Omega Vehicle Security Clock PTC900 User Manual

Users Guide  
Shop online at  
omega.com  
For latest product manuals:  
omegamanual.info  
PTC900/PTC901  
Panel-Mount Programmable  
Timer and Real-Time Clock  
LP0678A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
z 6-DIGIT 0.56" RED SUNLIGHT READABLE DISPLAY  
z 4 SEPARATE DISPLAYS (Timer, Counter, Real-Time Clock, and Date)  
z CYCLE COUNTING CAPABILITY  
z PROGRAMMABLE FUNCTION KEYS/USER INPUTS  
z FOUR SETPOINT ALARM OUTPUTS (W/Plug-in card)  
z COMMUNICATIONS AND BUS CAPABILITIES (W/Plug-in card)  
z PC SOFTWARE AVAILABLE FOR METER CONFIGURATION  
z NEMA 4X/IP65 SEALED FRONT BEZEL  
The meters can have up to four setpoint outputs, determined by the optional  
plug-in cards. The setpoint plug-in cards provide dual FORM-C relays (5A),  
quad FORM-A relays (3A) or either quad sinking or quad sourcing open  
collector logic outputs. The outputs can be assigned to the timer, counter, RTC  
date, and RTC time. The outputs can also be independently configured to suit a  
variety of control and alarm requirements.  
Plug-in cards can also provide serial communications. These include RS232,  
RS485, and Modbus. Display values, setpoint alarm values and setpoint states  
can be controlled through serial communications. With the RS232 or RS485  
communication card installed, it is possible to configure the meter using a  
Windows® based program. The meter configuration data can be saved to a file  
for later recall.  
Once the meters have been initially configured, the parameter list may be  
locked out from further modification entirely, or the setpoint, timer start/stop  
values, counter start/stop values, RTC time SET, and Display Intensity can be  
made accessible. This lockout is possible through a security code or user input.  
The meters have been specifically designed for harsh industrial environments.  
With a NEMA 4X/IP65 sealed bezel and extensive testing to meet CE  
requirements, the meter provides a tough yet reliable application solution.  
GENERAL DESCRIPTION  
The PTC900 (Timer) and PTC901 (Clock/Timer) offer many features and  
performance capabilities to suit a wide range of industrial applications. Both can  
function as an Elapsed Timer or Preset Timer, while the PTC901 also offers  
Real-Time Clock with Date capability. The Plug-in option cards allow the  
opportunity to configure the meter for the present application, while providing  
easy upgrades for future needs.  
Both units can function as an Elapsed Time Indicator. By using two separate  
signal inputs and 23 selectable timer ranges, the meters can be programmed to  
meet most any timing application. With the addition of a Plug-in Setpoint card,  
they can easily become a dual or quad output preset timer.  
The PTC901 can also operate as a Real-Time Clock (RTC), with the Real-  
Time Clock Card already installed. The meter is capable of displaying time in  
12 or 24-hour time formats. The 12-hour format can be displayed in hours and  
minutes, with or without an AM/PM indication or in hours, minutes, and  
seconds. The 24-hour format can be displayed in hours and minutes or in hours,  
minutes, and seconds. The PTC901 is also capable of a calendar display in  
which the day, month and/or year can be displayed. The meter will recognize  
leap years, and can automatically adjust for Daylight Savings Time. The Real-  
Time Clock has the ability to externally synchronize with other PTC901 meters  
to provide a uniform display network throughout the plant.  
If the application calls for both a Preset Timer and a Real-Time Clock at the  
same time, the PTC901 can handle this requirement as well. The meter provides  
up to four different displays, accessed via front panel push buttons or external  
inputs. The displays are Timer (TMR), which displays the current timer value;  
Count (CNT), which displays the current cycle counter value; Date (DAT),  
which displays the current programmed date; and Real-Time Clock, which  
displays the current time. A battery-backed Real-Time Clock plug-in card is  
provided with the PTC901. This card, which includes a lithium coin-cell battery,  
will maintain the time and date when main power is removed.  
SAFETY SUMMARY  
All safety related regulations, local codes and instructions that appear in this  
literature or on equipment must be observed to ensure personal safety and to  
prevent damage to either the instrument or equipment connected to it. If  
equipment is used in a manner not specified by the manufacturer, the protection  
provided by the equipment may be impaired.  
Do not use this unit to directly command motors, valves, or other actuators  
not equipped with safeguards. To do so can be potentially harmful to persons or  
equipment in the event of a fault to the unit.  
The meters accept inputs from a variety of sources including switch contacts  
and outputs from CMOS or TTL circuits. The input can be configured to trigger  
on the edge or level of the incoming pulse. Internal jumpers are available to allow  
the selection for sinking inputs (active low) or sourcing inputs (active high).  
The front panel keys and three user inputs are programmable to perform  
various meter functions. One of the functions includes exchanging parameter  
lists, allowing for two separate listings of setpoint values, timer start/stop  
values, counter start/stop values and RTC daily on and off values.  
CAUTION: Risk of Danger.  
Read complete instructions prior to  
installation and operation of the unit.  
CAUTION: Risk of electric shock.  
Note: Recommended minimum clearance (behind the panel) for mounting  
clip installation is 2.1" (53.4) H x 5" (127) W.  
DIMENSIONS In inches (mm)  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
General Meter Specifications. . . . . . . . . . . . . 4  
Optional Plug-In Cards and Accessories . . . . 5  
Installing the Meter . . . . . . . . . . . . . . . . . . . . 6  
Setting the Jumpers . . . . . . . . . . . . . . . . . . . 6  
Installing Plug-In Cards. . . . . . . . . . . . . . . . . 7  
Wiring the Meter . . . . . . . . . . . . . . . . . . . . . . 7  
Reviewing the Front Buttons and Display . . 10  
Programming the Meter. . . . . . . . . . . . . . . . 11  
Factory Service Operations. . . . . . . . . . . . . 26  
Programming Overview. . . . . . . . . . . . . . . . 29  
GENERAL METER SPECIFICATIONS  
1. DISPLAY: 6 digit, 0.56" (14.2 mm) red sunlight readable or standard green  
11. USER INPUTS: Three programmable user inputs  
LED  
Logic inputs configurable as Current Sinking (active low) or Current  
Sourcing (active high) through a single plug jumper.  
Current Sinking (active low): VIL = 0.9 V max., 22Kpull-up to +12 VDC.  
Current Sourcing (active high): VIH = 3.6 V min., 22Kpull-down, Max.  
Continuous Input: 30 VDC.  
Isolation To Timer Input Common: Not isolated  
Response Time: 10 msec  
12. MEMORY: Non-volatile E2PROM retains all programming parameters and  
2. POWER:  
AC Versions (PTC901, PTC900):  
AC Power: 85 to 250 VAC, 50/60 Hz, 18 VA  
Isolation: 2300 Vrms for 1 min. to all inputs and outputs. (300 V working)  
DC Versions (PTC901-LV, PTC900-LV):  
DC Power: 11 to 36 VDC, 14 W  
(Derate operating temperature to 40°C if operating <15 VDC and three  
Plug-in cards are installed)  
display values.  
AC Power: 24 VAC, ± 10%, 50/60 Hz, 15 VA  
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working)  
13. ENVIRONMENTAL CONDITIONS:  
Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in  
cards installed)  
3. SENSOR POWER: 12 VDC, ±10%, 100 mA max. Short circuit protected.  
Storage Temperature Range: -40 to 60°C  
4. ANNUNCIATORS:  
Operating and Storage Humidity: 0 to 85% max. RH non-condensing  
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z  
direction for 1.5 hours, 2 g’s.  
Shock According to IEC 68-2-27: Operational 25 g (10g relay), 11 msec in 3  
directions.  
TMR - Timer Display  
SP1 - Setpoint 1 Output  
SP2 - Setpoint 2 Output  
SP3 - Setpoint 3 Output  
SP4 - Setpoint 4 Output  
CNT - Cycle Counter Display  
DAT - Real-Time Clock Date Display  
- Real-Time Clock Time Display  
Altitude: Up to 2000 meters  
5. KEYPAD: 3 programmable function keys, 5 keys total.  
14. CERTIFICATIONS AND COMPLIANCE:  
SAFETY  
6. TIMER DISPLAY:  
Timer Range: 23 Selectable Ranges  
Timing Accuracy: ± 0.01%  
Minimum Digit Resolution: 0.001 Sec.  
Maximum Least Significant Digit Resolution: 1 Hr.  
Maximum Display: 999999  
UL Recognized Component, File # E313607, UL61010A-1, CSA C22.2  
No. 61010-1  
Recognized to U.S. and Canadian requirements under the Component  
Recognition Program of Underwriters Laboratories, Inc.  
UL Listed, File # E313547, UL508, CSA C22.2 No. 14-M95  
LISTED by Und. Lab. Inc. to U.S and Canadian safety standards  
Type 4X Enclosure rating (Face only), UL50  
IEC 61010-1, EN 61010-1: Safety requirements for electrical  
equipment for measurement, control, and laboratory use, Part 1.  
IP65 Enclosure rating (face only), IEC 529  
7. CYCLE COUNTER DISPLAY:  
Counter Range: 0 to 999999  
Digit Resolution: 1 cycle  
Maximum Count Rate: 50 Hz  
8. REAL-TIME/DATE DISPLAY (PTC901):  
Real-Time Display: 5 display formats  
Hr/Min/Sec (12 or 24 Hr. format); Hr/Min (24 Hr.); Hr/Min (12 Hr. with  
or without AM/PM indication)  
Date Display: 7 display formats  
Month/Day or Day/Month (numeric or 3-letter Month format);  
Month/Day/Year or Day/Month/Year (all numeric);  
Day of Week/Day (3-letter Day of Week format)  
9. REAL-TIME CLOCK CARD: Field replaceable plug-in card  
Time Accuracy: ± 5 secs./Month (1 min./year) with end-user calibration  
Battery: Lithium 2025 coin cell  
Battery Life Expectancy: 10 yrs. typical  
Synchronization Interface: Two-wire multi-drop network (RS485 hardware),  
32 units max., operates up to 4000 ft.  
IP20 Enclosure rating (rear of unit), IEC 529  
ELECTROMAGNETIC COMPATIBILITY  
Immunity to EN 50082-2  
Electrostatic discharge  
Electromagnetic RF fields  
EN 61000-4-2 Level 3; 8 Kv air  
EN 61000-4-3 Level 3; 10 V/m  
80 MHz - 1 GHz  
EN 61000-4-4 Level 4; 2 Kv I/O  
Level 3; 2 Kv power  
Fast transients (burst)  
RF conducted interference  
EN 61000-4-6 Level 3; 10 V/rms  
150 KHz - 80 MHz  
Emissions to EN 50081-1  
RF interference  
EN 55022  
Enclosure class B  
Power mains class B  
Isolation To Timer & User Input Commons: 500 Vrms for 1 min.  
Working Voltage: 50 V. Not isolated from all other commons.  
Note:  
10. TIMER INPUTS A and B:  
Refer to the EMC Installation Guidelines section for more information.  
Logic inputs configurable as Current Sinking (active low) or Current  
Sourcing (active high) via a single plug jumper.  
Current Sinking (active low): VIL = 0.9 V max., 22Kpull-up to +12 VDC.  
Current Sourcing (active high): VIH = 3.6 V min., 22Kpull-down, Max.  
Continuous Input: 30 VDC.  
Timer Input Pulse Width: 1 msec min.  
Timer Start/Stop Response Time: 1 msec max.  
Filter: Software filtering provided for switch contact debounce. Filter  
enabled or disabled through programming.  
If enabled, filter results in 50 msec start/stop response time for successive  
pulses on the same input terminal.  
15. CONNECTIONS: High compression, cage-clamp terminal block  
Wire Strip Length: 0.3" (7.5 mm)  
Wire Gage: 30-14 AWG copper wire  
Torque: 4.5 inch-lbs (0.51 N-m) max.  
16. CONSTRUCTION: This meter is rated for NEMA 4X/IP65 outoor use.  
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece  
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and  
mounting clip included.  
17. WEIGHT: 10.1 oz. (286 g)  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL PLUG-IN CARDS AND ACCESSORIES  
WARNING: Disconnect all power to the unit before  
SETPOINT CARDS (LDP6-CDS)  
The PTC900/PTC/901 series has 4 available setpoint alarm output plug-in  
installing Plug-in cards.  
cards. Only one of these cards can be installed at a time. (Logic state of the  
outputs can be reversed in the programming.) These plug-in cards include:  
Adding Option Cards  
LDP6-CDS10 - Dual Relay, FORM-C, Normally open & closed  
LDP6-CDS20 - Quad Relay, FORM-A, Normally open only  
LDP6-CDS30 - Isolated quad sinking NPN open collector  
LDP6-CDS40 - Isolated quad sourcing PNP open collector  
The PTC900/PTC/901 series meters can be fitted with up to three optional  
plug-in cards. The details for each plug-in card can be reviewed in the  
specification section below. Only one card from each function type can be  
installed at one time. The function types include Setpoint Alarms (LDP6-CDS),  
Communications (LDP6-CDC), and Real-Time Clock Card (LDP6-RTC). The  
plug-in cards can be installed initially or at a later date.  
DUAL RELAY CARD  
Type: Two FORM-C relays  
Isolation To Timer & User Input Commons: 2300 Vrms for 1 min.  
Working Voltage: 240 Vrms  
Contact Rating:  
One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive load),  
1/8 HP @120 VAC, inductive load  
Total current with both relays energized not to exceed 5 amps  
Life Expectancy: 100 K cycles min. at full load rating. External RC snubber  
extends relay life for operation with inductive loads  
Response Time: 5 msec. nominal with 3 msec. nominal release  
Timed Output Accuracy: ±0.01% -10 msec.  
COMMUNICATION CARDS (LDP6-CDC)  
A variety of communication protocols are available for the PTC900/PTC/901  
series. Only one of these cards can be installed at a time. When programming  
the unit via the Windows® based software program, the RS232 or RS485 Cards  
must be used.  
LDP6-CDC10 - RS485 Serial (Terminal) LDP6-CDC1C - RS485 (Connector)  
LDP6-CDC20 - RS232 Serial (Terminal) LDP6-CDC2C - RS232 (Connector)  
LDP6-CDC40 - Modbus (Terminal)  
LDP6-CDC4C - Modbus (Connector)  
QUAD RELAY CARD  
Type: Four FORM-A relays  
Isolation To Timer & User Input Commons: 2300 Vrms for 1 min.  
Working Voltage: 250 Vrms  
Contact Rating:  
SERIAL COMMUNICATIONS CARD  
Type: RS485 or RS232  
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.  
Working Voltage: 50 V. Not Isolated from all other commons.  
Data: 7/8 bits  
Baud: 300 to 19,200  
Parity: No, Odd or Even  
Bus Address: Selectable 0 to 99, Max. 32 meters per line (RS485)  
Transmit Delay: Selectable for 2 to 50 msec or 50 to 100 msec (RS485)  
One Relay Energized: 3 amps @ 250 VAC or 30 VDC (resistive load), 1/10  
HP @ 120 VAC, inductive load  
Total current with all four relays energized not to exceed 4 amps  
Life Expectancy: 100K cycles min. at full load rating. External RC snubber  
extends relay life for operation with inductive loads  
Response Time: 5 msec. nominal with 3 msec. nominal release  
Timed Output Accuracy: ±0.01% -10 msec.  
MODBUS CARD  
Type: RS485; RTU and ASCII MODBUS modes  
Isolation To Sensor & User Input Commons: 500 Vrms for 1 minute.  
Working Voltage: 50 V. Not isolated from all other commons.  
Baud Rates: 300 to 38,400.  
Data: 7/8 bits  
Parity: No, Odd, or Even  
QUAD SINKING OPEN COLLECTOR CARD  
Type: Four isolated sinking NPN transistors.  
Isolation To Timer & User Input Commons: 500 Vrms for 1 min.  
Working Voltage: 50 V. Not Isolated from all other commons.  
Rating: 100 mA max @ VSAT = 0.7 V max. VMAX = 30 V  
Response Time: 400 µsec. nominal with 2 msec. nominal turnoff  
Timed Output Accuracy: ±0.01% -10 msec.  
Addresses: 1 to 247.  
Transmit Delay: Programmable; See Transmit Delay explanation.  
QUAD SOURCING OPEN COLLECTOR CARD  
Type: Four isolated sourcing PNP transistors.  
PROGRAMMING SOFTWARE  
DP6-SOFT is a Windows® based program that allows configuration of the  
PTC900/PTC/901 meters from a PC. This software offers standard drop-down  
menu commands, that make it easy to program the meter. The PTC900/PTC/901  
program can then be saved in a PC file for future use. A serial plug-in card is  
required to program the meter using the software.  
Isolation To Timer & User Input Commons: 500 Vrms for 1 min.  
Working Voltage: 50 V. Not Isolated from all other commons.  
Rating: Internal supply: 24 VDC ± 10% , 30 mA max. total  
External supply: 30 VDC max., 100 mA max. each output  
Response Time: 400 µsec. nominal with 2 msec. nominal turnoff  
Timed Output Accuracy: ±0.01% -10 msec.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 INSTALLING THE METER  
Installation  
The meter meets NEMA 4X/IP65 requirements for indoor use when properly  
installed. The meter is intended to be mounted into an enclosed panel. Prepare  
the panel cutout to the dimensions shown. Remove the panel latch from the  
meter. Slide the panel gasket over the  
While holding the meter in place, push the panel latch over the rear of the  
meter so that the tabs of the panel latch engage in the slots on the case. The  
panel latch should be engaged in the farthest forward slot possible. To achieve  
a proper seal, tighten the latch screws evenly until the meter is snug in the panel  
(Torque to approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.  
rear of the meter to the back of the  
bezel. The meter should be  
installed fully assembled.  
