RSB-i&s-05
INSTALLATION AND SERVICE MANUAL
HYDRONIC HEATING BOILERS and
DOMESTIC WATER HEATERS
45,000 - 500,000 Btu/hr MODELS
IMPORTANT:
ƽ WARNING
This is a gas appliance and should be installed by a
licensed electrician and/or certified gas supplier.
Service must be performed by a qualified service
installer, service agency or the gas supplier.
Improper Installation, Adjustment,
Alteration, Service or Maintenance
can cause injury or property damage.
Refer to this manual. For assistance or
additional information consult a qualified
installer, service agency or the gas supplier.
WARRANTY
CHECKING EQUIPMENT
Installation and service must be performed by a
qualified service installer, service agency or the gas
supplier.
Upon receiving equipment, check for signs of shipping
damage. Pay particular attention to parts accompanying
the appliance which may show signs of being hit or
otherwise being mishandled. Verify total number of
pieces shown on packing slip with those actually
received. In case there is damage or a shortage,
immediately notify carrier.
Factory warranty (shipped with appliance) does not
apply to appliances improperly installed or improperly
operated.
Experience has shown that improper installation or
system design, rather than faulty equipment, is the
cause of most operating problems.
DO NOT Use this appliance if any part has been
under water. The possible damage to a flooded
appliance can be extensive and present numerous
safety hazards. Any appliance that has been under
water must be replaced.
1. Excessive water hardness causing
a
lime
buildup in the copper tube is not the fault of
the equipment and is not covered under the
manufacturer’s warranty (see Water Treatment
and Water Chemistry).
ƽ WARNING
2. Excessive pitting and erosion on the inside of
the copper tube may be caused by too much
water velocity through the tubes and is not
covered by the manufacturer’s warranty (see
Boiler Flow Rates and Temperature Rise for
flow requirements).
If the information in this manual is not followed
exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
This appliance MUST NOT be installed in any
location where gasoline or flammable vapors are
likely to be present, unless the installation is such to
eliminate the probable ignition of gasoline or
flammable vapors.
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any
phone in your building.
SPECIAL INSTRUCTIONS TO OWNER
Note: Retain this manual for future reference.
This manual supplies information for the installation,
operation and servicing of the appliance. It is strongly
recommended that this manual be reviewed completely
before proceeding with an installation.
• Immediately call your gas supplier from a
neighbors phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fire department.
• Installation and service MUST BE performed by
a qualified installer, service agency or the gas
supplier.
Download from Www.Somanuals.com. All Manuals Search And Download.
CODES
The equipment shall be installed in accordance with
installation regulations in force in the local area where
the installation is to be made. These regulations shall
be carefully followed in all cases. Authorities having
jurisdiction shall be consulted before installations are
made. In the absence of such requirements, the instal-
lation shall conform to the latest edition of the National
Fuel Gas Code, ANSI Z223.1. Where required by the
authority having jurisdiction, the installation must
conform to American Society of Mechanical Engineers
Safety Code for Controls and Safety Devices for Auto-
matically Fired Boilers, ASME CSD-1. All boilers
conform to the latest edition of the ASME Boiler and
Pressure Vessel Code, Section IV. Where required by
the authority having jurisdiction, the installation must
comply with the Canadian Association Code,
CAN/CGA-B149.1 and/or B149.2 and/or local codes.
This appliance meets the safe lighting performance FIG. 2 Typical Boiler (Rear View) Cabinet Construction
criteria with the gas manifold and control assembly
LOCATION OF UNIT
provided as specified in the ANSI standards for
gas-fired appliances, ANSI Z21.13 and ANSI Z21.10.3.
1. Locate the appliance so that if water connections
should leak, water damage will not occur. When
such locations cannot be avoided, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance. The pan
must not restrict combustion air flow. Under no
circumstances is the manufacturer to be held
responsible for water damage in connection with
this appliance, or any of its components.
INSTALLATION PROCEDURE
2. The appliance must be installed indoors where it is
protected from exposure to wind, rain and weather.
3. The appliance must be installed so that the ignition
system components are protected from water
(dripping, spraying, rain, etc.) during appliance
operation and service (circulator replacement,
control replacement, etc.,).
4. Appliances located in a residential garage and in
adjacent spaces that open to the garage and are not
part of the living space of a dwelling unit must be
installed so that all burners and burner ignition
devices have a minimum clearance of not less than
18" (46cm) above the floor. The appliance must be
located or protected so that it is not subject to
physical damage by a moving vehicle.
FIG. 1 Typical (Front View) Cabinet Construction
5. DO NOT install this appliance in any location
where gasoline or flammable vapors are likely to
be present.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
CLEARANCE FROM
COMBUSTIBLE CONSTRUCTION
Clearances from Combustible Construction:
29"
Right Side - 6"
Rear - 6"
Left Side - 18" (24" suggested for service)
Front - 18" (24" suggested for service)
Top - (measured from the top of the unit)
45,000 - 180,000 Btu/hr Models - 14"
199,999 - 500,000 Btu/hr Models - 29"
All units have been approved for alcove installation (an
ALCOVE is a closet enclosure without a front door).
6"
6"
18"
The boiler must not be installed on carpeting.
18"
All units have been approved for use on combustible
surfaces.
Allow sufficient space for servicing pipe connections,
pump and other auxiliary equipment, as well as the
appliance.
FIG. 4 Clearances Models 199,999 - 500,000 Btu/hr
COMBUSTION AND VENTILATION AIR
REQUIREMENTS FOR
CONVENTIONALLY VENTED
APPLIANCES
Provisions for combustion and ventilation air must be in
accordance with Section 5.3, Air for Combustion and
Ventilation, of the latest edition of the National Fuel
Gas Code, ANSI Z223.1, in Canada, the latest edition of
CGA Standard B149 Installation Code for Gas Burning
Appliances and Equipment, or applicable provisions of
the local building codes.
The room where the appliance is installed MUST be
provided with properly sized openings to assure
adequate combustion air and proper ventilation when
the appliance is installed with conventional venting.
FIG. 3 Clearances Models 45,000 - 180,000 Btu/hr
4
Download from Www.Somanuals.com. All Manuals Search And Download.
FIG. 5 Combustion Air Direct from Outside
FIG. 7 Combustion Air from Interior Space
1. If air is taken directly from outside the building
with no duct, provide two permanent openings:
3. If air is taken from another interior space that is
adequately ventilated, each of the two openings
specified above should have a net free area of one
2
a. Combustion air opening, with a minimum free
area of one square inch per 4000 Btu/hr input
square inch for each 1000 Btu/hr (22cm per kW)
of input, but not less than 100 square inches
2
2
(5.5cm per kW). This opening must be located
(645cm ).
within 12" (30cm) of the floor.
b. Ventilation air opening, with a minimum free
area of one square inch per 4000 Btu/hr input
2
(5.5cm per kW). This opening must be located
within 12" (30cm) of the ceiling.
FIG. 8 Combustion Air from Outside Single Opening
4. If a single combustion air opening is provided to
bring combustion air in directly from the outdoors,
the opening must be sized based on a minimum free
area of one square inch per 3000 Btu/hr
FIG. 6 Combustion Air Through Ducts
2
(7cm per kW). This opening must be located
2. If combustion and ventilation air is taken from
the outdoors using a duct to deliver the air
to the room where the appliance is installed, each of
the two openings should be sized based on a
within 12" (30cm) of the ceiling.
minimum free area of one square inch per
2
2000 Btu/hr (11cm per kW).
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Outside air openings shall directly communicate with
the outdoors. When combustion air is drawn from the
outside through a duct, the net free area of each of the
two openings must have twice (2 times) the free area
required for Outside Air/2 Openings. Table A lists the
requirements for the appliance only, additional gas fired
appliances located in the same room will require an
increase in the net free area to supply adequate
combustion air for all appliances. Combustion air
requirements are based on the latest edition of the
National Fuel Gas Code, ANSI Z223.1, in Canada refer
to National Standard CAN B149.1 or B149.2. Check all
local code requirements for combustion air.
ƽ CAUTION
Under no circumstances should the room where
the appliance is installed ever be under a
negative pressure. Particular care should be
taken where exhaust fans, attic fans, clothes
dryers, compressors, air handling units, etc.,
may take away air from the appliance.
The combustion air supply must be completely free of
any flammable vapors that may ignite or chemical
fumes which may be corrosive to the appliance.
Common corrosive chemical fumes which must be
avoided are fluorocarbons and other halogenated
compounds, most commonly present as refrigerants or
All dimensions are based on net free area in square
inches. Metal louvers or screens reduce the free area of
a combustion air opening a minimum of approximately
25%. Check with louver manufacturers for exact net
free area of louvers. Where two openings are provided,
one must be within 12" (30 cm) of the ceiling and one
must be within 12" (30 cm) of the floor of the room
where the appliance is installed. Each opening must
have a net free area as specified in Table A. Single
openings shall be located within 12" (30 cm) of the
ceiling.
solvents,
such
as
freon,
tricholorethylene,
perchlorethylene, chlorine, etc. These chemicals, when
burned, form acids which quickly attack the heat
exchanger finned tubes, headers, flue collectors, and the
vent system. The result is improper combustion and a
non-warrantable, premature appliance failure.
TABLE - A
MINIMUM RECOMMENDED COMBUSTION AIR SUPPLY
Combustion Air Source
Input
Btu/hr
Outside Air/2
Openings
Outside Air/1
Opening
Inside Air/2
Openings
45,000
75,000
90,000
12 in2
19 in2
23 in2
34 in2
45 in2
50 in2
55 in2
56 in2
67 in2
68 in2
79 in2
90 in2
100 in2
125 in2
15 in2
25 in2
30 in2
45 in2
60 in2
67 in2
74 in2
75 in2
89 in2
90 in2
105 in2
120 in2
133 in2
167 in2
100 in2
100 in2
100 in2
135 in2
180 in2
200 in2
224 in2
225 in2
269 in2
270 in2
315 in2
360 in2
400 in2
500 in2
135,000
180,000
199,999
215,000
225,000
260,000
270,000
315,000
360,000
399,999
500,000
6
Download from Www.Somanuals.com. All Manuals Search And Download.
EXHAUST FANS: Any fan or equipment which ex-
hausts air from the room where the appliance is installed
may deplete the combustion air supply and/or cause a
down draft in the venting system, spilling flue products
into the room. Spillage of flue products from the
venting system into an occupied living space can cause
a very hazardous condition that must be corrected im-
mediately. If a fan is used to supply combustion air to
the room where the appliance is installed, the installer
must make sure that it does not cause drafts which could
lead to nuisance operational problems with the
appliance.
VENTING
FIG. 9 Conventional Negative Draft Vertical Venting
Vent installations for connection to gas vents or
chimneys must be in accordance with Part 7, “Venting
of Equipment,” of the latest edition of the National Fuel
Gas Code, ANSI Z223.1, in Canada, the latest edition of
CGA Standard B149 Installation Code for Gas Burning
Appliances and Equipment or applicable provisions of
the local building codes.
A CONVENTIONAL NEGATIVE DRAFT
VENTING SYSTEM
The negative draft in a conventional vent installation
must be within the range of a negative 0.02 to 0.05
inches water column to ensure proper operation. All
draft readings are made while the appliance is in stable
operation (approximately 2 to 5 minutes).
Adequate combustion and ventilation air must be
supplied to the room where the appliance is installed in
accordance with the latest edition of the National Fuel
Gas Code, ANSI Z223.1, in Canada, the latest edition of
CGA Standard B149 Installation Code for Gas Burning
Appliances and Equipment, or applicable provisions of
the local building codes.
Multiple appliance installations with combined venting
or common venting with other negative draft applianc-
es require that each appliance must have draft within
the proper range. If the draft measured above the
appliance’s built-in draft diverter exceeds the specified
range in a dedicated chimney for a single appliance
installation or in combined venting with other negative
draft appliances, a barometric damper must be installed
to control draft.
The distance of the vent terminal from adjacent
buildings, windows that open and building openings
MUST comply with the latest edition of the National
Fuel Gas Code, ANSI Z223.1, in Canada, the latest
edition of CGA Standard B149 Installation Code for
Gas Burning Appliances and Equipment.
TABLE - B
VENT PIPE SIZES
Input Btu/hr
Flue Size
Vent connection is made directly to the top of the
appliance. This appliance is designed with a built-in
draft diverter. No additional external draft hood is re-
quired. The connection from the appliance vent to the
common vent or chimney must be made as direct as
possible.
45,000
75,000
90,000
4"
5"
5"
6"
7"
7"
7"
8"
8"
9"
10"
135,000
180,000
199,999
215,000
260,000
315,000
360,000
399,999
500,000
10"
7
Download from Www.Somanuals.com. All Manuals Search And Download.
On a conventionally vented, negative draft appliance,
the connection from the vent to the chimney or vent
termination on the outside of the building MUST be
made with listed Type “B” double wall (or equivalent)
vent connectors and must be direct as possible with no
reduction in diameter. Use the National Fuel Gas Code
venting tables for double wall vent to properly size all
vent connectors and stacks. The Type “B” vent and
accessories, such as firestop spacers, thimbles, caps,
etc., MUST be installed in accordance with the
manufacturer’s listing. The vent connector and firestop
must provide correct spacing to combustible surfaces
and seal to the vent connector on the upper and lower
sides of each floor or ceiling through which the vent
connector passes.
(a) Seal any unused opening in the common
venting system.
(b) Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion
and other deficiencies which could cause an
unsafe condition.
(c) Insofar as is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to
the common venting system are located and
other spaces of the building. Turn on clothes
dryers and any other appliances not connected
to the common venting system. Turn on any
exhaust fans, such as range hoods and
bathroom exhausts, so they will operate at
maximum speed. Do not operate a summer ex-
haust fan. Close fireplace dampers.
Any vent materials used must be listed by a nationally
recognized test agency for use as vent material.
Locate appliance as close as possible to a chimney or
gas vent.
(d) Place in operation the appliance being
inspected. Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
Avoid long horizontal runs of the vent pipe, 90° elbows,
reductions and restrictions. Horizontal portions of the
venting system shall be supported to prevent sagging.
Horizontal runs must slope upwards not less than 1/4
inch per foot (21 mm/m) from the appliance to the vent
terminal. Follow manufacturer’s instructions.
