AC Power
For Business-Critical Continuity™
Liebert® GXT3™ UPS 230V 700VA-3000VA
User Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
IMPORTANT SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
GLOSSARY OF SYMBOLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Available Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Appearance and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3.1 Appearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3.2 Rear Panel Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5.1 Mains (AC) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5.2 Manual Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5.3 Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5.4 Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5.5 Frequency Converter Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
What’s Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Preparation for Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.1 Installation Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.1 Tower Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.2 Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.5.1 Connecting to AC Mains and Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.5.2 Connecting Battery Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Connecting Communication Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.6.1 Connecting USB Communication Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cables . . . . . . . . . . . 16
OPERATION AND DISPLAY PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.1.1 On/Alarm Silence/Manual Battery Test button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.1.2 Standby/Manual Bypass button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2.1 Level Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2.2 UPS Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
i
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Startup Checklist for the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Starting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Shut Down the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Disconnecting Input Power from the Liebert GXT3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Liebert IntelliSlot Communication Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.1.1 Liebert MultiLink. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
USB Port Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.2.1 Configuration Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Terminal Block Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.3.1 Any Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.3.2 Battery Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.3.3 On Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.3.4 Low Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Replacing the Internal Battery Pack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.1.1 Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Checking UPS Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Checking UPS Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
UPS Symptoms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7.1.1 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7.1.2 Audible Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
BATTERY CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
9.1
Product Warranty Registration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURES
Figure 1
Liebert GXT3-700RT230 - GXT3-3000RT230 UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rear panel components, Liebert GXT3 230V 2000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rear panel components, Liebert GXT3 230V 3000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Operating principle diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Support bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Remove the front plastic bezel cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Rotate the operation and display panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Tower installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 10 Pulling inner member from each bracket assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 11 Installing rear member of each bracket assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 12 Installing front member of each bracket assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 13 Fastening rear member and front member together . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 14 Installing inner members . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 15 Installing rack-mount ears. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 16 Insert the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 17 Operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 18 Battery level indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 19 Load level indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 20 Terminal Block Communication pin layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 21 Removing the front plastic bezel cover and battery door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 22 Disconnecting the battery plug and battery connector (front view). . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 23 Pulling out the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 24 Battery level indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 25 Battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
TABLES
UPS models, power ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Specification of input circuit breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Functions of the On/Alarm Silence/Manual Battery Test button . . . . . . . . . . . . . . . . . . . . . . . . . 17
Functions of the Standby/Manual Bypass button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
UPS status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Output voltage option, all models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Replacement battery pack model numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Indicator descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Audible alarm description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 10 Troubleshooting table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 11 Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 13 Operating temperature parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 14 Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 15 Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
iv
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY PRECAUTIONS
WARNING
injury or death.
!
Observe all cautions and warnings in this manual. Failure to do so may result in serious
Refer all UPS and battery service to properly trained and qualified service personnel. Do not
attempt to service this product yourself.
Opening or removing the cover may expose you to lethal voltages within this unit even when
it is apparently not operating and the input wiring is disconnected from the electrical source.
Never work alone.
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that must be followed during the installation and
maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or
operate this UPS.
UPS Safety Notes
The UPS contains no user-serviceable parts except the internal battery pack. Do not remove the
cover. Removing the cover may result in electric shock and will invalidate any implied warranty.
The UPS has an internal battery, so the output receptacles of the UPS may carry live voltage even if
the UPS is not connected to mains input power.
Before moving or rewiring the UPS, disconnect mains input power and the battery and make sure
that the UPS is completely shut down. Otherwise, the output terminal may carry live voltage,
presenting an electric shock hazard.
To ensure human safety and normal UPS operation, the UPS must be properly grounded before use.
When the UPS is connected to an IT power distribution system, the short-circuit protection device
must be installed on the neutral line.
Install and use the UPS in the following environments:
• Temperature: 0°C to 40°C (32 - 104°F); relative humidity: 0% to 95%, non-condensing)
• Out of direct sunlight
• Away from heat source
• Stable surface, not subject to vibrations or shocks
• Away from dust and other particulates
• Away from corrosive substances, salts and flammable gases
Keep the air inlet and outlet of the UPS unobstructed. Poor ventilation will increase the UPS internal
temperature and can shorten the life of the UPS and its batteries.
Keep liquid and other foreign objects away from the UPS.
In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher
may cause electric shock.
This UPS is not intended for use with life support and other designated critical devices. Maximum
load must not exceed that shown on the UPS rating label. This UPS is designed for data processing
equipment. If uncertain, consult your local dealer or Emerson Network Power® representative.
®
™
1
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Battery Safety
CAUTION
!
!
Do not dispose of the battery in a fire. The battery may explode.
Do not open or damage the battery. Released electrolyte is toxic and is harmful to skin and
eyes. If electrolyte comes into contact with the skin, wash the affected area immediately with
plenty of clean water and get medical attention.
CAUTION
A battery can present a risk of electrical shock and high short-circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove
the source of the ground. Contact with any part of a grounded battery can result in
electrical shock. The likelihood of such shock will be reduced if grounds are removed during
installation and maintenance (applicable to a UPS and a remote battery supply not having
a grounded supply circuit).
ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT3 series complies with the limits for a
Class A digital device. Operating this device in a residential area is likely to cause harmful
interference that users must correct at their own expense.
The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the
published technical standards. Continued compliance requires installation in accordance with these
instructions and use of accessories approved by Emerson®.
Information for the Protection of the Environment
UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic
cards, electronic components). The components removed must be taken to specialized collection and
disposal centers.
NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD APPLIANCES—This
product has been supplied from an environmentally aware manufacturer that complies with the
Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/CE.
The “crossed-out wheelie bin” symbol at right is placed on this product to
encourage you to recycle wherever possible. Please be environmentally
responsible and recycle this product through your recycling facility at its end
of life. Do not dispose of this product as unsorted municipal waste. Follow
local municipal waste ordinances for proper disposal provisions to reduce the
environmental impact of waste electrical and electronic equipment (WEEE).
For information regarding the scrapping of this equipment, please browse
http://www.eu.emersonnetworkpower.com (“Products session” or
“Contact us” session) or call our worldwide technical support.
• Toll Free: 00 80011554499
• Toll Number Based in Italy: +39 0298250222
®
™
Liebert GXT3
2
Download from Www.Somanuals.com. All Manuals Search And Download.
GLOSSARY OF SYMBOLS
Risk of electrical shock
Indicates caution followed by important instructions
!
AC input
AC output
Requests the user to consult the manual
i
+
-
Indicates the unit contains a valve-regulated lead acid battery
PbH2SO4
Recycle
R
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Battery Test
OFF/Bypass
WEEE
®
™
3
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
1.0 PRODUCT DESCRIPTION
The Liebert GXT3 is a compact, online uninterruptible power system (UPS) that continuously
conditions and regulates its output voltage. The Liebert GXT3 is designed to supply microcomputers
and other sensitive electronic equipment with clean sine wave input power, 700VA to 3000VA at
230V.
Upon generation, AC power is clean and stable. However, during transmission and distribution it is
subject to voltage sags, spikes and complete failure that may interrupt computer operations, cause
data loss and damage equipment.
The Liebert GXT3 protects equipment from these disturbances. The Liebert GXT3 continuously
charges its batteries from the mains, enabling it to supply power to connected loads, even when the
mains fail.
This section describes the UPS, its features, models, appearance and components, operating
principles and operating mode.
