Marley Engineered Products Air Conditioner E3606 1325HFD User Manual

Heated  
Air Curtains  
INSTALLATION & OPERATING INSTRUCTIONS & PARTS MANUAL  
MODELS:  
E3606-1325HFD, E3609-1325HFD  
E3806-1325HFD, E3809-1325HFD  
E4206-1325HFD, E4209-1325HFD  
E4806-1325HFD, E4809-1325HFD  
E6006-2325HFD, E6009-2325HFD  
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE, OR MAINTAIN THE PRODUCT DESCRIBED.  
PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS  
COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE!  
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.  
REFER TO INDIVIDUAL MODEL NUMBERS  
1
2
12 / ”  
FOR UNIT WIDTH  
7
8
11 / ”  
3
4
15 / ”  
Figure 2 Dimensions  
Figure 1  
Note that all dimensions are the same on all environmental  
series units. Model number indicates width of unit.  
(Example: E4800 indicates a 48” wide unit.)  
Description  
Air curtains produce a wall of continuously flowing air  
that acts as a thermal barrier against outside air and  
provides protection against insects, dust, odor, fumes  
and other contaminant’s. Maintains interior conditioned  
temperature by preventing heated or cooled air from  
escaping through open doorways.  
Heated air curtains are engineered to treat incoming  
cold air at customers’ entrance areas. Used over front  
door entrances, heated air curtains supplement existing  
heat to prevent infiltration of colder outside air. Heated  
units are not recommended for areas subject to high  
winds.  
Specifications and Performance  
CFM AT NOZZLE  
(HI/LOW)  
MODEL  
NUMBER  
HEATER  
VOLTAGE  
MOTOR  
VOLTAGE  
HEATER  
WATTS  
HEATER  
BTU/HR  
HEATER  
AMPS  
MOTOR  
SIZE  
E3606-1325HFD  
E3609-1325HFD  
E4206-1325HFD  
E4209-1325HFD  
E4806-1325HFD  
E4809-1325HFD  
E6006-2325HFD  
E6009-2325HFD  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
208/3  
6000  
9000  
6000  
9000  
6000  
9000  
6000  
9000  
20,478  
30,717  
20,478  
30,717  
20,478  
30,717  
20,478  
30,717  
16.7  
25.0  
16.7  
25.0  
16.7  
25.0  
16.7  
25.0  
2025  
2025  
2360  
2360  
2700  
2700  
3375  
3375  
1/4HP  
1/4HP  
1/4HP  
1/4HP  
1/4HP  
1/4HP  
1/4HP  
1/4HP  
Note: For multiple unit installations, recommended spacing between units should be a minimum of 3-inches and a maximum of 6-inches.  
Unit is allowed to extend beyond doorway width. Each unit must have individual power supply.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
1. Using template provided, determine mounting loca-  
3. Run proper size copper power supply conductors from  
the field power supply disconnects, (supplied by  
others) with insulation rated minimum 75°C (167.0°F).  
One set of conductors from 208VAC, 50/60Hz supply  
source shall be routed through the 3/4 inch conduit  
knockout, using a suitable knockout connected to the  
contactor contact terminals marked L1, L2, L3.  
4. The heater control box must have an unbroken  
electrical ground to minimize personal injury if an  
electrical fault should occur.  
tion.  
2. Drill holes and attach mounting hardware (not includ-  
ed).  
IMPORTANT: THE HARDWARE AND THE SUPPORT-  
ING STRUCTURE MUST BE CAPABLE OF SUPPORT-  
ING A MINIMUM 150 LB. LOAD.  
NOTE: All installation should be done to meet local  
building code.  
3. Mount cabinet on wall and securely tighten hardware.  
4. Replace motor/blower assembly in cabinet. Secure  
two wing nuts on blower base. Reconnect motor  
electric cord plug assembly & heater plug.  
5. Replace intake grille with louvers facing down and  
refasten knurled nuts.  