(e) Test for spillage at the draft hood/relief opening
after 5 minutes of main burner operation. Use
the flame of a match or candle, or smoke from
a cigarette, cigar or pipe.
Do not use an existing chimney as a raceway for a flue
pipe if another appliance or fireplace is vented through
the chimney.
(f) After it has been determined that each
appliance remaining connected to the common
venting system properly vents when tested as
outlined above, return doors, windows, exhaust
fans, fireplace dampers and other gas burning
appliances to their previous conditions of use.
The weight of the venting system must not rest on the
appliance. Adequate support of the venting system must
be provided in compliance with local codes and other
applicable codes. All connections should be secured
with rustproof sheet metal screws.
(g) Any improper operation of the common
venting system should be corrected so that the
installation conforms to the latest edition of the
National Fuel Gas Code, ANSI Z223.1. In
Canada, the latest edition of CGA Standard
B149 Installation Code for Gas Burning
Appliances and Equipment. When resizing any
portion of the common venting system, the
common venting system should be resized to
approach the minimum size as determined
using the appropriate tables in Part 11 in the
latest edition of the National Fuel Gas Code,
ANSI Z223.1. In Canada, the latest edition of
CGA Standard B149 Installation Code for Gas
Burning Appliances and Equipment.
Vent connectors serving appliances vented by natural
draft shall not be connected to any portion of a
mechanical draft system operating under positive
pressure. Connection to a positive pressure chimney
may cause flue products to be discharged into the living
space causing serious health injury.
Common venting systems may be too large when an
existing appliance is removed. At the time of removal
of an existing appliance, the following steps shall be
followed with each appliance remaining connected to
the common venting system placed in operation, while
other appliances remaining connected to the common
venting system are not in operation.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTING TERMINATION
FIG. 12 Vent Termination from Flat Roof 10’ or Less from
Parapet Wall
FIG. 10 Vent Termination from Peaked Roof 10’ or Less
from Ridge
10’ OR MORE
MORE THAN 10'
10'
3’
RIDGE
2' MIN
NOTE:
3' MIN
NO HEIGHT ABOVE
PARAPET REQUIRED
WHEN DISTANCE
FROM WALLS OR
WALL OR
PARAPET
PARAPETS IS MORE
CHIMNEY
THAN 10’.
FIG. 13 Vent Termination from Flat Roof More Than 10’ from
Parapet Wall
CHIMNEY
The vent cap should have a minimum clearance of 4
feet (1.22m) horizontally from and in no case above or
below, unless a 4 foot (1.22m) horizontal distance is
maintained from electric meters, gas meters, regulators
and relief equipment.
FIG. 11 Vent Termination from Peaked Roof More Than 10’
from Ridge
The vent terminal should be vertical and exhaust
outside the building at least 2 feet (0.61m) above the
highest point of the roof within a 10 foot (3.05m) radius
of the termination. The vertical termination must be a
minimum of 3 feet (0.91m) above the point of exit.
The venting system shall terminate at least 3 feet (0.9m)
above any forced air inlet within 10 feet (3.05m).
A vertical terminal less than 10 feet (3.05m) from a
parapet wall must be a minimum of 2 feet (0.61m)
higher than the parapet wall.
The venting system shall terminate at least 4 feet (1.2m)
below, 4 feet (1.2m) horizontally from, or 1 foot (30cm)
above any door, window or gravity air inlet into any
building.
Do not terminate the vent in a window well, stairwell,
alcove, courtyard or other recessed area. The vent can
not terminate below grade. The bottom of the vent
terminal shall be located at least 12 inches (30cm)
above grade.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
To avoid a blocked vent condition, keep the vent cap systems (Type “B” double wall or flexible or rigid
clear of snow, ice, leaves, debris, etc.
metallic liners) are recommended. Consult with local
code officials to determine code requirements or the
Flue gases will form a white plume in winter. Plume advisability of using or relining a masonry chimney.
could obstruct window view.
SIDEWALL VENTING
Flue gas condensate can freeze on exterior surfaces or
on the vent cap. Frozen condensate on the vent cap can
result in a blocked vent condition. Flue gas condensate
can cause discoloration of exterior building surfaces.
Adjacent brick or masonry surfaces should be protected
with a rust resistant sheet metal plate.
IMPORTANT
Examine the venting system at least once a year.
Check all joints and vent pipe connections for
tightness.
Also check for corrosion or
deterioration. Immediately correct any problems
observed in the venting system.
MASONRY CHIMNEY
INSTALLATION
FIG. 14 Sidewall Venting with an Induced Draft Fan
This appliance is NOT approved for sidewall venting
with the negative draft venting system as shipped from
the factory. An induced draft fan MUST be used if the
installation requires that the flue gases be vented out a
sidewall. A properly sized and installed induced draft
fan may also be used to vent the flue gases vertically if
required by jobsite restrictions. The induced draft fan
must be listed by a nationally recognized test agency, be
properly sized and installed per the recommendations of
the induced draft fan manufacturer and meet local code
requirements. Use care to ensure that the mechanical-
ly supplied draft does not exceed the range of a
negative 0.02 to 0.05 inches water column to ensure
proper operation. If draft exceeds the specified range,
the fan must be adjusted or the installation of a baro-
metric damper in the flue may be required to properly
control draft. An induced draft fan MUST be
interlocked into the appliance’s control circuit to start
when the appliance calls for heat. The induced draft fan
MUST also be equipped with a proving switch,
properly interlocked into the appliance’s control circuit
to prove fan operation before the main burners are
allowed to fire. A vertical or sidewall vent termination
for an induced draft fan MUST be installed per the
recommendations of the fan manufacturer and provide
proper clearances from any combustion or ventilation
openings, windows, doors or other openings into the
building. All induced draft fan installations must
comply with local code requirements.
A masonry chimney must be properly sized for the
installation of a gas fired appliance. Venting of an
appliance into a cold or oversized masonry chimney can
result in operational and safety problems. Exterior
masonry chimneys, with one or more sides exposed to
cold outdoor temperatures, are more likely to have
venting problems. The temperature of the flue gases
from an appliance may not be able to sufficiently heat
the masonry structure of the chimney to generate proper
draft. This will result in condensing of flue gases,
damage the masonry flue/tile, insufficient draft and
possible spillage of flue gases into an occupied living
space. Carefully inspect all chimney systems before
installation. If there is any doubt about the sizing or
condition of a masonry chimney, it must be relined with
a properly sized and approved chimney liner system.
Inspection of a Masonry Chimney
A masonry chimney must be carefully inspected to
determine its suitability for the venting of flue gases. A
clay tile lined chimney must be structurally sound,
straight and free of misaligned tile, gaps between
liner sections, missing sections of liner or any signs
of condensate drainage at the breaching or clean
out. If there is any doubt about the condition of a
masonry chimney, it must be relined. An unlined
masonry chimney must not be used to vent flue
gases from this appliance. An unlined chimney must be
relined with an approved chimney liner system when a
new appliance is being attached to it. Metallic liner
10
Download from Www.Somanuals.com. All Manuals Search And Download.
The part number for the automatic vent damper
required on this heating boiler is printed on the rating
plate. Vent damper regulations are design certified per
the latest edition of ANSI Z21.66.
AUTOMATIC VENT DAMPER
This heating boiler is design certified for use with the
automatic vent damper (FIG. 15) part number printed on
the boiler’s rating plate. A vent damper must be
installed on all residential heating boilers with inputs of
less than 300,000 Btu/hr to comply with minimum
efficiency requirements. A vent damper is factory
supplied with residential heating boilers with inputs of
45,000 thru 260,000 Btu/hr. A vent damper is optional
on all heating boilers above 260,000 Btu/hr. A vent
damper is available as an option on all water heaters.
The vent damper is a useful tool for saving energy when
installed inside the living space where air can
circulate freely around the appliance. The vent damper
will not save as much, if any, energy if it is installed in
locations such as:
-Unheated garage
-Attic
-Crawlspace
-Mechanical room that is vented outdoors
For installation and maintenance on the vent damper, refer
to the instructions supplied with the vent damper.
FIG. 15 Vent Damper and Vent Damper Terminal Block
ƽ WARNING
Residential heating boilers with inputs of less than
300,000 Btu/hr must have the vent damper properly
installed and the vent damper wire harness plugged into
the terminal block on the side of the control panel to
allow the boiler to function. Larger input heating
boilers and water heaters will have a jumper plug
installed in the terminal block to allow operation
without a damper. Remove the jumper plug from the
terminal block to connect an optional vent damper wire
harness. The jumper plug MUST be in place if an
optional vent damper is not used on water heaters and
larger input heating boilers.
The vent damper must be installed directly on the
flue outlet located on the top of the draft hood (see
Figure 15). Do not alter the wire harness supplied
with the vent damper. Follow the instructions
supplied with the vent damper.
ƽ CAUTION
An appliance which is shut down or will not
operate may experience freezing due to convective
air flow down the flue pipe connected to the unit.
Proper freeze protection must be provided, see
Freeze Protection.
ƽ CAUTION
Do not install the vent damper within 6" (152 mm)
of combustible materials.
Install the vent damper to service only the single
appliance for which it is intended. If improperly
installed, a hazardous condition such as an explosion or
carbon monoxide poisoning could result.
The damper position indicator must be in a visible
location with access for service following installation.
The damper must be in an open position when appliance
main burners are operating.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
GAS PRESSURE TEST
GAS SUPPLY
1. The appliance must be disconnected from the
gas supply piping system during any pressure
testing of that system at a test pressure in
excess of 1/2 PSIG (3.5kPa).
Verify that the appliance is supplied with the type gas
specified on the rating plate. This appliance is orificed
for operation up to 2000 feet altitude. The appliance
will be derated 4% per 1000 feet above 2000 feet eleva-
tion. Consult the factory for installations above 2000
feet elevation. Field conversions for operation at high
altitude must be performed by certified personnel only.
The appliance will be marked to indicate suitability for
high altitude operation.
2. The appliance must be isolated from the gas
supply piping system by closing a manual
shutoff valve during any pressure testing
of the gas supply piping system at test
pressures equal to or less than 1/2 PSIG
(3.5kPa).
GAS SUPPLY PRESSURE: Measured at the inlet
pressure tap located upstream of the combination gas
valve(s) see Figures 20 - 22, page 17.
3. The appliance and its gas connection must
be leak-tested before placing it in operation.
TABLE - C
GAS SUPPLY PRESSURE
GAS CONNECTION
Nat. Gas LP Gas
1. Safe operation of the appliance requires
properly sized gas supply piping. See data
in Table E.
Max. (Inches Water Column) 10.5
13
Min. (Inches Water Column) *4.5
Min. (Inches Water Column) **5.0
11
11
2. Gas pipe size may be larger than appliance
gas connection.
*Models 45,000 - 360,000 Btu/hr Only
**Models 399,999 - 500,000 Btu/hr Only
3. Installation of a union is suggested for ease
of service, see Figure 16 on page 14.
4. Install a manual main gas shutoff valve,
outside of the appliance gas connection and
before the gas valve or manifold connection,
when local codes require.
Maximum inlet gas pressure must not exceed the value
specified. Minimum value listed is for the purposes of
input adjustment.
MANIFOLD PRESSURE: Measured at the pressure
tap on the downstream side of the combination gas
valve(s) (see Figures 20 - 22 on page 17). The gas
regulator settings for single stage and two stage
operation are factory set to supply proper manifold
pressure for normal operation. To check manifold
pressure, see Manifold Adjustment Procedure. Do not
increase manifold pressure beyond specified
pressure settings shown below in Table D.
5. A trap (drip leg) MUST be provided by the
installer in the inlet of the gas connection to the
appliance, see Figure 16 on page 14.
6. The combination gas valve has an integral
vent limiting device and does not require
venting to atmosphere, outside the building.
TABLE - D
MANIFOLD PRESSURE
Single and Two-Stage
Two Stage
Btu/hr
Input Gas
Full or High Fire Settings
Natural Gas L.P. Gas
Low Fire Settings
Natural Gas
L.P. Gas
45,000
75,000
90,000 - 180,000
199,999
215,000 - 399,999
500,000
3.5"
2.4"
3.5"
2.9"
3.5"
10"
7"
10"
7.5"
10"
0.9"
0.9"
0.9"
0.9"
0.9"
N/A
2.5"
2.5"
2.5"
2.5"
2.5"
N/A
3.5" 10" (two valves)
12
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE - E
SUGGESTED GAS PIPE SIZE
SINGLE APPLIANCE INSTALLATIONS
Btu/hr
INPUT
45,000
75,000
90,000
135,000
180,000
199,999
215,000
260,000
315,000
360,000
399,999
500,000
DISTANCE FROM METER (In Feet)
0-50
1/2"
1/2"
1/2"
3/4"
1"
51 - 100
101 - 200
201 - 300
301 - 500
1 1/4"
1 1/4"
1 1/4"
1 1/2"
1 1/2"
2"
1/2"
3/4"
1"
3/4"
3/4"
1"
1"
1"
1"
1 1/4"
1 1/4"
1 1/4"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/2"
2"
1"
1"
1"
1"
1 1/4"
1 1/4"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
2"
2"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
2 1/2"
2 1/2"
2 1/2"
2"
2"
2"
2"
For each elbow or tee, add equivalent straight pipe from Table F to total length .
TABLE - F
TABLE G
GAS CONNECTIONS
FITTINGS TO EQUIVALENT
STRAIGHT PIPE
45,000 - 135,000
180,000 - 315,000
360,000 - 500,000
1/2"
3/4"
1"
Diameter Pipe (inches)
3/4 1 1/4 1 1/2
1
2
3
4
5
Equivalent length of Straight Pipe (feet)
10
2
2
3
4
5
14
20
7. Optional gas controls may require routing
of bleeds and vents to the atmosphere,
outside the building when required by local
codes.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE - H
MULTIPLE APPLIANCE INSTALLATIONS
GAS PIPING SIZE CHART
Nominal
Iron Pipe
Size, Inches
Length of Pipe in Straight Feet
10
20
30
205
384
789
40
174
328
677
50
155
292
595
923
60
141
267
543
830
70
128
246
502
769
80
121
226
472
707
90 100
113 106
210 200
441 410
666 636
125
95
150 175
86 79
200
74
3/4
1
369 256
697 477
179
369
564
164 149
333 308
513 472
974 871
138
287
441
820
1 1/4
1 1/2
2
1,400 974
2,150 1,500 1,210 1,020
4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100
2 1/2
3
6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300
11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
4
Maximum Capacity of Pipe in Thousands of BTU’s per hour for gas pressures of 13.5 Inches Water Column
(0.5 PSIG) or less and a pressure drop of 0.5 Inch Water Column (Based on the calorific value of Natural Gas,
1025 Btu/ft3 @ 0.60 Specific Gravity)
GAS PIPING
sufficient capacity. Verify pipe size with your gas
supplier.
