Orion Car Audio Universal Remote OE331 21 User Manual

GPC Plus Controller  
General Information &  
Application Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OE331-21-GPC  
GPC Plus Controller  
.20 Dia.  
Typ. of 4  
Description  
6.2“  
The OE331-21 General Purpose Con-  
troller Plus (GPC Plus) is used for con-  
trolling equipment or processes that  
cannot be controlled using HVAC con-  
trollers. The Prism computer front end  
software is used to interface with the  
GPC Plus controller functions. The  
GPC Plus Controller provides the flexi-  
bility to control, schedule and/or monitor  
equipment such as unit heaters, ex-  
haust fans, motorized louvers, etc.. The  
GPC Plus has (6) configurable inputs  
which will accept signals from thermis-  
tor temperature sensors, 4-20mA or 0-  
5VDC transmitters or dry contact clo-  
sures. An additional modular input is  
provided for connection of an OE271  
static pressure sensor. The GPC Plus  
has (5) relay outputs for on/off control  
and (2) analog outputs. With the addi-  
tion of the OE352 2 Slot Expansion  
Base Board and (1) OE357 4 Relay  
Expansion Board, (4) additional relay  
outputs are available providing for a  
maximum of (9) usable relay outputs.  
The GPC Plus also has (5) separate 2  
event per day schedules, each with its  
own optimal start functions built in. In  
addition the GPC Plus provides lead/lag  
start capabilities.  
U3  
CX1  
CX2  
RN1  
U2  
CX4  
1
U1  
U4  
TB1  
COMM  
V1  
V2  
V3  
T
SHLD  
R
CX5  
COM1-3  
U5  
LD6  
PAL  
R1  
R2  
R3  
COMM  
RS-485  
COMM  
1
RAM  
EPROM  
LD7  
PWR  
TUC-5R PLUS  
(1 MEG)  
YS101816 REV.  
1
HH  
2
U6  
LD8  
LED1  
R4  
R5  
C1  
LD9  
LED2  
P1  
COM4-5  
R1  
+VREF  
TB2  
CX6  
5.11V  
TEST POINT  
U7  
RV1  
V4  
V5  
EWDOG  
R28  
VREF ADJ  
1
7.3”  
INPUTS  
ADDRESS  
ADD  
U8  
6.6”  
1
2
+VDC  
RN5  
4
NE5090NPB3192  
0PS  
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
PU1  
8
U9  
D6  
16  
32  
CX10  
PU2  
C7  
D7  
PU3  
TOKEN  
R6  
C9  
NETWORK  
D8  
PU4  
U10  
SW1  
D9  
PU5  
L1  
CX12  
D11  
PU7  
D12  
R13  
X2  
C10  
3 6 9 9  
GND  
GND  
A
0 6 3 4 4 C M  
D14  
JP1  
SC1  
C13  
C12  
U13  
R15  
AOUT1  
U12  
AOUT2  
AIN7  
CX14  
C14  
R19  
C16  
U14  
CX13  
U15  
D15  
C20  
C17  
TB4  
GND  
C15  
R22  
D19  
TB3  
PJ1  
GND  
R24  
R25  
CX15  
T
4 C 7 8 2  
R26  
24VAC  
M
PRESSURE  
SENSOR  
EXPANSION  
VR1  
VR2  
T'STAT  
6.7”  
1.1”  
Mounting  
The GPC Plus is provided with an integral backplate for mounting inside of a control enclosure. It is recom-  
mended that the GPC Plus be mounted in the HVAC unit control enclosure, or in a control enclosure in the  
building equipment room. An optional factory control enclosure for the GPC Plus is available.  
Technical Data  
OE331-21-GPCPLUS  
GPC Plus Controller  
Power  
24 Volt AC Weight  
1.5 lb.  
RS-485  
Power Consumption  
Operating Temp  
Operating Humidity  
8 VA Maximum Network Connection  
Protocol  
HSI Open Protocol Token Passing  
RS-485 - 9600 Baud  
10°F to 149°F  
90% RH Non-Condensing Communications  
Inputs:  
Outputs:  
Types of Allowed  
Inputs  
Type III-10kohm sensors Total Relay Qty. On Board  
4-20ma sensors Total Relay Qty. Available With  
5
9
Optional Expansion Board  
N.O. Binary Contact  
N.C. Binary Contact Relay Power Rating  
(2 Amp @ 24 VAC)  
2
Total Inputs Available  
Static Pressure Inputs  
Configurable Inputs  
Schedules Available  
Three Year Warranty  
7
Analog Output Qty.  
