Paradox Hellas SA Network Card CAA470A EI02 User Manual

CAA470A-EI02  
PRINTED IN CANADA 07/2004  
Figure 3: Setting the A+ and B- jumpers  
Assign Address (1 and 2)  
Access during Communication Failure (5 and 6)  
DIP switches 5 and 6 determine the access to  
the protected doors during a communication  
failure.  
2-Door Expansion Module  
DIP switches 1 and 2 determine the 2-Door  
Expansion Module’s address in the network,  
regardless of the order that they are connected  
to the controller. Centaur recognizes the doors  
according to the DIP switch settings as shown in  
Figure 1.  
Jumpers set to low Jumpers set to high  
A+ B-  
A+ B-  
LOW  
HIGH  
LOW  
HIGH  
Switch Setting During a Communication Failure:  
Figure 1: Setting the network address  
“No Card”  
5 = off (0)  
6 = off (0)  
350mA/700mA Battery Charging Jumper  
The 350mA/700mA Jumper allows you to select the  
charging current for the backup battery of the 2-Door  
Expansion Module. Charging the battery at 350mA takes  
longer, but consumes less power. Charging the battery at  
700mA takes less time, but consumes more power.  
Access is denied to all cards and doors  
are locked until communication is restored.  
“2 Cards”  
5 = on (1)  
6 = off (0)  
Access is granted only when 2 cards of  
a valid format are presented to the reader.  
“All Cards”  
Access is granted when any card with  
a valid format is presented to the reader.  
5 = off (0)  
6 = on (1)  
CA-A470-A  
Instructions  
Figure 4: Setting the 350mA/700mA jumper  
Jumper set  
as 350mA  
Jumper set  
as 700mA  
“Unlock Door”  
Doors are unlocked until communication  
is restored.  
5 = on (1)  
6 = on (1)  
780 Industriel Blvd., Saint-Eustache (Quebec) J7R 5V3 CANADA  
Tel.: (450) 491-7444  
Fax: (450) 491-2313  
Activate Output on Communication Failure (7)  
DIP switch 7 determines if OUT5 and OUT6 will  
pulse during a communication failure. When DIP  
switch 7 placed in the ON position, the outputs on  
the device(s) connected to the OUT5 and OUT6  
terminals will pulse. For example, the LED on  
the reader can pulse to advise users that a  
communication failure has occurred.  
Programming in Centaur  
Using the Centaur Access Control Software, program the  
inputs, outputs, readers, and keypads connected to the 2-  
Door Expansion Module. The options are explained in the  
Centaur Access Control Software Reference Manual.  
Introduction  
Connected to the CT-V900 controller’s expansion bus, the  
2-Door Expansion Module (CA-A470-A) supports two  
readers, two BCD keypads, four zone inputs, 6 outputs  
and two locking devices.  
Centaur will identify the 2-Door Expansion Module by its  
address (see DIP Switches 1 to 4) and will recognize the  
devices as follows:  
DIP Switch (8)  
For future use.  
Address 1 Address 2 Address 3  
Doors  
EOL Jumper  
Specifications  
CA-A470-A Specifications:  
Place the EOL jumper ON if the 2-Door Expansion Module  
is at the beginning (Start Point) or at the end (End Point) of  
the E-bus Network (see Figure 2). Otherwise, place the  
Lock State during Communication Failure  
DIP switches 3 and 4 determine the state of  
Lock #1 and Lock #2 ONLY during a  
communication failure between the 2-Door  
Expansion Module and the controller (CT-V900-  
A). Normally, the lock outputs follow the Lock  
Control for the CT-V900-A. Therefore, the DIP  
switches should have the same setting as the Lock  
Control for the corresponding doors in Centaur.  
Keypad/Reader 1 Door 3  
Keypad/Reader 2 Door 4  
Door 5  
Door 6  
Door 7  
Door 8  
Readers:  
Keypads:  
Inputs:  
connect 2 per module  
connect 2 per module  
4 standard without ATZ, 1 tamper  
6 (open collector)  
EOL jumper OFF.  
Inputs  
Figure 2: Setting the Jumpers  
Z1  
Z2  
Z3  
Z4  
Input 17  
Input 18  
Input 19  
Input 20  
Input 21  
Input 22  
Input 23  
Input 24  
Input 25  
Input 26  
Input 27  
Input 28  
Outputs:  
Lock Outputs:  
2 lock outputs (Form C relays)  
each: 15A @ 16VDC (resistive)  
AC Power:  
Frequency:  
Aux. Current:  
Battery:  
16VAC, 40VA max.  
50Hz/60Hz  
Lock #1 = DIP switch 3  
Lock #2 = DIP switch 4  
Outputs  
OUT1  
OUT2  
OUT3  
OUT4  
OUT5  
OUT6  
Output 7  
Output 8  
Output 9  
Output 13 Output 19  
Output 14 Output 20  
Output 15 Output 21  
500mA (max.)  
OFF  
=
De-energized:  
12VDC, 7Ah  
During a communication failure, the normal state of  
the lock output is De-energized. When Lock #1 or  
Lock #2 is activated, power is applied to the  
corresponding lock output to unlock the door.  
Activation depends on the setting of the DIP switches  
5 & 6 (Access during Communication Failure).  
low battery = 10.2VDC  
low battery restore = 12.2VDC  
low battery cut-off = 8.5VDC  
Output 10 Output 16 Output 22  
Output 11 Output 17 Output 23  
Output 12 Output 18 Output 24  
Communication: expansion bus (E-Bus), RS-485, Plug  
and Play, 3 modules per CT-V900  
Doors cannot be defined as Door Type Elevator  
(Door Properties window, General tab, Door  
Type: Elevator) and the module does not support  
Interlock Inputs (Door Properties window, Inputs  
and Outputs tab, Interlock Input).  
o
o
o
o
Operating temp.: 5 C to 55 C (41 F to 133 F)  
ON  
=
Energized:  
During a communication failure, the normal state of  
the lock output is Energized. When Lock #1 or Lock  
#2 is activated, power is removed from the  
corresponding lock output to unlock the door.  
Activation depends on the setting of the DIP switches  
5 & 6 (Access during Communication Failure).  
High/Low Bias Jumpers  
DIP Switches  
Place the A+ and B- jumpers on LOW only if the 2-Door  
In order for new DIP switch settings to take effect,  
Expansion Module is at the beginning (Start Point) of the  
E-bus Network. Otherwise, place the A+ and B- jumpers  
on HIGH (see Figure 2 and Figure 3).  
the 2-Door Expansion Module’s power must be  
disconnected and then reconnected.  
Other modules in the system cannot activate the 2-  
Door Expansion Module’s outputs.  
De-energized: no power in normal state; requires  
power to activate.  
The 2-Door Expansion Module does not support  
Zone Doubling (see Figure 6).  
Energized: power in normal state; remove power  
to activate.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

MSi Laptop CX640 User Manual
NEC Air Conditioner RIH 6867 User Manual
Nokia Network Router M1122 User Manual
NordicTrack Treadmill NTL129054 User Manual
Nortel Networks Switch Contivity1510D User Manual
Oregon Scientific Radar Detector WMR90A User Manual
Palsonic Flat Panel Television TFTV683HD User Manual
Panasonic Electric Shaver ES2113 User Manual
Panasonic Electric Shaver ES2218 User Manual
Patton electronic Power Supply 2036 User Manual