1.1
Features
The UPS includes the following features:
• Intelligent battery management to extend the battery life
• Operation and display panel with LED for monitoring load percentage and battery capacity
independently
• Flexible network management with Liebert MultiLink® software
• Fan fault self-inspection and automated diagnostic function
• Intelligent fan operation, automatically changing rotation speed depending on system
requirements, to decrease power consumption and noise
• Input circuit breaker to ease recovery from overloads
• CE mark and safety approval from CE
• Communication options: USB port, Liebert IntelliSlot port and terminal block communication
®
• Dry contacts for remote monitoring
• Input power factor greater than 0.99
• Output voltage selection function
1.2
Available Models
Table 1
Model
GXT3-700RT230
UPS models, power ratings
Nominal Power Rating
700VA/630W
GXT3-1000RT230
GXT3-1500RT230
GXT3-2000RT230
GXT3-3000RT230
1000VA/900W
1500VA/1350W
2000VA/1800W
3000VA/2700W
®
™
Liebert GXT3
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
1.3
Appearance and Components
1.3.1 Appearance
The Liebert GXT3 rack/tower models in various power ratings have the same general appearance,
receptacles each has.
Figure 1
Liebert GXT3-700RT230 - GXT3-3000RT230 UPS
Ventilation Slots
Operation and Display Panel
1.3.2 Rear Panel Features
The rear panel of the Liebert GXT3 has these features:
• USB port
• Cooling fan
• C19 output receptacle (GXT3-3000RT230 only)
• Six C13 output receptacles
• Input circuit breaker
• Liebert IntelliSlot®
• Communication terminal block
• Input receptacle
Figure 2
Rear panel components, Liebert GXT3 230V 700VA, 1000VA and 1500VA models
Liebert IntelliSlot Port
C14 Input Receptacle
Input Circuit
Breaker
USB Port
External Battery
Connector
Terminal Block
Communication
C13 Output Receptacles
Cooling Fan
Figure 3
Rear panel components, Liebert GXT3 230V 2000VA models
Input Circuit
Breaker
C20 Input Receptacle
Liebert IntelliSlot Port
USB Port
External Battery
Connector
Terminal Block
Communication
C13 Output Receptacles
Cooling Fan
®
™
5
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Figure 4
Rear panel components, Liebert GXT3 230V 3000VA models
Output Circuit
Breakers
Input Circuit
Breaker
C20 Input Receptacle
Liebert IntelliSlot Port
USB Port
External Battery
Connector
C13 Output
Receptacles
Terminal Block
Communication
C19 Output
Receptacle
Cooling Fan
1.4
Major Components
Figure 5
Operating principle diagram
Input
Output
Dynamic
Bypass
TVSS & EMI/
RFI Filters
Rectifier/
PFC
L1
Inverter
L1
DC-to-DC
Converter
Battery
Charger
Battery
N
G
N
G
The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery
charger, DC-to-DC converter, battery, dynamic bypass and UPS output.
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
The Liebert GXT3 has surge protection and filters that protect the connected load from power surges
and sags, electromagnetic interference (EMI) and radio frequency interference (RFI). These features
can minimize any surges or interference present in the mains power. The filters also prevent surges
or interference generated by the UPS from adversely affecting other devices connected on the same
branch as the UPS.
®
™
Liebert GXT3
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
Rectifier/Power Factor Correction (PFC) Circuit
In normal operation, the Liebert GXT3’s rectifier/power factor correction (PFC) circuit converts mains
power to regulated DC power for use by the inverter while ensuring that the wave shape of the input
current used by the UPS is near ideal. Extracting this sine wave input current achieves two
objectives:
• Efficient power use by the UPS
• Reduced reflected harmonics
This results in cleaner power being available to other devices in the building that are not protected by
the UPS.
Inverter
In normal operation, the Liebert GXT3’s inverter utilizes the DC output of the PFC circuit to produce
precise, regulated sine wave AC power. When mains power fails, the inverter receives DC power from
the battery through the DC-to DC converter. In either operation mode, the UPS inverter is online,
continuously generating clean, precise, regulated AC output power.
Battery Charger
The battery charger utilizes energy from the mains power and precisely regulates it to continuously
float charge the batteries. The batteries are being charged whenever the Liebert GXT3 is plugged in,
even when the UPS is not turned On.
DC-to-DC Converter
The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for
the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage,
increasing reliability.
Battery
The Liebert GXT3 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery
design life, operate the Liebert GXT3 in an ambient temperature of 0°C to 25°C (32°F to 77°F).
Optional external battery cabinets are available to extend battery run times.
Dynamic Bypass
The Liebert GXT3 provides an alternate path for mains power to the connected loads in the unlikely
event of a UPS malfunction. Should the Liebert GXT3 have an overload, overtemperature, or UPS
failure condition, the UPS automatically transfers the connected loads to bypass.
NOTE
The bypass power path does not protect the connected loads from disturbances on the mains.
1.5
Operating Mode
The UPS operation modes include the following: Mains (AC) Mode, Bypass Mode, Battery Mode,
Battery Recharge Mode and Frequency Converter Mode.
For the descriptions of operation mode indicators and control buttons, refer to 3.0 - Operation and
1.5.1 Mains (AC) Mode
During Mains (AC) Mode, the mains provides energy to the Liebert GXT3. The filters, PFC circuit and
inverter process this power to provide high-level power to connected loads. Meanwhile, the UPS
maintains the batteries in a fully charged state.
®
™
7
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Description
1.5.2 Manual Bypass Mode
Manual Bypass Mode occurs when the Standby/Manual Bypass button is pressed and held for about
2 seconds while the Liebert GXT3 is in Mains (AC) Mode. Bypass operation is indicated by an audible
alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to 7.0 -
Troubleshooting). During Bypass Mode, mains power bypasses the inverter and provides energy to
the connected load.
NOTICE
Turning Off the UPS in Bypass Mode will result in loss of output power.
1.5.3 Battery Mode
The Liebert GXT3 enters Battery Mode when mains power fails or is outside acceptable values. The
battery system supplies power through the DC-to-DC converter to the inverter to generate clean AC
power for the connected loads.
When the Liebert GXT3 enters Battery Mode, the UPS sounds a half-second beep at 10-second
intervals. When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to
warn that the battery is getting low (this Low Battery Warning is user-configurable).
In Battery Mode, the AC Input indicator is Off and the Battery Level indicators illuminate to warn
that a mains problem has occurred. Each battery level indicator represents a 20% capacity level. As
NOTICE
Turning Off the Liebert GXT3 when it is in Battery Mode will result in loss of output power.
If the UPS is turned Off manually, it must be manually restarted after mains power returns.
If the UPS is turned Off by a communication signal or because the batteries are depleted, it
will operate as selected in the configuration program for Auto-Restart (Refer to 5.2.1 -
1.5.4 Battery Recharge Mode
Once mains power is applied to the Liebert GXT3, the Battery Charger begins charging the batteries.
1.5.5 Frequency Converter Mode
All models of the Liebert GXT3 are capable of frequency conversion. Frequency Conversion Mode can
be selected using the configuration program. Allowable frequency operating modes include:
• Auto Sensing - 50Hz or 60 Hz – Bypass Enabled
• Auto Sensing - 50Hz or 60 Hz – Bypass Disabled
• Frequency Converter - 50Hz – Bypass Disabled
• Frequency Converter - 60Hz – Bypass Disabled
NOTE
The default for all models of the Liebert GXT3 is “Auto Sensing - 50Hz or 60 Hz – Bypass
Enabled.”