Insert the meter into the  
Installation Environment  
The meter should be installed in a location that does not exceed the operating  
temperature and provides good air circulation. Placing the meter near devices  
that generate excessive heat should be avoided.  
panel cutout.  
The bezel should only be cleaned with a soft cloth and neutral soap product.  
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate  
the aging process of the bezel.  
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the  
keypad of the meter.  
PANEL CUT-OUT  
2.0 SETTING THE JUMPERS  
To access the jumpers, remove the meter base from the meter case by firmly  
squeezing and pulling back on the side rear finger tabs. This should lower the  
latch below the case slot (which is located just in front of the finger tabs). It is  
recommended to release the latch on one side, then start the other side latch.  
Timer Input Logic Jumper  
One jumper is used for the logic state of both timer inputs. Select the proper  
position to match the input being used.  
User Input Logic Jumper  
One jumper is used for the logic state of all user inputs. If the user inputs are  
not used, it is not necessary to check or move this jumper.  
Warning: Exposed line voltage exists on the circuit boards. Remove  
all power to the meter and load circuits before accessing inside of  
the meter.  
Main  
Circuit  
Board  
JUMPER SELECTIONS  
The  
indicates factory setting.  
SRC  
SNK  
USER  
INPUT  
TIMER  
INPUT  
JUMPER  
JUMPER  
SRC  
SNK  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.0 INSTALLING PLUG-IN CARDS  
The Plug-in cards are separately purchased optional cards that perform  
specific functions. These cards plug into the main circuit board of the meter. The  
Plug-in cards have many unique functions when used with the meters.  
To Install:  
1. With the case open, locate the Plug-in card connector for the card type to be  
installed. The types are keyed by position with different main circuit board  
connector locations. When installing the card, hold the meter by the rear  
terminals and not by the front display board.*  
CAUTION: The Plug-in card and main circuit board contain static  
sensitive components. Before handling the cards, discharge static  
charges from your body by touching a grounded bare metal  
object. Ideally, handle the cards at a static controlled clean  
workstation. Also, only handle the cards by the edges. Dirt, oil or  
other contaminants that may contact the cards can adversely  
affect circuit operation.  
2. Install the Plug-in card by aligning the card terminals with the slot bay in the  
rear cover. Be sure the connector is fully engaged and the tab on the Plug-in  
card rests in the alignment slot on the display board.  
3. Slide the meter base back into the case. Be sure the rear cover latches fully  
into the case.  
4. Apply the Plug-in card label to the bottom side of the meter. Do Not Cover  
the vents on the top surface of the meter. The surface of the case must be  
clean for the label to adhere properly. Apply the label to the area designated  
by the large case label.  
TOP VIEW  
Quad Sourcing Open Collector Output Card Supply Select  
* If installing the Quad sourcing Plug-in Card (LDP6-CDS40), set the jumper  
for internal or external supply operation before continuing.  
4.0 WIRING THE METER  
b. Connect the shield to earth ground at both ends of the cable, usually when  
the noise source frequency is above 1 MHz.  
c. Connect the shield to common of the meter and leave the other end of the  
shield unconnected and insulated from earth ground.  
WIRING OVERVIEW  
Electrical connections are made via screw-clamp terminals located on the  
back of the meter. All conductors should conform to the meter’s voltage and  
current ratings. All cabling should conform to appropriate standards of good  
installation, local codes and regulations. It is recommended that the power  
supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.  
When wiring the meter, compare the numbers embossed on the back of the  
meter case against those shown in wiring drawings for proper wire position.  
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded  
wires should be tinned with solder.) Insert the lead under the correct screw-  
clamp terminal and tighten until the wire is secure. (Pull wire to verify  
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two  
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).  
3. Never run Signal or Control cables in the same conduit or raceway with AC  
power lines, conductors feeding motors, solenoids, SCR controls, and  
heaters, etc. The cables should be ran in metal conduit that is properly  
grounded. This is especially useful in applications where cable runs are long  
and portable two-way radios are used in close proximity or if the installation  
is near a commercial radio transmitter.  
4. Signal or Control cables within an enclosure should be routed as far as possible  
from contactors, control relays, transformers, and other noisy components.  
5. In extremely high EMI environments, the use of external EMI suppression  
devices, such as ferrite suppression cores, is effective. Install them on Signal  
and Control cables as close to the unit as possible. Loop the cable through the  
core several times or use multiple cores on each cable for additional protection.  
Install line filters on the power input cable to the unit to suppress power line  
interference. Install them near the power entry point of the enclosure. The  
following EMI suppression devices (or equivalent) are recommended:  
Ferrite Suppression Cores for signal and control cables:  
Fair-Rite # 0443167251  
EMC INSTALLATION GUIDELINES  
Although this meter is designed with a high degree of immunity to Electro-  
Magnetic Interference (EMI), proper installation and wiring methods must be  
followed to ensure compatibility in each application. The type of the electrical  
noise, source or coupling method into the meter may be different for various  
installations. The meter becomes more immune to EMI with fewer I/O  
connections. Cable length, routing, and shield termination are very important  
and can mean the difference between a successful or troublesome installation.  
Listed below are some EMC guidelines for successful installation in an  
industrial environment.  
TDK # ZCAT3035-1330A  
Steward # 28B2029-0A0  
Line Filters for input power cables:  
Schaffner # FN610-1/07  
1. The meter should be mounted in a metal enclosure, which is properly  
connected to protective earth.  
Schaffner # FN670-1.8/07  
Corcom # 1 VR3  
2. Use shielded (screened) cables for all Signal and Control inputs. The shield  
(screen) pigtail connection should be made as short as possible. The  
connection point for the shield depends somewhat upon the application.  
Listed below are the recommended methods of connecting the shield, in order  
of their effectiveness.  
Note: Reference manufacturers instructions when installing a line filter.  
6. Long cable runs are more susceptible to EMI pickup than short cable runs.  
Therefore, keep cable runs as short as possible.  
7. Switching of inductive loads produces high EMI. Use of snubbers across  
inductive loads suppresses EMI.  
a. Connect the shield only at the panel where the unit is mounted to earth  
ground (protective earth).  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.1 POWER WIRING  
AC Power  
DC Power  
Terminal 1: VAC  
Terminal 1: +VDC  
Terminal 2: VAC  
Terminal 2: -VDC  
4.2 TIMER INPUT WIRING  
Before connecting the wires, the Timer Input logic jumper should be verified for proper position.  
Two Wire Proximity, Current Source  
Current Sinking Output  
Current Sourcing Output  
Switch or Isolated Transistor; Current Source  
Switch or Isolated Transistor; Current Sink  
Emitter Follower; Current Source  
Interfacing With TTL  
CAUTION: Timer Input common is NOT isolated from User Input common. In order to preserve the safety of the meter application, the timer input  
common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth ground potential. If not,  
hazardous voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the potential  
of the User Input Common with respect to earth ground; and the common of the isolated plug-in cards with respect to input common.  
4.3 USER INPUT WIRING  
Before connecting the wires, the Timer Input logic jumper should be verified for proper position. When the user input is configured for cycle  
count, in module 4, the count input should be wired between terminals 7 & 10.  
Sinking Logic  
Sourcing Logic  
Terminals 7-9  
Terminals 7-9:  
Connect external switching device between the  
}
+ VDC through external switching device  
appropriate User Input terminal and User Comm.  
Terminal 10  
Terminal 10:  
-VDC through external switching device  
The user inputs of the meter are internally  
pulled up to +12 V with 22 Kresistance.  
The input is active when it is pulled low  
(<0 .9 V).  
The user inputs of the meter are internally  
pulled down to 0 V with 22 Kresistance.  
The input is active when a voltage greater  
than 3.6 VDC is applied.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4 SETPOINT (ALARMS) WIRING  
SOURCING OUTPUT LOGIC CARD  
SETPOINT PLUG-IN CARD TERMINALS  
SINKING OUTPUT LOGIC CARD  
4.5 SERIAL COMMUNICATION WIRING  
RS232 Communications  
RS485 Communications  
The RS485 communication standard allows the connection of up to 32  
devices on a single pair of wires, distances up to 4,000 ft. and data rates as high  
as 10M baud. The same pair of wires is used to both transmit and receive data.  
RS485 is therefore always half-duplex, that is, data cannot be received and  
transmitted simultaneously.  
Terminal Block Connection Figure  
Extended Comms Connection Figure  
Terminal Block Connection Figure  
RS232 is intended to allow two devices to communicate over distances up to  
50 feet. Data Terminal Equipment (DTE) transmits data on the Transmitted Data  
(TXD) line and receives data on the Received Data (RXD) line. Data Computer  
Equipment (DCE) receives data on the TXD line and transmits data on the RXD  
line. The meter emulates a DTE. If the other device connected to the meter also  
emulates a DTE, the TXD and RXD lines must be interchanged for  
communications to take place. This is known as a null modem connection. Most  
printers emulate a DCE device while most computers emulate a DTE device.  
Some devices cannot accept more than two or three characters in succession  
without a pause in between. In these cases, the meter employs a busy function.  
As the meter begins to transmit data, the RXD line (RS232) is monitored to  
determine if the receiving device is “busy”. The receiving device asserts that it  
is busy by setting the RXD line to a space condition (logic 0). The meter then  
suspends transmission until the RXD line is released by the receiving device.  
Extended Comms Connection Figure  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.6 REAL-TIME CLOCK WIRING (PTC901)  
Time synchronization between multiple  
PTC901 meters can be accomplished through a  
hardware interface on the Real-Time Clock option  
card. This RS485 type interface allows connection  
of up to 32 PTC901 meters in a two-wire  
multidrop network, at distances up to 4000 ft.  
In a synchronization network, one PTC901  
meter is programmed as the Host, while all other  
meters are programmed as Slaves. Once every  
hour, the Host meter outputs  
a
time  
synchronization pulse onto the network. Upon  
receiving the synchronization pulse, each Slave  
meter automatically adjusts the minutes and  
seconds of its RTC Time setting to synchronize  
with the Host.  
Real-Time Clock Synchronization Figure  
5.0 REVIEWING THE FRONT BUTTONS AND DISPLAY  
KEY  
DSP  
PAR  
F1ꢁ  
DISPLAY MODE OPERATION  
PROGRAMMING MODE OPERATION  
Exit programming and return to Display Mode  
Store selected parameter and index to next parameter  
Increment selected parameter value or selections  
Decrement selected parameter value or selections  
Selects digit location in parameter values  
Index display through Timer, Cycle Counter, Date, and Time  
Access Programming Mode  
Function key 1; hold for 3 seconds for Second Function 1 **  
Function key 2; hold for 3 seconds for Second Function 2 **  
Reset (Function key) ***  
F2  
RST  
* Cycle counter and Real-Time Clock displays are locked out in Factory Settings.  
** Factory setting for the F1 and F2 keys is NO mode.  
*** Factory setting for the RST key is ꢀꢁꢂꢃꢄꢅ (Reset Display)  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 PROGRAMMING THE METER  
OVERVIEW  
PROGRAMMING MENU  
DISPLAY MODE  
module in sequence. Note that Modules 5 through 8 are only accessible when  
The meter normally operates in the Display Mode. In this mode, the meter  
displays can be viewed consecutively by pressing the DSP key. The  
annunciators to the left of the display indicate which display is currently shown;  
Timer (TMR), Cycle Counter (CNT), or Date (DAT). The Time Display for the  
Real-Time Clock is shown with no annunciator. Any of these displays can be  
locked from view through programming. (See Module 3.)  
the appropriate plug-in option card is installed. If lost or confused while  
programming, press the DSP key to exit programming mode and start over.  
When programming is complete, it is recommended to record the meter settings  
on the Parameter Value Chart and lock-out parameter programming with a User  
Input or lock-out code. (See Modules 2 and 3 for lock-out details.)  
PROGRAMMING MODE  
FACTORY SETTINGS  
Two programming modes are available.  
Factory Settings may be completely restored in Module 9. This is a good  
starting point if encountering programming problems. Throughout the module  
description sections which follow, the factory setting for each parameter is  
shown below the parameter display. In addition, all factory settings are listed on  
the Parameter Value Chart following the programming section.  
Full Programming Mode permits all parameters to be viewed and modified.  
Upon entering this mode, the front panel keys change to Programming Mode  
operations. This mode should not be entered while a process is running, since  
the meter timing functions and User Input response may not operate properly  
while in Full Programming Mode.  
Quick Programming Mode permits only certain parameters to be viewed and/or  
modified. When entering this mode, the front panel keys change to  
Programming Mode operations, and all meter functions continue to operate  
properly. Quick Programming Mode is configured in Module 3. The Display  
Intensity Level “ꢀꢄꢊꢅꢋ” parameter is only available in the Quick Programming  
Mode when the security code is non-zero. For a description, see Module 9—  
Factory Service Operations. Throughout this document, Programming Mode  
(without Quick in front) always refers to “Full” Programming Mode.  
ALTERNATING SELECTION DISPLAY  
In the module description sections which follow, the dual display with arrows  
appears for each programming parameter. This is used to illustrate the display  
alternating between the parameter (top display) and the parameter’s Factory  
Setting (bottom display). In most cases, selections or value ranges for the  
parameter will be listed on the right.  
Indicates Program Mode Alternating Display  
Parameter ꢌꢈꢍ ꢉ«  
PROGRAMMING TIPS  
The Programming Menu is organized into nine modules. (See above.) These  
modules group together parameters that are related in function. It is  
recommended to begin programming with Module 1 and proceed through each  
ꢊꢅꢋꢅꢊ Selection/Value  
ª
Factory Settings are shown.  
STEP BY STEP PROGRAMMING INSTRUCTIONS:  
PROGRAMMING MODE ENTRY (PAR KEY)  
NUMERICAL VALUE ENTRY (ARROW, RST & PAR KEYS)  
For parameters which require a numerical value entry, the arrow keys can be  
used to increment or decrement the display to the desired value. When an arrow  
key is pressed and held, the display automatically scrolls up or scrolls down.  
The longer the key is held, the faster the display scrolls.  
The Programming Mode is entered by pressing the PAR key. If this mode is  
not accessible, then meter programming is locked by either a security code or a  
hardware lock. (See Modules 2 and 3 for programming lock-out details.)  
In addition, the RST key can be used in combination with the arrow keys to  
enter numerical values. The RST key is pressed to select a specific digit to be  
changed, which blinks when selected. Once a digit is selected, the arrow keys  
are used to increment or decrement that digit to the desired number. The RST  
key is then pressed again to select the next digit to be changed. This “select and  
set” sequence is repeated until each digit is displaying the proper number.  
Pressing the PAR key stores and activates the displayed value, and also  
advances the meter to the next parameter.  
MODULE ENTRY (ARROW & PAR KEYS)  
Upon entering the Programming Mode, the display alternates between ꢆꢁꢇ  
and the present module (initially ꢈꢉ). The arrow keys (F1S and F2T) are used  
to select the desired module, which is then entered by pressing the PAR key.  
PARAMETER (MODULE) MENU (PAR KEY)  
Each module has a separate parameter menu. These menus are shown at the  
start of each module description section which follows. The PAR key is pressed  
to advance to a particular parameter to be changed, without changing the  
programming of preceding parameters. After completing a module, the display  
will return to ꢆꢁꢇ ꢈꢉ. From this point, programming may continue by selecting  
and entering additional modules. (See MODULE ENTRY above.)  
PROGRAMMING MODE EXIT (DSP KEY or PAR KEY at ꢆꢁꢇ ꢈꢉ)  
The Programming Mode is exited by pressing the DSP key (from anywhere  
in the Programming Mode) or the PAR key (with ꢆꢁꢇ ꢈꢉ displayed). This will  
commit any stored parameter changes to memory and return the meter to the  
Display Mode. If a parameter was just changed, the PAR key should be pressed  
to store the change before pressing the DSP key. (If power loss occurs before  
returning to the Display Mode, verify recent parameter changes.)  
PARAMETER SELECTION ENTRY (ARROW & PAR KEYS)  
For each parameter, the display alternates between the parameter and the  
present selection or value for that parameter. For parameters which have a list of  
selections, the arrow keys (F1S and F2T) are used to sequence through the list  
until the desired selection is displayed. Pressing the PAR key stores and activates  
the displayed selection, and also advances the meter to the next parameter.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.1 MODULE 1 - TIMER INPUT PARAMETERS (ꢏꢄꢌꢈꢆ)  
PARAMETER MENU  
Module 1 is the programming module for the Timer Input Parameters. In the  
ꢅꢀꢔꢅꢄꢑ, ꢅꢀꢁꢖꢄꢑ *  
Edge Triggered Operation - 2 Input  
ꢐꢇꢊꢀꢄꢑ, ꢐꢁꢖꢃꢄꢑ *  
Display Mode, the TMR annunciator indicates the Timer display is currently  
being shown. An EXCHANGE PARAMETER LISTS feature, which includes  
the Timer Start and Timer Stop Values, is explained in Module 2.  