1 (Modular ) Analog Output Signal  
Optimal Start Schedules  
(5) 2 Event per day Lead Lag Scheduling  
0-10 VDC  
6
(5) Total - (1) for Each Schedule  
(1) Output can be Configured  
WattMaster reserves the right to change specifications without notice  
Form: ORION-OE331-21-GPCPlusController-01A.doc  
Page 1 of 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OE331-21-GPCPLUS  
GPC Plus Controller  
All Communication Loop Wiring Is  
Straight Through  
U3  
T To T, R To R, SHLD To SHLD  
CX1  
CX2  
RN1  
U2  
CX4  
1
U1  
U4  
TB1  
V1  
V2  
V3  
Local Loop RS-485  
9600 Baud  
COMM  
T
Connect To  
Next Device On  
The Local Loop  
24VAC Power  
For Relay Outputs  
SHLD  
R
CX5  
COM1-3  
U5  
LD6  
PAL  
R1  
R2  
R3  
5 Relay Outputs Are  
Available On Board For  
On/Off Control Of  
Equipment. When  
Required 4 Additional  
Relay Outputs Are  
Available By Using The  
Optional OE357 4 Relay  
Output Expansion  
COMM  
RS-485  
COMM  
1
EPROM  
RAM  
Mini DIN Connector  
For Connection Of Modular  
Service Tool  
LD7  
PWR  
TUC-5R PLUS  
1
HH  
(1 MEG)  
YS101816 REV.  
2
U6  
LD8  
LED1  
R4  
R5  
C1  
LD9  
LED2  
P1  
COM4-5  
R1  
+VREF  
TB2  
CX6  
Pull-up Resistor- Typical  
5.11V  
TEST POINT  
U7  
RV1  
V4  
V5  
EWDOG  
R28  
Analog Inputs AIN1Thru AIN7  
Can Be Used For 10kOhm  
Type III Thermistor, 0-5VDC  
Signal, 4-20mA Signal Or Dry  
Contact Closure Inputs.  
As Required.  
VREF ADJ  
1
INPUTS  
ADD  
ADDRESS  
U8  
+VDC  
1
RN5  
2
NE5090NPB3192  
0PS  
PU1  
4
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
Board. See Below.  
U9  
D6  
8
CX10  
PU2  
16  
C7  
32  
D7  
PU3  
TOKEN  
NETWORK  
R6  
C9  
D8  
U10  
PU4  
SW1  
D9  
L1  
PU5  
CX12  
D11  
D12  
R13  
X2  
C10  
PU7  
9 9 3 6  
GND  
GND  
M C 3 4 0 6 4 A  
D14  
JP1  
SC1  
Note: When Using Sensors or  
Transducers With 4-20 mA Input  
Signal, The Pull-up Resistor For  
The Input Being Used Must Be  
Removed From The Controller  
Board And A 250 Ohm Resistor  
Must Be Wired Between The Input  
Terminal And The Ground Terminal  
On The Controller Board  
C13  
C12  
U13  
R15  
AOUT1  
U12  
AOUT2  
AIN7  
CX14  
C14  
R19  
C16  
U14  
CX13  
U15  
D15  
C17  
TB4  
GND  
PJ1  
C15  
R22  
D19  
TB3  
GND  
GND  
R24  
R25  
C20  
CX15  
Line Voltage  
R26  
24VAC  
24VAC  
PRESSURE  
SENSOR  
24VAC Transformer  
10 VA Mini mum  
EXPANSION  
T'STAT  
VR1  
VR2  
Not Used  
Splice If Req’d  
Analog Input AIN6 Can Only Be Used  
For Connection Of A Static Pressure  
Transducer With Modular Connector  
Connect To  
Expansion Board  
Base (When Used)  
Warning:  
24 VAC Must Be Connected So That All  
Ground Wires Remain Common. Failure To  
Do So Will Result In Damage To The  
Controller  
S.P.  
Transducer  
R 1 4  
D 3  
A C  
:
5 A 2 U 5 L 0 V  
A C T C O N T  
2 4 V D C  
- P S - 1 1 4 G P 5 L  
O M R O N  
A C  
:
5 A 2 U 5 L 0 V  
A C T C O N T  
K1  
U L N 2 8 0 3 A /  
OE357  
4 Relay Output  
Board  
Connect Tubing To High Pressure  
Port (Bottom Tube) and Route To Static  
Pressure Pickup Probe Located In Unit  
Discharge. Leave Port Marked “Lo” Open  
To Atmosphere  
2 4 V D C  
- P S - 1 1 4 G P 5 L  
O M R O N  
U1  
4 Additional Relay Outputs  
Are Available By Using The  
OE357 4 Relay Output  
Expansion Board. The  
OE352 2 Slot Expansion  
Base Board Is also  
K2  
7 4 H C 0 4 N  
A C  
:
5 A 2 U 5 L 0 V  
A C T C O N T  
2 4 V D C  
- P S - 1 1 4 G P 5 L  
O M R O N  
A C  
:
5 A 2 U 5 L 0 V  
A C T C O N T  
2 4 V D C  
- P S - 1 1 4 G P 5 L  
U2  
K3  
RN1  
O M R O N  
P C
YS101790  
4RLY IO BD.  
K4  
Required To Mount The  
OE357 Board.  
L M 3 5 8 N  
Y S 1 0 1 7 8 0  
O D M U T O L O A D L R S U L L 2 A R  
R 4  
R 5  
R 6  
I / O  
Jumper  
Setting  
OE352 2 Slot Expansion Base Board  
JOB NAME  
1.)24 VAC Must Be Connected So  
That All Ground Wires Remain  
Common.  
3.)All Communication Wiring To Be 18  
Ga. Minimum, 2 Conductor Twisted  
Pair With Shield. Belden #82760 Or  
Equivalent.  