FIELD CONTROL WIRING  
Electric heater is equipped with a step-down transformer  
for 24V control circuit. Thermostat model number RSV-  
130-R-54 must be used to energize heater with the fan  
motor. Connect thermostat wiring from thermostat to  
control leads in heated air curtain control box by means  
of conduit or equivalent. A 1/2 inch knockout is provided.  
Class 1 wiring is required.  
FIELD POWER WIRING  
WARNING: ALL AIR CURTAINS SHOULD BE  
INSTALLED BY QUALIFIED PERSONNEL.  
5. Replace heater control box cover.  
6. Unit is ready for operation.  
7. Restore power.  
1. Before wiring be sure that available power supply,  
voltage, phase and frequency corresponds to that  
specified on heater rating plate. In addition, make  
certain that service capacity is sufficient to handle load  
imposed by the equipment.  
NOTE: Air curtain has high/low selector switch. See  
Operation section for proper setting instructions.  
8. Upon completion of all installation, inspect unit for  
excessive vibration during operation. If excessive  
vibration is noticeable, disconnect power supply.  
Inspect mounting installation and refer to  
Troubleshooting Chart for probable cause.  
2. Install all wiring, protection and grounding in accor-  
dance with the National Electrical Code (NEC) and  
all local requirements.  
WARNING: THIS FAN HAS AN INTERNAL SELF  
RESETTING THERMAL OVERLOAD PROTECTOR.  
ALWAYS DISCONNECT FROM POWER SUPPLY  
BEFORE SERVICING.  
HEATER SECTION  
COLOR CODE  
RE - RED  
FIELD WIRING TO THERMOSTAT  
WH - WHITE  
BK/RD - BLACK W/ RED TRACER  
YE - YELLOW  
OR - ORANGE  
BU - BLUE  
THERMOSTAT  
LEGEND  
TERMINAL MARKING  
TB  
L1  
HR - HEAT RELAY  
TB - TERMINAL BLOCK  
TR TRANSFORMER  
PL - PILOT LIGHT  
FL - FUSE LINK  
TO POWER  
L2 SUPPLY  
HE - HEAT ELEMENT  
L3  
BU  
GR  
PLUG  
Figure 5 - Wiring Diagram  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
1. After power has been connected to unit, fans will start  
NOTE: Air direction settings shown in Figures 6 & 7.  
in either preset (high/low) speed selection.  
NOTE: Cold air will try to escape near floor level.  
Warm air will try to penetrate curtain near top of  
doorway. Air flow can be controlled by direction of  
nozzle louvers and by high/low settings.  
2. Air velocity is controlled by selection of high or low  
speed indicator. This feature allows the setting of air  
velocity to individual desired performance and energy  
efficiency.  
4. For multiple unit applications (wide openings), mount  
units a minimum of 3” apart to allow for proper air  
intake and discharge.  
3. Air direction at outlet can be controlled by adjustable  
vanes at the nozzle which compensates for possible  
draft conditions.  
Figure 6 - Desired Air Flow  
Adjustment for Temperature and  
Humidity Control.  
Figure 7 - Desired Air Flow Adjustment  
for Insect and Dust Control.  
Maintenance  
WARNING: ALL ELECTRIC POWER MUST BE  
DISCONNECTED WHEN INSTALLING OR SERVICING  
THIS EQUIPMENT. MORE THAN ONE DISCONNECT  
SWITCH MAY BE REQUIRED TO REMOVE POWER  
FROM THE UNIT.  
WARNING: ALWAYS DISCONNECT POWER SUPPLY  
BEFORE SERVICING.  
1. To remove motor/blower heater assembly, repeat  
Steps 4, 5 and 6 in Unpacking section.  
2. Place motor/blower assembly on workbench.  
LUBRICATION  
3. To replace blower wheel, remove the three slotted hex  
head screws on outer blower ring assembly (See  
Figure 8, Replacement Parts Illustration.) The wheel  
is held onto shaft by two hex head screws.  
Ball bearings are permanently lubricated and require no  
further lubrication.  
