OPTI UPS Power Supply DS1000E User Manual

* DS1000E / DS1000EL /  
DS2000E / DS2000EL /  
DS3000E / DS3000EL /  
DS6000E / DS6000EL  
DS1000E / DS2000E / DS3000E / DS6000E  
DS1000EL / DS2000EL / DS3000EL / DS6000EL  
High-Frequency Online UPS  
Features  
* Online Working Mode: All changeable structures, high output stability rate, zero out-off time.  
* Intelligent RS232 Communications Functions: To supervise and control the conditions of power supply and UPS  
through OPTI-UPS powersoft power supply supervision and control software. Also supporting OPTI-UPS SNMP network  
adapting apparatus to enhance the reliability of the system.  
* High Input Power Factor: The advanced PFC control technology to ensure input power factor larger than 0.95 when the  
output is full-loaded, so as to reduce the load on the power network.  
* Minimized Size: To enhance reliability of operation and reduce costs for the user.  
* High Efficiency and Low Wearing: Efficiency higher by 10%, less energy consumption, lesser noise and longer usage life.  
* Full-range of Protection Functions: Provision of super-high output voltage protection, low battery protection, trio  
super-high current protection and super-high input voltage protection, to enhance the adaptability to utility power supply  
and impact proof and ensure the safe operation of the user’s equipment and the UPS.  
* Three-Classes Over-Current Protection  
* Input Over-Voltage Protection  
Specifications  
MODEL NAME  
DS1000E  
DS1000EL  
DS2000E  
DS2000EL  
DS3000E  
DS3000EL  
DS6000E  
DS6000EL  
INPUT  
160 ~ 275 Vac  
AC voltage range  
Input Frequency range  
Number of phases  
Battery voltage (Vdc)  
OUTPUT  
50 +/-5 % Hz  
Three lines in single phase  
36  
72  
96  
120  
2000VA  
3000VA  
1000VA  
6000VA  
Power  
230 +/-2% V  
Voltage  
50 +/-0.2% Hz (battery mode)  
Sine wave THD < 3% (Linear load)  
0 ms  
50 +/-0.1% Hz (battery mode)  
Frequency  
Wave form  
Switching Time  
105%~125% Load, lasting 60  
seconds. 125%~150% Load,  
lasting 30 seconds.≥150% lasting  
300 milliseconds  
105%~130% Load, lasting 60 seconds.  
135%~150% Load, lasting 30 seconds.  
≥150% lasting 300 milliseconds  
Overload capacity  
Output mode  
Sockets  
Sockets and Terminal  
Terminal  
OTHER FEATURES  
Charge recovery time  
<12 hours (Standard time delay model)  
RS232 interface supports UPS power management software and SNMP protocol  
Communications interface  
Panel display  
LED displays operation status and  
LCD displays parameter of UPS  
LED displays operation status of UPS  
Warning functions  
Protection function  
Noise (dB)  
Battery low voltage, abnormal power supply, UPS malfunction  
Battery low voltage protection, overload protection, short-circuit protection and excess temperature protection  
< 45  
< 55  
Working temperature  
Relative humidity  
Dimensions (L x W x H) (mm)  
Weight (kg)  
0 - 40 C  
0~95% No condensation  
490 x 198 x 347  
465 x 155 x 225  
15 8.5  
637 x 253 x 680 637 x 253 x 500  
32  
17  
38  
18  
94.5  
36  
41-1.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Clothes Dryer T 4423 C User Manual
Miele Dishwasher G 601 User Manual
Multi Tech Systems Scanner FF100 User Manual
Napoleon Grills Charcoal Grill BIPRO 600 User Manual
Nikon Telephone 3100 ICP 40 L User Manual
Omron Healthcare Fitness Electronics HJ 203 User Manual
Optoma Technology Projector TX330 User Manual
Panasonic Air Conditioner CS E18JKR User Manual
Panasonic Vacuum Cleaner MC CG902 User Manual
Panasonic VCR AJ SD965 User Manual