Foreword
Using this document
Information may be found primarily by consulting:
◗ the contents,
◗ the index.
Pictograms
Important instructions that must always be followed.
Information, advice, help.
Visual indication.
Action.
Audio indication.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 3
Contents
1. Presentation
1.1 Comet EXtreme range .................................................................................................................. 6
4.5 and 6 kVA tower models ........................................................................................................... 6
4.5 and 6 kVA rack models ............................................................................................................. 6
9 and 12 kVA tower models ............................................................................................................ 7
9 and 12 kVA rack models .............................................................................................................. 7
1.2 Back ............................................................................................................................................... 8
Comet EXtreme 4.5 and 6 kVA ...................................................................................................... 8
Comet EXtreme 9 and 12 kVA ....................................................................................................... 8
1.3 Options .......................................................................................................................................... 9
EPO (Emergency Power Off) .......................................................................................................... 9
Transformer for galvanic isolation or earthing arrangement change .............................................. 9
Battery extensions for UPS backup times of 80 minutes ................................................................ 9
CLA module (Long backup time charger) for backup times of 2 to 8 hours .................................. 10
1.4 Control panel ............................................................................................................................... 11
2. Installation
2.1 Unpacking and checks ............................................................................................................... 12
Comet EXtreme 4.5 and 6 kVA .................................................................................................... 12
Comet EXtreme 9 and 12 kVA ..................................................................................................... 13
2.2 Installation of the rack version .................................................................................................. 14
2.3 Battery-module connections ..................................................................................................... 15
Comet EXtreme 4.5 and 6 kVA .................................................................................................... 15
Comet EXtreme 9 and 12 kVA ..................................................................................................... 15
2.4 Connection to the RS 232 communications port (optional) ................................................... 16
2.5 Installation of the communications-card option ...................................................................... 16
2.6 Connection to the connection modules ................................................................................... 17
3. Operation
3.1 ON LINE operating mode ........................................................................................................... 18
3.2 Start-up ........................................................................................................................................ 19
3.3 Bargraph indications .................................................................................................................. 19
Page 4 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
3.4 Failure of AC input power and operation on battery power.................................................... 20
Transfer to battery power .............................................................................................................. 20
Threshold for the low-battery shutdown warning .......................................................................... 20
End of backup time ....................................................................................................................... 20
Sleep mode ................................................................................................................................... 20
Return of AC input power .............................................................................................................. 20
3.5 Personalization ........................................................................................................................... 21
Function ........................................................................................................................................ 21
"ON / OFF conditions" tab............................................................................................................. 21
"Battery" tab .................................................................................................................................. 22
"Output" tab................................................................................................................................... 22
"By-pass" tab ................................................................................................................................ 22
3.6 Shutdown..................................................................................................................................... 23
Shutdown of connected equipment............................................................................................... 23
Complete shutdown of the UPS .................................................................................................... 23
4. Maintenance
4.1 Troubleshooting .......................................................................................................................... 24
4.2 Replacement of the electronic module ..................................................................................... 26
Disconnecting the connection module .......................................................................................... 26
Reconnecting the connection module ........................................................................................... 27
5. Environment ..................................................................................................................................... 28
6. Appendices
6.1 Glossary....................................................................................................................................... 29
6.2 Index............................................................................................................................................. 31
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 5
1. Presentation
1.1 Comet EXtreme range
4.5 and 6 kVA tower models
Dimensions in mm
(H x W x D)
Electronic module
Battery module
443 x 173 x 465
443 x 173 x 465
Weight in kg
Electronic module
Battery module
14
48
4.5 and 6 kVA rack models
Dimensions in mm
(H x W x D)
Electronic module
Battery module
177 (4U) x 483 x 462
177 (4U) x 483 x 462
Weight in kg
Electronic module
Battery module
18
51
Page 6 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Presentation
9 and 12 kVA tower models
Dimensions in mm
(H x W x D)
Electronic module
443 x 216 x 465
443 x 173 x 465
Battery module
Weight in kg
Electronic module
Battery module
22
48
9 and 12 kVA rack models
Dimensions in mm
(H x W x D)
Electronic module
Battery module
221 (5U) x 483 x 462
177 (4U) x 483 x 462
Weight in kg
Electronic module
Battery module
27
51
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 7
1. Presentation
1.2 Back
Comet EXtreme 4.5 and 6 kVA
1
2
RS232 communications port.