CAUTION
be present even when the AC input indicator is Off.
!
Do not touch the AC input receptacle when the UPS is operating. AC input voltages may still
®
™
Liebert GXT3
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
2.0 INSTALLATION
2.1
Unpacking and Inspection
Unpack the UPS and conduct the following checks:
• Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and
your local dealer or Emerson® representative immediately.
• Check the accessories against the delivery list. If there is any discrepancy, contact your local
dealer or your Emerson representative immediately.
2.2
What’s Included
With GXT3 UPS
• Terminal Block Communication terminals
• Compact Disk with:
• Liebert MultiLink®
• Configuration Program
• User Manual
• USB Cable: one, 2m (6-1/2 ft.) long
• Mounting hardware, including screws and handles
• Plastic tower stand sets: 2 (four pieces)
• Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
• for 700VA - 1500VA: (2) 10A IEC C13 C14 Output Cable, 2m (6-1/2 ft.) long
• for 2000VA - 3000VA:
• (3) 10A IEC C13 C14 Output Cable, 2m (6-1/2 ft.) long
• (1) CEE 7/7 (Schuko) to IEC C20 Input Cable, 2.5m (8-1/5 ft.) long
• (1) BS1363 (UK) to IEC C20 Input Cable, 2.5m (8-1/5 ft.) long
NOTE
The GXT3 External Battery Cabinet shipping package includes one battery cabinet, two
spacers for tower configuration and one DC power cable.
2.3
Preparation for Installation
2.3.1 Installation Environment
• Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off.
• Place the UPS in an area where airflow around the unit is unrestricted and away from water,
flammable liquids, gases, corrosives and conductive contaminants. Avoid direct sunlight.
NOTE
Operating the Liebert GXT3 in temperatures above 25°C (77°F) reduces battery life.
Installation Clearances
Maintain a clearance of at least 100mm (4 inches) in the front and rear of the Liebert GXT3. Do not
obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces
ventilation and heat dissipation, shortening the service life of the Liebert GXT3.
®
™
9
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
2.4
Mechanical Installation
The Liebert GXT3 may be installed as a tower or in a rack, depending on space and use
considerations. The Liebert GXT3 may be used alone, as a single UPS, or with up to four battery
cabinets.
NOTE
When installing the UPS or making input and output connections, comply with all relevant
safety codes and standards.
2.4.1 Tower Installation
To install the Liebert GXT3 as a tower:
Figure 6 Support bases
Spacers
Connectors
Support Bases
2. If optional Liebert external battery cabinets will be connected to the Liebert GXT3, take out the
spacers delivered with the battery cabinet.
assembled support bases, one in the front and one in the rear.
4. Adjust the direction of the operation and display panel and logo on the Liebert GXT3.
Figure 7
Remove the front plastic bezel cover
Front Plastic
Bezel Cover
b. Pull the operation and display panel, rotate it 90 degrees clockwise and snap it back into
®
™
Liebert GXT3
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Figure 8
Rotate the operation and display panel
Operation and Display Panel
Rotated Clockwise 90 Degrees
c. Pull the logo on the front plastic bezel cover, rotate it 90 degrees clockwise and snap it back
d. Replace the front plastic bezel cover on the Liebert GXT3. At this point, the UPS operation
and display panel and logo have been rotated 90 degrees clockwise, which provides upright
viewing for users.
5. Place the Liebert GXT3 and any battery cabinets on the support bases. Each Liebert GXT3 needs
Figure 9
Tower installation
Liebert GXT3 UPS
Liebert GXT3 UPS and
External Battery Cabinet
Operation and
Display Panel
Rotated for
Tower Operation
Support Bases
Support Bases
®
™
11
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
2.4.2 Rack Installation
NOTE
• When the Liebert GXT3 is installed in a rack, the UPS must be supported by a shelf,
brackets, or slide rails on each side. The factory-supplied rack-mount ears cannot support
the weight of the UPS. They are used to move the UPS into and out of the rack and attach the
UPS to the rack.
• Mounting hardware and slide rails are sold separately. Contact your local dealer or
Emerson® representative for these options and any assistance.
To install a Liebert GXT3 UPS in a rack:
1. Unpack the two bracket assemblies and mounting hardware from the rack-mounting kit
(P/N: RMKIT18-32). Bracket assembly includes inner member, front member and rear member.
They are interchangeable between left-hand and right-hand. Mounting hardware includes M4
screws and M5 screws.
2. Remove inner member of each bracket assembly by extending it to its outermost position,
depressing the retaining latch and then pulling the inner member from the bracket assembly (see
Figure 10 Pulling inner member from each bracket assembly
Bracket assembly
Retaining latch
Inner member
3. Determine the desired height and mounting position of the Liebert GXT3 inside the rack’s vertical
rails.
CAUTION
position.
!
Reduce risk of tipping the rack by installing the Liebert GXT3 in the lowest possible rack
4. Attach the rear member of each bracket assembly to the rack’s vertical rails with two factory-
®
™
Liebert GXT3
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Figure 11 Installing rear member of each bracket assembly
Vertical pole
M5 screw (4 pcs)
Rear member
Front member
5. Extend bracket assembly by sliding the front member forward until it touches the rack’s front
vertical rails (adjustable length: 18 inches to 32 inches).
6. Use two M5 screws to attach each front member onto the front vertical rails through the
installation holes. Make sure that the bracket assemblies are at the same mounting height on all
Figure 12 Installing front member of each bracket assembly
Front vertical pole
Front member
Rear member
M5 screw (4 pcs)
7. Fasten the rear and front members together using four M4 screws and four M4 nuts (M4 nuts
have been installed on the rear member before delivery) per bracket assembly, as shown in
Figure 13 Fastening rear member and front member together
Rear member
M4 screw (8 pcs)
M4 nut (8 pcs)
Front member
®
™
13
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
8. Fasten inner members pulled from the bracket assemblies in Step 2 to the UPS on both sides with
eight M4 screws provided in this kit. Make sure that the retaining latch is near the rear of the
Figure 14 Installing inner members
Liebert GXT3 UPS
Inner Member
Retaining Latch
M4 screw, 8 pieces
Figure 15 Installing rack-mount ears
Liebert GXT3 UPS
Ear, 2 pieces
M4 Screw, 8 pieces
10. Insert the UPS, with inner members attached, into bracket assemblies by inserting top and
bottom edges of inner members into the top and bottom curved tracks of front members and
Figure 16 Insert the UPS
Insert
Front Member
Inner Member
NOTE
Ends of inner members are tapered to allow the rear of the UPS to be angled upward before
insertion, if space allows.
The UPS should move smoothly into the bracket assemblies. If not, recheck alignment of front
®
™
Liebert GXT3
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
11. Through the rack-mount ears, use M5 screws provided in this kit to secure the front of the UPS to
the rack’s vertical rails to prevent the UPS from sliding out of position.
12. If optional Liebert external battery cabinets will be connected to the UPS, they can be placed all
on one side of the UPS or stacked beneath the UPS. The installation procedures are the same as
those for the UPS.
NOTE
Up to four external battery cabinets can be connected to the Liebert GXT3. Each cabinet will
increase the battery recharge time.
2.5
Cable Connection
The Liebert GXT3 rear panel has an input receptacle and output receptacles. Refer to 1.3.2 - Rear
Panel Features for details. The battery cables are supplied with the battery cabinet.
