Maytag Ventilation Hood ERV 150 User Manual

Installer Manual  
VENTILATION SYSTEMS  
VB0066  
Model Numbers  
HRV-150  
HRV-210  
ERV-150  
ERV-210  
06786-04/12/22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents (cont’d)  
8.0 INSTALLATION OF THE CONTROLS ..................................................22  
8.1 Dimensions and Specifications ................................................22  
8.2 Installation of the Main Control ..........................................22-23  
8.3 Electrical Connection to Optional Controls ..............................24  
8.4 Electrical Connection to the Furnace ......................................24  
9.0 WIRING DIAGRAM ............................................................................25  
10.0 AIR FLOW BALANCING................................................................26-27  
11.0 OVERALL VERIFICATION ..................................................................28  
11.1 Main Controls ..........................................................................28  
11.2 Optional Control ......................................................................28  
12.0 MAINTENANCE / INSTRUCTIONS FOR USER....................................29  
13.0 TROUBLESHOOTING ....................................................................30-31  
14.0 WARRANTY ......................................................................................32  
15.0 REFERENCES....................................................................................32  
About this Manual  
This manual uses the following symbols to emphasize particular information:  
WARNING  
!
010  
Identifies an instruction which, if not followed, might cause serious personal injuries including  
possibility of death.  
CAUTION  
Denotes an instruction which, if not followed, may severely damage the unit and/or its  
components.  
NOTE: Indicates supplementary information needed to fully complete an instruction.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 Service  
1.1 3-D DRAWING  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 Service (cont’d)  
1.2 PARTS ORDERING CHART  
150  
HRV  
150  
ERV  
210  
HRV  
210  
ERV  
No  
Description  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26*  
Double collar port #2  
Wing nut #10-32  
Balancing double collar port  
Inlet ring  
00866  
00874  
02256  
12913  
13504  
13507  
12645  
00886  
02418  
02419  
03117  
02420  
03132  
15770  
00887  
00672  
03096  
01825  
12643  
02253  
12620  
02021  
12459  
03124  
13046  
12895  
00866  
00874  
02256  
12913  
13555  
13507  
12645  
00886  
02418  
02419  
03117  
02420  
03136  
15770  
00887  
00672  
03096  
01825  
12643  
02253  
12620  
02021  
12459  
03124  
13046  
12895  
00866  
00874  
02256  
12913  
13556  
13507  
12645  
00886  
02418  
02419  
03117  
02420  
03133  
15770  
00887  
00672  
03097  
01825  
12649  
02253  
12620  
02021  
12459  
03124  
13046  
12895  
00866  
00874  
02256  
12913  
13506  
13507  
12645  
00886  
02418  
02419  
03117  
02420  
03137  
15770  
00887  
00672  
03097  
01825  
12649  
02253  
12620  
02021  
12459  
03124  
13046  
12895  
Motor assembly  
Electronic board V99  
Square balancing damper  
Door latches (latch)  
Drain connector  
Drain gasket 0.625”DI  
Washer 5/8” ID x 1” OD  
Nut 5/8-18  
Recovery core  
Door assembly  
Door latches (keeper)  
Hinge assembly  
Filter  
Switch E69 10A  
Damper assembly #2  
Plastic balancing damper  
Damper rod  
Double collar port #5  
Damper #1  
Damper actuator assembly  
Electronic box cover  
Thermistor kit  
* Item 26 not shown.  
Please take note that parts not listed are not available; those parts require assembly knowledge that only  
manufacturer can guarantee.  
TO ORDER PARTS: Contact your local distributor  
1.3 Technical Support (for assistance)  
For assistance, call on week days, 8:00 AM to 4:30 PM (Cental Standard Time).  
Technical Support Department  
tel: 1-866-2MAYTAG  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.0 Sizing  
These are the two most common methods used to evaluate the ventilation needs of a house:  
CSA F326 and Canadian Building Code:  
• High speed:  
10 cfm per room  
20 cfm for the master bedroom and the basement  
• Low speed: 40-60% of high speed  
ASHRAE Standard 62-2001:  
• 0.35 air change per hour  
Refer to ventilation code of your area to determine which method to use.  
Example:  
Second floor  
Main floor  
Laundry  
room  
Bedroom  
Master  
Bedroom  
Kitchen  
#2  
Living room  
Family room  
Dining room  
Bedroom  
#3  
Bedroom #1  
1320 ft2  
1320 ft2  
Basement  
Basement  
1320 ft2  
VH0021A  
CSA F326  
ASHRAE Standard 62-2001  
Volume of basement  
Volume of main floor  
Volume of second floor  
10560 ft3  
Kitchen  
(10 cfm)  
10560 ft3  
10560 ft3  
Dining room  
Living room  
Family room  
(10 cfm)  
(10 cfm)  
(10 cfm)  
(20 cfm)  
(10 cfm)  
(10 cfm)  
(10 cfm)  
(10 cfm)  
(10 cfm)  
(10 cfm)  
(10 cfm)  
(20 cfm)  
Total volume  
31680 ft3  
x .35/h  
Master bedroom  
Bedroom #1  
Bedroom #2  
Bedroom #3  
Bathroom #1  
Bathroom #2  
Bathroom #3  
Laundry room  
Basement  
11090 ft3/h  
÷ 60 (min/h)  
Total  
150 cfm  
Total  
185 cfm  
(high speed)  
(high speed)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.0  
Unit Type and Defrost Setting vs Geographical Location  
a
and/or  
Tbside  
seZSLETIONCHAR  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.0 Technical Data  
4.1 AIR DISTRIBUTION (NORMAL OPERATION)  
Applicable to all model numbers.  
