Galaxy PW 100 to 225 kVA
User’s Manual
This page intentionally left blank
ii
Chapter name
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS — This manual contains important instructions for EPS 6000
inverters that must be followed during installation, operation and maintenance of the equipment.
WARNING
Opening enclosures expose hazardous voltages. Always refer service to qualified personnel only.
ATTENTION
L'ouverture des cabinets expose des tensions dangereuses. Assurez-vous toujours que le service ne
soit fait que par des personnes qualifiees.
WARNUNG!
Offene Raeume entladen gefaehrliche Stromspannungen. Bitte wenden sie sich an qualifiziertes Dienstpersonal.
WARNING
To reduce the risk of fire or electric shock, install in a temperature and humidity controlled indoor area
free of conductive contaminants.
ATTENTION
Pour réduire le riske d'inccendie ou d'électrocution, installer dans une enciente intérieure contrôlée en
température et humidité et sans contaminants conducteurs.
WARNUNG!
Um die Gefahr von Feuer und elektrischem Schock zu reduzieren, muss das Geraet in einem temperatur -
und feuchtigkeitskontrolliertem Raum, frei von leitungsfaehigen Verunreinigungen, installiert werden.
WARNING
As standards, specifications, and designs are subject to change, please ask for confirmation of the
information given in this publication.
ATTENTION
Comme les normes, spécifications et produits peuvent changer, veuillez demander confirmation
des informations contenues dans cette publication.
WARNUNG!
Normen, Spezifizierungen und Plaene unterliegen Aenderungen. Bitte beantragen Sie schriftliche
Bestaetigung ueber Informationen die in dieser Herausgabe gemacht wurden.
NOTE
This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be required to correct
the interference at his own expense.
Important Safety Instructions
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
This page intentionally left blank
iv
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
user’s manual
Galaxy PW™
User’s Manual
Warranty
Seller warrants to the Ultimate Purchaser (the purchaser who buys for use, and not for resale) that all products furnished under this order and which are manufac-
tured by Seller will conform to final specifications, drawings, samples and other written descriptions approved in writing by Seller, and will be free from defects in
materials and workmanship. These warranties shall remain in effect for period of twelve (12) months after delivery to the Ultimate Purchaser. But if the Seller installs
the equipment or supplies technical direction of installation by contract, said one year shall run from the completion of installation, provided installation is not unrea-
sonably delayed by Ultimate Purchaser. Parts replaced or repaired in the warrant period shall carry the unexpired portion of the original warranty. A unit placed with
the Purchaser on consignment and then later purchased will be warranted for twelve (12) months from the time the Seller receives notification of the Purchaser’s
intent to purchase said consigned item. The foregoing in its entirety is subject to the provision that in no case will the total warranty period extend beyond 18 months
from date Seller ships equipment from point of manufacture.
The liability of Seller hereunder is limited to replacing or repairing at Seller’s factory or on the job site at Seller’s option, any part or parts which have been returned to
the Seller and which are defective or do not conform to such specifications, drawings or other written descriptions; provided that such part or parts are returned by
the Ultimate Purchaser within ninety (90) days after such defect is discovered. The Seller shall have the sole right to determine if the parts are to be repaired at the
job site or whether they are to be returned to the factory for repair or replacement. All items returned to Seller for repair or replacement must be sent freight prepaid
to its factory. Purchaser must obtain Seller’s Return Goods Authorization prior to returning items. The above conditions must be met if warranty is to be valid. Seller
will not be liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misapplication of the item, or for damage due to acci-
dent, abuse, or Act of God.
In no event shall the Seller be liable for loss, damage, or expense directly or indirectly arising from the use of the units, or from any other cause, except as expressly
stated in this warranty. Seller makes no warranties, express or implied, including any warranty as to merchantability or fitness for a particular purpose or use. Seller is
not liable for and Purchaser waives any right of action it has or may have against Seller for any consequential or special damages arising out of any breach of war-
ranty, and for any damages Purchaser may claim for damage to any property or injury or death to any person arising out of its purchase of the use, operation or
maintenance of the product. Seller will not be liable for any labor subcontracted or performed by Purchaser for preparation of warranted item for return to Seller’s fac-
tory or for preparation work for field repair or replacement. Invoicing of Seller for labor either performed or subcontracted by Purchaser will not be considered as a lia-
bility by the Seller.
This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a writing signed by an officer of the Seller. This war-
ranty shall extend to the Ultimate Purchaser but to no one else. Accessories supplied by Seller, but manufactured by others, carry any warranty the manufacturers
have made to Seller and which can be passed on to Ultimate Purchaser.
Seller makes no warranty with respect to whether the products sold hereunder infringe any patent, U.S. or foreign, and Buyer represents that any specially ordered
products do not infringe any patent. Buyer agrees to indemnify and hold Seller harmless from any liability by virtue of any patent claims where Buyer has ordered a
product conforming to Buyer’s specifications, or conforming to Buyer’s specific design.
Buyer has not relied and shall not rely on any oral representation regarding the Product sold hereunder and any oral representation shall not bind Seller and shall not
be part of any warranty.
There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS SYSTEMS, Inc. be responsible for consequential dam-
ages or for any damages except as expressly stated herein.
Service and Factory Repair - Call 1 - 800 - 438 - 7373
Direct questions about the operation, repair, or servicing of this equipment to MGE UPS SYSTEMS, Inc. Customer Support Services. Include the part number,
assembly number, and serial number of the unit in any correspondence. Should you require factory service for your equipment, contact MGE UPS SYSTEMS, Inc.
Customer Support Services and obtain a Return Goods Authorization (RGA) prior to shipping your unit. Never ship equipment to MGE UPS SYSTEMS, Inc. without
first obtaining an RGA.
Proprietary Rights Statement
The information in this manual is the property of MGE UPS SYSTEMS, Inc., and represents a proprietary article in which MGE UPS SYSTEMS, Inc., retains any and
all patent rights, including exclusive rights of use and/or manufacture and/or sale. Possession of this information does not convey any permission to reproduce, print,
or manufacture the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by an officer of MGE UPS SYS-
TEMS, Inc.
IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and MGE UPS SYSTEMS are trademarks of MGE UPS
SYSTEMS, Inc. Other trademarks that may be used herein are owned by their respective companies and are referred to in an editorial fashion only.
Revision History
Galaxy PW™ User's Manual
86-133060-00
Copyright © 2002 MGE UPS SYSTEMS. All rights reserved. Printed in U.S.A.
Revision: X1
08/02
Warranty
v
Download from Www.Somanuals.com. All Manuals Search And Download.
This page intentionally left blank
vi
Download from Www.Somanuals.com. All Manuals Search And Download.
contents
safety instructions ......................................................................................................iii
warranty .....................................................................................................................v
how to use this manual .............................................................................................2
introduction
general characteristics of Galaxy PW™ UPS ..........................................................3
system description ..................................................................................................4
different types of Galaxy PW™ systems ..................................................................5
isolation and protection devices ..............................................................................5
operation in on-line mode ........................................................................................6
inverter shutdown or overload ..................................................................................8
operation with an engine generator set......................................................................9
output voltage quality and continuity ........................................................................9
description of Galaxy PW™ cabinets
UPS ........................................................................................................................10
battery ......................................................................................................................10
control panel
general ....................................................................................................................11
indications ................................................................................................................11
start-up
system start-up ........................................................................................................13
start-up of a module ..............................................................................................13
shutdown
shutdown of the inverter ..........................................................................................14
shutdown of a rectifier/charger ..............................................................................14
control-panel display
general organization ................................................................................................15
display of messages ................................................................................................15
measurement system ..............................................................................................19
voltage measurements ............................................................................................19
current measurements ............................................................................................19
power and frequency measurements ....................................................................19
battery measurements ..........................................................................................20
selections and settings ..........................................................................................20
alarms
general ....................................................................................................................22
maintenance bypass ..............................................................................................22
environment information
signal reception ......................................................................................................23
signal transmission ................................................................................................23
logging and time-stamping
presentation of event time-stamping by Galaxy PW™............................................24
utilization via the Galaxy PW™ display ..................................................................24
utilization via Teleservice ........................................................................................27
maintenance
maintenance configuration........................................................................................28
battery maintenance ................................................................................................30
visual check ..............................................................................................................30
functional check ......................................................................................................30
options
galvanic and voltage matching transformers
maintenance bypass ................................................................................................31
electrical supervision ..............................................................................................31
Contents
1
Download from Www.Somanuals.com. All Manuals Search And Download.
how to use this manual
Galaxy PWTM 100 to 225 kVA
This manual is designed for ease of use and easy location of information.
To quickly find the meaning of terms used within the text, look in the Glossary.
This manual uses Noteboxes to convey important information. Noteboxes come in four varieties:
WARNING
CAUTION
A
WARNING
indicates information
provided to protect the
user and service
notebox
A
CAUTION notebox
indicates infor mation
provided to protect the
u s e r
p e r s o n n e l
p o s s i bl e
damage.
a n d
s e r v i c e
a g a i n s t
personnel against safety
hazards and/or possible
equipment damage
e q u i p m e n t
IMPORTANT
NOTE
An IMPORTANT notebox
A
N OT E
indicates infor mation
p r ov i d e d a s a n
n o t e b ox
indicates
information
provided as an operating
instruction, or as an
operating tip.
operating tip or an
equipment feature.
All products in the Galaxy PW™ range are protected by patents. They implement origi-
nal technology not available to competitors of MGE UPS SYSTEMS.
To take into account evolving standards and technology, equipment may be modified
without notice. Indications concerning technical characteristics and dimensions are not
binding unless confirmed by MGE UPS SYSTEMS.
This document may be copied only with the written consent of MGE UPS SYSTEMS.