2. Use new, properly threaded black iron pipe free
from chips. If tubing is used, make sure the ends
are cut squared, deburred and clean. All tubing
bends must be smooth and without deformation.
Avoid flexible gas connections. Internal diameter
of flexible lines may not provide proper volume of
gas.
3. Run pipe or tubing to the gas valve or manifold
inlet. If tubing is used, obtain a tube to pipe
coupling to connect the tubing to the gas valve
or manifold inlet.
4. Thread pipe the proper amount for insertion into gas
valve or manifold inlet as shown in Table H.
DO NOT OVER TIGHTEN. Over tightening may
result in damage to the gas valves. Valve distortion
or malfunction may result if the pipe is inserted too
deeply into the gas valve.
5. Apply a moderate amount of good quality pipe
compound (DO NOT use Teflon tape) to pipe
only, leaving two end threads bare.
FIG. 16 Gas Line Connection
All gas connections must be made with pipe joint
compound resistant to the action of liquefied petroleum
and natural gas. All piping must comply with local
codes. Tubing installations must comply with approved
standards and practices. Reference Figure 16 for a
typical installation.
6. Remove seal over gas valve or manifold inlet.
7. Connect pipe to gas valve or manifold inlet. Use
wrench to square ends of the gas valve (FIG. 17).
Install Piping to Control
1. The gas line should be a separate line direct
from the meter unless the existing gas line is of
14
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Turn the power “OFF” at the main disconnect
switch.
2. Turn gas valve control knob to “PILOT” position
on standing pilot models. Ensure that the standing
pilot remains on. If the pilot goes out, follow the
“Lighting Instructions” for standing pilot models
to light the pilot. Turn gas valve control knob to
“OFF” position on spark ignition models.
3. Remove the 1/8" hex plug located on the outlet
side of the gas valve and install a fitting suitable to
connect to a manometer or magnahelic gauge. See
Figure 18. Minimum range of scale should be up
to 5" w.c. for Natural gas models and 10" w.c. for
L.P. gas models.
FIG. 17 Wrench
8. For L.P. gas, consult your L.P. gas supplier for
expert installation.
4. The 500,000 Btu/hr model will have two gas
valves with a pressure regulator on each valve.
Repeat the following adjustment procedure to set
the manifold pressure on each gas valve.
IMPORTANT
Upon completion of any piping connections to the
gas system, leak test all gas connections with a soap
solution while system is under pressure.
Immediately repair any leaks found in the gas train
or related components. Do Not operate an
appliance with a leak in the gas train, valves or
related piping.
5. Remove pressure regulator adjustment cap screw
on the gas valve. See Figure 18 for location.
6. Turn the power “ON” at the main disconnect
switch.
7. Turn gas valve control knob to “ON” position.
8. Set the thermostat(s) to call for heat.
GAS MANIFOLD PRESSURE
ADJUSTMENT PROCEDURE
9. Observe gas regulator pressure when all burners
are firing. See Table D, Manifold Pressure for
proper regulator pressure settings.
Pressure Regulator Adjustment
(under cap screw)
10. If adjustment is necessary, turn regulator
adjustment screw clockwise to raise regulator gas
pressure, counterclockwise to lower gas pressure,
to proper setting. Note: Adjustment fitting is
plastic and may require slightly greater turning
force than a metal fitting.
Manometer
11. Turn the power “OFF” at the main disconnect
switch.
4
3
2
1
NOTE:
Do not increase regulator pressure beyond specified
pressure setting.
3.5"
0
1
2
3
12. Turn gas valve control knob to “PILOT” position
on standing pilot models. Turn gas valve control
knob to “OFF” position on spark ignition models.
Gas Valve
4
13. Remove fitting from the gas valve and replace the
1/8" hex plug that was previously removed and
tighten.
FIG. 18 Manifold Pressure Adjustment
15
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Repeat the adjustment procedure for the second 6. Turn on gas supply at the manual valve, turn on
gas valve on the 500,000 Btu/hr model. L.P. gas at tank if required.
15. Turn the gas valve control knob(s) to “ON” 7. Turn the power “ON” at the main disconnect
position. switch.
16. Turn the power “ON” at the main disconnect 8. Turn gas valve control knob to “PILOT”
switch. The appliance is now ready to operate.
position on standing pilot models. Follow the
“Lighting Instructions” for standing pilot models
to light the pilot. Turn gas valve control knob to
the “ON” position when the pilot is established.
Turn gas valve control knob(s) to the “ON”
position on spark ignition models.
If manifold pressure can not be properly adjusted, use
the following procedure to check gas supply pressure
with a manometer connected to the inlet pressure tap on
the gas control.
9. Set the thermostat(s) to call for heat.
CHECKING GAS SUPPLY PRESSURE
Gas Supply Pressure
10. Observe the gas supply pressure with all burners
firing. Ensure inlet pressure is within
specified range. Check gas supply pressure with all
other gas fired appliances in operation to ensure
proper gas volume during periods of peak gas
usage.
Manometer
8
7
6
5
4
3
2
1
0
1
2
11. If gas pressure is out of range, contact gas utility,
gas supplier, qualified installer or service agency
to determine necessary steps to provide proper gas
pressure to the control.
12. If the gas supply pressure is within the specified
range, proceed with the following steps to return
the appliance to service.
3
Gas Valve
4
5
6
7
8
13. Turn the power “OFF” at the main disconnect
switch.
FIG. 19 Gas Supply Pressure
14. Turn gas valve control knob to “PILOT” position on
standing pilot models. Turn gas valve control
knob(s) to “OFF” position on spark ignition models.
1. Turn the power “OFF” at the main disconnect
switch.
2. Turn gas valve control knob(s) to the “OFF”
position.
15. Shut off gas supply at the manual valve in the gas
piping to the appliance. If fuel supply is
L.P. Gas, shut off gas supply at the tank.
3. The 500,000 Btu/hr model will have two gas
valves. Turn the gas valve control knob on each
valve to the “OFF” position.
16. Remove the manometer and related fittings from
the “inlet” side of the gas valve, replace 1/8" hex
plug in gas valve.
4. Shut off gas supply at the manual valve in the gas
piping to the appliance. If fuel supply is L.P. gas,
shut off gas supply at the tank.
17. Turn on gas supply at the manual valve, turn on
L.P. Gas at tank if required.
5. Remove the 1/8" hex plug, located on the “inlet”
side of the gas valve and install a fitting suitable to
connect to a manometer or magnahelic gauge. On
two gas valve models, remove the hex plug from
the gas valve closest to the gas supply connection.
Range of scale should be 14" w.c. or greater to
check inlet pressure. See Figures 18 and 19 for
location.
18. Turn the power “ON” at the main disconnect
switch.
19. Turn the gas valve control knob(s) to the “ON”
position. If the pilot is not burning, follow the
“Lighting Instructions” for standing pilot models to
light the pilot. Spark ignition models will automat-
ically light the pilot on a call for heat.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
20. Set the thermostat to call for heat. The appliance
is now ready to operate.
IMPORTANT
Upon completion of any testing on the gas system,
leak test all gas connections with a soap solution
while main burners are operating. Immediately
repair any leak found in the gas train or related
components. Do Not operate an appliance with a
leak in the gas train, valves or related piping.
Check burner performance by cycling the system while
you observe burner response. Burners should ignite
promptly. Flame pattern should be stable, see
“Maintenance-Normal Flame Pattern.” Turn system
off and allow burners to cool, then cycle burners again
to ensure proper ignition and flame characteristics.
FIG. 22 M9 Gas Valve 45,000 - 399,999 Btu/hr Models
Each unit has a combination gas valve(s) to control the
gas supply to the burners. The 500,000 Btu/hr model
has two combination gas valves to supply gas to the
burners. The combination valve consists of a gas
regulator and two valve seats to meet the requirements
for redundant gas valves. The valve has a gas control
knob that must remain in the open position at all times
when the appliance is in service. Each gas valve has
pressure taps located on the inlet and outlet sides.
Manifold pressure is adjusted using the regulator
located on the valve. The manifold pressure is preset at
the factory and adjustment is not usually required. If
the manifold pressure is to be adjusted, follow the “Gas
Manifold Pressure Adjustment Procedure”, page 15 for
proper adjustment.
COMBINATION GAS VALVES
Pressure Regulator
Adjustment (under cap screw)
Outlet Pressure Tap
Inlet
Pressure
Tap
Pilot Outlet
Gas Control
Knob
Red Reset Button
Venting of Combination Gas Valves
The combination gas valve regulator used on all models
is equipped with an integral vent limiting orifice. The
vent limiter ensures that the volume of gas emitted from
the valve does not exceed the maximum safe leakage
rate allowed by agency requirements. Combination gas
valve/regulators equipped with integral vent limiters are
not required to have vent or relief lines piped to the
outdoors. A dust cap is provided at the vent termination
point on the valve to prevent blockage of the vent
limiter by foreign material. The combination gas valve
regulator with an integral vent limiter complies with the
safety code requirements of CSD-1, CF-190(a) as
shipped from the manufacturer without the installation
of additional vent lines.
FIG. 20 F1 Gas Valve 90,000 - 270,000 Btu/hr Models
FIG. 21 F9 Gas Valve 90,000 - 500,000 Btu/hr Models
17
Download from Www.Somanuals.com. All Manuals Search And Download.
WATER FLOW SWITCH (IF EQUIPPED)
RELIEF VALVE
FIG. 24A Water Flow Switch Water Heater - Side Connections
FIG. 23A Relief Valve - Water Heater
FLOW SWITCH
RELIEF
VALVE
FIG. 24B Water Flow Switch Boiler - Top Connections
A water flow switch is available as a factory supplied
option on all heating boilers and water heaters. The
flow switch should be wired between terminals X and
B. Remove the jumper between the X and B terminals
on the terminal strip. This wiring connection installs
the flow switch in the 24 VAC safety circuit to prove
water flow before main burner ignition. A flow switch
installed with the factory supplied minimum adjustment
setting requires a specific minimum flow to make the
switch and start burner operation. The minimum flow
requirement to actuate the switch is specified in Table I.
The flow rate required is a function of the diameter of
pipe and tee used for installation. Ensure that the pump
installed on the boiler or water heater will supply
adequate flow to make the flow switch contacts and
operate the boiler.
FIG. 23B Relief Valve - Boiler
This appliance is supplied with a relief valve(s) sized in
accordance with ASME Boiler and Pressure Vessel
Code, Section IV (“Heating Boilers”). The relief
valve(s) is mounted directly into the heat exchanger
inside the header. To prevent water damage, the dis-
charge from the relief valve shall be piped to a suitable
floor drain for disposal when relief occurs. No reducing
couplings or other restrictions shall be installed in the
discharge line. The discharge line shall allow complete
drainage of the valve and line. Relief valves should be
manually operated at least once a year.
ƽ CAUTION
Avoid contact with hot discharge water.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
A water flow switch meets most code requirements 4. To avoid serious damage, DO NOT energize the
for a low-water cut off device on boilers requiring
forced circulation for operation.
appliance until the system is full of water.
Serious damage may result.
5. Provide the unit with proper overload protection.
TABLE I
6. Install a wall thermostat on the inside wall. DO
NOT install the thermostat in an area affected by
drafts, sunlight, light fixtures, hot or cold water
pipes or near a fireplace. See “Terminal Strip Con-
nection of a Room Thermostat”, page 38 for proper
wiring connection.
MINIMUM FLOW RATE REQUIRED TO
ACTUATE FLOW SWITCH
Pipe Size
GPM Flow Rate
1 1/2"
2"
13
18
TABLE J
AMP DRAW DATA
45,000 thru 500,000 Btu/hr Models
LOW WATER CUTOFF (IF EQUIPPED)
MAXIMUM
A hot water boiler installed above radiation level must be
provided with a low water cutoff device either as part of
the unit or installed at the time the boiler is installed. An
electronic low water cutoff is available as a kit on all
units. Low water cutoffs should be inspected every six
months, including flushing of float types.
FIRING
TOTAL AMPS
@ 120 VAC
CONTROLS
F1 Standing Pilot (Single Stage
90,000 - 260,000 Btu/hr)
2.5
2.5
2.5
F9 Intermittent Pilot (Single Stage
90,000 - 399,999 Btu/hr)
TWO STAGE BURNER
CONTROL SYSTEM
F9 Intermittent Pilot (Single
Stage/2 valves 500,000 Btu/hr)
The 45,000 thru 500,000 Btu/hr boilers (M9) are
equipped with a two stage burner control system. The
45,000 thru 399,999 Btu/hr models will be equipped
with a two stage gas valve to control high/low burner
operation. The 500,000 Btu/hr model achieves two
stage burner firing by staging the operation of the two
combination gas valves.
M9 with Internal Pump
(45,000 - 260,000 Btu/hr)
2.0
2.0
M9 Intermittent Pilot (Two Stage
Valve 315,000 - 399,999 Btu/hr)
M9 Intermittent Pilot (Two Stage/2
valves 500,000 Btu/hr)
2.0
Pump Wiring for a Heating Boiler
ELECTRICAL CONNECTIONS
The heating boiler circulating pump must be purchased
locally. The maximum load for the pump switched by
the internal pump relay must not exceed 1 HP. The
current draw for a field installed 120 VAC pump MUST
be added to the boiler’s current draw to determine the
minimum wire size for 120 volt service.
This appliance is wired for 120 VAC service. The
appliance, when installed, must be electrically
grounded in accordance with the requirements of the
authority having jurisdiction or in the absence of such
requirements, with the latest edition of the National
Electrical Code ANSI/NFPA No. 70. When the unit is
installed in Canada, it must conform to the CSA C22.1,
Canadian Electrical Code, Part 1 and/or local Electrical
Codes.
1. All wiring between the appliance and field
installed devices shall be made with type T wire
[63° F(35° C) rise].