Edge Triggered Operation - 2 Input,  
with Display Hold  
Time  
Start  
Time  
Start  
Display  
Update  
Time Start,  
Display Update  
Time Start,  
Display Update  
INPUT A  
TIMER RANGE  
INPUT A  
INPUT B  
Time  
Stop  
Time  
Stop  
23 TIMER RANGE SELECTIONS  
Time Stop,  
Display Update  
ꢁꢓꢈꢔ«  
ª ꢒꢒꢒꢒꢒꢒ  
(= SEC; = MIN; = HR; = DAY)ꢕ  
INPUT B  
RANGE  
SELECTION  
MAXIMUM  
DISPLAY RESOLUTION  
DISPLAY  
RANGE  
MAXIMUM  
DISPLAY  
* - Timer is reset at Time Start edge.  
SELECTION DISPLAY RESOLUTION  
MINUTES/SECONDS  
SECONDS  
1 SEC  
0.1 SEC  
1 SEC  
0.1 SEC  
ꢈꢈꢈꢈꢗꢂꢂ ꢘꢘꢘꢘꢗꢒꢘ  
ꢈꢈꢈꢗꢂꢂꢗꢂ ꢘꢘꢘꢗꢒꢘꢗꢘ  
ꢈꢈꢗꢂꢂꢗꢂꢂ ꢘꢘꢗꢒꢘꢗꢘꢘ  
ꢈꢗꢂꢂꢗꢂꢂꢂ ꢘꢗꢒꢘꢗꢘꢘꢘ  
ꢒꢒꢒꢒꢒꢒ ꢘꢘꢘꢘꢘꢘ  
ꢒꢒꢒꢒꢒꢗꢒ ꢘꢘꢘꢘꢘꢗꢘ  
ꢒꢒꢒꢒꢗꢒꢒ ꢘꢘꢘꢘꢗꢘꢘ  
ꢒꢒꢒꢗꢒꢒꢒ ꢘꢘꢘꢗꢘꢘꢘ  
0.01 SEC  
0.001 SEC  
0.01 SEC  
0.001 SEC  
TIMER INPUT FILTERING  
ꢜꢌꢊꢃꢅ«  
ª
HOURS/MINUTES  
MINUTES  
ꢉꢈ  
ꢉꢚꢚ  
1 MIN  
0.1 MIN  
1 MIN  
0.1 MIN  
ꢐꢐꢐꢐꢗꢈꢈ ꢘꢘꢘꢘꢗꢒꢘ  
ꢐꢐꢐꢗꢈꢈꢗꢈ ꢘꢘꢘꢗꢒꢘꢗꢘ  
ꢐꢐꢗꢈꢈꢗꢈꢈ ꢘꢘꢗꢒꢘꢗꢘꢘ  
ꢐꢗꢈꢈꢗꢈꢈꢈ ꢘꢗꢒꢘꢗꢘꢘꢘ  
ꢈꢈꢈꢈꢈꢈ ꢘꢘꢘꢘꢘꢘ  
ꢈꢈꢈꢈꢈꢗꢈ ꢘꢘꢘꢘꢘꢗꢘ  
ꢈꢈꢈꢈꢗꢈꢈ ꢘꢘꢘꢘꢗꢘꢘ  
ꢈꢈꢈꢗꢈꢈꢈ ꢘꢘꢘꢗꢘꢘꢘ  
ꢉꢈ  
Provides a 50 msec debounce for the Timer Inputs (A and B). Select when  
0.01 MIN  
0.001 MIN  
0.01 MIN  
0.001 MIN  
using relays or switch contacts as a signal source.  
HOURS/MINUTES/SECONDS  
ꢐꢐꢗꢈꢈꢗꢂꢂ ꢘꢘꢗꢒꢘꢗꢒꢘ  
ꢐꢗꢈꢈꢗꢂꢂꢗꢂ ꢘꢗꢂꢘꢗꢂꢘꢗꢘ  
HOURS  
1 SEC  
1 HR  
0.1 HR  
ꢐꢐꢐꢐꢐꢐ ꢘꢘꢘꢘꢘꢘ  
ꢐꢐꢐꢐꢐꢗꢐ ꢘꢘꢘꢘꢘꢗꢘ  
ꢐꢐꢐꢐꢗꢐꢐ ꢘꢘꢘꢘꢗꢘꢘ  
ꢐꢐꢐꢗꢐꢐꢐ ꢘꢘꢘꢗꢘꢘꢘ  
0.1 SEC  
TIMING DIRECTION  
0.01 HR  
0.001 HR  
DAYS/HOURS/MINUTES  
ꢀꢀꢗꢐꢐꢗꢈꢈ ꢘꢘꢗꢑꢙꢗꢒꢘ  
1 MIN  
ꢃ ꢀꢞ«  
ꢝꢆ  
ꢝꢆ  
ꢀꢈ  
ª
TIMER INPUT OPERATION  
Timing direction can be reversed through a User Input. (See Module 2.)  
ꢊꢅꢋꢅꢊ ꢅꢀꢎꢅꢄꢏ ꢅꢀꢎꢅꢄꢑ ꢐꢇꢊꢀꢄꢑ  
ꢊꢅꢋꢁꢖꢃ ꢅꢀꢁꢖꢄꢏ ꢅꢀꢁꢖꢄꢑ ꢐꢁꢂꢃꢄꢑ  
ꢌꢈꢆ ꢉ«  
ª
ꢊꢅꢋꢅꢊ  
TIMER START VALUE  
This parameter determines how the Timer Input Signals affect the  
“Run/Stop” status of the Timer. The timing diagrams below reflect a Sinking  
input setup (active low). A Sourcing input setup (active high) is available  
through plug jumper selection (see Section 2.0). In this case, the logic levels of  
the timing diagrams would be inverted.  
The Timer can also be stopped using a Timer Stop Value or a Setpoint. This  
type of Stop condition is cleared when a Timer Reset occurs, or another start  
edge is applied.  
ꢃ ꢂꢃꢁ«  
ª ꢛꢛꢛꢛꢛꢛ  
ꢛꢛꢛꢛꢛꢛ to ꢘꢘꢘꢘꢘꢘ  
The Timer returns to this value whenever a Timer Reset occurs. The value is  
entered in the same display format as the Timer Range selected. Non-zero  
values are normally used for “timing down” applications, but they can also  
provide an “offset” value when timing up.  
For ꢊꢅꢋꢅꢊ and ꢅꢀꢎꢅꢄꢏ operation, Input B provides a level active Timer  
Inhibit function. This function is also available through a User Input (see  
Module 2). Timing diagrams are shown below for “ꢊꢅꢋꢅꢊ” through “ꢐꢇꢊꢀꢄꢑ”  
modes. The “ꢊꢅꢋꢁꢂꢃ” through “ꢐꢁꢂꢃꢄꢑ” modes are identical except the  
timer display value is also reset at “Time Start” edges. In the “ꢐꢇꢊꢀꢄꢑ” and  
ꢐꢁꢂꢃꢄꢑ” modes, the timer display value remains held and only updates when  
a Timer Start (Input A) or Timer Stop (Input B) edge occurs.  
TIMER STOP VALUE  
ꢃ ꢂꢃꢉ«  
ꢈꢉ  
ꢟꢅꢂ  
ª
ꢠꢈꢉ  
The Timer stops when this value is reached, regardless of the signal levels on  
the Timer Inputs. Selecting ꢟꢅwill display the ꢋꢓꢊꢝsub-menu where the Stop  
Value can be set or changed. The Stop Value is entered in the same display  
format as the Timer Range selected. This Stop condition is cleared when a  
Timer Reset occurs. Select ꢈꢉ if a Stop Value is not being used.  
ꢊꢅꢋꢅꢊ, ꢊꢅꢋꢁꢖꢃ *  
ꢅꢀꢔꢅꢄꢏ, ꢅꢀꢁꢖꢄꢏ *  
Edge Triggered Operation -1 Input  
Level Active (Gated) Operation  
Time  
Start  
Time Time  
Stop Start  
Time  
Stop  
Time  
Stop  
Time  
Stop  
Time  
Start  
Time  
Start  
ꢋꢓꢊꢝꢅ  
«
ꢛꢛꢛꢛꢛꢛ  
INPUT A  
INPUT A  
ꢛꢛꢛꢛꢛꢛ to ꢘꢘꢘꢘꢘꢘ  
ª
INPUT B - Timer Inhibit (Level Active)  
INPUT B - Timer Inhibit (Level Active)  
* - Timer is reset at Time Start edge.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FLASH TIMER ANNUNCIATOR  
TIMER RESET AT POWER-UP  
ꢃ ꢍꢄꢝ«  
ª
ꢜꢊꢤꢖ«  
ꢈꢉ  
ꢈꢉ ꢃꢄꢁꢝꢈ ꢃꢄꢂꢃꢉꢆ  
ꢈꢉ  
ꢟꢅꢂ  
ª
ꢈꢉ  
The Timer can be programmed to Reset at each meter power-up.  
This parameter allows the Timer annunciator (TMR) to flash when the Timer  
is running or stopped/inhibited. Select if a flashing indicator is not desired.  
TIMER INPUT STATE AT POWER-UP  
ꢌꢥꢆꢄꢝ«  
ª
ꢂꢃꢉꢆ  
ꢂꢓꢋꢅ  
ꢖꢃꢉꢆ  
Determines the “Run/Stop” State of the Timer at Power-up. This parameter  
does not apply to ꢊꢅꢋꢅꢊ timer input operation.  
ꢂꢃꢉꢆ - Timer Stopped at power-up, regardless of prior run/stop state  
ꢂꢓꢋꢅ - Timer assumes the same run/stop state it was in prior to power-down  
6.2 MODULE 2 - USER INPUT AND FRONT PANEL FUNCTION KEY  
PARAMETERS (ꢑꢄꢚꢈꢡ)  
PARAMETER MENU  
Module 2 is the programming module for the rear terminal User Inputs and  
front panel Function Keys.  
PROGRAMMING MODE LOCK-OUT  
ꢝꢂꢅꢁꢄ«  
ꢆꢊꢉꢡ  
Three rear terminal User Inputs are individually programmable to perform  
specific meter control functions. While in the Display Mode, the function is  
ª
executed when the User Input transitions to the active state. Refer to the User  
Input specifications for active state response times. Certain User Input functions  
are disabled in “Full” Programming Mode. User Inputs should be programmed  
while in the inactive state.  
Three front panel Function Keys, F1, F2 and RST, are also individually  
programmable to perform specific meter control functions. While in the Display  
Mode, the primary function is executed when the key is pressed. Holding the  
F1 or F2 Function Keys for three seconds executes a secondary function. It is  
possible to program a secondary function without a primary function. The front  
panel key functions are disabled in both Programming Modes.  
Programming Mode is locked-out, as long as activated (maintained action).  
In Module 3, certain parameters can be setup where they are still accessible  
during Programming Mode Lock-out. A security code can be configured to  
allow complete programming access during User Input lock-out. This parameter  
does not apply to the function keys. Program only one user input for this function.  
EXCHANGE PARAMETER LISTS  
In most cases, if more than one User Input and/or Function Key is  
programmed for the same function, the maintained (level active) functions will  
be performed while at least one of those User Inputs or Function Keys are  
activated. The momentary (edge triggered) functions are performed every time  
any of those User Inputs or Function Keys transition to the active state.  
Some functions have a sublist of parameters, which appears when PAR is  
pressed at the listed function. A sublist provides yes/no selection for Display  
Values or Setpoints which pertain to the programmed function. The function  
will only be performed on the parameters entered as Z&4 in the sublist. If a User  
Input or Function Key is configured for a function with a sublist, then that  
sublist will need to be scrolled through each time, in order to access any  
parameters for the User Inputs or Function Keys which follow.  
ꢝꢂꢅꢁꢄ«  
ꢊꢌꢂꢃ  
«  
ꢊꢌꢂꢃ  
ª
ª
Two lists of parameter entries are available for the Timer/Counter Start and  
Stop Values; Setpoint On/Off and Time-Out Values; and Setpoint Daily On/Off  
Occurrence (for Real-Time Clock option). The two lists are named ꢊꢌꢂꢃꢄꢓ and  
ꢊꢌꢂꢃꢄꢢ. If a User Input is used to select the list, then ꢊꢌꢂꢃꢄꢓ is selected when  
the User Input is in the inactive state and ꢊꢌꢂꢃꢄꢢ is selected when the User  
Input is in the active state (maintained action). If a front panel Function Key is  
used to select the list, then the list will toggle for each key press (momentary  
action). The display will only indicate which list is active when the list is  
changed or when entering any Programming Mode.  
To program the values for ꢊꢌꢂꢃꢄꢓ and ꢊꢌꢂꢃꢄꢢ, first complete the  
programming of all the parameters. Exit programming and switch to the other  
list. Re-enter programming and enter the Timer/Counter Start and Stop Values  
(ꢃ ꢂꢃꢁꢃ, ꢃ ꢂꢃꢉꢆ, ꢡ ꢂꢃꢁꢃ, ꢡ ꢂꢃꢉꢆ), and if applicable, the Setpoint On/Off and  
Time-Out Values (ꢂꢆꢄꢏ, ꢂꢆꢄꢑ, ꢂꢆꢄꢙ, ꢂꢆꢄꢣ, ꢂꢆꢉꢚꢄꢏ, ꢂꢆꢉꢚꢄꢑ, ꢂꢆꢉꢚꢄꢙ, ꢂꢆꢉꢚꢄꢣ,  
ꢃꢉꢝꢃꢄꢏ, ꢃꢉꢝꢃꢄꢑ, ꢃꢉꢝꢃꢄꢙ, ꢃꢉꢝꢃꢄꢣ), and the Setpoint Daily On/Off Occurrence  
(ꢀ ꢉꢈꢄꢏ, ꢀ ꢉꢈꢄꢑ, ꢀ ꢉꢈꢄꢙ, ꢀ ꢉꢈꢄꢣ, ꢀꢉꢚꢚꢄꢏ, ꢀꢉꢚꢚꢄꢑ, ꢀꢉꢚꢚꢄꢙ, ꢀꢉꢚꢚꢄꢣ). If any  
other parameters are changed, the other list values must be reprogrammed.  
Program only one user input for this function.  
NO FUNCTION  
«  
ꢈꢉ  
ꢝꢂꢅꢁꢄ«  
ª
ª
ꢈꢉ  
With this selection, NO function is performed. This is the factory setting for  
all user inputs and function keys except the Reset (RST) Key.  
Note: When downloading a software program containing List A/B, make sure  
that both the software and meter have the same list active. The active list in  
a software program is the one being displayed in Input Setup and/or Setpoint  
Alarms category.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DISPLAY SELECT (Level Active)  
DISPLAY HOLD (Level Active)  
ꢝꢂꢅꢁꢄ«  
ª ꢀꢂꢅꢊꢄꢊ  
ꢝꢂꢅꢁꢄ«  
ª ꢀꢄꢐꢉꢊꢀ  
«  
ª ꢀꢄꢐꢉꢊꢀ  
When active (maintained action), the meter continuously scrolls through all  
displays that are not “locked-out” in the Display mode. (See Module 3 for  
Display Lock-out details.) A sub-menu provides Scrolling Speed selection.  
When active (maintained action), the meter “freezes” the display values  
entered as ꢟꢅin the sublist, while normal meter operation continues internally.  
Program only one user input for this function.  
ꢂꢆꢅꢅꢀ  
«
ꢑꢗꢒ ꢂꢅꢡ  
DISPLAY  
DESCRIPTION  
FACTORY  
ꢑꢗꢒ ꢂꢅꢡ ꢒ ꢂꢅꢡ  
Timer  
t-dsp  
NO  
NO  
NO  
NO  
ª
Cycle Counter  
RTC Date  
RTC Time  
C-dsp  
rtC-d  
rtC-t  
DISPLAY SELECT (Edge Triggered)  
ꢝꢂꢅꢁꢄ«  
ª ꢀꢂꢅꢊꢄꢅ  
When activated (momentary action), the meter advances to the next display  
that is not “locked-out” in the Display mode. (See Module 3 for Display Lock-  
out details.)  
DISPLAY HOLD and RESET (Level Active Reset)  
ꢝꢂꢅꢁꢄ«  
ª ꢐꢁꢂꢃꢄꢊ  
«  
ª ꢐꢁꢂꢃꢄꢊ  
When activated, the meter “freezes” the display values entered as ꢟꢅꢂ in the  
sublist, before performing an internal Maintained Reset on the selected  
displays. This function does not apply to the RTC Time or Date displays.  
DISPLAY  
DESCRIPTION  
FACTORY  
DISPLAY RESET (Level Active)  
Timer  
t-dSp  
C-dSP  
NO  
NO  
ꢝꢂꢅꢁꢄ«  
ª ꢀꢁꢂꢃꢄꢊ  
«  
ª ꢀꢁꢂꢃꢄꢊ  
Cycle Counter  
When active (maintained action), the meter continually resets only the  
currently shown display. If the RTC Time or Date is displayed, this function  
applies to the Outputs assigned to the RTC, and does not Reset the actual RTC  
Time or Date display. (See Module 6 for details on Output Assignment and  
Output Reset with Display Reset.)  
DISPLAY HOLD and RESET (Edge Triggered Reset)  
ꢝꢂꢅꢁꢄ«  
ª ꢐꢁꢂꢃꢄꢅ  
«  
ª ꢐꢁꢂꢃꢄꢅ  
When activated, the meter “freezes” the display values entered as ꢟꢅꢂ in the  
sublist, before performing an internal Momentary Reset on the selected  
displays. This function does not apply to the RTC Time or Date displays.  
