PSB Speakers Microwave Oven G5C 0018 User Manual

PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
GLACIER  
Cycling Refrigerated Compressed Air Dryers with “Zero-Loss” Drain Trap  
Operation & Maintenance Manual  
MODELS G5C 0018 thru G5C 0250  
- TABLE OF CONTENTS -  
1.0  
GENERAL  
2
1.1 How to use this manual  
1.2 Symbols  
1.3 Warranty  
1.4 Standard Equipment  
1.5 Description of Operation  
1.6 Use  
1.7 General Safety Instructions  
2.0  
3.0  
MACHINE UNPACKING AND HANDLING  
2.1 Unpacking and handling  
2.2 Package disposal  
3
4
5
2.3 Returned Equipment  
SET-UP  
3.1 Positioning  
3.2 Installation  
3.3 Filling the thermal mass reservoir  
3.4 Start-Up  
3.5 Dryer Transportation or Long-Term Storage  
4.0  
MAINTENANCE  
4.1 Weekly  
4.2 Monthly  
4.3 Semi-annually  
5.0  
6.0  
EQUIPMENT DATA  
5
6
CONTROL PANEL OPERATION  
6.1 Status LEDs  
6.2 Button Functions  
6.3 Set Point Modification  
6.4 Digital Display  
6.5 Error Codes  
7.0  
8.0  
TROUBLESHOOTING  
7
8
INTELLIDRAIN  
8.1 Operation  
8.2 Controls  
8.3 Maintenance  
9.0  
10.0  
11.0  
12.0  
DIMENSIONAL DATA  
9
REFRIGERATION CIRCUIT DIAGRAMS  
ELECTRICAL WIRING DIAGRAMS  
SYSTEM INSTALLATION & LAYOUT  
10  
10  
13  
1/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
1.6 Use  
The use of a dryer is recommended for nearly all compressed air applications, but especially when high purity and low moisture  
content is required, such as in the pharmaceutical & food industry, medical applications and for coating & painting applications.  
1.7 General Safety Instructions  
Read this manual carefully before performing any operation. This machine has been designed and manufactured to be used only as  
described below. The supplier is not responsable for difficulties associated with operation other than the intended use or operation  
that is not in compliance with the instructions mentioned in this manual. All maintenance or cleaning operations involving interior  
parts must be performed by trained technicians only.  
ALWAYS:  
Always be familiar with all controls.  
Always be sure that the dryer is isolated from the compressed air network (inlet and outlet valves closed) and that internal  
pressure has been released before performing any maintenance.  
Always disconnect electrical power and allow 15 minutes for the inner parts to cool down before removing the protection panels.  
Always be sure to disconnect electrical power before removing the cooling fan protection grill.  
Always be sure that all protection panels are properly attached during operation and after any maintenance operation.  
NEVER:  
Never place flammable objects near the dryer.  
Never use the dryer if the power cable is faulty or the connection is not safe.  
Never allow anyone to operate the dryer without giving him/her proper instructions.  
Never make any alterations to safety parts.  
Never strike or use excessive force on internal parts.  
Never touch any part of the cooling circuit when the machine is running. They are very hot!  
Never drain the condensate directly into the sewage system... request PSB-General Air oil/water separator information  
All installation, use and maintenance operations must be perfomed according to the instructions detailed in this manual. All  
dryer maintenance should only be performed by qualified personnel taking the proper safety precautions.  
2.0 MACHINE UNPACKING AND HANDLING  
2.1 Unpacking and Handling  
The dryer is shipped on a wooden skid and packaged in a protective cardboard carton with banding straps. The package must  
always be lifted from the bottom and must be kept in an upright position at all times. Unpack the dryer by cutting straps (always  
wear safety gloves and eye protection and cut either with scissors or cutting nippers), removing the carton from the top and moving  
the dryer from the wooden pallet to the chosen position.  
2.2 Package Disposal  
It is recommended that the packaging materials be retained at least thoughout the warranty period. Should the dryer need to be  
transported for service, the original packaging will allow for easier and safer shipping.  
2.3 Returned Equipment  
Repack the dryer in its original carton or with one of the same dimensions.  
The dryer must be kept vertical and packed as supplied from the manufacturer.  
Do not transport the dryer without proper packing, shipment damage remains the responsibility of the sender.  
Materials returned without proper packing and authorization documents will not be accepted.  
3/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
3.0 SET-UP  
3.1 Positioning  
The dryer should be located in an area with a flat floor and protection against weather conditions and, if possible, direct sun light.  
