PowerTec Outboard Motor DFS 1 User Manual

POWERTEC  
Indus tria l Motors  
DFS-1  
SOFTWARE RELEASE 1.0  
MICROPROCESSOR BASED  
BRUSHLESS D.C.  
MOTOR CONTROLLER  
INSTALLATION AND  
OPERATION  
INSTRUCTION MANUAL  
PRODUCTION RELEASE  
AUGUST, 1994  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ERRATA  
Corrections to page 44 of the manual, Attachment A: Detailed Commands  
Read Speed/Status (81)  
Changes shown in gray  
[ST2] - 7 6 5 4 3 2 1 0  
Local/Remote (0,1)  
Master/slave (0,1)  
At Speed (1)  
Fwd. Dir. Set  
Fault Detected (1)  
Drive Enabled (1)  
Microprocessor Fault  
Zero Speed  
[ST1] - 7 6 5 4 3 2 1 0  
Bus not charged (1)  
IOC (1)  
Stall  
Inverse Time OL (1)  
Heatsink Thermal OT  
Commutation Fault  
Overvolt  
Undervolt  
DFS-01IM  
PM94290  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Additiona l Info  
DFS Software Modification For  
Dynamic Braking or Output Contactor  
Operation  
25 October, 1994  
Functional Description  
A new function for Contactor Aux has been added to the digital input choices. When configured as described  
in the example, 24VDC must be present at this input for the drive to run. Parameter #62, Contactor Delay, is a  
number of 25ms intervals that will occur between the DFS controller acceptance of a run command and the  
firing of the transistors. If the Contactor Aux input signal is low, the DFS starts the timer and closes the  
Contactor Output. If the Contactor Aux input does not switch high before the timer runs out, the drive will  
return to the stop condition. If the Contactor Aux input does switch high, the drive will start running when the  
timer runs out.  
Example Setup for Dynamic Braking  
1
2
3
Set Digital Input #7 mode to Contactor Aux, polarity to Active Low.  
Set Digital Output #4 mode to Contactor, polarity to Normally Closed.  
Set Contactor Delay to 20 (20 x 25ms = 500ms = 1/2 second).  
Run command causes the Contactor Output to close, the Contactor Relay opens, the feedback contacts close  
and the drive starts to run.  
Example Setup for Output Contactor  
1
2
3
Set Digital Input #7 mode to Contactor Aux, polarity to Active Low.  
Set Digital Output #4 mode to Contactor, polarity to Normally Closed.  
Set Contactor Delay to 10 (10 x 25ms = 250ms = 1/4 second).  
Run command causes the Contactor Output to close, the Contactor Relay closes, the feedback contacts close  
and the drive starts to run.  
The difference in the operation of the two types of contactors is that the Dynamic Braking Contactor is  
normally closed whereas the Output Contactor is normally open. In both contactors, the auxilliary contacts are  
normally open.  
Terms Used  
1
Contactor Aux - The digital input on the DFS board which is connected to the feedback contacts on the  
contactor relay.  
2
Contactor Output - The digital output on the DFS board which activates the solenoid on the contactor  
relay.  
3
4
Signal low - 0VDC  
Signal high - 24VDC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 INSTALLATION  
The DFS-1 printed circuit board mounts on  
any POWERTEC Brushless DC motor control  
except the Model 500. The Model 1000 is used here  
for illustration purposes only.  
There are two flat ribbon cables which must be  
connected from the DFS-1 to the other parts of the  
motor control: one goes to the Base Driver Board  
(part #141-105), and the other cable goes to the  
Capacitor Board (part #141-106). See figure 2 for  
the physical layout of the control and the location of  
these boards. If the DFS-1 board is being installed  
in the field, the cables should come with the new  
board, since the connectors on the DFS-1 end are  
different from the connectors on the Speed and  
Current controller ends of the previous cables. Make  
sure that you have these new cables before proceed-  
ing to install the board. If you do not have them, call  
POWERTEC's service department before proceed-  
ing.  
The DFS-1 board may be used as either a non-  
regenerative control or as a regenerative control.  
This selection is made by one of its parameter  
settings. The DFS-1 may be installed on a Model  
1000 non-regenerative brushless DC control, but if  
the unit is to be used for a regenerative application,  
a bus loader of the appropriate voltage and resistors  
of sufficient wattage must be added before the drive  
may be used regeneratively. If a bus loader is not  
installed before regenerative operation occurs, it is  
likely that the control will trip out repeatedly. A  
Model 1000AR will already have a bus loader and  
resistors attached.  
1.1 MOUNTING -- READ THIS ENTIRE  
SECTION BEFORE STARTING!  
The DFS-1 printed circuit board mounts on  
the Model 1000 or Model 1000AR motor control in  
place of both the Current Controller board (part  
#141-108) and the Speed Controller board (part  
#141-107 on the non-regenerative model 1000, part  
# 147-101 on the regenerative model 1000AR).  
These boards are mounted side by side on all  
standard motor controls. TB1 is located on the  
Current Controller (left hand board) and TB2 is on  
the Speed Controller (right hand board). The first  
eight connections which normally come into TB1  
(the motor cable leads) will connect to the same  
places on the DFS-1. The connections going into  
TB2 (mainly operators and speed pot) on the  
standard motor control will go to different connec-  
tions on the DFS-1.  
Figure 1: The DFS-1 replaces two boards.  
If the board is being installed to replace the  
boards on a standard control, unplug the strips on  
TB1 and TB2, but do not disconnect any wires from  
them yet. Unplug the 14-pin connector on P2 (at the  
Base Driver Board) and the 10-pin connector on P3  
(at the Capacitor Board). Remove these cables and  
the Speed and Current controller boards from the  
chassis and set them aside. Remove the studs at the  
top right of where the Current Controller board was,  
and at the top left of where the Speed Controller was  
located ( the center studs - see figure 1).  
Figure 2: The Model 1000 chassis  
Page 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTENTS  
Introduction ...............................................................................................................................1  
Summary of Warranty and Disclaimer ......................................................................................2  
WARNING! ...............................................................................................................................2  
1.0 Connections ........................................................................................................................3  
POWER CONNECTIONS: ............................................................................................................................ 3  
MOTOR ENCODER CABLE: ....................................................................................................................... 4  
ANALOG INPUTS: ........................................................................................................................................ 4  
ANALOG OUTPUTS:................................................................................................................................... 5  
FREQUENCY INPUT: ................................................................................................................................... 5  
FREQUENCY OUTPUT: ............................................................................................................................... 6  
DIGITAL INPUTS:......................................................................................................................................... 6  
DIGITAL OUTPUTS:..................................................................................................................................... 7  
COMMUNICATIONS: ................................................................................................................................... 7  
DEFAULT SETUP .......................................................................................................................................... 9  
2.0 Specifications ................................................................................................................... 11  
POWER SUPPLIES...................................................................................................................................... 11  
ANALOG INPUTS ....................................................................................................................................... 11  
ANALOG OUTPUTS ................................................................................................................................... 11  
FREQUENCY INPUTS AND OUTPUTS ................................................................................................... 12  
DIGITAL INPUTS ........................................................................................................................................ 12  
DIGITAL OUTPUTS .................................................................................................................................... 12  
COMMUNICATIONS .................................................................................................................................. 13  
3.0 DFS-1 Parameters............................................................................................................. 15  
1. UNIT ID ................................................................................................................................................ 15  
2. BAUD RATE ......................................................................................................................................... 15  
3. LOCAL / REMOTE CONTROL ........................................................................................................... 15  
4. COMMUNICATIONS PROTOCOL ..................................................................................................... 16  
5. MODES OF OPERATION..................................................................................................................... 16  
6. MAXIMUM MOTOR SPEED............................................................................................................... 17  
7. ENCODER PULSES PER REVOLUTION .......................................................................................... 17  
8. MASTER RAMP UP TIME .................................................................................................................. 18  
9. MASTER RAMP DOWN TIME ........................................................................................................... 18  
10. SLAVE RAMP UP TIME ...................................................................................................................... 18  
11. SLAVE RAMP DOWN TIME ............................................................................................................... 18  
12. MASTER PRESET SPEED ................................................................................................................... 19  
13. SLAVE RATIO PRESET ....................................................................................................................... 19  
14. ENGINEERING UNITS ........................................................................................................................ 19  
15. BASE RATIO ......................................................................................................................................... 19  
16. MAXIMUM RATIO .............................................................................................................................. 20  
17. ANALOG INPUT #1 MODE SELECT................................................................................................. 20  
18. ANALOG INPUT #1 SIGNAL CONDITIONING ............................................................................... 21  
19. ANALOG INPUT #1 LOW ENGINEERING UNITS (EGU) .............................................................. 21  
20. ANALOG INPUT #1 HIGH ENGINEERING UNITS (EGU) ............................................................. 22  
21. ANALOG INPUT #2 MODE SELECT................................................................................................. 22  
22. ANALOG INPUT #2 SIGNAL CONDITIONING ............................................................................... 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23. ANALOG INPUT #2 LOW ENGINEERING UNITS (EGU) .............................................................. 22  
24. ANALOG INPUT #2 HIGH ENGINEERING UNITS (EGU) ............................................................. 22  
25. ANALOG OUTPUT #1 MODE SELECT............................................................................................. 23  
26. ANALOG OUTPUT #1 LOW ENGINEERING UNITS (EGU) .......................................................... 23  
27. ANALOG OUTPUT #1 HIGH ENGINEERING UNITS (EGU) ......................................................... 23  
28. ANALOG OUTPUT #2 MODE SELECT............................................................................................. 23  
29. ANALOG OUTPUT #2 LOW ENGINEERING UNITS (EGU) .......................................................... 24  
30. ANALOG OUTPUT #2 HIGH ENGINEERING UNITS (EGU) ......................................................... 24  
31. DIGITAL INPUT #1 FUNCTION ......................................................................................................... 25  
32. DIGITAL INPUT #2 FUNCTION ......................................................................................................... 25  
33. DIGITAL INPUT #3 FUNCTION ......................................................................................................... 25  
34. DIGITAL INPUT #4 FUNCTION ......................................................................................................... 25  
35. DIGITAL INPUT #5 FUNCTION ......................................................................................................... 26  
36. DIGITAL INPUT #6 FUNCTION ......................................................................................................... 26  
37. DIGITAL INPUT #7 FUNCTION ......................................................................................................... 26  
38. DIGITAL OUTPUT #1 FUNCTION ..................................................................................................... 26  
39. DIGITAL OUTPUT #2 FUNCTION ..................................................................................................... 27  
40. DIGITAL OUTPUT #3 FUNCTION ..................................................................................................... 27  
41. DIGITAL OUTPUT #4 FUNCTION ..................................................................................................... 27  
42. DRIVE GAIN SETTING ....................................................................................................................... 27  
43. DRIVE STABILITY SETTING............................................................................................................. 27  
44. DRIVE MOTORING CURRENT LIMIT ............................................................................................. 27  
45. DRIVE REGENERATIVE CURRENT LIMIT..................................................................................... 28  
46. PULSE MULTIPLIER ........................................................................................................................... 28  
47. MODULATION AND OPERATION MODES ..................................................................................... 28  
48. JUMP OR MOP OPERATION .............................................................................................................. 28  
49. MASTER JUMP UP AMOUNT ............................................................................................................ 29  
50. MASTER JUMP DOWN AMOUNT .................................................................................................... 29  
51. SLAVE JUMP UP AMOUNT................................................................................................................ 29  
52. SLAVE JUMP DOWN AMOUNT ........................................................................................................ 29  
53. INPUT DEBOUNCE VALUE ............................................................................................................... 30  
54. FLOAT OR FREEZE ............................................................................................................................. 30  
55. MINIMUM RATIO ................................................................................................................................ 30  
56. COMMUNICATIONS TURNAROUND DELAY ................................................................................ 30  
57. MASTER JOG SPEED .......................................................................................................................... 31  
58. SLAVE JOG RATIO .............................................................................................................................. 31  
59. EGU TAG SELECT ............................................................................................................................... 31  
60. MASTER PRESET #2 ........................................................................................................................... 31  
61. SLAVE PRESET #2 ............................................................................................................................... 31  
4.0 DFS - 1 Setup .................................................................................................................. 33  
4.1 BASIC SETUP OF THE DFS-1 CONTROLLER................................................................................. 34  
4.2 MASTER MODE SETUP..................................................................................................................... 35  
4.3 SLAVE MODE SETUP......................................................................................................................... 36  
4.4 INPUTS AND OUTPUTS SETUP ....................................................................................................... 37  
4.5 COMMUNICATIONS SETUP ............................................................................................................. 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.0 DFS-1 ERROR CODES .................................................................................................. 39  
6.0 COMMUNICATION PROTOCOL .................................................................................. 41  
COMMAND LIST ........................................................................................................................................ 42  
PARAMETER LIST ..................................................................................................................................... 43  
ATTACHMENT A: DETAILED COMMANDS......................................................................................... 44  
ATTACHMENT B: PARAMETER DESCRIPTION .................................................................................. 50  
Additional Info ........................................................................................................................ 51  
Typical Output Contactor Connections ........................................................................................................ 52  
Typical Dynamic Braking Connections ........................................................................................................ 53  
Appendix A ............................................................................................................................. 55  
RETROFITTING THE MODEL 1000,1000A, OR 1000AR  
Appendix B.............................................................................................................................. 57  
MENU AND KEYPAD HIERARCHY  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE WAS INTENTIONALLY LEFT BLANK.  
Page 4  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
s the computer revolution takes greater  
control of industrial processes, there is  
a growing need for more intimate control of  
Programmable analog inputs and analog outputs  
allow many possibilities for control through external  
voltages, currents, and frequencies. They may also be  
used to monitor drive operation. Digital inputs and  
outputs (also programmable) give control and  
monitoring flexibility as well as coordination  
functions.  
A
the process parameters. It is becoming ever more  
necessary to control the important characteristics of  
motors directly from computers and microprocessor-  
based controllers. Such control cannot wait for  
operator intervention when changes occur in milli-  
seconds and tolerances are measured in thousandths.  
Provision is made for plug-in options which add  
input and output options and accomplish special  
functions. Optional software packages may be  
ordered for specific application needs.  
All of the operational characteristics of a motor  
are controllable by manipulating its speed, torque,  
and power. POWERTEC digitally implemented,  
speed, torque, and power control - the DFS-1.  
The Brushless DC motor and its control are  
digitally based, and are a natural choice for a  
computer controlled environment. Now computers  
and PLC's talk to the drive itself when the field-  
installable DFS-1 control board replaces the Speed  
and Current boards on the standard POWERTEC  
Brushless DC drive.  
One of the first things you will notice about the  
DFS-1 is that there are no adjustment potentiometers  
and no setup switches. All characteristics of the drive  
are controlled by software parameters which may be  
entered by the optional KDU-1 keypad or host  
computer. The KDU-1 keypad can be mounted on the  
DFS-1 board, in a remote location (usually the  
enclosure door), or in a handheld unit. A default set  
of parameters which represent the most common  
operating conditions will facilitate immediate  
operation and testing after installation.  
Capable of operating on a single drive or in  
networks, the DFS-1 is programmable by an optional  
keypad with its two line, 16-character display. A  
single computer port may be used to monitor and  
control up to 32 units in an RS-485 communications  
link.  
Page 5  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S UMMARY OF WARRANTY AND DIS CLAIMER  
POWERTEC Industrial Corporation warrants the DFS-1 to be free from defects in materials and work-  
manship for a period of one year from the date of shipment from the factory, or if purchased from an autho-  
rized POWERTEC distributor or Original Equipment Manufacturer, not more than 18 months from the date  
of shipment from the factory. Upon written notification to the factory of a possible defect in materials or  
workmanship, POWERTEC will, at its sole option, repair or replace, at the factory, such defective parts as it  
deems necessary to restore the unit to its original specifications.  
There is no other warranty, express or implied, including fitness of purpose for the application intended.  
This warranty does not cover accidental or intentional damage; physical or electrical misuse or abuse; defec-  
tive or incorrect installation; effects on other equipment or caused by other equipment; attempted use outside  
of specified ranges; or any other situation outside of the control of POWERTEC Industrial Corporation.  
The user is responsible for the application of the DFS-1 product and the programming thereof.  
This warranty does not encompass any other claims, including, but not limited to, special, incidental, or  
consequential damages.  
This manual has been assembled as a guide to the use of a POWERTEC product. It represents the best  
efforts to compile and present the information herein. Such errors as may appear in no way affect the above  
stated warranty. If mistakes of fact are found or suspected in this manual, please notify the factory or your  
distributor at once.  
WARNING!  
The DFS-1 contains static sensitive parts which may be damaged by careless handling of the printed  
circuit board. You can avoid this type of damage by always touching the frame of the drive before you touch  
the printed circuit board or any of its connections.  
The DFS-1 is supplied for field installation in a protective bag. Bring the bag into contact with the  
motor controller frame before removing the board from the bag.  
Page 6  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 CONNECTIONS  
in the motor junction box to the ground terminal on  
the drive. A wire must then be run from the ground  
terminal on the drive (next to the motor terminals) to  
an earth ground at or near the power source. The  
Model 1000 drive does not have the common  
circuitry connected to earth ground (chassis). In  
most cases this works best, but in some cases it does  
not. POWERTEC recommends connecting a short  
jumper wire from the drive common at any one of the  
several places available on the terminal strips to a  
nearby point on the drive chassis or backpanel that  
will establish this ground. This is more important in  
applications where multiple drives are connected  
together or serial communications from a host are  
used. All other POWERTEC drives have the  
common grounded by mounting screws on the  
regulator boards.  
POWER CONNECTIONS:  
POWERTEC Brushless DC motor controllers  
are supplied with nominal input voltages of 230, 380,  
and 460VAC. Three phase input power is required.  
The input is not phase sensitive. Connect the appro-  
priate power supply to the input fuses at L1, L2, and  
L3 (check nameplate for proper input voltage and  
capacity).  
Connect the output terminals T1, T2, and T3 to  
the respective terminals on the Brushless DC motor.  
It is very important that the T1 terminal on the motor  
connects to T1 on the drive, T2 of the motor connects  
to T2 of the drive, and T3 of the motor connects to  
T3 of the drive. An earth ground wire of the same  
gauge as the motor power leads or one gauge smaller  
(no smaller than #14 AWG) must be run from a bolt  
Orange  
Brown  
Red  
Blue  
Yellow  
Black  
Green  
Purple  
White  
Shield  
Run  
1
Motor  
Stop  
E-Stop  
2
3
4
5
T1  
T2  
T3  
6
7
8
Fwd Rev  
9
10  
RS-485  
Communications  
POWERTEC  
Brushless  
DC Drive  
G
A
B
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10  
10  
A
B
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10 11 12 13 14  
10 11 12 13 14  
A
B
1
1
2
2
3
3
4
4
DFS-1  
Board  
TB1  
TB2  
TB3  
T3  
T2  
T1  
L3  
L2  
L1  
Analog  
Speed Pot  
KDU Cable is  
Belden # 9463  
Blue Hose” or  
equivalent  
1
2
3
4
Keypad  
Display  
Unit  
Figure 3: Basic connections to the DFS-1 controlled POWERTEC Brushless DC motor control, using the factory default  
settings for some of the inputs and outputs. Note that the speed pot input is the default, and that using the 4-20mA input  
will require a change in the DFS-1 setup.  
Page 7  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
However, these standard connections will not be in  
the same physical positions as they are in the  
standard control, and the default setting will not  
take care of any optional modes of operation.  
There are three plug-in terminal strips on the  
bottom of the DFS-1 PC board labelled in sections  
from left to right: TB1, TB2, and TB3. Though the  
three sections look like two rows of strips, there is a  
small separator between each of the sections. Each  
of the sections has an upper row (A) and a lower row  
(B). The B row is closest to the PC board. The  
terminals are numbered consecutively from left to  
right on each level.  