Program only one user input for this function.  
DISPLAY RESET (Edge Triggered)  
ꢝꢂꢅꢁꢄ«  
ª ꢀꢁꢖꢃꢄꢅ  
«  
ª ꢀꢁꢖꢃꢄꢅ  
DISPLAY  
DESCRIPTION  
FACTORY  
Timer  
t-dSp  
C-dSP  
NO  
NO  
When activated (momentary action), the meter resets only the currently  
shown display. This is the factory setting for the Reset (RST) key. If the RTC  
Time or Date is displayed, this function applies to the Outputs assigned to the  
RTC, and does not Reset the actual RTC Time or Date display. (See Module 6  
for details on Output Assignment and Output Reset with Display Reset.)  
Cycle Counter  
INHIBIT (Level Active)  
ꢝꢂꢅꢁꢄ«  
ª ꢌꢈꢐꢌꢢꢃ  
«  
ª ꢌꢈꢐꢌꢢꢃ  
MAINTAINED RESET (Level Active)  
When active (maintained action), timing and counting ceases for the displays  
entered as ꢟꢅꢂ in the sublist. The inhibit function is not a ꢃ ꢖꢃꢁꢃ or ꢃ ꢖꢃꢉꢍ  
event in Setpoint programming. This function does not apply to RTC Time or  
Date displays. Program only one user input for this function.  
ꢝꢂꢅꢁꢄ«  
ꢁꢖꢃꢄꢊ  
«  
ꢁꢂꢃꢄꢊ  
ª
ª
When active (maintained action), the meter continually resets the displays  
entered as ꢟꢅꢂ in the sublist. The sublist appears when the PAR key is pressed.  
This function does not apply to the RTC Time or Date displays.  
DISPLAY  
DESCRIPTION  
Timer  
FACTORY  
t-dSp  
C-dSP  
NO  
NO  
Cycle Counter  
DISPLAY  
DESCRIPTION  
Timer  
FACTORY  
t-dSp  
C-dSP  
NO  
NO  
Cycle Counter  
CHANGE DIRECTION (Level Active)  
«  
ª ꢡꢦꢄꢀꢞꢁ  
ꢝꢂꢅꢁꢄ«  
ª ꢡꢦꢄꢀꢞꢁ  
MOMENTARY RESET (Edge Triggered)  
ꢝꢂꢅꢁꢄ«  
ª
«  
ꢁꢂꢃꢄꢅ  
When active (maintained action), the timing or counting direction for the  
display entered as ꢟꢅꢂ in the sublist, will be reversed from the direction set by  
the Timing Direction (ꢃꢄꢀꢞꢁ) and/or Counting Direction (ꢡꢄꢀꢞꢁ) parameters in  
Modules 1 and 4. (Program only one User Input per display for this function.)  
This function does not apply to RTC Time or Date displays.  
ª
ꢁꢂꢃꢄꢅ  
When activated (momentary action), the meter resets the displays entered as  
ꢟꢅꢂ in the sublist. Function does not apply to RTC Time or Date displays.  
DISPLAY  
DESCRIPTION  
Timer  
FACTORY  
DISPLAY  
DESCRIPTION  
FACTORY  
t-dSp  
C-dSP  
NO  
NO  
Timer  
t-dSp  
C-dSP  
NO  
NO  
Cycle Counter  
Cycle Counter  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHANGE DISPLAY INTENSITY LEVEL  
OUTPUT SET (Level Active)  
ꢝꢂꢅꢁꢄ«  
ꢀꢄꢊꢅꢋ  
«  
ꢀꢄꢊꢅꢋ  
«  
ª ꢉꢂꢅꢃꢄꢊ  
ꢝꢂꢅꢁꢄ«  
ª ꢧꢂꢅꢃꢄꢊ  
ª
ª
When activated (maintained action), the meter continually activates the  
When activated (momentary action), the display intensity changes to the next  
intensity level (of 4). The four levels correspond to Display Intensity Level  
(ꢀꢄꢊꢅꢋ) settings of 0, 3, 8 & 15. The intensity level, when changed via the User  
Input/Function Key, is not retained at power-down, unless Quick Programming  
or Full Programming mode is entered and exited. The unit will power-up at the  
last saved intensity level.  
output for all Setpoints entered as ꢟꢅꢂ in the sublist.  
DISPLAY  
DESCRIPTION  
Setpoint 1  
Setpoint 2  
Setpoint 3  
Setpoint 4  
FACTORY  
SP-1  
NO  
NO  
NO  
NO  
SP-2  
SP-3  
SP-4  
Note: The next two parameters only appear when an RS232 or RS485 Serial  
Communications Card is installed in the meter.  
OUTPUT SET (Edge Triggered)  
ꢝꢂꢅꢁꢄ«  
ª ꢉꢂꢅꢃꢄꢅ  
«  
ª ꢉꢂꢅꢃꢄꢅ  
PRINT REQUEST  
ꢝꢂꢅꢁꢄ«  
ꢆꢁꢞꢥꢃ  
«  
ꢆꢁꢞꢥꢃ  
When activated (momentary action), the meter activates the output for all  
Setpoints entered as ꢟꢅꢂ in the sublist.  
ª
ª
When activated, the meter issues a block print through the serial port. The  
specific values transmitted during a print request are selected with the Print  
Options parameter in Module 7. For User Inputs (level active), the meter  
transmits blocks repeatedly as long as the input is active. For Function Keys,  
(edge triggered) only one block is transmitted per key press.  
DISPLAY  
DESCRIPTION  
Setpoint 1  
Setpoint 2  
Setpoint 3  
Setpoint 4  
FACTORY  
SP-1  
NO  
NO  
NO  
NO  
SP-2  
SP-3  
SP-4  
PRINT REQUEST and RESET (Edge Triggered)  
OUTPUT RESET (Level Active)  
«  
ª ꢆꢁꢄꢁꢂꢃ  
ꢝꢂꢅꢁꢄ«  
ª ꢆꢁꢄꢁꢂꢃ  
ꢝꢂꢅꢁꢄ«  
ª ꢉꢁꢂꢃꢄꢊ  
«  
ª ꢉꢁꢂꢃꢄꢊ  
When activated (momentary action), the meter first issues a block print  
through the serial port, and then performs a Momentary Reset on the displays  
entered as ꢟꢅꢂ in the sublist. The specific values transmitted in the print block  
are selected with the Print Options parameter in Module 7. Only one transmit  
and reset occurs per User Input activation or Function Key press.  
When activated (maintained action), the meter continually deactivates the  
output for all Setpoints entered as ꢟꢅꢂ in the sublist.  
DISPLAY  
DESCRIPTION  
Setpoint 1  
Setpoint 2  
Setpoint 3  
Setpoint 4  
FACTORY  
SP-1  
NO  
NO  
NO  
NO  
SP-2  
SP-3  
SP-4  
DISPLAY  
DESCRIPTION  
Timer  
FACTORY  
t-dSp  
C-dSP  
NO  
NO  
Cycle Counter  
OUTPUT RESET (Edge Triggered)  
Note: The remaining parameters only appear when a Setpoint Card is  
installed in the meter.  
ꢝꢂꢅꢁꢄ«  
ª ꢉꢁꢂꢃꢄꢅ  
«  
ª ꢉꢁꢖꢃꢄꢅ  
OUTPUT HOLD (Level Active)  
«  
ª ꢉꢄꢐꢉꢊꢀ  
ꢝꢂꢅꢁꢄ«  
ª ꢉꢄꢐꢉꢊꢀ  
When activated (momentary action), the meter deactivates the output for all  
Setpoints entered as ꢟꢅꢂ in the sublist.  
DISPLAY  
DESCRIPTION  
Setpoint 1  
Setpoint 2  
Setpoint 3  
Setpoint 4  
FACTORY  
When active (maintained action), the meter “holds” (maintains) the present  
output state for all Setpoints entered as ꢟꢅꢂ in the sublist. Does not apply to  
Output Set and Reset User Inputs. Program only one user input for this function.  
SP-1  
NO  
NO  
NO  
NO  
SP-2  
SP-3  
SP-4  
DISPLAY  
DESCRIPTION  
Setpoint 1  
Setpoint 2  
Setpoint 3  
Setpoint 4  
FACTORY  
SP-1  
NO  
NO  
NO  
NO  
SP-2  
SP-3  
SP-4  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.3 MODULE 3 - DISPLAY AND PROGRAM LOCK-OUT  
PARAMETERS (ꢙꢄꢊꢉꢡ)  
PARAMETER MENU  
** These parameters only appear if a Setpoint option card is installed.  
= Setpoint Number 1 thru 4  
Module 3 is the programming module for setting the Display Lock-out  
Parameters and the “Quick Programming Mode” Value Access Parameters. In the  
Quick Programming mode, after the PROGRAM LOCKOUT PARAMETERS  
and before the Security Code (ꢡꢉꢀꢅ), a Display Intensity Level (ꢀꢄꢊꢅꢋ)  
parameter is available when the security code is non-zero. It allows the display  
intensity to be set to 1 of 16 levels (0-15).  
TIMER & CYCLE COUNTER START/STOP VALUE ACCESS  
ꢃ ꢂꢃꢁ« ꢃ ꢂꢃꢉ« ꢡ ꢂꢃꢁ« ꢡ ꢂꢃꢉ«  
ꢊꢉꢡ ª ꢊꢉꢡ ª ꢊꢉꢡ ª ꢊꢉꢡ  
ª
Timer & Counter Start/Stop Values can be programmed for ꢁꢅꢀ, ꢅꢈꢃ, or ꢊꢉꢡ.  
DISPLAY LOCK-OUT PARAMETERS  
When operating in the Display Mode, the meter displays can be viewed  
consecutively by repeatedly pressing the DSP key. The annunciators to the left  
of the display indicate which display is currently shown. Timer (TMR), Cycle  
Counter (CNT), or Date (DAT). The Time Display for the Real-Time Clock is  
shown with no annunciator. Any of these displays can be locked from view with  
the DISPLAY LOCK-OUT parameters. Using these parameters, each display  
can be programmed for “Read” or “Lock” defined as follows:  
PTC901: REAL-TIME CLOCK TIME SETTING ACCESS  
ꢂꢅꢃꢄ«  
ꢊꢉꢡ  
ꢅꢈꢃ ꢊꢉꢡ  
ª
This parameter can be programmed for ꢅꢈꢃ or ꢊꢉꢡ. Selecting ꢅꢈꢃ allows  
SELECTION  
Read  
DISPLAY  
ꢁꢅꢀ  
DESCRIPTION  
setting or changing the RTC Time in Quick Programming mode.  
Visible in Display Mode  
Not visible in Display Mode  
Lock  
ꢊꢉꢡ  
SECURITY CODE  
TIMER DISPLAY LOCK-OUT  
CYCLE COUNTER DISPLAY LOCK-OUT  
PTC901: REAL-TIME CLOCK DATE/TIME DISPLAY LOCK-OUT  
ꢡꢉꢀ«  
ꢛꢛꢛ  
ꢛꢛꢛ to ꢑꢒꢒ  
ª
ꢁꢃꢡꢄ« ꢁꢃꢡꢄ«  
ꢃꢄꢀꢂ« ꢡꢄꢀꢂ«  
ꢊꢉꢡ ª ꢊꢉꢡ  
ꢁꢅꢀ ª ꢊꢉꢡ ª  
Entry of a non-zero value will cause the ꢡꢉꢀꢅ prompt to appear when trying  
to access the “Full” Programming Mode. Access will only be allowed after  
entering a matching security code or the universal unlock code of ꢑꢑꢑ. With this  
lock-out, a User Input would not have to be used for the Program Lock-out  
function. Note however, the Security Code lock-out is overridden when an User  
Input, configured for Program Lock-out (ꢆꢊꢉꢡ), is not active (See Chart.)  
ª
These displays can be programmed for ꢁꢅꢀ or ꢊꢉꢡ. When a particular meter  
function is not used, the Display Lock-out should be set to ꢊꢉfor that display.  
PROGRAM LOCK-OUT PARAMETERS (VALUE ACCESS)  
“Full” Programming Mode permits all parameters to be viewed and  
modified. This programming mode can be locked with a Security Code and/or  
a User Input. When locked, and the PAR key is pressed, the meter enters a  
Quick Programming Mode. In this mode, access to Setpoint Values, Timer &  
Cycle Counter Start/Stop Values, and Time Setting for the Real-Time Clock can  
be programmed for “Read”, “Enter”, or “Lock” defined as follows:  
PROGRAMMING MODE ACCESS  
SECURITY USER INPUT USER INPUT MODE WHEN “PAR”  
FULL PROGRAMMING  
MODE ACCESS  
CODE  
SELECTION  
STATE  
KEY IS PRESSED  
0
———— Full Programming Immediate access  
After Quick Programming  
not ꢆꢊꢉꢡ  
SELECTION DISPLAY  
DESCRIPTION  
Read  
Visible, not changeable, in Quick Programming Mode  
Visible and changeable in Quick Programming Mode  
Not visible in Quick Programming Mode  
not 0  
not 0  
———— Quick Programming with correct Security  
code entry  
not ꢆꢊꢉꢡ  
ꢁꢅꢀ  
Enter  
Lock  
ꢅꢈꢃ  
ꢊꢉꢡ  
After Quick Programming  
Active  
Quick Programming with correct Security  
code entry  
ꢆꢊꢉꢡ  
SETPOINT 1 to 4 VALUE ACCESS ** (= 1 thru 4)  
not 0  
Not Active Full Programming Immediate access  
Active Quick Programming No access  
Not Active Full Programming Immediate access  
ꢆꢊꢉꢡ  
ꢆꢊꢉꢡ  
ꢆꢊꢉꢡ  
0
0
ꢂꢆꢄ« ꢂꢆꢉꢚꢄ« ꢃꢉꢋꢃꢄ«  
ꢊꢉꢡ  
ª
ª
ª
ꢊꢉꢡ  
ꢊꢉꢡ  
Throughout this bulletin, Programming Mode (without Quick in front) always  
refers to “Full” Programming.  
Setpoint Values for SP1 thru SP4 can be programmed for ꢁꢅꢀ, ꢅꢈꢃ, or ꢊꢉꢡ.  
ꢂꢆꢉꢚꢄꢥ and ꢃꢉꢝꢃꢄꢥ are only displayed when they apply to the Setpoint Action  
(ꢓꢡꢃꢄꢥ) programmed for that particular Setpoint. (See Module 6 for details.)  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.4 MODULE 4 - CYCLE COUNTER PARAMETERS (ꢣꢄꢡꢈꢃ)  
PARAMETER MENU  
Module 4 is the programming module for the Cycle Counter Parameters. In the  
Display Mode, the CNT annunciator indicates the Cycle Counter display is  
CYCLE COUNTER START VALUE  
currently being shown. An EXCHANGE PARAMETER LISTS feature, which  
includes the Cycle Counter Start and Stop Values, is explained in Module 2.  
ꢡ ꢂꢃꢁ«  
ꢛꢛꢛꢛꢛꢛ to ꢘꢘꢘ999  
ª ꢛꢛꢛꢛꢛꢛ  
CYCLE COUNTER COUNT SOURCE  
The Cycle Counter returns to this value whenever a Cycle Counter Reset  
occurs. Non-zero values are normally used for “down counting” applications,  
but they can also provide an “offset” value when counting up.  
ꢈꢉꢈꢅ ꢝꢂꢅꢁꢄꢏ ꢃꢄꢁꢂꢃ  
ꢛꢏꢄꢉꢈ ꢛꢏꢄꢉꢜꢜ ꢛꢑꢄꢉꢈ ꢛꢑꢄꢉꢚꢚ  
ꢛꢙꢄꢉꢈ ꢛꢙꢄꢛꢜꢜ ꢛꢣꢄꢉꢈ ꢛꢣꢄꢉꢚꢚ  
ꢡ ꢂꢁ«  
ꢈꢉꢈꢅ  
ª
CYCLE COUNTER STOP VALUE  
This parameter selects the source from which a count is added to or  
subtracted from the Cycle Counter. Select ꢈꢉꢈꢅ if the Cycle Counter is not  
being used, which will exit the module and bypass the remaining parameters.  
When ꢝꢂꢅꢁꢄꢏ is selected, a count is generated each time the User 1 Input is  
activated. When selected as the count source, User Input 1 can still be  
programmed to perform a User Function described in Module 2, if desired. In  
this case, the Cycle Counter would be counting the number of times the  
particular User Function occurred.  
The Timer Reset (ꢃꢄꢁꢂꢃ) selection generates a count when either a manual  
or automatic reset occurs. (See Module 6 for programming Automatic Resets.)  
The Output ON/OFF selections generate a count when the chosen output  
either activates or deactivates. These selections only appear when a Setpoint  
Card is installed. O3 and O4 selections only appear for Quad Setpoint cards.  
ꢩꢡꢂꢃꢉ«  
ꢈꢉ  
ꢈꢉ ꢟꢅꢂ  
ª
The Cycle Counter stops counting when this value is reached, regardless of  
the operation of the Timer. Selecting ꢟꢅꢂ will display the ꢋꢓꢊꢝꢅ sub-menu where  
the Stop Value can be set or changed. The Stop condition is cleared when a  
Cycle Counter Reset occurs. Select ꢈꢉ if a Stop Value is not used.  