The area must also be properly ventilated (& heated, if necessary) so that the temperature is kept between 40 °F and 110 °F when the  
dryer is running (remember that the operating dryer will add heat to the room). It must also be large enough to allow at least three  
feet of free space adjacent to both the condenser air inlet and outlet grills to allow for proper unit cooling.  
3.2 Installation  
Air by-pass piping is recommended to allow uninterrupted air service during instances of maintenance of repair.  
Prior to installation check to insure that the compressed air piping is free of debris or other contaminants.  
Connect the dryer to the compressed air line in accordance with one of the diagrams shown in section 11 and per unit labeling.  
Always use a back-up wrench to prevent damage to the connections during piping of the air inlet and outlet.  
Make sure that line power agrees with the unit data plate and the service complies with local electrical codes.  
Always include a fused safety switch in the line power supply (refer to data plate amperage for proper selection).  
A particulate filter is recommended at the air inlet to avoid any deposit of solid particles into the dryer.  
Position the dryer so that all controls can be easily read and so that all maintenance operations are easily performed.  
Connect the condensate drain tube in compliance with local regulations. The condensate is a pollutant and cannot be drained  
directly into the sewage system. A Motivair oil/water separator of suitable capacity is recommended.  
3.3 Filling The Thermal Mass Reservoir  
Remove the threaded plug (A) from the fill port located on the top panel of the dryer.  
Slowly fill the reservoir with clean, tap water until it can be seen coming from the flexible overflow tube (B) at the rear of the dryer.  
Replace the fill port plug.  
3.4 Start-Up  
Close inlet and outlet valves, switch on S1 and ON/OFF (hold for 3 seconds), and check for the pilot light on the control panel.  
Allow the dryer to run until the word “ICE” appears in the digital display (usually about 15 minutes).  
Open the outlet air valve completely and then gradually pressurize the dryer by slowly opening the inlet air valve.  
Compressed air flow rates in excess of rating will reduce performance but will not compromise safety.  
4/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
3.5 Dryer Transportation or Long-Term Storage  
Close inlet and outlet valves, switch off the devices (S1) and (ON/OFF), and disconnect power.  
Depressurize the air circuit using the condensate trap TEST button & remove the fill port plug to vent the reservoir.  
Drain the reservoir tank into a suitably sized container by removing right side panel (B) & turning drain valve (A) counter-  
clockwise.  
Replace the fill port plug & close the drain valve (A) by turning clockwise.  
4.0 MAINTENANCE  
4.1 Weekly  
Visually inspect for proper condensate drain operation.  
4.2 Monthly  
Isolate the dryer from the compressed air system by closing inlet & outlet valves and release pressure.  
Clean or replace condesate drain trap filter to remove any accumulated debris.  
4.3 Semi-annually  
Check compressor electrical current draw against amperage listed on the data plate.  
Remove power from the dryer and clean condenser finned surfaces with compressed air jet.  
5.0 EQUIPMENT DATA  
G5C-18  
18  
G5C-30  
30  
G5C-50  
60  
G5C-75  
75  
G5C-100  
100  
G5C-120  
120  
G5C-150  
150  
G5C-200  
200  
G5C-250  
250  
G5C-250  
250  
Model  
Capacity (scfm)*  
Compressor Power (HP)  
Power Supply (V/Ph/Hz)  
Rated Current (A)  
Full Load Current (A)  
Refrigerant Type  
1/6  
1/4  
1/3  
1/2  
¾
1
1-1/2  
230/1/60  
7.5  
1-1/2  
230/1/60  
7.5  
2
2
115/1/60  
1.1  
115/1/60  
3.7  
115/1/60  
5.2  
115/1/60  
6.8  
115/1/60  
8.1  
115/1/60  
9.2  
230/1/60  
8.5  
460/3/60  
3
2
4.6  
6.8  
8
9.8  
11  
8.7  
10.5  
12.5  
R-134a  
2.0  
5.2  
R-134a  
0.66  
1/2  
R-134a  
0.79  
1/2  
R-134a  
1.21  
3/4  
R-134a  
1.21  
3/4  
R-134a  
1.21  
¾
R-134a  
1.32  
1-1/2  
203  
R-134a  
1.75  
R-134a  
2.16  
R-134a  
2.0  
Refrigerant Charge (LBS)  
Connection Size F (NPT)  
Weight (lbs)  
1-1/2  
232  
1-1/2  
232  
1-1/2  
247  
1-1/2  
247  
66  
77  
119  
132  
141  
Max. Air Inlet (°F)  
Max. Ambient (°F)  
Max. Pressure (psig)  
113  
113  
113  
113  
113  
113  
113  
113  
113  
113  
104  
104  
104  
104  
104  
104  
104  
104  
104  
104  
230  
230  
230  
230  
230  
230  
230  
230  
230  
230  
*Rated capacity @ air inlet of 100°F & 100 psig, 100°F ambient & 33 – 39° F leaving dewpoint  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
5/16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
6/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
6.0 CONTROL PANEL OPERATION  
These dryers are equipped with an electronic controller. Please note that the SET POINT & other control parameters have been  
optimized and factory set. Altough the set point value can be displayed, the ability to alter these factory settings via the  
digital interface on the front panel has been removed to eliminate the possiblity of unit damage caused by improper settings.  