2.5.1 Connecting to AC Mains and Loads
NOTE
Ensure that all the loads are turned Off.
Prepare an input power supply that is properly protected by a circuit breaker in accordance
with national and local electrical codes. The wall receptacle must be grounded.
Emerson® recommends installing an upstream circuit breaker of the same series as the Liebert
GXT3’s input circuit breaker. The upstream breaker should have a higher capacity than the
UPS input circuit breaker.
Table 2
Specification of input circuit breaker
Rated Circuit
Model
Breaker
10A
GXT3-700RT230
GXT3-1000RT230
GXT3-1500RT230
GXT3-2000RT230
GXT3-3000RT230
10A
10A
16A
16A
1. Plug all loads into the output receptacles on the rear panel of the Liebert GXT3.
NOTE
1. Do not overload any one output receptacle.
2. Output cable length should not exceed 10m (32.8 ft).
3. Plug the input receptacle of the Liebert GXT3 into the input power connection.
2.5.2 Connecting Battery Cables
1. Switch Off the input breaker of the battery cabinet.
2. Take out the battery cable included with the battery cabinet.
3. Connect one end of the battery cable to the external battery connector on the rear panel of the
UPS, and connect the other end to any battery port on the rear panel of the battery cabinet.
4. Switch On the battery breaker on the rear of the external battery cabinet.
5. Use the Configuration Program included with the UPS to specify the number of external battery
®
™
15
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
2.6
Connecting Communication Cables
Communication cable connection includes USB and option card cables.
2.6.1 Connecting USB Communication Cables
1. Remove the USB communication cables from the accessories box.
2. Insert one end of the USB communication cable to the USB port on the rear panel of the Liebert
3. Insert the other end of the USB communication cable to the USB port of the computer.
2.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cables
1. Remove the protective cover of the Liebert IntelliSlot port on the Liebert GXT3 and set it aside.
2. Insert the Liebert IntelliSlot card into the Liebert IntelliSlot port and secure it with screws.
3. To connect any cable associated with a Liebert IntelliSlot card, refer to the user manual provided
with the card.
To configure and use the Liebert IntelliSlot communication card, refer to the card’s user manual.
Manuals for the various Liebert IntelliSlot cards are available at Liebert’s Web site:
®
™
Liebert GXT3
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation and Display Panel
3.0 OPERATION AND DISPLAY PANEL
Figure 1).
Figure 17 Operation and display panel
Battery Level Indicators
Load Level Indicators
Fault Indicator
Bypass Indicator
Inverter Indicator
AC Input Indicator
Liebert® GXT3
AC Power System
3000VA
On/Alarm Silence/Manual
Battery Test Button
Standby/Manual Bypass Button
Battery Indicator
3.1
Control Buttons
The operation and display panel has two control buttons: the On/Alarm Silence/Manual Battery Test
button and the Standby/Manual Bypass button.
3.1.1 On/Alarm Silence/Manual Battery Test button
The On/Alarm Silence/Manual Battery Test button controls output power to connected load(s) and
Table 3
Functions of the On/Alarm Silence/Manual Battery Test button
Function
Operation
Description
ON
Press the button once for 3 seconds
Press the button for at least half a second
To start up the UPS
1
2
Alarm silence
To silence alarms
Press the button for at least half a second while
operating in Mains (AC) Mode with no alarms present.
Manual Battery Test
To initiate a manual battery test
1. The low battery and bypass reminder alarms cannot be silenced.
2. After the alarm is silenced, UPS will reactivate the alarm system to alert of additional problems.
3.1.2 Standby/Manual Bypass button
The Standby/Manual Bypass button controls output power to connected load(s) and has two functions
Table 4
Functions of the Standby/Manual Bypass button
Function
Operation
Description
Press the button once and hold it for about
2 seconds.
To initiate a manual transfer of the connected
loads to the internal bypass, if available
Manual Bypass
Standby
Press the button twice within four seconds while To shut down the UPS and shut Off all power
the UPS is in Manual Bypass or Battery Mode.
to the connected loads
1. If the bypass is not available due to voltage or frequency, pressing this button once will be ignored.
2. Perform all necessary shutdown procedures on connected loads before turning Off the Liebert GXT3.
®
™
17
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation and Display Panel
3.2
Indicators
into two groups according to their applications: level indicators and UPS status indicators.
3.2.1 Level Indicators
Battery Level Indicators
The battery level indicator is composed of five sets of LED bars that illuminate and flash to indicate
the battery capacity level. The Liebert GXT3 battery capacity level is shown in 20% increments (±5%).
Figure 18 Battery level indicators
Charging
Discharging
0 - 20%
21 - 40%
41 - 60%
61 - 80%
81 - 100%
Flash OFF OFF OFF OFF
ON OFF OFF OFF OFF
ON Flash OFF OFF OFF
ON
ON
ON OFF OFF OFF
ON
ON Flash OFF OFF
ON
ON OFF OFF
ON
ON
ON Flash OFF
ON
ON
ON
ON
ON OFF
ON
ON
ON
ON Flash
ON
ON
ON
ON
ON
ON
ON
Fully
Charged
ON
ON
ON
ON
ON
ON
ON
Load Level Indicators
The load level indicator is composed of five sets of LED bars that illuminate to indicate the relative
load on the UPS output in 25% increments (±5%). The load level indicator will illuminate as shown in
Figure 19 Load level indicators
0 - 25%
ON OFF OFF OFF OFF
26 - 50%
OFF OFF OFF
ON
ON
ON
ON
ON
ON
ON
ON
51 - 75%
76 - 100%
Overload
ON
ON
ON
OFF OFF
ON
ON
OFF
ON
®
™
Liebert GXT3
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation and Display Panel
3.2.2 UPS Status Indicators
UPS status is indicated by five symbols: fault indicator, AC input indicator, battery indicator,
Table 5
UPS status indicators
UPS Status
Indicator
Icon
Color
Description
Fault Indicator
Red
On if the UPS has detected a fault; Off if there is no fault
On when the mains input power is normal; Off during mains
failure; flashing when mains power is outside specifications
AC input Indicator
Battery Indicator
Inverter Indicator
Bypass Indicator
Green
Amber
Green
Amber
On when the battery is supplying power; Off when the battery
is not supplying power
On when the inverter is supplying power; Off when the
inverter is not supplying power
On when the bypass is supplying power; Off when the bypass
is not supplying power; flashing when mains power is outside
specifications
®
™
19
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
4.0 OPERATION
This section describes checks to be made before starting the UPS, how to start the UPS, manual
battery test, manual bypass, shutting down the UPS and disconnecting the mains power from the
UPS.
NOTE
The Liebert GXT3’s battery has been fully charged before delivery, but some charge will be lost
during storage and shipping. To ensure that the battery has adequate reserve power to protect
the connected load, charge the battery for three hours before putting the UPS into service.
4.1
4.2
Startup Checklist for the Liebert GXT3
Before starting the UPS, perform these checks:
___ 1. Check that the input plugs and loads are connected properly and reliably.
___ 2. Check that the battery cable is connected properly.
___ 3. Check that the communication cables are connected properly.
Starting the UPS
2. Turn On the UPS by pressing the On/Alarm Silence/Manual Battery Test button for three
seconds.
After the button is pressed, the LEDs on the display will signal that the unit has initiated the
startup process.
3. Once the inverter LED has been illuminated, turn On the connected loads.
4. Check the status indicators to determine whether the Liebert GXT3 is operating normally.
5. Check the load level indicators to verify that the connected load does not exceed the UPS’s rated
capacity.