CLEANING  
1. The air door cabinet may be wiped off with a damp  
cloth. Do not allow motor to get wet. Do not use sol-  
vents or harsh detergents.  
NOTE: To re-assemble repeat steps 4 & 5 in  
installation section page 3.  
IMPORTANT: NOTE POSITION OR WHEELS TO  
PREVENT RUBBING WHEN REPLACED.  
NOTE: Keep air intake louvers clear of dirt and dust  
accumulation which could affect performance.  
4. To remove motor:  
2. Check blower wheels for accumulated dirt twice a year  
and clean. If disassembly is required, see GENERAL  
SERVICING section.  
a. Remove blower wheels. (See Step 3 above.)  
b. Remove blower scrolI (six hex head screws).  
c. Unscrew and remove motor mounts.  
GENERAL SERVICING  
5. Replace motor/blower assembly  
WARNING: IF SERVICING IS REQUIRED, IT SHOULD  
BE DONE BY QUALIFIED PERSONS ONLY.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Chart  
SYMPTOM  
POSSIBLE CAUSE(S)  
CORRECTIVE ACTION  
Fan inoperative  
1. Blown fuse or open circuit breaker.  
2. Electricity turned off.  
3. Loose cord connection.  
1. Replace fuse or reset circuit breaker.  
2. Contact local power company.  
3. Re-check all connections.  
4. Replace.  
4. Defective capacitor or motor.  
Excessive noise  
1. Wheel rubbing on housing.  
2. Motor base or blower not securely  
anchored.  
1. Center wheel.  
2. Tighten mounting bolts.  
3. Replace motor.  
3. Defective motor bearings.  
Insufficient air flow 1. Improper voltage.  
2. Outlet louvers closed.  
1. Reconnect to proper voltage.  
2. Open.  
3. Intakes obstructed.  
4. Dirty blower wheels.  
3. Remove any obstruction.  
4. Clean.  
5. Motor rotating in reverse direction.  
5. Reverse red and black power leads.  
Fans cut out on  
thermal overload  
(self-resets)  
1. Low voltage.  
2. Obstruction to blower wheel.  
1. Verify correct wire size.  
2. Remove obstruction.  
No heat  
1. Fuse link open.  
2. Heater element broken  
3. Control Transformer  
1. Replace with 4K4204H or 4K9204H.  
2. Replace with proper Ga. and watts.  
3. Replace with proper item.  
* 120-220 volt models only.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.  
Replacement Parts  
For Air Curtain Cabinets  
3
6
5
4
2
14  
s (7)  
12  
11  
16  
13  
15  
8
10  
9
9
2
6
3
8
4
5
Replacement Parts  
For Heater Units  
7
1C  
1D  
1A  
1B  
Figure 8 - Replacement Parts.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Replacement Parts List For Air Curtain Cabinets  
Key  
Part Numbers for Cabinets (length)  
No. Description  
36"  
38"  
42"  
48"  
60"  
1
2
3
4
5
6
Cabinet box assembly  
ACCA36A  
API3685  
AP0002  
ACL36  
ACEB  
ACFPSPC  
ACCA38A ACCA42A ACCA48A  
ACCA60A  
API6085  
AP0002  
ACL60  
Cabinet Intake Grille  
Cabinet Intake grill knurled nut  
Cabinet louver kit  
Electric box  
Electric box cover  
API3885  
AP0002  
ACL38  
ACEB  
API4285  
AP0002  
ACL42  
ACEB  
API4885  
AP0002  
ACL48  
ACEB  
ACEB  
ACFPSPC ACFPSPC ACFPSPC ACFPSPC  
Replacement Parts For 120 Volt Single Phase Motor Blower Assemblies  
Key  
No.  