ꢩꢋꢤꢊꢝꢅ  
«
ꢛꢛꢛꢛꢛꢛ  
ꢛꢛꢛꢛꢛꢛ to ꢘꢘꢘꢘꢘꢘ  
CYCLE COUNTER RESET AT POWER-UP  
CYCLE COUNTER COUNTING DIRECTION  
ꢡ ꢆꢄꢝ«  
ª
ꢡ ꢀꢞ«  
ꢝꢆ  
ꢈꢉ ꢟꢅꢂ  
ꢝꢆ ꢀꢈ  
ª
ꢈꢉ  
The Cycle Counter can be programmed to Reset at each meter power-up.  
Counting direction can be reversed through a User Input. (See Module 2.)  
6.5 MODULE 5 - TIMER OPERATING MODES (ꢒꢄꢉꢆꢅꢁ)  
This module can only be accessed if a Setpoint Card is installed.  
PARAMETER MENU  
* Only the value parameters which apply to the selected mode will appear.  
PREDEFINED TIMER OPERATING MODE  
The Predefined modes control the activation and deactivation of Output 1, in  
relation to Start and Reset signals applied to the Timer inputs. (See timing  
diagrams which follow.) When a selection other than ꢈꢉ is chosen, the  
parameters for Setpoint 1 (ꢂꢆꢄꢏ) in Module 6 are automatically configured to  
implement the selected operating mode. For some modes, parameters in  
Modules 1 and 2 are also automatically configured to properly implement the  
predefined mode. Refer to the chart shown with the timing diagrams for the  
specific parameters loaded for each predefined mode. Also, note the specific  
external wiring or plug jumper settings required for some modes.  
ON-dLY  
OF-dLY  
rEPEAt  
dLYINt  
INt-L  
- On-Delay Timing  
ꢃ ꢉꢆꢅ«  
ª
- Off-Delay Timing  
ꢈꢉ  
- Repeat Cycle Timing  
- On-Delay/Interval Timing  
- Interval Timing (Level Triggered)  
- Interval Timing (Edge Triggered)  
INt-E  
This parameter is used to select Predefined Operating Modes for the Timer.  
These modes cover a variety of timing applications frequently encountered in  
industrial control processes. When using a Predefined mode, the operator needs  
only to set the actual Setpoint On/Off or Time-out values for the particular  
application. However, each programming parameter will still be accessible, in  
order to make modifications to the predefined settings if desired.  
The Setpoint On/Off or Time-out values for the specific application should  
be entered directly in Module 5 after selecting the operating mode. Only the  
value parameters which apply to the selected mode are displayed. These values  
can also be entered through Module 6, Setpoint (Alarm) Parameters, if desired.  
Select ꢈꢉ if not using a Predefined Operating Mode, in which case Setpoint  
parameters must all be individually programmed for the particular application.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Timing Diagrams for Predefined Timer Operating Modes  
NOTE: Input A is shown as a Sourcing input (active high). If a Sinking input (active low) is used, the logic levels for Input A would be inverted.  
On-Delay / Interval Timing  
On-Delay Timing  
Input A  
ꢉꢈꢄꢀꢊꢟ  
ꢀꢊꢪꢌꢈꢃ  
Input A  
T
T
T1  
T2  
T
Output 1  
Output 1  
Off-Delay Timing  
Input A  
Interval Timing (Level triggered)  
ꢌꢈꢃꢄꢊ  
ꢉꢜꢄꢀꢊꢟ  
Input A  
T
T
T
T
Output 1  
Output 1  
The input signal must be wired to both the Input A and  
User Input 1 terminals. The Timer Input plug jumper and  
the User Input plug jumper must be set to opposite  
positions (one SNK, one SRC) and the Input signal must  
be a current sinking type (i.e. pulls input to common).  
The input signal must be wired to both the Input A and  
User Input 1 terminals. The Timer Input plug jumper and  
the User Input plug jumper must both be set to the  
same position (either both SNK or both SRC).  
Interval Timing (Edge triggered)  
Repeat Cycle Timing  
ꢁꢅꢆꢅꢓꢃ  
ꢌꢈꢃꢄꢅ  
Input A  
Input A  
T1  
T1  
T
T2  
T
T
Output 1  
Output 1  
Parameter Settings for Predefined Timer Operating Modes  
MODULE 1 - Timer Input Parameters (ꢏꢄꢌꢈꢆ)  
DISPLAY  
PARAMETER  
ON-dLY  
OF-dLY  
rEPEAt  
dLYINt  
INt-L  
INt-E  
Timer Input Operation  
INP OP  
EdrS-2 EdrS-2 EdrS-2 EdrS-2 LEVrSt EdrS-2  
MODULE 2 - User Input Parameters (ꢑꢄꢚꢈꢡ)  
DISPLAY  
USEr-1  
rSt  
PARAMETER  
ON-dLY  
OF-dLY  
rSt-L  
NO  
rEPEAt  
dLYINt  
INt-L  
INt-E  
User Input 1  
N/A  
N/A  
N/A  
N/A  
OrSt-E  
(SP1-YES)  
NO  
Reset Key  
NO  
NO  
NO  
NO  
MODULE 6 - Setpoint Parameters (ꢫꢄꢂꢆꢃ)  
DISPLAY  
PARAMETER  
ON-dLY  
OF-dLY  
rEPEAt  
dLYINt  
INt-L  
INt-E  
Setpoint Select  
SPSEL  
ASN-1  
ACt-1  
OUt-1  
ON-1  
SP-1  
t-dSP  
LAtCH  
NOr  
VALUE  
T*  
SP-1  
t-dSP  
SP-1  
t-dSP  
ON-OFF ON-OFF  
SP-1  
t-dSP  
t-OUt ON-OFF  
NOr NOr  
SP-1  
t-dSP  
SP-1  
t-dSP  
t-OUt  
NOr  
Setpoint Assignment  
Setpoint Action  
Output Logic  
NOr  
t-Strt  
N/A  
NOr  
VALUE  
T1*  
Setpoint On  
VALUE t-Strt t-Strt  
Setpoint On Value  
Setpoint Off  
T1*  
N/A  
N/A  
T2*  
N/A  
N/A  
N/A  
N/A  
T*  
SP-1  
N/A  
OFf-1  
SPOf-1  
tOUt-1  
tstP-1  
AUtO-1  
OrSd-1  
Lit-1  
P-UP-1  
VALUE  
T*  
VALUE  
T2*  
VALUE  
T*  
Setpoint Off Value  
Time-out Value  
N/A  
N/A  
N/A  
N/A  
N/A  
Timer Stop  
NO  
NO  
NO  
NOr  
OFF  
0-OFF  
NO  
NO  
NOr  
OFF  
NO  
0-OFF  
NO  
NOr  
OFF  
0-OFF  
NO  
NO  
NOr  
OFF  
0-OFF  
NO  
NO  
NOr  
OFF  
0-OFF  
NO  
NO  
NOr  
OFF  
Timer/Counter Auto Reset  
Output Reset w/display Reset  
Setpoint Annunciator  
Power-up State  
* Refer to timing diagrams. These parameters are the actual Setpoint On/Off or Time-Out values set by the user for the specific application.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.6 MODULE 6 - SETPOINT (ALARM) PARAMETERS (ꢫꢄꢂꢆꢃ)  
This module can only be accessed if a Setpoint Card is installed.  
PARAMETER MENU  
= Setpoint Number 1 thru 4  
Module 6 is the programming module for the Setpoint (Alarm) Output  
Parameters. This programming module can only be accessed if a Setpoint card  
is installed. Depending on the card installed, there will be two or four Setpoint  
outputs available. The Setpoint Assignment and Setpoint Action parameters  
determine the applicable Setpoint features, and dictate which subsequent  
parameters will appear for the Setpoint being programmed.  
OUTPUT LOGIC  
ꢉꢝꢃꢄ«  
ꢈꢉꢁ  
ꢈꢉꢁ  
ꢁꢅꢋ  
ª
Normal Output Logic (ꢈꢉꢁ) turns the output “on” when activated and “off”  
when deactivated. Reverse Output Logic (ꢁꢅꢋ) turns the output “off” when  
activated and “on” when deactivated.  
This section of the bulletin replaces the bulletin shipped with the Dual and  
Quad Setpoint plug-in cards. Discard the separate bulletin when using Setpoint  
plug-in cards with the PTC901 and PTC900.  
SETPOINT ON  
ꢋꢓꢊꢝꢅ  
ꢛꢏꢄꢉꢚꢚ  
ꢛꢙꢄꢉꢚꢚ  
ꢃꢄꢂꢃꢁꢃ ꢃꢄꢂꢃꢉꢆ  
ꢛꢑꢄꢛꢈ ꢛꢑꢄꢉꢚꢚ  
ꢛꢣꢄꢉꢈ ꢛꢣꢄꢉꢚꢚ  
ꢉꢈꢄ«  
ª ꢬꢋꢤꢊꢝꢅ  
ꢛꢏꢄꢉꢈ  
ꢛꢙꢄꢛꢈ  
SETPOINT SELECT  
This parameter determines when the Setpoint output will activate. Output  
activation can occur at a specific Setpoint Value (ꢋꢓꢊꢝꢅ) or can be triggered by  
various “events”, as shown in the parameter list. Such events include the Timer  
starting (ꢃꢄꢂꢃꢁꢃ) or stopping (ꢃꢄꢂꢃꢉꢆ), or by the action (event) that causes  
another Setpoint output to turn On or Off. When programmed for an event, the  
Setpoint must not be used as the Setpoint On event for another Setpoint.  
Selecting ꢋꢓꢊꢝdisplays a sub-menu where the Setpoint value is entered. The  
Setpoint value is based on the meter display to which the Setpoint is assigned  
(ꢓꢂꢈꢄꢥ). When assigned to the Timer or Cycle Counter, the Setpoint value is  
entered in the same format as the assigned display. When assigned to the Real-  
Time Clock Date Display (ꢁꢃꢡꢄꢀ), the date value is entered in month.day.year  
format (ꢥꢥꢗꢀꢀꢗꢪꢪ). When assigned to the Real-Time Clock Time Display (ꢁꢃꢡꢄꢃ),  
the Setpoint value is always entered in ꢐꢐꢄꢈꢈꢆ format (Hours-Minutes with  
AM/PM selection). In Setpoint One-shot mode (See Daily On Occurrence), the  
One-shot Setpoint is enabled (armed) by scrolling the AM/PM digit until the 2nd  
digit decimal point is lit.  
ꢂꢆꢂꢅ«  
ꢈꢉ  
ꢂꢆꢄꢙ  
ꢂꢆꢄꢏ  
ꢂꢆꢄꢣ  
ꢂꢆꢄꢑ  
ª
ꢈꢉ  
Select the Setpoint (alarm) output to be programmed. This provides access to  
the parameters for that particular Setpoint. The “” in the following parameter  
displays, reflects the chosen Setpoint number (1 thru 4). After the chosen  
Setpoint is programmed, the display returns to ꢂꢆꢂꢅꢊ ꢈꢉ. Select the next  
Setpoint to be programmed and continue this sequence for each Setpoint. Select  
ꢈꢉ to exit the module. ꢂꢆꢄꢙ and ꢂꢆꢄꢣ apply to Quad Setpoint cards only.  
SETPOINT ASSIGNMENT  
ꢓꢂꢈꢄ«  
ꢈꢉꢈꢅ  
ꢈꢉꢈꢅ ꢃꢄꢀꢂꢆ ꢡꢄꢀꢂꢆ ꢁꢃꢡꢄꢀ ꢁꢃꢡꢄꢃ  
ª
ꢂꢆꢄꢥ  
«
ꢛꢛꢛꢛꢛꢛ  
ꢛꢛꢛꢛꢛꢛ to ꢘꢘꢘꢘꢘꢘ  
Select the meter display to which the Setpoint is assigned: Timer (ꢃꢄꢀꢂꢆ),  
Cycle Counter (ꢡꢄꢀꢂꢆ), Real-Time Clock Date display (ꢁꢃꢡꢄꢀ) or Real-Time  
Clock Time display (ꢁꢃꢡꢄꢃ). (The ꢁꢃꢡꢄꢀ and ꢁꢃꢡꢄꢃ selections only appear if a  
Real-Time Clock option card is installed.)  
ª
SETPOINT OFF  
ꢋꢓꢊꢝꢅ ꢃꢄꢂꢃꢁꢃ ꢃꢄꢂꢃꢉꢆ  
ꢛꢏꢄꢉꢈ ꢛꢏꢄꢉꢚꢚ ꢛꢑꢄꢛꢈ ꢛꢑꢄꢉꢚꢚ  
ꢛꢙꢄꢛꢈ ꢛꢙꢄꢉꢚꢚ ꢛꢣꢄꢉꢈ ꢛꢣꢄꢉꢚꢚ  
By selecting ꢈꢉꢈꢅ, the Setpoint is not assigned to a specific display.  
However, the output can still be activated (set) and deactivated (reset) by  
various “events”. Such events include the Timer starting or stopping, or another  
Setpoint output turning On or Off. The output can also be set and reset through  
a User Input function or through serial communications.  
ꢉꢚꢜꢄ«  
ª ꢬꢋꢤꢊꢝꢅ  
The Setpoint Off parameter only appears when the Setpoint Action (ꢓꢡꢃꢄꢥ)  
is programmed for On-Off Output mode (ꢉꢈꢄꢉꢚꢚ). In this mode, this parameter  
determines when the Setpoint output will deactivate. Output deactivation can  
occur at a specific Setpoint Off Value (ꢋꢓꢊꢝꢅ) or can be triggered by various  
“events”, as shown in the parameter list. Such events include the Timer starting  
(ꢃꢄꢂꢃꢁꢃ) or stopping (ꢃꢄꢂꢃꢉꢆ), or by the action (event) that causes another  
Setpoint output to turn On or Off. When programmed for an event, the Setpoint  
must not be used as the Setpoint Off event for another Setpoint.  
Selecting ꢋꢓꢊꢝꢅ will display a sub-menu where the Setpoint Off value is  
entered. The Setpoint Off value is based on the meter display to which the  
Setpoint is assigned (ꢓꢂꢈꢄꢥ). When assigned to the Timer or Cycle Counter, the  
value is entered in the same format as the assigned display. When assigned to  
the Real-Time Clock Date Display (ꢁꢃꢡꢄꢀ), the date value is entered in  
month.day.year format (ꢥꢥꢗꢀꢀꢗꢪꢪ). When assigned to the Real-Time Clock Time  
Display (ꢁꢃꢡꢄꢃ), the value is always entered in ꢐꢐꢄꢈꢈꢆ format (Hours-Minutes  
with AM/PM selection).  
SETPOINT ACTION  
ꢓꢡꢃꢄ«  
ꢊꢓꢃꢡꢐ  
ꢊꢓꢃꢡꢐ ꢃꢄꢉꢝꢃ ꢉꢈꢄꢉꢚꢚ  
ª
This parameter determines the mode for output deactivation as shown below.  
Output activation is controlled by the SETPOINT ON parameter setting.  
DISPLAY  
DESCRIPTION  
Latched Output Mode  
Timed Output Mode  
On-Off Output Mode  
OUTPUT DEACTIVATES  
At Reset (Manual or Automatic)  
After “Time-Out Value” Elapses  
Based on “Setpoint Off” Setting  
LAtCH  
t-OUt  
ON-OFF  
ꢂꢆꢉꢜꢄꢥ  
«
ꢛꢛꢛꢏꢛꢛ  
The ꢃꢄꢉꢝand ꢉꢈꢄꢉꢜselections are not available when Setpoint is assigned  
to ꢁꢃꢡꢄꢀ.  
ꢛꢛꢛꢛꢛꢛ to ꢘꢘꢘꢘꢘꢘ  
ª
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TIME-OUT VALUE  
TIMER STOP  
ꢃꢉꢝꢃꢄ«  
ꢛꢛꢗꢛꢏꢗꢛꢛ  
ꢃꢂꢃꢆꢄ«  
ꢈꢉ  
ꢛꢛꢗꢛꢛꢗꢛꢑ to ꢘꢘꢗꢒꢘꢗꢘꢘ  
ꢈꢉ  
ꢉꢄꢉꢈ  
ꢉꢄꢉꢚꢚ  
ª
ª
The Time-Out Value only appears when the Setpoint Action (ꢓꢡꢃꢄꢥ) is  
programmed for Timed Output mode (ꢃꢄꢉꢝꢃ). In this mode, the Time-Out Value  
is the Setpoint Output time duration, from activation to deactivation. This value  
is always entered in minutes, seconds, and hundredths of seconds format. The  
maximum Time-Out Value is 99 minutes 59.99 seconds.  
Timer stops when the Setpoint output activates (ꢉꢄꢉꢈ) or deactivates (ꢉꢄꢉꢚꢚ).  
Select ꢈꢉ if the output should not affect the Timer Run/Stop status.  
Stopping the Timer as a result of this parameter does not constitute a ꢃꢄꢂꢃꢉꢆ  
condition (event) for the Setpoint On or Setpoint Off parameters.  