FILENAME  
2.)All Wiring To Be In Accordance With  
Local And National Electrical Codes  
and Specifications.  
4.)It Is Recommended That All  
Controllers Address Switches Are  
Set Before Installation.  
G-GPC-PlusCNTRL1A.CDR  
DRAWN BY:  
DATE:  
03/08/05  
B. Crews  
PAGE  
1 Of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DESCRIPTION:  
OE331-21-GPCPLUS  
GPC Plus Controller  
ADDRESS  
ADD  
This Switch Should Be  
In The OFF Position  
As Shown  
1
2
4
8
16  
32  
Note:  
The Power To The Controller Must Be Removed  
And Reconnected After Changing The Address  
Switch Settings In Order For Any Changes To  
Take Effect.  
TOKEN  
NETWORK  
ADDRESS  
ADDRESS  
ADD  
ADD  
Caution  
Disconnect All Communication Loop Wiring  
From The Controller Before Removing Power  
From The Controller. Reconnect Power And  
Then Reconnect Communication Loop Wiring.  
Controller  
Address Switch  
Address Switch Shown Is  
Set For Address 1  
Address Switch Shown Is  
Set For Address 13  
The Address For Each Controller  
Must Be Unique To The Other Controllers  
On The Local Loop.  
For Auto-Zone Systems The Address Must Be  
Set Between 18 to 30  
For All Other Systems The Address Can Be Set  
Between 1 to 59  
INPUTS  
ADD  
ADDRESS  
+VDC  
1
2
RN5  
PU1  
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
GND  
GND  
4
D6  
8
16  
CX10  
PU2  
C7  
32  
D7  
PU3  
R6  
TOKEN  
NETWORK  
D8  
U10  
PU4  
SW1  
D9  
L1  
C9  
PU5  
CX12  
D11  
D12  
R13  
X2  
PU7  
C10  
D14  
JP1  
SC1  
C13  
C16  
U13  
C12  
R15  
AOUT1  
U12  
AOUT2  
AIN7  
CX14  
C14  
R19  
U14  
CX13  
U15  
D15  
C17  
TB4  
GND  
PJ1  
C15  
R22  
D19  
TB3  
GND  
R24  
R25  
C20  
CX15  
R26  
24VAC  
PRESSURE  
SENSOR  
EXPANSION  
VR1  
VR2  
JOB NAME  
FILENAME  
G-GPC-PlusCNTRL1A.CDR  
1.)24 VAC Must Be Connected So  
That All Ground Wires Remain  
Common.  
3.)All Communication Wiring To Be 18  
Ga. Minimum, 2 Conductor Twisted  
Pair With Shield. Belden #82760 Or  
Equivalent.  
DRAWN BY:  
DESCRIPTION:  
DATE:  
03/08/05  
B. Crews  
2.)All Wiring To Be In Accordance With  
Local And National Electrical Codes  
and Specifications.  
PAGE  
4.)It Is Recommended That All  
Controllers Address Switches Are  
Set Before Installation.  
OE331-21-GPCPLUS  
GPC Plus Controller  
2 Of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Purpose Controller  
(GPCPlus )  
January 31, 2005  
Description  
The GPCPlus is a controller designed to “fill in the blanks” between standard off the  
shelf programs and minor non-standard applications. An example of a non-standard  
application might be exhaust fan control, based on building pressure or a simple boiler  
enable controller based on schedules or outdoor air temperature.  
The remainder of this document will describe the I/O configurations that are possible and  
will also include a few sample applications to aid the user in determining if this controller  
will meet their specific requirements.  
Main Status Screen  
The Main Status Screen provides real-time live updates of the current operating  
conditions and is used to access the various setpoint and configuration options.  
No control takes place until the user “configures” the operation of the GPCPlus. Access  
to the various configuration screens is made by a simple left mouse-click on the  
individual reading or output status box for each I/O Point. As a general rule, a left click  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
accesses the configuration for the selected item and a right click accesses the force mode  
options if any are available.  
Analog Inputs  
Relays  
Analog Outputs  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Week Schedules & Holidays  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Analog Input  
Configurations  
The first five analog inputs and input #7 can be configured in several different ways.  
Input #6 can be used for Static Pressure and accepts the standard pressure sensor with the  
phone jack connector, available from WattMaster Controls.  
The following configurations are available:  
1. Thermister Type III Temperature Sensors (Scaled for Fahrenheit)  
2. Thermister Type III Temperature Sensors (Scaled for Celsius)  
3. 4 – 20ma User Scaled  
4. 0 – 5 vdc User Scaled  
5. Wall Sensor Slide Offset  
6. Binary Contact Closure  
7. Read Global Analog Broadcast from another Controller  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Read Global Binary Broadcast from another Controller  
9. Sensor #6 can be assigned to read Static Pressure  
Each input is separately configured so combinations of any type of input on the same  
controller are possible.  
All readings can be overridden to specific values for test purposes. All thermister sensors  
can also be calibrated by entering positive or negative offsets to be applied to the current  
readings. All 4 – 20ma readings can be calibrated if the user has the exact current or  
resistance values available for entering in the calibration fields.  