Battery circuit breaker.
3
Communications-card option.
EXB battery module connectors.
Connector for battery extension modules.
Rating plate.
4
5
6
7
Manual by-pass switch.
Connection module.
8
9
Output terminal block.
10
Input terminal block.
Comet EXtreme 9 and 12 kVA
EXB battery modules connectors.
4
Page 8 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Presentation
1.3 Options
EPO (Emergency Power Off)
Available for both tower and rack versions of UPSs with standard backup times and for the battery
extensions, the EPO (Emergency Power Off) option lets you simultaneously switch off the UPS battery circuit
breaker and the upstream circuit breaker of your installation by connecting both of them to a single
emergency off button (not supplied).
For more details, visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/epo.htm
Transformer for galvanic isolation or earthing arrangement change
Comet EXtreme
Transfo 9 - 12 kVA
Comet EXtreme
Transfo 4.5 - 6 kVA
Nominal power
6 kVA
32 A
12 kVA
63 A
Nominal current
Input voltage
230V (+15%, -20%) 230V (+15%, -20%)
Voltage drop
2.2%
1.7%
Frequency
50/60 Hz (+/-10%)
50/60 Hz (+/-10%)
Isolation (EN 61558-1-2-4)
Operating temperature
Max. operating rel. humidity
Derating / altitude
Natural ventilation
Dimensions HxWxD (tower)
Dimensions HxWxD (rack 4U)
Weight (tower)
3.75 kV / 5 M ohms 3.75 kV / 5 M ohms
From 0° to +40°C
95%
From 0° to +40°C
95%
Pn-10% > 1000 m
IP20 ANAN
Pn-10% > 1000 m
IP20 ANAN
443 x 173 x 465 mm 443 x 216 x 465 mm
177 x 483 x 462 mm 177 x 483 x 462 mm
44 kg
48 kg
62 kg
67 kg
Weight (rack)
Important: to simplify installation, connect the Comet EXtreme Transformer downsteam of the UPSs.
Visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/transfo.htm
Battery extensions for UPS backup times of 80 minutes
Battery extensions for 4.5 or 6 kVA Comet EXtreme:
Comet EXtreme offers a standard
backup time of 9/12 minutes.
To increase backup time, it is possible
to connect Comet EXtreme EXB
modules to the UPSs.
Comet
EXtreme
EXB
Comet
EXtreme
EXB
Comet Comet
EXtreme EXtreme
EXB
4.5 /
6 kVA
Comet EXtreme
4.5 / 6 kVA
EXB
4.5 /
6 kVA
Visit our Web site: www.mgeups.com/
products/pdt230/smallups/extreme/
guide.htm.
+
+
+
4.5 /
6 kVA
4.5 /
6 kVA
4.5 kVA:
6 kVA:
12 min
9 min
30 min
23 min
54 min
40 min
80 min
75 min
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 9
1. Presentation
Battery extensions for 9 or 12 kVA Comet EXtreme:
Comet
EXtreme
EXB
Comet
EXtreme
EXB
Comet
EXtreme
EXB
Comet
EXtreme
EXB
Comet EXtreme
9 / 12 kVA
+
+
+
9 / 12 kVA
9 / 12 kVA
9 / 12 kVA
9 / 12 kVA
9 kVA:
12 kVA:
12 min
9 min
30 min
23 min
45 min
40 min
80 min
75 min
The Comet EXtreme EXB modules are available in "tower" and in "rack" models.
The Comet EXtreme EXB modules come with their connection cables.
CLA module (Long backup time charger) for backup times of 2 to 8 hours
Very long backup times, from 2 to 8 hours at full load, require a Comet EXtreme CLA module.