MOTOR ENCODER CABLE:  
The motor encoder cable is connected to plug-in  
terminal strip TB1:A on the DFS-1 PC board. A  
shielded cable must be used for the motor encoder  
cable. The recommended cable is a 9-conductor  
shielded cable (Belden Cable part # 9539 or equiva-  
lent). The shield should be connected at the drive end  
to the shield terminal (TB1:A1) and to terminal 10 (if  
there is one) at the motor terminal strip and if not (as  
on motors built prior to April 1992), the shield  
should be cut off at the motor end and taped up.  
The DFS-1 PC Board contains all of the func-  
tions necessary to operate the Brushless DC motor  
control according to the inputs connected to its  
terminals and the programmed information in  
memory. The DFS-1 board takes care of all speed,  
torque, and control functions. It takes speed informa-  
ANALOG INPUTS:  
There are two analog input ports to the DFS-1 on  
TB1:B. When used as a voltage input, both of the  
tion from the encoder, environmental information and analog inputs are a differential type of input with a  
current (load) information from the power output  
circuits of the drive, and compares all that informa-  
tion to the input conditions and programmed param-  
eters. It processes this information and turns the  
power transistors on and off according to the needs of  
the system.  
The DFS-1 is delivered with an installed set of  
default parameters which will allow it to operate with  
a standard set of connections (as illustrated in Figure  
3) of the types used with standard motor controls.  
minimum input impedance of 200 Kohms. When  
using one of the analog inputs for a voltage input, the  
input common at terminal 1 on TB1:B should be used  
for shields.  
When using an analog input as a milliamp input,  
the (-) side of the input (terminal 4 for Analog Input  
#1 or terminal 6 for Analog Input #2) should be  
connected to the common of the milliamp current  
source. The milliamp source should be connected to  
the (+) input (terminal 3 for Analog Input #1 or  
terminal 5 for Analog Input #2).  
A
B
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9 10  
9 10  
A
B
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9 10 11 12 13 14  
9 10 11 12 13 14  
A
B
1
1
2
2
3
3
4
4
TB1  
TB2  
TB3  
Figure 4: Assignments of the DFS-1 terminals. There are default assignments, but any of the analog and digital inputs  
and outputs (except the motor connections, power supplies, commons, emergency stop input, and frequency input) may be  
changed by setup.  
Page 8  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The default speed reference input is Analog  
Input #1, located on TB1:B. The default input is for  
a 0 to +10VDC for zero to full speed of the motor.  
Terminal 3 is the positive side of the input and  
terminal 4 is the negative side. If the speed signal  
being used is externally supplied, the differential  
input will have a noise cancelling effect. Terminal 1  
on TB1:B is a common for shields.  
Reference sources of +10VDC and -10VDC are  
supplied on the terminal strips at TB2:B2 and  
TB2:B7, respectively. The default speed pot connec-  
tions should be made as illustrated in figure 3. Notice  
that the (-) side of the differential input (terminal 4)  
is connected by a jumper to common (terminal 1),  
because the DFS-1 reference source is being used. If  
an external reference source is to be used, no jumper  
is necessary.  
4. Comm set (value is set via Communica-  
tions)  
5. Commanded speed  
Analog Output #1 default is a -10 to +10VDC  
signal representing motor speed. The outputs are on  
TB1:B terminals 8 (+) and 10 (-). The opposite  
polarity is available by a parameter change. See the  
description for parameters #26 and #27.  
The default for Analog Output #2, terminals 9  
(+) and 10 (-), is -10 to +10VDC representing motor  
load, 0% to 150% load. The opposite polarity is  
available by changing a parameter.  
The maximum output current for the analog  
outputs is 20 milliamps.  
FREQUENCY INPUT:  
IN THE DEFAULT SETUP, ONLY ANALOG  
INPUT #1 IS ACTIVE. WHILE THE OTHER  
ANALOG INPUT HAS A DEFAULT SETUP, IT IS  
NOT ACTIVE UNTIL THE USER CHANGES THE  
SETUP TO MAKE IT ACTIVE.  
The microprocessor will look ONLY to Analog  
Input #1 for speed information until it is told to do  
otherwise in the setup program.  
The other analog input to the DFS-1 is at TB1:B  
(lower level) terminals 5 (+) and 6 (-). Both of the  
inputs may be programmed for one of six inputs as  
shown in the table below.  
There is only one frequency input on the DFS-1.  
This input is used by the drive as the reference to  
follow when the drive is in the SLAVE Mode of  
operation. This input cannot be reassigned.  
If the DFS-1 is in the MASTER mode, it will  
ignore the frequency input.  
The Frequency input is located at TB2:A  
terminals 11(+) and 12 (-). This input is a differential  
line receiver type intended to interface directly with  
another DFS-1, a BCDMAX or CRM-1. There may  
be multiple slaves connected to a single Master by  
TB1:B  
(+) input term  
TB1:B  
(-) input term  
Input Signal Level  
-10 to +10 VDC  
jumper terms  
input impedance  
3
3
3
3
3
3
or 5  
or 5  
or 5  
or 5  
or 5  
or 5  
4 or 6  
4 or 6  
4 or 6  
4 or 6  
1
none **  
none **  
none **  
none **  
4 or 6 to 1  
4 or 6 to 1  
200 Kohms  
200 Kohms  
200 Kohms  
200 Kohms  
250 ohms  
250 ohms  
0
0
1
0
4
to +10 VDC  
to +5 VDC  
to +5 VDC  
to 20 mADC  
to 20 mADC  
1
** if the DFS-1 supplies are used, jumper 4 or 6 to 1 to establish the reference common.  
ANALOG OUTPUTS:  
daisy-chaining the frequency reference line. The last  
slave on the line should have the jumper at JP1 on the  
two rightmost pins. This inserts a terminating  
resistor at the end of the line to help eliminate  
electrical noise from the system. All others should  
be on the two leftmost pins.  
Contact POWERTEC’s Application Engineering  
Department before trying to use another type of  
frequency on this input.  
There are two analog outputs on TB1:B. Each of  
the outputs may be programmed in several ways:  
1. Disabled  
2. Actual speed (value is proportional to motor  
speed)  
3. Load output (value is proportional to motor  
load)  
Page 9  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FREQUENCY OUTPUT:  
DIGITAL INPUTS:  
There are two outputs available to supply a  
frequency for external use.  
There are eight digital control inputs on TB2:A  
as well as a +24VDC supply (TB2-A14) and com-  
mon (TB2-A1). The eight inputs are optical isolator  
input diodes with a common cathode connection at  
TB2-A2. When the +24VDC, DFS-1 supply is used  
to power the inputs, TB2:A2 must be jumpered to  
the 24VDC common terminal on TB2:A1.  
The functions of all inputs are programmable  
except Emergency Stop (TB2-A3). All digital inputs  
are electrically isolated from the DFS-1 power  
supplies and common when an external power supply  
is used to power the digital inputs (such as from a  
PLC).  
The first is located at TB2:B terminal 10 (+) and  
11 (-). This is an output which is intended to provide  
a reference frequency input for another DFS-1,  
BCDMAX or CRM-1. This output is not compatible  
with the DIGIMAX. It will provide a signal of +/-  
1.5V minimum when connected to another DFS-1's  
reference frequency input. This output on a unit  
configured as a master, operates at 16 times the  
frequency of the motor speed output reference. There  
is a 120 ohm termination resistor built into the output  
for transmission line termination.  
When operating the DFS as a slave, the output  
frequency is internally divided by 16 in addition to  
being multiplied by the set ratio from the slave. As a  
consequence, the frequency output from a DFS slave  
cannot be used as the reference to another DFS slave  
without some way of first multiplying this frequency  
by 16. POWERTEC’s Cascade Ratio Multiplier  
option board (4001-153430-XXX) can be used for  
this purpose. Contact the factory for any frequency  
following application which requires a reference  
source other than a master DFS.  
The default parameter setup is for a set of  
standard motor controller input connections on  
TB2:A terminal strip (see figure 3 on page 3).  
Five of the inputs are set up for standard push-  
button operation of the DFS-1. They are:  
Run  
Preset  
UP (increase)  
DOWN (decrease)  
Reverse  
4 (+)  
5 (+)  
6 (+)  
7 (+)  
8 (+)  
All of these inputs are referred to TB2-A2. Note  
that TB2-A2 (the common cathode connection) must  
The other frequency output is at TB2:B13. This  
is a 24VDC peak square wave referenced to the DFS- be jumpered to common (TB2:A1) in the basic  
1 common (TB2:B14). This signal is at the motor  
speed output reference frequency and may be used  
to interface with a DIGIMAX or a BLDC motor  
control. This output sources a maximum of 10mA  
and can sink 30mA.  
connections.  
Each of these inputs will take a +24VDC input  
(no more than 30VDC, not less than 18VDC). If an  
external source of +24VDC is used, TB2-A2 on the  
upper level must be connected to the negative side of  
the external source.  
Mode of Operation:  
Number of receivers:  
Maximum Cable Length:  
Maximum Frequency:  
Common Mode Voltage:  
maximum  
Driver Output:  
Driver Load:  
Driver Short Circuit: 1  
Driver Output Resistance:  
Receiver Input Resistance:  
Receiver Sensitivity:  
differential  
32 maximum  
4000 feet  
10 Megahertz  
+12V, -7V  
B
+/-1.5V minimum  
60 ohm minimum  
50 mA to ground  
120 ohms (ON)  
12 Kohms  
+/-200 mA  
Figure 5: Slaving DFS-1 units with the Reference Frequency Output.  
Page 10  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The programmable inputs (TB2-A4 through  
TB2-A10) may be programmed for jog, thread, or  
other preset speeds. The inputs may also be used to  
change torque levels, trim values, or ramp rates. Any  
value which can be affected by a parameter can be  
changed by a digital input.  
COMMUNICATIONS:  
The standard communications for the DFS-1 is  
the EIA standard RS-485 communications format  
over a single twisted pair cable into TB3:A terminals  
1 and 2. Terminal 3 is for the shield. DO NOT  
CONNECT TERMINAL 3 TO GROUND! Maxi-  
mum allowable distance for twisted pair operation is  
4000 meters (about 12,000 feet). Maximum nodes  
without repeaters is 32. Maximum communications  
rate is 38.4 kilobaud. The last unit on the comm line  
should have a jumper at JP2 on the rightmost 2 pins.  
All other units should have the jumper on the  
leftmost two pins.  
DIGITAL OUTPUTS:  
Digital outputs are located on TB2:B. The four  
outputs are normally open relay contacts. The  
contacts are rated at 120VAC at 1 amp, resistive.  
The default setup assigns the outputs as follows:  
Digital Out #1  
Digital Out #2  
Digital Out #3  
Digital Out #4  
Run  
No Fault  
At Speed  
Reverse  
There is an RS-485 local programming input at  
TB3:B for an optional keypad display unit.  
These assignments may be changed by parameters.  
All of the digital outputs are programmable and  
may be configured as Normally Open or Normally  
Closed. If more than one contact is required for a  
certain function, an external relay may be used, or  
more than one output may be programmed for the  
same function.  
RS485 Communications Connections:  
Most host or converter devices (including the  
RS232/485 converter made by POWERTEC) include  
1.2 Kohm pull up resistors which insure rx-tx- is  
pulled down to ground and rx/tx+ is pulled up to +5V  
when the line is inactive (tristated). This ensures the  
high impedance (floating) line does not change state  
due to noise when the line is not being driven. No  
matter how many units are connected in the network,  
only one such set of pull ups should be installed.  
NOTE: The Allen Bradley RS485 connections  
on their coprocessor module for the Series 5 PLCs do  
not provide these pull ups and must be installed or  
noise will prevent proper communications.  
TB1A-8  
1.2K ohm  
tx/rx+  
tx/rx-  
TB3A-1  
TB3A-2  
1.2K ohm  
TB3A-4  
Page 11  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE WAS INTENTIONALLY LEFT BLANK.  
Page 12  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEFAULT S ETUP  
The concept behind the DFS-1 calls for fully  
programmable inputs and outputs. The ability to  
change analog and digital inputs and outputs at will  
lends a whole new meaning to the word "flexibility".  
POWERTEC has established a set of "default"  
parameters which will leave the setup of the DFS-1  
in a way that will operate a motor in the basic  
configuration (see figure 3 on page 3 and figure 4 on  
page 4). There are two good reasons for doing this:  
1. This default setup allows the user to connect  
and operate a motor using common, everyday  
connections without having to program the DFS-1  
prior to its initial use.  
2. The default setup provides a baseline to  
which the user can return if it appears that something  
is wrong with either the user's setup or the motor  
control. There is a command which allows the "reset"  
of the setup to the default configuration.  
Page 13  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE WAS INTENTIONALLY LEFT BLANK.  
Page 14  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 .0 S PECIFICATIONS  
5.0 Each of the two inputs may be set up one of  
six ways:  
P OWER S UP P LIES  
1.  
2.  
3.  
4.  
5.  
6.  
-10 to +10  
0 to +10  
0 to 5  
1 to 5  
0 to 20  
4 to 20  
VDC  
VDC  
VDC  
VDC  
mADC  
mADC  
+24VDC • Available at TB2:A14, and TB2:B1.  
The combination is fused at 250 milliamps  
(mA). The fuse is self-healing.  
The opening of the fuse alerts the micro-  
processor.  
These supplies should only be used for  
push-buttons, relays, PLC outputs, etc.  
which interface directly with the DFS-1.  
They should not be used as general pur-  
pose supplies.  
6.0 Setup is by parameter selection (#18 for  
Analog Input #1 and parameter #22 for Analog  
Input #2).  
7.0 Voltage inputs are a differential input connec-  
tion.  
8.0 Input impedance of each input in voltage input  
mode is 200 Kilohms minimum.  
9.0 Input impedance in milliamp input mode is  
250 ohms.  
+10VDC • Reference supply available at TB1:B2.  
This output is rated at 100mA. This out-  
put is current limited and thermally pro-  
tected.  
Factory default setups are included so that the  
DFS-1 does not have to be programmed prior to its  
initial use. Factory defaults are only one of the many  
ways the DFS-1 can be set up.  
-10VDC • Reference supply available at TB1:B7.  
This output is rated at 100mA, current  
limited and thermally protected.  
+5VDC • Supply for motor encoder available at  
TB1:A9. This supply is fused at 100mA  
with a self-healing fuse. When the fuse  
opens, it alerts the microprocessor.  
Default setups are as follows:  
INPUT  
SETUP  
FUNCTION  
1.  
2.  
0 to +10VDC  
-10 to +10VDC General Purpose Input  
Speed Reference Input  
THIS SUPPLY IS FOR THE MOTOR ENCODER  
ONLY!  
ANALOG OUTPUTS  
1.0 There are two analog outputs on TB1:B.  
2.0 The analog outputs may be programmed for  
one of five modes:  
ANALOG INPUTS  
2.1 Disabled  
1.0 There are two analog inputs on TB1:B. (see  
section 1.2, page 4)  
2.0 Each input may be set up in one of several  
modes.  
3.0 Pre-programmed modes are:  
3.1 General purpose Input  
2.2 Motor Speed Output -10 to +10VDC  
= 0 to 100% (Actual Motor Speed)  
Default - Analog Output #1  
2.3 Motor Load Output -10 to +10VDC  
= 0 to 150%  
Default - Analog Output #2  
3.2 Speed Reference Input  
2.4 Set by Communications Link  
2.5 Commanded Motor Speed  
3.0 Output impedance is less than 100 ohms.  
4.0 Maximum output voltage is +/- 10VDC.  
5.0 Maximum current is 25mADC.  
3.3 Trim (dancer or load cell) Input  
3.4 External Motoring Torque Limit  
3.5 External Regenerative Torque Limit  
3.6 Horsepower Mode  
4.0 The mode of the input is set by parameter (#17  
for Analog Input #1 and parameter #21 for  
Analog Input #2).  
Page 15  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FREQUENCY INPUTS AND  
OUTPUTS  
DIGITAL INPUTS  
The eight digital inputs of the DFS-1 are  
optically coupled requiring +24VDC (+/-6VDC) at  
about 5mA each. These inputs are isolated from the  
common of the board.  
There is one frequency input and there are two  
frequency outputs available.  
All inputs are programmable as to function,  
EXCEPT the EMERGENCY STOP input. Inputs #1  
through #7 may be assigned as general purpose  
inputs.  
INPUT  
#1 REFERENCE FREQUENCY INPUT  
TB2:A Terminals 11 (+) and 12 (-).  
This is a line receiver type input which must be  
driven by a differential line driver output.  
This frequency input requires a frequency 16  
times the feedback from the motor.  
The feedback from the motor is normally 120  
PPR for 4 pole motors and 240 PPR for 8 pole  
motors.  
The defaults are as follows:  
TB2:A terminal 3(+)  
Emergency Stop  
(Cannot be reassigned)  
DI 1. TB2:A4(+)  
Run  
DI 2. TB2:A5(+)  
DI 3. TB2:A6(+)  
DI 4. TB2:A7(+)  
DI 5. TB2:A8(+)  
DI 6. TB2:A9(+)  
DI 7. TB2:A10(+)  
Preset Speed  
Up (Increase)  
Down (Decrease)  
Reverse  
Frequency Mode  
Local/Remote  
Normal input is 56 Kilohertz for 0 to full speed  
for a 1750 RPM motor with a 120ppr encoder.  
Terminal 13 is for the shield. Do not ground  
terminal 13 directly. It is internally terminated.  
OUTPUTS  
Inputs #1 through #7 may also be programmed  
for inverted input, i.e., active when input is low.  
#1  
REFERENCE FREQUENCY OUTPUT  
TB2:B Terminals 10 (+) and 11 (-),  
This is a differential line driver output which  
must be used with a differential line driver input.  
This frequency output is 16 times the reference  
frequency to the motor.  
DIGITAL OUTPUTS  
There are four dry contact outputs from the  
DFS-1. All of these outputs are on TB2:B. All  
outputs are programmable as to function, and all  
outputs may be set up as either normally open or  
normally closed.  
This output may drive up to 32 receivers.  
Connect the shield to terminal 12. This will  
ground the shield internally.  
#2  
MOTOR SPEED FREQUENCY OUTPUT  
TB2:B Terminals 13 (+) and 14 (common),  
Each relay output has a single, isolated, contact  
output which may be programmed as normally open  
or normally closed, with the contact rated at 1 Amp,  
125VAC resistive.  
The default assignments are as follows:  
DO 1. TB2:B terminals 2 and 3 Run relay contact  
Closed while running  
DO 2. TB2:B terminals 4 and 5 No fault relay  
Closed while no faults  
DO 3. TB2:B terminals 6 and 7 At Speed relay  
Closed when at speed  
This output is a +24VDC peak square wave at  
the motor feedback pulse rate, which is 2 times  
RPM for 4 pole motors and 4 times RPM for 8  
pole motors.  
The reference frequency input and output are  
capable of receiving and sending at up to 1 Mega-  
hertz.  
Motor Speed output emits frequencies up to 100  
Kilohertz.  
DO 4. TB2:B terminals 8 and 9 Remote Mode  
Closed when in Remote  
Page 16  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATIONS  
Standard: RS-485  
Data Rates: 300, 600, 1200, 2400, 4800, 9600,  
19.2K, and 38.4K baud  
Addresses: 1 to 255  
Protocols: POWERTEC Binary protocol  
Distance: 4000 meters (about 12,000 feet)  
maximum with twisted pair shielded  
cable  
Nodes:  
32 maximum  
Page 17  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE WAS INTENTIONALLY LEFT BLANK.  
Page 18  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3 .0 DFS -1 P ARAMETERS  
DFS-1 parameters are stored as DOUBLE  
rate set up in parameter #2. The parameter selects  
WORD values (32 bits), regardless of the actual size  
of the data. This method is used to simplify the entire  
system at a cost of a little extra data storage.  
A double word consists of four BYTES (8 bits).  
Each byte is a hexadecimal (base 16) value which  
ranges from 00h (0 decimal) to FFh (255 decimal).  
