New Buck Corporation Indoor Fireplace FP BR 10 ZC User Manual

MODEL FP-BR-10-ZC  
VENT-FREE  
March 2005  
NOTE: An unvented room heater hav-  
ing an input rating of more than 6,000  
Btu per hour shall not be installed in a  
bathroom.  
Manufacturer: NEW BUCK CORPORATION  
P.O. Box 69 8000 Highway 226 South  
Spruce Pine, NC 28777  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
Safety Information and Warnings................................................................................. 3  
Installation..................................................................................................................... 6  
Fireplace and Framing Dimensions .............................................................................. 7  
Fireplace Clearances ..................................................................................................... 8  
Finishing Your Fireplace .............................................................................................. 9  
Mantel Profiles For Zero Clearance............................................................................ 10  
Mantel Installation ..................................................................................................... 11  
Mobile Home Installation ........................................................................................... 13  
Gas Connection…………………………………………………………………… …13  
Producing Adequate Ventilation................................................................................. 14  
Ventilation Air Indoors............................................................................................... 16  
Ventilation Air Outdoors ............................................................................................ 17  
Gas Pressure Check..................................................................................................... 18  
Placement of Logs....................................................................................................... 19  
Lighting Instructions................................................................................................... 20  
Flame Check ............................................................................................................... 24  
Wiring Diagrams......................................................................................................... 25  
Important Safeguards.................................................................................................. 27  
Trouble Shooting ........................................................................................................ 28  
Service/Replacement Parts.......................................................................................... 32  
Warranty/Owner Registration..................................................................................... 35  
Page 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
The Model FP-BR10-ZC Vent-Free gas fireplace may be installed in any  
room in a Residential home or an After-Market* Manufactured Home.  
(Exception: This appliance may not be installed in a bathroom.)  
* (After Market: Completion of sale, not for the purpose of resale from the manufacturer).  
For After-Market Manufactured Home installation, check with state and local codes.  
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not  
convertible for use with other gases.  
NOTE: See page 14 for “Producing Adequate Ventilation”.  
CHOOSING THE LOCATION FOR YOUR FIREPLACE:  
Figure 1 shows some of the many ways your fireplace may be installed. Consider the traffic pattern in  
your room and the location of doors and windows. Moving air from ceiling fans, open doors, and hot air  
grills may cause the flames to soot. If a disturbance is found that affects the flames, it must be  
eliminated by turning off the ceiling fan, closing the door, or closing or moving the hot air register. A  
corner location may be best where space is limited.  
Your fireplace weighs no more than some of your fine furniture. If the fireplace is located near a load  
bearing wall, additional supports to the foundation will not be necessary. HEAVY FACINGS, SUCH  
AS BRICK, STONE, ETC., MAY REQUIRE ADDITIONAL FOUNDATION SUPPORT.  
NOTE: If this appliance is installed directly on carpeting, tile or other combustible material, other  
than wood flooring, the appliance shall be installed on a metal or wood panel extending the full  
width and depth of the appliance.  
FIGURE 1  
GAS LINES  
The gas supply line and electrical supply must  
be installed before framing in the fireplace by  
a licensed installer.  
DRAFTS  
Do not locate the fireplace in high traffic areas  
or areas exposed to high drafts and winds.  
Locate the fireplace away from furniture and  
draperies.  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fireplace and Framing Dimensions (ins.)  
25 1/8”  
24”  
11 5/8”  
20 3/8”  
26 1/8”  
26 1/8”  
GAS  
LINE  
1 3/4”  
8”  
25 1/8”  
13 1/2”  
FIGURE 2  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIREPLACE CLEARANCES  
depth. Alternatively, the carpeting, (vinyl) tile, etc. may be  
removed beneath the fireplace before installing.  
COMBUSTIBLE MATERIALS MUST NOT BE  
INSTALLED OVER OR TOUCH ANY BLACK  
PAINTED SURFACE. DO NOT BLOCK HEAT  
CIRCULATING AIR OUTLETS. DOING SO MAY  
RESULT IN POTENTIAL FIRE HAZARDS.  
1. Sidewall Clearances: Clearances from the side of the  
fireplace opening to any adjacent combustible wall should  
not be less than 7".  
The fireplace may be placed directly on a combustible floor, against  
a combustible wall at marked clear-ances, or on a raised wooden  
platform.  