STALE AIR  
TO OUTSIDE  
FRESH AIR  
FROM  
OUTSIDE  
FRESH AIR  
TO BUILDING  
STALE AIR  
FROM  
BUILDING  
VF0013  
4.2 AIR DISTRIBUTION (DEFROST MODE)  
Defrost Mode 1  
Applicable to model numbers:  
• HRV-150  
• HRV-210  
FRESH AIR  
TO BUILDING  
VF0020  
STALE AIR  
FROM  
BUILDING  
Defrost Mode 2  
Applicable to model numbers:  
• ERV-150  
• ERV-210  
STALE AIR  
TO OUTSIDE  
FRESH AIR TO  
STALE AIR  
FROM  
BUILDING  
BUILDING  
VF0012  
For defrost cycles tables, refer to Section 9.0, Wiring Diagram.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.0 Technical Data (cont’d)  
4.3 PERFORMANCE CHARTS  
MODEL NUMBER: ERV-150  
Electrical requirements: 120 volts, 1.3 Amps  
Exhaust Air Transfer Ratio: 0.06  
225  
200  
175  
150  
125  
100  
75  
VENTILATION PERFORMANCE  
External Static Net Supply  
Gross Air Flow  
Supply Exhaust  
Pressure  
Air Flow  
Pa in. w.g.  
l/s  
cfm  
l/s  
cfm  
l/s  
cfm  
25  
50  
75  
0.1  
0.2  
0.3  
81  
78  
72  
67  
55  
46  
36  
30  
173  
165  
152  
142  
117  
98  
87  
83  
76  
71  
59  
49  
39  
32  
184  
175  
162  
151  
124  
104  
82  
93  
86  
80  
77  
67  
56  
41  
24  
197  
182  
169  
163  
143  
118  
87  
Supply  
(l/s)  
Exhaust  
(l/s)  
100 0.4  
125 0.5  
150 0.6  
175 0.7  
200 0.8  
50  
77  
63  
25  
67  
51  
0
Note: Unit operating at maximum speed.  
VG0041  
0
25  
50  
75  
100  
125  
150  
Gross Airflow - l/s (0.47 l/s = 1 cfm)  
ENERGY PERFORMANCE  
Supply  
Net  
Airflow  
Average  
Sensible Recovery  
Apparent Sensible  
Latent Recovery  
Temperature  
Power  
Watts  
56  
80  
126  
64  
Efficiency  
Effectiveness  
Moisture Transfer  
°C  
0
°F  
32  
32  
32  
5
l/s  
cfm  
60  
100  
137  
65  
%
71  
64  
60  
56  
%
29  
47  
65  
31  
79  
0.53  
0.41  
0.36  
0.41  
HEATING  
COOLING  
0
73  
0
-15  
68  
81  
Total Recovery Efficiency  
35  
95  
28  
59  
52  
45  
MODEL NUMBER: ERV-210  
225  
Electrical requirements: 120 volts, 1.9 Amps  
Exhaust Air Transfer Ratio: 0.06  
200  
175  
150  
125  
100  
75  
VENTILATION PERFORMANCE  
External Static Net Supply  
Gross Air Flow  
Supply Exhaust  
l/s cfm l/s cfm  
Pressure  
Air Flow  
Pa in. w.g.  
l/s  
cfm  
Supply  
(l/s)  
Exhaust  
(l/s)  
25  
50  
75  
0.1  
0.2  
0.3  
109 231  
107 228  
101 214  
116 245  
114 241  
107 227  
101 213  
128 271  
123 260  
118 249  
110 233  
103 217  
100 0.4  
125 0.5  
150 0.6  
175 0.7  
200 0.8  
95  
86  
79  
62  
40  
201  
182  
167  
132  
85  
50  
91  
83  
66  
43  
193  
177  
140  
90  
92  
81  
55  
195  
172  
116  
25  
0
VG0042  
Note: Unit operating at maximum speed.  
0
25  
50  
75  
100  
125  
150  
Gross Airflow - l/s (0.47 l/s = 1 cfm)  
ENERGY PERFORMANCE  
Supply  
Net  
Airflow  
Average  
Sensible Recovery  
Apparent Sensible  
Latent Recovery  
Temperature  
Power  
Watts  
93  
130  
193  
122  
Efficiency  
Effectiveness  
Moisture Transfer  
°C  
0
°F  
32  
32  
32  
5
l/s  
cfm  
110  
157  
203  
110  
%
69  
64  
60  
55  
%
52  
74  
96  
52  
76  
0.45  
0.38  
0.30  
0.26  
HEATING  
COOLING  
0
71  
0
-15  
68  
76  
Total Recovery Efficiency  
35  
95  
50  
106  
89  
41  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.0 Technical Data (cont’d)  
4.3 PERFORMANCE CHARTS (CONTD)  
MODEL NUMBER: HRV-150  
Electrical requirements: 120 volts, 1.3 Amps  
Exhaust Air Transfer Ratio: 0.05  
225  
200  
175  
150  
125  
100  
75  
VENTILATION PERFORMANCE  
External Static Net Supply  
Gross Air Flow  
Supply Exhaust  
Pressure  
Air Flow  
Pa in. w.g.  
l/s  
cfm  
l/s  
cfm  
l/s  
cfm  
Supply  
(l/s)  
Exhaust  
(l/s)  
25  
50  
75  
0.1  
0.2  
0.3  
84  
80  
77  
69  
61  
46  
38  
177  
169  
163  
146  
130  
98  
88  
84  
81  
72  
65  
49  
40  
186  
178  
171  
153  
137  
103  
85  
90  
86  
81  
76  
66  
52  
31  
190  
182  
171  
161  
139  
110  
67  
100 0.4  
125 0.5  
150 0.6  
175 0.7  
50  
25  
81  
Note: Unit operating at maximum speed.  
0
VG0039  
0
25  
50  
75  
100  
125  
150  
Gross Airflow - l/s (0.47 l/s = 1 cfm)  
ENERGY PERFORMANCE  
Supply  
Net  
Airflow  
Average  
Sensible Recovery  
Apparent Sensible  
Latent Recovery  
Temperature  
Power  
Watts  
54  
78  
124  
62  
Efficiency  
Effectiveness  
Moisture Transfer  
°C  
0
°F  
32  
32  
32  
-13  
l/s  
cfm  
64  
97  
%
75  
67  
64  
67  
%
30  
46  
65  
26  
83  
-0.03  
0.01  
-0.02  
0.05  
HEATING  
COOLING  
0
74  
0
-25  
138  
55  
72  
89  
Total Recovery Efficiency  
Not tested  
35  
95  
MODEL NUMBER: HRV-210  
225  
Electrical requirements: 120 volts, 1.9 Amps  
Exhaust Air Transfer Ratio: 0.042  
200  
175  
150  
125  
100  
75  
VENTILATION PERFORMANCE  
External Static Net Supply  
Gross Air Flow  
Supply Exhaust  
l/s cfm l/s cfm  
Pressure  
Air Flow  
Pa in. w.g.  
l/s  
cfm  
50  
75  
0.2  
0.3  
120 253  
118 250  
111 235  
102 216  
124 264  
123 262  
116 245  
106 224  
126 268  
119 251  
114 241  
107 226  
Supply  
(l/s)  
Exhaust  
(l/s)  
100 0.4  
125 0.5  
150 0.6  
175 0.7  
200 0.8  
50  
87  
75  
57  
185  
160  
120  
91  
78  
59  
193  
167  
124  
96  
81  
57  
204  
172  
121  
25  
Note: Unit operating at maximum speed.  