The UPS is now providing conditioned power to the loads.
4.3
Manual Battery Test
To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least
half a second while operating from mains power with no alarm conditions present.
• If only the first two of the five LED segments illuminate, allow the UPS to recharge the batteries
for 24 hours.
• Retest the batteries after 24 hours of charging.
• After the batteries have been retested, if only two of the five Battery LEDs illuminate, contact
your local Emerson® representative or Emerson Network Power Channel Support.
• If none of the five Battery LEDs illuminate during a manual battery test, check the battery
connection and allow the UPS to recharge the batteries for 1 hour, then initiate a manual battery
test again.
• If none of the five Battery LEDs illuminate during the second manual battery test, replace
batteries and contact your local Emerson representative or Emerson Channel Support.
4.4
Manual Bypass
Press the Standby/Manual Bypass button once while the UPS is in Mains (AC) Mode and hold it for
about 2 seconds. The UPS will transfer the connected loads to the internal bypass. If the internal
bypass is not available because of mains power problems, pressing this button once will be ignored.
Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other
®
™
Liebert GXT3
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
4.5
4.6
Shut Down the Liebert GXT3
1. Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button and holding
it for about 2 seconds.
If manual bypass is not available, disregard the first step.
2. Press the Standby/Manual Bypass button twice within four seconds, each time holding it for
about two seconds, to shut down the UPS. The UPS will shut down about 30 seconds after the
button is pressed.
Power to the connected loads is now Off.
Disconnecting Input Power from the Liebert GXT3
disconnect the input cable plug.
2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this
indicates that the power-off is complete.
3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external
battery cabinet.
After powering Off the UPS, the UPS ceases output and the load is powered Off.
®
™
21
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Communication
5.0 COMMUNICATION
This section describes UPS communication over the three types of communication connections on the
rear of the Liebert GXT3:
• Liebert IntelliSlot port
• USB port (standard B-type)
• Terminal Block Communication
CAUTION
should be segregated and run separate from all other power cables.
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables
5.1
Liebert IntelliSlot Communication Cards
The Liebert IntelliSlot port accepts three optional cards:
• Liebert IntelliSlot SNMP Card
• Liebert IntelliSlot Relay Card
• Liebert IntelliSlot 485 Card.
The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the
network.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications
and delivers support for built-in shutdown for AS/400 systems.
The Liebert IntelliSlot 485 Card is used to connect the UPS and a BMS.
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the
UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at:
5.1.1 Liebert MultiLink
Liebert MultiLink monitors the UPS continuously and can shut down the computer or server in the
event of an extended power failure. Liebert MultiLink can also be configured to shut down the UPS.
Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot
SNMP Card or Liebert IntelliSlot Web Card is installed in the UPS. An optional Liebert MultiLink
License Kit permits shutting down the UPS over a network.
For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and
Emerson® representative.
®
™
Liebert GXT3
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Communication
5.2
USB Port Communication
The standard B-type USB port is used to connect the UPS and network server or other computer
system using Liebert MultiLink®. The configuration program can be completed through the
communication port.
5.2.1 Configuration Program
Accessing the Configuration Program via USB is a new feature of the Liebert GXT3. For most users,
the factory default settings will be adequate. This section illustrates the features available for
modification, as well as the factory default setting.
The USB configuration program allows these features of the Liebert GXT3 to be changed:
• Enable/Disable Auto-Restart
• Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass
disabled
• Set the Low Battery Warning alarm time from 2 to 30 minutes
• Enable/Disable the Auto-Battery test
• Enable/Disable Auto-Restart after removing Remote shutdown
• Set the wiring mode of Remote shutdown
• Set the Auto-Enable output
• Set the Auto-Battery test to 7, 14, 21 or 28 days
• Select the number of external battery cabinets connected to the UPS to adjust the remaining run
time calculated by Emerson® software products
Table 6
Output voltage option, all models
Output Voltage Option
220VAC, 230VAC and 240VAC
Factory Default Setting
230VAC
NOTICE
The output voltage settings cannot be changed while the UPS is On and powering connected
loads.
NOTE
Programming the output voltage of a 230V model of the Liebert GXT3 to 220V automatically
and Watt ratings).
NOTE
• This program is compatible with UPS models beginning with ‘GXT3,’ as in
‘GXT3-3000RT230.’ It is not compatible with earlier versions of the Liebert GXT UPS.
®
®
®
• A computer running Windows 2000 , XP or Vista is required to set up and run the
configuration program.
®
™
23
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Communication
5.3
Terminal Block Communication
Figure 20 Terminal Block Communication pin layout
1
2
Any Mode
Shut Down
3
4
Battery Mode
Shut Down
5
6
Battery Mode
Low Battery
7
8
5.3.1 Any Mode Shutdown
The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier,
inverter and static switch so that there is no power to the loads.
Any Mode Shutdown can be operated locally or remotely:
• Local Any Mode Shutdown can be performed by shorting Pin 1 and Pin 2.
• Remote Any Mode Shutdown can be performed using a switch connected to Pin 1 and Pin 2 and
mounted at a remote location.
NOTE
Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown,
depending on the settings in the configuration program.
A current-limited source for this optocoupler (+12VDC, 50mA) will be available from the UPS.
The connection to the UPS for remote connection will be via terminal block connector.
Any Mode Shutdown wiring must conform to all national, regional and local wiring
regulations.
WARNING
!
When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1
and Pin 2, the Liebert GXT3’s output can turn On automatically and without warning if the
Pin 1 and Pin 2 connection is changed.
®
™
Liebert GXT3
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Communication
5.3.2 Battery Mode Shutdown
Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and
static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power
for the UPS will still be active.
Battery Mode Shutdown can be performed locally or remotely:
• Local Battery Mode shutdown can be performed by shorting Pin3 and Pin4.
• Remote Battery Mode Shutdown can be performed using a switch connected to Pin3 and Pin4 and
mounted at remote location.
NOTE
Remote Power Off will be performed by NO contact.
A current-limited source for this optocoupler (+12VDC, 50mA) will be available from UPS.
The connection to the Liebert GXT3 for remote connection will be via terminal block connector.
Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes
and laws.
This signal must last for 1.5 seconds or longer.
A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute
shutdown timer. This timer cannot be stopped once triggered. If the mains power returns
during this countdown, the Liebert GXT3 will still shut down and must remain shut down for
10 seconds. Whether the UPS turns back On when the power is restored depends on the
auto-restart setting.
5.3.3 On Battery
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power
from the battery this dry contact will be closed.
5.3.4 Low Battery
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power
from the battery and has reached the Low Battery Warning time selected in the configuration
program, this dry contact will be closed.
NOTE
The rated values for the dry contacts for the On Battery and Low Battery signals are:
• Rated Voltage: 30V (AC or DC)
• Rated Current: 300mA
®
™
25
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
6.0 MAINTENANCE
This section describes replacing the internal battery pack, precautions, checking the Liebert GXT3’s
status and checking UPS functions.
WARNING
precautions should be observed before replacing the battery pack:
• Remove rings, watches and other metal objects.
• Use tools with insulated handles.
!
The battery can present a risk of electrical shock and high short circuit current. The following
• Do not lay tools or other metal objects on the batteries.
• If the battery kit is damaged in any way or shows signs of leakage, contact your local
Emerson® representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Handle, transport and recycle batteries in accordance with local regulations.