If the fireplace is to be installed on a raised wooden platform, the  
platform must be a continuous level surface. The fireplace must be  
secured in place so it cannot shift positions. The nailing flanges on  
the sides of the firebox make securing it to the framing easy. They  
were designed to allow the installation of 1/2" wallboard or plywood  
flush with the face of the fireplace.  
Only the header (see Figure 2) may rest on the stand-offs on top of  
the firebox.  
When the firebox is installed over carpeting, (vinyl) tile,or any  
combustible material other than wood flooring, it must be  
installed on a metal or wood panel extending its full width and  
2. Ceiling Clearances: The ceiling height should  
not be less than 42" from the top of the fireplace  
opening.  
1/2"  
17-3/4"  
INSTALLING THE FIREBOX  
Figure 3  
TOP  
13-1/2"  
VIEW  
This list of specific instructions will help you make certain that  
every installation operation is performed correctly. Complete the  
installation steps in the sequence shown. STATE AND LOCAL  
BUILDING CODES SHOULD BE CONSULTED IN ALL  
CASES AS TO THE PARTICULAR REQUIREMENTS  
CONCERNING THE INSTALLATION OF A FACTORY  
BUILT FIREPLACES. Select the location for the fireplace by  
taking into consideration the factors previously outlined in the  
“Choosing the Location.” See page 5.  
7" *  
26-1/8"  
* Note: Minimum 1/2" clearance  
NOT required at this point  
SIDE  
VIEW  
Framing the Firebox  
The width of the framed opening must be 26 1/8". The height of  
the framed opening must be 25 1/8". The entire fireplace can be  
elevated above the floor to achieve a raised hearth effect. This can  
be done by adding a small platform to achieve the desired height.  
NOTE: The wiring for the lower blower must be installed during  
the framing stage. The nailing flanges on both sides were designed  
to allow the installation of 1/2" wallboard or plywood flush with  
the face of the fireplace.  
13-1/2"  
25-1/8"  
When the framing is inside, the outside wall will be insulated. If  
the framing or chase is outside, thin insulation should be used in the  
framing on the back, sides, and top. The bottom should be  
insulated with a hard insulating board. This will prevent cold from  
going into the chase through the fireplace to the living space.  
Install the Firebox  
Install the firebox into the framed opening by placing it directly in  
front of the opening and sliding it into the proper position.  
Level the Firebox  
FRONT  
VIEW  
FRAMING  
HEADER  
Check the level of the firebox on the top edge of the fireplace face.  
Shim if necessary.  
25-1/8"  
Secure the Firebox  
Secure the fireplace to the framing. The nailing flanges on the  
firebox will make securing the firebox to the frame quick and easy.  
Use appropriate size nails or screws to secure the firebox.  
26-1/8"  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FINISHING YOUR FIREPLACE  
There is a wide variety of finishing material available Check to see whether man-made brick and stone are  
for your fireplace from formal wall treatments with made of non combustible materials before using them  
marble and mantels, to rustic wood paneling, stone or on the face of the fireplace. Some of these products  
brick. Non-Combustible materials used in this contain combustible materials.  
installation such as slate, tile, marble, etc. must be at coverings such as paneling or wallboard may not  
least 1/2" thick. overlap the black face of the fireplace. The space  
Combustible wall  
IT IS IMPORTANT THAT THE BLACK FACE OF between the wall covering and the fireplace should be  
THE FIREPLACE NOT BE COVERED WITH sealed with a heat resistant material such as rock wool  
ANY TYPE OF COMBUSTIBLE MATERIAL.  
insulation or mortar.  
Non-combustible facing materials such as marble, brick, NOTE: An “L” shaped steel lintel must be installed  
or ceramic tile may overlap the black face of the across the top of the firebox opening where facing  
fireplace up to the opening on either side of the materials such as brick or stone is used on the face of  
fireplace. Seal all joints between the black fireplace face the firebox. It acts as a support/firestop. It should be  
and the wall covering with a heat-resistant material such attached to the face of the fireplace with screws and  
as rock wool insulation or mortar. Be sure to use high sealed to the fireplace with a heat-resistant sealer.  
temperature adhesive or mortar when anchoring brick,  
stone, or tile to the face of the fireplace.  
CLEARANCES  
3. Mantel Clearances: We have provided 4 different  
situations to position your mantel. See Figure 5.  
4. Floor Clearances: No clearance is required if the  
appliance is installed per these instructions.  