2
How to Use this Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
introduction
User’s Manual
general characteristics of Galaxy PW™ UPS
UPS power rating in kVA
Normal AC input
100
130
150
180
200
225
number of conductors
rated voltage and tolerances
rated frequency and tolerances
THDI
3 phases
480 V ± 10% (adjustable to ± 15%)
60 Hz / ± 10%
< 14% < 11% < 10% < 8%
< 7.6% < 7.5%
power factor
up to 0,9
Bypass AC input
number of conductors
rated voltage and tolerances
rated frequency and tolerances
Load
3 phases
3 phases + neutral
480 V / ± 10%
60 Hz / ± 10%
number of conductors
Ph/Ph voltages
3 phases
480 V
3 phases + neutral
Ph/N voltages
277 V
voltage fluctuations
adjustable frequency and tolerances
(on battery power)
± 1%
60 Hz ± 0,05 Hz
synchronization with bypass
± 0.5 Hz (adjustable from ± 0.25 Hz to ± 2 Hz)
voltage variation for 0 to 100% load step change ± 2% (with battery)
permissible overloads
Isc Ph/Ph (% of I rated)
Isc Ph/N (% of I rated)
THDU Ph/Ph and Ph/N for linear load
THDU Ph/Ph and Ph/N for non-linear load
(at 80% of Pn)
150% for 1 minute, 125% for 10 minutes
4.7
7.4
3.6
5.7
3.2
5
2.6
4.1
2.4
3.7
2.1
3.3
< 1,5% Ph/Ph, < 2% Ph/N
< 2% Ph/Ph, < 3% Ph/N
Battery
standard battery type
UPS characteristics
active power (kW)
gas-recombination sealed lead-acid battery
100
130
91
150
92
180
200
225
93
efficiency at 50% load (%)
(values ± 1%)
90.5
92.5
92.5
efficiency at 100% load (%)
(values ± 1%)
92.5
93
93
93
93.5
93.5
heat losses (1)
in KW
8.1
9.8
11.3
13.5
13.9
14.1
in cal./s
1940
2350
2700
3240
3340
3380
storage temperature range
-25 °C to +70 °C
operating temperature range
relative humidity
0 °C to 35 °C (40 °C for 8 hours)
95% maximum
< 1000 meters
62
maximum operating altitude without derating
noise level (dBA)
63
64
65
67
68
dimensions (mm)
width
depth
height
1215
840
1900 ± 10
weight (lbs/kg)
3050/1388
standards
design
NFPA / NEC / NEMA / OSMA
UL 1778 - ULC
product and safety
electromagnetic compatibility
FCC Part 15, Subport J, Class A - IEEE587 / ANSI 62.41
(1): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system.
Introduction
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
Note
The system may also include:
■ Isolation or auto transformers on both
input and output.
■ 2 CB or 3 CB maintenance bypass
■ different remote control, indication and
display systems.
system description
(see figure 1)
■ the normal AC input and the bypass AC
input have different functions and,
depending on the installation, may be pro-
tected differently upstream and/or come
from different sources.
■ when increased power is required, sev-
eral Galaxy PW™ units may be connect-
ed in parallel (up to four). In this configura-
tion, an "isolation" function is added for
the UPS system as a whole for mainte-
nance purposes, without interrupting the
supply of power to the load.
■ a rectifier/charger module (A) converts
3-phase AC power from the normal AC
source supply (1) into DC power for the
normal inverter input and float charges or
recharges the battery;
■ a battery unit (D) provides backup
power for the inverter in the event of a
voltage drop or a normal AC source fail-
ure;
■ an inverter module (B) converts the DC
power supplied by the rectifier/charger
module or the battery unit into 3-phase AC
power for the load;
■ a static bypass module (C) ensures the
instantaneous transfer of the load to the
bypass AC source input in the event of an
inverter shutdown (initiated by the user or
by a protective device) or a sudden over-
load;
■ a maintenance bypass isolates the UPS
for maintenance and transfers the load to
bypass AC source input without interrupt-
ing the supply of power. The maintenance
bypass is made up of three manual
switches (Q3BP, Q4S and Q5N).
Schematic diagram of the Galaxy PW™ system
inverter (B):
DC to AC
power
rectifier/
charger (A):
AC to DC
power
isolation and
protection:
Q5N
*FUSE
*FUSE
(1)
normal
AC input
load
Q1
isolation
and
protection
QF1: isolation
and protection
harmonic
fliter
battery (D):
backup power
isolation:
Q4S
static bypass (C):
(2)
bypass
AC input
maintenance bypass:
Q3BP
Fig. 1 *The Fuse is to protect against catastrophic rectifier/inverter
semiconductor failure.
4
Introduction
Download from Www.Somanuals.com. All Manuals Search And Download.
User’s Manual
parallel UPS system
See figure 3 showing two parallel-connect-
ed (redundant) UPS units.
different types of Galaxy
PW™ systems
isolation and protection
devices
(See figure 1 on previous page):
■ Q1 (Molded circuit breaker NA):
❏ isolation of the rectifier/charger (A) from
the normal AC source (1);
❏ rectifier/charger (A) start-up;
■ QF1 (circuit breaker):
❏ battery (D) protection and isolation;
■ Q5N (switch):
❏ isolation of the UPS (B) from the load;
■ Q4S (switch):
❏ isolation of the static bypass (C) from
the bypass AC source (2);
■ Q3BP (switch):
❏ bypass switch for maintenance;
■ FUE (fuses):
❏ protection of the rectifier/charger (A)
from the normal AC source;
■ FUS (fuses):
single-UPS unit
Q3BP
A
B
C
Q5N
1
1
D
S
2
2
2
Galaxy 1
1
2
Galaxy 2
Fig. 2
Fig. 3
When increased power is required (two to
four parallel units), an external bypass
must be added (see figure 4).
❏ protection of the inverter (B) from the
load.
Q3BP
Note:
Q5N
■ switch Q3BP is lock on open position on
parallel UPS systems constituted to
increase available power.
1
2
2
Galaxy 1
1
2
external bypass for parallel
UPSs and the hot-swap
option
Galaxy 2
1
2
Galaxy 3
See figure 4.
1
2
■ Q5N: isolation of the inverters of all the
parallel UPS systems from the load;
■ Q3BP: bypass for maintenance.
Galaxy 4
Fig. 4
Introduction
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
operation with the normal AC battery time
source down
operation in on-line
mode
The available battery time during a normal
AC source outage depends on the:
■ rated capacity of the battery;
See figure 6.
In the event of a normal AC source failure
or voltage outside specified tolerances of
±10% in amplitude (±15% optionally), the
rectifier/charger (A) stops and the battery
(D) supplies the necessary backup power
to the load via the inverter (B). The bat-
tery, float-connected between the rectifi-
er/charger and the inverter, discharges
during this operating mode.
normal operation
Normal AC source power is available (see
figure 5).
■ lights 1 , 4 and 5 shine green on
the control panel;
■ the power necessary for the load is pro-
vided by the normal AC source (1) through
the rectifier/charger (A) and the inverter
(B);
■ the rectifier/charger (A) also supplies
the power to float charge and recharge the
battery if any.
The rectifier/charger output voltage (DC) is
regulated to supply:
❏ the float-charging or the recharging volt-
age for vented lead-acid or Ni/Cd batter-
ies,
❏ a single charge voltage for sealed lead-
acid batteries.
■ power consumed by the load;
■ temperature of the battery;
■ age of the battery.
The specified battery time corresponds to
a minimum duration at full rated load.
The actual backup time can therefore be
greater if the system operates below its
full rated load during the normal AC
source outage. Operation on battery
power can be extended beyond the speci-
fied time by reducing the load power con-
sumption (by disconnecting non-critical
loads).
A "low battery" warning signal is sent via
volt-free changeover contacts for remote
control devices when the battery voltage
reaches a level slightly above the mini-
mum level. This signal warns the user of
the imminent end of battery power. On the
device itself, the buzzer beeps rapidly.
The message "LOW-BATTERY SHUT-
DOWN WARNING" is displayed, followed
by the remaining backup time and the per-
cent load. Light 2 turns red and flashes.
Battery power stops when the voltage
supplied by the battery reaches the mini-
mum threshold. This results in inverter
shutdown and transfer of the load without
interruption to the bypass AC source. Light
Lights 2 , 4 and
The user is warned of battery operation by
the slow beeping of the buzzer (see
5
shine green.
6
figure 16) and the message "LOAD PRO-
TECTED, BATTERY DISCHARGING", fol-
lowed by the remaining backup time and
the percent load.
This information is also available via volt-
free changeover contacts for remote con-
trol devices.
The voltages depend on the number of
battery cells and the battery manufacturer.
Factory set, they may also be adjusted by
after-sales support technicians.
An electronic board continuously mea-
sures the battery temperature and auto-
matically adjusts the voltages.
2
4
5
1
2
A
B
1
Note:
In parallel Galaxy PW™ systems, the
power drawn by the load is equally shared
between the different units.
D
2
shines red (not flashing). The mes-
C
sage "LOAD NOT PROTECTED, ON-
LINE MODE" is displayed and the buzzer
sounds continuously.
2
Fig. 6
If the bypass AC source also fails, the
load is no longer supplied. The inverter
automatically shuts down when the time
on battery power exceeds three times the
specified backup time.
1
4
5
1
2
A
B
C
NOTE
1
The "low battery shut-
down" warning signal can
be sent with an adjustable
time delay prior to the
effective end of battery
power.
D
2
Fig. 5
6
Introduction
Download from Www.Somanuals.com. All Manuals Search And Download.
User’s Manual
The battery charge cycle takes place in
two steps (see figure 8):
operation with the normal AC
source restored
NOTE
■ step 1: the battery is recharged at a
constant current limited to 0.1C10 (i.e.
1/10th of the battery capacity specified for
a 10 hour discharge). The DC voltage
increases with the battery charge until the
charge level is reached;
■ step 2: the battery is recharged at con-
stant voltage equal to the charge level.
The charging current gradually decreases
until reaching a specified low value (float-
ing current).
