GENERAL DESCRIPTION  
The Omega PRG-501 and PRG501 Series Pressure Regulators have an advanced design  
consisting of a precision measurement capsule and a high gain servo amplifier to achieve  
high performance. The regulator can be used in a ‘dead end’ application and will exhaust  
whenever the setpoint is lowered. Changes in supply pressure have a minimal effect on  
the regulation accuracy. The regulator can be panel or pipe mounted. These regulators are  
unaffected by vibration and mounting position. A set point locknut is provided.  
The PRG101 has two ¼ NPT gauge ports available for mounting OMEGA® pressure  
gauges for local indication. The PRG501 is ideal for having a dial gauge reading when  
the unit is panel mounted. The dial gauge would be external to the panel.  
The PRG101 regulators are available in the following pressure ranges:  
Model No.  
PRG101-120  
PRG101-60  
PRG101-25  
Adjustable Range  
2-120 PSIG  
2-60 PSIG  
2-25 PSIG  
The PRG501 regulators are available in the following pressure ranges:  
Model No.  
Adjustable Range  
2-120 PSIG  
2-60 PSIG  
2-30 PSIG  
3-15 PSIG  
PRG501-120  
PRG501-60  
PRG501-30  
PRG501-X15  
OPERATION  
The PRG101 and PRG501 are precision pressure regulators, normally used with  
compressed air. The operation has been specifically designed for zero flow ‘dead end’  
service, but can provide large air flows up to 5L/sec (10scfm) when required. It maintains  
a highly stable outlet pressure against variation in supply pressure, flow, temperature and  
vibration. These instruments use small quantities of air for operation (0.5-2 litres/minute)  
and can be set to a minimum below 0.14 bar (2psi). Tight shut off is not possible.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BASIC MECHANISM  
The units use a piston to control a high gain pneumatic two-stage servo system. When  
increasing the regulated pressure the handwheel is turned clockwise, forcing the  
measuring capsule/piston assembly downward. This pushes the pilot diaphragm and  
control diaphragm downward. As a result, the main valve opens and the supply pressure  
enters the regulator. The resulting pressure change causes the measuring capsule to  
compress. This compression causes the pilot diaphragm and the control diaphragm to  
move upward, which then shuts the main valve.  
When decreasing the regulated pressure, the handwheel is turned counterclockwise,  
forcing the measuring capsule/piston assembly upward. This allows the pilot diaphragm  
and control diaphragm to move upward. As a result, the relief valve opens and air is  
exhausted through the vent. The resulting pressure drops causes the measuring capsule to  
expand. This expansion causes the pilot diaphragm and control diaphragm to move down,  
which then shuts the relief valve.  
To maintain a state of equilibrium, the action of the measuring capsule as described  
above ensures a precise constant pressure regulation. Air is bled at a constant rate through  
the bleed orifice so that a very small movement of the pilot valve induces a substantial  
pilot pressure change, which creates a high servo amplification.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Mounting  
The PRG101 is usually panel mounted into a minimum 11.5mm hole. Direct pipe  
mounting is also possible. To install on a panel remove the knob (grub screw) tension nut  
and mounting nut. Insert into the panel and replace the nuts and knob. The mounting nut  
should be retightened to a torque of 5Nm; set the tension nut to give adequate friction for  
the desired service. It is not necessary to remove the locknuts for installation; these may  
be reset if required to give a maximum pressure below the factory setting.  
Pneumatics  
All pneumatics ports are threaded ¼” NPT. Two gauge ports may be used as required,  
and are supplied sealed with pipe plugs.  
The following installation precautions are ESSENTIAL:  
Air supply- This can be between limits of 0.2 bar (3 psi) above the maximum required  
outlet pressure and 10 bar (150psi). The air supply must be filtered to 25 micron, with oil  
content below 1ppm and dew point at least -10˚C below lowest ambient temperature.  
Filtering and oil removal are vital for long life.  
Pipe Fitting – Fit appropriate pipe fittings for the pipe sizes required. DO NOT USE  
PTFE TAPE. Thread sealing can be easily achieved with loctite hydraulic seal or similar  
anaerobic seals.  
Pipe sizes – 6mm plastic tubes are commonly used, but increase to 8 or 10mm is  
desirable if long pipe runs of high flows are present. Plastic tubes (e.g. nylon) are  
convenient and clean.  
HEALTH AND SAFETY  
The units are simple pressure control instruments and present few safety hazards.  
Installation should be in accordance with BS6739 or other relevant national standards.  
Compressed air can produce accidents if not correctly used and the user is urged to  
adhere to established compressed air safety standard.  
These instruments contain no substance which presents hazards in normal use. The  
measuring capsule is constructed of beryllium copper, which can present disposal  
hazards; if a satisfactory disposal procedure is not available, scrap instruments should be  
returned to the factory.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSION DETAILS  
M ax. p re s s ure  
s to p lo c knuts  
T e ns io n nut  
4 3 .5 R E F  
L o c knut fo r  
m o unting  
B le e d s c re w  
E xhaus t  
s lo ts  
6 9 R E F  
O utle t  
p o rt  
Inle t p o rt  
G aug e  
1 3 .6 R E F  
5 4 R E F  
p o rt 1 /4 ”  
NP T  
Inle t p o rt  
1 /4 ” NP T  
5 4 R E F  
1 1 re q uire d fo r p ane l m o unting  
Ø
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M1846-09/02  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Food Warmer EGW2062 User Manual
Mr Coffee Coffeemaker DR User Manual
MSi Computer Drive US54G User Manual
MTD Lawn Mower 110 530A User Manual
Multiquip Power Roller T16 User Manual
Muratec All in One Printer MK3190 User Manual
NHT Speaker Sc 2 User Manual
Night Owl Optics Home Security System BUL User Manual
Omega Stud Sensor CDTX 90 User Manual
Panasonic Cell Phone 6275I User Manual