0
VG0040  
0
25  
50  
75  
100  
125  
150  
Gross Airflow - l/s (0.47 L/s = 1 cfm)  
ENERGY PERFORMANCE  
Supply  
Net  
Airflow  
Average  
Sensible Recovery  
Apparent Sensible  
Latent Recovery  
Temperature  
Power  
Watts  
92  
128  
191  
104  
Efficiency  
Effectiveness  
Moisture Transfer  
°C  
0
°F  
32  
32  
32  
-13  
l/s  
cfm  
109  
155  
215  
110  
%
70  
65  
62  
60  
%
51  
73  
77  
-0.01  
-0.02  
-0.01  
0.05  
HEATING  
COOLING  
0
72  
0
-25  
102  
52  
70  
94  
Total Recovery Efficiency  
Not tested  
35  
95  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.0 Technical Data (cont’d)  
4.4 DIMENSIONS  
6" (152mm)  
13-3/4" (349mm)  
30-1/4" (768mm)  
Model numbers:  
• ERV-150  
• HRV-150  
20" (508mm)  
2.5" (63mm)  
VK0040  
6" (152mm)  
Model numbers:  
30-1/4" (768mm)  
19" (483mm)  
• ERV-210  
• HRV-210  
20" (508mm)  
2.5" (63mm)  
VK0039  
4.5 CONTROLS AND FURNACE LINK OPTION  
Main controls:  
Optional control:  
Link option:  
• Basic Wall Control  
• Electronic Wall Control  
• 20/40/60-minute push button  
• Furnace interlock (use with  
forced air systems)  
4.6 SPECIFICATIONS  
Model numbers  
ERV-150, HRV-150  
65 lb (30 kg)  
ERV-210, HRV-210  
73 lb (33 kg)  
Weight  
Port Diameter  
Drain Diameter  
Installation  
6” (152 mm)  
1/2” (12 mm)  
6” (152 mm)  
1/2” (12 mm)  
Chains, springs and hooks (provided with the unit).  
High and low speeds factory set (optional increased low speed - BLUE wire).  
Motor Speed  
Electrical supply  
Power Consumption  
120 V, 60 Hz  
150 Watts  
120 V, 60 Hz  
225 Watts  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.0 Typical Installation  
There are three (3) common installation methods.  
5.1 FULLY DUCTED SYSTEM  
(Primarily for homes with radiant hot water or  
electric baseboard heating. See figure 1.)  
Moist, stale air is exhausted from the high  
humidity areas in the home, such as bathrooms,  
kitchen and laundry room. Fresh air is supplied  
to bedrooms and principal living areas.  
The use of bathroom fans and a range hood is  
suggested to better exhaust stale air.  
Homes with more than one level require at least  
one exhaust register at the highest level.  
See 6.5.1  
VH0024  
figure 1  
for details  
5.2 EXHAUST DUCTED SYSTEM (SOURCE POINT VENTILATION)  
(For homes with forced air heating. See figure 2.)  
Moist, stale air is exhausted from the high  
humidity areas in the home, such as bathrooms,  
kitchen and laundry room. Fresh air is supplied  
to the cold air return or the supply duct of the  
furnace.  
The use of bathroom fans and a range hood is  
suggested to better exhaust stale air.  
Homes with more than one level require at least  
one exhaust register at the highest level.  
NOTE: For this type of installation, it is not  
essential that the furnace blower runs  
when the unit is in operation, but we  
recommend it.  
See 6.5.2  
for details  
VH0025  
figure 2  
5.3 SIMPLIFIED (VOLUME VENTILATION)  
(For homes with forced air heating. See figure 3 or 4.)  
Fresh air and exhaust air flow through the furnace ducts wich simplifies the installation.  
The use of bathroom fans and a range hood is suggested to better exhaust stale air.  
NOTE: For the installation type shown in figure 4, furnace blower should be running when the unit is  
in operation.  
OR  
See 6.5.3  
See 6.5.3  
figure 3  
figure 4  
VH0026  
VH0027  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 Installation  
INSPECT THE CONTENTS OF THE BOX  
Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, door  
latches, door hinges, dampers, duct collars, cabinet, etc.  
Inspect the interior of the unit for damage. Ensure that the fan motor assembly, recovery core, insulation,  
dampers, damper actuator and drain pan are all intact.  
If the unit was damaged during shipping, contact your local distributor. (Claim must be made within  
24 hours after delivery.)  
Use checklist included with the unit to ensure that no parts are missing.  
6.1 ADJUSTING THE DAMPER ROD (FOR ERVS INSTALLED IN WARM REGIONS)  
Refer to Section 4.2 and observe the difference in the damper  
position at the right in diagrams Defrost Mode 1 and Defrost Mode 2:  
for Defrost Mode 1 the damper is completely closed, whereas  
for Defrost Mode 2 the damper is half closed. At the factory, all ERVs  
are assembled for defrost Mode 2. Therefore, if your installation  
is for an ERV in a warm region (zone D as defined in Section 3),  
1
the rod must be moved to position 1 (see figure 5).  
2
NOTE: Before attempting to change the position of the damper  
rod, place the unit on a table for easy access and remove  
the recovery core.  
VO0015  
figure 5  
CAUTION  
This is a delicate operation: to avoid injury proceed carefully and use the appropriate tools.  
6.2 LOCATING AND MOUNTING THE UNIT  
Choose an appropriate location for the unit:  
Within an area of the house where the temperature is above 10°C /  
50°F (basement, attic, furnace room, laundry room, etc.).  
Away from living areas (dining room, living room, bedroom), if possible.  
So as to provide easy access to the interior cabinet and to  
the control panel on the right hand side of the unit.  
Close to an exterior wall, so as to limit the length of the insulated  
flexible duct to and from the unit.  
VD0064  
figure 6  
Close to a drain. If no drain is close by, use a pail to collect  
run-off.  
Away from hot chimneys, electrical panel and other fire haz-  
ards.  
CAUTION  
Make sure the unit is level.  
Allow for a power source (110 V standard outlet).  
Hang the unit to ceiling joists with the 4 chains and  
springs provided (see figures 6 and 7).  
figure 7  
VD0038  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 Installation (cont’d)  
6.3 PLANNING OF THE DUCTWORK  
a) Follow the instructions in Section 6.4 below to determine the appropriate duct diameters for your system.  
b) Keep it simple. Plan for a minimum number of bends and joints. Keep the length of insulated duct to  
a minimum.  
c) Do not use wall cavities as ducts. Do not use branch lines smaller than 4” (102 mm) Ø.  
d) Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or  
a range hood. This would cause clogging of the recovery module. Use sheet metal for the kitchen  
exhaust duct.  
e) Be sure to plan for at least one exhaust register on the highest lived-in level of the house if it has  
2 floors or more.  