TIMER/COUNTER AUTO RESET  
PTC901: DAILY ON OCCURRENCE  
ꢓꢝꢃꢉꢄ«  
ꢈꢉ  
ꢈꢉ  
ꢉꢄꢉꢈ ꢉꢄꢉꢚꢚ  
ꢀ ꢉꢈꢄ«  
ꢈꢉ  
ꢈꢉ  
ꢟꢅꢂ  
ª
ª
When the Setpoint output activates (ꢉꢄꢉꢈ) or deactivates (ꢉꢄꢉꢚꢚ), the meter  
automatically resets the Setpoint Assignment display (ꢓꢂꢈꢄꢥ). Select ꢈꢉ if the  
Setpoint output should not cause the assigned display to reset. Does not apply  
to manual activations or deactivations by user input, function key, or serial  
communications.  
This parameter only appears when the Setpoint is assigned (ꢓꢂꢈꢄꢥ) to the  
Real-Time Clock Time display (ꢁꢃꢡꢄꢃ). This parameter determines the days of  
the week when the Setpoint output will activate.  
Selecting ꢪꢅꢂ displays a sublist for choosing the days of the week. On all  
days entered as ꢪꢅꢂ in the sublist, the output will activate. On all days entered  
as ꢈꢉ, the output will not activate. The output activation is repetitive, and will  
occur every week on the chosen day(s).  
OUTPUT RESET WITH DISPLAY RESET  
DISPLAY  
DESCRIPTION  
Sunday  
FACTORY  
ꢂꢭꢥ  
ꢠꢮꢇꢥ  
ꢃꢭꢅ  
ꢯꢅꢀ  
ꢃꢦꢭ  
ꢚꢁꢞ  
ꢈꢉ  
ꢉꢁꢂꢀꢄ«  
ꢈꢉ  
ꢈꢉ  
ꢟꢅꢂ  
Monday  
ꢟꢅꢂ  
ꢟꢅꢂ  
ꢟꢅꢂ  
ꢟꢅꢂ  
ꢟꢅꢂ  
ꢈꢉ  
ª
Tuesday  
Wednesday  
Thursday  
Friday  
When ꢟꢅꢂ is selected, the Setpoint output will reset when the Setpoint  
Assignment display (ꢓꢂꢈꢄꢥ) resets. Select ꢈꢉ if the Setpoint output should not  
reset when the assigned display resets.  
Saturday  
ꢂꢓꢃ  
Setpoint One-Shot Mode  
SETPOINT ANNUNCIATOR  
If all days are set to ꢈꢉ, the Setpoint will operate in “One-shot” mode. When  
a One-shot setpoint is enabled (armed), the setpoint output will activate at the  
set time and disable itself from activating again. To enable or re-enable a one-  
shot alarm, go to the Setpoint value entry display and press the Up or Dn key  
repeatedly while the AM/PM digit is selected (flashing). When the 2nd digit  
decimal point is lit, the Setpoint is enabled. The Setpoint enable status is saved  
at power-down. The enable state of the Setpoint is not affected or changed when  
the Parameter List is exchanged.  
The setpoint will turn off (de-activate) as programmed per the Setpoint  
Action selected. If ꢉꢈꢄꢉꢜꢜ mode is selected, program all the Daily Off days to  
ꢟꢅꢖ to have the Setpoint turn off at the next Daily Off Occurrence. The One-  
shot status can also be viewed or set from the Setpoint Off value entry display.  
ꢊꢞꢃꢄ«  
ꢈꢉꢁ  
ꢈꢉꢁ  
ꢁꢅꢝ ꢜꢊꢓꢂꢐ  
ꢉꢚꢚ  
ª
This parameter controls the illumination of the LED annunciator for the  
corresponding Setpoint output (ꢂꢆꢥ) as follows:  
Annunciator displayed when output is “on” (activated)  
Annunciator displayed when output is “off” (deactivated)  
Annunciator and display flashes when output is “on” (activated)  
Annunciator disabled  
Normal (ꢈꢉꢁ)  
Reverse (ꢁꢅꢋ)  
Flash (ꢚꢊꢓꢂꢐ)  
Off (ꢉꢚꢚ)  
PTC901: DAILY OFF OCCURRENCE  
SETPOINT POWER-UP STATE  
ꢀꢉꢜꢜꢄ«  
ꢈꢉ  
ꢆꢄꢝꢆꢄ«  
ª
ꢈꢉ  
ꢟꢅꢂ  
ꢉꢚꢚ  
ꢉꢈ  
ꢂꢓꢋꢅ  
ª
ꢉꢚꢚ  
Determines the on/off state of the Setpoint output at power-up. Regardless of  
This parameter only appears when the Setpoint is assigned (ꢓꢂꢈꢄꢥ) to the  
Real-Time Clock Time display (ꢁꢃꢡꢄꢃ) and when the Setpoint Action (ꢓꢡꢃꢄꢥ)  
is programmed for On-Off Output mode (ꢉꢈꢄꢉꢚꢚ). In this mode, this parameter  
determines the days of the week when the Setpoint output will deactivate.  
Selecting ꢪꢅꢂ displays a sublist for choosing the days of the week. On all  
days entered as ꢪꢅin the sublist, the output will deactivate. On all days entered  
as ꢈꢉ, the output will not deactivate. The output deactivation is repetitive, and  
will occur every week on the chosen day(s).  
output logic setting (normal or reverse).  
ꢉꢚꢚ Deactivates the Setpoint output at power-up  
ꢉꢈ  
Activates the Setpoint output at power-up  
ꢂꢓꢋꢅ Restores the output to the state it was in prior to power-down  
DISPLAY  
DESCRIPTION  
Sunday  
FACTORY  
ꢂꢭꢥ  
ꢠꢮꢇꢥ  
ꢃꢭꢅ  
ꢯꢅꢀ  
ꢃꢦꢭ  
ꢚꢁꢞ  
ꢈꢉ  
Monday  
ꢟꢅꢂ  
ꢟꢅꢂ  
ꢟꢅꢂ  
ꢟꢅꢂ  
ꢟꢅꢂ  
ꢈꢉ  
Tuesday  
Wednesday  
Thursday  
Friday  
Saturday  
ꢂꢓꢃ  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.7 MODULE 7 - SERIAL COMMUNICATIONS PARAMETERS (ꢰꢄꢒꢁꢊ)  
This module can only be accessed if a Serial Communications Card is installed.  
PARAMETER MENU  
* Only appears if the Real-Time Clock Card is installed.  
Module 7 is the programming module for the Serial Communications  
Parameters. These parameters are used to match the serial settings of the meter  
with those of the host computer or other serial device, such as a terminal or  
printer. This programming module can only be accessed if an RS232 or RS485  
Serial Communications card is installed.  
This section also includes an explanation of the commands and formatting  
required for communicating with the meter. In order to establish serial  
communications, the user must have host software that can send and receive  
ASCII characters. For serial hardware and wiring details, refer to section 4.5  
Serial Communication Wiring.  
ABBREVIATED PRINTING  
ꢓꢢꢢ«  
ꢈꢉ  
ꢈꢉ  
ꢟꢅꢂ  
ª
This parameter determines the formatting of data transmitted from the meter  
in response to a Transmit Value (T) command or a Block Print Request (P)  
command. Select ꢈꢉ for a Full print transmission, which consists of the meter  
address, mnemonics, and parameter data. Select ꢪꢅꢂ for abbreviated print  
transmissions, consisting of the parameter data only. This setting affects all the  
parameters selected in the PRINT OPTIONS. (Note: If the meter address is 00,  
the address will not be sent during a Full transmission.)  
This section of the PTC900/PTC901 bulletin replaces the bulletin shipped  
with the RS232 and RS485 serial communications plug-in cards. Discard the  
separate bulletin when using those serial plug-in cards with the  
PTC900/PTC901. Also, this section does NOT apply to the Modbus  
communication cards. For details on the operation of the Fieldbus cards, refer  
to the bulletin shipped with each card.  
PTC901: REAL-TIME CLOCK PRINT FORMATTING  
ꢁꢃꢡ ꢚ«  
ꢟꢅꢂ  
ꢈꢉ  
ꢟꢅꢂ  
BAUD RATE  
ª
ꢢꢓꢝ«  
ꢘꢫꢛꢛ  
This parameter determines the formatting of the Real-Time Clock (RTC)  
values transmitted from the meter in response to a Transmit Value (T) command  
or a Block Print Request (P) command. This parameter appears only when a  
Real-Time Clock plug-in option card is installed.  
When ꢟꢅꢂ is selected, RTC values are formatted as per the RTC Time and  
Date Display Formats programmed in Module 8. The Day of Week value is sent  
as a character string.  
ꢙꢛꢛ  
ꢣꢱꢛꢛ ꢘꢫꢛꢛ ꢏꢘꢑꢛꢛ  
ꢫꢛꢛ  
ꢏꢑꢛꢛ  
ꢑꢣꢛꢛ  
ª
Set the baud rate to match the other serial communications equipment on the  
serial link. Normally, the baud rate is set to the highest value at which all the  
serial equipment are capable of transmitting and receiving data.  
When ꢈꢉ is selected, the meter sends the RTC values as numeric data only.  
RTC Time/Date units are separated by a “.”. The Day is sent as a single number  
as shown below.  
DATA BITS  
ꢀꢓꢃ«  
TIME - Hours (24-Hr. format), Minutes, Seconds (HHMMSS)  
DATE - Month, Day, Year (mmddyy)  
DAY - 1 = Sunday thru 7 = Saturday  
ª
Select either 7- or 8-bit data word lengths. Set the word length to match the  
other serial communications equipment on the serial link.  
PRINT OPTIONS  
PARITY BIT  
ꢉꢆ«  
ꢆꢓ«  
ꢉꢀꢀ  
ꢈꢉ  
ꢉꢀꢀ ꢅꢋꢅꢈ  
ª
ꢈꢉ  
ª
This parameter selects the meter values transmitted in response to a Print  
Request. A Print Request is sometimes referred to as a block print because more  
than one parameter can be sent to a printer or computer as a block.  
This parameter only appears when the Data Bits parameter is set to a 7-bit  
data word length. Set the parity bit to match that of the other serial  
communications equipment on the serial link. The meter ignores parity when  
receiving data and sets the parity bit for outgoing data. If parity is set to ꢈꢉ, an  
additional stop bit is used to force the frame size to 10 bits.  
Selecting ꢪꢅꢂ displays a sublist for choosing the meter parameters to appear  
in the block print. All parameters entered as ꢪꢅꢂ in the sublist will be  
transmitted during a block print. Parameters entered as ꢈꢉ will not be sent.  
DISPLAY  
t-dsp  
C-dSP  
rtC-d  
rtC-t  
SPNt  
PARAMETER  
FACTORY MNEMONIC  
Timer  
TMR  
yES  
NO  
NO  
NO  
NO  
NO  
NO  
METER ADDRESS  
Cycle Counter  
CNT  
ꢓꢀꢀ«  
ꢛꢛ  
RTC Date*  
DAT  
ꢛꢛ to ꢘꢘ  
RTC Time*  
TIM  
ª
Setpoint Values*  
Setpoint Off/Time-Out Values*  
Timer/Cnt Start & Stop Values  
SP1 SP2 SP3 SP4  
SO1 SO2 SO3 SO4  
TST TSP CST CSP  
Enter the serial meter (node) address. With a single meter, an address is not  
needed and a value of zero can be used. With multiple meters (RS485  
applications), a unique 2 digit address number must be assigned to each meter.  
Addresses 98 and 99 are reserved to configure a unit as a serial real-time  
clock master. See Serial Real-time Clock Master Adressing.  
SpNtOF  
StrStp  
* These values are plug-in card dependent.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Command String Examples:  
SENDING SERIAL COMMANDS AND DATA  
When sending commands to the meter, a string containing at least one  
command character must be constructed. A command string consists of a  
command character, a value identifier, numerical data (if writing data to the  
meter) followed by the command terminator character * or $.  
1. Address = 17, Write 350 to Setpoint 1  
String: N17VE350$  
2. Address = 5, Cycle Counter value, response time of 50 to 100 msec. min.  
String: N05TB*  
Command Chart  
3. Address = 0, Reset Timer value  
String: RA*  
COMMAND DESCRIPTION  
NOTES  
Node (Meter) Address Address a specific meter. Must be followed by  
N
T
Transmitting Data To the Meter  
Specifier  
node address. Not required when address = 00.  
Numeric data sent to the meter must be limited to Transmit Details listed in the  
Register Identification Chart. Leading zeros are ignored. The meter ignores any  
decimal point and conforms the number to the scaled resolution. (ie. The meter’s  
scaled decimal point position is set for 0.0 and 25 is written to a register. The value  
of the register is now 2.5. In this case, write a value of 250 to equal 25.0).  
Read a register from the meter. Must be  
followed by register ID character.  
Transmit Value (read)  
Write to register of the meter. Must be followed  
by register ID character and numeric data.  
V
R
P
Value change (write)  
Reset  
Reset a register or output. Must be followed  
by register ID character  
For RTC Time [C] and Date [D] Value:  
Block Print Request Initiates a block print output. Registers are  
(read) defined in programming.  
Time - 24 Hours, Minutes, Seconds (HHMMSS)  
Ex: 083000 = 8:30 AM, 144500 = 2:45 PM  
Command String Construction  
Date - Month, Day, Year (mmddyy)  
Ex: 123101 = December 31, 2001  
The command string must be constructed in a specific sequence. The meter  
does not respond with an error message to invalid commands. The following  
procedure details construction of a command string:  
Day - 1 = Sunday through 7 = Saturday  
EX: 3 = Tuesday  
1. The first characters consist of the Node Address Specifier (N) followed by a  
1 or 2 character address number. The address number of the meter is  
programmable. If the node address is 0, this command and the node address  
itself may be omitted. The address suffix , “?” is the global broadcast address  
specifier. A command string that is sent with N? prefix will be accepted by  
all PAXCKs on the RS485 network (software code version 2.3 or greater).  
This is useful for setting all meters to the current time, date or day that may  
have unique meter addresses on a bus. It is important not to send (P)rint or  
(T)ransmit commands using N? prefix, as it will result in multiple meters  
responding at the same time. This is the only command that may be used in  
conjunction with other commands.  
Notes:  
1. Since the meter does not issue a reply to value change commands, follow  
with a transmit value command for readback verification.  
2. The date and day must be set separately.  
Transmitting Data From the Meter  
Data is transmitted from the meter in response to either a transmit command  
(T), a print block command (P) or User Function print request. The response  
from the meter is either a full field transmission or an abbreviated transmission.  
The meter response is established in Module 7.  
2. After the optional address specifier, the next character is the command  
character.  
Full Transmission (ꢓꢢꢢꢁ ꢈꢉ)  
=
3. The next character is the Register ID. This identifies the register that the  
command affects. The P command does not require a Register ID character.  
It prints according to the selections made in print the options. If constructing  
a value change command (writing data), the numeric data is sent next.  
4. All command strings must be terminated with the string termination  
characters * or $. The meter does not begin processing the command string  
until this character is received. See Timing Diagram figure for differences  
between terminating characters.  
BYTE DESCRIPTION  
1, 2 2 byte Node (Meter) Address field [00-99]  
3
<SP> (Space)  
4-6  
3 byte Register Mnemonic field  
7-18 12 byte numeric data field: 6 bytes for number, up to 3 for decimal points.  
19  
20  
21  
22  
23  
<CR> (Carriage return)  
<LF> (Line feed)  
<SP> (Space)✰  
<CR> (Carriage return)✰  
<LF> (Line feed)✰  
Note: On a change value command (V), if the command string is terminated  
with the * character, all values are stored in E2PROM memory. Values are  
not stored if the $ terminator is used.  
These characters only appear in the last line of a block print.  
Register Identification Chart  
REGISTER  
COMMAND 2 TRANSMIT DETAILS 3  
ID  
VALUE DESCRIPTION  
NAME 1  
TMR  
CNT  
TIM  
The first two characters transmitted are the unit address. If the address  
assigned is 0, two spaces are substituted. A space follows the unit address field.  
The next three characters are the register mnemonic.  
The numeric data is transmitted next. The numeric field is 12 characters long  
(decimal points are loaded depending on timer range selected). The data is right-  
aligned with leading spaces for any unfilled positions.  
The end of the response string is terminated with <CR> and <LF>. When a  
block print is finished, an extra <SP>, <CR>, and <LF> are used to provide  
separation between the transmissions.  
A
B
C
D
E
F
Timer Value  
T, V, R  
T, V, R  
T, V  
6 digit  
Cycle Counter Value  
RTC Time Value  
RTC Date Value  
Setpoint 1  
6 digit  
6 digit  
DAT  
SP1  
SP2  
SP3  
SP4  
SO1  
SO2  
SO3  
SO4  
TST  
CST  
TSP  
CSP  
MMR  
DAY  
SOR  
T, V  
6 digit  
T, V, R  
T, V, R  
T, V, R  
T, V, R  
T, V  
6 digit  
Setpoint 2  
6 digit  
G
H
I
Setpoint 3  
6 digit  
Setpoint 4  
6 digit  
Setpoint 1 Off Value  
Setpoint 2 Off Value  
Setpoint 3 Off Value  
Setpoint 4 Off Value  
Timer Start Value  
Cycle Counter Start Value  
Timer Stop Value  
Cycle Counter Stop Value  
Auto/Man Register  
Day of Week Value  
Setpoint Register  
6 digit  
J
T, V  
5 digit  
K
L
T, V  
6 digit  
T, V  
6 digit  
M
O
Q
S
U
W
X
T, V  
6 digit  
T, V  
6 digit  
T, V  
6 digit  
T, V  
6 digit  
T, V  
0 - auto, 1 - manual  
1 = Sun....7 = Sat  
0 - not active, 1 - active  
T, V  
T, V  
1. Register Names are also used as Register Mnemonics during full transmission.  
2. The registers associated with the P command are set up in Print Options (Module 7).  
3. Unless otherwise specified, the Transmit Details apply to both T and V  
Commands.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Auto/Manual Mode Register (MMR) ID: U  
Abbreviated Transmission (ꢓꢢꢢꢁ ꢟꢅꢂ)  
=
This register sets the controlling mode for the outputs. In Auto Mode (0) the  
meter controls the setpoint output. In Manual Mode (1) the outputs are defined  
by the registers SOR. When transferring from auto mode to manual mode, the  
meter holds the last output value (until the register is changed by a write). Each  
output may be independently changed to auto or manual. In a write command  
string (VU), any character besides 0 or 1 in a field will not change the  
corresponding output mode.  
