ARMOR
Condensing Water Heater
Submittal Sheet
AWP-Sub-08
ARMORTM CONDENSING WATER HEATER PACKAGE SYSTEM
JOB NAME ______________________________________________________________________
LOCATION ______________________________________________________________________
ARCH./ENGR.____________________________________________________________________
WHOLESALER __________________________________________________________________
MECH. CONTRACTOR ___________________________________________________________
MODEL NO. _____________________________________________________________________
TYPE GAS ______________________________________________________________________
Btu/hr INPUT_____________________________________________________________________
RECOVERY RATE IN GPH_______________________________________@________°F RISE
NOTES
Optional Equipment
Standard Features
> Up to 98% Thermal Efficiency
> Modulating Burner with 5:1 Turndown
> Direct-Spark Ignition
Smart System Features
> SMART SYSTEM Digital Operating Control
> Multi Color Graphic LCD Display
Alarm Bell
Condensate Neutralization Kit
High & Low Gas Pressure Switches
(AW 501-801)
Concentric Vent Kit
(3” & 4” PVC/CPVC only)
ModBus Communications
SMART SYSTEM PC Software
Room Air Vent Kits
> Built in Cascading Sequencer for up to 8 Water Heaters
> Lead Lag
> Low NOx Operation
> Sealed Combustion
> Efficiency Optimization
> Low Gas Pressure Operation
> Vertical & Horizontal Direct-Vent
> PVC, CPVC or SS Venting up to 100 Feet
> PVC/CPVC Sidewall Vent Termination
> Stainless Steel Heat Exchanger
> All Welded Construction, Gasketless Design
> 160 psi Working Pressure
> Building Management System Integration
> Modbus Communication (Optional)
> 0-10VDC Input to Control Modulation or Set point
> 0-10VDC Modulation Rate Output
> 0-10VDC Input to Enable/Disable call for heat
> Access to BMS Settings Through Graphic LCD Display
> Low Water Flow Safety Control & Indication
> Inlet & Outlet Temperature Sensors & Readout
> Flue Temperature Sensor
Stack Frame
Firing Control Systems
> ASME Construction (AW 286-800)
> Natural to L.P. Conversion Kit
> All Bronze Circulating Pump
> On/Off Switch
M9
M7
Standard Construction
California Code
> Water Heater Pump Control
> Pump Delay with Freeze Protection
> Pump Exercise
(AW 286-801)
> Flow Switch
M13
CSD1 / FM / GE Gap
(AW 501-801)
> ASME Temperature & Pressure Relief Valve (286-801) > Night Setback
> Temperature & Pressure Gauge (AW 501-801)
> Downstream Test Valves (AW 501-801)
> Adjustable Leveling Legs
> Building Recirculation loop Pump Control*
> Night Setback of Building Recirculation Loop*
> Time Clock
> Tank Sensor
> Maintenance Reminder
> Ability to program name and number into the product
> Adjustable High Limit w/ Manual Reset
as contact
> Automatic Reset High Limit
> High Voltage Terminal Strip
> 120 VAC / 60 Hertz / 1 Phase Power Supply
> Pump Control Contacts
> Water Heater Pump Control Contacts
> Building Recirculation Pump Control Contacts
> Low Voltage Terminal Strip
> 24 VAC Auxiliary Device Relay
> Auxiliary Proving Switch Contacts
> Flow Switch Contacts
> Alarm on Any Failure Contacts
> Runtime Contacts
> Tank Sensor Contacts
> Cascade Contacts
> Condensate Trap
> Zero Clearances to Combustible Material
> 5 Year Limited Warranty (See Warranty for Details)
> 1 Year Parts Warranty (See Warranty for Details)
> 0-10 VDC BMS External Control Contact
> 0-10VDC Boiler Rate Output Contacts
> Modbus Contacts
*Exclusive to Lochinvar
Download from Www.Somanuals.com. All Manuals Search And Download.
Armor Package Systems Gas Water Heater Dimensions & Specifications
PS Configuration
PU Configuration
AW 150-500 with a 119-504 gallon capacity
Jacketed and Insulated Lock-Temp Vertical Tank.
AW 150-500 with a 119-504 gallon capacity
Jacketed and Insulated Lock-Temp Vertical Tank.
VERTICAL ROUND JACKETED TANK DIMENSIONS
NOTE: Tanks over 500 gallon are available for package
systems. Vertical tanks over 650 gallons require breakaway
frames for shipping purposes. Consult factory for details.
Gallon
H
D
Weight
T
T
119
200
257
318
432
504
62-1/2”
77-1/4”
91”
80”
80”
28”
32”
34”
40”
46”
46”
345
600
1108
1290
1,512
1,623
92”
Package systems with multiple units or storage tanks 752 gallons and larger
will be designed as a “Breakaway” system. Breakaway systems are factory
disassembled for shipping purposes and require some field reassembly.
Consult factory for details.
NOTE: If overall dimensions are critical consult factory.
All package systems are skid mounted.
*Add 3” to tank H for I-Beam skid.
T
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
9/10—Printed in U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
|