2. Line voltage wire exterior to the appliance must be
enclosed in approved conduit or approved metal
clad cable.
3. The pump must run continuously when the
appliance is being fired.
FIG. 25 Standing Pilot System F1 Control Panel
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Temperature Control Settings
There are three setting knobs on the temperature control
unless your unit is specified as a boiler only with an
outdoor air reset option. If your unit is a boiler only with an
outdoor air reset option, there are additional controls for
this option. They are explained under Outdoor Air Reset
Option, page 22.
The three setting knobs on the temperature control are for
Set point, Differential, and High-Fire Offset (see
Figure 28).
FIG. 26 Intermittent Pilot System F9/M9 Control Panel
FIG. 28 Temperature Control
Maximum Set Point Determination
The maximum set point for the control is factory set.
Boilers can be set to 240°F max., water heaters are set to
190°F max., and specialty state and local codes to 200°F.
These maximum set points are established by cutting the
OJ1 and OJ2 jumpers located on the right side of the
temperature controller. The maximum set point is
determined as shown below in TABLE-K.
FIG. 27 Control Panel Assembly 500,000 Btu/hr
TEMPERATURE ADJUSTMENT
Operating Temperature Control
TABLE K
Maximum Set point Determination
NOTE:
Max.
The temperature controller is pre-set at the factory with
test settings. You may need to adjust the settings to meet
your specific needs.
OJ1
OJ2
Set Point
Connected
Cut
Connected
Connected
240°F
190°F
Connected
Cut
Cut
Cut
200°F
160°F
ƽ WARNING
Return water temperatures must not be less than
140°F. If lower return water temperatures are
required, follow the instructions for Low
Temperature Bypass Requirements or Three-Way
Valves, see page 35.
NOTE:
Anytime that OJ1 is the only jumper cut, a new
overlay is required under the Set Point knob on the
temperature controller because the scale has changed
to a maximum of 190°F.
Locating Temperature Control
Remove the control panel door on the front of the unit in
order to locate and access the temperature control.
Anytime the OJ2 jumper is cut (with or without OJ1),
a new overlay is required under the Set Point knob on
the temperature controller because the scale has
changed to a maximum of 200°F.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Set Point
for water heater applications. Connect this sensor to the
two blue wires in the upper left-hand corner of the control
panel.
The Set Point knob specifies the target outlet water
temperature in degrees, Fahrenheit. After the water
temperature reaches the set point, the temperature control
shuts off the burners.
Outdoor Air Temperature Sensor
The outside air temperature sensor will only be used for
boiler systems. The outside air sensor is optional. This
sensor allows you to tie boiler operation to the outdoor air
temperature. As outside temperatures drop, the control will
increase the temperature setting of the boiler. As outdoor
temperatures rise, the control will decrease the temperature
to the selected set point of the boiler. You can set the
control to shut the boiler off when a desired outdoor air
temperature level is reached.
Differential
The Differential specifies the number of degrees below the
set point that the control will allow the water temperature
to drop before it brings the unit back on again.
High-Fire Offset
The temperature control operates a two-stage firing system.
The two stages are High-Fire and Low-Fire. High-Fire
operates all burners at full rate while Low-Fire operates the
burners at approximately one-half rate.
You must purchase the sensor from the appliance
manufacturer. The sensor comes with a housing that helps
protect the sensor from the elements. Mount the air sensor
housing outdoors, under the eve of the roof. Make sure the
housing is out of direct sunlight. This will ensure that the
sensor will accurately read the true outdoor temperature.
Connect the outdoor air temperature sensor to the terminal
block on the outdoor air reset board. For more information
on wiring the sensor, see Wiring of Remote Sensors, this
page.
The High-Fire Offset knob specifies the number of degrees
below set point that the High-Fire stage shuts down. At that
point, the unit will continue to operate at the Low-Fire
stage until the set point is reached.
The High-Fire Offset knob has settings between 0°F and
20°F. If set at 0°F, the High-Fire Offset is disabled and the
unit will operate the High-Fire stage until the set point is
reached and the temperature control shuts the unit off.
No matter what the High-Fire Offset knob is set to, the unit
will light at Low Fire and operate for approximately 10 to Installation of Remote Sensors
120 seconds before the High-Fire stage actuates.
Make sure to insert the sensor all the way into the bulbwell,
leaving no air pocket between the front surface of the
sensor and the back of the bulbwell. Air pockets are
thermally non-conductive and will cause sensors to read
inaccurately.
Boiler Application
Standard boiler units are shipped with one sensor, the inlet
water temperature sensor. An optional sensor can be
purchased and installed for use as a remote system sensor.
Boilers with the outdoor air reset option also have an
outside air temperature sensor.
System Sensor
The system sensor is used for boiler applications. Install
the sensor in the system supply to the building.
Water Heater Application
Water heater units are shipped with two sensors; the inlet
water temperature sensor and the multi-purpose
temperature sensor to be used as a tank sensor.
Tank Sensor
The tank sensor is used in water heating applications.
Install the sensor in a water storage tank to measure water
temperature. For more information on wiring the sensor,
see Wiring of Remote Sensors below.
Temperature Control Sensors
This is a two-stage temperature control that controls the
burner ignition and pump functions. This temperature
controller can measure up to three different sensor inputs,
depending upon how the unit is set up. They are as follows:
1. Inlet Water Temperature Sensor
2. Multi-Purpose Temperature Sensor
3. Outside Air Temperature Sensor
Wiring of Remote Sensors
To wire remote sensors, follow the guidelines below. Take
care to correctly wire sensors to the unit. Erratic
temperature readings can be caused by poor wiring
practices. Twist the wires between the unit and the remote
sensor. Turn wires at least three or four turns per linear foot
of wiring. This provides protection against some types of
electrical interferences.
Inlet Water Temperature Sensor
1. Do not route temperature sensor wiring with building
power wiring.
This sensor measures the inlet water temperature coming
into the unit.
2. Do not locate temperature sensor wiring next to control
The inlet water temperature sensor is placed into the inlet
bulbwell on the boiler. This sensor is installed by the
factory in new units.
contactors.
3. Do not locate temperature sensor wiring near electric
motors.
Multi-Purpose Temperature Sensor
Depending upon how your unit is set up, this sensor can be
used as a system sensor in a boiler system or a tank sensor
4. Do not locate temperature sensor wiring near welding
equipment.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Make sure good mechanical connections are made to
the sensor, any interconnecting wiring and the
controller.
6. Do not mount sensor with leadwire end pointing up in
an area where condensation can occur.
7. Use shielded wiring to connect the sensor to the control
when the possibility of an electrically noisy
environment exists. Shielded cable is recommended on
all cable runs of more than 25 feet in length.
Ratio
The Ratio knob allows control over the reset ratio to be
used during Outdoor Air Reset. The allowable ratios are as
low as 0.5:1 or as high as 1.5:1.
Selecting the 0.5:1 ratio will increase the set point 0.5° for
every 1.0° drop in outdoor air temperature up to the
maximum set point temperature.
Selecting the 1.5:1 ratio will increase the set point 1.5° for
every 1.0° drop in outdoor air temperature up to the
maximum set point temperature.
NOTE:
If the outdoor design and boiler design temperatures are
known, the Ratio setting can be calculated using the
following formula:
Ground the cable shield at the connection to the boiler
temperature control only. Do not ground the shielded
cable at the sensor end.
Ratio = (boiler design temperature - operator set point)
(O.A. Max. setting - outdoor design temperature)
To maintain temperature accuracy, sensor wires should
be 18 AWG two conductor (18/2). Use shielded wire if
required.
Note that the reset set point cannot exceed the maximum
set point of the boiler thermostat.
OUTDOOR AIR RESET OPTION
Outdoor Air Reset Option
These settings are illustrated graphically in Figure 30.
For boilers ordered with the Outdoor Air Reset option,
there is an additional control (FIG. 29). There are three
setting knobs for Shutdown, Outdoor Air Max., and Ratio.
There is also a switch to turn the outdoor air shutdown
feature On or Off. An O.A. Sensor is also included.
(c)2002 L.C.
CN1
CN3
55
CN2
OJ1
CN7
50
60
65
O.A. SENSOR
CN4
45
CN8
ON
ENABLE
SW1
VR3
DISABLE
40
70
W1
CN5
CN6
OJ2
O.A. SHUTDOWN
SHUTDOWN
55
1.0
0.9
0.8
1.1
50
45
60
65
1.2
1.3
1.4
1.5
RATIO
10
0.7
0.6
W3
W2
VR1
VR2
0.5
40
70
W1
CN1
O.A. MAX.
CN9
160
11
12
9
10
200
8
7
140
120
15
20
HIGH-FIRE
OFFSET
5
FIG. 30 Outdoor Air Control Example Chart
13
14
15
220
6
Outdoor Air Shutdown Enable/Disable Switch
The Outdoor Air Shutdown Enable/Disable switch turns
the outdoor air shutdown feature On and Off. Disabling the
Outdoor Air Shutdown feature allows the unit to operate
regardless of the outdoor air temperature. This is needed
for indirect domestic hot water systems for example.
VR2
VR3
5
(F-)0
240
DIFFERENTIAL
OFF
TST2314
SETPOINT
FIG. 29 Optional Outdoor Air Reset Control
Shutdown
The Shutdown knob specifies the outdoor air lockout
temperature at which the control would prevent the unit
from operating.
ADDITIONAL TEMPERATURE
CONTROLS
High Water Temperature Limit Control
Outdoor Air Max (O.A. Max)
The O.A. Max knob allows a reset up to the maximum
outdoor air temperature specified by this knob setting.
When the outdoor air temperature is above the specified
setting, the unit will not function in the O.A. Reset Mode,
but will continue to run at the selected set point
temperature.
The appliance is supplied with a fixed setting, auto-reset
high water temperature limit control. The setting of this
control limits maximum discharge water temperature. If
water temperature exceeds the setting, the limit will
break the control circuit and shut down the appliance.
The limit control will only be reset after the water tem-
perature has cooled well below the setting of the limit.
The auto-reset high water temperature limit control is
mounted in the outlet side of the front header.
Note that the set point knob will now indicate the
“minimum” boiler temperature. Target temperature is
determined by the ratio and outdoor air temperature below
the O.A. Max setting.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Manual Reset High Water Temperature Limit
Control (Standard Fixed Settings on Water Heaters and
Optional Adjustable Settings on Boilers and Water Heaters)
Water heaters are supplied with a fixed setting, manual
reset high water temperature limit control. This manual
reset temperature limit control has a fixed limit setting
of 230°F (110°C). If water temperature exceeds this
setting, the limit will break the control circuit and shut
down the unit. The limit control can only be reset after
the water temperature has cooled well below the setting
of the limit. Reset of the limit control is accomplished
by pushing the Red Reset Button (Manual Reset High
Limit) (see Figures 25 - 27 on pages 19 and 20) located
on the front side of the control panel. A label on the
control panel indicates the exact location of the manual
reset high water temperature limit control.
FLAME ROLL-OUT SWITCH /
INTERLOCK SWITCH
BLOCKED VENT AND FLAME
ROLL-OUT/FLAME INTERLOCK SWITCH
FIG. 32 Flame Roll-Out/Flame Interlock Switch Location
All units are equipped with manual reset blocked vent
and flame roll-out / flame interlock switches. These
temperature switches are located in the controls
compartment and in the relief opening of the boiler’s
built-in draft hood. Each switch has a red reset button.
In the event the system has actuated to shut off the main
burner gas supply, wait for the boiler to cool, then press
the red reset to return the boiler to operation. Operation
of a blocked vent and/or flame roll-out / interlock
switch usually indicates a problem with the venting
system, obstruction of the heat exchanger flue gas
passageway and/or a combustion air supply problem.
The cause for operation of the blocked vent and/or
flame roll-out / interlock switch must be determined and
corrected. If the boiler cannot be restored to normal
operation, contact a qualified service installer, service
agency or the gas supplier.
FIG. 31 Blocked Vent Switch Location
INITIAL START-UP
Follow the Lighting Instructions on the label applied to
the appliance.
A. On water heaters and boilers with the system
pump delay option, the operating temperature
control will energize the pump relay which
energizes the pump on a call for heat. The
operating temperature control will de-energize
the pump relay approximately 30 seconds after
the call for heat ends. If either the inlet sensor
or the optional multi-purpose temperature
sensor reads below 40°F, the pump relay will
turn ON. When the temperature rises above
50°F the pump relay will turn OFF.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
On boilers, the pump will operate whenever the
“W” terminal is energized.
LIGHTING INSTRUCTIONS FOR
STANDING PILOT MODELS (F1)
MODELS 90,000 THRU 270,000 Btu/hr
INPUT FOR YOUR SAFETY READ
BEFORE OPERATING
B. Location - The appliance should be located
within a room having a temperature safely
above freezing [32°F(0°C)].
C. Shutdown and Draining - If, for any reason,
the appliance is shut off, the following
precautionary measures must be taken:
ƽ WARNING
If you do not follow these instructions exactly, a
fire or explosion may result causing property
damage, personal injury or loss of life.
1. Shut off gas supply,
2. Shut off water supply.
3. Shut off electrical supply.
A. This appliance has a pilot which must be
ignited by hand. When lighting the pilot,
follow these instructions exactly.
4. Drain the heat exchanger completely. Re-
move one 3/8" NPT plug or bulb well from the
inlet side and one from the outlet side of the
front header of the heat exchanger.
5. Drain the pump. Remove the 3/4" plug in
the bypass loop.
B. BEFORE OPERATING, smell around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than air
and will settle to the floor.
PRE-START CHECKLIST
WHAT TO DO IF YOU SMELL GAS
1. Inspect the burners to be sure they are properly
aligned.
Do not try to light any appliance.
2. Inspect the pilot gas line, thermocouple leads,
ignition leads and wire connections to the gas
valve to be sure none were damaged during
shipment.
Do not touch any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
3. Check to ensure that gas connections have been
made properly and the gas line is purged of air.
If you cannot reach your gas supplier, call the
fire department.
4. Check to ensure that water connections are tight
and the appliance and piping system have been
properly filled.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not turn by hand, don’t try to repair it, call a
qualified service technician. Force or attempted
repair may result in a fire or explosion.
5. Ensure that discharge from the relief valve has
been piped to a floor drain.