6.4 CALCULATING THE DUCT SIZE  
Use the table below to ensure that the ducts you intend to install will be carrying air flows at or  
under the recommended values. Avoid installing ducts that will have to carry air flows near the  
maximum values and never install a duct if its air flow exceeds the maximum value.  
end  
Duct  
Diameter  
Recommended  
Air Flow  
Maximum  
Air Flow  
branches  
5”ø  
4”(102 mm)  
5”(127 mm)  
40 cfm  
75 cfm  
19 l/s 68 m3/h 60 cfm  
28 l/s 102 m3/h  
70 cfm  
35 l/s 127 m3/h 110 cfm 52 l/s 187 m3/h  
main branch  
6”ø 140 cfm  
6”(152 mm) 120 cfm 57 l/s 204 m3/h 180 cfm 85 l/s 306 m3/h  
7”(178 mm) 185 cfm 87 l/s 314 m3/h 270 cfm 127 l/s 459 m3/h  
8”(203 mm) 260 cfm 123 l/s 442 m3/h 380 cfm 179 l/s 645 m3/h  
140 cfm  
VI0003  
NOTE: Examples 6.4.1 and 6.4.2 use imperial measures.  
The same calculation applies to metric measures.  
figure 8  
6.4.1 Example of calculation:  
Problem: My installation requires two exhaust registers (one for the kitchen, one for the bathroom).  
I will connect these registers to a main duct which will connect to the unit (high speed performance  
value of 140 cfm). What size of duct should I use for the main exhaust duct and for the two end  
branches leading to the registers? (See figure 8.)  
Solution: Simplified method. (For a more detailed method of calculating duct size refer to the  
ASHRAE or HRAI HANDBOOK).  
Main duct: Table above indicates a 6” Ø duct: recommended air flow: 120 cfm; maximum air flow:  
180 cfm. The high speed air flow of 140 cfm is close enough to the recommended value (120) and  
far enough away from the maximum value (180). Therefore a 6”Ø duct or larger is an appropriate  
choice for the main exhaust duct.  
End branches: Each end branch will have to transport an air flow of 70 cfm (140 divided by 2). Table  
above indicates a 5”Ø duct: recommended air flow: 75 cfm; maximum air flow: 110 cfm. The high  
speed air flow of 70 cfm is close enough to the recommended value (75) and far enough away  
from the maximum value (110). Therefore a 5”Ø duct or larger is an appropriate choice for the  
2 end branches.  
NOTE: A 4”Ø duct would have been too small because the maximum acceptable value for a 4”Ø  
duct is 60 cfm.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 Installation (cont’d)  
6.4 CALCULATING THE DUCT SIZE (CONTD)  
6.4.2 Example of a design for a fully ducted system for a unit having a high  
speed performance of 222 cfm (See figure 9).  
4”  
4”  
5”  
4” Ø 42 cfm  
4”  
5” Ø  
64 cfm  
4” Ø  
42 cfm  
5” Ø  
65 cfm  
6” Ø 96 cfm  
6”  
4”  
6”  
6” Ø 84 cfm  
6” Ø  
129 cfm  
6” Ø  
6”  
6”  
7”  
7”  
93 cfm  
6” Ø 138 cfm  
7” Ø 222 cfm  
VI0004  
7” Ø 222 cfm  
figure 9  
6.5 INSTALLING THE DUCTWORK AND REGISTERS  
WARNING  
!
010  
Never install a stale air exhaust register in a room where a combustion device is, such as a gas  
furnace, a gas water heater or a fireplace.  
6.5.1 Fully Ducted System (as illustrated in Section 5.1)  
Stale air exhaust ductwork:  
Install registers in areas where contaminants are produced: kitchen, bathrooms,  
laundry room, etc.  
Install registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR  
install them in the ceiling.  
Install the kitchen register at least 4 feet (1.2 m) from the range top.  
If possible, measure the velocity of the air flowing through the registers. If the velocity is high-  
er than 400 ft/min. (122 m/min), then the register type is too small. Replace with a larger one.  
Fresh air distribution ductwork:  
Install registers in bedrooms, dining room, living room and basement.  
Install registers either in the ceiling or high on the walls with air flow directed towards the  
ceiling. (The cooler air will then cross the upper part of the room, and mix with room air  
before descending to occupant level.)  
If a register must be floor installed, direct the air flow up the wall.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 Installation (cont’d)  
6.5 Installing the Ductwork and Registers (cont’d)  
6.5.2 Exhaust Ducted System (Source Point Ventilation) (as illustrated in Section 5.2)  
Stale air exhaust ductwork: (same as for Fully Ducted System, described on page 15)  
Fresh air distribution:  
WARNING  
!
010  
When performing duct connection to the furnace, installation must be done in accordance with all  
applicable codes and standards. Please refer to your local building code.  
CAUTION  
When performing connection to the furnace supply duct, this duct must be sized to support the  
additional airflow produced by the HRV/ERV. Also, use a steel duct with a backdraft damper to pre-  
vent the risk of overheating the HRV/ERV.  
There are two methods for connecting the unit to the furnace:  
Steel duct with  
Method 1: supply side connection  
backdraft damper  
• Cut an opening into the furnace supply duct at least  
18 inches (0.5 m) from the furnace.  
• Connect this opening to the fresh air distribution port  
of the HRV/ERV (use steel duct, see figure 10).  
• Make sure that the HRV/ERV duct forms an elbow  
inside the furnace ductwork.  
minimum  
18” (0.5 m)  
• If desired, interlock (synchronize) the furnace blower  
operation with the HRV/ERV operation.  
(See Section 8.4).  
VD0040  
figure 10  
Method 2: return side connection  
• Cut an opening into the furnace return duct not less than  
10 feet (3.1 m) from the furnace (A+B).  
A
• Connect this opening to the fresh air distribution port of  
the HRV/ERV (see figure 11).  
NOTE:For Method 2, it is not essential that the furnace  
blower runs when the HRV/ERV is in operation,  
but we recommend it. If desired, synchronize the  
furnace blower operation (see Section 8.4).  
B
VD0041  
A+B= not less  
than 10’ (3.1 m)  
figure 11  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 Installation (cont’d)  
6.5 Installing the Ductwork and Registers (cont’d)  
6.5.3 Simplified installation (Volume Ventilation) (as illustrated in Section 5.3)  
WARNING  
!