6.1
Replacing the Internal Battery Pack
The Liebert GXT3 is designed to allow the user to replace the internal battery pack safely. Refer to Table 7
for internal battery pack part numbers for Liebert GXT3 UPS:
Table 7
Replacement battery pack model numbers
Replacement Internal Battery
Quantity
Required
UPS Model Number
Pack Model Number
GXT3-5A48BATKIT
GXT3-5A48BATKIT
GXT3-7A48BATKIT
GXT3-9A48BATKIT
GXT3-9A72BATKIT
Liebert GXT3-700RT230
Liebert GXT3-1000RT230
Liebert GXT3-1500RT230
Liebert GXT3-2000RT230
Liebert GXT3-3000RT230
1
1
1
1
1
Read all safety cautions before proceeding. Contact your local dealer or Emerson representative to
obtain the part number and pricing of the appropriate replacement battery pack.
6.1.1 Battery Replacement Procedures
1. Gently remove the front plastic bezel cover from the UPS.
3. Lay the battery door and screws aside for reassembly.
Figure 21 Removing the front plastic bezel cover and battery door
Battery Door
Screws, 6
Front Bezel
4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown
®
™
Liebert GXT3
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Figure 22 Disconnecting the battery plug and battery connector (front view)
Battery Connector
Battery Connector
5. Grasp the battery handle and pull the internal battery pack out of the UPS, as shown in
Figure 23 Pulling out the battery
Internal Battery Pack
Battery
Handle
Pull Out with Battery Handle
6. Unpack the new internal battery pack. Take care not to destroy the packing.
Compare the new and old internal battery packs to make sure they are the same type and model.
Emerson® representative or Emerson Channel Support.
7. Line up and slide in the new internal battery pack.
8. Reconnect the battery plug and battery receptacle
9. Gently push the battery wire and internal battery pack back into the UPS.
10. Reattach the front battery door with the six screws.
11. Reattach the front plastic bezel cover to the UPS.
NOTE
The internal battery pack is hot-swappable. However, caution should be exercised because
during this procedure the load is unprotected from disturbances and power outages.
Do not replace the battery while the UPS is in Battery Mode. This will result in a loss of output
power and will drop the connected load.
6.2
Battery Charging
The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their
design life. The Liebert GXT3 charges the batteries continuously when it is connected to the mains
input power.
If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input
power for at least 24 hours every four to six months to ensure full recharge of the batteries.
®
™
27
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
6.3
6.4
Precautions
Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper
use can result in electrical shock or fire. To ensure safety, observe the following precautions:
• Turn Off and unplug the Liebert GXT3 before cleaning it.
• Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
• Never block or insert any objects into the ventilation holes or other openings of the UPS.
• Do not place the Liebert GXT3 power cord where it might be damaged.
Checking UPS Status
Emerson® recommends checking the UPS operation status every six months.
• Check whether the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?
• Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal
Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or
Emerson Channel Support.
• Check whether the battery is discharging. When the mains input is normal, the battery should
not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson
representative or Emerson Channel Support.
6.5
Checking UPS Functions
NOTE
UPS function check procedures may interrupt power supply to the connected load.
Emerson recommends checking the UPS functions once every six months.
Back up the load data before conducting the UPS functions check. Procedures are as follows:
1. Press the Standby/Manual Bypass button to check whether the buzzer and indicators are normal.
2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators
are On and the UPS is operating normally.
3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode.
The UPS should initiate a battery self-test. Check to determine whether the battery is operating
normally. If not, stop and contact your local Emerson representative or Emerson Channel Support
®
™
Liebert GXT3
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
7.0 TROUBLESHOOTING
This section indicates various UPS symptoms a user may encounter and provides a troubleshooting
guide in the event the UPS develops a problem. Use the following information to determine whether
external factors caused the problem and how to remedy the situation.
7.1
UPS Symptoms
The following symptoms indicate the Liebert GXT3 is malfunctioning:
• The relative indicators illuminate, indicating the UPS has detected a problem.
• An alarm buzzer sounds, alerting the user that the UPS requires attention.
7.1.1 Indicators
In addition to the fault indicator being illuminated, one or more of LED segments of battery level
indicator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 24. The
Figure 24 Battery level indicator
A
B
C
D
E
Table 8
Indicator descriptions
Diagnosis/Audible alarm
Indicator
A - E
A
On bypass from output overload (half-second beep every half-second)
On bypass due to overtemperature condition (1-second beep every 4 seconds)
On bypass due to DC bus overvoltage (1-second beep every 4 seconds)
On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)
On bypass due to PFC failure (1-second beep every 4 seconds)
B
C
D
E
On bypass due to inverter failure (1-second beep every 4 seconds)
UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery
charger failure) and continuous alarm
A&B
A&C
A&E
B&E
UPS failed battery test (2-second beep every 60 seconds)
Bypass feedback (1-second beep every 4 seconds)
Short circuit on the output
®
UPS shutdown by command from communication (USB port or Liebert IntelliSlot port) (no
audible)
C&E
Utility LED flash
L-N reverse
Battery Indicator
Flashing
Internal battery not connected (continuous horn); check battery connection, power down and
restart UPS
Bypass Indicator
Flashing
Mains power voltage or frequency is out of tolerance; bypass is unavailable
If the UPS experiences an overload, the UPS will transfer from bypass back to inverter approximately 5 minutes after the overload
ends.
®
™
29
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
7.1.2 Audible Alarm
An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS
Table 9
Audible alarm description
Condition
Alarm
Half-second beep every 10 seconds
Two half-second beeps every 5 seconds
1-second beep every 4 seconds
Continuous
Battery discharge
Low battery
UPS fault, load on bypass
UPS fault, no power to load
Overload
Half-second beep every half second
2-second beep every 60 seconds
Continuous
Battery replacement
Battery loss
Wiring problem (loss of proper grounding for UPS) Continuous
Bypass reminder 1-second beep every 2 minutes
7.2
Troubleshooting
In the event of an issue with the UPS, refer to Table 10 to determine the cause and solution. If the
fault persists, contact Emerson® Channel Support.
Table 10 Troubleshooting table
Problem
Cause
Solution
UPS fails to start when the
On/Alarm Silence/Manual
Battery Test button is pressed
Ensure UPS is Off. Disconnect all loads and ensure
nothing is lodged in output receptacles. Ensure loads
are not defective or shorted internally.
UPS is short-circuited or
overloaded
UPS is operating from battery mode. Ensure UPS is
securely plugged into the wall receptacle.
UPS is not plugged in
UPS is operating from battery mode. Save data and
close applications. Replace UPS input fuse, then restart
UPS.
UPS input protection fuse has
blown/opened
Battery indicator is illuminated
UPS is operating from battery mode. Save data and
Mains power is out of tolerance close applications. Ensure mains supply voltage is
within acceptable limits for UPS.
Keep UPS plugged in continuously at least 24 hours to
Batteries are not fully charged
recharge batteries.
Check load level indicator and reduce the load on the
UPS has reduced battery
backup time
UPS is overloaded
UPS.
Replace batteries. Contact your local dealer, Emerson
Batteries may not be able to
representative or Emerson Channel Support for
hold a full charge due to age
replacement battery kit.
Fault and Bypass indicators
and all LED segments of
battery level indicator are
illuminated
Check load level indicator and remove non-essential
UPS is overloaded or load is
loads. Recalculate the load and reduce number of loads
faulty
connected to UPS. Check load for faults.