6. Verify that properly sized combustion and
ventilation air openings are provided and not
obstructed in any way.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified
service technician to inspect the appliance. The
possible damage to a flooded appliance can be
extensive and present numerous safety hazards.
Any appliance that has been under water must
be replaced.
7. Check carefully for gas leaks.
8. Read the appliance’s safety warnings, lighting
instructions and check out procedure carefully,
before firing the system.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information.
2. Remove the control panel door.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Set the thermostat to the lowest setting (OFF).
4. Turn off all electrical power to the appliance.
5. Turn the gas control knob on the gas valve
clockwise to the “OFF” position.
FIG. 35 Lighting Wand
NOTE:
The information package shipped with the
appliance contains a wire lighting wand. The loop
end of the wand will hold a match. The wand
extends your reach to the pilot and makes lighting
the pilot easier.
FIG. 33 F1 Gas Valve 90,000 - 270,000 Btu/hr Models
6. Wait five (5) minutes to clear out any gas, then
smell for gas, including near the floor. If you smell
gas, STOP! Follow the steps in the“What To Do If
You Smell Gas” section in the safety information
on page 24. If you do not smell gas go on to the
next step.
10. Use the loop end of the wire lighting wand,
shipped with the instruction package, to hold the
match and reach the pilot. An access slot is
provided in the lower front jacket panel, beside the
burner, to insert the lighting wand and match to the
pilot. Lift the pilot cover (FIG. 35) to access the
pilot. Push down and hold in the red button on the
gas valve. This should start gas flow to the pilot.
Continue to hold the red button in for about one (1)
minute after the pilot is lit. Release the button and
it will pop back up. The pilot should remain lit. If
the pilot goes out, repeat steps 5 through 10.
7. Remove the lower panel door to gain access to the
pilot.
8. Find the pilot - Follow the metal tube from the gas
valve to the pilot. The pilot is located on the right
side of the burner approximately centered in the
burner tray.
If the red button does not pop up when released,
stop and immediately call your gas supplier.
If the pilot will not stay lit after several tries, turn
the gas control to “OFF” and call your
service technician or gas supplier.
11. Turn the gas control knob on the gas valve
counterclockwise to the “ON” position.
12. Turn on all electric power to the appliance.
13. Re-install the lower panel door.
14. Set the thermostat to the desired setting.
15. Re-install the control panel door.
FIG. 34 Pilot Location
9. Turn the control knob on the gas valve
counterclockwise to the “PILOT” position.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
5. After successful completion of test, turn the
control knob on the gas valve clockwise to the
“OFF” position. Do not force.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to the OFF position.
6. Carefully reconnect the thermocouple to the gas
valve.
2. Turn off all electric power to the appliance if
service is to be performed.
7. Follow the Lighting Instructions to relight the pilot
and establish normal operation.
3. Turn the gas control knob on the gas valve
clockwise to the “OFF” position. Do not force.
LIGHTING INSTRUCTIONS FOR SPARK
IGNITION PILOT MODELS (F9/M9)
MODELS 45,000 THRU 500,000 Btu/hr
INPUT FOR YOUR SAFETY READ
BEFORE OPERATING
ƽ WARNING
Should overheating occur or the gas fail to shut
off, turn off the external manual gas valve to the
appliance.
ƽ WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or loss of life.
SAFETY SHUTOFF TEST FOR
STANDING PILOT IGNITION SYSTEM
A. This appliance is equipped with an ignition
device which automatically lights the pilot. Do
not try to light the pilot by hand.
B. BEFORE OPERATING, smell around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than air
and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use
any phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
FIG. 36 Pilot with Thermocouple and Spark Ignition
1. With the main burners on and firing, unscrew the
thermocouple connection from the gas valve
(FIG 36) and remove from the fitting. See Figure
25 to locate the thermocouple outlet connection on
the gas valve.
If you cannot reach your gas supplier, call the
fire department.
C. Use only your hand to turn the gas control
knob. Never use tools. If the knob will not turn
by hand, don’t try to repair it, call a qualified
service technician. Force or attempted repair
may result in a fire or explosion.
2. The main gas valve should extinguish the burners
immediately after removal of the thermocouple.
3. If burners do not extinguish, immediately follow
D. Do not use this appliance if any part has been
under water. Immediately call a qualified
service technician to inspect the appliance. The
possible damage to a flooded boiler can be
extensive and present numerous safety hazards.
Any appliance that has been under water must
be replaced.
steps in “To Turn Off Gas To Appliance”.
4. Immediately call a qualified serviceman or
installer to repair an ignition system that fails to
operate properly and shut down the burners.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
TO TURN OFF GAS TO APPLIANCE
1. STOP! Read the safety information first.
2. Remove the control panel door.
1. Set the thermostat to the OFF position.
2. Turn off all electric power to the appliance if
service is to be performed.
3. Set the thermostat to the lowest setting (OFF).
4. Turn off all electrical power to the appliance.
3a. 45,000 - 135,000 and 399,999 - 500,000 Btu/hr
models, rotate the gas control knob on the gas
valve clockwise to the “OFF” position. Do not
force.
5. This appliance is equipped with an ignition device
which automatically lights the pilot. DO NOT try
to light the pilot by hand.
3b. 180,000 - 360,000 Btu/hr models, rotate the gas
control knob on the gas valve clockwise to the line
on the collar around the knob. Depress the knob
and continue rotation to the “OFF” position. Do
not force.
6a. 45,000 - 135,000 and 399,999 - 500,000 Btu/hr
models, rotate the gas control knob on the gas
valve clockwise to the “OFF” position.
6b. 180,000 - 360,000 Btu/hr models, rotate the gas
control knob on the gas valve clockwise to the line
on the collar around the knob. Depress the knob
and continue rotation to the “OFF” position.
ƽ WARNING
Should overheating occur or the gas fail to shut off,
turn off the external manual gas valve to the
appliance.
7. Wait five (5) minutes to clear out any gas, then
smell for gas, including near the floor. If you smell
gas, STOP! Follow the steps in the “What To Do
If You Smell Gas” section in the safety information
on page 26. If you do not smell gas go on to the
next step.
SAFETY SHUTOFF TEST FOR SPARK
IGNITION PILOT SYSTEM
1. Turn “OFF” gas supply to the appliance.
2. Turn thermostat to highest setting.
3. Turn electric power “ON”.
8a. 45,000 - 135,000 and 399,999 - 500,000 Btu/hr
models, rotate the gas control knob on the gas
valve counterclockwise to the “ON” position.
8b. 180,000 - 360,000 Btu/hr models, rotate the gas
control knob on the gas valve counter-
clockwise to the line on the collar around the knob.
Allow the knob to “pop” up, and continue rotation
to the “ON” position.
4. Pump relay pulls in to start pump.
5. The ignition will begin sparking at the pilot.
6. The ignition module will lock out after the 90
second trial for ignition period on the 45,000 thru
399,999 Btu/hr models and after the 15 second
trial for ignition period on the 500,000 Btu/hr
model.
9. Turn on all electric power to the appliance.
10. Set the thermostat to the desired setting.
11. Re-install the control panel door.
7. Immediately call a qualified serviceman or
installer to repair an ignition system that fails to
lock out and properly shut down burner operation.
12. If the appliance will not operate, follow the
instructions “To Turn Off Gas To Appliance” and
call your service technician or gas supplier.
8. After successful completion of the test, readjust
the thermostat to normal setting.
9. Turn “ON” gas supply.
10. Turn power “OFF” then “ON” to reset ignition
module.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
11. If ignition system fails to operate properly, repair 4. Freeze protection for a heating boiler or hot water
work must be performed by
serviceman or installer.
a
qualified
supply boiler using an indirect coil can be provided
by using hydronic system antifreeze. Follow the
manufacturers instructions.
DO NOT use
undiluted or automotive type antifreeze.
INTERMITTENT PILOT
SPARK IGNITION SYSTEM (F9/M9)
5. A snow screen should be installed to prevent snow
and ice accumulation around the appliance venting
system in cold climates.
The ignition module is not repairable. Any modification
or repairs will invalidate the warranty and may create
hazardous conditions that result in property damage,
personal injury, fire, explosion and/or toxic gases. A
faulty ignition module must be replaced with a new
module.
6. Shut-down and Draining - If for any reason, the
appliance is to be shut off, the following
precautionary measures must be taken:
(a) Shut off gas supply.
IGNITION and CONTROL TIMINGS
(b) Shut off water supply.
(c) Shut off electrical supply.
F1 Standing Pilot Models (thermocouple supervised)
Pilot Flame Failure Response Time - 180 Seconds
(d) Drain the unit completely. Remove one
threaded plug or bulb well from the inlet
side of the front header and one from the
outlet side of the front header on the heat
exchanger. Blow all water out of the heat
exchanger.
Maximum
F9/M9 Intermittent Spark Ignition Pilot Models
Pilot Trial for Ignition Period - 90 Seconds
(45,000 thru 399,999 Btu/hr models)
Pilot Trial for Ignition Period - 15 Seconds
(500,000 Btu/hr model)
(e) Drain pump and piping.
Pilot Failure Response Time - 0.8 Seconds at less than
1.0 µA flame current
FREEZE PROTECTION FOR A HEATING
BOILER SYSTEM (If Required)
Pump Delay Timing (Standard on Water Heaters and
Optional on Boilers) - 30 Seconds after burner shut-
down
1. Use only properly diluted inhibited glycol anti-
freeze designed for hydronic systems. Inhibited
propylene glycol is recommended for systems
where incidental contact with drinking water is
possible.
FREEZE PROTECTION
1. For water heaters, and boilers with the pump delay
option, if either the inlet sensor or the optional
multi-purpose temperature sensor reads below
40°F, the pump relay will turn ON. When the
temperature rises above 50°F the pump relay will
turn OFF.
ƽ CAUTION
DO NOT use undiluted or automotive type
antifreeze.
2. A solution of 50% propylene glycol will provide
maximum protection of approximately -30°F.
2. Location - Heating boilers and water heaters must
be located in a room having a temperature safely
above freezing [32°F(0°C)].
3. Follow the instructions from the glycol antifreeze
manufacturer. The quantity of glycol antifreeze
required is based on total system volume including
expansion tank volume.
3. Caution - A room where the appliance is installed
and operating under a negative pressure may
experience a downdraft in the flue of an appliance
which is not firing. The cold outside air pulled
down the flue may freeze a heat exchanger. This
condition must be corrected to provide adequate
freeze protection.
4. Glycol is more dense than water and changes the
viscosity of the system. The addition of glycol
will decrease heat transfer and increase frictional
loss in the heating boiler and related piping. A
larger pump with more capacity may be required to
maintain desired flow rates in a glycol system.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Local codes may require a back flow preventer or
actual disconnect from city water supply when
glycol antifreeze is added to the system.
a. Normal Flame: A normal flame is blue, with
slight yellow tips, with a well defined inner
cone and no flame lifting.
b. Yellow Tip: Yellow tip can be caused by
blockage or partial obstruction of air flow to
the burner(s).
WATER TREATMENT
In hard water areas, water treatment should be used to
reduce the introduction of minerals to the system.
Minerals in the water can collect in the heat exchanger
tubes and cause noise on operation. Excessive build up
of minerals in the heat exchanger can cause a
non-warrantable failure.
c. Yellow Flames: Yellow flames can be caused
by blockage of primary air flow to the
burner(s) or excessive gas input.
This
condition MUST be corrected immediately.
d. Lifting Flames: Lifting flames can be caused
by over firing the burner(s) or excessive
primary air.
MAINTENANCE
Listed below are items that must be checked to ensure
safe reliable operation. Verify proper operation after
servicing.
If improper flame is observed, examine the venting
system, ensure proper gas supply and adequate supply
of combustion and ventilation air.
ƽ CAUTION
3. Combustion Air Adjustment: This appliance uses
an atmospheric combustion process. Combustion
air is provided to the burners by the gas injection
pressure into the venturi of the burners. The
burners do not have an adjustable air shutter.
Adequate combustion air must be supplied to the
room where the appliance is installed to ensure
proper burner operation. Check frequently to be
sure the flow of combustion and ventilation air to
the unit is not obstructed. When the main burners
light, observe the burner flame. Flames should be
light blue in color with slight yellow tips; flames
should be settled on burner head with no lifting
when supplied with correct volume of combustion
air.
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation.
1. Examine the venting system at least once a year.
Check more often in the first year to determine
inspection interval. Check all joints and pipe
connections for tightness, corrosion or
deterioration. Clean louvers and/or screens in the
combustion air intake system as required. Have
the entire system, including the venting system,
periodically inspected by a qualified service
agency.
2. Visually check main burner flames at each start up
after long shutdown periods or at least every six
months.
4. Flue Gas Passageways Cleaning Procedures: Any
sign of soot around the outer jacket, at the burners
or in the areas between the fins on the copper heat
exchanger indicates a need for cleaning. The
following cleaning procedure must only be
performed by a qualified serviceman or installer.
Proper service is required to maintain safe
ƽ WARNING: The area around the burners is hot and direct contact could result in burns!
operation.
Properly installed and adjusted
appliances seldom need flue cleaning.
All gaskets on disassembled components must be
replaced with new gaskets on reassembly. Gasket kits
are available from your distributor.
FIG. 37 Burner Flames
29
Download from Www.Somanuals.com. All Manuals Search And Download.
e. Disconnect gas valve wiring and remove gas
manifold assembly.
INSPECTION CLEANING PROCEDURE
f. Remove ignition wire leading to the pilot
assembly from the ignition module.
ƽ WARNING
The combustion chamber lining in this appliance
contains ceramic fiber materials. Ceramic fibers can
transform into cristobalite (crystalline silica) when
exposed to temperatures above 2192°F (1200°C)
dependent upon the length of exposure time.*
g. Disconnect the wiring from the flame roll-
out/interlock switch, see Figure 32, page 23.
h. Remove the lower front jacket panel.
i. Remove the control panel mounting screws.
When removing the control panel, lay the
control panel to the side with the wiring intact,
being careful not to damage any of the wiring.
The International Agency for Research on Cancer
(I.A.R.C.) has concluded, "Crystalline silica inhaled in
the form of quartz or cristobalite from occupational
sources is carcinogenic to humans."**
Remove the combustion chamber door. Use
caution to prevent damage to burners,
refractory, pilot or wiring.