BYTE DESCRIPTION  
1-12 12 byte data field, 6 bytes for number, up to 3 bytes for decimal points.  
13  
14  
15  
16  
17  
<CR> (Carriage return)  
<LF> (Line feed)  
<SP> (Space)✰  
<CR> (Carriage return)✰  
<LF> (Line feed)✰  
U abcd  
d = SP4  
c = SP3  
b = SP2  
a = SP1  
These characters only appear in the last line of a block print.  
The abbreviated response suppresses the address and register mnemonics,  
leaving only the numeric part of the response.  
Note: Transmissions are formatted to match the way the parameter is displayed.  
This includes setpoints.  
Example: VU0011 places SP3 and SP4 in manual.  
Example: SP1 assigned to RTC. RTC format = 12:00 P.  
SP1 printout = 12:00 P.  
Setpoint Output Register (SOR) ID: X  
This register is used to view or change the states of the setpoint outputs.  
Reading from this register (TX) will show the present state of all the setpoint  
outputs. A “0” in the setpoint location means the output is inactive and a “1”  
means the output is active. The output logic parameter in Module 6 will affect  
the active logic state.  
Meter Response Examples:  
1. Address = 17, full field response, Cycle Counter = 875  
17 CNT  
2. Address = 0, full field response, Setpoint 2 = 250.5  
SP2 250.5<CR><LF>  
875 <CR><LF>  
X abcd  
d = SP4  
c = SP3  
b = SP2  
a = SP1  
3. Address = 0, abbreviated response, Setpoint 2 = 250, last line of block print  
250<CR><LF><SP><CR><LF>  
In Automatic Mode, the meter controls the setpoint output state. In Manual  
Mode, writing to this register (VX) will change the output state. Sending any  
character besides 0 or 1 in a field or if the corresponding output was not first in  
manual mode, the corresponding output value will not change.  
Example: VX10* will result in output 1 active and output 2 inactive.  
COMMAND RESPONSE TIME  
SERIAL TIMING  
The meter can only receive data or transmit data at any one time (half-duplex  
operation). During RS232 transmissions, the meter ignores commands while  
transmitting data, but instead uses RXD as a busy signal. When sending  
commands and data to the meter, a delay must be imposed before sending  
another command. This allows enough time for the meter to process the  
command and prepare for the next command.  
PROCESS TIME (t2)  
2-50 msec.  
COMMAND  
COMMENT  
Reset  
R
V
T
Write  
100-200 msec.  
2-50 msec. for $  
50-100 msec. for *  
2-50 msec. for $  
50-100 msec. for *  
Transmit  
Refer to the Timing Diagrams below. At the start of the time interval t1, the  
computer program prints or writes the string to the com port, thus initiating a  
transmission. During t1, the command characters are under transmission and at  
the end of this period, the command terminating character (*, $) is received by  
the meter. The time duration of t1 is dependent on the number of characters and  
baud rate of the channel.  
P
Print  
Timing Diagrams  
NO REPLY FROM METER  
t1 = (10 times the # of characters) / baud rate  
At the start of time interval t2, the meter starts the interpretation of the  
command and when complete, performs the command function. This time  
interval t2 varies. If no response from the meter is expected, the meter is ready  
to accept another command.  
If the meter is to reply with data, the time interval t2 is controlled by the use  
of the command terminating character. The '*' terminating character results in a  
response time window of 50 msec. minimum and 100 msec. maximum. This  
allows sufficient time for the release of the sending driver on the RS485 bus.  
Terminating the command line with '$' results in a response time window (t2) of  
2 msec. minimum and 50 msec. maximum. The faster response time of this  
terminating character requires that sending drivers release within 2 msec. after  
the terminating character is received.  
RESPONSE FROM METER  
At the beginning of time interval t3, the meter responds with the first  
character of the reply. As with t1, the time duration of t3 is dependent on the  
number of characters and baud rate of the channel. At the end of t3, the meter is  
ready to receive the next command.  
t3 = (10 times the # of characters) / baud rate  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION FORMAT  
Data is transferred from the meter through a serial communication channel.  
In serial communications, the voltage is switched between a high and low level  
at a predetermined rate (baud rate) using ASCII encoding. The receiving device  
reads the voltage levels at the same intervals and then translates the switched  
levels back to a character.  
Start Bit and Data Bits  
Data transmission always begins with the start bit. The start bit signals the  
receiving device to prepare for reception of data. One bit period later, the least  
significant bit of the ASCII encoded character is transmitted, followed by the  
remaining data bits. The receiving device then reads each bit position as they  
are transmitted.  
The voltage level conventions depend on the interface standard. The table  
lists the voltage levels for each standard.  
Parity Bit  
LOGIC  
INTERFACE STATE  
mark (idle)  
RS232*  
RS485*  
After the data bits, the parity bit is sent. The transmitter sets the parity bit to  
a zero or a one, so that the total number of ones contained in the transmission  
(including the parity bit) is either even or odd. This bit is used by the receiver  
to detect errors that may occur to an odd number of bits in the transmission.  
However, a single parity bit cannot detect errors that may occur to an even  
number of bits. Given this limitation, the parity bit is often ignored by the  
receiving device. The meter ignores the parity bit of incoming data and sets the  
parity bit to odd, even or none (mark parity) for outgoing data.  
1
0
TXD,RXD; -3 to -25 V  
TXD,RXD; +3 to +25 V  
a-b < -200 mV  
a-b > +200 mV  
space (active)  
* Voltage levels at the Receiver  
Data is transmitted one byte at a time with a variable idle period between  
characters. Each ASCII character is “framed” with a beginning start bit, an  
optional parity bit and one or more ending stop bits. The data format and baud  
rate must match that of other equipment in order for communication to take  
place. The figures list the data formats employed by the meter.  
Stop Bit  
The last character transmitted is the stop bit. The stop bit provides a single bit  
period pause to allow the receiver to prepare to re-synchronize to the start of a  
new transmission (start bit of next byte). The receiver then continuously looks  
for the occurrence of the start bit. If 7 data bits and no parity is selected, then 2  
stop bits are sent from the meter.  
Character Frame Figure  
6.8 MODULE 8 - REAL-TIME CLOCK PARAMETERS (ꢱꢄꢁꢃꢡ) - PTC901  
PARAMETER MENU  
Module 8 is the programming module for the Real-Time Clock (RTC) Date  
and Time Parameters. In the Display Mode, the DAT annunciator indicates the  
SET DATE  
RTC Date is currently being shown. The RTC Time display is shown with no  
annunciator. This programming module can only be accessed if a Real-Time  
Clock card is installed.  
ꢂꢅꢃꢄ«  
ꢈꢉ  
ꢟꢅꢂ  
ª
ꢈꢉ  
This parameter sets the Date for the Real-Time Clock. Selecting ꢟꢅꢂ will  
display the sub-menu where the Date can be set or changed. The RTC Date is  
entered in “Month.Day.Year” format (two-digit values). When the PAR key is  
pressed, the new Date is entered. Select ꢈꢉ to advance to the next parameter  
without changing the Date.  
SET TIME  
ꢂꢅꢃꢄ«  
ꢈꢉ  
ꢈꢉ  
ꢟꢅꢂ  
ª
ꢠꢥꢥꢗꢀꢀꢗꢟꢟ  
«
ꢛꢏꢗꢛꢏꢗꢛꢏ  
This parameter sets the Time for the Real-Time Clock. Selecting ꢟꢅꢂ will  
display the sub-menu where the Time can be set or changed. The RTC Time is  
entered in “Hours-Minutes”, 12-hour format, with AM/PM indication. When  
the PAR key is pressed, the new Time is entered and begins running. The  
“Seconds” always start from 00 when the Time is entered. Select to advance  
to the next parameter without changing the Time.  
MONTH.DAY.YEAR  
ª
SET DAY  
ꢀꢤ«  
ꢖꢭꢥ  
ꢖꢭꢥ ꢮꢇꢥ  
ꢃꢦꢭ ꢚꢁꢞ  
ꢃꢭꢅ  
ꢖꢤꢃ  
ꢯꢅꢀ  
ꢐꢐꢄꢈꢈꢆ  
«
ꢏꢑꢄꢛꢛꢓ  
HOURS-MINUTES Am/Pm  
ª
ª
Set the Day of the week for the Real-Time Clock.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To calibrate the RTC, install the meter in its normal operating environment,  
and set the time based on a known accurate reference (such as the WWV  
broadcast or the Atomic Clock reference which is available via the internet).  
After 30 days of normal operation, compare the RTC time to the reference, and  
note the amount of time gained or lost. Refer to the tables on the next page for  
the proper Offset value to enter, given the amount of time drift observed.  
TIME DISPLAY FORMAT  
ꢀꢖꢍꢄ«  
ª ꢏꢑꢄꢒꢘꢍ  
12-59p 12-59 23-59  
ꢀꢁꢂꢃꢄꢂꢃꢄ ꢑꢙꢗꢒꢘꢗꢒꢘ  
Select the format in which the Real-Time Clock Time will be displayed. The  
format selections depict the range for the RTC Time display, and DO NOT  
represent the current RTC Time. When the meter is operating in the Display  
Mode, the RTC Time display is shown with no annunciator.  
ꢉꢚꢚꢂꢅꢃ  
«
ª
ꢛꢛ to ꢫꢙ  
ꢛꢛ  
DATE DISPLAY FORMAT  
Selecting ꢪꢅꢂ for the ꢡꢓꢊ parameter displays the ꢉꢚꢚꢂꢅꢃ sub-menu where the  
present Offset value can be viewed or changed. The tables below show the  
value to enter, given the amount of time gained or lost in a 30-day period.  
ꢀꢂꢆꢄ«  
ª ꢏꢑꢄꢙꢏ  
ꢏꢑꢄꢙꢏ ꢙꢏꢄꢏꢑ ꢏꢑꢗꢙꢏꢗꢘꢘ ꢙꢏꢗꢏꢑꢗꢘꢘ  
+B/ꢅꢆꢀ ꢙꢏꢄꢲꢤꢈ sun-31  
Values 00 and 32 provide no Offset, and are not shown in the tables.  
Select the format in which the Real-Time Clock Date will be displayed. The  
format selections depict the range for the RTC Date display, and DO NOT  
represent the current RTC Date. When the meter is operating in the Display  
Mode, the RTC Date display is indicated by the DAT annunciator.  
IF RTC CLOCK GAINED TIME:  
USE VALUE FROM THIS TABLE  
SECONDS ENTER THIS SECONDS ENTER THIS  
GAINED IN  
30 DAYS  
OFFSET  
VALUE  
GAINED IN  
30 DAYS  
OFFSET  
VALUE  
AUTO CHANGE FOR DAYLIGHT SAVINGS TIME  
5
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
16  
90  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
11  
16  
21  
26  
32  
37  
42  
47  
53  
58  
63  
69  
74  
79  
84  
95  
ꢡꢦꢄꢀꢖ«  
ꢈꢉ  
100  
105  
111  
116  
121  
127  
132  
137  
142  
148  
153  
158  
163  
ꢈꢉ  
ꢟꢅꢂ  
ª
Selecting ꢪꢅꢂ allows the meter to automatically adjust the RTC Time for  
Daylight Savings Time. (Adjustment dates are U.S.A. standard only.) Avoid  
setpoints that occur during adjustment (Sundays 1 to 3 AM).  
METER TYPE FOR CLOCK SYNCHRONIZATION  
ꢖꢟꢈ«  
ꢂꢊꢓꢋꢅ  
ꢖꢊꢓꢋꢅ ꢐꢉꢂꢃ  
ª
Time synchronization between multiple PTC901 meters can be  
accomplished through a hardware interface on the Real-Time Clock option  
card. This RS485 type interface allows connection of up to 32 PTC901 meters  
in a two-wire multidrop network, at distances up to 4000 ft. (See Section 4.6,  
Real-Time Clock Wiring).  
In a Synchronization network, one PTC901 meter is programmed as the Host  
(ꢐꢉꢂꢃ), while all other meters are programmed as Slaves (ꢂꢊꢓꢋꢅ). Once every  
hour (at 30 min. past the hour), the Host meter outputs a time synchronization  
pulse onto the network. Upon receiving the synchronization pulse, each Slave  
meter automatically adjusts the Minutes and Seconds of its RTC Time setting to  
synchronize with the Host. Synchronization, using the Real-Time Clock Wiring,  
adjusts the Minutes and Seconds only, and does not change the Hours, AM/PM,  
Day or Date settings in the Slave meter's RTC.  
IF RTC CLOCK LOST TIME:  
USE VALUE FROM THIS TABLE  
SECONDS ENTER THIS SECONDS ENTER THIS  
LOST IN 30  
DAYS  
OFFSET  
VALUE  
LOST IN 30  
DAYS  
OFFSET  
VALUE  
Full-time synchronization (hours, minutes and seconds) is possible for  
PAXCKs that are connected in an RS485 network (RS485 Serial Option cards  
required). In this configuration, one meter is designated as the Serial RTC  
Master by setting the meter's address as 98 or 99 (see Serial Real-time Clock  
Addressing in Master Module 7). Every hour (at 30 min past the hour), the  
Serial RTC Master / Host will transmit the full time (Hours, minutes, seconds)  
to all meters through the RS485 serial card wiring network. The time, date, or  
day will also be transmitted and updated in the Slaves when changed in the  
programming of the Serial RTC Master. Only one meter should be configured  
as Master and that meter should also be configured as the Host.  
11  
21  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
179  
190  
200  
211  
221  
232  
243  
253  
264  
274  
285  
295  
306  
316  
327  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
32  
42  
53  
63  
74  
84  
95  
CALIBRATE REAL-TIME CLOCK  
105  
116  
127  
137  
148  
158  
169  
ꢡꢓ«  
ꢈꢉ  
ꢈꢉ  
ꢟꢅꢂ  
ª
* NOTE: DO NOT ADJUST TRIM CAP ON RTC CARD!  
The Real-Time Clock circuit uses a crystal controlled oscillator for high  
accuracy timekeeping. The oscillator is factory calibrated* and optimized for  
25°C ambient temperature operation. Since the PTC901 is designed to operate  
over a wide temperature range, and since the accuracy of a crystal oscillator  
varies with ambient temperature, some drift in the RTC time may be observed  
over an extended period. This is primarily seen in high or low temperature  
installations. To compensate for the wide operating temperature range, a  
calibration or “Offset” value can be entered, which effectively slows down or  
speeds up the clock to maintain accurate timekeeping.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.9 MODULE 9 - FACTORY SERVICE OPERATIONS (ꢘꢄꢚꢡꢂ)  
PARAMETER MENU  
DISPLAY INTENSITY LEVEL  
RESTORE FACTORY DEFAULTS  
Enter the desired Display Intensity Level (0-15) by  
using the arrow keys. The display will actively dim or  
brighten as the levels are changed. This parameter also  
appears in Quick Programming Mode when enabled.  
Use the RST and/or arrow keys to display ꢡꢉꢀꢅ ꢉꢫꢫ and  
press PAR. The meter will display ꢁꢅꢂꢅꢃ and then returns  
to ꢡꢉꢀꢅ ꢛꢒꢛ. Press DSP key to return to the Display Mode.  
This will overwrite all programmed user settings with the  
Eꢅ-&7 «  
ª
ꢡꢉꢀ«  
ꢕꢛꢫꢫ  
ª
Factory Default Settings shown in the Parameter Value Chart. For the PTC901,  
the Time and Date stored in the Real-Time Clock, as well as the RTC  
Claibration Offset value, are NOT overwritten by this parameter. However, the  
Time and Date Display Formats will revert back to the Factory Default Settings.  
TROUBLESHOOTING  
For further assistance, contact technical support at the appropriate company numbers listed.  
PROBLEM  
REMEDIES  
NO DISPLAY  
CHECK: Power level, power connections  
CHECK: User input set for program lock-out function is in Active state  
ENTER: Security code requested  
PROGRAMMING LOCKED-OUT  
CERTAIN DISPLAYS ARE LOCKED-OUT  
MODULES or PARAMETERS NOT ACCESSIBLE  
CHECK: Display Lock-out programming in Module 3  
CHECK: Corresponding plug-in card installation, Program Lock-out/ Value Access  
parameter programming in Module 3  
CHECK: Input wiring, Timer plug jumper setting, Timer input programming in Module 1,  
input signal level, Timer Inhibited by Input B or a user input  
TIMER NOT RUNNING  
CHECK: User input wiring, user input plug jumper setting, user input signal level,  
user input programming in Module 2  
USER INPUT NOT WORKING PROPERLY  
OUTPUTS NOT WORKING PROPERLY  
CHECK: Setpoint plug-in card installation, wiring, Setpoint programming in Module 6  
CHECK: RTC plug-in card installation, RTC programming in Module 8, check for  
proper battery installation, replace battery. DO NOT ADJUST TRIM CAP ON RTC CARD!  
