Panasonic Smoke Alarm 3309 User Manual

Fire alarm systems  
Enclosed analog  
heat detector  
3309  
Different modes for compatibility with other EBL systems / detectors  
Algorithms for class A1, A2 S or B S  
ATEX compliance  
Waterproof (IP67)  
General  
Algorithms  
The analog heat detector 3309 measures the  
EBL512 / EBL128 use algorithms for class  
A1, A2 S and B S, according to EN54-  
5:2000, for fire alarm detection. Via Win512  
/ Win128 is an algorithm selected for each  
3309 in NORMAL mode.  
temperature through a thermistor.  
The  
temperature range is 0°C to 100°C in steps  
of 0.5°C. The detector has an LED that will  
light up when the detector goes into alarm.  
The detector also has an output for an  
external LED, e.g. 2218.  
ATEX classification  
3309 complies with the ATEX classification  
Ex II 3GD EEx nA II T5.  
Programming/Compatibility  
The address setting tool 3314 is used to set  
the detector's COM loop address. The  
detector has an address label inside, where  
the address is to be written.  
Waterproof  
The thermistor, the LED, all electronics, etc.  
is mounted in a waterproof detector housing,  
mounted on a connection box.  
3314 is also used to set the detector mode.  
NORMAL mode (analog): Used in the  
Label holder  
A label holder, intended for a label showing  
"zone-address" or "technical number", can  
be mounted in the connection box.  
system EBL512 (SW version >2.0) and  
EBL128.  
The detector works as a  
temperature sensor where the analog  
readings (0°C to 100°C) are converted to  
digital "sensor values" that are read and  
evaluated by the c.i.e. Algorithms for  
class A1, A2 S or B S (set in Win512).  
When the class A1 or A2 S algorithm is  
used, 3309 is a spare part for detector  
2340 and when the class B S algorithm is  
used, 3309 is a spare part for 2341.  
Miscellaneous  
The COM loop is connected to the detector,  
which is provided with three pairs of flying  
leads with female push-on connectors.  
Product applications  
Used in the systems EBL512 / 128 / 1000 /  
2000.  
2330 mode (conventional): Used in the  
systems EBL512 / 1000 / 2000 as an  
equivalent to the enclosed addressable  
fixed temperature heat detector 2340  
(60°C), i.e. as a class A2 S heat detector  
(static response temperature 57°C).  
Heat detectors are normally used where  
smoke detectors can not be used or in rooms  
where the temperature can be expected to  
rise rapidly in case of a fire.  
The detector is intended for outdoor use  
(must not be exposed to heavy sunlight) or  
in high humidity indoor premises.  
2312 mode: Not used for 3309.  
Panasonic Electric Works Fire & Security Technology Europe AB  
Jungmansgatan 12, SE-211 19 Malmö, Sweden  
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99  
Download from Www.Somanuals.com. All Manuals Search And Download.  

MTD Snow Blower Attachment 190 822 User Manual
NAD DVD Player T 531 User Manual
NEC Network Router PathManager User Manual
Netopia Network Card Network Adapater User Manual
Niles Audio Speaker CM7SD User Manual
Nostalgia Electrics Food Processor PBM 200 User Manual
Omega Vehicle Security Automobile FSV100 User Manual
Oster Kitchen Grill SPR 060211 334 User Manual
Panasonic Camera Accessories HHR450A User Manual
Panasonic Switch FP X Series User Manual