Pelco Switch FR82011 User Manual

I N S T A L L A T I O N  
FT82011/FR82011  
Ethernet Media  
Converter  
®
One 10BASE-T/100BASE-TX Port and  
One 100BASE-FX Fiber Port  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
List of Illustrations  
List of Tables  
C
Troubleshooting with Rear-Panel Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
Important Safety Instructions  
1. Read these instructions.  
2. Keep these instructions.  
3. Heed all warnings.  
4. Follow all instructions.  
5. Do not use this apparatus near water.  
6. Clean only with dry cloth.  
7. Do not block any ventilation openings. Install in accordance with the manufacturer’s  
instructions.  
8. Do not install near any heat sources such as radiators, heat registers, stoves, or other  
apparatus (including amplifiers) that produce heat.  
9. Do not defeat the safety purpose of the polarized or grounding-type plug. A polarized plug has  
two blades with one wider than the other. A grounding plug has two blades and a third  
grounding prong. The wide blade or the third prong are provided for your safety. If the provided  
plug does not fit into your outlet consult an electrician for replacement of the obsolete outlet.  
10. Protect the power cord from being walked on or pinched particularly at plugs, convenience  
receptacles, and the points where they exit from the apparatus.  
11. Only use attachments/accessories specified by the manufacturer.  
12. Use only with the cart, stand, tripod, bracket, or table specified by the manufacturer, or sold  
with the apparatus. When a cart is used, use caution when moving the cart/apparatus  
combination to avoid injury from tip-over.  
13. Refer all servicing to qualified service personnel. Servicing is required when the apparatus has  
been damaged in any way, such as power-supply cord or plug is damaged, liquid has been  
spilled or objects have fallen into the apparatus, the apparatus has been exposed to rain or  
moisture, does not operate normally, or has been dropped.  
14. Apparatus shall not be exposed to dripping or splashing and that no objects filled with liquids,  
such as vases shall be placed on the apparatus.  
15. WARNING: To reduce the risk of fire or electric shock, do not expose this apparatus to rain or  
moisture.  
16. Installation should be done only by qualified personnel and conform to all local codes.  
17. Use only installation methods and materials capable of supporting four times the maximum  
specified load.  
18. A CCC-approved power cord must be used to power this equipment when used in China.  
19. CAUTION: These servicing instructions are for use by qualified service personnel only.  
To reduce the risk of electric shock do not perform any servicing other than that contained in  
the operating instructions unless you are qualified to do so.  
4
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
The product and/or manual may bear the following marks:  
This symbol indicates that dangerous voltage  
constituting a risk of electric shock is present  
within this unit.  
CAUTION:  
RISK OF ELECTRIC SHOCK.  
DO NOT OPEN.  
This symbol indicates that there are important  
operating and maintenance instructions in the  
literature accompanying this unit.  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
Regulatory Notices  
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two  
conditions: (1) this device may not cause harmful interference, and (2) this device must accept any  
interference received, including interference that may cause undesired operation.  
RADIO AND TELEVISION INTERFERENCE  
This equipment has been tested and found to comply with the limits of a Class A digital device,  
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection  
against harmful interference when the equipment is operated in a commercial environment. This  
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in  
accordance with the instruction manual, may cause harmful interference to radio communications.  
Operation of this equipment in a residential area is likely to cause harmful interference in which case  
the user will be required to correct the interference at his own expense.  
Changes and Modifications not expressly approved by the manufacturer or registrant of this  
equipment can void your authority to operate this equipment under Federal Communications  
Commission’s rules.  
This Class A digital apparatus complies with Canadian ICES-003.  
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.  
6
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Product Overview  
DESCRIPTION  
The FT82011/FR82011 Ethernet media converter converts 10BASE-T/100BASE-TX data to 100BASE-FX  
data and vice versa. Designed for point-to-point applications, the FT82011/FR82011 media converter  
provides one 10BASE-T/100BASE-TX port and one 100BASE-FX fiber port. The FT82011 and FR82011  
media converters are used in combination with one another to provide wavelength compatibility. Using  
wavelength division multiplexing (WDM), bidirectional data is transported in a single fiber (refer to  
ONE 10/100 Mbps  
CONNECTION  
ONE 10/100 Mbps  
CONNECTION  
FT82011  
FR82011  
ONE  
FIBER  
Figure 1. FT82011 and FR82011 Point-to-Point Application  
Features of the FT82011/FR82011 Ethernet media converter include the following:  
User-selectable 10BASE-T/100BASE-TX port functions:  
Autonegotiation between 10 Mbps and 100 Mbps data rates and between full-duplex  
and half-duplex modes  
10 Mbps or 100 Mbps selectable  
Full-duplex or half-duplex mode selectable  
Enabling/disabling of flow control  
NOTE: The 100BASE-FX fiber port is automatically forced to full-duplex 100 Mbps operation.  
Auto MDI/MDI-X (Medium Dependent Interface/Medium Dependent Interface Crossover)  
operation  
Link-down detection, which propagates a link-down status among all 10BASE-T/100BASE-TX  
and 100BASE-FX ports connected in the network when a 10BASE-T/100BASE-TX link or  
100BASE-FX link goes down. As a result, all ports are disabled and data transmission halts  
until the faulty link is restored.  
Compliant with IEEE 802.3, 802.3u, 802.3x standards  
Multimode fiber support for distances up to 2 km  
Single-mode fiber support for distances up to 46 km  
Laser diode for transmission of optical signals  
NOTE: The FT82011/FR82011 media converter is a Class 1 laser product that complies with  
FDA radiation performance standard 21CFR Subchapter J and with IEC 60825-1 Edition 1.2,  
2001-08.  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
     
Compatible with other Ethernet equipment:  
10BASE-T/100BASE-TX compatibility with all Pelco© and third-party 10BASE-T/  
100BASE-TX Ethernet devices  
Fiber optic compatibility with all Pelco Ethernet devices that support WDM  
Environmentally hardened  
Designed to meet NEMA TS 2 and Caltrans traffic signal control equipment standards for  
ambient operating temperature, mechanical shock and vibration, humidity with condensation,  
high-line/low-line voltage conditions, and transient voltage protection  
NOTE: Conformal coating is required for operation in environments with relative humidity  
above 95 percent (condensing).  