5. Front Clearances: From the Front of the fireplace  
To ensure a safe installation, the following must be  
carefully observed.  
1. Sidewall Clearances: Clearances from the right or  
left side of the fireplace opening to any adjacent  
combustible wall should not be less than 7", facing the  
to any combustible materials should not be any less  
unit.  
than 24”.  
2. Ceiling Clearances: The ceiling height should not  
be less than 42" from the top of the fireplace opening.  
NOTE: Adequate clearance around air openings  
must be maintained. Never cover any openings on  
the appliance with any type material.  
FIGURE 4  
CLEARANCE  
7" MIN.  
FROM FIREPLACE  
42" MIN.  
OPENING TO SIDE WALL  
CLEARANCE  
TO CEILING  
SIDE WALL  
LEFT SIDE  
RIGHT SIDE  
24” CLEARANCE TO FRONT  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MANTEL PROFILES FOR ZERO CLEARANCE CABINET  
MUST BE FOLLOWED  
MANTELS WITH 3/4" BASE  
CEILING  
12"  
3-1/2"  
COMBUSTIBLE  
3"  
MATERIAL  
10"  
COMBUSTIBLE  
MATERIAL  
42"  
3-1/2"  
3/4"  
3/4"  
3"  
2-1/2"  
STAND OFF  
LOUVERS  
HOOD  
2"  
FP-BR10-ZC  
STAND OFF  
LOUVERS  
HOOD  
2"  
FP-BR10-ZC  
Bottom of 3/4" Base or Support  
must be at least 2-1/2" from top  
of Unit if mantel is 10" wide or more.  
Bottom of 3/4" Base or Support  
must be Flush with top of Unit  
if mantel is 10" wide or less.  
MANTELS WITH 2-1/2" BASE  
SUPPORT  
12"  
COMBUSTIBLE  
MATERIAL  
COMBUSTIBLE  
MATERIAL  
12"  
6"  
3"  
SUPPORT  
3"  
2-1/2"  
2-1/2"  
2-1/2"  
STAND OFF  
STAND OFF  
LOUVERS  
HOOD  
LOUVERS  
HOOD  
2"  
2"  
FP-BR10-ZC  
FP-BR10-ZC  
Bottom of 2-1/2" Base or  
Support must be at least  
2-1/2" from top of Unit if  
Bottom of 2-1/2" Base or Support  
must be Flush with top of Unit  
if mantel is 12" wide or less.  
mantel is 12" wide or more.  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION OF MODEL FP - BR10- ZC  
WITH OPTIONAL WOODEN MANTEL  
(1) When choosing the right location for your heater and mantel keep the following in mind:  
NOTE: Due to high temperatures, this heater should be located out of traffic and away  
from furniture and draperies.  
NOTE: Kit No. (PA KDMH10) Deluxe Wooden Mantel for FP-BR10-ZC.  
Kit No. (PA KDM10) Standard Wooden Mantel for FP-BR10-ZC  
NOTE: See page 18 for “Gas Pressure Check”.  
(2) Screen(s) can not be removed or altered (Position screen(s) in the closed position before  
leaving heater unattended).  
(3) Follow instructions for assembly of (Optional) Wooden Mantel. See instructions supplied  
with mantel.  
(4) After mantel has been assembled, slide the heater from the rear into the opening of the  
mantel.  
NOTE: Place a cloth or blanket over the front portions of the mantel as not to scar the wood.  
(5) Center the heater in the opening of the mantel. See Figure 6.  
(6) Fasten mantel to hearth by using ½" wood screws.  
(7) Insert the nine (9) ½" wood screws provided with mantel through slots on nailing flange  
and secure in place. See Figure 6.  
(8) Position mantel and fireplace into desired location.  
(9) To light the heater, see “Lighting Instructions” pages 19 through 30. Make sure you have  
the right gas valve for Natural or LP gas.  
NOTE: Hook gas supply line into heater. Check for leaks using soap and water, not an open  
flame.  
NOTE: When used as a bedroom fireplace, the unit must be attached to the wall. Use the  
angle provided with the mantel. Also the safety screen must be kept mechanically secured  
to the unit as it is when it leaves the manufacturer.  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOP MANTEL  
1/2" WOOD  
SCREWS (9)  
REAR  
OF  
HEATER  
MANTEL BASE  
FIGURE 6  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
AFTER-MARKET MOBILE HOMES  
GAS CONNECTION  
CHECK GAS TYPE: Use only the type of gas indicated on the valve rating plate. If the type of gas  
vlisted on the plate is not your type of gas supply, DO NOT INSTALL . Contact your dealer for  
proper model.  