The largest number used in the DFS-1 parameters is  
99,999 decimal, which, in hexadecimal notation is  
0001 869Fh.  
from among eight industry standard baud rates:  
NUMBER BAUD RATE  
0000 0000h 38.4 Kilobaud (38,400 baud)  
. . . . 01 19.2 Kilobaud (19,200 baud)  
. . . . 02 9,600 baud  
. . . . 03 4,800 baud  
. . . . 04 2,400 baud  
. . . . 05 1,200 baud  
In many cases, information other than numbers  
is passed and stored in the parameters. The left byte  
is the most significant and the last byte is the least  
significant. The arrangement of the bytes for this  
purpose is: VL4 VL3 VL2 VL1 where VL4 is the  
Most Significant Bit (MSB) and VL1 is the Least  
Significant Bit (LSB). Each parameter breaks down  
the bytes accordingly.  
. . . . 06 600 baud  
. . . . 07 300 baud  
3.  
LOCAL / REMOTE CONTROL  
USE PARAMETER #3 TO SET UP WHICH  
FUNCTIONS ARE CONTROLLED REMOTELY.  
RANGE OF VALUES: 0000 0000h to 0000 007Fh  
0 to 127 (decimal)  
All four bytes are required in communications. A  
number which must be either 0 or 1 must be passed  
as either 0000 0000h or 0000 0001h.  
Default Value: 0000 0000h  
0 (decimal)  
Parameter #3 is first broken down into bytes, and  
then VL1 is further broken down into bits.  
When broken down into bits, 00h = 0000 0000b,  
and 7Fh = 0111 1111b.  
1.  
UNIT ID  
USE PARAMETER #1 TO IDENTIFY THE AD-  
DRESS OF THE UNIT ON A NETWORK.  
RANGE OF VALUES: 0000 0001h to 0000 00FFh  
1 to 255 (decimal)  
VL4 is always 00h.  
VL3 is always 00h.  
Default Value: 0000 0001h  
1 (decimal)  
VL2 is always 00h.  
VL1 is broken down into eight bits, which are  
numbered from right to left: 7654 3210h.  
The Unit ID number is installed in parameter #1.  
This serves as an address on the external communica-  
tions link. Two DFS-1 units cannot have the same  
address while installed on the same communications  
link.  
There are 254 possible addresses if the default  
value of 1 is not used as an address. Since the default  
value is 1, there could be a problem if a new unit is  
installed without changing the #1 parameter.  
Functions are assigned as follows:  
Bit Position Function  
7
6
5
4
3
2
1
0
NOT USED  
Master/Slave (not presently functional)  
Frequency Mode  
Reverse  
Down  
Up  
Preset  
Run  
2.  
BAUD RATE  
USE PARAMETER #2 TO SET THE COMMUNI-  
CATIONS SPEED OF THE NETWORK.  
RANGE OF VALUES: 0000 0000h to 0000 0007h  
0 to 7 (decimal)  
A zero in a bit position means that function may  
be controlled from an input terminal assigned to it. A  
one in a bit position means that the function may  
only be controlled via a communications link, such as  
the operator’s station connection or the external RS-  
485 communications link.  
Default Value: 0000 0002h  
2 (decimal)  
This establishes the rate at which data is ex-  
changed in the communications link. Every DFS-1 in  
the communications link must have the same baud  
For instance, if VL1 is given a value of 01 (0000  
Page 19  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
0001b) , the Run FUNCTION cannot be controlled  
from the terminal strip, but can only be controlled  
through the external communications link or the local  
comm link (keypad display unit).  
If VL1 has a value of 73 (0111 0011b), all  
functions except UP and DOWN are controlled  
remotely.  
5.  
MODES OF OPERATION  
USE PARAMETER #5 TO SET UP MASTER/  
SLAVE AND TORQUE LIMITING MODES.  
RANGE OF VALUES: 0000 0000h to 0003 0002h  
no decimal significance  
Default Value: 0000 0000h  
no decimal  
significance  
NOTE: Parameter #3 ONLY determines  
whether a FUNCTION is controlled locally or  
remotely. This parameter has nothing to do with the  
assignment of functions to terminals.  
Any input function can be assigned to any input  
terminal with the exception of the Emergency Stop  
input. The Emergency stop function is hard-wired on  
the DFS-1 board and cannot be changed by either  
programming or parameters.  
This parameter is a dual purpose command used  
to set operational modes of the DFS-1:  
VL2 VL1 sets the basic operation of the board.  
There are three modes of basic operation used to  
determine where the speed and/or torque commands  
originate:  
0000h MASTER mode (the board generates its  
own speed/torque based on its parameters)  
0001h SLAVE mode (the board follows an  
external signal in direct proportion)  
0002h INVERSE Slave mode (board follows  
an external signal in inverse  
If the RUN function is assigned to an input  
terminal, and this parameter is set to remote the RUN  
function control, the terminal will be IGNORED.  
4.  
COMMUNICATIONS  
PROTOCOL  
proportion)  
The DFS-1 board in MASTER mode generates  
its own speed and torque commands.  
USE PARAMETER #4 TO IDENTIFY THE NET-  
WORK COMMUNICATIONS LANGUAGE.  
RANGE OF VALUES: 0000 0000h to 0000 0001h  
0 to 1 (decimal)  
In SLAVE mode the board follows a reference  
frequency at TB2:A terminals 11(+) and 12(-), which  
should be nominally 16 times the desired speed of the  
motor. This signal is available from another DFS-1  
board or from a BCDMAX board. It may also come  
from another source which has a compatible line  
driver output. (See the description for frequency  
input elsewhere in this manual).  
In INVERSE slave mode, the board follows the  
external frequency in a proportion of 1/RATIO.  
Instead of setting a direct ratio of 0.5000, a ratio of  
2.0000 may be entered for half speed. This is useful  
in cases requiring draw settings where the slave is  
physically located before the master, which is set for  
line speed.  
Default Value: 0000 0000h  
0 (decimal)  
At the present time, the only communications  
protocol available is Powertec’s Binary protocol.  
This parameter has been included with the intent of  
providing alternative protocols at some time in the  
future.  
VL4 VL3 contains information on modified  
operational modes in which the torque in the motor is  
limited below the current limit level (current limits  
are always set by parameters 44 and 45). These  
optional modes are defined as follows:  
Page 20  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
0000h Normal current limits (motor current  
not limited at a lower level)  
7.  
ENCODER PULSES PER  
REVOLUTION  
0001h Motoring torque setpoint (motoring  
current to be limited at a lower level)  
0002h Regenerative torque setpoint (regenera-  
tive current to be limited at a lower  
level)  
0003h Horsepower setpoint (the product of  
motor current and motor speed is  
limited)  
USE PARAMETER #7 TO ESTABLISH THE  
PULSE FEEDBACK RATE FROM THE MOTOR.  
RANGE OF VALUES: 0000 0001h to 0000 4E20h  
1 TO 20,000 (decimal)  
Default Value: 0000 0078h  
120 (decimal)  
This parameter tells the DFS-1 the resolution of  
the encoder in Pulses Per Revolution (PPR). This is  
normally four times (4X) the rate of one channel of  
the motor’s encoder.  
Motors from the 42 frame through the 259T  
frame have a 30 PPR, two channel, quadrature  
internal encoder. For these motors using the internal  
encoders the parameter should be set to 120 PPR.  
Motors from 287TZ through 5010ATZ have an  
internal 60 PPR, two channel, quadrature encoder.  
The parameter for these motors using the internal  
encoders should be set to 240 PPR.  
External encoders may have almost any PPR  
rate, and they must have two channels in quadrature  
(the channels have the same pulse rate, but they are  
90° out of phase with each other). The pulse rate will  
be on the ENCODER nameplate.  
0004h through 000Fh available for future use  
When in the normal mode, the current in the  
motor is not controlled below current limit.  
If one of the modified operational modes is  
chosen, the torque/horsepower setpoint is selectable  
in one of three places:  
1. Analog Input #1 (must be set up in  
parameter #17)  
2. Analog Input #2 (must be set up in  
parameter #21)  
3. The Set Application Mode (8F)  
Command via communications  
If one of these three setpoints is not present, the  
setpoint defaults to the appropriate current limit  
level.  
Encoders with higher pulse rates are normally  
used to obtain lower speeds and/or finer resolution of  
motor shaft position. The most common external  
encoder on POWERTEC motors is a 600 PPR, two  
channel, quadrature optical encoder. For this encoder  
the PPR in this parameter will be 2400.  
For other encoders, multiply the pulse rate for  
one channel (the usual number given on the name-  
plate) by four and enter that number in this param-  
eter.  
This parameter may not be changed while  
running. Attempting to change this parameter while  
running will result in the effect being delayed until  
the next time a setpoint command is given or until  
the control is stopped. Changing this number will  
drastically affect the calibration of the system.  
(Also see Parameter 46)  
6.  
MAXIMUM MOTOR SPEED  
USE PARAMETER #6 TO SET THE ABSOLUTE  
MAXIMUM MOTOR SPEED.  
RANGE OF VALUES: 0000 0001h to 0000 2710h  
1 TO 10,000 (decimal)  
Default Value: 0000 06D6h  
1750 (decimal)  
The maximum motor speed parameter is set  
directly in Revolutions Per Minute (RPM) once the  
Encoder Pulses Per Revolution (PPR) is set in  
parameter # 7. If the incorrect PPR is set in param-  
eter #7, the maximum motor speed will not be correct  
and the motor may overspeed or not be able to go fast  
enough.  
The maximum motor speed is normally the  
number given on the nameplate of the motor. This  
number may be set higher than the motor nameplate  
in some situations because the Brushless DC motor is  
capable of some overspeed with light loads.  
This parameter may be set to a value which is  
lower than the motor’s base speed in cases where it is  
not desired to use the full speed of the motor.  
Page 21  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.  
MAS TER RAMP UP TIME  
10.  
S LAVE RAMP UP TIME  
USE PARAMETER #8 TO SET THE TIME TO  
RAMP FROM ZERO TO FULL SPEED.  
RANGE OF VALUES: 0000 0001h to 0003 E418h  
1 TO 255,000 (decimal)  
USE PARAMETER #10 TO SET THE UP RAMP  
TIME WHEN THE RATIO IS CHANGED.  
RANGE OF VALUES: 0000 0001h to 0003 E418h  
1 TO 255,000 (decimal)  
Default Value: 0000 2710h  
10,000 (decimal)  
Default Value: 0000 2710h  
10,000 (decimal)  
This is the acceleration time from zero speed to  
full speed in the MASTER mode. The time may be  
set from 1 millisecond (.001 sec.) to 255 seconds.  
The default is 10 seconds (10,000 mSec).  
The acceleration rate is calculated from zero to  
maximum motor speed (parameter 6). This rate is  
used when the speed command in MASTER mode is  
changed from a lower speed (including 0) to a higher  
speed.  
If the change in speed is from zero speed to full  
speed, the full amount of time will be used. If the  
change is from 25% speed to 75% speed, it will take  
1/2 of the time set in this parameter to reach the new  
speed. If the change is from 80% speed to 90%  
speed, it will take 1/10th the time in this parameter.  
The acceleration rate does not affect the JUMP  
UP change in speed.  
This is the acceleration rate in the SLAVE mode.  
The rate may be set from 1 millisecond (.001 sec.) to  
255 seconds. The default is 10 seconds (10,000  
mSec).  
This parameter sets a rate determined by the  
amount of time it takes to change from a ratio of  
0.0000 to a ratio of 1.0000. This rate is used when-  
ever the ratio setpoint in the SLAVE or INVERSE  
SLAVE mode is changed from a lower ratio (includ-  
ing 0) to a higher ratio.  
This rate does not affect the rate at which the  
DFS-1 responds to changes in the reference fre-  
quency, nor does it affect the ratio when the drive is  
started as a slave if parameter #54 is set to Freeze.  
This rate does not affect the Slave JUMP UP  
time.  
11.  
S LAVE RAMP DOWN TIME  
9.  
MAS TER RAMP DOWN TIME  
USE PARAMETER #11 TO SET THE down RAMP  
TIME WHEN THE RATIO IS CHANGED.  
RANGE OF VALUES: 0000 0001h to 0003 E418h  
1 TO 255,000 (decimal)  
USE PARAMETER #9 TO SET THE TIME TO  
RAMP FROM FULL TO ZERO SPEED.  
RANGE OF VALUES: 0000 0001h to 0003 E418h  
1 TO 255,000 (decimal)  
Default Value: 0000 2710h  
10,000 (decimal)  
Default Value: 0000 2710h  
10,000 (decimal)  
This is the deceleration rate in the SLAVE mode.  
The rate may be set from 1 millisecond (.001 sec.) to  
255 seconds. The default is 10 seconds (10,000  
mSec).  
This parameter sets a rate determined by the  
amount of time it takes to change from a ratio of  
1.0000 to a ratio of 0.0000. This rate is used when-  
ever the ratio setpoint in the SLAVE or INVERSE  
SLAVE mode is changed from a higher ratio to a  
lower ratio (including 0).  
This rate does not affect the rate at which the  
DFS - 1 responds to changes in the reference  
frequency, nor does it affect the ratio when the drive  
is stopped as a slave if parameter #54 is set to Freeze.  
This rate does not affect the slave JUMP time.  
This is the deceleration rate in the MASTER  
mode. The rate may be set from 1 millisecond (.001  
sec.) to 255 seconds. The default is 10 seconds.  
The rate is calculated from maximum speed  
(parameter 6) to zero speed. This rate is used  
whenever the speed command in the MASTER mode  
is changed from a higher speed to a lower speed  
(including 0).  
If the change in speed is from full speed to zero  
speed, the full amount of time will be used. If the  
change is from 75% speed to 25% speed, it will take  
1/2 of the time set in this parameter to reach the new  
speed. If the change is from 80% speed to 90%  
speed, it will take 1/10th the time in this parameter.  
The deceleration rate does not affect the JUMP  
DOWN change in speed.  
Page 22  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
tionship between motor speed and EGU is defined in  
parameter #14, which sets the value of EGU’s at full  
motor speed. This parameter is used to determine the  
relationship between units of commanded speed and  
RPM. The number entered in this parameter is  
equivalent to the number in parameter #6. This  
allows the user to enter speed commands in engineer-  
ing units (such as Feet Per Minute, Yards Per Minute,  
etc).  
Speed commands entered by commands #82 and  
#84 are entered in terms of this parameter. If the  
value of this parameter is the same as the value of  
parameter #6, then there is a 1:1 relationship between  
the Engineering Units and the RPM (i.e., enter 1750  
(06D6h) as a speed command for 1750 RPM).  
However, if this parameter is set to 1000  
12.  
MAS TER P RES ET S P EED  
USE PARAMETER #12 TO SET A PRESET SPEED  
WHICH CAN BE TOGGLED IN AND OUT.  
RANGE OF VALUES: 0000 0000h to 0000 2710h  
0 TO 10,000 (decimal)  
Default Value: 0000 00C8h  
100 (decimal)  
The MASTER preset speed is the speed to which  
the motor will go when a PRESET input is activated  
on one of the Digital inputs (any of the seven digital  
inputs may be programmed as a PRESET input)  
when the DFS-1 is in the MASTER mode. If more  
than one input is programmed as a PRESET input,  
they must both be present to activate the PRESET  
Speed function (the inputs are logically ANDed).  
(03E8h) and #6 is set to 1750, then the relationship is  
1:1.75. Entering 1000 (03E8h) as a command results  
in 1750 RPM, but entering 500 (01F4h) results in  
875 RPM.  
13.  
SLAVE RATIO PRESET  
USE PARAMETER #13 TO SET A PRESET RATIO  
WHICH CAN BE TOGGLED IN AND OUT.  
RANGE OF VALUES: 0000 0000h to 0001 869Fh  
0 TO 99,999 (decimal)  
15.  
BASE RATIO  
USE PARAMETER #15 TO SET THE “GEAR  
RATIO” OF THE MOTOR IN A SLAVE SYSTEM.  
RANGE OF VALUES: 0000 0001h to 0001 869Fh  
1 TO 99,999 (decimal)  
Default Value: 0000 2710h  
10,000 (decimal)  
The SLAVE preset ratio is the ratio to which the  
motor will go when a PRESET input is activated on  
one of the Digital inputs (any of the seven digital  
inputs may be programmed as a PRESET input)  
when the DFS-1 is in the SLAVE mode. If more than  
one input is programmed as a PRESET input, they  
must both be present to activate the PRESET Speed  
function (the inputs are logically ANDed).  
Note: For all ratio setpoints, 4 decimal places  
are implied. Therefore, the maximum ratio setpoint  
is 9.999.  
Default Value: 0000 2710h  
10,000 (decimal)  
This is the “gearing” ratio which corrects for the  
mechanics of the system and also for differences in  
motor speeds. The output frequency at TB2:B  
terminals 10 (+) and 11(-) is determined by the  
settings of the maximum motor speed (parameter #6)  
and the encoder PPR (parameter #7). The output  
frequency will be:  
Output Reference Frequency = Motor max RPM  
x Encoder PPR x 16 / 60  
14.  
ENGINEERING UNITS  
USE PARAMETER #14 TO SET THE ENGINEER-  
ING UNITS AT MAXIMUM MOTOR SPEED.  
RANGE OF VALUES: 0000 0001h to 0001 869Fh  
1 TO 99,999 (decimal)  
A 1750 RPM motor with a 120 PPR encoder  
puts out a reference frequency of 56 Kilohertz. This  
frequency varies with the commanded speed. When  
this frequency is used as a reference, it is first  
multiplied by the base ratio, and then by the SET-  
POINT. These steps change the frequency to the  
proper level.  
Default Value: 0000 06D6h  
1750 (decimal)  
Engineering Units (EGU) define the relationship  
between motor speed or torque and process reference  
points. It allows setting and reading of parameters in  
terms other than speed and torque. The basic rela-  
For example, it is generally useful in a slave  
system to be able to enter a SETPOINT of 1.0000 on  
Page 23  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
the slave unit to match the line speed, motor speed,  
or section (master). Many times, however, the  
gearing between the slave motor and the surface of a  
roll is not the same as the master, or the diameter of  
the rolls vary from section to section, or motors of  
different RPM’s may have to be tracked. The BASE  
RATIO is a correction factor which allows the  
SETPOINT to be adjusted.  
The following are other examples of how the  
Base Ratio parameter is used: if a standard 2500  
RPM motor is to follow a standard 1750 RPM motor,  
and both motors must attain their full speed at the  
same time, and a setpoint of 1.0000 is desired, enter  
1.4826 (2500/1750) into parameter #15 to make the  
follower motor go 48.26% faster when the setpoint is  
1.0000.  
If the surface speed of a lead roll is 100 FPM at  
1750 RPM (4-pole motor, 120 PPR encoder), and the  
surface speed of the follower roll is 100FPM at 1550  
RPM (4-pole motor, 120 PPR encoder), enter 0.8857  
in parameter #15 to make the follower roll go  
88.57% of the speed of the lead when the setpoint is  
set to 1.0000.  
If the lead motor is a 100 HP, 1750 RPM (8-pole,  
240PPR), and the follower is a 5 HP, 3000 RPM (4-  
pole, 120 PPR) motor, the reference output frequency  
of the lead is 1750 x 240 *16 / 60 = 112 kHz. The  
follower motor needs a frequency of 3000 x 120 *  
16 / 60 = 96 kHz to operate at a 1.0000 setpoint.  
Therefore the maximum 112 kHz must be reduced to  
a maximum of 96 kHz by setting the base ratio to  
0.8571.  
are implied. Therefore, the maximum ratio setpoint  
is 9.999.  
17.  
ANALOG INPUT #1 MODE  
SELECT  
USE PARAMETER #17 TO SELECT THE PUR-  
POSE OF A SIGNAL AT ANALOG INPUT #1.  
RANGE OF VALUES: 0000 0000h to 0000 001Fh  
0 TO 32 (decimal)  
Default Value: 0000 0001h  
1 (decimal)  
Analog Input #1 is a general purpose input  
which may be programmed for one of several modes  
of operation. The mode affects how the signal is used  
for setting or changing of the motor’s speed and/or  
torque.  
