315
9
Maintenance Bypass
Module
30--160kVA
Installation/Operation
Manual
164201177 Rev. C
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
For More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
2
3
3
2 Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Preparing the Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating an Installation Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preparing for Wiring the Maintenance Bypass Module . . . . . . . . . . . . .
Inspecting and Unpacking the Maintenance Bypass Module . . . . . . . .
Unloading the MBM from the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
6
6
6
7
9
3 Installing and Wiring the Maintenance Bypass Module . . . .
11
13
Line and Load Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Maintenance Bypass Module Operation . . . . . . . . . . . . . . . . . .
15
Preliminary Checks and Startup for UPS Equipped with
Maintenance Bypass Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
15
16
17
17
17
19
19
19
Maintenance Bypass Module Operation . . . . . . . . . . . . . . . . . . . . . . . . .
MBM Operation Without Kirk Key Interlocks . . . . . . . . . . . . . . . . . . . . . .
MBM Operation With Kirk Key Interlocks (Optional) . . . . . . . . . . . . . . . .
Kirk Key Solenoid Release Unit (SKRU) . . . . . . . . . . . . . . . . . . . . . . . . . .
MBM Transfer Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Short Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance Bypass Module Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A---1
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
List of Figures
Figure 1. Typical 30---160kVA MBM with Isolation Transformer . . . . . . . .
1
Figure 2. Front and Side View of Typical Maintenance Bypass
Module on Shipping Pallet (30---160kVA w/XFMR) . . . . . . . . . .
5
7
Figure 3. MBM as Shipped, with Outer Packaging and Pallet . . . . . . . . .
Figure 4. Detail of Shipping Supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
Figure 5. Top, Bottom, and Front View of Maintenance Bypass Module
(30---160kVA w/XFMR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
13
Figure 6. Typical Power Wiring Terminations of UPS Module
and Maintenance Bypass Module (30---160kVA) . . . . . . . . . . . .
Powerware 9315 Maintenance Bypass Module 30-160kVA
iv
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
The Powerware 9315 Maintenance Bypass Module (MBM) is a
floor-mounted, enclosed cabinet containing a UPS module, Maintenance
Isolation circuit breaker (MIS), and a maintenance Bypass circuit breakr
(MBP). An optional UPS Module Input Bypass circuit breaker (BIB) is available. The MBM
can be either free-standing or line-up-and-match. Figure 1 shows a typical MBM cabinet
with isolation transformer for a Powerware 9315 30---160kVA UPS and MBM cabinet
without isolation transformer for a Powerware 9315 30---160kVA UPS.
The equipment and devices described in this manual are provided for operation with the
specific UPS Modules (model and rating) described in the appendix.
BREAKER ANNUNCIATION
UTILITY INPUT,
IF BIB BREAKER
IS NOT
INSTALLED
CRITICAL LOAD
CONNECTIONS
MBP
UPS/PTC OUTPUT
CONNECTION
NEUTRAL
CONNECTIONS
MIS
OPTIONAL UPS
BYPASS
INPUT CONNECTIONS
BIB1
UTILITY INPUT,
IF BIB BREAKER
INSTALLED
BIB2
Figure 1. Typical 30---160kVA MBM with or without Isolation Transformer.
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Using This Manual
This manual contains installation and operation procedures for the MBM. Before
installation and operation, read through each procedure.
· Chapter 1 provides an overview of this manual and references for further
information.
· Chapter 2 tells you how to prepare your site for the installation of the MBM.
It discusses equipment environmental requirements, inspecting, and unpacking
cabinets.
· Chapter 3 describes how to install the MBM cabinet.
· Chapter 4 contains operating information for the MBM.
· Appendix A contains important information for planning and installing the MBM,
including wiring data and illustrations of cabinets.
Conventions Used in This Manual
This manual contains installation and operation procedures for the Maintenance
Bypass module.
· Bold type highlights important concepts in discussions, key terms in
procedures, and menu options.
· Italic type highlights notes, references to other system manuals, references
to other sections of this manual, and new terms where they are defined.
· Rectangular boxes containing bold type are warnings or cautions that pertain
to the system or its electrical connections. This important information indicates
possible dangers pertaining to personnel safety, equipment damage, critical
load protection, or operational concerns.
Powerware 9315 Maintenance Bypass Module 30-160kVA
2
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
For More Information
For more information on the installation and operation of the UPS system and its
accessories, refer to the following:
164200252
Powerware 9315 30---160 kVA UPS Operation
Each manual describes the UPS cabinet, Control Panel, and
Monitor Panel, and explains the functions of the UPS; discusses
the standard features of the UPS and optional accessories;
provides procedures for starting and stopping the UPS, and
information about maintenance and responding to system events.
These also describe the RS --- 485 and RS --- 232 serial
communications capabilities of the UPS system; discuss the two
communications ports on the Customer Interface Panel inside the
UPS and how to connect optional remote accessories to your
UPS system; and provide information about enabling, disabling,
and customizing building alarms.
164200253
164200292
Powerware 9315 30---80 kVA UPS Installation
Powerware 9315 100---160 kVA UPS Installation
Each manual contains the following information: how to prepare
the site and plan for installation, detailed step-by-step procedures
for installing each component of your system, how to join
cabinets in a line-up-and-match system, detailed illustrations of
cabinets and optional accessories, including dimensions and
connection points.
Contact the local Powerware Field Service office for information on how to obtain
copies of these manuals.
Getting Help
If you have a question about any of the information in this manual, or if you have a
question this manual does not answer, please call Powerware Field Service:
United States
Canada
1-800-843-9433
1-800-461-9166
Outside the U.S.
Call your local representative
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
3
Download from Www.Somanuals.com. All Manuals Search And Download.
This Page Intentionally Left Blank.
Powerware 9315 Maintenance Bypass Module 30-160kVA
164201177 Rev. C 041500
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Getting Started
This section describes how to install the Powerware 9315 Maintenance
Bypass Module (MBM). It contains instructions for installing the MBM and
basic site preparation procedures. Figure 2 shows the front and side view of the
MBM with or without transformer for a Powerware 9315 30---160kVA module.
The MBM is shipped as a separate item. Use a forklift or pallet jack to move the
packaged cabinet to the installation site, or as close as possible to the site, before
unloading.
The basic sequence of the installation steps is:
1. Prepare the site for the MBM installation.
2. Inspect, unpack, and unload the MBM.
3. Create an installation plan for wiring the MBM to the UPS system.
4. Prepare for wiring.
5. Complete the installation checklist from the PowerwareR 9315 Installation manual.
6. Have authorized service personnel perform preliminary checks and startup.
NOTE: Startup and operational checks should be performed only by authorized
service personnel. This service is usually offered as part of the sales
contract for your UPS system.
Figure 2. Front and Side View of Typical Maintenance Bypass Module on
Shipping Pallet (30---160kVA with or without XFMR)
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Preparing the Site
For the MBM to operate at peak efficiency, the installation site should meet the
environmental parameters outlined in the PowerwareÒ 9315 Operation manual
provided with the UPS system. The operating environment must meet the size and
weight requirements supplied in the PowerwareÒ 9315 Installation manual provided
with the UPS system. If the MBM is to be operated at an altitude higher than 1500
meters (5000 feet), contact the local sales or service office for important information
about high altitude operation.
The basic environmental requirements for operation of the MBM are:
Ambient Temperature Range
Recommended Operating Range 20---25˚C (68---77˚F)
Maximum Relative Humidity 95%
0 --- 40˚C (32---104˚F)
The MBM uses convection cooling to regulate internal component temperature. Air
inlets are in the front of the cabinet, and outlets are in the top. Clearance in front of
and above each cabinet for proper air circulation is essential.
Creating an Installation Plan
Before beginning to install the MBM, read and understand how this manual applies
to the system being installed. It is important to note that UPS module installation
procedures are contained in the PowerwareÒ 9315 Installation manual provided
with the UPS system. It is recommended to first understand how to install the UPS
modules. The information in Chapter 2 of this manual is a guide for installation of
the MBM to the UPS modules.