Right-Click on the desired analog input reading to access the pop-up menu shown above  
and then select the desired function. If you are calibrating or overriding the reading, the  
following window will pop-up. Enter the desired calibration offset or specific reading  
you wish to force the input to and press the Enter key. The window will automatically  
close and send the command to the controller. If you select the Clear Sensor Override  
option, a window will not appear but the clear command will be sent to the controller.  
- OR -  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Any or all readings can also be “broadcast” to other controllers on the communications  
loop. For example, the Outdoor Air Temperature is broadcast on channel #2 by any unit  
that happens to have the sensor attached. If none of the standard package units have the  
outdoor air sensor attached, you could attach it to the GPCPlus and select it for broadcast  
on channel #2. All other controllers would “hear” the broadcast and use it in their normal  
operations. On the other hand, if you are measuring something like return air humidity,  
do NOT select channel #2 to broadcast it on, since all the package unit controls are  
expecting the outdoor air temperature. If no package controllers exist on your system  
then you are free to use any available global channel for broadcast. There are 32 possible  
global analog channels and 16 possible global binary channels.  
Select global analogs to broadcast readings and global binary channels to broadcast  
contact closure (on/off) information.  
If you select one of the unassigned channels for broadcast, it is assumed that you have  
other GPCPlus units installed that expect to receive information on those channels since  
the standard package code does not listen for broadcasts on unassigned channels.  
CAUTION: If you elect to broadcast a reading from the GPCPlus to all  
other controllers on your installation, be sure to check the  
HELP screen to identify which Global Channels have  
already been assigned.  
Each input also provides high and low alarm limits if the user requires out of range  
values to notify service personnel. The alarm limits can be widened at night and they can  
also be forced to be out of limits for a user defined amount of time before an alarm  
occurs. This prevents false alarms if the reading temporarily exceeds the limit but then  
recovers and stays within the limits the remainder of the time.  
All readings are user scalable. That means you can display values with ± 1, ± 0.1, ± 0.1±  
0.01 or higher resolutions. Just keep in mind that the maximum value that can be sent  
from the controller is ±30,000 so if you have scaled your reading to ± 0.001 then the  
maximum value you can send is ± 30 with the 3 additional decimal values (30.000).  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Each input can also have an appendix selected to display with the reading to make them  
more user friendly. The possible appendix values are:  
(None)  
RH%  
%  
No Appendix Required  
Relative Humidity  
Percentage  
°F  
°C  
PPM  
PSI  
“WG  
“  
Degrees Fahrenheit  
Degrees Celsius  
Parts Per Million  
Pounds Per Square Inch  
Inches of Water Gauge  
Inches  
Ft.  
Feet  
RPM  
VDC  
BTU  
Revolutions Per Minute  
Volts Direct Current  
British Thermal Units  
On inputs selected for Binary Input Contact Closure, the user can select Normally Open  
or Normally Closed Contacts.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wall Sensor Slide Offset  
If you have configured a specific input to be connected to one of WattMasters’ standard  
OE212 or OE213 Flush Mount Wall Sensors which contain the optional slide offset, be  
sure to enter a value for “Maximum Slide Offset Effect”. This tells the controller how  
much effect to have on the selected setpoints when the slide is fully deflected up or down.  
When the slide is in the “center” position, it has no effect on the current setpoints.  
Note: There are separate outputs on the Flush Mount Wall Sensors  
for measuring the room temperature and reading the slide  
offset. Be sure to configure the correct input for the slide offset  
and do not use the temperature signal coming from the wall  
sensor for this option.  
The slide offset is normally used by one or more relay outputs, configured to “look” at  
this value and include its effect on their normal setpoints.  
As you can see on the sample screen, Relay #4 is set to activate if the LoadTemp rises  
above 72.0°F. It is also monitoring the Sensor Slide Adjust input on Analog Input #5. If  
the slide is pushed up, the Hi Limit Setpoint will rise to 74.0°F and the Lo Limit Setpoint  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
to 72.0°F. If the slide is pushed down, the Hi Limit Setpoint will drop to 70.0°F and the  
Lo Limit Setpoint to 68.0°F.  
Push-Button Override  
If you have configured a specific input to be connected to one of WattMasters’ standard  
OE211 or OE213 Flush Mount Wall Sensors which contain the optional push-button  
override, be sure to enter a value for “Push-Button Override Duration”. To use this option  
you must select which schedule will be affected by the override event. (See screen  
below).  
Optimal Start Temperatures  
You can configure any of the first five inputs to be used as the Optimal Start “Target  
Temperature” sensor. As with the override option, you must select which schedule will  
use this temperature for its optimal start calculations.  
You also must enter a Cooling and a Heating Target setpoint for this feature to work  
correctly.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Analog Input #6  
This analog input is reserved for Duct Static Pressure. This value can then be used to  
monitor the duct static or to actually control the duct static using an analog output and  
driving either inlet vanes or a VFD controller. It is not recommended that you attempt to  
use relays to control the duct static pressure, although this reading can be selected as a  
control source on the relay configuration screen.  
CAUTION: If you select two relays to control duct static, WattMaster  
Controls cannot assume any liability for equipment  
damage caused by over-pressurization of the duct work!  