For vented lead-acid batteries, the rectifi-
er/charger supplies the charging voltage
for 0 to 255 hours (parameter defined by
the after-sales support department) and
then the floating voltage. For sealed lead-
acid batteries, the charging and floating
voltages are the same.
If the normal AC source
failure is shorter than 0 to
255 seconds (default value
= 30 seconds) (parameter
defined by after-sales sup-
port department), the
charger automatically sup-
plies the floating voltage
given the low battery dis-
charge.
See figure 7.
When normal AC source power (1) is
restored or its voltage returns to within
specified tolerances, the system automati-
cally returns to its normal operating mode
described above (on the condition it did
not reach the end of battery power). If the
end of battery power was reached (with
the resulting inverter shutdown), the rectifi-
er/charger (A) restarts automatically, but
the inverter (B) must be restarted manual-
ly.
The rectifier/charger recharges the battery
(D) which was discharged during the
mains outage. During battery charging,
light
2
flashes green.
The message "BATTERY CHARGING" is
displayed, together with the value of the
recharging current and battery voltage.
Battery charge cycle
U charge/floating
(sealed batteries)
U/I
1
2
4
5
voltage
1
2
U "floating"
(vented batteries)
0,1 C10
A
B
C
current
1
D
current
limiting
constant voltage
decreasing current
t
2
Fig. 8
Fig. 7
Introduction
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
If the conditions are not satisfied, the
inverter will current limit to 165% of its
rated current for 1 second before stop-
ping;
■ in the event of a small but extended
overload (i.e. a continuous level of power
exceeding the full rated load), the inverter
will continue to supply power for a period
depending on the magnitude of the over-
load (10 minutes for a 125% overload, 1
minute for a 150% overload). See the
overload curve in figure 10;
■ in all three of the above cases, inverter
shutdown and supply of the load via the
bypass AC source results in the following
on the control panel:
❏ light 4 goes off,
❏ activation of the buzzer (continuous
beep),
parallel UPSs with redundancy
inverter shutdown or
overload
See figure 9 for devices or installations
operating in on-line mode with a bypass
AC source.
■ the shutdown of one UPS unit is of no
consequence for the load. The others
each take up an equal amount of load
power and the load continues to be sup-
plied normally;
Unit shutdown results in the following on
the control panel:
❏ lights 4 and 5 go off,
❏ activation of the buzzer (continuous
beep),
❏ the message "LOAD NOT PROTECT-
ED, PARALLEL ON-LINE MODE" is dis-
played;
■ in the event of an overload, the system
only loses its redundancy as long as the
overload is less than the total rated power
of the functioning units. If the overload is
greater, the operating mode is that previ-
ously described for systems without
redundancy.
3
5
1
2
A
B
C
1
D
2
❏ light 3 shines green,
❏ the message "LOAD NOT PROTECT-
ED, ON-LINE MODE" is displayed.
Fig. 9
parallel UPSs without redun-
dancy
single-UPS unit (on-line mode)
■ in the event of a UPS shutdown (initiat-
ed by the user or by an internal protective
device), the load is automatically trans-
ferred to the bypass AC source. If transfer
conditions are satisfied, transfer takes
place instantly, without interruption to the
load;
Note: transfer conditions are not satisfied
when bypass AC source characteristics
are outside tolerances (voltage: ±10%; fre-
quency as per personalization; phase sync
with inverter ±3°);
The shutdown of one inverter results in
overload on the other inverters in opera-
tion. Two cases may then arise:
■ if the overload on each remaining invert-
er is > than 1.65 ln, the load is immediate-
ly transferred to the bypass AC source;
■ if the overload is less than 1.65 ln, the
remaining inverters support the overload
(see curve in figure 14), and the load is
transferred to the bypass AC source;
■ after this transfer:
❏ the light 4 goes off,
■ in the event of a major transient over-
load (greater than 1.65 In), immediate
transfer takes place as above, without
interruption to the load.
The return to the inverter is automatic
when the overload disappears if the num-
ber of possible returns has not been
reached (0 to 255, programmable by per-
sonalization). If this number has been
reached, the load continues to be supplied
by the bypass AC source. This operating
mode allows start-up of load devices
causing high inrush currents.
❏ the buzzer is activated and sounds con-
tinuously,
❏ the light 3 goes on and turns green,
❏ the message "LOAD NOT PROTECT-
ED, PARALLEL ON-LINE MODE" is dis-
played.
I
1,5 In
1,35 In
1,25 In
This system requires satisfied transfer
conditions.
1,15 In
1,10 In
1,05 In
In
1
2
3
4
5
6
7
8
9
10
30
120 t (min)
Fig. 10
8
Introduction
Download from Www.Somanuals.com. All Manuals Search And Download.
User’s Manual
operation with an engine output voltage quality
When the bypass AC source frequency
returns to within the specified tolerances,
the inverter is gradually re-synchronized to
the bypass line at a rate of 0.5 Hz to 2
Hz/s (as per the value personalized by the
after-sales support department), thus
avoiding exposing the load to sudden fre-
quency variations.
generator set
and continuity
See figure 11 below.
If a stand-by generator is included in the
The output voltage is stable in amplitude
and frequency and is free of interruptions or
installation, it is generally started automati- transients outside specified tolerances, irre-
cally in the event of a normal AC source spective of normal AC source or load distur-
failure and connected to the main low volt- bances (outages, load step changes, etc.).
age switchboard. It is disconnected when
normal AC source power is restored.
With such a system, the required battery
time may be reduced to the time neces-
steady state voltage
regulation
For stable or slowly varying load condi-
tions, the inverter output voltage is regu-
lated to within ±0.5% in amplitude.
The frequency of the output voltage can
theoretically be regulated to within 0.1% of
the rated value, however the output fre-
quency range may be intentionally extend-
ed to a maximum of ±2 Hz so that the
inverter can remain synchronized with the
bypass AC source and its inherent fre-
quency fluctuations, thus enabling transfer
of the load to the bypass line at any time.
transient voltage regulation
The inverter output voltage is not notably
affected by instantaneous major variations
in load characteristics.
This is made possible by the PWM (Pulse
Width Modulation) chopping technique
and the microprocessor-based regulation
system that instantly compensates for any
variation. In particular, the inverter output
voltage remains within +/- 2% of the rated
voltage for load step changes of 0 to
100% or of 100 to 0%.
sary for starting and bringing on line the
stand-by generator. The battery (D) sup-
plies power to the inverter (B) during the
transfers:
■ normal AC source to the generator;
■ generator to the normal AC source.
The transfer sequences described above
(normal AC source ➜ battery, battery ➜
generator, generator ➜ battery, and bat-
tery ➜ normal AC source) are fully auto-
matic. They in no way affect the load and
require no manual operation by the user.
NOTE
NOTE
The output frequency
range can be personalized
and if necessary modified
on the customer site by a
qualified MGE UPS SYS-
TEMS support technician
from ±0.25 Hz to ±2 Hz in
0.25 HZ steps.
To avoid load surges on
the generator, the rectifi-
er/charger is started with
a 10 second maximum
current consumption
walk-in (lasting 3 to 10
seconds, depending on
the percent load).
When the bypass AC
source voltage moves out-
side this frequency range,
the inverter is desynchro-
nised and operates in
"free running" mode, with
the output frequency regu-
lated to a high level of
accuracy by a quartz
oscillator.
To avoid overloading an
undersized engine gener-
ator set, it is possible to
set a maximum power
level drawn by the nor-
mal AC input. Any addi-
tional power required is
supplied by the battery.
This modification can be
made on site by an MGE
UPS SYSTEMS field
engineer.
Example of an installation with an engine generator set
Galaxy PW
generator
main LV switchboard
C
B
Mains 2
Mains 1
G
A
HV system
D
Fig. 11
Introduction
9
Download from Www.Somanuals.com. All Manuals Search And Download.
description of
Galaxy PWTM 100 to 225 kVA
galaxy PW™ cabinets
Description of Galaxy
PW™ Cabinets
UPS cabinet
See figure 12 for the layout of the various
cabinet components.
1
2
2
2
3
11
Legend for figure 12:
1 - rectifier/charger module,
2 - inverter module,
3 - static-bypass module,
12
4
4 - card case for electronic control boards,
5 - rectifier/charger input fuses "FUE",
6 - inverter output fuses "FUS",
7 - normal AC input circuit breaker Q1,
8 - bypass AC input switch Q4S,
9 - maintenance bypass switch Q3BP
(locked in open position on parallel UPSs
for greater capacity),
13
5
3
6
10 - output switch Q5N,
11 - display board,
12 - Media Contacts 11 remote indications
board,
13 - backfeed protection.
8
9
10
7
GND
N
Fig. 12
2
2
2
2
battery cabinet
Figure 13 shows an example of compo-
nent layout in a battery cabinet or a bat-
tery circuit-breaker enclosure.
1
Legend for figure 13:
1 - battery isolation and protection circuit
breaker QF1,
2 - battery cells.
1
Fig. 13
Example only and may not represent actual units shipped
10
Description of Galaxy PWTM Cabinets
Download from Www.Somanuals.com. All Manuals Search And Download.
control panel
User’s Manual
"Static-bypass" light
3
general
indications
See figure 14.
■ light off: bypass AC source within speci-
fied tolerances and static bypass open;
■ light shines green: static bypass closed;
■ light shines red: the stored alarm indi-
cates one or several of the following
faults:
❏ bypass AC source voltage or frequency
outside specified tolerances,
❏ static-bypass fault,
❏ abnormally high internal static-bypass
temperature,
❏ static-bypass ventilation fault,
❏ power-supply fault for the static-bypass
control function,
❏ fault on the electronic board controlling
the transfer function,
❏ non-calibration or non-personalization of
the electronic control board for the invert-
er,
❏ fault on the electronic power-supply
board,
The control panel on Galaxy PW™ UPSs
comprises the basic controls and indica-
tions required to check the general status
of the system (see figure 14).