Environmental Considerations
The life of the maintenance bypass module is adversely affected if the installation
does not meet the following guidelines:
1. The MBM must be installed on a sealed concrete pad or floor.
2. The MBM must be installed in a dust-free environment.
3. The MBM must be installed in a humidity-controlled environment.
Preparing for Wiring the Maintenance Bypass Module
See Tables A-1 through A-6 in Appendix A of this manual for wiring requirements.
The power wiring for this equipment is rated at 90_C. If wire is run in an ambient
temperature greater than 30_C, higher temperature rating and/or larger size wire
may be necessary. Wiring should be installed through the bottom or top entry of
the module. For UPS external wiring requirements, including minimum AWG size
of external wiring, see the PowerwareÒ 9315 Installation manual provided with the
UPS system.
NOTE: Material and labor for external wiring are to be provided by designated
personnel.
Powerware 9315 Maintenance Bypass Module 30-160kVA
6
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Inspecting and Unpacking the Maintenance Bypass Module
The first task in preparing for installation of the MBM is inspecting and unpacking
the unit. The MBM arrives covered with protective packaging material as shown in
Figure 3.
OUTER
PACKAGING
LAMINATED PLYWOOD
AND POLYFOAM SKIDS
Figure 3. MBM as Shipped, with Outer Packaging and Pallet
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
7
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION:
Do not install a damaged MBM. Report any damage to the carrier and contact
the local sales or service office immediately.
2. Use a forklift or other material handling equipment to move the MBM to a
convenient unpacking area. Insert the forklift jacks between the laminated
plywood/polyfoam skids on the bottom of the unit.
CAUTION:
Do not tilt unit more than 10 degrees from vertical.
3. Set the pallet on a firm, level surface, allowing a minimum clearance of
4.6m (15 ft) on each side for removing the MBM from the pallet.
4. Cut the steel bands around the MBM.
5. Remove the protective cardboard covering from the MBM, cutting where
indicated, using a knife blade no longer than 25 mm (1 in.).
NOTE: Do not discard the packaging material. Instructions for unloading the MBM
from the pallet are printed on the cardboard. Please to refer to them.
6. Remove the plastic bag and foam packing material. Please discard or recycle
them in a responsible manner.
Powerware 9315 Maintenance Bypass Module 30-160kVA
8
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Unloading the MBM from the Pallet
The MBM pallet consists of four metal angle supports secured to plywood/polyfoam
laminated skids. The skids act as shock absorbers for the MBM during shipment.
WARNING:
Unit is extremely heavy. If unloading instructions are not closely
followed, the unit may tip and cause serious injury.
Turning the jacking bolts unevenly may cause the unit to become
unbalanced. To prevent tipping, raise and lower the jacking bolts
evenly and sequentially. The unit should only be raised approximately
3 mm (1/8 in.) above the floor (just enough to remove polyfoam skids).
1. Remove the doors. Remove the retaining screw located inside each door at
the bottom hinge pivot point, then lift off the door. Save the retaining screws
for reinstallation of the doors.
2. Locate the field kit packed inside the unit. Locate the four ½-in. jacking bolts
and install them in the threaded holes in the front and rear supports. Place a
floor protector underneath each jacking bolt, and screw the bolts down until
they contact the floor protectors. The floor protectors prevent the floor from
being damaged by the jacking bolts.
WARNING:
Module may fall. Do not loosen hardware attaching the side or front/rear
shipping supports to the module base. Also, do not loosen the shipping
supports from each other. The module must be lowered using jacking
bolts before the shipping supports can be removed.
3. Loosen, but do not remove the hardware holding the plywood/polyfoam skids
to the front and rear supports (labeled “1” in Figure 4 --- 8 places).
4. Turn each jacking bolt clockwise sequentially, no more than two full turns each,
until the foam cushions clear the floor by approximately 3 mm (1/8 in.).
5. After the plywood/polyfoam skids clear the floor, remove the hardware
loosened in step 3. Pull the skids out from under the MBM. Discard or recycle
them in a responsible manner.
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
9
Download from Www.Somanuals.com. All Manuals Search And Download.
DOOR
REAR
POLYFOAM
SKID
SUPPORT
2
FRONT
SIDE
SUPPORT
2
SUPPORT
1
FLOOR
PROTECTOR
(4 PLACES)
1
POLYFOAM
SKID
JACKING BOLT
(USE FRONT AND REAR)
1
Figure 4. Detail of Shipping Supports
6. Carefully and evenly lower the MBM by turning each jacking bolt
counterclockwise in sequence no more than two full turns each (maximum)
until the supports contact the floor, and the module is no longer supported by
the jacking bolts.
7. When the module is resting on the floor, remove the jacking bolts. Discard or
recycle them in a responsible manner.
8. Remove the hardware labeled “2” in Figure 4, holding the front, rear and side
supports to the module base (14 places). Discard or recycle the hardware and
support brackets in a responsible manner.
9. Install the doors removed in step 1. The MBM is now ready to be rolled to its
final location.
Powerware 9315 Maintenance Bypass Module 30-160kVA
10
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing and Wiring the
Maintenance Bypass Module
When the maintenance bypass module (MBM) has been moved to its installed
location, unpacked, and inspected, it is ready for installation. This section
discusses the typical process of installing the MBM in both the line-up and match
and free-standing situations. The MBM is shown in Figure 5.
Cooling Air Inlets
(Front)
Cable Entry, Top Plan View
(Front)
Cable Entry, Bottom Plan View
Figure 5. Top, Bottom, and Front View of Maintenance Bypass Module
(30---160kVA with or without XFMR)
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Refer to the following while installing the MBM:
· Dimensions in this manual are in millimeters and (inches).
· Do not tilt the unit more than 10˚ during installation.
· Remove the conduit landing plates to add conduit landing holes as required.
Plate material is 16 gauge steel (0.06 in. thick).
· Terminals are UL and CSA rated at 90˚C. A hex key tool is required to attach
wires to the terminals.
· Details about power wiring are provided in the tables of Appendix A of this
manual.
Figure 6 shows typical power wiring terminations of the UPS module and
Maintenance Bypass Module (30---160kVA). Refer to the Powerware 9315
Installation manual provided with the UPS system for location of UPS module
cabinet wiring terminations.
NOTE: Material and labor for external wiring are to be provided by designated
personnel.
BREAKER ANNUNCIATION
RIGHT DOOR
REMOVED
FOR
UTILITY INPUT,
IF BIB BREAKER
IS NOT
CLARITY
INSTALLED
CRITICAL LOAD
CONNECTIONS
MBP
MIS
UPS/PTC OUTPUT
CONNECTION
LEFT DOOR
NEUTRAL
CONNECTIONS
OPTIONAL UPS
BYPASS
INPUT CONNECTIONS
A/C Output
E9, E10, E11
Output
BIB1
BIB2
Neutral
Connection
(E12)
UTILITY INPUT,
IF BIB BREAKER
INSTALLED
TB1
TB2
UPS MODULE (30 -160kVA UPS Shown)
Maintenance Bypass Module
Figure 6. Typical Power Wiring Terminations of UPS Module and
Maintenance Bypass Module (30---160kVA)
Powerware 9315 Maintenance Bypass Module 30-160kVA
164201177 Rev. C 041500
12
Download from Www.Somanuals.com. All Manuals Search And Download.
The recommended location, for the Maintenance Bypass Module, is as close to the
installed UPS module as possible. Refer to the tables in Appendix A for wire rating
and sizing information
The MBM is packaged in a module similar to the UPS modules (same height,
width, depth). The MBM is designed as a standard line-up-and-match accessory
for the 30---160 KVA rated modules.
Wiring harness assemblies for connecting the UPS module bypass input and
output to the MBP are provided in separate shipping containers, if applicable. The
wiring harness assemblies are passed through the 3-inch wiring feed-through hole
located at the lower right side of the MBM cabinet, for connecting to the UPS input
and output terminals. Refer to Appendix A for UPS module to MBM wiring terminal
locations.
Line up and match connection (cables sold separately by Powerware)
· From the UPS to the MBM, the power cables are connected by mechanical
pressure lugs.
· From the UPS to the MBM, the control cables are connected to terminal blocks.
Remote connection (cables, lugs, and hardware supplied by others)
· All cables are terminated to MBM mechanical pressure lugs.