7
Part Numbers  
1/4HP  
Description  
Motor/Blower Assembly  
120V 1-ph  
ACMB125  
ACMB225  
ACMB325  
ACFPSH  
C1220  
220V 1-ph  
208-230/460V 3-ph  
8
9
Switch plate cover  
Rocker switch  
10  
11  
Cord, female plug  
Motor Assembly  
ACW316  
120V 1-ph  
220V 1-ph  
208-230/460V 3-ph  
ACM1025  
ACM2025  
ACM3025  
AP058  
12  
13  
14  
15  
16  
Resilient motor ring kit  
Capacitor  
ACCP1025  
ACBH67  
ACBW67R  
ACBW67L  
Blower housing  
Blower wheel-right  
Blower wheel-left  
Replacement Parts List For Heater Units  
REF.  
DESCRIPTION  
REPLACEMENT PARTS FOR 208V 3-PH HEATERS  
NO.  
1
6 KW  
9 KW  
QTY.  
Wire Guards  
A.  
18”  
12”  
6”  
APG0018  
APG0012  
APG0006  
APG0002  
APHC208-3  
AP0018  
APG0018  
APG0012  
APG0006  
APG0002  
APHC208-3  
AP0018  
-
-
-
-
1
1
B.  
C.  
D.  
2”  
2
3
4
5
6
7
8
Heater Control Box  
Heater Transformer  
Heater  
Fan  
RelayAP0020  
AP0020  
Heater Contactor  
Heater Element Set  
Heater Coil Fuse Link  
Wall Thermostat  
AP0021  
APHE06208-3  
AP0016  
AP0021  
APHE09208-3  
AP0016  
1
1
4
1
AP364860-T  
AP364860-T  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED WARRANTY  
All products manufactured by Marley Engineered Products are warranted against defects in workmanship and  
materials for eighteen months from date of installation. This warranty does not apply to damage from accident,  
misuse, or alteration; nor where the connected voltage is more than 5% above the nameplate voltage; nor to  
equipment improperly installed or wired or maintained in violation of the product’s installation instructions. All claims  
for warranty work must be accompanied by proof of the date of installation.  
The customer shall be responsible for all costs incurred in the removal or reinstallation of products, including labor  
costs, and shipping costs incurred to return products to Marley Engineered Products Service Center. Within the  
limitations of this warranty, inoperative units should be returned to the nearest Marley authorized service center  
or the Marley Engineered Products Service Center, and we will repair or replace, at our option, at no charge to you  
with return freight paid by Marley. It is agreed that such repair or replacement is the exclusive remedy available  
from Marley Engineered Products.  
THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, AND ALL  
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH  
EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM  
THIS AGREEMENT. MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL  
DAMAGES ARISING WITH RESPECT TO THE PRODUCT, WHETHER BASED UPON NEGLIGENCE, TORT,  
STRICT LIABILITY, OR CONTRACT.  
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above  
exclusion or limitation may not apply to you. This warranty gives you specific legal rights, and you may also have  
other rights which vary from state to state.  
For the address of your nearest authorized service center, contact Marley Engineered Products in Bennettsville,  
SC, at 1-800-642-4328. Merchandise returned to the factory must be accompanied by a return authorization and  
service identification tag, both available from Marley Engineered Products. When requesting return authorization,  
include all catalog numbers shown on the products.  
HOW TO ORDER REPAIR PARTS  
In order to obtain any needed repair or replacement  
parts, warranty service or technical information, please  
contact Marley Engineered Products Service Center  
toll-free by calling 1-800-642-HEAT.  
SPX Corporation  
470 Beauty Spot Rd. East  
Bennettsville, SC 29512 USA  
ECR 35189  
03-02  
Part No. 5200-2420-001  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  

Kyocera Printer FS 3700 User Manual
Lenovo Computer Monitor T540 User Manual
Life Fitness Home Gym 39735 User Manual
Makita Impact Driver BTL060 User Manual
Manhattan Computer Products Computer Drive 703253 User Manual
Marshall electronic Flat Panel Television 6 00518 02 User Manual
Maytag Clothes Dryer MEDZ600TB1 User Manual
McCulloch Trimmer MT2303 User Manual
Melissa Blender 746 026 User Manual
Micro Innovations Car Speaker M000174 19 User Manual