Comet
EXtreme
A
5
2
65Ah
-
12V
Comet
EXtreme
CLA
20
20
20
19
19
19
-65Ah
12V
-65Ah
-65Ah
12V
12V
65Ah
-
-65Ah
12V
65Ah
-65Ah
-
-65Ah
12V
12V
12V
12V
2
2
2
65Ah
-65Ah
12V
-
-65Ah
12V
12V
1
1
1
-65Ah
12V
65Ah
-65Ah
12V
-
-65Ah
12V
12V
65Ah
65Ah
-
-
65Ah
65Ah
65Ah
-
12V
-
-
12V
12V
12V
12V
65Ah
-
-65Ah
12V
-65Ah
12V
12V
2 h
4 h
8 h
-65Ah
12V
Page 10 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Presentation
1.4 Control panel
Alarms
% battery
% load
remaining
100%
80%
11
UPS overload
Electronics fault
Battery fault
100%
80%
50%
20%
12
13
50%
14
Ambient temp.
> 40°C
20%
15
16
Hold down to display
percent load.
Lamp test or buzzer OFF.
17
18
Operation on manual bypass.
Operation on automatic bypass.
bypass
bypass
19
20
Operation in ON-LINE mode.
Operation on battery power.
21
ON/OFF.
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 11
2. Installation
2.1 Unpacking and checks
Comet EXtreme 4.5 and 6 kVA
Electronic module
22
23
24
25
22
23
26
24
25
battery module
25
27
25
27
26
RS 232 communications cable.
Installation and user manual.
25
22
23 CD ROM with "Solution Pac" and
"UPS Driver" softwares.
26 Telescopic rails for mounting in 19" bay with mounting hardware.
27
Cable for connection to battery module.
24
Quick Start documentation.
Page 12 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Comet EXtreme 9 and 12 kVA
Electronic module
23
22
24
25
22
23
25
26
24
Battery module
25
27
27
25
27
27
26
RS 232 communications cable.
Installation and user manual.
25
22
23 CD ROM with "Solution Pac" and
"UPS Driver" softwares.
26 Telescopic rails for mounting in 19" bay with mounting hardware.
27 Cable for connection to battery module.
24
Quick Start documentation.
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 13
2. Installation
2.2 Installation of the rack version
Rack mounting diagram with rails
1
3
3
3
4
3
2
The rails and the necessary mounting hardware are supplied with the UPS in the package.
Page 14 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.3 Battery-module connections
Comet EXtreme 4.5 and 6 kVA
2
Check that the battery circuit breaker
is OFF.
4
27
Connect cable
battery modules.
to the connectors
of the electronic and
2
4
27
Comet EXtreme 9 and 12 kVA
2
Check that the battery circuit breaker
is OFF.
27
4
Connect cable
battery modules.
to the connectors
of the electronic and
2
4
27
4
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 15
2. Installation
2.4 Connection to the RS 232 communications port (optional)
1
22
22
1. Connect the RS 232 communications cable
port on the computer.
to the serial
22
2. Connect the RS 232 communications cable
1
to the RS 232
communications port
on the UPS.
The UPS can now communicate with all MGE UPS SYSTEMS
supervision, set-up or safety software.
1
Pin-out diagram for the RS 232 communications port
on the UPS.
RD TD
OV
5
4
3
2
1
9
8
7
6
RTS
2.5 Installation of the communications-card option
3
Slots for communications card.
It is not necessary to shut down the UPS to install
the communications card:
1. Remove the slot cover
.
3
2. Insert the card in the slot.
3. Secure the card with the two screws.
Page 16 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.6 Connection to the connection modules
This type of connection must be carried out by qualified electrical personnel.
2
Before carrying out any connections, check that the battery circuit breaker
and that the upstream protection devices ( AC-power source) are open (OFF).
is OFF
The overall cable diameter and the cross-sectional area
of the three wires depends on the UPS rating.
Comet EXtreme
9 to 12 kVA
Comet EXtreme
4,5 to 6 kVA
15 to 25.5 mm
15 to 25.5 mm
Cable diameter
Cross-sectional area of each wire
◗ Flexible wire
◗ Rigid wire
4 to 10 mm2
4 to 16 mm2
10 mm2
10 to 16 mm2
29
28
Recommended upstream circuit
breaker
◗ Nominal rating
(47 to 63Hz, 230V)
C60N 32A 2P
(maximum line
current = 26A)
C60N 63A 2P
(maximum line
current = 52A)
◗ Maximum rating
(47 to 63Hz, 187V)
C60N 40A 2P
(maximum line
current = 32A)
C60N 80A 2P
(maximum line
current = 64A)
28
1. Remove the terminal-block cover
.