If you require a Duct Static Pressure Sensor, you must use an OE271 sensor provided by  
WattMaster Controls for proper sensor readings. No other sensors are currently supported  
for this input.  
All setpoints related to duct static control pressures and alarm points are programmed on  
this screen which activates when you left-click on the pressure reading box.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Relay Output  
Configuration  
Control Methods  
Each individual output relay can be configured separately for one of the following  
methods of control listed below.  
0
1
2
3
4
5
6
7
= Not Configured  
= On Above High Limit Setpoint and Off Below Low Limit Setpoint  
= On Above High Limit Setpoint and On Below Low Limit Setpoint  
= Off Above High Limit Setpoint and On Below Low Limit Setpoint  
= Off Above High Limit Setpoint and Off Below Low Limit Setpoint  
= On with Contact Closure on Selected Input  
= Off with Contact Closure on Selected Input  
= Follow Schedule Only  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
9
= Follow Global Binary Only  
= Ventilation Control  
10 = Lead Relay for Lead/Lag Control  
11 = Lag Relay for Lead/Lag Control  
Control/Reset Sources  
The Control Source is also selectable. This control source can be an analog value or an  
on/off contact closure. The list of possible sources is shown below.  
0 = Not Configured  
1 = Sensor Input #1  
2 = Sensor Input #2  
3 = Sensor Input #3  
4 = Sensor Input #4  
5 = Sensor Input #5  
6 = Sensor Input #7  
7 = Static Pressure  
8 = Outdoor Air  
9 = Calculated Wetbulb Temperature (Requires a sensor configured for Humidity)  
The Logical AND Source and the Logical OR Source also use the same list of available  
sources for their control also.  
Enabling Relay  
Interaction between relays is possible via an Enabling Relay feature. This allows the user  
to prevent a specific relay from activating until one of the other relays has had a chance  
to activate (See Sample Configurations Section). This can include such things as waiting  
for a fan to start before operating a heating or cooling stage.  
Delay & Run Times  
The relay can also be forced to remain on for a minimum amount of time or remain off  
for a minimum amount of time to prevent rapid cycling on and off under borderline  
operating conditions. A Starting Delay Period is also available so that a relay must also  
wait this amount of time, once it is enabled to activate before the relay output is actually  
energized.  
Reset Source Limits  
The Reset Source Limits are only required if you need the controlling setpoint to vary  
between the Hi Limit Setpoint and Lo Limit Setpoint based on some other condition  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
such as outdoor air temperature. If no reset is required, simply enter the same values for  
the Control Source Hi and Lo Limit Setpoints. No Reset Source is required.  
If you do need the main Control Source Setpoint to reset, this is the range over which  
the Reset Source must change to cause the controlling setpoint to reset from the Lo Limit  
to the Hi Limit values you entered. For example: you want to reset the enable/disable  
point for a boiler enable signal based on the changing outdoor air temperature. You  
would enter the Minimum outdoor air temperature that would cause the Hi Limit  
Setpoint to be calculated and the Maximum outdoor air temperature that would cause the  
Lo Limit Setpoint to be calculated.  
Controlling Setpoint Deadband  
You should always enter a small deadband to prevent the relay from cycling on and off  
continuously due to a control source reading that is toggling right around the current  
setpoint. The deadband you enter is added to both sides of the setpoint to create an area  
where the relay does not stage on or off. For example: if your setpoint was 72°F and the  
deadband was set for 0.5°F, the relay can change state when the temperature rises above  
72.5°F or drops below 71.5°F. If you do not need unoccupied setback control, you must  
leave this setpoint = 0.0°F and use the High and Low setpoints to create a deadband.  
Controlling Schedule  
You can select one of the Internal Schedules to set the occupied or unoccupied mode of  
operation for the selected relay. If the relay does not require a schedule to be part of its  
control strategy, leave the selection at “None Selected”.  
AND/OR Conditional Tests  
If more than one criterion is required to make a decision, there are two other options  
available to aid in the decision process. An AND condition and an OR condition. If you  
don’t need additional tests, simply select the Not Configured option under the Control  
Method for each of these sources.  
If you need two events to be true before the output can activate, use the AND Control  
Method and select a Logical AND Source.  
If you want either the main Control Method OR an Alternate Control Method to activate  
the output, use the OR Control Method and select a Logical OR Source.  
You can combine all three options to create a condition where two events must be true or  
a third separate event must be true to activate the output.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Run Time Alarm  
If the selected relay output is controlling a device that needs periodic maintenance, you  
can enter a Run Time Alarm Delay period that, once exceeded, generates an alarm  
condition that will notify the user when it occurs. If you need to protect the equipment  
you can select the Disable Relay box and the relay will de-activate once this run time has  
been exceeded.  
Relay Output Type  
Some control methods require the relay contacts to be closed when the output is  
activated, others require the contacts to be open. You can select which method of control  
to use with this option.  
Global Binary Channel  
If this output was configured to follow a global binary broadcast, enter which channel (1  
- 16) the relay should follow. The output will be active when the binary value is “1” and  
will de-activate when the value is “0”.  