A description of the operation of the digital interface is provided below however, to facilitate factory-authorized adjustments.  
6.1 Status LEDs  
DP1  
DP2  
DP3  
On  
On  
On  
DX solenoid energized  
Condensate drain valve energized  
Compressor energized  
6.2 Button Functions  
Performs a test of the condensate discharge valve when pressed for more than 3 seconds during the normal  
TEST  
SET  
operation.  
Displays the set point value when pressed during normal operation.  
Stores all changes when pressed after changing set point.  
DOWN  
UP  
Decreases the displayed value when pressed during set point programming (see factory).  
Increases the displayed value when pressed during set point programming (see factory).  
Activates or deactivates unit operation when pressed for 3 seconds. When deactivated, the OFF message  
is displayed.  
ON/OFF  
6.3 Set Point Modification  
Press the SET button (the current set point value is displayed).  
Modify (see factory) the displayed set point value by using the UP or DOWN button (if modification is not performed in 15  
seconds the controller automatically returns to the normal operating display indicating the DEW POINT value).  
Confirm the new set value by pushing the SET button within 10 seconds of the modification, the flashing of the set point value  
confirms acceptance of the new data. If the modified data is not confirmed within 10 seconds, the new data will not be stored and  
the controller will revert to the previous set point.  
Please note that changes to the set point WILL adversely effect dryer operation and  
therefore should only be done by authorized technical service personnel.  
7/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
6.4 Digital Display  
Message (NOT flashing)  
Numeric Value  
“ICE”  
Description  
Dewpoint Temperature  
Energy Saving Standby Mode  
6.5 Error Codes  
The controller recognizes specific types of operational errors. When an error occurs the display shows a flashing alarm message  
alternating with the current dewpoint value, as described below:  
Message (flashing)  
Cause  
HtA  
PF1  
High Dewpoint Temperature  
Temperature Sensor failure  
All the alarms except for PF1 are automatically reset when the cause is removed. PF1 must be cleared by switching the unit off and  
then re-started. PF1 has a priority over all the other displayed messages.  
7.0 TROUBLESHOOTING  
SYMPTOM  
POSSIBLE ORIGIN  
SOLUTION  
Temperature shown in  
display is higher than  
preset value  
High compressed air inlet temperature  
High compressed air flow  
Reduce air temperature to within design limits  
Reduce air flow to within design limits  
Increase ventilation rate of installation area  
Clean condenser  
High ambient air temperature  
Fouled refrigerant condenser  
Low refrigerant charge  
Locate & repair leak & re-charge  
Repair or replace  
Faulty refrigerant compressor  
Faulty refrigerant solenoid valve  
Faulty fan thermostat  
Repair or replace  
Repair or replace  
Faulty control relay  
Repair or replace  
Refrigerant high pressure switch open  
Eliminate cause & reset switch  
Excessive air pressure  
drop across dryer  
Inlet/outlet piping reversed  
Thermostat sensor out of well  
Faulty thermostat  
Connect properly  
Re-install  
Repair or replace  
Ambient temperature below freezing  
Obstruction in air circuit  
Install dryer in heated space  
Locate & remove blockage  
Water present in air  
downstream of dryer  
Air by-pass valve open  
Close valve  
Condensate drain strainer fouled  
Faulty condensate drain  
Clean strainer  
Repair or replace  
See Symptom #1 above  
High dew point temperature  
8/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
Fan doesn't start and/or  
stop.  
Faulty fan thermostat or pressostat  
Low refrigerant charge  
Repair or replace  
Locate & repair leak & re-charge  
Install dryer in heated space  
Low load with low ambient temprature  
9/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
8.0 ZERO-LOSS DRAIN TRAP  
8.1 Operation  
The Zero-loss drain is designed to remove condensate from any compressed air application  
without air loss. It is completely automatic, and requires no external settings or  
adjustments.  
A two-stage condensate level sensor installed in the trap’s internal cavity signals both the  
beginning and the end of the discharge cycle so the trap discharges only liquid and no air is  
wasted regardless of load.  