Line and Load Wiring
The Maintenance Bypass Module provides a means to manually transfer the Critical
load from the UPS module via the UPS Module Bypass to a Maintenance Bypass
Module as may be necessary for shutting down the UPS Module for maintenance
or testing. The proper operation of the transfer is accomplished without interrupting
the load power.
The UPS Module Bypass AC Input and the Maintenance Bypass AC Input must be
from the same or synchronized AC sources. The UPS Module Bypass Input is
connected through the MBP cabinet via an optional Bypass Input Breaker (BIB), if
installed. The Maintenance Bypass Breaker (MBP) is placed in the secondary of the
stepdown transformer (480:208 VAC or 600:208 VAC) or connected directly to the
Maintenance Bypass source if the Isolation Transformer is not required.
UPS Module AC output connects through the MBM cabinet via isolation breaker
MIS. Critical Load terminals are located on the load side of breakers MBP and MIS.
The Critical Load may be transferred in a Make-Before-Break transfer sequence
between the UPS Bypass Source and the Maintenance Bypass source after UPS
output has been transferred from the UPS module and UPS bypass operating
mode. The MBP must first be closed to prevent power interruption and MIS opened
to provide UPS isolation from the Critical Load bus. Refer to the Transfer Sequence
placard affixed to the front of the MBM cabinet.
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
13
Download from Www.Somanuals.com. All Manuals Search And Download.
This Page Intentionally Left Blank.
Powerware 9315 Maintenance Bypass Module 30-160kVA
164201177 Rev. C 041500
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance Bypass Module Operation
This chapter provides preliminary checks, maintenance operations and a
schematic diagram of the maintenance bypass module.
Preliminary Checks and Startup for UPS Equipped with
Maintenance Bypass Module (MBM)
Installation inspection and startup procedures must be performed only by a
Powerware Corporation authorized service person. The procedure is normally part
of the sales contract for the UPS system.
WARNING:
Attempts to startup the UPS system yourself may damage equipment and/or
your critical load. Such attempts may also invalidate your system warranty.
Maintenance Bypass Module Operation
The MBM is provided for use with the Powerware 9315 (30---160kVA) UPS module.
WARNING:
Only persons familiar with the operation of this equipment should transfer loads.
Failure to follow the transfer sequence exactly may cause loss of power to the
critical load or may cause overload protection devices to function.
Operator Note:
MIS is to be OPENED only after MBP is CLOSED
MBP is to be OPENED only after MIS is CLOSED
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
15
Download from Www.Somanuals.com. All Manuals Search And Download.
MBM Operation Without Kirk Key Interlocks
The following transfer sequence is the recommended procedure for the
step-by-step load transfer from and back to the UPS when required. This
information is provided on a label located on the deadfront panel behind
the right front door of the MBM.
From UPS Bypass to Maintenance Bypass:
1. Confirm BIBs, if installed, are closed.
2. Transfer UPS from Normal to Bypass mode (see UPS Operation manual).
NOTE: For Parallel Redundant systems, transfer both UPS modules to
Bypass mode.
3. Close MBP breaker.
CAUTION:
Failure to close MBP breaker results in loss of power to the critical load.
4. Open MIS breaker.
5. Deenergize UPS before servicing unit (see UPS operation manual).
CAUTION:
For UPS electrical isolation, BIB breaker (if applicable) must be opened.
From Maintenance Bypass to UPS Bypass:
1. Confirm BIBs, if installed, are closed.
2. Transfer UPS from Normal to Bypass mode (see UPS Operation manual).
NOTE: For Parallel Redundant systems, transfer both UPS modules to
Bypass mode.
3. Close MIS breaker.
CAUTION:
Failure to close MIS breaker results in loss of power to the critical load.
4. Open MBP breaker.
5. To place UPS in Normal Mode, see UPS operation manual.
NOTE: While the UPS is in Normal Mode and the MIS breaker is closed, the MBP
breaker always trips OFF. Likewise, while the UPS is in Normal Mode and the
MBP is closed, the MIS breaker always trips OFF.
Powerware 9315 Maintenance Bypass Module 30-160kVA
16
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
MBM Operation With Kirk Key Interlocks (Optional)
The following transfer sequence is the recommended procedure for the
step-by-step load transfer from and back to the UPS when required. This
information is provided on a label located on the deadfront panel behind
the right front door of the MBM.
Kirk Key Solenoid Release Unit (SKRU)
The 120 VAC operating power for the Kirk Key Solenoid Release Unit (SKRU) is
derived from the Maintenance Bypass source.
The Kirk Key SKRU is provided to prevent access to the key, which is necessary to
initiate the transfer sequence. The operator must observe the instructions on the
Transfer Sequence nameplate mounted on the MBP Panelboard.
Electrical interlocks inhibit key release until UPS is in the Bypass mode.
MBM Transfer Sequences
From UPS Bypass to Maintenance Bypass:
1. Confirm BIBs, if installed, are closed.
2. Transfer UPS from Normal to Bypass mode (see UPS Operation manual).
NOTE: For Parallel Redundant systems, transfer both UPS modules to
Bypass mode.
3. Depress pushbutton on the solenoid key release unit (SKRU). Turn and
remove key “A”. Key “A” may be removed when UPS system is in Bypass
mode as indicated by illuminated pilot light.
4. Insert key “A” into MBP lock, retract bolt, close MBP breaker. Remove key “B”.
CAUTION:
Failure to close MBP breaker results in loss of power to the critical load.
5. Insert key “B’ into MIS lock, open MIS breaker, extend bolt. Remove key “A”.
6. Insert key “A” into solenoid and turn key to LOCK position.
7. Deenergize UPS before servicing (see UPS Operation manual).
CAUTION:
For UPS electrical isolation, BIB breaker (if applicable) must be opened.
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
17
Download from Www.Somanuals.com. All Manuals Search And Download.
From Maintenance Bypass to UPS Bypass:
1. Confirm BIBs, if installed, are closed.
2. Transfer UPS to Bypass mode (see UPS Operation manual).
NOTE: For Parallel Redundant systems, transfer both UPS modules to
Bypass mode.
3. Depress pushbutton on the Solenoid Key Release Unit (SKRU). Turn and
remove key “A”.
4. Insert key “A” into MIS lock, retract bolt, close MIS breaker. Remove key “B”.
CAUTION:
Failure to close MBP breaker results in loss of power to the critical load.
5. Insert key “B” into MBP lock, open MBP breaker, extend bolt. Remove key “A”.
6. Insert key “A” into solenoid and turn key to LOCK position.
7. See UPS Operation manual to place UPS in Normal mode.
WARNING:
Dangerous and potentially lethal voltages are present within the UPS enclosure.
When maintenance or repair activities are to be performed, the UPS and the UPS
Bypass power sources should be deenergized and verified with a meter before
working in the required area.
WARNING:
UPS equipment has power feeds that are derived from two or more power
sources.
Powerware 9315 Maintenance Bypass Module 30-160kVA
18
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Maintenance should be scheduled on a periodic basis, recommended not to
exceed one year. More frequent intervals are recommended if the equipment is
subjected to highly repetitive operations.
CAUTION:
Refer to Section 9 -- Maintaining the UPS System of the Powerware 9315
30--160kVA Operation manual, Powerware part number 164200252, before
beginning maintenance or repairs on the UPS equipment.
WARNING:
Dangerous and life-threatening voltages are present when the UPS is
operating. De-energize all equipment before physically touching potentially
live parts.
Periodic inspections of the maintenance bypass module should be made to
determine if components, wiring, and connections exhibit evidence of overheating.
Particular attention should be given to bolted connections. Maintenance
procedures should specify that the bolted connections be retorqued to values
listed on labels posted on the equipment.
CAUTION:
Overtightening of bolted connections containing compression washers
decreases the washer’s ability to maintain compression during heating and
cooling cycles.
Refer to circuit breaker manufacturer’s application and maintenance literature for
recommended maintenance practices and procedures.
Short Circuits
Short circuits are not considered normal phenomena in UPS applications. Tripping
of protective devices due to low impedance short circuits should be thoroughly
investigated for damage to conductors, insulation, and the protective devices in
accordance with the manufacturer’s recommendations.