Ensure UPS is not overloaded, ventilation holes are not
blocked and room ambient temperature is not
Fault and Bypass indicators
and diagnostic A indicator are
illuminated
UPS has been shut down due
excessive. Wait 30 minutes to allow UPS to cool, then
to temperature condition; load
restart UPS. If UPS cannot restart, contact your local
is on bypass power
®
dealer, Emerson representative or Emerson Channel
Support.
Fault and Bypass indicators
and diagnostic B indicator are
illuminated
UPS internal DC bus
overvoltage
UPS requires service. Contact your local dealer,
Emerson representative or Emerson Channel Support.
®
™
Liebert GXT3
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Table 10 Troubleshooting table (continued)
Problem
Cause
Solution
Fault and Bypass indicators
and diagnostic C indicator are
illuminated
UPS requires service. Contact your local dealer,
Emerson representative or Emerson Channel Support.
UPS DC/DC fault
®
Fault indicator and diagnostic
D indicator are illuminated
UPS PFC (Power Factor
Correction Circuit) fault
UPS requires service. Contact your local dealer,
Emerson representative or Emerson Channel Support.
Fault and Bypass indicators
and diagnostic E indicator are
illuminated
UPS requires service. Contact your local dealer,
Emerson representative or Emerson Channel Support.
UPS inverter fault
Fault indicator and diagnostic
A and C indicators are
illuminated
Replace batteries. Contact your local dealer, Emerson
representative or Emerson Channel Support.
UPS failed the battery test
Your UPS has received a signal or command from the
attached computer. If this was inadvertent, ensure the
communication cable used is correct for your system.
For assistance, contact your local dealer, Emerson
representative or Emerson Channel Support.
Fault and Bypass indicators
and diagnostic C and E
indicators are illuminated
UPS has been shut down by a
command from the
communications port(s)
UPS failure (includes dual-fan
failure, single-fan failure under
certain conditions and battery
charger failure) and continuous
alarm
Fault indicator and diagnostic
A and B indicators are
illuminated
Ensure fan is not blocked up. If the fault is not removed,
contact your local dealer, Emerson representative or
Emerson Channel Support.
UPS detected a line-to-neutral
reversal or a loss of proper
grounding for UPS; continuous
horn and UPS cannot start up
in standby status. This is active
only when power is first
AC input indicator is flashing.
Contact a qualified electrician to verify site wiring.
applied to the input. Once the
UPS is running, the AC input
indicator will flash, unless the
input wiring is correctly
changed.
Check battery connections, completely power down and
restart UPS.
NOTE: If the battery circuit opens while the UPS is
running, it will be detected when the next battery test is
performed.
Battery source is not available;
continuous horn.
Battery indicator is flashing.
Bypass indicator is flashing.
The AC input powers the PFC input and serves as the
bypass source. If the AC is present but the voltage or
frequency exceeds the acceptable range for safe
operation with a load, the bypass will be disabled and
this indicator will flash, indicating that the bypass is
unavailable.
Because the voltage or
frequency is outside
acceptable limits, the bypass is
disabled.
When reporting a UPS issue to Emerson, include the UPS model and serial number. These are on the
top panel of the Liebert GXT3.
®
™
31
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Battery Cabinet
8.0 BATTERY CABINET
Optional battery cabinets are available for the Liebert GXT3. The external battery connector and
Figure 25 Battery cabinet
Input Breaker
External Battery
Connector
WARNING
!
Do not contact the external battery connector and ground without wearing protective gloves
and clothing and taking other precautions against electrical shock. The battery loop and AC
input are not insulated, which may cause a dangerous voltage between the external battery
connector and ground.
NOTE
External battery connectors are wired in parallel. Either connector can be connected to the UPS
or to another battery cabinet.
NOTE
The length of the standard battery cable delivered with the battery cabinet is 0.65m (2.13ft).
®
™
Liebert GXT3
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
9.0 SPECIFICATIONS
Table 11
Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS
Product model
Parameters
GXT3-700RT230
700VA/630W
GXT3-1000RT230
1000VA/900W
Model Rating
Dimensions, D x W x H, mm (in)
Unit
497 x 430 x 85 (19.6 x 16.9 x 3.3)
Shipping
617 x 570 x 262 (24.3 x 22.4 x 10.3)
Weight, kg (lb)
Unit
16.8 (37)
20 (44)
Shipping
Input AC
Voltage Range (typical)
90% ~ 100% loading
70% ~ 90% loading
30% ~ 70% loading
0 ~ 30% loading
Frequency
230VAC nominal; variable based on output load
177VAC/280VAC
168VAC/280VAC
150VAC/280VAC
115VAC/280VAC
40Hz ~ 70Hz; Auto Sensing
C14
Input Power Receptacle
Output AC
AC-AC Efficiency
Output Receptacles
Voltage
> 88% AC-AC, minimum
C13 × 6
220/230/240VAC (user configurable); ±3%
50Hz or 60Hz
Frequency
Waveform
Sine wave
Mains (AC) Mode Overload
Internal Battery Charger
Charger Current
Battery
200% for 2 seconds; 150% for 1 minute with transfer to bypass
1.3
Type
Valve-regulated, nonspillable, lead acid
4 × 12V × 5.0Ah
Qty × V× Rating
Battery Mfr/Part#
Backup Time
YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245
3 hours to 90% capacity after full discharge with 100% load till UPS
auto-shutdown (Internal Batteries Only)
Recharge Time
Environmental Requirements
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
-15ºC to +50ºC (5ºF to 122ºF)
0%RH to 95%RH, non-condensing
Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating
15,240 (50,000 ft.) maximum
< 46 dBA, at 1 meter (3.2ft) from the rear
< 43 dBA, at 1 meter (3.2ft) from the front or sides
Audible Noise
Agency
Safety
RFI/EMI
IEC/EN/AS 62040-1:2008, GS mark
IEC/EN/AS 62040-2 2nd Ed (Category C2) = CISPR22 Class A
IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)
ISTA Procedure 1A
Surge Immunity
Transportation
®
™
33
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Table 12 Specifications of the Liebert GXT3-1500RT230, GXT3-2000RT230 and GXT3-3000RT230
Product model
GXT3-2000RT230
Parameters
GXT3-1500RT230
1500VA/1350W
GXT3-3000RT230
3000VA/2700W
Model Rating
2000VA/1800W
Dimensions, D x W x H, mm (in)
497 × 430 × 85
(19.6 x 16.9 x 3.3)
602 × 430 × 85
(23.7 x 16.9 x 3.3)
Unit
617 x 570 x 262
(24.3 x 22.4 x 10.3)
717 x 570 x 262
(28.2 x 22.4 x 10.3)
Shipping
Weight, kg (lb)
Unit
23.2 (51.1)
26 (57.3)
25.5 (56.1)
28 (61.7)
32.4 (71.4)
35 (77.2)
Shipping
Input AC
Voltage Range (typical)
90% ~ 100% loading
70% ~ 90% loading
30% ~ 70% loading
0 ~ 30% loading
Frequency