The following modes are provided for:  
0000 0000h General Purpose Input - can be  
read via the COMM port  
0000 0001h Speed Reference input - Sets the  
speed of the motor (see below)  
0000 0002h Trim Input - may be used for  
dancer or other transducer input  
(not yet implemented)  
0000 0003h External Torque Limit, Motoring -  
Used in conjunction with param-  
eter #5  
0000 0004h External Torque Limit, Regenera-  
tive - Used in conjunction with  
parameter #5  
0000 0005h External Horsepower Limit - Used  
in conjunction with parameter #5  
0000 0006h to 0000 001Fh Undefined -  
Reserved for future use  
If the SETPOINT needs to be something other  
than 1.0000, make a proportional adjustment in the  
base ratio. If the desired SETPOINT is 2.0000, use a  
base ratio of 1/2 of the value necessary for a 1.0000  
setpoint.  
If an undefined mode (...06h through ...1Fh) is  
selected, Analog Input #1 will be inoperative.  
The type of input is selected by parameter #18.  
Each type of input has a lowest value and a highest  
value.  
The effective range of the input is set by param-  
eters #19 and #20. Parameter #19 sets the low  
threshold level and parameter #20 sets the highest  
effective level. These two levels are set in EGU (see  
parameter #14).  
16.  
MAXIMUM RATIO  
USE PARAMETER #16 TO SET THE HIGHEST  
ALLOWABLE RATIO IN A SLAVE SYSTEM.  
RANGE OF VALUES: 0000 0001h to 0001 869Fh  
1 TO 99,999 (decimal)  
Default Value: 0001 869Fh  
99,999 (decimal)  
Set the maximum ratio in the system if it is to  
be lower than the default, which is the absolute  
maximum.  
As a general purpose input ( ... 00h) Analog  
input #1 may be used by the program to sense any  
analog signal representing an external parameter for  
use by the program.  
Note: For all ratio setpoints, 4 decimal places  
Page 24  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
As a Speed Reference input ( ...01h), Analog  
input #1 sets the speed of the controlled motor  
directly if the DFS-1 is set up in Master Mode  
(parameter #5 - VL2 VL1).  
0000 0006h  
to 0000 001Fh  
Undefined - Reserved for  
future use  
If the DFS-1 is in SLAVE mode, Analog Input  
#1, when set to ...01h will act as a Ratio SETPOINT.  
The External Torque Limits are used to set limits  
on the motor current which are below the current  
limit level. When parameter #5 VL4 VL3 is set to 00  
01h, or 00 02h, Analog Input #1 may be set to ...03h  
or ...04h respectively to supply the torque limiting  
reference.  
If an undefined mode (...06 through ...1F) is  
selected, Analog Input #1 will be inoperative.  
Choosing the incorrect signal conditioning for  
the actual input signal will result in erratic operation.  
19.  
ANALOG INPUT #1 LOW  
ENGINEERING UNITS (EGU)  
The External Horsepower Limit sets the maxi-  
mum horsepower produced by the drive. Horsepower  
is the PRODUCT of speed and torque. When motor  
speed is low, motor current is high, and when speed  
is high, current is low. The drive increases speed until  
sufficient load is developed and the product of load  
and speed equals the setpoint. After that is achieved,  
increasing load reduces speed, and decreasing load  
increases speed.  
USE PARAMETER #17 TO SELECT THE  
THRESHOLD OF ANALOG INPUT #1 EFFECT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to +99,999(dec.)  
Default Value: 0000 0000h  
0 (decimal)  
(See Parameter 14 for the definition  
and purpose of EGU)  
Parameter #19 sets the threshold level for  
effectiveness of Analog Input #1 at the lowest signal  
level.  
Assume that the maximum speed of the 1750  
RPM motor is set to 12500 EGU’s in parameter #14  
(representing, perhaps, 125.00 RPM on an extruder  
screw) and the Analog input is set for a Speed  
Reference Input of 0 to +10VDC. The default value  
of parameter 19 is 0. This means that when 0VDC is  
present at Analog Input #1, the result will be zero  
speed.  
18.  
ANALOG INPUT #1 SIGNAL  
CONDITIONING  
USE PARAMETER #17 TO SELECT THE FORM  
OF THE SIGNAL AT ANALOG INPUT #1.  
RANGE OF VALUES: 0000 0000h to 0000 001Fh  
0 TO 32 (decimal)  
Default Value: 0000 0001h  
1 (decimal)  
Six types of signals will be accepted by Analog  
Input #1. Parameter #18 selects the form of signal to  
be processed.  
Now, if we want to set a minimum speed on this  
system, we can set a value of 500 in parameter #19.  
This means that when 0VDC is present at Analog  
Input #1, the motor will run at a speed of 500/12500  
or 4 percent (70 rpm) of the maximum speed of the  
motor. (see also parameter #20).  
The six types of signals are:  
0000 0000h  
-10VDC to +10VDC  
bipolar voltage input with zero  
center value  
0000 0001h  
0000 0002h  
0000 0003h  
0000 0004h  
0000 0005h  
0 to +10VDC  
unipolar voltage signal  
0 to +5VDC  
unipolar voltage signal  
1 to +5VDC  
unipolar voltage signal  
0 to 20mA  
unipolar current signal  
4 to 20mA  
unipolar current signal  
Page 25  
Revised 7/95  
POWERTEC Ind. Corp.©  
DFS-1 Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input may not be set up as a Speed Reference Input.  
Attempting to set up a second Analog Input as a  
Speed Reference Input when one is already set up in  
that mode will cause the second input to be inopera-  
tive.  
2 0 . ANALOG INPUT #1 HIGH  
ENGINEERING UNITS (EGU)  
USE PARAMETER #18 TO SELECT THE MAXI-  
MUM ANALOG INPUT #1 EFFECT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to +99,999 (dec.)  
22.  
ANALOG INPUT #2 SIGNAL  
CONDITIONING  
Default Value: 0000 06D6h  
1750 (decimal)  
(See Parameter 14 for the definition  
USE PARAMETER #17 TO SELECT THE FORM  
OF THE SIGNAL AT ANALOG INPUT #1.  
RANGE OF VALUES: 0000 0000h to 0000 001Fh  
0 TO 32 (decimal)  
and purpose of EGU)  
Parameter #20 sets the maximum level for  
effectiveness of Analog Input #1 at the highest signal  
level.  
Default Value: 0000 0000h  
0 (decimal)  
Assume that the maximum speed of the 1750  
RPM motor is set to 12500 EGU’s in parameter #14  
(representing, perhaps, 125.00 RPM on an extruder  
screw) and the Analog input is set for a Speed  
Reference Input of 0 to +10VDC. The default value  
of parameter 20 is 1750. This means that when  
10VDC is present at Analog Input #1, the resulting  
speed will be 1750/12500 = 14 percent of maximum  
speed, or 245 RPM.  
Now, if we want to set the maximum speed of  
this system at 100.00, we set a value of 10000 in  
parameter #20. This means that when 10VDC is  
present at Analog Input #1, the motor will run at a  
speed of 10000/12500 = 80 percent of the maximum  
speed of the motor, or 1400 RPM. (see also param-  
eter #19).  
See parameter #18. Signal conditioning selection  
for Analog Input #2 is identical to Analog Input #1.  
23.  
ANALOG INPUT #2 LOW  
ENGINEERING UNITS (EGU)  
USE PARAMETER #23 TO SELECT THE  
MAXIMUM ANALOG INPUT #2 EFFECT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to +99,999 (dec.)  
Default Value: 0000 0000h  
0 (decimal)  
Analog Input #2 works exactly the same way  
that Analog Input #1 works. Parameter #23 does for  
Analog Input #2 what parameter #19 does for Analog  
Input #1. Refer to parameter #19.  
21.  
ANALOG INPUT #2 MODE  
SELECT  
2 4 . ANALOG INPUT #2 HIGH  
ENGINEERING UNITS (EGU)  
USE PARAMETER #21 TO SELECT THE PUR-  
POSE OF A SIGNAL AT ANALOG INPUT #2.  
RANGE OF VALUES: 0000 0000h to 0000 001Fh  
0 TO 32 (decimal)  
USE PARAMETER #24 TO SELECT THE  
MAXIMUM ANALOG INPUT #2 EFFECT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to +99,999 (dec.)  
Default Value: 0000 0000h  
0 (decimal)  
Default Value: 0000 0000h  
0 (decimal)  
See parameter #17. The operation of Analog  
Input #2 is identical to the operation of Analog Input  
#1, EXCEPT the parameters which set the form of  
the input signal (#22) and low and high EGU’s ( #23  
and #24).  
Both Analog Inputs #1 and #2 may be set up as  
General Purpose Inputs, but all other modes are  
mutually exclusive. If one of the Analog Inputs is set  
up as a Speed Reference Input, the other Analog  
Analog Input #2 works exactly the same way  
that Analog Input #1 works. Parameter #24 does for  
Analog Input #2 what parameter #20 does for Analog  
Input #1. Refer to parameter #20.  
Page 26  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25.  
ANALOG OUTPUT #1 MODE  
SELECT  
27.  
ANALOG OUTPUT #1 HIGH  
ENGINEERING UNITS (EGU)  
USE PARAMETER #25 TO SELECT THE  
SOURCE OF A SIGNAL AT ANALOG  
OUTPUT #1.  
RANGE OF VALUES: 0000 0000h to 0000 0003h  
0 to 4 (decimal)  
USE PARAMETER #27 TO SELECT THE MAXI-  
MUM ANALOG OUTPUT #1 EFFECT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to +99,998 (dec.)  
Default Value: 0000 0001h  
1 (decimal)  
Default Value: 0000 06D6h  
1750 (decimal)  
Analog Output #1 may be programmed for  
several modes of operation. The mode affects where  
the signal at Analog Output #1 comes from. The  
following modes are provided for:  
If parameter #27 is greater on the absolute scale  
than #26, voltage at Analog Output #1 will be scaled  
proportionally from low EGU’s (parameter #26) to  
+10VDC at the high engineering units (parameter  
#27).  
If #27 is less than #26, then output sense is  
inverted, i.e., the higher voltage (from -10VDC to  
+10VDC) will be at the low EGU setting (#26) and  
the lower voltage will be at the high EGU setting  
(parameter #27).  
0000 0000h  
0000 0001h  
Disabled.  
Actual Speed - Represents the speed  
of the motor from 0 to parameter #14.  
Load Output - Represents the load on  
the motor from 0 to 1500.  
Analog Output voltage set by  
communications from parameters #26  
and #27.  
0000 0002h  
0000 0003h  
28. ANALOG OUTPUT #2 MODE  
SELECT  
0000 0004h Commanded Speed  
If an undefined mode (...05h through ...1Fh) is  
selected, Analog Input #1 will be inoperative.  
USE PARAMETER #28 TO SELECT THE  
SOURCE OF A SIGNAL AT ANALOG  
OUTPUT #2.  
RANGE OF VALUES: 0000 0000h to 0000 0003h  
0 to 4 (decimal)  
26. ANALOG OUTPUT #1 LOW  
ENGINEERING UNITS (EGU)  
USE PARAMETER #26 TO SELECT THE  
THRESHOLD OF ANALOG OUTPUT #1 EFFECT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to +99,998 (dec.)  
Default Value: 0000 0000h  
0 (decimal)  
Analog Output #2 is a general purpose analog  
output which may be programmed for one of several  
modes of operation. The mode defines the origin of  
the signal at Analog Output #2. The following modes  
are provided for:  
Default Value: 0000 0000h  
0 (decimal)  
Parameter #26 sets the point, in EGU’s, at which  
the Analog Output #1 will be -10VDC.  
0000 0000h Disabled.  
0000 0001h Actual Speed - Represents the speed  
of the motor from 0 to parameter #14.  
0000 0002h Load Output - Represents the load on  
the motor from 0 to 1500.  
0000 0003h Analog Output voltage set by commu-  
nications from parameters #29 and  
#30.  
0000 0004h Commanded Speed  
If an undefined mode ...05h through ...1Fh is  
selected, Analog Input #2 will be inoperative.  
Page 27  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29. ANALOG OUTPUT #2 LOW  
ENGINEERING UNITS (EGU)  
30. ANALOG OUTPUT #2 HIGH  
ENGINEERING UNITS (EGU)  
USE PARAMETER #29 TO SELECT THE  
THRESHOLD OF ANALOG OUTPUT #2 EFFECT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to +99,998 (dec.)  
USE PARAMETER #30 TO SELECT THE MAXI-  
MUM ANALOG OUTPUT #2 EFFECT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to +99,998 (dec.)  
Default Value: 0000 0000h  
0 (decimal)  
Default Value: 0000 0096h  
150 (decimal)  
(See Parameter 14 for the definition  
and purpose of EGU)  
Parameter #29 sets the point, in EGU’s, at which  
the Analog Output #2 will be -10VDC.  
If parameter #30 is greater on the absolute scale  
than parameter #29, the voltage at Analog Output #2  
will be proportionally scaled from the low EGU’s  
(#29) to +10VDC at the high engineering units  
(#30).  
If parameter #30 is less than parameter #29 on  
the absolute scale, then the sense of the output will be  
inverted, i.e., the higher voltage (on an absolute scale  
from -10VDC to +10VDC) will be present at the low  
EGU setting (parameter #29) and the lower voltage  
will be output at the high EGU setting (parameter  
#30).  
Low EGU  
0
High EGU  
+1750  
+1750  
+1750  
+1750  
+1750  
+1750  
+400  
Speed  
Vout  
-10  
0
0
1750 (FWD)  
1750 (REV)  
0
+10 VDC  
0 VDC  
0
-1750  
-1750  
-1750  
-100  
+400  
+1750  
0 VDC  
1750 (FWD)  
1750 (REV)  
0
+10 VDC  
-10 VDC  
-6 VDC  
+6 VDC  
+5 VDC  
-100  
0
0
875 (FWD)  
Table of Values for Analog Outputs  
Page 28  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
31.  
DIGITAL INPUT #1 FUNCTION  
32.  
DIGITAL INPUT #2 FUNCTION  
USE PARAMETER #31 TO SELECT THE #1  
DIGITAL INPUT FUNCTION.  
USE PARAMETER #32 TO SELECT THE #2  
DIGITAL INPUT FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
Default Value: 0001 0001h  
no decimal  
significance  
Default Value: 0001 0002h  
no decimal  
significance  
VL4 and VL2 are always 00. VL1 determines  
function of the input. The following are predefined:  
The setting options are the same as parameter  
#31. The default, by factory setting, is 0001 0002h,  
which is a preset input which must have +24VDC  
applied with respect to TB2:A1 to be active.  
00h  
01h  
02h  
03h  
04h  
05h  
06h  
07h  
08h  
09h  
0Ah  
0Bh  
0Ch  
General Purpose Input  
Run Input  
Preset Input  
Up Input  
Down Input  
Reverse Input  
Frequency Mode  
Remote Input  
Master/Slave (not functional at present)  
Jog  
Preset 2  
Contactor Aux  
through 0Fh Not Assigned, selection  
will cause input to be General Purpose  
Input.  
33.  
DIGITAL INPUT #3  
FUNCTION  
USE PARAMETER #33 TO SELECT THE #3  
DIGITAL INPUT FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
Default Value: 0001 0003h  
no decimal  
significance  
The setting options are the same as parameter  
#31. The default, by factory setting, is 0001 0003h,  
which is an UP (increase) input which must have  
+24VDC applied with respect to TB2:A to be active.  
Any digital input may be assigned to any  
function. The factory defaults are included for testing  
purposes, to provide a baseline setup, and to be able  
to run the DFS-1 the first time before programming.  
VL3 contains the polarity flag, which is either  
00h or 01h. A 01h setting means that +24VDC must  
be applied to the input to make it active. A 00h  
setting means the input is active with no voltage  
applied.  
A Digital Input may get its +24VDC signal from  
any source with TB2:A1 common, and may be any  
parameter, transducer, or switch at which the pro-  
gram or communications wishes to look.  
34. DIGITAL INPUT #4  
FUNCTION  
USE PARAMETER #34 TO SELECT THE #4  
DIGITAL INPUT FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
Default Value: 0001 0004h  
no decimal  
significance  
The default, by factory setting, is 0001 0001h,  
which is a run input which must have +24VDC  
applied with respect to TB2:A1 to be active.  
The setting options are the same as parameter  
#31. The default, by factory setting, is 0001 0004h,  
which is an DOWN (decrease) input which must  
have +24VDC applied with respect to TB2:A1 to be  
active.  
Page 29  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35.  
DIGITAL INPUT #5  
FUNCTION  
38.  
DIGITAL OUTPUT #1  
FUNCTION  
USE PARAMETER #35 TO SELECT THE #5  
DIGITAL INPUT FUNCTION.  
USE PARAMETER #38 TO SELECT THE #1  
DIGITAL OUTPUT FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
Default Value: 0001 0005h  
no decimal  
significance  
Default Value: 0001 0004h  
no decimal  
significance  
The setting options are the same as parameter  
#31. The default, by factory setting, is 0001 0005h,  
which is a reverse input which must have +24VDC  
applied with respect to TB2:A 1 to be active.  
VL4 and VL2 are always 00. VL3 determines  
the function of the output. The following have been  
predefined:  
00h  
01h  
02h  
03h  
04h  
05h  
06h  
07h  
08h  
General Purpose Output  
No Fault Output  
At Speed Output  
Remote Output  
Run Hold  
Zero Speed  
Set by comm  
Contactor  
through 0Fh - Not Assigned,  
selection will cause output to be  
General Purpose Output.  
36.  
DIGITAL INPUT #6  
FUNCTION  
USE PARAMETER #36 TO SELECT THE #6  
DIGITAL INPUT FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
Default Value: 0001 0006h  
no decimal  
significance  
ANY DIGITAL OUTPUT MAY BE ASSIGNED  
ANY FUNCTION. The factory defaults are included  
for testing purposes, to provide a baseline setup, and  
to be able to run the DFS-1 the first time.  
VL3 contains the sense flag, which is either 00h  
or 01h. A 01h setting means that contact between the  
output terminals will be closed when the output  
function is active (a normally open contact). A 00h  
setting in VL3 means that the contact will be closed  
when the function is not active (a normally closed  
contact).  
The setting options are the same as parameter  
#31. The default, by factory setting, is 0001 0006h,  
which is the frequency mode input which must have  
+24VDC applied with respect to TB2:A 1 to be  
active.  
37.  
DIGITAL INPUT #7  
FUNCTION  
USE PARAMETER #37 TO SELECT THE #7  
DIGITAL INPUT FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
A General Purpose Output may be controlled by  
the program or communications.  
The default, by factory setting, is 0001 0004h,  
which is a run output which is a closed output contact  
when the run is active (true). This is normally used as  
a run hold contact, but it may be used as a run output  
contact for some other purpose if the run signal is  
maintained, rather than a momentary push-button.  
Default Value: 0001 0007h  
no decimal  
significance  
The setting options are the same as parameter  
#31. The default, by factory setting, is 0001 0007h,  
which is a local/remote input which must have  
+24VDC applied with respect to TB2:A 1 to activate  
remote.  
Page 30  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
which is the REMOTE output. When the DFS-1 is in  
the remote mode, the contact between the terminals  
closes (the contact closes because VL3 is set to 01h).  
39.  
DIGITAL OUTPUT #2  
FUNCTION  
USE PARAMETER #39 TO SELECT THE #2  
DIGITAL OUTPUT FUNCTION.  
4 2 . DRIVE GAIN SETTING  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
USE PARAMETER #42 TO SET THE INTERNAL  
CURRENT GAIN OF THE DRIVE.  
RANGE OF VALUES: 0000 0000h to 0000 00FFh  
0 to 255 (decimal)  
Default Value: 0000 0001h  
no decimal  
significance  
Default Value: 0000 0080h  
128 (decimal)  
The setting options are the same as parameter  
#38. The default, by factory setting, is 0000 0001h,  
which is the FAULT output. The internal FAULT  
circuitry of the DFS-1 is off when the input power is  
applied and energizes if there are NO FAULTS in the  
drive (the contact closes because VL1 is set to 01h).  