No performance adjustments required  
12 VDC or 24 VAC power supply  
Stand-alone and rack-mountable modular design  
LED indicators for monitoring of optic signal/laser status, 100BASE-FX port status including far  
end fault indication (FEFI), 10BASE-T/100BASE-TX port status, and operating power  
8
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODELS  
The FT82011 and FR82011 modules consist of the following series of models:  
Multimode Models:*  
FT82011MSTR-1 Ethernet media converter, one 10BASE-T/100BASE-TX port, one multimode ST  
fiber port, one fiber, fiber optic compatibity with FR82011MSTR-1 and other  
multimode ST Pelco Ethernet devices that support WDM  
FR82011MSTR-1 Ethernet media converter, one 10BASE-T/100BASE-TX port, one multimode ST  
fiber port, one fiber, fiber optic compatibility with FT82011MSTR-1 and other  
multimode ST Pelco Ethernet devices that support WDM  
FT82011MSCR-1 Ethernet media converter, one 10BASE-T/100BASE-TX port, one multimode SC  
fiber port, one fiber, fiber optic compatibility with FR82011MSCR-1 and other  
multimode SC Pelco Ethernet devices that support WDM  
FR82011MSCR-1 Ethernet media converter, one 10BASE-T/100BASE-TX port, one multimode SC  
fiber port, one fiber, fiber optic compatibility with FT82011MSCR-1 and other  
multimode SC Pelco Ethernet devices that support WDM  
Single-Mode Models:*†  
FT82011SSTR-1  
FR82011SSTR-1  
FT82011SSCR-1  
FR82011SSCR-1  
Ethernet media converter, one 10BASE-T/100BASE-TX port, one single-mode ST  
fiber port, one fiber, fiber optic compatibility with FT82011MSCR-1 and other  
single-mode ST Pelco Ethernet devices that support WDM  
Ethernet media converter, one 10BASE-T/100BASE-TX port, one single-mode ST  
fiber port, one fiber, fiber optic compatibility with FT82011SSTR-1 and other  
single-mode ST Pelco Ethernet devices that support WDM  
Ethernet media converter, one 10BASE-T/100BASE-TX port, one single-mode SC  
fiber port, one fiber, fiber optic compatibility with FR82011SSCR-1 and other  
single-mode SC Pelco Ethernet devices that support WDM  
Ethernet media converter, one 10BASE-T/100BASE-TX port, one single-mode SC  
fiber port, one fiber, fiber optic compatibility with FT82011SSCR-1 and other  
single-mode SC Pelco Ethernet devices that support WDM  
*For conformal coated models, replace the first letter F in the model number with the letter C.  
The conformal coated version of FT82011MSTR-1, for example, is CT82011MSTR-1.  
Single-mode FC connector is available upon request. Contact the factory for additional information.  
OPTIONAL ACCESSORIES  
The following optional accessories are available:  
WM5001-3U  
Wall mount base kit for single-width module  
WM5001-3UEXP Wall mount expansion kit for single-width module  
RK5000-3U  
19-inch rack mount chassis for 14 slots (no power), 3 RUs  
19-inch rack mount chassis for 12 slots with power, 3 RUs  
External rack power supply, 1 RU, dual 120 W power outputs  
Blank filler panel, single width  
RK5000PS-3U  
EPS5000-120  
RK5001B-3U  
RK5002B-3U  
RK5001-1UEXP  
Blank filler panel, double width  
Adapter kit that allows a 3 RU single-width fiber module to be used in  
RK5000PS-5U rack mount chassis  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
   
FRONT PANEL  
Figure 2 illustrates the front panel of the FT82011 and FR82011 modules.  
FT82011  
FR82011  
Figure 2. Front Panel of FT82011 and FR82011 Modules  
RESET BUTTON (restarts the unit)  
ì
î
ï
ñ
100BASE-FX STATUS LED  
OPTIC FAULT LED (optical signal status/laser status indicator)  
POWER LED (Pelco badge)  
For detailed information about the front-panel LEDs, refer to the Troubleshooting section.  
10  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
REAR PANEL  
Figure 3 illustrates the rear panel of the FT82011 and FR82011 modules.  
FT82011  
FR82011  
Figure 3. Rear Panel of FT82011 and FR82011 Modules (SC Fiber Connector Shown)  
ì
RACK POWER/ALARM CONNECTOR, 4-pin connector for power/alarm connection of rack-  
mounted module  
î
STAND-ALONE POWER CONNECTOR, 2-pin connector for power connection of stand-alone  
module; removable mating connector with screw terminals (not shown)  
ï
ñ
10BASE-T/100BASE-TX PORTS 1-4, RJ-45 connectors  
FIBER OPTIC PORT, single-fiber ST or SC connector (dependent on FT82041/FR82041 model);  
port A on FT82041 module and port B on FR82041 module  
ó
r
RJ-45 10BASE-T/100BASE-TX PORT STATUS LED, LEFT (link/activity status indicator)  
RJ-45 10BASE-T/100BASE-TX PORT STATUS LED, RIGHT (duplex mode/collision indicator)  
For additional information about rear-panel connections, refer to the Installation section. For detailed  
information about the RJ-45 LEDs, refer to the Troubleshooting section.  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
   
Installation  
PACKAGE CONTENTS  
The following items are supplied:  
1
1
FT82011 or FR82011 module  
Regulated switching power supply with four plug adapters (North American, Australian, U.K.,  
and European configurations); 100-240 VAC, 50-60 Hz input, 12 VDC output  
1
1
Wall clip with two 4-40 x 0.250-inch Phillips pan head screws with lock washers (for attachment  
of single module to wall)  
FT82011/FR82011 Fiber Transmitter and Receiver Installation manual (this manual)  
SETTING 10BASE-T/100BASE-TX PORT MODES OF OPERATION  
NOTE: As a matter of convenience, it is recommended that you verify the modes of operation for the  
10BASE-T/100-BASE-TX port and then change the mode settings—if necessary—before mounting  
the FT82011/FR82011 module into a rack or onto a wall.  