Always use an external regulator for all LP heaters to reduce the supply tank pressure to a maximum  
of 13” W.C. This in addition to the regulator furnished with the heater.  
The normal gas connection is 3/8” N.P.T. made at the right rear side of the appliance.  
NOTE: The connecting pipe must be internally tinned copper tubing for use with natural gas. Test  
for leaks using a solution of soap and water after completing the connection. DO NOT USE OPEN  
FLAME.  
INSTALLATION SUPPLIES  
Before installing the heater, gather the following materials:  
- external regulator  
- ground joint union  
- sediment trap  
- tee joint  
- pipe wrench  
- sealant (resistant to LP gas)  
(supplied by installer for propane)  
- piping (check local codes)  
- manual shutoff valve*  
- test gauge connection*  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCING ADEQUATE  
VENTILATION  
This section is for residential or manufactured (mobile) installation  
“This heater shall not be installed in a confined space or unusually tight construction unless  
provisions are provided for adequate combustion and ventilation air.”  
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space  
whose volume is less than 50 cubic feet per 1,000 BTU per hour (4.8m 3 per kw) of the  
aggregate input rating of all appliances installed in that space and an unconfined space as a  
space whose volume is not less than 50 cubic feet per 1,000 BTU per hour (4.8m 3 per kw) of  
the aggregate input rating of all appliances installed in that space. Rooms communicating  
directly with the space in which the appliances are installed, through openings not furnished  
with doors, are considered a part of the unconfined space.  
Unusually tight construction is defined as construction where:  
a) Walls and ceilings exposed to the outside atmosphere have a continuous water vapor  
retarder with a rating of 1 perm (6 x 10-11 kg per pa-sec-m2) or less with openings gasketed or  
sealed;  
b) Weather stripping has been added on openable windows and doors, and  
c) Caulking or sealants are applied to areas such as joints around window and door frames,  
between sole plates and floors, between wall-ceiling joints, between wall panels, at  
penetrations for plumbing, electrical, and gas lines, and at other openings.  
NOTE: SOME AREAS IN THE UNITED STATES HAVE HIGHER REQUIREMENTS  
FOR CUBIC FEET PER 1000 BTU/ HOUR INPUT. (EX. CINCINNATI, OHIO CODES  
REQUIRE 70 CUBIC FEET). CHECK YOUR LOCAL CODE BEFORE  
INSTALLATION.  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DETERMINING FRESH-AIR FLOW FOR  
HEATER LOCATION  
DETERMINE IF YOU HAVE A CONFINED OR UNCONFINED SPACE  
Use this worksheet to determine if you have confined or unconfined space.  
SPACE: Includes the room in which you will install heater plus adjoining rooms with  
doorless passageways or ventilation grills between the rooms.  
1. Determine the volume of the space (length x width x height).  
Length x Width x Height =_________cu.ft.(volume of space)  
EXAMPLE: 20 ft.(Length) x 16 ft.(Width) x 8 ft.(ceiling Height)=  
2560 cu. ft. (volume of space)  
If additional ventilation to adjoining room is supplied with grills or openings, add the  
volume of these rooms to the total volume of the space.  
2. Divide the space volume by 50 cubic feet to determine the maximum BTU/Hr the  
space can support.  
_________(volume of space)/50 cu. ft. =maximum BTU/Hr the space can support)  
EXAMPLE: 2560 cu. ft. (volume of space /50 cu. Ft .= 51.2 or  
51200 (maximum BTU/Hr the space can support)  
3. Add the BTU/Hr of all fuel burning appliances in the space.  
Vent-free heater  
Gas water heater*  
Gas furnace  
Vented gas heater  
Gas fireplace logs  
Other gas appliances*  
Total  
_______________BTU/Hr  
_______________BTU/Hr  
_______________BTU/Hr  
_______________BTU/Hr  
_______________BTU/Hr  
+ _______________BTU/Hr  
= _______________BTU/Hr  
Example: Gas water heater 40000 BTU/Hr  
Vent-free heater + 18000 BTU/Hr  
Total  
= 58000 BTU/Hr  
*Does not include direct-vent gas appliances. Direct-vent draws combustion air  
from the outdoors and vents to the outdoors.  