Testing has confirmed that the ceramic fibers in this
application do not reach 2192°F (1200°C).
*Reference Dyson, D., Butler, M., Hughes, R., Fisher,
R., and Hicks, G. The Devitrification of Alumino-
silicate Ceramic Fiber Materials - The Kinetics of the
Formation of Different Crystalline Phases, Ann.
Occup. Hyg. Vol. 41, No. 55, 1997.
INSPECTION AND CLEANING
j. Check the heat exchanger surface for sooting.
The external surfaces of the copper tubes
should be free of any soot deposits. (A slight
black smudge is normal with some types of
gases.) If abnormal soot deposits are present,
the heat exchanger must be cleaned and the
cause of the soot problem corrected. Proceed as
follows:
**Reference I.A.R.C. Monograph 68, June 1997.
NOTE:
The ceramic fiber material used in this appliance is an
irritant; when handling or replacing the ceramic materials
it is advisable that the installer follow these safety guides.
k. Remove soot from burners and bottom of the
finned tubes with a stiff bristle brush. Dirt
may also be removed from burner ports by
rinsing the burner thoroughly with water.
Drain and dry burners before re-installing.
Damaged burners must be replaced.
REMOVAL OF COMBUSTION CHAMBER LINING
OR BASE PANELS:
• Avoid breathing dust and contact with skin and eyes.
• Use NIOSH certified dust respirator (N95)
(http://www.cdc.gov/niosh/homepage.html).
• Lightly mist with water (only those areas being handled)
the combustion chamber lining or base insulation to
prevent airborne fibers.
An appliance installed in a dust or dirt contaminated
atmosphere will require cleaning of the burners on a 3
to 6 month schedule or more often, based on severity of
contamination. Contaminants can be drawn in with the
combustion air. Non-combustible particulate matter
such as dust, dirt, concrete dust or dry wall dust can
block burner ports and cause non-warrantable failure.
Use extreme care when operating an appliance for
temporary heat during new construction. The burners
will probably require a thorough cleaning before the
appliance is placed in service.
• Remove combustion chamber lining or base insulation
from the boiler and place it in a plastic bag for disposal.
• Wash potentially contaminated clothes separately from
other clothing. Rinse clothes thoroughly.
• NIOSH stated First Aid:
Eye: Irrigate immediately.
Breathing: Fresh air.
HEAT EXCHANGER/BURNER ACCESS
l. Remove gas manifold as described in steps a.
thru e. in “Heat Exchanger/Burner Access.”
a. Turn “OFF” main power to the appliance.
m. Loosen mounting screws and remove front
control panel.
b. Turn “OFF” external manual gas shutoff valve
to appliance.
n. Loosen screws on the upper front jacket panel
and remove toward front of the appliance. Use
caution to prevent damage to refractory on the
doors inner surface.
c. Remove the control panel door.
d. Remove the outer air deflector (FIG.38A )
30
Download from Www.Somanuals.com. All Manuals Search And Download.
o. Check “V” baffles on top of the heat 6. Keep appliance area clear and free from
exchanger. Remove and clean if necessary.
combustible materials, gasoline and other
flammable vapors and liquids.
p. Remove soot from the heat exchanger with a stiff
bristle brush. Soot may also be removed from the 7. Check frequently to be sure the flow of combus-
heat exchanger by washing thoroughly with
detergent and water. Remove the heat exchanger
before using water for cleaning. Rinse thoroughly
and dry before re-installing. Use a vacuum to
remove loose soot from surfaces and inner
chamber.
tion and ventilation air to the boiler is not
obstructed.
8. Inspection of Heat Exchanger Waterways:
Appliances operated in hard water areas should
have periodic inspections of the tubes to be sure
that no sediment or scale accumulates on the heat
transfer surfaces. Inspection plugs are located at
both ends of the heat exchanger. Inspection plugs
should be removed and tubes inspected at the end
of the first 45 days of operation and again at the
end of 90 days of operation. If no scale
accumulation is observed, inspections can be made
at the end of each six months of operation.
q. Remove the heat exchanger (HEX) filler bracket
(FIG. 38A).
r. The heat exchanger can be removed by sliding
towards the front of the appliance. Once the
heat exchanger is removed from the appliance,
a garden hose can be used to wash the tubes to
ensure that all soot is removed from the heat
exchanger surfaces.
9. Pilot Flame Adjustment Procedure - The pilot
flame should envelop 3/8" to 1/2" (10 to 13mm) of
the tip of the thermocouple (see Figure 38B).
s. Ensure that all burner ports are cleaned to
remove any soot. See Inspection and Cleaning
Procedure, page 30.
t. Carefully re-install the heat exchanger, “V”
"
baffles, jacket panels, and wires.
u. Reassemble all gas and water piping. Test for
gas leaks.
v. Cycle the appliance and check for proper
operation.
UPPER FRONT
JACKET PANEL
OUTER AIR
DEFLECTOR
FIG. 38B Pilot Flame on Thermocouple
a. Remove pilot adjustment cover screw on gas
valve. See Gas Valve Illustrations in the
Lighting Instructions section for location of
cover screw.
HEX FILLER
BRACKET
b. Turn inner adjustment screw clockwise to
decrease or counterclockwise to increase pilot
flame.
c. If difficulty is experienced in adjusting the
pilot flame, a tee may be installed in the pilot
line from the gas valve to the pilot burner.
FLAME ROLL-OUT SWITCH /
INTERLOCK SWITCH
LOWER FRONT
JACKET PANEL
FIG. 38A Outer Air Deflector and HEX Filler Bracket
5. Water Circulating Pump: Inspect pump every 6
months and oil if required. Use SAE 30
non-detergent oil or lubricant specified by pump
manufacturer.
d. Replace pilot adjustment cover screw on valve.
Tighten firmly after adjustment to prevent gas
leakage.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
expansion tank installed. Typically, an air charged
diaphragm-type expansion tank is used. The expansion
tank must be installed close to the boiler and on the
suction side of the system pump to ensure proper
operation. Caution: This boiler system should not be
operated at less than 12 PSIG. Hot water piping must
be supported by suitable hangers or floor stands, NOT
by the boiler. Copper pipe systems will be subject to
considerable expansion and contraction. Rigid pipe
hangers could allow the pipe to slide in the hanger
resulting in noise transmitted into the system. Padding
is recommended on rigid hangers installed with a
copper system. The boiler pressure relief valve must be
piped to a suitable floor drain. See the relief valve
section in the Installation and Service Manual.
IMPORTANT
Upon completion of any testing on the gas system,
leak test all gas connections with a soap solution
while main burners are operating. Immediately
repair any leak found in the gas train or related
components. Do Not operate an appliance with a
leak in the gas train, valves or related piping.
GAS TRAIN AND CONTROLS
ƽ CAUTION
A leak in a boiler system will cause the system to
intake fresh water constantly, which will cause the
tubes to accumulate a lime/scale build up. This will
cause a NON-WARRANTABLE FAILURE.
WATER CONNECTIONS
HEATING BOILERS ONLY
FIG. 39 Gas Train 45,000 - 399,999 Btu/hr Models
Heating Boilers with inputs of 45,000 - 260,000 Btu/hr
have 1 1/2" NPT inlet and outlet connections. Heating
boilers with inputs of 315,000 - 500,000 Btu/hr have 2"
NPT. All water heaters have 2" NPT. Caution: Field
installed reducing bushings may decrease flow resulting
in boiler noise or flashing to steam.
CIRCULATOR PUMP REQUIREMENTS
This is a low mass, high efficiency hot water boiler
which must have adequate flow for quiet, efficient
operation. The boiler circulating pump must be
purchased locally. The boiler circulator pump must
operate continuously while the boiler is firing. Pump
FIG. 40 Gas Train 500,000 Btu/hr Model
selection is critical to achieve proper operation.
A
PIPING OF THE BOILER SYSTEM
pump should be selected to achieve proper system
design water temperature rise. A heat exchanger
pressure drop chart (Table L) is provided to assist in
proper pump selection. Also provided is a System
Temperature Rise Chart (Table N). This table provides
GPM and boiler head-loss at various temperature rises
for each boiler based on Btu/hr input. Temperature rise
is the difference in boiler inlet temperature and boiler
outlet temperature while the boiler is firing. Example:
The boiler inlet temperature is 160°F and the boiler
outlet temperature is 180°F, this means that there is a
20°F temperature rise across the boiler.
The drawings in this section show typical heating
boiler piping installations. Before beginning the instal-
lation, consult local codes for specific plumbing
requirements. The installation should provide unions
and valves at the inlet and outlet of the boiler so it can
be isolated for service. The boiler circulating pump, air
separator, expansion tank and other components
required for proper installation must be purchased
locally. An air separation device must be supplied in
the installation piping to eliminate trapped air in the
system. Locate a system air vent at the highest point in
the system. The system must also have a properly sized
32
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE - L
HEAT EXCHANGER PRESSURE DROP CHART
FOOT HEAD LOSS
FIG. 41 Boiler Wiring - Circulation Pump to Junction Box
CIRCULATOR PUMP SPECIFICATIONS
PUMP INSTALLATION AND MAINTENANCE: The
boiler circulating pump must be purchased locally. For
installation and maintenance information on the
circulator pump, refer to the pump manufacturers
instruction package included with the pump.
1. Maximum operating pressure for the pump must
exceed system operating pressure.
2. Maximum water temperature should not exceed
nameplate rating.
BYPASS PUMP 45,000 - 260,000 Btu/hr
(Heating Boilers Only)
3. Cast iron circulators may be used for closed loop
systems.
These units are equipped with an integral bypass pump,
which is designed to provide efficiency optimization by
maintaining a constant flow through the unit’s heat
exchanger loop when building system flow is reduced.
The bypass pump assembly is standard equipment and is
NOT to be used as a system pump.
4. A properly sized expansion tank must be installed
near the boiler and located on the suction side of
the pump.
CIRCULATOR PUMP OPERATION
(Heating Boilers Only)
NOTE:
The bypass pump is dedicated to the unit and does not
affect the building’s system or primary/secondary
flow characteristics and will not circulate the
building.
Boilers are equipped with a relay for controlling the
circulation pump for the hot water loop. The relay turns
ON and OFF in response to the “W” input from the wall
thermostat or zone control.
EXPANSION TANK
The field installed boiler pump MUST NOT exceed
1 h.p. For continuous pump operation, wire the system
pump to the 120V supply. The pump should be
connected at the junction box as shown in Figure 41.
MAKE-UP WATER
AIR SEPARATOR
HEATING RETURN
LOOP
HEATING SUPPLY LOOP
FIG. 42 - Single Boiler Full System Flow
33
Download from Www.Somanuals.com. All Manuals Search And Download.
The installer must ensure that the boiler has adequate
flow without excessive temperature rise. The
PRIMARY/SECONDARY
BOILER PIPING
temperature rise on a multiple zone system should be
made when only the zone with the longest length and/or
highest head loss is open. Low system flow can result
in overheating of the boiler water which can cause short
burner on cycles, system noise and in extreme cases, a
knocking flash to steam. These conditions indicate the
need to open the bypass adjustment valve, installation
of a larger circulator pump or installation of the boiler
with a primary/secondary piping system. System noise
may also indicate an oversized boiler.
ƽ CAUTION
At no time should the system pressure be less than
12 PSIG.
MAKE-UP
WATER
FIG. 43 Primary/Secondary Piping of a Single Boiler
Heating boilers with inputs of 315,000 - 500,000 Btu/hr
or larger installed on multiple zone systems are recom-
mended to be installed with a primary/secondary piping
system as shown in Figure 43. A primary/secondary
piping system may also be installed on smaller input
boilers to ensure proper boiler flow rates. Primary/sec-
ondary piping is also ideal for systems using a mixture of
propylene glycol and water. A primary/secondary piping
system uses a dedicated pump to supply flow to the
boiler only. This pump is sized based on desired boiler
flow rate, boiler head loss and head loss in the secondary
system piping only. The secondary pump, installed in
the boiler piping, ensures a constant water flow rate to
the boiler for proper operation. Boiler installation with a
primary/secondary piping system can prevent noise
PRV
EXPANSION TANK
TO SYSTEM
LWCO
(OPTIONAL)
SYSTEM
PUMP
SECONDARY
BYPASS
12"
BOILER PUMP
AIR SEPARATOR
FROM
SYSTEM
FIG. 44 Boiler with Low Temperature Bypass Piping - Models
315,000 - 500,000 Btu/hr
problems caused by low system water flows.
A
A boiler operated with an inlet temperature of less than
140°F (60°C) must have a bypass to prevent problems
with condensation. A bypass as shown in Figure 44
must be piped into the system at the time of installation.
primary/secondary piping system is recommended on
any boiler where low water flow conditions may present
an operational problem.
A primary/secondary piping system is ideal for systems
filled with a propylene glycol and water mixture. A
glycol and water mixture is more dense than water only
and may result in a lower boiler flow rate. A lower
boiler flow may cause noise on operation or short
cycling of the burners. A larger secondary pump may
be used on a primary/secondary system to provide an
increased boiler flow rate. A glycol and water system
may require from 10 to 20% more flow to compensate
for the increased density of the glycol and its effect on
the heat transfer process in the boiler. The exact
increase in flow that may be required is based on the
type and percentage of glycol added to the boiler
system. Consult the manufacturer of the glycol for
additional recommendations when using a glycol and
water fill for your boiler system.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Low flow rates can result in overheating of the boiler
water which can cause short burner on cycles, system
noise and in extreme cases, a knocking flash to steam.
These conditions can cause operational problems and
non-warrantable failures of the boiler. If a three way
LOW TEMPERATURE BYPASS
REQUIREMENTS
This piping is like a primary/secondary boiler
installation with a bypass in the secondary boiler
piping. Inlet water temperatures below 140°F (60°C)
can excessively cool the products of combustion
resulting in condensation on the heat exchanger and in
the flue. Condensation can cause operational problems,
bad combustion, sooting, flue gas spillage and reduced
service life of the vent system and related components.