The FT82011/FR82011 module provides various configuration options that allow you to select the  
desired modes of operation for the 10BASE-T/100BASE-TX port. You can select the desired modes of  
operation by means of a TX Mode switch that is provided on the bottom of the module (refer to  
TX Mode  
0. Auto Neg / Dis FC  
1. 100 FD / Dis FC  
2. 100 HD / Dis FC  
3. 10 FD / Dis FC  
4. 10 HD / Dis FC  
5. Auto Neg / En FC  
6. 100 FD / En FC  
7. 100 HD / En FC  
8. 10 FD / En FC  
9. 10 HD / En FC  
TX MODE SWITCH  
Figure 4. TX Mode Switch for 10BASE-T/100BASE-TX Port  
12  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Using the TX Mode switch, you can do the following:  
Enable autonegotiation or select (force) a specific data rate and duplex mode:  
Enabling autonegotiation allows the FT82011/FR82011 module to automatically  
negotiate with the device to which the port is connected for data rate and duplex modes  
of operation: 10 Mbps or 100 Mbps data rate and half-duplex or full-duplex mode.  
The highest common denominator of operational modes is automatically selected.  
Autonegotiation is enabled by default.  
If autonegotiation is not desired, you can select a specific data rate and duplex mode:  
Data rate configuration allows you to select 10 Mbps or 100 Mbps.  
Duplex mode configuration allows you to select half-duplex mode or full-duplex  
mode.  
Enable or disable flow control. Flow control controls data transmission at the sending device  
to avoid overfilling buffers and losing data at the receiving device. When the buffers on the  
receiving device are full, a message is sent to the sending device to suspend the transmission  
until the data in the buffers has been processed.  
NOTE: For time-sensitive data applications (for example, video and audio applications), it is  
recommended that flow control be disabled.  
Flow control is disabled by default.  
With the FT82011/FR82011 module powered off, set each TX Mode switch to the desired 10BASE-T/  
100BASE-TX port modes of operation. Refer to Table A for TX Mode switch settings and  
corresponding modes of operation. Note that each 10BASE-T/100BASE-TX port operates  
independently of one another; therefore, each port can be set to different modes of operation as  
appropriate.  
Table A. TX Mode Switch Settings  
TX Mode  
Switch Position  
10BASE-T/100BASE-TX Modes of Operation  
Auto Neg/Dis FC—Enables autonegotiation between 10 Mbps and  
100 Mbps and between half-duplex and full-duplex modes, disables  
flow control (default setting)  
0
1
2
3
4
100 FD/Dis FC—Selects 100 Mbps full-duplex, disables flow control  
100 HD/DIS FC—Selects 100 Mbps half-duplex, disables flow control  
10 FD/Dis FC—Selects 10 Mbps full-duplex, disables flow control  
10 HD/Dis FC—Selects 10 Mbps half-duplex, disables flow control  
Auto Neg/En FC—Enables autonegotiation between 10 and 100 Mbps  
and between half-duplex and full-duplex modes, enables flow control  
5
6
7
8
9
100 FD/En FC—Selects 100 Mbps full-duplex, enables flow control  
100 HD/En FC—Selects 100 Mbps half-duplex, enables flow control  
10 FD/En FC—Selects 10 Mbps full-duplex, enables flow control  
10 HD/En FC—Selects 10 Mbps half-duplex, enables flow control  
NOTE: Switch positions 0-4 disable flow control. Positions 5-9 enable flow control.  
NOTE: TX Mode configuration must be set when the module is powered off. If you wish to change  
a TX Mode switch setting after the module has been powered on, power off the module, change the  
TX Mode switch setting, and then power on the module again.  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
 
MOUNTING  
The FT82011/FR82011 module can be mounted into a rack or can be used as a stand-alone module.  
As a stand-alone module, the unit can be placed on a desktop or can be mounted to a wall.  
NOTE: As a matter of convenience, it is recommended that you set the modes of operation for the  
10BASE-T/100-BASE-TX port—if required—before mounting the FT82011/FR82011 module into a  
rack or onto a wall. For information about setting the port modes of operation, refer to the Setting  
MOUNTING THE FT82011/FR82011 MODULE INTO A RACK  
The FT82011/FR82011 module can be installed into an RK5000 Series rack mount chassis, which can  
be mounted into an industry-standard 19-inch (48.26 cm) equipment rack. The RK5000 Series rack  
mount chassis includes the following models:  
RK5000PS-3U and RK5000-3U: Designed to accommodate fiber optic modules as follows:  
The RK5000PS-3U rack mount chassis provides 12 single-width module slots and a  
power supply.  
The RK5000-3U rack mount chassis provides 14 single-width module slots (a power  
supply is not included). Power to the modules can be supplied using the optional  
external power supply (EPS5000-120).  
For additional information, refer to the RK5000PS-3U/RK5000-3U Fiber Rack Mount Chassis  
Installation manual.  
RK5000PS-5U: Designed to accommodate Enduramodules but can also accommodate fiber  
optic modules with the use of the appropriate adapter kit. The RK5001-1UEXP adapter kit is  
required for installation of the FT82011/FR82011 module into the RK5000PS-5U chassis.  
For information about the RK5000PS-5U chassis, refer to the RK5000PS-5U Rack Mount Chassis  
Installation manual.  