230VAC nominal; variable based on output load
177VAC/280VAC
196VAC/280VAC
184VAC/280VAC
161VAC/280VAC
115VAC/280VAC
168VAC/280VAC
150VAC/280VAC
115VAC/280VAC
40Hz ~ 70Hz; Auto Sensing
Input Power Receptacle
Output AC
C14
C20
AC-AC Efficiency
Output Receptacles
Voltage
> 88% AC-AC, minimum
C13 x 6
C13 x 6; C19 x 1
220/230/240VAC (user configurable); ±3%
50Hz or 60Hz
Frequency
Waveform
Sine wave
Mains (AC) Mode Overload
200% for 2 seconds;
150% for 55 seconds
200% for 2 seconds; 150% for 50 seconds
Internal Battery Charger
Charger Current
Battery
1.88
2.71
2.5
Type
Valve-regulated, nonspillable, lead acid
Qty × V× Rating
Battery Mfr/Part#
4 × 12V × 7.2Ah
4 × 12V × 9.0Ah
6 × 12V × 9.0Ah
Panasonic/UP-RW1236
CSB/ GP 1272
Panasonic/UP-RW1245
CSB/ HR 1234W F2
Backup Time
3 hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
(Internal Batteries Only)
Recharge Time
Environmental Requirements
Operating Temp
0ºC to 40ºC (32ºF to 104ºF); Table 14 - Operating temperature parameters
-15ºC to +50ºC (5ºF to 122ºF)
Storage Temp
Relative Humidity
0%RH to 95%RH, non-condensing
Operating Elevation
Storage Elevation
Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating
15000m (50,000 ft.) maximum
< 45 dBA max. at 1 meter (3.2ft.) front and side < 48 dBA max. at 1 meter (3.2ft.) front and side
Audible Noise
< 46 dBA, at 1 meter (3.2ft.) rear
< 48 dBA, at 1 meter (3.2ft.) rear
Agency
Safety
RFI/EMI
IEC/EN/AS 62040-1:2008, GS mark
IEC/EN/AS 62040-2 2nd Ed. (Category C2) = CISPR22 Class A
IEC/EN 62040-2 2nd Ed. (IEC/EN 61000-4-5)
ISTA Procedure 1A
Surge Immunity
Transportation
®
™
Liebert GXT3
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Table 13 Battery cabinet specifications
Model Number
Parameter
GXT3-48VBATT
GXT3-72VBATT
GXT3-700RT230, GXT3-1000RT230,
GXT3-1500RT230, GXT3-2000RT230 GXT3-3000RT230
Used w/UPS Model
Dimensions, D x W x H, mm (in)
497 × 430 × 85
(19.7 x 16.9 x 3.3)
602 × 430 × 85
(23.6 x 16.9 x 3.3)
Unit
617 x 570 x 262
(24.3x 22.4 x 10.3)
717 x 570 x 262
(28.2 x 22.4 x 10.3)
Shipping
Weight, kg (lb)
Unit
32 (70.5)
35 (77.2)
42 (92.6)
Shipping
46 (101.4)
Battery parameters
Type
Valve-regulated, nonspillable, lead acid
Qty × V× Rating
Battery Mfr/Part#
Backup Time
2 × 4 × 12V × 9.0Ah
2 × 6 × 12V × 9.0Ah
Panasonic/UP-RW1245 CSB/HR 1234W F2
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
0ºC to 40ºC (32ºF to 104ºF)
-15ºC to +40ºC (19ºF to 104ºF)
0% to 95%, non-condensing
Operating Elevation
Storage Elevation
Up to 3000m (10,000 ft.) at 40ºC (104ºF) without derating
15000m (50,000 ft.) maximum
Agency
Safety
RFI/EMI
IEC/EN/AS 62040-1:2008, GS mark
FCC Part 15, Class A=CISPR22 Class B
IEC 62040-2 2nd Ed.: 2006
Surge Immunity
Transportation
ISTA Procedure 1A
Table 14 Operating temperature parameters
Ambient Temperature,
25-30 (77-86)
30-35 (86-95)
93%-86%
35-40 (95-104)
86%-79%
°C (°F)
Maximum Output Power
Factor Derating
100%-93%
@ Maximum Load
®
™
35
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Table 15 Battery run times
Run Time, Minutes
Number of
Load Percent
Batteries/Cabinets
of Capacity
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
700VA
105
62
1000VA
1500VA
75
2000VA
3000VA
77
91
38
73
33
21
15
11
8
35
37
37
31
22
21
32
23
16
15
27
17
11
11
Internal Battery
22
14
10
8
18
11
6
6
6
15
9
5
5
5
13
8
4
4
4
11
6
4
3
3
307
183
150
131
109
98
214
153
124
100
79
194
131
96
166
121
79
41
38
34
30
25
21
17
306
159
133
105
81
67
40
38
36
33
331
202
157
138
120
99
80
70
60
40
182
123
79
72
53
Internal Battery
+ 1 External Battery
Cabinet
41
46
66
38
38
81
41
35
31
72
38
32
26
63
36
27
21
41
34
23
18
374
314
212
186
160
149
139
128
112
105
480
341
319
225
206
187
163
155
148
141
337
216
166
152
136
121
104
93
310
185
148
126
103
83
311
160
134
105
81
Internal Battery
+ 2 External Battery
Cabinets
68
72
52
62
47
79
40
43
71
38
38
480
322
219
191
161
151
140
128
112
105
339
225
184
154
139
123
105
93
335
205
157
139
120
100
81
Internal Battery
+ 3 External Battery
Cabinets
71
79
62
71
51
®
™
Liebert GXT3
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Table 15 Battery run times (continued)
Run Time, Minutes
Number of
Batteries/Cabinets
Load Percent
of Capacity
700VA
480
480
338
322
305
217
202
186
164
159
1000VA
1500VA
480
315
215
184
157
145
133
120
105
96
2000VA
3000VA
480
303
187
156
141
127
108
97
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
480
340
316
220
198
166
158
149
141
133
346
301
186
156
141
126
107
95
Internal Battery
+ 4 External Battery
Cabinets
79
81
72
73
The times above are approximate. They are based on new, fully charged batteries with 100% resistive loads
and an ambient temperature of 77°F (25°C). To increase this time, turn Off non-essential loads (such as idle
computers and monitors) or add optional external battery cabinets.
9.1
Product Warranty Registration
To register for warranty protection, visit the Quick Links section of the Liebert Web site at:
Click on Product Warranty Registration and fill in the form.
If you have any questions, contact Emerson® Channel Applications Engineering at:
North America: 800-222-5877
Outside North America: 00-800-1155-4499
®
™
37
Liebert GXT3
Download from Www.Somanuals.com. All Manuals Search And Download.
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, a business of Emerson (NYSE:EMR),
is the global leader in enabling Business-Critical Continuity™
from grid to chip for telecommunication networks, data centers,
health care and industrial facilities. Emerson Network Power
provides innovative solutions and expertise in areas including
AC and DC power and precision cooling systems, embedded
computing and power, integrated racks and enclosures,
power switching and controls, infrastructure management,
and connectivity. All solutions are supported globally by local
Emerson Network Power service technicians. Liebert AC power,
precision cooling and monitoring products and services
from Emerson Network Power deliver Efficiency Without
Compromise™ by helping customers optimize their data center
infrastructure to reduce costs and deliver high availability.
Technical Support / Service
Web Site
Monitoring
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2010 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
Fax: +63 2 730 9572
or registered trademarks of their respective owners.
SLI-23180_REV5_06-13
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™
EmersonNetworkPower.com
AC Power
Connectivity
DC Power
Embedded Computing
Outside Plant
Racks & Integrated Cabinets
Embedded Power
Power Switching & Controls
Precision Cooling
Services
Infrastructure Management & Monitoring
Surge Protection
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.
©2010 Emerson Electric Co.
Download from Www.Somanuals.com. All Manuals Search And Download.
|