2. Remove the cable entry knockouts from the cover.
3. Loosen the cable clamp
4. Insert the cable supplying the equipment and the power cable
.
29
9
through the terminal-block cover 28.
10
28
29
Always connect the earthing wire first.
5. Connect the three wires of the equipment cable to the output
.
terminal block
9
Input terminal
block
6. Connect the three wires of the power cable to the input
terminal block
7. Tighten the cable clamp 29 .
10
9
.
10
Output terminal
block
28
8. Refit and secure the terminal-block cover
.
Earthing wires
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 17
3. Operation
3.1 ON-LINE operating mode
This is the normal operating mode for the UPS.
bypass
Two possible cases:
19
19
LED is ON: AC input power is available. Power is drawn
from the AC-power source and supplied to the protected
equipment via the UPS.
bypass
20
LED is ON: AC input power is not available. Power is drawn
from the battery and supplied to the protected equipment.
20
Page 18 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
3.2 Start-up
Prior to initial start-up, check the UPS voltage settings.
The frequency of the output voltage (50 or 60 Hz) is automatically set to that of the input source.
1. Close the upstream device (ON position) controlling the
supply of AC power to the UPS.
2
2. Set the battery circuit breaker(s)
The buzzer beeps three times.
If the supply frequency is different than the default value set on
to ON.
2
the UPS, the new value is set and the buzzer beeps 4 times.
21
3. Press the ON / OFF button
.
All the equipment connected to the UPS is now energised,
however it takes another 30 seconds before the UPS is fully
operational.
19
20
21
After this time, the equipment connected to the UPS is
protected.
19
◗ If LED or 20 do not go ON or if one of LED 11 , 12 , 13 or 14 flash, there is a fault (see section 4.1).
◗ In order to detect any wiring errors, it is essential that the AC-power source be present at the first switch-on.
Subsequently, the device may be switched-on without the presence of the AC-power source.
3.3 Bargraph indications
LEDs
to
provide three different indications.
14
11
1. Remaining backup time in percent (in ON-LINE mode).
11
12
13
14
15
2. Percent load drawn by the protected equipment,
when button is pressed.
15
3. Operating faults (flashing LED and beeps):
Overload.
11
12
13
14
bypass
UPS fault.
Battery fault.
Excessive ambient temperature.
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 19
3. Operation
3.4 Failure of AC input power and operation on battery power
AC input power is not available, the battery steps in to supply the protected equipment.
Transfer to battery power
When AC-power source goes outside tolerances or fails
completely, LED 20 goes ON and the buzzer beeps three times.
bypass
20
Threshold for the low-battery shutdown warning
The low-battery shutdown warning threshold can be set
by the user, with the "UPS Driver" software (default setting
bypass
equal to 20% of full backup time).
LED
flashes when the setted level is reached.
The buzzer beeps every three seconds when less than 10% of
backup time remains.
20
20
There is very little remaining battery backup time.
Close all applications because UPS automatic
shutdown is imminent.
End of backup time
The buzzer sounds continuously.
Press button
to turn the buzzer OFF.
16
16
bypass
The equipment is no longer supplied with power.
Sleep mode
This operating mode may be personalized using the "UPS Driver" software (see section 3.5).
It saves battery power when no equipment is connected to the UPS. Shutdown occurs after 5 minutes.
The UPS automatically restarts when the AC-power source returns to within tolerances.
Return of AC input power
If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart function
(activated by return of AC input power) has not been disabled (see section 3.5).
Page 20 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
3.5 Personalization
Function
Personalization parameters can be set and modified using the "UPS Driver" software installed on a computer
that is connected to the UPS (see section 2.3 Connection to the RS 232 communications port).