Maintenance Bypass Module Diagrams
See Appendix A for onelines and system configuration schematics
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
19
Download from Www.Somanuals.com. All Manuals Search And Download.
This Page Intentionally Left Blank.
Powerware 9315 Maintenance Bypass Module 30-160kVA
164201177 Rev. C 041500
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix A --- Customer Information
The information in this appendix will help you plan for and install your Maintenance Bypass
Module cabinet. This appendix contains the following:
· 164201177---1
· 164201177---2
· 164201177---3
· 164201177---4
Installation Notes
Typical MBM Cabinet --- 30-160kVA with or without XFMR
Typical UPS System with MBM
Oneline --- 30-160kVA, Reverse Transfer (RT), 480:480VAC,
600:600VAC, 400:400VAC
· 164201177---5
Oneline --- 30-160kVA, Reverse Transfer (RT), 480:208VAC,
600:208VAC
· 164201177---6
Oneline --- 30-160kVA, Reverse Transfer (RT), 208:208VAC,
· 164201177---7
Oneline --- 30-160kVA, Parallel, 480:480VAC, 600:600VAC,
400:400VAC
· 164201177---8
Oneline --- 30-160kVA, Parallel, 480:208VAC, 600:208VAC
Oneline --- 30-160kVA, Parallel, 208:208VAC
· 164201177---9
· 164201177---10 UPS Module Line Up and Match 1 through 3
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A --- 1
Download from Www.Somanuals.com. All Manuals Search And Download.
Table A--1. Ratings & External Wiring Requirements for Powerware 9315
M B M 3 0 --- 1 6 0 kVA, 480:208VAC/600:208VAC
Rating and External Wiring Requirement
Units
Rating 60 Hz
Basic unit rating at
0.8 lagging PF load
KVA
KW
160
128
130
104
100
80
80
64
UPS Input Voltage/Bypass Input
VOLTS
VOLTS
480
208
600
208
480
208
600
208
408
208
600
208
480
208
600
208
UPS Output Voltage
AC Input to Maintenance Bypass
(3) Phases, (1) Ground
AMPS
192
153
156
125
120
96
96
77
A
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
AC Input to UPS Bypass
(3) Phases, (1) Ground
AMPS
192
153
156
125
120
96
96
77
B
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
AC Output to Critical Load
(3) Phases, (1) Neutral, (1) Ground
AMPS
444
444
361
361
278
278
222
222
C
Conductor Size
Number per Phase
AWG/MCM
(each)
400
(2)
400
(2)
400
(2)
400
(2)
400
(2)
400
(2)
300
(1)
300
(1)
UPS/PTC Output to MBM Cabinet (MIS)
(3) Phases, (1) Neutral, (1) Ground
AMPS
444
444
361
361
278
278
222
222
D
Conductor Size
Number per Phase
AWG/MCM
(each)
400
(2)
400
(2)
400
(2)
400
(2)
400
(2)
400
(2)
300
(1)
300
(1)
Control Wiring to UPS
VOLTS
AMPS
120
1
120
1
120
1
120
1
120
1
120
1
120
1
120
1
E
(2) Conductors
Basic unit rating at
0.8 lagging PF load
KVA
KW
65
52
50
40
40
32
30
24
UPS Input Voltage/Bypass Input
VOLTS
VOLTS
480
208
600
208
480
208
600
208
480
208
600
208
480
208
600
208
UPS Output Voltage
AC Input to Maintenance Bypass
(3) Phases, (1) Ground
AMPS
78
63
60
48
48
38
36
29
A
Conductor Size
Number per Phase
AWG/MCM
(each)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
AC Input to UPS Bypass
(3) Phases, (1) Ground
AMPS
78
63
60
48
48
38
36
29
B
Conductor Size
Number per Phase
AWG/MCM
(each)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
AC Output to Critical Load
(3) Phases, (1) Neutral, (1) Ground
AMPS
180
180
139
139
111
111
83
83
C
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
UPS/PTC Output to MBM Cabinet (MIS)
(3) Phases, (1) Neutral, (1) Ground
AMPS
180
180
139
139
111
111
83
83
D
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
Control Wiring to UPS
VOLTS
AMPS
120
1
120
1
120
1
120
1
120
1
120
1
120
1
120
1
E
(2) Conductors
Note:
Callout letters
A, B, C, D,
and
E
map to drawing 164201177---5 (Reverse Transfer Connection) and
164201177---8 (Parallel Connection). Read and understand the notes on drawings when planning your installation.
DESCRIPTION:
INSTALLATION NOTES
DRAWING NO:
SHEET:
164201177---1
1 of 4
REVISION:
DATE:
C
041500
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 2
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Table A--2. Ratings & External Wiring Requirements for Powereware 9315
M B M 3 0 --- 1 6 0 kVA, 480:480VAC/600:600VAC
Rating and External Wiring Requirement
Units
Rating 60 Hz
Basic unit rating at
0.8 lagging PF load
KVA
KW
160
128
130
104
100
80
UPS Input Voltage/Bypass Input
VOLTS
VOLTS
480
480
600
600
480
480
600
600
480
480
600
600
UPS Output Voltage
AC Input to Maintenance Bypass
(3) Phases, (1) Ground
AMPS
192
153
156
125
120
96
A
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
AC Input to UPS Bypass
(3) Phases, (1) Ground
AMPS
192
153
156
125
120
96
B
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
AC Output to Critical Load
(3) Phases, (1) Neutral, (1) Ground
AMPS
192
153
156
125
120
96
C
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
UPS/PTC Output to MBM Cabinet (MIS)
(3) Phases, (1) Neutral, (1) Ground
AMPS
192
153
156
125
120
96
D
Conductor Size
Number per Phase
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
Control Wiring to UPS
VOLTS
AMPS
120
1
120
1
120
1
120
1
120
1
120
1
E
(2) Conductors
Basic unit rating at
0.8 lagging PF load
KVA
KW
80
64
65
52
50
40
40
32
30
24
UPS Input Voltage/Bypass Input
VOLTS
VOLTS
480
480
480
480
480
480
480
480
480
480
UPS Output Voltage
AC Input to Maintenance Bypass
(3) Phases, (1) Ground
AMPS
96
78
60
48
36
A
Conductor Size
Number per Phase
AWG/MCM
(each)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
AC Input to UPS Bypass
(3) Phases, (1) Ground
AMPS
96
78
60
48
36
B
Conductor Size
Number per Phase
AWG/MCM
(each)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
AC Output to Critical Load
(3) Phases, (1) Neutral, (1) Ground
AMPS
96
78
60
48
36
C
Conductor Size
Number per Phase
AWG/MCM
(each)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
UPS/PTC Output to MBM Cabinet (MIS)
(3) Phases, (1) Neutral, (1) Ground
AMPS
96
78
60
48
36
D
Conductor Size
Number per Phase
AWG/MCM
(each)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1)
Control Wiring to UPS
VOLTS
AMPS
120
1
120
1
120
1
120
1
120
1
E
(2) Conductors
Note:
Callout letters
A, B, C, D,
and
E
Map to drawing 164201177---4 (Reverse Transfer Connection) and
164201177---7 (Parallel Connection). Read and understand the notes on drawings when planning your installation.