Lead/Lag Control  
If you have configured this relay as the Lead relay in a Lead/Lag control scheme then  
you will also need to set the Changeover Interval and the Proof Failure Timeout Delay  
shown on the right hand side of the relay configuration screen.  
The Changeover Delay is used to toggle the Lag output into the Lead once the runtime  
hours of the Lead output exceed this amount of time on the Lag output.  
The Proof Failure Time Delay is the amount of time given for the “Proof of Flow” input  
to become active once the Lead or Lag output is energized. If this proof is not made  
within the specified amount of time, the controller switches to the Lag output in an  
attempt to get the controller running and then sets an alarm to flag the user that  
something is wrong.  
Hi/Lo Limit Setpoints  
All On/Off control methods require setpoints to be entered for control purposes. The  
relay state changes based on the control method selected and the current reading versus  
the Hi Limit Setpoint or Lo Limit Setpoint. If you have selected the On Above and  
Off Below method, then the relay would be active when the reading exceeds the Hi Limit  
Setpoint and it would not be active below the Lo Limit Setpoint. In either case, the user  
defined Deadband would also need to be satisfied before the actual relay change of state  
occurs.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ventilation Control  
You can configure an output to operate in a ventilation control mode. This means that the  
output is active for the Vent Mode ON Time and then cycles off for the Vent Mode OFF  
Time. If the output is not enabled by a schedule or another relay, it will continue to cycle  
indefinitely at this On/Off rate.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Analog Output  
Configuration  
Two Proportional Outputs ( 0 - 10 VDC ) are available to the user. This output operates  
using standard floating point control or a modified Proportional/Derivative control as  
configured by the user. The controlling setpoint can be reset by any other sensor reading  
or the outdoor air temperature and the output voltage range can be limited by the user to  
some range other than the standard 0 - 10 VDC.  
Possible Control Modes  
0 = Not Configured  
1 = Direct Acting Floating Point  
2 = Reverse Acting Floating Point  
3 = Direct Acting PID  
4 = Reverse Acting PID  
5 = Relief Pressure Control  
6 = Duct Static Pressure Control  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7 = Proportional Reset Signal  
8 = Economizer Control  
9 = Lead/Lag Pump VFD Control  
Possible Control Sources  
0 = Not Configured  
1 = Sensor Input #1  
2 = Sensor Input #2  
3 = Sensor Input #3  
4 = Sensor Input #4  
5 = Sensor Input #5  
6 = Sensor Input #7  
7 = Static Pressure  
8 = Outdoor Air  
9 = Calculated Wetbulb Temperature (Requires a sensor configured for Humidity)  
Floating Point Control  
If you select Direct or Reverse Acting Floating Point Control, this means that the output  
voltage on Direct Acting increases as the control signal goes above the setpoint and drops  
as the signal falls below the setpoint. In Reverse Acting mode, the voltage drops as the  
control signal goes above setpoint and falls when the control signal goes below setpoint.  
This type of control works best on very slow changing applications where the amount of  
time it would take to drive full on or full off is not critical. For faster response, the PID  
Control method is recommended.  
A deadband setpoint is available if you wish to set the Hi/Lo setpoints the same and only  
change the voltage if the control signal is further from setpoint than the deadband  
amount.  
PID Control  
The PID control is a WattMaster modified version of Proportional and Derivative Rate of  
Change Control. The only user setpoints required are the Calculation Interval which can  
speed up or slow down the control changes and whether or not to use the Rate of Change  
feature. Also, the minimum and maximum output range can be set to something other  
than full on or full off.  
This Rate of Change control is the preferred method for most valve or actuator control  
situations. It “self-adapts” to changing load conditions and “remembers” where it was the  
last time it was de-activated and attempts to restart the process at that known point  
whenever it is called back into action.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Economizer Control  
If you have configured the GPCPlus as a very simple Air Handling Unit, it has the ability  
to control the outside air dampers in a true first stage economizer cooling mode. This  
mode requires a Minimum Ventilation position that it maintains whenever the  
economizer is not enabled for cooling. It also needs to know which relay has been  
configured as the first compressor stage. Use the Outdoor Air Enable limits to set when  
the free cooling mode can be used in conjunction with scheduling and temperature  
demands.  
Alternate Override  
There are situations where we want normal control to be suspended temporarily  
whenever an unusual situation occurs. For example: we are using the economizer control  
method and we have installed a CO² sensor on this controller to use for Indoor Air  
Quality. If the CO² reading exceeds a specified level, this Alternate Override can take  
charge and move the output signal to a pre-designated level to bring the IAQ back under  
control.  
Proportional Reset Signal  
As the Reset Source goes from its Maximum Reset Source to its Minimum Reset  
Source the Controlling Setpoint goes from its Minimum Reset Setpoint limit to its  
Maximum Reset Setpoint limit.  
Since the reset limits can be set to any desired value, the user can initiate a reverse acting  
proportional reset or a direct acting proportional reset of the setpoint simply by crossing  
the min and max values if direct acting is required.  