The bypass allows part of the boiler discharge water to
be mixed with the cooler boiler return water to increase
the boiler inlet temperature above 140°F (60°C). This
should prevent the products of combustion from
condensing in most installations. The bypass should be
fully sized with a balancing valve to allow for proper
adjustment. A valve must also be provided on the boiler
discharge, after the bypass. Closing this discharge
valve forces water through the bypass. Start boiler
adjustment with the bypass valve in the full open
position and the boiler discharge valve half open. A
small amount of the higher temperature boiler discharge
water is mixed with the system water to maintain the
desired lower system temperature. A remote low tem-
perature range operator is recommended to control the
boiler operation based on the lower system temperature.
This remote operator should be wired across the R and
W terminals (see Room Thermostat Connection and
Terminal Strip Instructions).
valve must be installed, please pipe in
a
primary/secondary system as shown in Figure 45.
Based on boiler sizing and system flow requirements,
this piping may still result in boiler short cycling.
BOILER FLOW RATES
ƽ CAUTION
The maximum flow rate through the boiler with a
copper heat exchanger must not exceed 30 GPM.
MAKE-UP WATER
PRV
EXPANSION TANK
TO SYSTEM
LWCO
(OPTIONAL)
SYSTEM PUMP
AIR SEPARATOR
BYPASS VALVE
FROM SYSTEM
THREE WAY VALVES:
FIG. 46 Boiler Bypass Piping
SECONDARY
BOILER PUMP
The heat exchanger is generally capable of operating
within the flow rates of a residential heating system.
Should the flow rate exceed the maximum allowable
flow rate through the boiler (30 GPM) an external
bypass must be installed. The bypass should be fully
sized with a balancing valve to allow for proper
adjustment of flow. Flow rate can be determined by
measuring the temperature rise through the boiler.
FROM
EXPANSION
TANK
SYSTEM
PRV
MAKE-UP
WATER
LWCO
(OPTIONAL)
THREE-WAY VALVE
SLOW
The basic guide for minimum flow in this boiler is
based on a 40°F temperature rise in most installations.
Lower flow and a higher temperature rise is acceptable
if the boiler system is specifically designed for the
characteristics of a higher temperature rise. A system
not specifically designed for a higher temperature rise
may experience overheating of the boiler water. This
can cause short burner on cycles, system noise and in
extreme cases, a knocking flash to steam. These
conditions can lead to operational problems and
OPENING/SLOW
CLOSING
TO SYSTEM
AIR SEPARATOR
SYSTEM PUMP
FIG. 45 Boiler Piping with a 3-Way Valve
The installation of a three way valve on this boiler is not
generally recommended because most piping methods
allow the three way valve to vary flow to the boiler.
This boiler is a low mass, high efficiency unit which
requires a constant water flow rate for proper operation.
non-warrantable failures of the boiler.
High
temperature rise systems must be designed by a
qualified engineer.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
PLACING THE BOILER IN OPERATION
TABLE - M
MINIMUM REQUIRED FLOW FOR
HEATING BOILER
Filling the System: All air must be purged from the
system for proper operation. An air scoop and air vent
must be located close to the boiler outlet and there
should be a minimum distance between the cold water
feed and the system purge valve.
Input Btu/hr
GPM Flow
45,000
75,000
1.9
3.1
1. Close all drain cocks and air vents.
90,000
3.7
2. Open the makeup water valve and slowly fill the
system.
135,000
180,000
215,000
260,000
315,000
360,000
399,999
500,000
5.6
7.4
3. If a makeup water pump is employed, adjust the
pressure to provide a minimum of 12 psi at the
highest point in the system. If a pressure regulator
is also installed in the line, it should be adjusted to
the same pressure.
8.9
10.7
13.0
14.9
16.5
20.7
4. Close all valves. Purge one circuit at a time as
follows:
A. Open one circuit drain valve and let the water
drain for at least five minutes. Ensure that
there are no air bubbles visible in the water
stream before closing the drain valve.
NOTE:
Minimum flow is based on a 40°F temperature rise
across the boiler. Minimum flow may not prove a
flow switch installed in the boiler piping. Use care
when operating a boiler at or near the minimum
recommended flow because conditions unique to the
installation (system pressure, operation of multiple
zone valves, glycol, variations in flow, etc.,) may
result in overheating of the boiler water causing
noise or nuisance operation of safety limit
controls. Typical heating boiler applications will
operate with a 20°F to 30°F temperature rise across
the boiler.
B. Repeat this procedure for each circuit.
5. Open all valves after all circuits have been purged.
Make sure there are no system leaks.
NOTE:
Do not use petroleum based stop leak products. All
system leaks must be repaired. The constant
addition of make-up water can cause damage to the
boiler heat exchanger due to scale accumulation.
Scale reduces flow and heat transfer, causing
overheating of the heat exchanger.
TYPICAL HEATING BOILER
INSTALLATIONS
6. Run the system circulating pump for a minimum of
30 minutes with the boiler turned off.
General Plumbing Rules
1. Check all local codes.
7. Open all strainers in the system and check for
debris.
2. For serviceability of the boiler, always install
unions.
8. Recheck all air vents as described in step 4,
3. Always pipe pressure relief valves to an open
drain.
General Plumbing Rules.
9. Inspect the liquid level in the expansion tank. The
system must be full and under normal operating
pressure to ensure proper water level in the
expansion tank. Ensure that diaphragm type
expansion tanks are properly charged and not
water logged.
4. Locate system air vents at the highest point of the
system.
5. Expansion tank must be installed near the boiler
and on the suction side of the pump.
6. Support all water piping.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
10. Start the boiler according to the “Start-Up
Instructions” in this manual. Operate the system,
including the pump, boiler and radiation units, for
one hour.
INSTALLATION WITH A CHILLED
WATER SYSTEM
EXPANSION
11. Recheck the water level in the expansion tank. If
it exceeds half the tank volume, open the tank to
reduce the water level. Recheck pressure charge
on diaphragm type tanks.
TANK
HEATING AND
COOLING COIL
LOW WATER
FLOW SWITCH
PUMP
12. Shut down the entire system and vent all radiation
units and high points in the system.
OUT
IN
GAS
13. Close the water makeup valve and check the
strainer and pressure reducing valve for sediment
or debris. Reopen the water makeup valve.
CHILLER
SUPPLY
WATER
SUPPLY
BOILER
FIG. 47 Installation with a Chilled Water System
14. Verify system pressure with the boiler pressure
gauge before beginning regular operation.
Pipe refrigeration systems in parallel. Install duct coil
downstream at the cooling coil. Where the hot water
heating boiler is connected to a heating coil located in
the air handling units which may be exposed to
refrigeration air circulation, the boiler piping system
must be equipped with flow control valves or other
automatic means to prevent gravity circulation of the
boiler water during the cooling cycle. The coil must be
vented at the high point and hot water from the boiler
must enter the coil at this point. Due to the fast heating
capacity of the boiler, it is not necessary to provide a
ductstat to delay circulator operation. Also, omit
thermostat flow checks as the boiler is cold when
heating thermostat is satisfied. This provides greater
economy over maintaining standby heat.
15. Within three days of start-up, recheck and bleed all
air vents and the expansion tank using these
instructions.
TABLE - N
SYSTEM TEMPERATURE RISE CHART
Based on Boiler Output in Btu/hr
Btu/hr
10°F ꢀT
20°F ꢀT
30°F ꢀT
40°F ꢀT
50°F ꢀT
Input
Output
36,900
GPM Ft/hd GPM Ft/hd GPM Ft/hd GPM Ft/hd GPM Ft/hd
45,000
75,000
7.4
12.3
14.9
22.3
29.7
--
0.6
1.3
1.4
3.2
5.1
--
3.7
6.2
0.2
0.4
0.5
1.2
1.6
1.3
2.1
4.1
5.4
8.1
--
2.5
4.1
0.2
0.3
0.3
0.6
0.7
0.8
0.9
2.2
2.5
3.6
6.6
1.9
3.1
0.2
0.2
0.2
0.3
0.4
0.4
0.5
1.3
1.5
2.0
3.5
--
--
--
--
61,500
90,000
73,800
7.4
5.0
3.7
--
--
135,000
180,000
215,000
260,000
315,000
360,000
399,999
500,000
110,700
147,600
176,300
213,200
258,300
295,200
327,180
410,000
11.1
14.9
17.0
21.5
26.0
29.7
33.0
--
7.4
5.6
--
--
9.9
7.4
--
--
11.8
14.3
17.3
19.8
22.0
27.6
8.9
--
--
--
--
10.7
13.0
14.9
16.5
20.7
--
--
--
--
--
--
--
--
--
--
--
--
13.2
16.6
1.7
2.1
--
--
37
Download from Www.Somanuals.com. All Manuals Search And Download.
BOILER OPERATING
TEMPERATURE CONTROL
The operating temperature control is located in the
control panel, behind the control panel front access door.
The sensing element for the operator is placed in a bulb
well installed in the heat exchanger. Carefully observe
the discharge water temperature on the initial boiler on
cycles. The exact temperature set point is based on your
system’s requirements. Turn the control set point dial to
the desired operating water temperature. Observe the
boiler discharge temperature after each set point
adjustment to ensure proper operation.
ROOM THERMOSTAT OR REMOTE
THERMOSTAT CONNECTION
TO TERMINAL STRIP
A
FIG. 48 Terminal Strip Connections
A room thermostat or remote temperature control may
be connected to the boiler. The room thermostat should
be installed on an inside wall, away from the influences
of drafts, hot or cold water pipes, lighting fixtures,
televisions, sun rays or fireplaces. Follow the
manufacturers instructions supplied with the thermostat
for proper installation and adjustment. The boiler is
equipped with a terminal strip on the left side of the
control panel to allow easy connection (Figure 48).
POWER VENTER CONNECTION
TO TERMINAL STRIP
A terminal connection strip is provided for ease of
connection for Power Venting Systems, see Figure 48,
inset A.
TABLE - O
TERMINAL STRIP WIRING
Remove the jumper between the R and W terminals on
the terminal strip. Refer to the chart in this section to
determine maximum allowable length and wire gauge
recommended to connect the switching contacts of the
room thermostat to the R and W terminals on the
terminal strip. Connection to the terminal strip will
allow the room thermostat to make and break the
24VAC boiler control circuit turning the boiler on and
off based on the room ambient temperature
requirements. Set the boiler operating temperature
control as described in this section
Wire Gauge
Allowable Length
Maximum
12 GA
14 GA
16 GA
18 GA
100 ft
75 ft
50 ft
30 ft
DOMESTIC WATER HEATERS
90,000 - 500,000 Btu/hr MODELS
This section applies only to those units used to supply
direct fired domestic hot water and installed with a
storage tank(s). The use of a properly sized pump and
the control of water velocity, as explained in the Water
Velocity Control section, are important for correct
operation of your hot water heater.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
This section contains specific instructions for those
units used to supply domestic hot water. All warnings,
cautions, notes and instructions in the general
installation and service sections apply to these
instructions. Water heaters are designed for installation
with a storage tank. The use of a properly sized pump
and the control of water velocity, as explained below, is
important for correct operation of your water heater.
tank tappings to ensure proper flow. See Table Q
on page 40.
6. Multiple unit installations may also require a larger
circulating pump to achieve the specified flow
against the increased head loss of a multiple unit
common manifold piping.
If the temperature rise is too low, the water velocity is
too high. Adjust as follows:
WATER VELOCITY CONTROL
1. Slowly throttle the valve on the outlet side of the
water heater until the temperature rise is steady at
the required temperature rise as noted in Table P.
IMPORTANT - To ensure proper velocity through the
heat exchanger, it is necessary to regulate the
temperature rise across the heat exchanger from inlet to
outlet. This must be done on initial installation and
periodically rechecked. With the correct temperature
rise across the heat exchanger, you may be assured of
the proper velocity in the tubes. This will yield long life
and economical operation from your water heater.
Excessive lime build-up in the tube is a result of too
little velocity in the tubes. Excessive pitting or erosion
in the tube is caused by too much velocity through the
tubes. Care should be taken to measure temperature rise
and maintain a velocity as follows:
2. Sustained high water velocity and low temperature
rise may result in pitting or erosion of the
copper tubes in the heat exchanger. This is a
non-warrantable failure. Temperature rise must be
properly adjusted to achieve the specified flow
rate.
REQUIRED TEMPERATURE RISE
Temperature rise is based on the hardness of the potable
water to be heated. A different temperature rise is
specified for soft water with a hardness of 0 to 7 grains
per gallon or for unsoftened water with a hardness of 8
to 25 grains per gallon. The total dissolved solids shall
not exceed 350 ppm. If there is any doubt about the
hardness or total dissolved solids content of the
water to be heated, follow the temperature
guidelines for water with 8 to 25 grains of hardness
in Table P below. The majority of all potable water
supplies will fall within the range of 8 to 25 grains of
hardness. See Water Chemistry, page 40.
1. The pump must run continuously when the burners
are firing.
2. With the pump running and the water heater off,
the inlet and outlet thermometers should read the
same temperatures. If they do not, an adjustment
must be made to your final calculation.
3. Turn the water heater on and allow time for the
temperature to stabilize. Record the difference
between the inlet and outlet temperatures. This
difference will be the “temperature rise.”
TABLE - P
REQUIRED TEMPERATURE RISE
4. Compare the temperature rise on the heater with
the required temperature rise in Table P. Should
adjustment be needed, proceed as follows:
If the temperature rise is too high, the water velocity is
too low. Check the following:
Btu/hr
INPUT
0 to 7 Grains
Hardness
Temp. Rise F
8 to 25 Grains
Hardness
Temp. Rise °F
o
1. Check for restrictions in the outlet of the water
heater.
90,000
135,000
180,000
199,999
225,000
270,000
315,000
360,000
399,999
500,000
8
5
12
15
17
20
22
25
30
35
40
7
2. Be sure all valves are open between the water
heater and the tank.
10
11
12
15
17
20
22
28
3. Check the pump to be sure it is running properly
and that the pump motor is running in the proper
direction.
4. Be sure the circulation pipes between the water
heater and storage tank are not less than 1 1/2"
diameter for a single unit installation.
5. Common manifold piping for multiple unit instal-
lations will require larger minimum pipe sizes to
39
Download from Www.Somanuals.com. All Manuals Search And Download.
need to be increased. The tubes should not have a
bright shiny copper look. This would indicate that the
erosion process has begun and the flow rate will need to
be decreased. Once the proper flow rates have been
established the inspection intervals can be increased to
every 30 days, once a quarter, or to a bi-annual
inspection. This procedure should ensure proper
operation of the unit as long as the water quality stays
consistent.