010  
When performing duct connection to the furnace, installation must be done in accordance with all  
applicable codes and standards. Please refer to your local building code.  
CAUTION  
When performing connection to the furnace ducts (Method 1), these ducts must be sized to  
support the additional airflow produced by the HRV/ERV. Also, the supply duct must be a steel  
duct with a backdraft damper to prevent the risk of overheating HRV/ERV.  
There are two methods (figures 12 and 13) for connecting the unit to the furnace:  
Method 1: return-supply  
Method 2: return-return  
Steel duct with  
backdraft damper  
minimum  
18” (0.5 m)  
A
A+B= not less  
than 10’ (3.1 m)  
B
A
B
minimum 3’  
VD0043  
(0.9 m)  
figure 13  
A+B= not less  
than 10’ (3.1 m)  
VD0042  
figure 12  
Stale air intake:  
• Cut an opening into the furnace return duct (not less than 10 feet (3.1 m) from the  
furnace (A+B)).  
• Connect this opening to the stale air intake port on the HRV/ERV as shown .  
CAUTION  
If using Method 2, make sure the furnace blower operation is synchronized with the HRV/ERV  
operation! See Section 8.4.  
Fresh air distribution: (same instructions as for Method 1 or Method 2, Section 6.5.2).  
For method 2 (return-return) make sure there is a distance of at least 3 feet (0.9 m) between  
the 2 connections to the furnace.  
NOTE: For Method 1, it is not essential to synchronize the furnace blower operation  
with the HRV/ERV operation, but we recommend it.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 Installation (cont’d)  
6.6 CONNECTING DUCTS TO THE UNIT  
Insulated flexible duct  
Use the following procedure for connecting the insulated flexible duct to the ports on the unit (exhaust to  
outside and fresh air from outside).  
a) Pull back the insulation to expose the flexible duct.  
b) Connect the interior flexible duct to the port using a duct tie.  
c) Carefully seal the connection with duct tape.  
d) Pull the insulation over the joint and tuck it between the inner and outer rings of the double collar.  
e) Pull the vapor barrier over the insulation and over the outer ring of the double collar.  
f) Apply duct tape to the joint making an airtight seal. Avoid compressing the insulation when you pull the  
tape tightly around the joint. Compressed insulation loses its R value and causes water dripping due  
to condensation on the exterior surface of the duct.  
CAUTION  
Make sure that the vapor barrier on the insulated ducts does not tear during installation to avoid  
condensation within the duct.  
a)  
b)  
c)  
d), e)  
f)  
VJ0003  
VJ0004  
VJ0002  
VJ0001  
VJ0005  
Rigid duct:  
Use duct tape to connect the rigid ducts to the ports.  
CAUTION  
Do not use screws to connect rigid ducts to the ports.  
Make sure that the 2 balancing dampers are left in a fully open position before connecting the ducts to  
these ports (fresh air distribution port and stale air exhaust port as shown on figure 14).  
VJ0009  
figure 14  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 Installation (cont’d)  
6.7 INSTALLING THE EXTERIOR HOODS  
CAUTION  
All models require an exhaust hood with a backdraft damper. This damper closes when the unit is  
off and prevents unwanted cold air from entering the house.  
6”Ø  
(152 mm)  
Choose an appropriate location for  
installing the exterior hoods:  
Intake  
hood  
a minimum distance of 6 feet (1.8 m)  
between the hoods to avoid  
cross-contamination  
18”  
(457 mm)  
Exhaust  
hood  
18”  
(457 mm)  
a minimum distance of 18 inches (457 mm)  
from the ground  
6’  
(1.8 m)  
6’  
(1.8 m)  
Make sure the intake hood is at least 6 feet  
(1.8 m) away from any of the following:  
dryer exhaust, high efficiency furnace  
vent, central vacuum vent  
gas meter exhaust, gas barbecue-grill  
any exhaust from a combustion source  
garbage bin and any other source of  
contamination  
18”  
(457 mm)  
Optional duct  
location  
Tape and duct tie  
Caulking  
Refer to figure 15 for connecting the insulat-  
ed duct to the hoods. Place the “FRESH  
AIR INTAKE” sticker, provided in the instal-  
lation kit, on corresponding hood. An “Anti-  
Gust Intake Hood” should be installed in  
regions where a lot of snow is expected to  
fall.  
VD0028  
figure 15  
6.8 CONNECTING THE DRAIN  
12"(305 mm)  
1
2
3
VO0004  
VO0003  
VO0005  
Cut 2 sections of plastic tubing,  
about 12” (305 mm) long and  
attach them to each drain fitting.  
Attach the 2 plastic drain fittings  
to the unit using the gaskets,  
washers and nuts as shown.  
Join the 2 short sections to the “T”  
junction and main tube as  
shown.  
Make a water trap loop in the tube to prevent the unit from drawing  
unpleasant odors from the drain source. Make sure this loop is  
situated BELOW the “T” as shown. This will prevent water from  
being drawn back up into the unit in case of negative pressure. Run  
the tube to the floor drain or to an alternative drain pipe or pail. Be  
sure there is a slight slope for the run-off.  
Tie-wrap  
To drain  
4
VO0011  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.0 Control Devices  
7.1 Main Controls  
CAUTION  
All models require a main control.  
Basic model  
Electronic model  
CONDENSATI0N CONTROL  
CONDENSATI0N CONTROL  
C
-20  
-4  
C
C
-4  
F
-5  
41  
F
41  
F
AIR SUPPLY CONTROL  
CONDENSATION CONTROL  
MAXIMUM SPEED  
OFF  
AIR EXCHANGE IN PROGRESS  
AIR SUPPLY CONTROL  
MIN.  
AIR  
EXCHANGE  
MIN.  
MAX.  
20 MIN  
ON  
40 MIN.  
OFF  
MAX.  
CONTINUOUS  
INTERMITTENT  
VC0028  
VC0027  
MODELS  
Basic Electronic  
OFF Position  
X
X
X
X
X
X
X
X
X
X
Intermittent exchange (TBI) 20 ON - 40 OFF  
Low speed continuous exchange  
High speed continuous exchange  
Condensation control (Temperature scale)  
Mode indicator  
X
X
X
X
Detector  
types  
Air exchange indicator  
Condensation/Pollutant control max speed indicator  
Maintenance indicator with flashing intermittent  
Sliding button  
X
Switches  
Push button  
X
7.2 OPTIONAL CONTROL  
20/40/60-MINUTE PUSH-BUTTON TIMER:  
This remote illuminated switch is typically installed in bathrooms, kitchen and laundry room to provide  
20, 40 or 60 minutes of high speed ventilation at the push of a button. The switch is supplied and mounted  
on a white single gang wall plate.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.0 Control Devices (cont’d)  
7.3 OTHER FEATURES  
FURNACE INTERLOCK (for forced air heating system)  
The furnace fan can be interlocked so that it will run simultaneously with the ERV or HRV to ensure proper  
distribution of fresh air throughout the house (see table section 7.4, to see if it is available on your unit).  