4. Compare the maximum BTU/Hr the space can support with the actual amount of BTU/Hr  
used.  
____________BTU/Hr (maximum the space can support)  
____________BTU/Hr (actual amount of BTU/Hr used)  
Example: 51200 BTU/Hr (maximum the space can support)  
58000 BTU/Hr (actual amount of BTU/Hr used)  
The space in the above example is a confined space because the actual BTU/Hr used is more  
than the maximum BTU/Hr the space can support. You must provide additional fresh  
air. Your options are as follows:  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an  
unconfined space, remove door to adjoining room or add ventilation grills between rooms. See  
“Ventilation Air From Inside Building”, page 21.  
B. Vent room directly to the outdoors. See “Ventilation Air From Outdoors”, page 22.  
C. Install a lower BTU/Hr heater, if lower BTU/Hr size makes room unconfined.  
If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, the  
space is an unconfined space. You will need no additional fresh air ventilation.  
VENTILATION AIR  
VENTILATION AIR FROM INSIDE BUILDING  
This fresh air would come from an adjoining unconfined space. When venting to an adjoining space,  
you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the  
floor on the wall connecting the two spaces. (See Options 1 and 2, Figure 7.) You can also remove door  
into adjoining room. (See Option 3, Figure 7.)  
NOTE: Each opening shall have a minimum free area of 1 square inch per 1000 BTU’s per hour of the  
total input ratings of all gas utilization equipment in the confined space, but not less than 100 square  
inches.  
Figure 7 Ventilation Air From Inside Building  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTILATION AIR FROM OUTDOORS  
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent  
openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items  
directly to the outdoors. These spaces include attics and crawl spaces. Follow the National  
Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, “Air For Combustion and Ventilation” for  
required size of ventilation grills or ducts.  
IMPORTANT: Do not provide openings for inlet air into attic if attic has a thermostat-  
controlled power vent. Heated air entering the attic will activate the power unit.  
Ventilated Attic  
Outlet Air  
To Attic  
Outlet Air  
To Crawl  
Space  
Inlet Air  
Ventilation  
To Crawl Space  
Inlet Air  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS PRESSURE CHECK  
Check the inlet pressure to the burner to insure that it is as shown in the table below.  
NOTE: The pressure check point is located on the right side of the valve facing burner.  
The appliance and its appliance main gas valve must be disconnected from the gas supply  
piping system during any pressure testing of that system at test pressures in excess of 1/2  
psi (3.5kPa).  
The appliance must be isolated from the gas supply piping system by closing its equipment  
shut-off valve during any pressure testing of the gas supply piping system at test pressures  
equal to or less than 1/2 psi (3.5 kPa).  
MODEL  
Gas  
FP-BR10-ZC  
Natural  
FP-BR10-ZC  
Propane  
Maximum Heat Input  
Gas Inlet Pressure:  
Maximum  
Minimum  
Manifold Pressure  
10000  
10000  
10.5 ins. W.C.  
* 5 ins. W.C.  
3.5 ins. W.C.  
13 ins. W.C.  
*11 ins. W.C.  
9 ins. W.C.  
NOTE: On initial installation it may be necessary to bleed out air in the gas lines. Do this by  
holding the control knob and turning the knob to the pilot position for about 30 seconds.  
To check the Regulator pressure, remove the pressure tag plug at the left side of the Regulator  
facing the heater. The pressure should be checked with the heater burning and the control set  
on high. After measuring the pressure, replace the pressure tap plug,ensuring that there are no  
leaks.  
* For the purpose of minimum input adjustment.  
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOG PLACEMENT  
Logs are shipped secured in unit.  
NOTE: When operated for the first time, logs may emit a “paper burning” smell. This  
smell will gradually diminish and will be totally eliminated after the first few hours of  
operation. Do not use the blower at this time.  
Front View of Logs  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING INSTRUCTIONS  
Before operating this appliance, proceed through the following checklist  
.
1. Read and understand these instructions before operating this appliance.  
2. Check that there no leaks. If you smell gas do not attempt to light this appliance.  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FLAME CHECK  
A periodic check of the flames should be made. The pilot flame should always be present when  
the gas logs are in operation.  
FLAME: Propane (LP) should produce a flame that is 3"-4" above rear log. This flame should  
be yellow.  