The gain of the DFS-1 is set by parameter #42.  
The effect of the gain setting is to adjust an internal  
value which determines how many pulses of accumu-  
lated shaft position error it takes to reach current  
limit. A 00h will allow about 90 pulses of position  
error while a setting of FFh allows only about 9  
pulses, which makes the motor shaft very “stiff”, in  
that turning it only a few degrees causes current to  
increase very rapidly. A middle setting is the default.  
4 0 . DIGITAL OUTPUT #3  
FUNCTION  
USE PARAMETER #40 TO SELECT THE #3  
DIGITAL OUTPUT FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
43. DRIVE STABILITY SETTING  
USE PARAMETER #43 TO SET THE INTEGRAL  
CURRENT GAIN OF THE DRIVE.  
RANGE OF VALUES: 0000 0000h to 0000 00FFh  
0 to 255 (decimal)  
Default Value: 0001 0002h  
no decimal  
significance  
The setting options are the same as parameter  
#38. The default, by factory setting, is 0001 0002h,  
which is the AT SPEED output. The internal AT  
SPEED circuitry of the DFS-1 is on when the actual  
speed of the motor matches the commanded speed  
(the contact closes because VL3 is set to 01). There  
are no AT SPEED window parameters because the  
microprocessor filters and averages the speed signal.  
Default Value: 0000 0080h  
128 (decimal)  
The stability of the DFS-1 is set by parameter  
#43. The effect of the setting is to adjust an internal  
value which controls the integral and differential  
gains of the drive. Smaller numbers mean faster  
reaction to changes and for higher numbers reaction  
is more damped. A middle setting is the default.  
41.  
DIGITAL OUTPUT #4  
FUNCTION  
4 4 . DRIVE MOTORING  
CURRENT LIMIT  
USE PARAMETER #41 TO SELECT THE #4  
DIGITAL OUTPUT FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 000Fh  
no decimal significance  
USE PARAMETER #44 TO SET THE MOTORING  
CURRENT LIMIT OF THE DRIVE.  
RANGE OF VALUES: 0000 0000h to 0000 0096h  
0 to 150% (decimal)  
Default Value: 0001 0003h  
no decimal  
significance  
Default Value: 0000 0032h  
50% (decimal)  
Parameter #44 allows current limit settings of up  
to 150% and must be set in terms of MOTOR  
current. Other circuitry in the motor control will  
The setting options are the same as parameter  
#38. The default, by factory setting, is 0001 0003h,  
Page 31  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
limit the output DRIVE current to 150%. This  
parameter CANNOT OVERRIDE that limit, but this  
parameter may be set for an ultimate current limit on  
drives which are built with more capability than the  
motors they run. In this way, short term 300% current  
ratings can be obtained.  
Parameter #47 contains two pieces of informa-  
tion.  
VL4 VL3 sets the operational mode of the drive:  
0000h sets the drive for non-regenerative  
operation.  
0001h sets the drive for regenerative  
operation.  
4 5 . DRIVE REGENERATIVE  
CURRENT LIMIT  
VL2 VL1 sets the modulation mode for the  
drive:  
0000h sets the modulation for bottom  
transistors only.  
000h1 sets the modulation for top and bottom  
transistors.  
Normal setup is:  
USE PARAMETER #45 TO SET THE REGENERA-  
TIVE CURRENT LIMIT OF THE DRIVE.  
RANGE OF VALUES: 0000 0000h to 0000 0096h  
0 to 150% (decimal)  
Default Value: 0000 0032h  
50% (decimal)  
Non-regenerative drives:  
Regenerative drives:  
0000 0000h  
0001 0001h  
Parameter #44 allows current limit settings of up  
to 255% and must be set in terms of MOTOR  
current. Other circuitry in the motor control will limit  
the output DRIVE current to 150%. This parameter  
CANNOT OVERRIDE that limit, but this parameter  
may be set for an ultimate current limit on drives  
which are built with more capability than the motors  
they run. In this way, short term 300% current ratings  
can be obtained.  
Normally, in POWERTEC Brushless DC motor  
controls, non-regenerative drives modulate the  
bottom transistors only (this generates less heat and  
makes them more efficient). Regenerative drives  
modulate both top and bottom transistors for better  
control. There are some cases where modulating both  
top and bottom transistors in a non-regenerative drive  
may be desirable. This can be done by setting VL2  
VL1 to 0001h.  
4 6 . PULSE MULTIPLIER  
Note: If regenerative mode is used, the drive  
may require an optional DC bus loader to dissipate  
the regenerative energy and avoid over voltage faults.  
USE PARAMETER #46 TO SET THE VALUE BY  
WHICH THE ENCODER PULSE WILL BE  
MULTIPLIED.  
RANGE OF VALUES: 0000 0000h to 0000 0003h  
0 to 3 (decimal)  
4 8 . J UMP OR MOP OPERATION  
Default Value: 0000 0002h  
2 (decimal)  
USE PARAMETER #48 TO SET TEMPORARY OR  
PERMANENT UP/DOWN SPEED/RATIO  
CHANGES.  
RANGE OF VALUES: 0000 0000h to 0000 0001h  
0 to 1 (decimal)  
0= X 1  
1= X 2  
2= X 4  
3= Commutation Mode  
Encoder loss detection applies only when pulse  
multiplier is set to 4X.  
Default Value: 0000 0000h  
0 (decimal)  
47. MODULATION AND  
OPERATION MODES  
Parameter #48 selects whether the change in  
speed or ratio made by the up/down inputs is a  
temporary change which lasts as long as the up or  
down input is active (JUMP mode), or whether the  
change will remain after the up/down input has been  
released (MOP mode). The up/down functions may  
be generated by software through setting of param-  
eter #3.  
USE PARAMETER #47 TO SET REGEN / NON-  
REGEN AND MODULATION MODES.  
RANGE OF VALUES: 0000 0000h to 0001 0001h  
no decimal significance  
Default Value: 0000 0000h  
no decimal  
significance  
Page 32  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When parameter #48 is set to 0000 0000h, the  
DFS-1 is in the JUMP mode. In MASTER mode (set  
by parameter #5), when the UP input function is  
activated, the speed will increase by the amount set  
in parameter #49. As long as the UP function is  
active, the speed change will be held. When the UP  
function is released the speed returns to the SET-  
POINT. The same action applies to the DOWN  
function, the speed change set by parameter #50. In  
SLAVE mode, there is a temporary change in ratio  
determined by parameter #51 for UP and #52 for  
DOWN.  
5 0 . MAS TER J UMP DOWN  
AMOUNT  
USE PARAMETER #50 TO SET THE AMOUNT  
OF SPEED CHANGE ON A DOWN FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 869Fh  
0 to 99,999 (decimal)  
Default Value: 0000 0001h  
1 (decimal)  
Parameter #50 is the amount, in Engineering  
Units, by which the speed changes when the DOWN  
function is active.  
When parameter #48 is set to 0000 0001h, the  
DFS-1 is in the MOP mode. The MOP mode acts like  
a Motor Operated Potentiometer. When the UP  
function is activated, the speed, in MASTER mode,  
will change immediately by the amount in parameter  
#49. If the function is released within 1/2 second, that  
speed becomes the new SETPOINT. If the UP  
function is held for more than 1/2 second, the speed  
will begin to increase at the ACCEL rate (determined  
by parameter #8), increasing until the UP function is  
released. After the UP function is released, the speed  
will remain at the latest, which becomes the new  
SETPOINT. The same action applies in the MAS-  
TER mode to the DOWN function (with parameter  
#50 and the DECEL rate in parameter #9). In SLAVE  
mode, the immediate increase is set by parameter  
#51, the immediate decrease by parameter #52, and  
the rates by parameters #10 and #11, respectively.  
51.  
SLAVE J UMP UP AMOUNT  
USE PARAMETER #51 TO SET THE AMOUNT  
OF RATIO CHANGE ON AN UP FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 869Fh  
0 to 99,999 (decimal)  
Default Value: 0000 0001h  
1 (decimal)  
Parameter #51 is the amount, in Engineering  
Units, by which the ratio changes when the UP  
function is active.  
52.  
S LAVE J UMP DOWN  
AMOUNT  
USE PARAMETER #52 TO SET THE AMOUNT  
OF RATIO CHANGE ON A DOWN FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 869Fh  
0 to 99,999 (decimal)  
4 9 . MAS TER J UMP UP AMOUNT  
Default Value: 0000 0001h  
1 (decimal)  
USE PARAMETER #49 TO SET THE AMOUNT  
OF SPEED CHANGE ON AN UP FUNCTION.  
RANGE OF VALUES: 0000 0000h to 0001 869Fh  
0 to 99,999 (decimal)  
Parameter #52 is the amount, in Engineering  
Units, by which the ratio changes when the DOWN  
function is active.  
Default Value: 0000 0001h  
1 (decimal)  
Parameter #49 is the amount, in Engineering  
Units, by which the speed changes when the UP  
function is active.  
Page 33  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
53.  
INPUT DEBOUNCE VALUE  
55.  
MINIMUM RATIO  
USE PARAMETER #53 TO SET THE LENGTH OF  
TIME AN INPUT MUST BE ACTIVE TO BE  
ACTED UPON.  
USE PARAMETER #55 TO SET THE LENGTH OF  
TIME AN INPUT MUST BE ACTIVE TO BE  
ACTED UPON.  
RANGE OF VALUES: 0000 0000h to 0000 00FFh  
0 to 256 (decimal)  
RANGE OF VALUES: 0000 0000h to 0001 869Fh  
0 to 99,999 (decimal)  
Default Value: 0000 0001h  
1 (decimal)  
Default Value: 0000 0000h  
0 (decimal)  
Parameter #53 is the length of time, in 10  
milliseconds (1 millisecond =.01 second), that a  
digital input must be active before it is considered  
legitimate. It is used primarily to eliminate the  
contact bounce (which may generate multiple  
commands) from relays used on inputs, but it can  
also prevent noise problems from push-buttons.  
Parameter #55 is the minimum ratio allowed at  
any time in SLAVE mode.  
NOTE THAT THE RATIO CANNOT GO  
BELOW THIS VALUE, EVEN IN RESPONSE TO  
DOWN FUNCTIONS OR WHEN THE FLOAT  
PARAMETER IS SET. This parameter must be set  
with these restrictions in mind.  
5 4 . FLOAT OR FREEZE  
56. COMMUNICATIONS  
TURNAROUND DELAY  
USE PARAMETER #54 TO SELECT WHERE THE  
SETPOINT WILL BE ON START-UP.  
RANGE OF VALUES: 0000 0000h to 0000 0001h  
0 to 1 (decimal)  
SETS THE # OF 500 MICROSECOND DELAYS  
FROM TRANSFER TO TRANSMIT  
RANGE OF VALUES: 0000 0000h to 0000 007Fh  
0 to 128 (decimal  
Default Value: 0000 0000h  
0 (decimal)  
When parameter #54 is set to 0000 0000h, the  
SETPOINT at start-up (whether after a stop or after a  
power loss) is always at zero. The speed SETPOINT  
“floats” down with the motor speed. A new speed  
SETPOINT must be entered or the UP MOP function  
may be used to set speed.  
When parameter #54 is set to 0000 0001h, the  
SETPOINT at stop or power loss is “frozen” at the  
current value, and the DFS-1 will return to this speed  
when the drive next starts up. It is not necessary to  
enter a new SETPOINT on start-up if a return to the  
previous speed is desired.  
57.  
MAS TER J OG S P EED  
USE PARAMETER #57 TO SET A JOG SPEED  
WHICH CAN BE TOGGLED IN AND OUT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to 99,999 (decimal)  
Default Value: 0000 00C8h  
100 (decimal)  
The MASTER JOG Speed is the speed to which  
the motor will go when a JOG input is activated on  
one of the Digital inputs (any of the seven digital  
inputs may be programmed as a JOG input) when the  
DFS-1 is in the MASTER mode. If more than one  
input is programmed as a JOG input, they must both  
be present to activate the Master Jog Speed function  
(the inputs are logically ANDed).  
Parameter #54 also affects the SLAVE mode, but  
the SETPOINT cannot go to less than the value of  
the minimum ratio (parameter #55) in FLOAT mode.  
Page 34  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
58. SLAVE J OG RATIO  
61.  
S LAVE P RES ET # 2  
USE PARAMETER #58 TO SET A JOG SPEED  
WHICH CAN BE TOGGLED IN AND OUT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to 99,999 (decimal)  
USE PARAMETER #61 TO SET A  
PRESET SPEED WHICH CAN BE TOGGLED IN  
AND OUT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to 99,999 (decimal)  
Default Value: 0000 00C8h  
100 (decimal)  
Default Value: 0000 00C8h  
100 (decimal)  
The SLAVE JOG Speed is the speed to which  
the motor will go when a JOG input is activated on  
one of the Digital inputs (any of the seven digital  
inputs may be programmed as a JOG input) when the  
DFS-1 is in the SLAVE mode. If more than one input  
is programmed as a JOG input, they must both be  
present to activate the SLAVE JOG Speed function  
(the inputs are logically ANDed).  
The SLAVE PRESET #2 is the speed to which  
the motor will go when a PRESET #2 input is  
activated on one of the Digital inputs (any of the  
seven digital inputs may be programmed as a  
PRESET #2 input) when the DFS-1 is in the SLAVE  
mode. If more than one input is programmed as a  
PRESET #2 input, they must both be present to  
activate the SLAVE PRESET #2 function (the inputs  
are logically ANDed).  
59. EGU TAG SELECT  
(Parameter 59 not functional at present)  
RANGE OF VALUES: 0 TO F  
62. CONTACTOR DELAY  
0=  
1=  
2=  
3=  
4=  
5=  
UNK  
RPM  
GPM  
FPM  
SPM  
LBS-FT  
6=  
7=  
8=  
9=  
10=  
11=  
LBS/HR  
PCT  
CFM  
Y/MIN  
M/MIN  
IN/SEC  
0 (decimal)  
USE PARAMETER #62 TO SET TIME  
INTERVAL BETWEEN RUN COMMAND AND  
INITIAL FIRING OF TRANSISTORS.  
RANGE OF VALUES: 0000 0000 to 0000 0028h  
0 TO 40 (decimal)  
Default Value: 0000 0000h  
Default Value: 0000 0000h  
0 (decimal)  
This parameter sets the time interval between the  
acceptance of a run command and the initial firing of  
the transistors. If the Contactor Aux input does not  
become active in this time period, the transistors will  
not fire and the drive will return to a stop condition.  
The value of this parameter is in increments of 25ms.  
See the Additional Info section for examples.  
6 0 . MAS TER P RES ET # 2  
USE PARAMETER #60 TO SET A PRESET SPEED  
WHICH CAN BE TOGGLED IN AND OUT.  
RANGE OF VALUES: FFFE 7961h to 0001 869Fh  
-99,999 to 99,999 (decimal)  
Default Value: 0000 00C8h  
100 (decimal)  
The MASTER PRESET #2 is the speed to which  
the motor will go when a PRESET #2 input is  
activated on one of the Digital inputs (any of the  
seven digital inputs may be programmed as a  
PRESET #2 input) when the DFS-1 is in the MAS-  
TER mode. If more than one input is programmed as  
a PRESET #2 input, they must both be present to  
activate the MASTER PRESET #2 function (the  
inputs are logically ANDed).  
Page 35  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE WAS INTENTIONALLY LEFT BLANK.  
Page 36  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 .0 DFS - 1 S ETUP  
Parameter  
Maximum Motor Speed  
High Engineering Units  
Encoder Pulses Per Rev  
Pulse Multiplier  
Parameter  
Master Jump Up Amount  
Master Jump Down Amount  
Analog Input #1  
No.  
6
Value  
1750  
No.  
49  
50  
17  
25  
28  
53  
31  
32  
33  
34  
35  
38  
39  
40  
41  
Value  
1
1
14  
7
1750  
0-10VDC  
Speed  
120  
Analog Output #1  
Analog Output #2  
Input Debounce Value  
Digital Input #1  
46  
47  
42  
43  
44  
45  
48  
54  
5
x 4  
PWM Mode  
Non-Regen  
128  
Load  
Drive Gain  
10 mSec  
RUN  
Drive Stability  
128  
Motoring Current Limit  
Regenerative Current Limit  
Up/Down Function  
Float or Freeze Setpoint  
Mode of Operation  
Master Accel Rate  
Master Decel Rate  
Master Preset Speed  
Digital Input #2  
PRESET  
UP  
100  
Digital Input #3  
100  
Digital Input #4  
DOWN  
REVERSE  
RUN  
Jump  
Float  
Digital Input #5  
Digital Output #1  
Digital Output #2  
Digital Output #3  
Digital Output #4  
Master  
10k mSec  
10k mSec  
200  
NO FAULT  
AT SPD  
REMOTE  
8
9
12  
The DFS-1 is shipped with a default set of  
parameters which allows it to be connected as shown  
in Figure 3 on page 3 and run with basic push-  
buttons and a speed pot. This supplies a "baseline" of  
operation which may be used to test the functionality  
of the board.  
Making parameter changes requires the optional  
keypad display unit or a computer with serial  
communications capability.  
This section covers the basic steps necessary to  
set up the DFS-1 beyond the needs of the default  
parameters. The setup is arranged roughly from the  
most basic and common steps to the least commonly  
used parameter changes. You need only follow the  
steps until you have all the parameters you will use  
checked and/or changed.  
The above parameters are the most commonly  
used ones. For other default settings, refer to the  
parameter descriptions beginning on page 15.  
If your needs are met by the list above, then all  
you have to do is hook up the drive to power and to  
the motor and run it. No changes in parameter  
settings are necessary.  
For the purposes of this chapter, it will be  
assumed that the setup is being accomplished  
through the use of the KDU-1 keypad display unit.  
Page 37  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.1  
BASIC SETUP OF THE DFS-1 CONTROLLER  
1. SET PARAMETER #6 FOR THE MAXIMUM  
SPEED OF THE MOTOR IN RPM.  
6. SET PARAMETER #42 FOR THE DRIVE  
GAIN.  
The base speed of the motor is listed on the  
nameplate of the motor. If the base speed of the  
motor is other than 1750, you must change  
parameter #6. For instance, if the base speed of your  
motor is 2500 RPM, enter 2500 into parameter #6.  
This value is defaulted to 50% of the range and  
therefore set to 128. This should be adequate for  
many applications. If you are doing VERY close  
tracking with other motors, it may be necessary to  
increase this value, but it may be better to leave it  
alone in the initial setup.  
2. SET PARAMETER #14 TO THE  
ENGINEERING UNITS VALUE FOR  
PARAMETER #6.  
7. SET PARAMETER #43 FOR THE DRIVE  
STABILITY.  
This is a number which is set equal to the base speed  
of the motor. It may be any convenient value in  
process or reference terms. If the speed of the motor  
is 2500 RPM, but you want to scale this to 0 to  
100.00 %, enter 10000 in parameter #14.  
This value is also defaulted to 50% and, like  
parameter #42, is set to 128. If you have a high  
inertia or pulsating load, it may be necessary to  
increase this value, but it may be better to leave it  
alone in the initial setup.  
3. SET PARAMETER #7 TO THE PULSES PER  
REVOLUTION OF THE ENCODER.  
8. SET PARAMETER #44 FOR MOTORING  
CURRENT LIMIT.  
If the motor is a 4 pole motor (259TZ frame or  
smaller) this number will be 120 (the default). If  
the motor is an 8 pole motor, the number will be  
240. A 600 PPR quadrature encoder will be set up  
as 2400 in this parameter.  
This value is defaulted to 100% of motor current.  
There may be reasons to set this to a lower value  
(such as during start-up), but, unless the drive is  
specially set up, it doesn't do any good to set it to a  
higher value. Other circuitry limits output current  
to 150% of drive rating.  