PERMANENT MEMORY  
Our electronic controls have a default memory feature in the event of a power outage. Even the date of the  
last service reminder is maintained as a convenience to the homeowner.  
CONTROL UPGRADES  
All controls can be used on any ERV, so a Basic control can be upgraded to the Electronic in the future  
(see table in Section 7.4 below for control availability according to the units).  
7.4 MAIN AND OPTIONAL CONTROLS AVAILABLE FOR YOUR UNIT  
MAIN CONTROLS  
OPTIONAL CONTROL  
Model number  
BASIC ELECTRONIC 20/40/60-min. push-button timer Furnace Interlock  
ERV-150  
HRV-150  
ERV-210  
HRV-210  
X
X
X
X
X
X
X
X
X
X
X
X
Integrated  
Integrated  
Integrated  
Integrated  
7.5 SPECIAL COLD WEATHER TBI MODE FOR ERVS  
The enthalpic core installed in ERVs requires extra protection when the outside temperature drops below  
-15°C (5°F).  
A special operating mode called TBI (Time-Based Intermittent) is activated under these conditions.  
Characteristics of cold weather TBI mode  
• activated when the outside temperature drops below -15°C (5°F).  
• 20/40 cycle (20 minutes LOW speed followed by 40 minutes OFF).  
• usual control of air supply via the main wall control is suspended (except for the OFF position).  
• optional control (20/40/60-minute push button) retain its temporary high speed activation capability.  
• deactivated when the outside temperature warms up higher than -15°C (5°F).  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.0 Installation of the Controls  
8.1 DIMENSIONS AND SPECIFICATIONS (MAIN CONTROLS)  
13/8"  
(35 mm)  
Voltage:  
Dimensions: 5” x 5” x 1 3/8”  
12 volts DC  
5" (127 mm)  
(127 mm x 127 mm x 35 mm)  
VC0016  
FRONT VIEW  
SIDE VIEW  
8.2 INSTALLATION OF THE MAIN CONTROL  
(BASIC AND ELECTRONIC)  
CAUTION  
Never install more than one main control per unit.  
INSTRUCTIONS:  
1- Determine the location of the control. The wall control must be installed in a central location on the  
main floor. Typical locations for these controls are kitchen, main hallways and family room.  
2- Remove the button(s) and the cover plate of the control.  
VC0026  
ELECTRONIC  
BASIC  
2" (5 cm)  
3- Install the wall control 60 inches (1.5 m) from the floor and  
leave a free space of at least 2 inches (5 cm) to the right of  
the control to allow user to slide out the control instructions.  
Use the template provided in the control box to position the  
wire hole and the screw holes. Use the screws and the plastic  
anchors provided in the installation kit to secure the control.  
(See figure 16.)  
60" (1.5 m)  
VD0025  
figure 16  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.0 Installation of the Controls (cont’d)  
8.2 INSTALLATION OF THE MAIN CONTROL (cont’d)  
4- Connect the wires to the main control.  
(See figure 17.)  
figure 17  
5- Make sure the instruction pull-out is in the  
occupant’s language. If not, turn it to the other side.  
(See figure 18.)  
6- Reinstall the cover plate and the button(s).  
VC0061  
figure 18  
7- Connect the wires to their corresponding position inside the  
electrical compartment. Make sure the connections of the unit  
and of the wall control correspond exactly. (See figure 19.)  
Y R G B  
B
Y R G  
OL  
I OC  
F F  
VE0072  
figure 19  
8- Connect the optional control (if applicable) by referring to Section 8.3.  
9- Do the appropriate connection to the furnace (if applicable) by referring to Section 8.4.  
10- NOTE: If the unit is installed in a cold region (Zone A, as defined in Section 3.0), set up “extended  
defrost” by removing jumper JU1F on the main circuit board inside the electrical compartment  
(see Section 9.0).  
11- Plug in the unit and do the “overall verification” of the system as described in Section 11.0.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.0 Installation of the Controls (con’d)  
8.3 ELECTRICAL CONNECTION TO OPTIONAL CONTROLS  
MAIN PC BOARD  
9
8
7
6
5
4
3
2
1
OL  
OC  
I
J3  
J1  
1
2
3
4
5
6
7
8
9
0L  
I
REAR VIEW  
PUSH-BUTTON SWITCHES  
(5 switches maximum)  
VE0036A  
8.4 ELECTRICAL CONNECTION TO THE FURNACE  
WARNING  
!
010  
Never connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only  
use the low voltage class 2 circuit of the furnace blower control.  
For a furnace connected to cooling system:  
On some older thermostats, energizing the “R” and “G” terminals at the furnace has the effect of energizing  
“Y” at the thermostat and thereby turning on the cooling system. If you identify this type of thermostat, you  
must use the “alternate furnace interlock wiring”. An additional control relay will then have to be installed.  
Standard furnace interlock wiring  
Alternate furnace interlock wiring  
Unit Control Module  
9-PIN AMP PLUG  
THERMOSTAT  
TERMINALS  
W
R
G
Y
THERMOSTAT  
TERMINAL  
W
R
G
Y
J1  
1
2
3
4
5
6
7  
8
9
4 WIRES  
FOUR  
WIRES  
HRV CONTROL CONNECTOR  
J3  
2 WIRES  
heating only  
TWO WIRES  
heating only  
F
F
I
OC OL Y  
R
G
B
wiring  
nuts  
W
W
GRAY  
BROWN  
RED  
GREEN  
R
R
NC  
NO  
COM  
G
C
G
C
BLUE  
Y
Y
*FURNACE INTERLOCK  
RELAY  
Y
FURNACE  
24-VOLT  
TERMINAL BLOCK  
FURNACE  
24-VOLT  
TERMINAL BLOCK  
2 WIRES  
TWO WIRES  
COOLING SYSTEM  
COOLING SYSTEM  
*FURNACE INTERLOCK RELAY, PART # 12658  
VE0010A  
VE0009A  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.0 Wiring Diagram  
WARNING  
!