MOUNTING THE FT82011/FR82011 MODULE TO A WALL  
The FT82011/FR82011 module can be mounted to a wall in the following ways:  
Using the supplied wall clip for attachment of a single module to a wall. For installation  
instructions, refer to the Mounting the FT82011/FR82011 Module Using the Wall Clip section.  
Using the optional WM5001 wall mount kits, which are designed for mounting of single-width  
fiber optic modules. The WM5001-3U base kit allows mounting of a single module to a wall.  
The WM5001-3UEXP expansion kit allows mounting of an additional module. It is  
recommended that a maximum of three expansion kits be used with the base kit, allowing a  
maximum of four single-width modules to be mounted to a wall.  
NOTE: The WM5001 wall mount kits can be used with the WM5002 wall mount kits, which are  
designed for mounting of double-width fiber optic modules. If mounting a mix of single-width  
and double-width modules is desired, it is recommended that a maximum of two single-width  
modules and one double-width module be mounted in combination with one another.  
For mounting instructions using the wall mount kits, refer to the WM5000 Series Wall Mount  
Kit Installation manual.  
14  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Mounting the FT82011/FR82011 Module Using the Wall Clip  
NOTE: Before mounting the FT82011/FR82011 module to a wall, ensure that there is adequate space  
at both ends for viewing the front-panel LEDs and for making the various rear-panel cable  
connections.  
To attach the FT82011/FR82011 module to a wall using the supplied wall clip, refer to Figure 5 and do  
the following:  
1. Using the two vertical or horizontal wall-mounting holes, attach the wall clip to a wall using  
two screws (not provided).  
2. Slide the module into the clip until the two holes on the bottom of the module align with the  
two holes on the lower flange of the clip.  
3. Attach the module to the clip using the two Phillips pan head screws provided for the clip.  
UPPER  
FLANGE  
VERTICAL  
MOUNTING HOLE (2)  
HORIZONTAL  
MOUNTING HOLE (2)  
LOWER  
FLANGE  
SCREW, PHILLIPS  
PAN HEAD WITH  
LOCK WASHER (2)  
WALL CLIP  
Figure 5. Mounting the FT82011/FR82011 Module Using the Wall Clip  
C2653M (6/07)  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
CONNECTIONS  
Connections to the FT82011/FR82011 module are made on the rear panel of the unit (refer to Figure 6).  
POWER/ALARM CONNECTION  
FOR RACK-MOUNTED MODULE  
POWER CONNECTION  
FOR STAND-ALONE MODULE  
FIBER OPTIC CABLE  
10/100 NETWORK CABLE  
Figure 6. FT82011/FR82011 Module Connections  
As illustrated in Figure 6, FT82011/FR82011 connections consist of the following:  
Power connection  
NOTES:  
A 12 VDC or 24 VAC power supply can be used to power the module when used as a  
stand-alone unit. A 12 VDC power supply is provided. If a 24 VAC power supply is used,  
the power supply must be a Listed Direct Plug-In Power Unit marked as Class 2 and  
rated as 24 VAC, 0.50 A (minimum output).  
In extreme temperature conditions, it is recommended that an industrial-rated outdoor  
power supply be used.  
10BASE-T/100BASE-TX connections  
NOTES:  
Use Category 5e or a higher category of cable to connect to a 10BASE-T/100BASE-TX  
port. Cable length must not exceed 328 feet (100 meters).  
The 10BASE-T/100BASE-TX port is an auto MDI/MDI-X port; therefore, either a straight-  
through or crossover cable can be used. The port automatically detects the cable type  
that is used. Refer to the Appendix for RJ-45 MDI/MDI-X pinout information.  
16  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Fiber connection  
NOTE: Fiber port A of the FT82011 module connects to fiber port B of the FR82011 module or  
of any other Pelco Ethernet switch that supports wavelength division multiplexing (WDM).  
Similarly, fiber port B of the FR82011 module connects to fiber port A of the FT82011 module or  
of any other Pelco Ethernet switch that supports WDM. Note that port A and port B provide  
wavelength compatibility:  
Multimode fiber port A transmits data at 1310 nm and receives data at 850 nm.  
Multimode fiber port B transmits data at 850 nm and receives data at 1310 nm.  
Single-mode fiber port A transmits data at 1310 nm and receives data at 1550 nm.  
Single-mode fiber port B transmits data at 1550 nm and receives data at 1310 nm.  
C2653M (6/07)  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
LED indicators on the front and rear panels of the FT82011/FR82011 module allow you to monitor  
operational status:  
LED indicators on the front panel allow you to monitor operating power, 100BASE-FX port  
status, and optic signal/laser status. Refer to Table B for information about the front-panel  
indicators and associated troubleshooting guidelines.  
LED indicators on the rear panel allow you to monitor RJ-45 10BASE-T/100BASE-TX port  
status. Refer to Table C for information about the rear-panel indicators and associated  
troubleshooting guidelines.  
Table B. Troubleshooting with Front-Panel Indicators  
Indicator  
Color  
Meaning  
Possible Cause  
Corrective Action  
Power LED (Pelco badge)  
Blue  
Power is  
No action required.  
being applied  
to the module.  
Not lit  
Power is not Power connection is faulty.  
being applied  
to the module.  
Check power connection.  
If module is rack mounted,  
reseat module or power  
supply as necessary.  
Power supply has failed.  
Replace power supply.  
Loss of power occurs due to tripped circuit  
breakers, blown fuses, or faulty electrical  
service.  
Check circuit breakers,  
fuses, or electrical service  
as necessary.  
100BASE-FX Status LED (  
)
Green  
A fiber link is  
established.  
No action required.  
No action required.  
Flashing  
green  
Data activity  
is occurring  
on the fiber  
link—data is  
being trans-  
mitted or  
received.  