"Rectifier/charger" light
1
■ light off: rectifier/charger OFF;
■ light shines green: rectifier/charger ON;
■ light shines red: rectifier/charger fault,
the stored alarm indicates one or several
of the following faults:
❏ input circuit breaker Q1 open,
❏ protection fuse at the rectifier/charger
input (FUE) blown,
❏ abnormally high internal rectifier/charger
temperature,
❏ abnormally high battery charge current,
❏ abnormally high battery voltage,
❏ fault, non-calibration or non-personaliza-
tion of the electronic control board for the
rectifier/charger,
Located in the upper right part of the cabi-
net front, the control panel is designed to
provide an easy and rapid overview of
system status (see figure 14).
Interpretation of symbols is very simple
and requires no particular training. The
information concerns only the cabinet on
which the panel is located.
The panel indicates:
■ normal operation (load protected);
■ operation with load on battery power;
■ abnormal situations (operating problem);
■ dangerous situations (load not protect-
ed).
❏ fault on the electronic power-supply
board,
❏ fault on monitoring the "inverter ready"
response channels (parallel UPS system).
❏ abnormally high temperature in the har-
monic filter inductor.
"Inverter" light
4
"Battery light"
2
■ light off: inverter OFF;
■ light off: battery float charging;
■ light flashing green: battery recharging;
■ light shines green: load on battery
power;
■ light flashing red: low-battery shutdown
warning;
■ light shines red: battery at end of back-
up time and circuit breaker QF1 open, or
battery fault.
■ light flashing green: inverter starting,
inverter ON but not connected to the load;
■ light shines green: normal inverter oper-
ation;
■ light shines red: inverter fault, the stored
alarm indicates one or several of the fol-
lowing faults:
❏ inverter shutdown due to inverter output
voltage outside specified tolerances,
❏ protection fuse at the inverter output
(FUS) blown,
❏ abnormally high inverter-output trans-
former temperature,
❏ abnormally high inverter temperature,
❏ output-voltage fault (amplitude or phase)
(parallel UPSs),
1
2
3
4
5
6
1
2
❏ fault, non-calibration or non-personaliza-
tion of the electronic control board for the
inverter,
❏ fault on the electronic power-supply
board.
7
8
22
9
10
11
12
13
14
20
15
V
A
W.Hz
17
18
16
fault
19
21
Fig. 14
Control Panel
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
"Load" light
"V" key 13
"Alarm reset" key 20
5
■ light off: load not supplied;
This key is used to access voltage mea-
surements:
■ normal AC source phase-to-phase volt-
ages;
■ bypass AC source phase-to-phase and
phase-to-neutral voltages;
■ load phase-to-phase and phase-to-neu-
tral voltages.
This key is used to reset stored alarms.
The system accepts resetting only when
alarms have been cleared.
■ light shines green: load supplied via the
inverter or the bypass AC source (via the
static bypass).
Buzzer
6
"Buzzer reset" key 21
The buzzer sounds in the following situa-
tions:
■ load supplied by the bypass AC source;
■ load on battery;
This key is used to stop the buzzer.
However, new alarms set the buzzer off
again.
"A" key 14
This key is used to access current mea-
surements:
■ normal AC source, bypass AC source
and load currents;
■ percent load;
■ operating problems.
Display 22
The display continuously indicates the
system operating status.
It sounds slowly and discontinuously for a
minor problem or when the inverter is on
battery power.
When the alarm "LOW BATTERY SHUT-
DOWN" is activated, the buzzer sounds
more rapidly. Finally, if the inverter shuts
down, the beep is loud and continuous.
The buzzer may be reset by pressing a
button. If the buzzer is reset, a higher
level alarm will set it off again.
■ load crest factor.
"W.Hz" key 15
This key is used to access other measure-
ments:
■ normal AC source, bypass AC source
and inverter frequencies;
■ level of active and apparent power
drawn by the load;
"Inverter ON" button
This button is used to start the inverter
locally.
7
■ load power factor;
■ inverter load level (percent).
"Inverter OFF" button
8
This button turns the inverter off locally.
"Anomaly" indicator light 16
Keys 9 and 10
This indicator light indicates the presence
of anomalies.
These keys are used to select commands
in the main menu and access the sec-
ondary messages.
key 17
This key is used to access the primary
messages.
Key 11
This key is used to validate the user’s
choice.
"Battery" key 18
This key is used to access battery mea-
surements:
Key 12
■ battery voltage (or the DC voltage on
frequency converters without a battery);
■ battery current (charge or discharge);
■ battery temperature;
■ available battery backup time;
■ inverter load level (percent).
This key is used to access the main
menu: display language, display-contrast
setting, sound level of the buzzer, lamp
test, date and time settings, inverse-video
and event log.
"Forced-transfer" key 19
This key is used to voluntarily transfer the
load to the inverter or from the inverter to
the static bypass (return transfer). Transfer
and return transfer are carried out only fol-
lowing confirmation requested by the sys-
tem display and a warning as to the risk of
an interruption in the supply of power to
the load.
12
Control Panel
Download from Www.Somanuals.com. All Manuals Search And Download.
start-up
User’s Manual
parallel UPS unit for
increased output
system start-up
start-up of a module
single-UPS unit or redundant
parallel UPS
start-up of a rectifier/charger
■ rectifier/charger start-up is automatic
when the normal AC input circuit breaker
Q1 is closed:
❏ the green "rectifier/charger" light 1 on
the control panel goes on;
■ close battery circuit breaker QF1.
See figure 16.
Proceed in the following order:
■ check that all load devices are off or
that the load is disconnected;
■ close the upstream switch supplying
normal AC source power (on the LV
switchboard);
■ close the normal AC input circuit break-
ers Q1 on the UPS units. The system
powers up:
❏ the rectifier/chargers automatically start,
❏ the green "rectifier/charger" lights 1 in
the control panels go on,
❏ lights 2 turn red;
■ close the battery circuit breakers QF1;
❏ lights 2 go off;
❏ green lights 3 and 5 on the control
panels go on;
■ close output switches Q5N for the
inverters and in the external bypass unit;
■ open maintenance bypass switch Q3BP
in the external bypass unit;
■ press the "inverter on" button 7 on
each control panel:
❏ the green "inverter" lights 4 flash;
■ when a sufficient number of inverters
are ready, the inverter-output contactors
close:
See figure 15.
Proceed in the following order:
■ close the upstream switches supplying
normal and bypass AC source power (on
the LV switchboard);
■ close normal AC input switch Q1. The
system powers up:
❏ the rectifier/charger automatically starts,
❏ green light 1 on the control panel goes
on,
WARNING
Rectifier/charger start-up
is automatic when normal
AC input circuit breaker
Q1 is closed. DC voltage
is present in the DC bus.
❏ light 2 turns red;
■ close bypass AC input switch Q4S:
❏ green lights 3 and 5 on the control
panel go on;
■ close inverter output switch Q5N;
■ close battery circuit breaker QF1;
❏ light 2 goes off;
■ open maintenance bypass switch
Q3BP;
■ press the "inverter on" button 7 on the
control panel:
❏ the green "inverter" light 4 flashes,
❏ the inverter starts, then, if the bypass AC
source transfer conditions are satisfied,
the load is transferred to the inverter if the
on-line mode is selected.
❏ the green "static-bypass" light 3 goes
off,
start-up of an inverter
When the rectifier/charger is on:
■ press the "inverter ON" button 7 on the
control panel;
❏ the green "inverter" light 4 flashes.
Single-UPS unit
■ the inverter starts, then, if the bypass
AC source transfer conditions are satis-
fied, the load is transferred to the inverter
if the on-line mode is selected. For on-
line mode:
❏ the green "inverter" light 4 remains on,
❏ the "static-bypass" light 3 goes off.
❏ the green "inverter" lights 4 shine per-
manently green;
❏ the "static-bypass" lights 3 go off.
❏ the green "inverter" light 4 shines for
on-line mode.
Parallel UPS unit
■ the inverter starts and awaits the start of
the other inverters;
■ when they are all on or enough have
been started to supply the rated load
power, the output switch for each running
inverter closes and the load is supplied
with power:
Q1
Q1
Q5N
Q1
1
Q4S
Q3BP Q5N
1
0
1
1
1
1
1
1
0
1
2
3
0
0
0
0
0
0
0
0
0
1
2
3
4
5
0
QF1
1
0
1
1
1
1
Q5N
0
I
❏ the green "static-bypass" light 3 goes
off,
1
0
1
0
1
0
❏ the green "inverter" light 4 on the con-
trol panels of the running inverters goes
on.
QF1
0
I
1
0
1
1
1
0
0
0
4
6
Fig. 15
Fig. 16
Start-up
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
shutdown
shutdown of the inverter shutdown of a
rectifier/charger
It is recommended not to stop the rectifi-
■ press the "inverter OFF" button 8 on
the control panel for three seconds (see
figure 19).
er/charger because the battery will no
longer be charged. Except in the case of a
test of the inverter on battery power, the
rectifier/charger should be shutdown after
the inverter to avoid unnecessary battery
discharge.
Proceed in the following order:
■ open battery circuit breaker QF1;
■ open normal AC input circuit breaker
Q1:
single-UPS unit
■ the green "inverter" light 4 on the con-
trol panel goes off;
■ the green "static-bypass" light 3 goes
on;
■ the inverter stops;
■ if bypass AC source (Mains 2) transfer
conditions are satisfied, the inverter shuts
down and the load is transferred to the
bypass AC source;
■ if bypass AC source (Mains 2) transfer
conditions are not satisfied, the inverter
does not shut down. The message
"MAINS 2 OUTSIDE TOLERANCES,
TRANSFER DISABLED" is displayed.
❏ the rectifier/charger shuts down,
❏ the green "rectifier/charger" light 1
goes off.
parallel UPS unit
■ if the system is redundant, i.e. the other
parallel-connected inverters can supply
the load on their own, the inverter shuts
down and the green "inverter" light 4
goes off.