010  
Risk of electrical shocks. Before performing any maintenance or servicing, always disconnect the  
unit from its power source.  
. .  
. .  
. .  
. .  
. .  
. .  
. .  
L o g i c  
B
G R Y L O C O I  
F
F
9
6
7
4
J 3  
7 1 8 2 9 3  
4
5
6
A B C D E F G  
1
2
1
2
3
J U 1  
J 4  
J 1  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10.0 Air Flow Balancing  
WHAT YOU NEED TO BALANCE THE UNIT  
A magnehelic gauge capable of measuring 0 to  
0.25 inch of water (0 to 62.5 Pa) and 2 plastic  
tubes.  
G
Two ”Flow Measuring Stations” or two flow  
collars (the size will vary depending on the duct  
diameter).  
L
O
W
H
W
VP0006  
VP0005  
Flow collar  
Flow measuring station  
PRELIMINARY STAGES TO BALANCE THE UNIT  
Seal all the unit ductwork with tape. Close all windows and doors.  
Turn off all exhaust devices such as range hood, dryer and bathroom fans.  
Make sure all filters are clean (if it is not the first time you balance the unit).  
Make sure the balancing dampers are fully open (F and G in figure 20).  
Choose appropriate locations for the 2 flow collars (or flow measuring stations), according to figure 20:  
On the exhaust air duct (first measuring location, A)  
On the fresh air distribution duct (second measuring location, B  
At least 36” away from the unit; at least 12” before or after a 90° elbow; at least 12” away from a  
register.  
OR  
A
B
12¨(304mm)  
36¨(914mm)  
12¨(304mm)  
36¨(914mm)  
F
G
VP0012A  
Figure 20  
INSTALLATION OF FLOW COLLARS OR “FLOW MEASURING STATIONS”  
If you are using Flow Collars:  
Insert the flow collars in the duct at each location. Make sure their arrows are pointing in the direction  
of the airflow. Tape collars in place temporarily.  
If you are using “Flow Measuring Stations”:  
Cut a 1” (25.4mm) diameter hole in the duct at each location. Insert the “Flow Measuring Stations”.  
Make sure their arrows are pointing in the direction of the airflow. Tape the “Flow Measuring Stations”  
in place temporarily.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10.0 Air Flow Balancing (cont’d)  
BALANCING PROCEDURE  
1. Set the unit to high speed.  
Make sure that the furnace blower is ON if the installation is in any way connected to the ductwork of  
the cold air return. If not, leave furnace blower OFF. If the outside temperature is below 0°C / 32°F,  
make sure the unit is not running in defrost while balancing. (By waiting 10 minutes after plugging the  
unit in, you are assured that the unit is not in a defrost cycle.)  
2. Place the magnehelic gauge on a level surface and adjust it to zero.  
3. Connect tubing from gauge to flow collar (or “Flow Measuring Station”) in  
exhaust air stream at location A. Be sure to connect the tubes to their appropriate  
high/low fittings. If the gauge drops below zero, reverse the tubing connections.  
NOTE: It is suggested to start with the exhaust air flow reading because the  
exhaust has typically more restriction than the fresh air, especially in  
cases of fully ducted installations and exhaust ducted installation.  
LO  
W
HIGH  
FLO  
W
Place the magnehelic gauge upright and level. Record the readings.  
VP0003  
4. Move tubing to FRESH air flow on the other side of the unit (location B) and  
note readings.  
Adjust the fresh air balancing damper F until the reading at B is approximately  
the same as the reading at A. If the reading at B is less than the reading at A,  
then go back and adjust the exhaust balancing damper G to equal the fresh  
air flow.  
H
HIG  
W
LO  
OW  
FL  
VP0004  
5. Secure both dampers in place with tape or with a fastening screw.  
F
G
VD0069  
VD0052  
6. If you are using flow collars, remove them, reconnect the duct and seal with duct tape. If you are using  
“Flow Measuring Stations”, remove them and seal the holes with duct tape. Write the required air flow  
information on a label and stick it near the unit for future reference (date, maximum speed air flows,  
your name, phone number and business address).  
NOTES: Most flow collar kits provide a conversion chart located on the collar which enables you to convert  
magnehelic gauge readings to equivalent cfm values.  
The unit is considered balanced even if there is a difference of +/- 10 cfm (+/- 0.015 inch w.g.)  
between the two air flow readings.  
If you are only using one flow collar or one “Flow Measuring Station”, then, after completing the  
first reading, transfer this measuring device to the other side of the unit and take the second reading.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11.0 Overall Verification  
11.1 MAIN CONTROLS  
This procedure allows the installer to verify that all modes of operation are fully functional.  
During the verification of a main control, make sure that all optional remote controls are inactive.  
BASIC (6 different control scenarios to be tested)  
CONDENSATI0N CONTROL  
Set the slider  
switch to  
Off  
Set condensation control  
dial to  
Results expected  
fan speed  
1
2
3
4
5
6
maximum counterclockwise  
maximum clockwise  
maximum counterclockwise  
maximum clockwise  
maximum counterclockwise  
maximum clockwise  
motor off  
motor off  
low speed  
high speed  
high speed  
high speed  
Off  
Min.  
Min.  
Max.  
-20  
-4  
C
41  
F
AIR SUPPLY CONTROL  
OFF  
Max.  
MIN.  
AIR  
EXCHANGE  
MAX.  
VC0027  
ELECTRONIC (8 different control scenarios to be tested)  
CONDENSATI0N CONTROL  
Results expected  
Set air supply  
control to  
Set condensation control  
dial to  
Fan  
speed  
Exchange Max speed  
indicator  
(A)  
off  
indicator  
(B)  
off  
1
2
3
4
5
6
Off  
Off  
maximum counterclockwise  
maximum clockwise  
off  
off  
C
off  
off  
C
-4  
F
-5  
41  
F
Min.  
Min.  
Max.  
Max.  
maximum counterclockwise  
maximum clockwise  
maximum counterclockwise  
maximum clockwise  
low  
high  
high  
high  
on  
on  
on  
on  
off  
on  
off  
on  
CONDENSATION CONTROL  
MAXIMUM SPEED  
AIR EXCHANGE IN PROGRESS  
AIR SUPPLY CONTROL  
off 40 min off 40 min  
low 20 min on 20 min  
off  
off  
on  
MIN.  
MAX.  
7
8
Intermittent  
Intermittent  
maximum counterclockwise  
maximum clockwise  
20 MIN  
40 MIN.  
OFF  
ON  
CONTINUOUS  
INTERMITTENT  
high  
on  
VC0028  
A
B
11.2 OPTIONAL CONTROL  
First, turn OFF the main control device (Basic or Electronic) before checking the remote optional control.  