4. SET PARAMETER #46 TO X4 FOR MOST  
APPLICATIONS.  
9. SET PARAMETER #45 FOR REGENERATIVE  
CURRENT LIMIT.  
Notable exceptions are for a servo application with  
a 600 ppr encoder or other application where the  
output frequency of the encoder may exceed 40  
Khz. For example, a motor with a 600 ppr encoder  
will reach 46Khz at 1150 rpm. This assumes that  
parameter #7 (Encoder PPR) is set to 2400 and the  
pulse multiplier is set to X4. Where the motor  
would run faster than 1150 rpm, this parameter  
This value is defaulted to 100% of motor current.  
There may be reasons to set this to a lower value  
(such as during start-up), but, unless the drive is  
specially set up, it doesn't do any good to set it to a  
higher value. Other circuitry limits output current  
to 150% of drive rating.  
should be set to X2 and parameter #7 should be set 10. SET PARAMETER #5 FOR MASTER MODE  
to 1200 ppr. With these settings, the encoder  
frequency would reach 50 Khz @ 2500rpm. Above  
2500 rpm, the settings should be X1 for Pulse  
Multiplier and 600 ppr for parameter #7.  
OR A SLAVE MODE  
Setting this parameter determines which remaining  
parameters must be set up.  
If setting up in MASTER Mode, proceed to  
MASTER MODE SETUP (Section 4.2).  
5. SET PARAMETER #47 FOR THE  
MODULATION MODE.  
This parameter is defaulted to Non-Regenerative  
operation. If you want Regenerative operation, you  
must change it. Servo operation is regenerative  
operation. There is also an option for the method  
of modulation. See page 28.  
If setting up in a SLAVE mode, proceed to SLAVE  
MODE SETUP (Section 4.3).  
After setting MASTER or SLAVE, proceed to  
INPUTS AND OUTPUT (Section 4.4).  
Note: If regenerative mode is used, the drive may  
require an optional DC bus loader to dissapate the  
regenerative energy and avoid over voltage faults.  
If using an external communications, proceed to  
COMMUNICATIONS setup (Section 4.5).  
Page 38  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 .2  
MAS TER MODE S ETUP  
5. SET PARAMETER #12 FOR A MASTER  
PRESET SPEED.  
1. SET PARAMETER #5 FOR THE MASTER  
MODE.  
This step is optional, if you wish to use a preset  
speed which can be toggled by the PRESET  
function. Enter the speed in Engineering Units.  
Set the basic operation in this parameter to  
MASTER.  
This parameter also has options for current control  
(see page 16). Selecting MASTER into the  
parameter takes care of the normal MASTER mode  
operation case because the default is normal current  
limits.  
Other choices are torque limiting (either motoring  
or regenerative) and horsepower control. If one of  
these choices is made, it will be necessary to either:  
1. Set up one analog input for a reference (see  
INPUTS and OUTPUTS), or  
6. SET PARAMETER #54 FOR SETPOINT  
CONDITION (FLOAT OR FREEZE) AT  
START-UP.  
If you want the motor to return to the speed at which  
it was running prior to shutdown or power loss, set  
this parameter to Freeze.  
If you want the motor to wait for the speed to be  
reentered after a stop or power loss, enter Float in  
this parameter. See page 30.  
2. Make provision to supply reference through  
communications (see page 16).  
7. SET PARAMETER #48 FOR JUMP OR MOP  
MODE.  
2. SET PARAMETER #17 OR PARAMETER #21  
IF AN ANALOG INPUT IS TO BE USED.  
If an analog speed reference is to be used, either  
Analog Input #1 (see page 20) or Analog Input #2  
(see page 22) must be set to Speed Reference Input.  
By default, Analog Input #1 is set up as a Speed  
Reference Input and Analog Input #2 is a General  
Purpose Input.  
Jump mode operation is to make UP/DOWN speed  
changes temporary. MOP mode makes the DFS-1  
act like a Motor Operated Potentiometer. See page  
28.  
8. SET PARAMETER #49 FOR MASTER JUMP  
UP AMOUNT.  
This is the amount (in Engineering Units) by which  
the speed command will increase when the UP  
function is activated. See page 29.  
You must also set parameter #18 (0 to 10VDC by  
default) or parameter #22 (4 to 20 milliamps default)  
for the type of input. Then set up the scaling  
(Engineering units) in parameters #19 and #20 for  
Analog Input #1, or parameters #22 and #23 for  
Analog Input #2.  
If neither analog input is set up as a speed reference,  
then the speed reference must be supplied from the  
optional front panel control or from the  
communications.  
9. SET PARAMETER #50 FOR MASTER JUMP  
DOWN AMOUNT.  
This is the amount (in Engineering Units) by which  
the speed command will decrease when the DOWN  
function is activated. See page 29.  
3. SET PARAMETER #8 FOR THE MASTER  
ACCELERATION RATE.  
Set the master speed acceleration time in  
milliseconds (1 millisecond = .001 second). The  
range is from 0 (speed changes are step functions)  
to 255 seconds.  
4. SET PARAMETER #9 FOR THE MASTER  
DECELERATION RATE.  
Set the master speed deceleration time in  
milliseconds (1 millisecond = .001 second). The  
range is from 0 (speed changes are step functions)  
to 255 seconds.  
Page 39  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3  
S LAVE MODE S ETUP  
1. SET PARAMETER #5 FOR THE SLAVE  
MODE.  
6. SET PARAMETER #10 FOR THE SLAVE  
ACCELERATION RATE.  
Set basic operation in this parameter to 1 for SLAVE  
mode. For INVERSE SLAVE mode enter 2.  
INVERSE SLAVE mode affects the way a setpoint  
is entered.  
Set slave speed acceleration time in milliseconds  
(1 millisecond = .001 second). The range is from 0  
(speed changes are step functions) to 255 seconds.  
See page 18.  
This parameter also has options for current control  
(see page 16). Setting a 1 takes care of the normal 7. SET PARAMETER #11 FOR THE SLAVE  
SLAVE mode because the default is normal current  
limits.  
Other choices are torque limiting (either motoring  
or regenerative) and horsepower control. For these  
options see page 16.  
DECELERATION RATE.  
Set the slave speed deceleration time in milliseconds  
(1 millisecond = .001 sec). The range is from 0  
(speed changes are step functions) to 255 seconds.  
See page 18.  
2. SET PARAMETER #17 OR PARAMETER #21  
IF AN ANALOG INPUT IS TO BE USED.  
If an analog speed reference is to be followed in  
SLAVE mode, either Analog Input #1 (see page  
20) or Analog Input #2 (see page 22) must be set to  
1 (Speed Reference Input). By default, Analog Input  
#1 is set up as a Speed Reference Input.  
8. SET PARAMETER #13 FOR A SLAVE  
PRESET RATIO.  
This step is optional, if you wish to use a preset  
ratio which can be toggled by the PRESET function.  
Enter the speed in Engineering Units.  
9. SET PARAMETER #54 FOR SETPOINT  
CONDITION AT START-UP.  
You must also set parameter #18 (0 to 10VDC by  
default) or parameter #22 for the type of input. Then  
set up the scaling parameters #19 and #20, or #22  
and #23.  
If neither analog input is set up as a speed reference  
input, then the speed reference to be followed must  
be supplied from the Frequency Reference In.  
If you want the motor to return to the ratio at which  
it was running prior to shutdown or power loss, set  
this parameter to 1. If you want the motor to wait  
for the ratio to be reentered after a stop or power  
loss, enter 0. See page 30.  
10. SET PARAMETER #48 FOR JUMP OR MOP  
MODE.  
3. SET PARAMETER #15 FOR THE BASE  
RATIO.  
Jump mode operation is to make UP/DOWN ratio  
changes temporary. MOP mode makes the DFS-1  
act like a Motor Operated Potentiometer. See page  
28.  
This is the number which is used to allow the  
SETPOINT to be set at a desired number instead  
of at a number dictated by gear ratios, motor speeds,  
and other factors. See page 19.  
11. SET PARAMETERS #51 AND #52 FOR SLAVE  
JUMP UP/DOWN AMOUNTS.  
4. SET PARAMETER #16 FOR THE MAXIMUM  
RATIO.  
These are the amounts (in Engineering Units) by  
which the ratio command will increase or decrease  
when the UP or DOWN functions are activated.  
See page 29.  
This setting is the highest ratio allowed under any  
circumstances.  
5. SET PARAMETER #55 FOR THE MINIMUM  
RATIO.  
This setting is the smallest ratio allowed under any  
circumstances.  
Page 40  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 .4  
INP UTS AND OUTP UTS S ETUP  
1. SET PARAMETERS #17, #18, #19, AND #20  
TO SET UP ANALOG INPUT #1.  
4. SET PARAMETERS #28, #29, AND #30 TO  
SET UP ANALOG OUTPUT #2.  
If Analog Input #1 is to be used for speed reference,  
which is the default mode, and the reference is to  
be 0 to +10VDC, no action is necessary to change  
from the defaults. If the input is to be 4 to 20mA,  
then parameter #18 must be changed. Set up  
parameters #19 and #20 to conform with the speed  
range set up by parameter #14.  
If Analog Output #2 is to be used for a Load Output  
signal from -10 to +10VDC, then nothing needs to  
be done. If not used for this purpose, it may be used  
as a General Purpose Output, a Load Output, or a  
communications output port by changing parameter  
#28. Parameters #29 and #30 may be set up in  
Engineering Units.  
If Analog Input #1 is not used as a speed reference,  
it may be used for any other signal which may be 5. SET PARAMETERS #31 THROUGH #37 FOR  
useful to the processor or the external program. Pre-  
programmed purposes are listed on page 20, but  
the uses of the analog inputs are not limited to those  
items.  
DIGITAL INPUT FUNCTIONS.  
If the digital inputs as listed on page 6 are suitable,  
then no changes need to be made. However, note  
that any Digital Input may be used for ANY purpose  
and more than one input may be used for the same  
purpose (the inputs will be logically ANDed - i.e.,  
they must both be present to function). The same  
parameters make provisions for input sense. See  
page 25.  
2. SET PARAMETERS #21, #22, #23, AND #24  
TO SET UP ANALOG INPUT #2.  
If Analog Input #2 is to be used for Speed Reference  
Input, Analog Input #1 must be changed to  
something else by changing parameter #17 to  
something other than 1, and then changing 6. SET PARAMETERS #53 FOR DEBOUNCE  
parameter #21 to 1. Parameter #22 must be set up  
for the form of input (4 to 20mA is the default),  
and parameters #23 and #24 set up in EGU's  
conforming to parameter #14.  
Analog Input #2 may be used for any analog input  
the processor or program may need, either as a  
predefined use (see page20) or as a General Purpose  
Input.  
TIME.  
If the inputs are driven by relays or push-button,  
contact bounce and/or noise could generate multiple  
commands. This command sets the minimum time  
(in milliseconds) that a command must be present  
before it is considered valid.  
7. SET PARAMETERS #38, #39, #40, AND #41  
FOR DIGITAL OUTPUT FUNCTIONS.  
If the outputs listed on page 7 (the defaults) are  
suitable, no changes need to be made, but each  
output can be reassigned as necessary (see page 26  
- parameter #38) as required. The output relays can  
also be assigned as normally open or normally  
closed.  
3. SET PARAMETERS #25, #26, AND #27 TO  
SET UP ANALOG OUTPUT #1.  
If Analog Output #1 is to be used for a Speed Output  
signal from -10 to +10VDC, then nothing needs to  
be done. If not used for this purpose, it may be used  
as a General Purpose Output, a Load Output, or a  
communications output port by changing parameter  
#25. Parameters #26 and #27 may be set up in  
Engineering Units.  
Page 41  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. SET PARAMETER #3 TO SELECT WHICH  
FUNCTIONS ARE REMOTE.  
4 .5  
COMMUNICATIONS SETUP  
The local operator's panel operates at CPU level  
and does not require the setup of any  
communications parameters. The following setup  
is for an external communications link.  
Before connecting to the external communications  
link, the following parameters must be set properly.  
The other parameters may be set after the link is  
established.  
This parameter may be used to include or exclude  
control functions from local control and assign them  
to the remote link. The setup of this parameter has  
nothing to do with assigning functions to input  
terminals! This parameter ONLY AFFECTS  
WHETHER THE CONTROL OF THE  
FUNCTION IS LOCAL OR REMOTE.  
The default parameters set up the DFS-1 as follows:  
4. SET PARAMETER #4 TO SELECT THE  
COMMUNICATIONS PROTOCOL.  
This parameter selects the POWERTEC binary  
protocol.  
the unit has an address of 001  
the baud rate is 9600  
The unit is in local mode  
using a binary communications protocol  
5. SET PARAMETER #56 FOR  
COMMUNICATIONS TURN AROUND  
DELAY.  
Set parameter #56 to default to 2 though it may  
have to be set to 6 or 8 for most reliable  
communications with Allen Bradley devices.  
1. SET PARAMETER #1 FOR  
COMMUNICATIONS NETWORK ADDRESS.  
This is the address which the DFS-1 will respond  
to on the external comm link. Since the default is  
001, it might be a good idea to start the network  
addresses at 002 so that a unit being replaced does  
not cause an addressing conflict.  
Addresses up to 255 are valid, but the RS-485  
protocol only allows for 32 units on a single line  
without repeaters.  
2. SET PARAMETER #2 FOR  
COMMUNICATIONS NETWORK SPEED.  
This is the communications rate at which the DFS-  
1 will operate on an external comm link. Rates  
range from 300 baud to 38.4 Kilobaud (see page  
16).  
Page 42  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5 .0 DFS - 1 ERROR CODES  
ERROR CODES FOR ON-BOARD DIS P LAY  
The DFS-1 has a single-digit alphanumeric display to show error codes when something is wrong. Following is a  
list of the meanings of the numbers in that display:  
0
1
2
3
4
5
All conditions nominal  
Undervoltage trip ................................................. Line voltage dropped below minimum level  
Overvoltage trip of drive ...................................... Bus voltage exceeded safe limit  
Undervoltage timer tripped .................................. Line voltage low for too long  
Instantaneous overcurrent .................................... Excessive transistor current  
Loss of encoder signal.......................................... Encoder speed signals lost.  
Encoder loss detection applies only when pulse  
multiplier is set to 4X  
6
Motor thermal tripped .......................................... Motor is too hot or thermal is disconnected  
Commutation fault ............................................... Signals from position encoder lost  
+24VDC lost at TB2-A14 and TB2-B1 ............... Fuse FR1 overloaded  
+24VDC lost at TB3-B1 ...................................... Fuse FR2 overloaded  
+5VDC lost at TB1-A8 ........................................ Fuse FR4 overloaded  
+24VDC lost at TB1-A10 .................................... Fuse FR3 overloaded  
Current limit ......................................................... Drive is at maximum current output  
Timed Overload.................................................... Timed overcurrent has occured  
Display fault ......................................................... Fault in display module  
Applications fault ................................................. Fault in applications program  
7
8
9
A
B
C
D
E
F
Page 43  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE WAS INTENTIONALLY LEFT BLANK.  
Page 44  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 COMMUNICATIONS PROTOCOL  
GENERAL DEFINITIONS:  
[STX] - 02h - Start of data  
[ETX] - 03h - End of data  
[ACK] - 06h - Acknowledge  
[NAK] - 15h - Negative Acknowledge  
[DLE] - 10h - Data Link Escape  
[CMD] -xxh - Command to be executed  
[CSM] - xxh - Checksum, 2’s complement sum of the  
data between the [STX] and [ETX] characters  
GENERAL NOTES:  
1. The use of brackets in this document means that  
there is a single byte of information contained  
within the brackets. This convention is used to  
insure that the construction of the message is clear.  
2. If the below message was sent, the following  
checksum would be computed:  
DLE STX UID CMD  
DATA  
DLE ETX CSM  
[10] [02] [01] [82] [00][00][10][10][00] [10] [03] [6D]  
Note the delimited datum character. Since a 10h is  
the DLE, the only way the software can know that  
a 10h in the middle of a data word is datum and  
not the DLE is to put the datum in twice. The  
driver software must know that a single 10h is the  
DLE and not datum! The driver software must  
actually use only one 10h to compute the check-  
sum value.  
01 + 82 + 00 + 00 + 10 + 00 = 93: 2’s complement = 6D  
3. All data is sent in four bytes regardless of the  
needed length of data. For instance, parameter 48  
has the value of 0 for jump and 1 for MOP. The  
actual parameter is passed in communications  
however as a [00][00][00][00] for jump mode and  
a [00][00][00][01] for MOP mode. In this way, all  
data has an expected length of 4 bytes.  
Page 45  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8Ah Description: (Read Digital Input)  
Commands the unit to send the status of a  
digital input.  
COMMAND LIST  
Following is a list of commands to the unit.  
Detailed descriptions of each command are shown in  
attachment A beginning on page 55.  
8Bh Description: (Read Digital Output)  
Commands the unit to send the status of a  
digital output.  
Cmd # Description:  
8Ch Description: (Set Digital Output)  
Commands the unit to turn on or off a specific  
digital output.  
81h Description: (Status Request)  
Respond with the current operating status  
which includes commanded speed, actual  
speed, and status bits.  
8Dh Description: (Set Operational Mode)  
Allows setting run, stop, preset, reverse  
commands via comm link rather than through  
the hardwired inputs.  
82h Description: (Set Speed)  
Commands the unit to set a new speed (or  
ratio) but to delay changing to the new speed  
until a command to do so is given ( #83)  
8Eh Description: (Read Operational Mode)  
Allows reading the status of all command  
conditions.  
83h Description: (Execute Speed)  
Commands the unit to execute the speed  
commanded in (#82) above.  
8Fh Description: (Application Mode)  
Sets the setpoint for torque control or horse-  
power control or other type of special  
application when the setpoint is to be set by  
communication rather than analog input  
value.  
84h Description: (Set and Execute Speed)  
Commands the unit to set a new speed (or  
ratio) and change to it immediately without  
waiting for an execution command.  
85h Description: (Read Parameter)  
Commands the unit to send a specified current  
parameter setting.  
86h Description: (Write Parameter)  
Commands the unit to change a specific  
parameter to a new value.  
87h Description: (Read Analog Input)  
Commands the unit to send the value of an  
analog input.  
88h Description: (Read Analog Output)  
Commands the unit to send the value of an  
analog output.  
89h Description: (Write Analog Output)  
Commands the unit to put a specific value out  
on one of the analog outputs.  
Page 46  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SLAVE SETUP ONLY  
PARAMETER LIST:  
10  
11  
13  
15  
16  
51  
52  
55  
58  
61  
Slave Acceleration Rate  
Slave Deceleration Rate  
Slave Preset Ratio  
Base Ratio for Slave  
Maximum Ratio for slave  
Slave Jump Up Amount  
Slave Jump Down Amount  
Slave Minimum Ratio  
Slave Jog Ratio  
Following is a list of the parameters used in  
DFS-1. For a detailed description of each parameter  
see the list in attachment B beginning on page 57.  