The load is not affected in that the other
inverters continue to supply it normally;
■ if the system is not redundant, the other
inverters go to overload status.
If overload conditions are overrun, the
load is transferred to the bypass AC
source:
❏ the green lights 3 turn green,
❏ the green "inverter" light 4 goes off.
14
Shutdown
Download from Www.Somanuals.com. All Manuals Search And Download.
control-panel display
User’s Manual
Display of alarms
general organization
display of messages
primary message
The display is structured around primary
and secondary messages, measuring
tables and setting screens. As a rule, the
message displayed on the screen is
always a primary one. The secondary
messages, if any, are accessed by press-
In addition to keypad operations, the
graphical display brings up a window giv-
ing the overall device status. The mes-
sage displayed is then said to be primary
(see list in the paragraph below). A prima-
ry message can be used to access the
(ALARM MESSAGE N° 1)
ing keys 9 ▼ and 10 ▼ (see figure 16). measuring tables using keys 13 , 14 , 15
The presence of secondary messages is and 18 on the keypad (see figure 17 in
indicated by the arrow ↓ at the end of the the general appendix). The configuration
primary message. Return to the primary screens can be accessed by pressing key
messages is automatic if the keypad is not 12 .
(ALARM MESSAGE N° 2)
used for 2 minutes, or direct by pressing
key 17 (see figure 14). The display
screen lights up when a key is pressed,
and goes off if no key is pressed for 5
minutes.
A flashing arrow appears at the end of a
primary message if there is a problem or
an alarm; secondary messages can be
(LAST ALARM MESSAGE)
accessed by pressing key
9
on the key-
pad (see the list of secondary messages).
The presence of another message is indi-
cated by the arrows ↓ and ↑ at the end
of the secondary message. They can be
accessed by pressing keys 9 and 10
on the keypad.
The return to the primary message is
automatic after a 2 minute time delay or
by pressing key 17 on the keypad.
main screen
NOTE
Fig. 18
Most functions may be
directly accessed. For
example, when voltage
measurements are cur-
rently displayed, it is pos-
sible to directly access
current measurements by
pressing the "A" button.
IMPORTANT
Select English U. S. as
the display language to
match the displays as
presented in this manual.
1
2
3
4
5
6
1
2
7
8
22
9
10
11
12
13
14
20
15
V
A
W.Hz
17
18
16
fault
19
21
Fig. 17
Control-panel Display
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
list of primary messages
LOAD PROTECTED
LOAD PROTECTED
ECO MODE
BATTERY DISCHARGING
Remaining battery time (min) = XX
% kW used = XXX
LOAD PROTECTED
ON-LINE MODE
This is the normal display when there are
no problems: the load is supplied by the
inverter or the bypass AC source, and bat-
tery backup is available.
The load is supplied by the inverter, but
the normal AC source is down or outside
tolerances and power is supplied by the
battery.
This message indicates the remaining bat-
tery time in minutes prior to inverter shut-
down and the percent load. The battery
time calculation takes into account:
■ the percentage of full rated load power
currently being drawn;
■ the type of battery;
■ battery temperature;
■ battery age.
The buzzer sounds slowly and discontinu-
ously.
This is the normal display when there are
no alarms or problems and the load is cor-
rectly supplied by the inverter, in on-line
mode.
LOAD NOT PROTECTED
ECO MODE
↓
LOAD PROTECTED
PARALLEL ON-LINE MODE
This display indicates that the load is sup-
plied but has no battery backup. The
arrow ↓ indicates the presence of one or
more problems specified in secondary
messages.
This is the normal display when there are
no alarms or problems and the load is cor-
rectly supplied by the inverter in a parallel
UPS system, in on-line mode.
The buzzer sounds continuously.
LOAD FORCED TO INVERTER
ECO MODE
LOAD NOT PROTECTED
ON-LINE MODE
↓
LOAD PROTECTED,
LOW-BATTERY SHUTDOWN
WARNING,
Remaining battery time (min) = XX
% kW used = XXX
The load has been transferred to the
inverter following a specific request by the
user.
This display indicates that the load is not
supplied by the inverter, or that there is no
battery backup. The arrow ↓ indicates
the presence of one or more problems
specified in secondary messages.
This message replaces the preceding if
the power outage persists and the warning
level has been reached.
The buzzer sounds continuously.
The user is warned that the battery is
about to shut down.
The buzzer sounds rapidly and discontinu-
ously.
LOAD NOT PROTECTED
PARALLEL ON-LINE MODE
↓
Situation identical to that in the previous
screen, but for parallel UPS systems.
16
Control-panel Display
Download from Www.Somanuals.com. All Manuals Search And Download.
User’s Manual
list of secondary messages
MAINS 1 OUTSIDE TOLERANCES,
CHECK MAINS 1
INVERTER NOT IN PHASE WITH
MAINS 2.
TRANSFER DISABLED,
CHECK MAINS 2
LOAD ON MAINS 2
The normal AC source (M1) frequency or
voltage is outside specified tolerances and
the rectifier/charger has shut down. The
inverter is on battery power.
The load has been transferred to the
bypass AC source (M2) and is no longer
protected (only in on-line mode). The
buzzer sounds continuously.
The phase difference between the inverter
and the bypass AC source (M2) is outside
tolerances. Transfer of the load between
the inverter and the bypass AC source
(M2) will result in an interruption in the sup-
ply of power to the load.
For parallel UPSs, this message should be
interpreted as meaning the phase differ-
ence between the inverter for which the
message is displayed and the other invert-
ers is outside tolerances.
MAINS 1 INPUT SWITCH Q1
IS OPEN
MAINS 2 OUTSIDE TOLERANCES
TRANSFER DISABLED
CHECK MAINS 2
The normal AC input (M1) switch Q1 is
open. It must be closed for rectifier/charg-
er start-up. The buzzer sounds slowly and
discontinuously.
The bypass AC source (M2) frequency or
voltage is outside tolerances and the
inverter is unable to synchronize.
Transfer of the load from the inverter to
the bypass AC source (M2) or vice-versa
will result in an interruption of the supply
of power to the load. The buzzer sounds
slowly and discontinuously.
INTERNAL UPS FAULT,
LOAD TRANSFER FAULT,
CALL MAINTENANCE
UPS SHUTDOWN
BY AN EXTERNAL COMMAND
The inverter has received a command to
shut down. The command is in the form of
a signal from received the remote-indica-
tions relay board which has been set for
this function.
A fault has occurred in the static switch
that transfers the load between the invert-
er and the bypass AC source (M2).
Servicing by the after-sales support
department is required. The buzzer
sounds continuously.
BATTERY OVERTEMPERATURE,
CHECK VENTILATION
n the inverter is started again.
The battery temperature is outside toler-
ances. The buzzer sounds slowly and dis-
continuously.
MAINS 2 INPUT SWITCH Q4S IS
OPEN
OVERLOAD
RATED CURRENT PER PHASE =
XXX A
CHECK LOAD LEVEL
BATTERY ROOM VENTILATION
FAULT, CHECK VENTILATION
The bypass AC source (M2) input switch
Q4S is open, i.e. backup power for the
load via the bypass AC source (M2) is not
This display informs the user that load cur- available.
rent is greater than rated current, and
A fault requiring servicing has occurred in
the battery room ventilation system. The
rectifier/charger shuts down after a 30-
second time delay.
gives the value. The buzzer sounds con-
tinuously.
INVERTER OUTPUT SWITCH Q5N
IS OPEN
The user must take steps to re-establish
correct operation of the ventilation system.
This message also signals an abnormally
high temperature in the filter inductor.
The buzzer sounds slowly and discontinu-
ously.
UPS SHUTDOWN DUE TO AN
OVERLOAD,
CHECK LOAD LEVEL
Inverter output switch Q5N is open, i.e.
the load cannot be supplied via the inverter.
This message follows the preceding when
the overload persists. The UPS has shut
down and the buzzer sounds continuously.
Control-panel Display
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
BYPASS SWITCH Q3BP
IS CLOSED
THE BATTERY C.B. QF1 IS OPEN,
CHECK THE INSTALLATION
INVERTER NOT CONNECTED
This message may be displayed in parallel
UPS systems, when the inverter is not
connected to the load.
Maintenance bypass switch Q3BP is
closed. The system is in maintenance
configuration and the load is supplied by
the bypass AC source.
Battery circuit breaker QF1 is open. The
load is no longer protected because bat-
tery power is no longer available in the
event of a normal AC source outage. The
buzzer sounds continuously.
PARALLEL UPS,
FORCED TRANSFER INHIBITED
STATIC SWITCH (M2) OFF
DUE TO AN OVERLOAD
LOW BATTERY SHUTDOWN
This message is displayed when forced
connection is requested on a parallel UPS
system for a power extension.
The load is no longer supplied by the
The inverter has shut down at the end of
bypass AC source (M2), due to an extend- battery power. The buzzer sounds continu-
ed overload. The buzzer sounds continu-
ously.
ously.
INTERNAL UPS FAULT,
SELF-TEST FAULT
INTERNAL UPS FAULT,
INVERTER FAULT,
CALL MAINTENANCE
BATTERY CHARGING
Communication between the system and
the display is faulty. The buzzer sounds
slowly and discontinuously.
I BAT. = XXX A
U BAT. = XXX V
The battery is currently being recharged.
A fault has occurred in the inverter.
Servicing by the after-sales support
department is required. The buzzer
sounds continuously.
FORCED TRANSFER TO M2
REQUESTED,
BATTERY AT END OF SERVICE
LIFE CALL MAINTENANCE
POWER TO LOAD MAY BE INTER-
RUPTED
CONFIRM YOUR REQUEST WITH
The battery is nearing the end of its esti-
mated service life. This information is
based on average service-life calculations
since its initial installation. The buzzer
sounds slowly and discontinuously.