(Continued on next page)  
18  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Table B. Troubleshooting with Front-Panel Indicators (Continued)  
Indicator  
Color  
Meaning  
Possible Cause  
Corrective Action  
100BASE-FX Status LED ( ) (Continued)  
Red  
Ethernet link NOTE: In addition to a red 100BASE-FX  
Do any of the following to  
restore the link:  
If a laser fault has  
occurred, refer to the  
in this table for  
Status LED, the Optic Fault LED is green or  
flashing red and the left RJ-45 Port Status  
LED (Link/Activity) is not lit.  
is down.  
A link-down detection condition exists due to  
any of the following fault conditions:  
information.  
Laser fault (Optic Fault LED is flashing red)  
Check the cable and  
external equipment that  
connects to the  
10BASE-T/100BASE-TX  
port on the module. For  
additional information,  
refer to the RJ-45  
10BASE-T/100BASE-TX  
Port Status LED - Left  
section in this table.  
10BASE-T/100BASE-TX port on the  
module does not transmit data to or  
receive data from the external equipment  
connected to it:  
Disconnected or defective Category 5e  
(or higher) cable  
Defective 10BASE-T/100BASE-TX port  
on the module  
Problem with external equipment  
connected to the 10BASE-T/  
100BASE-TX port  
NOTE: A red 100BASE-FX Status LED  
provides a far-end fault indication (FEFI) when  
the remote fiber port cannot detect receipt of  
an optical signal (Optic Fault LED on the  
remote module is red). Due to link-down  
detection, however, the 100BASE-FX Status  
LED lights red regardless of whether the fault  
is due to the failure of a 100BASE-FX transmit  
link or a 10BASE-T/100BASE-TX link.  
Optic Fault LED (  
)
Green  
The optical  
No action required.  
signal is being  
received and  
laser is oper-  
ating properly.  
(Continued on next page)  
C2653M (6/07)  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Table B. Troubleshooting with Front-Panel Indicators (Continued)  
Indicator  
Color  
Meaning  
Possible Cause  
Optic Fault LED ( ) (Continued)  
Ethernet link NOTE: In addition to a red Optic Fault LED, Do any of the following to  
Corrective Action  
Red  
is down. the 100BASE-FX LED and the left RJ-45 Port restore the link:  
Status LED (Link/Activity) LED are not lit.  
Check the connections  
of the fiber optic cable.  
If the cable is  
A link-down detection condition exists due to  
any of the following fault conditions:  
disconnected, connect  
the cable. If the cable is  
defective, replace the  
cable.  
100BASE-FX port does not transmit or  
receive optical signal:  
Disconnected or defective fiber optic  
cable  
Clean, polish, or replace  
fiber optic cable con-  
nectors as necessary.  
Defective 100BASE-FX port on local or  
remote module  
Damaged or dirty fiber optic cable  
connectors on local or remote module  
Check for problems  
with the fiber optic  
installation, for exam-  
ple, excessive dB losses  
in connectors, splices,  
patch panels, cables,  
and so on.  
Optical dB losses in the fiber optic  
installation exceed the optical power  
budget specification stated in the  
Specifications section.  
Laser fault on remote module  
(Optic Fault LED is flashing red on the  
remote module)  
Check power connec-  
tion of the remote  
module. Replace power  
supply if necessary.  
Power not connected to remote  
module  
10BASE-T/100BASE-TX port on the remote  
module does not transmit data to or  
receive data from the external equipment  
connected to it:  
Check the cable and  
external equipment that  
connects to the  
10BASE-T/100BASE-TX  
port on the remote  
module.  
Disconnected or defective Category 5e  
(or higher) cable  
Defective 10BASE-T/100BASE-TX port  
If the 100BASE-FX port  
or 10BASE-T/  
100BASE-TX port on the  
module is defective,  
contact Product  
Problem with external equipment con-  
nected to the 10BASE-T/100BASE-TX  
port  
For additional information, refer to the  
RJ-45 10BASE-T/100BASE-TX Port Status  
LED - Left section in this table.  
Support.  
(Continued on next page)  
20  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Table B. Troubleshooting with Front-Panel Indicators (Continued)  
Indicator  
Color  
Meaning  
Possible Cause  
Optic Fault LED ( ) (Continued)  
Ethernet link NOTE: In addition to a flashing red Optic  
Corrective Action  
Flashing  
red  
Ensure that module oper-  
is down.  
Fault LED, the 100BASE-FX LED is red and the ates according to operat-  
left RJ-45 Port Status LED (Link/Activity) LED ing conditions stated in the  
is not lit.  
Specifications section, and  
then cycle the power.  
If problem persists,  
Laser has shut down due to either of the  
following fault conditions:  
contact Product Support.  
Module is operating in extreme  
environmental conditions; for example,  
operating temperature is below or above  
recommended range as stated in the  
Specifications section.  
Laser has reached end of life.  
C2653M (6/07)  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Table C. Troubleshooting with Rear-Panel Indicators  
Indicator  
Color  
Meaning  
Possible Cause  
Corrective Action  
RJ-45 10BASE-T/100BASE-TX Port Status LED - Left (Link/Activity)  
Amber  
A 10BASE-T  
link is estab-  
lished.  
If 10BASE-T operation is desired, no  
action is required. If 10BASE-T operation  
is not desired, refer to the Setting  
Operation section in this manual for  
information.  
Flashing Data activity  
amber  
If 10BASE-T operation is desired, no  
action is required. If 10BASE-T operation  
is not desired, refer to the Setting  
Operation section in this manual for  
information.  
is occurring  
on the  
10BASE-T  
link—datais  
being trans-  
mitted or  
received.  
Green  
A 100BASE-  
TX link is  
established.  
If 100BASE-TX operation is desired, no  
action is required. If 100BASE-TX  
operation is not desired, refer to the  
Modes of Operation section in this  
manual for information.  