Check that the RS 232 cable
is closed.
is correctly connected and that the battery circuit breaker 2
22
"UPS Driver" installation:
1 - Insert the Solution-Pac CD-ROM containing the UPS Driver software in the drive of a PC running
Windows.
2 - Open the Windows File manager or Explorer and select the CD-ROM drive.
3 - Double-click "\Emb\Index.htm", then "UPS Driver".
Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing
a number of tabs, each presenting a set of parameters.
"ON / OFF conditions" tab
Personalizable function
Default setting
Enabled
Automatic start
Cold start (battery power)
Forced shutdown
Enabled
Enabled
Sleep mode
Disabled
Enabled
UPS ON / OFF via software
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 21
3. Operation
"Battery" tab
Personalizable function
Default setting
Options
Once a week
Once a month
No test
"Battery test" intervals
Every day
"Low-battery shutdown warning" threshold
Charger
20% remaining battery
backup time
40% remaining battery
backup time
Standard
CLA (2, 4 or 8 hours)
"Output" tab
Rated AC-power source voltage (see figure 1)
Rated AC-power source frequency
Tolerance for AC-power source frequency
Alarm threshold for overload
230 V
50 Hz
200 V-208 V-220 V-240 V
60 Hz
± 5%
± 1% to ± 10% , in 1% steps
0 to 100%, in 10% steps
Enabled (click to add check)
100%
Restart inverter after short circuit
Disabled
"By-pass" tab
Authorized voltage range for transfer to bypass 187 V to 265 V (for
if fault or overload
187 V to 265 V,
in 1V steps
230 V rated voltage)
Authorized frequency range for transfer to bypass
if fault or overload
± 10%
± 1% to ± 10%, in 1% steps
Transfer to bypass if overload
Enabled
Disabled
Disabled (click to remove check)
Enabled (click to add check)
Transfer to bypass following a fault, whatever
the conditions on the AC-power source
The value selected for the rated UPS voltage impacts on the power available at UPS output
(see the diagram below).
Available power as a percentage
of the rated power
100%
95%
90%
66%
50%
Voltage in V
84
Fig. 1
Page 22 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
3.6 Shutdown
Shutdown of connected equipment
1. Press button
(return to the OFF position).
21
The connected equipment is no longer supplied with power,
but the battery is maintened charged if AC-power source is
present.
21
If the AC source fails, even though the connected
equipment is no longer supplied, the UPS operates on
battery power and therefore reduces the available
backup time.
Complete shutdown of the UPS
21
1. Press button
(return to the OFF position).
The connected equipment is no longer supplied with power.
2
2. Open the upstream device (OFF position) controlling the
supply of AC power to the UPS.
3. Switch the battery circuit breaker(s) 2 to OFF position.
The UPS is now de-energised and the batteries are
no longer recharged.
Warning: if the upstream source is not switched off, the UPS
remains in operation.
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 23
4. Maintenance
4.1 Troubleshooting
11 12 13
,
14
flash, there is a operating anomaly or an alarm.
If one or more LEDs
,
or
If a LED flashes, the bargraph data is no longer displayed.
Troubleshooting not requiring MGE after-sales support
Indication
LEDs 11, 12 ,
Signification
Correction
, 14 The UPS has detected a problem
concerning the wiring of the
connection module input.
Shut down the UPS and check that the
input power cable is properly connected to
the input terminal block and the load to the
output terminal block (see p. 17).
After correcting any wiring errors, restart
the UPS as indicated on page 19. If the
problem persists, call MGE after-sales
support.
13
flash and the buzzer
beeps.
LED 11 flashes and
the buzzer beeps.
UPS overload. Overload is too long
Check the power drawn by the equipment
or too high. The UPS cuts the supply and disconnect any non-priority devices.
of power to the connected equipment
and the buzzer beeps continuously.
LED 14 flashes.
The ambient temperature is higher
than 40° C.
Install the UPS in a room where the
ambient temperature is not greater than
40° C.
The UPS is not designed to
operate more than eight
hours under these conditions.
LED 17 is ON.
The UPS is in maintenance mode
(manual bypass)
See point 5 to 7 of in the "Reconnecting
the connection module" part of section 4.2.