INTERNAL UPS FAULT,
CHARGER FAULT,
CALL MAINTENANCE
KEY ↵
This message is displayed following
pressing of the "forced-transfer" key 20,
when the load is supplied via the inverter.
A fault has occurred in the rectifier/charg-
er. Servicing by the after-sales support
department is required.
EMERGENCY OFF
The buzzer sounds slowly and discontinu-
ously.
UPS SUPPLIED BY A GENERATOR
SET
This message is displayed when the
external emergency-off pushbutton is
pressed. The result is:
FORCED TRANSFER TO
INVERTER REQUESTED, POWER
TO LOAD MAY BE INTERRUPTED,
CONFIRM YOUR REQUEST WITH
KEY ↵
This message informs the user that the
UPS has received the order to limit the
current drawn by the rectifier/charger. It is
displayed when the corresponding signal
is transmitted by the remote indications
board which must be configured for this
function.
■ shutdown of the inverter;
■ shutdown of the rectifier/charger;
■ opening of the battery circuit breaker;
■ blocking of the static bypass;
■ opening of the backfeed protection con-
tactor (M2),
■ opening of the Q1 circuit breaker (M1),
■ activation of a relay contact on the
remote-indications relay board.
Servicing by the after-sales support
department is required.
The requested transfer to the inverter may
provoke an interruption in the supply of
power to the load if Mains 2 characteris-
tics are not within the specified tolerances.
VENTILATION FAULT
This message is displayed when a fault
occurs on a fan.
THE NUMBER OF UPS READY IS
INSUFFICIENT,
The buzzer sounds discontinuously.
LOAD TRANSFER IN STAND BY
This message may be displayed in non-
redundant, parallel UPS systems, when
the number of ready inverters in not suffi-
cient to supply the load.
18
Control-panel Display
Download from Www.Somanuals.com. All Manuals Search And Download.
User’s Manual
■ battery 3
❏ voltage;
measurement system
❏ charge or discharge current;
❏ remaining battery time (for the UPS unit
concerned);
The display may be used to read a num-
ber of input and output measurements
made at different points in the system.
See figure 18 .
❏ battery temperature;
■ inverter output 4
❏ frequency;
■ total load 6
❏ phase-to-neutral voltage,
❏ phase-to-phase voltages,
❏ currents of the three phases,
❏ frequency,
■ normal AC source 1
❏ phase-to-phase voltages,
❏ currents of the three phases,
❏ frequency;
■ bypass AC source 2
❏ phase-to-neutral voltage,
❏ phase-to-phase voltages,
❏ frequency,
❏ active and apparent power.
❏ currents of the three phases;
1
3
4
6
U - I - F
U - I
F
U - V - I - F - P
A
B
C
Q1
Q5N
1
2
QF1
D
2
U - V - I - F
Q4S
Fig. 19
RMS
U12
U23
U31
M1
M2
----
----
----
LOAD RMS
M2
----
----
----
LOAD
----
voltage measurements
These measurements may be accessed
by pressing the "V" key 13 . The following
data is displayed.
----
----
----
----
----
----
V1
V2
V3
----
Note:
M1: normal AC source
----
M2: bypass AC source
RMS
I1
M1
----
----
----
M2
----
----
----
LOAD FC-LOAD I-LOAD/I-NOM
current measurements
These measurements may be accessed
by pressing the "A" key 14 . The following
data is displayed.
----
----
----
-.--
-.--
-.--
---- %
---- %
---- %
I2
Note:
CF: crest factor
I3
power and frequency
measurements
These measurements may be accessed
by pressing the "W.HZ" key 16 . The fol-
lowing data is displayed.
LOAD KW
KVA
----
PL/PN = --- %
FP.LOAD = -.-
FREQ.HZ
M1 --.-
M2 --.-
INV --.-
P1
P2
P3
----
----
----
----
Note:
PF: power factor
----
Control-panel Display
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
battery measurements
BATTERY
These measurements may be accessed
by pressing the "battery" key 18 . The
following data is displayed.
U
I
= ---- V
= ---- A
REMAINING TIME
PL / PN
=
=
---- MIN
---- %
T° = ---- °C
selections and settings
These selections and settings may be
accessed by pressing the "contrast" key
12 . The following menu is displayed.
CHOOSE LANGUAGE
CONTRAST SETUP
BUZZER SETUP
LAMP TEST
DATE AND TIME
INVERSE VIDEO
PAST EVENTS
BATTERY TEST
■ selecting the language:
FRENCH
ENGLISH
GERMAN
ITALIAN
SPANISH
DUTCH
SWEDISH
PORTUGUESE
DISPLAY CONTRAST SETUP
■ adjusting the display contrast:
CHOOSE WITH KEYS ▼ OR
▼
▼
↵
VALIDATE WITH KEY
■ adjusting the buzzer volume:
BUZZER VOLUME SETUP
CHOOSE WITH KEYS ▼ OR
↵
VALIDATE WITH KEY
DATE AND TIME SETUP
■ lamp test:
When this function is selected, all the
lights shine orange for three seconds.
YEAR
----
--
MONTH
HOURS
--
--
DAY
■ set date and time:
Use the "▲ ▼" keys to enter the data and
confirm using the "↵" key.
MINUTES
--
SECONDS --
20
Control-panel Display
Download from Www.Somanuals.com. All Manuals Search And Download.
User’s Manual
■ inverse video:
When this function is selected, the text and
background colours are reversed (white
text on black or black text on white).
CHARGE LEVEL
= -- %
= -- MONTH
■ past events:
See section "logging and time-stamping".
REMAINING SERVICE LIFE
■ MANUAL TEST press key
■ battery test:
↵
↵
❏ the screen opposite is displayed when a
battery test is requested. It indicates the
battery charge status and the remaining
service life. A manual or automatic test
may be requested,
■ AUTO TEST
press key
TESTING BATTERY
U BATTERY =
❏ the screen opposite is displayed during
a battery test, whether manual or automat-
ic,
--- V
❏ the screen opposite is displayed follow-
ing a positive, manual battery test,
BATTERY TEST RESULT OK
❏ the screen opposite is displayed follow-
ing a negative, manual battery test,
BATTERY TEST RESULT NOT OK
❏ the screen opposite is displayed follow-
ing a positive, automatic battery test. It
indicates the time since the last test and
provides access to test settings,
TIME SINCE LAST TEST
WEEK -- DAY -- HOUR --
LAST BATTERY TEST RESULT OK
NEW PARAMETERS
YES = ▼ NO = ▼
❏ the screen opposite is displayed follow-
ing a negative, automatic battery test. It
indicates the time since the last test and
provides access to test settings,
TIME SINCE LAST TEST
WEEK -- DAY -- HOUR --
LAST BATTERY TEST RESULT NOT OK
NEW PARAMETERS
YES = ▼ NO = ▼
SELECT TIME OF NEXT TEST WITH KEYS ▼ ▼
❏ the screen opposite is displayed when
the user requests access to the automatic
test settings. It is possible to modify the
interval between two automatic tests,
↵
CHANGE UNITS WITH
WEEK -- DAY -- HOUR --
confirm with key
❏ the screen opposite is displayed when
the battery test cannot be completed.
TEST INTERRUPTED
CHECK PRESENCE OF THE BATTERY
CHECK ALARMS
Control-panel Display
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
alarms
general
maintenance bypass
The auto diagnostic system considers any
system status other than normal as a
problem.
Before taking any action, note down the
messages displayed on the control panel.
Certain problems may prevent the control
panel from functioning.
This operation is possible only if the sys-
tem includes a bypass AC source. It
results in the load being directly supplied
by the bypass AC source via maintenance
bypass switch Q3BP, thus ensuring a
higher level of security in the event of a
malfunction.
In this case, it is strongly recommend-
Switching procedures are explained on
ed to call the MGE UPS SYSTEMS after- drawings next to each switch in the UPS
sales support department.
cabinet and the external bypass unit. See
section "maintenance configuration".
■ If the load is still correctly supplied with
power, it has probably been transferred to
the bypass AC source (static bypass) and
is therefore no longer protected (if the sys-
tem is in on-line mode);
■ if the load is no longer supplied with
power, transfer it manually to the mainte-
nance bypass (see section below).
22
Alarms
Download from Www.Somanuals.com. All Manuals Search And Download.
environment information
User’s Manual
Terminals XR2, XR3, XR4 and XR5 on the
"Media Contacts 11" board of each type of
unit can be used to receive signals from
the operating environment and to transmit
signals concerning the operating status of
the UPS (see figure 16 for the position of
the board, item 12).
■ signal to open battery circuit break-
er(s) QF1 in the event the "emergency off"
button is pressed or to avoid an excessive
battery discharge (lasting more than three
times the rated backup time plus two
hours);
■ repo contact (volt-free changeover con-
tact) used to trip switching devices in the
event of an emergency shutdown.
■ "general alarm" information (volt-free
changeover contact) which includes:
❏ internal faults,
❏ information on temperatures outside tol-
erances in the battery room (optional),
❏ overload information (> In),
❏ static-switch ventilation and power-sup-
ply faults.
signal transmission
■ an auxiliary 24 V power supply, isolat-
ed and backed up, is used to supply:
❏ the undervoltage release of the battery
circuit breaker(s) QF1,
❏ the board that measures the tempera-
ture in the battery room;
■ "low battery" warning signal (volt-free
changeover contact) indicating that battery
time is about to run out. The warning
threshold may be personalized;
■ "load on UPS" signal (volt-free
changeover contact) indicating that the
load is supplied by the inverter. For a sin-
gle-UPS unit, one volt-free changeover
contact may be used to indicate that the
load is supplied by the bypass AC source;
■ "load on battery power" signal (volt-
free changeover contact) indicating that
the inverter is supplied by the battery in
the following cases:
signal reception
The signals should be provided by volt-
free contacts.