Direct Acting = As Temperature Rises the Setpoint Drops  
Reverse Acting = As Temperature Rises the Setpoint Rises  
An example of using Proportional Reset would be for Boiler Control. As the outside air  
temperature rises, we would like the boiler output temperature to drop. We would use the  
outside air temperature as the control source and set the Max Setpoint and Min Setpoint  
to the range we want to vary the voltage from 0 to 10.0 vdc. If we set the Max Setpoint to  
50° and the Min Setpoint to 60° then as the outside air rose from 50° to 60°, the output  
signal would drop from 10.0 vdc @ 50° to 0.0 vdc @ 60°. This is because we made the  
output Reverse Acting by setting the Max Setpoint lower than the Min Setpoint.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lead/Lag Pump VFD Control  
If you are using the GPCPlus as a Lead/Lag controller and you need to maintain loop  
pressure or some other analog signal, configure an output for this method of control.  
Then all you need to do is enter the control setpoint on the Lead Relay configuration  
screen and this output will attempt to modulate and maintain that level of control while  
the Lead/Lag control is active.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sample Configurations  
Sample #1  
The user would like to control 4 boilers. Each boiler is controlled from the same Water  
Temperature sensor but at a different temperature reading. Once a boiler is activated it  
must remain on at least 5 minutes and if a boiler is de-activated it must remain off at least  
10 minutes. Additionally, the boilers are locked out when the Outdoor Air Temperature is  
above 65°F.  
Analog Input #1 Configured as Thermister Type III Sensor  
Note that some Hi and Lo alarm limits were set and that the reading is in degrees  
Fahrenheit.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Analog Input #2 Configured as Outdoor Air Thermister Sensor  
Notice that we set this reading to broadcast on Global Analog Channel #2. That is  
because the Outside Air is normally read by one controller on a job and the remaining  
controllers look at Global Analog #2 for this value, including the GPC Plus. Even if this  
is the only controller on the job, you must set it to broadcast the outside air so the GPC  
Plus can “see” what the OA Temperature is.  
Analog Input #3 Configured as Not Configured  
Analog Input #4 Configured as Not Configured  
Analog Input #5 Configured as Not Configured  
Analog Input #6 Duct Static Pressure Sensor is not Required  
Analog Input #7 Configured as Not Configured  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Relay Output #1 Programming ( Used for Outdoor Air Enable / Disable )  
NOTE: Nothing is physically connected to Relay #1. Its only use is to  
enable or disable the other relays.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Relay Output #2 Programming ( Used for Boiler #1 )  
As you can see, the first boiler stage is enabled to operate if the water temperature is  
below 175°F and will remain on until it rises to 190°F. This first stage can only operate if  
the outdoor air enabling relay #1 is active. Once activated, the boiler must remain on for  
5 minutes (300 seconds) and once de-activated it must remain off for 10 minutes (600  
seconds).  
Since we are not resetting the operating setpoint, the Reset Source has been left as “None  
Selected”. We also don’t require a “Logical AND” or “Logical OR” condition so they  
have been left Not Configured. There is no need to enable this output from a schedule  
since it uses an Enabling Relay (OAT Enable) which does require the schedule before it  
can activate based on the Outside Air Temperature.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Relay Output #3 Programming ( Used for Boiler #2 )  
The second boiler stage is enabled to operate if the water temperature is below 170°F and  
will remain on until it rises to 180°F. The second stage can only operate if the first boiler  
stage relay #2 has been active for at least 5 minutes. Once activated, this stage must  
remain on for 5 minutes and once de-activated it must remain off for 10 minutes.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Relay Output #4 Programming ( Used for Boiler #3 )  
The third boiler stage is enabled to operate if the water temperature is below 160°F and  
will remain on until it rises to 175°F. The third stage can only operate if the second boiler  
stage relay #3 has been active for at least 5 minutes. Once activated, this stage must  
remain on for 5 minutes and once de-activated it must remain off for 10 minutes.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Relay Output #5 Programming ( Used for Boiler #4 )  
The fourth boiler stage is enabled to operate if the water temperature is below 150°F and  
will remain on until it rises to 170°F. The fourth stage can only operate if the third boiler  
stage relay #4 has been active for at least 5 minutes. Once activated, this stage must  
remain on for 5 minutes and once de-activated it must remain off for 10 minutes.  
The Starting Delay Period that was set for stages 2 to 4 prevent all four boiler stages  
from activating at the same time as soon as they are enabled to begin operation. Each  
stage must run for 5 minutes before the next stage can be activated.  
Analog Output Programming  
Control Source  
Not Configured  
Since no analog output control is required, simply leave the Control Source set to Not  
Configured on both outputs and no analog output control will take place.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Relay #1 enables the boilers to operate if the outdoor air temperature is below the low  
setpoint and the schedule is occupied. Each boiler is enabled to operate if the previous  
boiler is currently active and has been on for at least 5 minutes. All four boilers monitor  
the same analog input sensor for the Water Temperature reading. The #1 Enable Relay  
can monitor a global broadcast from another controller on the RS-485 communications  
loop for the outdoor air temperature but, in this case, we are reading the Outdoor Air  
Temperature on Analog Input #2. Notice on the Analog Output #2 configuration screen  
that it was also configured to broadcast on Global Analog Channel #2. That is because  
the GPC Plus doesn’t have any other way of knowing that it is the one reading the  
outdoor air temperature.  