DESCRIPTION:
INSTALLATION NOTES
DRAWING NO:
SHEET:
164201177---1
2 of 4
REVISION:
DATE:
C
041500
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A --- 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Table A--3. Ratings & External Wiring Requirements for Powerware 9315
M B M 3 0 --- 1 6 0 kVA, 208:208VAC
Rating and External Wiring Requirement
Units
Rating 60 Hz
Basic unit rating at
0.8 lagging PF load
KVA
KW
160 130 100
80
64
65
52
50
40
40
32
30
24
128 104
80
UPS Input Voltage/Bypass Input
VOLTS
VOLTS
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
UPS Output Voltage
AC Input to Maintenance Bypass
(3) Phases, (1) Neutral, (1) Ground
AMPS
444
361
278
222
180
139
111
83
A
Conductor Size
Number per Phase
AWG/MCM
(each)
400
(2)
400
(2)
400
(2)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
AC Input to UPS Bypass
(3) Phases, (1) Ground
AMPS
444
361
278
222
180
139
111
83
B
Conductor Size
Number per Phase
AWG/MCM
(each)
400
(2)
400
(2)
400
(2)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
AC Output to Critical Load
(3) Phases, (1) Neutral, (1) Ground
AMPS
444
361
278
222
180
139
111
83
C
Conductor Size
Number per Phase
AWG/MCM
(each)
400
(2)
400
(2)
400
(2)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
UPS/PTC Output to MBM Cabinet (MIS)
(3) Phases, (1) Neutral, (1) Ground
AMPS
444
361
278
222
180
139
111
83
D
Conductor Size
Number per Phase
AWG/MCM
(each)
400
(2)
400
(2)
400
(2)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
Control Wiring to UPS
VOLTS
AMPS
120
1
120
1
120
1
120
1
120
1
120
1
120
1
120
1
E
(2) Conductors
Note:
Callout letters
A, B, C, D,
and
E
map to drawing 164201177---6 (Reverse Transfer Connection) and
164201177---9 (Parallel Connection). Read and understand the notes on drawings when planning your installation.
DESCRIPTION:
INSTALLATION NOTES
DRAWING NO:
SHEET:
164201177---1
3 of 4
REVISION:
DATE:
C
041500
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 4
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Table A--4. Rating and External Wiring Requirements for Powerware 9315
M B M 5 0 --- 1 6 0 KVA, 380:380VAC, 400:400VAC, 415:415VAC
RATING AND EXTERNAL WIRING REQUIREMENT
UNITS
RATING 50/60 HZ
BASIC UNIT RATING AT
0.8 LAGGING PF LOAD
KVA
KW
160
128
130
104
100
80
80
64
65
52
50
40
40
32
30
24
UPS INPUT VOLTAGE
BYPASS INPUT/UPS OUTPUT VOLTAGE
VOLTS
VOLTS
380/400/415
380/400/415
AC INPUT TO MAINTENANCE BYPASS
(3) PHASES, (1) GROUND
AMPS
231
188
146
115
97
74
60
45
A
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
AC INPUT TO UPS BYPASS
(3) PHASES, (1) GROUND
AMPS
231
188
146
115
97
74
60
45
B
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
AC OUTPUT TO CRITICAL LOAD
(3) PHASES, (1) NEUTRAL, (1) GROUND
AMPS
231
188
146
115
97
74
60
45
C
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
UPS/PTC OUTPUT TO MBM CABINET (MIS)
(3) PHASE, (1) NEUTRAL, (1) GROUND
AMPS
231
188
146
115
97
74
60
45
D
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
CONTROL WIRING TO UPS
(2) CONDUCTORS
VOLTS
AMPS
120
1
120
1
120
1
120
1
120
1
120
1
120
1
120
1
E
Note:
Callout letters
A, B, C, D,
and
E
map to drawing 164201177---4 (Reverse Transfer Connection) and
164201177---7 (Parallel Connection). Read and understand the notes on drawings when planning your installation.
DESCRIPTION:
INSTALLATION NOTES
DRAWING NO:
SHEET:
164201177---1
4 of 4
REVISION:
DATE:
C
041500
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A --- 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table B. Circuit Breaker Requirements for Powerware 9315
M B M 3 0 --- 1 6 0 KVA, 380:380VAC, 400:400VAC, 415:415VAC, 600:600VAC,
480:208VAC, 600:208VAC, 208:208VAC, 480:480VAC.
BIB1 & BIB2
MBP & MIS
MBM
FAMILY
MBM
Model No.
V /V
in out
I /I
in out
Instantaneous
Instantaneous
Frame/Trip
Frame/Trip
Trip Range
150---1200A
150---1200A
150---1200A
375---3000A
150---1200A
150---1200A
150---1200A
150---1200A
150---1200A
150---1200A
375---3000A
150---1200A
150---1200A
150---1200A
150---1200A
150---1200A
150---1200A
375---3000A
Trip Range
375---3000A
150---1200A
375---3000A
375---3000A
150---1200A
150---1200A
150---1200A
375---3000A
150---1200A
375---3000A
375---3000A
150---1200A
150---1200A
150---1200A
375---3000A
150---1200A
375---3000A
375---3000A
MBM 50/30---48/20
MBM 50/30---48/48
MBM 50/30---60/20
MBM 50/30---20/20
MBM 50/30---38/38
MBM 50/30---40/40
MBM 50/30---41/41
MBM 50/40---48/20
MBM 50/40---48/48
MBM 50/40---60/20
MBM 50/40---20/20
MBM 50/40---38/38
MBM 50/40---40/40
MBM 50/40---41/41
MBM 50/50---48/20
MBM 50/50---48/48
MBM 50/50---60/20
MBM 50/50---20/20
480V/208V
480V/480V
600V/208V
208V/208V
380V/380V
400V/400V
410V/410V
480V/208V
480V/480V
600V/208V
208V/208V
380V/380V
400V/400V
415V/415V
480V/208V
480V/480V
600V/208V
208V/208V
36A/83A
36A/36A
29A/83A
83A/83A
45A/45A
45A/45A
45A/45A
48A/111A
48A/48A
38A/111A
111A/111A
60A/60A
60A/60A
60A/60A
60A/139A
60A/60A
48A/139A
139A/139A
100A/40A
100A/40A
100A/40A
250A/100A
100A/50A
100A/50A
100A/50A
100A/50A
100A/50A
100A/40A
250A/125A
100A/70A
100A/70A
100A/70A
100A/70A
100A/70A
100A/50A
250A/150A
250A/100A
100A/40A
250A/100A
250A/100A
100A/50A
100A/50A
100A/50A
250A/125A
100A/50A
250A/125A
250A/125A
100A/70A
100A/70A
100A/70A
250A/150A
100A/70A
250A/150A
250A/150A
MBM 50
30KVA
40KVA
50KVA
MBM 80/50---48/20
MBM 80/50---48/48
MBM 80/50---60/20
MBM 80/50---38/38
MBM 80/50---40/40
MBM 80/50---41/41
MBM 80/50---20/20
MBM 80/65---48/20
MBM 80/65---48/48
MBM 80/65---60/20
MBM 80/65---38/38
MBM 80/65---40/40
MBM 80/65---41/41
MBM 80/65---20/20
480V/208V
480V/480V
600V/208V
380V/380V
400V/400V
415V/415V
208V/208V
480V/208V
480V/480V
600V/208V
380V/380V
400V/400V
415V/415V
208V/208V
60A/139A
60A/60A
48A/139A
74A/74A
74A/74A
74A/74A
139A/139A
78A/180A
78A/78A
63A/180A
97A/97A
97A/97A
94A/94A
180A/180A
100A/70A
100A/70A
100A/50A
100A/80A
100A/80A
100A/80A
250A/150A
100A/80A
100A/80A
100A/70A
250A/100A
250A/100A
250A/100A
250A/200A
150---1200A
150---1200A
150---1200A
150---1200A
150---1200A
150---1200A
375---3000A
150---1200A
150---1200A
150---1200A
375---3000A
375---3000A
375---3000A
375---3000A
250A/150A
100A/70A
250A/150A
100A/80A
100A/80A
100A/80A
250A/150A
250A/200A
100A/80A
250A/200A
250A/100A
250A/100A
250A/100A
250A/200A
375---3000A
150---1200A
375---3000A
150---1200A
150---1200A
150---1200A
375---3000A
375---3000A
150---1200A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
MBM 80
50KVA
65KVA
NOTE: See Sheet 2 For Model Number Legend.
DESCRIPTION:
DRAWING NO:
REVISION:
INSTALLATION NOTES
SHEET:
164201177---1
1 of 2
DATE:
C
041500
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 6
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Table B. Circuit Breaker Requirements for Powerware 9315
M B M 3 0 --- 1 6 0 KVA, 380:380VAC, 400:400VAC, 415:415VAC, 600:600VAC,
480:208VAC, 600:208VAC, 208:208VAC, 480:480VAC.
BIB1 & BIB2
MBP & MIS
MBM
FAMILY
MBM
Model No.