■ emergency off:
An NC contact causes shutdown of the
inverter and the rectifier/charger, opening
of the battery circuit breaker, blocking of
the static bypass and activation of a relay
contact on the "Media Contacts 11" board;
■ battery room ventilation fault:
An NO contact causes shutdown of the
rectifier/charger;
NOTE
The maximum breaking
capacity of the
changeover contacts is
5A at 250V.
■ battery circuit breaker QF1 closed:
An NO contact prevents inverter start-up if
the circuit breaker is open;
❏ normal AC source outage or voltage
drop,
❏ rectifier/charger shutdown,
■ battery temperature:
A PC-board, placed near the battery, sup-
plies information on the battery tempera-
ture, thus enabling the rectifier/charger to
regulate the battery voltage;
■ "auxiliary" signals:
Depending on the selected settings, these
signals may be used to provoke:
❏ forced shutdown of the inverter (whatev-
er the status of the bypass AC source),
❏ protected shutdown of the inverter (load
transfer to the bypass AC source).
❏ limiting of the current drawn by the recti-
fier/charger (programmable value) when
supplied by an engine generator set with
an insufficient power rating. The additional
power required by the inverter is supplied
by the battery which discharges,
❏ rectifier/charger current limiting.
This signal, which may be used to initiate
process saving and shutdown procedures,
is time-delayed 30 seconds to avoid
unnecessary operations following micro-
breaks;
■ "maintenance position" signal (volt-
free changeover contact) indicating that:
❏ maintenance bypass switch Q3BP is
closed,
❏ bypass AC source input switch Q4S is
open,
❏ inverter output switch Q5N is open,
❏ battery circuit breaker QF1 is open;
❏ limiting of the battery charge current
(programmable value) if the normal AC
source is replaced by an engine generator
set with an insufficient power rating.
Environment Information
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
logging and time-stamping
presentation of event
time-stamping by Galaxy
PW™
Time-stamping of events by Galaxy PW™
makes it possible to:
■ consult measurement records for a
number of physical values concerning sys-
tem operation.
The time-stamping information may be
accessed via the Galaxy PW™ keypad
and display (standard equipment). This
information may also be forwarded for the
Teleservice function using the JBUS
RS232/485 communications board.
■ log the events;
■ consult the last 500 events that occurred
on the Galaxy PW™ UPS;
■ consult general statistical data on UPS
operation;
utilization via the Galaxy
PW™ display
main menu
The time and date can be set for the UPS
via the main menu on the display (see
below), using the DATE AND TIME com-
mand. The time-stamping information, sta-
tistics and measurement records are also
available via the same menu, using the
PAST EVENTS command.
DATE AND TIME SETUP
>YEAR
DAY
1997
8
MONTH
HOURS
9
8
MINUTES
11
SECONDS 42
▼ ▼
Simply select the desired command with
t▼hea">nd" s▼ignktehyast.cTahnebseelmecotveeddcuosminmgatnhde
can be confirmed by pressing the ↵ key.
setting the date and time for
the UPS
When the DATE AND TIME command is
selected, the screen presented opposite is
displayed:
■ the current values are automatically dis-
played;
■ you can modify any of the displayed val-
ues;
■ position the ">" sign opposite the value
to be modified. Then press the ↵ key;
■ use the ▼ and ▼ keys to modify the
value;
■ the ▼ key increments the value by one;
■ the ▼ key decrements the value by
one;
general instructions for using
most screens
For time-stamped events, the display
begins with the last event logged. To
access older events, press the ▼ key. If
during consultation, you wish to review
more recent events, press the ▼ key.
You can display the desired information
and enter commands using the ▼, ▼
and ↵ keys.
Press the
key to exit the time-stamp-
ing consultation mode and return to the
main menu. If no commands are entered
for five minutes, the system automatically
returns to the normal display mode.
You can scroll through the screens dis-
playing information. Press the ▼ and ▼
keys to scroll up and down through the
screens.
■ the selected value can be confirmed by
pressing the ↵ key. A second value may
then be selected for modification, again
using the ▼ and ▼ keys;
■ modifications are made and confirmed
value by value;
■ press the
key at any time to exit the
DATE AND TIME function.
24
Logging and time-stamping
Download from Www.Somanuals.com. All Manuals Search And Download.
User’s Manual
That is the only means to leave the func-
tion.
If no modifications to values are con-
firmed, exiting the function corresponds to
cancelling the request.
DATE AND TIME SETUP
>YEAR
DAY
1997
8
MONTH
HOURS
9
8
consulting logged (time-
stamped) events
MINUTES
11
SECONDS 42
▼ ▼
When the PAST EVENTS command is
selected, the system displays a screen
indicating the last event logged. Log
screens are very similar to those dis-
played for current events. However, log
screens include a line indicating the corre-
sponding date and time with the mention
"Appearance of" or "Disappearance of",
followed by the standard text for the event
(see example opposite). Consult the user
manual for indications on the meaning of
events.
Example:
02/09/1997 07:25:03 Appearance:
MAINS 2 INPUT SWITCH Q4S IS OPEN
Note: numerical values are never indicated in screens for time-stamped events.
The complete log may comprise up to 500
events. If over 500 events have occurred,
only the last 500 may be consulted:
■ press the ▼ key to display the event
that occurred just before the displayed
event. If the displayed event is the oldest
in the list, the display is not modified;
■ press the ▼ key to display the event
that occurred just after the displayed
event. If the displayed event is the most
recent in the list, the display is not modi-
fied.
For example:
03/09/1997 15:30:23 Disappearance:
OVERLOAD
RATED CURRENT PER PHASE
= _ _ _ A
CHECK LOAD LEVEL
consulting statistics
FIGURES SINCE COMMISSIONING
See the screen opposite.
total backup time (h):
0
0
■ total backup time (h): this is the total
time of operation on battery power since
initial startup of the UPS. It is expressed in
hours;
■ total time on static switch (h): this is
the total time of operation on the static
switch since initial startup of the UPS. It is
expressed in hours;
■ total time on UPS (d): this is the total
time that the load has been supplied by
the UPS since initial startup. It is
expressed in days;
total time on static switch (h):
total time on UPS (d):
3627
1
total time with Tbatt >25°C (h):
FIGURES SINCE RESET
last reset:
05/09/1997
0
elapsed backup time (min):
Logging and time-stamping
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
Use the ▼ and ▼ keys to shift between the beginning and the end of the display.
■ total time with Tbatt > 25° C (h): this
is the total time of operation with the bat-
tery temperature greater than 25° C since
initial startup of the UPS. It is expressed in
hours;
■ last reset: this is the date that the infor-
mation was last set to zero by the
Teleservice function;
■ elapsed backup time (min): this is the
total time of operation on battery power
since the last reset. It is expressed in min-
utes.
■ nb of backups: this is the number of
times the load was supplied by the UPS
from battery power since the last reset;
■ nb of backups < 1 min: this is the
number of times the load was supplied by
the UPS from battery power for less than
one minute, since the last reset;
FIGURES SINCE RESET
nb of backups:
0
0
0
0
0
0
0
nb of backups < 1 min:
1 min < nb of backups < 3 min:
nb of backups > 3 min:
nb of overloads < 5 s:
nb of overloads > 5 s:
nb of times TBatt. > 25°C:
■ 1 min < nb of backups < 3 min: this is
the number of times the load was supplied
by the UPS from battery power for more
than one minute and less than three min-
utes, since the last reset;
■ nb of backups > 3 min: this is the
number of times the load was supplied by
the UPS from battery power for more than
three minutes, since the last reset;
■ nb of overloads > 5 s: this is the num-
ber of times the UPS was overloaded (out-
put current greater than In) for more than
five seconds, since the last reset;
■ nb of overloads < 5 s: this is the num-
ber of times the UPS was overloaded (out- number of times the battery temperature
put current greater than In) for less than
five seconds, since the last reset;
■ nb of times TBatt. > 25° C: this is the
consulting recorded
measurements
was measured at over 25° C, since the
last reset.
Recorded measurements are presented in
the same manner (see opposite):
■ the lists indicate the last 30 measure-
ments recorded for the given parameter.
The chronological order of the measure-
ments is indicated in the figure opposite;
■ the most recent measurement is pre-
sented first, in the upper left-hand corner
of the list. The following measurement is
listed just below, and so on until the 30th
value listed in the bottom right-hand cor-
ner of the list;
PARAMETER NAME (units)
T=30 days
▼ last read: 05/09/1997
M(t+29T)|M(t+23T)|M(t+17T)|M(t+11T)|M(t+05T)
|
|
|
|
M(t+28T)|M(t+22T)|M(t+16T)|M(t+10T)|M(t+04T)
|
|
|
|
M(t+27T)|M(t+21T)|M(t+15T)|M(t+09T)|M(t+03T)
■ the period T between two successive
measurements is 30 days. The displayed
measurements are instantaneous values.
|
|
|
|
M(t+26T)|M(t+20T)|M(t+14T)|M(t+08T)|M(t+02T)
|
|
|
|
M(t+25T)|M(t+19T)|M(t+13T)|M(t+07T)| M(t+T)
|
|
|
|
NOTE
M(t+24T)|M(t+18T)|M(t+12T)|M(t+06T)|
M(t)
when this screen is
selected, approximately
ten seconds are required
to call up and display the
information.
If the number of mea-
surements is greater than
30, only the last 30 (the
most recent) are dis-
played
26
Logging and time-stamping
Download from Www.Somanuals.com. All Manuals Search And Download.
User’s Manual
The battery capacity is the value mea-
sured by the UPS microprocessor. It is
expressed in Ampere-hours. This value
changes over time depending on the para-
meters of the battery itself and its environ-
ment. This measurement is used to check
that the battery is capable of supplying the
rated power in the event of a mains out-
age.
BATTERY CAPACITY (Ah)
T=30 days
▼ last read: 05/09/1997
97 |
96 |
95 |
94 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0
0
0
0
0
0
0 |
The backup time is the value calculated
by the UPS microprocessor on the basis
of measurements carried out on the bat-
tery. It is expressed in minutes. The calcu-
lation uses the percent load and the bat-
tery charge status at the time of the mea-
surement.