The voltage output is not used so no control source is selected, and no other related  
setpoints require modification.  
Shown below is a sample Status Screen for this sample application. Notice that the  
boilers are not enabled even though the schedule is active because the outdoor air  
temperature is too high.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This next sample screen shows that the outdoor air temperature has dropped enough to  
enable the boilers to operate. The system has been running long enough to satisfy all 4  
Boilers 5 Minute Starting delay so they are all active at this point. It took roughly 20  
minutes to get all 5 relays active since each has a 5 minute Staging Delay time period.  
Keep in mind that although Relay #1 (OAT Enable) is active, nothing is connected to the  
output because its only function is to provide an outdoor air enable signal for the boiler  
staging.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sample #2  
The user would like to use the GPC Plus as a Lead/Lag Air Handling Unit Controller.  
The installation is located in a critical area that does not tolerate the space temperature  
going out of control. The method chosen was to install a backup AHU that would take  
over in case of failure on the Lead AHU. Also, since the units are identical, the owner  
wanted to equalize the run-times to lengthen the time between routine maintenance  
service calls. The easiest method for handling this was to use two, standard, off the shelf  
AHU controllers and a GPC Plus controller that would enable the appropriate AHU  
based on changeover and failure mode conditions. The GPC Plus would use contact  
closures to the Forced Occupied inputs of the AHU controllers to activate and de-activate  
the units. A failure mode would be indicated by the failure of the Supply Air  
Temperature to drop below or stay below a 60°F setpoint. Any temperature excursions  
above 60°F for more than one minute would indicate a failure had occurred and that the  
Lag AHU should be activated and an Alarm generated to let building maintenance know  
there was a problem.  
Analog Input #1 Configured as Thermister Type III Sensor to measure Supply Air  
As you can see, this input does not use a schedule for Night Setbacks since the unit will  
run 24 hours a day. It does however, monitor the Supply Air Temperature for values that  
are out of limits for more than a half hour and generates an alarm condition. This is a fall  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
back alarm condition because the Lead/Lag control should have already generated an  
alarm if something was wrong and the standby AHU was called into action. Be sure to  
check the Alarming Enabled box if you want this alarm to be reported back to the PRISM  
screen or to a Remote Pager.  
Analog Input #2 - #7 The remaining inputs are not required for this program.  
Relay Output #1 Programming ( Used for Lead AHU Enable Signal )  
This relay was chosen to be the Lead control output and was connected to AHU #1.  
Either AHU could have been selected as AHU #1, this was an arbitrary decision. The  
Supply Air was selected as the Control Source and the Proof Setpoint was set to 60.0°F.  
The AHU’s will change the Lead every 24 Hours and if the Supply Air rises above 60°  
for more than 60 seconds, it will be considered to be in failure mode and the Lag AHU  
will be activated. Also, an alarm will be generated so that an immediate service call can  
be made to determine the cause of failure. If both units should happen to fail, there is no  
further redundant capabilities and service personnel will need to correct the problems and  
then Reset the control from the Alarm Indicator Screen (shown later in this section).  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Relay Output #2 Programming ( Used for Lag AHU Enable Signal )  
There are no other settings required for the Lag Controller. All control logic from the  
Lead relay is used in the decision making process.  
Analog Outputs (No Analog Output Control is Required for this Program)  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Main Status Screen ( Normal Operations )  
As you can see on the Status Screen shown above, the unit is operating normally and the  
Supply Temperature is at 51.9°F, well within the normal operating range and no alarms  
are currently active.  
There are no schedules active since this unit is required to operate 24 hours a day. The  
relay outputs will operate their control modes around the clock if no schedule was  
selected on the relay configuration screen.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Main Status Screen ( Failure Mode )  
The Supply Air rose to 61.9°F and the Lag AHU was activated.  
The alarm screen indicates the Lead AHU failure.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Both AHU’s are now off because the Lag AHU failed to lower the Supply Air below  
60°F.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The alarm screen indicates both outputs failed to control the Supply Temperature. At this  
point, the service personnel will need to correct the problem and then select the Reset  
Pump/Fan button to restart the GPC Plus Lead/Lag control sequence.  
Although the button and alarm indicators show Lead Pump / Fan indicators, the outputs  
are not limited to those types of control. You just need to understand that the Lead Pump  
/ Fan controls AHU #1 in this sample and Standby Pump / Fan controls AHU #2.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Form: OR-GPCPlus-APP-01A  
All rights reserved  
Printed in the USA  
March 2005  
Copyright 2005  
WattMaster Controls Inc. 8500 NW River Park Drive Parkville MO 64152  
Download from Www.Somanuals.com. All Manuals Search And Download.  

MTD Trimmer 704rVP User Manual
Muratec All in One Printer MK3119 User Manual
Nextel comm Telephone NTN9368 A User Manual
Nokia Satellite TV System 112T User Manual
NordicTrack Home Gym NTTL11994 User Manual
NordicTrack Treadmill NTL10842 User Manual
Nortel Networks Network Router 114200 E User Manual
Onkyo Stereo System SR507 User Manual
Panasonic Stereo System CX DP801EUC User Manual
Parkside Soldering Gun PLBS 30 User Manual