Read and understand the following notes while planning your installation:  
1. Refer to national and local electric codes for acceptable external wiring practices.  
2. Material and labor for external wiring requirements are to be provided by others.  
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A---2  
and A---4. The power wiring for this equipment is rated at 90 degrees Celsius.  
4. The output of the UPS is not a separately derived source. Output neutral is not bonded to equipment ground through the main  
bonding jumper. Refer to NEC and local codes for proper grounding practices.  
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full  
lo a d in p u t c u r r e n t i n Ta b le A --- 2 a n d A --- 4 .  
6. The Bypass three-phase feeds should be symmetrical about ground.  
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.  
8. Control wiring must be installed in separate conduit from the power wiring.  
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with  
an optional (extra cost) mechanical interlock if required.  
10. Refer to UPS Installation Manual for proper Bypass terminating lugs at UPS cabinet or input transformer cabinet.  
11. Refer to Table C---3 for control wiring connections.  
12. Refer to Parallel Redundant System Manual for details.  
13. A Maintenance Bypass neutral feeder must be supplied when the MBM output neutral is used. If no Maintenance Bypass  
neutral is supplied, the MBM output neutral is not to be used. In neither case shall the MBM output neutral be bonded to ground.  
LEGEND  
MIS:  
MAINTENANCE ISOLATION BREAKER  
MAINTENANCE BYPASS BREAKER  
BYPASS INPUT BREAKER  
MBM:  
BIB:  
DESCRIPTION:  
SKRU:  
SOLENOID KEY RELEASE UNIT  
(MECHANICAL INTERLOCK)  
PARALLEL TIE CABINET  
ONELINE -- 30-160kVA, PARALLEL, 480:480VAC  
600:600VAC, 400:400VAC  
164201177---7  
PTC:  
RT:  
DRAWING NO:  
REVISION:  
SHEET:  
REVERSE TRANSFER  
1 of 1  
DATE:  
110100069  
A
080498  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A---17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Read and understand the following notes while planning your installation:  
1. Refer to national and local electric codes for acceptable external wiring practices.  
2. Material and labor for external wiring requirements are to be provided by others.  
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A---1.  
The power wiring for this equipment is rated at 90 degrees Celsius.  
4. The output of the UPS is a separately derived source. Output neutral is bonded to equipment ground through the main  
bonding jumper. Refer to NEC and local codes for proper grounding practices.  
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full  
load input current in Table A---1.  
6
The Bypass three-phase feeds should be symmetrical about ground.  
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.  
8. Control wiring must be installed in separate conduit from the power wiring.  
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with  
an optional (extra cost) mechanical interlock if required.  
10. Refer to UPS Installation Manual for proper Bypass terminating lugs.  
11. Refer to Table C---3 for control wiring connections.  
12. Refer to Parallel Redundant System Manual for details.  
LEGEND  
MIS:  
MAINTENANCE ISOLATION BREAKER  
MAINTENANCE BYPASS BREAKER  
BYPASS INPUT BREAKER  
MBP:  
BIB:  
DESCRIPTION:  
SKRU:  
SOLENOID KEY RELEASE UNIT  
(MECHANICAL INTERLOCK)  
PARALLEL TIE CABINET  
ONELINE -- 30-160kVA, PARALLEL  
480:208VAC, 600:208VAC  
PTC:  
RT:  
DRAWING NO:  
SHEET:  
164201177---8  
REVERSE TRANSFER  
1 of 1  
REVISION:  
DATE:  
110100068  
A
080498  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 18  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Read and understand the following notes while planning your installation:  
1. Refer to national and local electric codes for acceptable external wiring practices.  
2. Material and labor for external wiring requirements are to be provided by others.  
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A---3.  
The power wiring for this equipment is rated at 90 degrees Celsius.  
4. The output of the UPS is not a separately derived source. Output neutral is not bonded to equipment ground through the main  
bonding jumper. Refer to NEC and local codes for proper grounding practices.  
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full  
load input current in Table A---3.  
6. The Bypass three-phase feeds should be symmetrical about ground.  
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.  