REAL-TIME CLOCK NOT WORKING PROPERLY  
CHECK: Serial plug-in card installation, Serial wiring, Serial settings in Module 7,  
host settings  
SERIAL COMMUNICATIONS NOT WORKING  
PRESS: Reset key (If unable to clear, contact factory.)  
ERROR CODE (ꢅꢁꢁ ꢏꢄꢣ)  
Shaded areas are model dependent.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARAMETER VALUE CHART  
Programmer ________________ Date ________  
Clock Timer  
Meter# _____________ Security Code __________  
3-LOCDisplay and Program Lock-out Parameters  
1-INPTimer Input Parameters  
FACTORY  
SETTING  
FACTORY  
SETTING  
DISPLAY  
PARAMETER  
USER SETTING  
DISPLAY  
PARAMETER  
USER SETTING  
TIMER DISPLAY LOCK-OUT  
CYCLE COUNT DISPLAY LOCK-OUT  
RTC DATE DISPLAY LOCK-OUT  
RTC TIME DISPLAY LOCK-OUT  
SP1 ON VALUE ACCESS  
t-dSP  
C-dSP  
rtC-d  
rtC-t  
Sp-1  
rEd  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
LOC  
000  
TIMER RANGE  
rANGE  
SSSSSS  
LEVEL  
ꢛꢈ  
TIMER INPUT OPERATION  
TIMER INPUT FILTERING  
TIMING DIRECTION  
INP OP  
FILtEr  
t dir  
ꢝꢆ  
TIMER START VALUE (A)  
TIMER START VALUE (B)*  
TIMER STOP (A & B*)  
t Strt  
ꢛꢛꢛꢛꢛꢛ  
ꢛꢛꢛꢛꢛꢛ  
NO  
SP1 OFF VALUE ACCESS  
SP0F-1  
tOUt-1  
Sp-2  
SP1 TIME-OUT VALUE ACCESS  
SP2 ON VALUE ACCESS  
t StOP  
VaLUE  
TIMER STOP VALUE (A)  
TIMER STOP VALUE (B)*  
FLASH TIMER ANNUNCIATOR  
TIMER INPUT STATE AT POWER-UP  
TIMER RESET AT POWER-UP  
ꢛꢛꢛꢛꢛꢛ  
ꢛꢛꢛꢛꢛꢛ  
ꢈꢉ  
ꢂꢃꢉꢆ  
ꢈꢉ  
SP2 OFF VALUE ACCESS  
Sp0f-2  
tOUt-2  
sp-3  
SP2 TIME-OUT VALUE ACCESS  
SP3 ON VALUE ACCESS  
FLASH  
InP-UP  
t p-UP  
SP3 OFF VALUE ACCESS  
sp0f-3  
tOUt-3  
sp-4  
SP3 TIME-OUT VALUE ACCESS  
SP4 ON VALUE ACCESS  
SP4 OFF VALUE ACCESS  
sp0f-4  
tOUt-4  
t Strt  
t StOP  
C Strt  
C StOP  
SEt-t  
COdE  
2-FNCUser Input and Function Key Parameters  
SP4 TIME-OUT VALUE ACCESS  
TIMER START VALUE ACCESS  
TIMER STOP ACCESS  
FACTORY  
SETTING  
DISPLAY  
PARAMETER  
USER SETTING  
NO  
NO  
USER INPUT 1  
USEr-1  
USEr-2  
USEr-3  
F1  
COUNTER START VALUE ACCESS  
COUNTER STOP VALUE ACCESS  
RTC TIME SETTING ACCESS  
SECURITY CODE  
USER INPUT 2  
NO  
NO  
USER INPUT 3  
FUNCTION KEY 1  
NO  
FUNCTION KEY 2  
F2  
rSt  
SEC-F1  
drSt-E  
NO  
NO  
RESET KEY  
SECONDARY FUNCTION KEY F1  
SECONDARY FUNCTION KEY F2  
4-CNtCycle Counter Parameters  
SEC-F2  
FACTORY  
SETTING  
DISPLAY  
PARAMETER  
USER SETTING  
NONE  
UP  
CYCLE COUNTER COUNT SOURCE  
CYC. CNTR. COUNTING DIRECTION  
CYCLE COUNTER START VALUE (A)  
CYCLE COUNTER START VALUE (B)*  
CYCLE COUNTER STOP (A & B*)  
CYCLE COUNTER STOP VALUE (A)  
CYCLE COUNTER STOP VALUE (B)*  
CYC. CNTR. RESET AT POWER-UP  
C Src  
C dir  
C Strt  
000000  
000000  
NO  
C StOP  
VALUE  
000000  
OOOOOO  
NO  
C p-UP  
5-OPErTimer Operating Modes  
FACTORY  
SETTING  
DISPLAY  
PARAMETER  
USER SETTING  
PREDEFINED TIMER OPER. MODE  
SETPOINT 1 ON VALUE  
t OPEr  
SP-1  
SPOF-1  
tOUt-1  
NO  
ꢛꢛꢛꢛꢛꢛ  
000100  
ꢛꢛꢗꢛꢏꢗꢛꢛ  
SETPOINT 1 OFF VALUE  
SETPOINT 1 TIME-OUT VALUE  
* See Module 2, Exchanging Parameter Lists, for details on programming this value.  
Shaded areas are model dependent.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SP-1  
SP-2  
SP-3  
SP-4  
6-SPt Setpoint (Alarm) Parameters  
FACTORY  
SETTING  
FACTORY  
SETTING  
FACTORY  
SETTING  
FACTORY  
SETTING  
DISPLAY  
PARAMETER  
USER SETTING  
USER SETTING  
USER SETTING  
USER SETTING  
SETPOINT ASSIGNMENT  
SETPOINT ACTION  
ASM-n  
ACt-n  
OUt-n  
ON-n  
NONE  
LAtCH  
NOr  
VALUE  
VALUE  
NONE  
LAtCH  
NOr  
VALUE  
VALUE  
NONE  
LAtCH  
NOr  
VALUE  
VALUE  
NONE  
LAtCH  
NOr  
VALUE  
VALUE  
OUTPUT LOGIC  
SETPOINT ON (A)  
SETPOINT ON (B)*  
SETPOINT ON VALUE (A)  
SETPOINT ON VALUE (B)*  
SETPOINT OFF (A)  
SP-n  
000000  
000000  
VALUE  
VALUE  
000100  
000100  
ꢛꢛꢗꢛꢏꢗꢛꢛ  
ꢛꢛꢗꢛꢏꢗꢛꢛ  
Mon-Fri  
Mon-Fri  
Mon-Fri  
Mon-Fri  
NO  
000000  
000000  
VALUE  
VALUE  
000100  
000100  
ꢛꢛꢗꢛꢏꢗꢛꢛ  
ꢛꢛꢗꢛꢏꢗꢛꢛ  
Mon-Fri  
Mon-Fri  
Mon-Fri  
Mon-Fri  
NO  
000000  
000000  
VALUE  
VALUE  
000100  
000100  
ꢛꢛꢗꢛꢏꢗꢛꢛ  
ꢛꢛꢗꢛꢏꢗꢛꢛ  
Mon-Fri  
Mon-Fri  
Mon-Fri  
Mon-Fri  
NO  
000000  
000000  
VALUE  
VALUE  
000100  
000100  
ꢛꢛꢗꢛꢏꢗꢛꢛ  
ꢛꢛꢗꢛꢏꢗꢛꢛ  
Mon-Fri  
Mon-Fri  
Mon-Fri  
Mon-Fri  
NO  
OFF-n  
SPOF-n  
tOUt-n  
ꢀ ꢉꢈꢄꢥ  
ꢀꢉꢜꢜꢄꢥ  
SETPOINT OFF (B)*  
SETPOINT OFF VALUE (A)  
SETPOINT OFF VALUE (B)*  
TIME-OUT VALUE (A)  
TIME-OUT VALUE (B)*  
DAILY ON OCCURRENCE (A)  
DAILY ON OCCURRENCE (B)*  
DAILY OFF OCCURRENCE (A)  
DAILY OFF OCCURRENCE (B)*  
TIMER STOP  
ꢃꢂꢃꢆꢄꢥ  
ꢓꢝꢃꢉꢄꢥ  
ꢉꢁꢖꢀꢄꢥ  
ꢊꢞꢃꢄꢥ  
TIMER/COUNTER AUTO RESET  
OUTPUT RESET W/DISPLAY RESET  
SETPOINT ANNUNCIATOR  
POWER-UP STATE  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
NOr  
ꢉꢚꢚ  
NOr  
ꢉꢚꢚ  
NOr  
ꢉꢚꢚ  
NOr  
ꢉꢚꢚ  
ꢆꢄꢝꢍꢄꢥ  
7-SrLSerial Communication Parameters  
8-rtCReal-Time Clock Parameters  
FACTORY  
SETTING  
FACTORY  
SETTING  
DISPLAY  
PARAMETER  
USER SETTING  
DISPLAY  
PARAMETER  
USER SETTING  
12-59p  
12-31  
N0  
TIME DISPLAY FORMAT  
dSP-t  
dSP-d  
Ch-dSt  
SyNC  
CAL  
OFFSEt  
BAUD RATE  
DATA BITS  
PARITY BIT  
bAUd  
dAtA  
PAr  
Addr  
Abbr  
9600  
7
Odd  
00  
NO  
YES  
DATE DISPLAY FORMAT  
AUTO TIME CHANGE FOR D.S.T.  
SYNCHRONIZATION UNIT TYPE  
CALIBRATE REAL-TIME CLOCK  
RTC CALIBRATION OFFSET VALUE  
sLAVE  
METER UNIT ADDRESS  
ABBREVIATED PRINTING  
REAL-TIME CLOCK PRINT FORMAT  
PRINT OPTIONS  
00  
ꢁꢃꢡ ꢚꢃ  
OPt  
TIMER DISPLAY  
t-dSP  
C-dSP  
rtC-d  
rtC-t  
spNt  
YES  
NO  
NO  
NO  
NO  
NO  
CYCLE COUNTER DISPLAY  
RTC DATE DISPLAY  
9-fCSFactory Service Parameters  
RTC TIME DISPLAY  
FACTORY  
SETTING  
DISPLAY  
PARAMETER  
USER SETTING  
SETPOINT VALUES  
3
DISPLAY INTENSITY LEVEL  
d-LEV  
SETPOINT OFF/ TIME-OUT VALUES  
SPNtOF  
* See Module 2, Exchanging Parameter Lists, for details on programming this value.  
Shaded areas are model dependent.  
PTC901 Application  
A big application request has always been for  
Real-Time Clocks to display time throughout the  
plant. The challenge has been to keep all the  
various clock locations synchronized with the  
right time. With the new PTC901 Timer/Real-  
Time Clock this problem is history. You can install  
up to a maximum of 32 units. Simply select one of  
the units in the system as the host and the balance  
are programmed as slaves. The host will send out  
a synchronization pulse every hour to correct the  
time on any clock unit wired in the system.  
Real-Time Clock Synchronization Network  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PTC900/PTC901 PROGRAMMING QUICK OVERVIEW  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PART NUMBER INFORMATION  
DESCRIPTION  
PART NUMBERS  
Timer, 85-250 VAC power  
PTC900  
Timer, 11-36 VDC/24 VAC power  
PTC900-LV  
PTC900-GN  
PTC900-GN-LV  
PTC901  
Timer, 85-250 VAC power, green LED display  
Timer, 11-36 VDC/24 VAC power, green LED display  
Real-Time Clock, 85-250 VAC power  
Real-Time Clock, 11-36 VDC/24 VAC power  
Real-Time Clock, 85-250 VAC power, green LED display  
Real-Time Clock, 11-36 VDC/24 VAC power, green LED display  
PTC901-LV  
PTC901-GN  
PTC901-GN-LV  
ACCESSORIES  
DESCRIPTION  
PART NUMBERS  
Setpoint Alarms  
Dual Setpoint relay output Card  
DP6-CDS10  
DP6-CDS20  
DP6-CDS30  
DP6-CDS40  
Quad Setpoint relay output Card  
Quad Setpoint sinking open collector output Card  
Quad Setpoint sourcing open collector output Card  
Communications  
RS485 serial communications output card with terminal block  
Extended RS485 serial communications output card with dual RJ11 connectors  
RS232 serial communications output card with terminal block  
Extended RS232 serial communications output card with 9-pin D connector  
MODBUS communications output card with terminal block  
Extended MODBUS communications output card with dual RJ11 connectors  
Real-Time Clock  
DP6-CDC10  
DP6-CDC1C  
DP6-CDC20  
DP6-CDC2C  
DP6-CDC40  
DP6-CDC4C  
Real-Time Clock card  
PTC9-RTC00  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY/DISCLAIMER  
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a  
period of 25 months from date of purchase. OMEGAs WARRANTY adds an additional one (1) month grace  
period to the normal two (2) year product warranty to cover handling and shipping time. This ensures  
that OMEGAs customers receive maximum coverage on each product.  
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGAs Customer Service  
Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon  
examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge.  
OMEGAs WARRANTY does not apply to defects resulting from any action of the purchaser, including but  
not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or  
unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered  
with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat,  
moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside  
of OMEGAs control. Components in which wear is not warranted, include but are not limited to contact  
points, fuses, and triacs.  
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA  
neither assumes responsibility for any omissions or errors nor assumes liability for any  
damages that result from the use of its products in accordance with information provided by  
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the  
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR  
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF  
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY  
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF  
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of  
OMEGA with respect to this order, whether based on contract, warranty, negligence,  
indemnification, strict liability or otherwise, shall not exceed the purchase price of the  
component upon which liability is based. In no event shall OMEGA be liable for consequential,  
incidental or special damages.  
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic  
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical  
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity,  
medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth  
in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and  
hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in  
such a manner.  
RETURN REQUESTS/INQUIRIES  
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE  
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)  
NUMBER FROM OMEGAS CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING  
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any  
correspondence.  
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent  
breakage in transit.  
FOR WARRANTY RETURNS, please have the  
following information available BEFORE  
contacting OMEGA:  
1. Purchase Order number under which the product  
was PURCHASED,  
FOR NON-WARRANTY REPAIRS, consult OMEGA  
for current repair charges. Have the following  
information available BEFORE contacting OMEGA:  
1. Purchase Order number to cover the COST of the  
repair,  
2. Model and serial number of the product under  
warranty, and  
3. Repair instructions and/or specific problems  
relative to the product.  
2. Model and serial number of the product, and  
3. Repair instructions and/or specific problems  
relative to the product.  
OMEGAs policy is to make running changes, not model changes, whenever an improvement is possible. This affords our  
customers the latest in technology and engineering.  
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.  
© Copyright 2006 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,  
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the  
prior written consent of OMEGA ENGINEERING, INC.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where Do I Find Everything I Need for  
Process Measurement and Control?  
OMEGA…Of Course!  
Shop online at omega.com  
TEMPERATURE  
] Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies  
] Wire: Thermocouple, RTD & Thermistor  
] Calibrators & Ice Point References  
] Recorders, Controllers & Process Monitors  
] Infrared Pyrometers  
PRESSURE, STRAIN AND FORCE  
] Transducers & Strain Gages  
] Load Cells & Pressure Gages  
] Displacement Transducers  
] Instrumentation & Accessories  
FLOW/LEVEL  
] Rotameters, Gas Mass Flowmeters & Flow Computers  
] Air Velocity Indicators  
] Turbine/Paddlewheel Systems  
] Totalizers & Batch Controllers  
pH/CONDUCTIVITY  
] pH Electrodes, Testers & Accessories  
] Benchtop/Laboratory Meters  
] Controllers, Calibrators, Simulators & Pumps  
] Industrial pH & Conductivity Equipment  
DATA ACQUISITION  
] Data Acquisition & Engineering Software  
] Communications-Based Acquisition Systems  
] Plug-in Cards for Apple, IBM & Compatibles  
] Datalogging Systems  
] Recorders, Printers & Plotters  
HEATERS  
] Heating Cable  
] Cartridge & Strip Heaters  
] Immersion & Band Heaters  
] Flexible Heaters  
] Laboratory Heaters  
ENVIRONMENTAL  
MONITORING AND CONTROL  
] Metering & Control Instrumentation  
] Refractometers  
] Pumps & Tubing  
] Air, Soil & Water Monitors  
] Industrial Water & Wastewater Treatment  
] pH, Conductivity & Dissolved Oxygen Instruments  
M4494/0408  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Nady Systems Music Mixer PMX 420 User Manual
National Instruments Computer Hardware NI PXI PCI 5114 User Manual
Navman GPS Receiver Tracker500 500i User Manual
NEC Flat Panel Television MultiSync LCD3215 User Manual
NetComm Network Card SCINTRA600 User Manual
NordicTrack Treadmill NTL16950 User Manual
Omega Vehicle Security Power Supply LDN PS User Manual
Ozaki Worldwide Speaker EM67706 User Manual
Palm Cell Phone TreoTM 750 User Manual
Patton electronic Network Cables SN DTA User Manual