BACKUP (min)
T=30 days
▼ last read: 05/09/1997
120 |
115 |
110 |
105 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0
0
0
0
0
0
0 |
The load level is the ratio between the
power supplied by the UPS to the load at
the time of the measurement and the
rated output of the UPS. It is expressed as
a percentage.
OUTPUT LOAD LEVEL(%)
▼ last read: 05/09/1997
T=30 days
63 |
52 |
63 |
63 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0
0
0
0
0
0
0 |
utilization via Teleservice
When the optional JBUS RS232/485 com-
munications board is installed, the time-
stamped information can be sent to the
Teleservice center.
The center can remotely consult the same
information and carry out the same modifi-
cations as the user locally on the display.
Note that only the Teleservice centre can
reset the counters for the statistical data.
Logging and time-stamping
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
maintenance
maintenance
configuration
A
B
C
Q1
Q5N
1
2
QF1
single-UPS unit
See figure 19. During maintenance, the
UPS must be isolated from the normal and
bypass AC source, the battery and the
load.
D
Q4S
■ UPS isolation
Q3BP
Proceed in the following order (see figure
20):
❏ shut down the inverter (press the "invert-
er OFF" button 8 for three seconds),
❏ close bypass switch Q3BP,
❏ open isolating switches Q5N, Q4S, QF1
and Q1.
The UPS is powered down once the
capacitors have discharged (a few min-
utes);
■ start-up
Following servicing, proceed in the follow-
ing order (see figure 21):
❏ close switch Q1, then after approximate-
ly ten seconds, switches QF1, Q5N and
Q4S,
❏ open bypass switch Q3BP,
❏ start the inverter (press the "inverter ON"
button 7 ).
Fig. 19
Q1
1
Q4S
Q3BP Q5N
1
1
OFF
OFF
0
1
2
3
4
5
6
0
QF1
Q1
1
Q4S
Q3BP Q5N
1
1
1
1
1
1
1
2
3
4
5
6
0
0
0
0
0
0
0
0
0
I
0
0
1
0
1
1
1
1
1
1
OFF
0
0
0
0
1
0
1
1
1
0
1
1
0
0
0
1
0
1
0
0
QF1
0
I
1
0
1
1
1
0
0
0
CAUTION
■ work should be car-
ried out in accordance
with applicable safety
regulations;
Fig. 20
Fig. 21
■ to avoid interrupting
the load, the various
switching operations
must be carried out in the
correct order. Operations
are explained in dia-
grams placed next to the
switches;
■ the system cabinet is
only partially powered
down. The load is still
supplied via the bypass
AC source and switch
Q3BP.
28
Maintenance
Download from Www.Somanuals.com. All Manuals Search And Download.
User’s Manual
parallel UPS redundant and
for increased output
See figure 22.
■ isolate all UPSs
Proceed in the following order (see figure
23):
❏ shut down the inverters (press the
"inverter OFF" buttons 8 for three sec-
onds),
❏ close switch Q3BP and open switch
Q5N in the external bypass unit,
❏ open switches Q1, QF1 and Q5N on the
UPS units.
Q3BP
Q5N
Q1
Q5N
1
2
QF1
Q4S
2
Galaxy 1
1
2
Galaxy 2
Galaxy 3
Galaxy 4
1
2
1
2
■ start-up
Following servicing, proceed in the follow-
ing order (see figure 24):
❏ close switches Q5N on the UPS units,
❏ close switch in the external bypass unit,
❏ open switch Q3BP in the parallel-con-
nection unit,
Fig. 22
❏ close switches Q1 and QF1 on the UPS
units,
❏ start the inverters (press the "inverter
ON" buttons 7 ).
Galaxy PW
2
3
4
5
1
external bypass
1
1
1
1
1
Q3BP
Q5N
0
0
0
0
0
0
Q1
Q4S
Q5N
NOTE
1
1
1
1
0
0
0
5
6
7
We recommend that you
call on the after-sales
support department to
carry out these opera-
tions.
Note that for parallel
UPSs for increased out-
put, the entire installation
must be bypassed
because it is not possible
to isolate just one UPS
unit.
0
QF1
0
I
1
0
1
1
0
Fig. 23
Galaxy PW
2
3
4
5
1
external bypass
1
1
1
Q3BP
Q5N
0
0
0
0
Q1
Q4S
Q5N
1
1
1
1
1
1
0
0
0
0
0
5
6
7
0
QF1
0
I
1
0
1
1
0
Fig. 24
Maintenance
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Galaxy PWTM 100 to 225 kVA
battery maintenance
visual check
functional check
Consult the instructions supplied by the
battery manufacturer. Below are a few
general indications:
■ sealed lead-acid batteries: these bat-
teries require no maintenance, but check
■ Power down the system prior to any
maintenance operations.
Note: in redundant parallel UPS systems
the check may be carried out successively load due to incorrect transfer conditions or
on each UPS unit without interrupting the
■ Check that lights 1 , 2 and 3 on the
control panel are not red, to avoid an
interruption in the supply of power to the
a battery problem;
the terminals of each cell from time to time load. In other configurations, the load
■ press the "inverter OFF" button and
check that the buzzer and control panel
lights function correctly (see the section
on operating modes in the introduction);
■ press the "inverter ON" button and
check again that the control panel lights
function correctly;
■ run a transfer to battery test. With the
inverter on, open input circuit breaker Q1.
The orange "battery" light on the control
panel should light. After two minutes on
battery power, close input circuit breaker
Q1. The rectifier/charger should automati-
cally restart and the orange "battery" light
on the control panel should go off;
■ in parallel systems, run these tests on
each UPS unit.
and clean if necessary;
must be supplied via the maintenance
bypass (see "maintenance bypass" in the
"Alarm" section);
■ clean the system regularly, particularly
the air filter inlet and outlet grills. Check
that the air circulates freely in the cabi-
nets. Use a vacuum cleaner if necessary;
■ check that nothing hinders the ventila-
tion at the top and at the back of the sys-
tem.
■ vented lead-acid batteries:
❏ check the electrolyte level regularly and
add water if necessary,
❏ check the voltage of each cell to deter-
mine if it is necessary to equalize the bat-
tery,
❏ check the terminals of each cell and
clean if necessary.
CAUTION
Battery maintenance is
undertaken with the system
powered up. Operations must
be carried out in accordance
with applicable safety regula-
tions by qualified personnel
using insulated tools, gloves
and safety goggles.
Batteries contain danger-
ous substances that will harm
the environment if thrown
away. If you change the bat-
teries yourself, call on quali-
fied organizations for battery
recovery and recycling.
Pb
Pb
30
Maintenance
Download from Www.Somanuals.com. All Manuals Search And Download.
options
User’s Manual
The RJ45 connector of the communica-
tions option delivers information using the
SNMP protocol. The sticker located on the
board indicates the UPS MAC address.
Galvanic isolation and
voltage matching
transformers
The UPS can be equipped with an isola-
tion or auto transformer on both the input
and output to provide galvanic isolation or
voltage step-up or step-down as required.
electrical supervision
"Teleservice"
"Teleservice" is a contract offering continu-
ous remote supervision and maintenance
of UPS systems via a modem. Real-time
communication is established with our
"Teleservice" centre for communication of
all alarms and events occurring in the
installation.
0080C8ABAA01
■ your MAC address is written in the fol-
lowing way : 0080C8 ZZ XX YY ;
■ your default IP address is 168.8.xx.yy
(xx and yy are
Maintenance bypass
GTC board
Maintenance bypass option provides a
direct bypass AC input source (mains 2)
that can be used to supply the critical load
while the UPS is being serviced.
decimal values of XX and YY).
This electronic board provides user
access to the J-Bus communications pro-
tocol. Using the data and address tables
provided, the user can customize his
installation.
For example, MAC address 00 80 C8 AB
AA 01 is related to IP address
168.8.170.1.
Please refer to the "userman.doc" user
manual contained in the directory
"emb/galaxy/snmp/release3.xx" of the
Solution-Pac CD-ROM in order to discov-
er the management capabilities of your
SNMP Galaxy PW™ UPS.
Please contact your sales representative
for more detailed
information.
GTC + software
The user has access to the J-Bus protocol
and, in addition, the associated software
acquires system parameters (measure-
ments, status conditions) and transforms
them into diagrams, alarm messages and
tables. With the click of a mouse, the user
can locally or remotely supervise the UPS
system (comprising one or many UPS
units).
Two-channel network board
This electronic board comprises two ports,
each of which may be user set, either for
the U-Talk protocol or as a relay contact.
U-Talk is the protocol required to establish
contact with the communications software.
Relay contacts may be used for specific
network applications (IBM AS400, Novell,
etc.).
management of computer
networks
Integrated SNMP agent
This electronic board, installed in the UPS
system, enables direct connection to all
Ethernet networks using TCP/IP.
The UPSs may then be supervised via the
computer network. Furthermore, they can
be used to close system files without hav-
ing to add an external SNMP agent.
This board is fully compatible with
TM
"Solution Pac " software.
Options
31
Download from Www.Somanuals.com. All Manuals Search And Download.
This page intentionally left blank
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Reorder form
1660 Scenic Avenue
Costa Mesa, CA 92626
Use this form to order additional copies of this document, or to report any errors,
omissions, or other problems you have experienced.
NAME
COMPANY
STREET ADDRESS
CITY ___________________________________ STATE ___________ ZIP ______________
I would like to order ________ (quantity @ $50.00 each) additional copies of the:
Galaxy PW™
100 to 225 kVA
User’s Manual
86-133060-00 X1
I would like to report the following problems with this document:
33
Download from Www.Somanuals.com. All Manuals Search And Download.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
35
Download from Www.Somanuals.com. All Manuals Search And Download.