Flashing Data activity  
green  
If 100BASE-TX operation is desired, no  
action is required. If 100BASE-TX  
operation is not desired, refer to the  
Modes of Operation section in this  
manual for information.  
is occurring  
on the  
100BASE-TX  
link—datais  
being trans-  
mitted or  
received.  
(Continued on next page)  
22  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table C. Troubleshooting with Rear-Panel Indicators (Continued)  
Indicator  
Color  
Meaning  
Possible Cause  
Corrective Action  
RJ-45 10BASE-T/100BASE-TX Port Status LED - Left (Link/Activity) (Continued)  
Not lit  
Ethernet link A link-down detection condition Do any of the following to restore the  
is down.  
exists due to any of the following link:  
fault conditions:  
Check the cable that connects to the  
10BASE-T/100BASE-TX port on the  
module:  
10BASE-T/100BASE-TX fault  
on local module (Optic Fault  
LED is green or blinking red  
and 100BASE-FX Status LED is  
red)  
If the cable is disconnected from  
the module or from the  
10BASE-T/100BASE-TX compati-  
ble device, connect the cable.  
or  
10BASE-T/100BASE-TX fault  
on remote module (Optic Fault  
LED is red and 100BASE-FX  
Status LED is not lit on local  
module):  
If the cable is defective, replace  
the cable. Use Category 5e or  
higher cable.  
Ensure that the cable is the  
proper length. Cable length must  
not exceed 128 feet (100 meters).  
Disconnected or defective  
Category 5e (or higher)  
cable  
Replace the module if the  
10BASE-T/100BASE-TX port is  
defective.  
Cable is not the proper  
type.  
Check the external equipment that  
connects to the 10BASE-T/  
100BASE-TX port on the module.  
Ensure that the equipment is  
powered on.  
Cable is not the proper  
length.  
Defective 10BASE-T/  
100BASE-TX port  
Problem with external  
equipment connected to  
the 10BASE-T/  
Set the duplex mode setting on  
modules to match one another (auto-  
negotiation or forced half-duplex or  
full-duplex). Refer to the Setting  
of Operation section in this manual  
for information.  
100BASE-TX port  
Duplex mode setting (half-  
duplex or full-duplex) does  
not match the duplex mode  
setting of the remote  
module.  
Refer to the Optic Fault LED and  
this table to troubleshoot  
100BASE-FX port on the  
module does not transmit or  
receive optical signal (Optic  
Fault LED is red and  
100BASE-FX fault conditions.  
100BASE-FX Status LED is not  
lit).  
(Continued on next page)  
C2653M (6/07)  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table C. Troubleshooting with Rear-Panel Indicators (Continued)  
Indicator  
Color  
Meaning  
Possible Cause  
Corrective Action  
RJ-45 10BASE-T/100BASE-TX Port Status LED - Right (Duplex/Collision)  
Amber  
Port is set to  
10BASE-T  
full-duplex  
mode.  
If 10BASE-T full-duplex operation is  
desired, no action is required. If  
10BASE-T full-duplex operation is not  
desired, refer to the Setting 10BASE-T/  
section in this manual for information.  
Flashing Port is set to Normal or excessive collisions  
If a normal collision occurs, no action is  
required.  
If a problem with the network exists due  
to excessive collisions, do any of the  
following as appropriate:  
amber  
10BASE-T  
half-duplex  
mode and  
network  
occur on a half-duplex link.*  
collision has  
occurred.*  
If half-duplex mode is not required,  
set the TX Mode switch to full-  
duplex mode by means of auto  
negotiation or by forcing the mode  
(refer to the Setting 10BASE-T/  
tion section in this manual for  
information).  
If half-duplex mode is required, do  
any of the following as applicable:  
Replace the network cable if it is  
defective or if it is not the proper  
cable type. Use Category 5e or  
higher cable.  
Ensure that the cable is the  
proper length. Cable length must  
not exceed 328 feet (100 meters).  
Replace the network interface  
card (NIC) if it is defective or if it  
is incompatible.  
Segment the network.  
(Continued on next page)  
24  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table C. Troubleshooting with Rear-Panel Indicators (Continued)  
Indicator  
Color  
Meaning  
Possible Cause  
Corrective Action  
RJ-45 10BASE-T/100BASE-TX Port Status LED - Right (Duplex/Collision) (Continued)  
Green  
Port is set to  
100BASE-TX  
full-duplex  
mode.  
If 100BASE-TX full-duplex operation is  
desired, no action is required.  
If 100BASE-TX full-duplex operation is  
not desired, refer to the Setting  
Operation section in this manual for  
information.  
Flashing Port is set to Normal or excessive collisions  
If a normal collision occurs, no action is  
required.  
green  
100BASE-TX occur on a half-duplex link.*  
half-duplex  
mode and  
network  
If a problem with the network exists due  
to excessive collisions, do any of the  
following as appropriate:  
collision has  
occurred.*  
If half-duplex mode is not required,  
set the TX Mode switch to full-  
duplex mode by means of auto  
negotiation or by forcing the mode  
(refer to the Setting 10BASE-T/  
tion section in this manual for  
information).  
If half-duplex mode is required, do  
any of the following as applicable:  
Replace the cable if it is defective  
or if it is not the proper cable  
type. Use Category 5e or higher  
cable.  
Ensure that the cable is the  
proper length. Cable length must  
not exceed 328 feet (100 meters).  
Replace the network interface  
card (NIC) if it is defective or if it  
is incompatible.  
Segment the network.  
(Continued on next page)  
C2653M (6/07)  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table C. Troubleshooting with Rear-Panel Indicators (Continued)  
Indicator  
Color  
Meaning  
Possible Cause  
Corrective Action  
RJ-45 10BASE-T/100BASE-TX Port Status LED - Right (Duplex/Collision) (Continued)  
Not lit  
Port is set to  
10BASE-T  
half-duplex  
mode and no  
collisions  
are  
If 10BASE-T half-duplex operation is  
desired, no action is required.  
