Model 195ECM
ENGINEERING DATA
Performance
Net supply air flow in cfm (L/s) against external static pressure
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. The two
cores are arranged for highly efficient counter current airflow.
E.S.P
(external static pressure)
[cfm (L/s)]
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common ECM motor. 5 speed
fan operation. 120 VAC, 1.4 Amps.
@ 0.1" (25 Pa)
@ 0.2" (50 Pa)
@ 0.3" (75 Pa)
@ 0.4" (100 Pa)
@ 0.5" (125 Pa)
@ 0.6" (150 Pa)
@ 0.7" (175 Pa)
171 (81)
164 (77)
156 (74)
143 (67)
134 (63)
126 (59)
119 (56)
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester
straps that are supplied with the unit.
DEFROST
Damper defrost system.
Max. Temperature Recovery
88%
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
Sensible Effectiveness
@ 114 cfm (54 L/s)
32°F (0°C)
32°F (0°C)
88%
81%
CASE
*Sensible Efficiency
@ 114 cfm (54 L/s)
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance.
Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
*Sensible Efficiency
@ 119 cfm (56 L/s)
CONTROLS
-13°F (-25°C)
77%
120
34
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode (each mode has 5 speeds).
Control pad can be removed from HRV and remotely mounted.
VAC @ 60HZ
WATTS / Low speed
WATTS / High speed
Amp rating
Weight 106 lbs. (48 kg) Shipping Weight 108 lbs. (49 kg)
95
OPTIONAL MAIN CONTROLS
99-350 Lifestyle Ventilation Control 7/24 programmable ventilation, (3 wire) 20
gauge wire (min.) 100’ length
1.4
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs
99-109 Air Sentry Air Quality Monitor designed to accept remotely mounted
Control Pad, (3 wire) 20 gauge wire (min.) 100’ length
99-250 Ventilation Dehumidistat designed to accept remotely mounted Control
Pad, (4 wire) 20 gauge wire (min.) 100’ length
OPTIONAL TIMERS
99-104 Digital Electronic Timer - initiates high speed ventilation for 20, 40 or 60
minutes, (3 wire) 20 gauge wire (min.) 100’ length
99-101 Crank Timer - Initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100’ length
OPTIONAL ACCESSORIES
220
200
180
160
140
120
100
80
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6” (150 mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6” (150 mm)
99-185 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh screen
60
WARRANTY
40
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement
parts warranty.
20
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Static Pressure (in w.g.)
DIMENSIONS 195ECM inches (mm)
All units conform to
CSA and UL standards.
METAL CLASPS
FILTER
MOTOR
STALE AIR
FROM INSIDE
STALE AIR
TO OUTSIDE
ATTENTION
Ports
Ports
6" (150 mm)
7" (178 mm)
The ECM motor produces a tone that some may
find objectionable. We recommend the
FILTER
BLOWERS
installation of the optional 99-SILENCER6 on the
‘Stale Air from Inside’ and ‘Fresh Air to Inside’
ducts.
FRESH AIR
FRESH AIR
TO INSIDE
FROM OUTSIDE
49"
(1245)
DEFROST
DAMPER
14 3/4"
(375)
CONDENSATE
DRAINS
DEFROST AIR
FROM INSIDE
*NOTE: Front clearance of 25 inches (635 mm)
is recommended for servicing unit.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
TI-195ECM
Download from Www.Somanuals.com. All Manuals Search And Download.
|