NOTE:
Lower flows with soft water mean a higher
temperature rise. A higher temperature rise may
cause nuisance tripping of a high limit or opening
of a relief valve when providing very hot water. If
this presents a problem, increase the flow to the
temperature rise specified for 8 to 25 grains
hardness water.
COLD WATER SUPPLY
WATER CHEMISTRY
HOT WATER SUPPLY
EXPANSION TANK (IF REQUIRED)
The required temperature rise and the standard pump
sizing are based on the heating of potable water with
chemistry within the specified limits. Caution should
be used when heating water softened to less than 5
grains per gallon. Many commercial water softeners
reduce hardness to 0 grains which may result in long
term problems in the system. Softened water will
usually have a lower pH which can be aggressive and
corrosive causing non-warrantable damage to the
heater, pump, and associated piping.
RELIEF
VALVE
CIRCULATING PUMP
RELIEF
VALVE
LOCK-TEMP
STORAGE
TANK
DRAIN
BUILDING
RETURN
Corrosion due to water chemistry generally shows up
first in the hot water system because heated water
increases the rate of corrosive chemical reactions.
Follow the temperature rise recommendations when
heating soft water. Unsoftened water with a hardness of
8 to 25 grains per gallon and/or total dissolved solids
not exceeding 350 ppm requires a higher velocity and
lower temperature rise. As water is heated it becomes
less soluble. The dissolved minerals and solids will
precipitate and collect as scale if water velocity is not
properly controlled. Follow the temperature rise
requirements for unsoftened water. Consult the
manufacturer when heating potable water with hardness
or total dissolved solids exceeding these specifications.
Heating of high hardness and/or high total dissolved
solids water may require a larger circulating pump, an
optional cupro-nickel heat exchanger and a revised
temperature rise specification based on the water
chemistry of the water to be heated.
FIG. 49 Typical Water Heater Piping with Storage Tank
TABLE - Q
COMMON WATER MANIFOLD SIZE FOR
MULTIPLE HOT WATER SUPPLY BOILER
INSTALLATIONS
Pipe sizing chart provides minimum pipe size for
common manifold piping and tank tappings to in-
sure adequate flow.
Number of Units Common Manifold Size (Min)
1
2
3
4
5
6
2"
2"
2 1/2"
3"
3 1/2"
3 1/2"
SOFTENED WATER SYSTEMS
Decreasing the flow rate will reduce the erosion
process, however the heat exchanger should be
monitored to ensure the scale/liming process is not
made worse. The unit should be placed on a
comprehensive inspection schedule until optimum flow
rates can be established. Problematic water areas may
require heat exchanger inspection every two weeks.
The total scale accumulation should never exceed the
PUMP OPERATION
1. The water heater/hot water supply boiler must be
connected to a properly sized pump that circulates
water between the heater and storage tank.
2. Pump is sized to heater input and water hardness.
Care should be taken to size the pump
correctly. See “Water Chemistry”, this page.
thickness of a piece of paper.
Should scale
accumulation exceed this thickness the flow rate will
40
Download from Www.Somanuals.com. All Manuals Search And Download.
3. The pump must run continuously when the burners The sensor must also be connected to two blue wires
are firing.
provided in the upper left-hand corner of the control
panel. It will be necessary to add additional wire to
reach from the appliance to the remote water source.
Use twisted pair wire, minimum 18 gauge or larger. See
Table O, page 38 regarding distance versus wire gauge.
4. Lubricate the pump to the manufacturers recommen-
dations. Pump damage due to inadequate lubrica-
tion is non-warrantable.
5. A standard water heater/hot water supply boiler is
furnished with a 1/6 HP, 120 VAC, 3.6 AMP
circulating pump to be mounted on the units inlet
water connection. This pump is sized based on
installation of a single storage tank and heater in
close proximity. If the number of fittings and
straight pipe exceeds the quantities shown in this
section, a larger pump will be required.
EXTERNAL SENSOR FOR TANK, SYSTEM OR PUMP DELAY
NOTE: COLOR OF WIRES AND
REMOTE SENSOR CONNECTOR IS
LOCATED ON SIDE OF UNIT.
LEAD STYLES MAY VARY
WITH SENSOR PROVIDED.
CONNECTIONS ARE POLARITY
INSENSITIVE.
SIDE PANEL
The standard pump selection is based on the following
pipe and fittings from the unit to the storage tank:
6 - 90° elbows
2 - unions
2 - ball valves
1 - cold water tee
FIG. 50 External Sensor for Tank, System, or Pump Delay
HEAT EXCHANGER
Plus the following length of straight pipe based on the
heater size:
This is a highly sophisticated heat exchanger, designed
to carry water in such a way that it generates a scouring
action which keeps all interior surfaces free from
build-up of impurities. The straight-line, two pass
design of the tubes sends water into the headers at a
properly rated velocity. The configuration of the
headers, in turn, creates a high degree of turbulence
which is sufficient to keep all contaminants in
suspension. This “scouring action” provides greater
cost savings for owners. Tubes are always able to
transfer heat at peak efficiency. Every surface within
this water containing section is of a nonferrous material,
providing clear, clean, rust-free hot water. Straight
copper tubes-finned on the outside for maximum heat
transfer-glass lined cast iron one piece cored headers
make up an entirely rustproof unit. On all models,
header inspection plugs can be removed for field
inspection and cleaning of copper tubes. The entire
heat exchanger may be easily removed from the unit.
90,000 thru 360,000 Btu/hr Models
Not more than 45 feet of straight pipe
399,999 thru 500,000 Btu/hr Models
Not more than 25 feet of straight pipe
For every elbow and tee in excess of those shown
above, DEDUCT 5 FEET from maximum allowable
straight pipe in heater to tank circulating loop.
MINIMUM PUMP PERFORMANCE
Based on heating potable water with a hardness of 8 to
25 grains per gallon and total dissolved solids not
exceeding 350 ppm. See “Water Chemistry”, page 40.
BTU/hr INPUT
90,000 - 500,000
GPM
30
Ft. Hd.
8
THERMOSTAT SETTINGS
REMOTE SENSOR
INSTALLATION INSTRUCTIONS
1. The thermostat is adjusted to a low test setting
when shipped from the factory.
Water heaters are provided with an extra temperature
sensor that MUST BE field installed. The sensor is
shipped loose in the I & O packet. This remote
mounted sensor will be the primary temperature sensor
which will inform the appliance’s built-in thermostat
control. For domestic water heating, the sensor MUST
BE installed into a bulbwell on the storage tank. This
is required to maintain the desired temperature in the
tank and reduce cycling of the heater.
2. Set the thermostat to
a
maximum water
temperature of 125°F which will satisfy hot water
demands and prevent risk of scald injury.
Households with small children or invalids may
require 120°F or lower temperature setting to
reduce risk of scald injury. Some states may
require a lower temperature setting. Check with
41
Download from Www.Somanuals.com. All Manuals Search And Download.
your gas supplier for local requirements governing
the temperature setting. Remember, no water
heating system will provide exact temperature at
all times. Allow a few days of operation at this
setting to determine the correct temperature setting
consistent with your needs.
• Water temperature over 125°F (52°C)
can cause severe burns instantly or
death from scalds.
• Children, disabled and elderly are
at highest risk of being scalded.
• See instruction manual before
setting temperature at heating
appliance.
• Feel water before bathing or showering.
• If this appliance is used to produce
water that could scald if too hot,
such as domestic hot water use,
adjust the outlet control (limit) or use
temperature limiting valves to obtain
a maximum water temperature of
125°F (52°C).
NOTE:
(1) This water heater, when set at the lower
temperature setting, is not capable of producing
hot water of sufficient temperature for sanitizing
purposes. (2) Higher stored water temperature
increases the ability of the water heater to supply
desired quantities of hot water, however
remember:
ƽ WARNING
SHOULD OVERHEATING OCCUR OR THE
GAS SUPPLY FAIL TO SHUT OFF, DO NOT
TURN OFF OR DISCONNECT THE
ELECTRICAL SUPPLY TO THE PUMP.
INSTEAD, SHUT OFF THE GAS SUPPLY AT
ƽ CAUTION
Hotter water increases the risk of scald
injury.
A
LOCATION EXTERNAL TO
THE
APPLIANCE.
Incorrect piping of the cold water supply to the system
may result in excessive low temperature operation
causing condensate formation on the heat exchanger
and operational problems. The cold water supply
piping must be installed in the discharge piping from
the heater to the storage tank. This allows the cold water
to be tempered in the storage tank before entering the
heater. See typical installation drawings provided with
the unit for correct piping. Higher water temperatures
reduce condensate formation.
AUTOMATIC VENT DAMPERS
Automatic vent dampers are not required or furnished
on potable water heaters. All water heaters will have a
plug installed in the damper terminal on the side of the
control panel to allow operation without a vent damper.
The damper plug MUST be in place if an optional vent
damper is not used on a water heater. Water heaters with
inputs of 360,000 Btu/hr and less may be ordered with
the vent damper as an option. Remove the damper plug
from the terminal to connect an optional vent damper
wire harness. The optional damper must be properly
installed and the wire harness plugged into the terminal
on the side of the control panel to allow the unit to
function. See the “Automatic Vent Damper” section in
the basic portion of the manual.
ƽ CAUTION
Setting the temperature selector to higher settings
provides hotter water, which increases the risk of
scald injury.
The manufacturer recommends the use of a properly
sized thermostatic mixing valve to supply domestic hot
water at temperatures less than 140°F. Storing the
water at a higher temperature and thermostatically
mixing the water will increase the available quantity of
mixed hot water, greatly reduce the possibility of
condensate formation on the heat exchanger and help
prevent the growth of water born bacteria. Adequate
care MUST be taken to prevent potential scald injury
when storing water at 140°F and hotter.
ƽ CAUTION
Do not install an optional vent damper within 6"
(152mm) of combustible materials.
OPTIONAL RELIEF VALVE
This water heater/hot water supply boiler is normally
supplied with a temperature and pressure relief valve(s)
sized in accordance with applicable codes. Units may
be supplied with an optional pressure only relief
valve(s). When a water heater/hot water supply boiler
equipped with this optional relief valve is piped to a
separate storage vessel, the storage vessel must have a
properly installed temperature and pressure relief valve
which complies with local codes.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
THERMAL EXPANSION
A relief valve which discharges periodically may be due
to thermal expansion in a closed system. A hot water
supply boiler installed in a closed system, such as one
with a backflow preventer or check valve installed in
the cold water supply, shall be provided with means to
control expansion. Contact the water supplier or local
plumbing inspector on how to correct this situation.
Do not plug or cap the relief valve discharge!
CATHODIC PROTECTION
Hydrogen gas can be produced in a hot water system
that has not been used for a long period of time
(generally two weeks or more). Hydrogen gas is
extremely flammable. To prevent the possibility of
injury under these conditions, we recommend the hot
water faucet be open for several minutes at the kitchen
sink before you use any electrical appliance which is
connected to the hot water system. If hydrogen is
present, there will be an unusual sound such as air
escaping through the pipe as the hot water begins to
flow. There should be no smoking or open flames near
the faucet at the time it is open.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING GUIDE
45,000 - 500,000 Btu/hr Models - Boilers & Water Heaters F9/M9
Check for an open
Check continuity of the spark
cable. Check for 24VAC on
the TH terminal (gray wire) on
the ignition module.
Is the spark
sensor. If not open,
replace temperature
controller.
STEP 1:
STEP 2:
NO
NO
igniter sparking?
YES
Check the pilot
Is the pilot
staying ON?
NO
tube for gas.
YES
NO
Check for draft.
Replace ignition
module.
YES
Is there 24VAC
(tan wire) on the
4-pin connector
plug on the
Is there 24 VAC (purple
wire) on the 4-pin
connector plug on the
temperature controller?
YES
temperature
controller?
Replace ignition
module.
STEP 3:
Is the gas valve
getting 24VAC?
NO
YES
Check X and B on the
terminal strip if the flow
switch is installed. Check
for an open auto reset high
limit.
Check vent damper, 3-pin
louver relay connectors, and
venter proving.
NO
Check the vent damper or
the vent damper plug and
the voltage to and from the
transformer.
Check 24VAC at R and W on
the (EMS) terminal strip.
NO
YES
Check all safety limit devices.
Check 4-pin low water cutoff
connector.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING GUIDE
90,000 - 270,000 Btu/hr Models - Water Heaters F1
Check for an open
sensor. If not open,
replace temperature
controller.
Check for gas. Check the pilot
STEP 1:
STEP 2:
assembly and thermocouple.
Check the gas valve for proper
operation. Clean and replace.
Is the pilot lit?
NO
YES
NO
Is there 24 VAC
Is there 24VAC
(tan wire) on the
4-pin connector
plug on the
temperature
controller?
Is the gas valve
getting 24VAC?
(purple wire) on the 4-
pin connector plug on
the temperature
controller?
NO
YES
YES
YES
STEP 3:
Unit is running.
Check X and B on the
terminal strip if the flow
switch is installed. Check for
an open auto reset high limit.
Check vent damper 3-pin,
louver relay connectors, and
venter proving.
NO
Check the vent damper or
the vent damper plug and
the voltage to and from the
transformer.
Check 24VAC at R and W on
the (EMS) terminal strip.
NO
YES
Check all safety limit devices.
Check 4-pin low water cutoff
connector.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram - F1 Unit
90,000 - 270,000 Btu/hr Models
Wiring Diagram - F1 Unit
90,000 - 270,000 Btu/hr Models
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram - F9 Unit
90,000 - 399,999 Btu/hr Models
Wiring Diagram - F9 Unit
90,000 - 399,999 Btu/hr Models
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram - M9 Unit
45,000 - 399,999 Btu/hr Models
Wiring Diagram - M9 Unit
45,000 - 399,999 Btu/hr Models
48
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring Diagram - F9/M9 Unit
500,000 Btu/hr Models
Schematic Diagram - F9/M9 Unit
500,000 Btu/hr Models
49
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
50
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Revision 4 (RSB-i&s-04) reflects the removal of the inlet
pipe and installing the inlet sensor inside the header.
Revision 5 (RSB-i&s-05) reflects changes made to the
O.A. section.
RSB-i&s-05
CP-5M-4/08
52
Download from Www.Somanuals.com. All Manuals Search And Download.
|