At start-up, purge any air from the trap’s inlet connection by pushing the TEST button  
several times.  
The factory-installed inlet filter should be examined and cleaned daily for the first week of  
operation, and monthly thereafter.  
8.2 Controls  
Green LED:  
Red LED:  
Pushbutton:  
Electrical Power ON  
Discharge Solenoid Energized (valve open)  
Discharge TEST (Open Valve Manually)  
8.3 Maintenance  
Close the ball valve located on the filter/stop installed at the drain trap inlet.  
Depressurize the trap by by pushing the TEST button.  
Unscrew the plug in the end of the filter/stop to access the filter screen.  
Clean the filter screen with a compressed air jet.  
Reassemble and open filter/stop valve.  
10/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
9.0 DIMENSIONAL DATA  
MODEL G5C 18 THRU 30  
MODEL G5C 50 THRU 100  
MODEL G5C 120 THRU 250  
11/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
10.0 REFRIGERATION CIRCUIT DIAGRAMS  
1
2
3
4
5
6
7
Compressor  
8
9
Refrigerant Filter/Dryer  
DX Solenoid Valve  
Condenser  
Fan  
10 Fan Pressure Switch  
Air-to-Air Economizer  
Evaporator  
11 Refrig. High Pressure Switch  
12 Condensate Separator  
Zero-Loss Drain Valve  
Capiliary Tubes  
13 Condensate strainer & Shut-Off  
G5C 18 THRU 75 Cod. 713.001.04.00 – Rev. 01 – 28.09.00  
11.0 ELECTRICAL WIRING DIAGRAMS  
G5C 100 THRU 250 Cod. 713.001.01.00 – Rev. 01 – 28.09.00  
G5C 18 THRU 75 (115/1/60) Cod. 714.001.02.00  
12/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
G5C 100 (115/1/60) Cod. 714.001.01.00  
µ
G5C 120 (115/1/60) Cod. 714.003.03.00  
13/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
G5C 150 (230/1/60) Cod. 714.003.01.00 – Rev. 05 –10.01.01  
µ
ICE 200  
ICE 250  
µ
µ
µ
µ
µ
µ
14/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
G5C 200 - 250 (230/1/60) ELECTRIC WIRING DIAGRAM - Cod. 714.002.01.00 – Rev. 05 – 29.04.02  
G5C Dryers  
G5C 200 - 250 (230/1/60) TERMINAL BLOCK DIAGRAM - Cod. 714.002.01.00 – Rev. 05 – 29.04.02  
µ
µ
µ
µ
G5C 200 - 250 (230/1/60) COMPONENTS LAYOUT - Cod. 714.002.01.00 – Rev. 05 – 29.04.02  
15/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
G5C 250 (460/3/60) POWER WIRING DIAGRAM - Cod. 714.003.02.00 – Rev. 03 – 02.05.02  
G5C 250 (460/3/60) CONTROL WIRING DIAGRAM - Cod. 714.003.02.00 – Rev. 03 – 02.05.02  
16/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
G5C Dryers  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
G5C 250 (460/3/60) TERMINAL BLOCK DIAGRAM - Cod. 714.003.02.00 – Rev. 03 – 02.05.02  
G5C 250 (460/3/60) COMPONENTS LAYOUT - Cod. 714.003.02.00 – Rev. 03 – 02.05.02  
17/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501  
Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com [email protected]  
G5C 250 (460/3/60) PARTS LIST - Cod. 714.003.02.00 – Rev. 03 – 02.05.02  
G5C Dryers  
12.0 SYSTEM INSTALLATION & LAYOUT DIAGRAM  
1
2
3
4
5
6
7
8
9
Air Compressor  
Aftercooler  
Condensate Separator  
Receiver Tank  
Automatic Drain  
Particulate Prefilter  
Dryer  
IntelliDrainTM  
Filter 0.10 micron  
10 Filter 0.01micron  
11 Activated Carbon Filter  
12 Water/Oil Separator  
18/16  
Cod. 710.062.01.00 – Rev.08 – 02.05.02  
Download from Www.Somanuals.com. All Manuals Search And Download.  

PB Heat Boiler MI User Manual
Peerless Industries TV Mount SF650 User Manual
Pelco Blower BKMT10 230 User Manual
Philips Camcorder SJM2114 User Manual
Philips Iron HI515 User Manual
Pioneer CD Player PD F407 User Manual
Plantronics Network Card APC 4 User Manual
Polk Audio Speaker System AMR 130 User Manual
PowerTec Outboard Motor DFS 1 User Manual
ProForm Home Gym PFEL87073 User Manual