If 10BASE-T half-duplex operation is not  
desired, refer to the Setting 10BASE-T/  
section in this manual for information.  
detected.*  
*A collision is a normal event on a half-duplex Ethernet link. A collision occurs when two or more  
devices, referred to as stations, attempt to transmit at the same time on a shared physical medium.  
Ethernet uses the CSMA/CD (Carrier Sense Multiple Access/Collision Detect) media access method by  
which two or more stations share a common transmission medium. Using CSMA/CD, a station monitors  
the medium and transmits a message in bit-serial form when it senses that no other station is  
transmitting. If, after initiating a transmission, the message collides with that of another station, each  
transmitting station then intentionally transmits for an additional predefined period to ensure  
propagation of the collision throughout the system. To avoid another collision, each station waits a  
random amount of time (backoff) before attempting to transmit again.  
Excessive collisions occur when retransmission of a frame fails after 16 consecutive times and the  
frame is dropped. Excessive collisions may indicate that the network is becoming congested.  
26  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
PERFORMANCE  
Switch Type  
Unmanaged Layer 2  
Switch Method  
Data Rate  
Store and forward  
10/100 Mbps  
Compliance  
Interface  
IEEE 802.3, 802.3u, 802.3x  
Auto MDI/MDI-X  
Operating Mode  
Address Table Size  
Quality of Service  
Full-duplex or half-duplex  
1,024 MAC address entries with automatic learning and aging  
IEEE 802.1p priority, tag-based, four queues per port,  
weighted fair queuing scheduling  
Maximum Frame Size  
Untagged Ethernet frames up to 1,518 bytes  
Tagged Ethernet frames up to 1,522 bytes  
GENERAL  
Operating Temperature  
Input Power Requirements  
LED Indicators  
-40° to 167°F (-40° to 75°C)  
12 VDC or 24 VAC, 0.50 A  
Power  
100BASE-FX port status (link/activity, FEFI)  
Optic Fault (optic signal/laser status)  
10BASE-T/100BASE-TX port status (two LEDs:  
link/activity and speed, duplex/collision and speed)  
8.75" D x 1.08" W x 4.81" H  
Dimensions  
Unit Weight  
(22.23 x 2.74 x 12.22 cm)  
1.6 lb (0.73 kg)  
MECHANICAL  
Connectors  
Rack Power/Alarm  
Stand-Alone Power  
Electrical  
One 4-pin connector  
One 2-pin connector, screw terminal  
One RJ-45, 10BASE-T/100BASE-TX  
One single-fiber ST or SC  
Fiber Optic  
C2653M (6/07)  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPTICAL POWER BUDGET AND MAXIMUM TRANSMISSION DISTANCE  
Model Number  
Wavelength  
(Transmit/Receive)*  
Optical  
Power Transmission  
Maximum  
Transmitter  
End  
Receiver  
End  
Fiber Port A Fiber Port B Budget  
Multimode (62.5/125 μm)  
Distance  
26 dB2 km (1.2 mi)‡  
26 dB2 km (1.2 mi)‡  
FT82011MSTR-1 FR82011MSTR-1 1310/850 nm 850/1310 nm  
FT82011MSCR-1 FR82011MSCR-1 1310/850 nm 850/1310 nm  
Single-Mode (9/125 μm)  
46 km (28.6 mi)§  
FT82011SSTR-1 FR82011SSTR-1 1310/1550 nm 1550/1310 nm 28 dB  
FT82011SSCR-1 FR82011SSCR-1 1310/1550 nm 1550/1310 nm 28 dB 46 km (28.6 mi)§  
* The FT82011 and FR82011 modules are classified by the FDA as Class 1 laser products. For 850 nm,  
the Class 1 laser limit is <0.78 mW. For 1310 nm, the Class 1 laser limit is <15.6 mW. For 1550 nm,  
the Class 1 laser limit is <10.0 mW.  
When using 50/125 μm multimode fiber, subtract 3 dB from the optical power budget.  
Maximum transmission distance is limited by fiber bandwidth.  
§ Maximum transmission distance is based on attenuation of 0.5 dB/km plus a 5 dB buffer for  
connector and splice losses.  
NOTES:  
Single-mode FC connector is available upon request. Contact the factory for additional  
information.  
For conformal coated models, replace the first letter F in the model number with the letter C.  
The conformal coated version of FT82011MSTR-1, for example, is CT82011MSTR-1.  
For models with higher optical power budgets, contact the factory.  
28  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix. RJ-45 Connector Pinouts  
Figure 7 illustrates RJ-45 MDI/MDI-X connector pinouts.  
MDI (NORMAL MODE)  
MDI-X (CROSSED MODE)  
8
8
7
6
5
4
3
2
1
7
6
5
4
3
2
1
TX-  
RX-  
TX+  
RX-  
RX+  
RX+  
TX-  
TX+  
Figure 7. RJ-45 MDI/MDI-X Connector Pinouts  
Table D summarizes RJ-45 MDI/MDI-X connector pinouts.  
Table D. RJ-45 MDI/MDI-X Connector Pinouts  
MDI  
MDI-X  
Pin Number  
(Normal Mode)  
(Crossed Mode)  
1
2
3
4
5
6
7
8
RX+  
TX+  
RX-  
TX-  
TX+  
RX+  
Not used  
Not used  
TX-  
Not used  
Not used  
RX-  
Not used  
Not used  
Not used  
Not used  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
     
The materials used in the manufacture of this document and its components are compliant to the  
requirements of Directive 2002/95/EC.  
This equipment contains electrical or electronic components that must be recycled properly to  
comply with Directive 2002/96/EC of the European Union regarding the disposal of waste  
electrical and electronic equipment (WEEE). Contact your local dealer for procedures for recycling  
this equipment.  