8. Control wiring must be installed in separate conduit from the power wiring.  
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with  
an optional (extra cost) mechanical interlock if required.  
10. Refer to UPS Installation Manual for proper Bypass terminating lugs at UPS cabinet or at input transformer cabinet.  
11. Refer to Table C---3 for control wiring connections.  
12. Refer to Parallel Redundant System Manual for details.  
LEGEND  
MIS:  
MAINTENANCE ISOLATION BREAKER  
MAINTENANCE BYPASS BREAKER  
BYPASS INPUT BREAKER  
MBM:  
BIB:  
DESCRIPTION:  
SKRU:  
SOLENOID KEY RELEASE UNIT  
(MECHANICAL INTERLOCK)  
PARALLEL TIE CABINET  
ONELINE -- 30-160kVA, PARALLEL, 208:208VAC  
PTC:  
RT:  
DRAWING NO:  
SHEET:  
164201177---9  
REVERSE TRANSFER  
1 of 1  
REVISION:  
DATE:  
110100072  
A
080498  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A---19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(NOTE 4)  
LINE UP AND MATCH ARRANGEMENT #1  
Applicable to POWERWARE 9315 30---160 kVA  
UPS modules only. 160kVA UPS is shown.  
DESCRIPTION:  
LINE UP AND MATCH ARRANGEMENT #1  
DRAWING NO:  
REVISION:  
SHEET:  
164201177---10  
1 of 4  
DATE:  
A
080498  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 20  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(NOTE 5)  
(NOTE 5)  
(NOTE 2)  
(NOTE 4)  
LINE UP AND MATCH ARRANGEMENT #2  
Applicable to POWERWARE 9315 30---160 kVA  
UPS modules only. 160kVA UPS is shown.  
DESCRIPTION:  
LINE UP AND MATCH ARRANGEMENT #2  
DRAWING NO:  
REVISION:  
SHEET:  
164201177---10  
2 of 4  
DATE:  
A
080498  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A---21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(NOTE 3)  
(NOTE 4)  
(NOTE 4)  
LINE UP AND MATCH ARRANGEMENT #3  
Applicable to POWERWARE 9315 30---160 kVA  
UPS modules only. 160kVA UPS is shown.  
DESCRIPTION:  
LINE UP AND MATCH ARRANGEMENT #3  
DRAWING NO:  
REVISION:  
SHEET:  
164201177---10  
3 of 4  
DATE:  
A
080498  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
A --- 22  
164201177 Rev. C 041500  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1 Line up and match power and control interconnection wiring from  
MBM to UPS/Input Transformer cabinet is applicable for Reverse  
Transfer (Single UPS module) connection only and sold separately  
by Powerware Corporation.  
2 Run power cables underneath the transformer.  
3 External wiring is required and supplied by others.  
4 The PDM cabinet is applicable IF AND ONLY IF the MBM and UPS  
module outputs are 3 phase, 60Hz, 280VAC.  
5 Refer to Powerware 9315 UPS module installation manual for  
proper terminating lugs.  
DESCRIPTION:  
LINE UP AND MATCH ARRANGMENT NOTES  
DRAWING NO:  
SHEET:  
164201177---10  
4 of 4  
REVISION:  
DATE:  
A
080498  
Powerware 9315 Maintenance Bypass Module 30---160kVA  
164201177 Rev. C 041500  
A---23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This Page Intentionally Left Blank.  
Powerware 9315 Maintenance Bypass Module 30-160kVA  
164201177 Rev. C 041500  
A --- 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Peavey Car Stereo System Max 700 User Manual
Peavey Music Mixer 880FX User Manual
Philips Baby Monitor SBC SC 477 User Manual
Philips Blu ray Player DMR BW750 User Manual
Philips Network Card SWR1231 10 User Manual
Philips Security Camera VCM8161 00T User Manual
Pioneer CD Player PDR 04 User Manual
Pioneer DVD Player DV 220V K User Manual
Pioneer DVR DVR 540H S User Manual
Profile Oven JTP18BABB User Manual