V /V
in out
Ii /I
n
out
Instantaneous
Instantaneous
Frame/Trip
Frame/Trip
Trip Range
Trip Range
MBM 80/50---48/20
MBM 80/80---48/20
MBM 80/80---48/48
MBM 80/80---60/20
MBM 80/80---38/38
MBM 80/80---40/40
MBM 80/80---41/41
MBM 80/80---20/20
480V/208V
480V/208V
480V/480V
600V/208V
380V/380V
400V/400V
415V/415V
208V/208V
60A/139A
96A/222A
96A/96A
100A/70A
150---1200A
150---1200A
150---1200A
150---1200A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
900---7200A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
900---7200A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
250A/150A
250A/237A
100A/100A
250A/237A
250A/125A
250A/125A
250A/125A
250A/237A
600A/300A
250A/125A
600A/300A
250A/100A
250A/150A
250A/150A
250A/150A
600A/300A
600A/420A
250A/175A
600A/420A
250A/150A
250A/200A
250A/200A
250A/200A
600A/420A
600A/480A
250A/200A
600A/480A
250A/175A
250A/237A
250A/237A
250A/237A
600A/480A
375---3000A
375---3000A
150---1200A
375---3000A
375---3000A
375---3000A
375---3000A
375---3000A
900---7200A
375---3000A
900---7200A
375---3000A
375---3000A
375---3000A
375---3000A
900---7200A
900---7200A
375---3000A
900---7200A
375---3000A
375---3000A
375---3000A
375---3000A
900---7200A
900---7200A
375---3000A
900---7200A
375---3000A
375---3000A
375---3000A
375---3000A
900---7200A
MBM 80
100A/100A
100A/100A
100A/80A
77A/222A
115A/115A
115A/115A
115A/115A
222A/222A
120A/278A
120A/120A
96A/278A
96A/96A
80KVA
250A/125A
250A/125A
250A/125A
250A/237A
250A/125A
250A/125A
250A/100A
250A/100A
250A/150A
250A/150A
250A/150A
600A/300A
250A/175A
250A/175A
250A/150A
250A/150A
250A/200A
250A/200A
250A/200A
600A/420A
250A/200A
250A/200A
250A/175A
250A/175A
250A/237A
250A/237A
250A/237A
600A/480A
MBM 160
MBM 160/100---48/20 480V/208V
MBM 160/100---48/48 480V/480V
MBM 160/100---60/20 600V/208V
MBM 160/100---60/60 600V/600V
MBM 160/100---38/38 380V/380V
MBM 160/100---40/40 400V/400A
MBM 160/100---41/41 415V/415V
MBM 160/100---20/20 208V/208A
MBM 160/130---48/20 480V/208V
MBM 160/130---48/48 480V/480V
MBM 160/130---60/20 600V/208V
MBM 160/130---60/60 600V/600V
MBM 160/130---38/38 380V/380V
MBM 160/130---40/40 400V/400V
MBM 160/130---41/41 415V/415V
MBM 160/130---20/20 208V/208V
MBM 160/160---48/20 480V/208V
MBM 160/160---48/48 480V/480V
MBM 160/160---60/20 600V/208V
MBM 160/160---60/60 600V/600V
MBM 160/160---38/38 380V/380V
MBM 160/160---40/40 400V/400V
MBM 160/160---41/41 415V/415V
MBM 160/160---20/20 208V/208V
100KVA
130KVA
160KVA
146A/146A
146A/146A
146A/146A
278A/278A
156A/361A
156A/156A
125A/361A
125A/125A
188A/188A
188A/188A
188A/188A
361A/361A
192A/444A
192A/192A
153A/444A
153A/153A
231A/231A
231A/231A
231A/231A
444A/444A
NOTE: Model Number Legend
1. MBM 50/30---20/20 means MBM cabinet,
Family 50, 208V (input) and 208V (output),
model 30 (30kVA).
2. All breakers are 100% UL rated with
Interrupting Capacity (IC) of 65kAIC@480VAC.
DESCRIPTION:
DRAWING NO:
REVISION:
INSTALLATION NOTES
SHEET:
164201177---1
2 of 2
DATE:
C
041500
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A --- 7
Download from Www.Somanuals.com. All Manuals Search And Download.
Table C -- 1. Power Cable Terminations
With Optional BIB
Without Optional BIB
Tightening
Int.
Hex
Size
(In.)
Tightening
Int.
Hex
Size
(In.)
Terminal
Function
Size of
Presure
Terminal
Size of
Presure
Terminal
Powerware 9315
UPS Model in KVA
(see note below)
Terminal Function
Torque
N --- M
( lb --- in )
Torque
N --- M
( lb --- in )
2 --- #6 - 3 5 0
kcmil
1 --- #6 - 3 5 0
kcmil
30---160KVA,
38/38, 48/48, 60/60
30---80KVA, 20/20
31.1 (275)
31.1 (275)
56.5 (500)
31.1 (275)
3/8
3/8
1/2
3/8
31.1 (275)
31.1 (275)
3/8
3/8
(Note 2)
(Note 3)
2 --- #6 - 3 5 0
kcmil
(Note 2)
2 --- #6 - 3 5 0
kcmil
(Note 2)
E1,
E2,
E3
Phase A,
Phase B,
Phase C
30---160KVA,
48/20, 60/20
AC Input to
MBM
4 --- #2 - 6 0 0
kcmil
(Note 2)
3 --- #3 / 0 - 4 0 0
kcmil
(Note 3)
42.4 (375) 5/16
100---160KVA, 20/20
30---160KVA,
38/38, 48/48, 60/60, 48/20, 60/20
30---80KVA, 20/20
1 --- #6 - 3 5 0
kcmil
AC Input to
UPS Bypass
(BIB breaker
Load side)
N/A
N/A
N/A
N/A
N/A
N/A
B IB --- 2 ,
BIB---4,
B IB --- 6
Phase A,
Phase B,
Phase C
3 --- #3 / 0 - 4 0 0
kcmil
42.4 (375) 5/16
100---160KVA, 20/20
30---160KVA,
38/38, 48/48, 60/60
30---80KVA,
1 --- #6 - 3 5 0
kcmil
1 --- #6 - 3 5 0
kcmil
UPS Output
to MBM
(MIS breaker
Line side)
311 (275)
3/8
311 (275)
3/8
MIS --- 1 ,
MIS --- 3 ,
MIS --- 5
Phase A,
Phase B,
Phase C
48/20, 60/20, 20/20
3 --- #3 / 0 - 4 0 0
kcmil
3 --- #3 / 0 - 4 0 0
kcmil
100---160KVA,
48/20, 60/20, 20/20
42.4 (375) 5/16
42.4 (375) 5/16
30---160KVA,
38/38, 48/48, 60/60
30---80KVA,
2 --- #6 - 3 5 0
kcmil
2 --- #6 - 3 5 0
kcmil
31.1 (275)
3/8
31.1 (275)
3/8
MBM Output
to Critical
Load
E13,
E14,
E15
Phase A,
Phase B,
Phase C
48/20, 60/20, 20/20
4 --- #2 - 6 0 0
kcmil
4 --- #2 - 6 0 0
kcmil
100---160KVA,
48/20, 60/20, 20/20
56.5 (500)
56.5 (500)
31.1 (275)
1/2
1/2
3/8
56.5 (500)
56.5 (500)
31.1 (275)
1/2
1/2
3/8
12---#2-500
kcmil
12---#2-500
kcmil
Neutral Lug
E12
Neutral
Ground
30---160KVA, all voltages
30---160KVA, all voltages
Customer
Ground Lug
2 --- #6 - 3 5 0
kcmil
2 --- #6 - 3 5 0
kcmil
Ground
NOTES: Model Number Legend
1. 38/38: 380VAC in---380VAC out; 48/48: 480VAC in---480VAC out; 60/60: 600VAC in---600VAC out
48/20: 480VAC in---208VAC out; 60/20: 600VAC in---208VAC out; 20/20: 208VAC in---208VAC out
2. AC input wiring is connected to input lugs E1---E3. Lugs are located on the right side of BIB breaker.
3. A C inp ut w iring is connected directly to the line sid e of M BP b reaker (M BP --- 1, M BP --- 3, and M BP --- 5).
4. AC input wiring is connected to input lugs E1---E3.
DESCRIPTION:
INSTALLATION NOTES
DRAWING NO:
SHEET:
164201177---1
1 of 2
REVISION:
DATE:
C
041500
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 8
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Table C--2. Control Wiring Requirements and Termination Requirement for
Reverse Transfer (RT) System.