Param# Description  
COMMUNICATIONS SETUP  
1
2
Unit Identification number  
Baud Rate  
Slave Preset #2  
3
4
5
Local/Remote  
Communications Protocol  
Mode of Operation  
INPUT/OUTPUT SETUP  
Analog Input #1 Mode Select  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
62  
Analog Input #1 Input Signal Conditioning  
Analog Input #1 Low Engineering Units  
Analog Input #1 High Engineering Units  
Analog Input #2 Mode Select  
Analog Input #2 Input Signal Conditioning  
Analog Input #2 Low Engineering Units  
Analog Input #2 High Engineering Units  
Analog Output #1 Mode Select  
56  
Communication Response Delay  
BASIC DRIVE SETUP  
6
7
Maximum Motor Speed  
Encoder Pulses per Revolution  
Drive Gain Setting  
42  
43  
44  
45  
46  
47  
48  
14  
53  
54  
59  
Drive Stability Setting  
Motoring Current Limit  
Regenerative Current Limit  
Pulse Multiplier  
Pulse Width Modulation Mode  
Jump Or MOP Function  
High Engineering units  
Input Debounce Value  
Freeze or Float Setpoint  
EGU Tag Select  
Analog Output #1 Low Engineering Units  
Analog Output #1 High Engineering Units  
Analog Output #1 Mode Select  
Analog Output #1 Low Engineering Units  
Analog Output #1 High Engineering Units  
Digital Input #1 Mode and Polarity  
Digital Input #2 Mode and Polarity  
Digital Input #3 Mode and Polarity  
Digital Input #4 Mode and Polarity  
Digital Input #5 Mode and Polarity  
Digital Input #6 Mode and Polarity  
Digital Input #7 Mode and Polarity  
Digital Output #1 Mode and Polarity  
Digital Output #2 Mode and Polarity  
Digital Output #3 Mode and Polarity  
Digital Output #4 Mode and Polarity  
Contactor Delay  
MASTER SETUP ONLY  
12  
8
Master Preset Speed  
Master Acceleration Rate  
Master Deceleration Rate  
Master Jump Up Amount  
Master Jump Down Amount  
Master Jog Speed  
9
49  
50  
57  
60  
Master Preset #2  
FUTURE EXPANSION  
63  
Future General use parameters  
80-95 Future Special use parameters  
Page 47  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ATTACHMENT A: DETAILED COMMANDS  
Read Speed/Status (81)  
Set Speed (82)  
Command:  
Read Speed/Status  
Command: Set Speed  
Description:  
This command tells the unit to respond with it’s  
current commanded speed, actual speed, load value,  
& status.  
Description:  
This command tells the unit to set the new  
commanded speed to the value but not to execute it  
until told to do so by #83.  
CMD = [81]  
UID = [01] - [FF]  
CMD = [82]  
UID = [01] - [FF]  
Message:  
[DLE][STX][UID][CMD][DLE][ETX][CSM]  
Message:  
[DLE][STX][UID][CMD][CS4][CS3]  
[CS2][CS1][DLE][ETX][CSM]  
Response:  
[DLE][STX][UID][ACK][CS4][CS3][CS2][CS1][AS4][AS3][AS2]  
[AS1][LOD][ST2][ST1][DLE][ETX][CSM]  
Response:  
If no errors  
Definitions:  
[CS4]..[CS1] - Commanded speed, unsigned long integer  
[AS4]..[AS1] - Actual speed, unsigned long integer  
[DLE][STX][UID][ACK][DLE][ETX][CSM]  
else  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
[LOD]  
- Load percent  
[ST2]..[ST1] - UNIT Status. ST1 is fault codes.  
Definitions:  
[ST2] - 7 6 5 4 3 2 1 0  
Local/Remote (0,1)  
Master/slave (0,1)  
At Speed (1)  
[CS4]..[CS1] - Commanded speed, unsigned  
long integer  
[ERR]  
- Reported Error.  
[80] - Unit not in remote mode  
[81] - Illegal speed value  
[86] - Illegal command number  
FWD Direction Set (1)  
Fault Detected (1)  
Drive Enabled (1)  
Microprocessor  
Zero Speed  
Execute Speed (83)  
[ST1] - 7 6 5 4 3 2 1 0  
Bus not charged (1)  
IOC (1)  
Command: Execute Speed  
Description:  
This command tells the unit to execute the new  
commanded speed set in 82.  
Stall (1)  
Inverse Time OL (1)  
Heatsink Thermal OT  
Commutation Fault  
Over Volt  
CMD = [83]  
UID = [00] - [FF]  
Under Volt  
[ERR]- Reported error  
[86]- Illegal command number.  
Page 48  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Message:  
[ERR] - Reported Error.  
[80] - Unit not in remote mode  
[81] - Illegal speed value  
[DLE][STX][UID][CMD][DLE][ETX][CSM]  
[86] - Illegal Command number  
Response:  
If no errors and unit i.d. does not equal 0  
Read Parameter (85)  
[DLE][STX][UID][ACK][DLE][ETX][CSM]  
Command: Read Parameter  
If unit i.d. = 0 (global command) then no  
response at all but all DIGIMAXes will execute  
Description:  
simultaneously.  
else  
This command tells the unit to send the value of  
the selected parameter.  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
CMD = [85]  
UID = [01] - [FF]  
Definitions:  
[ERR] - Reported Error.  
[80] - Unit not in remote mode  
[86] - Illegal Command number  
Message:  
[DLE][STX][UID][CMD][PRM][DLE][ETX][CSM]  
Set & Execute Speed (84)  
Response:  
If no errors  
Command: Set & Execute Speed  
[DLE][STX][UID][ACK][DT4][DT3][DT2]DT1][DLE][ETX][CSM]  
else  
Description:  
This command tells the unit to set the new  
commanded speed to the value and execute it  
immediately.  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
Definitions:  
[DT4] THRU [DT1] Datum is returned as an  
long integer.  
CMD = [84]  
UID = [01] - [FF]  
[PRM] - Parameter number  
[ERR] - Reported Error  
Message:  
[82] - Illegal parameter number  
[86] - Illegal Command number  
[DLE][STX][UID][CMD][CS4][CS3][CS2][CS1][DLE][ETX][CSM]  
Response:  
If no errors  
Write Parameter (86)  
Command: Write Parameter  
[DLE][STX][UID][ACK][DLE][ETX][CSM]  
else  
Description:  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
This command tells the unit to change the value  
of the selected parameter.  
Definitions:  
[CS4]..[CS1] - Commanded speed, unsigned  
long integer  
CMD = [86]  
UID = [01] - [FF]  
Page 49  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Message:  
[ERR] - Reported error  
[DLE][STX][UID][CMD][PRM][VL4]  
[VL3][VL2][VL1][DLE][ETX][CSM]  
[80] - Unit not in remote mode  
[84] - Illegal channel number  
[86] - Illegal Command number  
Response:  
If no errors  
Read Analog Output (88)  
[DLE][STX][UID][ACK][DLE][ETX][CSM]  
else  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
Command: Read Analog Output  
Definitions:  
Description:  
This command tells the unit to return the value  
of one of the analog outputs.  
[PRM] - Parameter number  
[VL4]..[VL1] - parameter value cast as a long  
integer  
CMD = [88]  
[ERR] - Reported Error  
UID = [01] - [FF]  
[80] - Unit not in remote mode  
[82] - Illegal parameter number  
[83] - Illegal parameter value  
[86] - Illegal Command number  
DTA = [01] or [02] depending on which Analog  
output is being read.  
Message:  
Read Analog Input (87)  
[DLE][STX][UID][CMD][DTA][DLE][ETX][CSM]  
Command: Read Analog Input  
Response:  
If no errors  
Description:  
This command tells the unit to return the value  
of one of the analog inputs.  
[DLE][STX][UID][ACK][DA4][DA3]  
[DA2][DA1][DLE][ETX][CSM]  
else  
CMD = [87]  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
UID = [01] - [FF]  
ATD = [01 ]or [02] depending on which Analog input Definitions:  
is being read. [DTA] - Analog output number 01 or 02  
Message:  
[DA4] - [DA1] Value of analog output, cast as  
unsigned long.  
[DLE][STX][UID][CMD][ATD][DLE][ETX][CSM]  
[ERR] - Reported error  
[80] - Unit not in remote mode  
[84] - Illegal channel number  
[86] - Illegal Command number  
Response:  
If no errors  
[DLE][STX][UID][ACK][AD4][AD3]  
[AD2][AD1][DAT][DLE][ETX][CSM]  
else  
Write Analog Output (89)  
[DLE][STX][UID][NAK][ERR][DLR][ETX][CSM]  
Command: Write Analog Output  
Definitions:  
Description:  
[ATD] - Analog input number [01] or [02]  
[AD4] - Value of analog input, Most Sig Byte  
[AD1] - Value of analog input, Least Sig Byte  
This command tells the unit to put out a specific  
value of analog voltage on a selected analog output.  
Page 50  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CMD = [89]  
UID = [01] - [FF]  
DTA = [01 ]or [02] depending on which analog  
output  
Response:  
If no errors  
[DLE][STX][UID][ACK][VL4][VL3]  
[VL2][VL1][DLE][ETX][CSM]  
else  
Message:  
[DLE][STX][UID][CMD][DTA][VL4]  
[VL3][VL2][VL1][DLE][ETX][CSM]  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
Definitions:  
Response:  
If no errors  
[DIG] - Digital input number [01]* thru [07]  
([00]=Estop) not used  
[VL4] - Always 00  
[DLE][STX][UID][ACK][DLE][ETX][CSM]  
else  
[VL3] - Always 00  
[VL2] - Always 00  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
[VL1] - Status of input [00] = off [01] = on  
[ERR] - Reported error  
Definitions:  
[80] - Unit not in remote mode  
[84] - Illegal channel number  
[86] - Illegal Command number  
[DTA] - Analog output number 01 or 02  
[VL4]..[VL1] - Analog value cast as sealed  
between low EGU and high EGU.  
[ERR] - Reported Error  
Read Digital Output (8B)  
[80] - Unit not in remote mode  
[84] - Illegal channel number  
[85] - Illegal channel value  
Command: Read Digital Output  
[86] - Illegal Command number  
Description:  
This command tells the unit to return the value  
of one of the digital outputs.  
Read Digital Input (8A)  
CMD = [8B]  
UID = [01 ]- [FF]  
DIG = [01] - [04] depending on which Digital  
output is being read.  
Command: Read Digital Input  
Description:  
Message:  
This command tells the unit to return the value  
of one of the digital inputs.  
[DLE][STX][UID][CMD][DIG][DLE][ETX][CSM]  
CMD = [8A]  
Response:  
UID = [01] - [FF]  
If no errors:  
DIG = [01] - [07] depending on which digital input is  
being read.  
[DLE][STX][UID][ACK][VL4][VL3]  
[VL2][VL1][DLE][ETX][CSM]  
else  
Message:  
[DLE][STX][UID][NAK][ERR][DLR][ETX][CSM]  
[DLE][STX][UID][CMD][DIG][DLE][ETX][CSM]  
Page 51  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Definitions:  
[DIG] - Digital output number 01 to 04  
Set Operational Mode (8D)  
[VL4] - Always 00  
Command:  
Set Operational Mode  
[VL3] - Always 00  
[VL2] - Always 00  
Description:  
[VL1] - Status of output 00 = off 01 = on  
[ERR] - Reported error  
This command tells the unit to turn on or off  
specific input control functions such as run, stop, etc.  
Refer to parameter 3 which defines which input  
controls are allowed by communications link and  
which MUST BE controlled by inputs on the terminal  
strip. An error message will be produced if set mode  
attempts to change the condition of an input that is  
not allowed to be remotely changed.  
[80] - Unit not in remote mode  
[84] - Illegal channel number  
[86] - Illegal Command number  
Write Digital Output (8C)  
Command: Write Digital Output  
CMD = [8D]  
UID = [01] - [FF]  
SMH = [00] - [FF]  
Description:  
This command tells the unit to turn on or off a  
specific digital output contact.  
SML = [00] - [FE] depending on which CONTROL  
INPUT SEE PARAMETER # 3 FOR  
DEFINITION. This is a bit map that  
defines the desired state of each  
CMD = [8C]  
UID = [01] - [FF]  
control input as follows:  
7 6 5 4 3 2 1 0—Bit Position  
DIG = [01] - [04] depending on which Digital output  
0 0 0 0 0 0 0 0—Bit value can be 0 (off) or 1 (on)  
7 6 5 4 3 2 1 0—Digital input number  
Message:  
[DLE][STX][UID][CMD][DIG][VL4]  
[VL3][VL2][VL1][DLE][ETX][CSM]  
BIT PSN  
SML  
where: 0 is Estop  
1
2
3
4
5
6
7
is Run  
is Preset  
is Up input  
is Down input  
is Reverse mode  
is Frequency mode  
is Local/Remote (0 for local)  
Response:  
If no errors  
[DLE][STX][UID][ACK][DLE][ETX][CSM]  
else  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
Definitions:  
BIT PSN  
where: 0 is unused  
SMH  
[DIG] - Digital Output channel choice [00] thru  
[04]  
1
2
3
is Jog  
is Preset 2  
is Contactor Aux  
[VL4] - Always 00  
[VL3] - Always 00  
[VL2] - Always 00  
[VL1] - [00] or [01] contact being open or  
closed.  
Note that input 1 is Estop which must always be  
0 since this cannot be set remotely. This can ONLY  
be a hardwired function. This means the largest  
value for [00][00][SMH][SML] is [00][00][FF][FE].  
[ERR] - Reported Error  
[80] - Unit not in remote mode  
[84] - Illegal channel number  
[85] - Illegal channel value  
[86] - Illegal Command number  
Example: To turn on inputs 1 and 5 the value for  
[00][00][SMH][SML] is 0000 0022, or [22]. Inputs  
1 and 5 are defaulted to RUN and Reverse but can be  
redefined in parameters 31 through 37.  
Page 52  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Message:  
[DLE][STX][UID][CMD][00][00]  
[SMH][SML][DLE][ETX][CSM]  
If you wish to determine the status of the digital  
inputs you must use command 8A (Read Digital  
Input).  
Response:  
If no errors  
CMD = [8E]  
UID = [01] - [FF]  
[DLE][STX][UID][ACK][DLE][ETX][CSM]  
else  
Message:  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
[DLE][STX][UID][CMD][DLE][ETX][CSM]  
Definitions:  
[ERR] - Reported Error  
Response:  
[80] - Unit not in remote. Returned if this  
command is sent and remote mode is not  
allowed in parameter 3.  
[86] - Illegal Command number.  
[87] - Illegal input number.  
If no errors  
[DLE][STX][UID][ACK][00][00]  
[RMH][RML][DLE][ETX][CSM]  
else  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM]  
[88] - Illegal input value. Returned if remote  
mode is allowed but the specific input asked to  
be changed is not allowed in remote by param-  
eter # 3.  
Example: If the drive was in remote mode (from  
Parameter #3) and if the input assignments were the  
factory defaults, and the drive was in run, reverse,  
Down and not E-Stopped, then the value for [RML]  
would be constructed as follows:  
Read Operational Mode (8E)  
7 6 5 4 3 2 1 0 Bit Positions  
0 0 1 1 0 0 1 1 Input Status  
Command: Read Operational Mode  
[3  
3]  
[RMH][RML]= [00][33]  
Description:  
This command tells the unit to return the current  
status of the commands which are active whether  
from hardwired inputs or by remote. Note that run,  
for instance may not be allowed by param #3 from  
the terminal strip, but could be active from the comm  
link, or for that matter may even be mapped to  
operate from a different digital input. THE STATUS  
SHOWN HERE HAS NOTHING DIRECTLY TO  
DO WITH THE STATUS OF THE DIGITAL  
INPUTS EXCEPT FOR E-STOP STATUS  
WHICH IS ALWAYS HARDWIRED TO INPUT  
# 1. THE OTHER COMMANDS MAY OR MAY  
NOT BE ACTIVE FROM THE HARDWIRED  
INPUTS OR COULD BE REMAPPED. DO NOT  
BE CONFUSED BETWEEN COMMANDS  
SUCH AS RUN, STOP, REVERSE AND THE  
SOURCE OF THOSE COMMANDS WHICH  
MAY BE ANY OF THE DIGITAL INPUTS,  
EITHER OF THE TWO COMM INPUTS, OR  
INTERNAL SOFTWARE IN SPECIAL CASES.  
BIT PSN  
where: 0 is E-stop  
RML  
1
2
3
4
5
6
7
is Run  
is Preset  
is Up input  
is Down input  
is Reverse mode  
is Frequency mode  
is Local/Remote (0 for local)  
BIT PSN  
where: 0 is unused  
RMH  
1
2
3
is Jog  
is Preset 2  
is Contactor Aux  
Definitions:  
[ERR] - Reported error  
[82] - Illegal parameter number  
[86] - Illegal Command number  
Page 53  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application Mode (8F)  
any other mode than horsepower.  
Examples:  
Command: Application Mode Command  
[20] Motoring Torque setpoint can be 0 to 1000 (hex  
3E8) where torque is set in tenths of percent  
(1000 equals 100.0%) A torque of 100.0%  
would then be sent as [00][00][03][E8].  
Description:  
This command reads/sets the operating setpoint  
by communications rather than using an analog input  
for the setpoint when a special application mode is  
active (see parameter 5). The modes currently  
defined are shown below. It is possible in the future  
that additional application modes may be added.  
[21] Regen Torque same description as above  
[22] Horsepower setpoint has the same description  
as torque where hp is set in tenths of percent,  
100% maximum  
CMD = [8F]  
UID = [01] - [FF]  
AMD = [20],[21],[22],[23],[30],[31],[32]  
[23] Set speed/ratio with accel and decel ramp.  
This is used whenever a temporary setpoint for  
speed is desired and the ramp up and down rates  
are different from those in the parameter table.  
This setpoint and ramp rate is temporary and the  
drive will revert automatically back to the  
normal setpoint and ramp rates on any succes-  
sive commands. Speed/ratio requires 4 bytes,  
accel requires 4 bytes and decel requires 4 bytes.  
For instance a complete message including the  
header, etc. for a speed of 1400 rpm and accel  
rate of 10 seconds and decel rate of 5 seconds to  
unit # 5 would be:  
Message:  
[DLE][STX][UID][CMD][AMD][VL4]  
[VL3][VL2][VL1][DLE][ETX][CSM]  
Response:  
If no errors,  
[DLE][STX][UID][ACK][DLE][ETX][CSM]  
else,  
[DLE][STX][UID][NAK][ERR][DLE][ETX][CSM] [10][02][05][8F[23][00][00][05][78][00][00]  
[00][0A][00][00][00][05][10][03][CSM]  
Definitions:  
[AMD] - Application Mode  
[20] - Set Motoring torque setpoint  
ATTACHMENT B:  
PARAMETER DESCRIPTION:  
[21] - Set Regen torque setpoint  
[22] - Set Horsepower setpoint  
[23] - Set Speed/Ratio with ramp rate  
[30] - Read Motoring Torque Setpoint  
[31] - Read Regen Torque Setpoint  
[32] - Read Horsepower Setpoint  
Following is a list of the parameters for the DFS-  
1. All parameters are 4 byte values regardless of the  
data. For instance, parameter 5 is master slave and  
can be only [00] or [01] but the data bytes required  
for the parameter are [00][00][00][01] or  
[00][00][00][00]. This is done to keep communica-  
tions simple when dealing with parameter informa-  
tion, especially with any packed message.  
[VL4] - Depends on value passed  
[VL3] - Depends on value passed  
[VL2] - Depends on value passed  
[VL1] - Depends on value passed  
[ERR] - Reported Error  
59 through 63 are general use parameters for  
future use and not currently defined.  
[80] - Unit not in remote  
[82] - Illegal parameter number  
[86] - Illegal Command number  
[89] - Illegal Application value  
[8A] - Illegal Application  
80 through 95 are special use parameters for  
future use and not currently defined.  
An error message [8A] will be sent if a setpoint  
for horsepower [22] for instance is sent when  
parameter 5 is set to allow motoring torque limit, or  
Page 54  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Additiona l Info  
DFS S OFTWARE MODIFICATION FOR  
DYNAMIC BRAKING OR OUTPUT CONTACTOR  
OPERATION  
Functional Description  
A new function for Contactor Aux has been added to the digital input choices. When configured as  
described in the example, 24VDC must be present at this input for the drive to run. Parameter #62, Contactor  
Delay, is a number of 25ms intervals that will occur between the DFS controller acceptance of a run command  
and the firing of the transistors. If the Contactor Aux input signal is low, the DFS starts the timer and closes  
the Contactor Output. If the Contactor Aux input does not switch high before the timer runs out, the drive will  
return to the stop condition. If the Contactor Aux input does switch high, the drive will start running when the  
timer runs out.  
Example Setup for Dynamic Braking  
1
2
3
Set Digital Input #7 mode to Contactor Aux, polarity to Active Low.  
Set Digital Output #4 mode to Normally Open, polarity to Normally Closed.  