30  
C2653M (6/07)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT WARRANTY AND RETURN INFORMATION  
WARRANTY  
Pelco will repair or replace, without charge, any merchandise proved defective in material or workmanship for a period of one year after the date of  
shipment.  
Exceptions to this warranty are as noted below:  
Five years on fiber optic products and TW3000 Series unshielded twisted pair transmission products.  
Three years on Spectra® IV products.  
Three years on Genex® Series products (multiplexers, server, and keyboard).  
Three years on Camclosure® and fixed camera models, except the CC3701H-2, CC3701H-2X, CC3751H-2, CC3651H-2X, MC3651H-2, and MC3651H-  
2X camera models, which have a five-year warranty.  
Three years on PMCL200/300/400 Series LCD monitors.  
Two years on standard motorized or fixed focal length lenses.  
Two years on Legacy®, CM6700/CM6800/CM9700 Series matrix, and DF5/DF8 Series fixed dome products.  
Two years on Spectra III, Esprit®, ExSite, and PS20 scanners, including when used in continuous motion applications.  
Two years on Esprit and WW5700 Series window wiper (excluding wiper blades).  
Two years (except lamp and color wheel) on Digital Light Processing (DLP®) displays. The lamp and color wheel will be covered for a period of  
90 days. The air filter is not covered under warranty.  
Eighteen months on DX Series digital video recorders, NVR300 Series network video recorders, and EnduraSeries distributed network-based video  
products.  
One year (except video heads) on video cassette recorders (VCRs). Video heads will be covered for a period of six months.  
Six months on all pan and tilts, scanners or preset lenses used in continuous motion applications (that is, preset scan, tour and auto scan modes).  
Pelco will warrant all replacement parts and repairs for 90 days from the date of Pelco shipment. All goods requiring warranty repair shall be sent freight  
prepaid to Pelco, Clovis, California. Repairs made necessary by reason of misuse, alteration, normal wear, or accident are not covered under this  
warranty.  
Pelco assumes no risk and shall be subject to no liability for damages or loss resulting from the specific use or application made of the Products. Pelcos  
liability for any claim, whether based on breach of contract, negligence, infringement of any rights of any party or product liability, relating to the Products  
shall not exceed the price paid by the Dealer to Pelco for such Products. In no event will Pelco be liable for any special, incidental or consequential  
damages (including loss of use, loss of profit and claims of third parties) however caused, whether by the negligence of Pelco or otherwise.  
The above warranty provides the Dealer with specific legal rights. The Dealer may also have additional rights, which are subject to variation from state  
to state.  
If a warranty repair is required, the Dealer must contact Pelco at (800) 289-9100 or (559) 292-1981 to obtain a Repair Authorization number (RA), and  
provide the following information:  
1. Model and serial number  
2. Date of shipment, P.O. number, Sales Order number, or Pelco invoice number  
3. Details of the defect or problem  
If there is a dispute regarding the warranty of a product which does not fall under the warranty conditions stated above, please include a written  
explanation with the product when returned.  
Method of return shipment shall be the same or equal to the method by which the item was received by Pelco.  
RETURNS  
In order to expedite parts returned to the factory for repair or credit, please call the factory at (800) 289-9100 or (559) 292-1981 to obtain an authorization  
number (CA number if returned for credit, and RA number if returned for repair).  
All merchandise returned for credit may be subject to a 20% restocking and refurbishing charge.  
Goods returned for repair or credit should be clearly identified with the assigned CA or RA number and freight should be prepaid. Ship to the appropriate  
address below.  
If you are located within the continental U.S., Alaska, Hawaii or Puerto Rico, send goods to:  
Service Department  
Pelco  
3500 Pelco Way  
Clovis, CA 93612-5699  
If you are located outside the continental U.S., Alaska, Hawaii or Puerto Rico and are instructed to return goods to the USA, you may do one of the  
following:  
If the goods are to be sent by a COURIER SERVICE, send the goods to:  
If the goods are to be sent by a FREIGHT FORWARDER, send the goods to:  
Pelco  
Pelco c/o Expeditors  
3500 Pelco Way  
Clovis, CA 93612-5699 USA  
473 Eccles Avenue  
South San Francisco, CA 94080 USA  
Phone: 650-737-1700  
Fax: 650-737-0933  
REVISION HISTORY  
Manual #  
Date Comments  
C2653M-BETA 5/07 Preliminary version.  
C2653M 6/07 Official release.  
Pelco, the Pelco logo, Camclosure, Esprit, Genex, Legacy, and Spectra are registered trademarks of Pelco.  
Endura, ExSite, and Spectra III are trademarks of Pelco.  
DLP is a registered trademark of Texas Instruments, Inc.  
©Copyright 2007, Pelco.  
All rights reserved.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
Worldwide Headquarters  
3500 Pelco Way  
Clovis, California 93612 USA  
USA & Canada  
Tel: 800/289-9100  
Fax: 800/289-9150  
International  
Tel: 1-559/292-1981  
Fax: 1-559/348-1120  
ISO9001  
Australia Canada Finland France Germany Italy Macau The Netherlands Russia Singapore  
|
|
|
|
|
|
|
|
|
South Africa Spain Sweden United Arab Emirates United Kingdom United States  
|
|
|
|
|
Download from Www.Somanuals.com. All Manuals Search And Download.  

Pentax Digital Camera 15073 User Manual
Pentax Digital Camera ZX 7 User Manual
Philips Baby Accessories SCF176 User Manual
Philips Computer Monitor 107P40 User Manual
Philips GPS Receiver 190CW9 User Manual
Philips Switch SWV2054W User Manual
Philips Universal Remote SRU3003 27 User Manual
Philips VCR VR 107 User Manual
Planet Technology Network Router IAD 300 User Manual
PYLE Audio Car Stereo System PLD144 User Manual