To allow you to use MGE UPS SYSTEMS products effectively and carry out basic maintenance, we offer a
complete range of technical training courses in English and French.
USA Training Center
on Costa Mesa site:
MGE UPS SYSTEMS
1660, Scenic Avenue
Costa Mesa, CA 92626, USA
FRENCH Training Center
on Montbonnot site:
MGE UPS SYSTEMS
140, Avenue Jean Kuntzmann
Zirst - Montbonnot St Martin
38334 - ST ISMIER CEDEX - FRANCE
Tel: (1) 714 557 1636
Fax: (1) 714 557 7230
Email: [email protected]
Tel: (33) (0)4 76 18 34 15
Fax: (33) (0)4 76 18 45 21
Email: [email protected]
Page 24 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
Troubleshooting requiring MGE after-sales support
Indication
Signification
Correction
12
LED
beeps.
flashes and the buzzer UPS electronics have detected a UPS
fault.
Follow the UPS replacement
procedure (see section 4.2).
Depending on the UPS personalization
parameters (see section 3.5), there are Call the after-sales support
two possibilities:
department.
◗ the equipment connected to the UPS
continues to be supplied, but directly
from the AC-power source via the
automatic bypass for a maximum of 8
18
hours (LED
◗ the connected equipment is no longer
ON);
supplied.
The equipment connected to
the UPS is no longer protected.
LED
flashes.
A battery fault was detected during the Call the after-sales support
battery test.
13
department because the
batteries need replacing.
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 25
4. Maintenance
4.2 Replacement of the electronic module
Disconnecting the connection module
1. Turn the manual bypass switch 7 , located behind the UPS
(see section 1.2), from the NORMAL to the intermediate
position.
Before turning the switch,
see the manual
2. Check that LED
position.
is ON before continuing to the BYPASS
18
NORMAL
BY-PASS
7
If LED 18 is not ON, do not switch to the BYPASS
position and call the after-sales support
department.
bypass
3. Turn the manual bypass switch
position to the BYPASS position.
from the intermediate
7
18
The connected equipment is supplied by the AC-
power source, via the manual bypass.
21
4. Shut down the UPS by pressing button
position).
(return to the OFF
21
2
5. Switch the battery circuit breaker(s)
30
to the OFF position.
to free the connection
6. Remove the two fixing screws
module 8 (see next page).
7. Remove the connection cable(s) from the battery module(s).
Before turning the switch,
see the manual
BY-PASS
NORMAL
The UPS can be replaced. The connected equipment is
supplied by the AC-power source.
Page 26 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
Reconnecting the connection module
8
30
1. Secure the connection module
2. Reconnect the connection cable(s) to the battery module(s).
3. Switch the battery circuit breaker(s) to the ON position
using the two screws
.
17
2
18
19
21
and check that LED
is ON.
17
Check that UPS personalization settings still
correspond to the equipment to be supplied
(see section 3.5).
21
4. Press button
5. Check that LED
and wait 20 seconds.
18
is ON.
2
18
If LED
is not ON, do not switch the manual
bypass to the intermediate position and call the
after-sales support department.
7
6. Turn the manual bypass switch
to the intermediate position and check that LED
7. Turn the manual bypass switch from the intermediate
from the BYPASS position
17
is OFF.
7
position to the NORMAL position. LED 17 goes OFF and LED 19
goes ON.
30
8
The connected equipment is again protected by the UPS.
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 27
5. Environment
This product has been designed to respect the environment:
It does not contain CFCs or HCFCs.
It was manufactured in a factory certified ISO 14001.
UPS recycling at the end of service life:
MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable
regulations, all UPS products recovered at the end of their service life (contact your branch office).
Packing:
UPS packing materials must be recycled in compliance with all applicable regulations.
Warning:
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not
correctly recycled by specialized companies.
Page 28 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Appendices
6.1 Glossary
Authorized voltage
Upper and lower voltage thresholds within which the UPS can operate
range for transfer to
bypass if fault or overload
on the automatic bypass in the event of a UPS fault or overload.
Automatic bypass
Automatic switch controlled by the UPS, used to connect the equipment
directly to the AC-power source.