Natural gas should produce a flame that is 3"-4" above rear log. This flame should  
be mostly blue except for the top 1/2" which should be yellow.  
FLAME  
NATURAL  
PROPANE  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING DIAGRAM  
THERMOSTAT  
JUMPER  
MOTOR  
JUMPER  
JUMPER  
WHITE  
GREEN  
BLACK  
RHEOST  
BLACK  
POWER CORD  
Figure 10  
NOTE: “If any of the original wire as supplied with the appliance must be replaced, it must be  
replaced with a wire of at least a 105o C. temperature rating.”  
NOTE: Installation and repair should be done by a qualified service person. This heater  
should be inspected before use and at least annually by a qualified service person. More  
frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.  
It is imperative that control compartments and circulating air passageways of the heater be  
kept clean.  
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can  
cause improper and dangerous operation.  
Verify proper operation after servicing.  
Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE:  
#PESBRO84 Blower Motor  
Rating: 120 volts/60HZ/0.54 Amps. 1 P.H  
NOTE:  
For convenience, allow licensed electrician to install properly grounded  
3-plug receptacle near unit.  
Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFEGUARDS  
Although your gas logs are very realistic in appearance, it is not a real burning fireplace and must not be  
used for burning rejected material.  
To avoid irreparable damage to the heater or personal injury, matches, paper, garbage, or any other  
material must not be placed or thrown on top of the logs or into the flames.  
To avoid personal injury, do not touch hot surfaces when the heater is operating.  
Close supervision is necessary when the heater is being operated near children.  
CLEANING  
:
The appliance must be turned “OFF” before cleaning inside the firebox (burn  
area), make sure the pilot is “OFF” completely and the appliance has cooled.  
All cleaning should be carried out when the heater is cold. Limited cleaning is required  
with normal use. Dusting the front of the base, the top of the piezo cover, or the control  
knob panel may be required occasionally. Do not use cleaning fluids to clean the logs or  
any other part of the heater.  
If the flames show unusual shapes or behavior, or if burner fails to ignite properly, the  
burner holes may require cleaning. If this occurs, contact your nearest dealer to service the  
heater.  
The heater can be cleaned by removing the logs. Lift the logs gently, as not to damage the  
fiber pieces. The logs have been spot glued in place for shipping, use caution when  
removing. Lift each log by holding it carefully at each end. Use a vacuum cleaner to  
remove dust and loose particles from the base, logs and around the burner and ODS/Pilot.  
Gloves are recommended to prevent fibers from breaking the skin. If skin is broken, clean  
with soap and water.  
Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
POSSIBLE  
CAUSE  
OBSERVED  
PROBLEM  
SOLUTION  
1. I g n i t e r  
e l e c t r o d e  
1. Igniter button is pressed,  
no spark at ODS/Pilot  
1. Replace igniter  
positioned incorrectly.  
2. Igniter electrode broken  
3. Igniter electrode not con-  
nected to igniter cable  
4. Igniter cable pinched or  
wet  
2. Replace igniter  
3. Reconnect igniter cable  
4. Free igniter cable if  
pinched by any metal or  
tubing. Keep igniter  
cable dry.  
5. Piezo igniter nut is loose  
5. Tighten nut holding  
piezo igniter to heater  
cabinet. Nut is located  
inside heater cabinet at  
top  
6. Broken igniter cable  
7. Bad piezo igniter  
6. Replace igniter cable  
7. Replace piezo igniter  
1. Gas supply turned off or  
manual shutoff valve is  
closed  
2. Igniter button is pressed  
Spark at ODS/Pilot  
No Ignition  
1. Turn on gas supply or  
open manual shutoff  
valve  
2. Control knob not in  
“PILOT” position  
3. Control knob not pressed  
in while in “PILOT”  
position  
2. Turn control knob to  
“PILOT” position  
3. Press in control knob  
while in “PILOT”  
position  
4. Air in gas lines when  
installed  
4. Continue to hold down  
control knob. Repeat  
igniting operation until  
air is removed.  
Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Contact local propane  
gas company  
6. Clean ODS/Pilot or  
replace ODS/Pilot  
assembly  
5. Depleted gas supply  
6. ODS/Pilot is clogged  
7. Replace gas regulator  
7. Gas regulator setting is not  
correct  
3. ODS/Pilot lights but  
flame goes out when  
control knob is released  
1. Press control knob  
completely  
1. Control knob is not fully  
pressed in  
2. Control knob not pressed  
in long enough  
2. After ODS/Pilot lights  
keep control knob  
pressed 30 seconds  
3. Wait 1 (one) minute for  
safety interlock system  
to reset  
3. Safety interlock system  
has been triggered (if  
equipped)  
4. Fully open manual  
shutoff valve  
4. Manual shutoff valve not  
fully open  
5. Hand tighten until snug,  
then tighten 1/4 turn  
6. Contact local propane  
gas company. Clean  
ODS/Pilot (See  
5. Thermo-couple connection  
loose at control valve  
6. Pilot flame not touching  
thermo-couple, which  
allows thermo-couple to  
cool causing pilot flame to  
go out. This problem can  
be caused by one or both  
of the following:  
“Cleaning and  
Maintenance”), or  
replace ODS/Pilot  
assembly  
A) low gas pressure  
B) dirty or partially  
clogged ODS/Pilot  
7. Control valve damaged  
7. Replace valve control  
4. Burner does not light after  
ODS/Pilot is lit  
1. Clean burner (See  
“Cleaning and  
1. Burner orifice is clogged  
Maintenance”) or  
replace burner orifice  
2. Contact local propane  
gas company  
2. Inlet gas pressure is too  
low  
5. Delayed ignition of burner  
1. Contact local propane  
gas company  
1. Manifold pressure is too  
low  
2. Clean burner (“See  
Cleaning and Mainten-  
ance”) or replace burner  
orifice  
2. Burner orifice is clogged  
Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Burner backfiring during  
combustion  
1. Burner orifice is clogged  
or damaged  
1. Clean burner (See “Clean-  
ing and Maintenance “) or  
replace burner orifice  
2. Burner damaged  
2. Replace Burner  
3. Gas regulator defective  
3. Replace gas regulator  
7. Slight smoke or odor  
during initial operation  
1. Residues from  
1. Problem will stop after a  
few hours of operation  
manufacturing process  
8. Heater produces a whist-  
ling noise when burner is  
lit  
1. Turning control knob to  
“HI” position when  
burner is cold (if  
1. Turn control knob to  
“LOW” position and allow  
to warm  
equipped with this type  
of valve)  
2. Air in gas line  
2. Operate burner until air is  
removed from line. Call  
local propane company to  
check gas line.  
3. Air passageways on  
heater blocked  
4. Dirty or partially  
clogged burner orifice  
3. Observe minimum  
installation clearances  
4. Clean burner or replace  
orifice  
Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT: Operating heater where impurities in the air exist may create odors. Cleaning  
supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc.  
create fumes. These fumes may mix with combustion air and create odors.  
1. Metal expands while  
heating or contracts  
while cooling.  
1. This is common with most  
heaters. If noise is  
9. Heater produces a  
clinking/ticking noise  
just after burner is lit or  
shut off  
excessive, contact a  
qualified service person.  
1. Heater burning vapors  
from paint, hairspray,  
glues, etc. (See  
1. Ventilate room. Stop using  
odor causing products  
10. Heater produces  
unwanted odors  
while heater is running.  
Important above)  
2. Low fuel supply  
3. Gas leak (See  
2. Refill supply tank.  
3. Locate and control all  
leaks. See “Checking Gas  
Connections”.  
WARNING above)  
1. Not enough fresh air is  
available.  
1. Open window/door for  
ventilation  
11. Heater shuts off in use  
(ODS operates)  
2. Low line pressure  
3. ODS/Pilot is partially  
clogged  
2. Contact local propane co.  
3. Clean ODS/Pilot  
1. Gas leak (See  
1. Locate and correct all  
leaks (See “Checking Gas  
Connections”)  
12. Gas odor even when  
control knob is in “OFF”  
position  
WARNING above)  
2. Control valve defect  
2. Replace control valve  
1. Foreign matter between  
control valve and burner  
2. Gas leak (See  
1. Remove foreign matter  
from gas tubing  
2. Locate and correct all  
leaks “See “Checking Gas  
Connections”)  
13. Gas odor during  
combustion  
WARNING above)  
Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICING  
Repair and replacement work should only be performed by a qualified service technician.  
Always shut off the gas supply and make sure heater is cool before beginning any service  
operation. Check for gas leaks after servicing.  