Set Contactor Delay to 20 (20 x 25ms = 500ms = 1/2 second).  
Run command causes the Contactor Output to close, the Contactor Relay opens, the feedback contacts  
close and the drive starts to run.  
Example Setup for Output Contactor  
1
2
3
Set Digital Input #7 mode to Contactor Aux, polarity to Active Low.  
Set Digital Output #4 mode to Normally Open, polarity to Normally Closed.  
Set Contactor Delay to 10 (10 x 25ms = 250ms = 1/4 second).  
Run command causes the Contactor Output to close, the Contactor Relay closes, the feedback contacts  
close and the drive starts to run.  
The difference in the operation of the two types of contactors is that the Dynamic Braking Contactor is  
normally closed whereas the Output Contactor is normally open. In both contactors, the auxilliary contacts are  
normally open.  
Terms Used  
1
Contactor Aux - The digital input on the DFS board which is connected to the feedback contacts on the  
contactor relay.  
2
Contactor Output - The digital output on the DFS board which activates the solenoid on the contactor  
relay.  
3
4
Signal low - 0VDC  
Signal high - 24VDC  
Page 55  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
N O M M O C S N I O T A I C N U M O M C  
D L I E H S S N I O T A I C N U M O M C  
- S N I O T A I C N U M O M C  
N O M M O C y a l p s D i  
- Y A L P S D I  
+ Y A L P S D I  
+ S N I O T A I C N U M O M C  
E R W O P Y L A S I P D  
e r p a S c  
2 4 + V  
e c r S p a  
N O M M O C t u O  
T U O D E E S P  
p e S e d  
D L E I H S F E R Q E F R  
- N I Q E F R  
+ N I F E R Q E F R  
7 n I l a t i g D i  
6 n I l a t i g D i  
5 n I l a t i g D i  
4 n I l a t i g D i  
3 n I l a t i g D i  
2 n I l a t i g D i  
1 n I l a t i g D i  
O P S T E -  
N O M M O C o l u a t t g i i D  
- T U O F E R Q E F R  
+
U T O F E R Q E F R  
4 B u t O l a t g i i D  
4 A u t O l a t g i i D  
3 B u t O l a t g i i D  
3 A u t O l a t g i i D  
2 B u t O l a t g i i D  
2 A u t O l a t g i i D  
1 B u t O l a t g i i D  
1 A u t O l a t g i i D  
2 + 4 V  
o h d t e a s C N O M M O C  
n I p l u a t t i g i D  
N O M M C O  
e r p a S c  
e r p a S c  
N O M M O C t u O o g n a A l  
+ 2 t u O o g n a A l  
+ 1 t u O o g n a A l  
F E R V 0 - 1  
R E W O P L A M R E T H  
L A M R E T H  
R E W O P L L H A  
N O M O M C L L H A  
2 - n I o l g A n a  
+ 2 n I o g n a A l  
1 - n I o l g A n a  
+ 1 n I o g n a A l  
C D 1 + 0 V  
5
4
2
3
1
H S  
H S  
H S  
H S  
H S  
N O M M O C n I o g n a A l  
D L I E H S L L H A  
Page 56  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
N O M M O C S N I O T A I C N U M O M C  
D L I E H S S N I O T A I C N U M O M C  
- S N I O T A I C N U M O M C  
N O M M O C y a l p s D i  
- Y A L P S D I  
+ Y A L P S D I  
+ S N I O T A I C N U M O M C  
E R W O P Y L A S I P D  
e r p a S c  
2 4 + V  
e c r S p a  
N O M M O C t u O  
T U O D E E S P  
p e S e d  
D L E I H S F E R Q E F R  
- N I Q E F R  
+ N I F E R Q E F R  
7 n I l a t i g D i  
6 n I l a t i g D i  
5 n I l a t i g D i  
4 n I l a t i g D i  
3 n I l a t i g D i  
2 n I l a t i g D i  
1 n I l a t i g D i  
O P S T E -  
N O M M O C o l u a t t g i i D  
- T U O F E R Q E F R  
+
U T O F E R Q E F R  
4 B u t O l a t g i i D  
4 A u t O l a t g i i D  
3 B u t O l a t g i i D  
3 A u t O l a t g i i D  
2 B u t O l a t g i i D  
2 A u t O l a t g i i D  
1 B u t O l a t g i i D  
1 A u t O l a t g i i D  
2 + 4 V  
o h d t e a s C N O M M O C  
n I p l u a t t i g i D  
N O M M C O  
e r p a S c  
e r p a S c  
N O M M O C t u O o g n a A l  
+ 2 t u O o g n a A l  
+ 1 t u O o g n a A l  
F E R V 0 - 1  
R E W O P L A M R E T H  
L A M R E T H  
R E W O P L L H A  
N O M O M C L L H A  
2 - n I o l g A n a  
+ 2 n I o g n a A l  
1 - n I o l g A n a  
+ 1 n I o g n a A l  
C D 1 + 0 V  
5
4
2
3
1
H S  
H S  
H S  
H S  
H S  
N O M M O C n I o g n a A l  
D L I E H S L L H A  
Page 57  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE WAS INTENTIONALLY LEFT BLANK.  
Page 58  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A  
RETROFITTING THE MODEL 1 0 0 0 , 1 0 0 0 A, OR 1 0 0 0 AR  
The DFS-1 Model 1000 series retro-fit kit consists of:  
Quantity  
Quantity  
Quantity  
Quantity  
Quantity  
Quantity  
1
1
1
2
2
4
DFS-1 Printed Circuit Board with connector plugs  
10 Pin Connector Cable Part # 3570-141420-001  
14 Pin Connector Cable Part # 3570-141419-001  
Nylon Spacer #6 x 1/4” diam x 1/4” long  
Machine Screw, Pan-head, 6/32 x 1/2” long  
Star Washer, #6  
1. Disconnect the cables from the Current Controller board to the Driver board (P2) and  
the Capacitor board (P3) and let them hang for the time being.  
2. Remove the 141-108 Current Controller board and the 141-107 Speed Controller  
board and set them aside. These boards have two screws each which hold them to the  
metal rail at the bottom and two hex nuts each which hold them to the Fuse board at  
the top. Save two of the hex nuts to mount the DFS-1 board.  
3. There are four metal studs on the bottom of the Fuse board at the top of the drive. The  
two outside studs will be used to mount the DFS board, but the two center studs must  
be removed. Remove them and set them aside.  
4. Remove the 14 pin connector cable connected to the Driver board (left side of the  
chassis), and replace it with the new cable 3570-141419-001. WARNING: Do  
NOT use the original drive cables with the DFS-1 board. This will cause damage  
to the drive circuitry. Either end of the cable may be plugged into the Driver board.  
Let the other end hang down the left side of the chassis because it will connect to the  
left side of the DFS board.  
5. Remove the 10 pin connector cable connected to the Capacitor board (right side of  
the main chassis) and replace it with the new cable 3570-141420-001. Either end of  
the cable may be plugged into the Capacitor board. The other end of this cable will  
connect to the left side of the DFS-1 board, so make sure you stretch it across the  
chassis behind the DFS-1 board.  
6. Mount the top of the DFS-1 board on the two outside studs at the bottom of the Fuse  
board using a star washer on each and the hex nuts saved when the other boards were  
removed.  
7. Secure the bottom of the DFS-1 board to the rail, which previously supported the  
bottom of the Current and Speed boards, with the two screws supplied. The nylon  
spacers must be mounted between the DFS-1 board and the metal rail. Use a star  
washer between the DFS-1 board and the head of the screw.  
8. Connect the 14 Pin connector cable to P2 on the left side of the DFS-1 board.  
9. Connect the 10 Pin connector cable to P4 on the left side of the DFS-1 board.  
Turn to section 1.0 of the DFS-1 manual to make the connections required.  
Page 59  
Revised 7/95  
POWERTEC Ind. Corp.©  
DFS-1 Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE WAS INTENTIONALLY LEFT BLANK.  
Page 60  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B  
MENU AND KEYPAD HIERARCHY  
When the DFS-1 is shipped, the factory presets  
the unit’s parameters according to the motor and  
drive’s specifications. The following pages describe  
the keypad’s hierarchal menus when the KDU-1  
keypad and display unit has been installed and  
configured.  
At the opening menu level, the DFS-1’s status is  
displayed. The STATUS display shows the com-  
manded speed, the load as a percent of Full Load  
Amps, and the actual motor speed. If speed setpoint  
changes are allowed, the up and down arrows can be  
used to trim the drive.  
action will return the options represented by Fig. 1 on  
the following page.  
The charts on the following pages, show the  
hierachal order of the options available. In most  
every case, up and down arrow keys scroll through  
selection for a particular menu level while the  
ENTER key will either move to the next hierarchal  
level or set a point and save the change. The  
SELECT key will return to the top of the hierarchal  
level without saving any change. For example,  
pressing the Menu button will result in a two line  
display of SETUP/PARAMETERS. Pressing the  
Of the seven keys on the keypad, the CMD key is down triangle (arrow) will cause the next menu item,  
the only one which always has the same function. If SETUP/ENB/DSB BKLT to appear. At this point  
the drive is in LOCAL and there is no analog input pressing ENT will result in choices of up arrow to  
associated with speed reference, the CMD key will re- Enable and Down arrow to disable the LCD back-  
turn to the status display in the edit mode. This edit light. On the other hand, choosing the SEL will go  
mode can be recognized by the presence of a cursor back to the SETUP/ENB/DSB BKLT menu. In  
under one digit position of the commanded speed be- cases where a selection will go to another hierarchal  
ing displayed. In this mode, the right and left arrow level, this chart will show a Fig. number which refers  
keys move the cursor left and right changing the digit to the next chart. For example, in Figure 1, Param-  
position being edited. The up and down arrows will eters, pressing the ENTER key will take one to . . .  
modify the value of the digit being edited by increment- Fig. 2.  
ing or decrementing the value by one unit.  
The SEL key will always return to the next  
higher level without saving changes.  
The ENT key will save changes and return to the  
status display except in the Setup/Parameters mode  
where it will save changes and return to the previous  
parameter menu.  
NEMA standards define forward as counter-  
clockwise rotation of the shaft as viewed facing the  
front of the motor. On a brush DC motor, the front  
end is the commutator end while on a brushless DC  
motor the front end is the encoder end (normally  
opposite from the output shaft).  
While in the status display mode, pressing the  
FWD key will cause the motor to run in the forward  
(clockwise) mode.  
Likewise, pressing the REV key will cause the  
motor to run in the reverse (counterclockwise) mode.  
Pressing the STP key will command the motor to  
stop. The manner in which the motor stops is  
determined by Setup Parameters.  
In order to begin changing drive setup param-  
eters, one must first press the MENU button. This  
Page 61  
Revised 7/95  
DFS-1 Manual  
POWERTEC Ind. Corp.©  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 1.0  
Status  
Menu  
Select  
Date  
Enter  
*Local/Remote  
Enter  
*Parameters  
History  
Enter  
Enter  
Enter  
Enter  
Enter  
Fig. 2  
Fig. 30  
Enb/Dsb Bklt  
Contrast  
Time  
* Not visible in some modes.  
FIGURE  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLANK.  
ALLY LEFT  
INTENTION  
GE WAS  
THIS PA  
Page 64  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 2  
Fig. 3  
Fig. 4  
Select  
Communication  
Enter  
Select  
Input/Output  
Enter  
Fig. 2  
Fig. 2  
Select  
Fig. 1  
Parameters  
Enter  
Select  
Communications  
Enter  
Select  
Select  
Unit ID  
Analog In  
Enter  
Enter  
Enter  
Enter  
Enter  
Fig. 3  
Fig. 4  
Fig. 9  
Reset Parameters  
Enter  
Delay  
Digital Out  
Fig. 12  
Fig. 11  
Input/Output  
Slave  
Protocol  
Digital In  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
Analog Out  
Remote Modes  
Enter  
Fig. 10  
Fig. 5  
Fig. 6  
Fig. 7  
Fig. 8  
Master  
Baud Rate  
Enter  
Drive Setup  
FIGURES 2 - 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLANK.  
ALLY LEFT  
INTENTION  
GE WAS  
THIS PA  
Page 66  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 5  
Fig. 6  
Fig. 7  
Select  
Select  
Select  
Fig. 2  
Fig. 2  
Fig. 2  
Slave  
Master  
Drive Setup  
Enter  
Enter  
Enter  
Select  
Preset Ratio 1  
Select  
Preset Speed 1  
Enter  
Select  
Mode  
Enter  
Enter  
Enter  
Fig. 24  
Fig. 29  
Jog Ratio  
Jog Speed  
Set Point Control  
Enter  
Enter  
Minimum Ratio  
Enter  
Jump Down Delta  
Enter  
Input Debounce  
Enter  
Maximum Ratio  
Enter  
Jump Up Delta  
Decel Rate  
Accel Rate  
Preset 2  
High EGU  
Enter  
Enter  
Enter  
Enter  
Enter  
Base Ratio  
Up/Dn Function  
Enter  
Enter  
Fig. 28  
Fig. 27  
Fig. 26  
Jump Down Delta  
Enter  
PWM Mode  
Enter  
Jump up Delta  
Decel Rate  
Accel Rate  
Preset 2  
Pulse Multiplier  
Enter  
Enter  
Enter  
Enter  
Enter  
Regen I Limit  
Motor I Limit  
Stability  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
Gain  
Encoder PPR  
Max. Speed  
F
5 -  
IGURES  
Aux. Mode  
Enter  
Fig. 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLANK.  
ALLY LEFT  
INTENTION  
GE WAS  
THIS PA  
Page 68  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 9  
Fig. 10  
Fig. 11  
Fig. 12  
Sel.ect  
Select  
Sel.ect  
Sel.ect  
Fig. 4  
Fig. 4  
Fig. 4  
Fig. 4  
Analog In  
Analog Out  
Digital In  
Digital Ou  
Enter  
Enter  
Enter  
Select  
Select  
Select  
Select  
Channel #  
Channel # 1  
Channel # 1  
Channel # 1  
Channel # 7  
Channel # 6  
Channel # 5  
Channel # 4  
Channel # 3  
Channel # 2  
Enter  
Enter  
Enter  
Enter  
Enter  
Fig. 13  
Fig. 13  
Fig. 16  
Fig. 16  
Fig. 18  
Channel #  
Channel # 2  
Channel # 2  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
Fig. 18  
Fig. 18  
Fig. 18  
Fig. 18  
Fig. 18  
Fig. 18  
Channel #  
Channel #  
Fig. 8  
Fig. 3  
Remote  
Jog  
Remote  
Remote  
Preset  
Local  
Remote  
Up Input  
Local  
Remote  
Remote  
Remote  
Select  
Remote Modes  
Select  
Run  
Down Input  
Local  
Reverse Input  
Local  
Freq. Mode  
Enter  
r
Local  
Local  
Local  
FIGUR  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLANK.  
ALLY LEFT  
INTENTION  
GE WAS  
THIS PA  
Page 70  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 13  
Fig. 14  
Fig. 15  
Fig. 16  
Fig. 13  
Select  
Se.lect  
Select  
Fig. 13  
Select  
Fig. 9  
AI Channel  
# 1 or 2  
AO Channel  
#1 or 2  
Fig. 10  
AI Mode  
AI Sig. Condition  
Enter  
Enter  
Enter  
Select  
Select  
Select  
Select  
Mode  
General Purpose  
Modes 15 - 6  
-10 to +10VDC  
4 to 20mADC  
Mode  
Enter  
Enter  
En  
Fig. 14  
Enter  
Calibration  
High EGU  
Low EGU  
High EGU  
Low EGU  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
En  
En  
Horsepower  
0 to 20mADC  
1 to +5VDC  
0 to +5VDC  
0 to +10VDC  
Enter  
Torq Limit Regen  
Enter  
Enter  
Signal Condition  
Enter  
Torq Limit Motor  
Enter  
Fig. 15  
Trim (Dancer)  
Enter  
Speed Reference  
Enter  
FIGURE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLANK.  
ALLY LEFT  
INTENTION  
GE WAS  
THIS PA  
Page 72  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 17  
Fig. 18  
Fig. 19  
Fig  
Select  
Select  
Select  
Select  
Fig. 18  
Fig. 16  
Fig. 11  
Fig. 18  
DI Channel  
# 1 or 2  
AO Mode  
DI Mode  
DI P  
Enter  
Enter  
Enter  
Select  
General Purpose  
Select  
Select  
General Purpose  
Select  
Mode  
Activ  
Activ  
Enter  
Enter  
Enter  
Enter  
Fig. 19  
Fig. 20  
Modes 15 - 5  
Polarity  
Modes 15-11  
Enter  
Enter  
Enter  
Contactor Aux.  
Commanded Speed  
Enter  
Preset 2  
Jog  
Set by Comm  
Load Output  
Actual Speed  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
Master/Slave  
Local/Remote  
Frequency Mode  
Enter  
Reverse Input  
Up Input  
Enter  
Enter  
Enter  
Enter  
Enter  
Down Input  
Preset Input  
Run Input  
FIGURE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLANK.  
ALLY LEFT  
INTENTION  
GE WAS  
THIS PA  
Page 74  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 21  
Fig. 22  
Fig. 23  
Select  
Select  
Select  
Sel  
S
Fig. 12  
Fig. 21  
Fig. 21  
Fig. 7  
DO Channel  
# 1 or 2  
DO Polarity  
DO Mode  
Enter  
Enter  
Enter  
Select  
Select  
Normally Open  
Select  
General Purpose  
Mode  
Enter  
Enter  
Enter  
Enter  
Fig. 22  
Fig. 23  
Polarity  
Normally Closed  
Enter  
Modes 15 - 6  
Contactor  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
Enter  
Set by Comm  
Zero Speed  
Run hold  
Remote/Local  
At Speed  
No Fault  
FIGURE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLANK.  
ALLY LEFT  
INTENTION  
GE WAS  
THIS PA  
Page 76  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 25  
Fig. 26  
Fig. 27  
F
Select  
Select  
Select  
Select  
Fig. 7  
Fig. 7  
Fig. 7  
Fig. 7  
Aux. Mode  
Pulse Multiplier  
Enter  
PWM Mode  
Up  
Enter  
Enter  
Select  
Select  
Select  
Non Regen Norm  
Enter  
Selec  
J
Normal  
X 1  
Enter  
Enter  
Commutation Mode  
Modes 15 - 4  
Horsepower  
Regen, Both  
M
Enter  
Enter  
Enter  
Enter  
Enter  
X 4  
X 2  
Regen, Normal  
Enter  
Enter  
Non Regen Both  
Enter  
Regen I Limit  
Motor Torque  
Enter  
Enter  
FIGURES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLANK.  
ALLY LEFT  
INTENTION  
GE WAS  
THIS PA  
Page 78  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 29  
Fig. 30  
Select  
Setpoint Control  
Enter  
Select  
Fig. 1  
Fig. 7  
History  
Enter  
Select  
Select  
Freeze  
Float  
KDU-1 Version  
Enter  
Enter  
Enter  
Enter  
Comm Version  
Application Version  
Enter  
Control Version  
Enter  
Last Motor Start  
Enter  
Last Power On  
Motor Runtime  
Trips (last four)  
Reset Faults  
Enter  
Enter  
Enter  
Enter  
FIGURES 29 - 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLANK.  
ALLY LEFT  
INTENTION  
GE WAS  
THIS PA  
Page 80  
DFS-1 Manual  
Revised 7/95  
POWERTEC Ind. Corp. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Philips Camcorder SDR S50 User Manual
Philips Car Stereo System MCM204 User Manual
Philips Cassette Player AW 7500 User Manual
Philips Cell Phone CT6598 User Manual
Philips Cordless Telephone DECT7272S User Manual
Philips Indoor Furnishings P 5951 User Manual
Philips Portable DVD Player PET940 User Manual
Philips Speaker System SPA3210 User Manual
PYLE Audio Car Video System PLVWR940R User Manual
PYLE Audio Music Mixer PPH5MA User Manual