Automatic start following
return of AC input power
When AC input power returns following shutdown at the end of the battery
backup time, UPS automatic start can be enabled or disabled.
Backup time
Bargraph
Time that the connected equipment can operate on battery power.
Device on the front panel indicating the percent remaining backup time
or the percent load.
Battery test
Internal UPS test on battery status.
Cold start
See "Start on battery power".
Connection module
Unit grouping the receptacles for connection to the AC-power source
and the equipment.
Dialog box
A window in a computer program displayed for selection by the user of various
options and parameter settings.
Double conversion
The power supplied to the connected equipment is completely regenerated
by continuous double conversion, i.e. the AC power from the AC-power source
is rectified (AC - DC), then converted back (DC - AC) to AC power.
Equipment
Devices or systems connected to the UPS output.
Forced shutdown
Allows a "clean" of computer operating systems depending on the low battery
threshold setting. If the input source is restored during the time period
between the shutdown order and actual system shutdown, it causes a
voluntary interruption of the supply of power to the connected equipment
(lasting 10 seconds) after system shutdown.
Manual bypass
ON-LINE mode
Rotary switch controlled by the user, used to connect the equipment directly
to the AC-power source. Transfer of the load to the manual bypass enables
UPS maintenance or replacement, without interrupting the supply of power
to the connected equipment.
The normal UPS operating mode, by which the AC-power source supplies
the UPS, which in turn, following double conversion of the AC power,
supplies the connected equipment.
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 29
6. Appendices
Out of tolerance
The AC input source is either absent or its voltage or frequency is outside the
set limits.
Percent load
Personalization
Sleep mode
Ratio between the power drawn by the connected equipment and the total
power that the UPS can supply.
A number of UPS functions can be modified using the "UPS Driver" software
to better meet the user's needs.
This function shuts down the UPS after 5 minutes when it operates on
battery power and no load is detected on the UPS output. The UPS restarts
automatically as soon as the AC input source is restored.
Start on battery power
This function makes it possible to energize the connected equipment even
when AC input power is not available (operation exclusively on battery power).
Tolerance for AC-power
source frequency
The range of frequency supplied by the AC-power source within which
the UPS can operate in ON-LINE mode (double conversion).
UPS
Uninterruptible Power Supply.
UPS ON / OFF
via software
It is possible to enable or disable use of UPS ON / OFF controls
by the computer-system protection software.
Page 30 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Appendices
6.2 Index
A
AC power
O
Overload................................................... 11, 22, 24
Failure ........................................................... 20
Frequency tolerance ..................................... 22
Rated frequency ............................................ 22
Rated voltage ................................................ 22
Return............................................................ 20
P
Personalization ............................................. 21, 23
Battery .......................................................... 22
ON / OFF conditions..................................... 21
Output........................................................... 22
B
Bargraph .............................................................. 19
Battery
R
Rack ........................................................ 6-7, 12-14
Battery test .................................................... 22
End of backup time ....................................... 20
Fault ........................................................ 11, 19
Low-battery shutdown warning ..................... 20
Recycling ....................................................... 28
Transfer to battery power .............................. 20
Buzzer ................................................... 3, 11, 19-20
By-pass
S
Shutdown
Forced shutdown........................................... 21
UPS ON / OFF via software .......................... 21
UPS shutdown ........................................ 11, 23
Sleep mode ................................................... 20-21
Software
Automatic bypass .................................... 18, 25
Manual bypass ............................... 8, 11, 26-27
UPS Driver.............................12-13, 19, 21, 23
Start-up
Automatic start .............................................. 21
C
Communication .................................................... 16
Connection
T
Temperature
Communications card ................................... 16
Connection modules ..................................... 17
RS 232 communications port ........................ 16
Excessive ambient temp ...................11, 19, 24
U
UPS Driver .................................. 12-13, 19, 21, 23
F
Fault (UPS)
Load .............................................................. 11
Transfer to automatic bypass ........................ 25
L
LEDs
Lamp test....................................................... 11
M
Mode
ON-LINE mode........................................ 11, 18
Download from Www.Somanuals.com. All Manuals Search And Download.
51033212EN/AC - Page 31
Page 32 - 51033212EN/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
|