Size of
Pressure
Termination
(lb-in)
Size of
Pressure
Termination
(lb-in)
Maximum
Voltage and
Current
Connecting Point
in MBM Cabinet
Connection
Point in UPS
Recommended
Wire Size
Remarks
TB1 --- 12
TB1 --- 14
TB6 --- 1
TB6 --- 2
#18---#8
(55)
#18---#8
(55)
120VAC
1.0A
See Fig 1.
(Twisted Pair)
#18---#14
Table C--3. Control Wiring Requirements and Termination Requirement for
Parallel Redundant System.
Size of
Pressure
Termination
(lb-in)
Size of
Pressure
Termination
(lb-in)
Maximum
Voltage and
Current
Connecting Point
in MBM Cabinet
Connection Point
in UPS
Recommended
Wire Size
Remarks
TB1 --- 12
TB1 --- 13
TB1 --- 13
TB1 --- 14
TB6 --- 1 (UPS1)
TB6 --- 1 (UPS2)
TB6 --- 2 (UPS1)
TB6 --- 2 (UPS2)
#18---#8
(55)
#18---#8
(55)
120VAC
1.0A
See Fig 2.
(Twisted Pair)
#18---#14
NOTES FOR TABLES C--2 AND C--3:
· Install the copper wiring in a conduit separate from the power wiring.
· Control wiring is NEC Class 1.
· Control wiring from each UPS Module should be twisted.
UPS
UPS1
UPS2
K3
K3
K3
TB6
TB6
BLK
TB6
BLK
--- 1
--- 2
--- 1
--- 2
--- 1
WHT
--- 2
BLK
WHT
WHT
Twist Pair
Twist Pair
Twist Pair
--- 12 --- 13 --- 14
TB1
--- 12 --- 13
TB1
--- 14
MBM
MBM
Figure 2. (Parallel Redundant)
Figure 1. (Reverse Transfer)
DESCRIPTION:
DRAWING NO:
REVISION:
INSTALLATION NOTES
SHEET:
164201177---1
2 of 2
DATE:
C
041500
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A --- 9
Download from Www.Somanuals.com. All Manuals Search And Download.
DESCRIPTION:
TYPICAL MBM CABINET --
30-160kVA with or without XFMR
DRAWING NO:
REVISION:
SHEET:
164201177---2
1 of 3
Dimensions are in millimeters (inches)
DATE:
A
080498
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 10
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
BREAKER ANNUNCIATION
UTILITY INPUT,
IF BIB
BREAKER IS
NOT
INSTALLED
CRITICAL LOAD CONNECTIONS
MBP
MIS
UPS/PTC OUTPUT
CONNECTION
NEUTRAL CONNECTIONS
OPTIONAL UPS BYPASS
INPUT CONNECTIONS
BIB1
BIB2
UTILITY INPUT,
IF BIB
BREAKER
INSTALLED
DESCRIPTION:
TYPICAL MBM CABINET --
30-160kVA with or without XFMR
INTERIOR COMPONENTS
DRAWING NO:
REVISION:
SHEET:
164201177---2
2 of 3
DATE:
A
080498
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A---11
Download from Www.Somanuals.com. All Manuals Search And Download.
TOP VIEW
BOTTOM VIEW
DESCRIPTION: TYPICAL MBM CABINET --
30-160kVA with or without XFMR
TOP and BOTTOM VIEW
DRAWING NO:
SHEET:
164201177---2
3 of 3
Dimensions are in millimeters (inches)
REVISION:
DATE:
A
080498
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 12
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
PDM CABINET
(optional)
MBM CABINET
(optional)
INPUT
TRANSFORMER
CABINET
UPS
BATTERY CABINET
(optional)
CABINET
(optional)
30---160kVA UPS System with MBM
DESCRIPTION:
TYPICAL UPS SYSTEM WITH MBM
DRAWING NO:
REVISION:
SHEET:
164201177---3
1 of 1
DATE:
A
080498
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A---13
Download from Www.Somanuals.com. All Manuals Search And Download.
Read and understand the following notes while planning your installation:
1. Refer to national and local electric codes for acceptable external wiring practices.
2. Material and labor for external wiring requirements are to be provided by others.
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column
in Table A-2 and A-4. The power wiring for this equipment is rated at 90 degrees Celsius.
4. The output of the UPS is not a separately derived source. Output neutral is not bonded to equipment ground through the main
bonding jumper. Refer to NEC and local codes for proper grounding practices.
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full
load input current in Table A-2 and A-4.
6. The Bypass three-phase feeds should be symmetrical about ground.
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.
8. Control wiring must be installed in separate conduit from the power wiring.
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with
an optional (extra cost) mechanical interlock if required.
10. Refer to UPS Installation Manual for proper Bypass terminating lugs at UPS cabinet or input transformer cabinet.
11. Refer to Table C-2 for control wiring connections.
12. A Maintenance Bypass neutral feeder must be supplied when the MBM output neutral is used. If no Maintenance Bypass
neutral is supplied, the MBM output neutral is not to be used. In neither case shall the MBM output neutral be bonded to ground.
LEGEND
MIS:
MAINTENANCE ISOLATION BREAKER
MAINTENANCE BYPASS BREAKER
BYPASS INPUT BREAKER
SOLENOID KEY RELEASE UNIT
(MECHANICAL INTERLOCK)
REVERSE TRANSFER
MBP:
BIB:
DESCRIPTION:
ONELINE -- 30-160kVA, RT, 480:480VAC,
SKRU:
600:600VAC, 400:400VAC
DRAWING NO:
REVISION:
SHEET:
RT:
164201177---4
1 of 1
DATE:
110100057 D3
A
080498
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 14
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Read and understand the following notes while planning your installation:
1. Refer to national and local electric codes for acceptable external wiring practices.
2. Material and labor for external wiring requirements are to be provided by others.
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A---1.
The power wiring for this equipment is rated at 90 degrees Celsius.
4. The output of the UPS is a separately derived source. Output neutral is bonded to equipment ground through the main
bonding jumper. Refer to NEC and local codes for proper grounding practices.
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full
load input current in Table A---1.
6. The Bypass three-phase feeds should be symmetrical about ground.
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.
8. Control wiring must be installed in separate conduit from the power wiring.
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with
an optional (extra cost) mechanical interlock if required.
10. Refer to UPS Installation Manual for proper Bypass terminating lugs.
11. Refer to Table C-2 for control wiring connections.
LEGEND
MIS:
MAINTENANCE ISOLATION BREAKER
MAINTENANCE BYPASS BREAKER
BYPASS INPUT BREAKER
SOLENOID KEY RELEASE UNIT
(MECHANICAL INTERLOCK)
REVERSE TRANSFER
MBP:
BIB:
DESCRIPTION:
ONELINE -- 30-160kVA, RT,
480:208VAC, 600:208VAC
SKRU:
DRAWING NO:
REVISION:
SHEET:
RT:
164201177---5
1 of 1
DATE:
110100056 D1
A
080498
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A---15
Download from Www.Somanuals.com. All Manuals Search And Download.
Read and understand the following notes while planning your installation:
1. Refer to national and local electric codes for acceptable external wiring practices.
2. Material and labor for external wiring requirements are to be provided by others.
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A---3.
The power wiring for this equipment is rated at 90 degrees Celsius.
4. The output of the UPS is not a separately derived source. Output neutral is not bonded to equipment ground through the main
bonding jumper. Refer to NEC and local codes for proper grounding practices.
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full
load input current in Table A---3.
6. The Bypass three-phase feeds should be symmetrical about ground.
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.
8. Control wiring must be installed in separate conduit from the power wiring.
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with
an optional (extra cost) mechanical interlock if required.