REPAIR PARTS  
A parts list with exploded view follows. Always include correct name, part number, and model  
number of the heater when ordering service parts. Please contact your local dealer or  
Distributor when ordering, or if one is not available, you may contact:  
New Buck Corporation  
P.O. Box 69  
Spruce Pine, NC 28777  
(828)-765-6144  
Page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LIST  
Maxitrol Valve  
KEY #  
PART #  
DESCRIPTION  
QUANTITY  
1
GV 30B5A2L7B  
GV 30B5A2N7B  
PE 4966  
Maxitrol LP Valve  
Maxitrol Nat. Valve  
3/8" - 3/8" Elbow  
1
1
1
1
1
1
1
1A  
2
3
PS 112736  
Maxitrol Regulator Holder  
BR 10 Burner Base  
Single Burner  
4
PS 1024  
5
PO BR10 Burn  
PE TPT100/433  
6
Thermo-couple/ (Copreci)  
7
7A  
PE 21500053  
PE 2150054  
Copreci ODS Nat. Pilot  
Copreci ODS LP Pilot  
1
1
8
8A  
PE RV12LF30  
PE RV12LF90  
Maxitrol Regulator-Nat.  
Maxitrol Regulator-LP  
1
1
9
RF 14ALMTUB  
PH 1166  
1/4" Aluminum Tubing  
3/8" Street Elbow  
1
1
2
1
2
1
1
1
10  
11  
12  
13  
14  
15  
16  
PE 6482  
1/4" -1/8" Compression Adapter  
Orifice Nat. or LP  
PO Orifice  
PS 112726  
M1127 Burner Supports  
3/8" x 6 - 3/4" Burner Tube  
Angled Orifice Holder  
Blower Motor  
PO 38634ALMTUB  
PO 54ORFHLD  
PESBRO84  
Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWN UP VIEW OF BURNER ASSEMBLY  
*16 Not shown on this page. See page 25, figure 10 for wiring diagram.  
Page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEW BUCK CORPORATION  
We reserve the right to amend these specifications at any time without notice. The only  
warranty applicable is our standard written warranty. We offer no other warranty, expressed or  
implied.  
LIMITED WARRANTY  
MODEL FP-BR10-ZC  
New Buck warrants this product to be free from defects in materials and components for two  
(2) years from the date of first purchase, provided that the product has been properly installed,  
operated, and maintained in accordance with all applicable instructions. To make a claim  
under this warranty the Bill of Sale or canceled check must be presented.  
This warranty is extended only to the original retail purchaser and covers the cost of parts  
required to restore the heater to proper condition. Warranty parts MUST be obtained through  
an authorized Buck Stove dealer and/or New Buck, who will provide original factory  
replacement parts. Failure to use original factory replacement parts voids this warranty. The  
heater must be installed by a qualified installer in accordance with all local codes and  
instructions furnished with the unit.  
Warranty does not apply to parts that are not in original condition, normal wear and tear, or  
parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance  
or defects caused by improper installation.  
WARRANTY DOES NOT COVER:  
- Removal and re-installation cost  
- Labor costs for replacements or repairs  
- Transportation  
- Cost of service call to diagnose trouble  
- Painted surfaces  
- Damage or defect caused by improper installation, accident, misuse, abuse, or alteration  
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT  
GOVERNS THE SALE OF THE PRODUCT, THIS EXPRESS WARRANTY EXCLUDES  
ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION  
OF ANY AND ALL WARRANTIES, INCLUDING WARRANTIES OF  
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO ONE (1)  
YEAR FROM THE DATE OF FIRST PURCHASE. NEW BUCK LIABILITY IS HEREBY  
LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND NEW BUCK SHALL  
NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING  
INCIDENTAL OR CONSEQUENTIAL DAMAGES.  
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or  
limitation of incidental or consequential damages, so the above limitation on implied  
warranties, or exclusion on damages may not apply to you.  
This warranty gives you specific legal rights. Other rights may vary from state to state.  
Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Cooktop KM 6314 User Manual
Milwaukee Impact Driver 0779 20 User Manual
MTD Chipper 246 641A000 User Manual
MTD Tiller 214 031 000 User Manual
Multi Tech Systems Network Card ZDX Series User Manual
National Instruments Switch NI 78xxR User Manual
NHT Speaker Evolution System User Manual
Nortel Networks Network Router 142 User Manual
Omron Healthcare Fitness Electronics HJ 303 User Manual
Panasonic Telephone KX TC1230NZW KX TC1230ALW User Manual