20/40/60-MINUTE PUSH-BUTTON TIMER:  
Activate the push button. Within 2 seconds, push one time for 20 minutes, two times for  
40 minutes or three times for a 60-minute activation.  
Results expected:  
1. Motor speed: high for 20, 40 or 60 minutes.  
2. Indicator light goes “ON” and flashes every 5 seconds (one time to indicate a  
20 min.  
40 min.  
60 min.  
20-minute operation, two times for a 40-minute, and three times for a 60-minute  
operation).  
3. Air exchange indicator light goes “ON” (Electronic wall control only).  
NOTE: To stop activation, push one more time.  
VC0046  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12.0 Maintenance / Instructions for User  
WARNING  
!
010  
Risk of electrical shocks. Before performing any maintenance or servicing, always disconnect the  
unit from its power source.  
• Review with the user the steps required for the regular maintenance of her/his ventilation system.  
These steps are described in details in the user manual:  
FOUR TIMES A YEAR:  
Inspect the intake hood, and clean if needed.  
Clean the filters.  
Clean the interior of the cabinet and clean the door.  
Clean the condensation tray and inspect the drain tubing.  
ONCE A YEAR:  
Clean the recovery core.  
Clean the blades of the blower wheels if needed.  
• Warn the user of the necessity to rebalance the system following a major house renovation or following  
the installation of any extra registers.  
• Make sure the user understands how to use the main control as described in the user manual.  
• If the unit being installed is an ERV, then make sure the user understands the characteristics of the special  
cold weather TBI mode. The user should understand that his unit will not obey the settings on the main  
wall control when the temperature drops below -15°C (5°F). See Section 7.5.  
CAUTION  
Do not oil the motor. It is already permanently lubricated.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13.0 Troubleshooting  
NOTE: Inspect the unit before proceeding with these steps.  
Start-up troubleshooting:  
Problems  
Possible causes  
You should try this  
1. Unit does not work.  
• The circuit board may  
be defective.  
B
G
VE0082  
• Unplug the unit. Disconnect the main control  
and the optional(s) control(s) (if need be). Jump  
B and G terminals. Plug the unit. If the motor  
runs on high speed and the damper opens, the  
circuit board is not defective.  
2. The damper actuator • The 9-pin connector may  
does not work. have a loose connection.  
• Unplug the unit and check to make sure all the  
crimp connections are secured. Check the damper  
actuator connections as well.  
• The damper actuator may • Feed 120 V directly to the damper actuator. If the  
be defective.  
problem persists, replace the damper actuator.  
• The circuit board may  
be defective.  
• Replace the circuit board if the problem is not  
solved by the above.  
3. The wall control does • TBI mode is activated.  
not work OR  
• If the outside temperature is below -15°C (5°F)  
and the unit has an enthalpic recovery core  
(energy recovery core), then the TBI mode is  
probably activated. (See Section 7.5.)  
the indicators flashes  
every 8 seconds.  
• The wires may be in  
reverse position.  
• Ensure that the color coded wires have been  
connected to their appropriate places.  
• Erratic operation of the  
control every 8 seconds.  
• Unplug the unit. Wait 30 seconds. Plug it back in.  
• The wires may be broken. • Inspect every wire and replace any that are damaged.  
• There may be a short-circuit.With the help of a multimeter, check for continuity.  
• The wire in the wall OR  
the wall control may  
be defective.  
• Remove the wall control and test it right beside  
the unit using another shorter wirer. If the wall  
control works there, change the wire. If it does  
not, change the wall control.  
• The circuit board may  
be defective.  
• If the second wall control does not solve the  
problem, then replace the circuit board.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13.0 Troubleshooting (cont’d)  
Problems  
Possible causes  
You should try this  
4. The 20-minute push-button • The switch  
or the 20/40/60-minute may be defective.  
push-button timer does  
not workOR its indicator  
light does not stay on.  
OL  
OC  
VE0067  
• Unplug the unit. Disconnect the main control  
and the optional(s) control(s) (if need be). Jump  
the OL and OC terminals. Plug the unit. If the  
unit switches to high speed, replace the switch.  
5. The defrost cycle  
does not work  
• Ice deposits may be hindering • Remove the ice.  
the damper operation.  
(the fresh air duct is  
frozen OR the fresh airThe damper rod or the port • Inspect these parts and replace if necessary.  
distributed is very cold damper itself may be broken.  
OR the “AIR EXCHANGE”  
light flashes).  
• The damper actuator  
may be defective.  
• Plug in the unit and select “MIN” or “MAX”.  
Press the door switch and see if the port damper  
opens. If it doesn’t open, feed 120V directly to  
the damper actuator. If the port damper still does  
not open, replace the damper actuator.  
• The circuit board may  
be defective.  
• Unplug the unit. Unplug the defrost sensor wire  
(see J4 on electrical diagrams, Section 9.0).  
Plug the unit back in. Select “MIN” and make sure  
the unit is adjusted for low speed operation (turn  
all dehumidistats maximum counterclockwise).  
Wait 3 minutes. The unit should switch to high  
speed and the damper at the fresh air intake  
port should close (defrost mode). If this does  
not happen, then replace the circuit board.  
• The thermistor may  
be defective.  
• If the defrost mode works well after having  
disconnecting the thermistor wire (above test),  
this means the thermistor is probably defective.  
You should replace it.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.0 Warranty  
The standard warranty for the HRV or ERV unit is one year parts only. If this product was installed with a  
matched MAYTAG system, it carries a 10-year parts only warranty.  
15.0 References  
• HVI, “Installation Manual for Heat Recovery Ventilators”, 1987 edition.  
• ASHRAE 1984 Systems Handbook, chapter 11, “Air Distribution Design for Small Heating and  
Cooling Systems”.  
C
C
US  
R 2000  
LISTED  
LISTED  
Download from Www.Somanuals.com. All Manuals Search And Download.  

KWC Indoor Furnishings 10041002 User Manual
Leica Microscope Magnifier SCN400 User Manual
Lennox International Inc Thermostat 81M26 User Manual
LG Electronics Computer Monitor W2452V User Manual
Logitech Computer Keyboard K300 User Manual
Magnavox Flat Panel Television 15MF400T 37 User Manual
Maytag Microwave Oven 11 06 00 User Manual
Mazda Automobile 2001 626 User Manual
Melissa Vacuum Cleaner 640 113 User Manual
Memorex CRT Television MT1192 User Manual