Multiquip Portable Generator EGC 750C User Manual

750kW Containerized  
Diesel Generator Set  
Model  
Emissions  
Standby Rating  
Prime Rating  
60 Hertz  
EGC-750C  
EPA Certified  
750kW (937kVA)  
600kW (750kVA)  
750 KW  
(Shown with 40 ft. container and optional ISO trailer chassis)  
Standard Features  
Cummins Heavy Duty Diesel Engine  
Full Load Acceptance  
4-cycle design, turbocharged, aftercooled, direct injection  
Polymide blade cooling fan  
Accepts 100% of standby nameplate rating in one step, in compliance  
with NFPA, para 5-13.2.6  
Engine coolant heater  
Generator Control Panel  
Meets EPA emissions standards for mobile off-highway  
InteligenTM vibration-isolated controller  
Manual or remote engine start/stop  
RS232/Modbus communication support  
Safety shutdowns  
Fuel System  
1000 gallon, single wall fuel tank  
Fuel priming system  
Fuel/water separators and drip pan  
Electric fuel pump  
Externally mounted emergency stop switch  
Generator mainline circuit breaker, 100% rated electronically  
operated, UL listed  
External fuel fill  
Specially Designed Container  
®
30 micron Racor fuel filter system  
40 ft. ISO container, sound-attenuated, foam-lined for extremely  
quiet operation  
Alternator  
Brushless, 4-pole, synchronous, WYE connection  
Isolated operator control room  
Class H insulation system conforms to NEMA MG1-22, BS5000,  
CSA-C22-2, IEC-34-1 standards for temperature rise  
Solidly mounted battery rack and cooling system  
Intregral vibration isolators  
Drip-proof, self-venting, amortisseur windings  
Exterior polyurethane coating system provides long life in extreme  
operating conditions  
Epoxy impregnated windings with tropical insulation for increased  
environmental protection and long life  
Interior DC lights and timer switch  
Electronic Voltage Regulator  
Critical grade silencer with heat blankets  
Electronic automatic voltage regulator provides precise regulation  
Warranty  
Engine-generator sets are covered by an express written, one-year  
limited warranty  
Separate three-phase excitation for fast recovery from block loads  
and motor starting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
750kW Containerized  
Diesel Generator Set  
Cooling System  
Exhaust Manifold Type  
Radiator Design  
Dry  
Standard horizontal discharge  
Coolant Capacity - Engine and Radiator  
Water Pump Design/Type  
Coolant Flow  
53 gal. (201 L)  
Belt Driven, Centrifugal  
235 gal/min (889.5 L)  
27860 BTU/min (29.5 kW)  
42.7 hp (32.0 kW)  
Heat Rejection to Coolant (Standby)  
Fan Horsepower  
Inteligen Digital Genset Controller  
Digital Controller Features  
Fuel System  
Large graphic back-lit LCD display 128x64 pixel resolution  
Automatic and manual starting and stopping  
Phase sequence supervision  
Recommended Fuel  
Filter Micron Size - 98% Efficiency  
Total Fuel Flow  
ASTM-D975-No.1 or No. 2-D  
2
99 gal./hr. (374.7 L/Hr.)  
Automatic shutdown/alarm function  
Fuel Consumption  
Input frequency 50-60 Hz  
Diesel Fuel @ % of Load  
gal/hr  
16.0  
26.2  
40.5  
54.7  
L/hr  
61  
Parameters adjustable via PC or iG keyboard  
25%  
50%  
99  
Predefined and user definable configurations available.  