10. Refer to UPS Installation Manual for proper bypass terminating lugs at UPS cabinet or at input transformer cabinet.
11. Refer to Table C-2 for control wiring connections.
LEGEND
MIS:
MAINTENANCE ISOLATION BREAKER
MAINTENANCE BYPASS BREAKER
BYPASS INPUT BREAKER
SOLENOID KEY RELEASE UNIT
(MECHANICAL INTERLOCK)
REVERSE TRANSFER
MBM:
BIB:
SKRU:
DESCRIPTION: ONELINE -- 30-160kVA, RT, 208:208VAC
DRAWING NO:
SHEET:
RT:
164201177---6
1 of 1
REVISION:
DATE:
A
080498
110100058 D2
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 16
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Read and understand the following notes while planning your installation:
1. Refer to national and local electric codes for acceptable external wiring practices.
2. Material and labor for external wiring requirements are to be provided by others.
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A---2
and A---4. The power wiring for this equipment is rated at 90 degrees Celsius.
4. The output of the UPS is not a separately derived source. Output neutral is not bonded to equipment ground through the main
bonding jumper. Refer to NEC and local codes for proper grounding practices.
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full
lo a d in p u t c u r r e n t i n Ta b le A --- 2 a n d A --- 4 .
6. The Bypass three-phase feeds should be symmetrical about ground.
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.
8. Control wiring must be installed in separate conduit from the power wiring.
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with
an optional (extra cost) mechanical interlock if required.
10. Refer to UPS Installation Manual for proper Bypass terminating lugs at UPS cabinet or input transformer cabinet.
11. Refer to Table C---3 for control wiring connections.
12. Refer to Parallel Redundant System Manual for details.
13. A Maintenance Bypass neutral feeder must be supplied when the MBM output neutral is used. If no Maintenance Bypass
neutral is supplied, the MBM output neutral is not to be used. In neither case shall the MBM output neutral be bonded to ground.
LEGEND
MIS:
MAINTENANCE ISOLATION BREAKER
MAINTENANCE BYPASS BREAKER
BYPASS INPUT BREAKER
MBM:
BIB:
DESCRIPTION:
SKRU:
SOLENOID KEY RELEASE UNIT
(MECHANICAL INTERLOCK)
PARALLEL TIE CABINET
ONELINE -- 30-160kVA, PARALLEL, 480:480VAC
600:600VAC, 400:400VAC
164201177---7
PTC:
RT:
DRAWING NO:
REVISION:
SHEET:
REVERSE TRANSFER
1 of 1
DATE:
110100069
A
080498
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A---17
Download from Www.Somanuals.com. All Manuals Search And Download.
Read and understand the following notes while planning your installation:
1. Refer to national and local electric codes for acceptable external wiring practices.
2. Material and labor for external wiring requirements are to be provided by others.
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A---1.
The power wiring for this equipment is rated at 90 degrees Celsius.
4. The output of the UPS is a separately derived source. Output neutral is bonded to equipment ground through the main
bonding jumper. Refer to NEC and local codes for proper grounding practices.
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full
load input current in Table A---1.
6
The Bypass three-phase feeds should be symmetrical about ground.
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.
8. Control wiring must be installed in separate conduit from the power wiring.
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with
an optional (extra cost) mechanical interlock if required.
10. Refer to UPS Installation Manual for proper Bypass terminating lugs.
11. Refer to Table C---3 for control wiring connections.
12. Refer to Parallel Redundant System Manual for details.
LEGEND
MIS:
MAINTENANCE ISOLATION BREAKER
MAINTENANCE BYPASS BREAKER
BYPASS INPUT BREAKER
MBP:
BIB:
DESCRIPTION:
SKRU:
SOLENOID KEY RELEASE UNIT
(MECHANICAL INTERLOCK)
PARALLEL TIE CABINET
ONELINE -- 30-160kVA, PARALLEL
480:208VAC, 600:208VAC
PTC:
RT:
DRAWING NO:
SHEET:
164201177---8
REVERSE TRANSFER
1 of 1
REVISION:
DATE:
110100068
A
080498
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 18
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
Read and understand the following notes while planning your installation:
1. Refer to national and local electric codes for acceptable external wiring practices.
2. Material and labor for external wiring requirements are to be provided by others.
3. For external wiring requirement, including the minimum AWG size of external wiring, see the appropriate column in Table A---3.
The power wiring for this equipment is rated at 90 degrees Celsius.
4. The output of the UPS is not a separately derived source. Output neutral is not bonded to equipment ground through the main
bonding jumper. Refer to NEC and local codes for proper grounding practices.
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full
load input current in Table A---3.
6. The Bypass three-phase feeds should be symmetrical about ground.
7. Transfer sequence instructions for the MBM are placed on the breaker access panel behind the cabinet doors.
8. Control wiring must be installed in separate conduit from the power wiring.
9. Electronic interlock is a standard part of the maintenance bypass module cabinet. This electronic interlock can be replaced with
an optional (extra cost) mechanical interlock if required.
10. Refer to UPS Installation Manual for proper Bypass terminating lugs at UPS cabinet or at input transformer cabinet.
11. Refer to Table C---3 for control wiring connections.
12. Refer to Parallel Redundant System Manual for details.
LEGEND
MIS:
MAINTENANCE ISOLATION BREAKER
MAINTENANCE BYPASS BREAKER
BYPASS INPUT BREAKER
MBM:
BIB:
DESCRIPTION:
SKRU:
SOLENOID KEY RELEASE UNIT
(MECHANICAL INTERLOCK)
PARALLEL TIE CABINET
ONELINE -- 30-160kVA, PARALLEL, 208:208VAC
PTC:
RT:
DRAWING NO:
SHEET:
164201177---9
REVERSE TRANSFER
1 of 1
REVISION:
DATE:
110100072
A
080498
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A---19
Download from Www.Somanuals.com. All Manuals Search And Download.
(NOTE 4)
LINE UP AND MATCH ARRANGEMENT #1
Applicable to POWERWARE 9315 30---160 kVA
UPS modules only. 160kVA UPS is shown.
DESCRIPTION:
LINE UP AND MATCH ARRANGEMENT #1
DRAWING NO:
REVISION:
SHEET:
164201177---10
1 of 4
DATE:
A
080498
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 20
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
(NOTE 5)
(NOTE 5)
(NOTE 2)
(NOTE 4)
LINE UP AND MATCH ARRANGEMENT #2
Applicable to POWERWARE 9315 30---160 kVA
UPS modules only. 160kVA UPS is shown.
DESCRIPTION:
LINE UP AND MATCH ARRANGEMENT #2
DRAWING NO:
REVISION:
SHEET:
164201177---10
2 of 4
DATE:
A
080498
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A---21
Download from Www.Somanuals.com. All Manuals Search And Download.
(NOTE 3)
(NOTE 4)
(NOTE 4)
LINE UP AND MATCH ARRANGEMENT #3
Applicable to POWERWARE 9315 30---160 kVA
UPS modules only. 160kVA UPS is shown.
DESCRIPTION:
LINE UP AND MATCH ARRANGEMENT #3
DRAWING NO:
REVISION:
SHEET:
164201177---10
3 of 4
DATE:
A
080498
Powerware 9315 Maintenance Bypass Module 30-160kVA
A --- 22
164201177 Rev. C 041500
Download from Www.Somanuals.com. All Manuals Search And Download.
1 Line up and match power and control interconnection wiring from
MBM to UPS/Input Transformer cabinet is applicable for Reverse
Transfer (Single UPS module) connection only and sold separately
by Powerware Corporation.
2 Run power cables underneath the transformer.
3 External wiring is required and supplied by others.
4 The PDM cabinet is applicable IF AND ONLY IF the MBM and UPS
module outputs are 3 phase, 60Hz, 280VAC.
5 Refer to Powerware 9315 UPS module installation manual for
proper terminating lugs.
DESCRIPTION:
LINE UP AND MATCH ARRANGMENT NOTES
DRAWING NO:
SHEET:
164201177---10
4 of 4
REVISION:
DATE:
A
080498
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
A---23
Download from Www.Somanuals.com. All Manuals Search And Download.
This Page Intentionally Left Blank.
Powerware 9315 Maintenance Bypass Module 30-160kVA
164201177 Rev. C 041500
A --- 24
Download from Www.Somanuals.com. All Manuals Search And Download.
|