One configuration includes set of inputs/outputs and parameters  
75%  
153  
207  
100%  
Adjustable parameters for each configuration  
6 LED indicators  
Push buttons for simple control  
4 programmable outputs (out of 20 functions selection)  
4 binary configuration inputs  
Standby  
o
895 F  
Prime  
o
850 F  
Exhaust System  
Lamp test during start up  
Exhaust Temperature at Rated kW  
o
(479.4 C)  
o
(454.4 C)  
Real time clock  
6160 cfm  
(174.3 m3/min)  
5546 cfm  
(157 m3/min)  
Sealed membrane panel to IP65  
180 x 113 mm front panel mounted case  
Speed measurement from magnetic pickup  
Exhaust Flow at Rated kW  
Silencer Type  
Critical  
Maximum Allowable Backpressure  
Exhaust Outlet Size at hook-up  
41 in/wc (10.2 kPa)  
2 x 8 in.  
Oil pressure, Coolant temperature, Battery voltage and Fuel level  
measurements  
Running Hour Meter  
All Generator metering, kVAr, kW, V1-V3, Hz, I1-I3, kWh, kVAh  
Generator under/over voltage alarm/shutdown  
Generator under/over frequency alarm/shutdown  
Over Current alarm/shutdown  
Derating (60Hz)  
Ambient  
Temperature  
Altitude  
The engine may be operated up to 5000 ft.  
altitude and 95oF ambient temperature at the  
Standby rating, without derating. For  
operation at higher altitudes and ambient  
temperatures, the power should be derated  
according to the following factors:  
Warm up and cooling functions  
Above 5000ft. Above 95°F  
derate at 4% derate at 1%  
per 1000 ft. per 10°F  
Pre-lubrication function with timers  
Adjustable crank attempts  
Data logging  
Remote communications (RS232/Modbus)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
750kW Containerized  
Diesel Generator Set  
Optional Features and Accessories  
Container  
Generator Set  
ISO Trailer Chassis (40 ft.)  
Genset-to-Genset Paralleling Control System  
Double-wall Fuel Tank (900-gallon capacity)  
Fluid Containment  
Base Load-to-Utility Paralleling Control System  
Custom Outlet Panels  
Manual Fuel Valves (For Internal or External Fuel  
Supply)  
Rotary Voltage Selector Switch (High Wye/Low Wye  
Voltages)  
Entrance Ladder (6-Step, Aluminum Construction)  
Auxiliary Oil Reservoir with Level Control (15-gallon)  
Centrifugal Oil Filter System  
Fueling Ladder (Aluminum Step Construction with  
Hand Rail)  
Oil Pan Heater with Thermostat  
Interior Lights (AC Work lights)  
Alternator Strip Heater  
Custom Paint Colors (Artic White is Standard)  
AC Battery Charger with Shore Power Receptacle  
SPECIAL OPTIONS AVAILABLE UPON REQUEST  
40 ft Container  
Weight and Dimensions  
A
B
C
D
96 in.  
(2,438 mm) (12,192 mm) (4,137 mm) (5,054 mm)  
480 in.  
163 in.  
199 in  
Weight (Wet)*  
37,760 lbs (17,128 kg)  
44,500 lbs (20,185 kg)  
Weight (Wet with trailer)*  
* Weight is approximate. Wet weight does not include fuel.  
Backfeed to a utility system can cause electrocution and/or property damage. Do  
not connect to any building’s electrical system except through an approved device.  
Specifications are subject to change without notice.  
Your MQ Power dealer is:  
MQ POWER  
POST OFFICE BOX 6254  
CARSON, CA 90749  
310-537-3700  
800-421-1244  
FAX: 310-632-2656  
© COPYRIGHT 2007, MQ POWER  
Rev. 1 (03-07) EGC750C  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Napoleon Grills Gas Grill PTM450RB User Manual
NEC Server Express120Bb 6 User Manual
NEC Universal Remote SRU 5030 86 User Manual
Network Instruments Network Router WAN Probe Kit User Manual
NXR Range BX3031 User Manual
Oki Printer ML390 User Manual
Orion Car Audio Car Speaker XTR52 User Manual
Panasonic Air Conditioner CS E18CKE User Manual
Panasonic CD Player DVD K520D User Manual
Patton electronic Network Card 3P MF9 User Manual